ENG451 - 6 - Power System Protection
ENG451 - 6 - Power System Protection
Lecturer 05
Differential Protection
Transformer Size
• For sizes less than 2.5 MVA (by fuses), between 2.5 and 5 MVA (by
fuses, but instantaneous and time-delay overcurrent relays may be
more desirable from the standpoint of sensitivity and coordination with
protective relays on the high and low sides of the transformer),
between 5 and 10 MVA (by an overcurrent relay connected in a
differential configuration), above 10 MVA (a harmonic restraint,
differential relay or pressure and temperature relays)
Protection Options for Transformer
Voltage Level
• Higher voltages demand need more sophisticated and costly protective
devices due to deleterious effects of a delayed fault clearing and high
cost of HV transformer repairs
CT Ratios
• It may not be possible to obtain CT ratios on primary and secondary
side which will satisfy condition N1n1 = N2n2, as we must select CTs
with standard ratios
• The problem is somewhat alleviated by the fact that most relays
themselves provide different tap positions for each of the CT inputs to
the relay, thus, in effect, providing auxiliary CTs which can correct any
deviation from the desired ratios
• In any case, even with these adjustments, there remains some residual
ratio mismatch, which leads to a small differential current id during
normal conditions
Differential Protection of Transformers
• The secondary of two CTs may not be the same and therefore, some
voltage may appear across the relay coil which lead to a current
flowing through the relay called Spill Current. The spill current is due
to the CT mismatch. The spill current can cause unlike operation of
differential relay in some cases when the relay setting is sensitive or
spill current is large enough compare to the relay pick up current
Transformation Errors
• The errors of transformation of the two CTs may differ from each other
and leading to significant differential current when there is normal load
Differential Protection of Transformers
Tap Changers
• If the power transformer is equipped with a tap changer, it will
introduce a main transformer ratio change when the taps are changed
Magnetization inrush
• This phenomenon occurs when a transformer is energized, or when the
primary voltage returns to its normal value after the clearance of an
external fault
• The magnetizing inrush produces a current flow into the primary
winding that does not have any equivalent in the secondary winding.
The net effect is thus similar to the situation when there is an internal
fault on the transformer
Differential Protection of Transformers
Determine: The CTs, the pickup setting and the percentage differential
slope for the relay (available slopes are 10, 20 and 40%). What is the level
of fault current, for an unloaded transformer, for which the differential
relay will not operate?
Example – cont.
The rated primary and secondary currents are 289.8A and 181.8A,
respectively. Therefore:
• We may select CT ratios of 300:5 and 200:5 for the two sides
• These will produce 289.8×5/300=4.83A, and 181.8×5/200=4.54A in
the two CT secondaries
In order to reduce a mismatch between these currents, we may use the
relay taps of 4.8 and 4.5 or the CT on the primary and secondary sides:
• This will give us a value of 4.83/4.8, or 1.0062×5A, and 4.54/4.5, or
1.009×5A in the relay coils
• Thus, the differential current in the relay due to CT ratio mismatch
would amount to 1.009-1.006=0.003pu, or about 0.3%
Example – cont.
• The tap changer will change the main transformer ratio by 5%, when it
is in its extreme tap position. Thus, a total differential current of 5.3%
would result from these two causes
• If no information on unequal CT errors is available, we must make
appropriate assumptions (e.g., 10%) to select a proper percentage slope
for the relay characteristic. Therefore, its reasonable to assume that
errors in two CTs will not differ from each other by more than 10%
under all fault conditions.
• This gives a net differential current of 15.3% for the largest external
fault, while the tap changer is at its farthest position
• With about a 5% margin of safety, we may therefore select a 20%
differential slope for the relay
Example – cont.
For the pickup setting, we may select the lightest available setting.
• A typical available value is 0.25A
• The compensating CT, corrects the ratio and cancel the spill current
• In the first configuration the zero sequence is eliminated by the main
CTs
• In the second configuration, the compensating CT, eliminates the zero
sequence
Filtering Zero Sequence Currents