This document describes special P and D channels for the NORIMOS 3000 PLC. P channels are data delivered from firmware to the PLC. Channels described include node failure pulses, horn group necessity statuses, acknowledgement pulses, duty statuses, and alarm statuses. D channels allow instructions to be sent from the PLC to the firmware, such as broadcasting an engineer call. The document provides information on each channel's purpose and data values over several software versions.

Uploaded by

Ayobo Roland
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
141 views7 pages

I614e V109 N3000-PLC-SpecialChannels

This document describes special P and D channels for the NORIMOS 3000 PLC. P channels are data delivered from firmware to the PLC. Channels described include node failure pulses, horn group necessity statuses, acknowledgement pulses, duty statuses, and alarm statuses. D channels allow instructions to be sent from the PLC to the firmware, such as broadcasting an engineer call. The document provides information on each channel's purpose and data values over several software versions.

Uploaded by

Ayobo Roland
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

Info 614e

NORIMOS 3000
V109-N3_ALA
PLC – Special Channels Page 1 / 7

NORIMOS 3000
PLC Special Cannels
NORIS Marine Systems GmbH & Co. KG • Muggenhofer Strasse 95 • D - 90429 Nürnberg
Fon +49 (0) 911 32 01 - 0 • Fax +49 (0) 911 32 01 - 150 • [email protected] • http: // www.noris-automation.com
Info 614e
NORIMOS 3000
V109-N3_ALA
PLC – Special Channels Page 2 / 7

© 2004 NORIS Marine Systems GmbH & Co. KG


All Rights Reserved.

Change log

Status Issue Modified chapters Reason for modification

Release 101 2006-05-03 all Draft


Release 102 2006-08-21 P2, P9, P10, P21, D4 from N3-ALA-112ra: Modification/Improvement
Release 103 2006-12-15 D17 from N3-ALA-112s: Modification/Improvement
Version 104 2007-04-11 P2, D17 P2 corrected, D17 new
Version 105 2011-07-29 D8-4 new, P21, P22
Version 106 2011-10-19 P21, P22 Function changed
Version 107 2012-12-03 P21, P22 P21-6 new, P22-6 new
Version 108 2014-12-05 P5, P14 Bits 7 and 8 new
Version 109 2015-01-29 P10-4 added

Document: I614e_V109_N3000-PLC-Special-Channels.doc

Content
1 P Channels ......................................................................................................................... 3
2 D Channels ......................................................................................................................... 6

NORIS Marine Systems GmbH & Co. KG • Muggenhofer Strasse 95 • D - 90429 Nürnberg
Fon +49 (0) 911 32 01 - 0 • Fax +49 (0) 911 32 01 - 150 • [email protected] • http: // www.noris-automation.com
Info 614e
NORIMOS 3000
V109-N3_ALA
PLC – Special Channels Page 3 / 7

1 P Channels
P Channels are data, that are delivered from the firmware to the PLC.

P1: Pulse Node Failure


from N3-ALA-1.12pr:
Pulse P1-1: Node failure is active, reason not specified
Pulse P1-2: Node failure from CAN 1 ( = Plug X3 )
Pulse P1-3: Node failure from CAN 2 ( = Plug X4 )

P2: statically Horn 1 is necessary. That is the result out of the alarm state of the known
channels, not depending of the duty state of the node.
from: N3-ALA-1.12q: Horn groups, that are necessary, according to alarm state.
statically P2-1: Horn group 0 is necessary ( channel spec: 0x00 )
P2-2: Horn group 1 is necessary ( channel spec: 0x20 )

P2-8: Horn group 7 is necessary ( channel spec: 0xE0 )

P3: Free

P4: Pulse P4-1: Acoustical acknowledgement came from CANbus.

P5: Pulse P5-1: Acoustical acknowledgement came from keyboard or channel input
from N3-ALA-1.14ja and N3-ALA-1.24ja:
Pulse P5-7: Acoustical acknowledgement came from keyboard.
Pulse P5-8: Acoustical acknowledgement came from channel input

P6: statically P6-1: ECR manned

P7: statically P7-1: No duty

P8: statically P8-1: Engineer call is active, single or all engineer call
statically P8-2: All engineer call is active

P9: Free
from N3-ALA-1.12ra:
statically P9-1: Display buzzer has to be switched on, resulting bit of:
statically P9-2: Engineer alarm came from CANbus
statically P9-3: NO DUTY alarm came from CANbus
statically P9-4: Engineer call is active
statically P9-5: An alarm is active, acoustically not accepted

P10: statically Node failure


from N3-ALA-1.12qa:
statically P10-1: Node failure is active, reason not specified
statically P10-2: Node failure from CAN 1 ( = Plug X3 )
statically P10-3: Node failure from CAN 2 ( = Plug X4 )
from N3-ALA-1.14jb / 1.24jb:
statically P10-4: Error in measuring data in IO box

NORIS Marine Systems GmbH & Co. KG • Muggenhofer Strasse 95 • D - 90429 Nürnberg
Fon +49 (0) 911 32 01 - 0 • Fax +49 (0) 911 32 01 - 150 • [email protected] • http: // www.noris-automation.com
Info 614e
NORIMOS 3000
V109-N3_ALA
PLC – Special Channels Page 4 / 7

P11: statically P11-1: All engineer call was broadcasted ( that is an answer after the instruction of
PLC channel D1

P12: from N3-ALA-1.12p:


statically P12-1: Resulting bit for system failures in this node
statically P12-2: Failure in combination interface
statically P12-3: Insulation trouble
statically P12-4: Failure iBus / slave box
statically P12-5: Failure in specification
statically P12-6: Failure in PLC

P13: statically P13-1: Node is ON-DUTY

P14: Pulse P14-1: Optical acknowledgement came from keyboard or channel input
from N3-ALA-1.14ja and N3-ALA-1.24ja:
Pulse P14-7: Optical acknowledgement came from keyboard.
Pulse P14-8: Optical acknowledgement came from channel input

P15: Pulse P15-1: Optical acknowledgement came from CANbus

P16: statically P16-1: Engineer alarm came from CANbus

P17..P20: statically Bitwise declaration for the duty state of all nodes
P17: node 7... 0,
...,
P20: node 31...24

P21: from N3-ALA-1.13ng and N3-ALA-124hc and Lib-N3-ALA-124hc:


Local. Only own channels. Before S and P and watch channels and inhibition channels not were
excluded, and therefore in consequence of these channels also channels of other units were
included ( in case D4-7 was set ). In order to stay as compatible to old equipment P21 is working
locally.
PLEASE NOTE: In the releases from N3-ALA-113nd until N3-ALA-113nf and N3-ALA-124hb
respectively Lib-N3-ALA-124hb this function was global.
from N3-ALA-1.12o:
statically P21-1: Optically not accepted alarm is active:
Alarm1 or alarm 2 or sensor failure
Pulse P21-2: New alarm is active.
Alarm1 or alarm 2 or sensor failure
statically P21-3: Alarm1 or alarm 2 or sensor failure is active
statically P21-4: Sensor failure is active
from N3-ALA-1.12q:
statically P21-5: Alarm 1 or alarm 2 is active
from N3-ALA-1.14ib:
Pulse P21-6: New sensor failure is active.

NORIS Marine Systems GmbH & Co. KG • Muggenhofer Strasse 95 • D - 90429 Nürnberg
Fon +49 (0) 911 32 01 - 0 • Fax +49 (0) 911 32 01 - 150 • [email protected] • http: // www.noris-automation.com
Info 614e
NORIMOS 3000
V109-N3_ALA
PLC – Special Channels Page 5 / 7

P22: from N3-ALA-1.13ng respectively N3-ALA-124hc respectively Lib-N3-ALA-124hc:


Global. Same processing as P21, but for own and external channels
PLEASE NOTE: In the releases from N3-ALA-113nd until N3-ALA-113nf and N3-ALA-124hb
respectively Lib-N3-ALA-124hb this function was local.
statically P22-1: Optically not accepted alarm is active:
Alarm1 or alarm 2 or sensor failure
Pulse P22-2: New alarm is active.
Alarm1 or alarm 2 or sensor failure
statically P22-3: Alarm1 or alarm 2 or sensor failure is active
statically P22-4: Sensor failure is active
statically P22-5: Alarm 1 or alarm 2 is active
ab N3-ALA-1.14ib:
Pulse P22-6: New sensor failure is active.

from N3-ALA-1.12sb: Common error in node


The pin assignment is identical to that of the watch channel
statically P22-1: Failure in specification
P22-2: Failure in PLC
P22-3: Failure in connection to the IO -Moduls
P22-4: Failure in combination interface
P22-5: Failure insulation
P22-6: Failure in iBus, connection to the IO boxes
P22-7: Failure in one oft he two CAN busses
P22-8: free

NORIS Marine Systems GmbH & Co. KG • Muggenhofer Strasse 95 • D - 90429 Nürnberg
Fon +49 (0) 911 32 01 - 0 • Fax +49 (0) 911 32 01 - 150 • [email protected] • http: // www.noris-automation.com
Info 614e
NORIMOS 3000
V109-N3_ALA
PLC – Special Channels Page 6 / 7

2 D Channels
D channels are data, that are delivered from the PLC to the firmware.
D1: D1-1: Create engineer call via CANbus. Having done this is messaged via P channel
P11.

D2: D2-1: Create engineer alarm via CANbus

D3: D3-1: Create no duty alarm via CANbus


ab N3-ALA-1.14jb und N3-ALA-1.24jb:
D3-5: Do display channel addresses on the display with full HEX number of the node
number ( e.g. CAN system 2: 3A11 instead of 1A11 ).

D4: D4-1: Be ON-DUTY ( only switching ON is possible )


D4-2: Be OFF-DUTY ( only switching OFF is possible )
D4-3: Do not take the DUTY keys of the display
from N3_ALA_112ra:
D4-4: = 1: Control the buzzer inside the operating system
= 0: Control the buzzer inside the PLC
D4-5: Switch ON/OFF the buzzer ( only together with D4-1 = 0, else it is controlled by
the operating system )
D4-6: The buzzer shall work in flash mode
D4-7: Take all channels of the whole system for the request of the buzzer and
standard horn
else: check only the channels of this node
D4-8: Mount CAN failure in the watch channel

D5: Acknowledge acoustically, inside this node and broadcast on CANbus


from N3-ALA-112p:
D5-1: Accept acoustically, inside this node, and broadcast on CANbus
D5-2: Accept acoustically, only inside this node

D6: Accept optically, inside this node, and broadcast on CANbus


from: N3-ALA-112p:
D6-1: Accept optically, inside this node and broadcast on CANbus.
D6-2: Accept optically, only inside this node

D7: D7-1: Do not deliver any acoustical or optical acceptance from bottom, neither to the
operating system nor do broadcast on CANbus
D7-2: Do not broadcast any acoustical acceptance from bottom on CANbus
D7-3: Do not broadcast any optical acceptance from bottom on CANbus
D7-4: Do not deliver any acoustical acceptance from bottom to the operating system
D7-5: Do not deliver any optical acceptance from bottom to the operating system
D7-6: Any optical acceptance may only accept "visible" channels

NORIS Marine Systems GmbH & Co. KG • Muggenhofer Strasse 95 • D - 90429 Nürnberg
Fon +49 (0) 911 32 01 - 0 • Fax +49 (0) 911 32 01 - 150 • [email protected] • http: // www.noris-automation.com
Info 614e
NORIMOS 3000
V109-N3_ALA
PLC – Special Channels Page 7 / 7

D8: Do deliver any optical acceptance from CANbus only to the PLC channel P15,
not to the operating system
from N3-ALA-111g;
D8-1: Do deliver any optical acceptance from CANbus only to the PLC channel P15,
not to the operating system
D8-2: Do deliver any acoustical acceptance from CANbus only to the PLC channel
P4, not to the operating system
from N3-ALA-113a;
D8-4: Do not display faded out channels on the front plate oft he IO boxes.
from N3-ALA-112ra;
D8-8: Switch OFF dimmer for the LEDs ( LEDs in light state )

D9...D12: Be ON DUTY instruction bitwise for any nodes:


D9: Node 7...0,
...,
D12: Node 31...24

D13...D16: Be OFF DUTY instruction, bitwise for any nodes:


D13: Node 7...0,
...,
D16: Node 31...24

D17: from N3-ALA-112s: The limit value for the insulation is defined by 2 bits ( = 4 levels ). This value is
valid for measuring over the whole box. For measuring of single channels there
are other values.
The limit value is defined by the following table:
D17-2 D17-1 Limit value
0 0 7kOhm
0 1 20kOhm
1 0 50kOhm
1 1 90kOhm