Introduction
This manual describes the configuration and settings required for communicating with the
host devices used by NS-series Programmable Terminals for Host Link communications.
First familiarize yourself with the contents of the manuals related to NS-series
Programmable Terminals (the NS-series Setup Manual, NS-series Programming Manual, and
the CX-Designer online help), and then use this manual for Host Link communications.
1
1-1 Overview
This section provides an overview of connecting an NS-V1/V2 PT to an OMRON
Programmable Controller that supports Host Link communications.
The NS-V1/V2 PT is connected 1:1 to the CPU Unit or a Host Link Unit of an OMRON PLC.
Host Link communications are used to read and display or write the words and settings in the
host PLC.
NS-V1/V2 PT serial ports A and B can both be connected to a host by means of the Host Link
protocol.
Reference
When an NS-V1/V2 PT and a PLC are connected by
Host Link, it is not possible to change to RUN Mode.
If the PLC is set for RUN Mode, it is automatically
switched to Monitor Mode. For example, if a
compatible Programming Console is connected to
the PLC and the PLC operating mode is switched to
RUN mode, the password display for the Monitor
Mode will be displayed at the Programming Console.
2
1-2 Connection Configuration
This section describes the system configuration required for connecting to the host by Host
Link communications.
Reference
NS-series PTs without the -V1 or -V2 suffix do not
support Host Link communications. One of the above
NS-V1/V2 models must be used.
3
Communications Ports
Communications Applicable communications method
port
Serial port A Host Link
1:1 NT link
1:N NT link
Memory link
(Bar-code reader input)
(Temperature controller connection)
(CX-Designer connection)
Serial port B Host Link
1:1 NT link
1:N NT link
Memory link
(Bar-code reader input)
(Temperature controller connection)
(CX-Designer connection)
The following table shows the communications methods that can be used in combination
when serial ports A and B are used at the same time.
Serial port B
CX-Designer
Memory link
1:N NT Link
1:1 NT Link
connection
Temperature
Host Link
Bar-code
controller
reader
Host Link YES YES YES YES YES YES YES
1:1 NT link YES YES YES YES YES YES YES
Serial port A
4
Communications Setup
The following table shows the communications settings required at the NS-V1/V2 PT and the
host to connect to the host by means of Host Link communications.
Setup Settings (See note 2.)
location
NS-V1/V2 PT Baud rate: 9,600 or 19,200 bps (See note 1.)
Host Start bits: 1 bit
Data: 7 bits
Stop bits: 2 bits
Parity: Even
Host Link unit number: 0
Baud rate: 9,600 or 19,200 bps (See note 1.)
Note 1: The baud rate settings must be the same for both the NS-V1/V2 PT and the host.
2: Use the 1:N protocol setting.
C Series
C200HS, C200HX/HG/HE(-Z), CQM1, CQM1H, CPM2A/CPM2C, CPM1/CPM1A, C500,
C1000H, C2000H
CV Series
CV500, CV1000, CV2000, CVM1
CS/CJ Series
CS1G/CS1H, CS1G-H/CS1H-H, CJ1G, CJ1G-H/CJ1H-H, CJ1M, CP1H/CP1L, CJ2H
5
1-3 Connecting to the Host
The types of host that can be connected to a PT by using the serial ports on the NS-series PT
and connecting to an RS-232C port at the host are described here.
6
PLC Series CPU Units with Built-in Host Link CPU Units Connectable with Host Host Link Unit/
Function Link Units or Expansion Communications
Communications Board Board
C1000H-CPU01-EV1 C500-LK201-EV1
C2000H-CPU01-EV1
C1000H-CPU01-EV1 C500-LK203
C1000HF-CPUA1-EV1
C2000H-CPU01-EV1
CPM1-10/20/30CDR-@+CPM1-CIF01
CPM1A-10/20/30/40CD@-@+CPM1-
CIF01
CPM2A-30/40/60CD@@-@+CPM1-
CIF01 (Peripheral port connection)
CPM2C-10/20@@@@@@-@
(See note 1.)
CQM1-CPU21-E
CQM1-CPU41/42/43/44-EV1
CQM1H-CPU11/21/51/61 (See note 2.) CQM1H-CPU51/61 CQM1H-SCB41
CV Series CV500-CPU01-EV1 CV500-CPU01-EV1 CV500-LK201
(See note 3.) CV1000-CPU01-EV1 CV1000-CPU01-EV1
CV2000-CPU01-EV1 CV2000-CPU01-EV1
CVM1 Series CVM1-CPU01-EV2 CVM1-CPU01-EV2 CV500-LK201
(See note 3.) CVM1-CPU11-EV2 CVM1-CPU11-EV2
CVM1-CPU21-EV2 CVM1-CPU21-EV2
CompoBus/S SRM1-C02-V2
master
control unit
Note 1: Use a CPM2C-CN111 or CS1W-CN114/118 Connecting Cable, CPM1-CIF01
RS-232C Adapter, or CPM1-CIF11 RS-422A Adapter to connect.
2: The CQM1H-CPU11 does not have a built-in RS-232C port, so connect to the
peripheral port to the PT with a CS1W-CN118 Connecting Cable.
3: CPU Units of CVM1/CV-series PLCs without the suffix –EV@ cannot be connected.
The setting methods for each type of unit are described in the following.
7
Connecting to a C-series Host Link Unit
8
Setting the Rear Switches
• I/O port selection (selector switch)
Set this to RS-232C.
Synchronization
• Communications speed
(DIP SW2-1 to SW2-4)
0V Set these switches to 0010 to select
19,200 bps.
Synchronization
• Communications speed
(DIP SW2-1 to SW2-4)
0V
Set these switches to 0010 to select
19,200 bps.
9
C200H/C1000H/C2000H CPU Unit-mounted Type: C120-LK201-EV
10
Set the CPU Bus Unit settings directly from a Programming Device (e.g. CX-Programmer).
For details on the CPU Bus Unit settings, refer to the SYSMAC CVM1/CV-series Host Link
Unit Operation Manual (W205-E1-@).
11
m = DM 30000 + 100 × unit number (word address)
Allocation DM area word Writing Settings
Port 1 Port 2 Value
m m+10 8000 Host link mode, 2 stop bits, even parity, data length
7 bits
m+1 m+11 0000 Communications speed 9600 bps.
0007 Communications speed 19200 bps.
m+2 m+12 0000 Transmit delay time 0 ms.
m+3 m+13 0000 No CTS control Unit No.0 for host link
CJ1W-SCU21-V1 CJ1W-SCU41-V1
• Port 1
RS-232C
• Port 2 • Port 2
RS-232C RS-232C
12
The following table shows words allocated in the DM Area and setting details.
m = D30000 + 100 × unit number (word address)
Allocation DM area word Writing Value Setting details
Port 1 Port 2
m m+10 8000 Host link mode, 2 stop bits, even parity,
7-bit data length
m+1 m+11 0000 Baud rate: 9,600 bps
0007 Baud rate: 19,200 bps
m+2 m+12 0000 Transmission delay time: 0 ms
m+3 m+13 0000 No CTS control, Unit number 0 for host
link
PLC Setup
When connecting to a CVM1/CV series CPU Unit, set the following communications conditions for
the PLC Setup.
Item Setting at Host
Communications speed Set the same baud rate as set at the NS-series PT (See note.)
Stop bit 2 stop bits
Parity Even
Data length ASCII 7 bits
Unit # 00
Note: Set the Host Link communications speed (baud rate) to 9600 bps or 19200 bps with
the Communications Setting menu item in the CX-Designer and the System Menu for
the NS-series PT. For details, refer to 1-4 Settings for Host Link.
Either set PLC Setup directly from a Programming Device (e.g. CX-Programmer), or transmit
the PLC Setup made at a Programming Device to the CPU UNIT.
For details on the PLC Setup, refer to the SYSMAC CVM1/CV500/1000/2000 Operation
Manual: Ladder Diagrams (W202-E1-@).
13
Setting the Front Switches
C-series C200HS, C200HX/HG/HE(-Z)E, CPM1, CPM2A, CPM2C, CQM1, CQM1H CPU Units, SRM1
The connection method depends upon the model of PLC being used, as shown in the following
table.
PLC model Connection method
C200HS, CQM1 Connect to the CPU Unit’s built-in RS-232C port.
C200HX/HG/HE(-Z)E • Connect to the CPU Unit’s built-in RS-232C port.
• Connect to one of the RS-232C ports (port A or port B) on a Serial
Communications Board.
CQM1H • Connect to the CPU Unit’s built-in RS-232C port.
• Connect to the peripheral port through a CS1W-CN118
Connecting Cable.
• Connect to the RS-232C port (port 1) on a Serial Communications
Board.
CPM1 Connect to the peripheral port through a CPM1-CIF01
RS-232C Adapter.
CPM2A, SRM1 • Connect to the CPU Unit’s built-in RS-232C port.
• Connect to the peripheral port through a CPM1-CIF01 RS-232C
Adapter.
CPM2C Connect to the CPU Unit’s RS-232C port or the peripheral port
through a Connecting Cable (CPM2C-CN111, CS1W-CN118,
or CS1W-CN114).
(The CPM2C-CN111 splits the Unit’s communications port into
an RS-232C port and a peripheral port. A CPM1-CIF01
RS-232C Adapter is also required to connect to this peripheral
port.)
14
Item Setting at Host
Parity Even
Data length ASCII 7 bits
Unit # 00
Note: Set the Host Link communications speed (baud rate) to 9600 bps or 19200 bps with
the Communications Setting menu item in the CX-Designer and the System Menu for
the NS-series PT. For details, refer to 1-4 Settings for Host Link.
Set the PLC Setup area settings directly from a Programming Device (e.g. CX-Programmer).
For details on operations relating to the PLC Setup area, refer to the manual for the PLC
which is used.
The PLC Setup area word numbers and settings to be made depending on the unit and port
to which the connection is made are shown below.
CPM2A, CPM2C, CQM1H, or SRM1: Peripheral port connection
Word Writing Value Settings
DM6650 0001 Host link mode, no CTS control, communications conditions
set by the contents of DM
DM6651 0303 Data length 7 bits, 2 stop bits, even parity, communications
speed: 9600 bps
0304 Data length 7 bits, 2 stop bits, even parity, communications
speed: 19200 bps
DM6653 0000 Unit # 00
C200HS, C200HX/HG/HE(-Z)E, CPM2A, CPM2C, CQM1, CQM1H (other than the CPU11),
or SRM1: Built-in RS-232C port connection
Word Writing Value Settings
DM6645 0001 Host link mode, no CTS control, communications conditions
set by the contents of DM
DM6646 0303 Data length 7 bits, 2 stop bits, even parity, communications
speed: 9600 bps
0304 Data length 7 bits, 2 stop bits, even parity, communications
speed: 19200 bps
DM6648 0000 Unit # 00
15
C200HX/HG/HE(-Z)E: Board Port B Connection
Word Writing Value Settings
DM6550 0001 Host link mode, no CTS control, communications conditions
set by the contents of DM
DM6551 0303 Data length 7 bits, 2 stop bits, even parity, communications
speed: 9600 bps
0304 Data length 7 bits, 2 stop bits, even parity, communications
speed: 19200 bps
DM6553 0000 Unit # 00
CPM1 Connection
Word Writing Value Settings
DM6650 0001 Host link mode, communications conditions set by the
contents of DM area
DM6651 0303 Data length 7 bits, 2 stop bits, even parity, communications
speed: 9600 bps
0304 Data length 7 bits, 2 stop bits, even parity, communications
speed: 19200 bps
DM6653 0000 Unit # 00
Connecting to a CPM2C
The CPM2C PLCs do not have the same kind of port connectors found on CS-series PLCs.
The CPM2C’s communications port handles both RS-232C and peripheral port connections
which are divided internally. Therefore, when using the CPM2C, it is necessary to select
RS-232C or peripheral port connections, according to the kind of cable and port (on the
cable) used, as shown in the following table. Refer to the CPM2C Operation Manual for more
details.
Port connecting to PT PLC Setup
RS-232C port (D-Sub 9-pin) of CPM2C-CN111 Built-in RS-232C port settings
Peripheral port of CPM2C-CN111 Peripheral port settings
RS-232C port (D-Sub 9-pin) of CS1W-CN118 Built-in RS-232C port settings
Peripheral port of CS1W-CN114 Peripheral port settings
Peripheral port
16
RS-232C port communication condition setting
Set DIP SW5 to OFF to make the settings made in
PC Setup effective.
17
CS-series CPU Unit type: CS1G/H-CPU-EV1, CS1G/H-H
Connect to the built-in RS-232C port of the CPU Unit, or the RS-232C port of the
Communications Board. Note that the connection to a peripheral port must be made via an
RS-232C adapter (CS1W-CN118) specially designed for connecting to a peripheral port.
PLC Setup
When connecting to a CS-series CPU Unit, set the following communications conditions for
the PLC Setup area. Since the settings shown below are the PLC default settings for the CPU
Unit, no change to the PLC Setup is necessary as long as the communications speed is
maintained at 9600 bps.
Item Setting at Host
Communications speed Set the same baud rate as set at the NS-series PT (See note.)
Stop bits 2 stop bits
Parity Even
Data length ASCII 7 bits
Unit No. for the host link 00
Note: Set the Host Link communications speed (baud rate) to 9600 bps or 19200 bps with
the Communications Setting menu item in the CX-Designer and the System Menu for
the NS-series PT. For details, refer to 1-4 Settings for Host Link.
When the communications speed is set to 19200 bps., the PLC Setup of the CPU Unit
need to be changed.
Either set the PLC Setup directly from a Programming Device (Programming Console), or
transmit the PLC Setup made at a Programming Device (CX-Programmer) to the CPU Unit.
For details on PLC Setup, refer to the SYSMAC CS series Operation Manual (W339-E1-@).
18
DIP switches (inside the battery storage)
• Set SW4 to ON (establishing communication in
accordance with PC Setup) when connecting the NS-
series PT to a peripheral port.
• Set SW5 to OFF (establishing communication in
Peripheral port accordance with PC Setup) when connecting the NS-
This is used mainly for series PT to an RS-232C port.
connection to the
Programming Device.
(This also supports the
RS-232C unit connection.)
RS-232 port
This is used mainly for
connection to the RS-232C
unit.
(This also supports the
CX-Programmer.)
Serial Communications Board equipped with an RS-232C port for CS-series CPU Units:
CS1W-SCB41/21-V1
19
Check the model and series of the PLC and the type of the installed Board or Unit before
making a connection.
The PLC Units that provide an RS-422A Host Link interface and that can be connected to an
NS-series PT port to which an RS-232C/RS422A Link Adaptor (NS-AL002) is connected are
listed in the following table.
PLC CPU Units with Built-in Host Link CPU Units Connectable with Host Link Unit/
Series Function Host Link Units or Expansion Communications Board
Communications Board
CS CS1G-CPU42/43/44/45-EV1 CS1W-SCB41-V1
Series CS1H-CPU63/64/65/66/67-EV1
CS1G-CPU42H/43H/44H/45H
CS1H-CPU63H/64H/65H/66H/
67H
CJ CJ1G-CPU44/CPU45 CJ1W-SCU41-V1
Series CJ1G-CPU42H/43H/44H/45H
CJ1H-CPU65H/66H/67H
CJ1H-CPU65H/66H/67H-R
CJ2H-CPU64/65/66/67/68-EIP
CJ1M-CPU11/12/13/21/22/23
CP1H-XA40DR-A/XA40DT-D/XA CP1W-CIF11
40DT1-D/X40DR-A/X40DT-D/X4
0DT1-D/Y20DT-D
CP1L-L14DR-A/L14DR-D/L14DT-
D/L14DT1-D/L20DR-A/L20DR-D/
L20DT-D/L20DT1-D/M30DR-A/M
30DR-D/M30DT-D/M30DT1-D/M
40DR-A/M40DR-D/M40DT-D/M4
0DT1-D
C C1000H-CPU01-EV1 C120-LK202-EV1
Series C2000H-CPU01-EV1
C200HS-CPU01/03/21/23/31/33-E C200H-LK202-EV1
C200HE-CPU11/32/42-E
C200HE-CPU11/32/42-ZE
C200HG-CPU33/43/53/63-E
C200HG-CPU33/43/53/63-ZE
C200HX-CPU34/44/54/64-E
C200HX-
CPU34/44/54/64/65/85-ZE
C200HE-CPU32/42-E C200HW-COM03/06-EV
C200HE-CPU32/42-ZE 1
C200HG-CPU33/43/53/63-E
C200HG-CPU33/43/53/63-ZE
C200HX-CPU34/44/54/64-E
C200HX-
CPU34/44/54/64/65/85-ZE
C1000H-CPU01-EV1 C500-LK201-EV1
C2000H-CPU01-EV1
C1000H-CPU01-EV1 C500-LK203
C1000HF-CPUA1-EV1
C2000H-CPU01-EV1
CPM1-10/20CDR-@+CPM1-CIF11
CPM1A-10/20/30/40CD@-@+CPM1-CIF11
20
PLC CPU Units with Built-in Host Link CPU Units Connectable with Host Link Unit/
Series Function Host Link Units or Expansion Communications Board
Communications Board
CPM2A-30/40/60CD@@-@+CPM1-CIF11
(Peripheral port connection)
C CPM2C-10/20@@@@@@-@ (See note 1.)
Series
CQM1H-CPU51/61 CQM1H-SCB41
CV CV500-CPU01-EV1 CV500-CPU01-EV1 CV500-LK201
Series CV1000-CPU01-EV1 CV1000-CPU01-EV1
(See
note CV2000-CPU01-EV1 CV2000-CPU01-EV1
2.)
CVM1 CVM1-CPU01-EV2 CVM1-CPU01-EV2 CV500-LK201
Series CVM1-CPU11-EV2 CVM1-CPU11-EV2
(See
CVM1-CPU21-EV2 CVM1-CPU21-EV2
note
2.)
SRM1 SRM1-C02-V2+CPM1-CIF11
Note 1: Use a CPM2C-CN111 or CS1W-CN114/118 Connecting Cable, CPM1-CIF01
RS-232C Adapter, or CPM1-CIF11 RS-422A Adapter to connect.
2: CPU Units of CVM1/CV-series PLCs without the suffix -EV@ cannot be connected.
The RS-485 interface (2-wire method) provided by NS-series PTs is for connecting to an
OMRON Temperature Controller. Do not connect it to an NS-series PT or PLCs using RS-485.
The setting methods for each type of unit are described in the following.
21
Connecting to a C Series Host Link Unit
Terminator
22
C1000H/C2000H Rack-mounted Type: C500-LK201-EV1
I/O port
• Communications speed
(DIP SW2-1 to SW2-4)
0V
Set these switches to 0010 to select
19200 bps.
Set these switches to 1010 to select
9600 bps.
(0: OFF 1: ON)
23
C1000H(F)/C2000H Rack-mounted Type: C500-LK203
5V supply
Synchronization
• Communications speed
(DIP SW2-1 to SW2-4)
0V Set these switches to 0010 to select
19,200 bps.
Set these switches to 1010 to select
9,600 bps.
(0: OFF 1: ON)
24
Connecting to a CVM1/CV Series Host Link Unit
Set the CPU Bus Unit settings directly from a Programming Device (e.g., CX-Programmer).
For details on the CPU Bus Unit settings, refer to the SYSMAC CVM1/CV-series Host Link
Unit Operation Manual (W205-E1-@).
25
Setting the Front Switches
Communications port 2
(RS-232C/RS-422A)
PLC Setup
When connecting to a CVM1/CV-series CPU Unit, set the following communications
conditions for the PLC Setup.
Item Setting at Host
Communications speed Set the same baud rate as set at the NS-series PT (See note.)
Stop bit 2 stop bits
Parity Even
Data length ASCII 7 bits
Unit # 00
Note: Set the Host Link communications speed (baud rate) to 9600 bps or 19200 bps with
the Communications Setting menu item in the CX-Designer and the System Menu for
the NS-series PT. For details, refer to 1-4 Settings for Host Link.
Either set the PLC Setup directly from a Programming Device (e.g. CX-Programmer), or
transmit the PLC Setup made at a Programming Device to the CPU Unit.
For details on the PLC Setup, refer to the SYSMAC CVM1/CV500/CV1000/ CV2000
Operation Manual: Ladder Diagrams (W202-E1-@).
26
Setting the Front Switches
• I/O port selection (selector switch)
Set this to RS-422A.
Note
For CPUs manufactured before or
during June 1995 (lot No. @@65), the
existing DIP switch settings differ from
the PC Setup default values as follows.
- Existing DIP switch settings:
2,400 bps, 1 stop bit, even parity, 7 bit
data length
- PC Setup default values:
9,600 bps, 2 stop bits, even parity, 7
bit data length
For CPUs manufactured from July 1995
onward (lot No. @@75), the stipulated
values in the DIP switch settings also
are 9600 bps and 2 stop bits.
Reference
• There are no Communications Boards for the
C200HX/HG/HE(-Z)E in which port B is the RS-422A port.
• There are no Serial Communications Boards for the
CQM1H in which port 1 is the RS-422A port.
27
PLC Setup Area Settings
When connecting to a C200HX/HG/HE(-Z)E or CPM1, CPM2A, CPM2C, CQM1H CPU Units
or SRM1, set the following communications conditions for the PLC Setup area.
Item Setting at Host
I/O port RS-422A
Communications mode Host link mode
Communications speed Set the same baud rate as set at the NS-series PT (See note.)
Stop bit 2 stop bits
Parity Even
Data length ASCII 7 bits
Unit # 00
Note: Set the Host Link communications speed (baud rate) to 9600 bps or 19200 bps with
the Communications Setting menu item in the CX-Designer and the System Menu for
the NS-series PT. For details, refer to 1-4 Settings for Host Link.
Set the PLC Setup area settings directly from a Programming Device (e.g. CX-Programmer).
For details on operations relating to the PLC Setup area, refer to the manual for the PLC
which is used.
The PLC Setup area word numbers and settings to be made depending on the unit to which
the connection is made are shown below.
28
When using a CQM1H
Word # Writing Value Settings
DM6550 0001 Host link mode, no CTS control, communications
conditions set by the contents of DM area
DM6551 0303 Data length 7 bits, 2 stop bits, even parity,
communications speed: 9600 bps
0304 Data length 7 bits, 2 stop bits, even parity,
communications speed: 19200 bps
DM6553 0000 Unit # 00
Connecting to a CPM2C
The CPM2C PLCs do not have the same kind of port connectors found on CS-series PLCs.
The CPM2C’s communications port handles both RS-232C and peripheral port connections
which are divided internally. Therefore, when using the CPM2C, it is necessary to select
RS-232C or peripheral port connections, according to the kind of cable and port (on the
cable) used, as shown in the following table. Refer to the CPM2C Operation Manual for more
details.
Peripheral port
Peripheral port
RS-232C port
(D-Sub 9-pin, female)
29
Setting the Switches on an RS-422A Adapter
30
Connecting to a CJ-series Serial Communications Unit
• Port 1
RS-422A/485
31
1-4 Settings for Host Link
This section describes the procedure for making the NS-V1 PT settings for connecting to the
host by means of Host Link communications.
Use either serial port A or B. The flow of operations for connecting to the host is as follows:
(1) Design the screen data.
(2) Transfer the screen data.
(3) Set the communications method for serial port A or B
(4) Connect to the host.
32
(1) Press the Comm. Tab in the System Menu to display the Communications Setup Screen.
(For the NS5 PT, press the Comm. Button in the System Menu to display the screen, and
then press the ← and → Screen Switching Buttons to display the screen for page (2/3).
(2) Press the drop-down menu button and set Host Link as the communications method for
serial port A or B.
(3) Press the Detail Button to display the Host Link settings, and select Comm. Speed.
(4) Press the Write Button and press the Yes Button on the following dialog boxes to restart
the NS-V1/V2.
NS12/NS10/NS8-V1/V2 PT
(The screen is somewhat different for the NS12.)
NS5
33
1-4-4 Connecting to the Host
Connect in the same way as for a 1:1 NT Link, and use the same cables that are used for a
1:1 NT Link connection.
If cables must be prepared, refer to the relevant manuals for the PLC or Host Link Unit, and to
the NS Series Setup Manual (Cat. No. V083).
34
1-5 PLC Areas That Can Be Used for Communications
EM Area (Current
Common I/O Area
Area (TIM/CNT)
Auxiliary Relay
Timer/Counter
Holding Relay
Data Memory
bank) (EM)
Area (DM)
(CIO)
(HR)
(AR)
C200HS 00000 00000 00000 00000 00000 00000 -
C200HE/HG/HX(-Z) to to to to to to 00000
00511 00099 00027 00063 00511 06655 to
07000 06143
to
09999
C500 00000 00000 - 00000 00000 00000 -
to to to to to
00063 00031 00031 00127 00511
C1000H 00000 00000 00000 00000 00000 00000 -
to to to to to to
00255 00099 00027 00063 00511 04095
Ladder type PLCs
C2000H 00000 -
CQM1 to
06655
CQM1H 00000 00000
to to
06655 06143
CPM1/CPM1A 00000 00000 00000 00000 00000 00000 -
to to to to to to
00019 00019 00015 00015 00127 01023
00200 06144
to to
00255 06655
CPM2A/CPM2C 00000 00000 00000 00000 -
to to to to
00049 00023 00255 02047
00200 06144
to to
00255 06655
35
CVM1/CV-series PLCs
PLC model
Timer/Counter Area
Holding Relay (HR)
(TIM/CNT)
(DM)
CV500 00000 - 00000 - 00000 00000 -
CVM1-CPU01-V@ to to to to
02555 00511 00511 08191
CVM1-CPU11-V@ 00000 - 00000 - 00000 00000 -
to to to to
02555 00511 01023 09999
CV1000 00000 - 00000 - 00000 00000 -
CV2000 to to to to
CVM1-CPU11-V@ 02555 00511 01023 09999
CVM1-CPU21-V@
Note 1: The HR Area is included in the CIO Area. To use the HR Area, specify the CIO Area.
2: Do not use this area for creating screens. It cannot be used with Host Link
communications.
Timer/Counter
Holding Relay
Data Memory
Area (DM)
bank)
(HR)
(AR)
CP1H
(See note 2.)
CJ2H
36
1-6 Restrictions
Applicable Project Versions
When connecting to the host by means of Host Link communications, use version 6.0 or later
for creating the screen data (project) to be transferred to the NS-V1/V2 PT.
To use a project of version 5.x or earlier, first use CX-Designer to convert the project to
version 6.0 or later before transferring it to the NS-V1/V2 PT.
Applicable NS Models
Only NS-series PT models with a -V1/V2 suffix can be used to connect to the host by means
of Host Link communications. NS-series PT models without the -V1/V2 suffix cannot be
connected.
37
Revision History
The following table outlines the changes made to the manual during each revision. Page
numbers refer to the previous version.
03 July 2007 Pages 6 and 20: CJ-series CPU Unit model numbers
added.
04 June 2008 Cover: Added models to list of NS-series PT.
Page 3: Added 3 models to end of model table in
section 1-2-1.
Page 5: Added CJ2H to list of CS/CJ-series PLCs.
Pages 6 and 19: Added models to CJ-series PLCs in
table.
Page 26: Added CJ2H to PLC models listed in table.
38