X96A-programming Control Valve
X96A-programming Control Valve
ONOFF
CONTROLLER
X96A
VER 29.93
DESCRIPTION PAGE
Refer Indicator/
Fig 1 Function
Fig 1 Display
2
(2) SP
3 (4) Displays setpoints (SP1, SP2,
Setpoint
4
(2) SP3 or SP4 or input2)
(SP) Display
(5) (as selected by user)
Rx Tx
(6) Setpoint
status Indicate which setpoint is
(4)
indicator displayed on lower row
LEDs
TRANSMITTER
+
X X
S
mV/VIN In run mode, allows to enter
NO Q B
SSR setpoint mode.
Y RLY Y
C R B' mA INPUT In program mode, allows to
+
9
Z
NC + change value of parameter.
Check supply voltage with instrument sticker
FOR 2-WIRE S
TRANSMITTER USING
INTERNAL SUPPLY 2-WIRE RTD : SHORT Q & R
In program mode, at parameter
“VEr” if pressed for 6 sec, allows
85~265 V 1 21 31 P 11 P to enter calibration level.
V AC/DC S
2 22 32 Q 12 Q
INPUT2* INPUT1
3 X 23 X 33 R 13 R
* Scrolls forward through the
RLY1 4 Y RLY3* 24 Y 34 S 14 S
5 Z 25 Z 35 15
D+ programmable parameters in
RS485*
6 X 26 X 36 16 (6) program mode.
D
RLY2
* 7 Y RLY4* 27 Y 37 CJC 17 Allows to increment the value of
+
8 Z 28 Z 38 18 the selected parameter.
V/lout2 * +
VTX* 9 29 39 19
V/lout1 *
In run mode, resets alarm when in
10 30 20 latch alarm mode.
* - FACTORY OPTION
STK-711 Scrolls backward through the
programmable parameters in
Connection Diagram (For 20~35 V DC) program mode.
Allows to decrement the value of
EXT SSR* the selected parameter.
+
+ TRANSMITTER mV/VIN
X X
NO S Q B
SSR
Y RLY Y
C R B' mA INPUT
+
10
Z +
NC FOR 2-WIRE S
TRANSMITTER USING
INTERNAL SUPPLY 2-WIRE RTD : SHORT Q & R
+
1 21 31 P 11 P
24 V AC/DC VS
2 22 32 Q 12 Q
INPUT2* INPUT1
3 23 X 33 R 13 R
4 X RLY3* 24 Y 34 S 14 S
* D+
RLY1 5 Y 25 Z 35 15
RS485*
6 Z 26 X 36 16
D
7 X RLY4* 27 Y 37 CJC 17
* +
RLY2 8 Y 28 Z 38 18
V/lout2 * +
9 Z 29 39 19
V/lout1 *
VTX* 10 30 20
* - FACTORY OPTION
MAN#445R1/P4/24/311211/A
TABLE 1
RANGE LIMITS RANGE IN WHICH TYPICAL WORST CASE
SENSOR / INPUT (°C / EU) ACCURACY ACCURACY ACCURACY
IS SPECIFIED AT 30 °C (°C / EU)
LOW HIGH LOW HIGH (°C / EU)
SCALE SCALE SCALE SCALE
Input Group 1
Pt - 6% Rh / Pt - 30% Rh (B) 400 1820 400 1820 ±3 ±5
Chromel / Constantan (E) -270 850 0 850 ±1 ±3
Iron / Constantan (J) -210 760 0 760 ±1 ±3
Chromel / Alumel (K) -270 1372 -50 1200 ±1 ±3
Nicrosil / Nisil (N) -270 1300 -50 1200 ±1 ±3
Pt / Pt - 13% Rh (R) 0 1760 400 1760 ±2 ±5
Pt / Pt - 10% Rh (S) 0 1760 400 1760 ±2 ±5
Copper / Constantan (T) -270 400 -200 400 ±1 ±3
Pt100, 3-wire -200 850 -200 600 ± 0.3 ± 1.0
Linear (0~50 mV, 0~20 mA, 4~20 mA) -1999 9999 -1999 9999 ± 5 EU ± 20 EU
Input Group 2
The following inputs are available in Input Group 2 in addition to inputs of Input Group 1.
Tungsten - 5% Rh / Tungsten - 26% Rh (C) 0 2320 0 2320 ±3 ±5
Tungsten - 3% Rh / Tungsten - 25% Rh (D) 0 2310 0 2310 ±3 ±5
Tungsten / Tungsten - 26% Rh (G) 0 2310 0 2310 ±3 ±5
Cu53 0 180 0 180 ± 0.3 ± 0.5
Linear (0~10 mV, 0~100 mV, 0~200 mV,
0~1 V, 0~5 V, 0~10 V) -1999 9999 -1999 9999 ± 5 EU ± 20 EU
Linear (4~20 mA) with square root 0 9999 0 9999 ± 10 EU ± 40 EU
HYST HYST
3.2 Alarm Output
SP SP a) Latch (Ltch)
In latch output, once relay gets ON, it remains 'ON' until
alarm is acknowledged by key.
SP2A = dvhi SP2A = dvLo b) Hold
SP = SP1+ SP2 SP = SP1 - SP2 In alarm condition if instrument switched ON then it
Similarly for SP3A & SP4A Similarly for SP3A & SP4A doesn't show alarm output, it shows alarm condition in
second cycle when alarm appears.
c) Ltch.Hold
HYST It is the combination of latch & Hold outputs.
SP SP
HYST
4. BIAS MODE
In run mode upper display shows input1 and lower
·
SP2A = bnd.o SP2A = bnd.i +
display shows input2. Press together to
enter into bias mode
Upper display will show input1 and lower display will
·
bnd2 bnd2 flash "bia.1" (bias1 name) and its value alternately
SP2 SP2 To adjust the input1 press
· or . Input1(upper
display) will get modified accordingly and the new bias
SP SP1 value will also be seen on the lower display.
SP2 SP2 After the input1 is modified to the desired value save the
·
bnd2
new bias1 by pressing .
MAN#445R1/P5/24/311211/A
bnd2 The lower display will show input2 and upper will flash
·
"bia.2" and its value alternately. Follow above procedure
to adjust input2 ( or )
Similarly for SP3A/SP4A After the input2 is modified to the desired value save the
·
new bias2 by pressing . The instrument will
return to run mode with both the upper & lower display
showing the modified input 1& 2
5. PROGRAM MODE GUIDE
To enter program mode, press & hold
· & keys together, in run mode.
+
Press
· keys to increment the value of the selected parameter or increment the level, & press + keys to
decrement the value of the selected parameter, or decrement the level.
Use
· key to go to next parameter.
Use
· key to go to previous parameter.
To exit from the program mode & enter run mode, press
· & keys together.
+ PV
Selection of level init from option
1 Selection of level init OR
SP, inp, iout, init
+ SP
PV
2 Enter level init Next parameter is displayed
SP
PV
Storing of burn option for Burn option for relays is stored &
4 relays next parameter is displayed
SP
PV
Storing of burn option for Burn option for analog o/p is stored
6 analog output & next parameter is displayed
SP
PV
Pr.o1 is stored & next parameter
8 Storing of Pr.o1 is displayed
SP
PV
Pr.o2 is stored & next parameter
10 Storing of Pr.o2 is displayed
SP
MAN#445R1/P6/24/311211/A
Cont...
Cont... LEVEL init
PV
Storing of reverse / direct
12 Next parameter is displayed
mode SP
PV
Setpoint lock is stored & next
14 Storing of setpoint lock parameter is displayed
SP
PV
Parameter lock is stored & next
16 Storing of parameter lock parameter is displayed
SP
PV
Software filter is stored & next
18 Storing of software filter parameter is displayed
SP
+ PV
Set serial ID for
19 OR Adjust serial id for communication
communication + SP
PV
22 To access next parameter Next parameter is displayed
SP
PV
MAN#445R1/P7/24/311211/A
PV
Selection of level init from option
25 Selection of level setpoint +
SP
SP, inp, iout, init
PV
First parameter in level SP is
26 To enter setpoint level displayed
SP
SP
SP Parameter to be displayed on
+
Selection of parameter to be second row is selected from
27 displayed on second row
OR SP
options :
+
SP SP1, SP2, SP3, SP4, INP2
SP
PV
diS2 parameter is stored & next
28 Storing of diS2 parameter is displayed.
SP
+ SP
Selection of assignment of Relay 1 is assigned to Input 1
29 relay1
OR
or Input 2
+ SP
PV
Relay 1 assignment is stored &
30 Storing of relay1 assignment next parameter is displayed
SP
PV
Storing of alarm type for Relay1 alarm type is stored &
32 relay1 next parameter is displayed.
SP
PV
Alarm mode from relay1 is
Storing of alarm mode
34 PV stored and next parameter is
for relay1
displayed.
SP
PV
+
Set hysterisis/band1 value
35 for relay1
OR PV Hysterisis 1 is adjusted.
+
SP
Cont...
Cont... Level Setpoint
+ PV
Set cycle time for
37 proportional mode
OR Adjust cycle time for relay1
+ SP
PV
Cycle time 1 is stored & next
38 Storing of cycle time1 parameter is displayed.
SP
+ PV
39 Set maximum limit OR Max limit of output power for SP1
+ SP
PV
Max limit is stored & next
40 Storing of maximum limit parameter is displayed
SP
+ PV
41 Set minimum limit OR Min limit of output power for SP1
+ SP
PV
Minimum limit is stored & next
42 Storing of minimum limit parameter is displayed.
SP
+ SP
Selection of assignment of Relay 2 is assigned to
43 relay2
OR
Input 1 or Input 2
+ SP
PV
Relay 2 assignment is stored &
44 Storing of relay 2 assignment next parameter is displayed.
SP
SP
SP
Alarm type for relay2 is selected
from option :
SP FS.hi : High alarm
FS.Lo : Low alarm
+ SP
Selection of alarm type for du.hi : Deviation high alarm
45 relay2
OR
+ SP du.Lo : Deviation low alarm
bnd.i : Band in alarm
SP bnd.o : Band out alarm
SP
heat : heat mode
cool : cool mode
SP
PV
Storing of alarm type for Relay2 alarm type is stored &
46 relay2 next parameter is displayed.
SP
PV
Alarm mode from relay2 is
Storing of alarm mode
48 PV stored and next parameter is
for relay2
displayed.
MAN#445R1/P9/24/311211/A
SP
Cont...
Cont... Level Setpoint
PV
+
Set hysterisis/band value for
49 relay2
OR PV Hysterisis 2/band 2 is adjusted.
+
SP
+ PV
Set cycle time for
51 proportional mode
OR Adjust cycle time for relay2
+ SP
PV
Cycle time for relay2 is stored &
52 Storing of cycle time next parameter is displayed.
SP
+ PV
Maximum limit of output power
53 Adjust max limit OR
+ SP for SP2
PV
Maximum limit is stored &
54 Store max limit next parameter is displayed.
SP
+ PV
Minimum limit of output
55 Adjust min limit OR
power for SP2 is adjusted.
+ SP
PV
Minimum limit is stored &
56 Storing of minimum limit next parameter is displayed.
SP
+ SP
Selection of assignment of Relay 3 is assigned to
57 relay3
OR
Input 1 or Input 2
+ SP
PV
Storing of relay 3 Relay 3 assignment is stored &
58 assignment next parameter is displayed.
SP
SP
SP
Alarm type for relay3 is selected
from options :
SP FS.hi : High alarm
FS.Lo : Low alarm
+ SP
du.hi : Deviation high alarm
59 Select alarm type for relay3 OR
+ SP du.Lo : Deviation low alarm
bnd.i : Band in alarm
SP bnd.o : Band out alarm
SP
heat : heat mode
cool : cool mode
SP
PV
Storing of alarm type for Relay3 alarm type is stored &
MAN#445R1/P10/24/311211/A
Cont...
Cont... Level Setpoint
STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION
+ PV
63 Set hysterisis value for relay3 OR Hysterisis 3 is adjusted.
+ SP
PV
Hysterisis 3 is stored & next
64 Storing of hysterisis 3 parameter is displayed.
SP
+ SP
Selection of assignment of Relay 4 is assigned to
65 relay 4
OR
Input 1 or Input 2.
+ SP
PV
Relay 4 assignment is stored &
66 Storing of relay 4 assignment next parameter is displayed.
SP
SP
SP
Alarm type for relay4 is selected
from option :
SP FS.hi : High alarm
FS.Lo : Low alarm
+ SP
Select type of alarm for du.hi : Deviation high alarm
67 relay4
OR
+ SP du.Lo : Deviation low alarm
bnd.i : Band in alarm
SP bnd.o : Band out alarm
SP
heat : heat mode
cool : cool mode
SP
PV
Storing of alarm type for Alarm type is stored & next
68 relay4 parameter is displayed
SP
+ PV
71 Set hysterisis value for relay4 OR Hysterisis 4 is adjusted.
+ SP
MAN#445R1/P11/24/311211/A
PV
Hysterisis 4 is stored & next
72 Storing of hysterisis 4 parameter is displayed.
SP
5.3 LEVEL inP
+ PV
Select inP level from options :
73 Selection of level input OR
SP, inP, iout, init
+ SP
PV
First parameter of level inP is
74 Enter level inP displayed
SP
SP
SP
SP
PV
Input is stored & next parameter
76 Storing of input1 is displayed
SP
SP
Unit is selected from options :
+ SP Degree Centigrade
77 Selection of unit for display OR Degree Farrenite
+ SP Engineering unit for linear input
SP
only
MAN#445R1/P12/24/311211/A
Cont...
Cont... LEVEL inP
PV
Unit is stored & next parameter is
78 Storing of unit displayed
SP
PV
Resolution is stored and next
80 Storing of resolution parameter is displayed.
SP
+ PV
81 Set bias for input1 OR Adjust bias for input 1
+ SP
PV
Bias for input 1 is stored & next
82 Store bias for input 1 parameter is displayed.
SP
+ PV
Set high scale value for Adjust the high scale value for
83 input 1
OR
input1
+ SP
PV
Store high scale value for High scale for input1 is stored &
84 input1 next parameter is displayed
SP
+ PV
85 Set low scale value OR Adjust low scale value of input1
+ SP
PV
Low scale value 1 is stored &
86 Storing of low scale1 next parameter is displayed
SP
PV
Storing of minimum range of Minimum range is stored
90 input1 & next parameter is displayed
SP
Cont...
Cont... LEVEL inP
+
Same as 75
91 To select input2 OR Same as 75 Except for square root input
+
PV
Input 2 is stored & next parameter
92 Storing of input 2 is displayed
SP
PV
Resolution 2 is stored & next
94 Storing of resolution 2 parameter is displayed
SP
+ PV
95 Set bias of input2 OR Adjust bias for input 2
+ SP
PV
Bias for input 2 is stored & next
96 Store bias for input 2 parameter is displayed
SP
+ PV
Set high scale value for
97 OR Adjust high scale value for input2
input2
+ SP
PV
Highscale2 is stored & next
98 Storing of high scale2 parameter is displayed
SP
+ PV
99 Set low scale value for input2 OR Adjust low scale value for input2
+ SP
PV
Low scale 2 is stored & next
100 Storing of low scale2
SP
parameter is displayed
PV
Storing of minimum range of Minimum range is stored & next
104 input2 selected parameter is displayed
SP
5.4 LEVEL iout
+ PV
Select iout from options:
105 Selection of output level OR
SP, inp, iout, init
+ SP
PV
First parameter in level iout is
106 Enter level iout displayed
SP
+ SP
Selection of assignment of Output 1 is assigned to :
107 output 1
OR
Input 1 or Input 2
+ SP
PV
Output1 assignment is stored &
108 Store output 1 assignment next parameter is displayed
SP
SP
SP
+
Selection of type Select from options
109 of output1 (retransmission)
OR SP
0-20, 4-20, 20-4, 20-0, Volt output
+
SP
SP
PV
Output 1 type is stored & next
110 Storing of type of output 1 parameter is displayed
SP
+ PV
111 Set high scale for output 1 OR Adjust high scale for output1
+ SP
+ PV
Set low scale value for Adjust low scale value
113 output 1
OR
for output1
+ SP
+ SP
Selection of assignment of Output 2 is assigned to :
115 output 2
OR
Input 1, Input 2
+ SP
PV
Storing of output 2 Output 2 assignment is stored &
116 assignment next parameter is displayed
SP
MAN#445R1/P15/24/311211/A
Cont...
... Cont. LEVEL iout
SP
SP
+
Selection of type Select from options
117 of output2 (retransmission)
OR SP
0-20, 4-20, 20-4, 20-0, Volt output
+
SP
SP
PV
Output 2 type is stored & next
118 Storing of type of output2 parameter is displayed
SP
+ PV
119 Set high scale for output2 OR Adjust high scale for output 2
+ SP
+ PV
Set low scale value for
121 output2
OR Adjust lowscale value of output 2
+ SP
To enter calibration level press , when version number is being displayed in “init” level.
Note : Do not proceed through this section unless there is definite need to re-calibrate the instrument. All previous calibration data
will be lost. Do not attempt recalibration unless you have available appropriate calibration equipment. If calibration data is lost,
you will need to return the instrument to your supplier who may charge you a service fee to recalibrate the instrument.
The instrument will calculate the constants while exiting from program mode & store them in memory. Calibration should be
done with all parameters properly set (I/P, unit etc.)
Calibrate the displayed reading from the front panel. With this facility the zero & span calibration errors can be adjusted.
Select “input” correctly from level input. For eg. for rtd calibration select input “Pt100”, for mV/TC calibration select input “V50”
(0~50 mV). For CJC calibration select input “TC K”. For mA calibration select input either “0~20” or “4~20”.
For better accuracy select maximum range of high scale & low scale (level input)
PV
First parameter of level cal
124 Enter level Cal is displayed.
SP
SP
Select options
+
Calibration of 0~50mV Off : Calibration off
125 (input 1)
OR SP
+ On : Calibration on
SP Do : Allows to do calibration
PV
PV
To calibrate higher limit, feed Uncalibrated high value is
127 50 mV through calibrator SP displayed.
PV
+
Calibration is saved & program
131 To save calibration & exit
SP enters run mode
MAN#445R1/P17/24/311211/A
b) CJC (TC K calibration. Select “tc K” option of parameter “inp1” in level input) :For CJC calibration short the input terminals
(ter11 & ter12) with K type thermocouple wire.
PV
First parameter of level Cal is
133 Enter level Cal displayed.
SP
PV
Select options
+
Off : Calibration off
134 Calibration of TC K (input1) OR SP
+ On : Calibration on
SP Do : Allows to do calibration
PV
PV
+ PV
Adjust the CJC till it corresponds
137 Adjust the display OR
+ SP to the standard thermometer
PV
+
Calibration is saved & program
138 To save calibration & exit
SP enters run mode
PV
when version no.
139 Calibration level Level cal is selected
is displayed in level init SP
PV
First parameter of level cal
140 Enter level Cal is displayed.
SP
SP Select options
+
Off : Calibration off
141 Calibration of Pt100 (input1) OR SP
+ On : Calibration on
SP Do : Allows to do calibration
MAN#445R1/P18/24/311211/A
PV
Cont...
... Cont. Pt100 calibration
+ PV
Adjust the display to the required
144 Adjust the display OR
temperature (400 °C)
+ SP
+ PV
Adjust the display to required
146 Adjust the display OR
temperature (0°C)
+ SP
PV
+
Calibration is saved & program
147 To save calibration & exit
SP enters run mode
d) 4~20 mA input calibration. (Select option “4~20” of parameter “inp1” in level inp)
PV
First parameter of level cal
149 Enter level Cal is displayed.
SP
SP
Select options
+
Calibration of 4~20 mA Off : Calibration off
150 (input1)
OR SP
+ On : Calibration on
SP Do : Allows to do calibration
PV
PV
To calibrate higher limit, feed Uncalibrated high value of input
152 20mA through calibrator SP is displayed.
OR
+ SP
of input
Cont...
... Cont. 4~20 mA input calibration
PV
+
Calibration is saved & program
156 To save calibration & exit
SP enters run mode
e) Calibration of Input2
i) Calibration of 0-50 mV. Select “v50” option of parameter “inp2” in level inp
STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION
PV
when version no.
157 Calibration level Level cal is selected
is displayed in level init SP
PV
First parameter of level cal
158 Enter level Cal is displayed.
SP
PV
Parameter for calibration of input 2
159 Calibration of input 2 is displayed
SP
SP
Select options
+
Calibration of 0~50 mV Off : Calibration off
160 (input2)
OR SP
+ On : Calibration on
SP Do : Allows to do calibration
PV
PV
To calibrate higher limit, feed Uncalibrated high value is
162 50 mV through calibrator SP displayed.
SP
calibrator
Cont...
... Cont. Calibration of 0-50 mV
STEP NO. DESCRIPTION KEY TO BE PRESSED DISPLAY ACTION
PV
+ Calibration is saved & program
166 To save calibration & exit
SP enters run mode
Follow steps 159 to 166 to do calibration for other inputs (rtd, 4~20) of input 2
Calibration of linear current / voltage output can be done through front panel., With this facility ZERO & SPAN calibration error in
current / voltage output can be adjusted.
Select “4-20” option of parameter “o1.ty” in level iout.
Connect current meter at the output terminal
PV
First parameter of level cal
168 Enter level Cal is displayed.
SP
PV
Press key till Calibration parameter of output 1
169 Calibration of output 1 is displayed
display shows CL.01 SP
SP
Select options
+
Off : Calbration off
170 Calibration of output 1 OR SP
+ On : Calibration on
SP Do : Allows to do calibration
PV
+ PV
Adjust the display till current
172 Calibrate higher limit OR
output on meter is 20 mA
+ SP
PV
+ PV
Adjust the display till current
174 Calibrate lower limit OR
output on meter is 4mA
+ SP
PV
Calibration is saved & program
MAN#445R1/P21/24/311211/A
PV
176 Enter setpoint mode for 3 seconds While in run mode
SP
PV
177 Set value of setpoint1 OR Setpoint1 is adjusted
SP
PV
Adjusted setpoint1gets stored &
178 Storing of setpoint1 next parameter is displayed.
SP
PV
PV Adjusted setpoint2
180 Storing of setpoint2 gets stored & next
SP
parameter is displayed.
PV
181 Set value of setpoint3 OR Setpoint3 is adjusted.
SP
PV Adjusted setpoint3
182 Storing of setpoint3 gets stored & next
SP
parameter is displayed.
PV
183 Set value of setpoint 4 OR
SP
Setpoint4 is adjusted.
PV
Store setpoint4 & exit from
184 setpoint mode Enter run mode
SP
MAN#445R1/P22/24/311211/A
7. TROUBLE SHOOTING
This message occurs if input wires are not connected or Check input signal
broken
This message occurs in case of negative over range / Check input wiring
under range at input
This message occurs, if any parameter is corrupted Set the corrupted parameters to
their default values.
8. DATA CORRUPTION
In case of user programmed data corruption, a message 'dfLt' is given immediately on power on & the instrument does not
proceed further until the corrupted data is cleared by user.
The user has to reset the instrument by selecting “all” option of reset parameter in level init. Press & keys together
to go ahead. All parameters are set to their default values. Instrument now requires initial selection which includes input &
unit.
After pressing & keys together, it displays 'inpt none'. Select the desired input using + key.
After selecting input, press key once it displays 'unit none'. Select the desired unit using + key.
When selection is over, press & keys together which will enable the instrument to enter 'run' mode.
1 2 3 4 5 6 7 8 1 2 3 4
SW1 SW2
INPUT
1 2 3 4 5 6 7 8 1 2 3 4
0~1 V OFF ON OFF ON OFF OFF OFF OFF ON ON OFF OFF
0~5 V OFF OFF ON ON OFF OFF OFF OFF ON ON OFF OFF
0~10 V ON OFF OFF ON OFF OFF OFF OFF ON ON OFF OFF
0~10 mV OFF OFF OFF OFF ON OFF OFF OFF OFF ON OFF OFF
0~100 mV OFF OFF OFF OFF ON OFF OFF OFF ON OFF ON OFF
0~200 mV OFF OFF OFF OFF ON OFF OFF OFF ON OFF OFF ON
TC/0~50 mV OFF OFF OFF OFF OFF OFF ON ON ON OFF OFF OFF
RTD/Cu53 OFF OFF OFF OFF OFF ON ON ON ON OFF OFF OFF
mA OFF OFF OFF OFF OFF OFF ON ON ON OFF OFF OFF
MAN#445R1/P23/24/311211/A
FOR COMMUNICATION PROTOCOL PLEASE REFER BELOW.
The MODBUS/RTU protocol is messaging structure, widely When a message is sent from a master to a slave device the
used to establish master - slave communications between function code tells the slave what kind of action to perform.
intelligent devices. A modbus message sent from a master to Generally, the following functions are implemented in Radix
slave tells the selected slave what to do and what MODBUS products :
information to send back. The MODBUS/RTU protocol 3 READ HOLDING REGISTERS
works with RS232, RS485 and RS422 standards. 16 PRESET MULTIPLE REGISTERS
Slave address (Serial ID) is programmable parameter. Refer Parameter Type Hex Absolute
to instruction manual. address address
RO PV1-input1 Float 01 40001
12. RADIX PRODUCTS INCORPORATING
MODBUS / RTU PROTOCOL RO PV2-input2 Float 03 40003
RW SP1 Float 0D 40013
At present, the following products have the MODBUS/RTU
protocol incorporated : RW SP2 Float 0F 40015
RW SP3 Float 11 40017
1. Programmable 16-channel scanner - ISOSCAN RW SP4 Float 13 40019
2. PID controller - X Series
3. RPM/Rate Indicators - R490, RC722, … RO Relay Status Integer 15 40021
4. Humidity & temperature controller - HX96A RO Alarm Status Integer 16 40022
RO 2nd row display Integer 17 40023
13. SETTINGS
lndicator
Band rate 9600
Start bit 1
Data bit 8
Stop bit 1
Parity none
a) Host computer
b) RS232 to RS485 convertor
c) Intelligent devices (ISOSCAN, HX96A, X96A etc.)
d) RS485 bus
VS GND
Upto 32 devices
LOCAL
D+ D- D+ D- D+ D-
POWER
SUPPLY ISOSCAN X96A HX96A
MAN#445R1/P24/24/311211/A
Radix Electrosystems Pvt Ltd, B-14, 2nd Floor, Ghanshyam Indl. Estate, Veera Desai Road, Andheri (W), Mumbai - 400 053
Tel : 42537777 • Fax : + 91 22 42537700 • Email : [email protected] • www.radix.co.in
AN ISO 9001:2008 COMPANY