1. Module Overview
This analog voltage/current output module takes digital value data from
Processor Module and output an equivalent analog output voltage. This
is R – 2R type D/A conversion. It provides two isolated channels with 12-
bit resolution (11 bits + 1 sign bit). The channels provide voltage or
current range as :
This is discrete output type of module and data transfer with Processor
Module takes place in output scan.
The figure 1 on next page shows the front view of 2-channel analog
output module.
4332
ANALOG OUTPUT
2 CH – V /I
NO 24 V SUPPLY Module
Status
Front Shield LED
Plate
Terminal Block
Fixing Screw
VOUT1
01
GND1
02
I REF 1
03
SHIELD
04
I OUT1
05
GND 1
06
20 Pin 07
SHIELD
Removable 08
Terminal Block 09
VOUT2
GND2
10
I REF 2
11
SHIELD
12
I OUT2
13
GND 2
14
SHIELD
15
16
+24 V.
17
0V
18
EARTH
19
FG
20
2 CH
ANALOG OUTPUT
V/I
2. Module Operation
This chapter helps in getting started with the 2-channel analog output
module. It describes the basic operation of the module. This chapter
explains following points.
• Block Diagram
• Data Range and Resolution
• IO and Memory Mapping
Serial
Data Opto DAC1 Channel 1
Serial
Isolation R-2R
Interface 0 to ± 10 VDC
Output Signal
Control
Opto Output 1
Isolation Driver Voltage to
Current
Conversion 4 to 20 mA
CPU Output Signal
Serial
Data Opto DAC2 Channel 2
Serial
Isolation R-2R
Interface 0 to ± 10 VDC
Output Signal
Module
Interface Opto Output 2
Circuit Isolation Driver Voltage to
Current
Conversion 4 to 20 mA
Output Signal
No 24 V
Supply
Signal
Opto Miniature
+5V Isolation Glass + 24 VDC
+12 V
-12 V 0V
GND
Supply for +5 V DC to DC
Earth
DAC Circuit -5 V Converter
GND
0 VDC
$0000
4 mA 20 mA
$0 $ 7FF
For voltage range of –10 V to +10 V, the digital value ranges from -2048
to +2047 through 0.
Data
Output Data Data Output Data
(Hexadecimal
Value (Decimal) (Hexadecimal) Value (Decimal)
)
4 mA 0 0 11 mA 896 380
5 mA 128 80 12 mA 1024 400
6 mA 256 100 13 mA 1152 47F
7 mA 384 180 14 mA 1279 4FF
8 mA 512 200 15 mA 1407 57F
9 mA 640 280 16 mA 1535 5FF
10 mA 768 300 17 mA 1663 67F
18 mA 1791 6FF
19 mA 1919 77F
20 mA 2047 7FF
2.3 IO Mapping
The figure below shows I/O mapping related to 2-channel analog output
module.
Processor module
Input Output
Channel 1
Output Scan
Channel 1
Module
Channel 2 Interface circuit
Logic Scan
IMM_OUT
EN ENO
SLOT
Channel 2
Voltage
Output
VOUT1
01
GND1
02
I REF 1
Earth 03
SHIELD
04
Connect this shield to Connect this shield I OUT1
05
Earth busbar or to to ‘SHIELD’ GND 1
06
shield terminal on terminal. SHIELD
07
external Electronic
08
controller to which VOUT2
09
output signal is GND2
10
I REF 2
11
Current 12
SHIELD
Output 13
I OUT2
GND 2
14
SHIELD
15
16
+24 V.
Earth 17
0V
18
EARTH
19
FG
20
2 CH
+ 24 V GND Earth
Earth ANALOG OUTPUT
V/I
In figure 5, first channel is connected for analog voltage output (-10 VDC
to +10 VDC). For interfacing analog signals, 20-pin removable terminal
block is provided. Voltage output is taken from terminals V OUTn and
GNDn. n is a channel number.
Input module in first two slots consumes IB0 to IB7 of input image. 2-
channel analog output module in slot 2 consumes four bytes i.e. QB8 to
QB11 of output image. 16 DC output module in slot 3 consumes QB12
and QB13 of output image.
4.2 Programming
5. Troubleshooting
• Module as a whole
• Specific channel only
• Application Program.
Equipment required
Screw driver
Digital multi-meter with measuring facility for
DC voltage (with high precision)
Continuity and resistance
Set up for on line monitoring of application program as follows
PC with Programming and Documentation software.
PC to NEXGEN PLC Cable
Diagnosis Over
ON No 24V Supply OFF
LED status? O ERR LED
ON Status ? OFF
Replace Module
Module Error
ON System bit Status? OFF
Replace Module
YES Module NO
working OK?
Diagnosis Over
A
Voltage output OK as
NO per binary data? YES
Voltage output OK as
NO per binary data? YES
Voltage output OK as
YES per binary data? NO
* The fuse should be replaced by same type
strictly Diagnosis Over Contact MESSUNG
Rating - 315 mA, 250 V SYSTEMS
Sub- miniature fuse link no. 372
Make – WICKMANN
Note – For healthy operation of module always ensure that supply to module is within specified
range i.e. 18 VDC to 30 VDC including ripple.
If PLC is in 'STOP' mode, voltage output remains at zero whereas current output remains at 4 mA.
MESSUNG SYSTEMS