ATeS Catalog

The ATeS Automatic Transfer Switch provides continuous power for critical applications by automatically transferring power sources between the load. It features a microprocessor-based controller to ease transfers between a primary and alternate source. The switch monitors sources for under/over voltage and other faults. It can also remotely control generator operation and includes timers to prolong source stability during outages. The ATeS facilitates reliable automatic transfers and easy installation for applications such as data centers, telecom, and more.

Uploaded by

saravanan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
65 views2 pages

ATeS Catalog

The ATeS Automatic Transfer Switch provides continuous power for critical applications by automatically transferring power sources between the load. It features a microprocessor-based controller to ease transfers between a primary and alternate source. The switch monitors sources for under/over voltage and other faults. It can also remotely control generator operation and includes timers to prolong source stability during outages. The ATeS facilitates reliable automatic transfers and easy installation for applications such as data centers, telecom, and more.

Uploaded by

saravanan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

ATeS

Automatic Transfer
Switch
Real-Time Monitoring | Improve Productivity

CONTROL YOUR POWER SOURCES!

Mechanical Specification:
The smartest approach to provide continuous power for critical A1
applications is to transfer sources between the load. ATeS (Automatic J

Transfer Switch) is designed with automatic start/stop DG operation to N

ease the transfer between primary source to alternate source for


R OX
providing continuous power supply. SAFE LOAD SAFE LOAD AUTO

L
Features:

B1
B
U
K
Automatic Transfer switch with inbuilt micro processor based AMF
controller
AC 32B Utilization Category and in coherence with IEC-60947-6-1
Source I & Source II protection against under/over voltage, Single
phase missing and optional overload tripping logic. P P P

External remote control logic by using PLC, ATS Controller or Genset


Controller. A

Availability of over load tripping with inverse curve logic (optional).


Optional Wifi communication and cloud connectivity for IoT
applications.
ATS With Wifi & Free 12 months Cloud Monitoring
Automatic start/stop operation of DG on mains failure. Incoming Terminal
Fire alarm / external fault trip feature is provided. Top
Inbuilt control switch for selecting auto/manual mode.
ATeS C
High capacity to withstand short circuit. (Standard)

E
External indication terminal for Source healthiness and load ON
Bottom
Status .
3 Position isolation lock for Source I – Off – Source II.
Outgoing Terminal
Phase sequence Enable/ Disable feature for Source I / Source II
S
G

T Outgoing Terminal
Y
Benefits: Top
Y1
ATeS R
Smooth and high-speed load transfer in the event of power outage or (Reverse)
disturbances in the power supply. Bottom
C
Incorporated with Fire Alarm/External fault trip and plays a pivotal
Incoming Terminal
role in providing maximum immunity to the electrical system from
fire risk/faults.
Spec. Outline Size (mm) Mounting Size (mm)
Systematized with time delays (timers) to prolong the stability of
40/63/80A In A A1 B B1 C E G J K L N P R S T U OX Y Y1
power source during automatic switching of sources in the case of 63 195 226 117 107 195 126 175 215 87 7 81 25 12 18 2 107 6 43 94

blackout or loss of power. Spec. Outline Size (mm) Mounting Size (mm)

Facilitates easy installation and ensures reliable performance. 100/125A In A A1 B B1 C E G J K L N P R S T U OX Y Y1


125 210 243 119 107 195 125 172 228 86 6.5 89 30 15 34.7 2.4 107 8 41 91

Spec. Outline Size (mm) Mounting Size (mm)

Application: 160A In A A1 B B1 C E G J K L N P R S T U OX Y Y1
160 200 302 135 127 204 136 200.5 287 101 8 100 36 20 23.5 3.5 126.5 10 69 151

Airport and Railways Spec. Outline Size (mm) Mounting Size (mm)
IT Malls and Commercial buildings 200/250A In A A1 B B1 C E G J K L N P R S T U OX Y Y1
Automobile Industry 250 332 375 165 134 240 154 172 348 109 6.5 100 50 24 30 3.5 134 11 69 151
Data Centre and Telecommunications
Spec. Outline Size (mm) Mounting Size (mm)
Oil and Gas Industry
315/400/630A In A A1 B B1 C E G J K L N P R S T U OX Y Y1
Manufacturing Industry 630 387 436 260 222 285 220 172 406 180 9 103 65 40 50.5 5 222 13 84 191
Healthcare
Spec. Outline Size (mm) Mounting Size (mm)
Banking and Finance 800/1000/
In A A1 B B1 C E G J K L N P R S T U OX Y Y1
1200/1600A 1600 536 636 330 337 373 230 440 612 220 11 83.5 120 80 65 8 222 13 106 240

elmeasure.com 25
27
Technical Specification:
40/63/80 100/125A 160/200/250A 315/400/630A 800/1000/1200/1600A
ELECTRICAL CHARACTERISTICS
Current Rating 40/63/80 100/125A 160/200/250A 315/400/630A 800/1000/1200/1600A
No. of Poles 4
Rated Operating Voltage 415V
Rated Insulation Voltage
(Ui) V – Power Circuit 690V
Rated Insulation Voltage
(Ui) V – Control Circuit 500V

Rated impulse withstand


voltage (Uimp) - Power Circuit 8kV

Rated impulse withstand


voltage (Uimp) – Control Circuit 4kV
Utilization Category AC – 32B
Rated control Power supply
Voltage 230V/50Hz

Rated short circuit withstand


current (KA, Rms) Icw(0.1/1s) 7/5 kA 9/5 kA 12/25 kA 50/25 kA 25/50 kA

Rated short circuit Making


Capacity (KA, Peak) Icm 8 kA 8 kA 17 kA 26 kA 55 kA

Rated Limit short circuit current


(KA) Iq 120 kA
Operating Cycle 10000 8000 6000 5000
Motor operating Voltage 220V AC (150-280 VAC) / 50-60Hz
Auxiliary DC voltage 12-24V DC
Standard IEC 60947-6-1

MEASUREMENT PARAMETERS
Primary Source Voltage, Frequency & Current (Optional)
Secondary Source Voltage, Frequency & Current (Optional)
Measurements Monitored In-Built Display / Remote Display
Communication RS485 / Wifi ( Optional)

PROGRAM CONFIGURATION
Under Voltage(160-210V)/Over Voltage (240-280V) , Over Load with external CT, Under Frequency (40-48Hz) /Over
Primary Source
Frequency (50-60Hz) and Phase sequence Enable / Disable

Under Voltage(160-210V) / Over Voltage (240-285V), Over Load with external CT, Under Frequency (40-48Hz) /Over
Secondary Source
Frequency (50-60Hz) and Phase sequence Enable / Disable
Timers Recovery delay (3 to 600s), Transfer delay(3 to 600s), Generator Start / Stop delay (3 to 600s), Trip Delay (3-60)
Priority selection Source I and Source II
Overload Source I (10-110%) and Source II (10-110%)
Overload Trip cycles Up to 4 cycles (6-150s)
AC System Selection 3Phase /1Phase for Both Sources
Phase Sequence Enable/Disable

APPLICATIONS
Transfer Between Utility Applicable
to Backup Power
Transfer between Utility Applicable
to Utility Power
MODE OF OPERATION
Selection Mode Auto/Manual/Remote/Cloud
Position order I-OFF-II
Functionality On Load
Manual Emergency Operation Available

MECHANICAL CHARACTERISTIC
Mounting Position A
Outline Dimension in mm 226X117X195 243X119X195 375X165X240 436X260X285 636x330x373
Weight in kg 4 5 10 20 60

GENERAL CHARACTERISTIC
Ambient temperature -20o to 55o C
Air Humidity Not more than 50% @ 40o C
Altitude Not more than 2000 m

ELECTROMAGNETIC CHARACTERISTIC
Class Class B
Radio Frequency Transmission
EN55011
Test
Radio Frequency radiation
EN55011
Transmission Test