Test Report
Test Report
Sr.
Name of Test Brief Procedure & Specified value Results
No.
Interlock is working
Interlock:-ON/OFF the circuit breaker 5 times.
in ON Position
2 Mechanical
Operation Test Operating mechanism Test: - Open & Close Circuit breaker
Properly operate
05 times. The mechanical operation should work Properly.
Visual Inspection
& Verification of As per approved Drawing. Result Attached
5
Dimension.
3. Energy Meter:
Make Honeywell Model AS3500
Sr. No. 0703 0294 Accuracy Class 0.5
RELAY TESTS
Relay Make: DELAB
Model: DP-34
Sr. No: 146374-F
1. Characteristics Test
CT Ratio 200/5 A, In: 5A O/C Plug Setting at = 0.50 In, E/F Plug Setting at = 0.10 In
(A) O/C & E/F Test
Apply particular current with primary current injection set and measure
Operating time at trip terminal with timer.
Specified operative Applied current Specified operating time at Measured
Element
current multiple setting in Amp. Max. time setting in Sec. Values (Sec.)
R-Y 200x0.50=100 Amp 0.00 ~ 3.00 Sec
Y-B 200x0.50=100 Amp 0.00 ~ 3.00 Sec
B-R 200x0.50=100 Amp 0.00 ~ 3.00 Sec
E/F 200x0.10=20 Amp 0.00 ~ 3.00 Sec
(B) INTANTANEOUS ELEMENT TESTS. Setting at = 4 x In In = 5A
Element Sec. Current Test
R-Y Instantaneous
Y-B Instantaneous
B-R Instantaneous
E/F Instantaneous