0% found this document useful (0 votes)
88 views14 pages

08 33 23 Overhead Coiling Doors

This document provides specifications for overhead coiling doors for a University of Houston construction project. It includes sections related to general requirements, performance requirements to withstand wind and impacts, submittal requirements, and door material and construction details. Performance standards are specified for structural strength, operability under wind loads, and impact resistance. Sample submittal items and material requirements are outlined for door curtains, endlocks, bottom bars, guides, and hoods.

Uploaded by

omar shady
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
88 views14 pages

08 33 23 Overhead Coiling Doors

This document provides specifications for overhead coiling doors for a University of Houston construction project. It includes sections related to general requirements, performance requirements to withstand wind and impacts, submittal requirements, and door material and construction details. Performance standards are specified for structural strength, operability under wind loads, and impact resistance. Sample submittal items and material requirements are outlined for door curtains, endlocks, bottom bars, guides, and hoods.

Uploaded by

omar shady
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 14

University of Houston Master Construction Specifications

<%Insert Project Name%>

SECTION 08 33 23 - OVERHEAD COILING DOORS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Service doors.
2. Counter doors.

B. Related Sections:
1. Section 05 50 00 "Metal Fabrications" for miscellaneous steel supports.
2. Section 09 91 13 "Exterior Painting" and Section 09 91 23 "Interior Painting" for finish
painting of factory-primed doors.

1.3 PERFORMANCE REQUIREMENTS

A. Delegated Design: Design overhead coiling doors, including comprehensive engineering


analysis by a qualified professional engineer, using performance requirements and design
criteria indicated.

B. Structural Performance, Exterior Doors: Exterior overhead coiling doors shall withstand the
wind loads, the effects of gravity loads, and loads and stresses within limits and under
conditions indicated according to [SEI/ASCE 7] <Insert requirement>.

1. Wind Loads: [As indicated on Drawings] [Uniform pressure (velocity pressure) of 20


lbf/sq. ft., acting inward and outward] <Insert loads>.

a. Basic Wind Speed: [85 mph] [90 mph] [100 mph] [110 mph] <Insert value>.
b. Importance Factor: <Insert factor>.
c. Exposure Category: [A] [B] [C] [D].

2. Deflection Limits: Design overhead coiling doors to withstand design wind load without
evidencing permanent deformation or disengagement of door components.

C. Operability under Wind Load: Design overhead coiling doors to remain operable under
[design] [uniform pressure (velocity pressure) of 20 lbf/sq. ft.] <Insert load> wind load, acting
inward and outward.

AE Project #: <%Project Number%> Overhead Coiling Doors 08 33 23 - 1


Revision Date: 1/29/2018
University of Houston Master Construction Specifications
<%Insert Project Name%>

D. Windborne-Debris-Impact-Resistance Performance: Provide [glazed] [and] [impact-


protective] overhead coiling doors that pass missile-impact and cyclic-pressure tests when
tested according to [ASTM E 1886 and ASTM E 1996] <Insert requirement>.

1. Large Missile Test: For overhead coiling doors located within 30 feet of grade.

E. Operation Cycles: Provide overhead coiling door components and operators capable of
operating for not less than number of cycles indicated for each door. One operation cycle is
complete when a door is opened from the closed position to the fully open position and
returned to the closed position.

1.4 ACTION SUBMITTALS

A. Product Data: For each type and size of overhead coiling door and accessory. Include the
following:

1. Construction details, material descriptions, dimensions of individual components,


profiles for slats, and finishes.
2. Rated capacities, operating characteristics, electrical characteristics, and furnished
accessories.
3. For fire-rated doors, description of fire-release system including testing and resetting
instructions.

B. Shop Drawings: For each installation and for special components not dimensioned or detailed
in manufacturer's product data. Include plans, elevations, sections, details, and attachments
to other work.

1. Detail equipment assemblies and indicate dimensions, weights, loads, required


clearances, method of field assembly, components, and location and size of each field
connection.
2. Wiring Diagrams: For power, signal, and control wiring.

C. Samples for Initial Selection: Manufacturer's finish charts showing full range of colors and
textures available for units with factory-applied finishes.

1. Include similar Samples of accessories involving color selection.

D. Samples for Verification: For each type of exposed finish required, prepared on Samples of
size indicated below.

1. Curtain Slats: 12 inches long.


2. Bottom Bar: 6 inches long[ with sensor edge].
3. Guides: 6 inches long.
4. Brackets: 6 inches square.
5. Hood: 6 inches square.

AE Project #: <%Project Number%> Overhead Coiling Doors 08 33 23 - 2


Revision Date: 1/29/2018
University of Houston Master Construction Specifications
<%Insert Project Name%>

E. Delegated-Design Submittal: For overhead coiling doors indicated to comply with


performance requirements and design criteria, including analysis data signed and sealed by
the qualified professional engineer responsible for their preparation.

1. Detail fabrication and assembly of seismic restraints.


2. Summary of forces and loads on walls and jambs.

1.5 INFORMATIONAL SUBMITTALS

A. Qualification Data: For qualified Installer.

1.6 CLOSEOUT SUBMITTALS

A. Maintenance Data: For overhead coiling doors to include in maintenance manuals.

1.7 QUALITY ASSURANCE

A. Installer Qualifications: Manufacturer's authorized representative who is trained and


approved for both installation and maintenance of units required for this Project.

B. Source Limitations: Obtain overhead coiling doors from single source from single
manufacturer.

1. Obtain operators and controls from overhead coiling door manufacturer.

C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA  70, by
a qualified testing agency, and marked for intended location and application.

D. Regulatory Requirements: Comply with applicable provisions in [the U.S. Architectural &
Transportation Barriers Compliance Board's ADA-ABA Accessibility Guidelines] [and] [ICC/ANSI
A117.1].

PART 2 - PRODUCTS

2.1 DOOR CURTAIN MATERIALS AND CONSTRUCTION

A. Door Curtains: Fabricate overhead coiling-door curtain of interlocking metal slats, designed to
withstand wind loading indicated, in a continuous length for width of door without splices.
Unless otherwise indicated, provide slats of thickness and mechanical properties
recommended by door manufacturer for performance, size, and type of door indicated, and as
follows:
1. Steel Door Curtain Slats: Zinc-coated (galvanized), cold-rolled structural steel sheet;
complying with ASTM A 653/A 653M, with G90 (Z275) zinc coating; nominal sheet
thickness (coated) of 0.028 inch and as required to meet requirements.

AE Project #: <%Project Number%> Overhead Coiling Doors 08 33 23 - 3


Revision Date: 1/29/2018
University of Houston Master Construction Specifications
<%Insert Project Name%>

2. Aluminum Door Curtain Slats: ASTM B 209 sheet or ASTM B 221 extrusions, alloy and
temper standard with manufacturer for type of use and finish indicated; thickness of
0.050 inch and as required to meet requirements.

B. Endlocks and Windlocks for Service Doors: Malleable-iron casings galvanized after fabrication,
secured to curtain slats with galvanized rivets or high-strength nylon. Provide locks on not less
than alternate curtain slats for curtain alignment and resistance against lateral movement.

C. Endlocks for Counter Doors: Manufacturer's standard locks on not less than alternate curtain
slats for curtain alignment and resistance against lateral movement.

D. Bottom Bar for Service Doors: Consisting of two angles, each not less than 1-1/2 by 1-1/2 by
1/8 inch thick; fabricated from manufacturer's standard hot-dip galvanized steel, stainless
steel, or aluminum extrusions to match curtain slats and finish.

E. Bottom Bar for Counter Doors: Manufacturer's standard continuous channel or tubular shape,
fabricated from manufacturer's standard hot-dip galvanized steel, stainless steel, or aluminum
extrusions to match curtain slats and finish.

F. Astragal for Interior Doors: Equip each door bottom bar with a replaceable, adjustable,
continuous, compressible gasket of flexible vinyl, rubber, or neoprene as a cushion bumper.

G. Curtain Jamb Guides: Manufacturer's standard angles or channels and angles of same material
and finish as curtain slats unless otherwise indicated, with sufficient depth and strength to
retain curtain, to allow curtain to operate smoothly, and to withstand loading. Slot bolt holes
for guide adjustment. Provide removable stops on guides to prevent overtravel of
curtain[, and a continuous bar for holding windlocks].

2.2 HOOD

A. General: Form sheet metal hood to entirely enclose coiled curtain and operating mechanism
at opening head. Contour to fit end brackets to which hood is attached. Roll and reinforce top
and bottom edges for stiffness. Form closed ends for surface-mounted hoods and fascia for
any portion of between-jamb mounting that projects beyond wall face. Equip hood with
intermediate support brackets as required to prevent sagging.
1. Galvanized Steel: Nominal 0.028-inch- thick, hot-dip galvanized steel sheet with G90
(Z275) zinc coating, complying with ASTM A 653/A 653M.

2. Aluminum: 0.040-inch- thick aluminum sheet complying with ASTM B 209, of alloy and
temper recommended by manufacturer and finisher for type of use and finish indicated.

2.3 COUNTER DOORS

A. Integral Frame, Hood, and Fascia for Counter Door: Welded sheet metal assembly of the
following sheet metal:

AE Project #: <%Project Number%> Overhead Coiling Doors 08 33 23 - 4


Revision Date: 1/29/2018
University of Houston Master Construction Specifications
<%Insert Project Name%>

1. Galvanized Steel: Nominal [0.064-inch-] <Insert thickness> thick, hot-dip galvanized


steel sheet with G90 zinc coating, complying with ASTM A 653/A 653M.
2. Stainless Steel: [0.062-inch-] <Insert thickness> thick stainless-steel sheet, Type 304,
complying with ASTM A 666.

B. Integral Metal Sill for Counter Door: Fabricate sills as integral part of frame assembly of
Type 304 stainless steel in manufacturer's standard thickness with [No. 4] <Insert finish>
finish.

C. Fire-Rated, Laminate Counter: Fire-door manufacturer's high-pressure decorative laminate-


covered countertop, UL or ITS tested and labeled for 1-1/2-hour fire rating for approved use
with fire-door assembly.

2.4 LOCKING DEVICES

A. Slide Bolt: Fabricate with side-locking bolts to engage through slots in tracks for locking by
padlock, located on both left and right jamb sides, operable from coil side.

B. Locking Device Assembly: Fabricate with cylinder lock, spring-loaded dead bolt, operating
handle, cam plate, and adjustable locking bars to engage through slots in tracks.

1. Lock Cylinders: Provide cylinders [specified in Section 08 71 00 "Door Hardware"]


[standard with manufacturer] [and keyed to building keying system].
2. Keys: Provide [two] [three] <Insert number> for each cylinder.

C. Chain Lock Keeper: Suitable for padlock.

D. Safety Interlock Switch: Equip power-operated doors with safety interlock switch to disengage
power supply when door is locked.

2.5 CURTAIN ACCESSORIES

A. Smoke Seals: Equip each fire-rated door with smoke-seal perimeter gaskets for smoke and
draft control as required for door listing and labeling by a qualified testing agency.

B. Weatherseals: Equip each exterior door with weather-stripping gaskets fitted to entire
perimeter of door for a weathertight installation, unless otherwise indicated.

1. At door head, use 1/8-inch- thick, replaceable, continuous sheet secured to inside of
hood.
2. At door jambs, use replaceable, adjustable, continuous, flexible, 1/8-inch- thick seals of
flexible vinyl, rubber, or neoprene.

C. Push/Pull Handles: Equip each push-up-operated or emergency-operated door with lifting


handles on each side of door, finished to match door.

1. Provide pull-down straps or pole hooks for doors more than 84 inches high.

AE Project #: <%Project Number%> Overhead Coiling Doors 08 33 23 - 5


Revision Date: 1/29/2018
University of Houston Master Construction Specifications
<%Insert Project Name%>

2.6 COUNTERBALANCING MECHANISM

A. General: Counterbalance doors by means of manufacturer's standard mechanism with an


adjustable-tension, steel helical torsion spring mounted around a steel shaft and contained in
a spring barrel connected to top of curtain with barrel rings. Use grease-sealed bearings or
self-lubricating graphite bearings for rotating members.

B. Counterbalance Barrel: Fabricate spring barrel of manufacturer's standard hot-formed,


structural-quality, welded or seamless carbon-steel pipe, of sufficient diameter and wall
thickness to support rolled-up curtain without distortion of slats and to limit barrel deflection
to not more than 0.03 in./ft. of span under full load.

C. Spring Balance: One or more oil-tempered, heat-treated steel helical torsion springs. Size
springs to counterbalance weight of curtain, with uniform adjustment accessible from outside
barrel. Secure ends of springs to barrel and shaft with cast-steel barrel plugs.

D. Torsion Rod for Counterbalance Shaft: Fabricate of manufacturer's standard cold-rolled steel,
sized to hold fixed spring ends and carry torsional load.

E. Brackets: Manufacturer's standard mounting brackets of either cast iron or cold-rolled steel
plate.

2.7 MANUAL DOOR OPERATORS

A. Equip door with manufacturer's recommended manual door operator unless another type of
door operator is indicated.

B. Push-up Door Operation: Design counterbalance mechanism so required lift or pull for door
operation does not exceed 25 lbf .

C. Chain-Hoist Operator: Consisting of endless steel hand chain, chain-pocket wheel and guard,
and gear-reduction unit with a maximum 25 lbf force for door operation. Provide alloy-steel
hand chain with chain holder secured to operator guide.

D. Crank Operator: Consisting of crank and crank gearbox, steel crank drive shaft, and gear-
reduction unit, of type indicated. Size gears to require not more than 25 lbf force to turn
crank. Fabricate gearbox to be oil tight and to completely enclose operating mechanism.
Provide manufacturer's standard crank-locking device.

2.8 ELECTRIC DOOR OPERATORS

A. General: Electric door operator assembly of size and capacity recommended and provided by
door manufacturer for door[ and operation-cycles requirement] specified, with electric motor
and factory-prewired motor controls, starter, gear-reduction unit, solenoid-operated brake,
clutch, remote-control stations, control devices, integral gearing for locking door, and
accessories required for proper operation.

AE Project #: <%Project Number%> Overhead Coiling Doors 08 33 23 - 6


Revision Date: 1/29/2018
University of Houston Master Construction Specifications
<%Insert Project Name%>

1. Comply with NFPA 70.


2. Provide control equipment complying with NEMA ICS 1, NEMA ICS 2, and NEMA ICS 6,
with NFPA 70 Class 2 control circuit, maximum 24 V, ac or dc.

B. Usage Classification: Electric operator and components capable of operating for not less than
number of cycles per hour indicated for each door.

C. Door Operator Location(s): Operator location indicated for each door.

1. Top-of-Hood Mounted: Operator is mounted to the right or left door head plate with
the operator on top of the door-hood assembly and connected to the door drive shaft
with drive chain and sprockets. Headroom is required for this type of mounting.
2. Front-of-Hood Mounted: Operator is mounted to the right or left door head plate with
the operator on coil side of the door-hood assembly and connected to the door drive
shaft with drive chain and sprockets. Front clearance is required for this type of
mounting.
3. Wall Mounted: Operator is mounted to the inside front wall on the left or right side of
door and connected to door drive shaft with drive chain and sprockets. Side room is
required for this type of mounting. Wall mounted operator can also be mounted above
or below shaft; if above shaft, headroom is required.
4. Bench Mounted: Operator is mounted to the right or left door head plate and
connected to the door drive shaft with drive chain and sprockets. Side room is required
for this type of mounting.

D. Electric Motors: Comply with NEMA designation, temperature rating, service factor, enclosure
type, and efficiency requirements specified in Section 11 05 13 "Common Motor Requirements
for Equipment" unless otherwise indicated.

1. Electrical Characteristics:

a. Phase: [Single phase] [Polyphase].


b. Volts: [115] [208] [230] [460] <Insert value> V.
c. Hertz: 60.

2. Motor Type and Controller: Reversible motor and controller (disconnect switch) for
motor exposure indicated.
3. Motor Size: Minimum size as indicated. If not indicated, large enough to start,
accelerate, and operate door in either direction from any position, at a speed not less
than 8 in./sec. and not more than 12 in./sec., without exceeding nameplate ratings or
service factor.
4. Operating Controls, Controllers (Disconnect Switches), Wiring Devices, and Wiring:
Manufacturer's standard unless otherwise indicated.
5. Coordinate wiring requirements and electrical characteristics of motors and other
electrical devices with building electrical system and each location where installed.

E. Limit Switches: Equip each motorized door with adjustable switches interlocked with motor
controls and set to automatically stop door at fully opened and fully closed positions.

AE Project #: <%Project Number%> Overhead Coiling Doors 08 33 23 - 7


Revision Date: 1/29/2018
University of Houston Master Construction Specifications
<%Insert Project Name%>

F. Obstruction Detection Device: Equip motorized door with indicated external automatic safety
sensor capable of protecting full width of door opening.[  For non-fire-rated doors, activation
of device immediately stops and reverses downward door travel.] [  For fire-rated doors,
activation delays closing.]

1. Photoelectric Sensor: Manufacturer's standard system designed to detect an


obstruction in door opening without contact between door and obstruction.

a. Self-Monitoring Type: Designed to interface with door operator control circuit to


detect damage to or disconnection of sensing device. When self-monitoring
feature is activated, door closes only with sustained pressure on close button.

2. Sensor Edge: Automatic safety sensor edge, located within astragal or weather stripping
mounted to bottom bar. Contact with sensor activates device. Connect to control
circuit using manufacturer's standard take-up reel or self-coiling cable.

a. Self-Monitoring Type: Four-wire configured device designed to interface with


door operator control circuit to detect damage to or disconnection of sensor
edge.

G. Remote-Control Station: Momentary-contact, three-button control station with push-button


controls labeled "Open," "Close," and "Stop."

1. Interior units, full-guarded, surface-mounted, heavy-duty type, with general-purpose


NEMA ICS 6, Type 1 enclosure.
2. Exterior units, full-guarded, standard-duty, surface-mounted, weatherproof type,
NEMA ICS 6, Type 4 enclosure, key operated.

H. Emergency Manual Operation: Equip each electrically powered door with capability for
emergency manual operation. Design manual mechanism so required force for door operation
does not exceed [25 lbf] [30 lbf] <Insert force>.

I. Emergency Operation Disconnect Device: Equip operator with hand-operated disconnect


mechanism for automatically engaging manual operator and releasing brake for emergency
manual operation while disconnecting motor without affecting timing of limit switch. Mount
mechanism so it is accessible from floor level. Include interlock device to automatically
prevent motor from operating when emergency operator is engaged.

J. Motor Removal: Design operator so motor may be removed without disturbing limit-switch
adjustment and without affecting emergency manual operation.

K. Audible and Visual Signals: Audible alarm and visual indicator lights in compliance with
regulatory requirements for accessibility.

L. Radio-Control System: Consisting of the following:

1. Three-channel universal coaxial receiver to open, close, and stop door; [one] [two]
<Insert number> per operator.
2. Multifunction remote control.

AE Project #: <%Project Number%> Overhead Coiling Doors 08 33 23 - 8


Revision Date: 1/29/2018
University of Houston Master Construction Specifications
<%Insert Project Name%>

3. Remote-antenna mounting kit.

2.9 DOOR ASSEMBLY <Insert drawing designation>

A. Service Door: Overhead coiling door formed with curtain of interlocking metal slats.

1. Basis-of-Design Product: Subject to compliance with requirements, provide Series 620


rolling door by Overhead Door Corporation, or comparable product by one of the
following:

a. ACME Rolling Doors, model FWMO.


b. Cornell Iron Works, Inc.,model ESD10.
c. Substitutions: See Section 01 25 00 - Substitution Procedures.

B. Operation Cycles: Not less than [10,000] [20,000] [50,000] [100,000] <Insert number>.

1. Include tamperproof cycle counter.

C. Door Curtain Material: Galvanized steel .

D. Door Curtain Slats: [Curved] [Flat] profile slats of [1-1/4-inch] [1-1/2-inch] [1-7/8-inch] [2-5/8-
inch] [3-1/4-inch] <Insert dimension> center-to-center height.

E. Curtain Jamb Guides: Galvanized steel with exposed finish matching curtain slats.  Provide
continuous integral wear strips to prevent metal-to-metal contact and to minimize operational
noise.

F. Hood: [Match curtain material and finish] [Galvanized steel] [Stainless steel] [Aluminum].

1. Shape: Round .
2. Mounting: As shown on Drawings.

G. Locking Devices: Equip door with [slide bolt for padlock] [locking device assembly] [and] [chain
lock keeper].

1. Locking Device Assembly: [Single-jamb side] [Cremone type, both jamb sides] locking
bars, operable from [inside with thumb turn] [outside with cylinder] [outside only,
with cylinder] [inside and outside with cylinders] <Insert requirement>.

H. Manual Door Operator: [Push-up operation] [Chain-hoist operator] [Manufacturer's standard


crank operator] [Awning-crank operator] [Wall-crank operator].

1. Provide operator with manufacturer's standard removable operating arm.

I. Electric Door Operator:

1. Usage Classification: [Heavy duty, 60 to 90 cycles per hour] [Standard duty, up to 60


cycles per hour] [Medium duty, up to 15 cycles per hour] [Light duty, up to 10 cycles
per hour] <Insert classification>.

AE Project #: <%Project Number%> Overhead Coiling Doors 08 33 23 - 9


Revision Date: 1/29/2018
University of Houston Master Construction Specifications
<%Insert Project Name%>

2. Operator Location: [Top of hood] [Front of hood] [Wall] [Bench] [Through wall] [As
shown on Drawings].
3. Motor Exposure: [Interior] [Exterior, wet, and humid].
4. Emergency Manual Operation: [Push-up] [Chain] [Crank] type.
5. Obstruction-Detection Device: Automatic [photoelectric sensor] [electric sensor edge
on bottom bar] [pneumatic sensor edge on bottom bar] [; self-monitoring type].

a. Sensor Edge Bulb Color: [Black] [As selected by Architect from manufacturer's
full range] <Insert color>.

6. Remote-Control Station: [Interior] [Exterior] [Where shown on Drawings] <Insert


location>.
7. Other Equipment: [Audible and visual signals] [Radio-control system] <Insert device>.

J. Door Finish:

1. Aluminum Finish: [Mill] [Clear anodized] [Light bronze anodized] [Medium bronze
anodized] [Dark bronze anodized] [Black anodized] [Anodized color matching
Architect's sample] [Anodized color as selected by Architect from full range of industry
colors and color densities] <Insert color>.
2. Baked-Enamel or Powder-Coated Finish: [Color as indicated by manufacturer's
designations] [Color matching Architect's sample] [Color as selected by Architect from
manufacturer's full range] <Insert color and gloss>.
3. Factory Prime Finish: Manufacturer's standard color.
4. Stainless-Steel Finish: [No. 2B (bright, cold rolled)] [No. 4 (polished directional satin)]
<Insert finish>.
5. Interior Curtain-Slat Facing: [Match finish of exterior curtain-slat face] [PVC plastic]
<Insert finish>.

2.10 DOOR ASSEMBLY <Insert drawing designation>

A. Counter Door: Overhead coiling door formed with curtain of interlocking metal slats.

1. Basis-of-Design Product: Subject to compliance with requirements, provide Series 652


Counter shutter by Overhead Door Corporation, or comparable product by one of the
following:

a. ACME Rolling Doors, Counter Shutter.


b. Cornell Iron Works, Inc., model ESC10
c. Substitutions: See Section 01 25 00 - Substitution Procedures.

B. Operation Cycles: Not less than [10,000] [20,000] [50,000] [100,000] <Insert number>.

1. Include tamperproof cycle counter.

C. STC Rating: [26] <Insert STC rating>.

AE Project #: <%Project Number%> Overhead Coiling Doors 08 33 23 - 10


Revision Date: 1/29/2018
University of Houston Master Construction Specifications
<%Insert Project Name%>

D. Curtain R-Value: [4.5 deg F x h x sq. ft./Btu] [5.0 deg F x h x sq. ft./Btu] [6.0 deg F x h x sq.
ft./Btu] <Insert value>.

E. Door Curtain Material: [Galvanized steel] [Stainless steel] [Aluminum].

F. Door Curtain Slats: [Curved] [Flat] profile slats of [1-1/4-inch] [1-1/2-inch] [1-7/8-inch] [2-5/8-
inch] [3-1/4-inch] <Insert dimension> center-to-center height.

1. Perforated Slats: Approximately [1/16-inch pinholes] [3/32-inch pinholes] [7/8-inch-


wide by 3/8-inch- high slots] <Insert dimensions>.

G. Curtain Jamb Guides: [Galvanized steel] [Stainless steel] [Aluminum] with exposed finish
matching curtain slats.[  Provide continuous integral wear strips to prevent metal-to-metal
contact and to minimize operational noise.] [  Provide removable post(s) and jamb guides
where shown on Drawings.]

H. Hood: [Match curtain material and finish] [Galvanized steel] [Stainless steel] [Aluminum].

1. Shape: [Round] [Square] [As shown on Drawings] <Insert shape>.


2. Mounting: [Face of wall] [Between jambs] [As shown on Drawings].

I. Integral Frame, Hood, and Fascia for Counter Door: [Galvanized steel] [Stainless steel].

1. Mounting: [Face of wall] [Between jambs] [As shown on Drawings].

J. Sill Configuration for Counter Door: [No sill] [Integral metal sill].

K. Locking Devices: Equip door with [slide bolt for padlock] [locking device assembly] [and] [chain
lock keeper].

1. Locking Device Assembly: [Single-jamb side] [Cremone type, both jamb sides] locking
bars, operable from [inside with thumb turn] [outside with cylinder] [outside only,
with cylinder] [inside and outside with cylinders] <Insert requirement>.

L. Manual Door Operator: [Push-up operation] [Chain-hoist operator] [Manufacturer's standard


crank operator] [Awning-crank operator] [Wall-crank operator].

1. Provide operator with manufacturer's standard removable operating arm.

M. Electric Door Operator:

1. Usage Classification: [Heavy duty, 60 to 90 cycles per hour] [Standard duty, up to 60


cycles per hour] [Medium duty, up to 15 cycles per hour] [Light duty, up to 10 cycles
per hour] <Insert classification>.
2. Operator Location: [Top of hood] [Front of hood] [Wall] [Bench] [Through wall] [As
shown on Drawings].
3. Motor Exposure: [Interior] [Exterior, wet, and humid].
4. Emergency Manual Operation: [Push-up] [Chain] [Crank] type.

AE Project #: <%Project Number%> Overhead Coiling Doors 08 33 23 - 11


Revision Date: 1/29/2018
University of Houston Master Construction Specifications
<%Insert Project Name%>

5. Obstruction-Detection Device: Automatic [photoelectric sensor] [electric sensor edge


on bottom bar] [pneumatic sensor edge on bottom bar] [; self-monitoring type].

a. Sensor Edge Bulb Color: [Black] [As selected by Architect from manufacturer's
full range] <Insert color>.

6. Remote-Control Station: [Interior] [Exterior] [Where shown on Drawings] <Insert


location>.
7. Other Equipment: [Audible and visual signals] [Radio-control system] <Insert device>.

N. Door Finish:

1. Aluminum Finish: Clear anodized.

2.11 GENERAL FINISH REQUIREMENTS

A. Comply with NAAMM's "Metal Finishes Manual for Architectural and Metal Products" for
recommendations for applying and designating finishes.

B. Appearance of Finished Work: Noticeable variations in same piece are not acceptable.
Variations in appearance of adjoining components are acceptable if they are within the range
of approved Samples and are assembled or installed to minimize contrast.

2.12 ALUMINUM FINISHES

A. Mill Finish: Manufacturer's standard.

B. Clear Anodic Finish: AAMA 611, [AA-M12C22A41, Class I, 0.018 mm] [AA-M12C22A31, Class II,
0.010 mm] or thicker.

C. Color Anodic Finish: AAMA 611, [AA-M12C22A42/A44, Class I, 0.018 mm]


[AA-M12C22A32/A34, Class II, 0.010 mm] or thicker.

D. Baked-Enamel or Powder-Coat Finish: AAMA 2603. Comply with coating manufacturer's


written instructions for cleaning, conversion coating, application, and baking.

2.13 STEEL AND GALVANIZED-STEEL FINISHES

A. Factory Prime Finish: Manufacturer's standard primer, compatible with field-applied finish.
Comply with coating manufacturer's written instructions for cleaning, pretreatment,
application, and minimum dry film thickness.

B. Baked-Enamel or Powder-Coat Finish: Manufacturer's standard baked-on finish consisting of


prime coat and thermosetting topcoat. Comply with coating manufacturer's written
instructions for cleaning, pretreatment, application, and minimum dry film thickness.

AE Project #: <%Project Number%> Overhead Coiling Doors 08 33 23 - 12


Revision Date: 1/29/2018
University of Houston Master Construction Specifications
<%Insert Project Name%>

2.14 STAINLESS-STEEL FINISHES

A. Surface Preparation: Remove tool and die marks and stretch lines, or blend into finish.

B. Polished Finishes: Grind and polish surfaces to produce uniform finish, free of cross scratches.

1. Run grain of directional finishes with long dimension of each piece.


2. When polishing is completed, passivate and rinse surfaces. Remove embedded foreign
matter and leave surfaces chemically clean.
3. Directional Satin Finish: No. 4.

C. Bright, Cold-Rolled, Unpolished Finish: No. 2B.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine substrates areas and conditions, with Installer present, for compliance with
requirements for substrate construction and other conditions affecting performance of the
Work.

B. Examine locations of electrical connections.

C. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 INSTALLATION

A. Install overhead coiling doors and operating equipment complete with necessary hardware,
anchors, inserts, hangers, and equipment supports; according to manufacturer's written
instructions and as specified.

B. Install overhead coiling doors, hoods, and operators at the mounting locations indicated for
each door.

C. Accessibility: Install overhead coiling doors, switches, and controls along accessible routes in
compliance with regulatory requirements for accessibility.

D. Fire-Rated Doors: Install according to NFPA 80.

E. Smoke-Control Doors: Install according to NFPA 80 and NFPA 105.

3.3 STARTUP SERVICE

A. Engage a factory-authorized service representative to perform startup service.

AE Project #: <%Project Number%> Overhead Coiling Doors 08 33 23 - 13


Revision Date: 1/29/2018
University of Houston Master Construction Specifications
<%Insert Project Name%>

1. Perform installation and startup checks according to manufacturer's written


instructions.
2. Test and adjust controls and safeties. Replace damaged and malfunctioning controls
and equipment.
3. Test door closing when activated by detector or alarm-connected fire-release system.
Reset door-closing mechanism after successful test.

3.4 ADJUSTING

A. Adjust hardware and moving parts to function smoothly so that doors operate easily, free of
warp, twist, or distortion.

B. Lubricate bearings and sliding parts as recommended by manufacturer.

C. Adjust seals to provide weathertight fit around entire perimeter.

3.5 DEMONSTRATION

A. Engage a factory-authorized service representative to train Owner's maintenance personnel to


adjust, operate, and maintain overhead coiling doors.

END OF SECTION 08 33 23

AE Project #: <%Project Number%> Overhead Coiling Doors 08 33 23 - 14


Revision Date: 1/29/2018

You might also like