Types of Flow Meters For Different Applications
Types of Flow Meters For Different Applications
When choosing a flow meter to buy, one should consider such intangible factors as familiarity of plant personnel, their experience with c and
maintenance, spare parts availability, and meant time between failure history, etc., at the particular plant site. It is also recommended that the
cost of the installation be computed only after taking these steps. One of the most common flow measurement mistakes is the reversal of this
sequence: instead of selecting a sensor which will perform properly, an attempt is made to justify the use of a device because it is less
expensive. Those “inexpensive” purchases can be the costliest installations.
The basic operating principle of differential pressure flow meters is based on the premise that the pressure drop across the meter is proportional to the square of the flow rat
extracting the square root.
Differential pressure flow meters, like most flow meters, have a primary and secondary element. The primary element causes a change in kinetic energy, which creates the d
the pipe size, flow conditions, and the liquid’s properties. And, the measurement accuracy of the element must be good over a reasonable range. The secondary element mea
is converted to the actual flow value.
In practice, the orifice plat is installed in the pipe between two flanges. Acting as the primary device, the orifice constricts the flow of liquid to produce a differential pressure
detect the difference. Major advantages of orifices are that they have no moving parts, and their cost does not increase significantly with pipe size.
Conical and quadrant orifices are relatively new. The units were developed primarily to measure liquids with low Reynolds numbers. Essentially constant flow coefficients can
upstream bevel, the depth and angle of which must be calculated and machined for each application.
The segmental wedge is a variation of the segmental orifice. It is a restriction orifice primarily designed to measure the flow of liquids containing solids. The unit has the abili
desired square-root relationship. Its design is simple, and there is only one critical dimension the wedge gap. Pressure drop through the unit is only about half that of conven
Integral wedge assemblies combine the wedge element and pressure taps into a one-piece pipe coupling bolted to a conventional pressure transmitter. No special piping or fi
Metering accuracy of all orifice flowmeters depends on the installation conditions, the orifice area ratio, and the physical properties of the liquid being measured.
The flowmeters have no moving parts. They can be installed in large diameter pipes using flanged, welded or threaded-end fittings. Four or more pressure taps are usually in
can be used with most liquids, including those having a high solids content.
Figure 1: Oscillating-piston meter operates on magnetic drive principle so that liquid will not come in contact with parts. A partition plate between inlet and outlet ports forces
through the outlet port. The motion of the oscillating piston in the unit is transferred to a magnetic assembly in the measuring chamber, which is coupled to a follower magnet
Oval-gear meters have two rotating, oval-shaped gears with synchronized, close fitting teeth. A fixed quantity of liquid passes through the meter for each revolution. Shaft
Nutating-disk meters have a moveable disk mounted on a concentric sphere located in a spherical side-walled chamber. The pressure of the liquid passing through the me
rotating about its own axis. It is the only moving part in the measuring chamber.
A pin extending perpendicularly from the disk is connected to a mechanical counter that monitors the disk's rocking motions. Each cycle is proportional to a specific quantity o
variations below a given threshold will affect measuring accuracies. Many sizes and capacities are available. The units can be made from a wide selection of construction mat
Rotary-vane meters are available in several designs, but they all operate on the same principle. The basic unit consists of an equally divided, rotating impeller (containing
impeller is in continuous contact with the casing. A fixed volume of liquid is swept to the meter's outlet from each compartment as the impeller rotates. The revolutions of the
Helix flow meters consist of two radically pitched helical rotors geared together, with a small clearance between the rotors and the casing. The two rotors displace liquid ax
The number of electrical pulses counted for a given period of time is directly proportional to flow volume. A tachometer can be added to measure the turbine's rotational spee
specified and installed, have good accuracy, particularly with low-viscosity liquids.
A major concern with turbine meters is bearing wear. A "bearingless" design has been developed to avoid this problem. Liquid entering the meter travels through the spiraling
acts on a sphere, causing it to orbit in the space between the first stator and a similarly spiraled second stator. The orbiting movement of the sphere is detected electronically
rate.
Figure 3: Vortex meters operate on the principle that when a non-streamlined object is placed in the middle of a flow stream, a series of vortices are shed alternately downstre
proportional to the velocity of the liquid flowing in the pipeline.
The three major components of the flowmeter are a bluff body strut-mounted across the flowmeter bore, a sensor to detect the presence of the vortex and to generate an el
whose output is proportional to the flow rate, Fig. 4. The meter is equally suitable for flow rate or flow totalization measurements. Use for slurries or high viscosity liquids is n
Figure 4
Magmeter
Electromagnetic meters can handle most liquids and slurries, providing that the material being metered is electrically conductive. The flow tube mounts directly in the pipe. P
length of pipe because there are no moving parts or obstructions to the flow. The voltmeter can be attached directly to the flow tube or can be mounted remotely and conne
Electromagnetic flow meters operate on Faraday's law of electromagnetic induction that states that a voltage will be induced when a conductor moves through a magnetic fie
energized coils outside the flow tube, Fig. 5. The amount of voltage produced is directly proportional to the flow rate. Two electrodes mounted in the pipe wall detect the volt
Figure 5: Major components of obstruction-free electromagnetic flow meter’s flow tube include electrodes and coils.
Electromagnetic flow meters have major advantages: They can measure difficult and corrosive liquids and slurries; and they can measure forward as well as reverse flow with
consumption, and the need to obtain a full pipe and no flow to initially set the meter to zero. Recent improvements have eliminated these problems. Pulse-type excitation tec
only half the time in the unit. Zero settings are no longer required.
A portable Doppler meter capable of being operated on AC power or from a rechargeable power pack has recently been developed. The sensing heads are simply clamped to
weight, including the case, is 22 lb. A set of 4 to 20 millampere output terminals permits the unit to be connected to a strip chart recorder or other remote device.
Time-of-travel meters have transducers mounted on each side of the pipe. The configuration is such that the sound waves traveling between the devices are at a 45 deg. ang
between the transducers increases or decreases with the direction of transmission and the velocity of the liquid being measured. A time-differential relationship proportional t
directions. A limitation of time-of-travel meters is that the liquids being measured must be relatively free of entrained gas or solids to minimize signal scattering and absorptio
Coriolis flow meters are true mass meters that measure the mass rate of flow directly as opposed to volumetric flow. Because mass does not change, the meter is linear with
eliminates the need to compensate for changing temperature and pressure conditions. The meter is especially useful for measuring liquids whose viscosity varies with velocity
mass meters that measure the mass rate of flow directly as opposed to volumetric flow. Because mass does not change, the meter is linear without having to be adjusted for
compensate for changing temperature and pressure conditions. The meter is especially useful for measuring liquids whose viscosity varies with velocity at given temperatures
Coriolis meters are also available in various designs. A popular unit consists of a U-shaped flow tube enclosed in a sensor housing connected to an electronics unit. The sensi
can be located up to 500 feet from the sensor.
Inside the sensor housing, the U-shaped flow tube is vibrated at its natural frequency by a magnetic device located at the bend of the tube. The vibration is similar to that of
about 80 times/sec. As the liquid flows through the tube, it is forced to take on the vertical movement of the tube, Fig. 7. When the tube is moving upward during half of its c
pushing down on the tube.
Figure 7
Having been forced upward, the liquid flowing out of the meter resists having its vertical motion decreased by pushing up on the tube. This action causes the tube to twist. W
vibration cycle, it twists in the opposite direction.
Having been forced upward, the liquid flowing out of the meter resists having its vertical motion decreased by pushing up on the tube. This action causes the tube to twist. W
vibration cycle, it twists in the opposite direction. The ammount of twist is directly proportional to the mass flow rate of the liquid flowing through the tube. Magnetic sensors
which change as the tube twists. The sensors feed this information to the electronics unit, where it is processed and converted to a voltage proportional to mass flow rate. Th
to liquid nitrogen.
Thermal-type mass flowmeters have traditionally been used for gas measurements, but designs for liquid flow measurements are available. These mass meters also operate i
heated sensing element isolated from the fluid flow path. The flow stream conducts heat from the sensing element. The conducted heat is directly proportional to the mass f
electronics package includes the flow analyzer, temperature compensator, and a signal conditioner that provides a linear output directly proportional to mass flow.
RELATED PRODUCTS
Learn more about the FTB300_Series
Low Flow Indicating Paddlewheel Flow Meter
ORDER NOW
Related articles to:
Types of Flow Meters for Different Applications
Product Info What Is An Anemometer And What Does It Technical Learning Doppler Me
Measure? Meters
Introduction to Air Velocity Measurement
Flow Measurement
RELATED PRODUCTS
Learn more about the FTB300_Series
Low Flow Indicating Paddlewheel Flow Meter
ORDER NOW