Installed outside, almost always in wide- For this reason, and given the high
open areas, photovoltaic plants are value of the components and the high
particularly subject to atmospheric cost of any down time, it is always best
phenomena and can sustain damage from practice to fit PV plants with suitable surge
surges caused by lightning strikes. protection.
Zone B
– Direct current side inverter
– Protection of the inverter from surges of
atmospheric origin
– Always required
Alternating current Alternating current side inverter Protection of the inverter Required if distance between
C from surges of atmospheric and C and D is greater than 10 m
grid origin
Delivery point, alternating Protection of the electrical Always required No
D current-side plant origin installation from surges of
atmospheric and grid origin and
from direct lightning strikes Yes
–W
hen the pressure undergoes a sudden increase,
this could cause the pipes (the electrical wires)
or the equipment connected to them to break
–T
he safety relief valve uses the pressure in the pipe to
open the safety bleed outlet, letting a little of the liquid
(the discharge current) flow out
–W
hen the pressure has returned to normal,
the valve re-closes by itself
Normal water
pressure
A statistical question
– The lifespan of an SPD depends on its resilience connected
to its rated discharge current In,
End of life probability
Premature Longevous
but also to the number of times lightning strikes near the
system each year
– On average, a 20 kA SPD in Europe will reach the
20 years
end of its life after twenty years
– Given the long functional life of a PV plant
and the large number of SPDs installed, statistics tell us
that an SPD reaching the end of its life is far from an
improbable occurrence; some SPDs (premature) could reach
the end of their lives in the first few years of the system's SPD expected lifespan
operation ...
What happens to each SPD installed in the PV plant over the years?
20 years of life
OVR PV photovoltaic SPDs After approximately twenty years of use the electrical
resistance diminishes appreciably and the SPDs allow current
contain varistors which are subject to flow which becomes dangerous, overheating the product to
to slight wear at each electrical the point where it is damaged. This is called the end of life of
discharge. the SPD, which must be disconnected from the network
supply to prevent the risk of fire.
Given the difficulty in extinguishing an electric arc in direct
current, ABB has developed and patented a thermal
disconnector able to disconnect the end-of-life SPD in
complete safety. The operation of the thermal disconnector on
the OVR PV is explained in these three figures:
Operating principle of the SPD when At end-of-life, the opening of the Extinguishing of the electric arc when
it has not reached the end of its life thermal disconnector and ignition of an the patented device cuts in
electric arc in direct current
How much measures an electric arc: difference between alternating and direct current, An electric arc can spark between
indicative values for a 10 A current two electrodes because of the voltage
Minimum distance between electrodes to extinguish the arc present at their edges.
The extinguishing of the arc is more
Alternating current 400V complex in direct current than in
alternating current because the current
never passes through zero.
Direct current 600V - Extinguishing may take place at lesser
distances, for example by quickly
separating two electrodes.
Direct current 1000V - The thermal disconnector contained
in OVR PV photovoltaic SPDs is able
to extinguish the electric arc thanks
to the fast opening of the contact and
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
the isolation of the parts by insertion
of an obstacle in the path of the arc.
This calculation does not take into account the SPD's end of Today, the guide UTE C 61-740-51 and the future prEN
life, a particularly critical case since the SPD must extinguish 50539-11 are the only products standards for PV SPDs in the
a DC arc, which is much more difficult compared to an AC world to supply clear and unambiguous indications on the
arc. tests to be performed to ensure that an SPD is safe for PV
ABB's OVR PV SPDs are specifically designed for direct applications. UTE conformity is today an additional guarantee
current and their performance is specified on the product of the quality and safety of OVR PV.
documentation as well as being clearly printed on the
product.
OVR Facile 2 Among the new features of the software, the possibility to
choose surge protection for photovoltaic applications and the
Quick product selection software for possibility to print a personalised solution in just a few clicks.
protection against surges The software requires the installation of Microsoft Access or
Access Runtime.
Software: 2CSC432010E0902
Downloadable from the following address:
http://inside.abb.com/abblibrary/downloadcenter/
The new deskmat for the Protecting the electric system from surges is important for
personal safety, as well as to safeguard
OVR range precious electronic equipment. The new deskmat from the
Sistemi TT e TN-S 3P+N
OVR range is a complete tool to be kept on the desktop or
on the work bench, helping to quickly find the correct solution
L1
L2 Residual
L3 Current
Device
N
Circuit
brakers
or fuses
General
Switchgear Section
Switchgear
PE
In a main switchboard, if there is a lightning conductor or aerial supply and there is delicate equipment in the switchboard
OVR T1 3L 25 255
Circuit
brakers
1 3P+N 3 x 2CTB815101R0300 + 1 x 2CTB815101R0500 3 x OVR T1+2 25 255 TS + 1 x OVR T1 100 N 3 x 125A gG or fuses
EA 062 8 E 933N/125
OVR T2 3N 40 275s P
TT, TN-S
and
OVR T1 3N 25 255
DIRECT AND
INDIRECT 1P+N 1 x 2CTB815101R0300 + 1 x 2CTB815101R040 1 x OVR T1+2 25 255 TS + 1 x OVR T1 50 N 1 x 125A gG EA 059 4 E 931N/125 General
DISCHARGE Switchgear Section
2 TN-C 3P 3 x 2CTB815101R0300 3 x OVR T1+2 25 255 TS 3 x 125A gG EA 061 0 E 933/125 PEN
Switchgear
General
Switchgear Section
Switchgear
In a switchboard, if there is a lightning conductor or when the electricity supply is from an aerial line PE
2
DISCHARGE
L3
1P+N 2CTB803952R0800 OVR T2 1N 40 275s P 1P+N C25A S531795¹ S 201 Na - C25
L1
TN-C 3P 2CTB803853R2200 L2 OVR T2 3L 40 275s P Residual 3P+N C25A S468206¹
Circuit
S 203 - C25 Circuit
L3 Current brakers brakers
¹ 6 kA MCB. See the ABB System pro M compact catalogue for other models. ® Device or fuses or fuses
N
OVR T2 1N 40 275s P
OVR T2 3L 40 275s P
OVR T1 1N 25 255
OVR T1 3L 25 255
Circuit
brakers
or fuses
OVR T2 3N 40 275s P
General General
Class Maximum string Uoc Remote contact Code Type Size Code Switchgear Type Section Switchgear Section
Switchgear Switchgear
voltage PEN PE
Sistemi TT e TN-S 3P+N Sistema TNC 3P (230 V L-N) Sistema TT 1P+N Fotovoltaico
Systems L1 Systems L1 TT and TN-S, L Residual Photovoltaic L1
Current
TT and TN-S 3P+NL2 Residual TNC 3P (230 V L-N) L2
1P+N Systems N
Device
L2
L3 Current L3
Device
N
OVR T2 1N 40 275s P
OVR T2 3L 40 275s P
OVR T1 3N 25 255
OVR T1 1N 25 255
OVR T1 3L 25 255
OVR PV 40 600 P
Circuit Fuses
brakers
or fuses
OVR T2 1N 40 275s P
OVR T1 1N 25 255
OVR PV 40 600 P
General
Switchgear Section
Switchgear
PEN
General
Switchgear Section Section
Switchgear Switchgear
PE PE
Sistema TT 1P+N
L Residual
Current
N
Device Fotovoltaico
L1
Circuit L2
brakers
or fuses
OVR T2 1N 40 275s P
OVR T1 1N 25 255
Fuses
OVR PV 40 600 P
General
Switchgear Section
Switchgear
PE
Section
Switchgear
PE
Fotovoltaico
L1
L2
Fuses
Section
Switchgear
PE
S802PV-M25 and OTM switch
disconnectors.
Two reliable types,
one absolute safety.
From ABB's experience in the PV sector, two types
of switch disconnectors which are safe, reliable and
designed to meet all requirements. The S802PV-M25
has a maximum voltage of 650 V DC and is a switch
disconnector to be used downstream of photovoltaic
strings; it can be fed from both sides and with
interchangeable terminals. It ensures the safety of the
system during maintenance in only 3 modules.
The OTM series of switch disconnectors is particularly
indicated for isolating the PV field and the inverter on
the DC side and immediately after the inverter on the AC
side and is thus the ideal supplement for maintenance
of PV plants in complete safety, covering voltages up to
750 V DC.
The OTM series can be accessorised with ancilliary
contacts and knobs for the return rotating manoeuvre, and
can be integrated with the System pro M compact® line of
products and compatible with the OT series accessories.
The ABB range of SPDs offers global Aside from direct current side protection
protection for photovoltaic plants. against indirect lightning strikes with OVR
PV, ABB offers a complete range of
protective devices
for photovoltaic plants:
OVR T1
The Type-1 SPD is installed
in the main (AC side) switchboard at the system input and is
able to direct the voltage of a direct lightning strike to earth.
It is used as a first level of protection to ensure safety in the
case of a direct lightning strike.
OVR T2
Type-2 alternating current SPDs protect the inverter, the
equipment installed in the main switchboard and other
delicate equipment on the AC side. All OVR T2 devices
are fitted with end-of-life indicators and have simplified
maintenance, thanks to the possibility to replace only the
cartridge instead of the whole device.
OVR TC
The OVR TC data line SPDs protect the monitoring
lines of the PV plants from surges. They are installed in series
with the network and have removable cartridges, making
maintenance simple, without having to cut the power to
the telecommunications line.
Experience
– The OVR PV range has been designed by ABB specifically
for PV applications
Practicality
– All OVR PV models are multi-pole and have
terminals for the two poles and PE
– The wiring system is fast and foolproof, since bars or other
accessories are not required
Removable cartridges
– The SPD can always be reused
– If a single cartridge reaches the end of its life, it is not
necessary to replace the entire product
– Replacements can be made without cutting the power to
the panel
Integrated contact
– Available on all versions
– Does not take up extra modules
– Signals the SPD end of life to the remote supervision
systems
TS contact
Features
– SPDs designed by ABB specifically for
the protection of photovoltaic plants
– Auto-protected from end-of-life short
circuits up to 100 A DC thanks to the
integrated thermal protection with direct
current breaking capacity
– Removable cartridges
– Versions with and without
end-of-life signalling contact
– “Y” configuration for a safer protection
– OVR PV T1 and T2 version
Fuses
OVR PV
PE
Ordering codes
Impulse Maxi Nominal Voltage Max. Short circuit Order Bbn Price Price Weight Pack
current discharge discharge protection Cont. DC current details 3660308 1 group 1 unit
current current level Operating withstand piece piece
lmp lmax ln Up Voltage lscwpv
(10/350) (8/20) (8/20) Ucpv
kA kA kA kV V A Type code Order code EAN kg ppc.
Type 1 PV, 9 poles
6.25 - 6.25 1.9 670 100 OVR PV T1 6.25-600 P TS 2CTB803953R5700 518361 1.10 1
NEW
6.25 - 6.25 2.5 1000 100 OVR PV T1 6.25-1000 P TS 2CTB803953R6700 518378 1.10 1
Type 2 PV, 3 poles
- 40 20 1.4 670 100 OVR PV 40-600 P 2CTB803953R5300 516527 0.38 1
- 40 20 1.4 670 100 OVR PV 40-600 P TS 2CTB803953R5400 516527 0.39 1
- 40 20 3.8 1000 100 OVR PV 40-1000 P 2CTB803953R6400 516534 0.38 1
- 40 20 3.8 1000 100 OVR PV 40-1000 P TS 2CTB803953R6500 516541 0.39 1
Replacement cartridges for Surge Protective Devices
6.25 - - - 600 - OVR PV T1 6.25-600 C 2CTB803950R1000 518978 0.24 1
6.25 - - - 1000 - OVR PV T1 6.25-1000 C 2CTB803950R1000 518989 0.24 1
- 40 - - 600 - OVR PV 40-600 C 2CTB803950R0000 516558 0.12 1
- 40 - - 1000 - OVR PV 40-1000 C 2CTB803950R0100 516565 0.12 1
- - - - - - OVR PV MC 2CTB803950R0300 516756 0.12 1