3102213-En FW-UL6W FireWorks Workstation Installation Manual
3102213-En FW-UL6W FireWorks Workstation Installation Manual
Version
FCC compliance
This equipment has been tested and found to comply with the limits for
a Class B digital device, pursuant to part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and
used in accordance with the instructions, may cause harmful
interference to radio communications.
There is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio
or television reception, which can be determined by turning the
equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
Contact information
The FW-UL6W has been investigated against, and found • NFPA 15 Standard for Water Spray Fixed Systems
to be in compliance with, the following standards: for Fire Protection, 2012 edition
• CAN/ULC-S303-M91 Standard for Local Burglar • NFPA 16 Standard for the Installation of Foam-
Alarm Units and Systems, 1st edition Water Sprinkler and Foam-Water Spray Systems,
2011 edition
• CAN/ULC-S527-99 Standard for Control Units for
Fire Alarm Systems, 2nd edition • NFPA 17 Standard for Dry Chemical Extinguishing
Systems, 2013 edition
• CAN/ULC-S559-04 Standard for Equipment for Fire
Signal Receiving Centres and Systems, 1st edition • NFPA 17A Standard for Wet Chemical Extinguishing
Systems, 2013 edition
• CSA C22.1-12 Canadian Electrical Code, Part 1
• NFPA 70 National Electrical Code
• UL 365 Standard for Police Station Connected
Burglar Alarm Units and Systems, 4th edition • NFPA 72 National Fire Alarm Signaling Code
• UL 609 Standard for Local Burglar Alarm Units and • NFPA 2001 Standard on Clean Agent Fire
Systems, 11th edition Extinguishing Systems, 2012 edition
• UL 636 Standard for Holdup Alarm Units and • FM 3010 Approval Standard for Fire Alarm Signaling
Systems, 10th edition Systems, 2010 edition
Caution: Users should not attempt to make such Note: Note messages advise you of the possible loss of
connections themselves, but should contact the time or effort. They describe how to avoid the loss.
appropriate electric inspection authority, or electrician, Notes are also used to point out important information
as appropriate. that you should read.
Limitation of liability
To the maximum extent permitted by applicable law, in
no event will UTC be liable for any lost profits or
business opportunities, loss of use, business
interruption, loss of data, or any other indirect, special,
incidental, or consequential damages under any theory
of liability, whether based in contract, tort, negligence,
product liability, or otherwise. Because some
jurisdictions do not allow the exclusion or limitation of
liability for consequential or incidental damages the
preceding limitation may not apply to you. In any event
the total liability of UTC shall not exceed the purchase
price of the product. The foregoing limitation will apply to
the maximum extent permitted by applicable law,
regardless of whether UTC has been advised of the
possibility of such damages and regardless of whether
any remedy fails of its essential purpose.
Installation in accordance with this manual, applicable
codes, and the instructions of the authority having
jurisdiction is mandatory.
While every precaution has been taken during the
preparation of this manual to ensure the accuracy of its
contents, UTC assumes no responsibility for errors or
omissions.
Summary
This chapter provides a brief introduction to the
FW-UL6W workstation.
Content
Introduction 2
Description 2
Software product options 3
Front panel features 3
Rear panel features 4
Internal cable connections 4
Compatible monitors, option cards, and other
accessories 6
Minimum system configurations 6
Specifications 7
Product Description
Fan 8
Rear panel features JP6
JP8
X2 (PWR)
Fan 7
S1 Fan 6
Figure 6 shows the features found on the rear panel of
the FW-UL6W. X5 Fan 5
(5)
JP5 Fan 4
ISP1
JP9
Figure 6: Rear panel features Fan 3
JP10 Fan 2
COM PORT
JP11 Fan 1
(7) (6)
(1) From power supply (7) From front panel USB ports
(2) Memory slots (32 GB installed) (8) From front panel Power LED
(3) From PCWD6 COM PORT connector (9) From front panel ON/OFF key switch
(4) From power supply (10) From front panel Hard Drive LED
(5) From Drive 0 (11) Expansion slots for option cards
(6) From Drive 1 (12) PCWD6 card slot (PCWD6 card installed)
Model Description
Emergency Signaling
• FW-UL6W with PCWD6, keyboard, and mouse
• UL 864 Listed compatible monitor (see Table 4)
• PT-1S system event printer (if required)
• Radionics/Bosch D6600 (one per workstation)
Specifications
Operating system Windows 7 Professional SP1, 64-bit
Optical drives 1
Operating environment
Temperature 32 to 120°F (0 to 49°C)
Relative humidity 0 to 93% noncondensing
[2] Add 5.5 in. (14.0 cm) to the depth if an FW-UL6CC1 is installed.
Summary
This chapter provides instructions for installing your
FW-UL6W.
Content
Package contents 10
Installation 10
Installing the workstation on a bench 10
Installing the FW-UL6W in a rack 10
Connecting AC power 10
Connecting the keyboard and mouse 12
Connecting monitors 12
Ethernet port connections 12
Serial port connections 12
Securing I/O cable connections 13
Setting up the FW-UL6W 13
Turning on the FW-UL6W 13
Logging on to the FW-UL6W 13
Changing the Windows user account passwords 14
Setting up the monitors 15
Setting up the monitor touch screens 16
Connecting a PT-1S system event printer 18
3. Connect the line (BK), neutral (WH), and ground Figure 12: AC power connection
(GN) wires together. See Figure 11.
Strip the wires about 1/4-inch and use appropriately
sized, UL approved fasteners to connect the wires.
4. Using a ground pigtail, connect the ground wires to
the junction box. Make the ground pigtail from the
SPD to the junction box as short as possible.
5. Plug the AC power cord connector into the power
supply. See Figure 12.
(1) Limit connections to the same room, and within 8 ft. (2.4 m). (1) UL 2572 Communication Security Level 1.
(2) RJ-45 Ethernet patch cable, Cat 5e or better. Limit connection to
the same room, within 20 ft. (6.1 m) for UL or 59 ft. (18 m) for
Connecting monitors ULC, and enclose in conduit or equivalent protection against
mechanical injury.
Connect monitors to either of the video ports on the back
of the FW-UL6W. See Figure 15.
Serial port connections
Use the DVI-I cable supplied with the monitor or use the
HDMI adapter cable supplied with the workstation. Connect compatible serial devices to the FW-SP4I card
serial ports. See Figure 17. Do not use the DB-9 serial
Dual monitor systems may require additional setup. See
port connectors on the I/O panel on the back of the
“Setting up the monitors” on page 15.
workstation.
(1) Limit connections to the same room, and within 8 ft. (2.4 m).
Table 6: Windows user account default passwords 5. Click OK, and then close the Computer
User account name Password Management window.
Administrator ESTFW 6. Press Ctrl + Alt + Delete, and then click Change
Maintenance Admin Password.
USER USER 7. In the Old Password box, type the current password.
EstSupport Reserved for technical support use only 8. In the New Password box, type the new password.
Note: User account names and passwords are case sensitive. 9. In the Confirm New Password box, type the new
password again.
To log on to the FW-UL6W: 10. Press Enter.
1. In the User Name box, type the user account name.
Changing other user account passwords
2. In the Password box, type the user account
The system administrator can change other user
password.
account passwords without allowing them to change
3. Press Enter. their own account passwords.
3. In the Computer Management navigation pane, • Extends the Windows desktop across both monitors
double-click Local Users and Groups, and then click with the first monitor as the primary desktop and
the Users folder. second monitor as the extended desktop
4. For each user account, double-click the user name, Typically, when you extend the Windows desktop across
and then on the General tab, clear the User Cannot two monitors, the monitors are the same size, and they
Change Password check box. are placed next to each other with the primary desktop
on the left and the extended desktop on the right. See
5. Click OK, and then close the Computer
Figure 19.
Management window.
The next time a user logs on to their account, they can Figure 19: Typical dual monitor setup
change their password by pressing Ctrl + Alt + Delete,
and then clicking Change Password. Afterwards, the
system administrator can prevent them from changing it
again by selecting the User Cannot Change Password
option.
Figure 20: Extending the desktop to a larger monitor Cloning displays on dual monitor systems
Cloning displays places the Windows desktop on both
monitors. See Figure 23.
If you are using two different size monitors, the Intel HD
graphics driver automatically sets the resolution of both
monitors to the optimal resolution of the smaller monitor.
Figure 24: Touch screen connections To see how the touch screen controllers are mapped,
select a USB Controller icon on the General tab, and
then click the Display tab to see which display is
selected.
Notes
• FireWorks only supervises the system event printer
for loss of communication.
• FireWorks does not differentiate between a printer
that is turned off and a USB cable that is unplugged,
and does not provide supervision for “loss of power”
and “printer taken offline manually.”
• FireWorks does not display a printer fault event until
after another event occurs.
• FireWorks will not recognize the system event
printer automatically. You must add it to your
FireWorks project.
Summary
This chapter describes the different methods for
connecting FireWorks nodes.
Content
Introduction 20
Connecting an EST3 control panel 20
Using an FW-SP4I card serial port 20
Using an MN-COM1S 21
Connecting an EST3X control panel 22
Using an FW-SP4I card serial port 22
Using an MN-COM1S 22
Using a 3X-ETHx card 22
Connecting a Bosch/Radionics D6600 Communications
Receiver 23
Using an FW-SP4I card serial port 23
Using an MN-COM1S 24
Setting up the Bosch/Radionics D6600 and other
equipment 24
Connecting iO64 and iO500 control panels 25
Installing the com0com driver 25
Connecting the OH Network Receiver to the virtual
COM port 26
Connecting the OH2000E digital receiver to the
virtual COM port 26
Connecting an FW-HSSX1 VESDA Modbus High Level
Interface 26
[1] Requires 3-SDU V5.3, and C-CPU application code V1.30 Figure 28: EST3 serial port field wiring
[2] Requires 3-SDU V5.3, C-CPU application code V 1.30, and a
3X-ETHx option card CPU
5 - SGND
(1) 3 - TxD
2 - RxD
Connecting an EST3 control
panel (2)
You can use a serial port on an FW-SP4I card or you (1) To an FW-SP4I serial port by way of an RJ-45 to DB-9 adapter
cable supplied with the FW-SP4I card
can use an MN-COM1S to connect the FW-UL6W to an
(2) Supervised and power-limited
EST3 control panel. (3) EST3 CPU card
Configure the serial port on the EST3 control panel as Figure 30: Typical FW-SP4I card COM port assignments
follows:
• Port Type: Gateway Type III
• Baud Rate: 19.2 Kbaud
Configure the FireWorks serial port as shown in
Figure 29.
Note: You also need to know how Windows COM ports 1
are assigned to the FW-SP4I card serial ports. Figure 30
shows the typical Windows COM port assignments for 2
an FW-SP4I card.
3
Using an MN-COM1S
Figure 31 and Figure 32 show you how to connect an
EST3 control panel to the FW-UL6W using an
MN-COM1S.
(1)
EST3
(2) MN-COM1S
(3)
Using an MN-COM1S
Connect the FW-UL6W workstation to an EST3X control
panel the same way you connect an EST3 control panel.
For more information, see “Using an MN-COM1S” on
page 21.
(1)
EST3X
(2)
(3)
(1)
(2) (3)
(4)
Figure 38: DB-9 serial cable wiring diagram COM port settings
Baud: [9] (38,400)
Data bit: [8]
Stop bit: [1]
Parity: [0] (none)
BSFK fire bit: [1]
Output format: [2] (SIA - change requires hardware
reboot/cycle power)
CPU configuration
Using an MN-COM1S Enable input commands: [0] (no input commands)
Buzzer: [1] (buzzer on for any events)
Figure 39 shows you how to connect a Bosch/Radionics
External parallel printer: [1] (primary: all reports go to
D6600 to the FW-UL6W using an MN-COM1S.
this device)
Here are the steps to follow when setting up and Note: Each event type must be programmed in
configuring a Bosch/Radionics D6600, a control panel System Builder for FireWorks to display them
and its dialer, and the FW-UL6W. properly. Unprogrammed event types are defaulted
to the highest priority.
1. Set up and configure the Bosch/Radionics 6600
(firmware CPU-1.2.03). 5. Configure the DACR, lines, account information, the
events and their meaning, the event states, and
6. Install and set up the com0com driver. 5. In the Setup for com0com dialog box, rename the
virtual COM port pair to two unused Windows COM
7. Connect the OH Network Receiver and the
port numbers.
OH2000E digital receiver to the virtual COM port.
For example, rename the virtual COM ports to 4. Under Serial Port Properties, select the higher-
COM10 and COM11 as shown below. numbered virtual COM port from the Com Port list as
shown below.
Connecting an FW-HSSX1
VESDA Modbus High Level
Interface
Figure 41 shows how you connect an FW-UL6W
4. Click Apply, and then click Close.
workstation to an FW-HSSX1. For more information, see
FW-HSSX1 VESDA Modbus High Level Interface
Connecting the OH2000E digital Installation Sheet (P/N 3102240-EN).
receiver to the virtual COM port
1. On the System Builder Applications menu, click
Communications Manager.
2. Select an unassigned port from the Ports list.
3. Select the OH2000E digital receiver from the
Assigned Node list.
(1)
APS6A
(2) MN-COM1S
(3) (5)
(4)
Summary
This chapter provides instructions for programming your
FW-UL6W to meet UL 864 requirements.
Content
UL 864 programming requirements 30
Disabling the 24-hour trouble re-sound timer 31
Automatically canceling workstation silence 31
Delaying control panel local AC power fail events 31
Changing the event selection method 32
Assigning user rights to clear all receiver account
events 32
Filtering events 32
Changing to local mode of operation 33
Adjusting the trouble signal re-sound timer 33
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units
and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used as
indicated below.
Program feature or option Permitted in UL 864? Possible settings Settings permitted in UL 864
(Y/N)
Program feature or option Permitted in UL 864? Possible settings Settings permitted in UL 864
(Y/N)
Silencing the workstation gives you time to acknowledge 2. Enter the system configuration password.
new events posted on the system without the local 3. On the UL tab, under Property, select
trouble signal sounding in the background. You can UL_NINTH_EDITION_ACPOWER_TIMEOUT_
configure FireWorks to automatically re-sound the local HOURS.
trouble signal in the event you get pulled away from the
workstation or get distracted while you are
4. In the Value box, enter the amount of delay in hours. Note: The event selection method setting may conflict
Possible values: 0 to 45. with UL 864 requirements. To comply, clear the Clear All
Account Events check box.
5. Click Apply.
To assign the Clear All Account Events user right:
1. On the Applications menu, click User Manager, and
Changing the event selection then click the Access Group Configuration tab.
method 2. In the Access Groups list, click the access group.
3. Under Configuration Items, click System Control.
The event selection method determines which event is
automatically selected (has focus) when FireWorks 4. Check the Clear All Account Events check box.
posts a new event. Your options are:
• Maintain Selected Event: The currently selected
event remains selected. It does not change when a Filtering events
new event is posted.
• Select High Priority (default): The new event is The FireWorks event filters let you determine which
automatically selected only if it has a higher priority. events are displayed, printed, and saved in the history
Select this setting if you want the system to display file. By default, all events are displayed, printed, and
the oldest, highest priority event. saved.
• Select Newest: The new event is automatically Note: The event filter settings may conflict with UL 864
selected regardless of its priority. requirements. To comply, set the Display, Printer, and
History filters to allow all events.
• Select Newest (if higher or equal priority): The new
event is automatically selected only if its priority is To filter events:
higher than or is equal to the current event. Select
this setting if you want the system to display the 1. In System Builder, on the Applications menu, click
most recent highest priority event. Set Filtering Parameters.
Note: The event selection method setting may conflict 2. In the Set Filtering Parameters dialog box, check the
with UL 864 requirements. To comply, set the event Enable Filtering check box.
selection method for Select High Priority. 3. For each event type, do one of the following under
Display, Printer, and History:
To change the event selection method:
Check the check box to allow the event.
1. In System Control, click the Function menu.
— or —
2. Point to Event Selection Method, and then click one
of the choices described above. Clear the check box to block the event.
4. Click Apply.
Changing to local mode of 3. On the System Control tab, under Property, select
SYSCONTROL_RESOUND_HOUR_
operation CONFIGURABLE.
4. In the Value box, type the duration in hours.
Local mode of operation automatically acknowledges
Possible values: 0 to 99.
activation events and restoration events from the same
point — if both are present in the New Events list after 5 5. Click Apply.
to 30 minutes. By default, FireWorks is set for
proprietary mode.
Notes
• UL 864 requires the local trouble signal to re-sound
within 24 hours. Setting the adjustable trouble signal
re-sound timer for more than 24 hours violates UL
864 requirements.
• The adjustable trouble signal re-sound timer setting
overrides the 24-hour trouble re-sound timer setting.
Summary
This chapter covers problems that you may experience
while setting up and using your FW-UL6W and gives you
possible solutions.
Content
Fire alarm control panel to workstation communication
problems 36
Workstation communication 36
EST3 or EST3X communication 36
Workstation hard drive failure 36
Cleaning the filter 37
Cleaning the monitors 37
Fire alarm control panel to A communication failure between the control panel and
the workstation network appears as an internal trouble
workstation communication on zone 0607 (port 1 on EST3 or EST3X) or 0608 (port 2
on EST3).
problems
Different events can cause the 0607/0608 trouble state.
In this section, we assume that your fire network already Failure of the auxiliary port is identified on the control
operates correctly on its own. Refer to the appropriate panel and on the FireWorks displays.
technical reference manual for additional information
about your fire alarm control panel and network. Causes and solutions
RXD and TXD connections are crossed. Verify correct
Workstation communication connections. Is the cable correct? Is the panel
connection correct?
Problem The gateway port on the control panel is not configured,
The workstation is not communicating with a fire alarm or the FireWorks and control panel gateways are set
control panel. differently. Use the SDU configuration software to
configure the control panel port as Gateway 3. Make
Check the status bar. The LED indicators in the status sure the port is not configured for a printer. Make sure
bar turn from green to yellow when there is an RS-232 the gateway settings are correctly set and are the same
port communication problem. in both FireWorks and the control panel.
When multiple fire networks are connected to a single Communication baud rates for the control panel and the
workstation, you can identify which node has a problem workstation do not match. Set the control panel baud
by displaying the Node Status window. rate using the SDU program. Set the workstation baud
rate from the System Builder software to define the node
Causes and solutions (port) connected to the control panel. The suggested
RXD and TXD connections are crossed. Verify correct baud rate is 19,200.
connections using the system control menu or the F2
quick key. Is the cable correct? Is the panel connection
correct?
Workstation hard drive
Communication port configuration is wrong. Use System
Builder to check and correct the hardware, node, and failure
port settings for the node with trouble. Check for:
• Incorrect port selection or wiring FW-UL6W FireWorks workstation
• Baud rate mismatch between the workstation and The benefit of a FW-UL6W workstation is that the
fire network system remains operational if one of the hard drives fail.
If a hard drive fails, the screen displays a message to tell
The wrong drivers are installed. The COM ports should you of a degraded RAID volume.
not be configured for WinRT communications; they
should be configured for serial communications.
Figure 42: RAID volume degraded message
Note: Click the Help button for information on using Intel Cleaning the monitors
Rapid Storage Technology Enterprise.
Clean the monitors periodically to remove dust and other
particles that can scratch the screen. Use a soft, clean,
lint-free cloth or a camel hair brush.
Summary
This appendix provides instructions for sizing a UPS.
Content
UPS sizing calculations 40
UPS sizing calculations 6. Add the Derating to the Subtotal and enter the result
in Required VA.
NFPA guidelines require the use of a UL 1481 Listed 7. The required standby power (VA) you just calculated
uninterruptible power supply (UPS) for FireWorks must be maintained for the time period required by
workstations. The UPS must be UL Listed for Fire NFPA code.
Protection Signaling applications (UTRZ). It must provide
8. Calculate the required standby battery size in
120 V at 60 Hz as required by code or the local authority
ampere-hours according to the following equations.
having jurisdiction.
You will need to know the UPS conversion efficiency
Figure 45: UPS block diagram (EC) and battery voltage (VB). You’ll calculate the DC
power required by the UPS and the battery current.
These yield the battery size in ampere-hours.
PDC = VA / EC
Where:
PDC = DC power required by UPS
VA = Volt-amps you calculated
EC = UPS conversion efficiency
IB = PDC / VB
(1) Permanent mains connection (3) UL/ULC Listed trouble signal Where:
to UPS initiating device circuit IB = Battery current
(2) UL 1481 Listed UPS (4) Fire alarm control panel PDC = DC power required by UPS
VB = UPS battery voltage
Use Table 9 to calculate the volt-amp (VA) requirements
for the uninterruptible power supply to be used with the CB = IB x BP
FW-UL6W. Where:
CB = Battery capacity in amp-hours
To calculate UPS size: BP = Backup period from table
1. List the equipment to be protected by the UPS in the Note: Consult UPS manufacturer’s instructions for
Equipment column. specific battery sizing instructions. Remember that you
2. Record the power requirement for each piece of must provide for bypassing the UPS for servicing.
equipment in the Volts and Amperes columns.
You can find this information on the equipment tags.
3. Multiply the volts and amps for each piece of
equipment and write the result in the Power column.
The power on some equipment may be listed in
watts. You can use the following formula to convert
watts to VA. Use a power factor of 0.7, which is
typical for computer equipment.
VA = Watts x Power factor
4. Add the Power column and enter the result in
Subtotal.
5. Multiply the Subtotal by 0.25 and enter the result in
Derating.
Monitor 2 120
Subtotal
Required VA
Summary
This appendix lists the requirements you must meet for agency listings and approvals.
Content
UL/ULC listing requirements 44
FM approval requirements 45
UL ULC Requirement
Workstation computer
X X Any device connected to the workstation by copper wiring must limit connections to the same room, within 20 ft. (6.1 m) for UL
or 59 ft. (18 m) for ULC, and enclose in conduit or equivalent protection against mechanical injury. To connect devices outside
the room you must use fiber optic cable.
X X Each workstation requires a permanent connection to a dedicated fire alarm branch-circuit supply by way of a UL 1481 Listed
uninterruptible power supply (UPS) and a UL 1449 Listed Type 2 surge protection device installed at the power junction box.
The UPS must be UL Listed for fire protection (UTRZ), must provide 120 V at 60 Hz for a minimum of 24 hours in normal
(standby) and 15 minutes in alarm, and must be supervised.
X For proprietary installations, the workstation must be installed in a rack and locked to protect it from tampering. See Table 5 on
page 6 for a list of rack mounting accessories. No other equipment may be installed in the rack.
For annunciator installations, the workstation does not need to be rack mounted and may be installed on a bench.
X X When mounting the workstation on a bench, place the workstation horizontally on the surface along with the monitors,
keyboard, and mouse. When mounting the workstation on a bench, you must use an FW-UL6CC1 to secure cables and
connect conduit.
ULC only allows bench mounting in applications where the workstation is ancillary (no common controls).
X X UL 1076 and UL 1610 require an acknowledgement signal from the proprietary/central station. This is sometimes called
“closing confirmation” or “ring-back.”
To comply with UL 1076, connect FireWorks to the EST3 RS-232 serial port by way of a direct connection or by way of an
MN-COM1S interface module. In this configuration FireWorks functions as a “multiplex central station.” Program the sub-
states so that the security partitions activate an audible and visual signal at the security location. See FireWorks System
Builder Help for more information.
To comply with UL 1610, the EST3 communicates with the proprietary/central station by way of a 3-MODCOM(P) Digital Alarm
Communicator Transmitter (DACT). Program the EST3 to activate an audible and visual signal at the security location after it
confirms that the proprietary/central station received a partition arming (closing) message. See 3-SDU Help for more
information.
X X Security: A COM fault trouble to an EST3 system must be investigated immediately because it comes in as a COM fault and
not a security compromise.
X Security: The FireWorks receiving equipment is suitable for proprietary burglar alarm service, central station service, hold up
alarm service, and police station connect service with basic line security. For holdup alarm service, the CMS or FireWorks
must be manned 24 hours a day.
X X When applied per section “Connecting a Bosch/Radionics D6600 Communications Receiver” on page 23, FireWorks is
suitable for the following: UL/ULC Proprietary and Central Station Receiver for fire applications (one DACR per workstation),
UL/ULC Central Station Receiver for security applications (one D6600 per workstation). If more than one Osborne Hoffman
DACR is connected to a single FireWorks workstation in either application this configuration is considered ancillary and
requires acknowledgement at the DACR. These configurations are not suitable for use as Central Station Automation
Equipment.
X FireWorks with common controls can be used on standard LAN/WAN Ethernet networks for communication to the EST3
system as long as the EST3 system is used as the firefighter’s interface. For fire applications only.
Remote clients and ancillary fiber switches connected directly to the EST3 and to FireWorks must be UL Listed for ITE or fire,
and must be installed within the protected premises or per the authority having jurisdiction. For ULC applications, the use of
secure protocols needs to be applied, such as HTTPS, VPN, or another similar encryption method.
UL ULC Requirement
X When applied per section “Passing commands between control panels” on page 49, the control panels must be mounted in
the same room and positioned so both can be simultaneously observed. For use in UL 864 applications only.
X For CAN/ULC-S559 compliant proprietary fire signal receiving center applications, see EST Life Safety Systems
CAN-ULC-S559 Application Guide (P/N 3102245-EN).
PT-1S printer
Each system must include at least one PT-1S printer for printing event messages.
X X FireWorks Remote Client connections must be made using fiber optic cables.
In order to meet CAN/ULC-S527 requirements for Local applications, the FireWorks workstation requires a hardened
enclosure to protect all wiring and cables, including the mouse, the keyboard, and the monitors. Additionally, the
prioritization of signals is required to meet CAN/ULC-S527-99 Table 1 and CAN/ULC-S527-11 Table 4.
In lieu of the above requirements for hardened enclosure (see item c) and priority of signals (see items a, b, c & d):
a) When Local Security Services is installed in FireWorks, the main FireWorks workstation shall be installed
adjacent to the EST3.
b) When Local Security Services is installed in FireWorks, client workstations and remote clients shall be
classified for ancillary display purposes only and shall have no control capabilities.
c) The FireWorks workstation is not listed as the only means of annunciation (see CAN/ULC-S527-11, 4.11.3.2,
and 4.11.3.3).
d) CO events shall be programmed as Monitor events only.
In order to meet CAN/ULC-S559 requirements, no action is required for both Central Station and Proprietary Fire
Signal Receiving Centre and Systems as the FireWorks is listed for ULC Fire Only. Note: FireWorks is listed for
Emergency Signaling, US Only and Security, US Only.
FM approval requirements
To meet the requirements for FM approval (Proprietary Signaling Systems and Local Protective Signaling, US only):
• The FireWorks workstation must monitor and supervise the trouble contacts on the UPS (uninterruptible power
supply). If the UPS can report multiple trouble condition (e.g., UPS Trouble and UPS On Battery), then FireWorks
must distinctly annunciate each trouble condition.
• Plug the software key into one of the USB ports on the back of the workstation and install a FW-UL6CC1 cable
cover to protect it.
Summary
This appendix describes typical FW-UL6W applications.
Content
Ethernet network application 48
Redundant communication applications 48
Redundant serial communications 48
Redundant Ethernet communication application 49
Passing commands between control panels 49
Security applications 50
Fire applications 50
EST3
(1) (6)
(1) FW-UL6W, FW-SP4I card, and FW-UL6CC1.
(2) (5) MN-COM1S
(2) Primary serial connection to EST3 COM port 1. Limit connection
to the same room, within 20 ft. (6.1 m) for UL or 59 ft. (18 m) for
(3) (3) (4)
ULC, and enclose in conduit or equivalent protection against
mechanical injury.
(6) (3) Secondary serial connection to EST3 COM port 2. Limit
connection to the same room, within 20 ft. (6.1 m) for UL or 59 ft.
MN-COM1S
(18 m) for ULC, and enclose in conduit or equivalent protection
against mechanical injury.
(3) (4)
(6)
MN-COM1S
(3) (4)
Redundant Ethernet communication event, and then sending a command to another control
panel.
application
In a redundant Ethernet communication application, Figure 49: Command passing flow diagram
FireWorks uses two TCP/IP ports to connect to the fire
alarm system. If the primary port connection breaks,
FireWorks can still communicate using the redundant
port connection. See Figure 48.
(1) (6)
FireWorks
(2) (8) MN-COM1S
receives the
Event takes place event. The event
(3) (3) (4) FACP 2 receives
on FACP 1. The
Event is sent to
triggers a
command in
and executes the
command.
FireWorks. FireWorks. The
(7) command is sent
to FACP 2.
(8) (5)
FireWorks
receives the
(7) event. The event Event takes place
(6) FACP 1 receives
MN-COM1S
and executes the triggers a
command in
on FACP 2. The
Event is sent to
command.
FireWorks. The FireWorks.
(3) (4) command is sent
to FACP 1.
(1) FW-UL6W and FW-UL6CC1. (1) Locate the fire alarm control panels (FACP) in the same room and
(2) Ethernet connection. Limit connection to the same room, within 20 position them so both can be viewed at the same time. For use in
ft. (6.1 m) for UL or 59 ft. (18 m) for ULC, and enclose in conduit UL 864 applications only.
or equivalent protection against mechanical injury. (2) Serial or Ethernet connection. Limit connection to the same room,
(3) MN-FNSx Ethernet switch. within 20 ft. (6.1 m) for UL or 59 ft. (18 m) for ULC, and enclose in
(4) EST3/EST3X CPU and RS-232 option card. conduit or equivalent protection against mechanical injury.
(5) Other EST3/EST3X control panels in the same fire alarm network. (3) FW-UL6W and FW-UL6CC1. An FW-SP4I card is required for
(6) Dashed line indicates the same enclosure (or equivalent). serial connections.
(7) EST3/EST3X RS-485 network.
(8) Dedicated fiber network.
Example 1: An alarm event on panel 1 triggers a
command in FireWorks, which turns on the strobes on
panel 2.
Passing commands between Example 2: An alarm event on panel 2 triggers a
control panels command in FireWorks, which turns on the strobes on
panel 1.
The FireWorks workstation is capable of passing Example 3: Reset is pressed on panel 1, which triggers
commands between the following control panels: a command in FireWorks that resets panel 2.
• EST3 For commands like Reset or Signal Silence, program the
• EST3X command to execute in one direction only. For example,
do not configure your system so that pressing Reset on
FireWorks acts like a control panel by receiving the FACP 1 resets FACP 2 and pressing Reset on FACP 2
command or event (e.g. reset command or alarm event) resets FACP 1. Programming the command to execute
from one control panel, processing that command or
Security applications
The following applications are UL/ULC Listed for use
with EST3 systems only and can be used in a rack-
mount or bench-mount configuration:
• Police station connection with basic line security
• Central station alarm
• Proprietary
• Holdup alarm
Note: For information about these applications, refer to
the EST3 control panel documentation.
The following is optional equipment when bench
mounting or rack mounting your system for annunciator
only applications:
• PT-1S system event printer
• UL 1481 Listed UPS
• FW-UL6CC1
Summary
This appendix provides instructions for installing
Lantronix CPR Manager and setting up serial ports for
use with select serial devices.
Content
Introduction 52
Installing CPR Manager 52
Creating the Lantronix CPR port 52
Configuring the FireWorks COM port 53
Testing the connection 53
4. In the Com Ports dialog box, check the check box 4. Click Apply.
for the COM port you want to add, and then click
OK.
Testing the connection
Note: FireWorks Communication Manager supports
Once the equipment is set up and deployed, you can
up to 25 serial ports. Do not select Com26 or higher.
use Lantronix CPR Manager to test the connection.
6. On the Settings tab, do the following: 5. Verify that Com Status is Open and that the Network
Status indicates you are connected to the correct IP
In the Host box, type the IP address of the
address.
MN-COM1s connected to the target serial device.
6. Click Close.
In the TCP Port box, type 10001.
7. Click Save.
2 FM approval requirements, 45
front panel features, 3
24-hour trouble re-sound timer, 31
H
A
HDMI video port, 4
AC power connection, 10
activating your software key, 18
adjusting the trouble signal re-sound timer, 33
I
advisory messages, iii I/O panel, 4
air filter, 3 Industry Canada information, ii
assigning user rights to clear all receiver account events, 32
audio jacks, 4
automatically canceling workstation silence, 31 K
keyboard and mouse connection, 12
C
calibrating touch screens, 17 L
changing the event selection method, 32 limitation of liability, iii
changing to local mode of operation, 33 local mode of operation, 33
changing Windows user account passwords, 14 logging on, 13
cleaning monitors, 37
cleaning the filter, 37
command passing, 49 M
connecting, 12
mapping touch screens, 17
AC power, 10 minimum system configurations, 6
keyboard and mouse, 12
monitor connections, 12
monitors, 12
monitor touch screen setup, 16
connecting touch screens, 16
O
D
ON/OFF switch, 3
description, 2
disabling the 24-hour trouble re-sound timer, 31
DVI-I video port, 4 P
package contents, 10
E passing commands, 49
PS/2 keyboard port, 4
Ethernet network application, 48 PT-1S printer connection, 18
Ethernet ports, 4
event selection method, 32
R
F rack mounting accessories, 6
rear panel features, 4
features
receiver account events, clearing, 32
front panel, 3
redundant Ethernet communication application, 49
rear panel, 4 redundant serial communication application, 48
filtering events, 32
regulatory information, ii
fire applications, 50
S
security applications, 50
setting up monitor touch screens, 16
setting up monitors, 15
setting up the workstation, 13
specifications, 7
status LEDs, 3
T
trouble signal re-sound timer, 33
U
UL 2572 security and data protection, ii
UL 864 programming requirements, 30
UL/ULC listing requirements, 44
UPS sizing calculations, 40
USB mouse port, 4
USB ports
front, 3
rear, 4
W
workstation accessories, 6
workstation setup, 13
workstation silence, 31