Tower Spotting Data of 220 KV M/C Transmission Line: Nepal Electricity Authority
Tower Spotting Data of 220 KV M/C Transmission Line: Nepal Electricity Authority
of
1
2 TOWER SPOTTING DATA
3
4 Basic Wind Speed (in M/Sec) 47
5 Reliabilty Level (50 yr return period) 2
6 Terrain Category 2
2
7 Design wind Pressure Pd (in N/m ) 879
8 Design Code Referance IS 802(all part/sections) - 1995
9
10 Type of Conductor Twin HTLS/ phase or Twin BISON/ phase
11 Type of Ground wire One GSSW-7/3.35 + One OPGW
12
13 Sl
Description Tower MAY Tower MDY
No
14
15 1 Maximum Angle of Deviation 00 ~ 20 300 ~ 600 (*) (*) need revision
16 2 Normal Span (m) 350 350
17 Max Min Max Min
18 Downward Downward Downward Upward
3
19 Vertical load Limitation on weight
20 span for both (GW & Conductor)
21 i On both Span (m) 600 200 1000 (-) 1000
22 ii On one span (m) 360 100 600 (-) 600
23 Dev Angle Span (m) Dev Angle Span (m)
4
24 Permissible sum of Adjacent spans 2 700 60 700
25 (in m) subject to availability of Minimum 1 745 59 739
26 specified live metal clearance 0 789 58 777
27 Permissible one span for various 57 817
28 deviation angle shall not exceed 50% 56 856
29 the value shown for sum of 55 895
30 adjacent span 54 935
31 53 974
32 52 1014
33 51 1054
34 50 1095
35 49 1135
36 48 1176
37 47 1216
38 46 1257
39 45 1298
40 44 1340
41 43 & below 1381
ICB NO.
Arcon Powertrans Pvt Ltd
ICB-PMD-MCTLP-
Tower Spotting Data for 220 kV D/C Udipur - Bharatpur Transmission Line 016/17-01
Conductor - Twin HTLS :: Case Multi Circuit
PROJECT REV. PREP. BY CHKD BY DATE DRAWING NO.
200 kV M/C Transmission Lines
A VINITA MKK 16-Feb-18
CLIENT C502/Tspot/02
Nepal Electricity Authority
No.
1
2 General Details
3 1) All spans are in meter
4 2) All loads are in kgs
5
6 Tower MAY Tower MDY MAY+18/25m BE MDY+18/25m BE
7 Normal Span 350 350 350 350
8 Wind Span NC BWC NC BWC NC BWC NC BWC
9 350 210 350 210 250 150 250 150
10
11 4) Tower are classified as given below as per specification:
12
13 Deviation angle
Type of tower Typical use
14 (In degree)
15 To be used as tangent /suspension tower
16 with Single suspension
Tower MAY 0-2
17 insulator strings.
18
19
20
21
22
23
24
25
26
27
28
29 To be used as angle tower
30 To be used as tension tower for uplift
30 - 60
31 forces resulting from an uplift span
32 1000m in normal condition(both side) &
33 600m in broken wire condition(one side)
34 Tower MDY Complete dead end
0
35 To be used as section tower
36 15 On line side &substaion side(slack span)
37 Anchor tower for river crossing with
38 0 - 30 0 deg on crossing side and 0-30 deg
39 on line side.
40
41
ICB NO.
Arcon Powertrans Pvt Ltd
ICB-PMD-MCTLP-
Tower Spotting Data for 220 kV D/C Udipur - Bharatpur Transmission Line 016/17-01
Conductor - Twin HTLS :: Case Multi Circuit
PROJECT REV. PREP. BY CHKD BY DATE DRAWING NO.
200 kV M/C Transmission Lines
A VINITA MKK 16-Feb-18
CLIENT C502/Tspot/02
Nepal Electricity Authority
No.
1
2 CLEARANCES
3
4 1 Telecommunication Line crossing - The angle of crossing shall be as near as 90 deg. as possible
5 however deviation to an extent of 30 deg may be permitted under the exceptionally difficult situation.
6 For crossing angle below 60 deg , matter shall be refered to respective authorities.
7 Minimum distance between 220 kv D/C conductor & telecommunication lines shall be 3.0 m under
8 hot sag conductor condition
9
10 2 Limiting Distance between Angle Points - The number of consecutive spans between section towers
11 shall not exceed 15 Spans or 5 km whichever is lower in plain terrain.
12 In Hilly terrain number of consecutive towers shall be restricted to 10 spans or 3 kms,whichever is lower.
13 The section tower shall either be tower type MDY
14
15 3 Ground Clearance - The minimum ground clearance required shall be 7500 mm
16
17 4 Road crossing - For all the important road crossing, tension tower is to be used and the crossing span
18 shall not be exceed 200 meters. The minimum clearance between conductor and road top
19 surface shall be 7.5 m under hot sag condition. However it is preferable to keep 3.0m extra clearance.
21
22 5 Right of way - The right of way clearance shall be maintained as 35 m .
23
24
25 6 Span limitations - The permissible sum of adjacent spans of various angle of deviation are
26 subject to the condition that minimum specified live metal clearance & minimum ground clearance are available.
27 are available
28 The wind span for MAY+18m / +25m BE and MDY +18m /+25m BE shall be restricted to 250 m and
29 a limitation of 500m for sum of adjacent spans
30 7 No uplift in Tower type "MAY". - Tower "MAY" shall be spotted such that
31 vertical load of individual spans shall be acting downward only.
32
33 8 Electrical Clearance for Railway crossing
34 i Prior approval of Railway authority shall be obtained.
35 ii Mininum clearnce between lowest point of 220 kv line conductor and top of rail track
36 shall be minimum 17.9m under hot sag condition however approval of railway crossing from
37 railway authority shall be obtained in each railway crossing proposal
38 iii Mininum clearnce to be maintained between highest traction conductor and lowest
39 transmission line crossing conductor shall be 6580 mm for 220 kv.
40 as per regulation of power line crossing at railway tracks 1987.
41
ICB NO.
Arcon Powertrans Pvt Ltd
ICB-PMD-MCTLP-
Tower Spotting Data for 220 kV D/C Udipur - Bharatpur Transmission Line 016/17-01
Conductor - Twin HTLS :: Case Multi Circuit
PROJECT REV. PREP. BY CHKD BY DATE DRAWING NO.
200 kV M/C Transmission Lines
A VINITA MKK 16-Feb-18
CLIENT C502/Tspot/02
Nepal Electricity Authority
No.
7 ii for 33 kv : 4.58 m
12
13
14
15
16 11 Body Extensions i. -4.5m, -3m, -1.5m, 1.5m, +3 m, +6m, +9m, +18m & +25m Body extn For MAY
17 & Leg Extensions ii. -4.5m, -3m, -1.5m, 1.5m, +3 m, +6m, +9m, +18m & +25m Body extn For MDY
18
19
20
21
22 12 Broken wire Coditions
23 i Tower MAY Breakage of any one phase or ground wire
24
25 iii Tower MDY Breakage of any three phases on same side and on same span or any two
27 For dead end- all phases and ground wire broken on same side and same span
28
29
30
31
32
33
34
35
36
37
38
39
40
41
ICB NO.
Arcon Powertrans Pvt Ltd
ICB-PMD-MCTLP-
Tower Spotting Data for 220 kV M/C Udipur - Bharatpur Transmission Line 016/17-01
Conductor - Twin HTLS :: Case Multi Circuit
PROJECT REV. PREP. BY CHKD BY DATE DRAWING NO.
200 kV M/C Transmission Lines
A VINITA MKK 16-Feb-18
CLIENT C502/Tspot/02
Nepal Electricity Authority
No.
1
2
3 Design Load Tensions:
4
5 For Groundwire
6 Deviation angle 0° 60°
7 Tension(kg) Everyday temp. Full wind condition 3460 2996
8 Tension (kg) Everyday temp, No wind condition 1015 879
9
10 For Conductor
11 Deviation angle 0° 60°
12 Top CKT :: Tension(kg) Everyday temp. Full wind 8286 7176
13 Top CKT :: Tension (kg) Everyday temp, No wind 2924 2532
14 Bottom CKT :: Tension(kg) Everyday temp. Full wind 7771 6730
15 Bottom CKT :: Tension (kg) Everyday temp, No wind 2924 2532
16 Sag Tension Calculations: Conductor Properties
17 Conductor name HTLS ACSR Bison
18 UTS (kg) 13289 11981.6635
19 Area of conductor (sqmm) 484.5 431
20 Weight of conductor (kg/m) 1.621 1.444
21 Diameter of conductor (mm) 28.6 27.0
22 Modules of elasticity (kg/sqmm) 7036 7036
23 Coeff.of linear expansion (per deg C) 0.0000193 0.0000193
24
25 Initial /Starting Condition for sag tension calculations
26
27 Normal span 350
28 Wind pressure on conductor (kg/sqm) 0
29 Initial conductor temp.(deg c) 32
Initial conductor tension at above temp.
30
and wind condition (% of UTS or value in 22%
31 kg)
32
33 Standard Conditions
34 Temperature (deg C) 0 0 32 32 80
36 Top CKT :: Resultant Tension (kg) 3472 5027 2924 8286 2394
37 Top CKT :: Resultant Sag (mts) 7.149 4.938 8.49 2.995 10.368
38 Bottom CKT :: Resultant Tension (kg) 3472 4823 2924 7771 2394
39 Bottom CKT :: Resultant Sag (mts) 7.149 5.147 8.49 3.194 10.368
40
41
ICB NO.
Arcon Powertrans Pvt Ltd
ICB-PMD-MCTLP-
Tower Spotting Data for 220 kV M/C Udipur - Bharatpur Transmission Line 016/17-01
Conductor - Twin HTLS :: Case Multi Circuit
PROJECT REV. PREP. BY CHKD BY DATE DRAWING NO.
200 kV M/C Transmission Lines
A VINITA MKK 16-Feb-18
CLIENT C502/Tspot/02
Nepal Electricity Authority
No.
1
2 Earthwire Properties
3 Earthwire name GSSW 7/3.35
4 UTS (kg) 6230
5 Area of earthwire (sqmm) 61.7
6 Weight of earthwire (kg/m) 0.483
7 Diameter of earthwire (mm) 10.05
8 Modules of elasticity (kg/sqmm) 19000
9 Coeff.of linear expansion (per deg C) 0.0000115
10
11 Initial Condition
12 Normal span 350
13 Wind pressure on conductor (kg/sqm) 0
14 Initial conductor temp.(deg c) 0
% of initial earthwire sag at above temp.
15
and wind condition with respect to
16 conductor sag of same temp. and wind 90%
condition.
17
18
19 Standard Conditions
20 Temperature (deg C) 0 0 32 32 53
24
25 Stringing chart shall be prepared considering following starting condition
26
27 1 Equivalent span less than the 350m (Normal span): 32 deg C , No wind condition
28
29 2 Equivalent span more than the 350m (Normal span): 32 deg C , Full wind condition