BS 7346-1 1990 Components For Smoke and Heat Control Systems - Part 1 Specification For Natural
BS 7346-1 1990 Components For Smoke and Heat Control Systems - Part 1 Specification For Natural
1990
Incorporating
Amendment No. 1
The preparation of this British Standard was entrusted by the Fire Standards
Policy Committee (FSM/-) to Technical Committee FSM/14, upon which the
following bodies were represented:
The following bodies were also represented in the drafting of the standard,
through subcommittees and panels:
Contents
Page
Committees responsible Inside front cover
Foreword ii
1 Scope 1
2 Definitions 1
3 Construction 1
4 Heat and coefficient of performance testing of smoke and
heat exhaust ventilators 2
5 Climatic performance and testing of smoke and heat exhaust
ventilators 3
6 Certification of performance data 3
7 Servicing 3
Appendix A Coefficient of discharge test 4
Appendix B Temperature rise and expansion test 5
Appendix C Fire/heat test 6
Appendix D Rain testing of natural ventilators 7
Appendix E Service schedule 8
Figure 1 — Wind tunnel 4
Figure 2 — Apparatus for rain testing 8
Publications referred to Inside back cover
© BSI 02-1999 i
BS 7346-1:1990
Foreword
This Part of BS 7346 has been prepared under the direction of the Fire Standards
Policy Committee and is based on a draft prepared by the Smoke Ventilation
Association. It is one of a series of specifications for components of smoke and heat
control systems. The other Parts are as follows:
— Part 2: Specification for powered heat and smoke exhaust ventilators;
— Part 3: Specification for smoke curtains.
The use of smoke and heat exhaust ventilators has become widespread and their
value in assisting in the evacuation of people from buildings, reducing fire
damage and financial loss by preventing smoke logging, facilitating fire fighting,
reducing roof temperatures and retarding the lateral spread of fire is firmly
established. For these benefits to be obtained it is essential that smoke and heat
exhaust ventilators operate fully and reliably whenever called upon to do so
during their installed life.
A heat and smoke ventilation installation is intended to perform a positive role in
a fire emergency. Smoke and heat exhaust ventilators should be installed as part
of a properly designed smoke and heat exhaust scheme.
Assessed capability. Users of this British Standard are advised to consider the
desirability of assessment and registration of a supplier’s quality systems against
the appropriate Part of BS 5750 by a third party certification body.
A British Standard does not purport to include all the necessary provisions of a
contract. Users of British Standards are responsible for their correct application.
Compliance with a British Standard does not of itself confer immunity
from legal obligations.
Summary of pages
This document comprises a front cover, an inside front cover, pages i and ii,
pages 1 to 12, an inside back cover and a back cover.
This standard has been updated (see copyright date) and may have had
amendments incorporated. This will be indicated in the amendment table on
the inside front cover.
ii © BSI 02-1999
BS 7346-1:1990
1 Scope 2.7
thermal link
This Part of BS 7346 specifies performance
requirements for natural smoke and heat exhaust a heat sensitive mechanical linkage which parts
ventilators that are intended to be installed in when its temperature exceeds a specified limit
buildings to release the products of combustion in NOTE Thermal links can also be specified by time constant, so
the event of a fire. that they operate in a predetermined period.
© BSI 02-1999 1
BS 7346-1:1990
c) Automatic smoke detection system. The 4.4 The ventilator shall be mounted either
ventilator shall open following an alarm horizontally or vertically on a suitable test rig,
condition initiated by an automatic smoke depending on whether it is intended for roof or wall
detection system complying with BS 5839-1. application, to check its response to heat and to
3.1.6 The ventilator shall be so designed that it will determine the effects of differential expansion, in
always fail to the fully open position under fire accordance with 4.5, 4.6 and 4.7.
conditions. 4.5 The ventilator shall be subjected to a slow rate
3.1.7 When the ventilator has a life safety of temperature rise in accordance with B.4.1. The
(i.e. means of escape) application it shall be ventilator shall open smoothly to the fully open
activated in accordance with 3.1.5 c). position, and it shall remain in this position without
reduction in the ventilation area. Even if the gas
3.1.8 Manual overriding controls shall be provided
struts fail the ventilator shall be maintained in the
as part of the control system.
open position.
3.1.9 It shall be possible to test the ventilator,
4.6 The ventilator shall be subjected to a fast rate of
remotely open and closed, from working level in the
temperature rise in accordance with B.4.3. The
building.
ventilator shall open smoothly to the fully open
3.2 Resistance to corrosion position, and it shall remain in this position without
The ventilators and control system shall be reduction in the ventilation area. Even if the gas
constructed from materials resistant to natural struts fail the ventilator shall be maintained in the
atmospheric corrosion and sunlight, and shall be open position.
selected so as to prevent the possibility of galvanic 4.7 The ventilator shall open as follows:
corrosion between adjacent components. a) for both slow and rapid rate of rise of
3.3 Springs temperature tests, smoothly and swiftly to a fully
All springs shall be of stainless steel complying with open position so that there is no obstruction of
grade 316S31 of BS 970-1 or equivalent. passage of air through the ventilator at any time
during test;
NOTE Other types of device, such as gas springs, may also be
used in place of tension and compression springs. NOTE If the ventilator opens prematurely it is not deemed
to have failed the tests.
3.4 Bearings
b) for the slow rate of rise of temperature test,
All pivot points/bearings shall be designed to ensure within 3 min of the air temperature reaching the
free movement at all times. stated operating temperature of the heat
detector/operating mechanism;
4 Heat and coefficient of performance c) for the rapid rate of rise of temperature test,
testing of smoke and heat exhaust within 90 s of the air temperature reaching the
ventilators stated operating temperature of the heat
4.1 A standard production ventilator with a nominal detector/operating mechanism.
throat size of 1.5 m wide by 2.5 m long shall be 4.8 The ventilator shall open and close as intended,
submitted to the test schedule described in 4.2 without failure of any of the components necessary
to 4.7. If the size range is less than the specified size for operation, when the smoke and heat exhaust
above, then the largest ventilator in the range shall ventilator is operated 2 000 times, unless it is a dual
be tested. Ventilator designs for use in the vertical purpose ventilator, in which case it shall be
and horizontal positions shall be tested in both operated 30 000 times.
planes. 4.9 When tested in accordance with Appendix C, the
NOTE A test on one size of ventilator will allow an appraisal of ventilation opening shall remain clear from
other similar ventilators in the range even with different aspect obstruction throughout the test.
ratios except for coefficients of performance (see 4.3).
Ventilators of larger area or with unusual aspect ratios may need A similar ventilator of a smaller size may be used:
to be tested on an ad hoc basis. the ventilator shall have a minimum measured
4.2 The ventilator shall be inspected to ensure that throat area of 1.2 m × 1.2 m or the largest in the
it complies with the published performance data. range if smaller than this. If gas struts are used in
4.3 The coefficient of discharge of the ventilator the ventilator these should be carefully examined
shall be determined in accordance with Appendix A. for failure.
NOTE 1 If the gas struts fail the ventilator should be
maintained in the open position.
NOTE 2 If a range of gas struts is available for the ventilator, it
is to be tested with the highest pressure struts fitted.
2 © BSI 02-1999
BS 7346-1:1990
A ventilator shall have failed the test if one of the 5.5 Uninsulated roof mounted ventilators shall be
following apply: designed to withstand a snow load of 125 N/m2 and
a) it failed to open; shall be capable of opening with the snow load
applied. Insulated roof mounted ventilators shall be
b) it failed to open fully;
designed to withstand and operate with a snow load
c) when open, the ventilator, because of its of 300 N/m2. With roof angles a of between 30°
design: and 60° the load shall be modified by a correction
1) disturbed the free flow of smoke and hot factor of (60 – a)/30. If the roof angle exceeds 60°
gases from the rig; then the snow load shall be nil. If higher snow loads
2) deflected smoke and/or hot air onto the are required these shall be calculated in accordance
surface of the rig; with BS 6399-3.
d) having opened, it reclosed or partially closed 5.6 The ventilator shall be designed to open and
subsequently; withstand a side wind of 18 m/s (Beaufort Force 8)
when in the open position without flaps or louvres
e) the ventilator area became blocked or partially
closing.
blocked after the ventilator had opened.
NOTE 3 If the ventilator failed the test because of d) or e), the
manufacturer has the right to retest the ventilator to determine
6 Certification of performance data
the partially closed/blocked coefficient. Two further ventilators The manufacturer of the ventilator shall be able to
should then be fully tested in accordance with C.4. These also
should be tested as described in Appendix A, and the lowest
supply a Certificate of conformity to the
coefficient of discharge of all three ventilators can be used in the requirements set out in clause 4. This certificate
manufacturer’s published literature. Under these conditions the shall list the performance criteria and state where
ventilator will be said to have a “qualified” pass. the tests were carried out.
5 Climatic performance and testing of All instruments used shall carry a current
calibration certificate, traceable to a recognized
smoke and heat exhaust ventilators standard.
5.1 A standard production ventilator with a nominal
throat size of 1.5 m wide by 2.5 m long shall be 7 Servicing
submitted to the test schedule described in 5.2
The suppliers of the equipment shall be able to
to 5.6. If the size range is less than the specified size
provide a regular maintenance contract and/or to
above, then the largest ventilator in the range shall
recommend one or more servicing companies.
be tested. Ventilator designs for use in the vertical
NOTE It is recommended that after installation the ventilator
and horizontal positions shall be tested in both should be serviced at least once per year. The frequency may have
planes. to be increased if the application is in a particularly sensitive or
NOTE A test on one size of ventilator will allow an appraisal of dirty environment, i.e. such occupancies as bleach works and
other similar ventilators in the range. electroplating shops. The minimum recommended annual service
is shown in Appendix E.
5.2 The ventilator shall be inspected to ensure that For life safety (i.e. means of escape) applications the smoke
it complies with the published performance data ventilation system should be tested once per week.
and is a production sample.
5.3 When tested in accordance with Appendix D,
rain shall not visibly penetrate within the ventilator
boundary.
5.4 The ventilator shall be designed to withstand a
minimum wind load of 2.4 kN/m2 suction and
pressure, or higher where such wind loads are likely
to be imposed on the ventilator
(see CP3:Chapter V-2).
The ventilator shall be mounted on a suitable test
rig and tested to the design wind load. Loads shall
be applied as specified in CP 118, BS 449 or
BS 5950.
© BSI 02-1999 3
BS 7346-1:1990
Appendix A Coefficient of discharge A.3.3 A calibrated orifice plate or pitot tube scan, or
test other suitable method, to measure accurately the air
flows through the ventilator.
A.1 Principle
A.4 Test procedure
The ventilator is mounted in a wind tunnel, and the
air flow and pressure across the ventilator is A.4.1 Mount the open ventilator into the face of the
tunnel as shown in Figure 1.
measured over a range of values. The average
coefficient of discharge is calculated by comparison NOTE The minimum of 0.2 of the throat width at each side and
the minimum of 0.2 of the throat length at the top and bottom is
with the theoretical air flow through an equivalent to ensure that the static pressure tappings inside the tunnel are
opening, so that the aerodynamic free area can be not disturbed by the air flow.
calculated. The air flow shall be in the correct direction.
A.2 Scope There shall be a clear space in front of the tunnel
This test can be used for all natural smoke and heat equal to 1.5 times the largest throat dimension of
ventilators. the ventilator.
A.3 Apparatus A.4.2 Operate the fan driving the tunnel to produce
A.3.1 A suitable wind tunnel, with the facility to a range of different airflows through the ventilator.
cater for a range of air flow rates and pressures Record the static pressure, barometer pressure,
(see Figure 1). The face of the tunnel shall be large airflow and ambient temperature for each flow rate.
enough to accommodate the test ventilator. Take six sets of readings between 10 N/m2 and the
highest pressure difference available. Calculate the
A.3.2 A suitable manometer, to measure the static
coefficient of discharge of the ventilator from these
pressures inside the tunnel. readings.
4 © BSI 02-1999
BS 7346-1:1990
© BSI 02-1999 5
BS 7346-1:1990
B.3.4 The rig shall be provided with a means of B.4.3 Repeat the test as in B.4.1 but raise the air
controlling the air temperature within the rig and temperature at a rate of 60 °C/min until the heat
the rate of rise of this temperature. The sensitive device parts. Ventilators without a heat
temperature control of the rig shall be such that: sensitive device shall be manually actuated 3 min
a) the air temperature can be raised at 3 °C/min after the start of the test. Do not allow a 1 h dwell
with the air temperature in the rig being at all period in this test.
times within ± 5 °C of that required by the set B.5 Results
rate of change of temperature; B.5.1 Record full details of the ventilator under test,
b) the air temperature can be raised at 60 °C/min including details of the heat detector operating
with either: mechanism, e.g. fusible link, and its temperature
1) the air temperature in the rig being at all rating.
times within ± 10 °C of that required by the set B.5.2 The report shall state:
rate of change of temperature; or a) the air temperature at which the ventilator
2) the area under the temperature/time curve operated;
being at all times within ± 15 % of the area b) the time since the beginning of the test when
under the temperature/time curve resulting the ventilator operated;
from the test described in B.4.3. The tolerance
c) the time since the beginning of the test at
shall be calculated in accordance with 3.1.2 of
which the air temperature reached the stated
BS 476-20:1987.
operating temperature of the heat
It shall be possible to control the rate of rise of detector/operating mechanism, or the
temperature as described at least over the temperature reached at the time of manual
range 20 °C to 200 °C. actuation.
B.3.5 The air temperature in the rig shall be Record a) to c) for both the slow and the rapid rate
measured by temperature measuring equipment, of rise of temperature tests.
e.g. thermocouples, having a time constant not
B.5.3 Record any distortion or defect which
greater than 2 s. The temperature measuring
impaired the operation of the detector.
device(s) shall be situated as close as possible to the
heat detector/operating mechanism, i.e. fusible link,
of the ventilator where fitted.
Appendix C Fire/heat test
B.3.6 As well as controlling the temperature in the C.1 Principle
rig via a temperature controller, the temperature The ventilator is tested to destruction to ensure that
measured by the temperature measuring device(s) the ventilator opens under fire/extreme heat
shall also be continuously recorded against time. conditions and to ensure that the ventilator throat
B.4 Test procedure area does not reduce the available airway for smoke
release.
B.4.1 With the ventilator in position, and the chart
recorder running, raise the air temperature in the C.2 Scope
rig from ambient (25 °C maximum) at 3 °C/min The test can be used for ventilators incorporating
until 65 °C is reached. It shall be held at this any of the detectors and operating mechanisms
temperature for 1 h and then increased by 3 °C/min described in 3.1.5. However, if the detector
until the heat sensitive device operates. Ventilators mechanism is not integral with the ventilator
without a heat sensitive device shall be actuated [as in 3.1.5 b) and 3.1.5 c)] it is not practical for the
manually 3 min after the initiation of the increase detector mechanism to be incorporated into the test.
in temperature after the 1 h period. Note both the In such cases operation of the ventilator can be
air temperature and the time at which the manually initiated provided this is done in a similar
ventilator opens. In addition note any distortion of way to operation under fire conditions, e.g. air may
defect which impairs the operation of the ventilator. be released from a compressed air line to simulate
If gas struts are used in the ventilator these should the breaking of a frangible bulb, or an electric signal
be carefully examined for failure. may be used to simulate the operation of an electric
B.4.2 When the ventilator has operated, switch off heat or smoke detection system. Nevertheless, any
the heating elements or burners. Allow the rig to test and subsequent appraisal of a ventilator with a
cool to 25 °C or less and fit a new heat non-integral detection mechanism is not an
detector/operating mechanism to the ventilator appraisal of that detection mechanism.
where necessary.
6 © BSI 02-1999
BS 7346-1:1990
© BSI 02-1999 7
BS 7346-1:1990
NOTE One or more nozzles may be used depending on the Appendix E Service schedule
ventilator size.
b) To measure the rainfall rate, proceed as E.1 Principle
follows. Where smoke and heat exhaust systems are
1) Place the rain gauge in front of the test rig installed it is essential that they are serviced
within the spread of the nozzle. regularly and maintained in good working
condition. This service schedule sets the minimum
2) Turn on the nozzle or nozzles to be used
annual service requirements which shall be
having first covered the rain gauge to prevent
undertaken.
premature collection.
E.2 Scope
3) When the water emitted from the nozzles
has settled to an even flow rate uncover the This service schedule applies to equipment used in
rain gauge and collect the water for 15 min. natural smoke and heat exhaust ventilation
systems, i.e. ventilators, compressors, controls and
4) Calculate the rainfall. Adjust the water flow
interconnections.
rate and repeat 1) to 3) until a rainfall
of 75 mm/h is established. E.3 Service schedule
D.4.4 Wind speed shall be 13 m/s. E.3.1 Check ventilator fixing and weathering, and
clean off all dirt with a stiff (not wire) brush from
Position the anemometer directly in front of the rain
internal and external weathering channels and
test rig.
surfaces of the ventilator.
D.4.5 The test rig and ventilator shall be set at the
Check operation of the louvres, flaps and/or
required angle as given in D.2.2.
dampers, clean bearings and lubricate as necessary.
D.4.6 Turn the “rain” on and leave for 5 min before
Check operation of ventilators to ensure they open
turning on the “wind”. Leave the system under test
and close correctly. Replace any failed, distorted, or
for a further 15 min. During this time examine the
badly worn components or repair as necessary.
ventilator closely from below to determine if any
leaks are present and where they go. E.3.2 Fully service compressors once per year in
accordance with the manufacturer’s
D.4.7 After a further 15 min terminate the test and
recommendations and instructions by an approved
position the ventilator for the next part of the test.
agent. Leave the compressor operating at the
D.5 Results specified pressure. In addition to this annual service
D.5.1 Record full details of the ventilator under test. the client should ensure that on a weekly basis the
D.5.2 Note the wind speed and rainfall. oil level is checked and topped up as necessary, the
filter is cleaned, and condensate is drained if an
D.5.3 Note any leaks through the ventilator automatic drain is not fitted.
including where the leak originates and where it
NOTE The electrical supply to the compressor should be on
travels. automatic reset after loss of power.
8 © BSI 02-1999
BS 7346-1:1990
E.3.3 Check the operation of each control panel and E.4 Testing
override controls. Check the integrity of all internal E.4.1 After carrying out the service detailed in E.3,
connections and tighten/remake as necessary. the whole system should be tested to ensure that it
Where components are found to be faulty replace operates in accordance with the manufacturer’s
these. Check any remote sensors or detectors to specification.
ensure they are operating correctly.
E.4.2 A certificate (see E.5) should be issued to the
E.3.4 Check all interconnecting pneumatic user which details the service work and the tests
pipework and electrical systems to ensure the which have been carried out. Any repairs or
system functions correctly. modifications should be reported.
E.3.5 It is recommended that after installation the E.4.3 For life safety (i.e. means of escape)
ventilator should be serviced at least once per year. applications the user should test the smoke
The frequency may have to be increased if the ventilation system on a weekly basis and maintain
application is in a particularly sensitive or dirty a record of testing (see E.6).
environment, i.e. such occupancies as bleach works NOTE To comply with the requirements of the Health and
and electroplating shops. Safety at Work etc. Act 1974 and the IEE Regulations, it will be
necessary for the service work to be carried out by a suitably
qualified technician.
© BSI 02-1999 9
BS 7346-1:1990
10 © BSI 02-1999
BS 7346-1:1990
© BSI 02-1999 11
12 blank
BS 7346-1:1990
Publications referred to
© BSI 02-1999
|
|
|
|
|
|
|
|
|
BSI Ð British Standards Institution
|
|
|
|
|
|
| BSI is the independent national body responsible for preparing British Standards. It
|
| presents the UK view on standards in Europe and at the international level. It is
| incorporated by Royal Charter.
|
|
| Revisions
|
|
| British Standards are updated by amendment or revision. Users of British Standards
|
| should make sure that they possess the latest amendments or editions.
|
|
| It is the constant aim of BSI to improve the quality of our products and services. We
|
| would be grateful if anyone finding an inaccuracy or ambiguity while using this
| British Standard would inform the Secretary of the technical committee responsible,
|
| the identity of which can be found on the inside front cover. Tel: 020 8996 9000.
|
| Fax: 020 8996 7400.
|
|
| BSI offers members an individual updating service called PLUS which ensures that
|
| subscribers automatically receive the latest editions of standards.
|
|
| Buying standards
|
| Orders for all BSI, international and foreign standards publications should be
|
| addressed to Customer Services. Tel: 020 8996 9001. Fax: 020 8996 7001.
|
|
| In response to orders for international standards, it is BSI policy to supply the BSI
|
| implementation of those that have been published as British Standards, unless
|
| otherwise requested.
|
|
| Information on standards
|
| BSI provides a wide range of information on national, European and international
|
| standards through its Library and its Technical Help to Exporters Service. Various
|
| BSI electronic information services are also available which give details on all its
|
| products and services. Contact the Information Centre. Tel: 020 8996 7111.
|
| Fax: 020 8996 7048.
|
|
| Subscribing members of BSI are kept up to date with standards developments and
| receive substantial discounts on the purchase price of standards. For details of
|
| these and other benefits contact Membership Administration. Tel: 020 8996 7002.
|
| Fax: 020 8996 7001.
|
|
| Copyright
|
|
| Copyright subsists in all BSI publications. BSI also holds the copyright, in the UK, of
|
| the publications of the international standardization bodies. Except as permitted
| under the Copyright, Designs and Patents Act 1988 no extract may be reproduced,
|
| stored in a retrieval system or transmitted in any form or by any means ± electronic,
|
| photocopying, recording or otherwise ± without prior written permission from BSI.
|
|
| This does not preclude the free use, in the course of implementing the standard, of
|
| necessary details such as symbols, and size, type or grade designations. If these
|
| details are to be used for any other purpose than implementation then the prior
| written permission of BSI must be obtained.
|
|
| If permission is granted, the terms may include royalty payments or a licensing
|
| agreement. Details and advice can be obtained from the Copyright Manager.
|
| Tel: 020 8996 7070.
|
|
|
|
|
|
|
|
|
BSI |
|
389 Chiswick High Road |
|
London |
|
W4 4AL |
|
|
|
|
|
|