161KV High Voltage
161KV High Voltage
College of Engineering
Title
By
Supervisor
Hebron,May 2017
I
Abstract
This project is a Design of High Voltage Transmission system with 161KV and 1GW
between Hebron and Al Ezaria City using E-TAP Simulator, assessment program, and
tools. The core of the project is to Study, Calculate and Simulate all needed of electrical,
mechanical parameter and geographical data .using the E-TAP Simulator program which
has Simulation property, which allows us to analyze and study status of the network more
accurately.
This design faced some problems such as estimation of the load consumption to the
year of 2050, huge amount of current transfer and varied topography in the designed re-
gion. So the solution was to make an estimate of the annual consumption beyond 2016
based on Statistics taken from the Palestinian Bureau of Statistics from 1996 to 2015.
In addition, there is an Effect for mechanical force such as weight, tension and con-
ductor elongation due to change in temperature of surrounded , Number ,type of the steel
tower , install and balanced all devices along the track for line over boundary of the region
,spacing between all component of the system .
For protection, the problem was in the Type, amount, rating, and location of the
protection devices to operate the transmission line in the highest stability and reliability
status.
And finally to approximate the cost of construction for the transmission line per kilo-
meter.
II
Ï@
jÊÖ
, éK
P Q
ªË@ð ÉJ
Êm Ì '@ ú
æJK
YÓ á
K. 1GW ð 161KV ú
ÍA« Yêk. É® K ¡m Ì Õæ
Ò ñë ¨ðQåÖÏ @ @ Yêë
. èY«AÖÏ @ H@ ð XB@ ªK . ð , èY«AÓ l× @QK. ð ( E-TAP Simulator ) È@ l× AKQK
.
. . Ð@YjJAK. ½Ë Xð
éJ
ºJ
KA¾J
ÖÏ @ð éJ
KAK
QêºË@ ÉÓ@ñªË@ ©JÔg èA¿Am× ð H Akð é@ P X ñë ¨ðQåÖÏ @ @ Yë áÓ ¬YêË@
.
. .
ÊË AJË iJK ( E-TAP) È@ l× AK Q¯ , èQ¯ñ JÖÏ @ éJ ¯@ Qªm Ì '@ HAÓñʪÖ
éºJ . é@P X ð ÉJ
Êm' ÉÔ« éJ
KA¾Ó@
. .
. Ï @ð
.YÒJªÓð J
¯X ɾ .
QK
Y® JË@ ñë AêÒë @ áÓ àA¿ ú
æË@ð É¿ AÖ Ï @ ªK . AJ Jêk. @ð É® JË@ ¡m Ì ÕæÒJË@ ú¯ ÉÒªË@ ÈCgð
éJ
ÒºË@ ½Ë Y»ð ,2050 ÐA« úæk AîE. ÉÒªK úæË@ 鮢 JÖ Ï @ ú¯ é¯A¢ÊË ÐAªË@ ¼CîDCË iJ
jË@
ÐAªË@ ¼CîDCË QK
Y®K ÉÒªK. ÉmÌ '@ àA¿ ½Ë YË , 鮢JÖÏ @ è Yë ú
¯ éÊ®K éJ
®J
»ð ,ù
KAK. QêºË@ PAJ
JÊË èQ
J.ºË@
ÐA« úæk 1996 ÐA« áÓ úæJ
¢Ê®Ë@ ZAkB@ èQK@X
áÓ èQ¯ñ JÖÏ @ HAJ
KAkB@ úÎ « XAÒ J«BAK. é¯A¢ÊË
«
. èPY®Ö Ï @ éÒJ
®Ë@ á
J.K
úæj JÓ ÉÔ ð Ecexl l×. AKQK . úΫ AêËAgXAK ½Ë Xð ,2015
.
è Yë PQK
. @ áÓð , AJ Jêk. @ð úæË@ HAJ PQK
. ®ªË@
. @ áÓ I KA¿ éJ
ºJ
KA¾J
ÖÏ @ øñ®Ë@ H@ Q
K AK à
@ àAÒ»
ÉJÓB@ ¨ñJË@ ð áÓ jÖÏ @ èP@QmÌ '@ QK
AK Im J@ð YË@ ð à PñË@
QË@ ð é¢J
' HCñÖ Ï @ éËA¢ : ÉÓ@ñªË@
PAÖÏ @ Èñ£ úΫ iJ
m ɾ . AîDK P@ ñÓð AîDJ
J.K é®K
Q£ð h. @QK. B@ ½Ë@ Y»ð AëXY«ð HCñÒÊË
.AêªñË ÉJÓB@ HA ¯AÖ Ï @ð XYjÖÏ @
,AîDJ Ò» , ÐA¢ JÊË ÉJÓ B@
YjJË@ àA ¯ , éK
AÒmÌ '@ m
' AÒJ
¯ AÓ
@
½Ë Y»ð
èQêk. B@ ¨ñK PAJ
JkAK . I KA¿ HAK
èZA®» Q»
AK ÉÒªË@ ¡m Ì '@ ©J¢ ú¾Ë éK AÔg Q»
@ð Z@X
@ É ¯@ Õç' Y® JË AêË IAJÖ Ï @ ©¯ñÖ Ï @ð QK Y® JË@
. .
.
.
m'. éJ
¯ñKñÓ Q» @ð éJºÜ
. éJ
Ê« XAÒJ«B@ AJ JºÖ ß
IJ Ø
éK
XAJ¯B@ H@ Q
K Y® JË@ ùë ÕæÒ ø
@ ú¯ èXA« ÑëB@ éÊ¾Ö Ï @ àA ¯ , J . AÓ úÍ@ é¯A BAK .
III
Dedicated
TO
Our Friends
And
Bahaá
&
Yazeed
&
Youssef
IV
Acknowledgment
Our Appreciation To
Palestine Polytechnic University
College of Engineering and Technology
Department of Electrical Power Engineering
Our Supervisor Eng.Nizar Amro
V
Contents
Abstract I
Dedicated III
Acknowledgment IV
1 Introduction 1
1.1 Overview : . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Project General Description : . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.3 Project scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.4 Project Methodology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.5 Other Study . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3 Steel Tower 13
3.1 Transmission Tower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.2 Types of transmission towers. . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.3 Tower Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4 Protection Device 16
4.1 Faults Classification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.2 Requirements of Protection System . . . . . . . . . . . . . . . . . . . . . . 17
4.3 Types of protection devices . . . . . . . . . . . . . . . . . . . . . . . . . . 17
6 Economy 34
6.1 Capital Cost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
6.2 Operation and maintenance costs . . . . . . . . . . . . . . . . . . . . . . . 35
6.3 Energy loss costs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.4 Conductor Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
7 E-TAP Program 38
7.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.2 ETAP Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
7.3 Filling data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
7.3.1 Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
7.3.2 Transmission line . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
7.3.3 Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
7.4 Single Line Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
7.5 E-TAP Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
8 GIS &Sketch up 46
8.1 GIS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
8.2 Sketch up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
References 49
A Load Growth i
List of Figures
List of Tables
Chapter 1
Introduction
1.1 Overview :
The main idea of this project is Design of High Voltage Transmission Line 161KV and1
GW double circuit Between Hebron and Al Eizariya by Using E-TAP Simulator program,
then making the essential calculation and analysis for the transmission line such as esti-
mate the consumption, mechanical and electrical calculation, and reduction effect of the
corona.
In our project we will Simulate, Analyze the transmission system, detect all problems
and suggest the best solutions.
The project adopts on investigation and analysis of transmission network after plot it
on the simulator program , the program capabilities and properties allow us to study the
network from many side after make it ,show the status of the network component ,solve
the existing problems and weakness in the network .
2. Estimate the cost of this project and the benefits can get.
CHAPTER 1. INTRODUCTION 2
3. Detect most problem can may face us in the network and make strategy prevent it
to happen.
Chapter 2
A transmission line is the bulk transfer of electrical energy, from generating power plant
to electrical substations located near demand centers. [2, 5, 6, 4]
• Conductor
The electricity is transmitted at high voltages to reduce the energy lost in long
distance transmission.
• Spacers
Spacers are designed to keep the individual wires in a bundle separated by a fixed
distance.
• Insulators
Transmission line insulators are devices used to contain, separate or support elec-
trical conductors on high voltage electricity supply networks.
2. However, aluminum conductor have completely replaced Coper for over head line
because of the much lower cost and lighter weight of an aluminum conductor com-
pared with a coper conductor of the same resistance
Advantage
(a) It has lesser strength and more sag per span length than any other category
(b) Cost of ACSR is equal to AAC.
Advantage
Advantage
1. Weight of conductor.
2. Location of conductor.
3. Length of span.
4. Temperature.
5. Tensile strength.
6. Tension.
Here we discuss briefly about various factors sag and tension in electrical transmission
lines .
CHAPTER 2. CONDUCTOR AND INSULATOR 6
• Length of span Sag is proportional to the square of length of span . Hence, longer
the span greater will be the sag provided the tension and weight of the conductor
is constant.
• Temperature The value of sag greatly affected by the temperature. If the tem-
perature is high sag will be more because rise in temperature causes the conductors
to expand. Is the temperature is low, the conductor (being metallic) contracts and
hence sag is less due to which the tension in the conductor is increases.
• Tensile strength Sag inversely proportional to the tensile strength of the conductor
provided the other parameters are constant.
Sag Calculate
Sag calculation is classified to two cases:
Let
L= Length of span.
w = Weight per unit length of conductor.
T = Tension in the conductor.
Now consider any point on the conductor.Lets say point ’P’.By considering lowest point
O as the origin, let the co-ordinates of point P be x and y. Assuming that the curvature
is so small that curved length is equal to its horizontal projection (i.e., OP = x), the two
forces acting on the portion OP of the conductor are :
Consider a conductor suspended between two supports A and B which are at different
levels as shown in the following figure.
Let
L = Span length
h = Difference in levels between two supports
x1 = Distance of support at lower level (i.e., A) from O
x2 = Distance of support at higher level (i.e. B) from O
T = Tension in the conductor.
w = the weight per unit length of the conductor
s1 = sag at point A .
s2 = sag at point B.
wx21
S1 = (2.5)
2T
wx22
S2 = (2.6)
2T
also
x1 + x2 = l
then ,
l Th
X1 = − (2.7)
2 wl
l Th
X2 = + (2.8)
2 wl
• Wind force acts on the conductor to change the conductor self weight per unit length
horizontally in the direction of the air flow.
CHAPTER 2. CONDUCTOR AND INSULATOR 9
• Ice loading acts on the conductor to change the conductor self weight per unit length
vertically downward.
• Considering wind force and ice loading both at a time, the conductor will have a
resultant weight per unit length.
• The resultant weight will create an angle with the ice loading down ward direction.
Let us assume, w is the weight of the conductor per unit length. wi is the weight of ice
per unit length
wi = density of ice × volume of ice per unit (2.9)
= density of ice × πt(t + d)
where ,
density of ice =0.9167 g cm3
t = thickness of the coating ice = 0.5 cm.
d = diameter of the conductor = 20.46 mm.
the expression for sag and tension derived was under normal conditions at normal temper-
ature and the weight acting on the conductor was only its own weight. But in cold places
there is a ice coating formed on the conductor and also wind pressure nets horizontally
on the line conductor. The ice coating on the line conductor increases the total diameter
of the conductor and also the weight of the Conductor increases.
The total weight of the conductor i.e., both the conductor weight and the weight of the
ice acts vertically downwards whereas the wind force acts horizontally on the conductor.
Therefore, the vector sum of horizontal and vertical forces acting on the conductor gives
the total force shown in figure
W = weightof conductorperunitlength
= conductor material density × volume per unit length
q
Wt = (W + W i)2 + (W w)2 (2.10)
2.3 Corona
It is defined as ionization of air due to higher voltage (usually voltage above critical
voltage) which causes violet light around the conductor and hissing sound. It also produces
ozone gas therefore it is undesirable condition.
An increase in diameter reduces the surface field gradient and it helps to decrease
the Corona loss. Higher is the conductor size, the greater is the probability of
roughness of the conductor . the probability of increased corona loss is thus directly
related with the conductor surface for increased sizes of the conductors.
2.4 Insulator
An electrical insulator is a material whose internal electric charges do not flow freely, and
therefore make it nearly impossible to conduct an electric current under the influence of
an electric field. This contrasts with other materials, semiconductors and conductors,
which conduct electric current more easily. [7]
2. It must have very high dielectric strength to withstand the voltage stresses in High
Voltage system.
3. It must possesses high Insulation Resistance to prevent leakage current to the earth.
6. There must not be any entrance on the surface of electrical insulator so that the
moisture or gases can enter in it.
be glazed enough so that water should not be traced on it. Porcelain also should be free
from porosity since porosity is the main cause of deterioration of its dielectric property. It
must also be free from any impurity and air bubble inside the material which may affect
the insulator properties.
Glass Insulator
Now days glass insulator has become popular in transmission and distribution system.Annealed
tough glass is used for insulation purpose . Glass insulator has numbers of advantages
over conventional porcelain insulator.
Polymer Insulator In a polymer insulator has two parts, one is glass fiber reinforced
epoxy resin rod shaped core and other is silicone rubber or EPDM (Ethylene Propylene
Diene Monomer) made weather sheds. Rod shaped core is covered by weather sheds.
Weather sheds protect the insulator core from outside environment. As it is made of two
parts, core and weather sheds, polymer insulator is also called composite insulator. The
rod shaped core is fixed with Hop dip galvanized cast steel made end fittings in both sides.
Advantages of Polymer Insulator
• Because of lighter in weight and smaller in size, this insulator has lower installation
cost.
• Due to lighter weight polymer insulator imposes less load to the supporting struc-
ture.
• Moisture may enter in the core if there is any unwanted gap between core and
weather sheds. This may cause electrical failure of the insulator.
• Over crimping in end fittings may result to cracks in the core which leads to me-
chanical failure of polymer insulator
13
Chapter 3
Steel Tower
Chapter 4
Protection Device
Power-system protection is a branch of electrical power engineering that deals with the
protection of electrical power systems from faults. The objective of a protection scheme
is to keep the power system stable and to minimize the damage of the equipments and
property that would be caused by system faults, and maintain the delivery of electrical
energy to the consumers and protect humans from any electrical risks.[9, 10, 11, 2, 4]
• Symmetrical Faults.
In the balanced system the system impedance in each phase are identical and the
three-phase voltages and currents through the system are completely balanced.
Faults under symmetrical conditions are caused in the system accidentally through:
• Asymmetrical Faults.
Unbalanced system can result due to unsymmetrical faults, then system operation
may also become unbalanced when load not balanced. Most faults in the system
are unsymmetrical so it’s very important to pay attention.
Faults may occur as a cross country fault. Phase to earth fault has a current that
depends on the earthling system. Most faults on the transmission lines are caused by
lightning which results in the flash over of insulations.
• Selectivity: The circuit breaker must be able to detect and isolate the fault item
only.
• Fast operating: It means the ability of the protection system to isolate the faulty
part quickly, which leads to minimize the effect of the fault and increase the stability
of the power system.
• Economical It means obtaining the maximum protection with lower cost, but we
have to use a high quality protection devices which means more cost needed.
the spark resulting from arc. Accordingly, there are four types of circuit breakers are:
(a) Oil circuit breakers The oil circuit breaker is widely used in industrial fields.
This type used the oil in the process of extinguish the electrical spark when the
electric arc occurrence of bubbles forming working to extinguish the sparks.
(b) Air-blast circuit breakers
These circuit breaker used mainly in the high voltage applications. When the
fault happens cause separate the contacts then the electric arc is formed and
this leads to rush of air which acts to cool the spark and thus extinguish.
(c) Sulphur hexafluoride circuit breakers
This type of circuit breakers used SF6 gas, which has a great tendency to gain
electrons . Upon separation of the gas starts to flow contractors transforms
gas to negative ions. Lost electrons leads to the weakening of the electric arc
and thus extinguish the spark.
(d) Vacuum circuit a breaker
In this type of circuit breakers uses a vacuum that could be up to 10-7 Tor.
This vacuum provides a very high isolation. This isolation leads to extinguish
the spark too quickly.
2. Autorecloser
Is a self-controlling circuit breaker equipped with mechanism to being able to re-
connect the circuit after separating because of a fault in the system.
3. Current transformer (CT)
This type of transformer is used within the system of equipment protection. This
transformer works to step down the current that flowing in it for measurement
processes and also protect protection devices where this transformer connected in
series with an electrical system.
4. Voltage transformer
Like the current transformer, this transformer works to step down the voltage be-
tween its parties for different measurement processes where the transformer is con-
nected in parallel with the system.
5. Surge Arresters
Surge arresters are equipment used to eliminate the sudden impact of the lightning
on the system. Surge arresters used to protect a variety of devices and equipment
in the transmission system such as transformers.
6. Relays
Relays are developed and installed to protect the lines. The transmission line pro-
tection Relays, in the industry, are based on the fundamental frequency components
of the voltages and currents.
Principle of Operation
Where;
• Protective relay.
• Circuit breaker (CB).
• Current transformer (CT).
• Voltage transformer (VT)
• Coil of tripping the CB.
• Battery.
• Auxiliary switch.
• Circuit of tripping the CB
In summary the basic function of protection is to detect faults and to clear them as
soon as possible. It is also important that in the process the minimum amount of
equipment should be disconnected. Faults cause large amounts of currents to flow in
the components that would burn out if current flows are not promptly interrupted.
The voltages of the faulted phases decrease on the occurrence of a fault.
7. Protection zone:
As mentioned before, the aims of the power system is to generate, transmit, and
distribute the electrical energy, these aims need several equipment such as genera-
tors, transformers, transmission lines all these equipment are important so we have
to protect it to provide a continuity and safety supplying. We cannot protect it
randomly, so we divide the system into zones each zone called protection zone. The
figure below shows a simple power system divided into protection zones.
CHAPTER 4. PROTECTION DEVICE 20
Chapter 5
We noticed that the current is too high and the cross section area for the chosen
conductor is too large ,so we decides to choose double circuit, and the current will
be
I
Icircuit = = 1948.93A (5.3)
2
Even after selecting to divide the current into two circuits the current still high so
we decided to use three bundles for each phase
Icircuit
Ibundle = = 649.64A (5.4)
2
For ground conductor Usually for selection the ground conductor we take the half
of the bundle current referred to equation
Ibundle
Iground = = 324.82A (5.5)
2
Referred to the ACSR product catalog ,We choose Pigeon conductor
And we chose polymer insulator as the data sheet in the appendix The polymer
catalog number is 5110091201
where
gd = disruptive critical voltage gradient (Crest KV/cm)
md = roughness factor =0.98 to 0.93 for roughened and weather wires
r = radius of the conductor
δ = relative air density
D = separation between phase wire
Disruptive critical voltage ( The Peel’s formula )
D
Vd = 123 md r δ log KV to neutral (RM S) (5.7)
r
• The dielectric of air is proportional to its relative air density (δ)
where
0.386p
δ= (5.8)
273 + t
where
p = atmospheric pressure (mm of Hg )
t = temperature pressure (C)
When
p=950 mm of Hg, t =25 c ;
δ = 1.23
note :
1. Any increase in temperature raises ionisation and Corona starts at lower
voltage
2.any decrease in pressure increases the Volume and decreases the density .This
result in increased free-paths and there for decreased ionsation .
CHAPTER 5. DESIGN OF THE TRANSMISSION LINE SYSTEM 24
when
D = 31 cm , r = 1.023 cm , δ = 1.23 , md = 0.95,
31
Vd = 123 × 0.95 × 1.023 × 1.25 log( ) = 221.36 KV to neutral
1.023
Vd = 383.41 KV to line (RM S)
when
161
D = ? cm , r = 1.023 cm , δ = 1.23 , md = 0.95, Vd = √
3
= 93KV to neutral
V
( 123 md )
D = r 10 drδ = 4.29 cm
• The vertical distance between the first cross-arm and the second cross-arm =
5.085 m.
• The vertical distance between the second cross-arm and the third cross-arm =
5.085 m.
• The vertical distance between the third cross-arm and the ground = 19 m.
• The horizontal distance between the first circuit and, the second circuit = 1.1
m.
• The horizontal distance from the end of cross arm to the tower cage = 4.2 m.
• The height of the tower = 30 m.
• The horizontal distance between the tower legs = 4 m.
• weight of the tower =2570kg.
Table 5.2: Clearance (in [m]unit) from line with highest system voltage of:
To ground in unobstructed
countryside 6.2
To rock face or
steep slope 3.2
• Suspension towers.
• Tension towers.
• Angle towers.
• End tower.
Tension
w g L2
T =
8S
where ,
w= weigh of conductor per unit length (kg/m)
L= span of the conductor (m)
g = gravitational constant ( 9.81 N)
S= sag(m)
w=926.5kg/km
L=350m
g=9.81N
so,
we take the min. sag = 3m.
so,
the tension
926.5kg/km × 9.81 × 3502
T = = 46.39 kN f or each conductor.
8.3
For the sag, we take the min. sag which give the max tension.
Guy and stay wire
Stay wires or guys wire are galvanized steel wire strands that are used for sustaining
mechanical load. Generally, they are made up of 6 wires stranded around 1 wire,
twisting 7 wires together.
CHAPTER 5. DESIGN OF THE TRANSMISSION LINE SYSTEM 27
T1 h1 + T2 h2 + T3 h3
Th = (5.10)
hg
1
Th = (46.39 × 29 + 46.39 × 24 + 46.39 × 19) = 222.672 KN.
15
Where,
Th= is the horizontal component of guy wire tension.
T1 =is the horizontal load at height h1.
T2 =is the horizontal load at height h2.
T3 =is the horizontal load at height h3.
hg= is the height of attachment point of guy.
h1 =is the height of horizontal load T1.
h2 =is the height of horizontal load T2.
h3 =is the height of horizontal load T3.
hg
tan β = (5.11)
L
15
tan β = =3
5
hg
β = arctan = 71.5
L
This tension will be for the first guy for the first circuit, we will use two guy wire for
the tower who will have tension from one side or, tension from two side but, with
angle between them.
Tower grounding
Used to reduce earth wire potential and stress on insulators at the time of stroke
and also for safety.
Tower footing resistance will be 10 and should not be more than 20Ω under any
condition throughout the year.
Earth resistance depend upon soil resistivity (general 100 Ω-m).
• For rocky soil. The dimension for this base is (6.5×6.5)m in X-Y,with depth
3.5 m.
• For sandy soil. The dimension for this base is (7.5×7.5) m in X-Y, with depth
4 m.
• For rocky soil. The dimension for this base is (55) m in X-Y, with depth 2.5
m.
• For sandy soil. The dimension for this base is (66) m in X-Y, with depth 3 m.
The differential protection is used for the very high devices cost such as power
transformer which have rating higher than 5 MVA because the cost of this system
is very high and there are two type of this protection:
(a) Balanced current The principle of this type of protection system is shown in
the figure. The current transformers are connected in series with the system.
The Relay connected across the midpoint between them and the voltage on
the relay is equal zero. When the fault occurs outside the protective zone,
there is no current flow through the relay. So the differential relay does not
activate. In the case of the fault occurs inside the protective zone, the difference
between the current that flow in the CTs is flow through the relay then the
relay interrupted the circuit as shown in the figure.
CHAPTER 5. DESIGN OF THE TRANSMISSION LINE SYSTEM 30
(b) Balanced voltage In this type of differential protection, the current flow
the current transformers produce a voltage on the relays. The voltage on the
two relays is equal when the occurrence of the fault is outside the protective
zone. Accordingly, the Relay does not activate. But if the fault occurs inside
protective zone there is difference in the value of current in the secondary of
CTs. And therefore the relay activate and make interruption in the circuit as
shown in the figure.
Figure 5.6: the relay activate and make interruption in the circuit
Distance zone is non-unit protection, i.e., the protection zone is not exact. The dis-
tance protection is high-speed protection and is simply to apply. It can be employed as
a primary as well as backup protection. It is very commonly used in the protection of
transmission lines.
Distance relays are used for both phase fault and ground fault protection, and they
provide higher speed for clearing the fault. It is also independent of changes in the
magnitude of the short circuits, current and hence they are not much affected by the
change in the generation capacity and the system configuration. Thus, they eliminate
long clearing times for the fault near the power sources required by over current relay if
used for the purpose.
Design
Distance protection is so called because it is based on an electrical measure of distance
along a transmission line to a fault. The distance along the transmission line is directly
proportional to the series electrical impedance of the transmission line. Impedance is
defined as the ratio of voltage to current. Therefore, distance protection measures distance
to a fault by means of a measured voltage to measured current ratio computation the
philosophy of setting relay at Sonelgaz Group is three forward zones and one reverse zone
to protect HV transmission line between bus bar A and B with total impedance ZAB as
shown in figure.
In our design, we used a distance relay every 5 km. Every relay has four zones, three
of them used for forward protection, the fourth one used as a reverse protection.
First zone In practice it is normal to adjust the first zone relays (Z1) at A to protect
only up to 80% of the protective line (AB). This is a high speed unit and is used for the
primary protection of the protected line. This unit is not set to protect the entire line
to avoid undesired tripping due to over reach. Over reach may occur due to transients
during the fault condition.
CHAPTER 5. DESIGN OF THE TRANSMISSION LINE SYSTEM 32
Second zone It is set to cover about 20% of the second line (BC). The main object
of the second zone unit is to provide protection to the end zone of the first section which
is beyond the reach of the first unit. The setting of the second unit is so adjusted that it
operates the relay even for arcing faults at the end of the line. To achieve this, the unit
must take care beyond the end of the line. In other words its setting must take care of
under reach caused by arc resistance.
Under reach is also caused by intermediate current sources, errors in CT, and VT and
measurement performed by the relay. To take into account the under reaching tendency
caused by these factors, the normal practice is to set the second zone reach up to 20% of
the shortest adjoining line section. The protective zone of the second unit is known as
the second zone of protection. The second zone unit operates after a certain time delay.
Its operating time is 0,3 sec.
Third zone It is provided for back-up protection of the adjoining line. Its reach should
extend beyond the end of the adjoining line under the maximum under reach, which may
be caused by arcs, intermediate current sources and errors in CT, VT and measuring unit
The protective zone of the third stage is known as the third zone of protection.
Figure 5.8: Characteristic curve X (R) for setting zones for distance protection.
Figure represents the tripping time T1, T2 and T3 correspond to these three zones of
operation for circuit breaker installed at bus-bar A and MHO distance relay (RA).
The fourth setting zones for protected transmission line (forward and reverse) without
series FACTS.
ZAB = KZ ZL
KV T
KZ =
KCT
Where, ZAB is real total impedance of line AB, and KVT and KCT is ratio of voltage to
current respectively.
34
Chapter 6
Economy
The transmission line Life cycle costing model helps in accessing the total cost of owner-
ship of the project from the beginning to the end of its operational life covering various
stages like design, construction, operation and maintenance, and repair of the line . Each
transmission line project is unique and depends on the geography, regulations and lo-
cal conditions. The factors which influence the life cycle costs also vary from project to
project. The typical transmission line life cycle cost model incorporating various stages
is given by
(1 + i)2 − 1
P V of COM = COM (6.2)
i (1 + i)2
CHAPTER 6. ECONOMY 36
where, CIL is the initial cost of losses, I is the peak load current in amperes, R is the
resistance of the conductor in Ω/km, CIE is the incremental cost of energy in $/kWh and
Lf is the loss factor. The cost of losses for any year during the useful life can be calculated
using
CLn = CIL × CEE × Lg (6.5)
where, CLn is the cost of losses for any year n, CIL is the initial cost of losses, CEE is the
energy cost escalation and Lg is the load growth. [13]
P
P loss = I 2 R = ( √ )2 R
3 V cos θ
1
P loss ∝
V
CHAPTER 6. ECONOMY 37
Then
s
KV A
Veconomical = 5.5 L + KV
150
Where,
L:length of the line
KVA:transmitted /circuit.
OR
s
KW
Veconomical = 5.5 L + KV
100
•
M
T otal Cost = KA + +N $/annual
A
hr: working hours/annual =8760hr
Then, s
M
(Economical Area)A = (6.6)
K
Then,
R ckwhr
(Economical Area) = I 2 (hr)2 (6.7)
s.w L cunit
Then, s
M √
Cost of Conductor material = Cc = k = MK (6.8)
K
And also = cost of energy loss
N is Constant ,Then N = k A
M
T otal Cost = K 0 A + (6.9)
A
Where K 0 = k + K, K0 > K
38
Chapter 7
E-TAP Program
7.1 Introduction
ETAP Power Station is a fully graphical electrical transient analyzer program that can
run under the Microsoft Windows 98. NT. 4.0. 2000. Me. and XP environments. The
Windows NT, 4.0 and 2000 platforms provide the highest performance level for demanding
applications, such as large network analysis requiring intensive computation and online
monitoring and control applications.
Windows NT. 4.0. And 2000 also provide the highest levels of reliability, protec-
tion. And security of critical applications. Large Power Station projects (approximately
500 buses and larger) should be built and maintained via Windows NT. 4.0. Or 2000.
The Windows 98 and me platforms provide excellent performance for analysis of small
and medium size systems (a few hundred buses) and support a variety of other popular
applications.
7.3.1 Transformers
From the data for transformer Specifications and data we can fill this parameter rating.
In the E-TAP window below shows voltage rating and power rating that needed for power
flow calculation and short circuit analysis.
7.3.3 Load
In the following parameter that concerning load we put the power in MVA for lumped load
rating and choose a value of resistive load between 15% and 20% in domestic transformer
and smaller or larger value of ” R ” percentage in the industrial region because of induction
and synchronous motors, the E-TAP window show the parameter that filled for a Sponge
factory.
Chapter 8
GIS &Sketch up
8.1 GIS
A geographic information system (GIS) is a system designed to capture, store, manipu-
late, analyze, manage, and present spatial or geographic data.
The acronym GIS is sometimes used for geographic information science (GIScience) to
refer to the academic discipline that studies geographic information systems and is a large
domain within the broader academic discipline of Geo informatics.
GIS applications are tools that allow users to create interactive queries (user-created
searches), analyze spatial information, edit data in maps, and present the results of all
these operations. Geographic information science is the science underlying geographic
concepts, applications, and systems. To more details and Tower Coordination see ap-
pendix B
8.2 Sketch up
is a 3D modeling computer program for a wide range of drawing applications such as
architectural, interior design, landscape architecture, civil , mechanical and electrical
engineering . The program includes drawing layout functionality, allows surface rendering
in variable ” styles ”, supports third-party ”plug-in” programs hosted on a site called
Extension Warehouse to provide other capabilities.
Refrences
[1] Bougue, Michel, F Mariani, and S Bisnath. High Voltage Overhead Power Lines.
Johannesburg, South Africa: Crown Publications, 2010. Print.
[2] Mehta, V.K. and Mehta, R. (2005) Principles of power system: (including generation,
transmission, distribution, switchgear and protection). 4th edn. New Delhi: Chand (S.)
& Co Ltd ,India.
[3] Policy, IEEE-SA Copyright. IEEE-SA - national electrical safety code (NESC). n.d.
Web. 16 Dec. 2016.
[4] Transmission line design manual: A guide for the investigation, development, and
design of power transmission lines. 1980. Web. 16 Dec. 2016.
[5] Overhead power lines planning, design, construction (2003) Berlin, Heidelberg:
Springer Berlin Heidelberg.
[6] Bayliss, C.R. and Hardy, B.J. (2011) Transmission and distribution electrical engi-
neering. 4th edn. Oxford: Newnes (an imprint of Butterworth-Heinemann Ltd ).
[7] Looms, J S T. Insulators for High Voltages. London: Institution of Engineering and
Technology, 1988. Print.
[8] McDonald, John D. Electric Power Substations Engineering. 2nd ed. Boca Raton:
CRC Press, 2007. Print.
[9] Hewitson, L G, Mark Brown, and Ramesh Balakrishnan. Practical Power Systems
Protection. Amsterdam: Newnes (an imprint of Butterworth-Heinemann Ltd ), 2004.
Print.
[10] McDonald, John D., ed. Electric Power Substations Engieering, Third Edition. 3rd
ed. Boca Raton, FL: CRC Press, 2012. Print.
[11] Glover, Duncan J, Mulukutla S Sarma, and Thomas J Overbye. Power System Anal-
ysis and Design - 5th Edition. 5th ed. Stamford, CT: CENGAGE Learning Custom
Publishing, 2011. Print.
[12] Bisnath, S. The Planning, Design and Construction of Overhead Power Lines. Jo-
hannesburg, South Africa: Crown Publications, 2005. Print.
[13] Farr, John Vail V. Systems Life Cycle Costing: Economics Analysis, Estimation, and
Management. Boca Raton: Taylor & Francis, 2011. Print.
i
Appendix A
Load Growth
P1 = P0 (1 + x) (A.1)
P2 = P1 (1 + x) (A.2)
P2 = P0 (1 + x)2 (A.3)
Pn = P0 (1 + x)n (A.4)
log pn = log p0 + nlog(1 + x) (A.5)
And the estimated consumption will be equal to 8.8 GW,Based on that we decided to
transfer 1 GW in the transmission line system. AS shown in figure A.1
The table A.1 contain all real and estimation consumption over the period [1996-2050]
Appendix B
GIS Data
The pictures below shows the transmission path from Tarqumia to Al-Ezaria in sections.