Earth Electrode Test Sheet: No 8b, Down Town Road 7, P.O.Box 28, Phnom Penh, Kingdom of Cambodia
Earth Electrode Test Sheet: No 8b, Down Town Road 7, P.O.Box 28, Phnom Penh, Kingdom of Cambodia
SYSTEM
SCHEDULE
SPECIFICATION
REF. DRWG
1 LOCATION/STATION
2 SYSTEM/DUTY
3 DIAGRAM NO.
4 ERECTION CONTRACTOR
ACTION
ITEM DESIGNATION JUDGE
YES NO N/A
A INSPECTION
1 Inspect construction of electrodes.
2 Inspect boring and packing material.
3 Inspect bolted and clamped connections.
4 Check completed electrode cover lids.
B TEST
1 Measure and record resistance of each electrode not connected to ring.
Reading 1st 2nd 3rd Aver. Within 5% Electrode resistance Requirement JUDGE
NO. 1
NO. 2 ≤100Ω
NO. 3
C METHOD
The average of the three readings is taken as the electrodes resistance as long as all three readings are within 5% of one
another. If they exceed 5% the test must be repeated with the distance of test and auxiliary electrodes increased.
Electrodes that exceed a test value of 200Ω are prone to being unstable and a value of 20Ω is often quoted as being the
maximum allowable value. It should be noted that the maximum theoretical value is 1666W. This comes from ohm’s law,
where an installation relying on an electrode is provided with supplementary protection by a 30mA RCD.
50V ¸ 0.03A = 1666Ω ( maximum touch voltage is 50V )
REMARK