PCS S Series
PCS-915SC Centralized Busbar Relay • Voltage blocking is an option for the current differential
protection and breaker failure protection, which will improve
the reliability of current differential protection and breaker
failure protection.
• With CT circuit supervision function, once CT circuit failure is
detected, the user can choose discrimination zone or check
zone differential protection blocking.
• Both of phase segregated and three phase breaker failure
binary inputs can be connected for breaker failure protection,
users can choose whether or not blocked by the current
criterion. The overcurrent element of breaker failure protection
have been especially treated, the dropoff time of it is no more
than 12ms.
PCS-915SC centralized busbar relay integrates busbar differential • Selectable IEC, ANSI inverse-time characteristic curves, also
protection, bus coupler/section protection (includes overcurrent the curve can be defined by users and the inverse-time dropoff
protection, switch-onto-fault protection, dead zone fault protection curve selection is supported.
and breaker failure protection) and feeder protection (includes
With the disconnector position status monitor and memory
overcurrent protection, dead zone fault protection and breaker
function, the device can check the rationality of the memorized
failure protection). With its flexibility and the powerful PCS-Studio
disconnector position status and automatically correct the
configuration tool, PCS-915SC offers future-oriented busbar
error.
solutions with high investment security and low operating costs.
• Users can disable the discrimination zone differential element
by the external binary input during the busbar maintenance.
Also the bay can be disabled by the external binary input when
it is in maintenance.
• LCD can display real-time main wiring diagram, the number of
each bay, the state of each breaker and disconnector, current
and power flow, etc.
Functions
Protection and Control
• Busbar current differential protection (87B)
Features It consists of phase current differential protection and DPFC
differential protection. Voltage control element and CT
• Applicable for single busbar, single bus with bus section,
saturation blocking element are available to supervise the
double busbar, double busbar with bus section, etc. busbar
current differential protection.
arrangement, and the busbar differential protection can
connect up to 4 busbars and 32 bays.
° DPFC differential protection
• Comprehensive functionality including phase segregated DPFC differential protection is sensitive to high resistance
current differential protection, breaker failure protection, fault and is immune to load fluctuations.
overcurrent protection and dead zone protection, etc.
° Voltage control element
• The phase segregated differential protection adopts both of
The used voltage can be phase voltage, zero sequence
deviation of power frequency component (DPFC) and
voltage or negative sequence voltage.
steady-state component, that can guarantees fast and reliable
performance during CT saturation. It can ensure no
° Detection of CT saturation
mal-operation of external fault and fast operation of internal
Two principles for CT saturation detection are provided:
fault in the case of the correct transfer time of CT is no less
patented adaptive weighted anti-saturation algorithm and
than 3ms.
harmonic algorithm. It keeps the current differential
• With patented adaptive-weight anti-saturation algorithm and protection stable to external faults and quickly clears internal
harmonic restrain algorithm, the DPFC differential protection faults and external-to-internal evolving faults during CT
operates fast and not affected by load current, the typical saturation.
operation time is within 15ms.
79
www.nrec.com/en
Specifications
Electrical Specifications
AC Current Input
Phase rotation ABC or ACB
Nominal frequency (fn) 50Hz, 60Hz
Rated current (In) 1A/5A (settable)
Linear to 0.1A~200A
Thermal withstand
-continuously 20A
-for 10s 150A
-for 1s 500A
-for half a cycle 1250A
Burden <0.05VA/phase @1A or <0.25VA/phase @5A
AC Voltage Input
Phase rotation ABC or ACB
Nominal frequency (fn) 50Hz, 60Hz
Rated voltage (Un) 100V~130V
Linear to 1V~300V
Thermal withstand Phase-to-ground Phase-to-phase
-continuously 300V 519V
-10s 600V 1038V
-1s 660V 1141V
Burden at rated <0.01VA/phase @100V
Power Supply
Standard IEC 61000-4-29:2000
Rated voltage 110Vdc/125Vdc/220Vdc/250Vdc 110Vac/220Vac
Permissible voltage range 88~300Vdc 88~275Vac
Permissible AC ripple voltage ≤15% of the nominal auxiliary voltage
Burden
Quiescent condition <20W
Operating condition <40W
DC Analog Input
Standard IEC 60255-1: 2009
Input range 0-20mA 0~10V
Input resistance 230Ω >1MΩ
Accuracy 0.1% 0.1
86
PCS S Series
Binary Input: Settable pickup voltage and dropoff voltage
Rated voltage 24V 48V 110V 125V 220Vdc 250Vdc
Rated current drain 0.16mA 0.32mA 0.73mA 0.83mA 1.47mA 1.67mA
Pickup (default set) 15.12~28.2Vdc 30.24~57.6Vdc 69.3~132Vdc 78.75~160Vdc 138.6-264Vdc 157.5~300Vdc
Dropoff (default set) <12V <24V <55V <62.5V <110Vdc <125V
Maximum permissible voltage 350Vdc
Withstand voltage 2000Vac, 2800Vdc (continuously)
Response time for logic input ≤1ms
Binary Output: Tripping/signaling contact
Output mode Potential free contact
Max. system voltage 250Vac, 300Vdc
Continuous carry 10A
Pickup time (Typical Value) <5ms
Dropoff time (resistive load) <6ms
0.5A@48Vdc L/R=40ms
0.35A@110Vdc L/R=40ms
Breaking capacity
0.30A@125Vdc L/R=40ms
(10000 operations)
0.20A@220Vdc L/R=40ms
0.15A@250Vdc L/R=40ms
0.5A@48Vdc L/R=40ms
0.35A@110Vdc L/R=40ms
Cyclic capacity
0.30A@125Vdc L/R=40ms
(2.5 cycle/second)
0.20A@220Vdc L/R=40ms
0.15A@250Vdc L/R=40ms
30A@3s
Short duration current
50A@1s
Durability (Loaded contact) 10000 operations
Binary Output: Heavy-capacity tripping contact
Output mode Potential free contact
MOV protection(maximum voltage) 350Vdc, 275Vac
Continuous carry 10A
Pickup time (Typical Value) <1ms
Dropoff time (resistive load) <10ms
10A@48V L/R=40ms
Breaking capacity 10A@110V L/R=40ms
(10000 operations) 10A@125V L/R=40ms
10A@250V L/R=20ms
Cyclic capacity (4cycles in 10A@48V L/R=40ms
1 second, 10A@110V L/R=40ms
followed by 2 minutes idle 10A@125V L/R=40ms
for thermal dissipation) 10A@250V L/R=20ms
30A@3s
Short duration current
50A@1s
Durability (Loaded contact) 10000 operations
87
www.nrec.com/en
Mechanical Specifications
Chassis color Silver grey
Weight per device Approx. 23kg (6U, 1/1)
Chassis material Aluminum alloy
Location of terminal Rear panel of the device
Device structure Plug-in modular type @ rear side, integrated frontplate
Protection Class
Standard IEC 60529-2013
Front side IP52
Other sides IP50
Rear side, connection terminals IP20
Ambient Temperature and Humidity Range
Standard IEC 60255-1:2009
Operating temperature -40°C to +80°C (Readability of display may be impaired below -20°C or above 70°C)
Transport and storage temperature range -40°C to +80°C
Permissible humidity 5%-95%, without condensation
Pollution degree II
Altitude <3000m
Communication Port
EIA-485 Port
Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Protocol IEC 60870-5-103:1997
Max. capacity 32
Max. transmission distance 500m
Safety level Isolation to ELV level
Twisted pair Screened twisted pair cable
Copper Ethernet Port
Connector type RJ45
Transmission rate 100Mbits/s
Transmission standard 100Base-TX
Max. transmission distance 100m
Protocol IEC 60870-5-103:1997, DNP 3.0 or IEC 61850
Safety level Isolation to ELV level
88
PCS S Series
Optical Fibre Port: For Station Level
Characteristic Glass optical fiber
Connector type LC
Fibre type Multi mode
Max. transmission distance 2km
Wave length 1310nm
Transmission power 50μm: -24dBm 62.5μm: -20dBm
Minimum receiving power Min. -31.0dBm
Margin 50μm: -7dBm 62.5μm: -9dBm
Optical Fibre Port: For Process Level
Characteristic Glass optical fiber
Connector type LC
Fibre type Multi mode
Max. transmission distance 2km
Wave length 1310nm
Transmission power -20.0dBm ~ -14.0dBm
Minimum receiving power Min. -30.0dBm
Margin Min. +10.0dBm
Optical Fibre Port: For Synchronization Port
Characteristic Glass optical fiber
Connector type ST
Fibre type Multi mode
Wave length 850nm
Peak optical input power
Logic level HIGH Max. -40dBm
Logic level LOW Max. -10dBm, Min -24dBm
Print Port
Type RS-232
Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Printer type EPSON® 300K printer
Safety level Isolation to ELV level
Clock Synchronization Port
Type Serial port BNC connector
Input Demodulated IRIG-B or PPS
Nominal voltage 5Vdc+10%
Maximum voltage 8Vdc
Input impedance 2.5kΩ >1kΩ
Isolation 500Vdc 1.5kV (rms) for 1 min
89
www.nrec.com/en
Type Tests
Environmental Tests
Dry cold test IEC60068-2-1:2007
Dry heat test IEC60068-2-2:2007
Damp heat test, cyclic IEC60068-2-30:2005
Mechanical Tests
Vibration IEC 60255-21-1:1988 Class I
Shock and bump IEC 60255-21-2:1988 Class I
Electrical Tests
Standard IEC 60255-27:2013
Dielectric tests Test voltage 2kV, 50Hz, 1min
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100MΩ@500VDC
Electromagnetic Compatibility
IEC 60255-26:2013
1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
IEC 61000-4-2-2008
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
IEC 60255-26:2013 class III
Frequency sweep
Radiated amplitude-modulated
Radio frequency interference tests 10V/m (rms), f=80~1000MHz, 14000~2700MHz
Spot frequency
Radiated amplitude-modulated
10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
IEC 60255-26:2013
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
IEC 60255-26:2013
Surge immunity test Power supply, AC input, I/O port: class IV, 1.2/50us
Common mode: 4kV
Differential mode: 2kV
IEC 60255-26:2013
Conducted RF electromagnetic disturbance Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
Spot frequency
10V/m (rms), f=27MHz/68MHz
IEC 61000-4-8:2009
Power frequency magnetic field immunity
Class V, 100A/m for 1min, 1000A/m for 3s
90
PCS S Series
IEC 61000-4-9:2016
Pulse magnetic field immunity
Class V, 6.4/16μs, 1000A/m for 3s
IEC 61000-4-10:2016
Damped oscillatory magnetic field immunity
Class V, 100kHz & 1MHz–100A/m
IEC 60255-26:2013
Conducted emission 0.15MHz ~ 0.50MHz: 79dB(μV) quasi peak, 66dB(μV) average
0.50MHz ~ 30MHz: 73dB(μV) quasi peak, 60dB(μV) average
IEC 60255-26:2013
Below 30MHz ~ 230MHz: 40dB(μV/m) quasi peak @10m, 50dB(μV/m) quasi peak @3m
Radiated emission 1GHz 230MHz ~ 1000MHz: 47dB(μV/m) quasi peak @10m, 57dB(μV/m) quasi peak @3m
Above 1GHz ~ 3GHz: 56dB(μV/m) average, 76dB(μV/m) peak @3m
1GHz 3GHz ~ 6GHz: 60dB(μV/m) average, 80dB(μV/m) peak @3m
IEC 60255-26:2013
Voltage dips Up to 200ms for dips to 40% of rated voltage without reset
Auxiliary power supply performance 50ms for interruption without rebooting without energy
storage board (Typical application)
Voltage short interruptions
500ms for interruption without rebooting with energy
storage board (Typical application)
Terminals
Connection Type Wire Size
AC current Screw terminals, 1.5~4mm2 lead
AC voltage Screw terminals, 0.8~4mm2 lead
Power supply Screw terminals, 0.8~4mm2 lead
Contact I/O Screw terminals, 0.8~4mm2 lead
Grounding (Earthing) Connection BVR type, 0.8~4mm2 lead
Measurement Scope and Accuracy
Item Range Accuracy
Phase range 0° ~ 360° ≤±1°
Frequency fn±3 Hz ≤0.01Hz
Currents from protection measurement current transformers
≤ 1.0% of rating (0.05~1.00In)
Current 0.05~4.00In
≤ 0.5% of applied quantities (1.00~4.00In)
≤ 1.0% of rating (0.05~1.00Un)
Voltage 0.05~1.50Un
≤ 0.5% of applied quantities (1.00~1.50Un)
Management Function
Clock Performance
Real time clock accuracy ≤1s/day
Accuracy of GPS synchronization ≤1ms
External time synchronization IRIG-B (200-98), PPS, IEEE1588 or SNTP protocol
91
www.nrec.com/en
Fault and Disturbance Recording
Duration & Recording position Settable pre-disturbance, post-disturbance and maximum recorded duration
Sampling rate Up to 9.6kHz
Binary Input Signal
Resolution of binary input signal ≤1ms
Binary input mode Potential-free contact
92