Week 1 () 1) The Gas actuated relays (Buchholz relay) can be used to detect which type of faults inside the transformer? 1 point
Week 7 () 4) In digital transformer differential protection, the second slope of the differential characteristics will take care of the issues related to 1 point
5) For a transformer having configuration is Dyn11, which of the following statement is correct. 1 point
HV winding is Delta and LV winding is Star, HV leads LV by 30 degree
HV winding is Star and LV winding is Delta, HV leads LV by 30 degree
HV winding is Delta and LV winding is Star, LV leads HV by 30 degree
HV winding is Star and LV winding is Delta, LV leads HV by 30 degree
6) For a transformer having configuration is YNd11, which of the following statement is correct. 1 point
7) In transformer protection, the most common cross-blocking method used to restrain during magnetizing inrush current is 1 point
1-out-of-3
2-out-of-3
Per-phase-method
Averaging
IEC 61850-9
IEC 60073-1
IEC 60076-1
IEC 60075-1
9) Calculate the primary (TAP1) and secondary side (TAP2) TAP scaling factor considering below mentioned data: 1 point
5 MVA, 66/11 kV, YNd11 transformer having high voltage side CT ratio as 50/1 and low voltage side CT ratio as 100/5.
10) Using the below mentioned transformer data, calculate the operating (Iop) and restraining (Irst) current when the transformer is 1 point
operating at the Higher Tap i.e. at +2.5%.
Transformer data:
1500 MVA, 765/400 kV, YNa0d11 transformer having high voltage side CT ratio as 2000/1 and low voltage side CT ratio as 3000/1. TAP-HV =
0.5660 and TAP-LV = 0.7216. Tapping Range (Max ratio to Min ratio in %) = +5.50% to -5.50% in 11 steps.