SFI - Water Pump Calculation
SFI - Water Pump Calculation
Date: 22-Feb-21
The purpose of this calculation is to verify the sizing of water pump for module cleaning
system with the proper flow rate and pressure of water pump for SEAFRESH Solar
Rooftop 1,825.48kWp.
The calculation result could be summarized as following tables;
The following attachments are the calculation details of the above summary
Water Pump Calculation
For Factory 2
WATER PUMP SIZING CALCULATION
PROJECT : Solar Rooftop Project Installation Capacity 1,825.48kWp (F2-BP-01)_FAC2
From The Pressure Pump (m.) = Static Head + The total friction loss in water pipe
+ The pressure of Hose bibb
21.825 m.
The Pressure Pump (bar.) 2.1825 bar.
The Pressure Pump (PSI) 31.68 PSIG
Select 35.00 PSIG
Water Pump Calculation
For Factory 4
WATER PUMP SIZING CALCULATION
PROJECT : Solar Rooftop Project Installation Capacity 1,825.48kWp (F4-BP-01)_FAC4
From The Pressure Pump (m.) = Static Head + The total friction loss in water pipe
+ The pressure of Hose bibb
32.675 m.
The Pressure Pump (bar.) 3.2675 bar.
The Pressure Pump (PSI) 47.42 PSIG
Select 50.00 PSIG
Water Pump Calculation
For Factory 3
WATER PUMP SIZING CALCULATION
PROJECT : Solar Rooftop Project Installation Capacity 1,825.48kWp (F3-BP-01)_FAC3
From The Pressure Pump (m.) = Static Head + The total friction loss in water pipe
+ The pressure of Hose bibb
23.9 m.
The Pressure Pump (bar.) 2.39 bar.
The Pressure Pump (PSI) 34.69 PSIG
Select 35.00 PSIG