0% found this document useful (0 votes)
174 views84 pages

CT Ortea 2019 S07 DVS 2en

Ortea is an Italian company that has been manufacturing voltage stabilizers for over 45 years. It offers a wide range of electro-mechanical and static digital voltage stabilizers for single and three-phase applications up to 6000 kVA. Ortea prides itself on reliability, flexibility to customize products, speed of order fulfillment, ongoing research and development, and an integrated quality management system.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
174 views84 pages

CT Ortea 2019 S07 DVS 2en

Ortea is an Italian company that has been manufacturing voltage stabilizers for over 45 years. It offers a wide range of electro-mechanical and static digital voltage stabilizers for single and three-phase applications up to 6000 kVA. Ortea prides itself on reliability, flexibility to customize products, speed of order fulfillment, ongoing research and development, and an integrated quality management system.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 84

STABLE VOLTAGE SUPPLY INDEPENDENTLY FROM

INPUT FLUCTUATION IS THE KEY FEATURE TO ENSURE


ELECTRICAL EFFICIENCY AND RELIABILITY

VOLTAGE
STABILISERS
Founded in 1969, ORTEA SpA is a leading company in manufacturing and engineering voltage
stabilisers and magnetic components.
Over forty years in the business and ongoing technical research have made of ORTEA a competitive
and technologically advanced company. Close co-operation between design, production and
marketing enables to meet the requirements of a constantly growing number of customers.
In 1996 ORTEA joined ICAR Group, made of Italian and European industrial units specialised in
manufacturing capacitors and power factor correction systems.
Beside standard production, ORTEA can be extremely flexible in developing and manufacturing
special equipment according to User’s specification. All this thanks to the experience gained over
many years of applied technological development.
Such development includes IT tools that enable the technical staff to elaborate electrical and
mechanical designs for each «custom product» on a quick and cost-effective basis.

ORTEA is well established in the global market. Thanks to strategically positioned offices and
distributors and efficient commercial relations, ORTEA’s products are installed and working in a large
number of countries.
www.ortea.com

ORTEA headquarters (Italy)


ORTEA branches (Russia, Ivory Coast, Kenya, Venezuela, Thailand)
The belief that product quality and Customer satisfaction are the core of a modern organisation, led to
the implementation of an ISO9001:2015 certified Company Managing System.
The achievement of the ISO14001:2015 and OHSAS18001:2007 accreditation was a natural
integration in order to optimise the Company's performance, showing at the same time the
commitment towards environmental and safety at work issues.
Experience.
In its over 45 years of business, Ortea (founded in 1969) has gained experience and know-how that enabled
continuous growth and evolution. This never-ending process has allowed the Company to assume a leading role
worldwide in designing and manufacturing voltage stabilisers.

Reliability.
Thanks also to its long-established Quality System, ORTEA can ensure the production of reliable and long lasting
products, each one of them accurately tested.

Flexibility.
In addition to the standard production, ORTEA's extremely flexible organization is able to develop and manufacture
cost-effective special equipment based on the Customer's specification.

Speed.
ORTEA can manage the purchasing orders very quickly. Review of offer/order, design, production planning,
manufacturing and strict test routines: all the processes have been analysed and optimised in order to eliminate idle
time and shorten delivery terms.

Research & Development.


ORTEA invests a considerable amount in R&D concerning new products and technology. It is acknowledged that
modern challenges in a globalised and competitive market can be won only when you're «ahead of time».

Synergy.
Co-operation between Headquarters, Subsidiaries, Distributors and Customers aimed at a careful analysis of
markets and demand enable ORTEA the development of up-to-date products.
By working together, marketing, design, production and after-sales service allow the Company to meet the
necessities set forth by an increasingly globalised and competitive market.

After-sales.
The continuous monitoring and analysis of requests and claims carried out by the after-sales service enables the
improvement the quality of both products and service to the Customer.
ORTEA after-sales organization can act quickly, providing for precise issue analysis, supply of advise and know-how
and , if necessary, provision of spare parts in order to solve any anomaly.

Quality.
Aiming at providing for the best quality, the manufacturing process includes checks during production and detail
test sessions for each stabiliser.
The approved Integrated Managing System ensures the control of every manufacturing phase, starting from
checking the components at reception and ending with the best package in relation to the transport type.
The Integrated Managing System is ISO9001:2015 – ISO14001:2015 – OHSAS18001:2007 approved.

4
Digital voltage stabilisers Pg.
The issue 6
The solution 6
Criteria for choosing the right type 8

Electro-mechanical digital voltage stabilisers Pg.


Design criteria 10
Main components 11
Product range 13
Vega Single-phase 0.3-25kVA 14
Antares Single-phase 15-135kVA 18
Orion Three-phase 2-135kVA 22
Orion plus Three-phase 30-2000kVA 28
Sirius Three-phase 60-6000kVA 34
Sirius advance Three-phase 60-4000kVA 42

Power Quality Optimisers Pg.


OPTInet Three-phase 10-6000A 50

Static digital voltage stabilisers Pg.


Design criteria 56
Main components 57
Product range 57
Gemini / Gemini Plus Single-phase 4-40kVA 58
Aquarius / Aquarius Plus Three-phase 10-120kVA 60
Odyssey Three-phase 80-4000kVA 62

Accessories 67

Cabinets size 75

«Special» voltage stabilisers Pg.


Product range 77
BTS series Telecommunication (TLC) 78
DLC series Line conditioners 80
BC series Broadcasting 81
AOT series Mains filters 81
OUTDOOR series Outdoor installations 82
F&B series Food & Beverage, packaging and bottling industry 82

5
The issue
Electricity is perhaps the most essential raw material used by commerce and industry today. The
electricity produced in power plants is circulated through the electricity transmission and distribution
networks and it is supplied/delivered to consumers; the quality of electricity (known as «Power
Quality») is one of the important factors that determine the economic efficiency of both consumers and
electrical networks.
Electrical devices are designed to work in distributing systems defined by set nominal values in terms of
voltage and frequency (for example, 400V at 50Hz).
In actual fact, electric energy distribution might not ensure the stability of said nominal parameters.
Voltage in particular can vary even considerably in relation to the nominal value. These variation can
cause undesired and potentially dangerous conditions for the users.
Voltage "fluctuations' can be 'fast' and waste themselves away in a few milliseconds (for example,
distribution lines hit by lightning) or 'slow', with duration that can last several seconds, minutes or even
hours depending on the cause.
Slow fluctuations can be generated by increased voltage level ('surge' due to poor MV regulation at
distribution level, disconnection of large loads, overvoltage at generators output, etc) or – more
frequently – by decreased voltage level ('sags' due to connection of large loads, motor startup,
undersized distribution lines, faults to ground, poor MV voltage regulation, etc).
In case of voltage variation, the voltage stabiliser is the solution that guarantees for the best
cost/benefit ratio.
The continuous availability of stable voltage supply independently from input fluctuation is very often a
key feature to ensure efficiency and reliability for the User.
Reduced productivity, data loss, security failure, machine faults, inaccurate information and domestic
inconveniences are only a few examples of potential problems caused by unsteady supply. Obviously, all
that results in higher managing cost.

The solution
The voltage stabiliser has proven to be an effective solution able to prevent potentially dangerous
situations created by input voltage instability.

VOLTAGE
STABILISER

The main application fields where devices sensitive to voltage variations can be used include:
– Industrial sector: oil & gas, laser cutting, water shearing, tobacco industry, textile industry, galvanic
processes, machinery in general.
– Food & Beverage: industry, intensive breeding, food processing, packaging, bottling.
– Tertiary & servicing: banks, hotels & tourist resorts, data centre, laboratories, small businesses,
private users.
– Telecommunications: TV/Radio stations, telecom networks.
– Public sector: hospitals, public offices & institutions.
– Renewable sources: solar and wind farms.

6
In all these applications, voltage fluctuation, even though within the tolerance admitted by the
Standards, can generate operating issues. In that case, devices particularly sensitive can show errors
or malfunctions beyond the acceptable limit.

Typical situations where voltage can be subject to fluctuation beyond the admitted tolerance are:
– Loads supplied by weak or undersized distributing lines (rural areas or locations supplied by long
distributing lines such as breeding farms, tourist resorts, hotels, etc).
– Users located near distributing station and therefore subject to voltage increase.
– Private premises with high power installations (swimming pool pumps, big chillers, special lighting
systems, lifts) and/or particularly voltage sensitive loads (high power consumer electronics, etc.).
– Loads located near large industrial plants where individual high power devices (MV motors) can
induce voltage reduction at startup.
– Island operating loads (ships, offshore rigs, loads not connected to the public grid).

In comparison to other types of equipment, the voltage stabilser offers a number of advantages that
very often make it the optimum solution:
– Usually lower price.
– High output voltage stability guaranteed even for wide input fluctuation.
– Absence of introduced harmonic distortion.
– Robust and reliable construction, allowing for use in hard environments.
– Overload capability up to twice the rated current (max 2 mins).
– No concerns in terms of storage, transportation, maintenance and disposal due to the fact that
batteries are not used.
– Smooth and reliable regulation of the load voltage ensuring a ±0.5% accuracy even with important
input voltage variation.
– High efficiency.
– High inrush current withstand capability.
– Reduced dimension, simple to run, 'plug&play' operating mode.

Electro-mechanical or Static voltage stabilisers?


The static stabiliser is used when the correction speed represents the critical issue (for example,
computers, laboratory equipment, measuring benches and medical instrumentation). This kind of
stabiliser has correction time of 3 milliseconds for full regulation as compared to electro-mechanical
stabiliser correction time of 10-50 milliseconds (depends on the model) per volt.

7
Criteria for choosing the right type
Number of phases
The number of phases of a stabiliser depends on the type of load:
– single-phase load: single-phase stabiliser;
– combination of several single-phase loads on the same line: three-phase stabiliser or a single-phase stabiliser on each load;
– three-phase load: three-phase stabiliser.

Rated voltage
Due to the fact that the nominal voltage varies internationally, establish the rated voltage required at the stabiliser input and output. In case of three-
phase systems, provide with the line-to-line voltage value. The standard voltage stabiliser can operate with nominal voltage 380V-400V-415V (50Hz) or
440V-460V-480V (60Hz).
Input variation range
It's key information for the choice and the design of the stabiliser. Establish the amplitude of the oscillation of the input voltage and always keep a
safety margin on such percentage: for example, if the measured fluctuation is ±16%, then choose a stabiliser suitable for ±20% variation.
Note: if the input variation exceeds the nominal one, the difference is added to the output precision. For example, if a stabiliser designed for ±15% input
variation receives a +20% voltage, the output precision shall not be ±0.5% but ±5.5%.

Type of regulation
The three-phase voltage stabilisers perform an independent regulation on each phase. The connection to the distributing line neutral wire is
mandatory. Should the neutral wire not be available, a specific accessory component must be added.
Type of technology
In most applications, the electromechanical voltage stabiliser is a reliable and safe tool. In case of high regulation speed is required (milliseconds), it is
better to choose the solution with regulation by means of IGBT static switches.
Rated power
All the stabilisers are designed for the maximum input current, but it is advisable to consider an extra safety margin for possible future expansions.
In a voltage stabiliser, the power is expressed in kVA, whilst the load power is usually expressed in kW. Remember that the link between these two
measuring units is provided by the power factor (cos φ): kVA = kW / cos φ
Also, remember that if the power factor and/or the load power in kW cannot be easily established, measure the absorbed currents in order to allow for a
correct design of the stabiliser and keeping in mind that:
kVA (1-ph.) = load voltage x load current
kVA (3-ph.) = Ö3 x phase to phase load voltage x load current

Installation
Choose the other characteristics of the stabiliser considering the installation conditions.
The following aspect must be known:
– IP protection degree required.
– Indoor or outdoor installation.
– Site altitude and climatic characteristics.
– Ambient temperature.
– Possible environmental hazards such as aggressive atmosphere, exposure to chemical components and so on.

Accessories
A standard voltage stabiliser can be enriched with a number of accessories:
– Interruption and protection devices.
– Load protection against over/undervoltage.
– Bypass line.
– Input isolating transformer.
– Total protection kit.
– Surge arrestor (SPD).
– Integrated automatic power factor correction system.
– EMI/RFI filter.
– Neutral point reactor.
– Up to IP54 protection degree for both indoor and outdoor installation.

Special construction
By means of some modifications, it is possible to obtain special stabilisers able to:
– deal with asymmetrical input voltage variation (for example, from -25% to +10% of the nominal voltage);
– deliver an output voltage different from the input one (for example, Vin = 400V ±15%, Vout = 460V ±0.5%).

8
Electro-mechanical
digital voltage stabilisers

9
Electro-mechanical digital voltage stabilisers

Design criteria
A voltage stabiliser is a power device destined to be positioned between the mains and the User. The
purpose is to ensure that the User is fed a voltage subject to a variation much lower (±0.5% with regards
to the nominal value) that the one guaranteed by the distributing system.
The stabilization is performed on the «true rms» voltage and it is not affected by harmonics in the
mains. Due to the fact that the regulation does not involve any intervention on the sinewave, neither an
appreciable harmonic distortion nor a phase displacement is introduced on the downstream line.
The stabiliser is not affected by the load power factor (cos φ) and can operate with a load percentage
varying between 0% and 100% on each phase. Regulation speed depends on the input voltage variation
percentage and on the type of construction. Indicatively, said speed ranges between 8 and 30millisec/V.
Basically, a voltage stabiliser is made of a buck/boost transformer, a voltage regulator and an
electronic control. Based on a microprocessor that samples at high frequency the output voltage, the
control system drives the regulator gearmotor. By doing so, the regulator rollers change their position
and therefore the voltage drawn and supplied to the buck/boost transformer primary winding. Being the
secondary voltage of the buck/boost transformer in phase or in opposition to the supply, the voltage
drawn from the regulator is added or subtracted to the mains voltage, thus compensating its variations.
The voltage regulator is nothing but an autotransformer with continuously variable transformer ratio.
Depending on the stabiliser power, the regulator can be either toroidal or columnar.
The stabilisers are designed and built in compliance with the European Directives concerning CE
marking (Low Voltage and Electromagnetic Compatibility Directives).
Standard units are housed in an IP21 metallic enclosure RAL7035 painted. Cooling is guaranteed by
natural air circulation aided by extracting fans over a certain temperature.
The voltage stabiliser operating nominal voltage can be chosen from values (generally included in the
range 380V / 415V). Such setting can be performed at the factory or at the Customer's premises
according to the instructions given in the reference technical handbook.
On Sirius and Sirius Advance stabilisers, the output voltage reference and the main configuration
parameters can be set in different ways:
– through the local touch panel;
– directly by communicating with the microprocessor via a PC connection (through USB interfaces);
– from a remote station via Ethernet with MODBUS TCP/IP protocol.

Working principle of an electro-mechanical digital voltage stabiliser

BUCK/BOOST TRANSFORMER
U U1

V V1

W W1
OUTPUT
INPUT

REGULATOR

REGULATOR

REGULATOR
VOLTAGE

VOLTAGE

VOLTAGE

N N

M M M

DIGITAL CONTROL BOARD

10
Main components
1. Buck/boost transformer
Often referred to as 'booster' transformer, it is a standard dry-type transformer with the secondary
winding connected in series to the mains and the primary winding supplied by the voltage regulator.

2. Voltage regulator
Basically, it is an autotransformer with continuously variable transformer ratio. The voltage intake varies
depending on the position of the rolling contacts; therefore the voltage supplied to the booster
transformer primary winding also varies. Being the voltage across the regulator contacts (and
consequently that on the secondary winding of the booster transformer) either in phase or in opposition to
the supply voltage, it is then added or subtracted to the supply voltage, thus compensating its variations.

3. Auxiliary circuit with microprocessor


The DSP (Digital Signal Processor) microprocessor-based control circuit (specifically designed for
drives with totally digitalised signal) compares the output voltage value to the reference one sampling it
2000 times per second.
When an anomaly is detected, the control drives the voltage regulator gearmotor. By doing so, the
regulator rollers change their position thus varying the voltage drawn and supplied to the buck/boost
transformer primary winding. The input voltage variation is therefore automatically compensated.
The control system operates so that the output accuracy is ±0.5%. The microprocessor is fitted with the
soft stop function enabling a precise positoning of the regulator rollers regulation to work smoothly
even in case of strong fluctuation of the input voltage.

3
2 2 2
1

11
12
Electro-mechanical digital voltage stabilisers

Vega Single-phase 0.3-25kVA


Antares Single-phase 15-135kVA
Orion Three-phase 2-135kVA
Orion plus Three-phase 30-2000kVA
Sirius Three-phase 60-6000kVA
Sirius advance Three-phase 60-4000kVA

Single-phase Three-phase
Vega Antares Orion Orion plus Sirius Sirius advance
Output accuracy ±0,5% ü ü ü ü ü ü
Regulator rolling contacts ü ü ü ü ü ü
Toroidal regulator ü up to 80kVA ü up to 135kVA x x
Columnar regulator x from 100kVA x from 160kVA ü ü
Control electronic board ü ü ü ü ü ü
Local display ü x x x ü ü
Alarm signal code LCD Display LED (board) LED (board) x ü ü
External alarm LEDs x x x ü x x
External phase indication LEDs x x x ü x x
Acoustic alarm ü ü ü ü ü ü
USB connection x x x ü ü ü
RS485 connection l l l l ü ü
Ethernet connection x x x x ü ü
MODBUS TCP/IP protocol x x x x ü ü
Maintenance required signal x x x ü ü ü
Regulator protection (magneto-thermal) ü ü ü x x x
Regulator protection (electronic) x x x ü ü ü
Overvoltage protection SPD cl. I l l l l ü ü
Overvoltage protection SPD cl. II l l from 60kVA ü ü ü
Digital voltmeter ü x x x x x
Multimetre / Line analyser l ü ü ü x x
Touch Display x x x x ü ü
Air conditioning cooling x l l l l l
Load variation up to 100% ü ü ü ü ü ü
Overload up to 200% for 2 mins. ü ü ü ü ü ü
Harmonic distortion none introduced none introduced none introduced none introduced none introduced none introduced
IP21 degree protection ü ü ü ü ü ü
Protection degree other than IP21 l l l l l l
Indoor installation ü ü ü ü ü ü
Outdoor installation l l l l l l
Ambient temperature -25/+45°C -25/+45°C -25/+45°C -25/+45°C -25/+45°C -25/+45°C
Storage temperature -25/+60°C -25/+60°C -25/+60°C -25/+60°C -25/+60°C -25/+60°C
Max relative humidity 95% 95% 95% 95% 95% 95%
ü standard
x not available
l optional

13
Electro-mechanical digital voltage stabilisers WA
RRANTY

2
YEARS

single-phase
Vega 0.3-25kVA
Standard features
Selectable output voltage (dip-switch)* 220-230-240V
Output voltage accuracy ±0,5%
Frequency 50Hz ±5% or 60Hz ±5%
Admitted load variation Up to 100%
Cooling Natural ventilation
Ambient temperature -25/+45°C
Storage temperature -25/+60°C
Max relative humidity 95% (non condensing)
Admitted overload 200% 2 min.
Harmonic distortion None introduced
Colour RAL 7035
Protection degree IP21
Instrumentation Output digital voltmetre
Installation Indoor
* The output voltage can be adjusted by choosing one of the indicated values.
Such choice sets the new nominal value as a reference for all the stabiliser parameters.

Accessories
Interrupting devices
Load protection against over/undervoltage
Manual by-pass line
Input isolating transformer
SPD surge arrestor
EMI/RFI filters
IP54 protection degree for indoor and outdoor installation

Rating in relation to the input variation percentage


±15% ±20% ±25% ±30% +15%/-25% +15%/-35% +15%/-45%
1 0.7 0.5 0.3 0.7 0.5 0.3
2.5 2 1.5 1 2 1.5 1
5 4 3 2 4 3 2
7 5 4 3 5 4 3
10 7 5 4 7 5 4
15 10 7 5 10 7 5
20 15 10 7 15 10 7
25 20 15 10 20 15 10

All ORTEA stabilisers are designed and built in compliance with the Low Voltage and Electromagnetic Compatibility European Directives with regard to the
CE marking requirements. ORTEA products are built with suitable quality components and that the manufacturing process is constantly verified in
accordance with the Quality Control Plans which the Company applies in compliance with the ISO 9001:2015 Standards. The commitment towards
environmental issues and safety at work issues is guaranteed by the certification of the Management System according to the ISO14001:2015 and
OHSAS18001:2007 Standards. In order to obtain better performance, the products described in the present document can be altered by the Company at any
date and without prior notice. Technical data and descriptions do not hold therefore any contractual value.

14
Vega
single-phase
0.3-25kVA
Vega stabilisers are available for different ranges of input voltage fluctuation.
Standard models offer a double input connection so that with the same unit two different input
variations (±15/±20% or ±25/±30%) can be dealt with.
An automatic circuit breaker is mounted on the regulation circuit to protect against overload and short
circuit on the voltage regulator, whilst the auxiliary circuit is protected by fuses.
A digital display on the front panel shows the output voltage and the alarms (min/max output voltage,
gearmotor lock, internal overheating, regulator overload)
The control logic is based on a digital microprocessor.
All Vega stabilisers are fitted with the same control card, thus simplifying maintenance operations and
spare parts storage.

Wide range
– symmetrical: ±15%, ±20%, ±25%, ±30% (other on request)
– asyimmetrical: +15%/-25%, +15%/-35%, +15%/-45% (other on request)
Output voltage accuracy: ±0.5%.

Technology
Control logic based on digital microprocessor operating with a software
specifically developed for Ortea.

Long life
Ortea system voltage regulator with rollers (without brushes, which are
subject to heavy wear & tear).

Protection
The voltage regulator is protected by a circuit breaker with magneto thermal
release.
The auxiliary circuit is protected by fuses.

Instrumentation
A digital display providing with output voltage and alarm readings is fitted
on the front panel.

15
Electro-mechanical digital voltage stabilisers

Vega
single-phase
0.3-25kVA
Type

regulation
Maximum

Efficiency
variation

Cabinet
voltage

voltage

voltage
current

current

Weight
Output

Output
Rating

Speed
±0.5%
range

range
Input

Input

input
[%] [kVA] [V] [A] [V] [A] [%] [ms/V] Type [kg]

Input voltage variation range ±20%/±15% (the values listed in the table are referred to 230V nominal voltage)
0.7-20 ±20 0.7 184-276 3.8 3 12
230 >96 12 16
1-15 ±15 1 195-265 5 4.3 16
2-20 ±20 2 184-276 11 8.7 12
230 >96 12 24
2.5-15 ±15 2.5 195-265 13 11 16
4-20 ±20 4 184-276 22 17 12
230 >96 12 28
5-15 ±15 5 195-265 26 22 16
5-20 ±20 5 184-276 27 22 12
230 >98 13 41
7-15 ±15 7 195-265 36 30 16
7-20 ±20 7 184-276 38 30 12
230 >98 13 47
10-15 ±15 10 195-265 51 43 16
10-20 ±20 10 184-276 54 43 12
230 >98 13 55
15-15 ±15 15 195-265 77 65 16
15-20 ±20 15 184-276 82 65 12
230 >98 22 125
20-15 ±15 20 195-265 103 87 16
20-20 ±20 20 184-276 109 87 12
230 >98 22 145
25-15 ±15 25 195-265 128 109 16

Input voltage variation range ±30%/±25% (the values listed in the table are referred to 230V nominal voltage)
0.3-30 ±30 0.3 161-300 1.9 1.3 8
230 >96 12 16
0.5-25 ±25 0.5 172-288 2.9 2.2 10
1-30 ±30 1 161-300 6.2 4.3 8
230 >96 12 24
1.5-25 ±25 1.5 172-288 8.7 6.5 10
2-30 ±30 2 161-300 12 8.7 8
230 >96 12 28
3-25 ±25 3 172-288 17 13 10
3-30 ±30 3 161-300 19 13 8
230 >98 13 41
4-25 ±25 4 172-288 23 17 10
4-30 ±30 4 161-300 25 17 8
230 >98 13 47
5-25 ±25 5 172-288 29 22 10
5-30 ±30 5 161-300 31 22 8
230 >98 13 56
7-25 ±25 7 172-288 41 30 10
7-30 ±30 7 161-300 43 30 8
230 >98 22 125
10-25 ±25 10 172-288 58 43 10
10-30 ±30 10 161-300 62 43 8
230 >98 22 145
15-25 ±25 15 172-288 87 65 10

16
Vega
single-phase
0.3-25kVA
Type

regulation
Maximum

Efficiency
variation

Cabinet
voltage

voltage

voltage
current

current

Weight
Output

Output
Rating

Speed
±0.5%
range

range
Input

Input

input
[%] [kVA] [V] [A] [V] [A] [%] [ms/V] Type [kg]

Input voltage variation range +15%/-25% (the values listed in the table are referred to 230V nominal voltage)
0.7-15/25 +15/-25 0.7 172-265 4 230 3 >96 12 12 17
2-15/25 +15/-25 2 172-265 12 230 8.7 >96 12 12 25
4-15/25 +15/-25 4 172-265 23 230 17 >96 12 12 29
5-15/25 +15/-25 5 172-265 29 230 22 >98 12 13 42
7-15/25 +15/-25 7 172-265 41 230 30 >98 12 13 48
10-15/25 +15/-25 10 172-265 58 230 43 >98 12 13 56
15-15/25 +15/-25 15 172-265 87 230 65 >98 12 22 125
20-15/25 +15/-25 20 172-265 116 230 87 >98 12 22 145

Input voltage variation range +15%/-35% (the values listed in the table are referred to 230V nominal voltage)
0.5-15/35 +15/-35 0.5 150-265 3.4 230 2.2 >96 10 12 17
1.5-15/35 +15/-35 1.5 150-265 10 230 6.5 >96 10 12 25
3-15/35 +15/-35 3 150-265 20 230 13 >96 10 12 29
4-15/35 +15/-35 4 150-265 27 230 17 >98 10 13 42
5-15/35 +15/-35 5 150-265 33 230 22 >98 10 13 48
7-15/35 +15/-35 7 150-265 47 230 30 >98 10 13 56
10-15/35 +15/-35 10 150-265 67 230 43 >98 10 22 125
15-15/35 +15/-35 15 150-265 100 230 65 >98 10 22 145

Input voltage variation range +15%/-45% (the values listed in the table are referred to 230V nominal voltage)
0.3-15/45 +15/-45 0.3 126-265 2.4 230 1.3 >96 8 12 17
1-15/45 +15/-45 1 126-265 7.8 230 4.3 >96 8 12 25
2-15/45 +15/-45 2 126-265 16 230 8.7 >96 8 12 29
3-15/45 +15/-45 3 126-265 24 230 13 >98 8 13 42
4-15/45 +15/-45 4 126-265 32 230 17 >98 8 13 48
5-15/45 +15/-45 5 126-265 40 230 22 >98 8 13 56
7-15/45 +15/-45 7 126-265 56 230 30 >98 8 22 125
10-15/45 +15/-45 10 126-265 79 230 43 >98 8 22 145

17
Electro-mechanical digital voltage stabilisers WA
RRANTY

2
YEARS

single-phase
Antares 15-135kVA
Standard features
Selectable output voltage (dip-switch)* 220-230-240V
Output voltage accuracy ±0,5%
Frequency 50Hz ±5% or 60Hz ±5%
Admitted load variation Up to 100%
Cooling Natural ventilation (aided with fans)
Ambient temperature -25/+45°C
Storage temperature -25/+60°C
Max relative humidity 95% (non condensing)
Admitted overload 200% 2 min.
Harmonic distortion None introduced
Colour RAL 7035
Protection degree IP21
Instrumentation Output digital multimetre
Installation Indoor
Overvoltage protection Class II output surge arrestor
* The output voltage can be adjusted by choosing one of the indicated values.
Such choice sets the new nominal value as a reference for all the stabiliser parameters.

Accessories
Interrupting devices
Load protection against over/undervoltage
Manual by-pass line
Input isolating transformer
SPD surge arrestor
EMI/RFI filters
IP54 protection degree for indoor and outdoor installation

Rating in relation to the input variation percentage


±15% ±20% ±25% ±30% +15%/-25% +15%/-35% +15%/-45%
35 25 20 15 25 20 15
45 35 25 20 35 25 20
60 45 35 25 45 35 25
80 60 45 35 60 45 35
100 80 60 45 80 60 45
135 100 80 60 100 80 60

All ORTEA stabilisers are designed and built in compliance with the Low Voltage and Electromagnetic Compatibility European Directives with regard to the
CE marking requirements. ORTEA products are built with suitable quality components and that the manufacturing process is constantly verified in
accordance with the Quality Control Plans which the Company applies in compliance with the ISO 9001:2015 Standards. The commitment towards
environmental issues and safety at work issues is guaranteed by the certification of the Management System according to the ISO14001:2015 and
OHSAS18001:2007 Standards. In order to obtain better performance, the products described in the present document can be altered by the Company at any
date and without prior notice. Technical data and descriptions do not hold therefore any contractual value.

18
Antares
single-phase
15-135kVA
Antares stabilisers are available for different ranges of input voltage fluctuation.
Standard models offer a double input connection so that with the same unit two different input
variations (±1 5%/±20% or ±25%/±30%) can be dealt with.
An automatic circuit breaker is provided on the regulation circuit to protect against overload and short
circuit on the voltage regulator whilst the auxiliary circuit is protected by fuses.
The instrumentation consists of a digital multimetre installed on the cabinet front panel. The alarms
(min/max output voltage, gearmotor lock, internal overheating, regulator overload) are recognizable by
means of LEDs on the control card.
The control logic is based on a digital microprocessor.
All Antares stabilisers are fitted with the same control card, thus simplifying maintenance operations
and spare parts storage.

Wide range
– symmetrical: ±15%, ±20%, ±25%, ±30% (other on request)
– asyimmetrical: +15%/-25%, +15%/-35%, +15%/-45% (other on request)
Output voltage accuracy: ±0.5%.

Technology
Control logic based on digital microprocessor operating with a software
specifically developed for Ortea.

Long life
Ortea system voltage regulator with rollers (without brushes, which are
subject to heavy wear & tear).

Protection
The voltage regulator is protected by a circuit breaker with magneto thermal release.
The auxiliary circuit is protected by fuses.
Overvoltage protection: Class II output surge arrestor.

Instrumentation
The digital measuring instrumentation is installed on the front panel
and consist of an output digital multimetre.

19
Electro-mechanical digital voltage stabilisers

Antares
single-phase
15-135kVA
Type

regulation
Maximum

Efficiency
variation

Cabinet
voltage

voltage

voltage
current

current

Weight
Output

Output
Rating

Speed
±0.5%
range

range
Input

Input

input
[%] [kVA] [V] [A] [V] [A] [%] [ms/V] Type [kg]

Input voltage variation range ±20%/±15% (the values listed in the table are referred to 230V nominal voltage)
25-20 ±20 25 184-276 136 109 12
230 >98 23 180
35-15 ±15 35 195-265 179 152 16
35-20 ±20 35 184-276 190 152 12
230 >98 31 200
45-15 ±15 45 195-265 231 196 16
45-20 ±20 45 184-276 245 196 12
230 >98 40 320
60-15 ±15 60 195-265 308 261 16
60-20 ±20 60 184-276 326 261 12
230 >98 40 390
80-15 ±15 80 195-265 410 348 16
80-20 ±20 80 184-276 435 348 12
230 >98 51 550
100-15 ±15 100 195-265 513 435 16
100-20 ±20 100 184-276 543 435 12
230 >98 51 650
135-15 ±15 135 195-265 692 587 16

Input voltage variation range ±30%/±25% (the values listed in the table are referred to 230V nominal voltage)
15-30 ±30 15 161-300 93 65 8
230 >98 23 180
20-25 ±25 20 172-288 116 87 10
20-30 ±30 20 161-300 124 87 8
230 >98 31 200
25-25 ±25 25 172-288 145 109 10
25-30 ±30 25 161-300 155 109 8
230 >98 40 320
35-25 ±25 35 172-288 203 152 10
35-30 ±30 35 161-300 217 152 8
230 >98 40 390
45-25 ±25 45 172-288 262 196 10
45-30 ±30 45 161-300 280 196 8
230 >98 51 550
60-25 ±25 60 172-288 349 261 10
60-30 ±30 60 161-300 373 261 8
230 >98 51 650
80-25 ±25 80 172-288 465 348 10

20
Antares
single-phase
15-135kVA
Type

regulation
Maximum

Efficiency
variation

Cabinet
voltage

voltage

voltage
current

current

Weight
Output

Output
Rating

Speed
±0.5%
range

range
Input

Input

input
[%] [kVA] [V] [A] [V] [A] [%] [ms/V] Type [kg]

Input voltage variation range +15%/-25% (the values listed in the table are referred to 230V nominal voltage)
25-15/25 +15/-25 25 172-265 145 230 109 >98 14 23 190
35-15/25 +15/-25 35 172-265 203 230 152 >98 14 31 210
45-15/25 +15/-25 45 172-265 262 230 196 >98 14 40 330
60-15/25 +15/-25 60 172-265 349 230 261 >98 14 40 400
80-15/25 +15/-25 80 172-265 465 230 348 >98 14 51 560
100-15/25 +15/-25 100 172-265 581 230 435 >98 14 51 660

Input voltage variation range +15%/-35% (the values listed in the table are referred to 230V nominal voltage)
20-15/35 +15/-35 20 150-265 133 230 87 >98 11 23 200
25-15/35 +15/-35 25 150-265 167 230 109 >98 11 31 220
35-15/35 +15/-35 35 150-265 233 230 152 >98 11 40 340
45-15/35 +15/-35 45 150-265 300 230 196 >98 11 40 410
60-15/35 +15/-35 60 150-265 400 230 261 >98 11 51 570
80-15/35 +15/-35 80 150-265 533 230 348 >98 11 51 670

Input voltage variation range +15%/-45% (the values listed in the table are referred to 230V nominal voltage)
15-15/45 +15/-45 15 126-265 119 230 65 >98 9 23 210
20-15/45 +15/-45 20 126-265 159 230 87 >98 9 31 230
25-15/45 +15/-45 25 126-265 198 230 109 >98 9 40 350
35-15/45 +15/-45 35 126-265 278 230 152 >98 9 40 420
45-15/45 +15/-45 45 126-265 357 230 196 >98 9 51 580
60-15/45 +15/-45 60 126-265 476 230 261 >98 9 51 680

21
Electro-mechanical digital voltage stabilisers WA
RRANTY

2
YEARS

three-phase
Orion 2-135kVA
Standard features
Voltage stabilisation Independent phase control
Selectable output voltage (dip-switch)* 220-230-240V (L-N) / 380-400-415V (L-L)
Output voltage accuracy ±0,5%
Frequency 50Hz ±5% or 60Hz ±5%
Admitted load variation Up to 100%
Admitted load imbalance 100%
Cooling Natural air ventilation up to 45kVA ±15%
Aided with fans from 60kVA ±15%
Ambient temperature -25/+45°C
Storage temperature -25/+60°C
Max relative humidity 95% (non condensing)
Admitted overload 200% 2 min.
Harmonic distortion None introduced
Colour RAL 7035
Protection degree IP21
Instrumentation Output digital multimetre
Installation Indoor
Overvoltage protection Output Class II surge arrestor (over 60kVA ±15%)
* The output voltage can be adjusted by choosing one of the indicated values.
Such choice sets the new nominal value as a reference for all the stabiliser parameters.

Accessories
Interrupting devices
Load protection against over/undervoltage
Manual by-pass line
Input isolating transformer
SPD surge arrestor
EMI/RFI filters
Neutral point reactor
IP54 protection degree for indoor and outdoor installation

All ORTEA stabilisers are designed and built in compliance with the Low Voltage and Electromagnetic Compatibility European Directives with regard to the
CE marking requirements. ORTEA products are built with suitable quality components and that the manufacturing process is constantly verified in
accordance with the Quality Control Plans which the Company applies in compliance with the ISO 9001:2015 Standards. The commitment towards
environmental issues and safety at work issues is guaranteed by the certification of the Management System according to the ISO14001:2015 and
OHSAS18001:2007 Standards. In order to obtain better performance, the products described in the present document can be altered by the Company at any
date and without prior notice. Technical data and descriptions do not hold therefore any contractual value.

22
Orion
three-phase
2-135kVA
Rating in relation to the input variation percentage
±15% ±20% ±25% ±30% +15%/-25% +15%/-35% +15%/-45%
5 4 3 2 4 3 2
10 7 4 3 7 4 3
15 10 7 4 10 7 4
20 15 10 7 15 10 7
30 20 15 10 20 15 10
45 30 20 15 30 20 15
60 45 30 20 45 30 20
80 60 45 30 60 45 30
105 80 60 45 80 60 45
135 105 80 60 105 80 60

Orion stabilisers are available for different ranges of input voltage fluctuation.
Standard models offer a double input connection so that with the same unit two different input
variations (±1 5%/±20% or ±25%/±30%) can be dealt with.
The output voltage regulation is performed independently on each phase (stabilization of each phase-
to-neutral voltage).
Orion stabilisers are used with three-phase loads and single-phase loads with 100% current
imbalance across the phases and asymmetrical mains voltage.
For the correct operation, Orion voltage stabilisers require the neutral wire presence. Operation without
neutral wire connection is achievable by adding a device able to generate it (D/Yn isolating transformer
or neutral point reactor).
An automatic circuit breaker is mounted on the regulation circuit to protect against overload and short
circuit on the voltage regulator, whilst the auxiliary circuit is protected by fuses.
The instrumentation consists of a multi-task digital line analyser. Such instrument is able to provide
with information regarding the voltage stabiliser output parametres, such as phase and linked voltage,
current, power factor, active power, apparent power, reactive power, etc..
The alarms (min/max output voltage, gearmotor lock, internal overheating, regulator overload) are
recognizable by means of LEDs on the control card.
Voltage control and stabilisation, performed on the true RMS value, are managed by the digital
microprocessor.
Each phase of every stabiliser belonging to this range is controlled by the same control board used on
Vega and Antares models, thus simplifying maintenance operations and spare parts storage.
Up to 45kVA, the stabilisers are equipped with wheels for easy handling.

23
Electro-mechanical digital voltage stabilisers

Orion
three-phase
2-135kVA

Wide range
– symmetrical: ±15%, ±20%, ±25%, ±30% (other on request)
– asyimmetrical: +15%/-25%, +15%/-35%, +15%/-45% (other on request)
Output voltage accuracy: ±0.5%.

Technology
Control and stabilisation, performed on the true RMS value, are based on a digital
microprocessor operating with a software specifically developed for Ortea.
Independent regulation on each phase.

Long life
Ortea system voltage regulator with rollers (without brushes, which are
subject to heavy wear & tear).

Protection
The voltage regulator is protected by a circuit breaker with magneto thermal release.
The auxiliary circuit is protected by fuses.
Overvoltage protection: Class II output surge arrestor.

Instrumentation
Multi-task digital analyser mounted on the front panel (linked and phase voltage
current, frequency, power factor, active power, reactive power, apparent power etc.).

24
Orion
three-phase
2-135kVA
Type

regulation
Maximum

Efficiency
variation

Cabinet
voltage

voltage

voltage
current

current

Weight
Output

Output
Rating

Speed
±0.5%
range

range
Input

Input

input
[%] [kVA] [V] [A] [V] [A] [%] [ms/V] Type [kg]

Input voltage variation range ±20%/±15% (the values listed in the table are referred to 400V nominal voltage)
4-20 ±20 4 320-480 7.3 5.8 12
400 >96 22 90
5-15 ±15 5 340-460 8.5 7.2 16
7-20 ±20 7 320-480 13 10 12
400 >96 22 110
10-15 ±15 10 340-460 17 14 16
10-20 ±20 10 320-480 18 14 12
400 >96 22 140
15-15 ±15 15 340-460 25 22 16
15-20 ±20 15 320-480 27 22 12
400 >98 23 155
20-15 ±15 20 340-460 34 29 16
20-20 ±20 20 320-480 36 29 12
400 >98 23 180
30-15 ±15 30 340-460 51 43 16
30-20 ±20 30 320-480 54 43 12
400 >98 23 200
45-15 ±15 45 340-460 76 65 16
45-20 ±20 45 320-480 81 65 12
400 >98 31 310
60-15 ±15 60 340-460 102 87 16
60-20 ±20 60 320-480 108 86 12
400 >98 40 425
80-15 ±15 80 340-460 136 115 16
80-20 ±20 80 320-480 144 115 12
400 >98 51 510
105-15 ±15 105 340-460 178 152 16
105-20 ±20 105 320-480 189 152 12
400 >98 51 580
135-15 ±15 135 340-460 229 195 16

Input voltage variation range ±30%/±25% (the values listed in the table are referred to 400V nominal voltage)
2-30 ±30 2 280-520 4.1 2.9 8
400 >96 22 90
3-25 ±25 3 300-500 5.7 4.3 10
3-30 ±30 3 280-520 6.1 4.3 8
400 >96 22 110
4-25 ±25 4 300-500 7.7 5.8 10
4-30 ±30 4 280-520 8.3 5.8 8
400 >96 22 140
7-25 ±25 7 300-500 13 10 10
7-30 ±30 7 280-520 14 10 8
400 >98 23 155
10-25 ±25 10 300-500 19 14 10
10-30 ±30 10 280-520 21 14 8
400 >98 23 180
15-25 ±25 15 300-500 29 22 10
15-30 ±30 15 280-520 31 22 8
400 >98 23 200
20-25 ±25 20 300-500 38 29 10
20-30 ±30 20 280-520 41 29 8
400 >98 31 310
30-25 ±25 30 300-500 58 43 10
30-30 ±30 30 280-520 62 43 8
400 >98 40 425
45-25 ±25 45 300-500 87 65 10
45-30 ±30 45 280-520 93 65 8
400 >98 51 510
60-25 ±25 60 300-500 115 87 10
60-30 ±30 60 280-520 124 87 8
400 >98 51 580
80-25 ±25 80 300-500 154 115 10

25
26
Orion
three-phase
2-135kVA
Type

regulation
Maximum

Efficiency
variation

Cabinet
voltage

voltage

voltage
current

current

Weight
Output

Output
Rating

Speed
±0.5%
range

range
Input

Input

input
[%] [kVA] [V] [A] [V] [A] [%] [ms/V] Type [kg]

Input voltage variation range +15%/-25% (the values listed in the table are referred to 400V nominal voltage)
4-15/25 +15/-25 4 300-460 7.7 400 5.8 >96 14 22 100
7-15/25 +15/-25 7 300-460 13 400 10 >96 14 22 130
10-15/25 +15/-25 10 300-460 19 400 14 >96 14 22 150
15-15/25 +15/-25 15 300-460 29 400 22 >98 14 23 165
20-15/25 +15/-25 20 300-460 38 400 29 >98 14 23 190
30-15/25 +15/-25 30 300-460 58 400 43 >98 14 23 220
45-15/25 +15/-25 45 300-460 87 400 65 >98 14 40 330
60-15/25 +15/-25 60 300-460 115 400 87 >98 14 40 445
80-15/25 +15/-25 80 300-460 154 400 115 >98 14 51 530
105-15/25 +15/-25 105 300-460 202 400 152 >98 14 51 600

Input voltage variation range +15%/-35% (the values listed in the table are referred to 400V nominal voltage)
3-15/35 +15/-35 3 260-460 6.6 400 4.3 >96 10 22 100
4-15/35 +15/-35 4 260-460 8.9 400 5.8 >96 10 22 130
7-15/35 +15/-35 7 260-460 16 400 10 >96 10 22 150
10-15/35 +15/-35 10 260-460 22 400 14 >98 10 23 165
15-15/35 +15/-35 15 260-460 33 400 22 >98 10 23 190
20-15/35 +15/-35 20 260-460 44 400 29 >98 10 23 220
30-15/35 +15/-35 30 260-460 67 400 43 >98 10 40 330
45-15/35 +15/-35 45 260-460 100 400 65 >98 10 40 445
60-15/35 +15/-35 60 260-460 133 400 87 >98 10 51 530
80-15/35 +15/-35 80 260-460 178 400 115 >98 10 51 600

Input voltage variation range +15%/-45% (the values listed in the table are referred to 400V nominal voltage)
2-15/45 +15/-45 2 220-460 5.3 400 2.9 >96 8 22 100
3-15/45 +15/-45 3 220-460 7.8 400 4.3 >96 8 22 130
4-15/45 +15/-45 4 220-460 10 400 5.8 >96 8 22 150
7-15/45 +15/-45 7 220-460 18 400 10 >98 8 23 165
10-15/45 +15/-45 10 220-460 26 400 14 >98 8 23 190
15-15/45 +15/-45 15 220-460 39 400 22 >98 8 23 220
20-15/45 +15/-45 20 220-460 52 400 29 >98 8 40 330
30-15/45 +15/-45 30 220-460 79 400 43 >98 8 40 445
45-15/45 +15/-45 45 220-460 118 400 65 >98 8 51 530
60-15/45 +15/-45 60 220-460 157 400 87 >98 8 51 600

27
Electro-mechanical digital voltage stabilisers WA
RRANTY

2
YEARS

three-phase
Orion Plus 30-2000kVA
Standard features
Voltage stabilisation Independent phase control
PC selectable output voltage* from 210 to 255V (L-N)
from 360 to 440V (L-L)
Output voltage accuracy ±0,5%
Frequency 50Hz ±5% or 60Hz ±5%
Admitted load variation Up to 100%
Admitted load imbalance 100%
Cooling Natural air ventilation.
From 35°C aided with fans
Ambient temperature -25/+45°C
Storage temperature -25/+60°C
Max relative humidity 95% (non condensing)
Admitted overload 200% 2 min.
Harmonic distortion None introduced
Colour RAL 7035
Protection degree IP21
Instrumentation Input & output digital multimetre
Installation Indoor
Overvoltage protection – Class II output surge arrestor
– Optimal voltage return through supercapacitors
– in case of blackout
* The output voltage can be adjusted by choosing one of the indicated values.
Such choice sets the new nominal value as a reference for all the stabiliser parameters.

Accessories
Interrupting devices
Load protection against over/undervoltage
Manual by-pass line
Total protection kit
Input isolating transformer
Integrated automatic power factor correction system
SPD surge arrestor
EMI/RFI filters
Neutral point reactor
IP54 protection degree for indoor and outdoor installation

All ORTEA stabilisers are designed and built in compliance with the Low Voltage and Electromagnetic Compatibility European Directives with regard to the
CE marking requirements. ORTEA products are built with suitable quality components and that the manufacturing process is constantly verified in
accordance with the Quality Control Plans which the Company applies in compliance with the ISO 9001:2015 Standards. The commitment towards
environmental issues and safety at work issues is guaranteed by the certification of the Management System according to the ISO14001:2015 and
OHSAS18001:2007 Standards. In order to obtain better performance, the products described in the present document can be altered by the Company at any
date and without prior notice. Technical data and descriptions do not hold therefore any contractual value.

28
Orion Plus
three-phase
30-2000kVA
Rating in relation to the input variation percentage
±10% ±15% ±20% ±25% ±30% +15%/-35% +15%/-45%
125 80 60 45 30 45 30
160 105 80 60 45 60 45
200 135 105 80 60 80 60
250 160 135 90 80 90 80
320 200 160 135 105 135 105
400 250 200 160 135 160 135
500 320 250 200 160 200 160
630 400 320 250 200 250 200
800 500 400 320 250 320 250
1000 630 500 400 320 400 320
1250 800 630 500 400 500 400
1600 1000 800 630 500 630 500
2000 1250 1000 800 630 800 630

Orion Plus stabilisers are available for different ranges of input voltage fluctuation. In the ±15%/ ±20%
and ±25%/ ±30% types, the change of input range is obtained through different internal connections.
The Orion Plus voltage stabilisers regulate the output voltage independently on each phase.
Similarly to the Orion stabilisers, they can supply any single-phase, bi-phase and three-phase load
even in case of and up to 100% unbalanced load current and asymmetrical mains distribution.
In this configuration, the presence of the neutral wire is required. The stabiliser can also operate
without neutral wire by adding a device able to generate it (D/zn or D /yn isolating transformer or neutral
point reactor).
The stabilisers are cooled via natural air ventilation, assisted by extracting fans when the cabinet
internal temperature exceeds 35°C).
The instrumentation consists of two multi-task digital line analysers which are able to provide with
information regarding the status of the lines upstream and downstream the voltage stabiliser (phase
and linked voltages, current, power factor, active power, apparent power, reactive power, etc.)
The operating status of the stabiliser can be monitored by means of the LEDs on the front panel
displaying all the information regarding each phase operating mode ('power on'; reaching of voltage
regulation limits; increase/decrease of voltage regulation) and the possible alarms (minimum and
maximum voltage, maximum current: overtemperature; ventilation failure). The alarm indicators are
accompanied by an acoustic alarm.
– Up to 250kVA ±15%, the regulation circuit is protected against overload and short circuit on the
voltage regulator by an automatic circuit breaker.
– From 300kVA ±15%, an electronic voltage regulator protection system activates in case of overload
on the voltage regulator. In such condition, the load supply is not interrupted, but the stabiliser output
voltage is automatically set to the lower between the mains voltage and the pre-set output voltage.
The service continuity is guaranteed, although the voltage is not stabilised. When the overload
condition ceases to exist, the stabiliser switches automatically back to regular functioning.
The auxiliary circuits are protected by fuses.
The control logic, performed on the true RMS value, is based on DSP microprocessors.
The unit parameters and the output voltage reference can be set by using a personal computer, thus
allowing for dealing directly in the field with any problems related to voltage stability.
All Orion Plus stabilisers are provided with Class II SPD surge arrestors.

29
Electro-mechanical digital voltage stabilisers

Orion Plus
three-phase
30-2000kVA

Wide range
– symmetrical: ±10%, ±15%, ±20%, ±25%, ±30% (other on request)
– asyimmetrical: +15%/-35%, +15%/-45% (other on request)
Output voltage accuracy: ±0.5%.

Technology
Control and stabilisation, performed on the true RMS value, are based on a digital microprocessor
operating with a software specifically developed for Ortea.
Parameters and reference voltage can be set via a PC, thus allowing for adjustig the stabiliser
to the actual site conditions.
Independent regulation on each phase.
Long life
Ortea system voltage regulator with rollers (without brushes, which are subject to heavy wear & tear).
Depending on the rating, the voltage regulator could be toroidal or columnar.

Protection
Up to 250kVA ±15%: The voltage regulator is protected by a three-phase automatic circuit breaker.
The auxiliary circuit is protected by fuses.
Overvoltage protection: Class II output surge arrestor.

Protection
From 300kVA ±15%: The stabiliser is provided of an electronic voltage regulator protection
system activates in case of overload on the voltage regulator. In such conditions, the
load supply is not interrupted.
The auxiliary circuit is protected by fuses.
Overvoltage protection: Class II output surge arrestor.
Protection
Output voltage reset to the minimum value in case of blackout by means of supercapacitors
banks in order to ensure the correct shutdown.

Instrumentation
Two multi-task digital analyser mounted on the front panel (linked and phase voltage
current, frequency, power factor, active power, reactive power, apparent power etc.).

Monitoring
The stabiliser operating mode can be easily monitored by means of the LEDs on the front panel,
which provide with information and alarms.

30
Orion Plus
three-phase
30-2000kVA
Type

regulation
Maximum

Efficiency
variation

Cabinet
voltage

voltage

voltage
current

current

Weight
Output

Output
Rating

Speed
±0.5%
range

range
Input

Input

input
[%] [kVA] [V] [A] [V] [A] [%] [ms/V] Type [kg]

Input voltage variation range ±10% (the values listed in the table are referred to 400V nominal voltage)
135-10 ±10 135 360-440 216 400 194 >98 24 51 430
160-10 ±10 160 360-440 257 400 231 >98 24 51 490
200-10 ±10 200 360-440 321 400 289 >98 24 51 580
250-10 ±10 250 360-440 401 400 361 >98 30 42 670
320-10 ±10 320 360-440 513 400 462 >98 30 42 720
400-10 ±10 400 360-440 642 400 577 >98 30 42 800
500-10 ±10 500 360-440 802 400 722 >98 30 55 850
630-10 ±10 630 360-440 1010 400 909 >98 30 55 1100
800-10 ±10 800 360-440 1283 400 1155 >98 30 53 1300
1000-10 ±10 1000 360-440 1604 400 1443 >98 30 62 1530
1250-10 ±10 1250 360-440 2005 400 1804 >98 36 62 2200
1600-10 ±10 1600 360-440 2566 400 2309 >98 36 63 2400
2000-10 ±10 2000 360-440 3208 400 2887 >98 36 64 2650

Input voltage variation range ±20%/±15% (the values listed in the table are referred to 400V nominal voltage)
60-20 ±20 60 320-480 108 87 12
400 >98 51 430
80-15 ±15 80 340-460 136 115 16
80-20 ±20 80 320-480 144 115 12
400 >98 51 490
105-15 ±15 105 340-460 178 152 16
105-20 ±20 105 320-480 189 152 12
400 >98 51 580
135-15 ±15 135 340-460 229 195 16
135-20 ±20 135 320-480 243 195 15
400 >98 42 670
160-15 ±15 160 340-460 272 231 20
160-20 ±20 160 320-480 289 231 15
400 >98 42 720
200-15 ±15 200 340-460 340 289 20
200-20 ±20 200 320-480 361 289 15
400 >98 42 800
250-15 ±15 250 340-460 425 361 20
250-20 ±20 250 320-480 451 361 15
400 >98 55 850
320-15 ±15 320 340-460 543 462 20
320-20 ±20 320 320-480 577 462 15
400 >98 55 1100
400-15 ±15 400 340-460 679 577 20
400-20 ±20 400 320-480 722 577 15
400 >98 53 1300
500-15 ±15 500 340-460 849 722 20
500-20 ±20 500 320-480 902 722 15
400 >98 62 1530
630-15 ±15 630 340-460 1070 909 20
630-20 ±20 630 320-480 1137 909 18
400 >98 62 2200
800-15 ±15 800 340-460 1359 1155 24
800-20 ±20 800 320-480 1443 1155 18
400 >98 63 2400
1000-15 ±15 1000 340-460 1698 1443 24
1000-20 ±20 1000 320-480 1804 1443 18
400 >98 64 2650
1250-15 ±15 1250 340-460 2123 1804 24

31
Electro-mechanical digital voltage stabilisers

Orion Plus
three-phase
30-2000kVA
Type

regulation
Maximum

Efficiency
variation

Cabinet
voltage

voltage

voltage
current

current

Weight
Output

Output
Rating

Speed
±0.5%
range

range
Input

Input

input
[%] [kVA] [V] [A] [V] [A] [%] [ms/V] Type [kg]

Input voltage variation range ±30%/±25% (the values listed in the table are referred to 400V nominal voltage)
30-30 ±30 30 280-520 62 43 8
400 >98 51 430
45-25 ±25 45 300-500 87 65 10
45-30 ±30 45 280-520 93 65 8
400 >98 51 490
60-25 ±25 60 300-500 115 87 10
60-30 ±30 60 280-520 124 87 8
400 >98 51 580
80-25 ±25 80 300-500 154 115 10
80-30 ±30 80 280-520 165 115 10
400 >98 42 670
90-25 ±25 90 300-500 173 130 12
105-30 ±30 105 280-520 217 152 10
400 >98 42 720
135-25 ±25 135 300-500 260 195 12
135-30 ±30 135 280-520 278 195 10
400 >98 42 800
160-25 ±25 160 300-500 308 231 12
160-30 ±30 160 280-520 330 231 10
400 >98 55 850
200-25 ±25 200 300-500 385 289 12
200-30 ±30 200 280-520 412 289 10
400 >98 55 1100
250-25 ±25 250 300-500 481 361 12
250-30 ±30 250 280-520 516 361 10
400 >98 53 1300
320-25 ±25 320 300-500 616 462 12
320-30 ±30 300 280-520 660 462 10
400 >98 62 1530
400-25 ±25 400 300-500 770 577 12
400-30 ±30 400 280-520 825 577 12
400 >98 62 2200
500-25 ±25 500 300-500 962 722 15
500-30 ±30 500 280-520 1031 722 12
400 >98 63 2400
630-25 ±25 630 300-500 1212 909 15
630-30 ±30 630 280-520 1299 909 12
400 >98 64 2650
800-25 ±25 800 300-500 1540 1155 15

32
Orion Plus
three-phase
30-2000kVA
Type

regulation
Maximum

Efficiency
variation

Cabinet
voltage

voltage

voltage
current

current

Weight
Output

Output
Rating

Speed
±0.5%
range

range
Input

Input

input
[%] [kVA] [V] [A] [V] [A] [%] [ms/V] Type [kg]

Input voltage variation range +15%/-35% (the values listed in the table are referred to 400V nominal voltage)
45-15/35 +15/-35 45 260-460 100 400 65 >98 10 51 470
60-15/35 +15/-35 60 260-460 133 400 87 >98 10 51 550
80-15/35 +15/-35 80 260-460 178 400 115 >98 10 51 600
90-15/35 +15/-35 90 260-460 200 400 130 >98 12 68 900
135-15/35 +15/-35 135 260-460 300 400 195 >98 12 68 1000
160-15/35 +15/-35 160 260-460 355 400 231 >98 12 68 1100
200-15/35 +15/-35 200 260-460 444 400 289 >98 12 55 1200
250-15/35 +15/-35 250 260-460 555 400 361 >98 12 52 1450
320-15/35 +15/-35 320 260-460 711 400 462 >98 12 52 1700
400-15/35 +15/-35 400 260-460 888 400 577 >98 12 63 2300
500-15/35 +15/-35 500 260-460 1110 400 722 >98 15 63 3200
630-15/35 +15/-35 630 260-460 1399 400 909 >98 15 64 3400
800-15/35 +15/-35 800 260-460 1777 400 1155 >98 15 70 3850

Input voltage variation range +15%/-45% (the values listed in the table are referred to 400V nominal voltage)
30-15/45 +15/-45 30 220-460 79 400 43 >98 8 51 470
45-15/45 +15/-45 45 220-460 118 400 65 >98 8 51 550
60-15/45 +15/-45 60 220-460 157 400 87 >98 8 51 600
80-15/45 +15/-45 80 220-460 210 400 115 >98 10 68 900
105-15/45 +15/-45 105 220-460 276 400 152 >98 10 68 1000
135-15/45 +15/-45 135 220-460 354 400 195 >98 10 68 1100
160-15/45 +15/-45 160 220-460 420 400 231 >98 10 55 1200
200-15/45 +15/-45 200 220-460 525 400 289 >98 10 52 1450
250-15/45 +15/-45 250 220-460 656 400 361 >98 10 52 1700
320-15/45 +15/-45 300 220-460 840 400 462 >98 10 63 2300
400-15/45 +15/-45 400 220-460 1050 400 577 >98 12 63 3200
500-15/45 +15/-45 500 220-460 1312 400 722 >98 12 64 3400
630-15/45 +15/-45 630 220-460 1653 400 909 >98 12 70 3850

33
Electro-mechanical digital voltage stabilisers WA
RRANTY

3
YEARS

three-phase
Sirius 60-6000kVA
Standard features
Voltage stabilisation Independent phase control
Output voltage selectable via display, PC from 210 to 255V (L-N)
and/or Ethernet* from 360 to 440V (L-L)
Output voltage accuracy ±0,5%
Frequency 50Hz ±5% or 60Hz ±5%
Admitted load variation Up to 100%
Admitted load imbalance 100%
Cooling Natural air ventilation.
Above 35°C aided with fans
Ambient temperature -25/+45°C
Storage temperature -25/+60°C
Max relative humidity 95% (non condensing)
Admitted overload 200% 2 min.
Harmonic distortion None introduced
Colour RAL 7035
Protection degree IP21
User interface 10" touch panel (multilingual)
remotely available via VNC
Installation Indoor
Regulator overload protection Digital control
Communication system Ethernet / USB / MODBUS TCP/IP
Overvoltage protection – Class I input surge arrestor
– Class II output surge arrestor
– Optimal voltage return through supercapacitors
– in case of blackout
* The output voltage can be adjusted by choosing one of the indicated values.
Such choice sets the new nominal value as a reference for all the stabiliser parameters.

Accessories
Interrupting devices
Load protection against over/undervoltage
Manual by-pass line
Total protection kit
Input isolating transformer
Integrated automatic power factor correction system
EMI/RFI filters
Neutral point reactor
IP54 protection degree for indoor and outdoor installation

All ORTEA stabilisers are designed and built in compliance with the Low Voltage and Electromagnetic Compatibility European Directives with regard to the
CE marking requirements. ORTEA products are built with suitable quality components and that the manufacturing process is constantly verified in
accordance with the Quality Control Plans which the Company applies in compliance with the ISO 9001:2015 Standards. The commitment towards
environmental issues and safety at work issues is guaranteed by the certification of the Management System according to the ISO14001:2015 and
OHSAS18001:2007 Standards. In order to obtain better performance, the products described in the present document can be altered by the Company at any
date and without prior notice. Technical data and descriptions do not hold therefore any contractual value.

34
Sirius
three-phase
60-6000kVA
Rating in relation to the input variation percentage
±10% ±15% ±20% ±25% ±30% +15%/-35% +15%/-45%
200 125 100 80 60 80 60
250 160 125 100 80 100 80
320 200 160 125 100 125 100
400 250 200 160 125 160 125
500 320 250 200 160 200 160
630 400 320 250 200 250 200
800 500 400 320 250 320 250
1000 630 500 400 320 400 320
1250 800 630 500 400 500 400
1600 1000 800 630 500 630 500
2000 1250 1000 800 630 800 630
2500 1600 1250 1000 800 1000 800
3200 2000 1600 1250 1000 1250 1000
4000 2500 2000 1600 1250 1600 1250
5000 3200 2500 2000 1600 2000 1600
6000 4000 3200 2500 2000 2500 2000

Sirius stabilisers are available for different ranges of input voltage fluctuation. In the ±15%/ ±20% and
±25%/ ±30% types, the change of input range is obtained through different internal connections (only up
to 2000kVA ±15% and equivalent).
Sirius stabilisers are equipped with columnar voltage regulators which enable the achievement of high
ratings (up to 6000kVA) and a solid and reliable construction, thus meeting the most diverse
industrial applications.
The Sirius voltage stabilisers regulate the output voltage independently on each phase. Similarly to the
other models, they can supply any single-phase, bi-phase and three-phase load even in case of and up
to 100% unbalanced load current and asymmetrical mains distribution.
In any case, the presence of the neutral wire is required. The stabiliser can also operate without neutral
wire by adding a device able to generate it (D/zn or D /yn isolating transformer or neutral point reactor).
The stabilisers are cooled via natural air ventilation, assisted by extracting fans when the cabinet
internal temperature exceeds 35°C.
The user interface consists of a multilingual 10" touch panel (fitted with RS485 port) able to provide with
information regarding the status of the lines upstream and downstream the voltage stabiliser (phase
and linked voltages, current, power factor, active power, apparent power, reactive power, etc.), the
operating status of the stabiliser displaying all the information regarding each phase operating mode
('power on'; reaching of voltage regulation limits; increase/decrease of voltage regulation, etc.) and the
possible alarms (minimum and maximum voltage, maximum current, overtemperature, etc.). The alarm
indicators are accompanied by an acoustic alarm.
The display is remotable using VNC software.
It is also possible to communicate with the stabiliser with the Modbus TCP/IP protocol (standard
communication protocol between electronic industrial equipment) via an Ethernet connection with
RJ45 cable.
The control system is also provided with two USB ports for downloading stored data and uploading new
releases of the control card software.
The Sirius stabiliser is provided with an electronic voltage regulator protection system activates in
case of overload on the voltage regulator. In such condition the load supply is not interrupted, but the
stabiliser output voltage is automatically set to the lower between the mains voltage and the pre-set
output voltage. The service continuity is guaranteed, although the voltage is not stabilised. When the
overload condition ceases to exist, the stabiliser switches automatically back to regular functioning.
The control logic is managed by two DSP microprocessors (one performing the control and the other
one managing the measurements) which obtain the output voltage stabilisation by adjusting its true
RMS value.

35
Electro-mechanical digital voltage stabilisers

Sirius
three-phase
60-6000kVA
The whole system is supervised by a third 'bodyguard' microprocessor that controls the correct
functioning of the other microprocessors.
The unit parameters and reference output voltage value can be set via a PC connection, allowing for
promptly dealing in the field with any issues concerning voltage stability.
The output voltage is reset to the minimum value in case of blackout by means of supercapacitor banks
in order to ensure the correct shutdown.
All Sirius stabilisers are provided with Class I and Class II SPD surge arrestors.

Wide range
– symmetrical: ±10%, ±15%, ±20%, ±25%, ±30% (other on request)
– asyimmetrical: +15%/-35%, +15%/-45% (other on request)
Output voltage accuracy: ±0.5%.

Technology
Control and stabilisation, performed on the true RMS value, are based on two two-way
DSP-microprocessor operating with a software specifically developed for Ortea and under
the supervision provided by a third microprocessor (bodyguard).
Parameters and reference voltage can be set via a PC, thus allowing for solving any problems
related to voltage stability directly in the field.
Independent regulation on each phase.
Long life
Ortea system voltage regulator with rollers (without brushes, which are subject to heavy wear & tear).
Columnar voltage regulator make possible to achieve high ratings (up to 6000kVA) and a solid
and reliable construction

Protection
The stabiliser is provided of an electronic voltage regulator protection system activates in case
of overload on the voltage regulator.
In such conditions, the load supply is not interrupted.
The auxiliary circuit is protected by fuses.

Protection
Overvoltage protection:
– Class I input surge arrestor.
– Class II output surge arrestor.

Protection
Output voltage reset to the minimum value in case of blackout by means of supercapacitors
banks in order to ensure the correct shutdown.

User Interface
Multilingual 10" touch panel fitted with RS485 port (linked and phase voltage current, frequency, power factor,
active power, reactive power, apparent power etc.). The touch panel also displaying all the information
regarding each phase operating mode ('power on'; reaching of voltage regulation limits; increase/decrease
of voltage regulation, etc.) and the possible alarms (minimum and maximum voltage, maximum current,
overtemperature, etc.).
The display is remotable using VNC software.

36
Sirius
three-phase
60-6000kVA
Type

regulation
Maximum

Efficiency
variation

Cabinet
voltage

voltage

voltage
current

current

Weight
Output

Output
Rating

Speed
±0.5%
range

range
Input

Input

input
[%] [kVA] [V] [A] [V] [A] [%] [ms/V] Type [kg]

Input voltage variation range ±10% (the values listed in the table are referred to 400V nominal voltage)
200-10 ±10 200 360-440 321 400 289 >98 30 54 600
250-10 ±10 250 360-440 401 400 361 >98 30 42 670
320-10 ±10 320 360-440 513 400 462 >98 30 42 720
400-10 ±10 400 360-440 642 400 577 >98 30 42 800
500-10 ±10 500 360-440 802 400 722 >98 30 55 850
630-10 ±10 630 360-440 1010 400 909 >98 30 55 1100
800-10 ±10 800 360-440 1283 400 1155 >98 30 53 1400
1000-10 ±10 1000 360-440 1604 400 1443 >98 30 62 1700
1250-10 ±10 1250 360-440 2005 400 1804 >98 36 62 2200
1600-10 ±10 1600 360-440 2566 400 2312 >98 36 63 2400
2000-10 ±10 2000 360-440 3208 400 2887 >98 36 64 2650
2500-10 ±10 2500 360-440 4009 400 3609 >98 36 70 3500
3200-10 ±10 3200 360-440 5132 400 4619 >98 36 70 4100
4000-10 ±10 4000 360-440 6415 400 5774 >98 45 80 5250
5000-10 ±10 5000 360-440 8019 400 7217 >98 45 80 6050
6000-10 ±10 6000 360-440 9623 400 8661 >98 54 90 10000

37
Electro-mechanical digital voltage stabilisers

Sirius
three-phase
60-6000kVA
Type

regulation
Maximum

Efficiency
variation

Cabinet
voltage

voltage

voltage
current

current

Weight
Output

Output
Rating

Speed
±0.5%
range

range
Input

Input

input
[%] [kVA] [V] [A] [V] [A] [%] [ms/V] Type [kg]

Input voltage variation range ±20%/±15% (the values listed in the table are referred to 400V nominal voltage)
100-20 ±20 100 320-480 180 144 15
400 >98 54 600
125-15 ±15 125 340-460 212 180 20
125-20 ±20 125 320-480 226 180 15
400 >98 42 670
160-15 ±15 160 340-460 272 231 20
160-20 ±20 160 320-480 289 231 15
400 >98 42 720
200-15 ±15 200 340-460 340 289 20
200-20 ±20 200 320-480 361 289 15
400 >98 42 800
250-15 ±15 250 340-460 425 361 20
250-20 ±20 250 320-480 451 361 15
400 >98 55 850
320-15 ±15 320 340-460 543 462 20
320-20 ±20 320 320-480 577 462 15
400 >98 55 1100
400-15 ±15 400 340-460 679 577 20
400-20 ±20 400 320-480 722 577 15
400 >98 53 1400
500-15 ±15 500 340-460 849 722 20
500-20 ±20 500 320-480 902 722 15
400 >98 62 1700
630-15 ±15 630 340-460 1070 909 20
630-20 ±20 630 320-480 1137 909 18
400 >98 62 2200
800-15 ±15 800 340-460 1359 1155 24
800-20 ±20 800 320-480 1443 1155 18
400 >98 63 2400
1000-15 ±15 1000 340-460 1698 1443 24
1000-20 ±20 1000 320-480 1804 1443 18
400 >98 64 2650
1250-15 ±15 1250 340-460 2123 1804 24
1250-20 ±20 1250 320-480 2255 1804 18
400 >98 70 3500
1600-15 ±15 1600 340-460 2717 2309 24
1600-20 ±20 1600 320-480 2887 2309 18
400 >98 70 4150
2000-15 ±15 2000 340-460 3396 2887 24
2000-20 ±20 2000 320-480 3609 400 2887 >98 22 80 5250
2500-15 ±15 2500 340-460 4245 400 3609 >98 30 80 5250
2500-20 ±20 2500 320-480 4511 400 3609 >98 22 80 6050
3200-15 ±15 3200 340-460 5434 400 4619 >98 30 80 6050
3200-20 ±20 3200 320-480 5774 400 4619 >98 27 90 10000
4000-15 ±15 4000 340-460 6793 400 5774 >98 36 90 10000

38
Sirius
three-phase
60-6000kVA
Type

regulation
Maximum

Efficiency
variation

Cabinet
voltage

voltage

voltage
current

current

Weight
Output

Output
Rating

Speed
±0.5%
range

range
Input

Input

input
[%] [kVA] [V] [A] [V] [A] [%] [ms/V] Type [kg]

Input voltage variation range ±30%/±25% (the values listed in the table are referred to 400V nominal voltage)
60-30 ±30 60 280-520 124 87 10
400 >98 54 600
80-25 ±25 80 300-500 154 115 12
80-30 ±30 80 280-520 165 115 10
400 >98 42 670
100-25 ±25 100 300-500 192 144 12
100-30 ±30 100 280-520 206 144 10
400 >98 42 720
125-25 ±25 125 300-500 241 180 12
125-30 ±30 125 280-520 258 180 10
400 >98 42 800
160-25 ±25 160 300-500 308 231 12
160-30 ±30 160 280-520 330 231 10
400 >98 55 850
200-25 ±25 200 300-500 385 289 12
200-30 ±30 200 280-520 412 289 10
400 >98 55 1100
250-25 ±25 250 300-500 481 361 12
250-30 ±30 250 280-520 516 361 10
400 >98 53 1400
320-25 ±25 320 300-500 616 462 12
320-30 ±30 320 280-520 660 462 10
400 >98 62 1700
400-25 ±25 400 300-500 770 577 12
400-30 ±30 400 280-520 825 577 12
400 >98 62 2200
500-25 ±25 500 300-500 962 722 15
500-30 ±30 500 280-520 1031 722 12
400 >98 63 2400
630-25 ±25 630 300-500 1212 909 15
630-30 ±30 630 280-520 1299 909 12
400 >98 64 2650
800-25 ±25 800 300-500 1540 1155 15
800-30 ±30 800 280-520 1650 1155 12
400 >98 70 3500
1000-25 ±25 1000 300-500 1925 1443 15
1000-30 ±30 1000 280-520 2062 1443 12
400 >98 70 4150
1250-25 ±25 1250 300-500 2406 1804 15
1250-30 ±30 1250 280-520 2578 400 1804 >98 15 80 5250
1600-25 ±25 1600 300-500 3079 400 2309 >98 18 80 5250
1600-30 ±30 1600 280-520 3299 400 2309 >98 15 80 6050
2000-25 ±25 2000 300-500 3849 400 2887 >98 18 80 6050
2000-30 ±30 2000 280-520 4124 400 2887 >98 18 90 10000
2500-25 ±25 2500 300-500 4811 400 3609 >98 22 90 10000

39
Electro-mechanical digital voltage stabilisers

Sirius
three-phase
60-6000kVA
Type

regulation
Maximum

Efficiency
variation

Cabinet
voltage

voltage

voltage
current

current

Weight
Output

Output
Rating

Speed
±0.5%
range

range
Input

Input

input
[%] [kVA] [V] [A] [V] [A] [%] [ms/V] Type [kg]

Input voltage variation range +15%/-35% (the values listed in the table are referred to 400V nominal voltage)
80-15/35 +15/-35 80 260-460 178 400 115 >98 12 54 720
100-15/35 +15/-35 100 260-460 222 400 144 >98 12 68 800
125-15/35 +15/-35 125 260-460 278 400 180 >98 12 68 920
160-15/35 +15/-35 160 260-460 355 400 231 >98 12 68 1000
200-15/35 +15/-35 200 260-460 444 400 289 >98 12 55 1050
250-15/35 +15/-35 250 260-460 555 400 361 >98 12 52 1500
320-15/35 +15/-35 320 260-460 711 400 462 >98 12 52 1800
400-15/35 +15/-35 400 260-460 888 400 577 >98 12 63 2100
500-15/35 +15/-35 500 260-460 1110 400 722 >98 15 63 2900
630-15/35 +15/-35 630 260-460 1399 400 909 >98 15 64 3050
800-15/35 +15/-35 800 260-460 1777 400 1155 >98 15 70 3450
1000-15/35 +15/-35 1000 260-460 2221 400 1443 >98 15 70 3950
1250-15/35 +15/-35 1250 260-460 2776 400 1804 >98 15 72 4600
1600-15/35 +15/-35 1600 260-460 3553 400 2309 >98 18 82 7000
2000-15/35 +15/-35 2000 260-460 4441 400 2887 >98 18 82 8850
2500-15/35 +15/-35 2500 260-460 5552 400 3609 >98 22 92 12500

Input voltage variation range +15%/-45% (the values listed in the table are referred to 400V nominal voltage)
60-15/45 +15/-45 60 220-460 157 400 87 >98 10 54 800
80-15/45 +15/-45 80 220-460 210 400 115 >98 10 68 900
100-15/45 +15/-45 100 220-460 262 400 144 >98 10 68 1070
125-15/45 +15/-45 125 220-460 328 400 180 >98 10 68 1100
160-15/45 +15/-45 160 220-460 420 400 231 >98 10 55 1200
200-15/45 +15/-45 200 220-460 525 400 289 >98 10 52 1700
250-15/45 +15/-45 250 220-460 656 400 361 >98 10 52 2000
320-15/45 +15/-45 320 220-460 840 400 462 >98 10 63 2300
400-15/45 +15/-45 400 220-460 1050 400 577 >98 12 63 3200
500-15/45 +15/-45 500 220-460 1312 400 722 >98 12 64 3400
630-15/45 +15/-45 630 220-460 1653 400 909 >98 12 70 3850
800-15/45 +15/-45 800 220-460 2100 400 1155 >98 12 70 4400
1000-15/45 +15/-45 1000 220-460 2624 400 1443 >98 12 72 5100
1250-15/45 +15/-45 1250 220-460 3280 400 1804 >98 15 82 8000
1600-15/45 +15/-45 1600 220-460 4199 400 2309 >98 15 82 8900
2000-15/45 +15/-45 2000 220-460 5249 400 2887 >98 18 92 14000

40
41
Electro-mechanical digital voltage stabilisers WA
RRANTY

5
YEARS

three-phase
Sirius Advance 60-4000kVA
Standard features
Voltage stabilisation Independent phase control
Output voltage selectable via display, PC from 210 to 255V (L-N)
and/or Ethernet* from 360 to 440V (L-L)
Output voltage accuracy ±0,5%
Frequency 50 ±5% or 60Hz ±5%
Admitted load variation Up to 100%
Admitted load imbalance 100%
Cooling Natural air ventilation.
Above 35°C aided with fans
Ambient temperature -25/+45°C
Storage temperature -25/+60°C
Max relative humidity 95% (non condensing)
Admitted overload 200% 2 min.
Harmonic distortion None introduced
Colour RAL 7035
Protection degree IP21
User interface – 10" touch panel (multilingual)
– remotely available via VNC
– Reactive power regulator
Installation Indoor
Regulator overload protection Digital control
Communication system Ethernet / USB / MODBUS TCP/IP
Overvoltage protection – Class I input surge arrestor
– Class II output surge arrestor
– Optimal voltage return through supercapacitors
– in case of blackout
Total protection and by-pass kit – Input automatic circuit breaker
– By-pass switch made of an interlocked
– automatic circuit breaker
– Output interlocked motorized automatic circuit
– breaker with protection against overload,
– overvoltage, undervoltage, phase sequence
– error and phase failure
Integrated automatic power factor – Based on high energy density metallised poly-
correction system – propylene three-phase capacitors (Un = 525V)
– Three-phase blocking reactor (tuning frequency
– 180Hz)
* The output voltage can be adjusted by choosing one of the indicated values.
Such choice sets the new nominal value as a reference for all the stabiliser parameters.

All ORTEA stabilisers are designed and built in compliance with the Low Voltage and Electromagnetic Compatibility European Directives with regard to the
CE marking requirements. ORTEA products are built with suitable quality components and that the manufacturing process is constantly verified in
accordance with the Quality Control Plans which the Company applies in compliance with the ISO 9001:2015 Standards. The commitment towards
environmental issues and safety at work issues is guaranteed by the certification of the Management System according to the ISO14001:2015 and
OHSAS18001:2007 Standards. In order to obtain better performance, the products described in the present document can be altered by the Company at any
date and without prior notice. Technical data and descriptions do not hold therefore any contractual value.

42
Sirius Advance
three-phase
60-4000kVA
Accessories
Input isolating transformer
EMI/RFI filters
Neutral point reactor
IP54 protection degree for indoor and outdoor installation

Rating in relation to the input variation percentage


±15% ±20% ±25% ±30%
125 100 80 60
160 125 100 80
200 160 125 100
250 200 160 125
320 250 200 160
400 320 250 200
500 400 320 250
630 500 400 320
800 630 500 400
1000 800 630 500
1250 1000 800 630
1600 1250 1000 800
2000 1600 1250 1000
2500 2000 1600 1250
3200 2500 2000 1600
4000 3200 2500 2000

Sirius Advance voltage stabilisers derive from the SIRIUS type, of which they maintain the main
technical characteristics.
The standard integration of some functions and accessories usually offered as optional, complete and
enrich the equipment.
The additional features are:
– Input automatic circuit breaker;
– Bypass switch via an interlocked automatic circuit breaker;
– Output interlocked motorized automatic circuit breaker;
– Integrated automatic power factor correction system.
The input automatic circuit breaker (QF1) ensures protection against failure and/or short-circuits
inside the unit.
The bypass automatic circuit breaker (QF2) protects the line supplying the load against overload and
shortcircuits in bypass condition.
The output motorized automatic circuit breaker (QF3), interlocked with the bypass switch, protects
against overload, short-circuit, overvoltage, undervoltage, phase sequence error and phase failure.
The integrated automatic Power Factor Correction system maintains the power factor value (cos φ) to
a high level ensuring the known advantages for the users but also affecting the sizing of the stabiliser.
The PFC system exploits high energy density metallised polypropylene three-phase capacitors
(Un=525V) exclusively thus guaranteeing robustness and reliability. The addition of blocking reactors
(detuned filters) eliminates undesired harmonics and protects the capacitors.
The reactive power controller is mounted on the external control synoptic panel.

43
Electro-mechanical digital voltage stabilisers

Sirius Advance
three-phase
60-4000kVA

Wide range
– ±15%, ±20%, ±25%, ±30% (other on request)
Output voltage accuracy: ±0.5%.

Technology
Control and stabilisation, performed on the true RMS value, are based on two two-way
DSP-microprocessor operating with a software specifically developed for Ortea and under
the supervision provided by a third microprocessor (bodyguard).
Parameters and reference voltage can be set via a PC, thus allowing for solving any problems
related to voltage stability directly in the field.
Independent regulation on each phase.

Long life
Ortea system voltage regulator with rollers (without brushes, which are subject to heavy wear & tear).
Columnar voltage regulator make possible to achieve high ratings (up to 6000kVA) and a solid
and reliable construction
TY«WAR
AN R
T Y «W A R R

AN

5
Long life
Extended warranty: 5 years.
T Y «W A R
AN

YEARS
R

R AN
Y W AR

Protection
The stabiliser is provided of an electronic voltage regulator protection system activates in case
of overload on the voltage regulator.
In such conditions, the load supply is not interrupted.
The auxiliary circuit is protected by fuses.

Protection
Overvoltage protection:
– Class I input surge arrestor.
– Class II output surge arrestor.
OUTPUT
PFC
INPUT

QF2

DVS
QF1 QF3

AUTOMATIC AUTOMATIC
CIRCUIT BREAKER CIRCUIT BREAKER

44
Sirius Advance
three-phase
60-4000kVA

Protection
Output voltage reset to the minimum value in case of blackout by means of supercapacitors
banks in order to ensure the correct shutdown.

Protection
Total protection by-pass kit:
– Input automatic circuit breaker
– By-pass automatic circuit breaker
– Output motorized automatic circuit breaker

User Interface
Multilingual 10" touch panel fitted with RS485 port (linked and phase voltage current, frequency, power factor,
active power, reactive power, apparent power etc.). The touch panel also displaying all the information
regarding each phase operating mode ('power on'; reaching of voltage regulation limits; increase/decrease
of voltage regulation, etc.) and the possible alarms (minimum and maximum voltage, maximum current,
overtemperature, etc.). The display is remotable using VNC software.
Power Factor Correction
The PFC system exploits high energy density metallized polypropylene three-phase capacitors
(Un = 525V) exclusively thus guaranteeing robustness and reliability.
The addition of blocking reactors (detuned filters) eliminates undesired harmonics and
protects the capacitors.

Power Factor Correction


The reactive power regulator RPC are designed to provide the desired power factor while
minimizing the wearing on the banks of capacitors, accurate and reliable in measuring
and control functions are simple and intuitive in installation and construction.

45
Electro-mechanical digital voltage stabilisers

Sirius Advance
three-phase
60-4000kVA
Type

regulation
Maximum

Efficiency
variation

Cabinet
voltage

voltage

voltage
current

current

Weight
Output

Output
Rating

Speed
±0.5%
range

range
Input

Input

input
[%] [kVA] [V] [A] [V] [A] [%] [ms/V] Type [kg]

Input voltage variation range ±20%/±15% (the values listed in the table are referred to 400V nominal voltage)
100-20 ±20 100 320-480 180 144 15
400 >98 47 830
125-15 ±15 125 340-460 212 180 20
125-20 ±20 125 320-480 226 180 15
400 >98 47 900
160-15 ±15 160 340-460 272 231 20
160-20 ±20 160 320-480 289 231 15
400 >98 48 970
200-15 ±15 200 340-460 340 289 20
200-20 ±20 200 320-480 361 289 15
400 >98 48 1070
250-15 ±15 250 340-460 425 361 20
250-20 ±20 250 320-480 451 361 15
400 >98 48 1250
320-15 ±15 320 340-460 543 462 20
320-20 ±20 320 320-480 577 462 15
400 >98 50 1500
400-15 ±15 400 340-460 679 577 20
400-20 ±20 400 320-480 722 577 15
400 >98 57 1880
500-15 ±15 500 340-460 849 722 20
500-20 ±20 500 320-480 902 722 15
400 >98 64 2200
630-15 ±15 630 340-460 1070 909 20
630-20 ±20 630 320-480 1137 909 18
400 >98 64 2720
800-15 ±15 800 340-460 1359 1155 24
800-20 ±20 800 320-480 1443 1155 18
400 >98 72 2950
1000-15 ±15 1000 340-460 1698 1443 24
1000-20 ±20 1000 320-480 1804 1443 18
400 >98 73 4240
1250-15 ±15 1250 340-460 2123 1804 24
1250-20 ±20 1250 320-480 2255 1804 18
400 >98 74 5000
1600-15 ±15 1600 340-460 2717 2309 24
1600-20 ±20 1600 320-480 2887 2309 18
400 >98 75 5800
2000-15 ±15 2000 340-460 3396 2887 24
2000-20 ±20 2000 320-480 3609 400 2887 >98 22 85 7100
2500-15 ±15 2500 340-460 4245 400 3609 >98 30 88 7100
2500-20 ±20 2500 320-480 4511 400 3609 >98 22 88 8350
3200-15 ±15 3200 340-460 5434 400 4619 >98 30 89 8350
3200-20 ±20 3200 320-480 5774 400 4619 >98 27 95 11800
4000-15 ±15 4000 340-460 6793 400 5774 >98 36 95 11800

46
Sirius Advance
three-phase
60-4000kVA
Type

regulation
Maximum

Efficiency
variation

Cabinet
voltage

voltage

voltage
current

current

Weight
Output

Output
Rating

Speed
±0.5%
range

range
Input

Input

input
[%] [kVA] [V] [A] [V] [A] [%] [ms/V] Type [kg]

Input voltage variation range ±30%/±25% (the values listed in the table are referred to 400V nominal voltage)
60-30 ±30 60 280-520 124 87 10
400 >98 47 830
80-25 ±25 80 300-500 154 115 12
80-30 ±30 80 280-520 165 115 10
400 >98 47 900
100-25 ±25 100 300-500 192 144 12
100-30 ±30 100 280-520 206 144 10
400 >98 48 970
125-25 ±25 125 300-500 241 180 12
125-30 ±30 125 280-520 258 180 10
400 >98 48 1070
160-25 ±25 160 300-500 308 231 12
160-30 ±30 160 280-520 330 231 10
400 >98 48 1250
200-25 ±25 200 300-500 385 289 12
200-30 ±30 200 280-520 412 289 10
400 >98 50 1500
250-25 ±25 250 300-500 481 361 12
250-30 ±30 250 280-520 516 361 10
400 >98 57 1880
320-25 ±25 320 300-500 616 462 12
320-30 ±30 320 280-520 660 462 10
400 >98 64 2200
400-25 ±25 400 300-500 770 577 12
400-30 ±30 400 280-520 825 577 12
400 >98 64 2720
500-25 ±25 500 300-500 962 722 15
500-30 ±30 500 280-520 1031 722 12
400 >98 72 2950
630-25 ±25 630 300-500 1212 909 15
630-30 ±30 630 280-520 1299 909 12
400 >98 73 4240
800-25 ±25 800 300-500 1540 1155 15
800-30 ±30 800 280-520 1650 1155 12
400 >98 74 5000
1000-25 ±25 1000 300-500 1925 1443 15
1000-30 ±30 1000 280-520 2062 1443 12
400 >98 74 5800
1250-25 ±25 1250 300-500 2406 1804 15
1250-30 ±30 1250 280-520 2578 400 1804 >98 15 84 7100
1600-25 ±25 1600 300-500 3079 400 2309 >98 18 84 7100
1600-30 ±30 1600 280-520 3299 400 2309 >98 15 84 8350
2000-25 ±25 2000 300-500 3849 400 2887 >98 18 85 8350
2000-30 ±30 2000 280-520 4124 400 2887 >98 18 95 11800
2500-25 ±25 2500 300-500 4811 400 3609 >98 22 95 11800

47
48
49
Power Quality Optimisers WA
RRANTY

2
YEARS

three-phase
R

10-6000A
power quality
Standard features
Voltage stabilisation Independent phase control
Selectable output voltage* 380-400-415V
Output voltage accuracy ±0,5%
Frequency 50Hz ±5% or 60Hz ±5%
Admitted load variation Up to 100%
Admitted load imbalance 100%
Cooling Natural air ventilation.
From 35°C aided with fans
Ambient temperature -25/+45°C
Storage temperature -25/+60°C
Max relative humidity 95% (non condensing)
Admitted overload 200% 2 min.
Harmonic distortion None introduced
Colour RAL 7035
Protection degree IP21
Instrumentation From 10A to 2500A digital multimetre
from 3000A 10" touch panel (multilingual)
Installation Indoor
Overvoltage protection – Class I input surge arrestors**
– (standard from 3000A)
– Class II output surge arrestor**
– (standard from 90A)
– Optimal voltage return through supercapacitors
– in case of blackout (from 160A)
* The output voltage can be adjusted by choosing one of the indicated values.
Such choice sets the new nominal value as a reference for all the stabiliser parameters.
** Optional.

Accessories
Interrupting devices
Load protection against over/undervoltage
Manual by-pass line
Total protection kit
Input isolating transformer
Integrated automatic power factor correction system
SPD surge arrestor
EMI/RFI filters
Neutral point reactor
IP54 protection degree for indoor and outdoor installation

All ORTEA stabilisers are designed and built in compliance with the Low Voltage and Electromagnetic Compatibility European Directives with regard to the
CE marking requirements. ORTEA products are built with suitable quality components and that the manufacturing process is constantly verified in
accordance with the Quality Control Plans which the Company applies in compliance with the ISO 9001:2015 Standards. The commitment towards
environmental issues and safety at work issues is guaranteed by the certification of the Management System according to the ISO14001:2015 and
OHSAS18001:2007 Standards. In order to obtain better performance, the products described in the present document can be altered by the Company at any
date and without prior notice. Technical data and descriptions do not hold therefore any contractual value.

50
R

power quality
three-phase
10-6000A
OPTInet has been specifically designed to meet the ever increasing power quality issues that can be
easily found in a wide range of industrial applications.
OPTInet combines the established and consolidated characteristics proper of ORTEA voltage
stabilisers with features that enable the achievement of energy saving and power quality improvement.
One of the factors that most affect energy saving is given by the fact that electrical appliances are
usually designed to operate with an input voltage included in range rather than just one nominal voltage.
Nevertheless, supplying a device a voltage higher than the rated one implies higher consumption and
decrease of the expected life.
For example, supplying resistive loads 240V instead of 230V implies approximately 10% increase in the
power consumption
This situation can be found worldwide due to the fact that several distribution systems are rated for a
voltage higher than 400V (United Kingdom, Australia, parts of India, and so on): OPTInet provide with a
practical an efficient answer to such issue.
Furthermore, higher supplying voltage might induce problems in magnetic components (possibility of
magnetic core saturation).
Other factors such as proximity to power plants or distribution stations and voltage supplied at high
level to cover the far end of distribution lines might affect performance of the supplied loads and energy
bills.
In order to optimise energy consumption, the first step is a load survey performed by a qualified
technician aiming at assessing the existing situation, deciding what steps need to be taken and
estimating the potential energy savings. The survey is made necessary by the fact that not all loads are
voltage-sensitive.
To sum up, the main parametres that allow for the estimation of the energy saving are:
– Mains voltage different form the load nominal one: the higher the difference, the better the energy
saving.
– Level of load sensitivity to voltage variations.
An accurate analysis shall allow for the best solution in terms of design and rating. In some cases, it
could be more sensible and economical to install an optimiser only for specifi types of loads.
OPTInet is specifically designed to allow the adjustment of the voltage received from the mains and
bring it back to the value for which the load has been built.
OPTInet optimises the load performance, thus obtaining lower consumption, energy saving, cost
reduction and longer life expectancy.

Type of load sensitivity to the voltage variation


Consumed power is in this case directly proportional to the square of the supply voltage
• Incandescent, fluorescent
and discharge lamps
and the load can be defined as voltage dependant.
Using an optimiser can extend the expected life of the load by preventing the supplying
voltage from being higher than the nominal one.

• LED lamps No advantage with these lamps due to the fact that they are supllied a constant voltage.

• Asynchronous motor
Low rating motors (typically under 20/25kW), widely spread at a level both domestic and
industrial, are considered as voltage dependant.

• Inverter driven
asynchronous motors
If the motor is driven by an inverter (speed electronic control) then it becomes voltage
independent.
Usually, voltage dependant loads (low rating motors and heating systems) are mixed with
voltage independent loads (electronic devices). Only a careful investigation can establish
• Production lines the energy savings entity.
A typical application is provided by the refrigerating banks used in supermarkets, made of
combination of small motors directly fed by electronic units.

• Electronic devices
Small equipment such as computers, office machines and telecom systems are generally
fed via power supplies, which are insensitive to voltage variation.
· a little sensitive to voltage variation / · sensitive to voltage variation

51
Power Quality Optimisers

power quality
three-phase
10-6000A

Energy saving
Load voltage optimization ending in performance improvement, increase of the equipment life
expectancy and overall cost reduction.

Power Quality
Continuous voltage monitoring and regulation to a stable value aimed at providing for the optimum
supply protected from potential electromagnetic and radio-frequency noise.

Long life
Ortea system voltage regulator with rollers (without brushes, which are subject to heavy wear & tear).
Columnar voltage regulator make possible to achieve high ratings (up to 6000kVA) and a solid
and reliable construction

Technology
Control and stabilisation, performed on the true RMS value, are based on two two-way DSP-microprocessor
operating with a software specifically developed for Ortea and under the supervision provided by a third
microprocessor (bodyguard). Parameters and reference voltage can be set via a PC, thus allowing for
solving any problems related to voltage stability directly in the field.
Independent regulation on each phase.

52
R

power quality
three-phase
10-6000A
Type

Adjustable
Efficiency
Nominal

Cabinet
voltage
current

Weight
Rating

Speed
range
Input
[A] [kVA] [V] [%] [ms/V] Type [kg]

Input voltage variation range -0%/+15% (the values listed in the table are referred to 415V nominal voltage)
OPTInet 10 10 7 400-460 >97 16 22 90
OPTInet 20 20 15 400-460 >97 16 22 100
OPTInet 30 30 22 400-460 >97 16 22 110
OPTInet 40 40 30 400-460 >97 16 23 155
OPTInet 60 60 45 400-460 >97 16 23 180
OPTInet 90 90 65 400-460 >97 16 23 200
OPTInet 125 125 90 400-460 >97 16 31 320
OPTInet 160 160 115 400-460 >98 18 54 430
OPTInet 200 200 145 400-460 >98 18 54 490
OPTInet 260 260 185 400-460 >98 18 54 580
OPTInet 300 300 215 400-460 >98 18 55 710
OPTInet 350 350 250 400-460 >98 18 55 760
OPTInet 400 400 290 400-460 >98 18 55 850
OPTInet 450 450 325 400-460 >98 18 55 950
OPTInet 500 500 360 400-460 >98 18 55 1000
OPTInet 600 600 430 400-460 >98 18 55 1100
OPTInet 700 700 500 400-460 >98 18 55 1200
OPTInet 800 800 575 400-460 >98 18 55 1300
OPTInet 1000 1000 720 400-460 >98 18 55 1400
OPTInet 1250 1250 900 400-460 >98 18 67 1600
OPTInet 1600 1600 1150 400-460 >98 18 62 2000
OPTInet 2000 2000 1450 400-460 >98 18 63 2200
OPTInet 2500 2500 1800 400-460 >98 18 64 2400
OPTInet 3000 3000 2200 400-460 >98 24 70 4000
OPTInet 4000 4000 2900 400-460 >98 24 70 4300
OPTInet 5000 5000 3600 400-460 >98 30 80 6000
OPTInet 6000 6000 4300 400-460 >98 30 80 7300

53
54
Static digital
voltage stabilisers

55
Static digital voltage stabilisers

Design criteria
A voltage stabiliser is a power device destined to be positioned between the mains and the User. The
purpose is to ensure that the User is fed a voltage subject to a variation much lower (±0.5% with regards
to the nominal value) that the one guaranteed by the distributing system.
The static stabiliser is used when the correction speed represents the critical issue (for example,
computers, laboratory equipment, measuring benches and medical instrumentation).
The stabilisation is performed on the «true rms» voltage. The stabiliser is not affected by the load
power factor (cos φ) and can operate with a load percentage varying between 0% and 100% on each
phase.
Basically, a static voltage stabiliser is made of a buck/boost transformer, a conversion units and an
electronic control (with IGBT static switches).
The operating principle is similar to the one described for the electro-mechanical stabilisers. The
difference lies in the fact that the voltage compensation on the buck/boost primary winding is
performed by an electronic board through IGBT static switches instead of the autotransformer with
variable transformer ratio.
The control circuit compares the output voltage value to the adjusted one. When the percentage
variation is too high, the control drives the double conversion regulators. By doing so setting and
supplied the voltage to the buck/boost transformer primary winding. Being the secondary voltage of the
buck/boost transformer in phase or in opposition to the supply, the voltage drawn from the regulator is
added or subtracted to the mains voltage, thus compensating its variations with response time in
milliseconds.
The voltage stabiliser can operate with input and output voltage different (single-phase 220V/240V -
three-phase 380V/415V) from the rated voltage (single-phase 230V - three-phase 400V). Such setting
can be performed at the factory or at the Customer's premises according to the instructions given in the
handbook.
The stabilisers are designed and built in compliance with the European Directives concerning CE
marking (Low Voltage and Electromagnetic Compatibility Directives).

Working principle of a static digital voltage stabiliser GEMINI/AQUARIUS

INPUT BUCK/BOOST TRANSFORMER OUTPUT

DSP CONTROL

Working principle of a static digital voltage stabiliser IVC ODYSSEY

INPUT BUCK/BOOST TRANSFORMER OUTPUT


PRECHARGE

STATIC
SWITCH

DSP CONTROL

56
Gemini Single-phase 4-40kVA
Aquarius Three-phase 10-120kVA
Odyssey Three-phase 80-4000kVA

Main components
1. Buck/boost transformer
Often referred to as 'booster' transformer, it is a standard dry-type transformer with the secondary
winding connected in series to the mains and the primary winding supplied by the conversion regulator.

2. Conversion unit
AC/DC rectifier: it converts the phase to neutral voltage of the AC mains into DC voltage by means of a fully-
controlled IGBT bridge. The rectifier is sized in order to supply the inverter at full load.
DC/AC inverter: it converts the DC voltage coming from the rectifier into AC voltage, stabilised in amplitude.
The inverter uses the same IGBT technology as the rectifier.

3. Electronic control
IGBT microcontroller-based electronic control boards running the system in terms of regulation and
alarm management. They compare the output voltage value to the set one: if a difference is detected,
they generate the compensation necessary to bring back the output voltage to the nominal value
(provided that said difference falls in the working range).

57
Static digital voltage stabilisers WA
RRANTY

2
YEARS

single-phase
Gemini / Gemini Plus 4-40kVA
Standard features Gemini Gemini Plus
Voltage regulation IGBT control
Selectable output voltage* 220-230-240V
Output voltage accuracy ±1%
Frequency 50-60Hz ±5%
Admitted load variation Up to 100%
Cooling Forced ventilation
Ambient temperature -25/+45°C
Storage temperature -25/+60°C
Max relative humidity 95%
Admitted overload 150% 2 sec.
Harmonic distortion None introduced
Colour RAL 9005
Protection degree IP21
Instrumentation Output digital voltmetre
Installation Indoor
Overvoltage protection Output class II surge arrestor
Protection – EMI/RFI filters – EMI/RFI filters
– Automatic by-pass protection – Input automatic circuit breaker
– Automatic by-pass protection
– Manual maintenance by-pass
* The output voltage can be adjusted by choosing one of the indicated values.
Such choice sets the new nominal value as a reference for all the stabiliser parameters.

Rating in relation to the input variation percentage


±15% ±20% ±25% ±30%
10 7 5 4
15 10 7 5
20 15 10 7
30 20 15 10
40 30 20 15

Accessories
Interrupting devices
Load protection against over/undervoltage
Input isolating transformer
IP54 protection degree for indoor and outdoor installation

All ORTEA stabilisers are designed and built in compliance with the Low Voltage and Electromagnetic Compatibility European Directives with regard to the
CE marking requirements. ORTEA products are built with suitable quality components and that the manufacturing process is constantly verified in
accordance with the Quality Control Plans which the Company applies in compliance with the ISO 9001:2015 Standards. The commitment towards
environmental issues and safety at work issues is guaranteed by the certification of the Management System according to the ISO14001:2015 and
OHSAS18001:2007 Standards. In order to obtain better performance, the products described in the present document can be altered by the Company at any
date and without prior notice. Technical data and descriptions do not hold therefore any contractual value.

58
Gemini / Gemini Plus
single-phase
4-40kVA
Type

Correction
Maximum

Efficiency
variation

Cabinet
voltage

voltage

voltage
current

current

Weight
Output

Output
Rating
range

range
Input

Input

input

time
±1%
[%] [kVA] [V] [A] [V] [A] [%] Type [kg]

Gemini - Input voltage variation range ±20%/±15% (the values listed in the table are referred to 230V nominal voltage)
ES7-20 ±20 7 184-276 38 30
230 >98 half-cycle 13 30
ES10-15 ±15 10 195-265 51 43
ES10-20 ±20 10 184-276 54 43
230 >98 half-cycle 13 35
ES15-15 ±15 15 195-265 76 65
ES15-20 ±20 15 184-276 81 65
230 >98 half-cycle 22 50
ES20-15 ±15 20 195-265 102 87
ES20-20 ±20 20 184-276 109 87
230 >98 half-cycle 23 110
ES30-15 ±15 30 195-265 153 130
ES30-20 ±20 30 184-276 163 130
230 >98 half-cycle 23 125
ES40-15 ±15 40 195-265 205 174

Gemini - Input voltage variation range ±30%/±25% (the values listed in the table are referred to 230V nominal voltage)
ES4-30 ±30 4 161-300 25 17
230 >98 half-cycle 13 30
ES5-25 ±25 5 172-288 29 22
ES5-30 ±30 5 161-300 31 22
230 >98 half-cycle 13 35
ES7-25 ±25 7 172-288 40 30
ES7-30 ±30 7 161-300 44 30
230 >98 half-cycle 22 50
ES10-25 ±25 10 172-288 57 43
ES10-30 ±30 10 161-300 62 43
230 >98 half-cycle 23 110
ES15-25 ±25 15 172-288 87 65
ES15-30 ±30 15 161-300 93 65
230 >98 half-cycle 23 125
ES20-25 ±25 20 172-288 116 87

Gemini Plus - Input voltage variation range ±20%/±15% (the values listed in the table are referred to 230V nominal voltage)
ESP7-20 ±20 7 184-276 38 30
230 >98 half-cycle 13 32
ESP10-15 ±15 10 195-265 51 43
ESP10-20 ±20 10 184-276 54 43
230 >98 half-cycle 13 40
ESP15-15 ±15 15 195-265 76 65
ESP15-20 ±20 15 184-276 81 65
230 >98 half-cycle 22 57
ESP20-15 ±15 20 195-265 102 87
ESP20-20 ±20 20 184-276 109 87
230 >98 half-cycle 23 120
ESP30-15 ±15 30 195-265 153 130
ESP30-20 ±20 30 184-276 163 130
230 >98 half-cycle 23 135
ESP40-15 ±15 40 195-265 205 174

Gemini Plus - Input voltage variation range ±30%/±25% (the values listed in the table are referred to 230V nominal voltage)
ESP4-30 ±30 4 161-300 25 17
230 >98 half-cycle 13 32
ESP5-25 ±25 5 172-288 29 22
ESP5-30 ±30 5 161-300 31 22
230 >98 half-cycle 13 40
ESP7-25 ±25 7 172-288 40 30
ESP7-30 ±30 7 161-300 44 30
230 >98 half-cycle 22 57
ESP10-25 ±25 10 172-288 57 43
ESP10-30 ±30 10 161-300 62 43
230 >98 half-cycle 23 120
ESP15-25 ±25 15 172-288 87 65
ESP15-30 ±30 15 161-300 93 65
230 >98 half-cycle 23 135
ESP20-25 ±25 20 172-288 116 87

59
Static digital voltage stabilisers WA
RRANTY

2
YEARS

three-phase
Aquarius / Aquarius Plus 10-120kVA
Standard features Aquarius Aquarius Plus
Voltage regulation IGBT control
Voltage stabilisation Independent phase control
Selectable output voltage* 220-230-240V (L-N) / 380-400-415V (L-L)
Output voltage accuracy ±1%
Frequency 50-60Hz ±5%
Admitted load variation Up to 100%
Cooling Forced ventilation
Ambient temperature -25/+45°C
Storage temperature -25/+60°C
Max relative humidity 95%
Admitted overload 150% 2 sec.
Harmonic distortion None introduced
Colour RAL 9005
Protection degree IP21
Instrumentation Output digital multimetre
Installation Indoor
Overvoltage protection Output class II surge arrestor
Protection – EMI/RFI filters – EMI/RFI filters
– Automatic by-pass protection – Input automatic circuit breaker
– Automatic by-pass protection
– Manual maintenance by-pass
* The output voltage can be adjusted by choosing one of the indicated values.
Such choice sets the new nominal value as a reference for all the stabiliser parameters.

Rating in relation to the input variation percentage


±15% ±20% ±25% ±30%
30 20 15 10
45 30 20 15
60 45 30 20
90 60 45 30
120 90 60 45

Accessories
Interrupting devices
Load protection against over/undervoltage
Input isolating transformer
Integrated automatic power factor correction system
Neutral point reactor
IP54 protection degree for indoor and outdoor installation

All ORTEA stabilisers are designed and built in compliance with the Low Voltage and Electromagnetic Compatibility European Directives with regard to the
CE marking requirements. ORTEA products are built with suitable quality components and that the manufacturing process is constantly verified in
accordance with the Quality Control Plans which the Company applies in compliance with the ISO 9001:2015 Standards. The commitment towards
environmental issues and safety at work issues is guaranteed by the certification of the Management System according to the ISO14001:2015 and
OHSAS18001:2007 Standards. In order to obtain better performance, the products described in the present document can be altered by the Company at any
date and without prior notice. Technical data and descriptions do not hold therefore any contractual value.

60
Aquarius / Aquarius Plus
three-phase
10-120kVA
Type

Correction
Maximum

Efficiency
variation

Cabinet
voltage

voltage

voltage
current

current

Weight
Output

Output
Rating
range

range
Input

Input

input

time
±1%
[%] [kVA] [V] [A] [V] [A] [%] Type [kg]

Aquarius - Input voltage variation range ±20%/±15% (the values listed in the table are referred to 400V nominal voltage)
ET20-20 ±20 20 320-480 36 29
400 >98 half-cycle 23 120
ET30-15 ±15 30 340-460 51 43
ET30-20 ±20 30 320-480 54 43
400 >98 half-cycle 23 160
ET45-15 ±15 45 340-460 76 65
ET45-20 ±20 45 320-480 81 65
400 >98 half-cycle 31 200
ET60-15 ±15 60 340-460 102 87
ET60-20 ±20 60 320-480 109 87
400 >98 half-cycle 35 370
ET90-15 ±15 90 340-460 153 130
ET90-20 ±20 90 320-480 162 130
400 >98 half-cycle 35 390
ET120-15 ±15 120 340-460 204 173

Aquarius - Input voltage variation range ±30%/±25% (the values listed in the table are referred to 400V nominal voltage)
ET10-30 ±30 10 280-520 20 14
400 >98 half-cycle 23 120
ET15-25 ±25 15 300-500 29 22
ET15-30 ±30 15 280-520 31 22
400 >98 half-cycle 23 160
ET20-25 ±25 20 300-500 39 29
ET20-30 ±30 20 280-520 41 29
400 >98 half-cycle 31 200
ET30-25 ±25 30 300-500 57 43
ET30-30 ±30 30 280-520 61 43
400 >98 half-cycle 35 370
ET45-25 ±25 45 300-500 86 65
ET45-30 ±30 45 280-520 93 65
400 >98 half-cycle 35 390
ET60-25 ±25 60 300-500 116 87

Aquarius Plus - Input voltage variation range ±20%/±15% (the values listed in the table are referred to 400V nominal voltage)
ETP20-20 ±20 20 320-480 36 29
400 >98 half-cycle 23 130
ETP30-15 ±15 30 340-460 51 43
ETP30-20 ±20 30 320-480 54 43
400 >98 half-cycle 23 170
ETP45-15 ±15 45 340-460 76 65
ETP45-20 ±20 45 320-480 81 65
400 >98 half-cycle 31 220
ETP60-15 ±15 60 340-460 102 87
ETP60-20 ±20 60 320-480 109 87
400 >98 half-cycle 35 410
ETP90-15 ±15 90 340-460 153 130
ETP90-20 ±20 90 320-480 162 130
400 >98 half-cycle 35 430
ETP120-15 ±15 120 340-460 204 173

Aquarius Plus - Input voltage variation range ±30%/±25% (the values listed in the table are referred to 400V nominal voltage)
ETP10-30 ±30 10 280-520 20 14
400 >98 half-cycle 23 130
ETP15-25 ±25 15 300-500 29 22
ETP15-30 ±30 15 280-520 31 22
400 >98 half-cycle 23 170
ETP20-25 ±25 20 300-500 39 29
ETP20-30 ±30 20 280-520 41 29
400 >98 half-cycle 31 220
ETP30-25 ±25 30 300-500 57 43
ETP30-30 ±30 30 280-520 61 43
400 >98 half-cycle 35 410
ETP45-25 ±25 45 300-500 86 65
ETP45-30 ±30 45 280-520 93 65
400 >98 half-cycle 35 430
ETP60-25 ±25 60 300-500 116 87

61
Static digital voltage stabilisers IVC WA
RRANTY

2
YEARS

three-phase
Odyssey 80-4000kVA
Standard Features
Voltage regulation IGBT control (double conversion technology)
Voltage stabilisation Independent phase control
Available nominal voltage* 220-230-240V (L-N)
380-400-415V (440-460-480V**) (L-L)
Output voltage accuracy ±0,5%
Frequency 50Hz ±5% or 60Hz ±5%
Correction time <3 millisecs
Admitted load variation Up to 100%
Admitted load imbalance 100%
Cooling Forced Ventilation
Ambient temperature -20/+40°C
Storage temperature -25/+60°C
Max relative humidity <95% (non condensing)
Admitted overload 150% for 1 minute (at nominal imput voltage)
Colour RAL 9005
Protection degree IP21
User interface 10" Touch panel, multilingual (Ethernet communication)
Remotely available by dedicated «client»
Installation Indoor
Communication system MODBUS RTU (RS485)
Overvoltage protection – Input class I surge arrestors
– Output class II surge arrestors
Protection – Automatic by-pass protection
* The output voltage can be adjusted by choosing one of the indicated values.
Such choice sets the new nominal value as a reference for all the stabiliser parameters.
** 60Hz only.

Accessories
Interrupting devices
Short circuit output protection
Manual by-pass line
Total protection kit
Input isolating transformer
Integrated automatic power factor correction system
EMI/RFI filters
IP54 protection degree for indoor and outdoor installation

All ORTEA stabilisers are designed and built in compliance with the Low Voltage and Electromagnetic Compatibility European Directives with regard to the
CE marking requirements. ORTEA products are built with suitable quality components and that the manufacturing process is constantly verified in
accordance with the Quality Control Plans which the Company applies in compliance with the ISO 9001:2015 Standards. The commitment towards
environmental issues and safety at work issues is guaranteed by the certification of the Management System according to the ISO14001:2015 and
OHSAS18001:2007 Standards. In order to obtain better performance, the products described in the present document can be altered by the Company at any
date and without prior notice. Technical data and descriptions do not hold therefore any contractual value.

62
Odyssey
three-phase
80-4000kVA
Rating in relation to the input variation percentage
±15% ±20% ±25% ±30%
160 120 95 80
200 160 120 95
250 200 160 120
320 250 200 160
400 320 250 200
500 400 320 250
630 500 400 320
800 630 500 400
1000 800 630 500
1250 1000 800 630
1600 1250 1000 800
2000 1600 1250 1000
2500 2000 1600 1250
3200 2500 2000 1600
4000 3200 2500 2000

The use of the double conversion technology guarantees the insulation from the disturbances and the
distortions of the network and, together with the help provided by the electrolytic capacitors, makes it
possible to build machines for high power loads.
Odyssey can operate with a load variation range for each phase from 0 to 100%, it is not affected by
the power factor of the load and they can work with or without the neutral.
This voltage stabiliser can operate with different input and, consequently, output voltage (380V or 415V)
from the nominal one (400V). Such setting can be performed at the factory or at the Customer’s premises
according to the instructions given in the handbook. It is also possible to select an output voltage different
from the nominal one, but it is necessary to take into account the reduction of the power and the
adjustment interval of the machine.
The user interface is created using a multilingual «touch panel» (10") with an Ethernet communication port
which, via dedicated «client», allows remote control. Through the selection menu, it is possible to display
electrical values and set the operating parameters of the stabiliser.
It is also possible to communicate with the electronic component via the RS485 serial bus using the
Modbus RTU protocol.
The standard cabinet is an IP21 metal enclosure with RAL9005 finish for indoor installation.
Cooling is guaranteed by extracting fans.

63
Static digital voltage stabilisers IVC

Odyssey
three-phase
80-4000kVA
Type

dimensions*
Correction
Efficiency
variation

Weight*
Voltage

Cabinet
voltage
current

current
Output

output
Power

±0.5%
Rated

Rated
range

range
Input

Input

input

time
Max
[%] [kVA] [V] [A] [V] [A] [%] [ms] [WxDxH] [kg]

Input voltage variation range ±20%/±15% (the values listed in the table are referred to 400V nominal voltage)
120-20 ±20 120 320-480 217 173
400 >98 <3 1200x800x2000 650
160-15 ±15 160 340-460 272 231
160-20 ±20 160 320-480 289 231
400 >98 <3 1200x800x2000 700
200-15 ±15 200 340-460 340 289
200-20 ±20 200 320-480 361 289
400 >98 <3 1200x800x2000 750
250-15 ±15 250 340-460 425 361
250-20 ±20 250 320-480 451 361
400 >98 <3 1200x800x2000 850
320-15 ±15 320 340-460 543 462
320-20 ±20 320 320-480 577 462
400 >98 <3 1200x1000x2200 1000
400-15 ±15 400 340-460 679 577
400-20 ±20 400 320-480 722 577
400 >98 <3 1200x1000x2200 1200
500-15 ±15 500 340-460 849 722
500-20 ±20 500 320-480 902 722
400 >98 <3 1200x1000x2200 1500
630-15 ±15 630 340-460 1070 909
630-20 ±20 630 320-480 1137 909
400 >98 <3 2400x1000x2200 2000
800-15 ±15 800 340-460 1359 1155
800-20 ±20 800 320-480 1443 1155
400 >98 <3 2400x1000x2200 2200
1000-15 ±15 1000 340-460 1698 1443
1000-20 ±20 1000 320-480 1804 1443
400 >98 <3 2400x1000x2200 2800
1250-15 ±15 1250 340-460 2123 1804
1250-20 ±20 1250 320-480 2255 1804
400 >98 <3 4200x1000x2200 3800
1600-15 ±15 1600 340-460 2717 2309
1600-20 ±20 1600 320-480 2887 2309
400 >98 <3 4200x1000x2200 4000
2000-15 ±15 2000 340-460 3396 2887
2000-20 ±20 2000 320-480 3609 2887
400 >98 <3 4200x1000x2200 5600
2500-15 ±15 2500 340-460 4245 3609
2500-20 ±20 2500 320-480 4511 3609
400 >98 <3 4200x1000x2200 6900
3200-15 ±15 3200 340-460 5434 4619
3200-20 ±20 3200 320-480 5774 4619
400 >98 <3 4200x1400x2200 10300
4000-15 ±15 4000 340-460 6793 5774
* Sizes and weights may change.

64
Odyssey
three-phase
80-4000kVA
Type

dimensions*
Correction
Efficiency
variation

Weight*
Voltage

Cabinet
voltage
current

current
Output

output
Power

±0.5%
Rated

Rated
range

range
Input

Input

input

time
Max
[%] [kVA] [V] [A] [V] [A] [%] [ms] [WxDxH] [kg]

Input voltage variation range ±30%/±25% (the values listed in the table are referred to 400V nominal voltage)
80-30 ±30 80 280-520 165 115
400 >98 <3 1200x800x2000 650
95-25 ±25 95 300-500 183 137
95-30 ±30 95 280-520 196 137
400 >98 <3 1200x800x2000 700
120-25 ±25 120 300-500 231 173
120-30 ±30 120 280-520 247 173
400 >98 <3 1200x800x2000 750
160-25 ±25 160 300-500 308 231
160-30 ±30 160 280-520 330 231
400 >98 <3 1200x800x2000 850
200-25 ±25 200 300-500 385 289
200-30 ±30 200 280-520 412 289
400 >98 <3 1200x1000x2200 1000
250-25 ±25 250 300-500 481 361
250-30 ±30 250 280-520 516 361
400 >98 <3 1200x1000x2200 1200
320-25 ±25 320 300-500 616 462
320-30 ±30 320 280-520 660 462
400 >98 <3 1200x1000x2200 1500
400-25 ±25 400 300-500 770 577
400-30 ±30 400 280-520 825 577
400 >98 <3 2400x1000x2200 2000
500-25 ±25 500 300-500 962 722
500-30 ±30 500 280-520 1031 722
400 >98 <3 2400x1000x2200 2200
630-25 ±25 630 300-500 1212 909
630-30 ±30 630 280-520 1299 909
400 >98 <3 2400x1000x2200 2800
800-25 ±25 800 300-500 1540 1155
800-30 ±30 800 280-520 1650 1155
400 >98 <3 4200x1000x2200 3800
1000-25 ±25 1000 300-500 1925 1443
1000-30 ±30 1000 280-520 2062 1443
400 >98 <3 4200x1000x2200 4000
1250-25 ±25 1250 300-500 2406 1804
1250-30 ±30 1250 280-520 2578 1804
400 >98 <3 4200x1000x2200 5600
1600-25 ±25 1600 300-500 3079 2309
1600-30 ±30 1600 280-520 3299 2309
400 >98 <3 4200x1000x2200 6900
2000-25 ±25 2000 300-500 3849 2887
2000-30 ±30 2000 280-520 4124 2887
400 >98 <3 4200x1000x2200 10300
2500-25 ±25 2500 300-500 4811 3609
* Sizes and weights may change.

65
66
Accessories

67
Accessories
The characteristics described so far are relevant to the standard voltage stabilisers.
Accessories to perform specific tasks are available on request.
Combinations or one or more of the accessories listed in the following might result in an increase of the
stabiliser overall dimensions and weight.

Accessories
Interrupting devices
Load protection against over/undervoltage
Manual by-pass line
Total protection kit
Input isolating transformer
Integrated automatic power factor correction system
SPD surge arrestor
EMI/RFI filters
Neutral point reactor
IP54 protection degree for indoor and outdoor installation

Interrupting devices
Every voltage stabiliser can be fitted with an automatic circuit breaker with thermal and magnetic
release on the input and/or on the output. The input breaker protects the stabiliser and the downstream
line against potential short-circuits on the input line. The output breaker protects the stabiliser against
potential overload. The input breaker is sized according to the maximum input current, whilst the output
one is sized in relation to the stabiliser rated current.

Nominal Breaking Additional module Nominal Breaking Additional module


current capacity Length Weight current capacity Length Weight
[A] [kA] [mm] [kg] [A] [kA] [mm] [kg]

10 6 not needed 320 36 not needed


16 6 not needed 400 36 not needed
20 6 not needed 500 36 not needed
25 6 not needed 630 36 not needed
32 6 not needed 800 50 not needed
40 6 not needed 1000 50 not needed
50 6 not needed 1250 50 not needed
63 6 not needed 1600 50 not needed
80 10 not needed 2000 65 600 90
100 16 not needed 2500 65 600 90
125 18 not needed 3200 85 600 90
160 25 not needed 4000 85 600 90
200 36 not needed 5000 100 1200 200
250 36 not needed 6300 100 1200 200

68
Load protection against over/undervoltage
This circuit offers a double protection by:
– delaying the connection to the load each time the stabiliser switches on, so that the user can undergo
a smooth start-up with an already stabilised voltage;
– protecting the load from surges, sags and overload by disconnecting the load from the stabiliser.
The protection intervenes when the output voltage is outside the set range (with regard to the rated
value). When the supply goes back to the regular value, the load is automatically re-connected. Up to
320A, the protection is obtained with contactors. From 400A upwards, an automatic motorised circuit
breaker is used.
The protection must be sized according to the stabiliser nominal current.

Nominal Additional module Nominal Additional module


current Length Weight current Length Weight
[A] [mm] [kg] [A] [mm] [kg]

10 not needed 320 not needed


16 not needed 400 not needed
20 not needed 500 not needed
25 not needed 630 not needed
32 not needed 800 not needed
40 not needed 1000 600 80
50 not needed 1250 600 80
63 not needed 1600 600 80
80 not needed 2000 600 90
100 not needed 2500 600 90
125 not needed 3200 600 90
160 not needed 4000 1200 200
200 not needed 5000 1200 200
250 not needed 6300 1200 200

69
Accessories

Manual by-pass line


The bypass circuit enables the stabiliser to be segregated from the line supplying the load.
The operator can therefore access the internal components and perform maintenance or repairing
sessions without having to disconnect the load.
For the duration of the bypass condition, the load is directly fed by the mains: the voltage is therefore not
stabilised.

The by-pass line configuration can be:

1. – I-0-II changeover interlocked switch (QS) Additional module


Nominal
current Length Weight
[A] [mm] [kg]

OUTPUT
INPUT

I
0 320 400 70
II
DVS 400 400 70
QS QS
500 600 90
VOLTAGE CHANGEOVER
STABILISER INTERLOCKED 630 600 90
SWITCH
800 600 90
1000 600 90
Nominal Additional module 1250 600 90
current Length Weight 1600 600 90
[A] [mm] [kg] 2000 1600 200
2500 1600 200
10 not needed
16 not needed 3. – Input automatic circuit breaker (QF1)
20 not needed 3. – Output I-0-II changeover interlocked
25 not needed 3. – switch (QS2)
32 not needed
40 not needed

OUTPUT
50 not needed
INPUT

I
63 not needed 0
80 not needed II
DVS
100 not needed QF1 QS2
AUTOMATIC VOLTAGE CHANGEOVER
CIRCUIT STABILISER INTERLOCKED
BREAKER SWITCH
2. – Input disconnecting switch (QS1)
2. – Output I-0-II changeover interlocked
2. –switch (QS2) Nominal Additional module
current Length Weight
[A] [mm] [kg]
OUTPUT
INPUT

I
0
II 125 400 70
DVS
QS1 QS2
160 400 70
DISCONNECTING VOLTAGE CHANGEOVER 200 400 70
SWITCH STABILISER INTERLOCKED
SWITCH 250 400 70
320 400 70
400 400 70
Nominal Additional module
500 600 90
current Length Weight
630 600 90
[A] [mm] [kg] 800 600 90
1000 600 90
125 400 70 1250 600 90
160 400 70 1600 600 120
200 400 70 2000 1600 200
250 400 70 2500 1600 200

70
Total protection kit
The total protection kit includes:
– Input automatic circuit breaker (QF1).
– Bypass switch made of an interlocked automatic circuit breaker (QF2).
– Output interlocked motorized automatic circuit breaker (QF3).
The input automatic circuit breaker protects against potential faults and/or short-circuits inside the
unit. The bypass switch with automatic circuit breaker protects the load supplying line against overload
and short-circuits in bypass condition. The output motorized circuit breaker (interlocked with the
bypass circuit breaker) protects against overload, shortcircuit, overvoltage, undervoltage, phase
sequence error and phase failure
The total protection kit must be chosen according to the stabiliser maximum input current

Current Additional module


Input Output Length Weight
OUTPUT
INPUT

QF2
[A] [A] [mm] [kg]

DVS
QF1 QF3 200 160 400** 100
AUTOMATIC
CIRCUIT
VOLTAGE
STABILISER
AUTOMATIC
CIRCUIT
250 200 400** 100
BREAKER BREAKER
320 250 400** 110
400 320 400** 125
500 400 400** 125
QF1: Input automatic circuit breaker.
630 500 400** 125
QF2: Bypass switch made of an interlocked
800 630 600** 170
automatic circuit breaker.
1000 800 600** 200
QF3: Output automatic circuit breaker. 200
1250 1000 600**
QF3 is interlocked with QF2 by means of an 1600 1250 600** 200
individual key. When one of the breakers is 2000 1600 1200*** 630
closed, the other one is open and the closing 2500 2000 1200*** 640
spring cannot be manually loaded. 3200 2500 1200*** 650
4000 3200 1200*** 730
5000* 4000 2000*** 1100
6300* 5000 2000*** 1200
* Neutral wire sized for 50% of the rate current
** In case of stand alone by-pass add 400mm
*** In case of stand alone by-pass add 600mm

71
Accessories

Input isolating transformer


The input isolation transformer is the best solution to provide for:
– galvanic separation between the stabiliser and the mains;
– delta/star or delta/zig-zag connection in order to cancel the 3rd and triplen harmonics and improve
the balance of the phase voltages;
– generation of a fixed and steady neutral point;
– protection from overvoltage generated by connecting/disconnecting manoeuvres on the line.
The transformer is fitted with electrostatic screen between primary and secondary winding. It is also
possible to have high insulation level (10kV) between input and output.
The input isolating transformer must be chosen according to the stabiliser maximum input current.

Single-phase transformer for Dzn0 three-phase transformer for


VEGA & ANTARES ORION PLUS, SIRIUS & SIRIUS ADVANCE

Cabinet Additional Cabinet Additional


Current Power Current Power
(TRS+DVS) weight (TRS+DVS) weight
[A] [kVA] [tipo] [kg] [A] [kVA] [tipo] [kg]

8 2 13 48 130 90 51 430
13 3 13 59 144 100 51 580
21 5 22 79 158 110 51 600
34 8 22 95 180 125 51 630
43 10 23 110 202 140 51 660
52 12 23 113 231 160 51 710
65 15 23 115 260 180 51 750
86 20 23 125 289 200 51 800
108 25 31 135 325 225 55 910
130 30 31 150 361 250 55 960
173 40 40 160 404 280 55 1020
217 50 40 220 462 320 55 1070
273 63 40 240 505 350 55 1120
304 70 40 260 578 400 55 1210
347 80 2x40 285 650 450 55 1290
391 90 2x40 300 722 500 55 1430
435 100 2x41 335 910 630 61 1700
478 110 2x41 355 1156 800 61 2000
543 125 2x41 400 1445 1000 61 2450
770 175 2x41 455 1806 1250 62 3100
2312 1600 62 3600
2890 2x1000 63 4900
Dyn11 three-phase transformer for
3612 2x1250 63 5800
ORION
4650 2x1600 80 7200
Cabinet Additional 5780 2x2000 80 8600
Current Power
(TRS+DVS) weight 7250 2x2500 91 10600
[A] [kVA] [tipo] [kg]

17 12 31 135
21 15 31 145
28 20 31 170
36 25 40 205
43 30 40 225
57 40 40 290
72 50 2x40 335
91 63 2x40 365
101 70 2x40 370
115 80 2x40 395

72
Integrated automatic power factor correction system
A PFC system can be integrated in the same cabinet with a voltage stabiliser, offering the stabilisation
and the correction of the power factor of the plant in the same solution. The result is a stabilised supply
to the load and a higher power factor of the load itself, with the advantage of having available the
maximum active power. ORTEA PFC systems exploit high energy density metallised polypropylene
three-phase capacitors (Un=525V) exclusively thus guaranteeing robustness and reliability.
Furthermore, the detuned filter (included from 1000kVA) protects the system against possible
harmonics generated by non-linear loads.

DVS PFC Additional module DVS PFC Additional module


power power Length Weight power power Length Weight
[kVA] [kvar] [mm] [kg] [kVA] [kvar] [mm] [kg]

80 50 400 85 630 300 600 230


100 50 400 85 800 350 600 250
125 75 400 115 1000 500 1600 830
160 75 400 115 1250 600 1600 890
200 100 400 135 1600 750 2400 1245
250 150 600 160 2000 900 2400 1335
320 150 600 160 2500 1200 3200 1780
400 200 600 190 3200 1500 4800 2490
500 250 600 220 4000 2000 6400 3320

SPD surge arrestor


SPD arrestors protect the load and the stabiliser against voltage peaks of atmospheric or operational
origin by discharging them to ground.
The installation depends on the system configuration. For example, in case of high ratings the
suggested sequence would be: spark-gap arresters followed by an isolating device (ideally an isolating
transformer) and varistor-based arresters on the output.

Current Current
Type Discharge current Type Discharge current
[A] [A]

CLASS I ORTEA 25kA/pole 2 poles CLASS I DEHN 100kA 2 poles


CLASS I ORTEA 25kA/pole 4 poles CLASS I DEHN 200kA 4 poles
CLASS II ORTEA 20kA/pole 2 poles CLASS II DEHN 40kA 2 poles
CLASS II ORTEA 20kA/pole 4 poles CLASS II DEHN 40kA 4 poles

EMI/RFI filters
The addition of EMI/RFI filters is a valid solution to remove the electromagnetic interferences generated
by many electronic devices (converters, switching power supplies, motor drives, etc.).
The EMI/RFI filters must be chosen according to the stabiliser rated output current.

Rated current Rated current


Type Type
[A] [A]

FL170.50.00 50 FL155.800.00 800


FL170.100.00 100 FL155.1000.00 1000
FL170.150.00 150 FL155.1600.00 1600
FL170.300.00 300 FL155.2500.00 2500
FL170.500.00 500

73
Accessories

Neutral point reactor


The neutral point reactor creates a reference neutral for the system when the input AC mains does not
include the neutral connection or when a stable neutral is required to supply the load.
The neutral point inductor is available for all the voltage stabilisers.

THREE-PHASE
INPUT
U1 U2

V1 V2
VOLTAGE STABILISER
W1 W2

N
N

THREE-PHASE
+NEUTRAL
OUTPUT
NEUTRAL POINT REACTOR

IP54 protection degree for indoor and outdoor installation


IP54 indoor installation: These units are equipped with air conditioning units to ensure the correct
ventilation and cooling of the internal magnetic and electrical components. The cabinet is completely
sealed: this makes the stabiliser suitable for operating in damp and dusty environments.
IP54 outdoor installation: ORTEA's stabilisers are also available for outdoor installation.

74
Cabinet size

Dimensions [mm] Dimensions [mm]


Type Type
W D H W D H

11 210 400 200 60 600 1000 1800


12 300 460 300 61 1200 1000 1800
13 300 560 300 62 1800 1000 2000
63 2400 1000 2000
21 300 500 900 64 3000 1000 2000
22 410 530 1200 65 3600 1000 2000
23 410 680 1200 66 4200 1000 2000
67 1200 1000 2000
31 600 600 1600
32 600 600 2000 70 3600 1000 2100
33 800 600 2000 71 4200 1000 2100
35 800 600 1800 72 4800 1000 2100
36 1200 600 1600 73 5400 1000 2100
37 1200 600 2000 74 6000 1000 2100
75 6600 1000 2100
40 600 800 1600 76 7200 1000 2100
41 1000 800 1800
42 800 800 2000 80 3600 1400 2200
43 1200 800 1600 81 4200 1400 2200
44 2000 800 2000 82 4800 1400 2200
46 1800 800 1600 83 5400 1400 2200
47 1600 800 1800 84 6000 1400 2200
48 2200 800 1800 85 6600 1400 2200
49 2200 800 2000 86 7200 1400 2200
87 7800 1400 2200
50 2400 800 1800
51 600 800 1800 90 4200 2000 2400
52 1800 800 2000 91 5400 2000 2400
53 1200 800 2000 92 6000 2000 2400
54 600 800 2000 93 6600 2000 2400
55 1200 800 1800 94 7200 2000 2400
56 1800 800 1800 95 8400 2000 2400
57 2400 800 2000
58 3000 800 2000 C20 6000 2400 2400
59 3600 800 2100 C30 9000 2400 2400
HC40 12000 2400 2700

75
76
«Special»
voltage stabilisers

Beside designing and manufacturing customised stabilisers tailored on the Customer's requirements,
ORTEA developed product series particularly thought and optimised for specific necessities and/or
applications.
Here below is a list summarizing said series.

BTS series Telecommunication (TLC)

DLC series Line conditioners

BC series Broadcasting

AOT series Mains filters

OUTDOOR series Outdoor installations

F&B series Food & Beverage, packaging and bottling industry

77
«Special» voltage stabilisers

BTS series
The acronym BTS stands for Base Transceiver Station and is used to indicate all the transmitting and
receiving devices that enable the radio coverage in a telecom cell.
This is definitely an application where high quality voltage supply, regardless of the incoming
fluctuation, is very often the key for ensuring efficiency and reliability, fundamental qualities to
guarantee operating continuity.
Disrupted service, loss of data, security failure, inaccurate information and general inconvenience are
examples of possible problems caused by unstable supply. Of course, all this results in increased costs.
A voltage stabiliser is a device able to respond to changes in the voltage level on the input line caused by
sags (due to undersized distribution lines, connection of large loads to the network, ground faults, etc.)
and surges (generated by disconnection of large loads, increased voltage at the generating plant,
atmospheric events, etc.) The duration of such phenomena depends on their cause and is not easily
predictable. Sags are generally more common especially where the distribution is not efficient
The voltage stabiliser specifically designed for BTS sites has proved to be an efficient solution in the
telecommunication field.
In comparison to a standard voltage stabiliser, a BTS unit offers the following characteristics:
– IP54 metallic enclosure for outdoor installation.
– Manual by-pass.
– Input and output circuit breakers.
– Input digital voltmeter.
– Output Class II surge arrestors.
– Optional isolating transformer.
The stabilisers can be single-phase, three-phase or specifically designed for receiving a three-phase
input and releasing a single-phase output. With the three-phase configuration, the regulation is
performed independent on each phase and the voltage stabiliser requires the neutral wire presence for a
correct operation. If the neutral wire is not available, the addition of a D/Y isolating transformer or
neutral-point reactor is required.
Three-phase stabilisers can be used with three-phase loads and up to 100% unbalanced single-phase
loads, even in case of asymmetric mains.
The instrumentation is installed on the cabinet door. An output digital multimetre provides with
information on the line downstream the voltage stabiliser (phase and linked voltages, current, power
factor, active power, apparent power, reactive power, etc).
Minimum voltage, maximum voltage, internal overheating and overload on the voltage regulator are
signalled by an acoustic alarm.
The stabiliser exploits a microprocessor-based control logic.

Main features
– Power design based on the maximum input current.
– Regulation based on the «rms voltage» and insensitivity to harmonics on the mains.
– Full functionality with load charge variable from 0 to 100%.
– Up to 30% harmonic content admitted on the load current.
– Insensitivity to the load power factor.
– No generation of noticeable harmonics in the output voltage.

Protections and signals


– Motor rotation stop due to regulation reaching the limit switches.
– Maximum and minimum line voltage alarm.
– Ambient thermostat (set to 65°C).
– Automatic circuit breaker to protect the voltage regulator.
– Fuses to protect the auxiliary circuits.
– Class II surge arrestors.

78
BTS series

OUTPUT
INPUT

ISOLATING I
TRANSFORMER
0
II
DVS
QF1 QF2 QS
INPUT VOLTAGE OUTPUT
AUTOMATIC AUTOMATIC CHANGEOVER
STABILISER SWITCH
CIRCUIT CIRCUIT
BREAKER BREAKER

(optional) CLASS II SPD SURGE ARRESTOR

Standard features BTS1 BTS3 BTS3/1


Number of phases 1 3 3/1
Output voltage* 220-230-240V (L-N) 380-400-415V (L-L) 380-400-415V (L-L) input
220-230-240V (L-N) output
Nominal rating from 5kVA to 80kVA
Input voltage range ±15% - ±20% - ±25% - ±30% - +15%/-25% - +15%/-35% - +15%/-45%
Output voltage range ±0.5%
Frequency 50 ±5% or 60Hz ±5%
Admitted load variation Up to 100%
Admitted load imbalance n.a. 100% n.a.
Cooling Natural air ventilation (air extraction over 35°C)
Ambient temperature -25/+45°C
Storage temperature -25/+60°C
Maximum relative humidity 95% (non condensing)
Admitted overload 200% 2 min.
Harmonic distortion None introduced
Colour RAL 7035
Protection degree IP54
Installation Outdoor
Overvoltage protection class II surge arrestor
* The output voltage can be adjusted by choosing one of the indicated values.
Such choice sets the new nominal value as a reference for all the stabiliser parameters.

All ORTEA stabilisers are designed and built in compliance with the Low Voltage and Electromagnetic Compatibility European Directives with regard to the
CE marking requirements. ORTEA products are built with suitable quality components and that the manufacturing process is constantly verified in
accordance with the Quality Control Plans which the Company applies in compliance with the ISO 9001:2015 Standards. The commitment towards
environmental issues and safety at work issues is guaranteed by the certification of the Management System according to the ISO14001:2015 and
OHSAS18001:2007 Standards. In order to obtain better performance, the products described in the present document can be altered by the Company at any
date and without prior notice. Technical data and descriptions do not hold therefore any contractual value.

79
«Special» voltage stabilisers

DLC series
ORTEA product range is completed by a range of line conditioners based on voltage stabilisers and
provided with additional protective devices.
The following sketch shows the typical line conditioners:
– Input automatic circuit breaker (protection against short-circuit).
– Delta/Star or Delta/Zig-zag input isolation transformer (complete galvanic isolation between the
mains and the load and cancellation of third and triplen harmonics).
– Class 1 SPD surge protective device (protection against lightning).
– Class 2 SPD surge protective device (protection against transients).
– EMI/RFI filter (protection against electro-magnetic and radio-frequency noise).

Lybra Single-phase Vega/Antares + advanced protection 0.3-135kVA


Aries Three-phase Orion + advanced protection 2-250kVA
Aries Plus Three-phase Orion Plus + advanced protection 30-1250kVA
Discovery Three-phase Sirius + advanced protection 60-6000kVA
INPUT

OUTPUT
AUTOMATIC ISOLATING VOLTAGE EMI/RFI
CIRCUIT TRANSFORMER STABILISER FILTER
BREAKER

CLASS I SPD CLSS II SPD


SURGE ARRESTOR SURGE ARRESTOR

80
BC series
The acronym DVB stands for Digital Video Broadcasting and is used to indicate all the devices
transmitting and receiving digital signal. The availability of high quality voltage supply is the key for
ensuring operating continuity.
The BC series is specifically designed for DVB stations and consists of a digital voltage stabiliser able
to compensate for voltage variation on the input line generated by sags or surges, completed by
additional devices for the protection against transients and electric noise generated by electronic
appliances.
Usually, a BC stabiliser includes
– Digital voltage stabiliser.
– Isolating transformer.
– Input & output automatic circuit breakers.
– Input Class I surge arrestors.
– Output Class II surge arrestors.
– EMI/RFI filter.
– Instrumentation (voltmeter/multimetre).
For outdoor installation, the unit is housed in side an IP54 metallic enclosure.
Small ratings can be assembled in enclosures suitable for installation in 19” rack cabinets.

AOT series
AOTs (wave absorbers) are obtained by assembling in a cabinet a combination of protective devices to
deal with transients carried by the distributing lines.
In order to achieve the most complete protection level, the AOT combines two complementary
concepts: smoothing and filtering. The task is performed through surge arrestors, isolating
transformers, detuning reactors and capacitors.
AOTs must be installed upstream and in series to the equipment that needs protection in order to avoid
inductive and /or capacitive effects on the lines.
Usually, AOTs include:
– Input automatic circuit breaker.
– Parallel surge arrestors (redundant system).
– Isolating transformer.
– Capacitors.
– Detuning/blocking reactor
– Output automatic circuit breaker.
The operation can be divided in three phases:
1. The surge arrestors discharge to ground the direct overvoltage energy.
2. The isolating transformer ensures galvanic isolation between the mains and the equipment to be
protected.
3. The filtering module eliminates the residual energy.

81
«Special» voltage stabilisers

OUTDOOR series
All ORTEA voltage stabilisers can be assembled in cabinets specifically designed for outdoor
installation.
The standard outdoor cabinets are built for an IP54 protection degree and are painted with powder paint
for C3 anti-corrosion class (C4 on request).
On request, ORTEA is also able to provide with units destined to be installed in particularly aggressive
environments (for example, AISI304 and AISI316 stainless steel cabinets).

F&B series
Specifically designed for food & beverage, packaging and bottling industries, these voltage stabilisers
are housed in an IP54 cabinet cooled via air conditioning units.
The stabiliser is therefore protected against dust or other volatile substances and liquid sprays.
The configuration includes raised feet, so that normal cleaning routines can be performed underneath
the stabiliser.
On request, the cabinet can be in stainless steel.

82
Warranty terms

1.1 Warranty The proper / correct use of the equipment allows for full exploitation of
The purchased equipment is under warranty against any material or its characteristics in complete safety. For such purpose:
workmanship defects that might occurs within the terms indicated in – follow the instructions in the user manual;
the following starting from the date of purchase and for all mechanical, – check the integrity of equipment and components;
electrical and electronic parts. – comply with instructions and warnings provided;
During the warranty period, the Manufacturer will repair or replace any – check status of preservation and keep maintenance on the
defective parts, unless said defects are due to: equipment under control;
– improper handling, storage and/or use: – check the status of cables and electrical connections;
– wear & tear resulting from normal usage; – comply with the nameplate data such as (but not limited to) power,
– incompetence or negligence on the Buyer’s side when installing, voltage and amperage;
running and maintaining the unit; – use the equipment for the purpose intended by the Manufacturer;
– interventions performed by or on behalf of the Buyer without written – operate the equipment in the environmental conditions for which it
authorization; was designed;
– failure to comply with instructions given by the Manufacturer; – cut off the power supply in case of inspection, repair and
– removal, alteration or forgery of the nameplate and the data maintenance;
indicated thereof; and – use suitable work clothing and personal protective equipment
– fortuitous or force majeure events such as (but not limited to) fire, (PPE);
earthquake, flood, riot and revolution, war, political instability, – immediately report any malfunction (bad behaviour, suspicion of
terroristic act, strike, etc.). rupture, incorrect movement and noise beyond the standard level)
Moreover, the provided warranty will immediately become null and void to the department manager and switch off the equipment;
in case of: – comply with the recommended maintenance frequency, recording
– failure to comply with the payment terms; every control and comment related to the performed intervention.
– failure to carry out routine and / or extraordinary maintenance;
– improper use of the equipment; and 1.3 Misuse / Improper use
– external phenomena beyond the unit’s scope and control. The Manufacturer defines as «misuse / improper use» of the equipment
In case of failure, the Buyer shall contact the Head Office where the any other than what described in the previous paragraph and in addition
Manufacturer will decide whether the repair can be performed on to that:
location, or if the equipment has to be shipped to the Manufacturer's – modification of the operating parameters. Should it be necessary to
facilities or to an after-sale Service Centre authorised by the make any modification to the equipment, the Buyer shall contact
Manufacturer. the Manufacturer;
If the repairing intervention can be performed at the Buyer’s facility, all – use of unsuitable or inadequate energy sources;
the expenses relevant to travelling, boarding and lodging of the Seller – employment of not adequately trained/skilled personnel to run the
personnel shall be at the Buyer’s charge, whilst spare parts and labour unit;
costs shall be at the Manufacturer’s charge. However, the Buyer shall – failure to comply with the maintenance instructions or
produce copy of the purchasing document (invoice) and report the maintenance incorrectly carried out;
detected anomaly prior to the intervention. – use of non-original spare parts or unsuitable ones;
If the intervention is performed at the Manufacturer's facility, the – modification and / or tapering with the equipment safety devices;
equipment shall be duly packed and shipped back at the Buyer’s – performance of control operations, maintenance, or repairs without
expense and risk. The shipment after the repairing operations shall be having first disconnected the energy supply;
under the Manufacturer’s responsibility. – performance of temporary repairs or remedial measures not
Unless otherwise agreed upon in writing, this warranty does not cover complying with the instructions..
the replacement of the entire equipment under no circumstances
whatsoever. Nothing shall be due to the Buyer for the time in which the WARNING. The Manufacturer declines all responsibility for damage to
equipment is left idle. The Buyer may not claim any compensations persons or belongings due to improper use as defined above.
and/or reimbursements for expenses or indirect damages caused by
the equipment failure. 1.4 Warranty terms
Parts provided as spare parts and/or replacements are subject to the 24 months from invoice date for VEGA, ANTARES, ORION, ORION
same warranty terms. Repair or replacement of a defective part does PLUS, GEMINI, AQUARIUS and ODYSSEY.
not extend the original warranty period on the product as a whole. 36 months from invoice date for SIRIUS.
The competent place of jurisdiction for any disputes is in Monza (Italy). 60 months from invoice date for SIRIUS ADVANCE.

1.2 Proper use


While the unit is functioning, the operator must be protected from any
risks associated with the functioning mode.
CT-ORTEA-2019-S07-DVS-2EN
Companies are more and more
sensitive to Power Quality
issues because they can
cause troubles and damages
to equipments.

Our Power Quality solutions:

VOLTAGE STABILISERS
SAG COMPENSATOR
DRY-TYPE TRANSFORMERS
VOLTAGE OPTIMISERS
PFC SYSTEMS
ACTIVE HARMONIC FILTERS

ORTEA SpA
Via dei Chiosi, 21 The present document is reserved property of ORTEA SpA:
20873 Cavenago di Brianza MB | ITALY it is compulsory to inform head office and ask for authorisation before proceeding with any release or reproduction. ORTEA
SpA will not be held liable or responsible in any way for unauthorised copies, alterations or additions to the next or to the
tel. +39 02 95 917 800 illustrated parts of this document. Any modification involving company logo, certification symbols, names and official data is
strictly forbidden.
www.ortea.com In order to obtain better performance, ORTEA SpA reserves also the right to alter the products described in this document at
sales@ ortea.com any date and without prior notice. Technical data and descriptions do not therefore have any contractual value.

You might also like