QP+ QPV Enhanced Security Reset 2015-05-14 Quick Panel

This document provides instructions for resetting the enhanced security password on GE IP QuickPanel HMI devices. It outlines the following steps: 1. Upgrade the device firmware to the latest version to ensure it contains the necessary software fixes. 2. After installing the firmware, reset the enhanced security setting by clicking "Start | Programs | System – tap Reset Enhanced Security" and setting the "Enhanced Security" target property to False. 3. To clear projects and settings from the device's memory in preparation for a new download, follow the instructions to manually delete files and folders from the flash and SRAM storage using the Windows Explorer file browser.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
678 views4 pages

QP+ QPV Enhanced Security Reset 2015-05-14 Quick Panel

This document provides instructions for resetting the enhanced security password on GE IP QuickPanel HMI devices. It outlines the following steps: 1. Upgrade the device firmware to the latest version to ensure it contains the necessary software fixes. 2. After installing the firmware, reset the enhanced security setting by clicking "Start | Programs | System – tap Reset Enhanced Security" and setting the "Enhanced Security" target property to False. 3. To clear projects and settings from the device's memory in preparation for a new download, follow the instructions to manually delete files and folders from the flash and SRAM storage using the Windows Explorer file browser.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Enhanced Security password reset

QP+ and QuickPanel View / Control

ME version 8.50 and newer have the Enhanced Security turned on by default as a security measure.

To change default:

Inspector Window | Options TAB (far left) |Expand LD-PC / View and view properties of “Preferences” in the Inspector
window – see Figure 1

Figure 1

Proceed with below:

QP+

Upgrade to latest firmware – note that any configuration and projects will be removed

http://support.ge-
ip.com/support/index?page=dwchannel&actl=FIRMWARE_UPGRADES_TYPES&dProdFam=OPERATORINTERFACE&dProd
=QUICKPANELPLUS&dProdVer=&cat=FIRMWARE_UPGRADES_TYPES

7” download search article DN4145 (current version Build 20, note that next version – Build 21 - will contain software fix
- no need to changed DIP switch settings)

10” / 12” / 15” all use same firmware – search article DN4185 (current version Build 11, note that next version – Build 12
- will contain software fix - no need to changed DIP switch settings)

6” is released with software solution


After installing firmware, click Start | Programs | System – tap Reset Enhanced Security

Then set Target Property “Enhanced Security” to False

Figure 2

Proceed with download – done

QuickPanel View / Control – the below procedure fulfills the dual function of clearing a downloaded project and
Enhanced Security Password

Clear Memory in QuickPanel View / Control / +

Important Note: This procedure will clear the project from your HMI, preparing your HMI for a fresh download of the
project to your HMI.

When downloading a project to a QuickPanel View/Control HMI, files are left on the HMI that after repeated
downloads may interfere with View Runtime operation. This can be resolved by manually deleting files from the HMI.

Manual file deletion steps:

QuickPanel View / Control

If View Runtime is running – reboot HMI (start | programs | system | reboot | yes)
When HMI is powering up select ‘Don’t run Startup Programs’, this will result in the Desktop showing (and no
Runtime)

From HMI Taskbar click Start | Programs | Windows Explorer

Double click folder (to open) \Flash Storage\

Delete all files & folders – some folders cannot be deleted e.g. \Flash Storage\Documents and Settings & OS_Patches
(may or may not be present depending on version of CE on HMI – do not delete)

Return to root directory

Delete \fxViewRuntime\ directory (may or may not be present depending on Project)

Return to root directory

Double click folder (to open) \SRAM Storage\

Delete \fxViewRuntime\ directory

Close WINDOWS EXPLORER

Reboot panel

You have now removed files and folders - restart HMI and download

QuickPanel +

When HMI is powering up select ‘Don’t run Startup Programs’, this will result in the Desktop showing (and no
Runtime)

From HMI Taskbar click Start | Programs | Windows Explorer

Double click folder (to open) \Flash Storage\

Delete all files & folders

Return to root directory

Delete \fxViewRuntime\ directory (may or may not be present depending on Project)

Return to root directory

Double click folder (to open) \SRAM Storage\

Delete \fxViewRuntime\ directory


Close WINDOWS EXPLORER

Reboot panel

You have now removed files and folders – restart HMI and download