0% found this document useful (0 votes)
217 views20 pages

Applied - Product Portfolio-401

The document discusses Daikin's product portfolio for 2019, focusing on their chillers and air side equipment. It provides details on Daikin's ranges of air-cooled and water-cooled chillers, designed to suit applications from small to large. It also discusses their high efficiency inverter chiller ranges, highlighting benefits for installers, consultants, and end users such as high efficiencies, low noise and energy consumption, and rapid return on investment.

Uploaded by

dromar99
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
217 views20 pages

Applied - Product Portfolio-401

The document discusses Daikin's product portfolio for 2019, focusing on their chillers and air side equipment. It provides details on Daikin's ranges of air-cooled and water-cooled chillers, designed to suit applications from small to large. It also discusses their high efficiency inverter chiller ranges, highlighting benefits for installers, consultants, and end users such as high efficiencies, low noise and energy consumption, and rapid return on investment.

Uploaded by

dromar99
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 20

Product portfolio 2019

Chillers
and air side
equipment
Daikin Chillers

Whatever your needs in climate control or process chilling,


there is a system that has proved its value in many situations –
from factories and warehouses to hotels and department stores,
and even district cooling for residential applications.

Daikin’s ranges of air-cooled and water-cooled chillers are designed Highest efficiency
to suit every application – large or small – offering the ultimate
in flexibility and control. The unique combination of advanced Using the latest technology, Daikin achieves industry-leading
technology, experience and reliability make Daikin chillers the efficiency and energy-saving operation for outstanding cost
ideal choice. saving performance.

Daikin chillers have nominal cooling capacities of 5kW to 2,148kW › Lowest total cost of ownership
(air-cooled) or 13kW to 2,173kW (water-cooled). › Fast payback time
› Environment-friendly solutions

Worldwide experience
Quality, reliability
A global leader in HVAC solutions, Daikin has the world’s most
advanced facilities for air conditioning research and development, › Zero defect policy ensures quality of components and
meaning that we can manufacture all main chiller components finished products
(compressors, fans, condenser coils, software) in-house. › All chillers factory run and subjected to quality audit
before shipment
› Eurovent and AHRI certification

1 Product portfolio
High Efficiency Inverter Chiller Ranges

High efficiency inverter chiller ranges for


comfort and process cooling / heating.

Why break from tradition? ErP


compliant
› Seasonal efficiency
2021

› Low noise levels


› Low starting currents
› Available with HFC R-134a or Low GWP HFO R1234ze(E)

High efficiencies both at full load and part load

Benefits for the installer › Daikin compressor with in-built inverter and Variable Volume
Ratio (VVR) for optimised efficiency
> Factory leak-tested and pre-charged › In-house developed software with dynamic condensing pressure
> High serviceability management and innovative economiser control logic
> User-friendly smart controls which can be integrated
easily with building management systems
Rapid return on investment

› Payback of three years, compared to a non-inverter unit for


Benefits for the consultant comfort cooling applications
› Less than one year for process cooling applications
> Multiple options available, e.g. rapid restart, variable
speed water pumps, smart energy meter, EC fans
> Ideal for both new and retrofit projects: same Perfect comfort level
footprint as of non-inverter unit with higher
efficiencies and performance › Infinitely variable load regulation
› Precise leaving water temperature control thanks to
stepless regulation

Benefits for the end user


Compact design
> Rapid payback of three years for comfort
cooling applications › More compact heat exchanger with superior efficiencies
> 50% reduction of energy consumption › Reduced electrical panel dimensions thanks to the inverter
> Designed for sound-sensitive environments compressor mounted

Product portfolio 2
Products Overview

Air Cooled Chillers and Condensing Units


Heat
Compressor Efficiency version Sound version
exchanger

Refrigerant circuits
Refrigerant type *

exchanger ****
Free cooling **

exchanger ***

High ambient
Outdoor heat
Water heat

Standard

Standard
Premium

Reduced
Inverter

Swing

Screw
Scroll

High

Low
Cooling only

EWAQ-BAVP R-410A 1 y y y
BPHE
y
Cu/Al
y y
EWAQ~ACV3/ACW1 R-410A 1 y y y
BPHE
y
Cu/Al y y
EWAQ~CW R-410A 1-2 y y y
BPHE
y
Cu/Al
y y
EWAQ~G- R-410A 1 y y
BPHE
y
MC
y y y y
EWAT-B- NEW R32 1-2 y
OPT
y y
BPHE
y
MC
y y y y y
EWAD~T- B R-134a 2 y y
S&T
y
MC
y y y y y
y y y y y y y y
POA

EWAD~CZ R-134a 2-3


S&T Cu/Al

EWAD~CF R-134a 2 y
STD
y y
S&T
y
Cu/Al
y y y y
EWAD-TZ C NEW R-134a 1-2 y y y
BPHE y y y y y y y
S&T MC

EWAH-TZ C NEW R-1234ze 1-2 y y y


BPHE y y y y y y y
S&T MC

Heat pump

EWYQ-BAVP R-410A 1 y y y
BPHE
y
Cu/Al y y
EWYQ~ACV3/ACW1 R-410A 1 y y y
BPHE
y
Cu/Al
y y
EWYQ~CW R-410A 1-2 y y y
BPHE
y
Cu/Al y y
SEHVX~BW
SERHQ~BW1
R-410A 1 y y y
BPHE
y
Cu/Al
y y
EWYQ~G- R-410A 1 y y
BPHE
y
Cu/Al
y y y
EWYQ~F- R-410A 1-2 y y y y y y y
POA

BPHE Cu/Al

EWYT-B- NEW R32 1-2 y y


BPHE
y
Cu/Al
y y y y
EWYD~BZ R-134a 2-3 y y y
S&T
y
Cu/Al y y y
Multifunctional 4-Pipe Cooling and Heating

y y y y y y y y
POA

EWYD-4Z B NEW R-134a 2


S&T Cu/Al

Condensing unit

ERAD~E- R-134a 1 y y
Cu/Al y y y
* (GWP) : R-410A (2087.5), R-134a (1430), R32 (675), R1234ze (7)
** STD: Included as standard, OPT: Available option
*** BPHE: Brazed plate heat exchanger, S&T: Single pass shell and tube exchanger
**** MC: Microchannel exchanger, Cu/Al: Copper tube Aluminium fin exchanger
***** Mandatory commissioning by Daikin Airconditioning UK

3 Product portfolio
Mini chillers Air cooled screw chillers
Ideal for residential or light commercial applications, Daikin mini Manufactured for large capacities, Daikin screw chillers deliver
chillers are equipped with an inverter swing or scroll compressor unparalleled reliability and efficiency, both for comfort and process
allowing a smooth, more reliable and energy-efficient operation cooling. Equipped with an inverter, they provide high efficiency at
with low noise levels and class-leading ESEERs. part load.

Air cooled scroll chillers Ecodesign


Daikin scroll chillers are designed for small and medium cooling
and heating capacities. Our wide range of models match every
building’s air conditioning and process cooling needs.
Air cooled applied products indicated are
Ecodesign Lot 1 compliant (heat pumps
below 400kW valid from 25 September 2017)
ErP
compliant
and Lot 21 compliant (chillers below 2MW
valid from 31 December 2017).

Cooling capacity (kW)


Heating capacity (kW)

0 17.5 200 500 1,000 2,000

2~8

7~17

17~75

69.3~154

***** Mandatory commissioning


80~700

290~2,148

1,200~1,800

602~1,555

170~2,100

170~1,500

0 17.5 200 500 1,000 2,000


2~8
3~8
9~17
10~15
17~75
17~75
21~62
21~64
75~165
82~170
158~624
***** Mandatory commissioning

173~674
70~700
Available Autumn 2019
78~750
247~580
271~618

0 17.5 200 500 1,000 2,000


400~800
400~800

0 17.5 200 500 1,000 2,000

116~488

Product portfolio 4
Variable Volume Ratio (VVR)
EWAD-TZC Chiller Series NEW
The operating conditions of a chiller are subjected to sensible
changes due to the variation of ambient temperature and load
Top class efficiency request from the plant.

EER up to 3.6 Screw compressors increase the pressure of the refrigerant by


ESEER up to 5.5 forcing it into a progressively smaller volume, from the suction
to the discharge port. Once the geometry of the compressor is
Best choice for every application defined, the volume ratio is also defined.

Rapid payback: one year for process cooling and three years for Daikin compressors can modify their own geometry thanks to
comfort cooling applications variable volume ratio (VVR). The volume ratio will change by
moving the sliding valves.
New generation of Daikin inverter screw compressors VVR changes the point at Max.
compression
which the gas leaves the ratio
› Integrated inverter, refrigerant cooled compressor, and therefore
› Variable Volume Ratio technology (VVR) changes the pressures Min.
compression
at discharge, so they ratio
Variable Volume Ratio (VVR)
Discharge port are optimal under any
condition.
Inverter

Economizer
& Liquid
injection ports Liquid inlet
(VFD cooling)
Capacitors

Aluminium
cooling plate
Suction port Silent operation –
for distraction-free work
Microchannel condenser coils
Nothing disrupts the workplace more than the sound of machinery.
› High thermal efficiency So our engineers have brought the sound power levels right down
› Small volume, resulting in less refrigerant charge to just 90 dB(A)* at full load operating conditions - and even lower
› Light & durable design at part load conditions. Thanks to the special acoustic executions
› Easy cleaned on the compressor and a custom Daikin fan design with reduced
noise impact and vibration, the EWAD-TZB is ideal for even the
most sound-sensitive environment.

*400 kW size

5 Product portfolio
Providing a lifetime of comfort in

the most flexible way


Application flexibility Proven reliability
All our chillers and compressors are subjected to intensive
Ambient temperature Ambient up to 52°C @ full load performance, acoustic, endurance and vibration tests in Daikin
factories and at selected job-sites - even at extreme working
conditions. This ensures maximum reliability in every component –
Comfort cooling and the right technical solution for your application.

Brine High temperature


(e.g. ice storage
food process)
process cooling
(e.g. data center) Extensive options list
Chilled water
temperature › HFO (R1234ze) - full range available with low GWP HFO: EWAH-
TZC
Chilled water down to -8°C Chilled water up to 18°C
› Rapid restart - when a loss of cooling would be catastrophic, the
chiller can restart within 30 seconds of the power being restored
and reach full-load cooling capacity in less than 6 minutes

› VFD pumps - variable frequency pumps can be used to optimise


Compact design the working efficiency of the chiller and maximise energy savings,
also in primary variable flow systems
The EWAD-TC keeps installation space to a minimum, so it’s ideal
for both new and retrofit projects. In particular, the highly efficient › Refrigerant leak detection - rapid advanced warning of trouble,
compressor with its integrated inverter allows us to mount more so you can avoid any environmentally harmful and potentially
compact heat exchangers in the frame and, combined with the costly leaks in the refrigerant system
integrated compact control panel, deliver more power from a
reduced footprint. › Heat recovery - a plate to plate heat exchanger for each
refrigerant circuit is installed in series to the condenser coil, so
between 15-85% of the total heat rejection of the chiller can be
recovered
Simple to install.
› Partial heat recovery - a plate to plate heat exchanger for each
Even simpler to maintain refrigerant circuit is installed in series to the air condenser coil.
The plant manager controls the operation of the pump on the
Our chillers are completely factory assembled with all required recovery circuit, so between 15-20% of the total heat rejection of
options and pre-commissioned, with the unit’s software fine the chiller can be recovered
tuned and set points established to suit the application. They
also integrate easily with existing building management systems. › Smart sequencing capbility - master/slave sequencing function:
So on site, all that is required is to connect power supply, pipes, up to four units connected together for system optimisation and
communication cables and switch the unit on. without the need of external control systems.

Product portfolio 6
A New Generation
of Chillers
First air cooled chiller with
environmental friendly R-32
refrigerant

EWAT-B- Chiller Series NEW

Top class efficiency Sound flexibility


> Top class efficiency with ESEER up to 4.33 (with VFD fans) > Available in Standard, Low and Reduced sound configurations
> Available in Silver and Gold efficiency versions

Wide capacity range Extensive options list


> Wide capacity range: 80 – 700kW > Extensive option lists including glycol free, refrigerant
> Single and dual circuit version overlapping between 150kW migration free cooling (full version Daikin patented), hydronic
and 350kW kits (inverter pumps), heat recovery, refrigeration leak detection.
> Master/slave integrated as standard, allowing to manage up to
four units on the same system without the need of external
Environmentally friendly control devices.
> Compatible with Daikin on Site cloud based monitoring
> The Global Warming Potential (GWP) of R-32 refrigerant is 675,
which is one third of R-410A refrigerant
> As a single component refrigerant, R-32 is easier to recycle
and reuse
> Microchannel condensing coil allows for reduced
refrigerant charge

7 Product portfolio
NEW EWYT-B R32 Heat pump chiller
FOR 2019 available to order from Autumn 2019

Single-V layout
› Slim layout
› Higher flexibility: new intermediate sound
configuration for both Silver and Gold versions

Multi-V layout
› Brand new layout
› Better part load efficiency
vs previous generation:
• +4% with standard arrangement
• +7% with VFD fan option

+ FREE + Optimised
cooling heating

Free-cooling – Light (glycol free) Benefits

The new Daikin R-32 Multi-V Refrigerant migration system allowing › Glycol free solution
recovery of up to 25% of nominal unit › No refrigerant pump required
chiller series can be offered capacity. › No extra footprint vs standard unit,
with innovative free-cooling except on full free-cooling 4 fan models
options to further improve › No extra pressure drops on water side
energy efficiency and reduce Free-cooling – Full (glycol free)
running costs. Refrigerant migration system allowing
recovery up to 75% of nominal unit capacity.

Product portfolio 8
High efficiency and versatility
Daikin reimagines and delivers revolutionary air conditioning to the world. As the industry leader, we will
continue creating new value by anticipating the future needs of customers for all environments.
Daikin chillers and air side equipment provide the ultimate in reliability and flexibility. Our chillers, fan coil
units and air handlers deliver superior efficiency across a wide range of applications.

Sound
Compressor Water heat exchangers Efficiency version
version
Refrigerant circuits
Refrigerant Type *

Centrifugal
Evaporator Condenser
Inverter

Screw
Scroll

Standard

Standard
Premium
BPHE **

BPHE **
S&T ***

S&T ***

High
Water cooled chillers (Cooling only & Heating only)

EWWQ~K R-410A 1-2-4-6 y y y y y


EWHQ~G- R-410A 1 y y y y y
EWWQ~G- R-410A 1 y y y y y
EWWQ~L- R-410A 2 y y y y y
y y y y y
POA

EWWD~J- R-134a 1
2 pass

EWWD~G- R-134a 1-2 y y


1 pass
y
1 pass y y y
EWWD-VZ R-134a 1-2 y y y
Flooded y y y y y
1, 2, 3 pass 1 pass

EWWH-VZ NEW R-1234ze 1-2 y y y


Flooded y
1 pass y y y y
1, 2, 3 pass

Condenserless chillers

EWLQ~K R-410A 1-2 y y y y


EWLQ~G- R-410A 1 y y y y
EWLQ~L- R-410A 2 y y y y
y y y y
POA

EWLD~J- R-134a 1-2

EWLD~G- R-134a 1-2 y y


1 pass y y
EWLD~I- R-134a 1-2-3 y y
1 pass y y
Water cooled centrifugal chillers

y y y y y y
POA

EWWD~FZ R-134a 1 Flooded


1, 2, 3 pass 1, 2, 3 pass

* (GWP) : R-410A (2087.5), R-134a (1430), R32 (675), R1234ze (7)


** BPHE: Brazed plate heat exchanger
*** S&T: Shell and tube exchanger
**** Mandatory commissioning by Daikin Airconditioning UK,

9 Product portfolio
Water cooled scroll chillers Water cooled, oil free centrifugal chillers
These units are among the most efficient, quiet and reliable chillers With a small footprint, quiet compressor and ability to integrate
available today and can be easily integrated with the HVAC system easily within the existing HVAC systems, this chiller is the ideal
of your choice. Their compact, modular design makes them ideal solution for large cooling requirements (e.g. district cooling) and
for replacement projects. offers a return on investment throughout its lifecycle.

Water cooled screw chillers Ecodesign


The Daikin water cooled screw chillers provide the ideal solution
for sound sensitive environments. Applications range from comfort
Water cooled applied products indicated
are Ecodesign Lot 1 compliant (heat pumps
ErP
compliant
cooling to ice making. Operated as a heat pump, the higher leaving below 400kW valid from 25 September 2017)
water temperatures of up to 65°C provides an ideal solution for low and Lot 21 compliant (chillers below 2MW
pressure hot water (LPHW) or district heating schemes. valid from 31 December 2017).
Cooling capacity (kW)
Heating capacity (kW)

0 17.5 200 500 1,000 2,000


13~183
17~234
87~352
118~462
94~370

**** Mandatory commissioning


118~468
187~721
234~917
120~284
155~374
165~602
209~743
450~2,100
550~2,500
340~1,600
408~1,920

0 17.5 200 500 1,000 2,000

12~57

87~346
**** Mandatory commissioning

173~676

110~529

160~524

315~1,433

0 17.5 200 500 1,000 2,000

113~1,054

Product portfolio 10
EWWD-VZ chiller series Compact construction
› Small footprint, ideal for installation through existing doorways

Top class efficiency


Width reduced
EER up to 5.8 below 900mm
ESEER up to 8.5 with knock down
panel options*
Best choice for every application
* 900 kW unit size
Daikin inverter single screw compressors
offer significant power reduction at part load 1245 mm 865 mm
operation, over a non inverter screw. At the 40% footprint reduction in comparison with traditional
50% partload capacity step, there is a 32% water cooled series thanks to:
reduction in power input, which is 147% 1. New single pass condenser technology
increase on EER. › Counterflow design delivers high heat exchange performance
› Low water pressure drops < 30 kPa
Why choose an inverter chiller? 2. New integrated oil separator technology
› -25% energy consumption › Low oil carry over
› -25% CO2 emissions › Low refrigerant pressure drops
› -25% running costs
› Return on investment < 2 years vs non-inverter chiller

45% Why are we better than others?


non inverter Daikin EWWD-VZ
41%
40%
› Full inverter capacity control down to 20%
100% › No inefficient mechanical unloading slides
33% 35% Compressor speed
100%
80% 30%
% of full load power input

Running hours

23% 25%
60% Savings
20% Others
50% Mechanical
40% 15%
unloading < 50%
10%
20% Full inverter
5%
3% Daikin control down to
20%
0% 0% EWWD-VZ min load!
100% 75% 50% 25% Unit capacity Full Load 50% Load 20% Load (min) Compressor load

11 Product portfolio
The highest peak in
chiller technology
Optimised design Connectivity
› Flooded type technology maximising unit performance Remote access with one click
› Latest technology enhanced surface tubes › Remote monitoring
› System optimisation
› Preventive maintenance
Dashboards
Remote
Evaporator tubes: Remote HMI maintenance report
access
› Outside: cavities for
optimised nucleate boiling Daikin on site
› Inside: helical structure Cloud platform

Condenser tubes: Remote Via LAN or GSM modem


› Outside: optimised for software Diagnostics
upgrade
condensation
› Inside: helical structure

Application flexibility Future readiness


Widest operating envelope suitable for a variety of applications, R-134A refrigerant, still the
both heating and cooling. best choice today:
Up to 65°C hot water › Still most efficient refrigerant
production and with › Available in high quantities and at competitive prices
Condenser water (°C)
optimised efficiencies › No phase out planned in F-GAS regulation
› Classified as non flammable
Evaporator
Evaporator Water Water up R1234ze refrigerant, low GWP range EWWD-VZ
Heat pump
down to -8°C to +20°C › GWP <10 for BREEAM
› Same efficiency as R132a

Brine/Ice Comfort Data center


storage All VZ units are ‘new refrigerant ready’!
Possibility to retrofit R134a units in the future with lower GWP
Evaporator water (°C) refrigerant R513a (HFO blend).

Product portfolio 12
Daikin Air Handling Units

Daikin air handling units, with their


plug-and-play design and inherent
flexibility, can be configured and
combined specifically to meet
ventilation or air conditioning
requirements.

Unique Plug-and-Play ventilation solution


Daikin fresh air package
Benefits for the installer The Daikin fresh air package provides a complete solution,
including all unit controls (expansion valve, control box
› Single source of supply for complete ventilation solution and AHU controller) and sensors, factory mounted and
› Completely wired with temperature and pressure sensors configured. This unique solution allows for plug and play
› No need for 3rd party design of coils and condenser selection connection of our AHU series to Daikin ERQ and VRV
› Factory pre-configured to meet design requirements condensers or chillers.

Benefits for the consultant High efficiency


› ErP compliant and Eurovent certified Daikin heat pumps are renowned for their high energy
› Pre-defined configuration with factory fitted option flexibility efficiency. Integrating the AHU with a heat recovery system
› Use of highest efficiency components to meet current and is even more effective, since an office system can frequently
future regulations - ErP2018 compliant be in cooling mode, while the outdoor air is too cold to be
› Manufacturer defined control algorithm and interface with brought inside in an unconditioned state. In this case, heat
cooling units from the offices is simply transferred to heat up the cold
incoming fresh air.

Benefits for the end user


High comfort levels
› Reduced energy costs due to high heat recovery potential
and efficient IE4 EC fan motors Daikin ERQ and VRV units respond rapidly to fluctuations
› Visibility of unit operation via central I-touch Manager in supply air temperature, resulting in a steady indoor
or BMS front end temperature and high comfort levels for the end user.
› Complete Daikin solution The ultimate is the VRV range which improves comfort even
more by offering continuous heating, also during defrost.

Daikin fresh air package


ADT

ERQ

+ or = Unique Daikin
ventilation
solution

VRV IV Chiller

13 Product portfolio
Air Handling Units
ALB- Modular-L AHU with high efficiency heat recovery
Energy efficiency and indoor air quality EC fan
> Available in Pro and Smart versions > Air flow or pressure control
> Predefined sizes (Variable Air Volume – Constant Air Volume)
> IE4 premium efficiency motor > Nominal air flow programmed at factory
> High efficiency aluminium plate heat exchanger (heat recovery)
> Advanced control option on Pro version utilising Siemens Simple, quick installation
MicroTech control platform
> Simplified control option on Smart version utilising The Modular series’ Plug & Play design is more than just a
P1/P2 platform convenient feature for installers. It offers cost-saving benefits as
> Easy installation there is no need for expensive adjustments before the unit is
> Very low height commissioned. Plug & Play makes everyone’s life simpler, safer and
> Wide operating limits more economical.
> Free cooling capability
> Economy and Night mode operation
> Monitoring and control through Daikin ITM
D-AHU Modular L - Base Unit
Size ALB02*B(S) ALB03*B(S) ALB04*B(S) ALB05*B(S) ALB06*B(S) ALB07*B(S)
Supply/Extract Airflow [m3/s] 0.08 0.17 0.33 0.42 0.64 0.75
Thermal Efficiency [%] 93 93 93 92 94 93
Maximum ESP [Pa] 160 100 175 150 150 140
Unit Nominal Performance

Nominal Fan Current - Supply and Extract [A] 0.52 1.17 1.91 2.48 4.39 5.39
Nominal Power Input [kW] 0.12 0.27 0.44 0.57 1.01 1.24
SFPv [kW/m3/s] 1.50 1.50 1.50 1.50 1.50 1.50
Electrical Supply [V-Ph-Hz] 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
Length [mm] 1660 1800 2000 2000 2000 2000
Width [mm] 920 1100 1600 1600 2000 2000
Height [mm] 280 350 415 415 500 500
Weight [kg] 125 180 270 280 355 360
Duct Connection Size (mm) Width 250 400 500 500 700 700
Height 150 200 300 300 400 400
(1)
Sound Power Level - Lw dB(A) 53 61 62 58 63 60
Sound Pressure Level - Lp dB(A)(2) 34 39 41 37 46 41

*Indicates handing of unit, R=Right Hand, L = Left Hand. (S) Indicates Modular Light Smart. (1) Sound Power Level. (2) Sound Pressure Level according to EN3744, Surrounding, Directivity (Q=2) at a distance of 1.5m.
Includes, F7 Filter on supply air and M5 filter on return air, Mineral wool insulation, Aluzinc internal skin and Aluzinc Pre-Painted external skin. Modular L Smart units require BRC1E53C wired remote controller or Madoka
BRC1H519(W,S,K).

Notes:
Ancillary modules include Silencers, Electric Frost Coils & various Heating/Cooling Coil Modules will be delivered loose for installation at site.
The SFP figure shown in the above table is based at the nominal airflow and nominal ESP shown.

Flexibility
bility to meet your needs

Heat exchanger

Filterrs
Filters

Rectangular duct flange

Supply/Return fan Bypass damper


Unit structure

Product portfolio 14
Air Handling Units
ADT-F/B Modular-R AHU with high efficiency
heat recovery
Energy efficiency and indoor air quality EC fan
> Predefined sizes > Air flow or pressure control
> IE4 premium efficiency motor (Variable Air Volume – Constant Air Volume)
> High efficiency heat wheel (heat recovery) > Nominal air flow programmed at factory
> Compact design > Reduced noise with option NRLS
> Advanced control features
> Easy installation Simple, quick installation
> Indoor air quality compliant with VDI 6022 hygiene guideline The Modular series’ Plug & Play design is more than just a
> Operating limits from -25 °C, -40 °C with electric heaters, convenient feature for installers. It offers cost-saving benefits as
up to +46 °C ambient temperature there is no need for expensive adjustments before the unit is
> VRV IV and ERQ coupling capability commissioned. Plug & Play makes everyone’s life simpler, safer and
> Indoor and outdoor versions more economical.
> Free cooling capability
> Economy and Night mode operation
> Monitoring and control through Daikin ITM

D-AHU Modular R - Base Unit c/w Thermal Wheel & DX Module


Size ADT01FCD1 ADT02FCD1 ADT03FCD1 ADT04FCD1 ADT05FCD1 ADT06FCD1 ADT07FCD1 ADT08FCD1 ADT09FCD1 ADT10FCD1
Supply/Extract Airflow [m3/s] 0.42 0.52 0.97 1.43 1.86 2.05 2.80 3.63 4.07 5.83
Temp Efficiency Winter [%] 80.50 81.90 80.30 80.90 80.60 81.00 80.40 79.60 80.70 80.00
Temp Efficiency Summer [%] 79.90 81.20 79.70 80.30 80.00 80.40 79.70 79.00 80.10 79.40
Unit Nominal Performance

ESP nominal [Pa] 250 250 250 250 250 250 250 250 250 250
Nominal Fan Current - Supply/Extract [A] 3.3/3.3 3.1/3.1 1.9/1.9 4.1/4.1 3.8/3.8 4.0/4.0 9.0/9.0 7.7/7.7 4.0/4.0 9.0/9.0
Power Input Supply, Nominal [kW] 0.46 0.58 1.06 1.59 1.99 2.26 3.06 3.88 2 x 2.25 2 x 3.18
Power Input Extract, Nominal [kW] 0.45 0.56 1.02 1.54 1.93 2.18 2.94 3.74 2 x 2.18 2 x 3.05
3
SFPv [kW/m /s] 2.00 2.00 1.97 2.00 1.94 1.99 1.97 1.94 1.99 1.97
Electrical Supply [V-Ph-Hz] 230-1-50 230-1-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50
Length [mm] 2400 2400 2500 2620 2780 2980 3100 3150 2980 3100
Depth [mm] 720 820 990 1200 1400 1400 1600 1940 1940 2300
Height (Including Base Frame) [mm] 1320 1320 1540 1740 1740 1920 1920 2180 2460 2570
Weight [kg] 385 414 555 667 848 895 1070 1501 1606 1986
DX Total Cooling Capacity [kW] 3.9 4.6 8.7 13.0 16.9 18.6 25.4 34.1 37.8 52.9
Outdoor Unit Nominal Cooling Power Input [kW] - - - 3.51 4.53 5.22 7.42 2 x 4.53 2 x 5.22 2 x 7.42
Sound Power Level - Lw dB(A)(1) 73 76 74 78 79 79 84 81 81 88

D-AHU Modular R - Base Unit c/w Thermal Wheel & CHW Module
Size ADT01FCW1 ADT02FCW1 ADT03FCW1 ADT04FCW1 ADT05FCW1 ADT06FCW1 ADT07FCW1 ADT08FCW1 ADT09FCW1 ADT10FCW1
Supply/Extract Airflow [m3/s] 0.42 0.51 0.96 1.42 1.86 2.04 2.81 3.63 4.06 5.83
Temp Efficiency Winter [%] 80.70 82.00 80.40 81.00 80.60 81.10 80.40 79.60 80.80 80.00
Temp Efficiency Summer [%] 80.10 81.30 79.80 80.30 80.00 80.40 79.70 79.00 80.10 79.40
Unit Nominal Performance

ESP nominal [Pa] 250 250 250 250 250 250 250 250 250 250
Nominal Fan Current - Supply/Extract [A] 3.3/3.3 3.1/3.1 4.6/4.6 4.1/4.1 3.8/3.8 4.0/4.0 9.0/9.0 7.7/7.7 4.0/4.0 9.0/9.0
Power Input Supply, Nominal [kW] 0.46 0.58 1.11 1.59 2.02 2.29 3.13 3.95 2 x 2.28 2 x 3.25
Power Input Extract, Nominal [kW] 0.44 0.55 1.05 1.52 1.93 2.17 2.95 3.74 2 x 2.17 2 x 3.05
3
SFPv [kW/m /s] 2.00 1.99 2.00 2.00 1.94 1.99 1.98 1.94 2.00 1.97
Electrical Supply [V-Ph-Hz] 230-1-50 230-1-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50
Length [mm] 2400 2400 2500 2620 2780 2980 3100 3150 2980 3100
Depth [mm] 720 820 990 1200 1400 1400 1600 1940 1940 2300
Height (Including Base Frame) [mm] 1320 1320 1540 1740 1740 1920 1920 2180 2460 2570
Weight [kg] 383 413 555 668 850 900 1074 1499 1601 1988
Total Cooling Capacity [kW] 3.0 3.6 6.8 10.2 13.3 14.7 19.8 26.5 29.2 41.5
Outdoor Unit Nominal Cooling Power Input [kW] - - 2.56 3.9 5.52 5.8 7.47 9.45 12.7 15.1
Sound Power Level - Lw dB(A)(1) 74 76 77 78 79 79 85 81 81 88
(1)
Sound Power Level - Supply Air Unit Outlet
Includes G4/F7 filtration, Foam Insulation, Aluzinc internal skin and Aluzinc Pre-Painted external skin

Notes:
Default handing of units is right hand where all pipe connections and access will be from the right hand side of the unit when viewed looking in to the fresh air inlet.
Units can be supplied Left hand if advised at time of order.
Ancillary modules include Dual or Single Silencers, Electric or LPHW Frost Coils, Humidifier & various Heating/Cooling Coil Modules will be delivered loose for ‘Bolt-Up’ to main
module at site by the installer.

15 Product portfolio
Air Handling Units
ADT-E/A Modular-P AHU with high efficiency
heat recovery
Energy efficiency and indoor air quality EC fan
> Predefined sizes > Air flow or pressure control
> IE4 premium efficiency motor (Variable Air Volume – Constant Air Volume)
> High efficiency plate heat exchanger (heat recovery) > Nominal air flow programmed at factory
> Compact design > Reduced noise with option NRLS
> Advanced control features
> Easy installation Simple, quick installation
> Indoor air quality compliant with VDI 6022 hygiene guideline The Modular series’ Plug & Play design is more than just a
> Operating limits from -25 °C, -40 °C with electric heaters, convenient feature for installers. It offers cost-saving benefits as
up to +46 °C ambient temperature there is no need for expensive adjustments before the unit is
> VRV IV and ERQ coupling capability commissioned. Plug & Play makes everyone’s life simpler, safer and
> Indoor and outdoor versions more economical.
> Free cooling capability
> Economy and Night mode operation
> Monitoring and control through Daikin ITM

D-AHU Modular P - Base Unit c/w Plate Heat Exchanger & DX Module
Size ADT01ECD1 ADT02ECD1 ADT03ECD1 ADT04ECD1 ADT05ECD1 ADT06ECD1 ADT07ECD1 ADT08ECD1 ADT09ECD1 ADT10ECD1
Supply/Extract Airflow [m3/s] 0.50 0.61 0.98 1.31 1.67 1.89 2.33 3.51 4.02 5.28
Temp Efficiency Winter [%] 91.70 91.90 91.30 91.10 90.80 91.30 91.10 91.10 91.40 91.10
Temp Efficiency Summer [%] 82.70 83.10 82.10 81.80 81.50 82.10 81.80 81.90 82.30 82.90
Unit Nominal Performance

ESP Nominal [Pa] 250 250 250 250 250 250 250 250 250 250
Nominal Fan Current - Supply/Extract [A] 3.3/3.3 3.1/3.1 1.9/1.9 3.0/3.0 3.8/3.8 4.0/4.0 5.3/5.3 7.7/7.7 4.0/4.0 5.3/5.3
Power Input Supply, Nominal [kW] 0.5 0.65 1.01 1.4 1.75 2.02 2.44 3.71 2 x 2.15 2 x 2.77
Power Input Extract, Nominal [kW] 0.52 0.67 1.06 1.47 1.86 2.1 2.55 3.88 2 x 2.24 2 x 2.92
3
SFPv [kW/m /s] 1.88 1.98 1.94 2.00 2.00 2.00 1.98 2.00 2.00 1.99
Electrical Supply [V-Ph-Hz] 230-1-50 230-1-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50
Length [mm] 2730 2900 3310 3360 3500 3910 4040 4540 4760 4890
Depth [mm] 720 820 990 1200 1400 1400 1600 1940 1940 2300
Height (Including Base Frame) [mm] 1320 1320 1540 1740 1740 1920 1920 2180 2460 2570
Weight [kg] 402 421 591 695 882 956 1082 1618 1894 2305
DX Total Cooling Capacity [kW] 5.0 6.2 10.0 13.6 17.4 19.6 24.4 36.8 42.3 55.00
Outdoor Unit Nominal Cooling Power Input [kW] - - - 3.51 4.53 5.22 5.22 2 x 5.22 2 x 5.22 2 x 7.42
Sound Power Level - Lw dB(A)(1) 72 77 74 77 77 77 78 81 81 82

D-AHU Modular P - Base Unit c/w Plate Heat Exchanger & CHW Module
Size ADT01ECW1 ADT02ECW1 ADT03ECW1 ADT04ECW1 ADT05ECW1 ADT06ECW1 ADT07ECW1 ADT08ECW1 ADT09ECW1 ADT10ECW1
Supply/Extract Airflow [m3/s] 0.50 0.60 0.98 1.29 1.67 1.89 2.33 3.51 4.26 5.28
Temp Efficiency Winter [%] 91.70 92.00 91.30 91.10 90.80 91.30 91.10 91.10 91.20 91.10
Temp Efficiency Summer [%] 82.70 83.20 82.10 81.90 81.50 82.10 81.80 81.90 82.00 81.80
Unit Nominal Performance

ESP nominal [Pa] 250 250 250 250 250 250 250 250 250 250
Nominal Fan Current - Supply/Extract [A] 3.3/3.3 3.1/3.1 4.6/4.6 3.0/3.0 3.8/3.8 4.0/4.0 5.3/5.3 7.7/7.7 4.5/4.5 5.3/5.3
Power Input Supply, Nominal [kW] 0.52 0.66 1.12 1.42 1.82 2.1 2.54 3.85 2 x 2.36 2 x 2.90
Power Input Extract, Nominal [kW] 0.52 0.65 1.11 1.44 1.86 2.1 2.55 3.88 2 x 2.36 2 x 2.92
3
SFPv [kW/m /s] 1.90 1.95 2.00 2.00 2.00 2.00 1.98 2.00 2.00 2.00
Electrical Supply [V-Ph-Hz] 230-1-50 230-1-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50
Length [mm] 2730 2900 3310 3360 3500 3910 4040 4540 4760 4890
Depth [mm] 720 820 990 1200 1400 1400 1600 1940 1940 2300
Height (Including Base Frame) [mm] 1320 1320 1540 1740 1740 1920 1920 2180 2460 2570
Weight [kg] 401 420 591 696 885 961 1086 1616 1893 2308
Total Cooling Capacity [kW] 3.9 4.8 8.0 10.9 14.0 16.0 19.3 29.2 35.4 43.3
Outdoor Unit Nominal Cooling Power Input [kW] 1.27 1.61 2.57 3.9 5.8 5.8 7.59 13.5 13.5 15.4
Sound Power Level - Lw dB(A)(1) 73 77 77 77 78 77 78 81 81 83
(1)
Sound Power Level - Supply Air Unit Outlet
Includes G4/F7 filtration, Foam Insulation, Aluzinc internal skin and Aluzinc Pre-Painted external skin

Notes:
Default handing of units is right hand where all pipe connections and access will be from the right hand side of the unit when viewed looking in to the fresh air inlet.
Units can be supplied Left hand if advised at time of order.
Ancillary modules include Dual or Single Silencers, Electric or LPHW Frost Coils, Humidifier & various Heating/Cooling Coil Modules will be delivered loose for ‘Bolt-Up’ to main
module at site by the installer.

Product portfolio 16
Daikin Fan Coil Units

High efficiency Brushless DC Fan Coil units


for comfort cooling / heating.

Brushless DC Motors for:


› Higher operational efficiency

› Creates comfort control

› Low sound levels

Higher efficiency than AC (Alternative Current) motor

› Up to 70% energy savings


Benefits for the installer › No heat generation
› No power losses
› Reduced amount of sizes: less stock space needed › Higher efficiency than AC motors to reach set point
› Easy integration to BMS systems via modbus protocol › Increased life expectancy >10,000 hours

High comfort level


Benefits for the consultant
› Less fluctuation of air temperature and relative humidity
› Comprehensive range with single source of supply › More consistent output level
for all configurations › Stepless speed change for gradual air output
› Efficient Brushless DC fan motors for comfort and low › More accurate adjustments to reach set point
sound levels

Low sound levels


Benefits for the end user › Lower minimum rotation speed
› No start-stop sequence
› High comfort level › Gradual air output
› Up to 70% savings on running costs
› Controller with timer programmed operating mode

17 Product portfolio
Product Overview

Fan Coil Units


Type Model Product name Fan motor type Capacity

Floor standing unit


- For vertical mounting
Cooling: 0.60 - 10.08 kW
Floor standing unit - Continuous air flow regulation and fan speed modulation FWZ-AT/AF BLDC
- Up to 70% energy savings Heating: 0.69 - 11.18 kW
- Low sound levels

Flexi type unit


- For horizontal or vertical mounting
Cooling: 0.60 - 10.08 kW
- Continuous air flow regulation and fan speed modulation FWR-AT/AF BLDC
- Up to 70% energy savings Heating: 0.69 - 11.18 kW
- Low sound levels
Flexi type unit
Concealed flexi type unit
- For horizontal or vertical concealed mounting

FWECSA Controller Recommended


Cooling: 0.60 - 10.08 kW
- Continuous air flow regulation and fan speed modulation FWS-AT/AF BLDC
- Up to 70% energy savings Heating: 0.69 - 11.18 kW
- Low sound levels

Concealed ceiling unit with medium ESP


- For horizontal concealed mounting Cooling: 1.34 - 6.67 kW
- Instant adjustment to temperature and relative humidity changes FWP-AT BLDC
- Available static pressure up to 80 Pa Heating: 2.77 - 12.28 kW
- Low sound levels
Ducted unit
Concealed ceiling unit with high ESP
- For horizontal or vertical concealed mounting Cooling: 2.86 - 8.75 kW
- Available static pressure up to 120 Pa
FWN-AT/AF BLDC
Heating: 3.70 - 9.13 kW
- Easy maintenance

4-way blow ceiling mounted cassette


- 600 x 600 cassette
- Integrated fresh air intake Cooling: 1.4 - 5.2 kW
FWF-BT/BF AC
- Horizontal auto swing Heating: 2.3 - 6.7 kW
- Easy installation in corners
Ceiling mounted - Standard drain pump with 750 mm lift
cassette Round flow cassette
- 900 x 900 cassette
- 360° air discharge ensures uniform air flow Cooling: 4.0 - 8.7 kW
FWC-BT/BF BLDC
- Integrated fresh air intake Heating: 5.5 -12.1 kW
- Easy installation in corners
- Standard drain pump with 850 mm lift

Wall mounted unit


- High aesthetic cabinet design Cooling: 2.11 - 5.28 kW
Wall mounted unit - Optimum air distribution FWT-CT AC
- Easy installation Heating: 2.49 - 6.01 kW
- 3-speed fan motor

FWECSA Electronic Fan Coil Unit Controller


Main features:
› Management of Brushless DC fan motor using 0-10V/DC
› Management of on/off or proportional valves
› Management of electric heater
› Relative humidity control
› Cooling/heating mode switching based on air or water temperature
› Contact for remote activation (window contact or remote on/off )
› Weekly timer programmed operation
› Configurable digital output
› Master slave system on serial RS485
› Master slave system using conveyed waves (CW)
› BMS supervision system using Modbus RS485
› Easy user interface

Capacity conditions
EUROVENT conditions TYPICAL UK cooling conditions
Cooling 22°C db / 16.0°C wb - Entering water 7°C - Leaving water 12°C
27°C db / 19°C wb - Entering water 7°C - Leaving water 12°C 0 Pa External Static Pressure
Heating 4 Pipe 0% Glycol
20°C db - Entering water 70°C - Leaving water 60°C FWP and FWN Ducted FCU - Above capacities are based on 30 Pa and 60 Pa
Heating 2 Pipe External Static Pressure respectively
20°C db - Entering water 50°C - Flow rate as in cooling mode
FWS Uncased - Based on 20 Pa external static

Product portfolio 18
Save energy with Daikin ‘Total Inverter Solutions’

The present catalogue is drawn up by way of information only and does


Printed in the UK on FSC certified paper from sustainable sources.

not constitute an offer binding upon Daikin UK. Daikin UK has compiled the
content of this catalogue to the best of its knowledge. No express or implied
UKEPCEN19-401 / 06.19 / DesignHQ. Copyright 2019 Daikin

warranty is given for the completeness, accuracy, reliability or fitness for


particular purpose of its content and the products and services presented
therein. Specifications are subject to change without prior notice. Daikin UK
FSC
explicitly rejects any liability for any direct or indirect damage, in the broadest Daikin Europe N.V. participates in the Eurovent Certification programme for Air conditioners (AC),
sense, arising from or related to the use and/or interpretation of this catalogue. Liquid Chilling Packages (LCP), Air handling units (AHU) and Fan coil units (FCU), Check ongoing
All content is copyrighted by Daikin UK. validity of certificate online: www.eurovent-certification.com or using: www.certiflash.com

Daikin Airconditioning UK Limited The Heights Brooklands Weybridge Surrey KT13 0NY Tel 01932 879000 daikin.co.uk
Scottish Northern Midlands Western North Central South
Region Region Region Region London London London
01932 879330 01932 879340 01932 879370 01932 879320 01932 879360 01932 879350 01932 879355

You might also like