0% found this document useful (0 votes)
83 views8 pages

3RP25741NW30 Datasheet en

This document provides product details and specifications for the SIRIUS 3RP2574-1NW30 timing relay. It includes technical data, control circuit details, switching functions, inputs/outputs, electromagnetic compatibility, safety, and connection information.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
83 views8 pages

3RP25741NW30 Datasheet en

This document provides product details and specifications for the SIRIUS 3RP2574-1NW30 timing relay. It includes technical data, control circuit details, switching functions, inputs/outputs, electromagnetic compatibility, safety, and connection information.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

Data sheet 3RP2574-1NW30

Timing relay, electronic with star-delta (wye-delta) function 1 NO


delayed 1 NO instantaneous 1 time range, 1...20 s 12-240 V AC/DC
at 50/60 Hz AC screw terminal

product brand name SIRIUS


product designation timing relay
design of the product Star-delta (wye-delta) function
product type designation 3RP25

General technical data


● product component relay output Yes
● product component semi-conductor output No
product extension required remote control No
product extension optional remote control No

— insulation voltage for overvoltage category 300 V
III according to IEC 60664 with degree of
pollution 3 rated value
Test voltage for isolation test 2.5 kV
degree of pollution 3
surge voltage resistance rated value 4 000 V
● protection class IP IP20
● shock resistance acc. to IEC 60068-2-27 11g / 15 ms
● vibration resistance acc. to IEC 60068-2-6 10 ... 55 Hz / 0.35 mm

3RP2574-1NW30 Subject to change without notice


Page 1/8 09/29/2020 © Copyright Siemens
● mechanical service life (switching cycles) 10 000 000
typical
● Electrical endurance (switching cycles) at AC- 100 000
15 at 230 V typical
adjustable time 1 ... 20 s
Relative setting accuracy relating to full-scale value 5 %
thermal current 5 A
● recovery time 250 ms
reference code acc. to DIN EN 81346-2 K
relative repeat accuracy 1 %

Control circuit/ Control


Type of voltage of the control supply voltage AC/DC
Control supply voltage 1 at AC
● at 50 Hz 12 ... 240 V
● at 60 Hz 12 ... 240 V
control supply voltage frequency 1 50 ... 60 Hz
Control supply voltage 1
● at DC 12 ... 240 V
operating range factor control supply voltage rated
value at DC
● initial value 0.8
● full-scale value 1.1
operating range factor control supply voltage rated
value at AC at 50 Hz
● initial value 0.8
● full-scale value 1.1
operating range factor control supply voltage rated
value at AC at 60 Hz
● initial value 0.8
● full-scale value 1.1
Inrush current peak
● at 24 V 0.5 A
● at 240 V 5 A
Duration of inrush current peak
● at 24 V 0.4 ms
● at 240 V 0.5 ms

Switching Function
switching function
● ON-delay No
● ON-delay/instantaneous contact No
● passing make contact No
● passing make contact/instantaneous contact No

3RP2574-1NW30 Subject to change without notice


Page 2/8 09/29/2020 © Copyright Siemens
● OFF delay No
Switching function
● flashing symmetrically starting with No
interval/instantaneous
● flashing symmetrically starting with interval No
● flashing symmetrically starting with No
pulse/instantaneous
● flashing symmetrically starting with pulse No
● flashing asymmetrically starting with interval No
● flashing asymmetrically starting with pulse No
Switching function
● star-delta circuit with delay time No
● star-delta circuit Yes
● Switching function with control signal additive No
ON delay
● switching function with control signal passing No
break contact
● Switching function with control signal passing No
break contact/instantaneous
● Switching function with control signal OFF No
delay
● Switching function with control signal OFF No
delay/instantaneous
● Switching function with control signal pulse No
delayed
● Switching function with control signal pulse No
delayed/instantaneous
● switching function with control signal pulse- No
shaping
● Switching function with control signal pulse- No
shaping/instantaneous
● Switching function with control signal additive No
ON delay/instantaneous
● Switching function with control signal ON- No
delay/OFF-delay/instantaneous
● Switching function with control signal passing No
make contact
● Switching function with control signal passing No
make contact/instantaneous contact
Switching function of interval relay with control signal
● retrotriggerable with deactivated control No
signal/instantaneous contact
● retrotriggerable with activated control signal No

3RP2574-1NW30 Subject to change without notice


Page 3/8 09/29/2020 © Copyright Siemens
● retrotriggerable with activated control No
signal/instantaneous contact
● retriggerable with deactivated control signal No

Short-circuit protection
● design of the fuse link for short-circuit fuse gL/gG: 4 A
protection of the auxiliary switch required

Auxiliary circuit
Material of switching contacts AgSnO2
● number of NC contacts delayed switching 0
● number of NO contacts delayed switching 1
● number of CO contacts delayed switching 0
operating current of auxiliary contacts at AC-15
● at 24 V 3 A
● at 250 V 3 A
operating current of auxiliary contacts at DC-13
● at 24 V 1 A
● at 125 V 0.2 A
● at 250 V 0.1 A
operating frequency with 3RT2 contactor maximum 5 000 1/h
contact reliability of auxiliary contacts one incorrect switching operation of 100 million switching
operations (17 V, 5 mA)
contact rating of auxiliary contacts according to UL R300 / B300
influence of the surrounding temperature 1% in the whole temperature range to the set runtime
Power supply influence 1% in the whole voltage range to the set runtime
Switching capacity current with inductive load 0.01 ... 3 A

Inputs/ Outputs
● product function at the relay outputs switchover No
delayed/without delay
● Product function non-volatile No

Electromagnetic compatibility
EMI immunity
● acc. to IEC 61812-1 EN 61000-6-2
● conducted interference due to burst acc. to IEC 2 kV network connection / 1 kV control connection
61000-4-4
● Conducted interference due to conductor-earth 2 kV
surge acc. to IEC 61000-4-5
● Conducted interference due to conductor- 1 kV
conductor surge acc. to IEC 61000-4-5
field-bound parasitic coupling acc. to IEC 61000-4-3 10 V/m
electrostatic discharge acc. to IEC 61000-4-2 4 kV contact discharge / 8 kV air discharge

Safety related data

3RP2574-1NW30 Subject to change without notice


Page 4/8 09/29/2020 © Copyright Siemens
protection against electrical shock finger-safe
Type of insulation Basic insulation
category acc. to EN 954-1 none

Connections/ Terminals
● product function removable terminal for Yes
auxiliary and control circuit
● type of electrical connection for auxiliary and screw-type terminals
control current circuit
● type of connectable conductor cross-sections 1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
solid
● Type of connectable conductor cross-sections 1x (0.5 ... 4 mm²), 2x (0.5 ... 1.5 mm²)
finely stranded with core end processing
● Type of connectable conductor cross-sections 1x (20 ... 12), 2x (20 ... 14)
at AWG conductors solid
● type of connectable conductor cross-sections at 1x (20 ... 12), 2x (20 ... 14)
AWG conductors stranded
● connectable conductor cross-section solid 0.5 ... 4 mm²
● connectable conductor cross-section finely 0.5 ... 4 mm²
stranded with core end processing
AWG number as coded connectable conductor cross
section
● solid 20 ... 12
● stranded 20 ... 14
tightening torque 0.6 ... 0.8 N·m
design of the thread of the connection screw M3

Installation/ mounting/ dimensions


● mounting position any
● mounting type screw and snap-on mounting onto 35 mm standard mounting rail
height 100 mm
width 22.5 mm
depth 90 mm
required spacing
● with side-by-side mounting
— forwards 0 mm
— backwards 0 mm
— upwards 0 mm
— downwards 0 mm
— at the side 0 mm
● for grounded parts
— forwards 0 mm
— backwards 0 mm
— upwards 0 mm

3RP2574-1NW30 Subject to change without notice


Page 5/8 09/29/2020 © Copyright Siemens
— at the side 0 mm
— downwards 0 mm
● for live parts
— forwards 0 mm
— backwards 0 mm
— upwards 0 mm
— downwards 0 mm
— at the side 0 mm

Ambient conditions
● installation altitude at height above sea level 2 000 m
maximum
● ambient temperature during operation -25 ... +60 °C
● ambient temperature during storage -40 ... +85 °C
● ambient temperature during transport -40 ... +85 °C
relative humidity
● during operation 10 ... 95 %

Certificates/ approvals
General Product Approval EMC Declaration of
Conformity

Declaration of Test Certific- Marine / Shipping


Conformity ates
Miscellaneous Type Test Certific-
ates/Test Report

Marine / Shipping other


Confirmation

Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RP2574-1NW30

3RP2574-1NW30 Subject to change without notice


Page 6/8 09/29/2020 © Copyright Siemens
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RP2574-1NW30
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RP2574-1NW30
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RP2574-1NW30&lang=en
Characteristic: Derating
https://support.industry.siemens.com/cs/ww/en/ps/3RP2574-1NW30/manual

91.6

22.5 86.5

S IRIU S
3 RP2 5 7 4 - 1 NW3 0

A2 A2
1 2 ...2 4 0 V 1 2 ...2 4 0 V
AC/ DC AC/ DC

A1 A1
50

3 RP2 5 7 4 - 1 NW3 0
100

1 8 NO 2 8 NO
17C

3 RP2 5 7 4 - 1 NW3 0

3RP2574-1NW30 Subject to change without notice


Page 7/8 09/29/2020 © Copyright Siemens
17 C
A1

A1
-K

18 NO

28 NO
A2

A2

last modified: 09/23/2020

3RP2574-1NW30 Subject to change without notice


Page 8/8 09/29/2020 © Copyright Siemens