05 - para Load Share Rev 2 (2019)
05 - para Load Share Rev 2 (2019)
PARALLELING &
LOAD SHARING
CONTENT
01 | Generating Requirements
02 | Paralleling
03 | Synchronising
04 | Out of Phase
05 | Synchronising Aids
06 | Droop
07 | Isochronous Operation
08 | Loss of Excitation
2
Electrical Systems
Generating Requirements – I
SOLAS – part D Regulation 40
Electrical installations shall be such that:
• Incoming machine
– Same speed (frequency) as switchboard busbars
(usually a bit faster)
– Same voltage as switchboard busbars (4% - 5% deviation
is acceptable, however the closer the better)
– Instantaneous voltages in phase…
Out Of Phase Effect
Bus-Bar: RED Incoming Machine: BLUE (ish)
Synchro Switch
Incoming Generator
Analogue
Synchroscope
Analogue Synchroscope
There are two coils;
When commissioning it is
important to check the position of
the needle at synchronism as
indicated by independent means.
If the needle points to 6 0’clock at
synchronism, the busbar
connections must be reversed.
The digital synchroscope consists of a
Digital Synchroscope series of LED indicator lamps
arranged to show the phase angle
between the incoming and busbar
frequencies
Synchroniser
In addition an
“auto–
synchroniser” will
have a similar
layout, with the
addition of circuits
for remote control of
prime mover speed Breaker Close
and AVR trimmer. Close Enable
Switch
Often combined with
a power Control Voltage
management
system…
20
SYNCHRONISING LAMPS
Synchronising Lamps
Negative
Positive voltage greater in magnitude than the previous positive one
VRED – VBLUE = 0V
Disadvantages: Not always easy to tell when lamps are totally extinguished…
Incoming Generator
Lamps Bright Lamps are connected across different phases
Incoming Generator
3 – Lamp Sequence
Synchronism is indicated by the top lamp being extinguished and the other two lamps being of
equal brightness
Incoming Generator
Emergency Synchronising
If we have a failure of both the synchroscope and the sync lamps, can we parallel
machines?
Yes
- but with extreme caution
The voltmeter is attached across one phase as shown on the next slide – hence the caution!...
Emergency Synchronising
Incoming Generator
Paralleling
Paralleling Procedure
Let us assume that the checks on the generator have been
completed and the engine is up and running
No 1 Geny No 2 Geny
35
With Droop
No 1 Geny No 2 Geny
36
Droop Characteristic Effects
60 Hz 60 Hz
4%
Generator speed
Generator 1 speed
Generator 2 speed
Base line represents load share
of each generator
60 Hz 60 Hz
Generator 1 speed
Generator 2 speed
50 % 50 %
Switchboard Load
Generator 1 Load 100 %
100% Generator 2 Load
39
Droop Characteristic Effects
Generator 1 speed Generator 2 speed
4% Droop 2% Droop
If both machines have
different droop
characteristics, then when 60 Hz 60 Hz
loaded up they will not
share load equally
60 Hz 60 Hz
Switchboard Load
No1 Isochronous & No2 with Droop
60 Hz 60 Hz
Switchboard Load
L O S S O F E X C I TAT I O N
Loss Of Excitation
• Single Generator Operation
– Collapse of voltage output
– Trip on under voltage
• Parallel Operation
– Affected machine draws its excitation from the other running generator
– Both generator currents rise rapidly
– Excitation failure trip / overcurrent trip should operate & possible overload
situation
– If good generator trips first then this will deprive the other machine of
excitation resulting in it tripping and causing a blackout…
Finally … For Parallel Operation
• kW load share:
– Controlled by fuel input, and therefore the governor settings