SFI - Water Pump Calculation

The document provides water pump sizing calculations for 3 factories of a 1,825.48kWp solar rooftop project. The calculations determine: 1) A flow rate of 5.5 GPM is required for the water pump based on using 2 water points at 10 liters per minute each. 2) The water head pressures required are 35 PSIG for Factory 2, 50 PSIG for Factory 4, and 35 PSIG for Factory 3 based on static head, pipe friction losses, and hose bibb pressure.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
62 views8 pages

SFI - Water Pump Calculation

The document provides water pump sizing calculations for 3 factories of a 1,825.48kWp solar rooftop project. The calculations determine: 1) A flow rate of 5.5 GPM is required for the water pump based on using 2 water points at 10 liters per minute each. 2) The water head pressures required are 35 PSIG for Factory 2, 50 PSIG for Factory 4, and 35 PSIG for Factory 3 based on static head, pipe friction losses, and hose bibb pressure.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

SUMMARY REPORT

Water Pump Calculation

Owner: SEAFRESH INDUSTRY PUBLIC CO.M LTD.

Project: SEAFRESH Solar Rooftop 1,825.48kWp.

Date: 22-Feb-21
The purpose of this calculation is to verify the sizing of water pump for module cleaning
system with the proper flow rate and pressure of water pump for SEAFRESH Solar
Rooftop 1,825.48kWp.
The calculation result could be summarized as following tables;

Result for Water Pump


Water Pump Spec. Factory 2 Factory 4 Factory 3
Flow Rate of Pump 5.5 GPM 5.5 GPM 5.5 GPM
Head Pump 35.0 PSIG 50.0 PSIG 35.0 PSIG

The following attachments are the calculation details of the above summary
Water Pump Calculation
For Factory 2
WATER PUMP SIZING CALCULATION
PROJECT : Solar Rooftop Project Installation Capacity 1,825.48kWp (F2-BP-01)_FAC2

1. Find GPM of Water Pump


1.1) The required amount of water point being uesd 2 Points
1.2) The required flow rate at each point 10 Liters per minute
Then, The total flow rate is 20 Liters per minute
or 5.28 GPM
Hence, The proper flow rate of water pump is 5.5 GPM

2. Find The water head pump


2.1) The Static head difference 5 m.
2.2) The longest distance to hose bibb 105 m.
2.3) The frictional loss in water pipe (5%.) 5.25 m. Note; for 1 " HDPE water pipe
2.4) The frictional loss in joint (30% of friction loss in water pipe) 1.575 m.
Total friction loss in water pipe 6.825 m.
2.5) The Pressure of Hose bibb (1 bar) 10 m.

From The Pressure Pump (m.) = Static Head + The total friction loss in water pipe
+ The pressure of Hose bibb
21.825 m.
The Pressure Pump (bar.) 2.1825 bar.
The Pressure Pump (PSI) 31.68 PSIG
Select 35.00 PSIG
Water Pump Calculation
For Factory 4
WATER PUMP SIZING CALCULATION
PROJECT : Solar Rooftop Project Installation Capacity 1,825.48kWp (F4-BP-01)_FAC4

1. Find GPM of Water Pump


1.1) The required amount of water point being uesd 2 Points
1.2) The required flow rate at each point 10 Liters per minute
Then, The total flow rate is 20 Liters per minute
or 5.28 GPM
Hence, The proper flow rate of water pump is 5.5 GPM

2. Find The water head pump


2.1) The Static head difference 10 m.
2.2) The longest distance to hose bibb 195 m.
2.3) The frictional loss in water pipe (5%.) 9.75 m. Note; for 1 " HDPE water pipe
2.4) The frictional loss in joint (30% of friction loss in water pipe) 2.925 m.
Total friction loss in water pipe 12.675 m.
2.5) The Pressure of Hose bibb (1 bar) 10 m.

From The Pressure Pump (m.) = Static Head + The total friction loss in water pipe
+ The pressure of Hose bibb
32.675 m.
The Pressure Pump (bar.) 3.2675 bar.
The Pressure Pump (PSI) 47.42 PSIG
Select 50.00 PSIG
Water Pump Calculation
For Factory 3
WATER PUMP SIZING CALCULATION
PROJECT : Solar Rooftop Project Installation Capacity 1,825.48kWp (F3-BP-01)_FAC3

1. Find GPM of Water Pump


1.1) The required amount of water point being uesd 2 Points
1.2) The required flow rate at each point 10 Liters per minute
Then, The total flow rate is 20 Liters per minute
or 5.28 GPM
Hence, The proper flow rate of water pump is 5.5 GPM

2. Find The water head pump


2.1) The Static head difference 10 m.
2.2) The longest distance to hose bibb 60 m.
2.3) The frictional loss in water pipe (5%.) 3 m. Note; for 1 " HDPE water pipe
2.4) The frictional loss in joint (30% of friction loss in water pipe) 0.9 m.
Total friction loss in water pipe 3.9 m.
2.5) The Pressure of Hose bibb (1 bar) 10 m.

From The Pressure Pump (m.) = Static Head + The total friction loss in water pipe
+ The pressure of Hose bibb
23.9 m.
The Pressure Pump (bar.) 2.39 bar.
The Pressure Pump (PSI) 34.69 PSIG
Select 35.00 PSIG