RN 02 00001 01 11 EL NPC MI 000066 (01) M.sub For DMS RTU For Electrical Network (C)

The document is a material submittal form for a DMS RTU project in Riyadh City. It provides project details such as the project name, contractor, consultant, specifications reference, and submittal number. It requests attachments including load approval documents, purchase agreements, drawings, specifications, data sheets, deviation statements if needed, certificates, catalogs, and previous approvals. It provides spaces for the consultant's recommendation, ADDC's approval status and comments.

Uploaded by

Cheap Trick
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
489 views440 pages

RN 02 00001 01 11 EL NPC MI 000066 (01) M.sub For DMS RTU For Electrical Network (C)

The document is a material submittal form for a DMS RTU project in Riyadh City. It provides project details such as the project name, contractor, consultant, specifications reference, and submittal number. It requests attachments including load approval documents, purchase agreements, drawings, specifications, data sheets, deviation statements if needed, certificates, catalogs, and previous approvals. It provides spaces for the consultant's recommendation, ADDC's approval status and comments.

Uploaded by

Cheap Trick
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Bulk Consumer

MATERIAL SUBMITTAL FORM FOR


Non Bulk Consumer
PRIVATE PROJECTS
Temp.Consumer

Riyadh City Development – Infrastructure


Project Name Material Descripition : DMS RTU for Power Network
and Streetscape – Phase 6

Load Demand Manufacturer / Supplier


M/s. LUCY Middle East L.L.C
Notification (LDN) No. : Name / Place of Origin
NATIONAL PROJECTS &
Contractor : Model / Type : DMS RTU- Gemini 3
CONSTRUCTION LLC.

ADWEA/ADDC/AADC STANDARD : S-AA-


Consultant : PARSONS Specification Ref./Clause No. : CPS-RTUDMS-RMU (Rev.0-2015 Clause
1,2,3,4,5,6,7,8,9 & 10

Submittal Ref No : RN-02-00001-01-11-EL-NPC-MI-000066 Date : 31-May-23

Name & Contact Details of the Contractor


Attachments :
Copy of Approved Load Demand Notification (LDN) Yes. No.
Copy of Purchase Agreement issued by ADDC for
( See Note Below) Yes. No.
Non Bulk Consumer

Copy of Approved SLD/Contract Drawing/Sketch Yes. No.

Copy of Related ADWEA Specification Yes. No.

Completed Technical Data Sheet Yes. No.

Deviation Statement (any deviation from the ADWEA/Project's specification on No.


Yes. a separate sheet)

Copy of Certificates (Type test,Non toxicity or Other) Yes. No.

Catalogue/Brochure Yes. No.

Manufacturer Quality Cetificate (ISO or Other) Yes. No.


Contractor's Stamp, Signature & Date
Copy of Previous approvals and references Yes. No.

For Use of Consultant :


Recommended
Recommended Not Recommended
as noted below
Comments :

Stamp, Signature & Date

For Use of ADDC :


Status : Approved Not approved

Approved Except As Noted


Comments :

Stamp, Signature & Date

Notes-
1. The above Comments and/or approvals do not relieve the Contractor from his obligation under the Contract
to ensure conformance to thespecification. Any specification deviations found subsequent to approval shall
be corrected by the CONTRACTOR to the satisfaction of ADDC.

2. This approval is not a purchase agreement . As a normal practice, ADDC will supply and install required
materials for Non Bulk Consumers. Non Bulk consumers shall procure material only if they have written
agreement issued by Asset Directorate.
MATERIAL DATA SHEET

Project Name and


Riyadh City Development – Infrastructure and Streetscape – Phase 6
Contract No. :

ADWEA/ADDC/AADC STANDARD : S-AA-CPS-RTUDMS-RMU


Submittal Ref. No. & Date : RN-02-00001-01-11-EL-NPC-MI-000066
(Rev.0-2015 Clause 1,2,3,4,5,6,7,8,9 & 10

Material Description : DMS RTU for Power Network B.O.Q Item No. : Bill No-11

Material's Technical
S. No. Description Unit
Specification / Data

1 DMS RTU S-AA-CPS-RTUDMS-RMU (Rev.0-2015

Contractor Consultant ADDC


Stamp, Signature & Date Stamp, Signature & Date Stamp, Signature & Date
MATERIAL DEVIATION FORM
(DEVIATION FROM THE PROJECT SPECIFICATION)

Project Name & Riyadh City Development – Infrastructure


Material Descripition : DMS RTU for Power Network
Contract No. : and Streetscape – Phase 6

NATIONAL PROJECTS & Manufacturer / Supplier


Contractor : M/s. LUCY Middle East L.L.C
CONSTRUCTION LLC Name / Place of Origin

Consultant : PARSONS Model / Type : DMS RTU- Gemini 3

ADWEA/ADDC/AADC STANDARD : S-AA-CPS-RTUDMS-


Submittal Ref No : RN-02-00001-01-11-EL-NPC-MI-000063 Specification Clause No. :
RMU (Rev.0-2015 Clause 1,2,3,4,5,6,7,8,9 & 10

Date : 31-May-23 B.O.Q Item No. : Bill No:-11

Deviation Description :
No Deviation

Reasons/Justifications :

Contractor's Stamp
Signature & Date
Bulk Consumer

CHECK LIST FOR DMS/SCADA SUBMITTALS Non Bulk Consumer

Temp.Consumer

Project Name RIYADH CITY PH-6A&6B Material Descripition : DMS-RTU

Consultant : PARSONS Contractor : NPC

Submittal Ref No : Date : 31-05-2023

Name & Contact Details of the Contractor

General Documents Required for All Submissions


1. Scope of Work & BOQ Y
2. All Previous ADDC Comments Sheet with Reply
Y
(for revised submittal Only)

1 3. Approved Vendor/Contractor List Y

4. Technical Calelogue of Manufacturers Y

5. Certificate/Trade License Y

RTU Y

1. Station SLD Y

2. SLD Showing feeding arrangement from the source Y

3. Country of Origin Certificate Y

4. Signal List Y

5. Tele-information Plan Y

6. Cable overview Y
2
7. Adaptation Design Y

8. I/O Connection Diagram Y

9. GIS names of all Stations Y

10. RTU Layout & Detailed Design Y

11. SAT Procedure Y

12. FAT Procedure & FAT Report (if the FAT was waived) Y

DMS Interface Panel

1. Station SLD

2. Interface panel layout

3. Signal List

4. Cable overview

3 5. SWG Schematic Drawing

6. Wiring Adaptation Design

7. Data/Compliance sheet

8. SAT /FAT Procedures

9. Catalogues for all equipment’s inside the IP

SCADA Submittal Checklist Page 1


Bulk Consumer

CHECK LIST FOR DMS/SCADA SUBMITTALS Non Bulk Consumer

Temp.Consumer

Project Name RIYADH CITY PH-6A&6B Material Descripition : DMS-RTU

Consultant :
PARSONS
Contractor : NPC

Submittal Ref No : Date : 31-05-2023

Name & Contact Details of the Contractor

Fiber Optic (Material)

a) Cable

b) Termination Box

c) Joints & Accessories

1. Data/Compliance sheet
4
2. FAT Procedure & FAT Report (if the FAT was waived)

Fiber Optic Cable Route

1. Cable Total length

2. Manhole Details

5 3. Single line diagram(SLD)

4. Termination / Splice joint scheme

5. FOC layout in A0 size

SCMS

1. SCMS Architecture/Block diagram

2. SCMS Functional Specification

3. Equipment List for SCMS

4. Station Controller Panel drawing

5. Common Alarm Panel drawing

6 6. HMI Typical Screen

7. SCMS Room Layout drawing

8. Signal list, SCMS Datasheet & DMS Datasheet

9. SCMS SAT Procedure

10. SCMS FAT Procedure

11. SCMS O& M Manual

DC System

7 1. Detail design of DC System

SCADA Submittal Checklist Page 2


Bulk Consumer

CHECK LIST FOR DMS/SCADA SUBMITTALS Non Bulk Consumer

Temp.Consumer

Project Name RIYADH CITY PH-6A&6B Material Descripition : DMS-RTU

Consultant : PARSONS Contractor : NPC

Submittal Ref No : Date : 31-05-2023

Name & Contact Details of the Contractor

GPRS/3G Modem

1. Communication design

8 2. Data sheet

3. SAT Procedure

Ethernet Switch

1. Approved Network Scheme


9
2. Data sheet

Media Convertor / LL Modem

1. Communication design
10
2. Data sheet

Contractor's Stamp, Signature & Date


Notes-
1. The submittals will be returned if the check list are not attached

SCADA Submittal Checklist Page 3


REVIEW / COMMENTS SHEET
Project Name : Riyadh City Development-Infrastructure and Streetscape-Phase-06
Project Description : Infrastructure & Streetscape

Material Submittal for DMS RTU for Electrical Network


SUBJECT/TITLE : ORIGINATOR : NPC-TGC Joint Venture

DOCUMENT REF. NO. : RN-02-00001-01-11-QM-NPC-SO-000066 REVISION NO. : 01

Sl.
Comments Response
No.
Refer the attached ADDC comments sheet,
01 Refer to the Manufacturer's Response Annexure 1
Document Reference: ADDC/CPD/PM D/CR&ERP /HAN/RCN/605 715
02 Submit the corresponding I/0 RTU datasheet aligned with the QRM SLD. Refer to the Manufacturer's Response Annexure 1
03 The station type in signal list shall be corrected. Refer to the Manufacturer's Response Annexure 1
04 Communication design shall be submitted separately for ADDC approval. Refer to the Manufacturer's Response Annexure 1
Please clarify OMS integration scope. Also confirm how many stations are considered for
05 Refer to the Manufacturer's Response Annexure 1
OMS integration in this project
06 Overcurrent and earth fault shall be separate signals if relay has sufficient output contacts Refer to the Manufacturer's Response Annexure 1

07 Schneider SLD and Lucy SLD is provided. Please clarify RTU is used for which application Refer to the Manufacturer's Response Annexure 1
Please note that each station’s detailed design shall be segregated as per GIS name of the
08 station. Design shall include RTU design and all related documentation and adaptation design Refer to the Manufacturer's Response Annexure 1
for the specific station
Contractor is requested to resubmit the material submittal complying to the ADDC comments
09 Refer to the Manufacturer's Response Annexure 1
as attached

Reviewed / Commented by : JN DATE:

Template Ref. no.: RS-02-00001-00-19-OA-KBR-FO-000005 | Rev. 03 Page 1 of 1


Ref: Baniyas North/ NMD /SS/ AK & NS/ 23

From: Hardware Section

Review of Contractor’s Document

Document ADDC/CPD/PMD/CR&ERP/DTS/TAS/23/619973
reference

Riyadh City North - Material Submittal of DMS RTU for


Contract
Electrical Network

Title Material Submittal of DMS RTU for Electrical Network

Date 03/05/2023

Comments

1- L/R switch shall be shown in RTU layout.

2- Adaptation material catalogues shall be provided including (terminals, command


relays…, EXT).

3- Clarification on integration works shall be provided.

4- I/O sheet for TRM station to be corrected.


Ref: DMSD/SS/AOK&AM/2023/

From: SCADA Support Department


Hardware Section

Review of Contractor’s Document

Document Reference Ref.: ADDC/CPD/PMD/CR&ERP/HAN/RCN/605715

Project Riyadh City North Infrastructure Development

Title Material Submittal of DMS RTU for Electrical Network

Date 30 Jan 23

Status of document Not approved

Comments:

1- Pleases submit the corresponding I/O RTU datasheet aligned with the QRM SLD.
2- Please correct the station type in signal list.
3- GIS names of the stations to be provided.
4- FAT shall be performed as per ADDC standards and requirements.
5- Communication design shall be submitted separately for approval.
6- Please clarify DMS integration scope. Also confirm how many stations are considered for DMS
integration in this project.
7- Overcurrent and earth fault shall be separate signals if relay has sufficient output contacts.
8- Schneider SLD and Lucy SLD is provided. Please clarify RTU is used for which application.
9- Please note that each station detailed design shall be segregated as per GIS name of the station.
Design shall include RTU design and all related documentation and adaptation design for the
specific station.

1of 1
DMS RTU Material Submittal

Gemini 3 RTU

Rev.01 Compliance to ADDC comments

Ref. No. ADDC/CPD/PMD/CR&ERP/DTS/TAS/23/619973. Dated: 03/05/2023


& Ref.: ADDC/CPD/PMD/CR&ERP/HAN/RCN/605715. Dated 30/01/2023
Index

Annexure 1 - Response to ADDC comments on rev.01

Annexure 2 - RTU GA drawing showing L/R switch

Annexure 3 - Catalogue of Terminal & Relays

Annexure 4 - I/O of TRNM RMU

Annexure 5 - List of GIS SS to be integrated

Annexure 6 - Signal List

Annexure 7 - Full documents of RTU material submittal


Annexure 1. Response to ADDC comments on rev.00
Project : Riyadh City Phase 6A&6B
Consultant : Parsons
Contractor : National Projects & Comnstruction LLC
RTU Manufacture : LUCY Switchgear
Supplier : Elsewedy Electric LLC

Compliance to comments. Ref: ADDC/CPD/PMD/CR&ERP/DTS/TAS/23/619973


Item ADDC Comments LUCY Response

1 L/R switch shall be shown in RTU layout. Complied, L/R swiytch is shown in the drawing. refer
attached in Annexure 2
Adaptation material catalogues shall be
2 provided including (terminals, command relays…, EXT). Complied, refer attached in Annexure 3

3 Clarification on integration works shall be provided. Integration Povided, CONTRACTOR SCOPE NPC

I/O sheet for TRM station to be corrected. Complied, refer attached Annexure 4
4

Compliance to comments. Ref.: ADDC/CPD/PMD/CR&ERP/HAN/RCN/605715

Item ADDC Comments LUCY Response


Pleases submit the corresponding I/O RTU datasheet
1 Complied, refer attached in Annexure 4
aligned with the QRM SLD.

2 Please correct the station type in signal list. Complied, refer attached in Annexure 6

3 GIS names of the stations to be provided. Complied, refer attached in Annexure 5

FAT shall be performed as per ADDC standards and r Complied


4 equirements.
Communication design shall be submitted separately
5 for approval.
Complied, to be submitt separately

Please clarify DMS integration scope. Also confirm how many Confirmed, NPC will provide Integration for the 6 station
6 stations are considered for DMS integration in this project. as mentioned in Annexure 5
Overcurrent and earth fault shall be separate signals Complied, refer to annexure 6 signal list
7 if relay has sufficient output contacts.
Riyadh City is compose of two sectors, sector 6A RMU is schneider &
Schneider SLD and Lucy SLD is provided. Please clarify
8 RTU is used for which application.
sector 6B RMU is Lucy. each sector with each RMU has 3 station to
integrate. refer annexure 5
Please note that each station detailed design shall
9 Complied, refer to annexure 6 signal list
be segregated as per GIS name of the station.
Design shall include RTU design and all related documentation
Complied, refer to annexure 6 signal list
and adaptation design for the specific station
Ref: Baniyas North/ NMD /SS/ AK & NS/ 23

From: Hardware Section

Review of Contractor’s Document

Document ADDC/CPD/PMD/CR&ERP/DTS/TAS/23/619973
reference

Riyadh City North - Material Submittal of DMS RTU for


Contract
Electrical Network

Title Material Submittal of DMS RTU for Electrical Network

Date 03/05/2023

Comments

1- L/R switch shall be shown in RTU layout.

2- Adaptation material catalogues shall be provided including (terminals, command


relays…, EXT).

3- Clarification on integration works shall be provided.

4- I/O sheet for TRM station to be corrected.


Ref: DMSD/SS/AOK&AM/2023/

From: SCADA Support Department


Hardware Section

Review of Contractor’s Document

Document Reference Ref.: ADDC/CPD/PMD/CR&ERP/HAN/RCN/605715

Project Riyadh City North Infrastructure Development

Title Material Submittal of DMS RTU for Electrical Network

Date 30 Jan 23

Status of document Not approved

Comments:

1- Pleases submit the corresponding I/O RTU datasheet aligned with the QRM SLD.
2- Please correct the station type in signal list.
3- GIS names of the stations to be provided.
4- FAT shall be performed as per ADDC standards and requirements.
5- Communication design shall be submitted separately for approval.
6- Please clarify DMS integration scope. Also confirm how many stations are considered for DMS
integration in this project.
7- Overcurrent and earth fault shall be separate signals if relay has sufficient output contacts.
8- Schneider SLD and Lucy SLD is provided. Please clarify RTU is used for which application.
9- Please note that each station detailed design shall be segregated as per GIS name of the station.
Design shall include RTU design and all related documentation and adaptation design for the
specific station.

1of 1
Annexure 2: RTU Drawing showing L/R Switch
1 2 3 4 5 6 7 8 9 10

A A

EARTH
POINT

B B

GEMINI 3
RTU LED INTERNAL
C C
MODULES LIGHTS UR5i SL
ROUTER COMMS MCB
(METAL CONDENSATION
PSM G-3 MCM G-3 DSM G-3 DSM G-3 OPTION) VENT UR5i
ROUTER
Lite

GEMINI 3 RTU
OK PWR CAN OK PWR CAN OK PWR CAN OK PWR CAN

DC SUPPLY LOCAL REMOTE OFF IN 8 IN 8


LOGIC SUPPLY
MOTOR SUPPLY DUMMY MODE AUTO A B IN 9 A B IN 9

MODULE CONFIGURATION (PLASTIC


SW875

IN 10 IN 10 PWR
HMI GEMINI 3
FAN / SWITCHED AUX L809 Module
Id
Module
Id
lu OPTION)
TVS808

C809
Electric
USB

DC 1
RS232-B

L808
C808
DC 2 L807 A B A B
IP IP
TVS806

C807
J905
24V AUX L806
C806
IP IP
C805

DC 1+ IN 1 IN 1
DEBUG

X650

DC 1-
DC OUTPUTS

SW A IN 2 SW A IN 2
DC 2+ R803
J803

DC 2-
J901
IN 3 IN 3

G-3 DSM DSM


24V AUX IN 4 IN 4
G-3 G-3
ETH-1

PSM MCM
J904

D
0V
24V AUX
0V DOOR SW J801
IN 5
IN 6
IN 5
IN 6
Lite
G-3 MCM
G-3
CAN
OK PWR CAN
OK PWR CAN

IN 8 HMI D
TVS653
IN 7 IN 7 OK PWR
G-3
SENSOR

OK OK IN 8
24V DC

TVS804

OK PWR CAN PWR CAN PWR CAN


INPUT

J902
IN 9
OP M+ OP M+ OK PWR CAN PSM TE OFF A B
T + - 0

L804
C804
OP OP Lite PWR CAN LOCAL REMO IN 9 IN 10
C803
B
RS232-A

OK
RS485

L803
A
TVS802

L802
OP OP MODE AUTO IN 10
DC SUPPLY DUMMY
C802

SW875
Module
OUTPUT
24V AUX

C801
L801 OP 1 OP 1
/FAN

LY Id
LOGIC SUPP
DC SUPPLY LOCAL REMOTE OFF Module
C800
L800

IN 8 IN 8 MOTOR SUPP
LY
1

Id A B
SW B SW B L80
IP

808
TVS656

C809
CT A CT A

TVS
9
A B IP
LOGIC SUPPLY
L80

RS232-B
J802
PWROK MENU
C808
IP

USB
8

IN 1

806
L80

HED AUX IP
C807

TVS
DUMMY MODE A B A B
7

IN 9 IN 9 FAN / SWITC
L80

IN 2
5
ETH-0

C806
IN 1
J90

AUTO
HMI

MOTOR SUPPLY
6

HMI
C80

DC 1 5

IN 2 SW A IN 3

0
X65
SW875
CT B CT B DC 2 IN 3 IN 4
SW A

DEBUG
R80
J80
3 PW
R
IN 10 IN 10 24V AUX IN 5
3
J800
1 IN 4
DC 1+ IN 6
J90

OPEN IN 5 GEM
lu

ETH-1
DC 1-
PSM MCM Lucy Lucy IN 7

DC OUTPUTS
4
IN 6 INI
DSM DSM
J90
DC 2+
Lite ACT DC 2- IN 7 OP M+ 3
LOCAL 24V AUX TVSJ80
6531
OP M+ OP
FAN / SWITCHED AUX DOOR SW

804
0V
Module Module

TVS
CLOSE
MODE
REMOTE 24V AUX
2
OP OP
L809
J90

0V L80
OP 1
Id Id OP
C804

TVS808
C809 C80 4

RS232-A
802
USB
L80 3

DC 1

T + - 0
OFF 3
OP 1

TVS
24V DC
INPUT
RS232-B
L80
L808

RS485
C802

SENSOR
C80 2
C808 L80 1
CT A
SW B
1

DC 2 L807 A B A B C80
L80 0
0

SW B CT A
IP IP

TVS806

656
C807

OUTPUT

TVS
24V AUX
J905 J80

/FAN
2

24V AUX L806


C806
IP IP
CT B

ETH-0
CT B

PSU
C805

HMI
DC 1+ IN 1 IN 1 Lucy

DEBUG
J80
0

X650
RELAYS DC 1-
Lucy
DSM

DC OUTPUTS
SW A IN 2 SW A IN 2 MCM lu DSM PW
R
DC 2+ R803
J803

DC 2-
J901
IN 3 IN 3 PSM
OK

MEN
24V AUX IN 4 IN 4 Lite U

ETH-1
J904 OP
EN
0V IN 5 IN 5
E 24V AUX CLO E
0V IN 6 IN 6 SE LOCA
L
DOOR SW J801
REMO
TEM AC
T
TVS653
IN 7 IN 7 OFF OD
E
SENSOR

24V DC

TVS804
INPUT
J902
OP M+ OP M+

T + - 0
L804
C804
C803 OP OP

RS232-A
RS485
L803

TVS802
L802
OP OP
C802
OUTPUT
24V AUX

C801
L801 OP 1 OP 1
/FAN

C800
L800

1
SW B SW B
SUPPLY

TVS656
CT A CT A
NiMH
J802

MCB

ETH-0
11 AH

HMI
CT B CT B
BATT J800

PSM
Lite
MCM lu DSM
Lucy
DSM
Lucy

F F
DOOR &
BATTERY
SWITCH PSM lite
MCM MODULE
MODULE
EXPANSION SLOT

G
DSM MODULES G

UMBILICAL LOCAL REMOTE SWITCH


PAINTED STEEL ENTRY VIA SPLIT
ENCLOSURE - IP55
SEE SHEET 2 FOR ENCLOSURE DIMENSIONS
GLAND PLATE
ECN STANDARD TOLERANCES: ISO 2768-m.
FOR ADDITIONAL INFO. SEE DRG. 72219 C COPYRIGHT LUCY ELECTRIC (EMS). ALL RIGHTS RESERVED. ALL DIMENSIONS IN MILLIMETERS UNLESS OTHERWISE STATED
NUMBER

MOD. jones_mc DRAWN jones_mc G3 RTU, 5 SLOT IP55, MCM, IEC 104,
MOD.
APPRV. __
DRAWN
APPRV. CO
PSM-lite, 1X12V-COMMS, 2x DSM, LOCAL
H H
REM SW, 11AH NIMH, HMI, OEM PSU & TEMP
DATE 06/01/21 DATE 06/01/21 SENSOR, UR5i ROUTER - ADDC
MATERIAL: FINISH: ENGINEERING SOURCING CRITICALITY: SHEET NO: PROJECTION DO NOT SCALE THE REPRODUCTION OR TRANSMISSION OF ALL OR PART OF THIS
FROM A3 WORK, WHETHER BY PHOTOCOPYING OR STORING IN ANY MEDIUM
00 CATEGORY 2 1 OF 3
1st ANGLE IF IN DOUBT ASK
BY ELECTRONIC MEANS OR OTHERWISE, WITHOUT THE PRIOR
WRITTEN PERMISSION OF THE OWNER, IS PROHIBITED. AUT0004360 REV. 1
Annexure 3: Catalogue of Terminal & Relays
for adaption materials
ADR241S
AM-521-01-04–XX-XX-XX-XX
DRAWOUT

Protection Features: • Latching of fault current up to last 5

• 4 Element (3 Phase + EF) Over faults with time stamping.

Current IDMT/DMT with instant Trip. • Disturbance Recorder: Actual

• 16 x 2 back - lit LCD display for waveform of current along with

settings. logical and physical status are

• Display of Load Current in terms of captured and saved in the built-in

primary & secondary. memory, with date time stamping for

• Over current, Earth Fault, Cold analyzing fault condition & fault

Load Pickup, Thermal Overload, location.

Under Current and Inrush • Password protection for all settings.

Blocking Protection functions. • Programmable (Non- Volatile)

• Separate curve selection for Phase setting by local keys as well as

and EF. remote setting by communication

• Selection of Curve: Eleven selectable port.

curves Definite Time / IEC S Inverse • Relay can be made either IDMT or

/ IEC S Inverse (1.3 Sec) / IEC V Define time

Inverse / IEC E Inverse / UK LT • 2 Setting Groups.

Inverse / IEEE M Inverse / IEEE V • Fully communicable with IEC

Inverse / IEEE E Inverse / US Inverse standard open protocol IEC 60870-

/ US ST Inverse 5-103.

• Design using DSP technology.

Doc ID : ADR241S_DO/PC/01
Rev No.: 01
Page No.: 1 of 30
ADR241S
AM-521-01-04–XX-XX-XX-XX
DRAWOUT

• IP54 Compliance (Required necessary protection and monitoring


optional Protective Cover) functions required for compact RMU,
The High speed Digital Signal Controller
Relay Design Features: continuously monitors line phase current

• An Auxiliary Voltage supply is not and E/F current through CTs along with

required. (Aux. supply is different status input’s through optical

Optional) isolated status connections. The high-

• Low energy pulse output tripping for speed micro-controller samples these

RMU current signals through 12-bit A/D

• Self Power Design. converter. The Digital Signal performs

• USB (at front) and RS485 (at rear powerful Numerical Algorithms to find

side) Communication Port for out RMS of fundamental & harmonic

remote SCADA contents of the current. All

• Continuous monitoring of internal measurement is tuned to fundamental

hardware modules and error frequency i.e. 50Hz or 60Hz depending

message generation in case of failure upon setting, thus relay remain stable

of any critical components. during distorted waveform by various

• Facility to synchronised Relay time industrial load. All these measure values

from SCADA. are then used for different protection

• Site Selectable Frequency i.e. 50 / function such as IDMT / DT Over current

60 Hz. protection, E/F protection, Cold load

• Available with 1A or 5A CT pickup, Thermal Overload etc. These

secondary. measured values are also displayed on

• 4 Optically isolated digital inputs. large 16 x 2 LCD display for metering

• One dedicated input for CB status purpose. The power supply module is

(CBNO), one dedicated input for special electronics circuit which derives

Remote Trip and two spare status power from current flowing through line;

inputs for SCADA. (Same as selected therefore external power supply is not

Auxiliary supply voltage). required. The minimum required current

• 1 C/O potential free contact for to power ON relay is 20% in any one

Protection Healthy and 3 potential phase or 12% in any 2 phases or 8% in

free contacts for Phase, EF and Trip. all three phases. Relay also provides
pulse output to Trip the RMU or compact
CB having low energy tripping coil.
Description:
ADR241S is second generation of
Numerical Self Powered OC / EF
IDMT/DT Relay. It consist all the

Doc ID : ADR241S_DO/PC/01
Rev No.: 01
Page No.: 2 of 30
ADR241S
AM-521-01-04–XX-XX-XX-XX
DRAWOUT

Technical Specifications:
Current Input:
1. CT secondary : 1 Amp or 5 Amp to be specify while ordering
2. Nominal Burden at : OC CT < 4.2 VA (@ In = 1 A)
In : EF CT < 0.10 VA ( @ In= 1A)
(without tripping
condition)
3. Thermal Withstand : 50 x rated current (In) for 1sec
Capacity : 30 x rated current (In) for 3sec
: 2 x rated current (In) continuous
4. Operating Range : For OC 0.2 – 35 In
: For EF 0.1 – 35 In
5. Measurement : Typical ± 2% at In for Phase and EF
Accuracy
6. Nominal Frequency : 50 / 60 Hz (Site selectable)
Range For Current
Inputs
7. Minimum current : In 1Ø ≥ 20%, 2Ø ≥ 12% and 3Ø ≥ 10%.
require to energize
the relay
8. Frequency : 45 Hz – 65 Hz
measurement
range
9. Current Detailed information of CT requirements is given on page no.
transformer 7
requirements

Auxiliary Supply voltage:


1. Nominal operating : 100 – 230V DC /AC (50Hz / 60Hz) or 24 - 50 VDC
range (ordering option)
2. Voltage operating : 80% of lower nominal range and 120% of upper nominal
range range (For DC Supply)
: 80% of lower nominal rang and 110% of upper nominal
range (For AC Supply)
3. Nominal Burden on 100-230VAC : <10 VA No output or LED energized.
100 – 230V : <12VA with status S1, S2 & S3 energise
Auxiliary Power
Supply 100-230 VDC : <4W No output or LED energized.
: <4W with status S1, S2 & S3 energise
4. Nominal Burden on : <3 watt No output or LED energized.
24 - 50 VDC : <4 watt with status S1, S2 & S3 energise
Auxiliary Power
Supply
5. Tolerable AC ripple : Up to 15% of highest dc supply, As per IEC 60255-11:
2008

Doc ID : ADR241S_DO/PC/01
Rev No.: 01
Page No.: 14 of 30
ADR241S
AM-521-01-04–XX-XX-XX-XX
DRAWOUT

6. Relay power up : <50ms


time with Aux.
Supply
7. Auxiliary Power : As per IEC 60255-11
Supply Voltage 100 - 230Vdc, the relay withstand for 50 ms;
Interruption
(without powering 100 - 230Vac, the relay withstand for 50 ms;
by CT): 24-50Vdc, the relay withstand for 20 ms;

Opto Isolated input :


1. Opto Isolated input :Same as Auxiliary supply range
operating Range 100 – 230V DC /AC (50Hz / 60Hz)
2. VA Burden of Opto : For AC at nominal voltage range (100 to 230V) < 0.8 VA
Isolated Status : For DC at nominal voltage range (100 to 230V) < 0.8 Watt
Input (S1, S2 &
S3)
3. VA burden of : For AC at nominal voltage range (100 to 230V) < 12 VA
Status S4 (Remote : For DC at nominal voltage range (100 to 230V) < 4 Watt
Trip)
Note : Relay take power from Remote trip input to power it
electronics and provide tripping output to CB even if there
is NO Auxiliary supply and CT current is less than minimum
operating value
4. Operating voltage : 80% of lower nominal range to 110% of upper nominal
range range (For AC)
: 80% of lower nominal range to 120% of upper nominal
range (For DC)
5. Pick up Voltage : 60V – 80Volts (for 100V – 230 Volts Aux. Supply )
(Logic High)
6. Drop off voltage : 30V – 60Volts (for 100V – 230 Volts Aux. Supply )
range
(Logic Low)
7. Filtering Time : < 40ms for S1, S2 & S3
8. Logic input : For S1, S2 & S3 filtering time + 5ms ± 5 ms
recognition time : 3.5sec for Remote Trip ± 5%

Output Contact:
1. Output contacts Continuous : 5A/250Vac
Make & carry : 30Amp for 3sec AC /DC
Short time withstand Carry : 50Amp for 1sec AC /DC
Breaking capacity AC- 1250VA max. 5A or 300V(PF
0.4)
DC- 100W Resistive max. 5A or
300V
50Watt Inductive (L/R 45ms) max.

Doc ID : ADR241S_DO/PC/01
Rev No.: 01
Page No.: 15 of 30
DUTKD2.5

Approval

General Data
Type DUTKD2.5

Wire Termination Technology Screw clamp

Ratings 1000V / 24A / 2.5mm2 / 0.4 Nm

Screw Size M2.6

Dimensions & Weight


Height (mm) 56

Height (inches) 2.20

Width (mm) 62

Width (inches) 2.44

Thickness (mm) 5

Thickness (inches) 0.19


Material Data
Housing Polyamide66

Standard Colour Grey

Rated Conductor Size


Stranded Wire - min (mm2) 0.5

Stranded Wire - max (mm2) 2.5

Solid Wire - min (mm2) 0.5

Solid Wire - max (mm2) 4

Ratings - IEC
Standard IEC 60947-7-1

Rated Voltage (V) 1000V

Rated Current (A) 24A

Rated Cross Section (mm2) 2.5

Rated torque (Nm) 0.4 Nm

Short Time Withstand Current (kA) 0.3

Rated Impulse Withstand Voltage(kV) 6

Pollution Degree lll

Material group I
Accessories
End plate

DUTKD4EP
Height: 38.25mm
Width : 62mm
Thickness : 1.5mm
Marking Label:
Label KN5.5
Datasheet

KUDD4CC2
Terminal Type - KUDD4CC2 , Component Housings terminal block, nominal voltage: 500 V, Diode : 1N 4007 , Common Cathode
,Diode current: 1 A , Diode Reverse Voltage - 1000 V, Rated cross-section - 2.5 mm², connection method: Screw connection,
number of connections: 3, cross-section: 0.5 mm² - 2.5 mm², mounting type: TS 35/7.5, TS 35/15 , TS 32

Approvals

General Information

Product Name KUDD4CC2


Connection Method Screw Connection
Rating 500 V/Diode Current - 1 A/2.5 mm2/0.4 Nm
HSN Number 85389000
Standard Packing Qty(in No) 100
Country Of Origin India
Screw thread M3

Dimensions & Weight

Width 6 mm 0.24 inch


Length 54 mm 2.13 inch
Height 59.2 mm 2.33 inch
Weight of std. Packing Unit 1.38 Kg

Material Data

Insulating Material Polyamide 6,6


Standard Colour Gray
Colour Variants Red , Yellow , Blue , Black , Green , Khakhi , Gray ,

Rated Conductor Size

Conductor cross section flexible min 0.5 mm2


Conductor cross section flexible max 2.5 mm2
Conductor cross section solid min 0.5 mm2
Conductor cross section solid max 2.5 mm2

1 https://www.elmex.net/
Datasheet

Ratings - IEC

Connection in acc. with standard IEC 60947-7-1


Nominal Voltage Un 500 V
Nominal Current In Diode Current - 1 A
Nominal cross section 2.5 mm2
Short-time current NAV kA
Rated surge voltage 6 kV
Degree of pollution 3

2 https://www.elmex.net/
Datasheet

KULTD6
Terminal Type - KULTD6, Test Disconnect Terminal Block, nominal voltage: 1000 V, nominal current: 41 A, Rated cross-section- 6
mm² , connection method: Screw connection with spring support, number of connections: 2, cross-section: 0.5 mm² - 10 mm² ,
AWG: 24-8,mounting type: TS35/7.5, TS35/15 and TS32

Approvals

General Information

Product Name KULTD6


Connection Method Screw Connection with spring support
Rating 1000 V/41 A/6 mm2/1 Nm
HSN Number 85389000
Standard Packing Qty(in No) 50
Country Of Origin India
Screw thread M3.5

Dimensions & Weight

Width 8 mm 0.31 inch


Length 85.5 mm 3.37 inch
Height 71 mm 2.8 inch
Weight of std. Packing Unit 2.05 Kg

Material Data

Insulating Material Polyamide 6,6


Standard Colour Gray
Colour Variants Red , Yellow , Blue , Black , Green , Khakhi ,

Rated Conductor Size

Conductor cross section flexible min 0.5 mm2


Conductor cross section flexible max 6 mm2
Conductor cross section solid min 0.5 mm2
Conductor cross section solid max 10 mm2

1 https://www.elmex.net/
Datasheet

Ratings - IEC

Connection in acc. with standard IEC 60947-7-1


Nominal Voltage Un 1000 V
Nominal Current In 41 A
Nominal cross section 6 mm2
Short-time current 0.72 kA
Rated surge voltage 8 kV
Degree of pollution 3

Ratings - ATEX

ATEX Standard EN 60079-7


ATEX Nominal Voltage Un 550 V
ATEX Nominal Current In 32 A
ATEX Cross Sec. Flexible Max. 6 mm2

Ratings - CSA

CSA Standard CSA C22.2 No. 158


B - CSA Nominal Voltage UN 600 V
B - CSA Nominal Current IN 35 A
B - CSA Wire Min 24 AWG
B - CSA Wire Max 8 AWG

Ratings - UL

UL Standard UL 1059
B - UL Nominal Voltage UN 600 V
B - UL Nominal Current IN 35 A
B - UL Wire Min 24 AWG
B - UL Wire Max 8 AWG

2 https://www.elmex.net/
Datasheet

KUT4N
Terminal Type - KUT4N , Feed-through terminal block for photo voltaic applications , nominal voltage: 1000 V, nominal current: 32
A, connection method: Screw connection, number of connections: 2, cross section: 0.5 mm² - 4 mm², AWG: 20 - 10, mounting
type: TS 35/7.5, TS 35/15 , TS 32

Approvals

General Information

Product Name KUT4N


Connection Method Screw Connection
Rating 1000 V/32 A/4 mm2/0.5 Nm
HSN Number 85389000
Standard Packing Qty(in No) 100
Country Of Origin INDIA
Screw thread M3

Dimensions & Weight

Width 6 mm 0.24 inch


Length 44.25 mm 1.74 inch
Height 50.8 mm 2 inch
Weight of std. Packing Unit 1.25 Kg

Material Data

Insulating Material Polyamide 6,6


Standard Colour Gray
Colour Variants Red , Yellow , Blue , Black , Green , Khakhi ,

Rated Conductor Size

Conductor cross section flexible min 0.5 mm2


Conductor cross section flexible max 4 mm2
Conductor cross section solid min 0.5 mm2
Conductor cross section solid max 4 mm2

1 https://www.elmex.net/
Datasheet

Ratings - IEC

Connection in acc. with standard IEC 60947-7-1


Nominal Voltage Un 1000 V
Nominal Current In 32 A
Nominal cross section 4 mm2
Short-time current 0.48 kA
Rated surge voltage 12 kV
Degree of pollution 3

Ratings - ATEX

ATEX Standard EN 60079-7


ATEX Nominal Voltage Un 630 V
ATEX Nominal Current In 24 A
ATEX Cross Sec. Flexible Max. 4 mm2

Ratings - CSA

CSA Standard
B - CSA Nominal Voltage UN 0V
B - CSA Nominal Current IN 0A
B - CSA Wire Min 0 AWG
B - CSA Wire Max 0 AWG

Ratings - UL

UL Standard UL 1059
B - UL Nominal Voltage UN 600 V
B - UL Nominal Current IN 30 A
B - UL Wire Min 20 AWG
B - UL Wire Max 10 AWG

2 https://www.elmex.net/
Annexure 4. I/O of TRM
TRM-RMU

Station Type : Station Name : Station Address: IP Address: MAC Address:


SS Substation RD1833 RD1833

RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling Box )


Object ADDR EC 870

I/ O Text / Description
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status
Baytype ( Comment ) Remarks
YY01 RTU DO 01 LUCY TB2 - 01 030/000/108 Station 2 00 00 C.Station (22kV Common) - DC DUMMY RELAY OFF - YY01 DO-17B
YY01 RTU DO 02 LUCY TB2 - 01 030/000/108 Station 2 00 00 C.Station (22kV Common) - DC DUMMY RELAY ON - YY01 DO-18B
YY01 RTU DO 03 LUCY TB1 DO-1B 01 055/001/112 Station 2 SS - 11 A01-FE (22kV Feeder LBS - 1) - DC LISO_C LOAD ISOLATOR OPEN W101 C J01-3 MDF J01 137
YY01 RTU DO 04 LUCY TB1 DO-2B 01 055/001/112 Station 2 SS - 11 A01-FE (22kV Feeder LBS - 1) - DC LISC_C LOAD ISOLATOR CLOSED W101 D J01-4 MDF J01 138
YY01 RTU DO 05 LUCY TB1 DO-3B 01 056/002/104 Station 2 SS - 11 A02-FE (22kV Transformer CB - 1) - DC CBO_C CIRCUIT BREAKER OPEN W102 C J02-42 MDF J02 199
01 056/002/104 Station 2 SS - 11 A02-FE (22kV Transformer CB - 1) - DC CBC_C CIRCUIT BREAKER CLOSED

YY01 RTU DO 06 LUCY TB1 DO-5B 01 055/004/112 Station 2 SS - 11 A04-FE (22kV Feeder LBS - 2) - DC LISO_C LOAD ISOLATOR OPEN W101 K J04-17 MDF J04 137
YY01 RTU DO 07 LUCY TB1 DO-6B 01 055/004/112 Station 2 SS - 11 A04-FE (22kV Feeder LBS - 2) - DC LISC_C LOAD ISOLATOR CLOSED W101 L J04-18 MDF J04 138

YY01 RTU +24V DC LUCY TB1 24VS 01 +24V DC W101 A J01-1 MDF J01
YY01 RTU OV DC LUCY TB1 OVS 01 0V DC W101 B J01-2 MDF J01
YY01 RTU C/R LUCY TB1 DI-1B 01 Common Return (C/R) W101 G J01-7 MDF J01 69
YY01 RTU C/R LUCY TB2 DI-19B 01 Common Return (C/R) W101 J J04-64 MDF J04 69
YY01 RTU C/R LUCY TB1 DI-5B 01 Common Return (C/R) W101 N J04-21 MDF J04 69
YY01 RTU A1 01 LUCY TB1 AI-13A 01 056/002/132 Station 2 SS - 11 A02-FE (22kV Transformer CB - 1) - M A+ CURRENT + W102 T J02-122 MDF J02 205
YY01 RTU A1 02 LUCY TB1 AI-13B 01 056/002/132 Station 2 SS - 11 A02-FE (22kV Transformer CB - 1) - M A- CURRENT - W102 V J02-124 MDF J02 206
YY01 RTU A1 03 LUCY TB1 AI-14A 01 056/003/132 Station 2 SS - 11 A03-FE (22kV Transformer CB - 2) - M A+ CURRENT + W103 T J03-122 MDF J03 205
YY01 RTU A1 04 LUCY TB1 AI-14B 01 056/003/132 Station 2 SS - 11 A03-FE (22kV Transformer CB - 2) - M A- CURRENT - W103 V J03-124 MDF J03 206

YY01 RTU PS L1 01 RTU AC SUPPLY W501 bk YH01 230V AC P


YY01 RTU PS N 01 RTU AC SUPPLY W501 bu YH01 230V AC N

YY01 RTU +24V DC LUCY TB1 24VS 01 +24V DC W102 A J02-41 MDF J02 121
YY01 RTU C/R LUCY TB1 DI-3B 01 Common Return (C/R) W102 G J02-33 MDF J02 69
YY01 RTU C/R LUCY TB2 DI-20B 01 Common Return (C/R) W102 J CS-43 MDF J02 69
YY01 RTU C/R LUCY TB1 DI-10B 01 Common Return (C/R) W102 M J02-95 MDF J02 69
YY01 RTU C/R LUCY TB1 DI-9B 01 Common Return (C/R) W102 P J02-98 MDF J02 69

YY01 RTU +24V DC LUCY TB1 24VS 01 +24V DC W103 A J03-41 MDF J03 121
YY01 RTU C/R LUCY TB1 DI-7B 01 Common Return (C/R) W103 G J03-33 MDF J03 69
YY01 RTU C/R LUCY TB2 DI-20B 01 Common Return (C/R) W103 J CS-43 MDF J03 69
YY01 RTU C/R LUCY TB1 DI-12B 01 Common Return (C/R) W103 M J03-95 MDF J03 69
YY01 RTU C/R LUCY TB1 DI-11B 01 Common Return (C/R) W103 P J03-98 MDF J03 69
Station Type : Station Name :
SS Substation RD1833

RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling Box )


Object ADDR EC 870

I/ O Text / Description
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status
Baytype ( Comment ) Remarks
YY01 RTU DI 01 LUCY TB2 - 01 030/000/005 Station 2 00 00 C.Station (22kV Common) - DP DUM OFF DUMMY RELAY OFF - 0 YY01 DI-15A
YY01 RTU DI 02 LUCY TB2 - 01 030/000/005 Station 2 00 00 C.Station (22kV Common) - DP DUM ON DUMMY RELAY ON - 0 YY01 DI-16A
YY01 RTU DI 03 LUCY TB1 - 01 030/000/042 Station 2 00 00 C.Station (22kV Common) - SP MCBA MCB Alarm - 0 YY01
YY01 RTU DI 04 LUCY TB1 - 01 030/000/250 Station 2 00 00 C.Station (22kV Common) - SP 24VDCAL 24V DC Alarm - 0 YY01
YY01 RTU DI 05 LUCY TB1 - 01 030/000/201 Station 2 00 00 C.Station (22kV Common) - SP STNL/R Station Control Local / Remote - 0 YY01
YY01 RTU DI 06 LUCY TB2 DI-20A 01 030/000/041 Station 2 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W102 H CS-44 MDF CS 58
01 030/000/041 Station 2 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W103 H CS-44 MDF CS 58

YY01 RTU DI 07 LUCY TB1 DI-1A 01 055/001/012 Station 2 SS - 11 A01-FE (22kV Feeder LBS - 1) - DP LISO LOAD ISOLATOR OPEN W101 F J01-9 MDF J01 23
YY01 RTU DI 08 LUCY TB1 DI-2A 01 055/001/012 Station 2 SS - 11 A01-FE (22kV Feeder LBS - 1) - DP LISC LOAD ISOLATOR CLOSED W101 E J01-8 MDF J01 24
YY01 RTU DI 15 LUCY TB2 DI-19A 01 055/001/031 Station 2 SS - 11 A01-FE (22kV Feeder LBS - 1) - SP EFI Earth Fault Indication W101 H J01-66 MDF J01 48

YY01 RTU DI 09 LUCY TB1 DI-3A 01 056/002/001 Station 2 SS - 11 A02-FE (22kV Transformer CB - 1) - DP CBO CIRCUIT BREAKER OPEN W102 F J02-35 MDF J02 1
YY01 RTU DI 10 LUCY TB1 DI-4A 01 056/002/001 Station 2 SS - 11 A02-FE (22kV Transformer CB - 1) - DP CBC CIRCUIT BREAKER CLOSED W102 E J02-34 MDF J02 2
YY01 RTU DI 11 LUCY TB1 DI-9A 01 056/002/205 Station 2 SS - 11 A02-FE (22kV Transformer CB - 1) - FL OCEFT Over Current/Earth Fault Trip W102 R J02-96 MDF J02 55
YY01 RTU DI 12 LUCY TB1 DI-10A 01 056/002/247 Station 2 SS - 11 A02-FE (22kV Transformer CB - 1) - SP PRF Protection Relay Faulty W102 N J02-93 MDF J02 333

YY01 RTU DI 13 LUCY TB1 DI-5A 01 055/004/012 (22kV Feeder LBS - 2) - SS - 11 A04-FE (22kV Feeder LBS - 2) - DP LISO LOAD ISOLATOR OPEN W101 P J04-23 MDF J04 23
YY01 RTU DI 14 LUCY TB1 DI-6A 01 055/004/012 (22kV Feeder LBS - 2) - SS - 11 A04-FE (22kV Feeder LBS - 2) - DP LISC LOAD ISOLATOR CLOSED W101 M J04-22 MDF J04 24
IO Typical QRM

Station Type : Station Name : Station Address: IP Address: MAC Address:


SS Substation RD1823 RD1823
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling
I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status

Box )
Baytype ( Comment ) Remarks
YY01 RTU DO 01 LUCY DSM 2A - 01 030/000/108 RD1823 00 00 C.Station (11kV Common) - DC DUMMY RELAY OFF - YY01 DO-17B
YY01 RTU DO 02 LUCY DSM 2A - 01 030/000/108 RD1823 00 00 C.Station (11kV Common) - DC DUMMY RELAY ON - YY01 DO-18B
YY01 RTU DO 03 LUCY DSM 1A DO-SW A 01 041/001/112 RD1823 SS - 22 A01-FE (22kV Feeder LBS - 1) - DC LISO_C LOAD ISOLATOR OPEN W101 C J01.XK MDF J01 9
YY01 RTU DO 04 LUCY DSM 1A DO-SW A 01 041/001/112 RD1823 SS - 22 A01-FE (22kV Feeder LBS - 1) - DC LISC_C LOAD ISOLATOR CLOSED W101 D J01.XK MDF J01 7
YY01 RTU DO 05 LUCY DSM 1B DO-SW B 01 042/002/104 RD1823 SS - 22 A02-FE (22kV Transformer CB - 1) DC CBO_C CIRCUIT BREAKER OPEN W102 C J02.XK MDF J02 4
01 042/002/104 RD1823 SS - 22 -A02-FE (22kV Transformer CB - 1) DC CBC_C CIRCUIT BREAKER CLOSED
YY01 RTU DO 06 LUCY DSM 2A DO-SW A 01 041/003/112 RD1823 SS - 22 -A03-FE (22kV Feeder LBS - 2) - DC LISO_C LOAD ISOLATOR OPEN W101 K J03.XK MDF J03 9
YY01 RTU DO 07 LUCY DSM 2A DO-SW A 01 041/003/112 RD1823 SS - 22 A03-FE (22kV Feeder LBS - 2) - DC LISC_C LOAD ISOLATOR CLOSED W101 L J03.XK MDF J03 7
YY01 RTU DO 08 LUCY DSM 2B DO-SW B 01 042/004/104 RD1823 SS - 22 A04-FE (22kV Transformer CB - 2) DC CBO_C CIRCUIT BREAKER OPEN W103 C J04.XK MDF J04 4
01 042/002/104 RD1823 SS - 22 -A04-FE (22kV Transformer CB - 2) DC CBC_C CIRCUIT BREAKER CLOSED
-
YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W101 A J01.XK MDF J01 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J01.XK MDF J01 2
YY01 RTU C/R LUCY DSM 1A DI SW A 01 Common Return (C/R) W102 G J01.XK MDF J01 2&4
YY01 RTU C/R LUCY DSM 1A DI 1 01 Common Return (C/R) W102 J J01.XK MDF J01 6
YY01 RTU C/R LUCY DSM 1A DI 4 01 Common Return (C/R) W102 M J01.XK MDF J01
YY01 RTU C/R LUCY DSM 2 A DI SW A 01 Common Return (C/R) W102 P J03.XK MDF J03 2&4
YY01 RTU C/R LUCY DSM 2 A DI 3 01 Common Return (C/R) W102 P J03.XK MDF J03 6
YY01 RTU C/R LUCY DSM 2 A DI 4 01 Common Return (C/R) W102 P J03.XK MDF J03

YY01 RTU A1 01 LUCY DSM 1B AI-SW B 01 042/002/132 RD1823 SS - 22 A02-FE (22kV Transformer CB - 1) M A+ CURRENT + W102 T J02.XK MDF J02 5
YY01 RTU A1 02 LUCY DSM 1B AI-SW B 01 042/002/132 RD1823 SS - 22 -A02-FE (22kV Transformer CB - 1) M A- CURRENT - W102 V J02.XK MDF J02 6
YY01 RTU A1 03 LUCY DSM 2B AI-SW B 01 042/004/132 RD1823 SS - 22 -A04-FE (22kV Transformer CB - 2) M A+ CURRENT + W103 T J04.XK MDF J04 5
YY01 RTU A1 04 LUCY DSM 2B AI-SW B 01 042/004/132 RD1823 SS - 22 -A04-FE (22kV Transformer CB - 2) M A- CURRENT - W103 V J04.XK MDF J04 6
-
YY01 RTU PS L1 01 RTU AC SUPPLY W501 bk YH01 230V AC P
YY01 RTU PS N 01 RTU AC SUPPLY W501 bu YH01 230V AC N

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J02.XK MDF J02 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J02.XK MDF J02 2
YY01 RTU C/R LUCY DSM 1B DI SW B 01 Common Return (C/R) W103 G J02.XK MDF J02 2&4
YY01 RTU C/R LUCY DSM 1B DI 4 01 Common Return (C/R) W103 J xx MDF J02 8
YY01 RTU C/R LUCY DSM 1B DI 2 01 Common Return (C/R) W103 M J02.XK MDF J02 8 & 10
YY01 RTU C/R LUCY DSM 1B DI 1 01 Common Return (C/R) W103 P J02.XK MDF J02 12

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J04.XK MDF J04 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J04.XK MDF J04 2
YY01 RTU C/R LUCY DSM 2B DI SW B 01 Common Return (C/R) W103 G J04.XK MDF J04 2&4
YY01 RTU C/R LUCY DSM 2B DI 4 01 Common Return (C/R) W103 J J04.XK MDF J04 8
YY01 RTU C/R LUCY DSM 2B DI 2 01 Common Return (C/R) W103 M J04.XK MDF J04 8 & 10
YY01 RTU C/R LUCY DSM 2B DI 1 01 Common Return (C/R) W103 P J04.XK MDF J04 12
IO Typical QRM(L EFI)

Station Type : Station Name :


SS Substation RD1823
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling Box


I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status
Baytype ( Comment ) Remarks

)
YY01 RTU DI 01 LUCY DSM 2A - 01 030/000/005 RD1823 00 00 C.Station (22kV Common) - DP DUM OFF DUMMY RELAY OFF - 0 YY01 DI-15A
YY01 RTU DI 02 LUCY DSM 2A - 01 030/000/005 RD1823 00 00 C.Station (22kV Common) - DP DUM ON DUMMY RELAY ON - 0 YY01 DI-16A
YY01 RTU DI 03 LUCY MCM - 01 030/000/042 RD1823 00 00 C.Station (22kV Common) - SP MCBA MCB Alarm - 0 YY01
YY01 RTU DI 04 LUCY ADEL - 01 030/000/250 RD1823 00 00 C.Station (22kV Common) - SP 24VDCAL 24V DC Alarm - 0 YY01
YY01 RTU DI 05 LUCY MCM - 01 030/000/201 RD1823 00 00 C.Station (22kV Common) - SP STNL/R Station Control Local / Remote - 0 YY01
YY01 RTU DI 06 LUCY DSM 2A DI-3 01 030/000/041 RD1823 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W102 H XX MDF CS 7
01 030/000/041 RD1823 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W103 H XX MDF CS 8

YY01 RTU DI 07 LUCY DSM 1A DI-SWA Open 01 041/001/012 RD1823 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISO LOAD ISOLATOR OPEN W101 F J01.XK MDF J01 1
YY01 RTU DI 08 LUCY DSM 1A DI-SWA Close 01 041/001/012 RD1823 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISC LOAD ISOLATOR CLOSED W101 E J01.XK MDF J01 3
YY01 RTU DI 15 LUCY DSM 1A DI-1 01 041/003/033 RD1823 SS - 22 A03-FE (22kV Feeder LBS - 2) - SP EFI Earth Fault Indication W101 H J01.XK MDF J01 5

YY01 RTU DI 09 LUCY DSM 1B DI-SWA Open 01 042/002/001 RD1823 SS - 22 A02-FE (22kV Transformer CB - 1) DP CBO CIRCUIT BREAKER OPEN W102 F J02.XK MDF J02 3
YY01 RTU DI 10 LUCY DSM 1B DI-SWA Close 01 042/002/001 RD1823 SS - 22 -A02-FE (22kV Transformer CB - 1) DP CBC CIRCUIT BREAKER CLOSED W102 E J02.XK MDF J02 1
YY01 RTU DI 11 LUCY DSM 1B DI-2 01 042/002/205 RD1823 SS - 22 -A02-FE (22kV Transformer CB - 1) FL OCEFT Over Current/Earth Fault Trip W102 R J02.XK MDF J02 7&9
YY01 RTU DI 12 LUCY DSM 1B DI-1 01 042/002/247 RD1823 SS - 22 -A02-FE (22kV Transformer CB - 1) SP PRF Protection Relay Faulty W102 N J02.XK MDF J02 11
-

YY01 RTU DI 13 LUCY DSM 2A DI-SWA Open 01 041/003/012 RD1823 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISO LOAD ISOLATOR OPEN W101 P J03.XK MDF J03 1
YY01 RTU DI 14 LUCY DSM 2A DI-SWA Close 01 041/003/012 RD1823 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISC LOAD ISOLATOR CLOSED W101 M J03.XK MDF J03 3

YY01 RTU DI 16 LUCY DSM 2B DI-SWA Open 01 042/004/001 RD1823 SS - 22 A04-FE (22kV Transformer CB - 2) DP CBO CIRCUIT BREAKER OPEN W103 F J04.XK MDF J04 3
YY01 RTU DI 17 LUCY DSM 2B DI-SWA Close 01 042/004/001 RD1823 SS - 22 -A04-FE (22kV Transformer CB - 2) DP CBC CIRCUIT BREAKER CLOSED W103 E J04.XK MDF J04 1
YY01 RTU DI 18 LUCY DSM 2B DI-2 01 042/004/205 RD1823 SS - 22 -A04-FE (22kV Transformer CB - 2) FL OCEFT Over Current/Earth Fault Trip W103 R J04.XK MDF J04 7&9
YY01 RTU DI 19 LUCY DSM 2B DI-1 01 042/004/247 RD1823 SS - 22 -
A04-FE (22kV Transformer CB - 2) - SP PRF Protection Relay Faulty W103 N J04.XK MDF J04 11
IO Typical QRM

Station Type : Station Name : Station Address: IP Address: MAC Address:


SS Substation RD1910 RD1910
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling
I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status

Box )
Baytype ( Comment ) Remarks
YY01 RTU DO 01 LUCY DSM 2A - 01 030/000/108 RD1910 00 00 C.Station (22kV Common) DC DUMMY RELAY OFF - YY01 DO-17B
YY01 RTU DO 02 LUCY DSM 2A - 01 030/000/108 RD1910 00 00 -C.Station (22kV Common) DC DUMMY RELAY ON - YY01 DO-18B
YY01 RTU DO 03 LUCY DSM 1A DO-SW A 01 041/001/112 RD1910 SS - 22 A01-FE (22kV Feeder-LBS - 1) - DC LISO_C LOAD ISOLATOR OPEN W101 C J01.XK MDF J01 9
YY01 RTU DO 04 LUCY DSM 1A DO-SW A 01 041/001/112 RD1910 SS - 22 A01-FE (22kV Feeder LBS - 1) - DC LISC_C LOAD ISOLATOR CLOSED W101 D J01.XK MDF J01 7
YY01 RTU DO 05 LUCY DSM 1B DO-SW B 01 042/002/104 RD1910 SS - 22 A02-FE (22kV Transformer CB - 1) DC CBO_C CIRCUIT BREAKER OPEN W102 C J02.XK MDF J02 4
01 042/002/104 RD1910 SS - 22 -A02-FE (22kV Transformer CB - 1) DC CBC_C CIRCUIT BREAKER CLOSED
YY01 RTU DO 06 LUCY DSM 2A DO-SW A 01 041/003/112 RD1910 SS - 22 -A03-FE (22kV Feeder LBS - 2) - DC LISO_C LOAD ISOLATOR OPEN W101 K J03.XK MDF J03 9
YY01 RTU DO 07 LUCY DSM 2A DO-SW A 01 041/003/112 RD1910 SS - 22 A03-FE (22kV Feeder LBS - 2) - DC LISC_C LOAD ISOLATOR CLOSED W101 L J03.XK MDF J03 7
YY01 RTU DO 08 LUCY DSM 2B DO-SW B 01 042/004/104 RD1910 SS - 22 A04-FE (22kV Transformer CB - 2) DC CBO_C CIRCUIT BREAKER OPEN W103 C J04.XK MDF J04 4
01 042/002/104 RD1910 SS - 22 -A04-FE (22kV Transformer CB - 2) DC CBC_C CIRCUIT BREAKER CLOSED
-
YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W101 A J01.XK MDF J01 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J01.XK MDF J01 2
YY01 RTU C/R LUCY DSM 1A DI SW A 01 Common Return (C/R) W102 G J01.XK MDF J01 2&4
YY01 RTU C/R LUCY DSM 1A DI 1 01 Common Return (C/R) W102 J J01.XK MDF J01 6
YY01 RTU C/R LUCY DSM 1A DI 4 01 Common Return (C/R) W102 M J01.XK MDF J01
YY01 RTU C/R LUCY DSM 2 A DI SW A 01 Common Return (C/R) W102 P J03.XK MDF J03 2&4
YY01 RTU C/R LUCY DSM 2 A DI 3 01 Common Return (C/R) W102 P J03.XK MDF J03 6
YY01 RTU C/R LUCY DSM 2 A DI 4 01 Common Return (C/R) W102 P J03.XK MDF J03

YY01 RTU A1 01 LUCY DSM 1B AI-SW B 01 042/002/132 RD1910 SS - 22 A02-FE (22kV Transformer CB - 1) M A+ CURRENT + W102 T J02.XK MDF J02 5
YY01 RTU A1 02 LUCY DSM 1B AI-SW B 01 042/002/132 RD1910 SS - 22 -A02-FE (22kV Transformer CB - 1) M A- CURRENT - W102 V J02.XK MDF J02 6
YY01 RTU A1 03 LUCY DSM 2B AI-SW B 01 042/004/132 RD1910 SS - 22 -A04-FE (22kV Transformer CB - 2) M A+ CURRENT + W103 T J04.XK MDF J04 5
YY01 RTU A1 04 LUCY DSM 2B AI-SW B 01 042/004/132 RD1910 SS - 22 -A04-FE (22kV Transformer CB - 2) M A- CURRENT - W103 V J04.XK MDF J04 6
-
YY01 RTU PS L1 01 RTU AC SUPPLY W501 bk YH01 230V AC P
YY01 RTU PS N 01 RTU AC SUPPLY W501 bu YH01 230V AC N

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J02.XK MDF J02 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J02.XK MDF J02 2
YY01 RTU C/R LUCY DSM 1B DI SW B 01 Common Return (C/R) W103 G J02.XK MDF J02 2&4
YY01 RTU C/R LUCY DSM 1B DI 4 01 Common Return (C/R) W103 J xx MDF J02 8
YY01 RTU C/R LUCY DSM 1B DI 2 01 Common Return (C/R) W103 M J02.XK MDF J02 8 & 10
YY01 RTU C/R LUCY DSM 1B DI 1 01 Common Return (C/R) W103 P J02.XK MDF J02 12

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J04.XK MDF J04 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J04.XK MDF J04 2
YY01 RTU C/R LUCY DSM 2B DI SW B 01 Common Return (C/R) W103 G J04.XK MDF J04 2&4
YY01 RTU C/R LUCY DSM 2B DI 4 01 Common Return (C/R) W103 J J04.XK MDF J04 8
YY01 RTU C/R LUCY DSM 2B DI 2 01 Common Return (C/R) W103 M J04.XK MDF J04 8 & 10
YY01 RTU C/R LUCY DSM 2B DI 1 01 Common Return (C/R) W103 P J04.XK MDF J04 12
IO Typical QRM(L EFI)

Station Type : Station Name :


SS Substation RD1910
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling Box


I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status
Baytype ( Comment ) Remarks

)
YY01 RTU DI 01 LUCY DSM 2A - 01 030/000/005 RD1823 00 00 C.Station (22kV Common) - DP DUM OFF DUMMY RELAY OFF - 0 YY01 DI-15A
YY01 RTU DI 02 LUCY DSM 2A - 01 030/000/005 RD1823 00 00 C.Station (22kV Common) - DP DUM ON DUMMY RELAY ON - 0 YY01 DI-16A
YY01 RTU DI 03 LUCY MCM - 01 030/000/042 RD1823 00 00 C.Station (22kV Common) - SP MCBA MCB Alarm - 0 YY01
YY01 RTU DI 04 LUCY ADEL - 01 030/000/250 RD1823 00 00 C.Station (22kV Common) - SP 24VDCAL 24V DC Alarm - 0 YY01
YY01 RTU DI 05 LUCY MCM - 01 030/000/201 RD1823 00 00 C.Station (22kV Common) - SP STNL/R Station Control Local / Remote - 0 YY01
YY01 RTU DI 06 LUCY DSM 2A DI-3 01 030/000/041 RD1823 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W102 H XX MDF CS 7
01 030/000/041 RD1823 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W103 H XX MDF CS 8

YY01 RTU DI 07 LUCY DSM 1A DI-SWA Open 01 041/001/012 RD1823 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISO LOAD ISOLATOR OPEN W101 F J01.XK MDF J01 1
YY01 RTU DI 08 LUCY DSM 1A DI-SWA Close 01 041/001/012 RD1823 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISC LOAD ISOLATOR CLOSED W101 E J01.XK MDF J01 3
YY01 RTU DI 15 LUCY DSM 1A DI-1 01 041/003/033 RD1823 SS - 22 A03-FE (22kV Feeder LBS - 2) - SP EFI Earth Fault Indication W101 H J01.XK MDF J01 5

YY01 RTU DI 09 LUCY DSM 1B DI-SWA Open 01 042/002/001 RD1823 SS - 22 A02-FE (22kV Transformer CB - 1) DP CBO CIRCUIT BREAKER OPEN W102 F J02.XK MDF J02 3
YY01 RTU DI 10 LUCY DSM 1B DI-SWA Close 01 042/002/001 RD1823 SS - 22 -A02-FE (22kV Transformer CB - 1) DP CBC CIRCUIT BREAKER CLOSED W102 E J02.XK MDF J02 1
YY01 RTU DI 11 LUCY DSM 1B DI-2 01 042/002/205 RD1823 SS - 22 -A02-FE (22kV Transformer CB - 1) FL OCEFT Over Current/Earth Fault Trip W102 R J02.XK MDF J02 7&9
YY01 RTU DI 12 LUCY DSM 1B DI-1 01 042/002/247 RD1823 SS - 22 -A02-FE (22kV Transformer CB - 1) SP PRF Protection Relay Faulty W102 N J02.XK MDF J02 11
-

YY01 RTU DI 13 LUCY DSM 2A DI-SWA Open 01 041/003/012 RD1823 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISO LOAD ISOLATOR OPEN W101 P J03.XK MDF J03 1
YY01 RTU DI 14 LUCY DSM 2A DI-SWA Close 01 041/003/012 RD1823 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISC LOAD ISOLATOR CLOSED W101 M J03.XK MDF J03 3

YY01 RTU DI 16 LUCY DSM 2B DI-SWA Open 01 042/004/001 RD1823 SS - 22 A04-FE (22kV Transformer CB - 2) DP CBO CIRCUIT BREAKER OPEN W103 F J04.XK MDF J04 3
YY01 RTU DI 17 LUCY DSM 2B DI-SWA Close 01 042/004/001 RD1823 SS - 22 -A04-FE (22kV Transformer CB - 2) DP CBC CIRCUIT BREAKER CLOSED W103 E J04.XK MDF J04 1
YY01 RTU DI 18 LUCY DSM 2B DI-2 01 042/004/205 RD1823 SS - 22 -A04-FE (22kV Transformer CB - 2) FL OCEFT Over Current/Earth Fault Trip W103 R J04.XK MDF J04 7&9
YY01 RTU DI 19 LUCY DSM 2B DI-1 01 042/004/247 RD1823 SS - 22 -
A04-FE (22kV Transformer CB - 2) - SP PRF Protection Relay Faulty W103 N J04.XK MDF J04 11
IO Typical QRM

Station Type : Station Name : Station Address: IP Address: MAC Address:


SS Substation RD2412 RD2412
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling
I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status

Box )
Baytype ( Comment ) Remarks
YY01 RTU DO 01 LUCY DSM 2A - 01 030/000/108 RD2412 00 00 C.Station (22kV Common) DC DUMMY RELAY OFF - YY01 DO-17B
YY01 RTU DO 02 LUCY DSM 2A - 01 030/000/108 RD2412 00 00 -C.Station (22kV Common) DC DUMMY RELAY ON - YY01 DO-18B
YY01 RTU DO 03 LUCY DSM 1A DO-SW A 01 041/001/112 RD2412 SS - 22 A01-FE (22kV Feeder-LBS - 1) - DC LISO_C LOAD ISOLATOR OPEN W101 C J01.XK MDF J01 9
YY01 RTU DO 04 LUCY DSM 1A DO-SW A 01 041/001/112 RD2412 SS - 22 A01-FE (22kV Feeder LBS - 1) - DC LISC_C LOAD ISOLATOR CLOSED W101 D J01.XK MDF J01 7
YY01 RTU DO 05 LUCY DSM 1B DO-SW B 01 042/002/104 RD2412 SS - 22 A02-FE (22kV Transformer CB - 1) DC CBO_C CIRCUIT BREAKER OPEN W102 C J02.XK MDF J02 4
01 042/002/104 RD2412 SS - 22 -A02-FE (22kV Transformer CB - 1) DC CBC_C CIRCUIT BREAKER CLOSED
YY01 RTU DO 06 LUCY DSM 2A DO-SW A 01 041/003/112 RD2412 SS - 22 -A03-FE (22kV Feeder LBS - 2) - DC LISO_C LOAD ISOLATOR OPEN W101 K J03.XK MDF J03 9
YY01 RTU DO 07 LUCY DSM 2A DO-SW A 01 041/003/112 RD2412 SS - 22 A03-FE (22kV Feeder LBS - 2) - DC LISC_C LOAD ISOLATOR CLOSED W101 L J03.XK MDF J03 7
YY01 RTU DO 08 LUCY DSM 2B DO-SW B 01 042/004/104 RD2412 SS - 22 A04-FE (22kV Transformer CB - 2) DC CBO_C CIRCUIT BREAKER OPEN W103 C J04.XK MDF J04 4
01 042/002/104 RD2412 SS - 22 -A04-FE (22kV Transformer CB - 2) DC CBC_C CIRCUIT BREAKER CLOSED
-
YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W101 A J01.XK MDF J01 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J01.XK MDF J01 2
YY01 RTU C/R LUCY DSM 1A DI SW A 01 Common Return (C/R) W102 G J01.XK MDF J01 2&4
YY01 RTU C/R LUCY DSM 1A DI 1 01 Common Return (C/R) W102 J J01.XK MDF J01 6
YY01 RTU C/R LUCY DSM 1A DI 4 01 Common Return (C/R) W102 M J01.XK MDF J01
YY01 RTU C/R LUCY DSM 2 A DI SW A 01 Common Return (C/R) W102 P J03.XK MDF J03 2&4
YY01 RTU C/R LUCY DSM 2 A DI 3 01 Common Return (C/R) W102 P J03.XK MDF J03 6
YY01 RTU C/R LUCY DSM 2 A DI 4 01 Common Return (C/R) W102 P J03.XK MDF J03

YY01 RTU A1 01 LUCY DSM 1B AI-SW B 01 042/002/132 RD2412 SS - 22 A02-FE (22kV Transformer CB - 1) M A+ CURRENT + W102 T J02.XK MDF J02 5
YY01 RTU A1 02 LUCY DSM 1B AI-SW B 01 042/002/132 RD2412 SS - 22 -A02-FE (22kV Transformer CB - 1) M A- CURRENT - W102 V J02.XK MDF J02 6
YY01 RTU A1 03 LUCY DSM 2B AI-SW B 01 042/004/132 RD2412 SS - 22 -A04-FE (22kV Transformer CB - 2) M A+ CURRENT + W103 T J04.XK MDF J04 5
YY01 RTU A1 04 LUCY DSM 2B AI-SW B 01 042/004/132 RD2412 SS - 22 -A04-FE (22kV Transformer CB - 2) M A- CURRENT - W103 V J04.XK MDF J04 6
-
YY01 RTU PS L1 01 RTU AC SUPPLY W501 bk YH01 230V AC P
YY01 RTU PS N 01 RTU AC SUPPLY W501 bu YH01 230V AC N

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J02.XK MDF J02 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J02.XK MDF J02 2
YY01 RTU C/R LUCY DSM 1B DI SW B 01 Common Return (C/R) W103 G J02.XK MDF J02 2&4
YY01 RTU C/R LUCY DSM 1B DI 4 01 Common Return (C/R) W103 J xx MDF J02 8
YY01 RTU C/R LUCY DSM 1B DI 2 01 Common Return (C/R) W103 M J02.XK MDF J02 8 & 10
YY01 RTU C/R LUCY DSM 1B DI 1 01 Common Return (C/R) W103 P J02.XK MDF J02 12

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J04.XK MDF J04 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J04.XK MDF J04 2
YY01 RTU C/R LUCY DSM 2B DI SW B 01 Common Return (C/R) W103 G J04.XK MDF J04 2&4
YY01 RTU C/R LUCY DSM 2B DI 4 01 Common Return (C/R) W103 J J04.XK MDF J04 8
YY01 RTU C/R LUCY DSM 2B DI 2 01 Common Return (C/R) W103 M J04.XK MDF J04 8 & 10
YY01 RTU C/R LUCY DSM 2B DI 1 01 Common Return (C/R) W103 P J04.XK MDF J04 12
IO Typical QRM(L EFI)

Station Type : Station Name :


SS Substation RD2412
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling Box


I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status
Baytype ( Comment ) Remarks

)
YY01 RTU DI 01 LUCY DSM 2A - 01 030/000/005 RD2412 00 00 C.Station (22kV Common) - DP DUM OFF DUMMY RELAY OFF - 0 YY01 DI-15A
YY01 RTU DI 02 LUCY DSM 2A - 01 030/000/005 RD2412 00 00 C.Station (22kV Common) - DP DUM ON DUMMY RELAY ON - 0 YY01 DI-16A
YY01 RTU DI 03 LUCY MCM - 01 030/000/042 RD2412 00 00 C.Station (22kV Common) - SP MCBA MCB Alarm - 0 YY01
YY01 RTU DI 04 LUCY ADEL - 01 030/000/250 RD2412 00 00 C.Station (22kV Common) - SP 24VDCAL 24V DC Alarm - 0 YY01
YY01 RTU DI 05 LUCY MCM - 01 030/000/201 RD2412 00 00 C.Station (22kV Common) - SP STNL/R Station Control Local / Remote - 0 YY01
YY01 RTU DI 06 LUCY DSM 2A DI-3 01 030/000/041 RD2412 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W102 H XX MDF CS 7
01 030/000/041 RD2412 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W103 H XX MDF CS 8

YY01 RTU DI 07 LUCY DSM 1A DI-SWA Open 01 041/001/012 RD2412 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISO LOAD ISOLATOR OPEN W101 F J01.XK MDF J01 1
YY01 RTU DI 08 LUCY DSM 1A DI-SWA Close 01 041/001/012 RD2412 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISC LOAD ISOLATOR CLOSED W101 E J01.XK MDF J01 3
YY01 RTU DI 15 LUCY DSM 1A DI-1 01 041/003/033 RD2412 SS - 22 A03-FE (22kV Feeder LBS - 2) - SP EFI Earth Fault Indication W101 H J01.XK MDF J01 5

YY01 RTU DI 09 LUCY DSM 1B DI-SWA Open 01 042/002/001 RD2412 SS - 22 A02-FE (22kV Transformer CB - 1) DP CBO CIRCUIT BREAKER OPEN W102 F J02.XK MDF J02 3
YY01 RTU DI 10 LUCY DSM 1B DI-SWA Close 01 042/002/001 RD2412 SS - 22 -A02-FE (22kV Transformer CB - 1) DP CBC CIRCUIT BREAKER CLOSED W102 E J02.XK MDF J02 1
YY01 RTU DI 11 LUCY DSM 1B DI-2 01 042/002/205 RD2412 SS - 22 -A02-FE (22kV Transformer CB - 1) FL OCEFT Over Current/Earth Fault Trip W102 R J02.XK MDF J02 7&9
YY01 RTU DI 12 LUCY DSM 1B DI-1 01 042/002/247 RD2412 SS - 22 -A02-FE (22kV Transformer CB - 1) SP PRF Protection Relay Faulty W102 N J02.XK MDF J02 11
-

YY01 RTU DI 13 LUCY DSM 2A DI-SWA Open 01 041/003/012 RD2412 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISO LOAD ISOLATOR OPEN W101 P J03.XK MDF J03 1
YY01 RTU DI 14 LUCY DSM 2A DI-SWA Close 01 041/003/012 RD2412 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISC LOAD ISOLATOR CLOSED W101 M J03.XK MDF J03 3

YY01 RTU DI 16 LUCY DSM 2B DI-SWA Open 01 042/004/001 RD2412 SS - 22 A04-FE (22kV Transformer CB - 2) DP CBO CIRCUIT BREAKER OPEN W103 F J04.XK MDF J04 3
YY01 RTU DI 17 LUCY DSM 2B DI-SWA Close 01 042/004/001 RD2412 SS - 22 -A04-FE (22kV Transformer CB - 2) DP CBC CIRCUIT BREAKER CLOSED W103 E J04.XK MDF J04 1
YY01 RTU DI 18 LUCY DSM 2B DI-2 01 042/004/205 RD2412 SS - 22 -A04-FE (22kV Transformer CB - 2) FL OCEFT Over Current/Earth Fault Trip W103 R J04.XK MDF J04 7&9
YY01 RTU DI 19 LUCY DSM 2B DI-1 01 042/004/247 RD2412 SS - 22 -
A04-FE (22kV Transformer CB - 2) - SP PRF Protection Relay Faulty W103 N J04.XK MDF J04 11
IO Typical QRM

Station Type : Station Name : Station Address: IP Address: MAC Address:


SS Substation RD3012 RD3012
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling
I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status

Box )
Baytype ( Comment ) Remarks
YY01 RTU DO 01 LUCY DSM 2A - 01 030/000/108 RD3012 00 00 C.Station (22kV Common) DC DUMMY RELAY OFF - YY01 DO-17B
YY01 RTU DO 02 LUCY DSM 2A - 01 030/000/108 RD3012 00 00 -C.Station (22kV Common) DC DUMMY RELAY ON - YY01 DO-18B
YY01 RTU DO 03 LUCY DSM 1A DO-SW A 01 041/001/112 RD3012 SS - 22 A01-FE (22kV Feeder-LBS - 1) - DC LISO_C LOAD ISOLATOR OPEN W101 C J01.XK MDF J01 9
YY01 RTU DO 04 LUCY DSM 1A DO-SW A 01 041/001/112 RD3012 SS - 22 A01-FE (22kV Feeder LBS - 1) - DC LISC_C LOAD ISOLATOR CLOSED W101 D J01.XK MDF J01 7
YY01 RTU DO 05 LUCY DSM 1B DO-SW B 01 042/002/104 RD3012 SS - 22 A02-FE (22kV Transformer CB - 1) DC CBO_C CIRCUIT BREAKER OPEN W102 C J02.XK MDF J02 4
01 042/002/104 RD3012 SS - 22 -A02-FE (22kV Transformer CB - 1) DC CBC_C CIRCUIT BREAKER CLOSED
YY01 RTU DO 06 LUCY DSM 2A DO-SW A 01 041/003/112 RD3012 SS - 22 -A03-FE (22kV Feeder LBS - 2) - DC LISO_C LOAD ISOLATOR OPEN W101 K J03.XK MDF J03 9
YY01 RTU DO 07 LUCY DSM 2A DO-SW A 01 041/003/112 RD3012 SS - 22 A03-FE (22kV Feeder LBS - 2) - DC LISC_C LOAD ISOLATOR CLOSED W101 L J03.XK MDF J03 7
YY01 RTU DO 08 LUCY DSM 2B DO-SW B 01 042/004/104 RD3012 SS - 22 A04-FE (22kV Transformer CB - 2) DC CBO_C CIRCUIT BREAKER OPEN W103 C J04.XK MDF J04 4
01 042/002/104 RD3012 SS - 22 -A04-FE (22kV Transformer CB - 2) DC CBC_C CIRCUIT BREAKER CLOSED
-
YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W101 A J01.XK MDF J01 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J01.XK MDF J01 2
YY01 RTU C/R LUCY DSM 1A DI SW A 01 Common Return (C/R) W102 G J01.XK MDF J01 2&4
YY01 RTU C/R LUCY DSM 1A DI 1 01 Common Return (C/R) W102 J J01.XK MDF J01 6
YY01 RTU C/R LUCY DSM 1A DI 4 01 Common Return (C/R) W102 M J01.XK MDF J01
YY01 RTU C/R LUCY DSM 2 A DI SW A 01 Common Return (C/R) W102 P J03.XK MDF J03 2&4
YY01 RTU C/R LUCY DSM 2 A DI 3 01 Common Return (C/R) W102 P J03.XK MDF J03 6
YY01 RTU C/R LUCY DSM 2 A DI 4 01 Common Return (C/R) W102 P J03.XK MDF J03

YY01 RTU A1 01 LUCY DSM 1B AI-SW B 01 042/002/132 RD3012 SS - 22 A02-FE (22kV Transformer CB - 1) M A+ CURRENT + W102 T J02.XK MDF J02 5
YY01 RTU A1 02 LUCY DSM 1B AI-SW B 01 042/002/132 RD3012 SS - 22 -A02-FE (22kV Transformer CB - 1) M A- CURRENT - W102 V J02.XK MDF J02 6
YY01 RTU A1 03 LUCY DSM 2B AI-SW B 01 042/004/132 RD3012 SS - 22 -A04-FE (22kV Transformer CB - 2) M A+ CURRENT + W103 T J04.XK MDF J04 5
YY01 RTU A1 04 LUCY DSM 2B AI-SW B 01 042/004/132 RD3012 SS - 22 -A04-FE (22kV Transformer CB - 2) M A- CURRENT - W103 V J04.XK MDF J04 6
-
YY01 RTU PS L1 01 RTU AC SUPPLY W501 bk YH01 230V AC P
YY01 RTU PS N 01 RTU AC SUPPLY W501 bu YH01 230V AC N

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J02.XK MDF J02 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J02.XK MDF J02 2
YY01 RTU C/R LUCY DSM 1B DI SW B 01 Common Return (C/R) W103 G J02.XK MDF J02 2&4
YY01 RTU C/R LUCY DSM 1B DI 4 01 Common Return (C/R) W103 J xx MDF J02 8
YY01 RTU C/R LUCY DSM 1B DI 2 01 Common Return (C/R) W103 M J02.XK MDF J02 8 & 10
YY01 RTU C/R LUCY DSM 1B DI 1 01 Common Return (C/R) W103 P J02.XK MDF J02 12

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J04.XK MDF J04 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J04.XK MDF J04 2
YY01 RTU C/R LUCY DSM 2B DI SW B 01 Common Return (C/R) W103 G J04.XK MDF J04 2&4
YY01 RTU C/R LUCY DSM 2B DI 4 01 Common Return (C/R) W103 J J04.XK MDF J04 8
YY01 RTU C/R LUCY DSM 2B DI 2 01 Common Return (C/R) W103 M J04.XK MDF J04 8 & 10
YY01 RTU C/R LUCY DSM 2B DI 1 01 Common Return (C/R) W103 P J04.XK MDF J04 12
IO Typical QRM(L EFI)

Station Type : Station Name :


SS Substation RD2412
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling Box


I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status
Baytype ( Comment ) Remarks

)
YY01 RTU DI 01 LUCY DSM 2A - 01 030/000/005 RD3012 00 00 C.Station (22kV Common) - DP DUM OFF DUMMY RELAY OFF - 0 YY01 DI-15A
YY01 RTU DI 02 LUCY DSM 2A - 01 030/000/005 RD3012 00 00 C.Station (22kV Common) - DP DUM ON DUMMY RELAY ON - 0 YY01 DI-16A
YY01 RTU DI 03 LUCY MCM - 01 030/000/042 RD3012 00 00 C.Station (22kV Common) - SP MCBA MCB Alarm - 0 YY01
YY01 RTU DI 04 LUCY ADEL - 01 030/000/250 RD3012 00 00 C.Station (22kV Common) - SP 24VDCAL 24V DC Alarm - 0 YY01
YY01 RTU DI 05 LUCY MCM - 01 030/000/201 RD3012 00 00 C.Station (22kV Common) - SP STNL/R Station Control Local / Remote - 0 YY01
YY01 RTU DI 06 LUCY DSM 2A DI-3 01 030/000/041 RD3012 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W102 H XX MDF CS 7
01 030/000/041 RD3012 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W103 H XX MDF CS 8

YY01 RTU DI 07 LUCY DSM 1A DI-SWA Open 01 041/001/012 RD3012 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISO LOAD ISOLATOR OPEN W101 F J01.XK MDF J01 1
YY01 RTU DI 08 LUCY DSM 1A DI-SWA Close 01 041/001/012 RD3012 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISC LOAD ISOLATOR CLOSED W101 E J01.XK MDF J01 3
YY01 RTU DI 15 LUCY DSM 1A DI-1 01 041/003/033 RD3012 SS - 22 A03-FE (22kV Feeder LBS - 2) - SP EFI Earth Fault Indication W101 H J01.XK MDF J01 5

YY01 RTU DI 09 LUCY DSM 1B DI-SWA Open 01 042/002/001 RD3012 SS - 22 A02-FE (22kV Transformer CB - 1) DP CBO CIRCUIT BREAKER OPEN W102 F J02.XK MDF J02 3
YY01 RTU DI 10 LUCY DSM 1B DI-SWA Close 01 042/002/001 RD3012 SS - 22 -A02-FE (22kV Transformer CB - 1) DP CBC CIRCUIT BREAKER CLOSED W102 E J02.XK MDF J02 1
YY01 RTU DI 11 LUCY DSM 1B DI-2 01 042/002/205 RD3012 SS - 22 -A02-FE (22kV Transformer CB - 1) FL OCEFT Over Current/Earth Fault Trip W102 R J02.XK MDF J02 7&9
YY01 RTU DI 12 LUCY DSM 1B DI-1 01 042/002/247 RD3012 SS - 22 -A02-FE (22kV Transformer CB - 1) SP PRF Protection Relay Faulty W102 N J02.XK MDF J02 11
-

YY01 RTU DI 13 LUCY DSM 2A DI-SWA Open 01 041/003/012 RD3012 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISO LOAD ISOLATOR OPEN W101 P J03.XK MDF J03 1
YY01 RTU DI 14 LUCY DSM 2A DI-SWA Close 01 041/003/012 RD3012 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISC LOAD ISOLATOR CLOSED W101 M J03.XK MDF J03 3

YY01 RTU DI 16 LUCY DSM 2B DI-SWA Open 01 042/004/001 RD3012 SS - 22 A04-FE (22kV Transformer CB - 2) DP CBO CIRCUIT BREAKER OPEN W103 F J04.XK MDF J04 3
YY01 RTU DI 17 LUCY DSM 2B DI-SWA Close 01 042/004/001 RD3012 SS - 22 -A04-FE (22kV Transformer CB - 2) DP CBC CIRCUIT BREAKER CLOSED W103 E J04.XK MDF J04 1
YY01 RTU DI 18 LUCY DSM 2B DI-2 01 042/004/205 RD3012 SS - 22 -A04-FE (22kV Transformer CB - 2) FL OCEFT Over Current/Earth Fault Trip W103 R J04.XK MDF J04 7&9
YY01 RTU DI 19 LUCY DSM 2B DI-1 01 042/004/247 RD3012 SS - 22 -
A04-FE (22kV Transformer CB - 2) - SP PRF Protection Relay Faulty W103 N J04.XK MDF J04 11
IO Typical QRM

Station Type : Station Name : Station Address: IP Address: MAC Address:


SS Substation RD3013 RD3013
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling
I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status

Box )
Baytype ( Comment ) Remarks
YY01 RTU DO 01 LUCY DSM 2A - 01 030/000/108 RD3013 00 00 C.Station (22kV Common) DC DUMMY RELAY OFF - YY01 DO-17B
YY01 RTU DO 02 LUCY DSM 2A - 01 030/000/108 RD3013 00 00 -C.Station (22kV Common) DC DUMMY RELAY ON - YY01 DO-18B
YY01 RTU DO 03 LUCY DSM 1A DO-SW A 01 041/001/112 RD3013 SS - 22 A01-FE (22kV Feeder-LBS - 1) - DC LISO_C LOAD ISOLATOR OPEN W101 C J01.XK MDF J01 9
YY01 RTU DO 04 LUCY DSM 1A DO-SW A 01 041/001/112 RD3013 SS - 22 A01-FE (22kV Feeder LBS - 1) - DC LISC_C LOAD ISOLATOR CLOSED W101 D J01.XK MDF J01 7
YY01 RTU DO 05 LUCY DSM 1B DO-SW B 01 042/002/104 RD3013 SS - 22 A02-FE (22kV Transformer CB - 1) DC CBO_C CIRCUIT BREAKER OPEN W102 C J02.XK MDF J02 4
01 042/002/104 RD3013 SS - 22 -A02-FE (22kV Transformer CB - 1) DC CBC_C CIRCUIT BREAKER CLOSED
YY01 RTU DO 06 LUCY DSM 2A DO-SW A 01 041/003/112 RD3013 SS - 22 -A03-FE (22kV Feeder LBS - 2) - DC LISO_C LOAD ISOLATOR OPEN W101 K J03.XK MDF J03 9
YY01 RTU DO 07 LUCY DSM 2A DO-SW A 01 041/003/112 RD3013 SS - 22 A03-FE (22kV Feeder LBS - 2) - DC LISC_C LOAD ISOLATOR CLOSED W101 L J03.XK MDF J03 7
YY01 RTU DO 08 LUCY DSM 2B DO-SW B 01 042/004/104 RD3013 SS - 22 A04-FE (22kV Transformer CB - 2) DC CBO_C CIRCUIT BREAKER OPEN W103 C J04.XK MDF J04 4
01 042/002/104 RD3013 SS - 22 -A04-FE (22kV Transformer CB - 2) DC CBC_C CIRCUIT BREAKER CLOSED
-
YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W101 A J01.XK MDF J01 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J01.XK MDF J01 2
YY01 RTU C/R LUCY DSM 1A DI SW A 01 Common Return (C/R) W102 G J01.XK MDF J01 2&4
YY01 RTU C/R LUCY DSM 1A DI 1 01 Common Return (C/R) W102 J J01.XK MDF J01 6
YY01 RTU C/R LUCY DSM 1A DI 4 01 Common Return (C/R) W102 M J01.XK MDF J01
YY01 RTU C/R LUCY DSM 2 A DI SW A 01 Common Return (C/R) W102 P J03.XK MDF J03 2&4
YY01 RTU C/R LUCY DSM 2 A DI 3 01 Common Return (C/R) W102 P J03.XK MDF J03 6
YY01 RTU C/R LUCY DSM 2 A DI 4 01 Common Return (C/R) W102 P J03.XK MDF J03

YY01 RTU A1 01 LUCY DSM 1B AI-SW B 01 042/002/132 RD3013 SS - 22 A02-FE (22kV Transformer CB - 1) M A+ CURRENT + W102 T J02.XK MDF J02 5
YY01 RTU A1 02 LUCY DSM 1B AI-SW B 01 042/002/132 RD3013 SS - 22 -A02-FE (22kV Transformer CB - 1) M A- CURRENT - W102 V J02.XK MDF J02 6
YY01 RTU A1 03 LUCY DSM 2B AI-SW B 01 042/004/132 RD3013 SS - 22 -A04-FE (22kV Transformer CB - 2) M A+ CURRENT + W103 T J04.XK MDF J04 5
YY01 RTU A1 04 LUCY DSM 2B AI-SW B 01 042/004/132 RD3013 SS - 22 -A04-FE (22kV Transformer CB - 2) M A- CURRENT - W103 V J04.XK MDF J04 6
-
YY01 RTU PS L1 01 RTU AC SUPPLY W501 bk YH01 230V AC P
YY01 RTU PS N 01 RTU AC SUPPLY W501 bu YH01 230V AC N

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J02.XK MDF J02 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J02.XK MDF J02 2
YY01 RTU C/R LUCY DSM 1B DI SW B 01 Common Return (C/R) W103 G J02.XK MDF J02 2&4
YY01 RTU C/R LUCY DSM 1B DI 4 01 Common Return (C/R) W103 J xx MDF J02 8
YY01 RTU C/R LUCY DSM 1B DI 2 01 Common Return (C/R) W103 M J02.XK MDF J02 8 & 10
YY01 RTU C/R LUCY DSM 1B DI 1 01 Common Return (C/R) W103 P J02.XK MDF J02 12

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J04.XK MDF J04 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J04.XK MDF J04 2
YY01 RTU C/R LUCY DSM 2B DI SW B 01 Common Return (C/R) W103 G J04.XK MDF J04 2&4
YY01 RTU C/R LUCY DSM 2B DI 4 01 Common Return (C/R) W103 J J04.XK MDF J04 8
YY01 RTU C/R LUCY DSM 2B DI 2 01 Common Return (C/R) W103 M J04.XK MDF J04 8 & 10
YY01 RTU C/R LUCY DSM 2B DI 1 01 Common Return (C/R) W103 P J04.XK MDF J04 12
IO Typical QRM(L EFI)

Station Type : Station Name :


SS Substation RD2412
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling Box


I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status
Baytype ( Comment ) Remarks

)
YY01 RTU DI 01 LUCY DSM 2A - 01 030/000/005 RD3013 00 00 C.Station (22kV Common) - DP DUM OFF DUMMY RELAY OFF - 0 YY01 DI-15A
YY01 RTU DI 02 LUCY DSM 2A - 01 030/000/005 RD3013 00 00 C.Station (22kV Common) - DP DUM ON DUMMY RELAY ON - 0 YY01 DI-16A
YY01 RTU DI 03 LUCY MCM - 01 030/000/042 RD3013 00 00 C.Station (22kV Common) - SP MCBA MCB Alarm - 0 YY01
YY01 RTU DI 04 LUCY ADEL - 01 030/000/250 RD3013 00 00 C.Station (22kV Common) - SP 24VDCAL 24V DC Alarm - 0 YY01
YY01 RTU DI 05 LUCY MCM - 01 030/000/201 RD3013 00 00 C.Station (22kV Common) - SP STNL/R Station Control Local / Remote - 0 YY01
YY01 RTU DI 06 LUCY DSM 2A DI-3 01 030/000/041 RD3013 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W102 H XX MDF CS 7
01 030/000/041 RD3013 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W103 H XX MDF CS 8

YY01 RTU DI 07 LUCY DSM 1A DI-SWA Open 01 041/001/012 RD3013 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISO LOAD ISOLATOR OPEN W101 F J01.XK MDF J01 1
YY01 RTU DI 08 LUCY DSM 1A DI-SWA Close 01 041/001/012 RD3013 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISC LOAD ISOLATOR CLOSED W101 E J01.XK MDF J01 3
YY01 RTU DI 15 LUCY DSM 1A DI-1 01 041/003/033 RD3013 SS - 22 A03-FE (22kV Feeder LBS - 2) - SP EFI Earth Fault Indication W101 H J01.XK MDF J01 5

YY01 RTU DI 09 LUCY DSM 1B DI-SWA Open 01 042/002/001 RD3013 SS - 22 A02-FE (22kV Transformer CB - 1) DP CBO CIRCUIT BREAKER OPEN W102 F J02.XK MDF J02 3
YY01 RTU DI 10 LUCY DSM 1B DI-SWA Close 01 042/002/001 RD3013 SS - 22 -A02-FE (22kV Transformer CB - 1) DP CBC CIRCUIT BREAKER CLOSED W102 E J02.XK MDF J02 1
YY01 RTU DI 11 LUCY DSM 1B DI-2 01 042/002/205 RD3013 SS - 22 -A02-FE (22kV Transformer CB - 1) FL OCEFT Over Current/Earth Fault Trip W102 R J02.XK MDF J02 7&9
YY01 RTU DI 12 LUCY DSM 1B DI-1 01 042/002/247 RD3013 SS - 22 -A02-FE (22kV Transformer CB - 1) SP PRF Protection Relay Faulty W102 N J02.XK MDF J02 11
-

YY01 RTU DI 13 LUCY DSM 2A DI-SWA Open 01 041/003/012 RD3013 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISO LOAD ISOLATOR OPEN W101 P J03.XK MDF J03 1
YY01 RTU DI 14 LUCY DSM 2A DI-SWA Close 01 041/003/012 RD3013 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISC LOAD ISOLATOR CLOSED W101 M J03.XK MDF J03 3

YY01 RTU DI 16 LUCY DSM 2B DI-SWA Open 01 042/004/001 RD3013 SS - 22 A04-FE (22kV Transformer CB - 2) DP CBO CIRCUIT BREAKER OPEN W103 F J04.XK MDF J04 3
YY01 RTU DI 17 LUCY DSM 2B DI-SWA Close 01 042/004/001 RD3013 SS - 22 -A04-FE (22kV Transformer CB - 2) DP CBC CIRCUIT BREAKER CLOSED W103 E J04.XK MDF J04 1
YY01 RTU DI 18 LUCY DSM 2B DI-2 01 042/004/205 RD3013 SS - 22 -A04-FE (22kV Transformer CB - 2) FL OCEFT Over Current/Earth Fault Trip W103 R J04.XK MDF J04 7&9
YY01 RTU DI 19 LUCY DSM 2B DI-1 01 042/004/247 RD3013 SS - 22 -
A04-FE (22kV Transformer CB - 2) - SP PRF Protection Relay Faulty W103 N J04.XK MDF J04 11
Annexure 5. Substation GIS names to be Integrate
LIST OF SUBSTATION Reqierd DMS-RTU & FOTB

No SUBSTATION Phase RMU No of TR

1 RD1823 6B Lucy 2 TR
2 RD1833 6B Lucy 1 TR
3 RD1910 6B Lucy 2 TR
4 RD2412 6A SCHNEIDER 2 TR
5 RD3012 6A SCHNEIDER 2 TR
6 RD3013 6A SCHNEIDER 2 TR
Annexure 6. Signal List
RTU I/O Connection Schedule

Connections For TRM & QRM Version with 19 Way Umbilical Cable: -
CABLE [1] – K01 & K03 -SW1 and SW2

Non
GEMINI V3.0 Umbilical RMU MB
Alarm /
Description Non- Remarks
Cable
RTU Terminal No Terminal No Active
Core No
State
`+'24V DC (Permeant supply from
TB1 +24VS 1 XJ 1 -
ADEL)
TB2 - 0VS 2 XJ 2 0V DC -
DSM 1A-5-DO SW Open 3 J01.XK 9 K01 Open command NO
DSM 1A-4-DO SW Close 4 J01.XK 7 K01 Close command NO
DSM 1A-21-DI SW Open 6 J01.XK 1 K01 Close Indication NO
DSM 1A-20-DI SW Close 7 J01.XK 3 K01 Open Indication NO
DSM 1A-19-DI Common 5 J01.XK 2&4 K01 Common Indication -

DSM 1A-22-DI 1 9 J01.XK 5 K01/K03 Earth Fault Indicator NO

K01/K03 Earth Fault Indicator


DSM 1A-24-DI 1 Common 8 J01.XK 6 -
Common
DSM 1A-18-DI 4 11 - - Spare -
DSM 1A-6-DI 4 Common 10 - - Spare -
DSM 2A-5-DO SW Open 14 J03.XK 9 K03 Open command NO
DSM 2A-4-DO SW Close 15 J03.XK 7 K03 Close command NO
DSM 2A-21-DI SW Open 17 J03.XK 1 K03 Close Indication NO
DSM 2A-20-DI SW Close 18 J03.XK 3 K03 Open Indication NO
DSM 2A-19-DI Common 16 J03.XK 2&4 K03 Common Indication -
DSM 2A-9-DI 3 20 XX 7 SF6 Pressure Low NO
DSM 2A-8-DI 3 Common 19 XX 8 SF6 Pressure Low Common -
DSM 2A-18-DI 4 22 - - Spare -
DSM 2A-6-DI 4 Common 21 - - Spare -

Lucy RTU 1 of 4
RTU I/O Connection Schedule

Connections For TRM & QRM Version with 19 Way Umbilical Cable: -
CABLE [2] – K02 -CB1

Non
GEMINI V3.0 Umbilical RMU MB
Alarm /
Description Non-
Cable Remarks
RTU Terminal No Terminal No Active
Core No
State
`+'24V DC (Permeant supply from
TB1+24VP 1 J02.XK 3 -
ADEL)
TB1 - 0VP 2 - 0 Vdc -
DSM 1B-5-DO SW Open 3 J02.XK 4 K02 Open Command NO
DSM 1B-4-DO SW Close - - - Spare -
DSM 1B-21-DI SW Open 5 J02.XK 1 K02 Close Indication NO
DSM 1B-20-DI SW Close 6 J02.XK 3 K02 Open Indication NO
DSM 1B-19-DI Common 4 J02.XK 2&4 K02 Common Indication -
DSM 1B-18-DI 4 14 XX 7 SF6 Pressure Low NO
DSM 1B-6-DI 4 Common 13 XX 8 SF6 Pressure Low Common -
K02 Overcurrent/Earth fault trip
DSM 1B-7-DI 2 7 J02.XK 7&9 -
Common
DSM 1B-8-DI 2 Common 8 J02.XK 8 & 10 K02 Overcurrent/Earth fault trip NO
K02 Protection Relay Failure
DSM 1B-24-DI 1 10 J02.XK 11 -
Common
DSM 1B-22-DI 1 Common 9 J02.XK 12 K02 Protection Relay Failure NO
DSM 1B - DO 1 Common 15 - - Spare DO Common -
DSM 1B - DO Common 16 - - Spare DO -
DSM 1B- J2-2 11 J02.XK 5 K02 Y Phase CT -
DSM 1B- J2-5 common 12 J02.XK 6 K02 Y Phase CT -

Lucy RTU 2 of 4
Connections For TRM & QRM Version with 19 Way Umbilical Cable: -
CABLE [3] – K04 -CB2
Non
GEMINI V3.0 Umbilical RMU MB
Alarm /
Description Non-
Cable Remarks
RTU Terminal No Terminal No Active
Core No
State
`+'24V DC (Permeant supply from
TB1+24VP 1 J04.XK 3 -
ADEL)
TB1 - 0VP 2 - 0 Vdc -
DSM 2B-5-DO SW Open 3 J04.XK 4 K04 Open Command NO
DSM 2B-4-DO SW Close - - - Spare -
DSM 2B-21-DI SW Open 5 J04.XK 1 K04 Close Indication NO
DSM 2B-20-DI SW Close 6 J04.XK 3 K04 Open Indication NO
DSM 2B-19-DI Common 4 J04.XK 2&4 K04 Common Indication -
DSM 2B-18-DI 4 14 XX 7 SF6 Pressure Low NO
DSM 2B-6-DI 4 Common 13 XX 8 SF6 Pressure Low Common -
K04 Overcurrent/Earth fault trip
DSM 2B-7-DI 2 7 J04.XK 7&9 -
Common
DSM 2B-8-DI 2 Common 8 J04.XK 8 & 10 K04 Overcurrent/Earth fault trip NO
K04 Protection Relay Failure
DSM 2B-24-DI 1 10 J04.XK 11 -
Common
DSM 2B-22-DI 1 Common 9 J04.XK 12 K04 Protection Relay Failure NO
DSM 2B - DO 1 Common 15 - - Spare DO Common -
DSM 2B - DO Common 16 - - Spare DO -
DSM 2B- J2-2 11 J04.XK 5 K04 Y Phase CT -
DSM 2B- J2-5 common 12 J04.XK 6 K04 Y Phase CT -

Lucy RTU 3 of 4
Annexure 7. RTU complete submittal
Bulk Consumer

CHECK LIST FOR DMS/SCADA SUBMITTALS Non Bulk Consumer

Temp.Consumer

Project Name RIYADH CITY PH-6A&6B Material Descripition : DMS-RTU

Consultant : PARSONS Contractor : NPC

Submittal Ref No : Date : 25-05-2023

Name & Contact Details of the Contractor

General Documents Required for All Submissions


1. Scope of Work & BOQ Y
2. All Previous ADDC Comments Sheet with Reply
Y
(for revised submittal Only)

1 3. Approved Vendor/Contractor List Y

4. Technical Calelogue of Manufacturers Y

5. Certificate/Trade License Y

RTU Y

1. Station SLD Y

2. SLD Showing feeding arrangement from the source Y

3. Country of Origin Certificate Y

4. Signal List Y

5. Tele-information Plan Y

6. Cable overview Y
2
7. Adaptation Design Y

8. I/O Connection Diagram Y

9. GIS names of all Stations Y

10. RTU Layout & Detailed Design Y

11. SAT Procedure Y

12. FAT Procedure & FAT Report (if the FAT was waived) Y

DMS Interface Panel

1. Station SLD

2. Interface panel layout

3. Signal List

4. Cable overview

3 5. SWG Schematic Drawing

6. Wiring Adaptation Design

7. Data/Compliance sheet

8. SAT /FAT Procedures

9. Catalogues for all equipment’s inside the IP

SCADA Submittal Checklist Page 1


Bulk Consumer

CHECK LIST FOR DMS/SCADA SUBMITTALS Non Bulk Consumer

Temp.Consumer

Project Name RIYADH CITY PH-6A&6B Material Descripition : DMS-RTU

Consultant :
PARSONS
Contractor : NPC

Submittal Ref No : Date : 25-05-2023

Name & Contact Details of the Contractor

Fiber Optic (Material)

a) Cable

b) Termination Box

c) Joints & Accessories

1. Data/Compliance sheet
4
2. FAT Procedure & FAT Report (if the FAT was waived)

Fiber Optic Cable Route

1. Cable Total length

2. Manhole Details

5 3. Single line diagram(SLD)

4. Termination / Splice joint scheme

5. FOC layout in A0 size

SCMS

1. SCMS Architecture/Block diagram

2. SCMS Functional Specification

3. Equipment List for SCMS

4. Station Controller Panel drawing

5. Common Alarm Panel drawing

6 6. HMI Typical Screen

7. SCMS Room Layout drawing

8. Signal list, SCMS Datasheet & DMS Datasheet

9. SCMS SAT Procedure

10. SCMS FAT Procedure

11. SCMS O& M Manual

DC System

7 1. Detail design of DC System

SCADA Submittal Checklist Page 2


Bulk Consumer

CHECK LIST FOR DMS/SCADA SUBMITTALS Non Bulk Consumer

Temp.Consumer

Project Name RIYADH CITY PH-6A&6B Material Descripition : DMS-RTU

Consultant : PARSONS Contractor : NPC

Submittal Ref No : Date : 25-05-2023

Name & Contact Details of the Contractor

GPRS/3G Modem

1. Communication design

8 2. Data sheet

3. SAT Procedure

Ethernet Switch

1. Approved Network Scheme


9
2. Data sheet

Media Convertor / LL Modem

1. Communication design
10
2. Data sheet

Contractor's Stamp, Signature & Date


Notes-
1. The submittals will be returned if the check list are not attached

SCADA Submittal Checklist Page 3


GENERAL DOCUMENTS
Contractor : National Projects & Contruction LLC 1

RTU
Employer : ALDAR Projects 2

Consultant : PARSONS

Client : ADDC

SS : RMU Substations

Internal Project No:

Project Name : Madinat Al Riyadh City Ph-6A & 6B

MATERIAL SUBMITTAL: DMS-RTU for RMU.Rev.01


BOQ
Contractor : National Projects & Contruction LLC 1

Approved ADWEA VL
Employer : ALDAR Projects 2

Consultant : PARSONS 3 Technical Catalogue

Client : ADDC 4 Compliance Statement

RTU Data Sheet


SS : RMU Substations 5

6 Company Profile
Internal Project No:

Project Name : Madinat Al Riyadh City Ph-6A & 6B 7 Trade License

MATERIAL SUBMITTAL: DMS-RTU for RMU.Rev.01


(General Documents)
BOQ
Contractor : National Projects & Contruction LLC 1

Approved ADWEA VL
Employer : ALDAR Projects 2

Consultant : PARSONS 3 Technical Catalogue

Client : ADDC 4 Compliance Statement

RTU Data Sheet


SS : RMU Substations 5

6 Company Profile
Internal Project No:

Project Name : Madinat Al Riyadh City Ph-6A & 6B 7 Trade License

MATERIAL SUBMITTAL: DMS-RTU for RMU.Rev.01

(General Documents)
BOQ

Item
Description Quantity
No
1 13028010006 - DMS- RTU panel for 22KV RMU QRM (2F+2T) COMPLETE WITH
ETHERNET SWITCHES / CABLES AND ALL related accessories as per latest ADDC specs
5
13028010037 -DMS -RTU panel for 22KV RMU TRM (2F+1T) complete with ethernet
2 switches / cables and all related accessories as per latest ADDC specs 1
BOQ
Contractor : National Projects & Contruction LLC 1

Approved ADWEA VL
Employer : ALDAR Projects 2

Consultant : PARSONS 3 Technical Catalogue

Client : ADDC 4 Compliance Statement

RTU Data Sheet


SS : RMU Substations 5

6 Company Profile
Internal Project No:

Project Name : Madinat Al Riyadh City Ph-6A & 6B 7 Trade License

MATERIAL SUBMITTAL: DMS-RTU for RMU.Rev.01


(General Documents)
COMMERCIAL DIRECTORY VENDORS LIST
Product Group : 0507010
Description : RTU'S (REMOTE TERMINAL UNITS)
Manufacturer Name Country Agent Name SEC decision Models Conditions Remarks Validation date
Principal Plant Address Evaluated by Approval date
9900175 SIEMENS AG Germany 01-Jan-2015
Berlin SEC
9902121 ABB AG POWER SYSTEM Germany OMEIR BIN YOUSUF & SONS RPQSC/ RTU520, RTU560 19-Dec-2021
DIVISION FORMERLY (ABB MANNHIEM SEC 23/3374/2016
UTILITY AUTOMATION) 19-Dec-2016
9903789 MICROSOL Ireland 01-Jan-2015
PRJ
9907673 LUCY SWITCHGEAR United Kingdom LUCY MIDDLE EAST - ABU DHABI 31/G/RPQC/ GEMINI 3 14-Jan-2026
OXFORD RPQSC 01/2021/
14-Jan-2021
9910081 MICROSOL United Kingdom 01-Jan-2015
PRJ
99101812 SIA LEXEL FABRIKA Latvia 651/G/RPQSC/ SAITEL DR, 12-Nov-2023
RIGA RPQSC 20/18 SAITEL DP
12-Nov-2018
9910704 TECHNO TRADE S.A. Belgium SEC/096/487/2009 01-Jan-2015
SEC 09-Mar-2009
99110583 SIEMENS LIMITED -INDIA India 1186/G/RPQC/14/19 SICAM A8000 08-Sep-2024
GOA RPQSC 08-Sep-2019 Series
9912483 SELTA SPA Italy 738/G/RPQC/ 10-Dec-2025
MILAN RPQSC 18/2020
10-Dec-2020
99143703 ZIV AUTOMATION IRELAND Ireland 669/G/RPQC/ 02-Nov-2025
LIMITED BRUTON RPQSC 16/2020
CHAMBERS 02-Nov-2020
99149023 WAGO GMBH Germany MCM-FIELDCORE 679/G/RPQC/ FOR WATER 02-Nov-2025
32423 MINDEN RPQSC 16/2020 APPLICATION
02-Nov-2020
9942837 SCHNEIDER ELECTRIC France SCHNEIDER ELECTRIC INDUSTRIES - 807/G/RPQC/ MICOM C264-RTU 24-Dec-2025
PROTECTION & CONTROLE - LATTES CEDEX SA 19/2020
FRANCE RPQSC 24-Dec-2020
9943166 BRODERSEN SYSTEMS A/S Denmark 435/G/RPQC/ RTU M /RTU N 27-Jul-2027
ROEDOVRE SEC 10/2022 SERIES (water
27-Jul-2022 application)
99461012 BECKHOFF AUTOMATION FZE Germany 308/G/RPQC/ CX9020 13-May-2027
HÜLSHORSTWEG RPQSC 06/2022
20 13-May-2022
9946996 NETCONTROL AB (FORMERLY Sweden AUTOCHIM SYSTEMS - ABU DHABI - MPQC/ NETCON 500 01-Jan-2015
RADIUS LTD.) (ASAD) L L C 01/1091/2014
PRJ 20-Jan-2014

Report Managed By : ADWEA - Companies Registration Section E-mail : CRS@adwea.ae Tel : 80023932
262 / 318 Report Generated On : 3-Oct-2022 3:00:03 AM
Company Name : LUCY MIDDLE EAST - ABU DHABI Fax:0097126222797
Attention : Rahamthulla Shariff
Registration Number :9913734/9907673 Date : 18/01/2021
Subject : Pre-Qualification Status
We have pleasure to inform you that M/s. LUCY SWITCHGEAR, United Kingdom, Code No. 9907673.
has been pre-qualified as a possible source to supply of the following products. which has been rated as
per the schedule below:
S.No PG No. PG Description Current Status Validation Model PRODUCT CONDITION Plant
Date REMARK S Address
1 0305060 RING MAIN UNIT / RMU Qualified 19-Oct-2022 OXFORD
MATERIALS
2 0507010 RTU'S (REMOTE TERMINAL Qualified 14-Jan-2026 GEMINI 3 OXFORD
UNITS)

However, you have to maintain and update your company records in the Commercial
directory to avoid any inactivation due to such. These record shall be maintained and updated
through e-registration system and shall include but not limited to the following documents once they
are renewed.
1. Respective licenses
2. Agency certificates and Agreements where applicable
3. Any other changes in your address, contact person, owners/sponsors etc.
Please note that at the time of release of enquiries, a further short listing takes place based on
exhibited interest at that time and the specifics of material/equipment in question as needed.
You are advised to quote your registration No.(9913734) in all future correspondence.

Regards,

Ali Abdullah Al Shehhi

Companies Registration Section Manager

This e-mail and file(s) transmitted with it are confidential and intended solely for the individual or entity to whom they are
addressed. If you are not the intended recipient, or have received the e-mail in error, please notify the sender and delete this e-
mail (and file(s) if attached) from your system. You are not authorized to copy, distribute or use this e-mail or any of its
attachment(s) unless by the prior consent of the sender. Any views presented in this email are solely those of the sender and do
not necessarily represent Abu Dhabi Distribution Company. ADDC accepts no liability for any damage caused by any virus/worms
transmitted by this e-mail.

OUR VISION | ADDC will be amongst the top quartile performers worldwide in water & electricity utilities by 2020.
OUR MISSION | Ensure the sustainable supply of water and electricity to support the vision of the Abu Dhabi Government.
OUR VALUES | Teamwork, Stakeholder Focus, Integrity, Continual Improvement and Corporate Citizenship
Please consider the environment before printing this e-mail

1 of 1
BOQ
Contractor : National Projects & Contruction LLC 1

Approved ADWEA VL
Employer : ALDAR Projects 2

Consultant : PARSONS 3 Technical Catalogue

Client : ADDC 4 Compliance Statement

RTU Data Sheet


SS : RMU Substations 5

6 Company Profile
Internal Project No:

Project Name : Madinat Al Riyadh City Ph-6A & 6B 7 Trade License

MATERIAL SUBMITTAL: DMS-RTU for RMU.Rev.01


(General Documents)
CBI2801224A Input: Single-phase 115 – 230 - 277 Vac
Output Selectable Load:12 Vdc 15A; 24 Vdc 10A
Output Battery charging: 12 Vdc 15A; 24 Vdc 10A
Suited for the following battery types: Open Lead Acid,
Sealed Lead Acid, Lead Gel, Lead Crystal, Ni-Cd & Li-On
Automatic diagnostic of battery status, Battery Life Test
function (internal Battery Impedance)
Charging curve IUoU, constant voltage and current
Four charging levels: Boost, Absorption, Trickle, Recovery
Protected against short circuit and inverted polarity
Signal output: for battery Fault, Mains or Back-UP
Modbus RTU for all parameter battery and system
Protection degree IP20 ; Space saving

Technical features Continuous current ( With battery) Iload= In+ Ibatt 2 x In


Power Management: Thanks to the All In One units (DC-UPS), it will be possible to optimize power Max. current Output Load (Main) Iload (4 sec.) 3 x In max.
management. The available power is automatically allocated between load and battery, supplying Max. current Output Load (Back Up)Iload (4 sec.) 2 x In max.
power to the load is the first priority of the unit thus it is not necessary to double the power, because Push Button or Start From Battery
also the power going to the battery will go to the load if the load requires that. The maximum Remote Input Control (RTCONN cable) Without Main
available current on the load output is 3 times the value of the device rated current In.
Battery Care: it’s the concept base on algorithms that implement rapid and automatic charging, four
0.5; 2.5; 10; 15; 20; 30;
Time Buffering; min (switch output off without main input)
state of charge, battery charge optimization during time, flat batteries recovery and real time 45; 60; ∞
diagnostic during installation and operation. The Real Time Auto-diagnostic system, monitoring Short-circuit protection Yes
battery faults such as, battery Sulfated, elements in short circuit, accidental reverse polarity Over Load protection Yes
connection, disconnection of the battery, they can easily be detected and removed by help of Blink Over Voltage Output protection Yes (typ. 35 Vdc)
Code of Diagnosis Led; during the installation and after sell. The continuous monitoring of battery
efficiency, reduces battery damage risk and allows a safe operation in permanent connection. Each Overheating Thermal protection Yes
device is suited for all battery types, by means of jumpers it is possible setting predefined curves for Load Output 24 Vdc (jumper selection)
Open Lead Acid, Sealed Lead Acid, Gel, Ni-Cd(option). They are programmed for Fast charging level,
Output voltage (at In) 22 - 28.8 Vdc
boost and trickle, but they can be changed to single charging level by the user. A rugged casing for
DIN rail mounting, IP20 protection degree. They are extremely compact and cost-effective. Nominal current In = Iload 10 A  5% In
Interconnections: The platform communication for ADELSYSTEM devices allows the connection of all Threshold alarm Battery almost flat 20 – 21 Vdc batt
components in a simple but very powerful way. A protocol communication based on MODbus-RTU Protections against total discharge 19 – 20 Vdc batt
technology. It allows to communicate with all the accessories provided by ADELSYSTEM and to
develop an independent system for electrical continuity. At the same time, it allows monitoring and Load Output 12 Vdc (jumper selection)
control all parameters in the system, even from the other side of the world, by means of application Output voltage (at In) 10 - 14.4 Vdc
tools on the cloud. ADELSYSTEM allows you to implement very simple but sophisticated monitoring Nominal current In = Iload 15 A  5% In
and control for your energy system and opens your mind to new ways to approach your applications. Threshold alarm Battery almost flat 10 – 11 Vdc batt
Norms and Certifications Protections against total discharge 9 – 10 Vdc batt
In Conformity to EMC Directive 2014/30/EU: Emission EN IEC 61000-6-4; Immunity EN
IEC 61000-6-2. In conformity to Low Voltage Directive 2014/35/EU: Electrical safety EN
Battery Output
Output Voltage Battery Follow Out Load
IEC 60950-1. In conformity RoHS Directive 2011/65/EU as amended by 2015/863/EU.
Boost charge (25 °C) (at In) 2.4 V/cell.
In conformity to DIN41773 Charging cycle. Compliant with EN54-4 Fire alarm systems
Max. time Bust Charge 15 h
detection when installed in a IP30 Cabinet.
Min. time Bust Charge 1 min.
Climatic Data Jumper Configuration battery type (V cell) 2.23; 2.25; 2.27; 2.3;
Ambient temperature (operation) -25 ÷ +70°C Ni-Cd (optional); when Trickle Charging mode NiCd: 1.5 (20 cell.)
De Rating Ta > 50°C - 2.5%(In) / °C Charging current max Ibatt In  5%
Ambient temperature Storage -40 ÷ +85°C Charging current limiting Iadj 10 ÷ 100 % / Ibat
Humidity at 25 °C no condensation 95% to 25°C Reverse battery protection Yes
Cooling Auto convention Sulfated battery check Yes (by Jumper)
General Data Detection of element in short circuit Yes
Insulation voltage (IN/OUT) 3000 Vac Quiescent Current on the battery  5 mA
Insulation voltage (input / ground) 1605 Vac Charging Curve automatic: IUoU 4 stage
Insulation voltage (Output / ground) 500 Vac Remote Input Control (RTCONN cable) Boost /Trickle
Protection Class (EN/IEC 60529) IP20
Signal Output (free switch contacts)
Reliability: MTBF IEC 61709 > 300.000 h
Main or Backup Power Yes
Pollution Degree Environment 2
Low Battery Yes
Connection Terminal Blocks screw Type 2,5mm(24–14AWG)
Fault Battery Yes
Connection Terminal IEC
Protection class (PE Connected) I, with PE Type of Signal Output Contact
Dimensions (w-h-d) (Approx.) 100x115x135 mm Max. Current can be switched (EN60947.4.1):
Weight (Approx.) 0.85 kg Max. DC1: 30 Vdc 1 A; AC1: 60 Vac 1A Resistive load
Min.1mA at 5 Vdc Min permissive load
Input Data
Nominal Input Voltage (2 x Vac) 115 – 230 – 277 Signal Input / Output
Input Voltage range (Vac) 90 – 305 Temp. Comp. Battery Charger (with external probe) RJ11 Yes (Aux 1)
Modbus (RJ45) Yes..(Aux 2)
Inrush Current (Vn – In nom. Load) I2t  16 A  5 msec.
Modbus (RJ45) Yes (Aux 3)
Frequency 47 ÷ 63 Hz
Input Current (115 – 230 Vac) 3.3 – 2.2 A
Internal fuse (not replaceable) 6.3 A
External Fuse (recommended) MCB curve B 16 A
General Output Data
Select Output Voltage 12 or 24 Vdc. By: Jumper Enabling
Turn-On delay after applying mains voltage 1 sec. (max)
Start up with Strong Load (capacitive load) Yes, Unlimited
Efficiency (at 50% of rated current)  91 %
Dissipation power load max (W) 28
Residual Ripple  80 mVpp
Continuous current (without battery) Iload= In In A

All specifications are subject to change without notice


All specifications are subject to change without notice
ADELsystem
Via Luigi Barchi 9/B 42124 Reggio Emilia Italy
www.adelsystem.com
1 2 3 4 5 6 7 8 9 10

A A

EARTH
POINT

B B

GEMINI 3
RTU LED INTERNAL
C C
MODULES LIGHTS UR5i SL
ROUTER COMMS MCB
(METAL CONDENSATION
PSM G-3 MCM G-3 DSM G-3 DSM G-3 OPTION) VENT UR5i
ROUTER
Lite

GEMINI 3 RTU
OK PWR CAN OK PWR CAN OK PWR CAN OK PWR CAN

DC SUPPLY LOCAL REMOTE OFF IN 8 IN 8


LOGIC SUPPLY
MOTOR SUPPLY DUMMY MODE AUTO A B IN 9 A B IN 9

MODULE CONFIGURATION (PLASTIC


SW875

IN 10 IN 10 PWR
HMI GEMINI 3
FAN / SWITCHED AUX L809 Module
Id
Module
Id
lu OPTION)
TVS808

C809
Electric
USB

DC 1
RS232-B

L808
C808
DC 2 L807 A B A B
IP IP
TVS806

C807
J905
24V AUX L806
C806
IP IP
C805

DC 1+ IN 1 IN 1
DEBUG

X650

DC 1-
DC OUTPUTS

SW A IN 2 SW A IN 2
DC 2+ R803
J803

DC 2-
J901
IN 3 IN 3

G-3 DSM DSM


24V AUX IN 4 IN 4
G-3 G-3
ETH-1

PSM MCM
J904

D
0V
24V AUX
0V DOOR SW J801
IN 5
IN 6
IN 5
IN 6
Lite
G-3 MCM
G-3
CAN
OK PWR CAN
OK PWR CAN

IN 8 HMI D
TVS653
IN 7 IN 7 OK PWR
G-3
SENSOR

OK OK IN 8
24V DC

TVS804

OK PWR CAN PWR CAN PWR CAN


INPUT

J902
IN 9
OP M+ OP M+ OK PWR CAN PSM TE OFF A B
T + - 0

L804
C804
OP OP Lite PWR CAN LOCAL REMO IN 9 IN 10
C803
B
RS232-A

OK
RS485

L803
A
TVS802

L802
OP OP MODE AUTO IN 10
DC SUPPLY DUMMY
C802

SW875
Module
OUTPUT
24V AUX

C801
L801 OP 1 OP 1
/FAN

LY Id
LOGIC SUPP
DC SUPPLY LOCAL REMOTE OFF Module
C800
L800

IN 8 IN 8 MOTOR SUPP
LY
1

Id A B
SW B SW B L80
IP

808
TVS656

C809
CT A CT A

TVS
9
A B IP
LOGIC SUPPLY
L80

RS232-B
J802
PWROK MENU
C808
IP

USB
8

IN 1

806
L80

HED AUX IP
C807

TVS
DUMMY MODE A B A B
7

IN 9 IN 9 FAN / SWITC
L80

IN 2
5
ETH-0

C806
IN 1
J90

AUTO
HMI

MOTOR SUPPLY
6

HMI
C80

DC 1 5

IN 2 SW A IN 3

0
X65
SW875
CT B CT B DC 2 IN 3 IN 4
SW A

DEBUG
R80
J80
3 PW
R
IN 10 IN 10 24V AUX IN 5
3
J800
1 IN 4
DC 1+ IN 6
J90

OPEN IN 5 GEM
lu

ETH-1
DC 1-
PSM MCM Lucy Lucy IN 7

DC OUTPUTS
4
IN 6 INI
DSM DSM
J90
DC 2+
Lite ACT DC 2- IN 7 OP M+ 3
LOCAL 24V AUX TVSJ80
6531
OP M+ OP
FAN / SWITCHED AUX DOOR SW

804
0V
Module Module

TVS
CLOSE
MODE
REMOTE 24V AUX
2
OP OP
L809
J90

0V L80
OP 1
Id Id OP
C804

TVS808
C809 C80 4

RS232-A
802
USB
L80 3

DC 1

T + - 0
OFF 3
OP 1

TVS
24V DC
INPUT
RS232-B
L80
L808

RS485
C802

SENSOR
C80 2
C808 L80 1
CT A
SW B
1

DC 2 L807 A B A B C80
L80 0
0

SW B CT A
IP IP

TVS806

656
C807

OUTPUT

TVS
24V AUX
J905 J80

/FAN
2

24V AUX L806


C806
IP IP
CT B

ETH-0
CT B

PSU
C805

HMI
DC 1+ IN 1 IN 1 Lucy

DEBUG
J80
0

X650
RELAYS DC 1-
Lucy
DSM

DC OUTPUTS
SW A IN 2 SW A IN 2 MCM lu DSM PW
R
DC 2+ R803
J803

DC 2-
J901
IN 3 IN 3 PSM
OK

MEN
24V AUX IN 4 IN 4 Lite U

ETH-1
J904 OP
EN
0V IN 5 IN 5
E 24V AUX CLO E
0V IN 6 IN 6 SE LOCA
L
DOOR SW J801
REMO
TEM AC
T
TVS653
IN 7 IN 7 OFF OD
E
SENSOR

24V DC

TVS804
INPUT
J902
OP M+ OP M+

T + - 0
L804
C804
C803 OP OP

RS232-A
RS485
L803

TVS802
L802
OP OP
C802
OUTPUT
24V AUX

C801
L801 OP 1 OP 1
/FAN

C800
L800

1
SW B SW B
SUPPLY

TVS656
CT A CT A
NiMH
J802

MCB

ETH-0
11 AH

HMI
CT B CT B
BATT J800

PSM
Lite
MCM lu DSM
Lucy
DSM
Lucy

F F
DOOR &
BATTERY
SWITCH PSM lite
MCM MODULE
MODULE
EXPANSION SLOT

G
DSM MODULES G

UMBILICAL LOCAL REMOTE SWITCH


PAINTED STEEL ENTRY VIA SPLIT
ENCLOSURE - IP55
SEE SHEET 2 FOR ENCLOSURE DIMENSIONS
GLAND PLATE
ECN STANDARD TOLERANCES: ISO 2768-m.
FOR ADDITIONAL INFO. SEE DRG. 72219 C COPYRIGHT LUCY ELECTRIC (EMS). ALL RIGHTS RESERVED. ALL DIMENSIONS IN MILLIMETERS UNLESS OTHERWISE STATED
NUMBER

MOD. jones_mc DRAWN jones_mc G3 RTU, 5 SLOT IP55, MCM, IEC 104,
MOD.
APPRV. __
DRAWN
APPRV. CO
PSM-lite, 1X12V-COMMS, 2x DSM, LOCAL
H H
REM SW, 11AH NIMH, HMI, OEM PSU & TEMP
DATE 06/01/21 DATE 06/01/21 SENSOR, UR5i ROUTER - ADDC
MATERIAL: FINISH: ENGINEERING SOURCING CRITICALITY: SHEET NO: PROJECTION DO NOT SCALE THE REPRODUCTION OR TRANSMISSION OF ALL OR PART OF THIS
FROM A3 WORK, WHETHER BY PHOTOCOPYING OR STORING IN ANY MEDIUM
00 CATEGORY 2 1 OF 3
1st ANGLE IF IN DOUBT ASK
BY ELECTRONIC MEANS OR OTHERWISE, WITHOUT THE PRIOR
WRITTEN PERMISSION OF THE OWNER, IS PROHIBITED. AUT0004360 REV. 1
1 2 3 4 5 6 7 8 9 10

A A

268

220

M 10
B B

C C

635 REF

600

530
D D

E E

35
453

400

330
F F
290

48
241

G G

ECN STANDARD TOLERANCES: ISO 2768-m.


FOR ADDITIONAL INFO. SEE DRG. 72219 C COPYRIGHT LUCY ELECTRIC (EMS). ALL RIGHTS RESERVED. ALL DIMENSIONS IN MILLIMETERS UNLESS OTHERWISE STATED
NUMBER

MOD. jones_mc DRAWN jones_mc G3 RTU, 5 SLOT IP55, MCM, IEC 104,
MOD.
APPRV. __
DRAWN
APPRV. CO
PSM-lite, 1X12V-COMMS, 2x DSM, LOCAL
H H
REM SW, 11AH NIMH, HMI, OEM PSU & TEMP
DATE 06/01/21 DATE 06/01/21 SENSOR, UR5i ROUTER - ADDC
MATERIAL: FINISH: ENGINEERING SOURCING CRITICALITY: SHEET NO: PROJECTION DO NOT SCALE THE REPRODUCTION OR TRANSMISSION OF ALL OR PART OF THIS
FROM A3 WORK, WHETHER BY PHOTOCOPYING OR STORING IN ANY MEDIUM
00 CATEGORY 2 2 OF 3
1st ANGLE IF IN DOUBT ASK
BY ELECTRONIC MEANS OR OTHERWISE, WITHOUT THE PRIOR
WRITTEN PERMISSION OF THE OWNER, IS PROHIBITED. AUT0004360 REV. 1
1 2 3 4 5 6 7 8 9 10

A A

PSM
Lite
G-3 MCM G-3 DSM G-3 DSM G-3
OK PWR CAN OK PWR CAN OK PWR CAN OK PWR CAN

DC SUPPLY LOCAL REMOTE OFF IN 8 IN 8


LOGIC SUPPLY
MOTOR SUPPLY DUMMY MODE AUTO A B IN 9 A B IN 9

SW875
IN 10 IN 10 PWR
HMI GEMINI 3
FAN / SWITCHED AUX Module Module

lu
L809
Id Id

TVS808
C809
Electric

USB
DC 1

RS232-B
L808
C808
DC 2 L807 A B A B
IP IP

TVS806
C807
J905
24V AUX L806
C806
IP IP
C805

B DC 1+ IN 1 IN 1 B

DEBUG

X650
DC 1-

DC OUTPUTS
SW A IN 2 SW A IN 2
DC 2+ R803
J803

DC 2-
J901
IN 3 IN 3
24V AUX IN 4 IN 4

ETH-1
J904
0V IN 5 IN 5
24V AUX
0V IN 6 IN 6
DOOR SW J801
TVS653
IN 7 IN 7

SENSOR

24V DC

TVS804
INPUT
J902
OP M+ OP M+

T + - 0
L804
C804
C803 OP OP

RS232-A
RS485
L803

TVS802
L802
OP OP
C802

OUTPUT
24V AUX
C801
L801 OP 1 OP 1

/FAN
C800
L800

1
SW B SW B

TVS656
J802 CT A CT A
PWROK MENU

ETH-0
HMI
CT B CT B
J800

OPEN
PSM
Lite
MCM lu DSM
Lucy
DSM
Lucy

ACT
LOCAL
CLOSE
MODE
REMOTE
OFF

56
C C

164 35 177

D D

46

255

224
E E

145
F F

G G

ECN STANDARD TOLERANCES: ISO 2768-m.


FOR ADDITIONAL INFO. SEE DRG. 72219 C COPYRIGHT LUCY ELECTRIC (EMS). ALL RIGHTS RESERVED. ALL DIMENSIONS IN MILLIMETERS UNLESS OTHERWISE STATED
NUMBER

MOD. jones_mc DRAWN jones_mc G3 RTU, 5 SLOT IP55, MCM, IEC 104,
MOD.
APPRV. ___
DRAWN
APPRV. CO
PSM-lite, 1X12V-COMMS, 2x DSM, LOCAL
H H
REM SW, 11AH NIMH, HMI, OEM PSU & TEMP
DATE 06/01/21 DATE 06/01/21 SENSOR, UR5i ROUTER - ADDC
MATERIAL: FINISH: ENGINEERING SOURCING CRITICALITY: SHEET NO: PROJECTION DO NOT SCALE THE REPRODUCTION OR TRANSMISSION OF ALL OR PART OF THIS
FROM A3 WORK, WHETHER BY PHOTOCOPYING OR STORING IN ANY MEDIUM
00 CATEGORY 2 3 OF 3
1st ANGLE IF IN DOUBT ASK
BY ELECTRONIC MEANS OR OTHERWISE, WITHOUT THE PRIOR
WRITTEN PERMISSION OF THE OWNER, IS PROHIBITED. AUT0004360 REV. 1
A B C D E F G H J K

120mm 690mm 10000mm 1500mm


100mm
0 J2 0

24W MiniFit
MINIFIT JR 24W CONNECTOR
DSM2 SW A

To J3 pin 3
To J3 pin 15
Overall Label
Switch 3: DSM2/SWA M4 M5
J3 J4
M6 M7 Gland M25
Gland M25 Black on White Wire ID labels
6 DUMMY CB CLOSED 150mm Cable tie 150mm Cable tie
1 6 slightly loose on all wires to 1
5 J21 DUMMY CB CLOSED
5 4 DUMMY CB OPEN allow rotation
4 J5 DUMMY CB OPEN
3
3 2
Wires to be covered in spiral wrap W6
2 J20
1
1
3.5mm Term Block
AUT0003815 _ 3 SW1 + 3
TRM/QRM
DSM2 A 1
RS1 +24V (switched actuator supply) K5 / 1 - 1
J17 viewed from cable entry side 2
RS1 0V (actuator supply) K22 / 1 - 2
3
2 J1 / J3 W5 M3 4 RS1 (K01) Open Command (o/p) K10 / 1 - 3 2
To J3 pin 3
To J3 pin 15
RS1 (K01) Close Command (o/p) K12 / 1 - 4
13 1 Spiral Wrap 9mm id M2 M8 M1 Gland Locknut M25
5
6 RS1 (K01) Indication Common L3 / 1 - 7
Flexible Steel Conduit RS1 (K01) Indication Closed (i/p) L4 / 1 - 8
14 2 Gland Locknut M25 M9 Carrier strip 7
RS1 (K01) Indication Opened (i/p) L5 / 1 - 9
15 3 Cable marker S 8
J1 9 RS1/RS3 (K01/K03) EF Indication Common L61 / 1 - 64 / 78
16 4
M14 M10 10 RS1/RS3 (K01/K03) EF Indication L63 / 1 - 66 / 80
MINIFIT JR 24W CONNECTOR Brady Label Cable marker W RS1 (K01) Spare Indication Common - 153
17 5 24W MiniFit M11 11
RS1 (K01) Spare Indication (i/p) - 154
DSM1 SW A Cable marker 1
3 18 6 M12 12
RS2 +24V (switched actuator supply) 3
Cable marker + M13 13 K5 / 2 - 15
19 7 RS2 0V (actuator supply) K22 / 2 - 16
Cable marker 3 14
20 8 RS2 (K03) Open Command (o/p) K10 / 2 - 17
Overall Label 15
16 RS2 (K03) Close Command (o/p) K12 / 2 - 18
21 9 Switch 1: DSM1/SWA RS2 (K03) Indication Common L3 / 2 - 21
17
22 10 RS2 (K03) Indication Closed (i/p) L4 / 2 - 22
18
19 RS2 (K03) Indication Opened (i/p) L5 / 2 - 23
23 11 Low Gas Indication Common L30 - 43
20
24 12 Low Gas Indication L32 - 45
21
4 22 RS2 (K03) Spare Indication Common - 165 4
Connectors viewed from cable entry side RS2 (K03) Spare Indication (i/p) - 166

Cable DSM1/SWA DSM2/SWA Function Wire Flying Lead End


Ident J1 J3
Pin Pin

1 1 RS1 Actuator +VE (switched) 1.5mmsq Black Pin Crimp


2 13 RS1 Actuator -VE (0V) 1.5mmsq Black Pin Crimp
5 3 5 RS1 (K01) Open Command 1 mmsq Red Pin Crimp 5
Dress cable from J1 as shown above
4 4 RS1 (K01) Close Command 1 mmsq Red Pin Crimp
5 19 RS1 (K01) Indication Common 1 mmsq Red Pin Crimp
6 21 SW1 (K01) Closed Indication 1 mmsq Red Pin Crimp
7 20 RS1 (K01) Open Indication 1 mmsq Red Pin Crimp
8 24 RS1/3 (K01/3) EF Ind Common 1 mmsq Red Pin Crimp
J24 9 22 RS1/3 (K01/3) EF Ind 1 mmsq Red Pin Crimp
Socket Crimp for connectors J1 & J2 10 6 RS1 (K01) Spare Ind Common 1 mmsq Red Pin Crimp
11 18 RS1 (K01) Spare Ind 1 mmsq Red Pin Crimp
6 12 1 RS2 Actuator +VE (switched) 1.5mmsq Black Pin Crimp 6
13 13 RS2 Actuator -VE (0V) 1.5mmsq Black Pin Crimp
14 5 RS2 (K03) Open Command 1 mmsq Red Pin Crimp
15 4 RS2 (K03) Close Command 1 mmsq Red Pin Crimp
W1 Wire Black 1.5 sqmm Tri-rated 16 19 RS2 (K03) Indication Common 1 mmsq Red Pin Crimp
2 x 12.31m 17 21 RS2 (K03) Closed Indication 1 mmsq Red Pin Crimp
18 20 RS2 (K03) Open Indication 1 mmsq Red Pin Crimp
19 8 Low Gas Common Ind 1 mmsq Red Pin Crimp
W2 Wire Black 1sqmm Tri-rated
20 9 Low Gas Ind 1 mmsq Red Pin Crimp
17 x 12.31m
7 21 6 RS2 (K03) Spare Ind Common 1 mmsq Red Pin Crimp 7
W3 Wire Black 1sqmm Tri-rated 22 18 RS2 (K03) Spare Ind 1 mmsq Red Pin Crimp
4 x 100 mm

NOTES
8 8
1. Fit wire identification labels on both ends of all wires
M15 Seal-top Bag
for labels

REV DATE REF CHANGE DESIGN


THE COPYRIGHT IN THIS DOCUMENT IS THE PROPERTY OF DATE: SCHEMATIC NUMBER: TITLE: Gemini 3 RTU (DSM) to RMU 10m
1 25/06/19 ... Electric
2 09/08/19 ....
Initial Release Based on AUT0003200
Add wiring for dummy close signal
LUCY SWITCHGEAR (EMS) LTD, TRADING AS LUCY ELECTRIC
THE DOCUMENT IS SUPPLIED BY LUCY SWITCHGEAR (EMS) LTD
30/08/2019 AUT0003815 SHEET
TRM/QRM SW1 & 3 to Flying Leads
9 TITLE: 9
3 30/08/19 ECR 22948 Correct conduit gland part no. & dummy CB wires ON THE EXPRESS TERMS THAT IT BE TREATED AS UNIT 14 THORPE LANE FILE
. ../../.. .... ............ CONFIDENTAL, AND THAT IT MAY NOT BE COPIED, USED, THORPE WAY IND. EST. SHEET: NAME: AUT0003815_3 G3 Umbilical DSM RTU 10m T
. ../../.. .... ............ OR DISCLOSED FOR ANY OTHER PURPOSE THAN THAT BANBURY OX16 4UT
. ../../.. .... ............ WHICH IT IS SUPPLIED WITHOUT EXPRESS WRITTEN CONSENT. +44(0)1295 270448 1 of 1 BY: CHO REV: 3
A B C D E F G H J K
A B C D E F G H J K

160mm 690mm 10000mm 1500mm


0 0

Relay - A1

Trip Coil Interposing Relay


1 1

A1 A2

Wire Black 1sqmm Tri-rated


14 14
2 W2 2
W1
Relay - 14

Overall Labels (supplied loose) 13 13 Wire Black 1.5 sqmm Tri-rated


2 x 550 mm 12.8m
Switch 2: DSM1/CT B 12 12
Switch 4: DSM2/CT B
M4 M1 M5
Gland M25 Flexible Steel Conduit Gland M25
1 = +24V DC Perm
To DIN
Rail
MINIFIT 6W CONNECTOR Term Black on White Wire ID labels
3 J2 Wires to be covered in spiral wrap slightly loose on all wires to 3
allow rotation
4 1
5 2 AUT0003814 _ 3 W7
6 3
Lucy TRM/QRM
1
J1 J2
W6 M3 2 +24VDC Permanent (Trip Coil Supply) K1 - 41
6W MiniFit MINIFIT JR 24W CONNECTOR Bag with loose parts 0VDC Permanent To be assigned
J1 3
4 13 1 Spiral Wrap 9mm id M2 See below Gland Locknut M25 4
CB Trip (Open) Command (o/p) K2 - 42 4
14 2 Gland Locknut M25 CB Indication common L3 / * - 33
SUPPLY LOOSE IN A BAG CABLE TIED TO CABLE 5
24W MiniFit CB Indication Closed (i/p) L4 / * - 34
15 3 M6 6
Carrier strip for ovalgrip cable markers CB Indication Opened (i/p) L5 / * - 35
M13 7 CB Relay Trip Common (i/p)
16 4 M7 Ovalgrip cable marker S 8 RL11 - 96

17 5
110mm Brady Label
M8 Ovalgrip cable marker W
9
CB Relay Trip (i/p)
CB Watchdog Relay (i/p)
RL13 - 98
RL01 - 93
10
CB Watchdog Relay Common (i/p)
18 6 M9 Ovalgrip cable marker 2 11
1 CB Phase Y (S1) CT (i/p)
RL03 - 95
D30 - 122
12
19 7 M10 Ovalgrip cable marker 4 13
1 CB Phase Y (S2) CT (i/p) D130 - 124
5 CB Spare Indication Common (i/p) - 155 5
20 8 Socket Crimp for connectors J1 & J2 Overall Labels (supplied loose)
M11 150mm Cable tie 14
CB Spare Indication (i/p) - 156
15
21 9 M12 150mm Cable tie 16 CB Spare Output (volt-free N/O) - 151 / 165
Switch 2: DSM1/SWB CB Spare Output (volt-free N/O) - 152 / 166
22 10
Switch 4: DSM2/SWB
23 11
24 12
Connectors viewed from cable entry side
Cable DSM DSM Interposing Function Wire Flying Lead End
6 Ident J1 J2 Relay 6
Pin Pin Terminal

N/A 1 A1 +24VDC Switched to interposing rly 1 mmsq N/A

1 DIN +24VDC (Permanent-Trip Coil Sply) 1.5mmsq Red Pin Crimp


Term
Dress cable from J1 as shown above 2 13 0VDC (Permanent) 1.5mmsq Red Pin Crimp
3 14 Trip (Open) Command 1 mmsq Red Pin Crimp
7 4 19 Switch Indication Common 1 mmsq Red Pin Crimp 7
5 21 Closed Indication 1 mmsq Red Pin Crimp
W3 Wire Black 1.5 sqmm Tri-rated 6 20 Open Indication 1 mmsq Red Pin Crimp
2x12.3m 7 8 Relay Trip Common 1 mmsq Red Pin Crimp
8 7 Relay Trip 1 mmsq Red Pin Crimp
W4 Wire Black 1.5 sqmm Tri-rated 9 22 Watchdog Relay 1 mmsq Red Pin Crimp
4x12.35m 10 24 Watchdog Relay Common 1 mmsq Red Pin Crimp
11 2 CT L2 (Y Phase) 1.5mmsq Blue 15mm hook blade
W5 Wire Black 1sqmm Tri-rated
12 5 CT Common 1.5mmsq Blue 15mm hook blade
12 x 12.3m
13 6 Spare Indication Common 1 mmsq Red Pin Crimp NOTES
8 14 18 Spare Indication 1 mmsq Red Pin Crimp 8
15 15 Spare Output 1 mmsq Red Pin Crimp 1. Fit wire identification labels on both ends of all wires
16 3 Spare Output 1 mmsq Red Pin Crimp

REV DATE REF CHANGE DESIGN


THE COPYRIGHT IN THIS DOCUMENT IS THE PROPERTY OF DATE: SCHEMATIC NUMBER: TITLE: Gemini 3 RTU (DSM/FPM) to RMU 10m
1 25/06/19 ... Electric
2 24/07/19 ECR 22749
Initial Release Based on AUT0003200
Spare O/P added
LUCY SWITCHGEAR (EMS) LTD, TRADING AS LUCY ELECTRIC
THE DOCUMENT IS SUPPLIED BY LUCY SWITCHGEAR (EMS) LTD
27/08/2019 AUT0003814 SHEET
to Flying Leads
9 TITLE: 9
3 27/08/19 ECR 22948 Correct conduit gland part no. ON THE EXPRESS TERMS THAT IT BE TREATED AS UNIT 14 THORPE LANE FILE
M14 Seal-top Bag . ../../.. .... ............ CONFIDENTAL, AND THAT IT MAY NOT BE COPIED, USED, THORPE WAY IND. EST. SHEET: NAME: AUT0003814_3 G3 UMBILICAL ADDC_ADWE
for labels . ../../.. .... ............ OR DISCLOSED FOR ANY OTHER PURPOSE THAN THAT BANBURY OX16 4UT
. ../../.. .... ............ WHICH IT IS SUPPLIED WITHOUT EXPRESS WRITTEN CONSENT. +44(0)1295 270448 1 of 1 BY: CHO REV: 3
A B C D E F G H J K
Distribution Substation Automation
Client : Abu Dhabi Distribution Company (ADDC)
Contract No. :
Distribution Substation :TRM / QRM

List of Components in RTU


SN Items QTY Remarks
1 MCM(Master Control Module) 1

2 PSM(Power Supply Module) 1

3 DSM(Dual Switch Module) 2

4 Battery Charger 1

5 Battery 1

Page 1 of 1
List Of Componenets REV.1
BOQ
Contractor : National Projects & Contruction LLC 1

Approved ADWEA VL
Employer : ALDAR Projects 2

Consultant : PARSONS 3 Technical Catalogue

Client : ADDC 4 Compliance Statement

RTU Data Sheet


SS : RMU Substations 5

6 Company Profile
Internal Project No:

Project Name : Madinat Al Riyadh City Ph-6A & 6B 7 Trade License

MATERIAL SUBMITTAL: DMS-RTU for RMU.Rev.01


(General Documents)
BOQ
Contractor : National Projects & Contruction LLC 1

Approved ADWEA VL
Employer : ALDAR Projects 2

Consultant : PARSONS 3 Technical Catalogue

Client : ADDC 4 Compliance Statement

RTU Data Sheet


SS : RMU Substations 5

6 Company Profile
Internal Project No:

Project Name : Madinat Al Riyadh City Ph-6A & 6B 7 Trade License

MATERIAL SUBMITTAL: DMS-RTU for RMU.Rev.01


(General Documents)
BOQ
Contractor : National Projects & Contruction LLC 1

Approved ADWEA VL
Employer : ALDAR Projects 2

Consultant : PARSONS 3 Technical Catalogue

Client : ADDC 4 Compliance Statement

RTU Data Sheet


SS : RMU Substations 5

6 Company Profile
Internal Project No:

Project Name : Madinat Al Riyadh City Ph-6A & 6B 7 Trade License

MATERIAL SUBMITTAL: DMS-RTU for RMU.Rev.01


(General Documents)
engineering intelligent solutions
www.lucyelectric.com

Business profile

engineering intelligent solutions


About us

The team at Lucy Electric are experts


in secondary distribution and
automation solutions, enabling the
safe, efficient and reliable delivery
of electricity to homes and
businesses worldwide.
We use our engineering excellence to design and
manufacture high quality, best-in-class, ring main
units, switchgear products and services tailored to
meet our customers’ needs. Working at the forefront
of developments in the industry, our experienced
engineers design and deliver network automation
projects from concept to deployment, completing an
end to end solution through the operational life cycle.

Innovation is vital to our business and during 2015 our


investment in research and development increased as
we continue to create high performance solutions at
the cutting edge of switchgear design.

With over 100 years’ industry experience, we


understand the challenges our customers face now and
in the future. Our focus is to work in partnership with
our customers and we respond quickly and effectively,
always looking for the best solution.

Page 2
Our vision

To be the leader in engineering intelligent switchgear solutions through


excellence in customer service and innovation.

Our heritage

Lucy Electric is part of W Lucy & Co. Ltd, an international Group of four diversified
businesses. Established in 1812 the company has grown over an unbroken
timeline to include specialist businesses in street lighting control; iron, aluminium
and copper castings; real estate management; as well as medium and low voltage
switching and automation solutions for secondary electrical distribution systems.

The Group employs over

1,300 people worldwide

Annual turnover, over

£
200m

Page 3
Experts in distribution
network automation
As distribution networks become more complex, Network Operators are
increasingly looking to automation solutions to help them maximise existing assets,
reduce faults, minimise losses and maintain power quality.

Lucy Electric is an expert in secondary distribution Gemini 3 RTU


network automation with an extensive range of products
and services designed to deliver enhanced network Our latest generation range of remote terminal units,
intelligence, the highest levels of operational efficiency Gemini 3, offers customers a highly flexible platform for
and easy flexible upgrades to meet our customers’ advanced feeder automation. Delivering fast response
changing needs. and timely data, the unique modular design of the
Gemini 3 allows flexibility and scalability to be built
Our highly experienced engineers work at the forefront into network automation projects.
of design and implementation for automation projects,
advising customers from concept to delivery and offering Using different plug-in modules the units can be
a full range of post implementation services. configured from a simple monitoring-only device to a
sophisticated High Voltage (HV) multi-switch controller.
From retrofit solutions, which enhance the existing asset The future-proofed design evolves to meet customers’
base, to the latest generation, automation-ready ring changing needs by adding or upgrading individual
main units, remote terminal units, SCADA, Distribution modules, without the need to recalibrate.
Management Systems (DMS) and Low Voltage (LV)
monitoring systems, for both underground and overhead The Gemini 3’s secure, multi-stage switching sequences
networks, our extensive range of products and services guarantee the safe operation of switchgear and units can
provide everything our customers need to efficiently and be remotely accessed during support activities to ensure
cost effectively automate their distribution network safe and reliable operation.
Cyber Security of Distribution Automation systems is a
challenging and necessary component of the solutions
we deliver. From the operating systems and application
code running within our Remote Terminal Unit (RTU)
products to the communications infrastructures we
deploy, we take every possible step to ensure that the
systems are secure and resistant to attack. Our experts are
constantly keeping up to date with the latest threats and,
if necessary, we release timely updates
to maintain the integrity of our products.

Network Management Solutions


Lucy Electric’s network management solutions deliver
robust control and monitoring of medium voltage
networks. The range includes both Distribution
Management Systems (DMS) and Supervisory Control
and Data Acquisition (SCADA) systems, giving
customers an enhanced overview and the ability to
remotely manage their network.

Working together the DMS and SCADA systems


provide network operators with real-time network
information and modelling to improve the overall
operational efficiency of the network and rapidly
locate and resolve faults.

Page 4
GridKey
Our solutions extend into low voltage monitoring
via the GridKey range. GridKey is a world-leading
LV continuous monitoring system which measures,
communicates and stores real-time data, translating
this into actionable information through a suite of
analysis tools.

Using the information, distribution network


operators are able to quickly diagnose, locate and
resolve faults, better protect assets through planned
maintenance and reduce capital and operational
costs. The system allows operators to identify areas
of concern across the LV distribution network, so
that the stresses of load and voltage fluctuation
can be proactively managed and power quality
can be maintained.

MCU Transmits
Data to Database

MCU GridKey Sensor Feeder

Secondary Database DNO Control Centre


Substation

LV Supply

Power Station

Page 5
Best-in-class switchgear solutions
Lucy Electric is a global leader in secondary power distribution solutions,
specialising in high-performance switchgear for utility, industrial and commercial
applications. With reliability, safety and value built-in as standard, our best-in-class
products are continually developed to anticipate changing market needs.

Medium voltage ring main units Low voltage cut outs


(RMU)
We are a market leader in the design and manufacture Providing a robust and durable solution for the vast
of high performance, medium voltage SF6 gas and oil majority of LV protection and distribution requirements
insulated RMUs for transformer or ground mounted up to 630 A, the cut out range offers robust performance,
applications. Suitable for both indoor and outdoor versatility and a service life in excess of 20 years.
locations our RMUs are capable of operating in the most The range includes:
extreme environmental conditions. Our range includes:
Pole Mounted Cut Outs
Aegis Plus – SF6 insulated compact and modular Heavy duty cut outs
with vacuum circuit breaker protection, front cable Outdoor house service cut outs
termination, and 3 and 4 switching functions in a single Indoor house service cut outs
stainless steel enclosure – 24 kV Substation LV

Sabre – SF6 insulated with vacuum circuit breaker


protection, lateral and rear cable termination, fully
weather proof with IP54 for outdoor applications – 24 kV

Trident – Oil insulated with fuse protection, lateral and


rear cable termination. Designed for harsh and corrosive
environmental conditions – 15.5 kV

High/Medium voltage switch


disconnectors
Our best-in-class range of high and medium voltage
switch disconnectors include pole or structure mounted
air break disconnectors and air and gas load break
switches. The range includes:

Rapier AX – Air break switch disconnectors with


12 / 15.5 / 24 / 36 kV options

Rapier GX SF6 – Enclosed load break switches


with 15 / 26 / 38 kV options

Rapier DSB – Double side break switch disconnectors


with options up to 145 kV

Low voltage distribution cabinets


415 V
Our comprehensive product portfolio includes wall,
ground and transformer mounting cabinets suitable for a
variety of different applications. The cabinet features the
enhanced safety Aculok fuse handle.

Page 6
Aegis Plus

Sabre

Gemini 3 RTU

Sa
bre

Rapier GX

Page 7
Whole life cycle approach to
maximse your assets
Our expert Energy Services team works with our customers to help them make the
most of their network assets across the whole product life cycle. We offer end-to-
end solutions, from design and specification of projects through installation and
commissioning, to whole life maintenance and product support.

From a simple service to a fully outsourced turnkey


solution, our complete life cycle management
approach ensures customers can maximise the
value of their assets and make the most of
their internal resources.

Our aim at Lucy Electric is to ensure that our


customers consistently get the very best
from our technology – and their budgets.

Whatever the market or commercial challenges,


we work closely with you to find the right solution
for the job to help plan for future challenges
and opportunities.

Our range of services includes all aspects of


consulting design and engineering; equipment
supply, implementation and installation;
operations and maintenance; data management
and customer care.

Enhancing your capabilities


Our Skills Academy training centre offers customers All Lucy Electric trainers are experts in installing,
a range of training courses in the management and maintaining and operating Lucy Electric and other
maintenance of our switchgear and automation switchgear and automation manufacturer's products in
product range. With over 100 years’ experience in the field.
the design and manufacture of switchgear and in
excess of 500,000 ring main units installed globally,
we have the knowledge and expertise to provide an
exceptionally high level of training.

We offer focused classes in small training groups


at both basic and advanced product training levels.
Candidates gain hands on practical experience at an
appropriate level for their knowledge base and have
the opportunity for further academic training.

Courses can be delivered at customer sites or at our


own facilities either within a classroom environment
or in the practical training centre.

Page 8
Protecting our environment

We take our environmental responsibilities very seriously at Lucy Electric.


We recognise that our operations have an impact on the local, regional and
global environment within which people live and work, and that sustainable
growth is only possible through careful stewardship of our impacts.

Developing environmentally sound products that provide We regularly review our environmental performance
maximum operator safety is fundamental to the success and ensure it complies with all national environmental
of our business. We make sure that all our site operations regulations, laws and codes of practice, as well as
safeguard health, minimise energy use, emissions and our internal Environmental Policy. Our environmental
waste, and conserve natural resources. management system is ISO 14001 certified and the
Certified Emissions Measurement and Reduction Scheme
(CEMARS) independently verifies our greenhouse
gas emissions management and reduction plan, in
compliance with ISO 14064–1.

Business with integrity


Our Corporate Social Responsibility
policy sets out the principles we follow
and the programmes we have developed
to focus on the areas where we have
significant impact or influence.

As a responsible manufacturer built on our proud


heritage and driven by strong principles, quality, value
and integrity are at the heart of our business strategy. We
believe in respecting the interests of all our stakeholders:
partners, customers, suppliers and the wider community
and we actively look for opportunities to improve the
environment and to contribute to the wellbeing of the
communities in which we trade.

We expect all of our employees to uphold the highest


standards of business conduct and ethics during
commercial operations, and to comply fully with all legal
and regulatory requirements of the region in which the
business operates.

Page 9
Our global reach

Lucy Electric has a international presence with a strong local focus. Over the last
few years we have invested significantly in infrastructure, developing centres
for manufacturing and engineering excellence in regions across the world.

Our head office in Thame, Oxfordshire, is the centre of In 2015 Lucy Electric acquired all Crompton Greaves
excellence for our engineering capabilities. Providing (CG's) equity interests in CG Lucy Switchgear Ltd, an
engineering design, specification and Energy Services to Indian company and changed its name to Lucy Electric
our customers and business partners worldwide. India a medium voltage, secondary power distribution
business unit. This is part of Lucy Electric’s strategy to
Based in Dubai, our state-of-the-art, operational grow its business in developing markets and will allow
excellence centre manufactures and distributes Lucy the company to meet the growing demand for electrical
Electric’s best-in-class ring main units and overhead line infrastructure equipment and the development of Smart
equipment. This is supported by a number of sites in Grid projects in India.
Saudi Arabia, India and the UK, manufacturing critical
components for sub-assembly, overhead line equipment Additionally we have offices in Saudi Arabia, United Arab
and providing final assembly for regional markets. Emirates, South Africa, Kenya, Ghana, China, Malaysia
and Thailand and an established network of industrial
In 2014 Lucy Electric opened a new facility in Thailand, partners, giving us a presence in over 30 countries
which manufactures ring main units and overhead line worldwide.
equipment for South East Asia and international markets,
combining British technology, design and innovation with
Thai manufacturing excellence.

UK
Thame
United Arab Emirates
Banbury
Dubai
China
Beijing

India
Vadodara
Nasik
Thailand
Rayong
Bangkok

Malaysia
South Africa
Kuala Lumpur
Johannesburg Saudi Arabia
Dammam
Jeddah
Riyadh

Offices Factories

Page 10
Providing products
and services to meet our
customers requirements

Page 11
Contractor : National Projects & Contruction LLC 1 GENERAL DOCUMENTS

Employer : ALDAR Projects 2 RTU

Consultant : PARSONS

Client : ADDC

SS : RMU Substations

Internal Project No:

Project Name : Madinat Al Riyadh City Ph-6A & 6B

MATERIAL SUBMITTAL: DMS-RTU for RMU


(General Documents)
Contractor : National Projects & Contruction LLC 1 SLD

Over All SLD


Employer : ALDAR Projects 2

Country of Origin
Consultant : PARSONS 3

Signal List
Client : ADDC 4

Tele-Information Plan
SS : RMU Substations 5

6 Cable Overview List


Internal Project No:

Adaptation Design
Project Name : Madinat Al Riyadh City Ph-6A & 6B 7

8 I/O Connection Diagram

MATERIAL SUBMITTAL: DMS-RTU for RMU.Rev.01


9 RTU Functional Specification

10 RTU Detailed Design

11 RTU Method Statement

12 RTU FAT Procedure

13 RTU SAT Procedure

14 POINT TO POINT TEST PROCEDURE

15 Warranty Certificate
Contractor : National Projects & Contruction LLC 1 SLD

Over All SLD


Employer : ALDAR Projects 2

Country of Origin
Consultant : PARSONS 3

Signal List
Client : ADDC 4

Tele-Information Plan
SS : RMU Substations 5

6 Cable Overview List


Internal Project No:

Adaptation Design
Project Name : Madinat Al Riyadh City Ph-6A & 6B 7

8 I/O Connection Diagram

MATERIAL SUBMITTAL: DMS-RTU for RMU.Rev.01


9 RTU Functional Specification

10 RTU Detailed Design

11 RTU Method Statement

12 RTU FAT Procedure

13 RTU SAT Procedure

14 POINT TO POINT TEST PROCEDURE

15 Warranty Certificate
LUCY RMU SLD

SS No.
1. RD-1823 -2TR- PHASE 6B
2. RD-1833 -1TR- PHASE 6B
3. RD-1910 -2TR- PHASE 6B
SCHNEIDER RMU SLD

SS No.
1. RD-2412 -2TR- PHASE 6A
2. RD-3012 -2TR- PHASE 6A
3. RD-3013 -2TR- PHASE 6A
Contractor : National Projects & Contruction LLC 1 SLD

Over All SLD


Employer : ALDAR Projects 2

Country of Origin
Consultant : PARSONS 3

Signal List
Client : ADDC 4

Tele-Information Plan
SS : RMU Substations 5

6 Cable Overview List


Internal Project No:

Adaptation Design
Project Name : Madinat Al Riyadh City Ph-6A & 6B 7

8 I/O Connection Diagram

MATERIAL SUBMITTAL: DMS-RTU for RMU.Rev.01


9 RTU Functional Specification

10 RTU Detailed Design

11 RTU Method Statement

12 RTU FAT Procedure

13 RTU SAT Procedure

14 POINT TO POINT TEST PROCEDURE

15 Warranty Certificate
LEGEND :
FROM 132/22kV, 60MVA FROM 132/22kV, 60MVA 22kV CABLES - (PSS-1)
TRANSFORMER-1 TRANSFORMER-2
SS 1 - 23
EXISTING PRIMARY SUBSTATION - 1
2500A 2500A
SECTOR NUMBER
BUS SECTION-1 BUS SECTION-2 SUBSTATION NUMBER
22kV, 2500A, 31.5kA, 1s 22kV, 2500A, 31.5kA, 1s 22/0.415 kV SUB STATION
SS1- LF 17
LOOP NUMBER
630A 630A 630A 630A 630A 630A 630A 630A 630A 1250A 1250A 1250A 1250A 1250A 1250A 630A 630A 630A 630A 630A 630A 630A 630A LOOP FEEDER
PRIMARY SUBSTATION NO.1

2500A 2500A EXISTING SUBSTATION

PROPOSED SUBSTATION

PROPOSED BUILDING SUBSTATION


LP01A LP02A LP03A LP04A LP05A LP06A LP07A LP08A LP17A LP17B LP08B LP07B LP06B LP05B LP04B LP03B LP02B LP01B

1500KVA TRANSFORMER

TX.01
LOOP-1: LOOP-2: LOOP-3: LOOP-4: LOOP-5: LOOP-6: LOOP-7: LOOP-8: LOOP-17: 12 MVAR 12 MVAR 1000KVA TRANSFORMER
TCL=144.10 MVA TCL=144.84 MVA TCL=133.83 MVA TCL=134.91 MVA TCL=138.29 MVA TCL=140.88 MVA TCL=133.29 MVA TCL=139.09 MVA TCL=134.52 MVA
1000kVA CAPACITOR CAPACITOR
SL=64.81 MVA SL=65.14 MVA SL=59.86 MVA SL=60.24 MVA SL=62.12 MVA SL=62.90 MVA SL=59.77 MVA SL=63.76 MVA SL=60.81 MVA
BANK-1 BANK-2
22/0.415kV FLL=25.87 MVA FLL=26.07 MVA FLL=24.42 MVA FLL=24.28 MVA FLL=24.89 MVA FLL=25.36 MVA FLL=24.63 MVA FLL=24.85 MVA FLL=24.88 MVA
500KVA TRANSFORMER
SPARE PSS1-LF18

RD1118 SHS0108 RD0815 SHS1616 SHS0308 SHS0802 SS16-6 RD1116 SHS0604 SHS0610 SHS0817 RD1209 PLOT = RD22_M01 RD1210 SHS0403 PLOT = RD8_M01
TCL=4.14 MVA TCL=6.30 MVA TCL=4.30 MVA TCL=5.01 MVA TCL=4.50 MVA TCL=6.32 MVA TCL=0.81 MVA TCL=2.00 MVA TCL=6.27 MVA TCL=6.30 MVA TCL=4.09 MVA TCL=4.14 MVA TCL= 0.65 MVA TCL=5.01 MVA TCL=6.16 MVA TCL= 0.65 MVA 630A CIRCUIT BREAKER
SL=2.79 MVA SL=2.77 MVA SL=1.79 MVA SL= 0.37 MVA SL=2.71 MVA SL=0.37 MVA
SL=1.83 MVA SL=1.88 MVA SL=2.49 MVA SL=1.99 MVA SL=2.77 MVA SL=0.81 MVA SL=0.88 MVA SL=2.77 MVA SL=1.83 MVA SL=2.23 MVA (WITH DRAWABLE TYPE)

SHS0606 RD1115
EARTHING SWITCH
SHS0201 TCL=6.30 MVA TCL=5.44 MVA SHS0607
RD0816 SHS1214
TCL=6.60 MVA TCL=6.30 MVA
TCL=2.14 MVA SHS0311 SL=2.84 MVA
SL=2.77 MVA SL=2.36 MVA
SL=2.77 MVA SHS0310 TCL=2.07 MVA STATION TRANSFORMER
SL=0.94 MVA SHS1902 SHS1904 RD1831 PLOT = RD18_CF03 SHS1905 TCL=4.84 MVA SL=0.92 MVA
TCL=4.84 MVA SHS1801
SHS1615 RD1401 TCL=4.19 MVA TCL=4.30 MVA TCL=3.64 MVA TCL= 0.60 MVA TCL=6.30 MVA RD3016 SHS0104
RD1119 SL=2.12 MVA TCL=6.24 MVA SL=2.12 MVA
TCL=4.61 MVA TCL=5.65 MVA SL=1.88 MVA SL=1.88 MVA SL=1.64 MVA SL=0.34 MVA SL=2.77 MVA TCL=4.90 MVA TCL=6.39 MVA
TCL=2.14 MVA SHS0109
TCL=6.24 MVA SL=2.01 MVA SL=2.56 MVA PLOT = RD11_M02 SHS0601
SL=2.76 MVA SL=2.21 MVA
SHS0404
TCL=6.30 MVA SL=2.81 MVA
CAPACITOR BANK
SL=0.94 MVA
SL=2.74 MVA TCL= 0.65 MVA TCL=6.30 MVA SL=2.77 MVA

RD0817
SHS0202 SL=0.37 MVA SL=2.77 MVA SHS0609
TCL=6.30 MVA SHS1205
BUS DUCT
TCL=5.55 MVA
TCL=4.30 MVA SL=2.45 MVA SL=2.77 MVA TCL=6.16 MVA
SL=1.88 MVA PLOT = RD18_M07 SL=2.71 MVA
SHS0312 SHS1909
TCL=6.30 MVA TCL= 0.65 MVA
SHS1908
TCL=6.36 MVA
RD1828
TCL=5.24 MVA
SHS1906
TCL=6.30 MVA
PLOT = RD9_CR01 OPEN LOOP
TCL=4.16 MVA PLOT = RD11_CF09 SHS0602 TCL=2.00 MVA
SL=1.83 MVA TCL= 0.60 MVA SL=2.77 MVA SL=0.37 MVA SL=2.82 MVA SL=2.30 MVA SL=2.77 MVA TCL=6.30 MVA SL=1.26 MVA
SHS0804 RD1908
SHS1614 SL=0.34 MVA SL=2.77 MVA RD3014
RD1121 TCL=6.32 MVA TCL=5.96 MVA RD0814
TCL=5.94 MVA PLOT = RD10_M02 SHS0204 TCL=2.14 MVA
TCL=1.84 MVA SL=2.77 MVA SL=2.64 MVA TCL=4.30 MVA
RD0708 SL=2.59 MVA TCL= 0.65 MVA TCL=6.40 MVA SL=0.94 MVA SHS1206
SL=0.85 MVA PLOT = RD8_E01 RD1720 SL=1.88 MVA
TCL=4.21 MVA SL=0.37 MVA SL=2.80 MVA TCL=6.30 MVA
TCL= 4.24 MVA SL=2.77 MVA TCL=4.33 MVA
SL=1.86 MVA SHS0605 RD1117 SL=1.89 MVA
SL=2.40 MVA RD1827 RD2709 RD2708 RD2520 SHS2510
TCL=5.97 MVA TCL=3.22 MVA
SHS0801 TCL=4.00 MVA TCL=2.81 MVA TCL=3.19 MVA TCL=2.95 MVA TCL=6.16 MVA PLOT = RD9_CF02
SL=2.66 MVA SL=1.41 MVA
TCL=6.05 MVA SL=1.77 MVA SL=1.26 MVA SL=1.41 MVA SL=1.30 MVA SL=2.71 MVA TCL= 0.58 MVA
SL=2.65 MVA SL=0.33 MVA
RD1008 PLOT = RD10_CF02
SHS0808 TCL=5.54 MVA TCL= 0.60 MVA SHS1803
SHS0901 SHS1209
SHS1617 TCL=2.55 MVA SL=2.47 MVA SHS0608 SHS0603 SL=0.34 MVA TCL=6.00 MVA SHS2906
TCL=6.31 MVA TCL=6.30 MVA
RD1120 TCL=3.92 MVA SL=1.11 MVA TCL=6.30 MVA TCL=6.43 MVA SL=2.65 MVA TCL=6.16 MVA RD0813
SL=2.76 MVA SL=2.77 MVA
TCL=2.92 MVA SL=1.73 MVA SL=2.77 MVA SL=2.83 MVA SL=2.71 MVA TCL=4.24 MVA
SHS1912 RD1822 SHS1916 SHS1917 PLOT = RD25_CF10 SL=1.85 MVA
SL=1.30 MVA
TCL=4.30 MVA TCL=4.30 MVA TCL=4.23 MVA TCL=4.30 MVA TCL= 0.90 MVA
SHS0401 SHS0805 RD1725 SHS1002
TCL=6.30 MVA SL=1.88 MVA SL=1.88 MVA SL=1.87 MVA SL=1.88 MVA SL=0.51 MVA TCL=6.30 MVA
TCL=3.72 MVA SHS0203 SHS2701 TCL=2.14 MVA
SL=2.77 MVA TCL=5.59 MVA SHS1805 TCL=6.18 MVA SL=2.77 MVA
SL=1.62 MVA PLOT = RD11_E02 SL=0.94 MVA
RD1512 SL=2.44 MVA TCL= 4.66 MVA TCL=6.27 MVA SL=2.79 MVA PLOT = RD16_M01
TCL=2.04 MVA SL=2.64 MVA SL=2.71 MVA TCL= 0.65 MVA
SL=0.91 MVA SHS0810 SHS1202 SL=0.37 MVA
TCL=3.62 MVA RD1824 RD1825 RD1820 TCL=6.30 MVA
SHS1612 SHS1913 SHS1915 RD3015
RD1111 SL=1.58 MVA TCL=2.16 MVA TCL=4.30 MVA TCL=4.77 MVA TCL=6.43 MVA TCL=1.87 MVA SL=2.77 MVA SHS0103
TCL=2.69 MVA TCL=5.17 MVA
TCL=5.75 MVA SL=1.18 MVA RD1007 PLOT = RD11_CF07 SL=0.94 MVA SL=1.88 MVA SL=2.12 MVA SL=2.83 MVA SL=0.82 MVA RD1911 SHS2702 SL=2.33 MVA TCL=6.41 MVA
SL=2.57 MVA SHS0806 TCL= 1.30 MVA TCL=1.98 MVA TCL=6.30 MVA RD2710 SL=2.83 MVA
TCL=6.12 MVA
PLOT = RD15_M02 TCL=3.71 MVA SL=0.74 MVA SL=0.91 MVA SL=2.77 MVA TCL=6.41 MVA
SL=2.78 MVA RD1613
TCL= 0.65 MVA SL=1.62 MVA SL=2.83 MVA
RD707 TCL=0.47 MVA SHS1001
TCL=3.01 MVA SL=0.37 MVA SL=0.13 MVA TCL=6.30 MVA
SL=1.34 MVA SL=2.77 MVA
PLOT = RD12_CF01 RD1826 PLOT = RD18_M03 SHS1914 RD1821 SHS1923 SHS1806
SHS0809 SHS0205 TCL= 0.88 MVA TCL=2.14 MVA TCL= 0.65 MVA TCL=4.30 MVA TCL=2.14 MVA TCL=0.81MVA TCL=6.05 MVA SHS2705 RD1619
TCL=3.39 MVA TCL=6.46 MVA SL=0.50 MVA SL=0.94 MVA SL=0.37 MVA SL=1.88 MVA SL=0.94 MVA SL=0.81 MVA SL=2.65 MVA TCL=6.30 MVA TCL=4.30 MVA
SHS1711 SL=1.48 MVA SL=1.88 MVA RD3013
PLOT = RD11_CF08 SHS0803 SL=2.83 MVA SL=2.77 MVA
SHS0902 TCL=3.14 MVA RD2707 TCL=4.84 MVA RD1612 SHS0102
TCL= 0.90 MVA TCL=6.32 MVA SL=1.37 MVA TCL=2.98 MVA TCL=6.52 MVA SL=2.17 MVA TCL=2.00 MVA TCL=6.36 MVA
SL=0.51 MVA SL=2.77 MVA SL=1.30 MVA SL=2.83 MVA SL=0.88 MVA SL=2.80 MVA
PLOT = RD12_CF03 LOOP FEEDER PSS1-LF17 SHS2603

SHS0402 SHS0206
TCL=6.02 MVA
TCL= 1.04 MVA
SL=0.59 MVA SHS1910
TCL=4.30 MVA
SHS1911
TCL=4.17 MVA
SHS1907
TCL=6.43 MVA
RD1829
TCL=4.02 MVA
PLOT = RD20_E01
TCL= 5.05 MVA
TCL=6.45 MVA
SL=2.83 MVA SHS2704
TCL=6.43 MVA
PLOT = RD17_M03
TENDER DOCUMENT
TCL=6.43 MVA SL=2.86 MVA TCL= 0.65 MVA
SL=2.68 MVA SL=1.88 MVA SL=1.86 MVA SL=2.83 MVA SL=1.80 MVA SL=2.83 MVA
SL=2.83 MVA SHS0807 SHS1208 SL=0.37 MVA
SHS0903 RD1611
TCL=6.32 MVA TCL=6.30 MVA
TCL=6.31 MVA RD1508 RD1112 SHS2602 RD1728 TCL=2.95 MVA
SHS1802 SL=2.77 MVA SL=2.77 MVA RD3012
SL=2.76 MVA TCL=4.47 MVA TCL=2.50 MVA TCL=6.32 MVA TCL=6.41 MVA SL=1.30 MVA
PLOT = RD11_CF04 TCL=6.38 MVA SL=1.98 MVA SL=2.83 MVA TCL=4.27 MVA PLOT = RD8_M02
SL=1.15MVA SL=2.77 MVA
TCL= 2.00 MVA SL=2.83 MVA SL=1.89 MVA TCL= 0.65 MVA
SL=1.13 MVA SHS2706 SL=0.37 MVA
TCL=6.11 MVA
SL=2.74 MVA
PLOT = RD15_CF11 PLOT = RD11_CF06 SHS2601 RD1907
00 15-SEP-19 ISSUED FOR TENDER KAM
TCL= 0.60 MVA TCL= 1.40 MVA TCL=6.43 MVA TCL=4.14 MVA REV. DATE DESCRIPTION APPR'D
RD709 SL=0.34 MVA SL=0.79 MVA SL=2.83 MVA SL=1.83 MVA RD1734
PLOT = RD15_CF09 RD1402 SHS1207 RD1729
TCL=2.14 MVA
TCL= 1.30 MVA TCL=6.39 MVA TCL=6.30 MVA TCL=6.30 MVA
TCL=2.07 MVA
SL=0.92 MVA
Client
SL=0.94 MVA SL=2.80 MVA LOOP FEEDER PSS1-LF8 SL=2.77 MVA
SHS1804 SL=0.74 MVA SL=2.78 MVA
RD2606 SHS2803 RD3010
PLOT = RD11_M01 TCL=6.32 MVA TCL=2.80 MVA TCL=5.87 MVA TCL=4.28 MVA RD0812
TCL= 0.65 MVA SL=2.77 MVA SL=1.26 MVA SL=2.58 MVA SL=1.89 MVA TCL=5.03 MVA
SL=0.37 MVA SHS0904 RD1823 SL=2.21 MVA
TCL=6.32 MVA TCL=3.22 MVA
SL=2.77 MVA SL=1.41 MVA
PLOT = RD28_CF02 SHS3001 PLOT = RD28_E02 RD2806 RD2804 SHS2802 SHS2801 RD2607
PLOT = RD15_CF08 TCL= 1.60 MVA TCL= 8.07 MVA SHS1019
TCL=6.27 MVA TCL=3.19 MVA TCL=3.22 MVA TCL=6.16 MVA TCL=6.30 MVA TCL=3.22 MVA
TCL= 1.40 MVA PLOT = RD14_M02 SHS1204 TCL=6.43 MVA
PLOT = RD7_CF02 SL=0.79 MVA TCL= 0.65 MVA
SL= 0.91 MVA SL=2.77 MVA SL= 4.58 MVA SL=1.41 MVA SL=1.41 MVA SL=2.71 MVA SL=2.77 MVA SL=1.41 MVA
TCL=6.30 MVA SL=2.83 MVA SHS1003
PMC
LOOP FEEDER PSS1-LF7
TCL= 0.60 MVA SL=0.37 MVA SL=2.77 MVA TCL=5.30 MVA
SL=0.34 MVA SHS0905 SHS1901 SHS2901 RD1730 SL=2.77 MVA
SHS2604 SHS2605 SHS2703 RD2711 PLOT = RD28_CR01 PLOT = RD28_M01 RD2805 PLOT = RD28_CF02
TCL=6.11 MVA TCL=6.19 MVA TCL=6.27 MVA TCL=4.16 MVA
SHS0306 TCL=6.27 MVA TCL=4.17 MVA TCL=6.30 MVA TCL=2.94 MVA TCL= 0.71 MVA TCL= 0.65 MVA TCL=2.43 MVA TCL= 0.60 MVA SHS0101
SL=2.69 MVA SL=2.74 MVA SL=2.77 MVA SL=1.86 MVA
TCL=2.96 MVA SL=2.78 MVA SL=1.88 MVA SL=2.77 MVA SL=1.32 MVA SL= 0.38 MVA SL= 0.37 MVA SL=1.10 MVA SL= 0.34 MVA TCL=6.30 MVA
SL=1.30 MVA SL=2.77 MVA
LOOP FEEDER PSS1-LF6 PLOT = RD17_M08
PLOT = RD15_CF05
TCL= 2.00 MVA TCL= 0.65 MVA
SHS0811 SHS0812 SHS0813 SHS0816 SHS0815 RD1618 PLOT = RD16_E02 RD1622 SHS1201 SHS1203 SL=0.37 MVA
PLOT = RD15_M01
SL=1.13 MVA
TCL=6.32 MVA TCL=3.86 MVA TCL=3.21 MVA TCL=3.83 MVA TCL=3.86 MVA TCL=2.81 MVA TCL= 7.19 MVA TCL=4.30 MVA TCL=6.20 MVA TCL=6.30 MVA RD1737 Consultant
TCL= 0.65 MVA SL=2.77 MVA SL=1.68 MVA SL=1.40 MVA SL=1.67 MVA SL=1.68 MVA SL=1.18 MVA SL= 4.08 MVA SL=1.88 MVA SL=2.79 MVA SL=2.77 MVA TCL=1.87 MVA
SL=0.37 MVA SL=0.82 MVA SHS1004
RD710 SHS1903 RD3131
TCL=2.64 MVA TCL=6.30 MVA
TCL=6.16 MVA LOOP FEEDER PSS1-LF5 TCL=4.04 MVA
SHS0305 SL=1.25 MVA SL=2.77 MVA SHS0111
SL=2.71 MVA SL=1.77 MVA
TCL=2.84 MVA TCL=6.30 MVA
SL=1.25 MVA SHS1010 RD1736 SHS1014 PLOT = RD17_M02 PLOT = RD17_CF04 RD1727 SHS1013 SHS1016 SHS1017 SHS1018 SHS1015 SL=2.80 MVA
TCL=6.20 MVA TCL=4.27 MVA TCL=6.43 MVA TCL= 0.65 MVA TCL= 0.60 MVA TCL=5.24 MVA TCL=6.30 MVA TCL=6.34 MVA TCL=6.16 MVA TCL=4.27 MVA TCL=6.30 MVA
SL=2.74 MVA SL=1.89 MVA SL=2.83 MVA SL= 0.37 MVA SL= 0.34 MVA SL=2.33 MVA SL=2.77 MVA SL=2.78 MVA SL=2.71 MVA SL=1.89 MVA SL=2.77 MVA Project / Contract
RD1509 PLOT = RD17_CF05
TCL=1.97 MVA TCL= 0.60 MVA
SL=0.91 MVA LOOP FEEDER PSS1-LF4 SL=0.34 MVA
RIYADH CITY NORTH
SHS0301 SHS0405
SHS1712
TCL=4.30 MVA
SL=1.88 MVA
SHS1714
TCL=4.27 MVA
SL=1.87 MVA
SHS1705
TCL=3.87 MVA
SL=1.73 MVA
SHS1701
TCL=2.00 MVA
SL=0.88 MVA
SHS1710
TCL=5.99 MVA
SL=2.62 MVA
RD2928
TCL=3.08 MVA
SL=1.41 MVA
RD3124
TCL=6.08 MVA
SL=2.69 MVA
SHS2308
TCL=5.62 MVA
SL=2.70 MVA
RD3132
TCL=5.96 MVA
SL=2.64 MVA
PLOT = RD31_M08
TCL= 0.65 MVA
SL=0.37 MVA PLOT = RD17_CR02 SHS0110
ALL PHASES
TCL=4.14 MVA TCL=6.41 MVA TCL= 0.59 MVA TCL=6.24 MVA
SL=1.86 MVA SL=2.83 MVA SL=0.32 MVA SL=2.74 MVA Drawing Title
LOOP FEEDER PSS1-LF3

SHS0906 SHS0907 PLOT = RD15_CF10 PLOT = RD15_CF03 PLOT = RD15_M03 SHS0409 SHS1005 SHS1007 RD1735 SHS1008
TEMPORARY FEEDING
TCL=6.32 MVA
SL=2.77 MVA
TCL=6.18 MVA
SL=2.71 MVA
TCL= 0.90 MVA
SL= 0.51 MVA
TCL= 1.60 MVA
SL= 0.91 MVA
TCL= 0.65 MVA
SL= 0.37 MVA
TCL=0.40 MVA
SL=0.40 MVA
TCL=6.16 MVA
SL=2.71 MVA
TCL=6.30 MVA
SL=2.77 MVA
TCL=2.95 MVA
SL=1.30 MVA
TCL=4.27 MVA
SL=1.89 MVA ARRANGEMENTS FOR ALL PLOTS WITH
SHS0302
LOOP FEEDER PSS1-LF2 PSS-1 TRANSCO SUBSTATION - SHEET 1/2
SHS0107
TCL=3.61 MVA TCL=6.30 MVA
SL=1.59 MVA SHS0406 RD0712 RD1733 RD1732 RD1731 SS1006 SS1009 SS1012 SS1011 RD1726 PLOT = RD17_M01
TCL=6.30 MVA TCL=6.30 MVA TCL=4.23 MVA SL=2.77 MVA
TCL=6.27 MVA TCL=5.04 MVA TCL=6.27 MVA TCL=3.82 MVA TCL=4.81 MVA TCL=6.27 MVA TCL=6.30 MVA TCL= 0.65 MVA CONTRACT No: JOB No:
SL=2.77 MVA SL=2.23 MVA SL=2.77 MVA SL=1.65 MVA SL=2.12 MVA SL=2.77 MVA SL=2.77 MVA SL=2.77 MVA SL=2.77 MVA SL=1.89 MVA SL=0.37 MVA
DRAWN DESIGNED CHECKED APPROVED
LOOP FEEDER PSS1-LF1
ST SD MSA KAM
SHS0307 RD0711 RD1721 RD1722 RD1724 PLOT = RD18_E03 RD1818 RD1615 PLOT = RD14_M01 SHS0105 SHS0106
PLOT = RD9_CF01
TCL=1.00 MVA
SL=0.57 MVA
SHS0309
TCL=2.71 MVA
SL=1.19 MVA
SHS0303
TCL=3.46 MVA
SL=1.54 MVA
TCL=4.32 MVA
SL=1.82 MVA
TCL=3.06 MVA
SL=1.30 MVA
TCL=5.29 MVA
SL=2.35 MVA
TCL=2.14 MVA
SL=0.94 MVA
TCL=4.14 MVA
SL=1.83 MVA
TCL= 4.26 MVA
SL= 2.42 MVA
TCL=4.84 MVA
SL=2.12 MVA
TCL=2.68 MVA
SL=1.18 MVA
TCL= 0.65 MVA
SL= 0.37 MVA
TCL=6.24 MVA
SL=2.74 MVA
TCL=6.30 MVA
SL=2.77 MVA
DATE 15-SEP-2019 ACTUAL SIZE A1
Drawing Scale. N.T.S
REFER SHEET REFER SHEET
NO.RN-02-00001-00-07-EL-PIL-DG-000302 NO.RN-02-00001-00-07-EL-PIL-DG-000302
Drawing No.
00
ISSUED FOR CONSTRUCTION_Rev-00 RN-02-00001-00-07-EL-PIL-DG-000301
\\Xeuae03fs01\uaeauh_trp\PROJECTS\351159 Riyadh North\04 Users\CADD\Issued for Construction Drawings_(Dec 2021)\00-ALL PHASE\ELECTRICAL\CAD\ELECTRICAL MV SCHEMATIC DIAGRAM\RN-02-00001-00-07-EL-PIL-DG-000301-06_DELETED FOR AD-1.dwg
Last Saved By: P002959B Last Saved Date: 12/19/2021 5:57 PM Printed Date: 12/19/2021 9:02 PM Printed By: Chirayath, Subeesh [NN-AE]
LEGEND :

REFER SHEET REFER SHEET 22kV CABLES - (PSS-1)


NO.RN-02-00001-00-07-EL-PIL-DG-000301 NO.RN-02-00001-00-07-EL-PIL-DG-000301 SS 1 - 23
FROM 132/22kV, 60MVA FROM 132/22kV, 60MVA SECTOR NUMBER
TRANSFORMER-4 TRANSFORMER-3
EXISTING PRIMARY SUBSTATION - 1 SUBSTATION NUMBER
2500A 2500A
22/0.415 kV SUB STATION
BUS SECTION-4 BUS SECTION-3 SS1- LF 17
22kV, 2500A, 31.5kA, 1s 22kV, 2500A, 31.5kA, 1s
LOOP NUMBER
LOOP FEEDER
PRIMARY SUBSTATION NO.1
630A 630A 630A 630A 630A 630A 630A 630A 630A 1250A 1250A 1250A 1250A 1250A 1250A 630A 630A 630A 630A 630A 630A 630A 630A

EXISTING SUBSTATION

2500A 2500A
PROPOSED SUBSTATION

PROPOSED BUILDING SUBSTATION

1500KVA TRANSFORMER
LP09A LP10A LP11A LP12A LP13A LP14A LP15A LP16A LP16B LP15B LP14B LP13B LP12B LP11B LP10B LP09B
1000KVA TRANSFORMER
TX.02
1000kVA LOOP-9: LOOP-10: LOOP-11: LOOP-12: LOOP-13: LOOP-14: LOOP-15: LOOP-16:
12 MVAR 12 MVAR
500KVA TRANSFORMER
TCL=118.76 MVA TCL=63.96 MVA TCL=139.11 MVA TCL=136.27 MVA TCL=139.35 MVA TCL=137.30 MVA TCL=137.61 MVA TCL=138.45 MVA
22/0.415kV SL=52.40 MVA SL=28.44 MVA SL=63.09 MVA SL=61.16 MVA SL=63.04 MVA SL=64.32 MVA SL=62.74 MVA SL=62.71 MVA CAPACITOR CAPACITOR
FLL=21.38 MVA FLL=11.51 MVA FLL=25.04 MVA FLL=24.94 MVA FLL=25.08 MVA FLL=24.71 MVA FLL=24.77 MVA FLL=24.92 MVA BANK-4 BANK-3
630A CIRCUIT BREAKER
SPARE PSS1-LF20 (WITH DRAWABLE TYPE)

SHS1106
TCL=6.30 MVA
RD1311
TCL= 1.06 MVA
PLOT=RD13_E02 SHS1304
TCL=6.30 MVA
RD2310 PLOT=RD23_CR02 RD3126 RD3212
SPARE PSS1-LF19 RD2923 RD3130 RD3120 RD2410 SHS1404 RD3217 RD1114 SHS1101 EARTHING SWITCH
TCL= 3.12 MVA TCL= 1.49 MVA TCL= 2.12 MVA TCL= 6.28 MVA TCL= 4.30 MVA TCL= 4.30 MVA TCL= 2.07 MVA TCL= 4.94 MVA TCL= 6.07 MVA TCL=6.29 MVA TCL= 4.14 MVA TCL= 4.13 MVA TCL=6.36 MVA
SL=2.79 MVA SL=0.47 MVA SL=1.77 MVA SL=2.77 MVA SL=0.71 MVA SL=1.14 MVA SL=2.76 MVA SL=1.88 MVA SL=1.88 MVA SL=0.91 MVA SL=2.17 MVA SL=2.69 MVA SL=2.77 MVA SL=1.84 MVA SL=1.85 MVA SL=2.82 MVA
STATION TRANSFORMER

SHS2301 CAPACITOR BANK


RD1215 SHS2403 RD3210 SHS3007 TCL=5.43 MVA RD3121 RD3215
TCL= 5.60 MVA PLOT=RD23_CF01 TCL=6.25 MVA SHS2311 TCL= 4.30 MVA TCL=6.30 MVA SL=2.62 MVA TCL= 5.35 MVA PLOT=RD24_M01 TCL= 4.30 MVA
SHS1402 RD2312
SL=2.47 MVA TCL=6.30 MVA TCL= 1.60 MVA SL=2.77 MVA TCL=5.69 MVA SL=1.88 MVA SL=2.77 MVA SL=2.36 MVA TCL= 0.65 MVA
TCL= 3.98 MVA SL=1.88 MVA BUS DUCT
SL=2.77 MVA SL=0.91 MVA SL=2.73 MVA SL=0.37 MVA
SL=1.78 MVA
SHS1105 SHS0814
TCL=6.43 MVA TCL=6.05 MVA OPEN LOOP
SL=2.83 MVA RD3128 SL=2.68 MVA
SHS2302 RD2922 TCL= 4.81 MVA
RD1307 SHS2404 TCL=6.37 MVA SL=2.11 MVA SHS1305
TCL= 6.16 MVA SHS2314 RD2415
TCL= 4.19 MVA PLOT=RD23_CF05 TCL=6.30 MVA SHS2309 SL=2.79 MVA TCL=5.83 MVA TCL=6.26 MVA
SL=2.73 MVA TCL= 6.30 MVA
SL=1.88 MVA TCL= 1.40 MVA SL=2.77 MVA TCL=5.83 MVA SL=2.79 MVA SL=2.76 MVA
SHS1503 SL=0.79 MVA SL=2.79 MVA SL=2.77 MVA RD2311
TCL=2.13 MVA TCL= 2.81 MVA
SL=0.93 MVA SL=1.26 MVA
RD3129
PLOT=RD31_CR04 SHS3005 TCL= 5.22 MVA
TCL= 0.67 MVA TCL=6.19 MVA SL=2.28 MVA
RD1309 RD1308 PLOT=RD23_CF03 RD2411 PLOT=RD32_CF02 RD1403
SL=0.36 MVA SL=2.74 MVA SHS2315 SHS2405
TCL= 4.30 MVA TCL= 4.30 MVA TCL= 2.00 MVA TCL= 2.14 MVA PLOT=RD31_M02 TCL=5.69 MVA TCL=6.30 MVA TCL= 0.60 MVA TCL= 0.81 MVA
SL=1.88 MVA SL=1.88 MVA SL=1.13 MVA SL=0.94 MVA TCL= 0.65 MVA SL=2.73 MVA SL=2.77 MVA SL=0.34 MVA SL=0.41 MVA
RD1211 SL=0.37 MVA RD1113
TCL= 4.30 MVA SHS1501 SHS1401 TCL= 6.30 MVA
PLOT=RD31_M01
SL=1.90 MVA TCL=6.06 MVA TCL=6.24 MVA
PLOT=RD31_E02 SHS3003 TCL= 0.65 MVA SL=2.77 MVA
SL=2.66 MVA SL=2.74 MVA
TCL= 4.57 MVA TCL=6.27 MVA SL=0.37 MVA
PLOT=RD23_CF06 SL=2.59 MVA SL=2.77 MVA RD3214
PLOT=RD13_CF02 RD2412 SHS2316 SHS2407
TCL= 0.60 MVA TCL= 0.90 MVA TCL= 4.19 MVA SHS2313 TCL=5.83 MVA TCL=6.37 MVA TCL= 4.22 MVA
SL=0.34 MVA SL=0.51 MVA SL=1.88 MVA TCL=5.81 MVA SL=2.79 MVA SL=2.81 MVA SL=1.87 MVA
SL=2.78 MVA
SHS1103 RD3133 SHS0818
TCL=6.33 MVA SHS2304 RD2919 TCL= 2.12 MVA TCL=6.39 MVA
SHS1502 SHS1403
SL=2.78 MVA TCL=5.56 MVA TCL= 0.92 MVA SL=0.93 MVA SL=2.80 MVA
TCL=4.16 MVA TCL=6.30 MVA
SL=2.70 MVA SL=0.47 MVA
SL=1.85 MVA RD2309 SHS2408 SL=2.77 MVA
RD1310 PLOT=RD31_CF02 SHS1303
TCL= 3.89 MVA RD2413 TCL=6.34 MVA
TCL= 6.16 MVA SHS2312 TCL= 0.60 MVA TCL=6.27 MVA
SL=1.71 MVA TCL= 3.08 MVA SL=2.82 MVA
SL=2.71 MVA TCL=5.76 MVA SL=0.34 MVA SL=2.77 MVA
SL=1.35 MVA
SL=2.76 MVA SHS2303
SHS2305 RD2920 TCL=5.56 MVA
TCL=5.69 MVA TCL= 5.67 MVA SL=2.67 MVA
SL=2.73 MVA SL=2.55 MVA
SHS1506 PLOT=RD23_E01
SHS0702 TCL=6.34 MVA SHS2401 RD2414 RD1213
PLOT=RD21_CF02 SHS1629 RD3125 TCL= 4.82 MVA SHS1302 SHS1702
TCL=6.30 MVA SL=2.77 MVA TCL=6.15 MVA SHS2504 TCL= 3.22 MVA TCL= 2.02 MVA
TCL= 1.0 MVA TCL=4.09 MVA SHS2307 TCL= 5.53 MVA SL=2.73 MVA TCL=6.12 MVA TCL=2.77 MVA
SL=2.77 MVA SL=2.73 MVA TCL=6.17 MVA SL=1.41 MVA SL=0.95 MVA
SL=0.57 MVA SL=1.79 MVA TCL=5.81 MVA SL=2.52 MVA SL=2.74 MVA SL=1.25 MVA
SL=2.74 MVA SHS2306
SL=2.78 MVA SHS2310 PLOT=RD29_M02
TCL=5.42 MVA TCL=5.66 MVA
TCL= 0.65 MVA
SL=2.65 MVA SL=2.71 MVA
SL=0.37 MVA

SHS1626
TCL=6.16 MVA
SHS1509
SHS2402
TCL=6.43 MVA SHS2503 SHS2317
PLOT=RD25_CF11
TCL= 0.60 MVA SHS1405 SHS1301
TENDER DOCUMENT
TCL=0.50 MVA SL=2.83 MVA TCL=6.30 MVA SHS3016 TCL=5.83 MVA TCL=6.30 MVA TCL=6.30 MVA
SL=2.73 MVA SL=0.34 MVA
SL=0.50 MVA SL=2.77 MVA TCL=6.02 MVA RD3122 PLOT=RD29_CF05 RD2921 SL=2.79 MVA SL=2.77 MVA SL=2.77 MVA
SL=2.68 MVA TCL= 5.72 MVA TCL= 0.60 MVA TCL= 4.30 MVA
SHS1706 APT SL=2.57 MVA SL=0.34 MVA SL=1.88 MVA SHS1704 APT
TCL=2.32 MVA TCL=2.48 MVA
SL=1.06 MVA RD2409 SL=1.13 MVA
TCL= 4.13 MVA PLOT=RD25_M01
SHS1628 TCL= 0.65 MVA RD3211
TCL=5.66 MVA SL=1.85 MVA SHS2505 SHS2318
SHS3015 TCL=5.88 MVA SL=0.37 MVA TCL= 3.22 MVA
SL=2.47 MVA SHS1601 TCL=6.30 MVA RD3123 SHS3006 SHS3009 SHS1406
TCL=2.01 MVA TCL=6.30 MVA SL=2.82 MVA SL=1.41 MVA 00 15-SEP-19 ISSUED FOR TENDER KAM
SL=2.77 MVA TCL= 4.80 MVA TCL=6.30 MVA TCL=6.41 MVA TCL=6.24 MVA
SHS0703 SL=0.89 MVA SL=2.77 MVA SL=2.77 MVA SL=2.83 MVA SL=2.74 MVA
SL=2.11 MVA PLOT=RD12_CF04 REV. DATE DESCRIPTION APPR'D
TCL=6.11 MVA TCL= 0.60 MVA
SL=2.68 MVA
SHS2406 LOOP FEEDER PSS1-LF16
SL=0.34 MVA Client
TCL=6.41 MVA RD2518
SHS1627 TCL= 4.04 MVA RD3213 RD1511
PLOT=RD20_CR03 SL=2.83 MVA PLOT=RD25_CF07 SHS2319
TCL=2.16 MVA RD2927 RD2925 SL=1.83 MVA TCL= 2.86 MVA TCL= 6.24 MVA
TCL= 1.11 MVA TCL= 1.04 MVA SHS2902 RD3011 SHS2903 SHS2904 SHS3010 SHS3008 SHS3002 SHS3004 TCL=5.67 MVA
SL=0.95 MVA TCL= 2.14 MVA TCL= 6.30 MVA SL=1.35 MVA SL=2.77 MVA
SL=0.60 MVA SHS1602 SL=0.59 MVA TCL=6.16 MVA TCL= 4.14 MVA TCL=6.30 MVA TCL=6.16 MVA TCL=6.25 MVA TCL=6.27 MVA TCL=6.24 MVA TCL=6.18 MVA SL=2.73 MVA
SL=0.94 MVA SL=2.77 MVA SHS1407
TCL=6.34 MVA SL=2.71 MVA SL=1.83 MVA SL=2.77 MVA SL=2.71 MVA SL=2.77 MVA SL=2.77 MVA SL=2.74 MVA SL=2.75 MVA TCL=4.23 MVA
SL=2.79 MVA SL=1.87 MVA
RD2514 LOOP FEEDER PSS1-LF15
TCL= 6.30 MVA
PLOT=RD20_CR04
TCL= 1.43 MVA
SL=2.77 MVA PLOT=RD25_CF01 SHS3013 SHS3014 RD2924 SHS3011 SHS3012 PLOT=RD29_CF04 PLOT=RD29_M01 RD2929 RD2926
SHS2506
TCL=6.03 MVA
SHS1306
TCL=5.91 MVA
RD1510 PMC
TCL= 0.96 MVA TCL=6.30 MVA TCL=6.30 MVA TCL=6.30 MVA TCL=6.12 MVA TCL= 3.13 MVA
SL=0.76 MVA TCL= 3.08 MVA TCL= 0.60 MVA TCL= 0.65 MVA TCL= 3.22 MVA TCL= 6.26 MVA SL=2.65 MVA SL=2.64 MVA
SL=0.55 MVA SL=2.77 MVA SL=2.77 MVA SL=2.77 MVA SL=2.74 MVA SL=1.38 MVA
SL=1.35 MVA SL=0.34 MVA SL=0.37 MVA SL=1.41 MVA SL=2.78 MVA
SHS1604 RD2516
PLOT=RD20_CR02
TCL=6.30 MVA TCL= 6.30 MVA
TCL= 0.75 MVA LOOP FEEDER PSS1-LF14
SL=2.76 MVA PLOT=RD25_CF09 SL=2.77 MVA
SL=0.40 MVA
SHS0705 TCL= 1.30 MVA PLOT=RD32_P30
SHS1621 SHS2908 SHS2912 PLOT=RD30_E03 SHS2907 SHS2905 PLOT=RD30_CF03 PLOT=RD30_M01 PLOT=RD30_E04 SHS2507 SHS0706
TCL=6.30 MVA TCL=6.02 MVA SL=0.74 MVA RD2917 RD2918 PLOT=RD30_CF02 RD1614
TCL=6.23 MVA TCL=2.14 MVA TCL=6.32 MVA TCL=6.27 MVA TCL=4.16 MVA TCL= 1.64 MVA TCL=6.27 MVA
SL=2.77 MVA TCL= 4.19 MVA TCL= 2.14 MVA TCL= 8.88 MVA TCL= 0.60 MVA TCL= 0.65 MVA TCL= 2.62 MVA TCL= 1.30 MVA TCL= 1.74 MVA
SL=2.72 MVA SL=2.73 MVA SL=0.94 MVA SL=2.77 MVA SL=2.77 MVA SL=0.93 MVA SL=2.77 MVA
SL=1.88 MVA SL=0.94 MVA SL=5.03 MVA SL=0.34 MVA SL=0.37 MVA SL=1.49 MVA SL=0.74 MVA SL=1.83 MVA
SL=0.80 MVA Consultant
LOOP FEEDER PSS1-LF13

SHS1624 RD1819 SHS2501 SHS2502 PLOT=RD25_M02 SHS2514 SHS2509 PLOT=RD25_E02 RD2515 SHS2508 RD2519 RD2513 SHS1307
SHS1707 APT TCL=6.30 MVA TCL=6.30 MVA TCL=6.16 MVA TCL=6.16 MVA TCL=6.30 MVA RD1617
TCL=2.13 MVA TCL= 3.08 MVA TCL= 0.65 MVA TCL= 2.45 MVA TCL= 3.08 MVA TCL= 3.08 MVA TCL= 3.08 MVA TCL=6.30 MVA
TCL=2.53 MVA SL=2.77 MVA SL=2.77 MVA SL=2.71 MVA SL=2.71 MVA TCL= 2.99 MVA
SL=0.93 MVA SL=1.35 MVA SL=0.37 MVA SL=1.39 MVA SL=1.35 MVA SL=2.77 MVA SL=1.35 MVA SL=1.35 MVA SL=2.77 MVA
SL=1.15 MVA SL=1.31 MVA
Project / Contract
LOOP FEEDER PSS1-LF12

SHS1606 SHS1605 SHS1607 PLOT=RD18_E02 PLOT=RD25_CF08 PLOT=RD25_CF05 PLOT=RD25_CF03 RD2512


RIYADH CITY NORTH
ALL PHASES
TCL=4.29 MVA TCL=6.30 MVA TCL=7.63 MVA TCL= 9.41 MVA TCL= 1.40 MVA TCL= 2.00 MVA TCL= 1.60 MVA TCL= 3.71 MVA
SL=1.89 MVA SL=2.80 MVA SL=1.77 MVA SL=5.34 MVA SL=0.79 MVA SL=1.13 MVA SL=0.91 MVA SL=1.65 MVA

LOOP FEEDER PSS1-LF11


SHS1611 PLOT=RD16_CF02
TCL=5.69 MVA TCL= 0.60 MVA Drawing Title
SL=2.48 MVA SL=0.34 MVA
SHS1625
TCL=4.10 MVA
SL=1.83 MVA
SHS1623
TCL=0.95 MVA
SL=0.43 MVA
SHS1620
TCL=4.87 MVA
SL=2.19 MVA
PLOT=RD21_CR04
TCL= 0.75 MVA
PLOT=RD21_CR05
TCL= 0.82 MVA
PLOT=RD21_CR06
TCL= 0.66 MVA
PLOT=RD21_CR07
TCL= 0.67 MVA
PLOT=RD21_CR08
TCL= 0.67 MVA
PLOT=RD21_CF03
TCL= 1.04 MVA
SHS1619
TCL=2.53 MVA
RD2308
TCL= 4.24 MVA
RD3216
TCL= 5.92 MVA
SHS1309
TCL=2.16 MVA TEMPORARY FEEDING
SL=0.40 MVA SL=0.44 MVA SL=0.36 MVA SL=0.36 MVA SL=0.36 MVA SL=0.59 MVA SL=1.21 MVA SL=1.85 MVA SL=2.65 MVA SL=0.94 MVA

LOOP FEEDER PSS1-LF10


ARRANGEMENTS FOR ALL PLOTS WITH
PSS-1 TRANSCO SUBSTATION - SHEET 2/2
SHS0707 RD1212 PLOT=RD12_M01 SHS0708 RD1214
TCL=6.19 MVA TCL= 3.22 MVA TCL= 0.65 MVA TCL=6.23 MVA TCL= 4.30 MVA
SL=2.77 MVA SL=1.41 MVA SL=0.37 MVA SL=2.74 MVA SL=1.88 MVA CONTRACT No: JOB No:
LOOP FEEDER PSS1-LF9
DRAWN DESIGNED CHECKED APPROVED
RD1830 PLOT=RD18_M02 RD1723 RD1616 RD1620
SHS1603 SHS1713 RD2517 RD1909 RD1910 PLOT=RD19_M01
RD1621
TCL= 2.67 MVA TCL= 1.87 MVA
ST SD MSA KAM
TCL=5.60 MVA TCL=2.69 MVA TCL= 5.22 MVA TCL= 0.65 MVA TCL= 4.33 MVA TCL= 2.14 MVA
TCL= 6.17 MVA TCL= 6.19 MVA TCL= 4.27 MVA TCL= 0.65 MVA SL=2.30 MVA SL=1.89 MVA SL=1.20 MVA SL=0.82 MVA
SL=0.37 MVA
SL=1.80 MVA SL=1.19 MVA SL=2.75 MVA SL=2.65 MVA SL=1.89 MVA SL=0.37 MVA
SL=0.94 MVA
DATE 15-SEP-2019 ACTUAL SIZE A1
Drawing Scale. N.T.S

Drawing No.
ISSUED FOR CONSTRUCTION_Rev-00 RN-02-00001-00-07-EL-PIL-DG-000302 00
\\Xeuae03fs01\uaeauh_trp\PROJECTS\351159 Riyadh North\04 Users\CADD\Issued for Construction Drawings_(Dec 2021)\00-ALL PHASE\ELECTRICAL\CAD\ELECTRICAL MV SCHEMATIC DIAGRAM\RN-02-00001-00-07-EL-PIL-DG-000301-06_DELETED FOR AD-1.dwg
Last Saved By: P002959B Last Saved Date: 12/19/2021 5:57 PM Printed Date: 12/19/2021 9:02 PM Printed By: Chirayath, Subeesh [NN-AE]
LEGEND :
FROM 132/22kV, 60MVA FROM 132/22kV, 60MVA 22kV CABLES - (PSS-1)
TRANSFORMER-1 TRANSFORMER-2 SS 1 - 23
EXISTING PRIMARY SUBSTATION - 1
SECTOR NUMBER
2500A 2500A
BUS SECTION-1 BUS SECTION-2
SUBSTATION NUMBER
22kV, 2500A, 31.5kA, 1s 22kV, 2500A, 31.5kA, 1s 22/0.415 kV SUB STATION
SS1- LF 17
LOOP NUMBER
630A 630A 630A 630A 630A 630A 630A 630A 630A 1250A 1250A 1250A 1250A 1250A 1250A 630A 630A 630A 630A 630A 630A 630A 630A LOOP FEEDER
PRIMARY SUBSTATION NO.1

2500A 2500A
EXISTING SUBSTATION

PROPOSED SUBSTATION

PROPOSED BUILDING SUBSTATION


LP01A LP02A LP03A LP04A LP05A LP06A LP07A LP08A LP17A LP18A LP18A LP17B LP08B LP07B LP06B LP05B LP04B LP03B LP02B LP01B

1500KVA TRANSFORMER

TX.01
LOOP-1: LOOP-2: LOOP-3: LOOP-4: LOOP-5: LOOP-6: LOOP-7: LOOP-8: LOOP-17: LOOP-18: 12 MVAR 12 MVAR 1000KVA TRANSFORMER
TCL=72.40 MVA TCL=72.40 MVA TCL=69.73 MVA TCL=71.44 MVA TCL=68.83 MVA TCL=69.21 MVA TCL=69.23 MVA TCL=69.15 MVA TCL=70.62 MVA TCL=71.70 MVA
1000kVA CAPACITOR CAPACITOR
SL=33.11 MVA SL=32.60 MVA SL=30.92 MVA SL=31.76 MVA SL=31.48 MVA SL=30.38 MVA SL=31.10 MVA SL=32.00 MVA SL=32.08 MVA SL=31.69 MVA
BANK-1 BANK-2
22/0.415kV FLL=12.97 MVA FLL=13.03 MVA FLL=12.55 MVA FLL=12.86 MVA FLL=12.39 MVA FLL=12.46 MVA FLL=13.10 MVA FLL=12.71 MVA FLL=12.91 MVA
FLL=12.26 MVA
500KVA TRANSFORMER

RD1118 SHS0108 RD0815 SHS1616 SHS0308 SHS0802 SS16-6 RD1116 SHS1902 SHS0105 PLOT = RD8_M01 PLOT = RD20_E01 SHS0604 SHS0610 SHS0817 RD1209 PLOT = RD22_M01 RD1210 SHS0403 PLOT = RD14_M01
TCL=4.14 MVA TCL=6.30 MVA TCL=4.30 MVA TCL=5.01 MVA TCL=4.50 MVA TCL=6.32 MVA TCL=0.81 MVA TCL=2.00 MVA TCL=4.19 MVA TCL=6.24 MVA TCL= 0.65 MVA TCL= 5.05 MVA TCL=6.27 MVA TCL=6.30 MVA TCL=4.09 MVA TCL=4.14 MVA TCL= 0.65 MVA TCL=5.01 MVA TCL=6.16 MVA TCL= 0.65 MVA
630A CIRCUIT BREAKER
SL=1.83 MVA SL=2.79 MVA SL=1.88 MVA SL=2.49 MVA SL=1.99 MVA SL=2.77 MVA SL=0.81 MVA SL=0.88 MVA SL=1.88 MVA SL=2.74 MVA SL=0.37 MVA SL=2.86 MVA SL=2.77 MVA SL=2.77 MVA SL=1.79 MVA SL=1.83 MVA SL= 0.37 MVA SL=2.23 MVA SL=2.71 MVA SL= 0.37 MVA (WITH DRAWABLE TYPE)

EARTHING SWITCH

STATION TRANSFORMER
RD1829
SHS0104 TCL=4.02 MVA CAPACITOR BANK
SHS0606 SHS0106 RD1115
TCL=6.30 MVA TCL=6.39 MVA SL=1.80 MVA
TCL=6.30 MVA SL=2.81 MVA TCL=5.44 MVA
SL=2.77 MVA
SL=2.77 MVA
SL=2.36 MVA BUS DUCT
RD1119 RD1615
TCL=2.14 MVA SHS1904 TCL=2.68 MVA
SHS0311 SHS0310 SL=1.18 MVA
SL=0.94 MVA TCL=4.84 MVA TCL=4.30 MVA
TCL=4.84 MVA
SL=2.12 MVA SL=1.88 MVA
SHS0201 SHS0607 SL=2.12 MVA
RD1401 RD1618 SHS0907
TCL=6.60 MVA TCL=6.30 MVA TCL=2.81 MVA
TCL=5.65 MVA TCL=6.18 MVA
SL=2.84 MVA SL=2.77 MVA SL=1.18 MVA
SL=2.56 MVA SHS1907 SL=2.71 MVA
SHS1615 TCL=6.43 MVA SHS1710
TCL=4.61 MVA SL=2.83 MVA TCL=5.99 MVA
RD0816 SHS0107 RD0814
SL=2.01 MVA TCL=4.30 MVA SL=2.62 MVA
TCL=2.14 MVA PLOT = RD11_M02 TCL=6.30 MVA SHS0601
SHS0109 SL=0.94 MVA TCL= 0.65 MVA SL=2.77 MVA SL=1.88 MVA TCL=6.30 MVA SHS0404
TCL=6.24 MVA SL=0.37 MVA SL=2.77 MVA TCL=6.30 MVA
SL=2.74 MVA RD1831 SL=2.77 MVA
TCL=3.64 MVA
SL=1.64 MVA

RD1121 RD1818
TCL=1.84 MVA SHS1911 TCL=4.84 MVA
SL=0.85 MVA TCL=4.17 MVA SL=2.12 MVA
SHS0312 PLOT = RD9_CR01
SL=1.86 MVA
TCL=4.16 MVA TCL=2.00 MVA
SL=1.83 MVA SL=1.26 MVA
SHS0110 RD0813
SHS0202 SHS0609
TCL=6.24 MVA TCL=4.24 MVA
TCL=5.55 MVA TCL=6.30 MVA
PLOT = RD11_CF09 SL=2.74 MVA SL=1.85 MVA SHS0602
SL=2.45 MVA PLOT = RD18_CF03 SL=2.77 MVA
SHS0804 TCL= 0.60 MVA TCL=6.30 MVA SHS0815 SHS0906
TCL= 0.60 MVA SL=2.77 MVA
TCL=6.32 MVA SL=0.34 MVA TCL=3.86 MVA TCL=6.32 MVA
SL=0.34 MVA
SL=2.77 MVA SL=1.68 MVA SL=2.77 MVA

SHS1910
TCL=4.30 MVA
SHS1614 SL=1.88 MVA SHS1701
TCL=5.94 MVA TCL=2.00 MVA
RD1120 SL=2.59 MVA SL=0.88 MVA PLOT = RD18_E03
TCL=2.92 MVA TCL= 4.26 MVA
RD0817 SHS0111 SHS0103
SL=1.30 MVA SL= 2.42 MVA
TCL=4.30 MVA SHS1905 TCL=6.30 MVA TCL=6.41 MVA
SL=1.88 MVA SHS0801 TCL=6.30 MVA SL=2.80 MVA SL=2.83 MVA PLOT = RD9_CF02
SHS0605 RD1117
TCL=6.05 MVA TCL=5.97 MVA SL=2.77 MVA TCL= 0.58 MVA
TCL=3.22 MVA
PLOT = RD8_E01 SL=2.65 MVA SL=2.66 MVA SL=1.41 MVA SL=0.33 MVA RD1720
TCL= 4.24 MVA TCL=4.33 MVA
PLOT = RD10_M02 SHS0204
SL=2.40 MVA RD1826 SL=1.89 MVA
TCL= 0.65 MVA TCL=6.40 MVA
SL=0.37 MVA LOOP FEEDER PSS1-LF18 TCL=2.14 MVA
SL=0.94 MVA
SL=2.80 MVA
TENDER DOCUMENT
RD0812 PLOT = RD8_M02 SHS0102
SHS0101
SHS0808 TCL=5.03 MVA TCL= 0.65 MVA TCL=6.36 MVA RD1509
TCL=6.30 MVA SHS0816
TCL=2.55 MVA SL=2.21 MVA SL=0.37 MVA SL=2.80 MVA TCL=1.97 MVA
SL=2.77 MVA TCL=3.83 MVA
SL=1.11 MVA SHS1906 SL=1.67 MVA SL=0.91 MVA
TCL=6.30 MVA
SL=2.77 MVA LOOP FEEDER PSS1-LF17
RD1111 RD1724
TCL=5.75 MVA SHS0608 SHS0603 TCL=4.14 MVA
TCL=6.30 MVA RD1828 SHS1908 PLOT = RD18_M07 SHS1909 PLOT = RD18_M03 TCL=6.43 MVA SL=1.83 MVA
SL=2.57 MVA
SL=2.77 MVA TCL=5.24 MVA TCL=6.36 MVA TCL= 0.65 MVA TCL=6.30 MVA TCL= 0.65 MVA SL=2.83 MVA
SL=2.30 MVA SL=2.82 MVA SL=0.37 MVA SL=2.77 MVA SL=0.37 MVA 00 15-SEP-19 ISSUED FOR TENDER KAM
SHS1617 SHS0805 PLOT = RD17_CF04 REV. DATE DESCRIPTION APPR'D
TCL= 0.60 MVA SHS1705
TCL=3.92 MVA TCL=3.72 MVA
TCL=3.87 MVA
SL=1.73 MVA SL=1.62 MVA SL= 0.34 MVA
SL=1.73 MVA Client
RD1008 LOOP FEEDER PSS1-LF8 PLOT = RD10_CF02
TCL=5.54 MVA TCL= 0.60 MVA
RD0708 SL=2.47 MVA SL=0.34 MVA
TCL=4.21 MVA PLOT = RD11_E02 PLOT = RD11_CF07 PLOT = RD12_CF01 PLOT = RD12_CF03 RD1112 PLOT = RD11_CF06 PLOT = RD28_CF02
SL=1.86 MVA TCL= 4.66 MVA TCL= 1.30 MVA TCL= 0.88 MVA TCL= 1.04 MVA TCL=2.50 MVA TCL= 1.40 MVA TCL= 1.60 MVA
SL=2.64 MVA SL=0.74 MVA SL=0.50 MVA SL=0.59 MVA SL=1.15MVA SL=0.79 MVA SL= 0.91 MVA

SHS0810 SHS0813 PLOT = RD15_M01


PLOT = RD11_CF08 RD0712 RD1722
TCL= 0.90 MVA
SHS0401
TCL=6.30 MVA TCL=3.62 MVA TCL=3.21 MVA TCL= 0.65 MVA
TCL=5.04 MVA TCL=2.14 MVA
PMC
SL=1.58 MVA LOOP FEEDER PSS1-LF7 SL=1.40 MVA SL=0.37 MVA
SL=0.51 MVA SL=2.77 MVA SL=2.23 MVA SL=0.94 MVA

SHS0203 RD1007 SHS0205 SHS0206


TCL=5.59 MVA TCL=6.12 MVA TCL=6.46 MVA TCL=6.02 MVA
SHS0806 PLOT = RD17_M02
SL=2.44 MVA SL=2.78 MVA SL=2.83 MVA SL=2.68 MVA
TCL=3.71 MVA TCL= 0.65 MVA
SL=1.62 MVA LOOP FEEDER PSS1-LF6 SL= 0.37 MVA

SHS0809 SHS0807 RD1402 PLOT = RD14_M02 SHS0811 SHS0812 Consultant


TCL=3.39 MVA TCL=6.32 MVA TCL=6.39 MVA TCL= 0.65 MVA TCL=6.32 MVA TCL=3.86 MVA
SHS1612 SL=1.48 MVA SL=2.77 MVA SL=0.37 MVA SL=2.77 MVA SL=1.68 MVA SHS1714
SL=2.80 MVA
TCL=2.69 MVA TCL=4.27 MVA
SL=1.18 MVA SL=1.87 MVA
LOOP FEEDER PSS1-LF5
PLOT = RD11_CF04 RD1721
TCL= 2.00 MVA SHS1010 RD1736 TCL=5.29 MVA
SHS0803 RD1508 PLOT = RD15_CF09 PLOT = RD15_CF08 PLOT = RD15_CF05 SHS1014
SL=1.13 MVA
TCL=2.98 MVA TCL=4.47 MVA TCL= 1.30 MVA TCL= 1.40 MVA TCL= 2.00 MVA TCL=6.20 MVA TCL=4.27 MVA TCL=6.43 MVA
SL=2.35 MVA Project / Contract
SHS0901 SL=1.30 MVA SL=1.98 MVA SL=0.74 MVA SL=0.79 MVA SL=1.13 MVA SL=2.74 MVA SL=1.89 MVA SL=2.83 MVA SHS0905
TCL=6.31 MVA TCL=6.11 MVA
SL=2.76 MVA LOOP FEEDER PSS1-LF4
SL=2.69 MVA
RIYADH CITY NORTH
SHS1711
TCL=3.14 MVA
SHS1802
TCL=6.38 MVA
SHS1804
TCL=6.32 MVA
SHS1901
TCL=6.19 MVA
SHS1903
TCL=6.16 MVA
SHS1712
TCL=4.30 MVA
ALL PHASES
SL=1.37 MVA SL=2.83 MVA SL=2.77 MVA SL=2.74 MVA SL=2.71 MVA SL=1.88 MVA
SHS0406
RD707
TCL=3.01 MVA TCL=6.27 MVA Drawing Title
LOOP FEEDER PSS1-LF3 SL=2.77 MVA
SL=1.34 MVA
ULTIMATE POWER SUPPLY
RD1512 PLOT = RD15_M02 PLOT = RD15_CF11
PLOT = RD11_M01
TCL=2.04 MVA
SL=0.91 MVA
TCL= 0.65 MVA
SL=0.37 MVA
SHS0902
TCL=6.32 MVA
SL=2.77 MVA
SHS0903
TCL=6.31 MVA
SL=2.76 MVA
TCL= 0.60 MVA
SL=0.34 MVA
SHS0904
TCL=6.32 MVA
SL=2.77 MVA RD0711
22kV SINGLE LINE DIAGRAM
TCL= 0.65 MVA
SL=0.37 MVA
LOOP FEEDER PSS1-LF2
TCL=3.06 MVA
SL=1.30 MVA PRIMARY SUBSTATION PSS-1, SHEET 1/2
RD710 SHS0405
SHS0402 RD709 PLOT = RD7_CF02 TCL=2.64 MVA TCL=6.41 MVA CONTRACT No: JOB No:
TCL=6.43 MVA TCL=2.14 MVA TCL= 0.60 MVA SL=1.25 MVA SL=2.83 MVA
SL=2.83 MVA SL=0.94 MVA SL=0.34 MVA
DRAWN DESIGNED CHECKED APPROVED
LOOP FEEDER PSS1-LF1 ST SD MSA KAM
SHS0306
TCL=2.96 MVA
SL=1.30 MVA
SHS0305
TCL=2.84 MVA
SL=1.25 MVA
SHS0301
TCL=4.14 MVA
SHS0302
TCL=3.61 MVA
SL=1.59 MVA
PLOT = RD9_CF01
TCL= 1.00 MVA
SHS0309
TCL=2.71 MVA
SL=1.19 MVA
SHS0303
TCL=3.46 MVA
SL=1.54 MVA
SHS0307
TCL=4.32 MVA
SL=1.82 MVA
DATE 15-SEP-2019 ACTUAL SIZE A1
SL= 0.57 MVA
SL=1.86 MVA Drawing Scale. N.T.S
REFER SHEET REFER SHEET
NO.RN-02-00001-00-07-EL-PIL-DG-000304 NO.RN-02-00001-00-07-EL-PIL-DG-000304
Drawing No.
RN-02-00001-00-07-EL-PIL-DG-000303 00
ISSUED FOR CONSTRUCTION_Rev-00
\\Xeuae03fs01\uaeauh_trp\PROJECTS\351159 Riyadh North\04 Users\CADD\Issued for Construction Drawings_(Dec 2021)\00-ALL PHASE\ELECTRICAL\CAD\ELECTRICAL MV SCHEMATIC DIAGRAM\RN-02-00001-00-07-EL-PIL-DG-000301-06_DELETED FOR AD-1.dwg
Last Saved By: P002959B Last Saved Date: 12/19/2021 5:57 PM Printed Date: 12/19/2021 9:03 PM Printed By: Chirayath, Subeesh [NN-AE]
LEGEND :

REFER SHEET REFER SHEET 22kV CABLES - (PSS-1)


NO.RN-02-00001-00-07-EL-PIL-DG-000303 NO.RN-02-00001-00-07-EL-PIL-DG-000303 SS 1 - 23
FROM 132/22kV, 60MVA FROM 132/22kV, 60MVA SECTOR NUMBER
TRANSFORMER-4 TRANSFORMER-3
EXISTING PRIMARY SUBSTATION - 1 SUBSTATION NUMBER
2500A 2500A
22/0.415 kV SUB STATION
BUS SECTION-4 BUS SECTION-3 SS1- LF 17
22kV, 2500A, 31.5kA, 1s 22kV, 2500A, 31.5kA, 1s
LOOP NUMBER
LOOP FEEDER
PRIMARY SUBSTATION NO.1
630A 630A 630A 630A 630A 630A 630A 630A 630A 1250A 1250A 1250A 1250A 1250A 1250A 630A 630A 630A 630A 630A 630A 630A 630A

EXISTING SUBSTATION

2500A 2500A
PROPOSED SUBSTATION

PROPOSED BUILDING SUBSTATION

1500KVA TRANSFORMER
LP09A LP10A LP11A LP12A LP13A LP14A LP15A LP16A LP16B LP15B LP14B LP13B LP12B LP11B LP10B LP09B
1000KVA TRANSFORMER
TX.02
1000kVA LOOP-9: LOOP-10: LOOP-11: LOOP-12: LOOP-13: LOOP-14: LOOP-15: LOOP-16:
12 MVAR 12 MVAR
500KVA TRANSFORMER
TCL=69.92 MVA TCL=63.96 MVA TCL=70.46 MVA TCL=72.14 MVA TCL=69.64 MVA TCL=71.86 MVA TCL=67.33 MVA TCL=70.15 MVA
22/0.415kV SL=30.63 MVA SL=28.44 MVA SL=31.53 MVA SL=32.41 MVA SL=31.63 MVA SL=33.89 MVA SL=31.58 MVA SL=32.30 MVA CAPACITOR CAPACITOR
FLL=12.59 MVA FLL=11.51 MVA FLL=12.68 MVA FLL=12.99 MVA FLL=12.53 MVA FLL=12.93 MVA FLL=12.12 MVA FLL=12.63 MVA BANK-4 BANK-3
630A CIRCUIT BREAKER
SPARE PSS1-LF20 (WITH DRAWABLE TYPE)

SHS1106
TCL=6.30 MVA
RD1311
TCL= 1.06 MVA
RD2308 SHS1304
TCL=6.30 MVA
RD2310 PLOT=RD23_CR02 RD3130 RD3212
SPARE PSS1-LF19 SHS2904 SHS2301 RD3120 RD2410 SHS1404 RD3217 RD1114 SHS1101
TCL=6.36MVA
EARTHING SWITCH
TCL= 4.24 MVA TCL= 1.49 MVA TCL= 2.12 MVA TCL= 2.07 MVA TCL= 4.30 MVA TCL=6.16 MVA TCL=5.43 MVA TCL= 4.94 MVA TCL= 6.07 MVA TCL=6.29 MVA TCL= 4.14 MVA TCL= 4.13 MVA
SL=2.79 MVA SL=0.47 MVA SL=1.85 MVA SL=2.77 MVA SL=0.71 MVA SL=1.14 MVA SL=0.91 MVA SL=1.88 MVA SL=2.71 MVA SL=2.62 MVA SL=2.69 MVA SL=2.77 MVA SL=1.84 MVA SL=1.85 MVA SL=2.82 MVA
SL=2.17 MVA
STATION TRANSFORMER

CAPACITOR BANK

BUS DUCT

RD3210 SHS2903
TCL= 4.30 MVA TCL=6.30 MVA
PLOT=RD23_CF01 RD3126 SL=1.88 MVA SL=2.77 MVA RD3128 PLOT=RD24_M01
TCL= 1.60 MVA TCL= 6.28 MVA TCL= 4.81 MVA TCL= 0.65 MVA
SL=0.91 MVA SHS2403 SL=2.76 MVA SL=2.11 MVA RD3121 SL=0.37 MVA
RD3216 TCL=6.25 MVA TCL= 5.35 MVA RD3215
TCL= 5.92 MVA SL=2.77 MVA SL=2.36 MVA TCL= 4.30 MVA
SHS1105 SL=2.65 MVA SHS1402 RD2312 SHS0814
SL=1.88 MVA
TCL=6.43 MVA TCL=6.30 MVA TCL= 3.98 MVA TCL=6.05MVA
SL=2.83 MVA SL=2.77 MVA SL=1.78 MVA SL=2.68 MVA

RD1211 RD1113
TCL= 4.30 MVA TCL= 6.30 MVA
SL=1.90 MVA SL=2.77 MVA
SHS2302 RD3011
TCL=6.37 MVA TCL= 4.14 MVA
SL=2.79 MVA SL=1.83 MVA

PLOT=RD23_CF05 SHS2311 RD3129 RD2415


TCL= 1.40 MVA TCL=5.69 MVA TCL= 5.22 MVA TCL= 6.30 MVA
SL=0.79 MVA SL=2.73 MVA SL=2.28 MVA SL=2.77 MVA

SHS2404 SHS2314
TCL=6.30 MVA TCL=5.83 MVA
SL=2.77 MVA SL=2.79 MVA

RD1309 RD1403
TCL= 4.30 MVA SHS1503 RD2311 TCL= 0.81 MVA
PLOT=RD31_CR04 SHS2902
SL=1.88 MVA TCL=2.13 MVA TCL=6.16 MVA TCL= 2.81 MVA SL=0.41 MVA
SL=0.93 MVA TCL= 0.67 MVA SL=1.26 MVA
SHS0702 SL=0.36 MVA SL=2.71 MVA RD1213
TCL=6.30 MVA SHS1309 TCL= 2.02 MVA
SHS1305
SL=2.77 MVA TCL=2.16 MVA TCL=6.26 MVA SL=0.95 MVA
SL=0.94 MVA PLOT=RD23_CF03 PLOT=RD31_M01 SL=2.76 MVA
SHS2309 SHS2405
TCL= 2.00 MVA TCL=5.83 MVA TCL= 0.65 MVA TCL=6.30 MVA
SL=1.13 MVA SL=2.79 MVA SL=0.37 MVA SL=2.77 MVA

TENDER DOCUMENT
RD2411 SHS2315
TCL= 2.14 MVA TCL=5.69 MVA
SL=0.94 MVA PLOT=RD31_E02 RD3123 SL=2.73 MVA
TCL= 4.57 MVA TCL= 4.80 MVA
SL=2.59 MVA SL=2.11 MVA

SHS1103 SHS0818
TCL=6.33 MVA TCL=6.39MVA 00 15-SEP-19 ISSUED FOR TENDER KAM
SL=2.78 MVA SHS1501 SHS1401 SL=2.80 MVA
SHS0703 PLOT=RD12_CF04
TCL=6.11 MVA
TCL=6.06 MVA PLOT=RD23_CF06 PLOT=RD31_M02 RD3133 SHS2407 TCL=6.24 MVA REV. DATE DESCRIPTION APPR'D
SL=2.66 MVA TCL= 0.90 MVA TCL=6.37 MVA TCL= 0.60 MVA
SL=2.68 MVA TCL= 0.65 MVA TCL= 2.12 MVA SL=2.74 MVA
SL=0.51 MVA SL=0.37 MVA LOOP FEEDER PSS1-LF16 SL=0.93 MVA SL=2.81 MVA SL=0.34 MVA Client
SHS2304 SHS2305 SHS2310 RD3122
SHS1307 TCL=5.42 MVA PLOT=RD32_CF02
TCL=5.56 MVA TCL=5.69 MVA TCL= 5.72 MVA
TCL=6.30 MVA SL=2.65 MVA TCL= 0.60 MVA
SL=2.70 MVA SL=2.73 MVA SL=2.57 MVA
SL=2.77 MVA SL=0.34 MVA

PLOT=RD30_E04 SHS2316
LOOP FEEDER PSS1-LF15
TCL= 2.62 MVA TCL=5.83 MVA
SL=1.49 MVA
SHS2313 SHS2312 SHS2307 SHS2306 SHS2303 SL=2.79 MVA PMC
TCL=5.81 MVA TCL=5.76 MVA TCL=5.81 MVA TCL=5.66 MVA TCL=5.56 MVA
SL=2.78 MVA SL=2.76 MVA SL=2.78 MVA SL=2.71 MVA SL=2.67 MVA

RD2309 SHS2408
TCL= 3.89 MVA LOOP FEEDER PSS1-LF14
TCL=6.34 MVA
PLOT=RD21_CF02 SL=1.71 MVA SL=2.82 MVA SHS1702
TCL= 1.0 MVA SHS0705 SHS2319 SHS2318 SHS2317 RD3125 PLOT=RD31_CF02 SHS0706 TCL=2.77MVA
TCL=6.30 MVA PLOT=RD30_CF02 TCL=5.67 MVA TCL=5.88 MVA TCL=5.83 MVA TCL= 5.53 MVA TCL= 0.60 MVA
SL=0.57 MVA TCL=6.27 MVA SL=1.25 MVA
SL=2.77 MVA SHS1502 TCL= 1.30 MVA SL=2.73 MVA SL=2.82 MVA SL=2.79 MVA SL=2.52 MVA SL=0.34 MVA SHS1403 SL=2.77 MVA
TCL=4.16 MVA SL=0.74 MVA TCL=6.30 MVA Consultant
SL=1.85 MVA SL=2.77 MVA
LOOP FEEDER PSS1-LF13

SHS2401 SHS2402 RD2409 SHS2406 RD2414


TCL=6.15 MVA TCL=6.43 MVA TCL= 4.13 MVA TCL=6.41 MVA TCL= 3.22 MVA
PLOT=RD32_P30 SL=2.73 MVA SL=2.83 MVA SL=1.85 MVA SL=2.83 MVA SL=1.41 MVA RD3214
TCL= 1.64 MVA TCL= 4.22 MVA
SL=0.93 MVA SL=1.87 MVA Project / Contract
LOOP FEEDER PSS1-LF12

SHS1407
TCL=4.23 MVA
SHS1406
TCL=6.24 MVA
SHS1405 PLOT=RD23_E01 RIYADH CITY NORTH
ALL PHASES
SL=1.87 MVA TCL=6.30 MVA TCL= 4.82 MVA
SL=2.74 MVA SL=2.77 MVA SL=2.73 MVA

LOOP FEEDER PSS1-LF11


SHS1706 APT SHS1704 APT
TCL=2.32 MVA TCL=2.48MVA Drawing Title
SHS1306 SHS1301 SHS1302
SL=1.06 MVA RD3213 RD3211 SHS1303 SL=1.13 MVA
TCL=5.91 MVA
SL=2.64 MVA TCL= 2.86 MVA
SL=1.35 MVA
TCL= 3.22 MVA
SL=1.41 MVA
TCL=6.30 MVA
SL=2.77 MVA
TCL=6.12 MVA
SL=2.74 MVA
TCL=6.27 MVA
SL=2.77 MVA
ULTIMATE POWER SUPPLY
LOOP FEEDER PSS1-LF10
22kV SINGLE LINE DIAGRAM
PLOT=RD12_M01
PRIMARY SUBSTATION PSS-1, SHEET 2/2
SHS0707 RD1212 SHS0708 RD1214
TCL=6.19 MVA TCL= 3.22 MVA TCL= 0.65 MVA TCL=6.23 MVA TCL= 4.30 MVA
SL=2.77 MVA SL=1.41 MVA SL=0.37 MVA SL=2.74 MVA SL=1.88 MVA
CONTRACT No: JOB No:
LOOP FEEDER PSS1-LF9 DRAWN DESIGNED CHECKED APPROVED
PLOT=RD20_CR03 PLOT=RD20_CR02 SHS1707 APT SHS1611
TCL= 1.11 MVA TCL= 0.75 MVA TCL=2.53 MVA TCL=5.69 MVA
SHS1603 SHS1713 ST SD MSA KAM
TCL=5.60 MVA TCL=2.69 MVA
SL=0.60 MVA SL=0.40 MVA SL=1.15 MVA SL=2.48 MVA SL=1.80 MVA SL=1.19 MVA
DATE 15-SEP-2019 ACTUAL SIZE A1
Drawing Scale. N.T.S

Drawing No.
ISSUED FOR CONSTRUCTION_Rev-00 RN-02-00001-00-07-EL-PIL-DG-000304 00
\\Xeuae03fs01\uaeauh_trp\PROJECTS\351159 Riyadh North\04 Users\CADD\Issued for Construction Drawings_(Dec 2021)\00-ALL PHASE\ELECTRICAL\CAD\ELECTRICAL MV SCHEMATIC DIAGRAM\RN-02-00001-00-07-EL-PIL-DG-000301-06_DELETED FOR AD-1.dwg
Last Saved By: P002959B Last Saved Date: 12/19/2021 5:57 PM Printed Date: 12/19/2021 9:03 PM Printed By: Chirayath, Subeesh [NN-AE]
LEGEND :
FROM 132/22kV, 60MVA FROM 132/22kV, 60MVA 22kV CABLES - (PSS-2)
TRANSFORMER-1 TRANSFORMER-2 SS 1 - 23
PRIMARY SUBSTATION - 2
SECTOR NUMBER
2500A 2500A
BUS SECTION-1 BUS SECTION-2
SUBSTATION NUMBER
22kV, 2500A, 31.5kA, 1s 22kV, 2500A, 31.5kA, 1s 22/0.415 kV SUB STATION
SS2- LF 17
LOOP NUMBER
630A 630A 630A 630A 630A 630A 630A 630A 630A 1250A 1250A 1250A 1250A 1250A 1250A 630A 630A 630A 630A 630A 630A 630A 630A LOOP FEEDER
PRIMARY SUBSTATION NO.2

2500A 2500A
EXISTING SUBSTATION

PROPOSED SUBSTATION

PROPOSED BUILDING SUBSTATION


LP01A LP02A LP03A LP04A LP05A LP06A LP07A LP08A LP08B LP07B LP06B LP05B LP04B LP03B LP02B LP01B

1500KVA TRANSFORMER

TX.01
LOOP-1: LOOP-2: LOOP-3: LOOP-4: LOOP-5: LOOP-6: LOOP-7: LOOP-8: 12 MVAR 12 MVAR 1000KVA TRANSFORMER
TCL=72.44 MVA TCL=64.10 MVA TCL=63.47 MVA TCL=69.46 MVA TCL=71.67 MVA TCL=64.06 MVA TCL=69.94 MVA TCL=48.84 MVA
1000kVA CAPACITOR CAPACITOR
SL=32.54 MVA SL=28.94 MVA SL=28.48 MVA SL=30.64 MVA SL=32.52 MVA SL=28.67 MVA SL=31.76 MVA SL=21.77 MVA
BANK-1 BANK-2
22/0.415kV FLL=13.04 MVA FLL=11.87 MVA FLL=11.43 MVA FLL=12.50 MVA FLL=12.90 MVA FLL=11.53 MVA FLL=12.59 MVA FLL=8.79 MVA
500KVA TRANSFORMER
SPARE PSS1-LF18

RD1733 PLOT = RD15_CF10 RD2928 RD1727 PLOT = RD16_E02 RD2606 SHS3001 RD2517 RD1511 SHS1805 SHS2701 SHS1801 RD1725 RD3124 SHS1214 SHS1002
TCL=6.27 MVA TCL= 0.90 MVA TCL=3.08 MVA TCL=5.24 MVA TCL= 7.19 MVA TCL=2.80 MVA TCL=6.27 MVA TCL= 6.17 MVA TCL= 6.24 MVA TCL=6.27 MVA TCL=6.18 MVA TCL=6.24 MVA TCL=2.14 MVA TCL=6.08 MVA TCL=2.07 MVA TCL=6.30 MVA
630A CIRCUIT BREAKER
SL=2.77 MVA SL= 0.51 MVA SL=1.41 MVA SL=2.33 MVA SL= 4.08 MVA SL=1.26 MVA SL=2.77 MVA SL=2.75 MVA
SPARE PSS1-LF17
SL=2.77 MVA SL=2.71 MVA SL=2.79 MVA SL=2.76 MVA SL=0.94 MVA SL=2.69 MVA SL=0.92 MVA SL=2.77 MVA (WITH DRAWABLE TYPE)

EARTHING SWITCH

STATION TRANSFORMER

CAPACITOR BANK

BUS DUCT
RD1909 RD1510
TCL= 6.19 MVA TCL= 3.13 MVA
PLOT = RD15_CF03 SL=2.65 MVA SL=1.38 MVA SHS1205
TCL= 1.60 MVA TCL=6.16 MVA
SL= 0.91 MVA SHS2604 SHS2702 SL=2.71 MVA
TCL=6.27 MVA TCL=6.30 MVA
SL=2.78 MVA SL=2.77 MVA

RD3016 PLOT = RD28_E02 RD1911 SHS2308


TCL=4.90 MVA TCL= 8.07 MVA TCL=1.98 MVA TCL=5.62 MVA
SL=2.21 MVA SL= 4.58 MVA SL=0.91 MVA SL=2.70 MVA
RD1732 SHS1001
RD1622 RD1908 TCL=6.30 MVA
TCL=3.82 MVA
TCL=4.30 MVA TCL=5.96 MVA SL=2.77 MVA
SL=1.65 MVA
SL=1.88 MVA SL=2.64 MVA
SHS1013 RD2710
TCL=6.30 MVA RD1910 RD1614 TCL=6.41 MVA
SL=2.77 MVA TCL= 4.27 MVA TCL= 1.74 MVA SL=2.83 MVA
SL=1.89 MVA SL=0.80 MVA
PLOT = RD15_M03 SHS1206
TCL= 0.65 MVA TCL=6.30 MVA
SL= 0.37 MVA SL=2.77 MVA

SHS2605 SHS2705
TCL=4.17 MVA TCL=6.30 MVA
SL=1.88 MVA SL=2.77 MVA

PLOT=RD19_M01 RD1617
RD2806 TCL= 0.65 MVA TCL= 2.99 MVA SHS1806
RD3014 TCL=3.19 MVA RD3132
SL=0.37 MVA SL=1.31 MVA TCL=6.05 MVA
TCL=2.14 MVA SL=1.41 MVA TCL=5.96 MVA
SL=2.65 MVA
SL=0.94 MVA SL=2.64 MVA
SHS0409 SHS1209
TCL=0.40 MVA TCL=6.30 MVA
SL=0.40 MVA SL=2.77 MVA
RD1731 PLOT = RD17_M03
TCL=4.81 MVA TCL= 0.65 MVA
SHS1803
SL=2.12 MVA
SHS1201
TCL=6.20 MVA
SL=2.79 MVA
TCL=6.00 MVA
SL=2.65 MVA
SL=0.37 MVA
TENDER DOCUMENT
SHS2703 SHS2704
TCL=6.30 MVA TCL=6.43 MVA
SL=2.77 MVA SL=2.83 MVA
SHS1016 RD2707
TCL=6.34 MVA TCL=6.52 MVA
RD1830 PLOT=RD16_CF02 SL=2.83 MVA
SL=2.78 MVA
TCL= 5.22 MVA TCL= 0.60 MVA
SL=2.30 MVA SL=0.34 MVA

00 15-SEP-19 ISSUED FOR TENDER KAM


SHS1005 PLOT = RD16_M01 REV. DATE DESCRIPTION APPR'D
TCL=6.16 MVA TCL= 0.65 MVA
SL=2.71 MVA SL=0.37 MVA Client
RD2804 LOOP FEEDER PSS2-LF8 SHS2603
SHS2906 PLOT = RD31_M08
TCL=3.22 MVA TCL=6.45 MVA
TCL=6.16 MVA TCL= 0.65 MVA
SL=1.41 MVA PLOT=RD18_M02 RD1723 RD1621 RD1616 RD1620 SL=2.83 MVA
SL=2.71 MVA SL=0.37 MVA
TCL= 0.65 MVA TCL= 4.33 MVA TCL= 2.14 MVA TCL= 2.67 MVA TCL= 1.87 MVA
SL=0.37 MVA SL=1.89 MVA SL=0.94 MVA SL=1.20 MVA SL=0.82 MVA

RD2711 SHS2706
TCL=6.11 MVA
TCL=2.94 MVA
SL=1.32 MVA SL=2.74 MVA
PMC
LOOP FEEDER PSS2-LF7
SS1006 RD1734
TCL=6.27 MVA SHS2802 SHS2801 RD2607 SHS2601 SHS2602 TCL=2.07 MVA
SL=2.77 MVA SHS1203 TCL=6.16 MVA TCL=6.30 MVA TCL=3.22 MVA TCL=6.43 MVA TCL=6.32 MVA SHS1202 SL=0.92 MVA
TCL=6.30 MVA SL=2.71 MVA SL=2.77 MVA SL=1.41 MVA SL=2.83 MVA SL=2.77 MVA TCL=6.30 MVA
SHS1007 SL=2.77 MVA RD1613
SL=2.77 MVA
TCL=6.30 MVA TCL=0.47 MVA
SL=2.77 MVA LOOP FEEDER PSS2-LF6 SL=0.13 MVA

PLOT = RD28_CR01 PLOT = RD28_M01 RD2805 PLOT = RD28_CF02 SHS2803


TCL= 0.71 MVA TCL= 0.65 MVA TCL=2.43 MVA TCL= 0.60 MVA TCL=5.87 MVA Consultant
SL= 0.38 MVA SL= 0.37 MVA SL=1.10 MVA SL= 0.34 MVA SL=2.58 MVA
SHS1017 RD1728
TCL=6.16 MVA TCL=6.41 MVA
SL=2.71 MVA LOOP FEEDER PSS2-LF5 SL=2.83 MVA

SHS1204 SHS1207 SHS1208 RD1619


RD3015 TCL=6.30 MVA TCL=6.30 MVA TCL=6.30 MVA TCL=4.30 MVA RD3131
TCL=5.17 MVA SL=2.77 MVA SL=2.77 MVA SL=2.77 MVA SL=1.88 MVA TCL=4.04 MVA Project / Contract
SL=2.33 MVA SL=1.77 MVA

LOOP FEEDER PSS2-LF4 RIYADH CITY NORTH


ALL PHASES
RD1735 RD1612
SHS1018 SHS1015 PLOT = RD17_M08 SHS1019 RD1729
TCL=2.95 MVA TCL=2.00 MVA
TCL=4.27 MVA TCL=6.30 MVA TCL= 0.65 MVA TCL=6.43 MVA TCL=6.30 MVA
SL=1.30 MVA SL=0.88 MVA
SL=1.89 MVA SL=2.77 MVA SL=0.37 MVA SL=2.83 MVA SL=2.78 MVA

Drawing Title
LOOP FEEDER PSS2-LF3

SS1009 RD3013 RD3012 RD3010 SHS2901 SHS1003


TCL=5.30 MVA
ULTIMATE POWER SUPPLY
TCL=6.30 MVA
SL=2.77 MVA
TCL=4.84 MVA
SL=2.17 MVA
TCL=4.27 MVA
SL=1.89 MVA
TCL=4.28 MVA
SL=1.89 MVA
TCL=6.27 MVA
SL=2.77 MVA
SL=2.77 MVA 22kV SINGLE LINE DIAGRAM
LOOP FEEDER PSS2-LF2
PRIMARY SUBSTATION PSS-2, SHEET 1/2
PLOT = RD17_CF05 RD1737 RD1730 RD1823 RD1907
SHS1008 RD1611
TCL= 0.60 MVA
TCL=4.27 MVA
SL=0.34 MVA
TCL=1.87 MVA TCL=4.16 MVA TCL=3.22 MVA TCL=4.14 MVA TCL=2.95 MVA CONTRACT No: JOB No:
SL=1.89 MVA SL=0.82 MVA SL=1.86 MVA SL=1.41 MVA SL=1.83 MVA SL=1.30 MVA
DRAWN DESIGNED CHECKED APPROVED
LOOP FEEDER PSS2-LF1
ST SD MSA KAM
SS1012 SS1011 RD1726 PLOT = RD17_M01 SHS1004
TCL=6.30 MVA
SL=2.77 MVA
TCL=6.30 MVA
SL=2.77 MVA
TCL=4.23 MVA
SL=1.89 MVA
TCL= 0.65 MVA
SL=0.37 MVA
PLOT = RD17_CR02
TCL= 0.59 MVA
SL=0.32 MVA
TCL=6.30 MVA
SL=2.77 MVA
DATE 15-SEP-2019 ACTUAL SIZE A1
Drawing Scale. N.T.S
REFER SHEET REFER SHEET
NO.RN-02-00001-00-07-EL-PIL-DG-000306 NO.RN-02-00001-00-07-EL-PIL-DG-000306
Drawing No.
ISSUED FOR CONSTRUCTION_Rev-00 RN-02-00001-00-07-EL-PIL-DG-000305 00
\\Xeuae03fs01\uaeauh_trp\PROJECTS\351159 Riyadh North\04 Users\CADD\Issued for Construction Drawings_(Dec 2021)\00-ALL PHASE\ELECTRICAL\CAD\ELECTRICAL MV SCHEMATIC DIAGRAM\RN-02-00001-00-07-EL-PIL-DG-000301-06_DELETED FOR AD-1.dwg
Last Saved By: P002959B Last Saved Date: 12/19/2021 5:57 PM Printed Date: 12/19/2021 9:03 PM Printed By: Chirayath, Subeesh [NN-AE]
LEGEND :

REFER SHEET REFER SHEET 22kV CABLES - (PSS-2)


NO.RN-02-00001-00-07-EL-PIL-DG-000305 NO.RN-02-00001-00-07-EL-PIL-DG-000305 SS 1 - 23
FROM 132/22kV, 60MVA FROM 132/22kV, 60MVA SECTOR NUMBER
TRANSFORMER-4 TRANSFORMER-3
PRIMARY SUBSTATION - 2 SUBSTATION NUMBER
2500A 2500A 22/0.415 kV SUB STATION
BUS SECTION-4 BUS SECTION-3 SS2- LF 17
22kV, 2500A, 31.5kA, 1s 22kV, 2500A, 31.5kA, 1s
LOOP NUMBER
LOOP FEEDER
PRIMARY SUBSTATION NO.2
630A 630A 630A 630A 630A 630A 630A 630A 630A 1250A 1250A 1250A 1250A 1250A 1250A 630A 630A 630A 630A 630A 630A 630A 630A

EXISTING SUBSTATION

2500A 2500A
PROPOSED SUBSTATION

PROPOSED BUILDING SUBSTATION

1500KVA TRANSFORMER
LP09A LP10A LP11A LP12A LP13A LP14A LP15A LP15B LP14B LP13B LP12B LP11B LP10B LP09B
1000KVA TRANSFORMER
TX.02
1000kVA LOOP-9:
TCL=68.65 MVA
LOOP-10:
TCL=64.13 MVA
LOOP-11:
TCL=69.72 MVA
LOOP-12:
TCL=65.44 MVA
LOOP-13:
TCL=70.28 MVA
LOOP-14:
TCL=68.30 MVA
LOOP-15:
TCL=63.90 MVA 12 MVAR 12 MVAR
500KVA TRANSFORMER
22/0.415kV SL=31.56 MVA SL=28.75 MVA SL=31.42 MVA SL=30.43 MVA SL=31.16 MVA SL=30.42 MVA SL=28.73 MVA CAPACITOR CAPACITOR
FLL=12.36 MVA FLL=11.95 MVA FLL=12.55 MVA FLL=11.78 MVA FLL=12.65 MVA FLL=12.29 MVA FLL=12.17 MVA BANK-4 BANK-3
630A CIRCUIT BREAKER
SPARE PSS1-LF20
(WITH DRAWABLE TYPE)

RD2514 PLOT=RD30_M01 SHS1619


PLOT=RD13_E02 SHS1506
TCL=6.34 MVA TCL= 6.30 MVA
RD2412 SHS3016 SHS3010 RD1827 SPARE PSS1-LF19
SHS1914
TCL=4.30 MVA
RD2923 RD2921
TCL= 0.65 MVA
PLOT=RD25_CF11 RD2516
TCL= 6.30 MVA TCL=2.53 MVA
EARTHING SWITCH
TCL= 3.12 MVA TCL= 4.19 MVA TCL=6.02 MVA TCL=6.25 MVA TCL=4.00 MVA TCL= 4.30 MVA TCL= 4.30 MVA TCL= 0.60 MVA
SL=1.77 MVA SL=2.77 MVA SL=2.77 MVA SL=1.88 MVA SL=2.68 MVA SL=2.77 MVA SL=1.77 MVA SL=1.88 MVA SL=1.88 MVA SL=1.88 MVA SL=0.37 MVA SL=0.34 MVA SL=2.77 MVA SL=1.21 MVA
STATION TRANSFORMER
SPARE PSS1-LF16

CAPACITOR BANK

BUS DUCT

RD2709 RD1821
TCL=2.81 MVA TCL=2.14 MVA
RD1215 SL=1.26 MVA SL=0.94 MVA PLOT=RD21_CF03
TCL= 5.60 MVA TCL= 1.04 MVA
SL=2.47 MVA SL=0.59 MVA
PLOT=RD25_CF09 SHS3008 SHS3007 PLOT=RD25_M01
TCL= 1.30 MVA TCL=6.27 MVA TCL=6.30 MVA SHS3009 TCL= 0.65 MVA
SL=0.74 MVA SHS3015 SL=2.77 MVA SL=2.77 MVA TCL=6.41 MVA SL=0.37 MVA
RD2413 TCL=6.30 MVA PLOT=RD30_CF03
SL=2.83 MVA
TCL= 3.08 MVA SL=2.77 MVA TCL= 0.60 MVA
SL=1.35 MVA SL=0.34 MVA
SHS1509 RD2512
TCL=0.50 MVA RD2708 TCL= 3.71 MVA
SL=0.50 MVA SHS1923
TCL=3.19 MVA TCL=0.81MVA SL=1.65 MVA
SL=1.41 MVA SL=0.81 MVA
RD1307 PLOT=RD21_CR08
TCL= 4.19 MVA TCL= 0.67 MVA
SL=1.88 MVA SL=0.36 MVA

RD1819 SHS3002 RD2922 RD2518


TCL= 3.08 MVA TCL=6.24 MVA TCL= 6.16 MVA TCL= 4.04 MVA
SL=1.35 MVA SL=2.74 MVA SL=2.73 MVA
RD2520 RD1820 SL=1.83 MVA
RD2927 TCL=2.95 MVA TCL=1.87 MVA RD2925
TCL= 2.14 MVA SL=1.30 MVA SL=0.82 MVA TCL= 6.30 MVA
SL=0.94 MVA SL=2.77 MVA
RD1308 SHS2504 SHS2905 PLOT=RD21_CR07
TCL= 4.30 MVA TCL=6.17 MVA TCL=6.27 MVA TCL= 0.67 MVA
SL=1.88 MVA SL=2.74 MVA SL=2.77 MVA SL=0.36 MVA

SHS1601 PLOT=RD25_CF03
TCL=2.01 MVA TCL= 1.60 MVA
SL=0.89 MVA
SHS2510
TCL=6.16 MVA
SHS1915
TCL=6.43 MVA
SL=0.91 MVA
TENDER DOCUMENT
SL=2.71 MVA SL=2.83 MVA
SHS3004 SHS3005
SHS2501 TCL=6.18 MVA TCL=6.19 MVA SHS2506
TCL=6.30 MVA SL=2.75 MVA TCL=6.03 MVA
SL=2.74 MVA
SL=2.77 MVA SL=2.65 MVA PLOT=RD21_CR06
PLOT=RD13_CF02
TCL= 0.66 MVA
TCL= 0.60 MVA
SHS3013 RD2926 SL=0.36 MVA
SL=0.34 MVA
TCL=6.30 MVA TCL= 6.26 MVA
SL=2.77 MVA SL=2.78 MVA
00 15-SEP-19 ISSUED FOR TENDER KAM
REV. DATE DESCRIPTION APPR'D
SHS2503 PLOT = RD25_CF10 RD1825 SHS2907
TCL=6.30 MVA TCL= 0.90 MVA TCL=4.77 MVA TCL=6.32 MVA Client
SL=2.77 MVA SL=0.51 MVA SL=2.12 MVA SL=2.77 MVA

RD1310 PLOT=RD21_CR05
TCL= 6.16 MVA SHS3006 SHS3003 TCL= 0.82 MVA
SL=2.71 MVA TCL=6.30 MVA LOOP FEEDER PSS2-LF15 TCL=6.27 MVA SL=0.44 MVA
SHS2502 SHS2507
SHS1602 TCL=6.30 MVA SL=2.77 MVA SL=2.77 MVA TCL=4.16 MVA PLOT=RD25_CF05
TCL=6.34 MVA SL=2.77 MVA SHS1917
TCL=4.30 MVA
SHS1916
TCL=4.23 MVA
RD1822
TCL=4.30 MVA
SHS1912
TCL=4.30 MVA
RD1824
TCL=2.16 MVA
SHS1913
TCL=4.30 MVA
SL=1.83 MVA TCL= 2.00 MVA PMC
SL=2.79 MVA SL=1.13 MVA
SL=1.88 MVA SL=1.87 MVA SL=1.88 MVA SL=1.88 MVA SL=0.94 MVA SL=1.88 MVA

SHS3014 RD2929
TCL=6.30 MVA LOOP FEEDER PSS2-LF14 TCL= 3.22 MVA
SL=2.77 MVA SL=1.41 MVA
PLOT=RD29_CF05 PLOT=RD29_M02 RD2920 RD2919
TCL= 0.60 MVA TCL= 0.65 MVA TCL= 5.67 MVA TCL= 0.92 MVA
SL=0.34 MVA SL=0.37 MVA SL=2.55 MVA SL=0.47 MVA
SHS1629 PLOT=RD21_CR04 Consultant
SHS2505 PLOT=RD30_E03 TCL= 0.75 MVA
TCL=4.09 MVA
TCL=6.30 MVA LOOP FEEDER PSS2-LF13 TCL= 8.88 MVA SL=0.40 MVA
SL=1.79 MVA
SL=2.77 MVA SL=5.03 MVA

RD2924 SHS3011 SHS3012 PLOT=RD29_CF04 PLOT=RD29_M01


TCL= 3.08 MVA TCL=6.30 MVA TCL=6.12 MVA TCL= 0.60 MVA TCL= 0.65 MVA
PLOT=RD25_M02 SL=2.77 MVA SL=2.74 MVA SL=0.34 MVA SL=0.37 MVA RD2513
SL=1.35 MVA
TCL= 3.08 MVA
TCL= 0.65 MVA
SL=0.37 MVA SL=1.35 MVA Project / Contract
LOOP FEEDER PSS2-LF12

PLOT=RD25_CF07
TCL= 1.04 MVA
PLOT=RD25_CF01
TCL= 0.96 MVA
RD2917
TCL= 4.19 MVA
RD2918
TCL= 2.14 MVA
SHS2908
TCL=6.23 MVA
SHS2912
TCL=2.14 MVA RIYADH CITY NORTH
SHS1626
TCL=6.16 MVA
SHS1604
TCL=6.30 MVA
SL=0.59 MVA SL=0.55 MVA SL=1.88 MVA SL=0.94 MVA
SL=2.73 MVA SL=0.94 MVA
PLOT=RD25_CF08
TCL= 1.40 MVA SHS1620
ALL PHASES
SL=2.76 MVA LOOP FEEDER PSS2-LF11 SL=0.79 MVA TCL=4.87 MVA
SL=2.73 MVA SL=2.19 MVA
Drawing Title
SHS2514 SHS2509
TCL=6.16 MVA
SL=2.71 MVA
TCL=6.16 MVA
SL=2.71 MVA
PLOT=RD25_E02
TCL= 2.45 MVA
RD2515
TCL= 3.08 MVA
SL=1.35 MVA
SHS2508
TCL=6.30 MVA
SL=2.77 MVA
RD2519
TCL= 3.08 MVA
SL=1.35 MVA
ULTIMATE POWER SUPPLY
SL=1.39 MVA

LOOP FEEDER PSS2-LF10


22kV SINGLE LINE DIAGRAM
SHS1606 SHS1605 SHS1607
PRIMARY SUBSTATION PSS-2, SHEET 2/2
PLOT=RD18_E02
TCL=4.29 MVA TCL=6.30 MVA TCL=7.63 MVA TCL= 9.41 MVA
SL=1.89 MVA SL=2.80 MVA SL=1.77 MVA SL=5.34 MVA
CONTRACT No: JOB No:
LOOP FEEDER PSS2-LF9
DRAWN DESIGNED CHECKED APPROVED
SHS1628 SHS1627 PLOT=RD20_CR04 SHS1621 SHS1624
TCL=5.66 MVA TCL=2.16 MVA TCL=6.02 MVA TCL=2.13 MVA SHS1625 SHS1623 ST SD MSA KAM
TCL= 1.43 MVA TCL=4.10 MVA TCL=0.95 MVA
SL=2.47 MVA SL=0.95 MVA SL=0.76 MVA SL=2.72 MVA SL=0.93 MVA
SL=1.83 MVA SL=0.43 MVA
DATE 15-SEP-2019 ACTUAL SIZE A1
Drawing Scale. N.T.S

Drawing No.
ISSUED FOR CONSTRUCTION_Rev-00 RN-02-00001-00-07-EL-PIL-DG-000306 00
\\Xeuae03fs01\uaeauh_trp\PROJECTS\351159 Riyadh North\04 Users\CADD\Issued for Construction Drawings_(Dec 2021)\00-ALL PHASE\ELECTRICAL\CAD\ELECTRICAL MV SCHEMATIC DIAGRAM\RN-02-00001-00-07-EL-PIL-DG-000301-06_DELETED FOR AD-1.dwg
Last Saved By: P002959B Last Saved Date: 12/19/2021 5:57 PM Printed Date: 12/19/2021 9:03 PM Printed By: Chirayath, Subeesh [NN-AE]
NOTES :
1. ACTUAL LOADS AND POWER CONSUMPTION ON A
NUMBER OF SIMILAR EXISTING DEVELOPMENTS IN
ABUDHABI HAVE BEEN STUDIED BY ADDC / ARCADIS.
AS ADVISED BY ADDC AND BASED ON COMPARISON
AGAINST THE ESTIMATED / CALCULATED LOADS, AN
AVERAGE ACTUAL DEMAND FACTOR OF 0.18 HAS BEEN
APPLIED AT THE TOTAL CONNECTED LOAD (TCL) LEVEL
TO OBTAIN THE MAXIMUM DEMAND LOAD AT THE 22kV
EXISTING PRIMARY SUBSTATION : SHSPRY1 - PSS1 FEEDER LEVEL.

FROM 132/22kV, 60MVA FROM 132/22kV, 60MVA FROM 132/22kV, 60MVA FROM 132/22kV, 60MVA
LEGEND :
TRANSFORMER-1 TRANSFORMER-2 TRANSFORMER-4 TRANSFORMER-3
22kV EXISTING CABLES - (PSS-1)
PRIMARY SUBSTATION BY OTHERS

PRIMARY SUBSTATION BY OTHERS


BUS SECTION-1 2500A BUS SECTION-2 2500A BUS SECTION-4 2500A BUS SECTION-3 2500A
22kV, 2500A, 31.5kA, 1s 22kV, 2500A, 31.5kA, 1s 22kV, 2500A, 31.5kA, 1s 22kV, 2500A, 31.5kA, 1s
(3Cx300mm² XLPE / SWA / PVC Cu)
630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 1250A 1250A 1250A 1250A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 1250A 1250A 1250A 1250A 1250A 1250A 630A 630A 630A 630A 630A 630A 630A 630A

22kV PROPOSED CABLES - (PSS-1)


2500A 2500A 2500A 2500A
(3Cx400mm² XLPE / SWA / PVC AL)
22kV CABLE TO BE CANCELED
LP01A LP02A LP03A LP04A LP05A LP06A LP07A LP08A LP17A LP17B LP08B LP07B LP06B LP05B LP04B LP03B LP02B LP01B LP09A LP10A LP11A LP12A LP13A LP14A LP15A LP16A LP16B LP15B LP14B LP13B LP12B LP11B LP10B LP09B
LOOP-1: LOOP-2: LOOP-3: LOOP-4: LOOP-5: LOOP-6: LOOP-7: LOOP-8: LOOP-17: LOOP-9: LOOP-10: LOOP-11: LOOP-12: LOOP-13: LOOP-14: LOOP-15: LOOP-16:
3275.0M
TX.01 TCL=138.17 MVA
SLL=61.71 MVA
TCL=142.05 MVA
SLL=64.05 MVA
TCL=137.31 MVA
SLL=61.89 MVA
TCL=137.95 MVA
SLL=61.26 MVA
TCL=142.02 MVA
SLL=63.81 MVA
TCL=141.39 MVA
SLL=62.96 MVA
TCL=130.42 MVA
SLL=58.24 MVA
TCL=140.90 MVA
SLL=64.60 MVA
TCL=136.72 MVA
SLL=61.68 MVA 12 MVAR 12 MVAR
2480.0M
1295.0M
2875.0M 1690.0M

PLOT=RD22_M01 6700.0M 5710.0M 5189.0M


TX.02
TCL=123.52 MVA
SLL=55.23 MVA
TCL=69.40 MVA
SLL=30.78 MVA
TCL=137.28 MVA
SLL=61.84 MVA
TCL=130.77 MVA
SLL=60.45 MVA
TCL=142.40 MVA
SLL=64.60 MVA
TCL=146.05 MVA
SLL=67.28 MVA
TCL=138.33 MVA
SLL=61.13 MVA
TCL=140.46 MVA
SLL=62.94 MVA 12 MVAR 12 MVAR
10480.0M
2600.0M 2110.0M RD3122 2260.0M 435.0M SS 1 - 23
1000kVA FLL=24.87 MVA FLL=25.57 MVA FLL=25.04 MVA FLL=24.83 MVA FLL=25.56 MVA FLL=25.45 MVA FLL=24.14 MVA FLL=25.36 MVA FLL=25.27 MVA PLOT=RD20_E01 1995.0M 2780.0M RD1209 1000kVA FLL=22.23 MVA FLL=12.49 MVA FLL=24.71 MVA FLL=24.04 MVA FLL=25.10 MVA FLL=25.71 MVA FLL=24.90 MVA FLL=25.28 MVA TCL=5.53 MVA
CAPACITOR CAPACITOR TCL=5.04 MVA TCL=0.65 MVA CAPACITOR CAPACITOR RD2923 RD3130
22/0.415kV TCL=4.54 MVA 22/0.415kV SLL=2.51 MVA
4055.0M
RD1009
2663.0M

SHS1618
3347.0M 3150.0M 1867.0M
1135.0M 5295.0M
BANK-1
SPARE PSS1-LF18
BANK-2 SLL=2.86 MVA
SHS0604
TCL=5.87 MVA
SHS0610
TCL=6.00 MVA
SHS0817
TCL=2.99 MVA
SLL=2.00 MVA SLL=0.37 MVA SHS1214
TCL=2.00 MVA
SLL=0.88 MVA
SHS0403
TCL=5.89 MVA PLOT=RD8_M01
1000.0M
1000.0M
1820.0M 2210.0M 3655.0M 3965.0M 3215.0M
1320.0M
BANK-4
SPARE PSS1-LF20
(FOR RIYADH CITY SOUTH )
BANK-3 TCL=5.62 MVA
SLL=2.47 MVA
TCL=3.72 MVA
SLL=1.64 MVA
RD3120
TCL=4.68 MVA
SLL=2.08 MVA
SHS1404
TCL=5.89 MVA
SLL=2.59 MVA
RD3217
TCL=5.20 MVA
SLL=2.31 MVA 780.0M
SECTOR NUMBER
1735.0M 6838.0M TCL=1.87 MVA SHS1902 SLL=2.59 MVA SLL=2.59 MVA SLL=1.33 MVA SLL=2.59 MVA TCL=0.65 MVA PLOT=RD13_E02
SHS0308 SHS0802 RD1116 SHS1106 SHS1304 RD2310 1865.0M
RD1118
TCL=5.06 MVA
IPS- 1
TCL=0.77 MVA
SLL=0.62 MVA
SLL=0.82 MVA

PLOT=RD21_C24
TCL=0.76 MVA
SLL=0.38 MVA
TCL=5.97 MVA
SLL=2.62 MVA
SS16-6
TCL=0.81 MVA
SLL=0.81 MVA
TCL=2.11 MVA
SLL=0.88 MVA
TCL=3.76 MVA
SLL=1.65 MVA
3890.0M
RD1829
TCL=5.10 MVA
1385.0M
3020.0M
SLL=0.37 MVA
TCL=5.49 MVA
SLL=2.44 MVA
RD1311
TCL=1.06 MVA
SLL=0.47 MVA
TCL=3.12 MVA
SLL=1.77 MVA
TCL=5.89 MVA
SLL=2.56 MVA
TCL=2.27 MVA
SLL=1.00 MVA PLOT=RD23_CR02
TCL=2.12 MVA RD3126
RD3212
TCL=5.35 MVA
SLL=2.36 MVA
SPARE PSS1-LF19
(FOR RIYADH CITY SOUTH ) RD2410
TCL=5.93 MVA RD1114
2185.0M
SUBSTATION NUMBER
SLL=2.28 MVA SLL=2.61 MVA TCL=4.82 MVA
SLL=2.24 MVA TCL=1.06 MVA 575.0M 760.0M SHS0310 SLL=1.14 MVA TCL=5.88 MVA
22/0.415 kV SUB STATION
1282.0M SLL=2.15 MVA
1725.0M SLL=0.46 MVA SLL=2.58 MVA 380.0M
RD1115 SHS0607 3115.0M
RD0815 61.0M 635.0M 575.0M 335.0M RD3016 235.0M
5019.0M 100.0M TCL=5.19 MVA TCL=5.89 MVA 400.0M 650.0M
TCL=5.11 MVA PLOT=RD9_C5 RD1404 490.0M TCL=5.65 MVA 735.0M
SHS0606 SHS1904 SLL=2.24 MVA SLL=2.59 MVA 827.0M 1440.0M 1090.0M SHS3007 SHS1101
SHS0108 SLL=2.24 MVA TCL=0.99 MVA TCL=2.60 MVA SHS1907 SLL=2.54 MVA 535.0M SHS2301
1122.0M TCL=5.89 MVA 470.0M TCL=5.63 MVA
SS1- LF 17
TCL=5.89 MVA TCL=6.11 MVA TCL=3.89 MVA PLOT=RD9_C26 SHS1105 TCL=6.00 MVA
SLL=0.43 MVA SLL=1.12 MVA TCL=5.89 MVA SHS1801 SHS1402 SLL=2.59 MVA SLL=2.48 MVA
478.0M SLL=2.56 MVA SLL=2.59 MVA SLL=1.71 MVA TCL=0.99 MVA TCL=5.89 MVA RD1215 1050.0M SLL=2.62 MVA RD3215
SLL=2.59 MVA TCL=5.83 MVA 120.0M PLOT=RD24_M01 RD2312
SLL=0.43 MVA 513.0M SLL=2.59 MVA TCL=5.49 MVA TCL=5.89 MVA RD3210 TCL=4.97 MVA
PLOT=RD21_C23 SLL=2.57 MVA SLL=2.59 MVA RD3121 TCL=0.65 MVA TCL=4.65 MVA
SHS0201 540.0M 545.0M SHS0404 SLL=2.41 MVA 150.0M 595.0M TCL=5.76 MVA SLL=2.18 MVA
SHS2403 SLL=0.37 MVA SLL=2.08 MVA

LOOP NUMBER
TCL=1.01 MVA 595.0M TCL=5.89 MVA SLL=2.53 MVA TCL=5.35 MVA
RD1119 88.0M TCL=5.96 MVA SHS0601 TCL=5.85 MVA
1160.0M SLL=0.44 MVA 540.0M 260.0M SHS0609 SLL=2.59 MVA SLL=2.36 MVA
TCL=2.14 MVA PLOT=RD9_C6 RD1401 SLL=2.60 MVA 510.0M TCL=5.89 MVA SLL=2.59 MVA 920.0M
RD1831 SHS1911 TCL=5.89 MVA 410.0M 960.0M
SLL=0.94 MVA 95.0M TCL=0.99 MVA TCL=5.29 MVA PLOT=RD11_M02 SLL=2.59 MVA 400.0M
RD0816 TCL=3.91 MVA TCL=3.90 MVA SLL=2.59 MVA PLOT=RD9_C29 SHS2311 250.0M 200.0M
772.0M SLL=2.41 MVA
TCL=2.00 MVA
SLL=0.88 MVA
SLL=0.43 MVA TCL=0.65 MVA
SLL=0.37 MVA
SLL=1.76 MVA SLL=1.74 MVA
655.0M
TCL=1.08 MVA
SLL=0.47 MVA
RD3014
TCL=3.76 MVA
SLL=1.65 MVA RD1618
SHS0104
TCL=5.70 MVA
SLL=2.50 MVA
RD1309
TCL=5.89 MVA
SLL=2.53 MVA
135.0M 2620.0M
PLOT=RD23_CF01
TCL=5.96 MVA
SLL=2.61 MVA 1240.0M
RD2922
RD3128
TCL=5.76 MVA
170.0M 945.0M
LOOP FEEDER
PLOT=RD21_C22 540.0M 645.0M TCL=1.60 MVA TCL=5.89 MVA
SHS0109 TCL=2.95 MVA 1684.0M SHS1503 SLL=2.52 MVA 110.0M

PRIMARY SUBSTATION NO.1


80.0M 535.0M 810.0M SLL=0.91 MVA SHS2302
TCL=5.84 MVA TCL=0.88 MVA SHS0804 SLL=1.24 MVA RD1307 TCL=2.94 MVA SLL=2.62 MVA
285.0M SHS0602 RD1908 85.0M 355.0M TCL=5.56 MVA 965.0M
SLL=2.56 MVA SLL=0.38 MVA PLOT=RD9_C8 TCL=5.24 MVA 485.0M SHS1910 TCL=3.78 MVA SLL=1.27 MVA 390.0M RD1113
873.0M TCL=5.89 MVA SHS0204 TCL=6.07 MVA PLOT=RD9_C30 465.0M SLL=2.44 MVA
TCL=0.99 MVA SLL=2.30 MVA 400.0M PLOT=RD18_CF03 TCL=4.03 MVA IPS- 1 SLL=1.72 MVA TCL=6.00 MVA
545.0M SLL=2.59 MVA TCL=5.78 MVA SLL=2.69 MVA TCL=1.08 MVA PLOT=RD23_M02 SHS1305
SLL=0.43 MVA TCL=0.60 MVA SLL=1.77 MVA 430.0M RD2415 SLL=2.59 MVA
PLOT=RD11_CF09 SLL=2.53 MVA TCL=0.77 MVA SHS2404 SHS2309 TCL=0.65 MVA TCL=5.60 MVA
SLL=0.34 MVA SLL=0.47 MVA SHS1103 TCL=5.87 MVA
SHS1616 TCL=0.60 MVA 940.0M SLL=0.62 MVA TCL=6.01 MVA TCL=5.96 MVA SLL=0.37 MVA SLL=2.46 MVA
TCL=5.98 MVA SHS2314 SLL=2.58 MVA
RD0817 540.0M SLL=0.34 MVA 418.0M 310.0M 125.0M SLL=2.64 MVA SLL=2.61 MVA 760.0M
325.0M SLL=2.58 MVA TCL=5.96 MVA
RD1121
TCL=2.24 MVA
SLL=1.03 MVA
TCL=5.79 MVA
SLL=2.53 MVA
PLOT=RD21_C19
90.0M
PLOT=RD9_C9
TCL=0.99 MVA
SHS0808
TCL=2.09 MVA
SLL=0.94 MVA
SHS0202
TCL=5.93 MVA
SLL=2.63 MVA
155.0M
SHS1905
650.0M
RD1826
TCL=2.41 MVA
385.0M

RD1117
235.0M
SHS2906
TCL=5.71 MVA
SLL=2.51 MVA
346.0M
730.0M
SHS1505
TCL=2.25 MVA
460.0M 580.0M
SLL=2.61 MVA

SHS0814
EXISTING SUBSTATION
TCL=1.12 MVA PLOT=RD9_CR01 SLL=0.98 MVA RD3129 265.0M
SLL=0.43 MVA 355.0M SLL=1.06 MVA TCL=4.68 MVA 1035.0M PLOT=RD23_CF05 TCL=5.55 MVA
SLL=0.49 MVA TCL=5.87 MVA TCL=2.00 MVA SHS1205 650.0M 1020.0M TCL=5.42 MVA
540.0M SLL=2.06 MVA RD0814 RD1308 TCL=0.84 MVA PLOT=RD31_CR04 915.0M SLL=2.46 MVA
SLL=2.58 MVA SLL=1.26 MVA TCL=5.89 MVA 575.0M SLL=2.38 MVA
84.0M 340.0M SHS0605 TCL=5.51 MVA PLOT=RD21_CF02 TCL=5.62 MVA SLL=0.48 MVA TCL=0.67 MVA
270.0M SLL=2.59 MVA SHS3005 405.0M
PLOT=RD14_MR30 TCL=5.83 MVA SLL=2.41 MVA TCL=1.00 MVA 1265.0M SLL=2.47 MVA SLL=0.36 MVA PLOT=RD32_CF02 640.0M
726.0M 95.0M TCL=5.84 MVA 665.0M
52.0M TCL=2.65 MVA SLL=2.60 MVA SHS1803 RD1720 SLL=0.57 MVA 410.0M TCL=0.60 MVA
PLOT=RD21_C21 3300M SLL=2.58 MVA RD2311
PLOT=RD18_M03 TCL=3.95 MVA

PLOT=RD8_E01
RD0708
TCL=4.86 MVA
SLL=2.14 MVA
TCL=1.01 MVA
SLL=0.44 MVA
PLOT=RD9_C10
TCL=0.99 MVA
SLL=0.43 MVA
SLL=1.15 MVA

265.0M
500.0M
SHS1906
TCL=0.65 MVA
SLL=0.37 MVA
475.0M
PLOT=
RD10_CF02
TCL=6.04 MVA
SLL=2.67 MVA
200.0M
PLOT=RD9_CF02
TCL=0.58 MVA
RD3015
SLL=1.74 MVA
SHS1501
TCL=3.76 MVA
100.0M
RD2411
TCL=2.81 MVA
SLL=1.24 MVA SHS2315
SHS2405
TCL=6.12 MVA
SLL=2.69 MVA
TCL=3.54 MVA
SLL=1.62 MVA
SLL=0.34 MVA
EXISTING SUBSTATION
TCL=5.89 MVA SHS0603 TCL=5.58 MVA 760.0M PLOT=RD23_CF03 70.0M
344.0M TCL=4.24 MVA
SLL=2.40 MVA SHS1615
230.0M
PLOT=RD14_MR06
TCL=1.58 MVA SHS0608
295.0M SLL=2.59 MVA
435.0M
TCL=6.00 MVA
SLL=2.59 MVA
TCL=0.60 MVA
SLL=0.34 MVA
1018.0M
SLL=0.33 MVA
SLL=2.50 MVA
SHS1706
TCL=1.51 MVA
RD1211
TCL=4.41 MVA 580.0M
SLL=1.65 MVA
TCL=2.00 MVA
SLL=1.13 MVA 500.0M
370.0M

295.0M
TCL=5.81 MVA
SLL=2.55 MVA
160.0M RD1213
TCL=3.48 MVA
TO BE CANCELED (TOWN HOUSE AREA)
266.0M 170.0M SHS1914 933.0M SLL=0.74 MVA SLL=1.95 MVA PLOT=RD31_M01
SLL=0.69 MVA TCL=5.87 MVA SLL=1.60 MVA
PLOT=RD9_C16 PLOT= PLOT=RD31_E02
PLOT=RD10_M02 SLL=2.53 MVA 585.0M TCL=4.03 MVA 754.0M 938.0M TCL=0.65 MVA RD3214
1610.0M PLOT=RD21_C20 TCL=0.99 MVA RD17_IRRPS01 5550.0M TCL=5.63 MVA 355.0M
RD1120 TCL=0.65 MVA SLL=1.77 MVA SHS2313 SLL=0.37 MVA TCL=4.75 MVA
TCL=1.02 MVA RD1828 PLOT=RD13_CF02 SLL=3.19 MVA SHS3003
TCL=3.33 MVA SLL=0.43 MVA SLL=0.37 MVA 8255.0M TCL=0.72 MVA TCL=5.83 MVA
SLL=0.45 MVA TCL=5.92 MVA 7760.0M TCL=0.60 MVA TCL=5.87 MVA SLL=2.13 MVA
SLL=1.47 MVA SHS0810 SLL=0.39 MVA RD1725 260.0M 440.0M 555.0M SLL=2.56 MVA 400.0M

36.0M
325.0M
SLL=2.59 MVA
460.0M
RD1821
SHS1805
TCL=5.88 MVA
SHS2701
TCL=5.80 MVA
TCL=3.65 MVA
SLL=1.59 MVA
1150.0M RD0813
TCL=5.32 MVA
SLL=2.33 MVA
SLL=0.34 MVA
140.0M
SLL=2.59 MVA

RD3135
SHS2407
TCL=5.89 MVA
380.0M 200.0M
PROPOSED PUBLIC SUBSTATION
SHS0901 88.0M 220.0M PLOT=RD11_E02 RD3013 SHS1206
PLOT=RD9_C17 TCL=2.00 MVA SLL=2.59 MVA SLL=2.55 MVA SHS1002 740.0M TCL=1.06 MVA SLL=2.59 MVA
TCL=5.84 MVA 410.0M 5602.0M TCL=5.49 MVA TCL=5.89 MVA 620.0M 960.0M
SHS1614 TCL=0.99 MVA PLOT=RD14_MR07 TCL=4.66 MVA SLL=0.88 MVA TCL=5.89 MVA SLL=0.47 MVA
1475.0M SLL=2.56 MVA TCL=2.30 MVA SLL=2.64 MVA SLL=2.47 MVA SLL=2.59 MVA 710.0M PLOT=RD23_CF06
SLL=0.43 MVA TCL=1.16 MVA SHS1908 SHS1202 SLL=2.60 MVA PLOT=RD20_CR03 SHS1502 SHS2304 765.0M
785.0M
7515.0M
SLL=1.11 MVA SLL=0.51 MVA TCL=5.98 MVA TCL=6.43 MVA TCL=1.80 MVA TCL=0.90 MVA RD2412 SHS1401

PROPOSED BUILDING INTEGRATED


120.0M TCL=1.11 MVA TCL=5.89 MVA SHS1303
SLL=2.64 MVA SLL=2.59 MVA SLL=0.78 MVA SLL=0.51 MVA TCL=4.59 MVA SLL=2.62 MVA RD2919 RD3133 TCL=5.84 MVA
350.0M 430.0M SLL=0.60 MVA RD1310 855.0M TCL=5.89 MVA
RD2710 SLL=2.06 MVA TCL=2.00 MVA TCL=2.80 MVA SLL=2.56 MVA
616.0M TCL=5.92 MVA 590.0M
600.0M SLL=2.59 MVA
SHS1923 TCL=5.96 MVA SLL=0.88 MVA SLL=1.23 MVA
173.0M 175.0M RD1911 690.0M 249.0M SLL=2.59 MVA
220.0M TCL=0.81MVA SLL=2.61 MVA 420.0M

243.0M
52.0M
PLOT=RD21_C2
PLOT=RD9_C7
TCL=0.99 MVA
SLL=0.43 MVA
PLOT=RD14_MR08
TCL=1.02 MVA
SLL=0.45 MVA RD1008
PLOT=RD11_CF07
TCL=0.82 MVA
130.0M
PLOT=RD18_M07
SLL=0.81 MVA TCL=2.28 MVA
SLL=1.03 MVA 650.0M SHS1209 349.0M 260.0M 200.0M
SHS2312
TCL=5.76 MVA
790.0M

SHS2408 RD1403
SUBSTATION
SHS0401 TCL=1.11 MVA SLL=0.46 MVA 450.0M TCL=5.89 MVA 100.0M 280.0M SHS2316 TCL=5.85 MVA TCL=1.78 MVA
TCL=6.16 MVA TCL=0.65 MVA RD1619 SLL=2.52 MVA
TCL=5.90 MVA SLL=0.49 MVA SLL=2.59 MVA 269.0M
280.0M TCL=6.04 MVA SLL=2.58 MVA SLL=0.88 MVA
SLL=2.65 MVA SLL=0.37 MVA 620.0M SHS2702 TCL=3.89 MVA 300.0M 1250.0M SHS1504 220.0M
SLL=2.59 MVA 895.0M SLL=2.64 MVA
RD1512 RD1820 TCL=5.89 MVA SLL=1.71 MVA PLOT=RD20_CR02 TCL=1.73 MVA RD2309 SHS2305 590.0M
RD1111 117.0M 220.0M 345.0M RD2707 RD3012 RD2920
TCL=3.01 MVA TCL=2.00 MVA SLL=2.59 MVA TCL=0.75 MVA SHS1629 SLL=0.75 MVA TCL=3.89 MVA TCL=5.83 MVA
TCL=5.75 MVA SLL=1.33 MVA PLOT=RD9_101A PLOT=RD14_MR09 235.0M TCL=5.89 MVA TCL=3.76 MVA TCL=5.67 MVA SHS2303
460.0M SLL=0.88 MVA SLL=0.40 MVA TCL=3.02 MVA SLL=1.71 MVA SLL=2.56 MVA
SLL=2.57 MVA TCL=2.96 MVA TCL=1.02 MVA 235.0M SHS1806 SLL=2.59 MVA SLL=1.65 MVA 430.0M SLL=2.57 MVA TCL=5.83 MVA
PLOT=RD21_C14
TCL=1.18 MVA
SLL=0.52 MVA
SLL=1.29 MVA
97.0M
SLL=0.45 MVA
PLOT=RD11_CF10
TCL=0.94 MVA
SLL=0.53 MVA
RD1832
TCL=1.08 MVA 425.0M
TCL=6.03 MVA
SLL=2.64 MVA
232.0M
SHS0103
TCL=5.85 MVA
SLL=2.58 MVA
SLL=1.32 MVA
RD2413
TCL=3.55 MVA 445.0M
SLL=2.56 MVA

425.0M
720.0M SHS1302 PROPOSED CABLE CUT & JOINT WITH
115.0M
PLOT=RD9_C23
TCL=0.99 MVA
210.0M
PLOT=RD14_MR10 195.0M
SLL=0.53 MVA
SHS1915
TCL=6.12 MVA
335.0M
510.0M
1665.0M
RD1823
PLOT=RD16_M01
TCL=0.65 MVA
SLL=0.37 MVA
990.0M
SHS1707 470.0M
395.0M

SHS1508
SLL=1.58 MVA

600.0M 691.0M
670.0M 300.0M
TCL=5.53 MVA
SLL=2.50 MVA 3Cx400mm² XLPE / SWA / PVC AL
SLL=0.43 MVA SHS1208 TCL=2.74 MVA 760.0M SHS2307
TCL=1.03 MVA 135.0M SLL=2.69 MVA TCL=3.22 MVA PLOT=RD29_M02
416.0M 85.0M 625.0M 2899.0M TCL=5.89 MVA 660.0M SLL=1.19 MVA TCL=5.83 MVA
473.0M SLL=0.45 MVA SLL=1.41 MVA SHS2310 TCL=0.65 MVA 160.0M RD2414
PLOT=RD11_CF03 SHS1909 SHS2705 SLL=2.59 MVA SHS1626 SLL=2.56 MVA PLOT=RD31_CF02
PLOT=RD21_C15 TCL=5.62 MVA SLL=0.37 MVA TCL=4.16 MVA
TCL=3.47 MVA TCL=4.95 MVA 915.0M TCL=0.60 MVA 550.0M
PLOT=RD15_M02 TCL=1.03 MVA 109.0M TCL=5.99 MVA SHS2603 TCL=5.89 MVA SHS2401 SLL=2.49 MVA SLL=1.83 MVA
SHS0203 SLL=1.97 MVA 695.0M PLOT=RD21_C11 SLL=2.21 MVA SHS2306
SLL=0.45 MVA SLL=2.63 MVA TCL=5.91 MVA SLL=2.59 MVA 155.0M 365.0M TCL=5.85 MVA SLL=0.34 MVA
TCL=0.65 MVA
1500KVA TRANSFORMER
SHS0311 290.0M TCL=5.66 MVA 2180.0M RD3010 TCL=6.03 MVA
RD1825 SLL=2.59 MVA TCL=1.02 MVA SLL=2.60 MVA 860.0M
SLL=0.37 MVA PLOT=RD14_MR19 SLL=2.48 MVA RD1728 TCL=4.85 MVA SLL=2.64 MVA SHS1403
SLL=0.45 MVA SHS2504
TCL=5.44 MVA TCL=5.73 MVA SLL=2.13 MVA RD1613 SHS1001 325.0M TCL=5.73 MVA
SHS0312 TCL=1.00 MVA 260.0M TCL=6.08 MVA 5758.0M
SLL=2.36 MVA SLL=2.53 MVA TCL=5.89 MVA 342.0M SLL=2.53 MVA
SLL=0.44 MVA 360.0M TCL=1.68 MVA SLL=2.66 MVA 510.0M
RD707 128.0M SLL=2.59 MVA 145.0M
PLOT=RD11_CF08 PLOT=RD9_C25 430.0M SLL=0.75 MVA SHS3016
RD1827 680.0M SHS1506
TCL=0.90 MVA
SLL=0.51 MVA
TCL=3.96 MVA
SLL=1.76 MVA
PLOT=RD21_C18
TCL=0.93 MVA
SLL=0.41 MVA
TCL=0.99 MVA
SLL=0.43 MVA 275.0M
525.0M
RD1112
TCL=4.00 MVA
SLL=1.77 MVA 250.0M
590.0M
490.0M
SHS1207
TCL=6.30 MVA
SLL=2.59 MVA
110.0M
170.0M
PLOT=RD21_C12
TCL=1.10 MVA SHS1628
TCL=3.23 MVA
SLL=1.44 MVA
TCL=5.89 MVA
SLL=2.62 MVA
RD3134
TCL=2.62 MVA
SLL=1.16 MVA
PLOT=
RD29_CF05
12100.0M
615.0M SHS1301
TCL=5.84 MVA
SLL=2.56 MVA
1250KVA TRANSFORMER
114.0M PLOT=RD14_MR20 TCL=3.87 MVA TCL=0.60 MVA RD3125 SHS0818
TCL=3.69 MVA SHS1913 RD1729 SLL=0.48 MVA RD2921 1710.0M
TCL=1.00 MVA SHS2602 SLL=1.71 MVA 150.0M SLL=0.34 MVA TCL=5.67 MVA TCL=5.22 MVA
PLOT=RD9_102A SLL=1.71 MVA TCL=4.03 MVA TCL=5.90 MVA 150.0M SHS0102 TCL=5.35 MVA
350.0M SLL=0.44 MVA 1540.0M TCL=5.78 MVA 665.0M SLL=2.58 MVA SLL=2.30 MVA

190.0M
216.0M
PLOT=RD21_C17
TCL=1.98 MVA
SLL=0.86 MVA RD1007
TCL=5.94 MVA
RD2709
TCL=3.76 MVA
SLL=1.77 MVA SLL=2.53 MVA SHS2704
TCL=5.89 MVA
SLL=2.61 MVA TCL=5.82 MVA
SLL=2.57 MVA
445.0M
295.0M
SHS2402
RD2929
500.0M SLL=2.36 MVA

PLOT=RD25_CF11
1000KVA TRANSFORMER
TCL=0.91 MVA 165.0M SLL=2.65 MVA 1030.0M SLL=1.68 MVA SLL=2.59 MVA 985.0M TCL=6.12 MVA
SHS0902 500.0M SHS1611 630.0M SHS1507 SLL=2.69 MVA TCL=4.70 MVA TCL=0.60 MVA
SLL=0.40 MVA PLOT=RD14_MR21 SHS2901 SHS2503 585.0M 1070.0M PLOT=RD12_CF04
TCL=5.98 MVA 113.0M PLOT=RD11_CF06 LOOP FEEDER PSS1-LF17 160.0M 451.0M TCL=1.40 MVA SLL=2.60 MVA 2510.0M 505.0M 550.0M SLL=0.34 MVA
TCL=1.00 MVA TCL=0.60 MVA
630KVA TRANSFORMER
PLOT=RD11_CF04 SHS1019 TCL=5.87 MVA 145.0M SLL=0.62 MVA TCL=6.12 MVA
SLL=2.63 MVA PLOT=RD9_MU01 SLL=0.44 MVA TCL=0.94 MVA 410.0M SHS1204 TCL=5.97 MVA SLL=2.59 MVA SLL=0.34 MVA
TCL=2.00 MVA 645.0M SHS0702 SLL=2.69 MVA
TCL=1.98 MVA SLL=0.53 MVA 1690.0M 200.0M 464.0M 1450.0M 200.0M 490.0M 335.0M 435.0M TCL=6.03 MVA RD1612 601.0M
SLL=1.13 MVA SLL=2.62 MVA TCL=5.89 MVA SHS1627 SHS2317 1070.0M
102.0M SLL=0.86 MVA SLL=2.59 MVA TCL=2.00 MVA TCL=2.85 MVA TCL=5.81 MVA
SHS2601 PLOT=RD21_C7 SLL=2.59 MVA SHS3006
354.0M PLOT=RD21_C16 SLL=0.88 MVA SLL=1.18 MVA RD3123 SLL=2.55 MVA
235.0M RD1824 TCL=5.89 MVA 665.0M TCL=1.04 MVA TCL=5.84 MVA SHS3009
TCL=1.04 MVA
SLL=0.45 MVA
634.0M
SHS0809
TCL=1.46 MVA
325.0M
170.0M
RD2708
TCL=4.73 MVA
SLL=2.06 MVA
RD2520
TCL=3.62 MVA
SLL=1.60 MVA
SHS2510
TCL=6.12 MVA
SLL=2.68 MVA
PLOT=RD25_CF10 SHS1917
TCL=0.90 MVA
SLL=0.51 MVA
TCL=4.03 MVA
SLL=1.77 MVA
SHS1916 RD1822 SHS1912
TCL=3.82 MVA TCL=4.43 MVA TCL=4.03 MVA
SLL=1.70 MVA SLL=1.94 MVA SLL=1.77 MVA
TCL=2.30 MVA
SLL=1.00 MVA
SLL=2.59 MVA
190.0M 2830.0M
SLL=0.45 MVA 425.0M 770.0M
410.0M TCL=5.17 MVA
SLL=2.27 MVA
SLL=2.56 MVA TCL=5.97 MVA
SLL=2.62 MVA
RD3211
TCL=3.62 MVA
SLL=1.59 MVA
SHS1702
TCL=2.53 MVA
500KVA TRANSFORMER
140.0M SLL=0.65 MVA PLOT=RD11_CF02 PLOT=RD17_M08 332.0M 570.0M SHS3015 320.0M 155.0M PLOT=RD23_E01 SLL=1.14 MVA
SHS0801 SHS0205 550.0M SHS1509
TCL= 1.60 MVA SHS2706 TCL=0.65 MVA TCL=5.89 MVA TCL=4.82 MVA
112.0M TCL=2.41 MVA TCL=5.92 MVA 2495.0M TCL=0.50 MVA RD3136
SLL= 0.91 MVA TCL=5.87 MVA SLL=0.37 MVA SHS2406 SLL=2.60 MVA SLL=2.73 MVA
PLOT=RD11_M01
TCL=0.65 MVA
570.0M
PLOT=RD21_C13
TCL=1.14 MVA
SLL=1.06 MVA

150.0M
SLL=2.59 MVA
LOOP FEEDER PSS1-LF8
650.0M
SLL=2.59 MVA
SHS1203
TCL=5.89 MVA
RD3131
TCL=5.33 MVA
2392.0M PLOT=RD17_M03
TCL=0.65 MVA
SLL=0.37 MVA
100.0M
PLOT=RD21_C6 PLOT=RD20_CR04
SLL=0.50 MVA TCL=5.98 MVA
SLL=2.64 MVA
SHS2505
TCL=6.12 MVA
SLL=2.69 MVA
830.0M
LOOP FEEDER PSS1-LF16
487.0M
TCL=1.46 MVA
SLL=0.65 MVA 630A CIRCUIT BREAKER
SLL=0.37 MVA SLL=2.34 MVA
SLL=0.50 MVA
(WITH DRAWABLE TYPE)
SLL=2.59 MVA TCL=1.01 MVA TCL=1.43 MVA PLOT=RD25_M01
205.0M PLOT=RD14_MR22 10725.0M 785.0M 250.0M 1195.0M 665.0M 365.0M 540.0M 278.0M
SHS0402 SLL=0.44 MVA SLL=0.76 MVA 445.0M 485.0M 635.0M 3020.0M 775.0M 140.0M 1150.0M 1295.0M 785.0M 636.0M TCL=0.65 MVA 700.0M
TCL=1.17 MVA RD2925
TCL=5.89 MVA PLOT=RD14_MR28 SHS1015 SLL=0.37 MVA
SLL=0.51 MVA PLOT=RD8_M02 TCL=5.89 MVA
SLL=2.59 MVA SHS0903 TCL=1.73 MVA TCL=5.89 MVA 715.0M
PLOT=RD28_E02 RD2806 RD2804 SHS2801 TCL=0.65 MVA SHS2902 SHS2904 SHS3010 SHS3008 SHS3002 SHS3004 SLL=2.59 MVA
TCL=5.97 MVA SLL=0.75 MVA SHS3001 SHS2802 RD2607 SLL=2.59 MVA RD3011 SHS2903 RD2931 RD2930
262.0M SHS1617 900.0M RD1611 SLL=0.37 MVA TCL=5.91 MVA
SLL=2.62 MVA TCL=5.89 MVA TCL= 8.07 MVA TCL=3.87 MVA TCL=4.27 MVA TCL=5.89 MVA TCL=5.89 MVA TCL=4.41 MVA 365.0M TCL=5.89 MVA TCL=4.68 MVA TCL=5.76 MVA TCL=5.89 MVA TCL=5.85 MVA TCL=1.60 MVA TCL=5.89 MVA TCL=1.06 MVA TCL=5.97 MVA SHS2318
PLOT=RD9_C1 SHS1610 450.0M 380.0M
SLL=2.59 MVA SLL= 4.58 MVA SLL=1.71 MVA SLL=1.89 MVA SLL=2.59 MVA SLL=2.59 MVA 720.0M 590.0M TCL=2.95 MVA SLL=2.59 MVA SLL=2.59 MVA SLL=2.59 MVA SLL=2.59 MVA SLL=2.62 MVA SLL=2.63 MVA
TCL=0.93 MVA
SLL=0.40 MVA
SHS1613 88.0M
PLOT=RD14_MR27
200.0M
PLOT=RD14_MR23
TCL=1.38 MVA SHS0206
SLL=1.94 MVA

975.0M
SLL=1.30 MVA
PLOT=RD21_C31
TCL=1.19 MVA 550.0M
1720.0M
RD2927
TCL=3.33 MVA
SLL=2.06 MVA SLL=2.53 MVA SLL=0.71 MVA SLL=0.47 MVA TCL=5.93 MVA
SLL=2.60 MVA
RD3213
610.0M
EARTHING SWITCH
SHS2803 SHS1201 SLL=0.52 MVA 524.0M TCL=4.01 MVA
445.0M TCL=0.89 MVA SLL=0.60 MVA TCL=5.76 MVA 340.0M SLL=1.47 MVA 115.0M
TCL=5.88 MVA TCL=5.93 MVA SHS1018 PLOT=RD31_M08 SLL=1.77 MVA
SLL=0.39 MVA RD2926 645.0M
SLL=2.56 MVA SLL=2.58 MVA SLL=2.61 MVA TCL=3.95 MVA TCL=0.65 MVA PLOT=RD21_C4 PLOT=RD25_CF07 570.0M
85.0M PLOT=RD21_C10 TCL=1.09 MVA 790.0M TCL=4.14 MVA TCL=5.35 MVA
SLL=1.74 MVA SLL=0.37 MVA SHS1601 535.0M SHS1704
PLOT=RD9_C2
TCL=0.88 MVA
SLL=0.38 MVA 505.0M
186.0M TCL=1.04 MVA
SLL=0.45 MVA
150.0M
SHS0805 100.0M
TCL=2.33MVA SHS0807
470.0M
185.0M
SLL=0.48 MVA
295.0M
TCL=3.44 MVA
SLL=1.53 MVA
SLL=2.35 MVA SLL=2.39 MVA

SHS2319
RD2518
TCL=4.31 MVA
STATION TRANSFORMER
PLOT=RD21_C27 1845.0M
SLL=1.03 MVA TCL=5.22 MVA LOOP FEEDER PSS1-LF7 650.0M PLOT=RD16_CF01A 325.0M TCL=5.80 MVA SLL=1.95 MVA
12750.0M TCL=1.18 MVA LOOP FEEDER PSS1-LF15
PLOT=RD21_C8 SLL=2.30 MVA TCL=0.98 MVA 320.0M 510.0M SLL=2.56 MVA
SHS1017 SLL=0.51 MVA 551.0M
TCL=1.08 MVA 617.0M

PLOT=RD9_C11
TCL=0.99 MVA
281.0M
PLOT=RD15_CF11
TCL=0.60 MVA
SLL=0.47 MVA
128.0M
270.0M
540.0M 610.0M 425.0M 305.0M 345.0M 1520.0M 180.0M 670.0M 185.0M
SLL= 0.56 MVA TCL=5.89 MVA
SLL=2.59 MVA
290.0M
330.0M
140.0M
SHS3013
TCL=5.76 MVA
530.0M SHS3014
TCL=5.76 MVA
420.0M RD2924
TCL=3.87 MVA
300.0M SHS3011
TCL=5.89 MVA
435.0M SHS3012
TCL=5.74 MVA
385.0M PLOT=RD29_CF04
TCL=0.60 MVA
500.0M PLOT=RD29_M01
TCL=0.65 MVA
SHS1405
TCL=5.89 MVA
CAPACITOR BANK
SLL=2.53 MVA SLL=2.53 MVA SLL=1.71 MVA SLL=2.59 MVA SLL=2.59 MVA SLL=0.34 MVA SLL=0.37 MVA 620.0M
SLL=0.43 MVA SLL=0.34 MVA PLOT=RD14_MR26 RD2711 PLOT=RD28_CF02 SHS1609 145.0M 876.0M SLL=2.59 MVA
RD1402 RD2606 SHS2604 SHS2605 RD2712 SHS2703 PLOT=RD28_CR01 PLOT=RD28_M01 RD2805 575.0M
RD709 RD3132 TCL=2.54 MVA PLOT=RD20_C8
TCL=1.08 MVA
SLL=0.47 MVA 606.0M
TCL=0.99 MVA
SLL=0.43 MVA
90.0M
TCL=4.27 MVA
SLL=1.89 MVA
TCL=3.34 MVA
SLL=1.49 MVA
TCL=5.83 MVA
SLL=2.56 MVA
TCL=3.70 MVA
SLL=1.66 MVA
TCL=1.73 MVA
SLL=0.77 MVA
TCL=5.89 MVA
SLL=2.59 MVA
TCL=3.37 MVA
SLL=1.50 MVA
TCL= 0.71 MVA
SLL= 0.38 MVA
TCL= 0.65 MVA
SLL= 0.37 MVA
TCL=2.43 MVA TCL= 0.60 MVA
SLL=1.10 MVA SLL= 0.34 MVA
RD1622
TCL=4.30 MVA
SLL=1.88 MVA
425.0M
RD1738
TCL=5.69 MVA
SLL=2.52 MVA
SLL=1.13 MVA
PLOT=RD21_C26
TCL=0.99 MVA
SLL=0.43 MVA
PLOT=
RD25_CF01
PLOT=
RD30_E04
425.0M
TCL=1.06 MVA
SLL=0.46 MVA BUS DUCT
165.0M TCL=1.06 MVA 220.0M RD0812 TCL=1.10 MVA TCL=2.62 MVA
SHS1612 PLOT=RD14_MR25 SLL=0.62 MVA SLL=1.49 MVA
PLOT= RD9_C13 SLL=0.47 MVA TCL=5.57 MVA SHS2506
TCL=0.99 MVA
SLL=0.43 MVA
TCL=0.98 MVA
SLL=0.43 MVA 165.0M
305.0M
RD1734
SLL=2.44 MVA

130.0M 540.0M
RD2514
TCL=6.12 MVA
SLL=2.69 MVA
TCL=6.08 MVA
SLL=2.67 MVA
SHS1306
TCL=5.80 MVA
SLL=2.58 MVA
OPEN LOOP
68.0M PLOT=RD14_M02 PLOT=RD16_E02 200.0M
370.0M 280.0M TCL=3.28 MVA
606.0M PLOT=RD14_MR24 TCL=0.65 MVA TCL=7.19 MVA 876.0M 565.0M
SLL=1.45 MVA
TCL=1.04 MVA SLL=0.37 MVA SLL= 4.08 MVA SHS1016 SHS1621 9080.0M
TCL=5.93 MVA 250.0M RD1210 SHS0706 100.0M
70.0M SHS1711 SLL=0.45 MVA TCL=1.28 MVA

DETAILED DESIGN
LOOP FEEDER PSS1-LF6 SLL=2.60 MVA TCL=5.28 MVA TCL=5.87 MVA
PLOT=RD9_C12 TCL=2.67 MVA SHS2308 SLL=0.62 MVA LOOP FEEDER PSS1-LF14
570.0M 475.0M 180.0M 85.0M 375.0M 205.0M 200.0M 3110.0M SLL=2.35 MVA SLL=2.59 MVA
TCL=0.99 MVA 420.0M SLL=1.27 MVA 160.0M 115.0M 145.0M 170.0M 140.0M 575.0M TCL=6.03 MVA
140.0M SHS1602 1290.0M 595.0M
SLL=0.43 MVA SHS0904 SLL=2.64 MVA
PLOT=RD14_MR05 RD1907 TCL=3.95 MVA 1185.0M 3275.0M 890.0M 270.0M 415.0M 1251.0M 290.0M 155.0M 1115.0M
TCL=6.01 MVA TCL=0.94 MVA PLOT=RD20_C7
TCL=3.08 MVA SLL=1.78 MVA
SLL=2.63 MVA SLL=0.41 MVA 515.0M 522.0M TCL=1.66 MVA
SHS0811 SHS0812 SHS0813 SHS0815 SHS0816 SLL=1.35 MVA SHS1603 130.0M PLOT= SLL=0.72 MVA

1110.0M 40.0M
TCL=4.41 MVA TCL=1.46 MVA
SLL=1.94 MVA SLL=0.65 MVA
PLOT=RD14_MR29
TCL=1.33 MVA TCL=3.37 MVA
SLL=0.59 MVA SLL=1.47 MVA
PLOT=RD14_MR18
TCL=0.97 MVA
SLL=0.42 MVA
PLOT=RD14_MR17
TCL=1.00 MVA
SLL=0.44 MVA
TCL=1.46 MVA
SLL=0.65 MVA
PLOT=RD14_MR16
TCL=1.00 MVA
SLL=0.44 MVA
PLOT=RD14_MR15
TCL=1.00 MVA
SLL=0.44 MVA
PLOT=RD14_MR14
TCL=1.03 MVA
SLL=0.45 MVA
PLOT=RD14_MR13
TCL=1.02 MVA
SLL=0.45 MVA
PLOT=RD14_MR12 PLOT=RD14_MR11
TCL=1.00 MVA
SLL=0.44 MVA
TCL=1.03 MVA
SLL=0.45 MVA
SHS1013
TCL=5.62 MVA
TCL=2.96 MVA
SLL=1.29 MVA
SHS1622
RD25_CF09
TCL=3.12 MVA
RD2917
TCL=4.54 MVA
SLL=2.00 MVA
RD2918
TCL=3.62 MVA
SLL=1.59 MVA
SHS2908
TCL=5.75 MVA
SLL=2.53 MVA
SHS2912
TCL=1.89 MVA
PLOT=RD30_E03
TCL=8.88 MVA
SLL=5.03 MVA
SHS2907
TCL=5.80 MVA
SLL=2.49 MVA
SHS2905
TCL=5.76 MVA
SLL=2.53 MVA
PLOT=RD30_CF03
TCL=0.60 MVA
SLL=0.34 MVA
PLOT=RD30_M01
TCL=0.65 MVA
SLL=0.37 MVA
PLOT=RD30_CF02
TCL=3.28 MVA
SLL=1.86 MVA
SHS2507
TCL=4.03 MVA
SHS1406
TCL=5.73 MVA
140.0M
A6 19-NOV-20 ISSUED FOR APPROVAL MB
SHS0306 TCL=3.07 MVA SLL=0.82 MVA SLL=2.52 MVA
SLL=2.47 MVA SLL=1.77 MVA SLL=1.77 MVA
190.0M
PLOT=RD14_MR04
TCL=1.01 MVA
2070.0M
477.0M SLL=1.20 MVA
A5 01-OCT-20 ISSUED FOR APPROVAL MB
SHS0305 SLL=0.44 MVA
TCL=1.17 MVA
SLL=0.55 MVA
PLOT=RD7_CF02
TCL=0.60 MVA
1014.0M
SHS1802 92.0M
415.0M
110.0M
550.0M 600.0M PLOT=RD32_P30
A4 24-AUG-20 ISSUED FOR APPROVAL MB
RD1727 RD3124 SHS0101 3595.0M
SLL=0.34 MVA TCL=5.97 MVA 2416.0M TCL=1.64 MVA 310.0M
TCL=5.64 MVA

260.0M SHS0905
SLL=2.64 MVA PLOT=RD14_MR03
TCL=1.02 MVA
SLL=2.51 MVA
TCL=5.79 MVA
SLL=2.57 MVA
RD1730 SHS1003
TCL=6.05 MVA
SLL=2.65 MVA 660.0M
PLOT=RD21_C33
TCL=1.25 MVA
SLL=0.55 MVA
600.0M SLL=0.93 MVA A3 07-JUL-20 ISSUED FOR APPROVAL MB
SHS0301 TCL=5.89 MVA SLL=0.45 MVA TCL=5.54 MVA TCL=5.89 MVA LOOP FEEDER PSS1-LF13
LOOP FEEDER PSS1-LF5
TCL=1.31 MVA
SLL=0.58 MVA
SLL=2.60 MVA
926.0M
177.0M 106.0M 204.0M 1962.0M 128.0M 145.0M 1143.0M 489.0M 350.0M 350.0M 570.0M 325.0M
SLL=2.47 MVA SLL=2.59 MVA
RD1819 3750.0M SHS2501 585.0M SHS2502 230.0M PLOT=RD25_M02 780.0M SHS2514 750.0M SHS2509 1370.0M PLOT=RD25_E02 210.0M RD2515 355.0M SHS2508 510.0M RD2519 370.0M RD2513
A2 02-MAR-20 ISSUED FOR APPROVAL MB
200.0M TCL=6.05 MVA TCL=0.65 MVA TCL=6.13 MVA TCL=6.10 MVA TCL=3.60 MVA TCL=3.62 MVA TCL=6.12 MVA TCL=3.08 MVA TCL=3.60 MVA SHS1407
TCL=2.99 MVA TCL=6.12 MVA
SHS0806 PLOT=RD14_MR02
TCL=0.92 MVA
PLOT=RD14_MR01 SHS0803 RD1508 PLOT=RD15_CF08
TCL=3.05 MVA
PLOT=RD15_CF05
TCL=1.00 MVA
SHS1010
TCL=5.81 MVA
RD1736 SHS1014 PLOT=RD17_M02 PLOT=RD17_CF04
3670.0M
667.0M
SHS1608
TCL=2.51 MVA
SHS1624
TCL=1.20 MVA
SHS1604
TCL=5.42 MVA
SLL=1.32 MVA SLL=2.69 MVA SLL=2.65 MVA SLL=0.37 MVA SLL=2.69 MVA SLL=2.67 MVA SLL=2.04 MVA SLL=1.59 MVA SLL=2.69 MVA SLL=1.35 MVA SLL=1.59 MVA TCL=3.87 MVA
SLL=1.71 MVA
685.0M
PLOT=RD20_C5
TCL=0.99 MVA
SLL=0.43 MVA
A1 22-DEC-19 ISSUED FOR APPROVAL MB
TCL=1.41 MVA TCL=1.60 MVA TCL=4.84 MVA TCL=4.43 MVA TCL=5.62 MVA TCL= 0.65 MVA TCL= 0.60 MVA SLL=0.53 MVA SLL=2.38 MVA
SLL=0.40 MVA SLL=0.61 MVA SLL=0.71 MVA SLL=2.21 MVA SLL=1.73 MVA SLL=0.57 MVA SLL=2.60 MVA SLL=2.47 MVA SLL= 0.37 MVA SLL= 0.34 MVA SLL=1.10 MVA

SHS0302
425.0M
275.0M
315.0M SHS1804
TCL=6.04 MVA
SLL=1.97 MVA
RD2928
TCL=3.46 MVA
RD1737
TCL=2.25 MVA SHS1307
REV. DATE DESCRIPTION APPR'D
708.0M 2400.0M TCL=5.89 MVA
SLL=2.64 MVA SLL=1.51 MVA SLL=1.00 MVA
PLOT= RD9_C14
TCL=0.99 MVA
SLL=0.43 MVA
PLOT=RD15_M01
556.0M
SHS1625
460.0M

RD2409
SLL=2.59 MVA
Client
TCL=0.65 MVA TCL=1.43 MVA 2510.0M
TCL=3.51 MVA
SLL=0.37 MVA 3803.0M SLL=0.63 MVA
935.0M SLL=1.59 MVA
3850.0M 585.0M
360.0M 475.0M
745.0M
RD1511
RD710 LOOP FEEDER PSS1-LF4 LOOP FEEDER PSS1-LF12 TCL=5.96 MVA
SHS1309
156.0M TCL=3.39 MVA PLOT= SLL=2.64 MVA
SHS0111 TCL=3.76 MVA
PLOT= RD9_C15 SLL=1.57 MVA 682.0M 1255.0M 693.0M 577.0M 490.0M 514.0M 495.0M PLOT=RD21_C30 153.0M PLOT=RD21_C28 102.0M PLOT=RD21_C29 415.0M PLOT=RD20_C4 270.0M PLOT=RD20_C3 73.0M PLOT=RD20_C2 80.0M PLOT=RD20_C1 423.0M RD17_CR02 SHS1606 665.0M SHS1605 330.0M SHS1607 5650.0M 1745.0M 120.0M 115.0M 190.0M 2020.0M RD2516 1025.0M
TCL=5.89 MVA PLOT=RD18_E02 PLOT=RD25_CF08 PLOT=RD25_CF05 PLOT=RD25_CF03 RD2512 SLL=1.65 MVA
TCL=0.99 MVA TCL= 1.10 MVA TCL= 1.10 MVA TCL= 1.08 MVA TCL= 0.99 MVA TCL= 0.99 MVA TCL= 0.99 MVA TCL= 0.80 MVA TCL=0.59 MVA 285.0M TCL=3.79 MVA TCL=5.36 MVA TCL=3.36 MVA TCL=9.41 MVA TCL=0.91 MVA TCL=2.00 MVA TCL=1.60 MVA TCL=3.26 MVA TCL=6.01 MVA
SLL=0.43 MVA 261.0M SLL=2.62 MVA
SLL= 0.48 MVA SLL= 0.48 MVA SLL= 0.47 MVA SLL= 0.43 MVA SLL= 0.43 MVA SLL= 0.43 MVA SLL= 0.35 MVA SLL=0.32 MVA SLL=1.64 MVA SLL=2.38 MVA SLL=1.51 MVA SLL=5.34 MVA SLL=0.52 MVA SLL=1.13 MVA SLL=0.91 MVA SLL=1.46 MVA SLL=2.64 MVA
SHS1901 SHS1903 SHS1712 SHS1714 SHS1705 SHS1703 SHS1701 SHS1710 SHS1708
TCL=5.92 MVA TCL=5.89 MVA TCL=3.62 MVA TCL=2.97 MVA TCL=2.92 MVA TCL=2.86 MVA TCL=1.44 MVA TCL=4.46 MVA TCL=2.32 MVA
SLL=1.10 MVA 895.0M
SLL=2.62 MVA SLL=2.59 MVA SLL=1.71 MVA SLL=1.30 MVA SLL=1.26 MVA SLL=1.26 MVA SLL=0.65 MVA SLL=1.96 MVA SHS1004 575.0M
RD1509 TCL=5.84 MVA 250.0M
SHS1623 RD1510
TCL=3.66 MVA 160.0M SLL=2.56 MVA TCL=1.17 MVA TCL=2.92 MVA
210.0M SLL=1.65 MVA SLL=0.51 MVA
PLOT= SLL=1.30 MVA
RD17_CF05 RD3216

PLOT= RD9_C18
TCL=1.06 MVA
566.0M
TCL=0.60 MVA
SLL=0.34 MVA
626.0M
TCL=5.76 MVA
SLL=2.53 MVA

RD1214
PMC
SLL=0.46 MVA 446.0M 300.0M TCL=3.76 MVA
SLL=1.65 MVA 1130.0M
LOOP FEEDER PSS1-LF3 375.0M LOOP FEEDER PSS1-LF11

SHS0906 284.0M SHS0907 986.0M PLOT=RD15_CF04 199.0M PLOT=RD15_CF13 120.0M PLOT=RD15_CF03 59.0M PLOT=RD15_CF09 56.0M PLOT=RD15_M03 492.0M SHS0409 957.0M SHS1005 691.0M SHS1007 807.0M RD1735 145.0M SHS1008 145.0M SHS1620 75.0M PLOT=RD21_C38 170.0M PLOT=RD21_C37 170.0M 2735.0M RD2308 1710.0M
PLOT=RD21_CF03
TCL=5.78 MVA TCL=5.97 MVA TCL= 0.90 MVA TCL= 1.60 MVA TCL= 0.81 MVA TCL= 2.00 MVA TCL= 0.65 MVA TCL=0.40 MVA TCL=5.94 MVA TCL=5.89 MVA TCL=3.81 MVA TCL=3.73 MVA TCL=1.22 MVA TCL=1.02 MVA TCL=0.88 MVA TCL=1.02 MVA TCL=5.36 MVA RD1614
SLL=0.40 MVA SLL=2.62 MVA SLL=2.59 MVA SLL=0.60 MVA 195.0M PLOT=RD21_C35 335.0M PLOT=RD21_CR04 90.0M PLOT=RD21_CR05 90.0M 90.0M PLOT=RD21_CR07 85.0M PLOT=RD21_CR08 160.0M
SHS0313 SLL=2.53 MVA SLL=2.62 MVA SLL= 0.51 MVA SLL= 0.91 MVA SLL= 0.46 MVA SLL= 1.13 MVA SLL= 0.37 MVA SLL=1.71 MVA SLL=1.65 MVA SHS0110 SHS0703 SLL=0.44 MVA SLL=0.38 MVA PLOT=RD21_CR06 PLOT=RD21_C22 SLL=0.58 MVA SLL=2.37 MVA TCL=2.42 MVA
SHS1709 TCL=1.12 MVA TCL=0.82 MVA TCL=0.67 MVA TCL=0.63 MVA SHS1619
TCL=5.97 MVA TCL=5.97 MVA TCL=0.75 MVA TCL=0.66 MVA TCL=0.88 MVA SLL=1.09 MVA
SHS0405 TCL=1.98 MVA SLL=0.49 MVA SLL=0.44 MVA SLL=0.36 MVA SLL=0.34 MVA
SLL=2.62 MVA SLL=2.62 MVA SLL=0.40 MVA SLL=0.36 MVA SLL=0.38 MVA
TCL=5.60 MVA 413.0M SLL=0.87 MVA
825.0M SLL=2.47 MVA
SHS0304
TCL=1.15 MVA
SLL=0.52 MVA

523.0M 580.0M
200.0M
825.0M
PLOT=RD9_CF01
TCL=1.00 MVA LOOP FEEDER PSS1-LF2
1354.0M 690.0M 460.0M Consultant
LOOP FEEDER PSS1-LF10
SLL=0.57 MVA
SHS0406 400.0M RD0712 1280.0M RD1733 896.0M RD1732 1252.0M RD1731 4059.0M SS1006 423.0M SS1009 700.0M PLOT=RD17_M07 127.0M SHS1012 976.0M SS1011 369.0M RD1726 172.0M PLOT=RD17_M01 SHS0705 395.0M 290.0M 160.0M SHS0708 RD1617
SHS1713 PLOT=RD12_M01
TCL=5.60 MVA TCL=4.50 MVA TCL=5.87 MVA TCL=4.04 MVA TCL=5.24 MVA TCL=5.89 MVA TCL=5.89 MVA TCL=0.65 MVA TCL=5.89 MVA TCL=5.89 MVA TCL=4.83 MVA TCL=0.65 MVA TCL=5.89 MVA TCL=5.82 MVA TCL=3.66 MVA
TCL=2.43 MVA TCL=0.65 MVA
SLL=2.47 MVA SLL=1.99 MVA SLL=2.59 MVA SLL=1.74 MVA SLL=2.33 MVA SLL=2.62 MVA SLL=2.59 MVA SLL=0.37 MVA SLL=2.59 MVA SLL=2.59 MVA SLL=2.16 MVA SLL=0.37 MVA SLL=2.59 MVA SHS0707 695.0M RD1212 SLL=2.57 MVA SLL=1.67 MVA
80.0M SLL=1.08 MVA SLL=0.37 MVA
SHS0309 TCL=5.89 MVA TCL=4.00 MVA
TCL=0.65 MVA SHS0107 SLL=2.59 MVA SLL=1.77 MVA
SLL=0.32 MVA TCL=5.62 MVA
SLL=2.47 MVA

PLOT=RD9_C27 240.0M
TCL=1.03 MVA
SLL=0.45 MVA

PLOT=RD9_C24
TCL=1.05 MVA
150.0M 314.0M

230.0M
Project / Contract
SLL=0.46 MVA
LOOP FEEDER PSS1-LF1 2310.0M 660.0M 480.0M LOOP FEEDER PSS1-LF9
97.0M 89.0M 106.0M 500.0M 1667.0M 1325.0M 670.0M 833.0M 1932.0M 454.0M 1937.0M 195.0M 4343.0M 598.0M 535.0M 690.0M 770.0M 1840.0M 800.0M 790.0M 300.0M 820.0M
62.0M

PLOT=RD9_C22
TCL=1.16 MVA
SLL=0.50 MVA
PLOT=RD9_C21
TCL=0.94 MVA
SLL=0.41 MVA
SHS0303
TCL=1.03 MVA
SLL=0.45 MVA
SHS0307
TCL=1.24 MVA
SLL=0.61 MVA
PLOT=RD9_C3
TCL=1.03 MVA
SLL=0.45 MVA
RD0711
TCL=2.92 MVA
SLL=1.24 MVA
RD1721
TCL=5.30 MVA
SLL=2.35 MVA
RD1722
TCL=2.81 MVA
SLL=1.24 MVA
RD1724
TCL=5.49 MVA
SLL=2.41 MVA
RD1833
TCL=2.43 MVA
SLL=1.06 MVA
RD1818
TCL=3.09 MVA
SLL=1.36 MVA
RD1615
TCL=2.68 MVA
SLL=1.18 MVA
PLOT=RD14_M01
TCL=0.65 MVA
SLL= 0.37 MVA
SHS0105
TCL=5.84 MVA
SLL=2.50 MVA
SHS0106
TCL=5.76 MVA
SLL=2.53 MVA
RD2517
TCL=6.04 MVA
SLL=2.68 MVA
RD1909
TCL=5.89 MVA
SLL=2.58 MVA
RD1910
TCL=4.79 MVA
SLL=2.11 MVA
PLOT=RD19_M01
TCL=0.65 MVA
SLL=0.37 MVA
RD1830
TCL=5.22 MVA
SLL=2.30 MVA
PLOT=RD18_M02
TCL=0.65 MVA
SLL=0.37 MVA
RD1723
TCL=4.62 MVA
SLL=2.03 MVA
RD1621
TCL=2.68 MVA
SLL=1.18 MVA
RD1616
TCL=2.67 MVA
SLL=1.20 MVA
RD1620
TCL=2.68 MVA
SLL=1.18 MVA
PLOT=RD16_CF02
TCL=0.60 MVA
SLL=0.34 MVA RIYADH CITY NORTH
ALL PHASES
Drawing Title
INTERIM POWER SUPPLY
22kV SINGLE LINE DIAGRAM
PRIMARY SUBSTATION PSS-1
CONTRACT No: JOB No:
DRAWN DESIGNED CHECKED APPROVED
ST MSD MSA MB

DATE 10-OCT-2019 ACTUAL SIZE A1


Drawing Scale. N.T.S

Drawing No.
A6
ISSUED FOR CONSTRUCTION_Rev-00 RN-02-00001-00-07-EL-PIL-DG-000311
c:\pw_working\dxb\client\p006236b\d0351524\RN-02-00001-00-07-EL-PIL-DG-000311-12.dwg
Last Saved By: P002959B Last Saved Date: 11/19/2020 6:01 PM Printed Date: 11/24/2020 4:25 PM Printed By: Randhi, Venkata
NOTES :
1. ACTUAL LOADS AND POWER CONSUMPTION ON A
NUMBER OF SIMILAR EXISTING DEVELOPMENTS IN
ABUDHABI HAVE BEEN STUDIED BY ADDC / ARCADIS.
AS ADVISED BY ADDC AND BASED ON COMPARISON
EXISTING PRIMARY SUBSTATION :- SHSPRY1
1 - PSS1 AGAINST THE ESTIMATED / CALCULATED LOADS, AN
AVERAGE ACTUAL DEMAND FACTOR OF 0.18 HAS BEEN
FROM 132/22kV, 60MVA
TRANSFORMER-1
FROM 132/22kV, 60MVA
TRANSFORMER-2
FROM 132/22kV, 60MVA
TRANSFORMER-4
FROM 132/22kV, 60MVA
TRANSFORMER-3
APPLIED AT THE TOTAL CONNECTED LOAD (TCL) LEVEL
PRIMARY SUBSTATION BY OTHERS

PRIMARY SUBSTATION BY OTHERS


BUS SECTION-1
22kV, 2500A, 31.5kA, 1s
2500A BUS SECTION-2
22kV, 2500A, 31.5kA, 1s
2500A BUS SECTION-4
22kV, 2500A, 31.5kA, 1s
2500A BUS SECTION-3
22kV, 2500A, 31.5kA, 1s
2500A
TO OBTAIN THE MAXIMUM DEMAND LOAD AT THE 22kV
630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 1250A 1250A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 1250A 1250A 1250A 1250A 1250A 1250A 630A 630A 630A 630A 630A 630A 630A 630A FEEDER LEVEL.
2500A 2500A 2500A 2500A

LEGEND :
22kV EXISTING CABLES
LP01A LP02A LP03A LP04A LP05A LP06A LP07A LP08A LP17A LP18A LP18B LP17B LP08B LP07B LP06B LP05B LP04B LP03B LP02B LP01B LP09A LP10A LP11A LP12A LP13A LP14A LP15A LP16A LP16B LP15B LP14B LP13B LP12B LP11B LP10B LP09B

TX.01
LOOP-1:
TCL=68.47 MVA
TCL=67.96
LOOP-2:
TCL=69.75 MVA
TCL=69.76
LOOP-3:
TCL=68.93 MVA
TCL=69.62
LOOP-4:
TCL=63.40 MVA
TCL=70.33
LOOP-5:
TCL=64.85 MVA
TCL=71.07
LOOP-6:
TCL=69.76 MVA
TCL=69.90
LOOP-7:
TCL=66.95 MVA
LOOP-8:
TCL=69.28 MVA
TCL=70.83
LOOP-17:
TCL=70.56 MVA
LOOP-18:
TCL=70.07 MVA
TCL=70.21
2480.0M
PLOT=RD20_E01 2780.0M
2875.0M
RD1209 6700.0M TX.02
LOOP-9:
TCL=66.73 MVA
TCL=72.08
LOOP-10:
TCL=64.22 MVA
TCL=69.40
LOOP-11:
TCL=69.09 MVA
TCL=68.86
LOOP-12:
TCL=71.50 MVA
TCL=67.35
LOOP-13:
TCL=71.62 MVA
TCL=69.44
LOOP-14:
TCL=71.12 MVA
TCL=70.97
LOOP-15:
TCL=70.42 MVA
TCL=67.69
LOOP-16:
TCL=68.82 MVA
TCL=70.32 10480.0M
3275.0M (3Cx300mm² XLPE / SWA / PVC Cu)
SLL=31.48 MVA
SLL=30.74 SLL=31.94 MVA
SLL=31.95 SLL=30.59 MVA
SLL=30.87 SLL=28.02 MVA
SLL=31.26 SLL=29.78 MVA
SLL=32.49 SLL=30.65 MVA
SLL=30.85 SLL=29.99 MVA SLL=31.86 MVA
SLL=32.74 SLL=32.05 MVA SLL=30.97 MVA 12 MVAR 12 MVAR 5183.0M 1985.0M 1690.0M 5710.0M SLL=29.90 MVA
SLL=32.20 SLL=28.43 MVA
SLL=30.78 SLL=30.82 MVA
SLL=30.72 SLL=31.84 MVA
SLL=30.35 SLL=32.84 MVA
SLL=31.40 SLL=32.29 MVA
SLL=31.59 SLL=31.74 MVA
SLL=29.75 SLL=31.02 MVA
SLL=31.75 12 MVAR 12 MVAR 2600.0M 2110.0M RD3122 435.0M 780.0M
1000kVA TCL=5.04 MVA 1295.0M TCL=4.54 MVA 5189.0M 2260.0M

22kV PROPOSED CABLES - (PSS-1)


FLL=12.26 MVA
FLL=12.23 FLL=12.55 MVA
FLL=12.56 FLL=12.41 MVA
FLL=12.53 FLL=11.41 MVA
FLL=12.66 FLL=11.67 MVA
FLL=12.79 FLL=12.56 MVA
FLL=12.58 FLL=12.69 MVA
FLL=12.72 FLL=12.29 MVA
FLL=12.75 FLL=12.70 MVA FLL=12.61 MVA
FLL=12.64 1995.0M 1000kVA FLL=12.01 MVA
FLL=12.97 FLL=11.56 MVA
FLL=12.49 FLL=12.44 MVA
FLL=12.39 FLL=12.87 MVA
FLL=12.12 FLL=12.89 MVA
FLL=12.50 FLL=12.80 MVA
FLL=12.77 FLL=12.68 MVA
FLL=12.18 FLL=12.39 MVA
FLL=12.66 TCL=5.53 MVA
CAPACITOR CAPACITOR SLL=2.86 MVA SLL=2.00 MVA CAPACITOR CAPACITOR RD3130
22/0.415kV 22/0.415kV SLL=2.51 MVA
4055.0M 2663.0M 3347.0M
BANK-1 BANK-2 PLOT=RD8_M01 BANK-4 BANK-3 TCL=3.72 MVA RD3120 SHS1404 RD3217
1735.0M 1135.0M 5295.0M SHS0604 SHS0610 SHS0817 SHS0403 TCL=0.65 MVA SPARE PSS1-LF20 RD1114
3150.0M 1867.0M 1000.0M 2210.0M 3655.0M 3965.0M 3215.0M SLL=1.64 MVA
TCL=4.66 MVA
(3Cx400mm² XLPE / SWA / PVC AL)
TCL=5.87 MVA TCL=6.00 MVA TCL=2.99 MVA TCL=5.89 MVA SLL=0.37 MVA 1000.0M 1320.0M TCL=5.89 MVA TCL=5.20 MVA TCL=4.82 MVA
RD1009 1385.0M (FOR RIYADH CITY SOUTH) SLL=2.07 MVA SLL=2.59 MVA SLL=2.31 MVA
RD1118 TCL=1.87 MVA SHS1902 SLL=2.59 MVA SLL=2.59 MVA SLL=1.33 MVA SLL=2.59 MVA SLL=2.15 MVA
IPS- 1 SHS0308 SHS0802 RD1116 PLOT=RD22_M01 SHS1106 SHS1304 RD2310 1865.0M
TCL=5.06 MVA SLL=0.82 MVA SHS1618 SS16-6 TCL=3.76 MVA 3890.0M SHS0310 RD1311 TCL=2.27 MVA RD3212 SPARE PSS1-LF19 RD2410
TCL=0.77 MVA TCL=0.76 MVA TCL=5.97 MVA TCL=2.11 MVA TCL=0.65 MVA TCL=5.49 MVA TCL=5.89 MVA
SLL=2.24 MVA TCL=0.81 MVA SLL=1.65 MVA TCL=1.06 MVA PLOT=RD23_CR02 TCL=5.35 MVA
SLL=0.62 MVA SLL=0.38 MVA SLL=2.62 MVA SLL=0.88 MVA SLL=0.37 MVA SLL=2.44 MVA SLL=2.56 MVA SLL=1.00 MVA (FOR RIYADH CITY SOUTH) TCL=5.93 MVA
SLL=0.81 MVA RD1829 575.0M PLOT=RD9_C26 SLL=0.47 MVA TCL=2.12 MVA RD3126 SLL=2.36 MVA SLL=2.61 MVA

6838.0M
1721.0M
RD0815
PLOT=RD21_C24
TCL=1.06 MVA 61.0M 635.0M 575.0M
4664.0M
TCL=5.10 MVA RD1115
SLL=2.28 MVA TCL=5.19 MVA
SLL=2.24 MVA
760.0M

SHS0607
TCL=0.99 MVA
SLL=0.43 MVA
SHS0404
TCL=5.89 MVA
SLL=2.59 MVA
SLL=1.14 MVA TCL=5.88 MVA
SLL=2.58 MVA
RD2923
1282.0M
235.0M
22kV PROPOSED CABLES - (PSS-2)
540.0M 490.0M 4950.0M 1090.0M 650.0M
478.0M

RD1119
SHS0108
TCL=5.89 MVA
TCL=5.11 MVA
SLL=2.24 MVA
SLL=0.46 MVA
PLOT=RD9_C5
TCL=0.99 MVA
SLL=0.43 MVA
RD1404
TCL=2.60 MVA
SLL=1.12 MVA
1122.0M
SHS0606
TCL=6.11 MVA
SHS1904
TCL=3.89 MVA
SHS1907
TCL=5.89 MVA
SLL=2.59 MVA 540.0M
TCL=5.89 MVA
SLL=2.59 MVA 3115.0M

SHS1801
410.0M
PLOT=RD9_C29 120.0M
400.0M

SHS1105
RD2308
TCL=5.36 MVA
SHS1402
TCL=5.89 MVA
1050.0M
535.0M
TCL=5.62 MVA
SLL=2.47 MVA SHS2301
TCL=6.00 MVA
735.0M
470.0M (3Cx400mm² XLPE / SWA / PVC AL)
SLL=2.59 MVA SLL=1.71 MVA TCL=1.08 MVA 827.0M TCL=5.89 MVA SLL=2.37 MVA SLL=2.59 MVA SLL=2.62 MVA RD3215
TCL=2.14 MVA SLL=2.56 MVA TCL=5.83 MVA PLOT=RD23_M01 RD2312
100.0M 260.0M SHS0601 SLL=0.47 MVA SLL=2.59 MVA RD3210 TCL=4.97 MVA
TCL=4.65 MVA
22kV CABLE TO BE CANCELED FOR
SLL=0.94 MVA SLL=2.57 MVA RD3121 TCL=0.65 MVA
SHS0201 SHS1911 TCL=5.89 MVA 545.0M 290.0M 595.0M TCL=5.76 MVA SLL=2.18 MVA
1250.0M SHS2403 SLL=0.37 MVA SLL=2.08 MVA
595.0M TCL=5.96 MVA TCL=3.90 MVA SLL=2.59 MVA 1650.0M SLL=2.53 MVA TCL=5.35 MVA
88.0M TCL=5.85 MVA 380.0M SLL=2.36 MVA
1163.0M RD1401 SLL=2.60 MVA 510.0M SLL=1.74 MVA SHS0609 920.0M
PLOT=RD9_C6 285.0M PLOT=RD13_E02 2620.0M SLL=2.59 MVA

772.0M
RD0816
TCL=2.00 MVA
PLOT=RD21_C23
TCL=1.01 MVA
TCL=0.99 MVA
SLL=0.43 MVA
TCL=5.29 MVA
SLL=2.41 MVA
PLOT=RD11_M02
TCL=0.65 MVA
RD1831
TCL=3.91 MVA
535.0M
SHS1910 645.0M
TCL=5.89 MVA
SLL=2.59 MVA 655.0M
RD1908
85.0M
PLOT=RD9_C30
TCL=1.08 MVA
2416.0M
RD7_IRRPS01
TCL=0.77 MVA SHS0104 RD1309
400.0M TCL=3.12 MVA
SLL=1.77 MVA SHS1503
SHS2311
TCL=5.96 MVA
SHS3007
TCL=5.89 MVA
200.0M
LOAD TRANSFER TO PSS-2
SLL=0.88 MVA SLL=0.44 MVA SLL=0.37 MVA SLL=1.76 MVA TCL=4.03 MVA SHS0602 TCL=6.07 MVA SLL=0.47 MVA RD2928
SLL=0.62 MVA TCL=5.70 MVA TCL=5.89 MVA TCL=2.94 MVA PLOT=RD23_CF01 SLL=2.61 MVA 1240.0M SLL=2.59 MVA RD3128 -
873.0M
SHS0109 95.0M
80.0M
540.0M
SHS0804
SLL=1.77 MVA TCL=5.89 MVA
SLL=2.59 MVA 810.0M
SLL=2.69 MVA TCL=3.46 MVA
SLL=1.51 MVA
RD1730
TCL=5.54 MVA
SLL=2.50 MVA SLL=2.53 MVA
1440.0M
SLL=1.27 MVA TCL=1.60 MVA
SLL=0.91 MVA SHS2302
TCL=5.76 MVA
SLL=2.52 MVA 110.0M
170.0M 945.0M
SS 1 23
TCL=5.84 MVA 650.0M 235.0M SLL=2.47 MVA 1684.0M RD1215 355.0M TCL=5.56 MVA
PLOT=RD21_C22 PLOT=RD9_C8 TCL=5.24 MVA 390.0M
SLL=2.56 MVA 485.0M PLOT=RD9_CR01 5315.0M TCL=5.49 MVA RD1113
TCL=0.84 MVA 155.0M SHS0204 SLL=2.44 MVA

SECTOR NUMBER
RD1121 TCL=0.99 MVA SLL=2.30 MVA 400.0M RD1826 1035.0M RD1720 1265.0M 465.0M 250.0M TCL=6.00 MVA
545.0M SLL=0.38 MVA TCL=5.78 MVA TCL=2.00 MVA SLL=2.41 MVA PLOT=RD23_M02 SHS1305
TCL=2.24 MVA SLL=0.43 MVA TCL=2.41 MVA RD3016 TCL=3.95 MVA 430.0M 310.0M RD2415 SLL=2.59 MVA
PLOT=RD18_CF03 SHS1803 SLL=1.26 MVA SHS2404 TCL=5.60 MVA
SLL=1.03 MVA PLOT=RD11_CF09 SLL=1.06 MVA 374.0M SLL=2.53 MVA TCL=5.65 MVA SLL=1.74 MVA SHS1103
SHS2309
TCL=5.87 MVA TCL=0.65 MVA
TCL=0.60 MVA TCL=0.60 MVA TCL=6.04 MVA TCL=6.01 MVA TCL=5.96 MVA SLL=0.37 MVA SLL=2.46 MVA
95.0M SLL=2.54 MVA TCL=5.98 MVA 155.0M RD2922 SHS2314 SLL=2.58 MVA 2200.0M
RD0817 540.0M SLL=0.34 MVA SLL=0.34 MVA SLL=2.67 MVA 418.0M SLL=2.64 MVA SLL=2.61 MVA 760.0M

SUBSTATION NUMBER
RD1117 667.0M SLL=2.58 MVA 135.0M TCL=5.89 MVA TCL=5.96 MVA
SHS1616 PLOT=RD18_M03
TCL=5.79 MVA 90.0M SHS0808 SHS0202 TCL=4.68 MVA 270.0M 200.0M SLL=2.62 MVA SLL=2.61 MVA
TCL=0.65 MVA RD1737 PLOT=RD23_CF05 460.0M
SLL=2.53 MVA 325.0M TCL=2.09 MVA TCL=5.93 MVA SLL=2.06 MVA PLOT= RD0814 RD1307
PLOT=RD9_C9 SLL=0.37 MVA PLOT=RD9_CF02 TCL=2.25 MVA SHS1505 TCL=0.84 MVA
TCL=0.99 MVA SLL=0.94 MVA SLL=2.63 MVA 475.0M RD10_CF02 1018.0M 960.0M TCL=5.51 MVA TCL=3.78 MVA
TCL=0.58 MVA SLL=1.00 MVA TCL=2.23 MVA SLL=0.48 MVA RD3129 265.0M
650.0M

22/0.415 kV SUB STATION


PLOT=RD21_C19 SLL=0.43 MVA 355.0M 758.0M SHS0603 TCL=0.60 MVA SLL=2.41 MVA 1020.0M SLL=1.72 MVA
344.0M 500.0M PLOT= SLL=0.33 MVA SLL=0.97 MVA TCL=5.42 MVA
540.0M TCL=1.12 MVA TCL=6.00 MVA SLL=0.34 MVA PLOT=RD31_CR04 915.0M
SHS0605 435.0M RD17_IRRPS01 RD3014 PLOT=RD21_CF02 575.0M SLL=2.38 MVA
SLL=0.49 MVA 340.0M SHS1905 SLL=2.59 MVA TCL=0.67 MVA
TCL=5.83 MVA TCL=0.72 MVA TCL=3.76 MVA TCL=1.00 MVA 580.0M 405.0M 640.0M
SS1- LF 17
726.0M PLOT=RD14_MR30 TCL=5.87 MVA RD2411 SLL=0.36 MVA 665.0M PLOT=RD32_CF02
52.0M TCL=2.65 MVA SLL=2.60 MVA RD1827 SLL=0.39 MVA SLL=1.65 MVA SLL=0.57 MVA 730.0M TCL=0.60 MVA
RD1120 84.0M SLL=2.58 MVA 745.0M 155.0M TCL=2.81 MVA RD2311
SLL=1.15 MVA TCL=4.00 MVA 410.0M SHS2405 SLL=0.34 MVA
TCL=3.33 MVA PLOT=RD9_C10 1818.0M SLL=1.24 MVA TCL=3.54 MVA
RD0708 SLL=1.77 MVA RD1308 TCL=6.12 MVA RD1213
SLL=1.47 MVA PLOT=RD21_C21 TCL=0.99 MVA 500.0M SLL=1.62 MVA
TCL=4.86 MVA 265.0M TCL=5.62 MVA PLOT=RD23_CF03 SLL=2.69 MVA TCL=3.48 MVA

LOOP NUMBER
TCL=1.01 MVA SLL=0.43 MVA SHS3005 SHS2315
PLOT=RD8_E01 SLL=2.14 MVA 585.0M SLL=2.47 MVA TCL=2.00 MVA 70.0M SLL=1.60 MVA
SLL=0.44 MVA 230.0M SHS1906 760.0M TCL=5.84 MVA TCL=5.81 MVA
TCL=4.24 MVA SLL=1.13 MVA 370.0M
PLOT=RD14_MR06 295.0M TCL=5.89 MVA SHS1914 SHS1706 RD1211 1400.0M SLL=2.58 MVA SLL=2.55 MVA
SLL=2.40 MVA 160.0M
SLL=2.59 MVA TCL=4.03 MVA TCL=1.51 MVA TCL=4.41 MVA SHS1501
TCL=1.58 MVA SHS0608 940.0M

LOOP FEEDER
170.0M SLL=0.69 MVA SLL=1.77 MVA 933.0M SLL=0.74 MVA SLL=1.95 MVA TCL=3.76 MVA PLOT=RD31_M01
SHS1615 TCL=5.87 MVA 580.0M PLOT=RD31_E02 420.0M
PLOT=RD9_C16 PLOT=RD10_M02 SLL=1.65 MVA TCL=0.65 MVA
616.0M SLL=2.53 MVA 5550.0M TCL=5.63 MVA RD3214
1619.0M 266.0M TCL=0.99 MVA TCL=0.65 MVA 7760.0M 8255.0M SHS2313 295.0M SLL=0.37 MVA 355.0M
410.0M 460.0M PLOT=RD13_CF02 SLL=3.19 MVA TCL=4.75 MVA
SLL=0.43 MVA SLL=0.37 MVA TCL=5.83 MVA
PLOT=RD21_C20 RD1828 TCL=0.60 MVA SLL=2.13 MVA

RD1111
TCL=5.75 MVA
TCL=1.02 MVA
SLL=0.45 MVA
36.0M
SHS0810

325.0M
TCL=5.92 MVA
SLL=2.59 MVA
RD1821
TCL=2.00 MVA
SLL=0.88 MVA
SHS1805 SHS2701
TCL=5.80 MVA
5602.0M
RD1725
TCL=3.65 MVA
SLL=1.59 MVA
PLOT=
RD17_CR02
TCL=0.59 MVA
RD0813
TCL=5.32 MVA
260.0M SLL=0.34 MVA 217.0M
SLL=2.56 MVA SHS3003
TCL=5.87 MVA
SLL=2.59 MVA
400.0M

SHS2407
380.0M
PRIMARY SUBSTATION NO.1
TCL=5.88 MVA SHS2906 SLL=0.32 MVA SLL=2.33 MVA RD3135 TCL=5.89 MVA
SLL=2.57 MVA SHS0901 220.0M PLOT=RD11_E02
PLOT=RD9_C17 SLL=2.59 MVA SLL=2.55 MVA TCL=5.71 MVA 740.0M TCL=1.06 MVA SLL=2.59 MVA
TCL=5.84 MVA TCL=4.66 MVA PLOT= 620.0M 960.0M
88.0M TCL=0.99 MVA PLOT=RD14_MR07 130.0M SLL=2.51 MVA 710.0M SLL=0.47 MVA
1475.0M SLL=2.56 MVA SLL=2.64 MVA 7515.0M RD23_CF06
TCL=1.16 MVA SHS1908 SHS1202
EXISTING SUBSTATION
SHS1614 SLL=0.43 MVA 350.0M RD1727 PLOT=RD20_CR03 SHS2304 785.0M
TCL=5.98 MVA RD1310 TCL=0.90 MVA SHS2908 SHS1401
SLL=0.51 MVA 120.0M TCL=6.43 MVA TCL=5.64 MVA RD1731 TCL=1.11 MVA TCL=5.89 MVA SHS1303
TCL=2.30 MVA SLL=2.64 MVA SHS1923 TCL=5.92 MVA SLL=0.51 MVA TCL=5.75 MVA RD2919 RD3133 TCL=5.84 MVA
SLL=2.59 MVA SLL=2.51 MVA 160.0M TCL=5.24 MVA SLL=0.60 MVA 855.0M SLL=2.62 MVA TCL=5.89 MVA
SLL=1.11 MVA TCL=0.81MVA 430.0M SLL=2.59 MVA SLL=2.53 MVA TCL=2.00 MVA TCL=2.80 MVA SLL=2.56 MVA
SLL=2.33 MVA RD2409 SLL=2.59 MVA RD1511
SLL=0.81 MVA 3300.0M SLL=0.88 MVA SLL=1.23 MVA 590.0M
600.0M TCL=5.96 MVA
416.0M 173.0M 690.0M TCL=3.51 MVA
220.0M 175.0M RD1911
PLOT=RD9_C7 1252.0M SLL=1.59 MVA 790.0M SLL=2.64 MVA
PLOT=RD14_MR08 PLOT=RD11_CF07 235.0M TCL=2.28 MVA 415.0M
245.0M TCL=0.99 MVA TCL=1.02 MVA PLOT=RD18_M07 SLL=1.03 MVA PLOT= SHS2312
52.0M TCL=0.82 MVA 650.0M SHS1013 349.0M SHS2408
SLL=0.43 MVA RD1008 TCL=0.65 MVA 620.0M RD3015 RD17_CF05 225.0M TCL=5.76 MVA
SHS0401 SLL=0.45 MVA SLL=0.46 MVA 80.0M 1250.0M 890.0M 280.0M TCL=5.85 MVA
TCL=6.16 MVA RD1820 TCL=5.62 MVA TCL=5.58 MVA TCL=0.60 MVA SLL=2.52 MVA SHS2316

EXISTING SUBSTATION
PLOT=RD11_CF08 PLOT=RD21_C2 SLL=0.37 MVA RD1619 280.0M SLL=2.58 MVA
TCL=5.90 MVA SLL=2.65 MVA SLL=2.47 MVA SLL=2.50 MVA TCL=6.04 MVA
TCL=0.90 MVA TCL=1.11 MVA TCL=2.00 MVA SHS2702 TCL=3.89 MVA SLL=0.34 MVA SHS2912 220.0M
SLL=2.59 MVA SHS1629 RD2920 SLL=2.64 MVA
SLL=0.51 MVA RD1512 SLL=0.49 MVA SLL=0.88 MVA TCL=5.89 MVA SLL=1.71 MVA PLOT=RD20_CR02 SHS1502 RD2309 TCL=1.89 MVA SHS2305 590.0M
117.0M 220.0M 345.0M TCL=3.02 MVA TCL=5.67 MVA
TCL=3.01 MVA 625.0M SLL=2.59 MVA RD1732 TCL=0.75 MVA TCL=1.80 MVA TCL=3.89 MVA SLL=0.82 MVA TCL=5.83 MVA
SLL=1.32 MVA SLL=2.57 MVA

TO BE CANCELED (TOWN HOUSE AREA)


SLL=1.33 MVA PLOT=RD9_101A PLOT=RD14_MR09 235.0M RD1832 SLL=2.56 MVA SHS2303
SHS1806 515.0M TCL=4.04 MVA SLL=0.40 MVA SLL=0.78 MVA SLL=1.71 MVA
TCL=2.96 MVA TCL=1.02 MVA TCL=1.08 MVA 758.0M TCL=5.83 MVA 425.0M 895.0M
PLOT=RD11_CF10 425.0M TCL=6.03 MVA SLL=1.74 MVA SHS0103
460.0M SLL=1.29 MVA SLL=0.45 MVA SLL=0.53 MVA SLL=2.56 MVA PLOT=
TCL=0.94 MVA SLL=2.64 MVA SHS1016 TCL=5.85 MVA 365.0M
1150.0M 375.0M 445.0M SHS1302 RD12_CF04
PLOT=RD21_C14 97.0M SLL=0.53 MVA SHS1915 TCL=5.93 MVA 896.0M SLL=2.58 MVA 300.0M RD2414 720.0M
TCL=6.12 MVA 510.0M SLL=2.60 MVA TCL=5.53 MVA TCL=0.60 MVA
TCL=1.18 MVA 360.0M 470.0M 260.0M 270.0M TCL=4.16 MVA
190.0M PLOT=RD9_C23 210.0M SLL=2.69 MVA 335.0M SLL=2.50 MVA SLL=0.34 MVA
SLL=0.52 MVA 990.0M 600.0M 160.0M PLOT=RD31_CF02 SLL=1.83 MVA
TCL=0.99 MVA PLOT=RD14_MR10 195.0M SHS1909 SHS1504
160.0M SHS1208 SHS2307 SHS2306 TCL=0.60 MVA RD1510
SLL=0.43 MVA TCL=1.03 MVA RD3013 SHS1626 TCL=1.73 MVA 760.0M PLOT=RD30_E03
135.0M TCL=5.99 MVA SHS1008 TCL=6.03 MVA SLL=0.34 MVA
473.0M 2899.0M TCL=5.89 MVA 280.0M TCL=4.95 MVA SLL=0.75 MVA TCL=8.88 MVA TCL=5.83 MVA TCL=2.92 MVA
SLL=0.45 MVA SLL=2.63 MVA TCL=5.49 MVA TCL=3.73 MVA SHS1707 SHS2310 SLL=2.64 MVA

PROPOSED PUBLIC SUBSTATION


PLOT=RD11_CF04 PLOT=RD11_CF03 695.0M SLL=2.59 MVA SLL=2.21 MVA SLL=5.03 MVA SLL=2.56 MVA 570.0M SLL=1.30 MVA
85.0M SHS2705 SLL=2.47 MVA SLL=1.65 MVA TCL=5.62 MVA 670.0M
TCL=2.00 MVA RD1825 RD1738
109.0M TCL=3.47 MVA SHS2603 TCL=5.89 MVA SHS2401 SLL=2.49 MVA
SLL=1.13 MVA PLOT=RD15_M02 SHS0203 TCL=1.06 MVA RD1733 860.0M
PLOT=RD21_C15 SLL=1.97 MVA TCL=5.44 MVA TCL=5.91 MVA SLL=2.59 MVA TCL=5.85 MVA
TCL=0.65 MVA SHS0311 290.0M TCL=5.66 MVA 1540.0M SLL=0.47 MVA TCL=5.87 MVA PLOT=RD29_M02
TCL=1.03 MVA SLL=2.36 MVA SLL=2.59 MVA 395.0M SLL=2.60 MVA
SLL=0.37 MVA PLOT=RD14_MR19 SLL=2.48 MVA 145.0M SLL=2.59 MVA TCL=0.65 MVA SHS1403
SLL=0.45 MVA 615.0M
TCL=1.00 MVA 415.0M SLL=0.37 MVA TCL=5.73 MVA SHS1301
SHS0312 260.0M 450.0M 342.0M 680.0M 5758.0M
SLL=0.44 MVA 510.0M 9043.0M SLL=2.53 MVA TCL=5.84 MVA
LOOP FEEDER PSS1-LF18
RD707 PLOT=RD9_C25 250.0M 425.0M SHS1508 SHS2907 SLL=2.56 MVA
430.0M SHS1628

140.0M
TCL=3.96 MVA
SLL=1.76 MVA
PLOT=RD21_C18
TCL=0.93 MVA
128.0M TCL=0.99 MVA
SLL=0.43 MVA 275.0M
PLOT=RD14_MR20 525.0M
RD1112
RD2709
TCL=3.76 MVA
758.0M
LOOP FEEDER PSS1-LF17
SHS1913
TCL=4.03 MVA
SLL=1.77 MVA
590.0M
490.0M
SHS1207
TCL=6.30 MVA
SLL=2.59 MVA
SHS1017
TCL=5.89 MVA
SLL=2.59 MVA
RD3012
TCL=3.76 MVA
RD1735
TCL=3.81 MVA
SLL=1.71 MVA
TCL=3.87 MVA
SLL=1.71 MVA
TCL=2.74 MVA
SLL=1.19 MVA
TCL=5.80 MVA
SLL=2.49 MVA
RD3134
TCL=2.62 MVA
SLL=1.16 MVA 145.0M
RD3125
TCL=5.67 MVA
SLL=2.58 MVA
1130.0M
PROPOSED BUILDING INTEGRATED
114.0M TCL=3.69 MVA SLL=1.65 MVA

SUBSTATION
SLL=0.41 MVA TCL=1.00 MVA SLL=1.68 MVA SHS2602 938.0M 150.0M
PLOT=RD9_102A SLL=1.71 MVA SHS0102 PLOT=
392.0M SLL=0.44 MVA TCL=5.78 MVA 1251.0M 2600.0M
TCL=1.98 MVA LOOP FEEDER PSS1-LF17 TCL=5.82 MVA RD29_CF05
PLOT=RD11_M01 SLL=2.53 MVA 807.0M
SLL=0.86 MVA RD1007 SHS2704 325.0M SLL=2.57 MVA TCL=0.60 MVA
TCL=0.65 MVA 645.0M 160.0M 2510.0M
216.0M TCL=5.94 MVA 1690.0M 200.0M 464.0M 1450.0M 200.0M 490.0M 335.0M 435.0M TCL=5.89 MVA PLOT=RD21_C11 SHS2402 SLL=0.34 MVA
SLL=0.37 MVA SHS2905 SHS3016 RD2921 PLOT=RD25_CF11
165.0M SLL=2.65 MVA 1030.0M SLL=2.59 MVA 985.0M SHS1018 TCL=1.02 MVA TCL=6.12 MVA RD3123
PLOT=RD21_C17 TCL=5.76 MVA TCL=5.89 MVA TCL=5.35 MVA TCL=0.60 MVA
SHS0902 PLOT=RD14_MR21 TCL=3.95 MVA SLL=0.45 MVA 630.0M SLL=2.69 MVA TCL=5.17 MVA 550.0M 585.0M
TCL=0.91 MVA 325.0M SLL=2.53 MVA SLL=2.62 MVA SLL=2.36 MVA SLL=0.34 MVA 1070.0M
TCL=5.98 MVA 113.0M TCL=1.00 MVA PLOT=RD11_CF06 RD2708 RD2520 SHS2510 PLOT=RD25_CF10 SHS1917 SHS1916 RD1822 SHS1912 RD1824 SLL=1.74 MVA 660.0M SHS1002 RD1614
SLL=2.27 MVA
SLL=2.63 MVA SLL=0.40 MVA PLOT=RD9_MU01 SLL=0.44 MVA TCL=0.94 MVA TCL=4.73 MVA TCL=3.62 MVA TCL=6.12 MVA TCL=0.90 MVA TCL=4.03 MVA TCL=3.82 MVA TCL=4.43 MVA TCL=4.03 MVA TCL=2.30 MVA 410.0M SHS1204 SHS1007 TCL=5.89 MVA TCL=2.42 MVA
SLL=2.68 MVA SLL=1.77 MVA SLL=1.70 MVA SLL=1.94 MVA SLL=1.77 MVA SLL=1.00 MVA TCL=5.89 MVA SLL=2.60 MVA SHS0702
TCL=1.98 MVA SLL=0.53 MVA SLL=2.06 MVA SLL=1.60 MVA SLL=0.51 MVA TCL=6.03 MVA SHS1627 SHS2317 SLL=1.09 MVA
170.0M TCL=5.89 MVA
262.0M
354.0M 102.0M
SLL=0.86 MVA

235.0M 325.0M
SHS2601
TCL=5.89 MVA
SLL=2.59 MVA
665.0M
SLL=2.59 MVA
975.0M
RD3010
SLL=2.59 MVA

691.0M
PLOT=RD21_C12
TCL=1.10 MVA
SLL=0.48 MVA
SLL=2.59 MVA TCL=2.85 MVA
SLL=1.18 MVA
SHS1506
TCL=3.23 MVA
SLL=1.44 MVA
290.0M
547.0M 830.0M
505.0M
SHS3009
TCL=5.97 MVA
SLL=2.62 MVA
TCL=5.81 MVA
SLL=2.55 MVA
RD3211
PROPOSED CABLE CUT & JOINT WITH
PLOT=RD14_M01 PLOT=RD21_C16 SHS0809 SHS1015 TCL=4.85 MVA 770.0M SHS3006 TCL=3.62 MVA
TCL=0.65 MVA
SLL= 0.37 MVA
TCL=1.04 MVA
SLL=0.45 MVA
SHS0801
634.0M TCL=1.46 MVA
SLL=0.65 MVA
SHS0205
170.0M
PLOT=RD11_CF02
TCL= 1.60 MVA
LOOP FEEDER PSS1-LF8

SHS2706
550.0M
TCL=5.89 MVA
SLL=2.59 MVA
SLL=2.13 MVA
332.0M 2495.0M
PLOT=RD30_CF03
TCL=0.60 MVA
SLL=0.34 MVA
RD2929
TCL=4.70 MVA
SLL=2.60 MVA
SHS2902
TCL=5.89 MVA
SLL=2.59 MVA
LOOP FEEDER PSS1-LF16
TCL=5.84 MVA
SLL=2.56 MVA
639.0M
155.0M PLOT=RD23_E01
TCL=4.82 MVA
SLL=1.59 MVA
3Cx400mm² XLPE / SWA / PVC AL
TCL=2.41 MVA TCL=5.92 MVA 445.0M PLOT=RD20_CR04 295.0M SHS2406 7604.0M
SLL= 0.91 MVA TCL=5.87 MVA SHS1005 320.0M SLL=2.73 MVA 230.0M
570.0M SLL=1.06 MVA SLL=2.59 MVA 650.0M TCL=1.43 MVA RD2925
SLL=2.59 MVA 150.0M TCL=5.94 MVA 232.0M TCL=5.98 MVA
112.0M LOOP FEEDER PSS1-LF8 SHS1203 SHS1611 SLL=0.76 MVA SLL=2.64 MVA TCL=5.89 MVA
150.0M 278.0M SLL=2.62 MVA
TCL=5.89 MVA 155.0M SLL=2.59 MVA
PLOT=RD21_C13 RD3136

RD1615
195.0M

TCL=2.68 MVA
SHS0402
TCL=5.89 MVA
TCL=1.14 MVA
SLL=0.50 MVA
205.0M
PLOT=RD14_MR28
PLOT=RD14_MR22
TCL=1.17 MVA
SLL=0.51 MVA
10725.0M 785.0M 250.0M 1195.0M 665.0M 365.0M 540.0M
SLL=2.59 MVA
PLOT=RD17_M08
TCL=0.65 MVA
SLL=0.37 MVA
SHS2901
TCL=5.87 MVA
SLL=2.59 MVA
957.0M

PLOT=RD8_M02
PLOT=RD21_C7
TCL=1.04 MVA 450.0M
SHS1507
TCL=1.40 MVA
SLL=0.62 MVA PLOT=RD30_M01
SHS3015
TCL=5.89 MVA
SLL=2.60 MVA
445.0M 485.0M 635.0M 3020.0M 775.0M 140.0M 1150.0M 1295.0M 785.0M 636.0M TCL=1.46 MVA
SLL=0.65 MVA
PLOT=RD25_M01
TCL=0.65 MVA
SLL=0.37 MVA
700.0M
RD1617
1500KVA TRANSFORMER
SLL=2.59 MVA SHS0903 TCL=1.73 MVA TCL=0.65 MVA TCL=3.66 MVA
SLL=1.18 MVA TCL=0.65 MVA SLL=0.45 MVA SHS3004
TCL=5.97 MVA SLL=0.75 MVA SHS3001 PLOT=RD28_E02 RD2806 RD2804 SHS2802 SHS2801 RD2607 SLL=0.37 MVA RD3011 SHS2903 SHS2904 SHS3010 RD2931 SHS3008 RD2930 SHS3002
SLL=0.37 MVA PLOT=RD21_C31 SLL=1.67 MVA
SLL=2.62 MVA 900.0M TCL=5.89 MVA TCL= 8.07 MVA TCL=3.87 MVA TCL=4.27 MVA TCL=5.89 MVA TCL=5.89 MVA TCL=4.41 MVA 365.0M SHS1001 TCL=4.68 MVA TCL=5.76 MVA TCL=5.89 MVA TCL=5.85 MVA TCL=1.60 MVA TCL=5.89 MVA TCL=1.06 MVA TCL=5.97 MVA TCL=5.91 MVA
TCL=1.19 MVA
SHS1617
88.0M PLOT=RD14_MR23
TCL=1.38 MVA
200.0M SLL=2.59 MVA SLL= 4.58 MVA SLL=1.71 MVA SLL=1.89 MVA SLL=2.59 MVA SLL=2.59 MVA SLL=1.94 MVA 720.0M 190.0M

SHS1019
SHS0409
TCL=0.40 MVA
SLL=0.40 MVA
TCL=5.89 MVA
SLL=2.59 MVA 100.0M
PLOT=RD21_C6
SLL=0.52 MVA

380.0M
SLL=2.06 MVA SLL=2.53 MVA SLL=2.59 MVA SLL=2.59 MVA SLL=0.71 MVA SLL=2.59 MVA SLL=0.47 MVA SLL=2.62 MVA SLL=2.63 MVA
601.0M
715.0M
RD3213
1250KVA TRANSFORMER
PLOT=RD14_MR27 SHS0206 SHS1201 TCL=5.97 MVA 650.0M TCL=4.01 MVA
SLL=0.60 MVA SHS2803 1115.0M
1937.0M SHS1613 TCL=0.89 MVA TCL=5.76 MVA TCL=5.93 MVA SLL=2.62 MVA TCL=1.01 MVA 225.0M SLL=1.77 MVA
TCL=5.88 MVA 295.0M RD2927 645.0M
SLL=0.39 MVA SLL=2.56 MVA LOOP FEEDER PSS1-LF7 SLL=2.61 MVA SLL=0.44 MVA
SLL=2.58 MVA
RD1818
TCL=3.09 MVA
SLL=1.36 MVA
258.0M
445.0M

PLOT=RD21_C10
TCL=1.04 MVA
100.0M

SHS0805 470.0M
500.0M
2830.0M 790.0M
PLOT=RD21_C27
TCL=1.18 MVA
425.0M PLOT=RD30_CF02
TCL=3.28 MVA
SLL=1.86 MVA
TCL=3.33 MVA
SLL=1.47 MVA
LOOP FEEDER PSS1-LF15
RD2926
TCL=5.35 MVA
SLL=2.39 MVA
SHS2318
TCL=5.93 MVA
SLL=2.60 MVA RD2518
230.0M 1000KVA TRANSFORMER
505.0M SHS0807 185.0M SLL=0.51 MVA
SLL=0.45 MVA TCL=2.33MVA 145.0M SHS1610 TCL=4.31 MVA
TCL=5.22 MVA PLOT= RD1729 RD3131 PLOT=RD15_M03 SHS1509
SLL=1.03 MVA 12750.0M LOOP FEEDER PSS1-LF7 650.0M SLL=1.95 MVA
RD16_CF01A TCL=5.90 MVA TCL=5.33 MVA TCL= 0.65 MVA

630KVA TRANSFORMER
150.0M SLL=2.30 MVA TCL=0.50 MVA 510.0M
TCL=0.98 MVA SLL=2.61 MVA SLL=2.34 MVA SLL= 0.37 MVA SLL=0.50 MVA 524.0M
617.0M
PLOT=RD21_C8 540.0M 610.0M 425.0M 305.0M 345.0M 1520.0M 180.0M 670.0M 185.0M SLL= 0.56 MVA 145.0M
128.0M 340.0M SHS3013 530.0M SHS3014 420.0M RD2924 300.0M SHS3011 435.0M SHS3012 385.0M PLOT=RD29_CF04 500.0M PLOT=RD29_M01
454.0M PLOT=RD15_CF11 TCL=1.08 MVA PLOT=RD14_MR26 PLOT=RD21_C26 TCL=5.76 MVA TCL=5.89 MVA SHS1405
531.0M TCL=5.76 MVA TCL=3.87 MVA TCL=5.74 MVA TCL=0.60 MVA TCL=0.65 MVA 535.0M PLOT=RD16_CF02
TCL=0.60 MVA SLL=0.47 MVA 270.0M PLOT=RD21_C4 876.0M TCL=5.89 MVA
TCL=0.99 MVA TCL=0.99 MVA SLL=2.53 MVA SLL=2.53 MVA SLL=1.71 MVA SLL=2.59 MVA SLL=2.59 MVA SLL=0.34 MVA SLL=0.37 MVA 620.0M TCL=0.60 MVA
RD1833 SLL=0.34 MVA SLL=0.43 MVA SHS2604 SHS2605 SHS2703 RD2711 PLOT=RD28_CF02 110.0M TCL=1.09 MVA SLL=0.43 MVA SLL=2.59 MVA
RD1402 RD2606 RD2712 PLOT=RD28_CR01 PLOT=RD28_M01 RD2805 575.0M SLL=0.34 MVA
TCL=2.43 MVA RD709 SLL=0.48 MVA
TCL=5.83 MVA TCL=3.70 MVA TCL=5.89 MVA TCL=3.37 MVA TCL=2.43 MVA TCL= 0.60 MVA 425.0M
500KVA TRANSFORMER
TCL=4.27 MVA TCL=3.34 MVA TCL=1.73 MVA TCL= 0.71 MVA TCL= 0.65 MVA RD1622
SLL=1.06 MVA TCL=1.08 MVA 90.0M SLL=2.56 MVA SLL=1.66 MVA SLL=2.59 MVA SLL=1.50 MVA SLL= 0.38 MVA SLL= 0.37 MVA SLL=1.10 MVA SLL= 0.34 MVA PLOT=
SLL=1.89 MVA SLL=1.49 MVA SLL=0.77 MVA TCL=4.30 MVA RD1728 590.0M
SLL=0.47 MVA SLL=1.88 MVA PLOT=RD17_M03 RD30_E04
PLOT=RD14_MR25 TCL=5.73 MVA SHS2319
TCL=0.65 MVA RD0812 TCL=2.62 MVA
606.0M TCL=0.98 MVA SLL=2.53 MVA 330.0M TCL=5.80 MVA
SLL=0.37 MVA TCL=5.57 MVA SLL=1.49 MVA SHS2506
SLL=0.43 MVA SLL=2.56 MVA SHS1306
SLL=2.44 MVA TCL=6.08 MVA
1932.0M

410.0M
SHS1612 68.0M
PLOT=RD14_MR24 PLOT=RD14_M02
165.0M
305.0M
PLOT=RD16_E02 2180.0M
PLOT=RD31_M08
TCL=0.65 MVA
SLL=0.37 MVA
PLOT=RD15_CF09
TCL= 2.00 MVA
SLL= 1.13 MVA
SHS1609
TCL=2.54 MVA
130.0M 550.0M
RD2514
1900.0M SLL=2.67 MVA TCL=5.80 MVA
SLL=2.58 MVA
820.0M
630A CIRCUIT BREAKER
RD1724 TCL=1.04 MVA TCL=7.19 MVA SLL=1.13 MVA TCL=6.12 MVA LOOP FEEDER PSS1-LF14 565.0M

(WITH DRAWABLE TYPE)


TCL=0.65 MVA
TCL=5.49 MVA SLL=0.45 MVA SLL= 4.08 MVA RD1823 SHS1621 SLL=2.69 MVA
SLL=0.37 MVA SHS0706
SLL=2.41 MVA 606.0M TCL=3.22 MVA 531.0M 320.0M RD1210 TCL=1.28 MVA SHS1601 700.0M TCL=5.87 MVA
140.0M LOOP FEEDER PSS1-LF6 SLL=1.41 MVA TCL=5.28 MVA SLL=0.62 MVA
SHS1711 TCL=3.44 MVA SLL=2.59 MVA
420.0M 570.0M 475.0M 180.0M 85.0M 375.0M 160.0M 115.0M 145.0M 205.0M 170.0M 140.0M 200.0M 3110.0M 575.0M SLL=2.35 MVA
TCL=2.67 MVA PLOT=RD14_MR05 290.0M 250.0M SLL=1.53 MVA 595.0M
SHS0904 TCL=0.94 MVA 915.0M 665.0M 570.0M 1185.0M

EARTHING SWITCH
SLL=1.27 MVA 1290.0M 895.0M 1720.0M 140.0M 9080.0M
TCL=6.01 MVA SLL=0.41 MVA RD1620
833.0M SLL=2.63 MVA 1665.0M 522.0M TCL=2.68 MVA
SHS0811 SHS0812 SHS0813 SHS0815 SHS0816 SHS1603 130.0M PLOT=
PLOT=RD14_MR29 PLOT=RD14_MR18 PLOT=RD14_MR17 PLOT=RD14_MR16 PLOT=RD14_MR15 PLOT=RD14_MR14 PLOT=RD14_MR13 PLOT=RD14_MR12 PLOT=RD14_MR11 RD2707 RD3132 RD2412 RD2413 SHS2504 SHS2503 SHS2505 PLOT=RD25_CF07 PLOT=RD25_CF01 RD2917 RD2918 SLL=1.18 MVA
TCL=4.41 MVA TCL=1.46 MVA TCL=1.33 MVA TCL=1.46 MVA TCL=2.96 MVA RD25_CF09 SHS1406 140.0M
RD1722 TCL=3.37 MVA TCL=0.97 MVA TCL=1.00 MVA TCL=1.00 MVA TCL=1.00 MVA TCL=1.03 MVA TCL=1.02 MVA TCL=1.00 MVA TCL=1.03 MVA TCL=5.89 MVA TCL=5.69 MVA SHS1622 TCL=4.59 MVA TCL=3.55 MVA TCL=6.08 MVA TCL=6.12 MVA TCL=6.12 MVA TCL=4.14 MVA TCL=1.10 MVA TCL=4.54 MVA TCL=3.62 MVA SHS2507
1110.0M 40.0M SLL=1.94 MVA SLL=0.65 MVA SLL=0.59 MVA SLL=0.65 MVA PLOT=RD15_CF03 RD1734 SLL=1.29 MVA TCL=3.12 MVA TCL=5.73 MVA
TCL=2.81 MVA SLL=1.47 MVA SLL=0.42 MVA SLL=0.44 MVA SLL=0.44 MVA SLL=0.44 MVA SLL=0.45 MVA SLL=0.45 MVA SLL=0.44 MVA SLL=0.45 MVA SLL=2.59 MVA SLL=2.52 MVA TCL=3.09 MVA SLL=2.06 MVA SLL=1.58 MVA SLL=2.66 MVA SLL=2.69 MVA SLL=2.69 MVA SLL=2.35 MVA SLL=0.62 MVA SLL=2.00 MVA SLL=1.59 MVA TCL=4.03 MVA
PLOT=RD14_MR04 TCL= 0.81 MVA TCL=3.28 MVA 540.0M SLL=1.77 MVA SLL=2.52 MVA
SLL=1.24 MVA SLL=1.20 MVA SLL=1.77 MVA

STATION TRANSFORMER
TCL=1.01 MVA SLL= 0.46 MVA SLL=1.45 MVA
SLL=0.44 MVA

1014.0M 300.0M 300.0M


PLOT=RD7_CF02 200.0M 110.0M
92.0M 600.0M
670.0M TCL=0.60 MVA RD2710 PLOT=RD32_P30

CAPACITOR BANK
PLOT=RD14_MR03 169.0M SHS0101 SHS1602 3595.0M
RD1721 SLL=0.34 MVA TCL=5.96 MVA TCL=6.05 MVA PLOT=RD21_C33 TCL=1.64 MVA
SHS1802 TCL=1.02 MVA TCL=3.95 MVA LOOP FEEDER PSS1-LF13
TCL=5.30 MVA TCL=5.97 MVA SLL=2.61 MVA SLL=2.65 MVA TCL=1.25 MVA 600.0M SLL=0.93 MVA
SHS0905 SLL=0.45 MVA 675.0M SHS2308 660.0M SLL=1.78 MVA
SLL=2.35 MVA SLL=2.64 MVA 477.0M SLL=0.55 MVA
TCL=5.89 MVA TCL=6.03 MVA RD1616
LOOP FEEDER PSS1-LF5 TCL=2.67 MVA
SLL=2.60 MVA SLL=2.64 MVA
SLL=1.20 MVA

1325.0M
177.0M 106.0M 204.0M 1962.0M 128.0M 145.0M 1143.0M 489.0M 350.0M 350.0M 570.0M 325.0M

SHS1608
200.0M
SHS1624
RD1819
TCL=2.99 MVA
SLL=1.32 MVA
3750.0M SHS2501
TCL=6.12 MVA
SLL=2.69 MVA
585.0M SHS2502
TCL=6.05 MVA
SLL=2.65 MVA
230.0M PLOT=RD25_M02 780.0M
TCL=0.65 MVA
SLL=0.37 MVA
SHS2514
TCL=6.13 MVA
SLL=2.69 MVA
750.0M SHS2509
TCL=6.10 MVA
SLL=2.67 MVA
1370.0M PLOT=RD25_E02 210.0M
TCL=3.60 MVA
SLL=2.04 MVA
RD2515
TCL=3.62 MVA
SLL=1.59 MVA
355.0M SHS2508
TCL=6.12 MVA
SLL=2.69 MVA
510.0M RD2519
TCL=3.08 MVA
SLL=1.35 MVA
370.0M RD2513
TCL=3.60 MVA
SLL=1.59 MVA
SHS1407
TCL=3.87 MVA
BUS DUCT
RD0711 SHS0806 PLOT=RD14_MR02 PLOT=RD14_MR01 SHS0803 RD1508 PLOT=RD15_CF08 PLOT=RD15_CF05 SHS1010 RD1736 SHS1014 PLOT=RD17_M02 PLOT=RD17_CF04 TCL=1.20 MVA SLL=1.71 MVA
926.0M TCL=2.51 MVA 685.0M
TCL=2.92 MVA TCL=0.92 MVA TCL=1.41 MVA TCL=1.60 MVA TCL=4.84 MVA TCL=3.05 MVA TCL=1.00 MVA TCL=5.81 MVA TCL=4.43 MVA TCL=5.62 MVA TCL= 0.65 MVA TCL= 0.60 MVA PLOT=RD15_CF13 SLL=0.53 MVA
SLL=1.10 MVA
SLL=1.24 MVA
275.0M
356.0M
SLL=0.40 MVA SLL=0.61 MVA SLL=0.71 MVA SLL=2.21 MVA SLL=1.73 MVA SLL=0.57 MVA SLL=2.60 MVA SLL=1.97 MVA SLL=2.47 MVA SLL= 0.37 MVA SLL= 0.34 MVA 2070.0M TCL= 1.60 MVA
SLL= 0.91 MVA
SHS1003
TCL=5.89 MVA
SLL=2.59 MVA
708.0M
550.0M SHS1307 790.0M
OPEN LOOP
SHS1804 TCL=5.89 MVA
TCL=6.04 MVA RD3124 460.0M SHS1604 SLL=2.59 MVA

DETAILED DESIGN
SLL=2.64 MVA TCL=5.79 MVA TCL=5.42 MVA
PLOT=RD15_M01 SHS1625 2600.0M
1667.0M TCL=0.65 MVA SLL=2.57 MVA SLL=2.38 MVA
TCL=1.43 MVA
SLL=0.37 MVA 198.0M LOOP FEEDER PSS1-LF12
SLL=0.63 MVA RD1621
PLOT=RD9_C3 585.0M TCL=2.68 MVA
360.0M 475.0M
TCL=1.03 MVA 3803.0M SLL=1.18 MVA
SLL=0.45 MVA 935.0M
RD710 LOOP FEEDER PSS1-LF4 1730.0M SHS1309
TCL=3.39 MVA
SLL=1.57 MVA 682.0M 1255.0M 693.0M 577.0M 490.0M 514.0M 495.0M 153.0M 102.0M 415.0M 270.0M 73.0M 80.0M 423.0M 2620.0M
SHS0111
TCL=5.89 MVA
SHS1606 665.0M SHS1605 330.0M SHS1607 5650.0M PLOT=RD18_E02 1745.0M PLOT=RD25_CF08 120.0M PLOT=RD25_CF05 115.0M PLOT=RD25_CF03 190.0M RD2512 2020.0M RD2516
TCL=3.76 MVA
SLL=1.65 MVA
A6 19-NOV-20 ISSUED FOR APPROVAL MB
285.0M TCL=3.79 MVA TCL=5.36 MVA TCL=3.36 MVA TCL=9.41 MVA TCL=0.91 MVA TCL=2.00 MVA TCL=1.60 MVA TCL=3.26 MVA TCL=6.01 MVA
300.0M SLL=2.62 MVA

SHS0307
500.0M
SHS1901
TCL=5.92 MVA
SHS1903
TCL=5.89 MVA
SHS1712
TCL=3.62 MVA
SHS1714
TCL=2.97 MVA
SHS1705
TCL=2.92 MVA
SHS1703
TCL=2.86 MVA
SHS1701
TCL=1.44 MVA
PLOT=RD21_C30 PLOT=RD21_C28
TCL= 1.10 MVA TCL= 1.10 MVA
PLOT=RD21_C29
TCL= 1.08 MVA
PLOT=RD20_C4
TCL= 0.99 MVA
PLOT=RD20_C3
TCL= 0.99 MVA
PLOT=RD20_C2
TCL= 0.99 MVA
PLOT=RD20_C1
TCL= 0.80 MVA
SHS1710
TCL=4.46 MVA PLOT=RD15_CF04 556.0M
SHS1708
TCL=2.32 MVA
SLL=1.64 MVA SLL=2.38 MVA SLL=1.51 MVA SLL=5.34 MVA SLL=0.52 MVA SLL=1.13 MVA SLL=0.91 MVA SLL=1.46 MVA SLL=2.64 MVA
A5 01-OCT-20 ISSUED FOR APPROVAL MB
TCL=1.24 MVA SLL=2.62 MVA SLL=2.59 MVA SLL=1.71 MVA SLL=1.30 MVA SLL=1.26 MVA SLL=1.26 MVA SLL=0.65 MVA SLL= 0.48 MVA SLL= 0.47 MVA SLL= 0.43 MVA SLL= 0.43 MVA SLL= 0.43 MVA SLL= 0.35 MVA SLL=1.96 MVA TCL= 0.90 MVA SLL=1.10 MVA
SLL= 0.48 MVA 575.0M 800.0M
SLL=0.61 MVA RD1509
TCL=3.66 MVA
SLL= 0.51 MVA
SHS1623
TCL=1.17 MVA
250.0M

RD1723
A4 24-AUG-20 ISSUED FOR APPROVAL MB
SLL=1.65 MVA SLL=0.51 MVA
TCL=4.62 MVA

106.0M
LOOP FEEDER PSS1-LF3 RD3216
TCL=5.76 MVA
SLL=2.53 MVA
SLL=2.03 MVA
A3 07-JUL-20 ISSUED FOR APPROVAL MB
SHS0303 2438.0M
566.0M LOOP FEEDER PSS1-LF11
626.0M 2723.0M
TCL=1.01 MVA
SLL=0.45 MVA 444.0M 300.0M
RD1214
TCL=3.76 MVA A2 02-MAR-20 ISSUED FOR APPROVAL MB
SLL=1.65 MVA

SHS0906
TCL=5.78 MVA
284.0M SHS0907
TCL=5.97 MVA
985.0M
RD1907
220.0M
RD1611
2392.0M 451.0M
RD1612 RD1613
155.0M 453.0M
PLOT=RD16_M01
249.0M
SHS1209 SHS1206
754.0M 346.0M
SHS1205
513.0M
RD1618 SHS1214
145.0M SHS1620 75.0M
TCL=1.22 MVA
PLOT=RD21_C38 170.0M 170.0M
PLOT=RD21_CF03
4300.0M A1 22-DEC-19 ISSUED FOR APPROVAL MB
TCL=1.68 MVA TCL=2.00 MVA TCL=1.02 MVA 1840.0M
TCL=3.08 MVA TCL=2.95 MVA TCL=2.00 MVA TCL=0.65 MVA TCL=5.89 MVA TCL=5.89 MVA TCL=5.89 MVA TCL=2.95 MVA PLOT=RD21_C37 195.0M PLOT=RD21_C35 335.0M PLOT=RD21_CR04 90.0M PLOT=RD21_CR05 90.0M 90.0M PLOT=RD21_CR07 85.0M PLOT=RD21_CR08 160.0M TCL=1.02 MVA
89.0M SLL=2.53 MVA SLL=2.62 MVA SHS0110 SLL=0.60 MVA SLL=0.44 MVA PLOT=RD21_CR06 PLOT=RD21_C22
PLOT=RD9_C21
TCL=0.94 MVA
SHS0405
TCL=5.60 MVA
SLL=1.35 MVA SLL=1.30 MVA SLL=0.88 MVA SLL=0.75 MVA SLL=0.37 MVA SLL=2.59 MVA SLL=2.59 MVA SLL=2.59 MVA SLL=1.24 MVA SLL=0.88 MVA
SHS1004
TCL=5.84 MVA
TCL=5.97 MVA
SLL=2.62 MVA
SHS1709
TCL=1.98 MVA
SLL=0.87 MVA
SHS0703
TCL=5.97 MVA
SLL=2.62 MVA
TCL=0.88 MVA
SLL=0.38 MVA
TCL=1.12 MVA
SLL=0.49 MVA
TCL=0.75 MVA
SLL=0.40 MVA
TCL=0.82 MVA
SLL=0.44 MVA
TCL=0.66 MVA
SLL=0.36 MVA
TCL=0.67 MVA
SLL=0.36 MVA
TCL=0.63 MVA
SLL=0.34 MVA
TCL=0.88 MVA
SLL=0.38 MVA
SLL=0.58 MVA SHS1619
REV. DATE DESCRIPTION APPR'D
SLL=0.41 MVA SLL=2.47 MVA SLL=2.56 MVA
PLOT=RD18_M02
TCL=0.65 MVA
SLL=0.37 MVA
Client
995.0M LOOP FEEDER PSS1-LF2
97.0M

PLOT=RD9_C22 523.0M 413.0M


200.0M
TCL=1.16 MVA 1354.0M 690.0M 460.0M
SLL=0.50 MVA
LOOP FEEDER PSS1-LF10

SHS0406 400.0M RD0712 1280.0M SHS1006 423.0M SHS1009 700.0M PLOT=RD17_M07 127.0M SHS1012 976.0M SHS1011 369.0M RD1726 172.0M PLOT=RD17_M01 SHS0705 395.0M SHS0707 160.0M SHS0708
SHS1713 695.0M
62.0M TCL=5.60 MVA TCL=4.50 MVA TCL=5.89 MVA TCL=5.89 MVA TCL=0.65 MVA TCL=5.89 MVA TCL=5.89 MVA TCL=4.83 MVA TCL=0.65 MVA TCL=5.89 MVA TCL=5.89 MVA TCL=5.82 MVA 770.0M
TCL=2.43 MVA
SLL=2.47 MVA SLL=1.99 MVA SLL=2.62 MVA SLL=2.59 MVA SLL=0.37 MVA SLL=2.59 MVA SLL=2.59 MVA SLL=2.16 MVA SLL=0.37 MVA SLL=2.59 MVA SLL=2.59 MVA RD1212 290.0M PLOT=RD12_M01 SLL=2.57 MVA
SLL=1.08 MVA
TCL=4.00 MVA TCL=0.65 MVA
PLOT=RD9_C24 SHS0107 SLL=1.77 MVA SLL=0.37 MVA
TCL=1.05 MVA TCL=5.62 MVA
SLL=0.46 MVA SLL=2.47 MVA
9431.0M RD1830
4664.0M TCL=5.22 MVA
SLL=2.30 MVA
150.0M
PLOT=RD9_C27
TCL=1.03 MVA 314.0M
4200.0M
2200.0M
PMC
SLL=0.45 MVA 6555.0M
LOOP FEEDER PSS1-LF1
LOOP FEEDER PSS1-LF09 690.0M
598.0M
240.0M 80.0M 825.0M 825.0M 440.0M 156.0M 425.0M 260.0M 190.0M 70.0M 165.0M 281.0M 85.0M 200.0M SHS0814 965.0M 3200.0M 660.0M
SHS0105 SHS0106 PLOT=RD20_C5 310.0M PLOT=RD20_C7 100.0M PLOT=RD20_C8 610.0M SHS1702 SHS0818 550.0M RD1403 SHS1101 RD2517 480.0M RD1910 535.0M PLOT=RD19_M01
1070.0M TCL=5.55 MVA RD1909
SHS0309 PLOT=RD9_CF01 SHS0304 PLOT= RD9_C18 PLOT= RD9_C14 SHS0305 PLOT= RD9_C12 PLOT= RD9_C13 PLOT= RD9_C11 PLOT= RD9_C2 PLOT= RD9_C1 TCL=5.84 MVA TCL=5.76 MVA TCL=0.99 MVA TCL=1.66 MVA TCL=1.06 MVA SHS1704 TCL=2.53 MVA TCL=5.22 MVA TCL=1.78 MVA TCL=5.63 MVA TCL=6.04 MVA TCL=4.79 MVA TCL=0.65 MVA
PLOT= RD9_C15 SHS0301 TCL=5.89 MVA
TCL=0.65 MVA SLL=2.50 MVA SLL=2.53 MVA SLL=0.43 MVA SLL=0.72 MVA SLL=0.46 MVA SLL=1.14 MVA SLL=2.30 MVA SLL=0.88 MVA SLL=2.46 MVA SLL=2.48 MVA SLL=2.68 MVA SLL=2.11 MVA SLL=0.37 MVA
TCL=1.00 MVA TCL=1.15 MVA TCL=1.06 MVA TCL=0.99 MVA TCL=0.99 MVA TCL=1.31 MVA TCL=1.17 MVA TCL=0.99 MVA TCL=0.99 MVA TCL=0.99 MVA TCL=0.88 MVA TCL=0.93 MVA SLL=2.58 MVA
SLL=0.32 MVA SLL=0.57 MVA SLL=0.52 MVA SLL=0.46 MVA SLL=0.43 MVA SLL=0.43 MVA SHS0302 SLL=0.58 MVA SLL=0.55 MVA SHS0306 SLL=0.43 MVA SLL=0.43 MVA SLL=0.43 MVA SLL=0.38 MVA SLL=0.40 MVA
SHS0313
LOOP FEEDER PSS2-LF15

LOOP FEEDER PSS2-LF15 LOOP FEEDER PSS2-LF15

LOOP FEEDER PSS2-LF8 LOOP FEEDER PSS2-LF8

LOOP FEEDER PSS2-LF8 LOOP FEEDER PSS2-LF8 LOOP FEEDER PSS2-LF8


Consultant
LOOP FEEDER PSS2-LF1 LOOP FEEDER PSS2-LF7

LOOP FEEDER PSS2-LF2 LOOP FEEDER PSS2-LF6 LOOP FEEDER PSS2-LF9

LOOP FEEDER
PSS2-LF7 LOOP FEEDER PSS2-LF5 LOOP FEEDER PSS2-LF11 LOOP FEEDER PSS2-LF10

Project / Contract
LOOP FEEDER PSS2-LF3 LOOP FEEDER PSS2-LF4 LOOP FEEDER PSS2-LF13 LOOP FEEDER PSS2-LF12

LOOP FEEDER PSS2-LF4 LOOP FEEDER PSS2-LF3 LOOP FEEDER PSS2-LF10 LOOP FEEDER PSS2-LF14
RIYADH CITY NORTH
LOOP FEEDER PSS2-LF5

LOOP FEEDER
PSS2-LF6
LOOP FEEDER PSS2-LF2

LOOP FEEDER PSS2-LF1


LOOP FEEDER PSS2-LF12

LOOP FEEDER PSS2-LF9 LOOP FEEDER PSS2-LF14


LOOP FEEDER PSS2-LF13

LOOP FEEDER
PSS2-LF11
ALL PHASES
LOOP FEEDER PSS2-LF8 Drawing Title

SPARE PSS1-LF17 (FOR RIYADH CITY SOUTH)


SPARE PSS1-LF16 (FOR RIYADH CITY SOUTH)

SPARE PSS1-LF19 (FOR RIYADH CITY SOUTH)


ULTIMATE POWER SUPPLY
12 MVAR
SPARE PSS1-LF18 (FOR RIYADH CITY SOUTH)

12 MVAR
12
MVAR
SPARE PSS1-LF20 (FOR RIYADH CITY SOUTH)

12
MVAR
22kV SINGLE LINE DIAGRAM
PRIMARY SUBSTATION BY OTHERS

PRIMARY SUBSTATION BY OTHERS


TX.01

PRIMARY SUBSTATION PSS-1 AND PSS-2


CAPACITOR CAPACITOR TX.02 CAPACITOR CAPACITOR
1000kVA LOOP-1: LOOP-2: LOOP-3: LOOP-4: LOOP-5: LOOP-6: LOOP-7: LOOP-8: LOOP-9: LOOP-10: LOOP-11: LOOP-12: LOOP-13: LOOP-14: LOOP-15:
TCL=70.65 MVA
TCL=72.29 TCL=65.12 MVA
TCL=67.69 TCL=67.09 MVA
TCL=67.62 TCL=66.09 MVA
TCL=70.95 TCL=68.71 MVA
TCL=71.49MVA TCL=63.56 MVA
TCL=63.46 TCL=70.06 MVA
TCL=70.07 TCL=49.59 MVA
TCL=51.45 BANK-1 BANK-2 1000kVA TCL=67.88 MVA
TCL=68.42 TCL=58.78 MVA
TCL=63.42 TCL=69.65 MVA
TCL=72.96 TCL=68.74 MVA
TCL=75.09 TCL=70.75 MVA
TCL=70.64 TCL=70.04 MVA
TCL=70.14 TCL=65.29 MVA
TCL=66.16 BANK-4 BANK-3
22/0.415kV SLL=31.36 MVA
SLL=32.10 SLL=29.50 MVA
SLL=31.03 SLL=30.03 MVA
SLL=29.99 SLL=29.13 MVA
SLL=31.31 SLL=31.18 MVA
SLL=32.11 SLL=28.36 MVA
SLL=28.25 SLL=31.86 MVA 22/0.415kV SLL=30.89 MVA
SLL=31.12 SLL=28.17 MVA
SLL=30.10 SLL=31.41 MVA
SLL=33.20 SLL=32.16 MVA
SLL=35.69 SLL=31.40 MVA
SLL=31.38 SLL=31.14 MVA
SLL=31.19 SLL=29.40 MVA
SLL=29.63
SLL=22.22 MVA
SLL=23.03
FLL=12.72 MVA
FLL=13.01 FLL=12.05 MVA
FLL=12.51 FLL=12.08 MVA
FLL=12.17 FLL=11.90 MVA
FLL=12.77 FLL=12.37 MVA
FLL=12.87 FLL=11.44 MVA
FLL=11.42 FLL=12.61 MVA FLL=8.93 MVA
FLL=9.26 FLL=12.22 MVA
FLL=12.32 FLL=10.99 MVA
FLL=11.91 FLL=12.54 MVA
FLL=12.60 FLL=12.37 MVA
FLL=12.93 FLL=12.74 MVA
FLL=12.72 FLL=12.61 MVA
FLL=12.63 FLL=12.42 MVA
FLL=12.57
LP01A LP02A LP03A LP04A LP05A LP06A LP07A LP08A LP08B LP07B LP06B LP05B LP04B LP03B LP02B LP01B LP09A LP10A LP11A LP12A LP13A LP14A LP15A LP15B LP14B LP13B LP12B LP11B LP10B LP09B

CONTRACT No: JOB No:


2500A 2500A 2500A 2500A

DRAWN DESIGNED CHECKED APPROVED


630A 630A 630A 630A 630A 630A 630A 630A 630A 1250A 1250A 1250A 1250A 1250A 1250A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 1250A 1250A 1250A 1250A 1250A 1250A 1250A 1250A 630A 630A 630A 630A 630A 630A 630A

BUS SECTION-1 BUS SECTION-2 BUS SECTION-4 BUS SECTION-3


ST MSD MSA MB
22kV, 2500A, 31.5kA, 1s 2500A 22kV, 2500A, 31.5kA, 1s 2500A 22kV, 2500A, 31.5kA, 1s 2500A 22kV, 2500A, 31.5kA, 1s 2500A
FROM 132/22kV, 60MVA
TRANSFORMER-1
FROM 132/22kV, 60MVA
TRANSFORMER-2
FROM 132/22kV, 60MVA
TRANSFORMER-4
FROM 132/22kV, 60MVA
TRANSFORMER-3
DATE 10-OCT-2019 ACTUAL SIZE A1
Drawing Scale. N.T.S
PROPOSED PRIMARY SUBSTATION - 2

Drawing No.
A6
FOR INFORMATION ONLY RN-02-00001-00-07-EL-PIL-DG-000312
c:\pw_working\dxb\client\p006236b\d0351524\RN-02-00001-00-07-EL-PIL-DG-000311-12.dwg
Last Saved By: P002959B Last Saved Date: 11/19/2020 6:01 PM Printed Date: 11/24/2020 4:25 PM Printed By: Randhi, Venkata
Contractor : National Projects & Contruction LLC 1 SLD

Over All SLD


Employer : ALDAR Projects 2

Country of Origin
Consultant : PARSONS 3

Signal List
Client : ADDC 4

Tele-Information Plan
SS : RMU Substations 5

6 Cable Overview List


Internal Project No:

Adaptation Design
Project Name : Madinat Al Riyadh City Ph-6A & 6B 7

8 I/O Connection Diagram

MATERIAL SUBMITTAL: DMS-RTU for RMU.Rev.01


9 RTU Functional Specification

10 RTU Detailed Design

11 RTU Method Statement

12 RTU FAT Procedure

13 RTU SAT Procedure

14 POINT TO POINT TEST PROCEDURE

15 Warranty Certificate
Contractor : National Projects & Contruction LLC 1 SLD

Over All SLD


Employer : ALDAR Projects 2

Country of Origin
Consultant : PARSONS 3

Signal List
Client : ADDC 4

Tele-Information Plan
SS : RMU Substations 5

6 Cable Overview List


Internal Project No:

Adaptation Design
Project Name : Madinat Al Riyadh City Ph-6A & 6B 7

8 I/O Connection Diagram

MATERIAL SUBMITTAL: DMS-RTU for RMU.Rev.01


9 RTU Functional Specification

10 RTU Detailed Design

11 RTU Method Statement

12 RTU FAT Procedure

13 RTU SAT Procedure

14 POINT TO POINT TEST PROCEDURE

15 Warranty Certificate
LUCY RMU SIGNAL LIST

SS No.
1. RD-1823 -2TR- PHASE 6B
2. RD-1833 -1TR- PHASE 6B
3. RD-1910 -2TR- PHASE 6B
IO Typical QRM

Station Type : Station Name : Station Address: IP Address: MAC Address:


SS Substation RD1910 RD1910
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling
I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status

Box )
Baytype ( Comment ) Remarks
YY01 RTU DO 01 LUCY DSM 2A - 01 030/000/108 RD1910 00 00 C.Station (22kV Common) DC DUMMY RELAY OFF - YY01 DO-17B
YY01 RTU DO 02 LUCY DSM 2A - 01 030/000/108 RD1910 00 00 -C.Station (22kV Common) DC DUMMY RELAY ON - YY01 DO-18B
YY01 RTU DO 03 LUCY DSM 1A DO-SW A 01 041/001/112 RD1910 SS - 22 A01-FE (22kV Feeder-LBS - 1) - DC LISO_C LOAD ISOLATOR OPEN W101 C J01.XK MDF J01 9
YY01 RTU DO 04 LUCY DSM 1A DO-SW A 01 041/001/112 RD1910 SS - 22 A01-FE (22kV Feeder LBS - 1) - DC LISC_C LOAD ISOLATOR CLOSED W101 D J01.XK MDF J01 7
YY01 RTU DO 05 LUCY DSM 1B DO-SW B 01 042/002/104 RD1910 SS - 22 A02-FE (22kV Transformer CB - 1) DC CBO_C CIRCUIT BREAKER OPEN W102 C J02.XK MDF J02 4
01 042/002/104 RD1910 SS - 22 -A02-FE (22kV Transformer CB - 1) DC CBC_C CIRCUIT BREAKER CLOSED
YY01 RTU DO 06 LUCY DSM 2A DO-SW A 01 041/003/112 RD1910 SS - 22 -A03-FE (22kV Feeder LBS - 2) - DC LISO_C LOAD ISOLATOR OPEN W101 K J03.XK MDF J03 9
YY01 RTU DO 07 LUCY DSM 2A DO-SW A 01 041/003/112 RD1910 SS - 22 A03-FE (22kV Feeder LBS - 2) - DC LISC_C LOAD ISOLATOR CLOSED W101 L J03.XK MDF J03 7
YY01 RTU DO 08 LUCY DSM 2B DO-SW B 01 042/004/104 RD1910 SS - 22 A04-FE (22kV Transformer CB - 2) DC CBO_C CIRCUIT BREAKER OPEN W103 C J04.XK MDF J04 4
01 042/002/104 RD1910 SS - 22 -A04-FE (22kV Transformer CB - 2) DC CBC_C CIRCUIT BREAKER CLOSED
-
YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W101 A J01.XK MDF J01 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J01.XK MDF J01 2
YY01 RTU C/R LUCY DSM 1A DI SW A 01 Common Return (C/R) W102 G J01.XK MDF J01 2&4
YY01 RTU C/R LUCY DSM 1A DI 1 01 Common Return (C/R) W102 J J01.XK MDF J01 6
YY01 RTU C/R LUCY DSM 1A DI 4 01 Common Return (C/R) W102 M J01.XK MDF J01
YY01 RTU C/R LUCY DSM 2 A DI SW A 01 Common Return (C/R) W102 P J03.XK MDF J03 2&4
YY01 RTU C/R LUCY DSM 2 A DI 3 01 Common Return (C/R) W102 P J03.XK MDF J03 6
YY01 RTU C/R LUCY DSM 2 A DI 4 01 Common Return (C/R) W102 P J03.XK MDF J03

YY01 RTU A1 01 LUCY DSM 1B AI-SW B 01 042/002/132 RD1910 SS - 22 A02-FE (22kV Transformer CB - 1) M A+ CURRENT + W102 T J02.XK MDF J02 5
YY01 RTU A1 02 LUCY DSM 1B AI-SW B 01 042/002/132 RD1910 SS - 22 -A02-FE (22kV Transformer CB - 1) M A- CURRENT - W102 V J02.XK MDF J02 6
YY01 RTU A1 03 LUCY DSM 2B AI-SW B 01 042/004/132 RD1910 SS - 22 -A04-FE (22kV Transformer CB - 2) M A+ CURRENT + W103 T J04.XK MDF J04 5
YY01 RTU A1 04 LUCY DSM 2B AI-SW B 01 042/004/132 RD1910 SS - 22 -A04-FE (22kV Transformer CB - 2) M A- CURRENT - W103 V J04.XK MDF J04 6
-
YY01 RTU PS L1 01 RTU AC SUPPLY W501 bk YH01 230V AC P
YY01 RTU PS N 01 RTU AC SUPPLY W501 bu YH01 230V AC N

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J02.XK MDF J02 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J02.XK MDF J02 2
YY01 RTU C/R LUCY DSM 1B DI SW B 01 Common Return (C/R) W103 G J02.XK MDF J02 2&4
YY01 RTU C/R LUCY DSM 1B DI 4 01 Common Return (C/R) W103 J xx MDF J02 8
YY01 RTU C/R LUCY DSM 1B DI 2 01 Common Return (C/R) W103 M J02.XK MDF J02 8 & 10
YY01 RTU C/R LUCY DSM 1B DI 1 01 Common Return (C/R) W103 P J02.XK MDF J02 12

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J04.XK MDF J04 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J04.XK MDF J04 2
YY01 RTU C/R LUCY DSM 2B DI SW B 01 Common Return (C/R) W103 G J04.XK MDF J04 2&4
YY01 RTU C/R LUCY DSM 2B DI 4 01 Common Return (C/R) W103 J J04.XK MDF J04 8
YY01 RTU C/R LUCY DSM 2B DI 2 01 Common Return (C/R) W103 M J04.XK MDF J04 8 & 10
YY01 RTU C/R LUCY DSM 2B DI 1 01 Common Return (C/R) W103 P J04.XK MDF J04 12
IO Typical QRM(L EFI)

Station Type : Station Name :


SS Substation RD1910
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling Box


I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status
Baytype ( Comment ) Remarks

)
YY01 RTU DI 01 LUCY DSM 2A - 01 030/000/005 RD1823 00 00 C.Station (22kV Common) - DP DUM OFF DUMMY RELAY OFF - 0 YY01 DI-15A
YY01 RTU DI 02 LUCY DSM 2A - 01 030/000/005 RD1823 00 00 C.Station (22kV Common) - DP DUM ON DUMMY RELAY ON - 0 YY01 DI-16A
YY01 RTU DI 03 LUCY MCM - 01 030/000/042 RD1823 00 00 C.Station (22kV Common) - SP MCBA MCB Alarm - 0 YY01
YY01 RTU DI 04 LUCY ADEL - 01 030/000/250 RD1823 00 00 C.Station (22kV Common) - SP 24VDCAL 24V DC Alarm - 0 YY01
YY01 RTU DI 05 LUCY MCM - 01 030/000/201 RD1823 00 00 C.Station (22kV Common) - SP STNL/R Station Control Local / Remote - 0 YY01
YY01 RTU DI 06 LUCY DSM 2A DI-3 01 030/000/041 RD1823 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W102 H XX MDF CS 7
01 030/000/041 RD1823 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W103 H XX MDF CS 8

YY01 RTU DI 07 LUCY DSM 1A DI-SWA Open 01 041/001/012 RD1823 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISO LOAD ISOLATOR OPEN W101 F J01.XK MDF J01 1
YY01 RTU DI 08 LUCY DSM 1A DI-SWA Close 01 041/001/012 RD1823 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISC LOAD ISOLATOR CLOSED W101 E J01.XK MDF J01 3
YY01 RTU DI 15 LUCY DSM 1A DI-1 01 041/003/033 RD1823 SS - 22 A03-FE (22kV Feeder LBS - 2) - SP EFI Earth Fault Indication W101 H J01.XK MDF J01 5

YY01 RTU DI 09 LUCY DSM 1B DI-SWA Open 01 042/002/001 RD1823 SS - 22 A02-FE (22kV Transformer CB - 1) DP CBO CIRCUIT BREAKER OPEN W102 F J02.XK MDF J02 3
YY01 RTU DI 10 LUCY DSM 1B DI-SWA Close 01 042/002/001 RD1823 SS - 22 -A02-FE (22kV Transformer CB - 1) DP CBC CIRCUIT BREAKER CLOSED W102 E J02.XK MDF J02 1
YY01 RTU DI 11 LUCY DSM 1B DI-2 01 042/002/205 RD1823 SS - 22 -A02-FE (22kV Transformer CB - 1) FL OCEFT Over Current/Earth Fault Trip W102 R J02.XK MDF J02 7&9
YY01 RTU DI 12 LUCY DSM 1B DI-1 01 042/002/247 RD1823 SS - 22 -A02-FE (22kV Transformer CB - 1) SP PRF Protection Relay Faulty W102 N J02.XK MDF J02 11
-

YY01 RTU DI 13 LUCY DSM 2A DI-SWA Open 01 041/003/012 RD1823 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISO LOAD ISOLATOR OPEN W101 P J03.XK MDF J03 1
YY01 RTU DI 14 LUCY DSM 2A DI-SWA Close 01 041/003/012 RD1823 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISC LOAD ISOLATOR CLOSED W101 M J03.XK MDF J03 3

YY01 RTU DI 16 LUCY DSM 2B DI-SWA Open 01 042/004/001 RD1823 SS - 22 A04-FE (22kV Transformer CB - 2) DP CBO CIRCUIT BREAKER OPEN W103 F J04.XK MDF J04 3
YY01 RTU DI 17 LUCY DSM 2B DI-SWA Close 01 042/004/001 RD1823 SS - 22 -A04-FE (22kV Transformer CB - 2) DP CBC CIRCUIT BREAKER CLOSED W103 E J04.XK MDF J04 1
YY01 RTU DI 18 LUCY DSM 2B DI-2 01 042/004/205 RD1823 SS - 22 -A04-FE (22kV Transformer CB - 2) FL OCEFT Over Current/Earth Fault Trip W103 R J04.XK MDF J04 7&9
YY01 RTU DI 19 LUCY DSM 2B DI-1 01 042/004/247 RD1823 SS - 22 -
A04-FE (22kV Transformer CB - 2) - SP PRF Protection Relay Faulty W103 N J04.XK MDF J04 11
TRM-RMU

Station Type : Station Name : Station Address: IP Address: MAC Address:


SS Substation RD1833 RD1833

RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling Box )


Object ADDR EC 870

I/ O Text / Description
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status
Baytype ( Comment ) Remarks
YY01 RTU DO 01 LUCY TB2 - 01 030/000/108 Station 2 00 00 C.Station (22kV Common) - DC DUMMY RELAY OFF - YY01 DO-17B
YY01 RTU DO 02 LUCY TB2 - 01 030/000/108 Station 2 00 00 C.Station (22kV Common) - DC DUMMY RELAY ON - YY01 DO-18B
YY01 RTU DO 03 LUCY TB1 DO-1B 01 055/001/112 Station 2 SS - 11 A01-FE (22kV Feeder LBS - 1) - DC LISO_C LOAD ISOLATOR OPEN W101 C J01-3 MDF J01 137
YY01 RTU DO 04 LUCY TB1 DO-2B 01 055/001/112 Station 2 SS - 11 A01-FE (22kV Feeder LBS - 1) - DC LISC_C LOAD ISOLATOR CLOSED W101 D J01-4 MDF J01 138
YY01 RTU DO 05 LUCY TB1 DO-3B 01 056/002/104 Station 2 SS - 11 A02-FE (22kV Transformer CB - 1) - DC CBO_C CIRCUIT BREAKER OPEN W102 C J02-42 MDF J02 199
01 056/002/104 Station 2 SS - 11 A02-FE (22kV Transformer CB - 1) - DC CBC_C CIRCUIT BREAKER CLOSED

YY01 RTU DO 06 LUCY TB1 DO-5B 01 055/004/112 Station 2 SS - 11 A04-FE (22kV Feeder LBS - 2) - DC LISO_C LOAD ISOLATOR OPEN W101 K J04-17 MDF J04 137
YY01 RTU DO 07 LUCY TB1 DO-6B 01 055/004/112 Station 2 SS - 11 A04-FE (22kV Feeder LBS - 2) - DC LISC_C LOAD ISOLATOR CLOSED W101 L J04-18 MDF J04 138

YY01 RTU +24V DC LUCY TB1 24VS 01 +24V DC W101 A J01-1 MDF J01
YY01 RTU OV DC LUCY TB1 OVS 01 0V DC W101 B J01-2 MDF J01
YY01 RTU C/R LUCY TB1 DI-1B 01 Common Return (C/R) W101 G J01-7 MDF J01 69
YY01 RTU C/R LUCY TB2 DI-19B 01 Common Return (C/R) W101 J J04-64 MDF J04 69
YY01 RTU C/R LUCY TB1 DI-5B 01 Common Return (C/R) W101 N J04-21 MDF J04 69
YY01 RTU A1 01 LUCY TB1 AI-13A 01 056/002/132 Station 2 SS - 11 A02-FE (22kV Transformer CB - 1) - M A+ CURRENT + W102 T J02-122 MDF J02 205
YY01 RTU A1 02 LUCY TB1 AI-13B 01 056/002/132 Station 2 SS - 11 A02-FE (22kV Transformer CB - 1) - M A- CURRENT - W102 V J02-124 MDF J02 206
YY01 RTU A1 03 LUCY TB1 AI-14A 01 056/003/132 Station 2 SS - 11 A03-FE (22kV Transformer CB - 2) - M A+ CURRENT + W103 T J03-122 MDF J03 205
YY01 RTU A1 04 LUCY TB1 AI-14B 01 056/003/132 Station 2 SS - 11 A03-FE (22kV Transformer CB - 2) - M A- CURRENT - W103 V J03-124 MDF J03 206

YY01 RTU PS L1 01 RTU AC SUPPLY W501 bk YH01 230V AC P


YY01 RTU PS N 01 RTU AC SUPPLY W501 bu YH01 230V AC N

YY01 RTU +24V DC LUCY TB1 24VS 01 +24V DC W102 A J02-41 MDF J02 121
YY01 RTU C/R LUCY TB1 DI-3B 01 Common Return (C/R) W102 G J02-33 MDF J02 69
YY01 RTU C/R LUCY TB2 DI-20B 01 Common Return (C/R) W102 J CS-43 MDF J02 69
YY01 RTU C/R LUCY TB1 DI-10B 01 Common Return (C/R) W102 M J02-95 MDF J02 69
YY01 RTU C/R LUCY TB1 DI-9B 01 Common Return (C/R) W102 P J02-98 MDF J02 69

YY01 RTU +24V DC LUCY TB1 24VS 01 +24V DC W103 A J03-41 MDF J03 121
YY01 RTU C/R LUCY TB1 DI-7B 01 Common Return (C/R) W103 G J03-33 MDF J03 69
YY01 RTU C/R LUCY TB2 DI-20B 01 Common Return (C/R) W103 J CS-43 MDF J03 69
YY01 RTU C/R LUCY TB1 DI-12B 01 Common Return (C/R) W103 M J03-95 MDF J03 69
YY01 RTU C/R LUCY TB1 DI-11B 01 Common Return (C/R) W103 P J03-98 MDF J03 69
Station Type : Station Name :
SS Substation

RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling Box )


Object ADDR EC 870

I/ O Text / Description
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status
Baytype ( Comment ) Remarks
YY01 RTU DI 01 LUCY TB2 - 01 030/000/005 Station 2 00 00 C.Station (22kV Common) - DP DUM OFF DUMMY RELAY OFF - 0 YY01 DI-15A
YY01 RTU DI 02 LUCY TB2 - 01 030/000/005 Station 2 00 00 C.Station (22kV Common) - DP DUM ON DUMMY RELAY ON - 0 YY01 DI-16A
YY01 RTU DI 03 LUCY TB1 - 01 030/000/042 Station 2 00 00 C.Station (22kV Common) - SP MCBA MCB Alarm - 0 YY01
YY01 RTU DI 04 LUCY TB1 - 01 030/000/250 Station 2 00 00 C.Station (22kV Common) - SP 24VDCAL 24V DC Alarm - 0 YY01
YY01 RTU DI 05 LUCY TB1 - 01 030/000/201 Station 2 00 00 C.Station (22kV Common) - SP STNL/R Station Control Local / Remote - 0 YY01
YY01 RTU DI 06 LUCY TB2 DI-20A 01 030/000/041 Station 2 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W102 H CS-44 MDF CS 58
01 030/000/041 Station 2 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W103 H CS-44 MDF CS 58

YY01 RTU DI 07 LUCY TB1 DI-1A 01 055/001/012 Station 2 SS - 11 A01-FE (22kV Feeder LBS - 1) - DP LISO LOAD ISOLATOR OPEN W101 F J01-9 MDF J01 23
YY01 RTU DI 08 LUCY TB1 DI-2A 01 055/001/012 Station 2 SS - 11 A01-FE (22kV Feeder LBS - 1) - DP LISC LOAD ISOLATOR CLOSED W101 E J01-8 MDF J01 24
YY01 RTU DI 15 LUCY TB2 DI-19A 01 055/001/031 Station 2 SS - 11 A01-FE (22kV Feeder LBS - 1) - SP EFI Earth Fault Indication W101 H J01-66 MDF J01 48

YY01 RTU DI 09 LUCY TB1 DI-3A 01 056/002/001 Station 2 SS - 11 A02-FE (22kV Transformer CB - 1) - DP CBO CIRCUIT BREAKER OPEN W102 F J02-35 MDF J02 1
YY01 RTU DI 10 LUCY TB1 DI-4A 01 056/002/001 Station 2 SS - 11 A02-FE (22kV Transformer CB - 1) - DP CBC CIRCUIT BREAKER CLOSED W102 E J02-34 MDF J02 2
YY01 RTU DI 11 LUCY TB1 DI-9A 01 056/002/205 Station 2 SS - 11 A02-FE (22kV Transformer CB - 1) - FL OCEFT Over Current/Earth Fault Trip W102 R J02-96 MDF J02 55
YY01 RTU DI 12 LUCY TB1 DI-10A 01 056/002/247 Station 2 SS - 11 A02-FE (22kV Transformer CB - 1) - SP PRF Protection Relay Faulty W102 N J02-93 MDF J02 333

YY01 RTU DI 13 LUCY TB1 DI-5A 01 055/004/012 (22kV Feeder LBS - 2) - SS - 11 A04-FE (22kV Feeder LBS - 2) - DP LISO LOAD ISOLATOR OPEN W101 P J04-23 MDF J04 23
YY01 RTU DI 14 LUCY TB1 DI-6A 01 055/004/012 (22kV Feeder LBS - 2) - SS - 11 A04-FE (22kV Feeder LBS - 2) - DP LISC LOAD ISOLATOR CLOSED W101 M J04-22 MDF J04 24
IO Typical QRM

Station Type : Station Name : Station Address: IP Address: MAC Address:


SS Substation RD1823 RD1823
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling
I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status

Box )
Baytype ( Comment ) Remarks
YY01 RTU DO 01 LUCY DSM 2A - 01 030/000/108 RD1823 00 00 C.Station (11kV Common) - DC DUMMY RELAY OFF - YY01 DO-17B
YY01 RTU DO 02 LUCY DSM 2A - 01 030/000/108 RD1823 00 00 C.Station (11kV Common) - DC DUMMY RELAY ON - YY01 DO-18B
YY01 RTU DO 03 LUCY DSM 1A DO-SW A 01 041/001/112 RD1823 SS - 22 A01-FE (22kV Feeder LBS - 1) - DC LISO_C LOAD ISOLATOR OPEN W101 C J01.XK MDF J01 9
YY01 RTU DO 04 LUCY DSM 1A DO-SW A 01 041/001/112 RD1823 SS - 22 A01-FE (22kV Feeder LBS - 1) - DC LISC_C LOAD ISOLATOR CLOSED W101 D J01.XK MDF J01 7
YY01 RTU DO 05 LUCY DSM 1B DO-SW B 01 042/002/104 RD1823 SS - 22 A02-FE (22kV Transformer CB - 1) DC CBO_C CIRCUIT BREAKER OPEN W102 C J02.XK MDF J02 4
01 042/002/104 RD1823 SS - 22 -A02-FE (22kV Transformer CB - 1) DC CBC_C CIRCUIT BREAKER CLOSED
YY01 RTU DO 06 LUCY DSM 2A DO-SW A 01 041/003/112 RD1823 SS - 22 -A03-FE (22kV Feeder LBS - 2) - DC LISO_C LOAD ISOLATOR OPEN W101 K J03.XK MDF J03 9
YY01 RTU DO 07 LUCY DSM 2A DO-SW A 01 041/003/112 RD1823 SS - 22 A03-FE (22kV Feeder LBS - 2) - DC LISC_C LOAD ISOLATOR CLOSED W101 L J03.XK MDF J03 7
YY01 RTU DO 08 LUCY DSM 2B DO-SW B 01 042/004/104 RD1823 SS - 22 A04-FE (22kV Transformer CB - 2) DC CBO_C CIRCUIT BREAKER OPEN W103 C J04.XK MDF J04 4
01 042/002/104 RD1823 SS - 22 -A04-FE (22kV Transformer CB - 2) DC CBC_C CIRCUIT BREAKER CLOSED
-
YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W101 A J01.XK MDF J01 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J01.XK MDF J01 2
YY01 RTU C/R LUCY DSM 1A DI SW A 01 Common Return (C/R) W102 G J01.XK MDF J01 2&4
YY01 RTU C/R LUCY DSM 1A DI 1 01 Common Return (C/R) W102 J J01.XK MDF J01 6
YY01 RTU C/R LUCY DSM 1A DI 4 01 Common Return (C/R) W102 M J01.XK MDF J01
YY01 RTU C/R LUCY DSM 2 A DI SW A 01 Common Return (C/R) W102 P J03.XK MDF J03 2&4
YY01 RTU C/R LUCY DSM 2 A DI 3 01 Common Return (C/R) W102 P J03.XK MDF J03 6
YY01 RTU C/R LUCY DSM 2 A DI 4 01 Common Return (C/R) W102 P J03.XK MDF J03

YY01 RTU A1 01 LUCY DSM 1B AI-SW B 01 042/002/132 RD1823 SS - 22 A02-FE (22kV Transformer CB - 1) M A+ CURRENT + W102 T J02.XK MDF J02 5
YY01 RTU A1 02 LUCY DSM 1B AI-SW B 01 042/002/132 RD1823 SS - 22 -A02-FE (22kV Transformer CB - 1) M A- CURRENT - W102 V J02.XK MDF J02 6
YY01 RTU A1 03 LUCY DSM 2B AI-SW B 01 042/004/132 RD1823 SS - 22 -A04-FE (22kV Transformer CB - 2) M A+ CURRENT + W103 T J04.XK MDF J04 5
YY01 RTU A1 04 LUCY DSM 2B AI-SW B 01 042/004/132 RD1823 SS - 22 -A04-FE (22kV Transformer CB - 2) M A- CURRENT - W103 V J04.XK MDF J04 6
-
YY01 RTU PS L1 01 RTU AC SUPPLY W501 bk YH01 230V AC P
YY01 RTU PS N 01 RTU AC SUPPLY W501 bu YH01 230V AC N

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J02.XK MDF J02 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J02.XK MDF J02 2
YY01 RTU C/R LUCY DSM 1B DI SW B 01 Common Return (C/R) W103 G J02.XK MDF J02 2&4
YY01 RTU C/R LUCY DSM 1B DI 4 01 Common Return (C/R) W103 J xx MDF J02 8
YY01 RTU C/R LUCY DSM 1B DI 2 01 Common Return (C/R) W103 M J02.XK MDF J02 8 & 10
YY01 RTU C/R LUCY DSM 1B DI 1 01 Common Return (C/R) W103 P J02.XK MDF J02 12

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J04.XK MDF J04 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J04.XK MDF J04 2
YY01 RTU C/R LUCY DSM 2B DI SW B 01 Common Return (C/R) W103 G J04.XK MDF J04 2&4
YY01 RTU C/R LUCY DSM 2B DI 4 01 Common Return (C/R) W103 J J04.XK MDF J04 8
YY01 RTU C/R LUCY DSM 2B DI 2 01 Common Return (C/R) W103 M J04.XK MDF J04 8 & 10
YY01 RTU C/R LUCY DSM 2B DI 1 01 Common Return (C/R) W103 P J04.XK MDF J04 12
IO Typical QRM(L EFI)

Station Type : Station Name :


SS Substation RD1823
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling Box


I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status
Baytype ( Comment ) Remarks

)
YY01 RTU DI 01 LUCY DSM 2A - 01 030/000/005 RD1823 00 00 C.Station (22kV Common) - DP DUM OFF DUMMY RELAY OFF - 0 YY01 DI-15A
YY01 RTU DI 02 LUCY DSM 2A - 01 030/000/005 RD1823 00 00 C.Station (22kV Common) - DP DUM ON DUMMY RELAY ON - 0 YY01 DI-16A
YY01 RTU DI 03 LUCY MCM - 01 030/000/042 RD1823 00 00 C.Station (22kV Common) - SP MCBA MCB Alarm - 0 YY01
YY01 RTU DI 04 LUCY ADEL - 01 030/000/250 RD1823 00 00 C.Station (22kV Common) - SP 24VDCAL 24V DC Alarm - 0 YY01
YY01 RTU DI 05 LUCY MCM - 01 030/000/201 RD1823 00 00 C.Station (22kV Common) - SP STNL/R Station Control Local / Remote - 0 YY01
YY01 RTU DI 06 LUCY DSM 2A DI-3 01 030/000/041 RD1823 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W102 H XX MDF CS 7
01 030/000/041 RD1823 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W103 H XX MDF CS 8

YY01 RTU DI 07 LUCY DSM 1A DI-SWA Open 01 041/001/012 RD1823 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISO LOAD ISOLATOR OPEN W101 F J01.XK MDF J01 1
YY01 RTU DI 08 LUCY DSM 1A DI-SWA Close 01 041/001/012 RD1823 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISC LOAD ISOLATOR CLOSED W101 E J01.XK MDF J01 3
YY01 RTU DI 15 LUCY DSM 1A DI-1 01 041/003/033 RD1823 SS - 22 A03-FE (22kV Feeder LBS - 2) - SP EFI Earth Fault Indication W101 H J01.XK MDF J01 5

YY01 RTU DI 09 LUCY DSM 1B DI-SWA Open 01 042/002/001 RD1823 SS - 22 A02-FE (22kV Transformer CB - 1) DP CBO CIRCUIT BREAKER OPEN W102 F J02.XK MDF J02 3
YY01 RTU DI 10 LUCY DSM 1B DI-SWA Close 01 042/002/001 RD1823 SS - 22 -A02-FE (22kV Transformer CB - 1) DP CBC CIRCUIT BREAKER CLOSED W102 E J02.XK MDF J02 1
YY01 RTU DI 11 LUCY DSM 1B DI-2 01 042/002/205 RD1823 SS - 22 -A02-FE (22kV Transformer CB - 1) FL OCEFT Over Current/Earth Fault Trip W102 R J02.XK MDF J02 7&9
YY01 RTU DI 12 LUCY DSM 1B DI-1 01 042/002/247 RD1823 SS - 22 -A02-FE (22kV Transformer CB - 1) SP PRF Protection Relay Faulty W102 N J02.XK MDF J02 11
-

YY01 RTU DI 13 LUCY DSM 2A DI-SWA Open 01 041/003/012 RD1823 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISO LOAD ISOLATOR OPEN W101 P J03.XK MDF J03 1
YY01 RTU DI 14 LUCY DSM 2A DI-SWA Close 01 041/003/012 RD1823 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISC LOAD ISOLATOR CLOSED W101 M J03.XK MDF J03 3

YY01 RTU DI 16 LUCY DSM 2B DI-SWA Open 01 042/004/001 RD1823 SS - 22 A04-FE (22kV Transformer CB - 2) DP CBO CIRCUIT BREAKER OPEN W103 F J04.XK MDF J04 3
YY01 RTU DI 17 LUCY DSM 2B DI-SWA Close 01 042/004/001 RD1823 SS - 22 -A04-FE (22kV Transformer CB - 2) DP CBC CIRCUIT BREAKER CLOSED W103 E J04.XK MDF J04 1
YY01 RTU DI 18 LUCY DSM 2B DI-2 01 042/004/205 RD1823 SS - 22 -A04-FE (22kV Transformer CB - 2) FL OCEFT Over Current/Earth Fault Trip W103 R J04.XK MDF J04 7&9
YY01 RTU DI 19 LUCY DSM 2B DI-1 01 042/004/247 RD1823 SS - 22 -
A04-FE (22kV Transformer CB - 2) - SP PRF Protection Relay Faulty W103 N J04.XK MDF J04 11
RTU I/O Connection Schedule

Cable Schedule - RTU to Switchgear (QRM)

CABLE [1]
Connections for QRM Version with 24 Way Umbilical Cable: -

Non Alarm
Umbilical /
GEMINI V3.0 RMU MB
Cable Description Non
RTU Terminal No Terminal No
Core No Active
State
DSM 1A +24VS 1 K5/1 1 `+'24V DC (Switched) -
DSM 1A - 0VS 2 K22/1 2 ` 0V DC -
DSM 1A -SW1 DO 3 K10/1 3 J01 Open command NO
DSM 1A-SW1 DO 4 K12/1 4 J01 Close command NO
DSM 1A -SW1 DI 5 L4/1 8 J01 Close Indication NO
DSM 1A -SW1 DI 6 L5/1 9 J01 Open Indication NO
DSM 1A -DI COM 7 L3/1 7 J01 Common Indication -
DSM 1A -DI 1 8 L63/1 66/80 J01/J03 Earth Fault Indicator NO
DSM 1A -DI COM 9 L61/1 64/78 J01/J03 Earth Fault Indicator Common -
DSM 1A -DI 4 10 - Spare DI NO
DSM 1A – DI COM 11 - Spare DI Com -
DSM 2A +24VS 12 K5/2 15 `+'24V DC (Switched) NO
DSM 2A - 0VS 13 K22/2 16 ` 0V DC -
DSM 2A -SW1 DO 14 K10/2 17 J03 Open command NO
DSM 2A -SW1 DO 15 K12/2 18 J03 Close command NO
DSM 2A -SW1 DI 16 L4/2 22 J03 Close Indication NO
DSM 2A -SW1 DI 17 L5/2 23 J03 Open Indication NO
DSM 2A -DI COM 18 L3/2 21 J03 Common Indication -
DSM 2A -DI COM 19 L30 43 Low Gas Indicator Common -
DSM 2A -DI 3 20 L32 45 Low Gas Indicator NO
DSM 2A -DI 4 21 - Spare DI NO
DSM 2A – DI COM 22 - Spare DI com
Cable Schedule - RTU to Switchgear (QRM)

CABLE [2]
Connections for QRM Version with 19 Way Umbilical Cable: -

Non
Alarm
Umbilical
GEMINI V3.0 RMU MB /
Cable Description
RTU Terminal No Terminal No Non
Core No
Active
State
Aux TB 1 from Charger 1 K1 41 `+'24V DC (Switched to Interposing relay) -
Aux TB 2 from Charger 2 - 139/143/160 ` 0 Vdc -
DSM 1B -SW2 DO 3 K2 42 J02 Open Command NO
DSM 1B -SW2 DO 4 - - Spare -
DSM 1B -SW2 DI 5 L4/3 34 J02 Close Indication NO
DSM 1B -SW2 DI 6 L5/3 35 J02 Open Indication NO
DSM 1B -DI COM 7 L3/3 33 J02 Common Indication -
DSM 1B -DI COM 8 RL11 96 J02 Overcurrent/Earth fault trip Common NO
DSM 1B -DI 2 9 RL13 98 J02 Overcurrent/Earth fault trip -
DSM 1B -DI COM 10 RL03 95 J02 Protection Relay Failure Common -
DSM 1B -DI 4 11 RL01 93 J02 Protection Relay Failure -
DSM 1B -AI CT B 12 D30 122 J02 Y Phase CT -
DSM 1B -AI CT B 13 D130 124 J02 Y Phase CT -
DSM 1B -DI 4 14 - Spare DI NO
DSM 1B -DI COM 15 - Spare DI com
DSM 1B -DO 1 16 - Spare DI NO
DSM 1B- DO1 COM 17 - Spare DI com
Cable Schedule - RTU to Switchgear (QRM)

CABLE [3]
Connections for QRM Version Only with 19 Way Umbilical Cable: -

Non
Alarm
Umbilical
GEMINI V3.0 RMU MB /
Cable Description
RTU Terminal No Terminal No Non
Core No
Active
State
Aux TB 3 from Charger 1 K1 41 `+'24V DC (Switched to Interposing relay) -
Aux TB 4 from Charger 2 - 139/143/160 ` 0 Vdc -
DSM 2B -SW2 DO 3 K2 42 J04 Open Command NO
DSM 2B -SW2 DO 4 - - Spare -
DSM 2B -SW2 DI 5 L4/4 34 J04 Close Indication NO
DSM 2B -SW2 DI 6 L5/4 35 J04 Open Indication NO
DSM 2B -DI COM 7 L3/4 33 J04 Common Indication -
DSM 2B -DI COM 8 RL11 96 J04 Overcurrent/Earth fault trip Common NO
DSM 2B -DI 2 9 RL13 98 J04 Overcurrent/Earth fault trip -
DSM 2B -DI COM 10 RL03 95 J04 Protection Relay Failure Common -
DSM 2B -DI 4 11 RL01 93 J04 Protection Relay Failure -
DSM 2B -AI CT B 12 D30 122 J04 Y Phase CT -
DSM 2B -AI CT B 13 D130 124 J04 Y Phase CT -
DSM 2B -DI 4 14 - Spare DI NO
DSM 2B -DI COM 15 - Spare DI com
DSM 2B -DO 1 16 - Spare DI NO
DSM 2B- DO1 COM 17 - Spare DI com
Cable Overview / QRM

Cable
From To Description
tag

W500 LV power supply MCB Box Incoming LV Supply


W501 MCB Box RTU Panel Outgoing LV supply
W101 RTU Panel DMS IFC Cable 1: MV Switchgear Control & Monitoring (Umbilical cable)
W102 RTU Panel DMS IFC Cable 2: MV Switchgear Control & Monitoring (Umbilical cable)
W103 RTU Panel DMS IFC Cable 3: MV Switchgear Control & Monitoring (Umbilical cable)
RTU I/O Connection Schedule

Cable Schedule - RTU to Switchgear (TRM)

CABLE [1]
Connections for QRM Version with 24 Way Umbilical Cable: -

Non Alarm
Umbilical /
GEMINI V3.0 RMU MB
Cable Description Non
RTU Terminal No Terminal No
Core No Active
State
DSM 1A +24VS 1 K5/1 1 `+'24V DC (Switched) -
DSM 1A - 0VS 2 K22/1 2 ` 0V DC -
DSM 1A -SW1 DO 3 K10/1 3 J01 Open command NO
DSM 1A-SW1 DO 4 K12/1 4 J01 Close command NO
DSM 1A -SW1 DI 5 L4/1 8 J01 Close Indication NO
DSM 1A -SW1 DI 6 L5/1 9 J01 Open Indication NO
DSM 1A -DI COM 7 L3/1 7 J01 Common Indication -
DSM 1A -DI 1 8 L63/1 66/80 J01/J03 Earth Fault Indicator NO
DSM 1A -DI COM 9 L61/1 64/78 J01/J03 Earth Fault Indicator Common -
DSM 1A -DI 4 10 - Spare DI NO
DSM 1A – DI COM 11 - Spare DI Com -
DSM 2A +24VS 12 K5/2 15 `+'24V DC (Switched) NO
DSM 2A - 0VS 13 K22/2 16 ` 0V DC -
DSM 2A -SW1 DO 14 K10/2 17 J03 Open command NO
DSM 2A -SW1 DO 15 K12/2 18 J03 Close command NO
DSM 2A -SW1 DI 16 L4/2 22 J03 Close Indication NO
DSM 2A -SW1 DI 17 L5/2 23 J03 Open Indication NO
DSM 2A -DI COM 18 L3/2 21 J03 Common Indication -
DSM 2A -DI COM 19 L30 43 Low Gas Indicator Common -
DSM 2A -DI 3 20 L32 45 Low Gas Indicator NO
DSM 2A -DI 4 21 - Spare DI NO
DSM 2A – DI COM 22 - Spare DI com
Cable Schedule - RTU to Switchgear (TRM)

CABLE [2]
Connections for QRM Version with 19 Way Umbilical Cable: -

Non
Alarm
Umbilical
GEMINI V3.0 RMU MB /
Cable Description
RTU Terminal No Terminal No Non
Core No
Active
State
Aux TB 1 from Charger 1 K1 41 `+'24V DC (Switched to Interposing relay) -
Aux TB 2 from Charger 2 - 139/143/160 ` 0 Vdc -
DSM 1B -SW2 DO 3 K2 42 K02 Open Command NO
DSM 1B -SW2 DO 4 - - Spare -
DSM 1B -SW2 DI 5 L4/3 34 J02 Close Indication NO
DSM 1B -SW2 DI 6 L5/3 35 J02 Open Indication NO
DSM 1B -DI COM 7 L3/3 33 J02 Common Indication -
DSM 1B -DI COM 8 RL11 96 J02 Overcurrent/Earth fault trip Common NO
DSM 1B -DI 2 9 RL13 98 J02 Overcurrent/Earth fault trip -
DSM 1B -DI COM 10 RL03 95 J02 Protection Relay Failure Common -
DSM 1B -DI 4 11 RL01 93 J02 Protection Relay Failure -
DSM 1B -AI CT B 12 D30 122 J02 Y Phase CT -
DSM 1B -AI CT B 13 D130 124 J02 Y Phase CT -
DSM 1B -DI 4 14 - Spare DI NO
DSM 1B -DI COM 15 - Spare DI com
DSM 1B -DO 1 16 - Spare DI NO
DSM 1B- DO1 COM 17 - Spare DI com
Cable Overview / QRM

Cable
From To Description
tag

W500 LV power supply MCB Box Incoming LV Supply


W501 MCB Box RTU Panel Outgoing LV supply
W101 RTU Panel DMS IFC Cable 1: MV Switchgear Control & Monitoring (Umbilical cable)
W102 RTU Panel DMS IFC Cable 2: MV Switchgear Control & Monitoring (Umbilical cable)
SCHNEIDER RMU SIGNAL LIST

SS No.
1. RD-2412 -2TR- PHASE 6A
2. RD-3012 -2TR- PHASE 6A
3. RD-3013 -2TR- PHASE 6A
IO Typical QRM

Station Type : Station Name : Station Address: IP Address: MAC Address:


SS Substation RD3013 RD3013
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling
I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status

Box )
Baytype ( Comment ) Remarks
YY01 RTU DO 01 LUCY DSM 2A - 01 030/000/108 RD3013 00 00 C.Station (22kV Common) DC DUMMY RELAY OFF - YY01 DO-17B
YY01 RTU DO 02 LUCY DSM 2A - 01 030/000/108 RD3013 00 00 -C.Station (22kV Common) DC DUMMY RELAY ON - YY01 DO-18B
YY01 RTU DO 03 LUCY DSM 1A DO-SW A 01 041/001/112 RD3013 SS - 22 A01-FE (22kV Feeder-LBS - 1) - DC LISO_C LOAD ISOLATOR OPEN W101 C J01.XK MDF J01 9
YY01 RTU DO 04 LUCY DSM 1A DO-SW A 01 041/001/112 RD3013 SS - 22 A01-FE (22kV Feeder LBS - 1) - DC LISC_C LOAD ISOLATOR CLOSED W101 D J01.XK MDF J01 7
YY01 RTU DO 05 LUCY DSM 1B DO-SW B 01 042/002/104 RD3013 SS - 22 A02-FE (22kV Transformer CB - 1) DC CBO_C CIRCUIT BREAKER OPEN W102 C J02.XK MDF J02 4
01 042/002/104 RD3013 SS - 22 -A02-FE (22kV Transformer CB - 1) DC CBC_C CIRCUIT BREAKER CLOSED
YY01 RTU DO 06 LUCY DSM 2A DO-SW A 01 041/003/112 RD3013 SS - 22 -A03-FE (22kV Feeder LBS - 2) - DC LISO_C LOAD ISOLATOR OPEN W101 K J03.XK MDF J03 9
YY01 RTU DO 07 LUCY DSM 2A DO-SW A 01 041/003/112 RD3013 SS - 22 A03-FE (22kV Feeder LBS - 2) - DC LISC_C LOAD ISOLATOR CLOSED W101 L J03.XK MDF J03 7
YY01 RTU DO 08 LUCY DSM 2B DO-SW B 01 042/004/104 RD3013 SS - 22 A04-FE (22kV Transformer CB - 2) DC CBO_C CIRCUIT BREAKER OPEN W103 C J04.XK MDF J04 4
01 042/002/104 RD3013 SS - 22 -A04-FE (22kV Transformer CB - 2) DC CBC_C CIRCUIT BREAKER CLOSED
-
YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W101 A J01.XK MDF J01 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J01.XK MDF J01 2
YY01 RTU C/R LUCY DSM 1A DI SW A 01 Common Return (C/R) W102 G J01.XK MDF J01 2&4
YY01 RTU C/R LUCY DSM 1A DI 1 01 Common Return (C/R) W102 J J01.XK MDF J01 6
YY01 RTU C/R LUCY DSM 1A DI 4 01 Common Return (C/R) W102 M J01.XK MDF J01
YY01 RTU C/R LUCY DSM 2 A DI SW A 01 Common Return (C/R) W102 P J03.XK MDF J03 2&4
YY01 RTU C/R LUCY DSM 2 A DI 3 01 Common Return (C/R) W102 P J03.XK MDF J03 6
YY01 RTU C/R LUCY DSM 2 A DI 4 01 Common Return (C/R) W102 P J03.XK MDF J03

YY01 RTU A1 01 LUCY DSM 1B AI-SW B 01 042/002/132 RD3013 SS - 22 A02-FE (22kV Transformer CB - 1) M A+ CURRENT + W102 T J02.XK MDF J02 5
YY01 RTU A1 02 LUCY DSM 1B AI-SW B 01 042/002/132 RD3013 SS - 22 -A02-FE (22kV Transformer CB - 1) M A- CURRENT - W102 V J02.XK MDF J02 6
YY01 RTU A1 03 LUCY DSM 2B AI-SW B 01 042/004/132 RD3013 SS - 22 -A04-FE (22kV Transformer CB - 2) M A+ CURRENT + W103 T J04.XK MDF J04 5
YY01 RTU A1 04 LUCY DSM 2B AI-SW B 01 042/004/132 RD3013 SS - 22 -A04-FE (22kV Transformer CB - 2) M A- CURRENT - W103 V J04.XK MDF J04 6
-
YY01 RTU PS L1 01 RTU AC SUPPLY W501 bk YH01 230V AC P
YY01 RTU PS N 01 RTU AC SUPPLY W501 bu YH01 230V AC N

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J02.XK MDF J02 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J02.XK MDF J02 2
YY01 RTU C/R LUCY DSM 1B DI SW B 01 Common Return (C/R) W103 G J02.XK MDF J02 2&4
YY01 RTU C/R LUCY DSM 1B DI 4 01 Common Return (C/R) W103 J xx MDF J02 8
YY01 RTU C/R LUCY DSM 1B DI 2 01 Common Return (C/R) W103 M J02.XK MDF J02 8 & 10
YY01 RTU C/R LUCY DSM 1B DI 1 01 Common Return (C/R) W103 P J02.XK MDF J02 12

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J04.XK MDF J04 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J04.XK MDF J04 2
YY01 RTU C/R LUCY DSM 2B DI SW B 01 Common Return (C/R) W103 G J04.XK MDF J04 2&4
YY01 RTU C/R LUCY DSM 2B DI 4 01 Common Return (C/R) W103 J J04.XK MDF J04 8
YY01 RTU C/R LUCY DSM 2B DI 2 01 Common Return (C/R) W103 M J04.XK MDF J04 8 & 10
YY01 RTU C/R LUCY DSM 2B DI 1 01 Common Return (C/R) W103 P J04.XK MDF J04 12
IO Typical QRM(L EFI)

Station Type : Station Name :


SS Substation RD2412
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling Box


I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status
Baytype ( Comment ) Remarks

)
YY01 RTU DI 01 LUCY DSM 2A - 01 030/000/005 RD3013 00 00 C.Station (22kV Common) - DP DUM OFF DUMMY RELAY OFF - 0 YY01 DI-15A
YY01 RTU DI 02 LUCY DSM 2A - 01 030/000/005 RD3013 00 00 C.Station (22kV Common) - DP DUM ON DUMMY RELAY ON - 0 YY01 DI-16A
YY01 RTU DI 03 LUCY MCM - 01 030/000/042 RD3013 00 00 C.Station (22kV Common) - SP MCBA MCB Alarm - 0 YY01
YY01 RTU DI 04 LUCY ADEL - 01 030/000/250 RD3013 00 00 C.Station (22kV Common) - SP 24VDCAL 24V DC Alarm - 0 YY01
YY01 RTU DI 05 LUCY MCM - 01 030/000/201 RD3013 00 00 C.Station (22kV Common) - SP STNL/R Station Control Local / Remote - 0 YY01
YY01 RTU DI 06 LUCY DSM 2A DI-3 01 030/000/041 RD3013 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W102 H XX MDF CS 7
01 030/000/041 RD3013 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W103 H XX MDF CS 8

YY01 RTU DI 07 LUCY DSM 1A DI-SWA Open 01 041/001/012 RD3013 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISO LOAD ISOLATOR OPEN W101 F J01.XK MDF J01 1
YY01 RTU DI 08 LUCY DSM 1A DI-SWA Close 01 041/001/012 RD3013 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISC LOAD ISOLATOR CLOSED W101 E J01.XK MDF J01 3
YY01 RTU DI 15 LUCY DSM 1A DI-1 01 041/003/033 RD3013 SS - 22 A03-FE (22kV Feeder LBS - 2) - SP EFI Earth Fault Indication W101 H J01.XK MDF J01 5

YY01 RTU DI 09 LUCY DSM 1B DI-SWA Open 01 042/002/001 RD3013 SS - 22 A02-FE (22kV Transformer CB - 1) DP CBO CIRCUIT BREAKER OPEN W102 F J02.XK MDF J02 3
YY01 RTU DI 10 LUCY DSM 1B DI-SWA Close 01 042/002/001 RD3013 SS - 22 -A02-FE (22kV Transformer CB - 1) DP CBC CIRCUIT BREAKER CLOSED W102 E J02.XK MDF J02 1
YY01 RTU DI 11 LUCY DSM 1B DI-2 01 042/002/205 RD3013 SS - 22 -A02-FE (22kV Transformer CB - 1) FL OCEFT Over Current/Earth Fault Trip W102 R J02.XK MDF J02 7&9
YY01 RTU DI 12 LUCY DSM 1B DI-1 01 042/002/247 RD3013 SS - 22 -A02-FE (22kV Transformer CB - 1) SP PRF Protection Relay Faulty W102 N J02.XK MDF J02 11
-

YY01 RTU DI 13 LUCY DSM 2A DI-SWA Open 01 041/003/012 RD3013 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISO LOAD ISOLATOR OPEN W101 P J03.XK MDF J03 1
YY01 RTU DI 14 LUCY DSM 2A DI-SWA Close 01 041/003/012 RD3013 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISC LOAD ISOLATOR CLOSED W101 M J03.XK MDF J03 3

YY01 RTU DI 16 LUCY DSM 2B DI-SWA Open 01 042/004/001 RD3013 SS - 22 A04-FE (22kV Transformer CB - 2) DP CBO CIRCUIT BREAKER OPEN W103 F J04.XK MDF J04 3
YY01 RTU DI 17 LUCY DSM 2B DI-SWA Close 01 042/004/001 RD3013 SS - 22 -A04-FE (22kV Transformer CB - 2) DP CBC CIRCUIT BREAKER CLOSED W103 E J04.XK MDF J04 1
YY01 RTU DI 18 LUCY DSM 2B DI-2 01 042/004/205 RD3013 SS - 22 -A04-FE (22kV Transformer CB - 2) FL OCEFT Over Current/Earth Fault Trip W103 R J04.XK MDF J04 7&9
YY01 RTU DI 19 LUCY DSM 2B DI-1 01 042/004/247 RD3013 SS - 22 -
A04-FE (22kV Transformer CB - 2) - SP PRF Protection Relay Faulty W103 N J04.XK MDF J04 11
IO Typical QRM

Station Type : Station Name : Station Address: IP Address: MAC Address:


SS Substation RD3012 RD3012
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling
I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status

Box )
Baytype ( Comment ) Remarks
YY01 RTU DO 01 LUCY DSM 2A - 01 030/000/108 RD3012 00 00 C.Station (22kV Common) DC DUMMY RELAY OFF - YY01 DO-17B
YY01 RTU DO 02 LUCY DSM 2A - 01 030/000/108 RD3012 00 00 -C.Station (22kV Common) DC DUMMY RELAY ON - YY01 DO-18B
YY01 RTU DO 03 LUCY DSM 1A DO-SW A 01 041/001/112 RD3012 SS - 22 A01-FE (22kV Feeder-LBS - 1) - DC LISO_C LOAD ISOLATOR OPEN W101 C J01.XK MDF J01 9
YY01 RTU DO 04 LUCY DSM 1A DO-SW A 01 041/001/112 RD3012 SS - 22 A01-FE (22kV Feeder LBS - 1) - DC LISC_C LOAD ISOLATOR CLOSED W101 D J01.XK MDF J01 7
YY01 RTU DO 05 LUCY DSM 1B DO-SW B 01 042/002/104 RD3012 SS - 22 A02-FE (22kV Transformer CB - 1) DC CBO_C CIRCUIT BREAKER OPEN W102 C J02.XK MDF J02 4
01 042/002/104 RD3012 SS - 22 -A02-FE (22kV Transformer CB - 1) DC CBC_C CIRCUIT BREAKER CLOSED
YY01 RTU DO 06 LUCY DSM 2A DO-SW A 01 041/003/112 RD3012 SS - 22 -A03-FE (22kV Feeder LBS - 2) - DC LISO_C LOAD ISOLATOR OPEN W101 K J03.XK MDF J03 9
YY01 RTU DO 07 LUCY DSM 2A DO-SW A 01 041/003/112 RD3012 SS - 22 A03-FE (22kV Feeder LBS - 2) - DC LISC_C LOAD ISOLATOR CLOSED W101 L J03.XK MDF J03 7
YY01 RTU DO 08 LUCY DSM 2B DO-SW B 01 042/004/104 RD3012 SS - 22 A04-FE (22kV Transformer CB - 2) DC CBO_C CIRCUIT BREAKER OPEN W103 C J04.XK MDF J04 4
01 042/002/104 RD3012 SS - 22 -A04-FE (22kV Transformer CB - 2) DC CBC_C CIRCUIT BREAKER CLOSED
-
YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W101 A J01.XK MDF J01 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J01.XK MDF J01 2
YY01 RTU C/R LUCY DSM 1A DI SW A 01 Common Return (C/R) W102 G J01.XK MDF J01 2&4
YY01 RTU C/R LUCY DSM 1A DI 1 01 Common Return (C/R) W102 J J01.XK MDF J01 6
YY01 RTU C/R LUCY DSM 1A DI 4 01 Common Return (C/R) W102 M J01.XK MDF J01
YY01 RTU C/R LUCY DSM 2 A DI SW A 01 Common Return (C/R) W102 P J03.XK MDF J03 2&4
YY01 RTU C/R LUCY DSM 2 A DI 3 01 Common Return (C/R) W102 P J03.XK MDF J03 6
YY01 RTU C/R LUCY DSM 2 A DI 4 01 Common Return (C/R) W102 P J03.XK MDF J03

YY01 RTU A1 01 LUCY DSM 1B AI-SW B 01 042/002/132 RD3012 SS - 22 A02-FE (22kV Transformer CB - 1) M A+ CURRENT + W102 T J02.XK MDF J02 5
YY01 RTU A1 02 LUCY DSM 1B AI-SW B 01 042/002/132 RD3012 SS - 22 -A02-FE (22kV Transformer CB - 1) M A- CURRENT - W102 V J02.XK MDF J02 6
YY01 RTU A1 03 LUCY DSM 2B AI-SW B 01 042/004/132 RD3012 SS - 22 -A04-FE (22kV Transformer CB - 2) M A+ CURRENT + W103 T J04.XK MDF J04 5
YY01 RTU A1 04 LUCY DSM 2B AI-SW B 01 042/004/132 RD3012 SS - 22 -A04-FE (22kV Transformer CB - 2) M A- CURRENT - W103 V J04.XK MDF J04 6
-
YY01 RTU PS L1 01 RTU AC SUPPLY W501 bk YH01 230V AC P
YY01 RTU PS N 01 RTU AC SUPPLY W501 bu YH01 230V AC N

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J02.XK MDF J02 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J02.XK MDF J02 2
YY01 RTU C/R LUCY DSM 1B DI SW B 01 Common Return (C/R) W103 G J02.XK MDF J02 2&4
YY01 RTU C/R LUCY DSM 1B DI 4 01 Common Return (C/R) W103 J xx MDF J02 8
YY01 RTU C/R LUCY DSM 1B DI 2 01 Common Return (C/R) W103 M J02.XK MDF J02 8 & 10
YY01 RTU C/R LUCY DSM 1B DI 1 01 Common Return (C/R) W103 P J02.XK MDF J02 12

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J04.XK MDF J04 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J04.XK MDF J04 2
YY01 RTU C/R LUCY DSM 2B DI SW B 01 Common Return (C/R) W103 G J04.XK MDF J04 2&4
YY01 RTU C/R LUCY DSM 2B DI 4 01 Common Return (C/R) W103 J J04.XK MDF J04 8
YY01 RTU C/R LUCY DSM 2B DI 2 01 Common Return (C/R) W103 M J04.XK MDF J04 8 & 10
YY01 RTU C/R LUCY DSM 2B DI 1 01 Common Return (C/R) W103 P J04.XK MDF J04 12
IO Typical QRM(L EFI)

Station Type : Station Name :


SS Substation RD2412
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling Box


I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status
Baytype ( Comment ) Remarks

)
YY01 RTU DI 01 LUCY DSM 2A - 01 030/000/005 RD3012 00 00 C.Station (22kV Common) - DP DUM OFF DUMMY RELAY OFF - 0 YY01 DI-15A
YY01 RTU DI 02 LUCY DSM 2A - 01 030/000/005 RD3012 00 00 C.Station (22kV Common) - DP DUM ON DUMMY RELAY ON - 0 YY01 DI-16A
YY01 RTU DI 03 LUCY MCM - 01 030/000/042 RD3012 00 00 C.Station (22kV Common) - SP MCBA MCB Alarm - 0 YY01
YY01 RTU DI 04 LUCY ADEL - 01 030/000/250 RD3012 00 00 C.Station (22kV Common) - SP 24VDCAL 24V DC Alarm - 0 YY01
YY01 RTU DI 05 LUCY MCM - 01 030/000/201 RD3012 00 00 C.Station (22kV Common) - SP STNL/R Station Control Local / Remote - 0 YY01
YY01 RTU DI 06 LUCY DSM 2A DI-3 01 030/000/041 RD3012 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W102 H XX MDF CS 7
01 030/000/041 RD3012 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W103 H XX MDF CS 8

YY01 RTU DI 07 LUCY DSM 1A DI-SWA Open 01 041/001/012 RD3012 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISO LOAD ISOLATOR OPEN W101 F J01.XK MDF J01 1
YY01 RTU DI 08 LUCY DSM 1A DI-SWA Close 01 041/001/012 RD3012 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISC LOAD ISOLATOR CLOSED W101 E J01.XK MDF J01 3
YY01 RTU DI 15 LUCY DSM 1A DI-1 01 041/003/033 RD3012 SS - 22 A03-FE (22kV Feeder LBS - 2) - SP EFI Earth Fault Indication W101 H J01.XK MDF J01 5

YY01 RTU DI 09 LUCY DSM 1B DI-SWA Open 01 042/002/001 RD3012 SS - 22 A02-FE (22kV Transformer CB - 1) DP CBO CIRCUIT BREAKER OPEN W102 F J02.XK MDF J02 3
YY01 RTU DI 10 LUCY DSM 1B DI-SWA Close 01 042/002/001 RD3012 SS - 22 -A02-FE (22kV Transformer CB - 1) DP CBC CIRCUIT BREAKER CLOSED W102 E J02.XK MDF J02 1
YY01 RTU DI 11 LUCY DSM 1B DI-2 01 042/002/205 RD3012 SS - 22 -A02-FE (22kV Transformer CB - 1) FL OCEFT Over Current/Earth Fault Trip W102 R J02.XK MDF J02 7&9
YY01 RTU DI 12 LUCY DSM 1B DI-1 01 042/002/247 RD3012 SS - 22 -A02-FE (22kV Transformer CB - 1) SP PRF Protection Relay Faulty W102 N J02.XK MDF J02 11
-

YY01 RTU DI 13 LUCY DSM 2A DI-SWA Open 01 041/003/012 RD3012 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISO LOAD ISOLATOR OPEN W101 P J03.XK MDF J03 1
YY01 RTU DI 14 LUCY DSM 2A DI-SWA Close 01 041/003/012 RD3012 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISC LOAD ISOLATOR CLOSED W101 M J03.XK MDF J03 3

YY01 RTU DI 16 LUCY DSM 2B DI-SWA Open 01 042/004/001 RD3012 SS - 22 A04-FE (22kV Transformer CB - 2) DP CBO CIRCUIT BREAKER OPEN W103 F J04.XK MDF J04 3
YY01 RTU DI 17 LUCY DSM 2B DI-SWA Close 01 042/004/001 RD3012 SS - 22 -A04-FE (22kV Transformer CB - 2) DP CBC CIRCUIT BREAKER CLOSED W103 E J04.XK MDF J04 1
YY01 RTU DI 18 LUCY DSM 2B DI-2 01 042/004/205 RD3012 SS - 22 -A04-FE (22kV Transformer CB - 2) FL OCEFT Over Current/Earth Fault Trip W103 R J04.XK MDF J04 7&9
YY01 RTU DI 19 LUCY DSM 2B DI-1 01 042/004/247 RD3012 SS - 22 -
A04-FE (22kV Transformer CB - 2) - SP PRF Protection Relay Faulty W103 N J04.XK MDF J04 11
IO Typical QRM

Station Type : Station Name : Station Address: IP Address: MAC Address:


SS Substation RD2412 RD2412
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling
I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status

Box )
Baytype ( Comment ) Remarks
YY01 RTU DO 01 LUCY DSM 2A - 01 030/000/108 RD2412 00 00 C.Station (22kV Common) DC DUMMY RELAY OFF - YY01 DO-17B
YY01 RTU DO 02 LUCY DSM 2A - 01 030/000/108 RD2412 00 00 -C.Station (22kV Common) DC DUMMY RELAY ON - YY01 DO-18B
YY01 RTU DO 03 LUCY DSM 1A DO-SW A 01 041/001/112 RD2412 SS - 22 A01-FE (22kV Feeder-LBS - 1) - DC LISO_C LOAD ISOLATOR OPEN W101 C J01.XK MDF J01 9
YY01 RTU DO 04 LUCY DSM 1A DO-SW A 01 041/001/112 RD2412 SS - 22 A01-FE (22kV Feeder LBS - 1) - DC LISC_C LOAD ISOLATOR CLOSED W101 D J01.XK MDF J01 7
YY01 RTU DO 05 LUCY DSM 1B DO-SW B 01 042/002/104 RD2412 SS - 22 A02-FE (22kV Transformer CB - 1) DC CBO_C CIRCUIT BREAKER OPEN W102 C J02.XK MDF J02 4
01 042/002/104 RD2412 SS - 22 -A02-FE (22kV Transformer CB - 1) DC CBC_C CIRCUIT BREAKER CLOSED
YY01 RTU DO 06 LUCY DSM 2A DO-SW A 01 041/003/112 RD2412 SS - 22 -A03-FE (22kV Feeder LBS - 2) - DC LISO_C LOAD ISOLATOR OPEN W101 K J03.XK MDF J03 9
YY01 RTU DO 07 LUCY DSM 2A DO-SW A 01 041/003/112 RD2412 SS - 22 A03-FE (22kV Feeder LBS - 2) - DC LISC_C LOAD ISOLATOR CLOSED W101 L J03.XK MDF J03 7
YY01 RTU DO 08 LUCY DSM 2B DO-SW B 01 042/004/104 RD2412 SS - 22 A04-FE (22kV Transformer CB - 2) DC CBO_C CIRCUIT BREAKER OPEN W103 C J04.XK MDF J04 4
01 042/002/104 RD2412 SS - 22 -A04-FE (22kV Transformer CB - 2) DC CBC_C CIRCUIT BREAKER CLOSED
-
YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W101 A J01.XK MDF J01 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J01.XK MDF J01 2
YY01 RTU C/R LUCY DSM 1A DI SW A 01 Common Return (C/R) W102 G J01.XK MDF J01 2&4
YY01 RTU C/R LUCY DSM 1A DI 1 01 Common Return (C/R) W102 J J01.XK MDF J01 6
YY01 RTU C/R LUCY DSM 1A DI 4 01 Common Return (C/R) W102 M J01.XK MDF J01
YY01 RTU C/R LUCY DSM 2 A DI SW A 01 Common Return (C/R) W102 P J03.XK MDF J03 2&4
YY01 RTU C/R LUCY DSM 2 A DI 3 01 Common Return (C/R) W102 P J03.XK MDF J03 6
YY01 RTU C/R LUCY DSM 2 A DI 4 01 Common Return (C/R) W102 P J03.XK MDF J03

YY01 RTU A1 01 LUCY DSM 1B AI-SW B 01 042/002/132 RD2412 SS - 22 A02-FE (22kV Transformer CB - 1) M A+ CURRENT + W102 T J02.XK MDF J02 5
YY01 RTU A1 02 LUCY DSM 1B AI-SW B 01 042/002/132 RD2412 SS - 22 -A02-FE (22kV Transformer CB - 1) M A- CURRENT - W102 V J02.XK MDF J02 6
YY01 RTU A1 03 LUCY DSM 2B AI-SW B 01 042/004/132 RD2412 SS - 22 -A04-FE (22kV Transformer CB - 2) M A+ CURRENT + W103 T J04.XK MDF J04 5
YY01 RTU A1 04 LUCY DSM 2B AI-SW B 01 042/004/132 RD2412 SS - 22 -A04-FE (22kV Transformer CB - 2) M A- CURRENT - W103 V J04.XK MDF J04 6
-
YY01 RTU PS L1 01 RTU AC SUPPLY W501 bk YH01 230V AC P
YY01 RTU PS N 01 RTU AC SUPPLY W501 bu YH01 230V AC N

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J02.XK MDF J02 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J02.XK MDF J02 2
YY01 RTU C/R LUCY DSM 1B DI SW B 01 Common Return (C/R) W103 G J02.XK MDF J02 2&4
YY01 RTU C/R LUCY DSM 1B DI 4 01 Common Return (C/R) W103 J xx MDF J02 8
YY01 RTU C/R LUCY DSM 1B DI 2 01 Common Return (C/R) W103 M J02.XK MDF J02 8 & 10
YY01 RTU C/R LUCY DSM 1B DI 1 01 Common Return (C/R) W103 P J02.XK MDF J02 12

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J04.XK MDF J04 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J04.XK MDF J04 2
YY01 RTU C/R LUCY DSM 2B DI SW B 01 Common Return (C/R) W103 G J04.XK MDF J04 2&4
YY01 RTU C/R LUCY DSM 2B DI 4 01 Common Return (C/R) W103 J J04.XK MDF J04 8
YY01 RTU C/R LUCY DSM 2B DI 2 01 Common Return (C/R) W103 M J04.XK MDF J04 8 & 10
YY01 RTU C/R LUCY DSM 2B DI 1 01 Common Return (C/R) W103 P J04.XK MDF J04 12
IO Typical QRM(L EFI)

Station Type : Station Name :


SS Substation RD2412
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling Box


I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status
Baytype ( Comment ) Remarks

)
YY01 RTU DI 01 LUCY DSM 2A - 01 030/000/005 RD2412 00 00 C.Station (22kV Common) - DP DUM OFF DUMMY RELAY OFF - 0 YY01 DI-15A
YY01 RTU DI 02 LUCY DSM 2A - 01 030/000/005 RD2412 00 00 C.Station (22kV Common) - DP DUM ON DUMMY RELAY ON - 0 YY01 DI-16A
YY01 RTU DI 03 LUCY MCM - 01 030/000/042 RD2412 00 00 C.Station (22kV Common) - SP MCBA MCB Alarm - 0 YY01
YY01 RTU DI 04 LUCY ADEL - 01 030/000/250 RD2412 00 00 C.Station (22kV Common) - SP 24VDCAL 24V DC Alarm - 0 YY01
YY01 RTU DI 05 LUCY MCM - 01 030/000/201 RD2412 00 00 C.Station (22kV Common) - SP STNL/R Station Control Local / Remote - 0 YY01
YY01 RTU DI 06 LUCY DSM 2A DI-3 01 030/000/041 RD2412 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W102 H XX MDF CS 7
01 030/000/041 RD2412 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W103 H XX MDF CS 8

YY01 RTU DI 07 LUCY DSM 1A DI-SWA Open 01 041/001/012 RD2412 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISO LOAD ISOLATOR OPEN W101 F J01.XK MDF J01 1
YY01 RTU DI 08 LUCY DSM 1A DI-SWA Close 01 041/001/012 RD2412 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISC LOAD ISOLATOR CLOSED W101 E J01.XK MDF J01 3
YY01 RTU DI 15 LUCY DSM 1A DI-1 01 041/003/033 RD2412 SS - 22 A03-FE (22kV Feeder LBS - 2) - SP EFI Earth Fault Indication W101 H J01.XK MDF J01 5

YY01 RTU DI 09 LUCY DSM 1B DI-SWA Open 01 042/002/001 RD2412 SS - 22 A02-FE (22kV Transformer CB - 1) DP CBO CIRCUIT BREAKER OPEN W102 F J02.XK MDF J02 3
YY01 RTU DI 10 LUCY DSM 1B DI-SWA Close 01 042/002/001 RD2412 SS - 22 -A02-FE (22kV Transformer CB - 1) DP CBC CIRCUIT BREAKER CLOSED W102 E J02.XK MDF J02 1
YY01 RTU DI 11 LUCY DSM 1B DI-2 01 042/002/205 RD2412 SS - 22 -A02-FE (22kV Transformer CB - 1) FL OCEFT Over Current/Earth Fault Trip W102 R J02.XK MDF J02 7&9
YY01 RTU DI 12 LUCY DSM 1B DI-1 01 042/002/247 RD2412 SS - 22 -A02-FE (22kV Transformer CB - 1) SP PRF Protection Relay Faulty W102 N J02.XK MDF J02 11
-

YY01 RTU DI 13 LUCY DSM 2A DI-SWA Open 01 041/003/012 RD2412 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISO LOAD ISOLATOR OPEN W101 P J03.XK MDF J03 1
YY01 RTU DI 14 LUCY DSM 2A DI-SWA Close 01 041/003/012 RD2412 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISC LOAD ISOLATOR CLOSED W101 M J03.XK MDF J03 3

YY01 RTU DI 16 LUCY DSM 2B DI-SWA Open 01 042/004/001 RD2412 SS - 22 A04-FE (22kV Transformer CB - 2) DP CBO CIRCUIT BREAKER OPEN W103 F J04.XK MDF J04 3
YY01 RTU DI 17 LUCY DSM 2B DI-SWA Close 01 042/004/001 RD2412 SS - 22 -A04-FE (22kV Transformer CB - 2) DP CBC CIRCUIT BREAKER CLOSED W103 E J04.XK MDF J04 1
YY01 RTU DI 18 LUCY DSM 2B DI-2 01 042/004/205 RD2412 SS - 22 -A04-FE (22kV Transformer CB - 2) FL OCEFT Over Current/Earth Fault Trip W103 R J04.XK MDF J04 7&9
YY01 RTU DI 19 LUCY DSM 2B DI-1 01 042/004/247 RD2412 SS - 22 -
A04-FE (22kV Transformer CB - 2) - SP PRF Protection Relay Faulty W103 N J04.XK MDF J04 11
SCHNEIDER RMU Signal List for QRM (2 Ring Feeders + 2 Transformer Feeders)
Terminal
Signal Description Ferrule no. Remarks
no.
TRANSFORMER FEEDER-1 CIRCUIT BREAKER INDICATION
A1 J01-XK-2
Transformer Breaker-1 Closed
A2 J01-XK-69
A3 J01-XK-1
Transformer Breaker-1 Opened
A4 J01-XK-69
K102 J01-XK-333
Protection Relay (O/C + SBEF) Faulty
K103 J01-XK-69
K106 J01-XK-54
Over Current (O/C) Trip
K107 J01-XK-69
K104 J01-XK-55
Earth Fault (E/F) / SBEF Trip
K105 J01-XK-69
TRANSFORMER FEEDER-1 CIRCUIT BREAKER COMMAND
H3 J01-XK-121
Transformer Breaker-1 Open
H17 J01-XK-199
TRANSFORMER FEEDER-1 LOAD CURRENT
K108 J01-XK-205
Y-Phase Load Current
K109 J01-XK-206

L01 J02-XK-48
EFI Earth Fault Status
L02 J02-XK-69
B1 J02-XK-24
Ring Switch-1 Closed
B2 J02-XK-69
B3 J02-XK-23
Ring Switch-1 Opened
B4 J02-XK-69
RING SWITCH-1 COMMAND

Common B17 J02-XK-199


Ring Switch-1 Close B18 J02-XK-138
Ring Switch-1 Open B19 J02-XK-137
TRANSFORMER FEEDER-2 CIRCUIT BREAKER INDICATION
C1 J03-XK-2
Transformer Breaker-2 Closed
C2 J03-XK-69
C3 J03-XK-1
Transformer Breaker-2 Opened
C4 J03-XK-69
K202 J03-XK-333
Protection Relay (O/C + SBEF) Faulty
K203 J03-XK-69
K206 J03-XK-54
Over Current (O/C) Trip
K207 J03-XK-69
K204 J03-XK-55
Earth Fault (E/F) / SBEF Trip
K205 J03-XK-69
TRANSFORMER FEEDER-2 CIRCUIT BREAKER COMMAND
H3 J03-XK-121
Transformer Breaker-2 Open
H18 J03-XK-199
SCHNEIDER RMU Signal List for QRM (2 Ring Feeders + 2 Transformer Feeders)
Terminal
Signal Description Ferrule no. Remarks
no.
TRANSFORMER FEEDER-2 LOAD CURRENT
K208 J03-XK-205
Y-Phase Load Current
K209 J03-XK-206
RING SWITCH-2 INDICATION
D1 J04-XK-24
Ring Switch-2 Closed
D2 J04-XK-69
D3 J04-XK-23
Ring Switch-2 Opened
D4 J04-XK-69
RING SWITCH-2 COMMAND

Common D17 J04-XK-199


Ring Switch-2 Close D18 J04-XK-138
Ring Switch-2 Open D19 J04-XK-137
COMMON SIGNAL INDICATION
P1 XK7-58
SF6 Level-1 Indication (Low)
P2 XK7-69
P3 XK7-58
SF6 Level-2 Indication (Very Low)
P4 XK7-69
L03 XK7-59
MCB Off (AC+DC) Indication
L04 XK7-69
SCHNEIDER RMU Signal List for QRM (2 Ring Feeders + 1 Transformer Feeder)
Terminal
Signal Description Ferrule no. Remarks
no.
RING SWITCH-1 INDICATION
L01 J01-XK-48
EFI Earth Fault Status
L02 J01-XK-69
A1 J01-XK-24
Ring Switch-1 Closed
A2 J01-XK-69
A3 J01-XK-23
Ring Switch-1 Opened
A4 J01-XK-69
RING SWITCH-1 COMMAND

Common A17 J01-XK-199


Ring Switch-1 Close A18 J01-XK-138
Ring Switch-1 Open A19 J01-XK-137
TRANSFORMER FEEDER CIRCUIT BREAKER INDICATION
B1 J02-XK-2
Transformer Breaker Closed
B2 J02-XK-69
B3 J02-XK-1
Transformer Breaker Opened
B4 J02-XK-69
K102 J02-XK-333
Protection Relay (O/C + SBEF) Faulty
K103 J02-XK-69
K106 J02-XK-54
Over Current (O/C) Trip
K107 J02-XK-69
K104 J02-XK-55
Earth Fault (E/F) / SBEF Trip
K105 J02-XK-69
TRANSFORMER FEEDER CIRCUIT BREAKER COMMAND
H3 J02-XK-121
Transformer Breaker Open
H13 J02-XK-199
TRANSFORMER FEEDER LOAD CURRENT
K108 J02-XK-205
Y-Phase Load Current
K109 J02-XK-206
RING SWITCH-2 INDICATION
C1 J03-XK-24
Ring Switch-2 Closed
C2 J03-XK-69
C3 J03-XK-23
Ring Switch-2 Opened
C4 J03-XK-69
RING SWITCH-2 COMMAND

Common C17 J03-XK-199


Ring Switch-2 Close C18 J03-XK-138
Ring Switch-2 Open C19 J03-XK-137
SCHNEIDER RMU Signal List for QRM (2 Ring Feeders + 1 Transformer Feeder)
Terminal
Signal Description Ferrule no. Remarks
no.
COMMON SIGNAL INDICATION
P1 XK6-58
SF6 Level-1 Indication (Low)
P2 XK6-69
P3 XK6-58
SF6 Level-2 Indication (Very Low)
P4 XK6-69
L03 XK6-59
MCB Off (AC+DC) Indication
L04 XK6-69
Contractor : National Projects & Contruction LLC 1 SLD

Over All SLD


Employer : ALDAR Projects 2

Country of Origin
Consultant : PARSONS 3

Signal List
Client : ADDC 4

Tele-Information Plan
SS : RMU Substations 5

6 Cable Overview List


Internal Project No:

Adaptation Design
Project Name : Madinat Al Riyadh City Ph-6A & 6B 7

8 I/O Connection Diagram

MATERIAL SUBMITTAL: DMS-RTU for RMU.Rev.01


9 RTU Functional Specification

10 RTU Detailed Design

11 RTU Method Statement

12 RTU FAT Procedure

13 RTU SAT Procedure

14 POINT TO POINT TEST PROCEDURE

15 Warranty Certificate
QRM
Station No.
Distribution Substation Automation
Client : Abu Dhabi Distribution Company (ADDC) RD-1823 -2TR- PHASE 6B,
Contract No. : RD-1910 -2TR- PHASE 6B,
Distribution Substation :QRM RD-2412 -2TR- PHASE 6A,
RD-3012 -2TR- PHASE 6A,
RD-3013 -2TR- PHASE 6A

Overcurrent Trip / Earth fault Trip

Protection Relay Failure "WD"


DUMMY RELAY OFF/ON
RMU-QRM

Earth fault Indication

Station Control Local


Circuit Breaker op/cl
Circuit Breaker op

SF6 Pressure Low


Status Indications

Alarm Indications
Remote Control

Telemetering
Dummy off/on

24VDC Alarm
Fleetings
Current I (A)

MCB AC fail
Remarks
LBS op/cl

LBS op/cl
Log.Feeder Name DUM OFF/ON_C

DUM OFF/ON
Bay No. Feeder Type
(H=33KV; J=22KV)

MCBAc Off
LBSO/C_C

OCT / EFT
LBSO/C
CBO_C

CBO/C

SF6PL
STN L

DCSF
PRF
EFI
A
Total RTU signals: 8 6 2 2 2 10 8 2 3 1 2 6 1 2 1 1 1

K01 (RS1) CF J01.CF 2 . . . 2 . . 1 . . . . .

K02 (CB1) TCF J02.CFT . 1 . 1 . 2 . . 1 . 1 . .

K03 (RS2) CF J03.CF 2 . . . 2 . . 1" . . . . .

K04 (CB2) TCF J04.CFT . 1 . 1 . 2 . . 1 . 1 . .

CS Station . . 2 . . . 2 . . 1 1 1 1

Legent
CF : Cable Feeder
TCF: Trafo Cable Feeder Page 1 of 1
CS : Common Station Alarms REV.1
Distribution Substation Automation
Client : Abu Dhabi Distribution Company (ADDC)
Contract No. :
Distribution Substation :TRM

TRM
Station No.
RD-1833 -1TR- PHASE 6B

Overcurrent Trip / Earth fault Trip

Protection Relay Failure "WD"


RMU-TRM

DUMMY RELAY OFF/ON

Earth fault Indication

Station Control Local


Circuit Breaker op/cl
Circuit Breaker op

SF6 Pressure Low


Status Indications

Alarm Indications
Remote Control

Telemetering
Dummy off/on

24VDC Alarm
Fleetings
Current I (A)

MCB AC fail
Remarks

LBS op/cl

LBS op/cl
DUM OFF/ON_C
Log.Feeder Name

DUM OFF/ON
Bay No. Feeder Type
(H=33KV; J=22KV)

MCBAc Off
LBSO/C_C

OCT / EFT
LBSO/C
CBO_C

CBO/C

SF6PL
STN L

DCSF
PRF
EFI
A
Total RTU signals: 7 5 2 1 1 8 6 2 2 1 1 5 1 1 1 1 1

K01 (RS1) CF J01.CF 2 . . . 2 . . 1 . . . . .

K02 (CB1) TCF J02.TCF . 1 . 1 . 2 . . 1 . 1 . .

K03 (RS2) CF J03.CF 2 . . . 2 . . 1" . . . . .

CS Station . . 2 . . . 2 . . 1 . 1 1 1

Legent
CF : Cable Feeder
TCF: Trafo Cable Feeder Page 1 of 1
CS : Common Station Alarms REV.1
Contractor : National Projects & Contruction LLC 1 SLD

Over All SLD


Employer : ALDAR Projects 2

Country of Origin
Consultant : PARSONS 3

Signal List
Client : ADDC 4

Tele-Information Plan
SS : RMU Substations 5

6 Cable Overview List


Internal Project No:

Adaptation Design
Project Name : Madinat Al Riyadh City Ph-6A & 6B 7

8 I/O Connection Diagram

MATERIAL SUBMITTAL: DMS-RTU for RMU.Rev.01


9 RTU Functional Specification

10 RTU Detailed Design

11 RTU Method Statement

12 RTU FAT Procedure

13 RTU SAT Procedure

14 POINT TO POINT TEST PROCEDURE

15 Warranty Certificate
Cable Overview / TRM
RD-1833 -1TR- PHASE 6B

Cable
From To Description
tag

W500 LV power supply MCB Box Incoming LV Supply


W501 MCB Box RTU Panel Outgoing LV supply
W101 RTU Panel DMS IFC Cable 1: MV Switchgear Control & Monitoring (Umbilical cable)
W102 RTU Panel DMS IFC Cable 2: MV Switchgear Control & Monitoring (Umbilical cable)
Cable Overview / QRM
RD-1823 -2TR- PHASE 6B, RD-1910 -2TR-
PHASE 6B, RD-2412 -2TR- PHASE 6A, RD-3012
-2TR- PHASE 6A, RD-3013 -2TR- PHASE 6A

Cable
From To Description
tag

W500 LV power supply MCB Box Incoming LV Supply


W501 MCB Box RTU Panel Outgoing LV supply
W101 RTU Panel DMS IFC Cable 1: MV Switchgear Control & Monitoring (Umbilical cable)
W102 RTU Panel DMS IFC Cable 2: MV Switchgear Control & Monitoring (Umbilical cable)
W103 RTU Panel DMS IFC Cable 3: MV Switchgear Control & Monitoring (Umbilical cable)
Contractor : National Projects & Contruction LLC 1 SLD

Over All SLD


Employer : ALDAR Projects 2

Country of Origin
Consultant : PARSONS 3

Signal List
Client : ADDC 4

Tele-Information Plan
SS : RMU Substations 5

6 Cable Overview List


Internal Project No:

Adaptation Design
Project Name : Madinat Al Riyadh City Ph-6A & 6B 7

8 I/O Connection Diagram

MATERIAL SUBMITTAL: DMS-RTU for RMU.Rev.01


9 RTU Functional Specification

10 RTU Detailed Design

11 RTU Method Statement

12 RTU FAT Procedure

13 RTU SAT Procedure

14 POINT TO POINT TEST PROCEDURE

15 Warranty Certificate
LUCY RMU

SS No.

1. RD-1823 -2TR- PHASE 6B


2. RD-1833 -1TR- PHASE 6B
3. RD-1910 -2TR- PHASE 6B
SCHNEIDER RMU

SS No.
1. RD-2412 -2TR- PHASE 6A
2. RD-3012 -2TR- PHASE 6A
3. RD-3013 -2TR- PHASE 6A
4 PANEL BOARD - CONTROL & SIGNAL CABLE SCHEDULE
Project Madinat Al Riyadh - Phase 6, INFRASTRUCTURE & STREET SCAPE Equipment 22kV Switchgear to RTU Panel
END USER ABU DHABI DISTRIBUTION COMPANY Pg. No. 2
FROM TO
Cable Tag No. Required Qty for each Total Qty for each
Core Nos. Feeder/ Feeder Remarks No. of Run
TB No. DEVICE No. TB No. EQUIPMENT Ferrule No. Ferrule No. Substation(meters) substation in meters
Name
1 J01-XK-1 -- -- J01-XK-1/___ ___/J01-XK-1 CB-1 ON
2 J01-XK-3 -- -- J01-XK-3/___ ___/J01-XK-3 CB-1 OFF
3 J01-XK-7 J01-XK/ Transformer -- -- J01-XK-7/___ ___/J01-XK-7 PROTECTION RELAY (O/C + SBEF)FAULTY
RTU PANEL
4 J01-XK-9 Feeder-1 -- -- J01-XK-9/___ ___/J01-XK-9 OVERCURRENT TRIP
5 J01-XK-11 -- -- J01-XK-11/___ ___/J01-XK-11 EARTH FAULT & SBEF TRIP
6 J01-XK-12 -- -- J01-XK-12/___ ___/J01-XK-12 COMMON
7 J02-XK-1 -- -- J02-XK-1/___ ___/J02-XK-1 RING SWITCH-1 ON
J02-XK/ Ring Switch-
8 J02-XK-3 -- -- RTU PANEL J02-XK-3/___ ___/J02-XK-3 RING SWITCH-1 OFF
1
9 J02-XK-4 -- -- J02-XK-4/___ ___/J02-XK-4 COMMON
C1 10 J03-XK-1 -- -- J03-XK-1/___ ___/J03-XK-1 CB-2 ON 1 10 10
11 J03-XK-3 -- -- J03-XK-3/___ ___/J03-XK-3 CB-2 OFF
12 J03-XK-7 J03-XK/ Transformer -- -- J03-XK-7/___ ___/J03-XK-7 PROTECTION RELAY (O/C + SBEF)FAULTY
RTU PANEL
13 J03-XK-9 Feeder-2 -- -- J03-XK-9/___ ___/J03-XK-9 OVERCURRENT TRIP
14 J03-XK-11 -- -- J03-XK-11/___ ___/J03-XK-11 EARTH FAULT & SBEF TRIP
15 J03-XK-12 -- -- J03-XK-12/___ ___/J03-XK-12 COMMON
16 J04-XK-1 -- -- J04-XK-1/___ ___/J04-XK-1 RING SWITCH-2 ON
J04-XK/ Ring Switch-
17 J04-XK-3 -- -- RTU PANEL J04-XK-3/___ ___/J04-XK-3 RING SWITCH-2 OFF
2
18 J04-XK-4 -- -- J04-XK-4/___ ___/J04-XK-4 COMMON
19 SPARE
1 XK1-1 -- -- XK1-1/___ ___/XK1-1 EARTH FAULT STATUS FROM EFI
2 XK1-3 -- -- XK1-2/___ ___/XK1-2 SF6 LEVEL-1 INDICATION (LOW)
3 XK1-5 COMMON -- -- RTU PANEL XK1-4/___ ___/XK1-4 SF6 LEVEL-2 INDICATION (VERY LOW)
4 XK1-7 -- -- XK1-6/___ ___/XK1-6 MCB OFF (AC+DC)
5 XK1-8 -- -- XK1-8/___ ___/XK1-8 COMMON
6 SPARE
7 SPARE
8 SPARE
9 SPARE
C2 10 SPARE 1 10 10
11 SPARE
12 SPARE
13 SPARE
14 SPARE
15 SPARE
16 SPARE
17 SPARE
18 SPARE
19 SPARE
4 PANEL BOARD - CONTROL & SIGNAL CABLE SCHEDULE
Project Madinat Al Riyadh - Phase 6, INFRASTRUCTURE & STREET SCAPE Equipment 22kV Switchgear to RTU Panel
END USER ABU DHABI DISTRIBUTION COMPANY Pg. No. 2
FROM TO
Cable Tag No. Required Qty for each Total Qty for each
Core Nos. Feeder/ Feeder Remarks No. of Run
TB No. DEVICE No. TB No. EQUIPMENT Ferrule No. Ferrule No. Substation(meters) substation in meters
Name
1 J01-XK-5 J01-XK/ Transformer -- -- J01-XK-5/___ ___/J01-XK-5
RTU PANEL OPEN COMMAND
2 J01-XK-6 Feeder-1 -- -- J01-XK-6/___ ___/J01-XK-6
3 J02-XK-6 -- -- J02-XK-6/___ ___/J02-XK-6 CLOSE COMMAND
J02-XK/ Ring Switch-
C3 4 J02-XK-7 -- -- RTU PANEL J02-XK-7/___ ___/J02-XK-7 OPEN COMMAND 1 10 10
1
5 J02-XK-5 -- -- J02-XK-5/___ ___/J02-XK-5 COMMON
6 SPARE
7 SPARE
1 J03-XK-5 J03-XK/ Transformer -- -- J03-XK-5/___ ___/J03-XK-5
RTU PANEL OPEN COMMAND
2 J03-XK-6 Feeder-2 -- -- J03-XK-6/___ ___/J03-XK-6
3 J04-XK-6 -- -- J04-XK-6/___ ___/J04-XK-6 CLOSE COMMAND
J04-XK/ Ring Switch-
C4 4 J04-XK-7 -- -- RTU PANEL J04-XK-7/___ ___/J04-XK-7 OPEN COMMAND 1 10 10
2
5 J04-XK-5 -- -- J04-XK-5/___ ___/J04-XK-5 COMMON
6 SPARE
7 SPARE

1 J01-XK-13 -- -- J01-XK-13/___ ___/J01-XK-13


Transformer Feeder- CURRENT SIGNAL FROM TRANSDUCER OF TRAFO.
C5 RTU PANEL 1 10 10
1 FDR-1
2 J01-XK-14 -- -- J01-XK-14/___ ___/J01-XK-14

1 J03-XK-13 -- -- J03-XK-13/___ ___/J03-XK-13


Transformer Feeder- CURRENT SIGNAL FROM TRANSDUCER OF TRAFO.
C6 RTU PANEL 1 10 10
2 FDR-2
2 J03-XK-14 -- -- J03-XK-14/___ ___/J03-XK-14
RTU I/O Connection Schedule

Cable Schedule - RTU to Switchgear (QRM)

CABLE [1]
Connections for QRM Version with 24 Way Umbilical Cable: -

Non Alarm
Umbilical /
GEMINI V3.0 RMU MB
Cable Description Non
RTU Terminal No Terminal No
Core No Active
State
DSM 1A +24VS 1 K5/1 1 `+'24V DC (Switched) -
DSM 1A - 0VS 2 K22/1 2 ` 0V DC -
DSM 1A -SW1 DO 3 K10/1 3 J01 Open command NO
DSM 1A-SW1 DO 4 K12/1 4 J01 Close command NO
DSM 1A -SW1 DI 5 L4/1 8 J01 Close Indication NO
DSM 1A -SW1 DI 6 L5/1 9 J01 Open Indication NO
DSM 1A -DI COM 7 L3/1 7 J01 Common Indication -
DSM 1A -DI 1 8 L63/1 66/80 J01/J03 Earth Fault Indicator NO
DSM 1A -DI COM 9 L61/1 64/78 J01/J03 Earth Fault Indicator Common -
DSM 1A -DI 4 10 - Spare DI NO
DSM 1A – DI COM 11 - Spare DI Com -
DSM 2A +24VS 12 K5/2 15 `+'24V DC (Switched) NO
DSM 2A - 0VS 13 K22/2 16 ` 0V DC -
DSM 2A -SW1 DO 14 K10/2 17 J03 Open command NO
DSM 2A -SW1 DO 15 K12/2 18 J03 Close command NO
DSM 2A -SW1 DI 16 L4/2 22 J03 Close Indication NO
DSM 2A -SW1 DI 17 L5/2 23 J03 Open Indication NO
DSM 2A -DI COM 18 L3/2 21 J03 Common Indication -
DSM 2A -DI COM 19 L30 43 Low Gas Indicator Common -
DSM 2A -DI 3 20 L32 45 Low Gas Indicator NO
DSM 2A -DI 4 21 - Spare DI NO
DSM 2A – DI COM 22 - Spare DI com
Cable Schedule - RTU to Switchgear (QRM)

CABLE [2]
Connections for QRM Version with 19 Way Umbilical Cable: -

Non
Alarm
Umbilical
GEMINI V3.0 RMU MB /
Cable Description
RTU Terminal No Terminal No Non
Core No
Active
State
Aux TB 1 from Charger 1 K1 41 `+'24V DC (Switched to Interposing relay) -
Aux TB 2 from Charger 2 - 139/143/160 ` 0 Vdc -
DSM 1B -SW2 DO 3 K2 42 J02 Open Command NO
DSM 1B -SW2 DO 4 - - Spare -
DSM 1B -SW2 DI 5 L4/3 34 J02 Close Indication NO
DSM 1B -SW2 DI 6 L5/3 35 J02 Open Indication NO
DSM 1B -DI COM 7 L3/3 33 J02 Common Indication -
DSM 1B -DI COM 8 RL11 96 J02 Overcurrent/Earth fault trip Common NO
DSM 1B -DI 2 9 RL13 98 J02 Overcurrent/Earth fault trip -
DSM 1B -DI COM 10 RL03 95 J02 Protection Relay Failure Common -
DSM 1B -DI 4 11 RL01 93 J02 Protection Relay Failure -
DSM 1B -AI CT B 12 D30 122 J02 Y Phase CT -
DSM 1B -AI CT B 13 D130 124 J02 Y Phase CT -
DSM 1B -DI 4 14 - Spare DI NO
DSM 1B -DI COM 15 - Spare DI com
DSM 1B -DO 1 16 - Spare DI NO
DSM 1B- DO1 COM 17 - Spare DI com
Cable Schedule - RTU to Switchgear (QRM)

CABLE [3]
Connections for QRM Version Only with 19 Way Umbilical Cable: -

Non
Alarm
Umbilical
GEMINI V3.0 RMU MB /
Cable Description
RTU Terminal No Terminal No Non
Core No
Active
State
Aux TB 3 from Charger 1 K1 41 `+'24V DC (Switched to Interposing relay) -
Aux TB 4 from Charger 2 - 139/143/160 ` 0 Vdc -
DSM 2B -SW2 DO 3 K2 42 J04 Open Command NO
DSM 2B -SW2 DO 4 - - Spare -
DSM 2B -SW2 DI 5 L4/4 34 J04 Close Indication NO
DSM 2B -SW2 DI 6 L5/4 35 J04 Open Indication NO
DSM 2B -DI COM 7 L3/4 33 J04 Common Indication -
DSM 2B -DI COM 8 RL11 96 J04 Overcurrent/Earth fault trip Common NO
DSM 2B -DI 2 9 RL13 98 J04 Overcurrent/Earth fault trip -
DSM 2B -DI COM 10 RL03 95 J04 Protection Relay Failure Common -
DSM 2B -DI 4 11 RL01 93 J04 Protection Relay Failure -
DSM 2B -AI CT B 12 D30 122 J04 Y Phase CT -
DSM 2B -AI CT B 13 D130 124 J04 Y Phase CT -
DSM 2B -DI 4 14 - Spare DI NO
DSM 2B -DI COM 15 - Spare DI com
DSM 2B -DO 1 16 - Spare DI NO
DSM 2B- DO1 COM 17 - Spare DI com
Cable Overview / QRM

Cable
From To Description
tag

W500 LV power supply MCB Box Incoming LV Supply


W501 MCB Box RTU Panel Outgoing LV supply
W101 RTU Panel DMS IFC Cable 1: MV Switchgear Control & Monitoring (Umbilical cable)
W102 RTU Panel DMS IFC Cable 2: MV Switchgear Control & Monitoring (Umbilical cable)
W103 RTU Panel DMS IFC Cable 3: MV Switchgear Control & Monitoring (Umbilical cable)
RTU I/O Connection Schedule

Cable Schedule - RTU to Switchgear (TRM)

CABLE [1]
Connections for QRM Version with 24 Way Umbilical Cable: -

Non Alarm
Umbilical /
GEMINI V3.0 RMU MB
Cable Description Non
RTU Terminal No Terminal No
Core No Active
State
DSM 1A +24VS 1 K5/1 1 `+'24V DC (Switched) -
DSM 1A - 0VS 2 K22/1 2 ` 0V DC -
DSM 1A -SW1 DO 3 K10/1 3 J01 Open command NO
DSM 1A-SW1 DO 4 K12/1 4 J01 Close command NO
DSM 1A -SW1 DI 5 L4/1 8 J01 Close Indication NO
DSM 1A -SW1 DI 6 L5/1 9 J01 Open Indication NO
DSM 1A -DI COM 7 L3/1 7 J01 Common Indication -
DSM 1A -DI 1 8 L63/1 66/80 J01/J03 Earth Fault Indicator NO
DSM 1A -DI COM 9 L61/1 64/78 J01/J03 Earth Fault Indicator Common -
DSM 1A -DI 4 10 - Spare DI NO
DSM 1A – DI COM 11 - Spare DI Com -
DSM 2A +24VS 12 K5/2 15 `+'24V DC (Switched) NO
DSM 2A - 0VS 13 K22/2 16 ` 0V DC -
DSM 2A -SW1 DO 14 K10/2 17 J03 Open command NO
DSM 2A -SW1 DO 15 K12/2 18 J03 Close command NO
DSM 2A -SW1 DI 16 L4/2 22 J03 Close Indication NO
DSM 2A -SW1 DI 17 L5/2 23 J03 Open Indication NO
DSM 2A -DI COM 18 L3/2 21 J03 Common Indication -
DSM 2A -DI COM 19 L30 43 Low Gas Indicator Common -
DSM 2A -DI 3 20 L32 45 Low Gas Indicator NO
DSM 2A -DI 4 21 - Spare DI NO
DSM 2A – DI COM 22 - Spare DI com
Cable Schedule - RTU to Switchgear (TRM)

CABLE [2]
Connections for QRM Version with 19 Way Umbilical Cable: -

Non
Alarm
Umbilical
GEMINI V3.0 RMU MB /
Cable Description
RTU Terminal No Terminal No Non
Core No
Active
State
Aux TB 1 from Charger 1 K1 41 `+'24V DC (Switched to Interposing relay) -
Aux TB 2 from Charger 2 - 139/143/160 ` 0 Vdc -
DSM 1B -SW2 DO 3 K2 42 K02 Open Command NO
DSM 1B -SW2 DO 4 - - Spare -
DSM 1B -SW2 DI 5 L4/3 34 J02 Close Indication NO
DSM 1B -SW2 DI 6 L5/3 35 J02 Open Indication NO
DSM 1B -DI COM 7 L3/3 33 J02 Common Indication -
DSM 1B -DI COM 8 RL11 96 J02 Overcurrent/Earth fault trip Common NO
DSM 1B -DI 2 9 RL13 98 J02 Overcurrent/Earth fault trip -
DSM 1B -DI COM 10 RL03 95 J02 Protection Relay Failure Common -
DSM 1B -DI 4 11 RL01 93 J02 Protection Relay Failure -
DSM 1B -AI CT B 12 D30 122 J02 Y Phase CT -
DSM 1B -AI CT B 13 D130 124 J02 Y Phase CT -
DSM 1B -DI 4 14 - Spare DI NO
DSM 1B -DI COM 15 - Spare DI com
DSM 1B -DO 1 16 - Spare DI NO
DSM 1B- DO1 COM 17 - Spare DI com
Cable Overview / QRM

Cable
From To Description
tag

W500 LV power supply MCB Box Incoming LV Supply


W501 MCB Box RTU Panel Outgoing LV supply
W101 RTU Panel DMS IFC Cable 1: MV Switchgear Control & Monitoring (Umbilical cable)
W102 RTU Panel DMS IFC Cable 2: MV Switchgear Control & Monitoring (Umbilical cable)
Contractor : National Projects & Contruction LLC 1 SLD

Over All SLD


Employer : ALDAR Projects 2

Country of Origin
Consultant : PARSONS 3

Signal List
Client : ADDC 4

Tele-Information Plan
SS : RMU Substations 5

6 Cable Overview List


Internal Project No:

Adaptation Design
Project Name : Madinat Al Riyadh City Ph-6A & 6B 7

8 I/O Connection Diagram

MATERIAL SUBMITTAL: DMS-RTU for RMU.Rev.01


9 RTU Functional Specification

10 RTU Detailed Design

11 RTU Method Statement

12 RTU FAT Procedure

13 RTU SAT Procedure

14 POINT TO POINT TEST PROCEDURE

15 Warranty Certificate
IO Typical QRM

Station Type : Station Name : Station Address: IP Address: MAC Address:


SS Substation RD3013 RD3013
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling
I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status

Box )
Baytype ( Comment ) Remarks
YY01 RTU DO 01 LUCY DSM 2A - 01 030/000/108 RD3013 00 00 C.Station (22kV Common) DC DUMMY RELAY OFF - YY01 DO-17B
YY01 RTU DO 02 LUCY DSM 2A - 01 030/000/108 RD3013 00 00 -C.Station (22kV Common) DC DUMMY RELAY ON - YY01 DO-18B
YY01 RTU DO 03 LUCY DSM 1A DO-SW A 01 041/001/112 RD3013 SS - 22 A01-FE (22kV Feeder-LBS - 1) - DC LISO_C LOAD ISOLATOR OPEN W101 C J01.XK MDF J01 9
YY01 RTU DO 04 LUCY DSM 1A DO-SW A 01 041/001/112 RD3013 SS - 22 A01-FE (22kV Feeder LBS - 1) - DC LISC_C LOAD ISOLATOR CLOSED W101 D J01.XK MDF J01 7
YY01 RTU DO 05 LUCY DSM 1B DO-SW B 01 042/002/104 RD3013 SS - 22 A02-FE (22kV Transformer CB - 1) DC CBO_C CIRCUIT BREAKER OPEN W102 C J02.XK MDF J02 4
01 042/002/104 RD3013 SS - 22 -A02-FE (22kV Transformer CB - 1) DC CBC_C CIRCUIT BREAKER CLOSED
YY01 RTU DO 06 LUCY DSM 2A DO-SW A 01 041/003/112 RD3013 SS - 22 -A03-FE (22kV Feeder LBS - 2) - DC LISO_C LOAD ISOLATOR OPEN W101 K J03.XK MDF J03 9
YY01 RTU DO 07 LUCY DSM 2A DO-SW A 01 041/003/112 RD3013 SS - 22 A03-FE (22kV Feeder LBS - 2) - DC LISC_C LOAD ISOLATOR CLOSED W101 L J03.XK MDF J03 7
YY01 RTU DO 08 LUCY DSM 2B DO-SW B 01 042/004/104 RD3013 SS - 22 A04-FE (22kV Transformer CB - 2) DC CBO_C CIRCUIT BREAKER OPEN W103 C J04.XK MDF J04 4
01 042/002/104 RD3013 SS - 22 -A04-FE (22kV Transformer CB - 2) DC CBC_C CIRCUIT BREAKER CLOSED
-
YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W101 A J01.XK MDF J01 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J01.XK MDF J01 2
YY01 RTU C/R LUCY DSM 1A DI SW A 01 Common Return (C/R) W102 G J01.XK MDF J01 2&4
YY01 RTU C/R LUCY DSM 1A DI 1 01 Common Return (C/R) W102 J J01.XK MDF J01 6
YY01 RTU C/R LUCY DSM 1A DI 4 01 Common Return (C/R) W102 M J01.XK MDF J01
YY01 RTU C/R LUCY DSM 2 A DI SW A 01 Common Return (C/R) W102 P J03.XK MDF J03 2&4
YY01 RTU C/R LUCY DSM 2 A DI 3 01 Common Return (C/R) W102 P J03.XK MDF J03 6
YY01 RTU C/R LUCY DSM 2 A DI 4 01 Common Return (C/R) W102 P J03.XK MDF J03

YY01 RTU A1 01 LUCY DSM 1B AI-SW B 01 042/002/132 RD3013 SS - 22 A02-FE (22kV Transformer CB - 1) M A+ CURRENT + W102 T J02.XK MDF J02 5
YY01 RTU A1 02 LUCY DSM 1B AI-SW B 01 042/002/132 RD3013 SS - 22 -A02-FE (22kV Transformer CB - 1) M A- CURRENT - W102 V J02.XK MDF J02 6
YY01 RTU A1 03 LUCY DSM 2B AI-SW B 01 042/004/132 RD3013 SS - 22 -A04-FE (22kV Transformer CB - 2) M A+ CURRENT + W103 T J04.XK MDF J04 5
YY01 RTU A1 04 LUCY DSM 2B AI-SW B 01 042/004/132 RD3013 SS - 22 -A04-FE (22kV Transformer CB - 2) M A- CURRENT - W103 V J04.XK MDF J04 6
-
YY01 RTU PS L1 01 RTU AC SUPPLY W501 bk YH01 230V AC P
YY01 RTU PS N 01 RTU AC SUPPLY W501 bu YH01 230V AC N

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J02.XK MDF J02 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J02.XK MDF J02 2
YY01 RTU C/R LUCY DSM 1B DI SW B 01 Common Return (C/R) W103 G J02.XK MDF J02 2&4
YY01 RTU C/R LUCY DSM 1B DI 4 01 Common Return (C/R) W103 J xx MDF J02 8
YY01 RTU C/R LUCY DSM 1B DI 2 01 Common Return (C/R) W103 M J02.XK MDF J02 8 & 10
YY01 RTU C/R LUCY DSM 1B DI 1 01 Common Return (C/R) W103 P J02.XK MDF J02 12

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J04.XK MDF J04 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J04.XK MDF J04 2
YY01 RTU C/R LUCY DSM 2B DI SW B 01 Common Return (C/R) W103 G J04.XK MDF J04 2&4
YY01 RTU C/R LUCY DSM 2B DI 4 01 Common Return (C/R) W103 J J04.XK MDF J04 8
YY01 RTU C/R LUCY DSM 2B DI 2 01 Common Return (C/R) W103 M J04.XK MDF J04 8 & 10
YY01 RTU C/R LUCY DSM 2B DI 1 01 Common Return (C/R) W103 P J04.XK MDF J04 12
IO Typical QRM(L EFI)

Station Type : Station Name :


SS Substation RD2412
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling Box


I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status
Baytype ( Comment ) Remarks

)
YY01 RTU DI 01 LUCY DSM 2A - 01 030/000/005 RD3013 00 00 C.Station (22kV Common) - DP DUM OFF DUMMY RELAY OFF - 0 YY01 DI-15A
YY01 RTU DI 02 LUCY DSM 2A - 01 030/000/005 RD3013 00 00 C.Station (22kV Common) - DP DUM ON DUMMY RELAY ON - 0 YY01 DI-16A
YY01 RTU DI 03 LUCY MCM - 01 030/000/042 RD3013 00 00 C.Station (22kV Common) - SP MCBA MCB Alarm - 0 YY01
YY01 RTU DI 04 LUCY ADEL - 01 030/000/250 RD3013 00 00 C.Station (22kV Common) - SP 24VDCAL 24V DC Alarm - 0 YY01
YY01 RTU DI 05 LUCY MCM - 01 030/000/201 RD3013 00 00 C.Station (22kV Common) - SP STNL/R Station Control Local / Remote - 0 YY01
YY01 RTU DI 06 LUCY DSM 2A DI-3 01 030/000/041 RD3013 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W102 H XX MDF CS 7
01 030/000/041 RD3013 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W103 H XX MDF CS 8

YY01 RTU DI 07 LUCY DSM 1A DI-SWA Open 01 041/001/012 RD3013 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISO LOAD ISOLATOR OPEN W101 F J01.XK MDF J01 1
YY01 RTU DI 08 LUCY DSM 1A DI-SWA Close 01 041/001/012 RD3013 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISC LOAD ISOLATOR CLOSED W101 E J01.XK MDF J01 3
YY01 RTU DI 15 LUCY DSM 1A DI-1 01 041/003/033 RD3013 SS - 22 A03-FE (22kV Feeder LBS - 2) - SP EFI Earth Fault Indication W101 H J01.XK MDF J01 5

YY01 RTU DI 09 LUCY DSM 1B DI-SWA Open 01 042/002/001 RD3013 SS - 22 A02-FE (22kV Transformer CB - 1) DP CBO CIRCUIT BREAKER OPEN W102 F J02.XK MDF J02 3
YY01 RTU DI 10 LUCY DSM 1B DI-SWA Close 01 042/002/001 RD3013 SS - 22 -A02-FE (22kV Transformer CB - 1) DP CBC CIRCUIT BREAKER CLOSED W102 E J02.XK MDF J02 1
YY01 RTU DI 11 LUCY DSM 1B DI-2 01 042/002/205 RD3013 SS - 22 -A02-FE (22kV Transformer CB - 1) FL OCEFT Over Current/Earth Fault Trip W102 R J02.XK MDF J02 7&9
YY01 RTU DI 12 LUCY DSM 1B DI-1 01 042/002/247 RD3013 SS - 22 -A02-FE (22kV Transformer CB - 1) SP PRF Protection Relay Faulty W102 N J02.XK MDF J02 11
-

YY01 RTU DI 13 LUCY DSM 2A DI-SWA Open 01 041/003/012 RD3013 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISO LOAD ISOLATOR OPEN W101 P J03.XK MDF J03 1
YY01 RTU DI 14 LUCY DSM 2A DI-SWA Close 01 041/003/012 RD3013 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISC LOAD ISOLATOR CLOSED W101 M J03.XK MDF J03 3

YY01 RTU DI 16 LUCY DSM 2B DI-SWA Open 01 042/004/001 RD3013 SS - 22 A04-FE (22kV Transformer CB - 2) DP CBO CIRCUIT BREAKER OPEN W103 F J04.XK MDF J04 3
YY01 RTU DI 17 LUCY DSM 2B DI-SWA Close 01 042/004/001 RD3013 SS - 22 -A04-FE (22kV Transformer CB - 2) DP CBC CIRCUIT BREAKER CLOSED W103 E J04.XK MDF J04 1
YY01 RTU DI 18 LUCY DSM 2B DI-2 01 042/004/205 RD3013 SS - 22 -A04-FE (22kV Transformer CB - 2) FL OCEFT Over Current/Earth Fault Trip W103 R J04.XK MDF J04 7&9
YY01 RTU DI 19 LUCY DSM 2B DI-1 01 042/004/247 RD3013 SS - 22 -
A04-FE (22kV Transformer CB - 2) - SP PRF Protection Relay Faulty W103 N J04.XK MDF J04 11
IO Typical QRM

Station Type : Station Name : Station Address: IP Address: MAC Address:


SS Substation RD3012 RD3012
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling
I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status

Box )
Baytype ( Comment ) Remarks
YY01 RTU DO 01 LUCY DSM 2A - 01 030/000/108 RD3012 00 00 C.Station (22kV Common) DC DUMMY RELAY OFF - YY01 DO-17B
YY01 RTU DO 02 LUCY DSM 2A - 01 030/000/108 RD3012 00 00 -C.Station (22kV Common) DC DUMMY RELAY ON - YY01 DO-18B
YY01 RTU DO 03 LUCY DSM 1A DO-SW A 01 041/001/112 RD3012 SS - 22 A01-FE (22kV Feeder-LBS - 1) - DC LISO_C LOAD ISOLATOR OPEN W101 C J01.XK MDF J01 9
YY01 RTU DO 04 LUCY DSM 1A DO-SW A 01 041/001/112 RD3012 SS - 22 A01-FE (22kV Feeder LBS - 1) - DC LISC_C LOAD ISOLATOR CLOSED W101 D J01.XK MDF J01 7
YY01 RTU DO 05 LUCY DSM 1B DO-SW B 01 042/002/104 RD3012 SS - 22 A02-FE (22kV Transformer CB - 1) DC CBO_C CIRCUIT BREAKER OPEN W102 C J02.XK MDF J02 4
01 042/002/104 RD3012 SS - 22 -A02-FE (22kV Transformer CB - 1) DC CBC_C CIRCUIT BREAKER CLOSED
YY01 RTU DO 06 LUCY DSM 2A DO-SW A 01 041/003/112 RD3012 SS - 22 -A03-FE (22kV Feeder LBS - 2) - DC LISO_C LOAD ISOLATOR OPEN W101 K J03.XK MDF J03 9
YY01 RTU DO 07 LUCY DSM 2A DO-SW A 01 041/003/112 RD3012 SS - 22 A03-FE (22kV Feeder LBS - 2) - DC LISC_C LOAD ISOLATOR CLOSED W101 L J03.XK MDF J03 7
YY01 RTU DO 08 LUCY DSM 2B DO-SW B 01 042/004/104 RD3012 SS - 22 A04-FE (22kV Transformer CB - 2) DC CBO_C CIRCUIT BREAKER OPEN W103 C J04.XK MDF J04 4
01 042/002/104 RD3012 SS - 22 -A04-FE (22kV Transformer CB - 2) DC CBC_C CIRCUIT BREAKER CLOSED
-
YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W101 A J01.XK MDF J01 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J01.XK MDF J01 2
YY01 RTU C/R LUCY DSM 1A DI SW A 01 Common Return (C/R) W102 G J01.XK MDF J01 2&4
YY01 RTU C/R LUCY DSM 1A DI 1 01 Common Return (C/R) W102 J J01.XK MDF J01 6
YY01 RTU C/R LUCY DSM 1A DI 4 01 Common Return (C/R) W102 M J01.XK MDF J01
YY01 RTU C/R LUCY DSM 2 A DI SW A 01 Common Return (C/R) W102 P J03.XK MDF J03 2&4
YY01 RTU C/R LUCY DSM 2 A DI 3 01 Common Return (C/R) W102 P J03.XK MDF J03 6
YY01 RTU C/R LUCY DSM 2 A DI 4 01 Common Return (C/R) W102 P J03.XK MDF J03

YY01 RTU A1 01 LUCY DSM 1B AI-SW B 01 042/002/132 RD3012 SS - 22 A02-FE (22kV Transformer CB - 1) M A+ CURRENT + W102 T J02.XK MDF J02 5
YY01 RTU A1 02 LUCY DSM 1B AI-SW B 01 042/002/132 RD3012 SS - 22 -A02-FE (22kV Transformer CB - 1) M A- CURRENT - W102 V J02.XK MDF J02 6
YY01 RTU A1 03 LUCY DSM 2B AI-SW B 01 042/004/132 RD3012 SS - 22 -A04-FE (22kV Transformer CB - 2) M A+ CURRENT + W103 T J04.XK MDF J04 5
YY01 RTU A1 04 LUCY DSM 2B AI-SW B 01 042/004/132 RD3012 SS - 22 -A04-FE (22kV Transformer CB - 2) M A- CURRENT - W103 V J04.XK MDF J04 6
-
YY01 RTU PS L1 01 RTU AC SUPPLY W501 bk YH01 230V AC P
YY01 RTU PS N 01 RTU AC SUPPLY W501 bu YH01 230V AC N

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J02.XK MDF J02 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J02.XK MDF J02 2
YY01 RTU C/R LUCY DSM 1B DI SW B 01 Common Return (C/R) W103 G J02.XK MDF J02 2&4
YY01 RTU C/R LUCY DSM 1B DI 4 01 Common Return (C/R) W103 J xx MDF J02 8
YY01 RTU C/R LUCY DSM 1B DI 2 01 Common Return (C/R) W103 M J02.XK MDF J02 8 & 10
YY01 RTU C/R LUCY DSM 1B DI 1 01 Common Return (C/R) W103 P J02.XK MDF J02 12

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J04.XK MDF J04 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J04.XK MDF J04 2
YY01 RTU C/R LUCY DSM 2B DI SW B 01 Common Return (C/R) W103 G J04.XK MDF J04 2&4
YY01 RTU C/R LUCY DSM 2B DI 4 01 Common Return (C/R) W103 J J04.XK MDF J04 8
YY01 RTU C/R LUCY DSM 2B DI 2 01 Common Return (C/R) W103 M J04.XK MDF J04 8 & 10
YY01 RTU C/R LUCY DSM 2B DI 1 01 Common Return (C/R) W103 P J04.XK MDF J04 12
IO Typical QRM(L EFI)

Station Type : Station Name :


SS Substation RD2412
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling Box


I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status
Baytype ( Comment ) Remarks

)
YY01 RTU DI 01 LUCY DSM 2A - 01 030/000/005 RD3012 00 00 C.Station (22kV Common) - DP DUM OFF DUMMY RELAY OFF - 0 YY01 DI-15A
YY01 RTU DI 02 LUCY DSM 2A - 01 030/000/005 RD3012 00 00 C.Station (22kV Common) - DP DUM ON DUMMY RELAY ON - 0 YY01 DI-16A
YY01 RTU DI 03 LUCY MCM - 01 030/000/042 RD3012 00 00 C.Station (22kV Common) - SP MCBA MCB Alarm - 0 YY01
YY01 RTU DI 04 LUCY ADEL - 01 030/000/250 RD3012 00 00 C.Station (22kV Common) - SP 24VDCAL 24V DC Alarm - 0 YY01
YY01 RTU DI 05 LUCY MCM - 01 030/000/201 RD3012 00 00 C.Station (22kV Common) - SP STNL/R Station Control Local / Remote - 0 YY01
YY01 RTU DI 06 LUCY DSM 2A DI-3 01 030/000/041 RD3012 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W102 H XX MDF CS 7
01 030/000/041 RD3012 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W103 H XX MDF CS 8

YY01 RTU DI 07 LUCY DSM 1A DI-SWA Open 01 041/001/012 RD3012 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISO LOAD ISOLATOR OPEN W101 F J01.XK MDF J01 1
YY01 RTU DI 08 LUCY DSM 1A DI-SWA Close 01 041/001/012 RD3012 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISC LOAD ISOLATOR CLOSED W101 E J01.XK MDF J01 3
YY01 RTU DI 15 LUCY DSM 1A DI-1 01 041/003/033 RD3012 SS - 22 A03-FE (22kV Feeder LBS - 2) - SP EFI Earth Fault Indication W101 H J01.XK MDF J01 5

YY01 RTU DI 09 LUCY DSM 1B DI-SWA Open 01 042/002/001 RD3012 SS - 22 A02-FE (22kV Transformer CB - 1) DP CBO CIRCUIT BREAKER OPEN W102 F J02.XK MDF J02 3
YY01 RTU DI 10 LUCY DSM 1B DI-SWA Close 01 042/002/001 RD3012 SS - 22 -A02-FE (22kV Transformer CB - 1) DP CBC CIRCUIT BREAKER CLOSED W102 E J02.XK MDF J02 1
YY01 RTU DI 11 LUCY DSM 1B DI-2 01 042/002/205 RD3012 SS - 22 -A02-FE (22kV Transformer CB - 1) FL OCEFT Over Current/Earth Fault Trip W102 R J02.XK MDF J02 7&9
YY01 RTU DI 12 LUCY DSM 1B DI-1 01 042/002/247 RD3012 SS - 22 -A02-FE (22kV Transformer CB - 1) SP PRF Protection Relay Faulty W102 N J02.XK MDF J02 11
-

YY01 RTU DI 13 LUCY DSM 2A DI-SWA Open 01 041/003/012 RD3012 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISO LOAD ISOLATOR OPEN W101 P J03.XK MDF J03 1
YY01 RTU DI 14 LUCY DSM 2A DI-SWA Close 01 041/003/012 RD3012 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISC LOAD ISOLATOR CLOSED W101 M J03.XK MDF J03 3

YY01 RTU DI 16 LUCY DSM 2B DI-SWA Open 01 042/004/001 RD3012 SS - 22 A04-FE (22kV Transformer CB - 2) DP CBO CIRCUIT BREAKER OPEN W103 F J04.XK MDF J04 3
YY01 RTU DI 17 LUCY DSM 2B DI-SWA Close 01 042/004/001 RD3012 SS - 22 -A04-FE (22kV Transformer CB - 2) DP CBC CIRCUIT BREAKER CLOSED W103 E J04.XK MDF J04 1
YY01 RTU DI 18 LUCY DSM 2B DI-2 01 042/004/205 RD3012 SS - 22 -A04-FE (22kV Transformer CB - 2) FL OCEFT Over Current/Earth Fault Trip W103 R J04.XK MDF J04 7&9
YY01 RTU DI 19 LUCY DSM 2B DI-1 01 042/004/247 RD3012 SS - 22 -
A04-FE (22kV Transformer CB - 2) - SP PRF Protection Relay Faulty W103 N J04.XK MDF J04 11
IO Typical QRM

Station Type : Station Name : Station Address: IP Address: MAC Address:


SS Substation RD2412 RD2412
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling
I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status

Box )
Baytype ( Comment ) Remarks
YY01 RTU DO 01 LUCY DSM 2A - 01 030/000/108 RD2412 00 00 C.Station (22kV Common) DC DUMMY RELAY OFF - YY01 DO-17B
YY01 RTU DO 02 LUCY DSM 2A - 01 030/000/108 RD2412 00 00 -C.Station (22kV Common) DC DUMMY RELAY ON - YY01 DO-18B
YY01 RTU DO 03 LUCY DSM 1A DO-SW A 01 041/001/112 RD2412 SS - 22 A01-FE (22kV Feeder-LBS - 1) - DC LISO_C LOAD ISOLATOR OPEN W101 C J01.XK MDF J01 9
YY01 RTU DO 04 LUCY DSM 1A DO-SW A 01 041/001/112 RD2412 SS - 22 A01-FE (22kV Feeder LBS - 1) - DC LISC_C LOAD ISOLATOR CLOSED W101 D J01.XK MDF J01 7
YY01 RTU DO 05 LUCY DSM 1B DO-SW B 01 042/002/104 RD2412 SS - 22 A02-FE (22kV Transformer CB - 1) DC CBO_C CIRCUIT BREAKER OPEN W102 C J02.XK MDF J02 4
01 042/002/104 RD2412 SS - 22 -A02-FE (22kV Transformer CB - 1) DC CBC_C CIRCUIT BREAKER CLOSED
YY01 RTU DO 06 LUCY DSM 2A DO-SW A 01 041/003/112 RD2412 SS - 22 -A03-FE (22kV Feeder LBS - 2) - DC LISO_C LOAD ISOLATOR OPEN W101 K J03.XK MDF J03 9
YY01 RTU DO 07 LUCY DSM 2A DO-SW A 01 041/003/112 RD2412 SS - 22 A03-FE (22kV Feeder LBS - 2) - DC LISC_C LOAD ISOLATOR CLOSED W101 L J03.XK MDF J03 7
YY01 RTU DO 08 LUCY DSM 2B DO-SW B 01 042/004/104 RD2412 SS - 22 A04-FE (22kV Transformer CB - 2) DC CBO_C CIRCUIT BREAKER OPEN W103 C J04.XK MDF J04 4
01 042/002/104 RD2412 SS - 22 -A04-FE (22kV Transformer CB - 2) DC CBC_C CIRCUIT BREAKER CLOSED
-
YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W101 A J01.XK MDF J01 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J01.XK MDF J01 2
YY01 RTU C/R LUCY DSM 1A DI SW A 01 Common Return (C/R) W102 G J01.XK MDF J01 2&4
YY01 RTU C/R LUCY DSM 1A DI 1 01 Common Return (C/R) W102 J J01.XK MDF J01 6
YY01 RTU C/R LUCY DSM 1A DI 4 01 Common Return (C/R) W102 M J01.XK MDF J01
YY01 RTU C/R LUCY DSM 2 A DI SW A 01 Common Return (C/R) W102 P J03.XK MDF J03 2&4
YY01 RTU C/R LUCY DSM 2 A DI 3 01 Common Return (C/R) W102 P J03.XK MDF J03 6
YY01 RTU C/R LUCY DSM 2 A DI 4 01 Common Return (C/R) W102 P J03.XK MDF J03

YY01 RTU A1 01 LUCY DSM 1B AI-SW B 01 042/002/132 RD2412 SS - 22 A02-FE (22kV Transformer CB - 1) M A+ CURRENT + W102 T J02.XK MDF J02 5
YY01 RTU A1 02 LUCY DSM 1B AI-SW B 01 042/002/132 RD2412 SS - 22 -A02-FE (22kV Transformer CB - 1) M A- CURRENT - W102 V J02.XK MDF J02 6
YY01 RTU A1 03 LUCY DSM 2B AI-SW B 01 042/004/132 RD2412 SS - 22 -A04-FE (22kV Transformer CB - 2) M A+ CURRENT + W103 T J04.XK MDF J04 5
YY01 RTU A1 04 LUCY DSM 2B AI-SW B 01 042/004/132 RD2412 SS - 22 -A04-FE (22kV Transformer CB - 2) M A- CURRENT - W103 V J04.XK MDF J04 6
-
YY01 RTU PS L1 01 RTU AC SUPPLY W501 bk YH01 230V AC P
YY01 RTU PS N 01 RTU AC SUPPLY W501 bu YH01 230V AC N

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J02.XK MDF J02 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J02.XK MDF J02 2
YY01 RTU C/R LUCY DSM 1B DI SW B 01 Common Return (C/R) W103 G J02.XK MDF J02 2&4
YY01 RTU C/R LUCY DSM 1B DI 4 01 Common Return (C/R) W103 J xx MDF J02 8
YY01 RTU C/R LUCY DSM 1B DI 2 01 Common Return (C/R) W103 M J02.XK MDF J02 8 & 10
YY01 RTU C/R LUCY DSM 1B DI 1 01 Common Return (C/R) W103 P J02.XK MDF J02 12

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J04.XK MDF J04 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J04.XK MDF J04 2
YY01 RTU C/R LUCY DSM 2B DI SW B 01 Common Return (C/R) W103 G J04.XK MDF J04 2&4
YY01 RTU C/R LUCY DSM 2B DI 4 01 Common Return (C/R) W103 J J04.XK MDF J04 8
YY01 RTU C/R LUCY DSM 2B DI 2 01 Common Return (C/R) W103 M J04.XK MDF J04 8 & 10
YY01 RTU C/R LUCY DSM 2B DI 1 01 Common Return (C/R) W103 P J04.XK MDF J04 12
IO Typical QRM(L EFI)

Station Type : Station Name :


SS Substation RD2412
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling Box


I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status
Baytype ( Comment ) Remarks

)
YY01 RTU DI 01 LUCY DSM 2A - 01 030/000/005 RD2412 00 00 C.Station (22kV Common) - DP DUM OFF DUMMY RELAY OFF - 0 YY01 DI-15A
YY01 RTU DI 02 LUCY DSM 2A - 01 030/000/005 RD2412 00 00 C.Station (22kV Common) - DP DUM ON DUMMY RELAY ON - 0 YY01 DI-16A
YY01 RTU DI 03 LUCY MCM - 01 030/000/042 RD2412 00 00 C.Station (22kV Common) - SP MCBA MCB Alarm - 0 YY01
YY01 RTU DI 04 LUCY ADEL - 01 030/000/250 RD2412 00 00 C.Station (22kV Common) - SP 24VDCAL 24V DC Alarm - 0 YY01
YY01 RTU DI 05 LUCY MCM - 01 030/000/201 RD2412 00 00 C.Station (22kV Common) - SP STNL/R Station Control Local / Remote - 0 YY01
YY01 RTU DI 06 LUCY DSM 2A DI-3 01 030/000/041 RD2412 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W102 H XX MDF CS 7
01 030/000/041 RD2412 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W103 H XX MDF CS 8

YY01 RTU DI 07 LUCY DSM 1A DI-SWA Open 01 041/001/012 RD2412 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISO LOAD ISOLATOR OPEN W101 F J01.XK MDF J01 1
YY01 RTU DI 08 LUCY DSM 1A DI-SWA Close 01 041/001/012 RD2412 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISC LOAD ISOLATOR CLOSED W101 E J01.XK MDF J01 3
YY01 RTU DI 15 LUCY DSM 1A DI-1 01 041/003/033 RD2412 SS - 22 A03-FE (22kV Feeder LBS - 2) - SP EFI Earth Fault Indication W101 H J01.XK MDF J01 5

YY01 RTU DI 09 LUCY DSM 1B DI-SWA Open 01 042/002/001 RD2412 SS - 22 A02-FE (22kV Transformer CB - 1) DP CBO CIRCUIT BREAKER OPEN W102 F J02.XK MDF J02 3
YY01 RTU DI 10 LUCY DSM 1B DI-SWA Close 01 042/002/001 RD2412 SS - 22 -A02-FE (22kV Transformer CB - 1) DP CBC CIRCUIT BREAKER CLOSED W102 E J02.XK MDF J02 1
YY01 RTU DI 11 LUCY DSM 1B DI-2 01 042/002/205 RD2412 SS - 22 -A02-FE (22kV Transformer CB - 1) FL OCEFT Over Current/Earth Fault Trip W102 R J02.XK MDF J02 7&9
YY01 RTU DI 12 LUCY DSM 1B DI-1 01 042/002/247 RD2412 SS - 22 -A02-FE (22kV Transformer CB - 1) SP PRF Protection Relay Faulty W102 N J02.XK MDF J02 11
-

YY01 RTU DI 13 LUCY DSM 2A DI-SWA Open 01 041/003/012 RD2412 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISO LOAD ISOLATOR OPEN W101 P J03.XK MDF J03 1
YY01 RTU DI 14 LUCY DSM 2A DI-SWA Close 01 041/003/012 RD2412 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISC LOAD ISOLATOR CLOSED W101 M J03.XK MDF J03 3

YY01 RTU DI 16 LUCY DSM 2B DI-SWA Open 01 042/004/001 RD2412 SS - 22 A04-FE (22kV Transformer CB - 2) DP CBO CIRCUIT BREAKER OPEN W103 F J04.XK MDF J04 3
YY01 RTU DI 17 LUCY DSM 2B DI-SWA Close 01 042/004/001 RD2412 SS - 22 -A04-FE (22kV Transformer CB - 2) DP CBC CIRCUIT BREAKER CLOSED W103 E J04.XK MDF J04 1
YY01 RTU DI 18 LUCY DSM 2B DI-2 01 042/004/205 RD2412 SS - 22 -A04-FE (22kV Transformer CB - 2) FL OCEFT Over Current/Earth Fault Trip W103 R J04.XK MDF J04 7&9
YY01 RTU DI 19 LUCY DSM 2B DI-1 01 042/004/247 RD2412 SS - 22 -
A04-FE (22kV Transformer CB - 2) - SP PRF Protection Relay Faulty W103 N J04.XK MDF J04 11
IO Typical QRM

Station Type : Station Name : Station Address: IP Address: MAC Address:


SS Substation RD1910 RD1910
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling
I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status

Box )
Baytype ( Comment ) Remarks
YY01 RTU DO 01 LUCY DSM 2A - 01 030/000/108 RD1910 00 00 C.Station (22kV Common) DC DUMMY RELAY OFF - YY01 DO-17B
YY01 RTU DO 02 LUCY DSM 2A - 01 030/000/108 RD1910 00 00 -C.Station (22kV Common) DC DUMMY RELAY ON - YY01 DO-18B
YY01 RTU DO 03 LUCY DSM 1A DO-SW A 01 041/001/112 RD1910 SS - 22 A01-FE (22kV Feeder-LBS - 1) - DC LISO_C LOAD ISOLATOR OPEN W101 C J01.XK MDF J01 9
YY01 RTU DO 04 LUCY DSM 1A DO-SW A 01 041/001/112 RD1910 SS - 22 A01-FE (22kV Feeder LBS - 1) - DC LISC_C LOAD ISOLATOR CLOSED W101 D J01.XK MDF J01 7
YY01 RTU DO 05 LUCY DSM 1B DO-SW B 01 042/002/104 RD1910 SS - 22 A02-FE (22kV Transformer CB - 1) DC CBO_C CIRCUIT BREAKER OPEN W102 C J02.XK MDF J02 4
01 042/002/104 RD1910 SS - 22 -A02-FE (22kV Transformer CB - 1) DC CBC_C CIRCUIT BREAKER CLOSED
YY01 RTU DO 06 LUCY DSM 2A DO-SW A 01 041/003/112 RD1910 SS - 22 -A03-FE (22kV Feeder LBS - 2) - DC LISO_C LOAD ISOLATOR OPEN W101 K J03.XK MDF J03 9
YY01 RTU DO 07 LUCY DSM 2A DO-SW A 01 041/003/112 RD1910 SS - 22 A03-FE (22kV Feeder LBS - 2) - DC LISC_C LOAD ISOLATOR CLOSED W101 L J03.XK MDF J03 7
YY01 RTU DO 08 LUCY DSM 2B DO-SW B 01 042/004/104 RD1910 SS - 22 A04-FE (22kV Transformer CB - 2) DC CBO_C CIRCUIT BREAKER OPEN W103 C J04.XK MDF J04 4
01 042/002/104 RD1910 SS - 22 -A04-FE (22kV Transformer CB - 2) DC CBC_C CIRCUIT BREAKER CLOSED
-
YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W101 A J01.XK MDF J01 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J01.XK MDF J01 2
YY01 RTU C/R LUCY DSM 1A DI SW A 01 Common Return (C/R) W102 G J01.XK MDF J01 2&4
YY01 RTU C/R LUCY DSM 1A DI 1 01 Common Return (C/R) W102 J J01.XK MDF J01 6
YY01 RTU C/R LUCY DSM 1A DI 4 01 Common Return (C/R) W102 M J01.XK MDF J01
YY01 RTU C/R LUCY DSM 2 A DI SW A 01 Common Return (C/R) W102 P J03.XK MDF J03 2&4
YY01 RTU C/R LUCY DSM 2 A DI 3 01 Common Return (C/R) W102 P J03.XK MDF J03 6
YY01 RTU C/R LUCY DSM 2 A DI 4 01 Common Return (C/R) W102 P J03.XK MDF J03

YY01 RTU A1 01 LUCY DSM 1B AI-SW B 01 042/002/132 RD1910 SS - 22 A02-FE (22kV Transformer CB - 1) M A+ CURRENT + W102 T J02.XK MDF J02 5
YY01 RTU A1 02 LUCY DSM 1B AI-SW B 01 042/002/132 RD1910 SS - 22 -A02-FE (22kV Transformer CB - 1) M A- CURRENT - W102 V J02.XK MDF J02 6
YY01 RTU A1 03 LUCY DSM 2B AI-SW B 01 042/004/132 RD1910 SS - 22 -A04-FE (22kV Transformer CB - 2) M A+ CURRENT + W103 T J04.XK MDF J04 5
YY01 RTU A1 04 LUCY DSM 2B AI-SW B 01 042/004/132 RD1910 SS - 22 -A04-FE (22kV Transformer CB - 2) M A- CURRENT - W103 V J04.XK MDF J04 6
-
YY01 RTU PS L1 01 RTU AC SUPPLY W501 bk YH01 230V AC P
YY01 RTU PS N 01 RTU AC SUPPLY W501 bu YH01 230V AC N

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J02.XK MDF J02 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J02.XK MDF J02 2
YY01 RTU C/R LUCY DSM 1B DI SW B 01 Common Return (C/R) W103 G J02.XK MDF J02 2&4
YY01 RTU C/R LUCY DSM 1B DI 4 01 Common Return (C/R) W103 J xx MDF J02 8
YY01 RTU C/R LUCY DSM 1B DI 2 01 Common Return (C/R) W103 M J02.XK MDF J02 8 & 10
YY01 RTU C/R LUCY DSM 1B DI 1 01 Common Return (C/R) W103 P J02.XK MDF J02 12

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J04.XK MDF J04 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J04.XK MDF J04 2
YY01 RTU C/R LUCY DSM 2B DI SW B 01 Common Return (C/R) W103 G J04.XK MDF J04 2&4
YY01 RTU C/R LUCY DSM 2B DI 4 01 Common Return (C/R) W103 J J04.XK MDF J04 8
YY01 RTU C/R LUCY DSM 2B DI 2 01 Common Return (C/R) W103 M J04.XK MDF J04 8 & 10
YY01 RTU C/R LUCY DSM 2B DI 1 01 Common Return (C/R) W103 P J04.XK MDF J04 12
IO Typical QRM(L EFI)

Station Type : Station Name :


SS Substation RD1910
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling Box


I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status
Baytype ( Comment ) Remarks

)
YY01 RTU DI 01 LUCY DSM 2A - 01 030/000/005 RD1823 00 00 C.Station (22kV Common) - DP DUM OFF DUMMY RELAY OFF - 0 YY01 DI-15A
YY01 RTU DI 02 LUCY DSM 2A - 01 030/000/005 RD1823 00 00 C.Station (22kV Common) - DP DUM ON DUMMY RELAY ON - 0 YY01 DI-16A
YY01 RTU DI 03 LUCY MCM - 01 030/000/042 RD1823 00 00 C.Station (22kV Common) - SP MCBA MCB Alarm - 0 YY01
YY01 RTU DI 04 LUCY ADEL - 01 030/000/250 RD1823 00 00 C.Station (22kV Common) - SP 24VDCAL 24V DC Alarm - 0 YY01
YY01 RTU DI 05 LUCY MCM - 01 030/000/201 RD1823 00 00 C.Station (22kV Common) - SP STNL/R Station Control Local / Remote - 0 YY01
YY01 RTU DI 06 LUCY DSM 2A DI-3 01 030/000/041 RD1823 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W102 H XX MDF CS 7
01 030/000/041 RD1823 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W103 H XX MDF CS 8

YY01 RTU DI 07 LUCY DSM 1A DI-SWA Open 01 041/001/012 RD1823 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISO LOAD ISOLATOR OPEN W101 F J01.XK MDF J01 1
YY01 RTU DI 08 LUCY DSM 1A DI-SWA Close 01 041/001/012 RD1823 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISC LOAD ISOLATOR CLOSED W101 E J01.XK MDF J01 3
YY01 RTU DI 15 LUCY DSM 1A DI-1 01 041/003/033 RD1823 SS - 22 A03-FE (22kV Feeder LBS - 2) - SP EFI Earth Fault Indication W101 H J01.XK MDF J01 5

YY01 RTU DI 09 LUCY DSM 1B DI-SWA Open 01 042/002/001 RD1823 SS - 22 A02-FE (22kV Transformer CB - 1) DP CBO CIRCUIT BREAKER OPEN W102 F J02.XK MDF J02 3
YY01 RTU DI 10 LUCY DSM 1B DI-SWA Close 01 042/002/001 RD1823 SS - 22 -A02-FE (22kV Transformer CB - 1) DP CBC CIRCUIT BREAKER CLOSED W102 E J02.XK MDF J02 1
YY01 RTU DI 11 LUCY DSM 1B DI-2 01 042/002/205 RD1823 SS - 22 -A02-FE (22kV Transformer CB - 1) FL OCEFT Over Current/Earth Fault Trip W102 R J02.XK MDF J02 7&9
YY01 RTU DI 12 LUCY DSM 1B DI-1 01 042/002/247 RD1823 SS - 22 -A02-FE (22kV Transformer CB - 1) SP PRF Protection Relay Faulty W102 N J02.XK MDF J02 11
-

YY01 RTU DI 13 LUCY DSM 2A DI-SWA Open 01 041/003/012 RD1823 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISO LOAD ISOLATOR OPEN W101 P J03.XK MDF J03 1
YY01 RTU DI 14 LUCY DSM 2A DI-SWA Close 01 041/003/012 RD1823 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISC LOAD ISOLATOR CLOSED W101 M J03.XK MDF J03 3

YY01 RTU DI 16 LUCY DSM 2B DI-SWA Open 01 042/004/001 RD1823 SS - 22 A04-FE (22kV Transformer CB - 2) DP CBO CIRCUIT BREAKER OPEN W103 F J04.XK MDF J04 3
YY01 RTU DI 17 LUCY DSM 2B DI-SWA Close 01 042/004/001 RD1823 SS - 22 -A04-FE (22kV Transformer CB - 2) DP CBC CIRCUIT BREAKER CLOSED W103 E J04.XK MDF J04 1
YY01 RTU DI 18 LUCY DSM 2B DI-2 01 042/004/205 RD1823 SS - 22 -A04-FE (22kV Transformer CB - 2) FL OCEFT Over Current/Earth Fault Trip W103 R J04.XK MDF J04 7&9
YY01 RTU DI 19 LUCY DSM 2B DI-1 01 042/004/247 RD1823 SS - 22 -
A04-FE (22kV Transformer CB - 2) - SP PRF Protection Relay Faulty W103 N J04.XK MDF J04 11
TRM-RMU

Station Type : Station Name : Station Address: IP Address: MAC Address:


SS Substation RD1833 RD1833

RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling Box )


Object ADDR EC 870

I/ O Text / Description
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status
Baytype ( Comment ) Remarks
YY01 RTU DO 01 LUCY TB2 - 01 030/000/108 Station 2 00 00 C.Station (22kV Common) - DC DUMMY RELAY OFF - YY01 DO-17B
YY01 RTU DO 02 LUCY TB2 - 01 030/000/108 Station 2 00 00 C.Station (22kV Common) - DC DUMMY RELAY ON - YY01 DO-18B
YY01 RTU DO 03 LUCY TB1 DO-1B 01 055/001/112 Station 2 SS - 11 A01-FE (22kV Feeder LBS - 1) - DC LISO_C LOAD ISOLATOR OPEN W101 C J01-3 MDF J01 137
YY01 RTU DO 04 LUCY TB1 DO-2B 01 055/001/112 Station 2 SS - 11 A01-FE (22kV Feeder LBS - 1) - DC LISC_C LOAD ISOLATOR CLOSED W101 D J01-4 MDF J01 138
YY01 RTU DO 05 LUCY TB1 DO-3B 01 056/002/104 Station 2 SS - 11 A02-FE (22kV Transformer CB - 1) - DC CBO_C CIRCUIT BREAKER OPEN W102 C J02-42 MDF J02 199
01 056/002/104 Station 2 SS - 11 A02-FE (22kV Transformer CB - 1) - DC CBC_C CIRCUIT BREAKER CLOSED

YY01 RTU DO 06 LUCY TB1 DO-5B 01 055/004/112 Station 2 SS - 11 A04-FE (22kV Feeder LBS - 2) - DC LISO_C LOAD ISOLATOR OPEN W101 K J04-17 MDF J04 137
YY01 RTU DO 07 LUCY TB1 DO-6B 01 055/004/112 Station 2 SS - 11 A04-FE (22kV Feeder LBS - 2) - DC LISC_C LOAD ISOLATOR CLOSED W101 L J04-18 MDF J04 138

YY01 RTU +24V DC LUCY TB1 24VS 01 +24V DC W101 A J01-1 MDF J01
YY01 RTU OV DC LUCY TB1 OVS 01 0V DC W101 B J01-2 MDF J01
YY01 RTU C/R LUCY TB1 DI-1B 01 Common Return (C/R) W101 G J01-7 MDF J01 69
YY01 RTU C/R LUCY TB2 DI-19B 01 Common Return (C/R) W101 J J04-64 MDF J04 69
YY01 RTU C/R LUCY TB1 DI-5B 01 Common Return (C/R) W101 N J04-21 MDF J04 69
YY01 RTU A1 01 LUCY TB1 AI-13A 01 056/002/132 Station 2 SS - 11 A02-FE (22kV Transformer CB - 1) - M A+ CURRENT + W102 T J02-122 MDF J02 205
YY01 RTU A1 02 LUCY TB1 AI-13B 01 056/002/132 Station 2 SS - 11 A02-FE (22kV Transformer CB - 1) - M A- CURRENT - W102 V J02-124 MDF J02 206
YY01 RTU A1 03 LUCY TB1 AI-14A 01 056/003/132 Station 2 SS - 11 A03-FE (22kV Transformer CB - 2) - M A+ CURRENT + W103 T J03-122 MDF J03 205
YY01 RTU A1 04 LUCY TB1 AI-14B 01 056/003/132 Station 2 SS - 11 A03-FE (22kV Transformer CB - 2) - M A- CURRENT - W103 V J03-124 MDF J03 206

YY01 RTU PS L1 01 RTU AC SUPPLY W501 bk YH01 230V AC P


YY01 RTU PS N 01 RTU AC SUPPLY W501 bu YH01 230V AC N

YY01 RTU +24V DC LUCY TB1 24VS 01 +24V DC W102 A J02-41 MDF J02 121
YY01 RTU C/R LUCY TB1 DI-3B 01 Common Return (C/R) W102 G J02-33 MDF J02 69
YY01 RTU C/R LUCY TB2 DI-20B 01 Common Return (C/R) W102 J CS-43 MDF J02 69
YY01 RTU C/R LUCY TB1 DI-10B 01 Common Return (C/R) W102 M J02-95 MDF J02 69
YY01 RTU C/R LUCY TB1 DI-9B 01 Common Return (C/R) W102 P J02-98 MDF J02 69

YY01 RTU +24V DC LUCY TB1 24VS 01 +24V DC W103 A J03-41 MDF J03 121
YY01 RTU C/R LUCY TB1 DI-7B 01 Common Return (C/R) W103 G J03-33 MDF J03 69
YY01 RTU C/R LUCY TB2 DI-20B 01 Common Return (C/R) W103 J CS-43 MDF J03 69
YY01 RTU C/R LUCY TB1 DI-12B 01 Common Return (C/R) W103 M J03-95 MDF J03 69
YY01 RTU C/R LUCY TB1 DI-11B 01 Common Return (C/R) W103 P J03-98 MDF J03 69
Station Type : Station Name :
SS Substation

RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling Box )


Object ADDR EC 870

I/ O Text / Description
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status
Baytype ( Comment ) Remarks
YY01 RTU DI 01 LUCY TB2 - 01 030/000/005 Station 2 00 00 C.Station (22kV Common) - DP DUM OFF DUMMY RELAY OFF - 0 YY01 DI-15A
YY01 RTU DI 02 LUCY TB2 - 01 030/000/005 Station 2 00 00 C.Station (22kV Common) - DP DUM ON DUMMY RELAY ON - 0 YY01 DI-16A
YY01 RTU DI 03 LUCY TB1 - 01 030/000/042 Station 2 00 00 C.Station (22kV Common) - SP MCBA MCB Alarm - 0 YY01
YY01 RTU DI 04 LUCY TB1 - 01 030/000/250 Station 2 00 00 C.Station (22kV Common) - SP 24VDCAL 24V DC Alarm - 0 YY01
YY01 RTU DI 05 LUCY TB1 - 01 030/000/201 Station 2 00 00 C.Station (22kV Common) - SP STNL/R Station Control Local / Remote - 0 YY01
YY01 RTU DI 06 LUCY TB2 DI-20A 01 030/000/041 Station 2 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W102 H CS-44 MDF CS 58
01 030/000/041 Station 2 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W103 H CS-44 MDF CS 58

YY01 RTU DI 07 LUCY TB1 DI-1A 01 055/001/012 Station 2 SS - 11 A01-FE (22kV Feeder LBS - 1) - DP LISO LOAD ISOLATOR OPEN W101 F J01-9 MDF J01 23
YY01 RTU DI 08 LUCY TB1 DI-2A 01 055/001/012 Station 2 SS - 11 A01-FE (22kV Feeder LBS - 1) - DP LISC LOAD ISOLATOR CLOSED W101 E J01-8 MDF J01 24
YY01 RTU DI 15 LUCY TB2 DI-19A 01 055/001/031 Station 2 SS - 11 A01-FE (22kV Feeder LBS - 1) - SP EFI Earth Fault Indication W101 H J01-66 MDF J01 48

YY01 RTU DI 09 LUCY TB1 DI-3A 01 056/002/001 Station 2 SS - 11 A02-FE (22kV Transformer CB - 1) - DP CBO CIRCUIT BREAKER OPEN W102 F J02-35 MDF J02 1
YY01 RTU DI 10 LUCY TB1 DI-4A 01 056/002/001 Station 2 SS - 11 A02-FE (22kV Transformer CB - 1) - DP CBC CIRCUIT BREAKER CLOSED W102 E J02-34 MDF J02 2
YY01 RTU DI 11 LUCY TB1 DI-9A 01 056/002/205 Station 2 SS - 11 A02-FE (22kV Transformer CB - 1) - FL OCEFT Over Current/Earth Fault Trip W102 R J02-96 MDF J02 55
YY01 RTU DI 12 LUCY TB1 DI-10A 01 056/002/247 Station 2 SS - 11 A02-FE (22kV Transformer CB - 1) - SP PRF Protection Relay Faulty W102 N J02-93 MDF J02 333

YY01 RTU DI 13 LUCY TB1 DI-5A 01 055/004/012 (22kV Feeder LBS - 2) - SS - 11 A04-FE (22kV Feeder LBS - 2) - DP LISO LOAD ISOLATOR OPEN W101 P J04-23 MDF J04 23
YY01 RTU DI 14 LUCY TB1 DI-6A 01 055/004/012 (22kV Feeder LBS - 2) - SS - 11 A04-FE (22kV Feeder LBS - 2) - DP LISC LOAD ISOLATOR CLOSED W101 M J04-22 MDF J04 24
IO Typical QRM

Station Type : Station Name : Station Address: IP Address: MAC Address:


SS Substation RD1823 RD1823
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling
I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status

Box )
Baytype ( Comment ) Remarks
YY01 RTU DO 01 LUCY DSM 2A - 01 030/000/108 RD1823 00 00 C.Station (11kV Common) - DC DUMMY RELAY OFF - YY01 DO-17B
YY01 RTU DO 02 LUCY DSM 2A - 01 030/000/108 RD1823 00 00 C.Station (11kV Common) - DC DUMMY RELAY ON - YY01 DO-18B
YY01 RTU DO 03 LUCY DSM 1A DO-SW A 01 041/001/112 RD1823 SS - 22 A01-FE (22kV Feeder LBS - 1) - DC LISO_C LOAD ISOLATOR OPEN W101 C J01.XK MDF J01 9
YY01 RTU DO 04 LUCY DSM 1A DO-SW A 01 041/001/112 RD1823 SS - 22 A01-FE (22kV Feeder LBS - 1) - DC LISC_C LOAD ISOLATOR CLOSED W101 D J01.XK MDF J01 7
YY01 RTU DO 05 LUCY DSM 1B DO-SW B 01 042/002/104 RD1823 SS - 22 A02-FE (22kV Transformer CB - 1) DC CBO_C CIRCUIT BREAKER OPEN W102 C J02.XK MDF J02 4
01 042/002/104 RD1823 SS - 22 -A02-FE (22kV Transformer CB - 1) DC CBC_C CIRCUIT BREAKER CLOSED
YY01 RTU DO 06 LUCY DSM 2A DO-SW A 01 041/003/112 RD1823 SS - 22 -A03-FE (22kV Feeder LBS - 2) - DC LISO_C LOAD ISOLATOR OPEN W101 K J03.XK MDF J03 9
YY01 RTU DO 07 LUCY DSM 2A DO-SW A 01 041/003/112 RD1823 SS - 22 A03-FE (22kV Feeder LBS - 2) - DC LISC_C LOAD ISOLATOR CLOSED W101 L J03.XK MDF J03 7
YY01 RTU DO 08 LUCY DSM 2B DO-SW B 01 042/004/104 RD1823 SS - 22 A04-FE (22kV Transformer CB - 2) DC CBO_C CIRCUIT BREAKER OPEN W103 C J04.XK MDF J04 4
01 042/002/104 RD1823 SS - 22 -A04-FE (22kV Transformer CB - 2) DC CBC_C CIRCUIT BREAKER CLOSED
-
YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W101 A J01.XK MDF J01 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J01.XK MDF J01 2
YY01 RTU C/R LUCY DSM 1A DI SW A 01 Common Return (C/R) W102 G J01.XK MDF J01 2&4
YY01 RTU C/R LUCY DSM 1A DI 1 01 Common Return (C/R) W102 J J01.XK MDF J01 6
YY01 RTU C/R LUCY DSM 1A DI 4 01 Common Return (C/R) W102 M J01.XK MDF J01
YY01 RTU C/R LUCY DSM 2 A DI SW A 01 Common Return (C/R) W102 P J03.XK MDF J03 2&4
YY01 RTU C/R LUCY DSM 2 A DI 3 01 Common Return (C/R) W102 P J03.XK MDF J03 6
YY01 RTU C/R LUCY DSM 2 A DI 4 01 Common Return (C/R) W102 P J03.XK MDF J03

YY01 RTU A1 01 LUCY DSM 1B AI-SW B 01 042/002/132 RD1823 SS - 22 A02-FE (22kV Transformer CB - 1) M A+ CURRENT + W102 T J02.XK MDF J02 5
YY01 RTU A1 02 LUCY DSM 1B AI-SW B 01 042/002/132 RD1823 SS - 22 -A02-FE (22kV Transformer CB - 1) M A- CURRENT - W102 V J02.XK MDF J02 6
YY01 RTU A1 03 LUCY DSM 2B AI-SW B 01 042/004/132 RD1823 SS - 22 -A04-FE (22kV Transformer CB - 2) M A+ CURRENT + W103 T J04.XK MDF J04 5
YY01 RTU A1 04 LUCY DSM 2B AI-SW B 01 042/004/132 RD1823 SS - 22 -A04-FE (22kV Transformer CB - 2) M A- CURRENT - W103 V J04.XK MDF J04 6
-
YY01 RTU PS L1 01 RTU AC SUPPLY W501 bk YH01 230V AC P
YY01 RTU PS N 01 RTU AC SUPPLY W501 bu YH01 230V AC N

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J02.XK MDF J02 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J02.XK MDF J02 2
YY01 RTU C/R LUCY DSM 1B DI SW B 01 Common Return (C/R) W103 G J02.XK MDF J02 2&4
YY01 RTU C/R LUCY DSM 1B DI 4 01 Common Return (C/R) W103 J xx MDF J02 8
YY01 RTU C/R LUCY DSM 1B DI 2 01 Common Return (C/R) W103 M J02.XK MDF J02 8 & 10
YY01 RTU C/R LUCY DSM 1B DI 1 01 Common Return (C/R) W103 P J02.XK MDF J02 12

YY01 RTU +24V DC LUCY TB1 24VP 01 +24V DC W103 A J04.XK MDF J04 1
YY01 RTU OV DC LUCY TB1 OVP 01 0V DC W101 B J04.XK MDF J04 2
YY01 RTU C/R LUCY DSM 2B DI SW B 01 Common Return (C/R) W103 G J04.XK MDF J04 2&4
YY01 RTU C/R LUCY DSM 2B DI 4 01 Common Return (C/R) W103 J J04.XK MDF J04 8
YY01 RTU C/R LUCY DSM 2B DI 2 01 Common Return (C/R) W103 M J04.XK MDF J04 8 & 10
YY01 RTU C/R LUCY DSM 2B DI 1 01 Common Return (C/R) W103 P J04.XK MDF J04 12
IO Typical QRM(L EFI)

Station Type : Station Name :


SS Substation RD1823
RTU Location SIGNAL Crossconnection

Inter.Loop ( Marshalling Box


I/ O Text / Description
Object ADDR EC 870
Terminal Connector

83 - Slot / Bay Type


Module Connector

82 - Voltage Level

External Cable
Module ADDR
In/ Output No.

Terminal / No
Module Type

Cable Core

Destination
81 - station
Frame/Slot

Short Text

Character
I / O Type
Cubicle

Status
Baytype ( Comment ) Remarks

)
YY01 RTU DI 01 LUCY DSM 2A - 01 030/000/005 RD1823 00 00 C.Station (22kV Common) - DP DUM OFF DUMMY RELAY OFF - 0 YY01 DI-15A
YY01 RTU DI 02 LUCY DSM 2A - 01 030/000/005 RD1823 00 00 C.Station (22kV Common) - DP DUM ON DUMMY RELAY ON - 0 YY01 DI-16A
YY01 RTU DI 03 LUCY MCM - 01 030/000/042 RD1823 00 00 C.Station (22kV Common) - SP MCBA MCB Alarm - 0 YY01
YY01 RTU DI 04 LUCY ADEL - 01 030/000/250 RD1823 00 00 C.Station (22kV Common) - SP 24VDCAL 24V DC Alarm - 0 YY01
YY01 RTU DI 05 LUCY MCM - 01 030/000/201 RD1823 00 00 C.Station (22kV Common) - SP STNL/R Station Control Local / Remote - 0 YY01
YY01 RTU DI 06 LUCY DSM 2A DI-3 01 030/000/041 RD1823 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W102 H XX MDF CS 7
01 030/000/041 RD1823 00 00 C.Station (22kV Common) - SP SF6AL SF6 Alarm W103 H XX MDF CS 8

YY01 RTU DI 07 LUCY DSM 1A DI-SWA Open 01 041/001/012 RD1823 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISO LOAD ISOLATOR OPEN W101 F J01.XK MDF J01 1
YY01 RTU DI 08 LUCY DSM 1A DI-SWA Close 01 041/001/012 RD1823 SS - 22 A01-FE (22kV Feeder LBS - 1) - DP LISC LOAD ISOLATOR CLOSED W101 E J01.XK MDF J01 3
YY01 RTU DI 15 LUCY DSM 1A DI-1 01 041/003/033 RD1823 SS - 22 A03-FE (22kV Feeder LBS - 2) - SP EFI Earth Fault Indication W101 H J01.XK MDF J01 5

YY01 RTU DI 09 LUCY DSM 1B DI-SWA Open 01 042/002/001 RD1823 SS - 22 A02-FE (22kV Transformer CB - 1) DP CBO CIRCUIT BREAKER OPEN W102 F J02.XK MDF J02 3
YY01 RTU DI 10 LUCY DSM 1B DI-SWA Close 01 042/002/001 RD1823 SS - 22 -A02-FE (22kV Transformer CB - 1) DP CBC CIRCUIT BREAKER CLOSED W102 E J02.XK MDF J02 1
YY01 RTU DI 11 LUCY DSM 1B DI-2 01 042/002/205 RD1823 SS - 22 -A02-FE (22kV Transformer CB - 1) FL OCEFT Over Current/Earth Fault Trip W102 R J02.XK MDF J02 7&9
YY01 RTU DI 12 LUCY DSM 1B DI-1 01 042/002/247 RD1823 SS - 22 -A02-FE (22kV Transformer CB - 1) SP PRF Protection Relay Faulty W102 N J02.XK MDF J02 11
-

YY01 RTU DI 13 LUCY DSM 2A DI-SWA Open 01 041/003/012 RD1823 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISO LOAD ISOLATOR OPEN W101 P J03.XK MDF J03 1
YY01 RTU DI 14 LUCY DSM 2A DI-SWA Close 01 041/003/012 RD1823 SS - 22 A03-FE (22kV Feeder LBS - 2) - DP LISC LOAD ISOLATOR CLOSED W101 M J03.XK MDF J03 3

YY01 RTU DI 16 LUCY DSM 2B DI-SWA Open 01 042/004/001 RD1823 SS - 22 A04-FE (22kV Transformer CB - 2) DP CBO CIRCUIT BREAKER OPEN W103 F J04.XK MDF J04 3
YY01 RTU DI 17 LUCY DSM 2B DI-SWA Close 01 042/004/001 RD1823 SS - 22 -A04-FE (22kV Transformer CB - 2) DP CBC CIRCUIT BREAKER CLOSED W103 E J04.XK MDF J04 1
YY01 RTU DI 18 LUCY DSM 2B DI-2 01 042/004/205 RD1823 SS - 22 -A04-FE (22kV Transformer CB - 2) FL OCEFT Over Current/Earth Fault Trip W103 R J04.XK MDF J04 7&9
YY01 RTU DI 19 LUCY DSM 2B DI-1 01 042/004/247 RD1823 SS - 22 -
A04-FE (22kV Transformer CB - 2) - SP PRF Protection Relay Faulty W103 N J04.XK MDF J04 11
Contractor : National Projects & Contruction LLC 1 SLD

Over All SLD


Employer : ALDAR Projects 2

Country of Origin
Consultant : PARSONS 3

Signal List
Client : ADDC 4

Tele-Information Plan
SS : RMU Substations 5

6 Cable Overview List


Internal Project No:

Adaptation Design
Project Name : Madinat Al Riyadh City Ph-6A & 6B 7

8 I/O Connection Diagram

MATERIAL SUBMITTAL: DMS-RTU for RMU.Rev.01


9 RTU Functional Specification

10 RTU Detailed Design

11 RTU Method Statement

12 RTU FAT Procedure

13 RTU SAT Procedure

14 POINT TO POINT TEST PROCEDURE

15 Warranty Certificate
Gemini 3
Installation, Operation and
Maintenance Manual

LIOM07-002 December 2015


Copyright
© 2015 Lucy Electric (EMS) Limited. All rights
reserved.
This document contains confidential information
that shall not be transmitted to any third party
without written consent of Lucy Electric (EMS)
Limited. The same applies to file copying (including
but not limited to electronic copies), wholly or
partially.
It is prohibited to change any and all versions of this
document in any manner whatsoever, including but
not limited to dividing it into parts. In case of a
conflict between an electronic version (e.g. PDF file)
and the original paper version provided by Lucy
Electric (EMS) Limited, the latter will prevail.
Lucy Electric (EMS) Limited and/or its associated
companies disclaim liability for any direct, indirect,
consequential or incidental damages that may result
from the use of the information or data, or from the
inability to use the information or data contained
in this document.
Gemini 3 is a registered trademark of Lucy Electric
(EMS) Limited. All other product and company names
mentioned are trademarks or registered trademarks
of their respective owners.

ii
Safety information

HAZARDOUS VOLTAGE

DANGER
DEATH OR SEVERE PERSONAL INJURY WILL RESULT IF THE FOLLOWING PROPER PRECAUTIONS ARE
NOT TAKEN
■ Isolate or disconnect the equipment from the mains supply before opening the unit for any reason.
There are live parts inside.
■ This unit contains internal protection fuses. Follow guidelines in troubleshooting section before
replacement of these devices. Only suitably trained personnel are permitted to remove covers on
the equipment.
■ The Gemini 3 must always be earthed when connected to a mains supply. For continued protection
against risk of fire or electric shock, replace fuses with the same type and rating.
■ The Gemini 3 power supply unit contains large capacitors. Wait approximately two minutes for
them to fully discharge before changing modules or power supplies.
■ The Gemini 3 contains high capacity batteries which can present a risk of electrical shock and high
circuit current. Do not allow them to become shorted together.
■ If the RTU is connected to one, two or three CTs, and the connector in the RTU is not plugged into
the control unit, there could be dangerous voltages on the connector block. The CT connections
must always be shorted in the switchgear marshalling box before disconnecting the connector
from the control unit.
■ In order for the RTU to function correctly and in compliance with the CE & ENA specifications
detailed in Appendix C – EMC and environmental tests, the RTU must be installed and maintained
to the instructions detailed in Maintenance (page 27) and electricity network industry best practice.
■ The Gemini 3 may contain a linear actuator capable of supplying a very large force. Before working
inside the enclosure or any component coupled to the actuator, it is recommended that the RTU
power supplies should be turned off and verified as electrically isolated.
■ The Gemini 3 enclosure with batteries weighs over 40kg. Standard health and safety procedures
should be followed when lifting or moving it.

iii
Contents
Chapter 1: GEMINI 3 RTU OVERVIEW.......................................................................................7
UPGRADEABILITY.............................................................................................................................................................8
BACKPLANE......................................................................................................................................................................8
FIRMWARE AND CONFIGURATION UPDATES....................................................................................................................8

Chapter 2: GEMINI 3 COMPONENTS.........................................................................................9


DOOR AND BATTERY SWITCHES.....................................................................................................................................10
BATTERIES......................................................................................................................................................................10
SPARE FUSES..................................................................................................................................................................11
GEMINI 3 RTU MODULES................................................................................................................................................11
COMMUNICATIONS CHANNEL........................................................................................................................................12

Chapter 3: INSTALLATION.......................................................................................................16
UNIT INSTALLATION GUIDELINES....................................................................................................................................17
UNIT INSTALLATION CHECKLIST......................................................................................................................................17
MODULE INSTALLATION GUIDELINES..............................................................................................................................18
POSITIONING THE RTU....................................................................................................................................................18
MOUNTING THE RTU......................................................................................................................................................19
LOW-VOLTAGE SUPPLY AND ELECTRICAL INSTALLATION...............................................................................................20
EARTHING THE RTU .......................................................................................................................................................23
UMBILICAL CABLES TO SWITCHGEAR – INSTALLATION...................................................................................................24
ENVIRONMENTAL CONDITIONS......................................................................................................................................26
SOFTWARE CONFIGURATION..........................................................................................................................................27

Chapter 4: COMMISSIONING..................................................................................................29
HARDWARE....................................................................................................................................................................29
SOFTWARE.....................................................................................................................................................................30

Chapter 5: MAINTENANCE......................................................................................................32
MAINTENANCE GUIDELINES...........................................................................................................................................32
MAINTAINING AND UPGRADING THE RTU......................................................................................................................32

Appendix A: TECHNICAL SPECIFICATION................................................................................34

Appendix B: MODULE LED STATES..........................................................................................36


MCM (MASTER CONTROL MODULE) LEDS.......................................................................................................................36
PSM (POWER SUPPLY MODULE) LEDS.............................................................................................................................36
DSM (DUAL SWITCH MODULE) LEDS...............................................................................................................................37
IOM (INPUT OUTPUT MODULE) LEDS..............................................................................................................................39
FPM (FAULT PASSAGE MODULE) LEDS............................................................................................................................39

Appendix C: MODULE CONNECTOR DETAILS..........................................................................40


MCM (MASTER CONTROL MODULE) CONNECTOR DETAILS.............................................................................................41
PSM (POWER SUPPLY MODULE) CONNECTOR DETAILS...................................................................................................44

iv
DSM (DUAL SWITCH MODULE) CONNECTOR DETAILS.....................................................................................................46
IOM (INPUT OUTPUT MODULE) CONNECTOR DETAILS....................................................................................................49
FPM (FAULT PASSAGE MODULE) CONNECTOR DETAILS..................................................................................................52

Appendix D: GEMINI 3 CUBICLE SPECIFICATION....................................................................54


CUBICLE CONNECTIONS.................................................................................................................................................54
DIMENSIONS..................................................................................................................................................................60

Appendix E: EMC AND ENVIRONMENTAL TESTS....................................................................61


OVERALL........................................................................................................................................................................61
EMC TESTS.....................................................................................................................................................................61
ELECTRICAL TESTS..........................................................................................................................................................62
ENVIRONMENTAL TESTS.................................................................................................................................................62
MECHANICAL TESTS.......................................................................................................................................................63

GLOSSARY...............................................................................................................................64

v
Figures
Figure 1: Example SCADA network.........................................................................................................................7
Figure 2: Internal layout of a typical 5-slot cubicle RTU with 5 modules fitted.....................................................9
Figure 3: Example GPRS modem installation........................................................................................................13
Figure 4: Example radio installation – Wood & Douglas ER450...........................................................................14
Figure 5: Typical fibre media converter................................................................................................................14
Figure 6: Typical automated secondary RMU substation (Lucy VRN2a & Gemini RTU)........................................16
Figure 7: Typical automated overhead line switch (Lucy GX-RC & Gemini RTU)..................................................17
Figure 8: Free-standing RTU (5-slot cubicle).........................................................................................................19
Figure 9: Wall-mounted RTU (5-slot cubicle)........................................................................................................20
Figure 10: 5-slot cubicle RTU mounted on Lucy VRN2a switchgear.....................................................................20
Figure 11: Manual voltage selector......................................................................................................................21
Figure 12: Example electrical installation.............................................................................................................21
Figure 13: Schematic representation of isolation transformer.............................................................................22
Figure 14: Substation earthing guidelines............................................................................................................22
Figure 15: Typical underground earthing configuration.......................................................................................24
Figure 16: Umbilical cable connection from the RTU to a Lucy VRN2a marshalling box......................................25
Figure 17: Typical fixed gland plate......................................................................................................................25
Figure 18: Typical split gland plate.......................................................................................................................26
Figure 19: Gemini 3 with a sunshade fitted..........................................................................................................27
Figure 20: Gemini 3 without a sunshade fitted....................................................................................................27
Figure 21: Lucy RMU simulator connected to a Gemini 3.....................................................................................30
Figure 22: MCM connector details........................................................................................................................41
Figure 23: PSM connector details.........................................................................................................................44
Figure 24: DSM connector details.........................................................................................................................46
Figure 25: IOM connector details..........................................................................................................................49
Figure 26: FPM connector details.........................................................................................................................52
Figure 27: 5-slot cubicle RTU dimensional/mounting details...............................................................................60

vi
December 2015 LIOM07-002

Chapter

1
Gemini 3 RTU overview
The Gemini 3 is a general-purpose Remote Terminal Unit (RTU) designed to remotely monitor and
control medium/high voltage switchgear. It will normally be used in conjunction with a SCADA system
to control a number of switchgear units covering a wide area, as shown in the figure below:

Figure 1: Example SCADA network

The Gemini 3 RTU has a modular design allowing a wide range of systems to be configured, ranging
from a very simple monitoring device through to a sophisticated multi-switch control unit with high
input count of analogue and digital signals as well as secure switchgear control outputs. A wide range
of modules is available which can monitor and safely control the switchgear in the very difficult
electrical and environmental conditions experienced by the switchgear.

Gemini 3 7
LIOM07-002 December 2015

Upgradeability
The Gemini 3 is a highly versatile RTU which can be upgraded by adding extra modules. For example,
a two-module device (initially fitted in a five-module cubicle) can be upgraded from a purely monitoring
RTU to a fully-monitored one, two, three or four-switch control RTU.
This is a major advantage in areas where monitoring is required at all sites but the location of the
switching sites is unknown, uncertain or variable. This represents a considerable cost saving in the
planning and implementation of networks while preserving the ultimate in flexibility.
Further flexibility is possible with OEM variants for fitting into customers’ own cabinets.

Backplane
The backplane supports 5 modules, allowing a range of RTU configurations to be assembled. The
backplane contains the following signals:
■ Bus architecture
■ Logic supply
■ Switch supply
■ CAN bus
■ Local/remote option

Firmware and configuration updates


With a suitable TCP/IP based comms device fitted, firmware and configuration updates can be installed
remotely without the need to visit the RTU. This provides significant flexibility in updating the RTU
when the network configuration changes and prevents unnecessary journeys to remote and inaccessible
RTU sites.

8 Gemini 3
December 2015 LIOM07-002

Chapter

2
Gemini 3 components

Figure 2: Internal layout of a typical 5-slot cubicle RTU with 5 modules fitted

Switches The door and battery switches


For more information, see Door and battery switches (page 10).

Battery pack The rechargeable sealed lead-acid or nickel–metal hydride battery pack
For more information, see Batteries (page 10).

Modules The backplane housing the Master Control Module (MCM) and its slave modules
For more information, see Gemini 3 RTU modules (page 11).

Cubicle The outer enclosure of the RTU


For more information, see Gemini 3 cubicle specification (page 54).

Modem A modem or other device communicates with the SCADA system via a communications channel
For more information, see Communications channel (page 12).

Power supply The manually-switchable AC power supply unit


unit
HMI An optional module for controlling and monitoring the RTU locally
For more information, see HMI (Human Machine Interface) overview (page 12).

Spare fuses A set of spare fuses is attached to the inner door of the RTU
For more information, see Spare fuses (page 11).

Gemini 3 9
LIOM07-002 December 2015

Door and battery switches

Door switch Puts the RTU in power-saving mode when the door is closed.
In power-saving mode, the LEDs on the modules and the HMI are powered off.

Battery switch Isolates the battery so that you can change the battery or test its voltage off-load.
Isolating the battery also assists when powering down the RTU, as without the switch you have to pull
the battery fuse.
Note This item is an optional extra.

Batteries
The RTU can be supplied with either sealed lead-acid (SLA) or nickel–metal hydride (NiMH high
temperature) batteries. These are for running the ring switch or CB actuators and for providing backup
power for the RTU.
The batteries are wired with a high-current 24 V connector and a temperature sensor connector. Both
connectors plug in to the PSM module. This wiring loom contains circuitry that also identifies the
battery type so that the RTU applies the appropriate charging routines.

Optimal battery charging


The temperature sensor is used to make sure that the batteries are optimally charged and cannot be
overheated. For sealed lead-acid (SLA) batteries, this sensor is mounted close to the batteries, and
for nickel–metal hydride (NiMH high temperature) batteries, it is embedded within the battery
pack.

Battery deep-discharge protection


The RTU prevents the batteries from becoming fully discharged if the terminal voltage reaches a
certain (programmable) minimum level. Fully discharging batteries (particularly sealed lead acid ones)
can permanently damage them and should be avoided.

10 Gemini 3
December 2015 LIOM07-002

Battery test
The RTU can perform a periodic battery test by disconnecting the charger from the battery and
applying a load to the batteries. The RTU then measures the terminal voltage and current of the
battery throughout the test to determine its condition.
Note The battery test can also be started from the SCADA control centre.

Spare fuses
The fuses on the Gemini 3 RTU are user replaceable. The spare fuses are attached to the bottom of
the inner door of the RTU.

Name Description Location

F1 AUXILIARY 1-amp auxiliary output fuse PSU side panel

F2 INPUT 3.15-amp mains fuse PSU side panel

F3 BATTERY 15-amp battery fuse Door switch housing

How do I know if a fuse is blown?


■ F1 AUXILIARY = There is no visible indication that this fuse is blown. If the auxiliary socket is not
providing power, then this may be the cause.
■ F2 INPUT = The AC SUPPLY LED on the PSM (Power Supply Module) will indicate a problem by
glowing red.
■ F3 BATTERY = The BATT HEALTH LED on the PSM (Power Supply Module) will indicate a problem
by glowing red.

Gemini 3 RTU modules


The Gemini 3 Remote Terminal Unit is a very flexible device due to its modular design. It is supplied
as standard in a 5-slot cubicle. (Other cubicle versions are available on request.)
This allows various RTU configurations to be built up from a range of modules. These have been
specially designed for the safe control and monitoring of electrical switchgear in the primary and
secondary distribution sectors.
At its simplest, a basic monitoring-only RTU may consist of just a Master Control Module (MCM) and
an Input Output Module (IOM) fitted to a back-plate assembly for direct mounting in an existing
enclosure.
Typically, to allow expansion to a controlling RTU a Power Supply Module (PSM) would also be fitted.
(The PSM module is required in order to use the Dual Switch Module (DSM).) To simplify installation,
the whole device is supplied in a suitable cubicle.
Additional modules can then be fitted according to evolving control and monitoring requirements.
These additional modules give the following features:
■ Digital input points (single and double points)
■ Analogue input points
■ Control outputs
■ Fault detection functions
■ Power meter functions (future module)

Gemini 3 11
LIOM07-002 December 2015

General module features


All modules have the following general features which underpin the quality of construction and
repeatability when it comes to measurement of parameters.
■ Built-in diagnostics
■ Status indicators
■ Continuous-status monitoring
■ Each module registered by serial number/type
■ Defined responsibilities
■ Factory-calibrated measurements
■ Module replacement does not affect calibration
■ Safety checks and interlocks

MCM (Master Control Module) overview


The MCM contains the main processor for the RTU. It supervises all modules and handles the protocol
communications.
Note All configurations of the RTU must have an MCM fitted.

PSM (Power Supply Module) overview


The PSM works with the DSM to provide secure switching operations. It also generates regulated
power for the other modules and external communication equipment and provides smart battery
charging to maintain a secure supply.

DSM (Dual Switch Module) overview


The DSM provides the inputs and outputs to perform a secure interlocked control via a selected
protocol and has a mixture of digital inputs, analogue inputs, and relay outputs. It can be used to
trigger actuator (servomotor) control inputs. One DSM can control up to two ring switch actuators.

IOM (Input Output Module) overview


The IOM is a general-purpose module that covers digital and analogue inputs and relay outputs. It
can be used as additional I/O to a multi-switch control RTU or in a monitoring-only RTU.

FPM (Fault Passage Module) overview


The FPM is a dual fault passage indicator module that detects and issues alarms for overcurrent and
earth faults. In addition, two inputs for 4-20mA sensors are available.

HMI (Human Machine Interface) overview


The HMI can be used instead of a computer to provide local control and monitoring of the Gemini 3.

Communications channel
The Gemini 3 RTU is designed to communicate with a central SCADA/DMS System via a communications
channel. This communications channel can take a variety of forms including the following:
■ High or low-power data radio system

12 Gemini 3
December 2015 LIOM07-002

■ GPRS, 3G or 4G Ethernet modem


■ Fibre optic media converter
■ Power line carrier communication device
■ Standard PSTN telephone line
■ Satellite modem
■ RS-232 serial devices
Various mounting options are available to cater for different communications devices.

GPRS modem
A GPRS modem uses the mobile phone network to transmit TCP/IP data across the network and is
generally fitted with either a serial RS-232 port or an RJ45 Ethernet for communication with the RTU.
The figure below shows an example GPRS modem installation with the comms supply wiring (top
side), antenna connection, and Ethernet connection to the MCM. The Gemini 3 provides a
battery-backed 12 V supply to power the unit.
The modem shown is an INSYS 5.1 Ethernet modem. See Ports page in the Gemini 3 Configuration
Tool Help for information about changing the communication parameters for this type of modem.
These modems generally have a wide DC input voltage range of 9 to 36 V.

Figure 3: Example GPRS modem installation

Radio
Digital data radios operating at UHF or VHF frequencies can be used to transmit serial protocol data
to the SCADA system from the RTU. The serial interface used is generally RS-232. This kind of radio
typically uses a battery-backed 12 V DC supply which is supplied by the Gemini 3. The protocol data
to/from the MCM is fed to the serial input of the radio.

Gemini 3 13
LIOM07-002 December 2015

Figure 4: Example radio installation – Wood & Douglas ER450

Ethernet
It is becoming more common today for substations to be connected to the Internet using a Virtual
Private Network (VPN) via a local TCP/IP network. This means that the RTU will be connected to either
to a router or WiFi (or similar) terminal external to the RTU.
In this case, the MCM will be wired directly from its isolated Ethernet port to the router/WIFI device
using a Cat 5 Ethernet cable and the RTU can be given an IP address by the LAN (Local Area Network)
manager.

Fibre
Protocol transmission through fibre-optic cables uses TCP/IP, which requires a media converter to
convert the signals on the MCM Ethernet port to optical-fibre format.
The figure below shows a typical media converter (Westermo MCW-211) using low-loss fibre which
exits the RTU at the gland plate then on to the local fibre patch panel in the substation. The Gemini
3 provides a battery-backed 12 V supply to power the unit.

Figure 5: Typical fibre media converter

14 Gemini 3
December 2015 LIOM07-002

RS-232 serial communications devices


Most common SCADA protocols allow for serial data transmission through RS-232 ports. The following
communications devices generally use serial communications:
■ Low-power radio
■ Standard PSTN telephone line
■ Satellite modem
■ Power Line Carrier communications
Standard serial ports use a standard D-sub 9-pin connector. The communications parameters are set
using the RTU Configuration Tool. See Ports page in the Gemini 3 Configuration Tool Help for
information about changing the communications parameters for this type of modem.
Typical parameters to be set are baud rate, parity, flow control, and stop bits.

Gemini 3 15
LIOM07-002 December 2015

Chapter

3
Installation
The Gemini 3 RTU can be installed at both ground-mounted and overhead line-mounted switchgear
sites.
For ground-mounted switchgear, the RTU is mounted within a secondary substation environment:

Figure 6: Typical automated secondary RMU substation (Lucy VRN2a & Gemini RTU)

16 Gemini 3
December 2015 LIOM07-002

For overhead line-mounted switchgear, the RTU will normally be pole-mounted:

Figure 7: Typical automated overhead line switch (Lucy GX-RC & Gemini RTU)

Unit installation guidelines


It is essential to plan the installation of the Gemini 3 RTU carefully in order to achieve good, safe,
and consistent performance.

Unit installation checklist


The following installation checklist will help you to make sure that all necessary actions have been
considered:
■ Mounting and positioning arrangements – wall, floor, switchgear or pole
■ LV supply – 85-130 or 190-265 VAC (100/200 W min, RTU configuration dependant)
■ Batteries
■ Earthing – electrical safety
■ Earthing – protective to safeguard RTU

Gemini 3 17
LIOM07-002 December 2015

■ Comms installation – antenna location, coverage check, cable routing, etc. as appropriate
■ Length of umbilical cables required (5 m or 10 m standard, for others consult Lucy)
■ Environmental conditions – high & low temperature extremes (a sunshade may be required; consider
effects of condensation, dust)

Module installation guidelines


Make sure to follow these guidelines when you are installing modules:
■ Modules may be fitted in any position in the backplane, and in any order.
■ Accidentally fitting a module upside-down is possible, although it will not work since it will not
be physically connected.
■ If you are installing a module into the backplane, take care to fit it evenly on to the location pegs.
■ Tighten the module retention screws evenly. This will ensure that the module connector at the
back mates correctly with the backplane connector.
■ Don’t over-tighten the module retention screws – hand tight is sufficient.
■ Modules should not be fitted and removed whilst the RTU is running.
■ The RTU cannot be fitted with more than one module of the types that do not have a rotary ID
selector, such as the PSM and the MCM. Fitting two of them is not permitted and will prevent the
RTU from functioning.
■ Modules that have the rotary ID selector must be set to a different ID for each module of a particular
type. For example, in order to fit 2 DSMs, one must have one ID (for example, 1) and the other
must have a different ID (for example, 2). They will subsequently be referred to as DSM1 and DSM2
respectively.
■ Modules can be assigned any valid ID, but it will simplify fault finding to number modules from
1, running from left to right.
■ Valid module IDs are 1–7. ID 0 is reserved for factory test, and 8 and 9 are not available. As a result,
seven is the maximum number of modules of the same type that can be fitted into the same
backplane.
■ If two modules are fitted with the same ID, removing one may not re-establish the normal RTU
functionality – either remove both of them and re-fit one, or remove one and power up the RTU.
■ In order to avoid the previously described problem, it is advisable to set the module ID before
fitting it into the backplane.
■ Adding or replacing a module does not make it work immediately. You need to register the new
module using the Configuration Tool. An unregistered module is not enabled by the MCM and
cannot be operated. However, some basic operations (such as the battery-charging process in the
PSM) may start straight away.
■ Any operation such as a switchgear operation requires the necessary modules to be properly
configured and registered.

Positioning the RTU


The Gemini 3 RTU should be positioned as close to the switchgear as possible. There are some
advantages to this approach:
■ The RTU can be solidly earthed to the switchgear to minimize damaging voltage spikes caused by
faults or lightning strikes.

18 Gemini 3
December 2015 LIOM07-002

■ It keeps the umbilical cable length to a minimum (thereby reducing undesirable drops in voltage
supplied to the actuators). This is important in order to get maximum runtime from the batteries.

Mounting the RTU


The Gemini 3 RTU has the following mounting options:
■ A dual-purpose stand for either floor or wall mounting
Note This item is an optional extra.

■ A bracket for switchgear mounting

Figure 8: Free-standing RTU (5-slot cubicle)

Gemini 3 19
LIOM07-002 December 2015

Figure 9: Wall-mounted RTU (5-slot cubicle)

Figure 10: 5-slot cubicle RTU mounted on Lucy VRN2a switchgear

Low-voltage supply and electrical installation


The Gemini 3 is normally powered by an AC voltage supply (115/230 VAC nominal, 60/50 Hz). The
input range is switch selectable using the manual voltage selector on the Power Supply Unit (PSU).
Note The manual voltage selector may be marked for 120/240 V, but this is subject to change.

20 Gemini 3
December 2015 LIOM07-002

Figure 11: Manual voltage selector

For more information about the power supply, see Power Supply I/P (from LV) in Technical specification
(page 34).
The figure below shows an example electrical installation with AC input through the gland plate to
the terminal block and on to the Power Supply Unit (PSU).

Figure 12: Example electrical installation

A 5 kV isolation transformer is fitted as standard.

Gemini 3 21
LIOM07-002 December 2015

Figure 13: Schematic representation of isolation transformer

The output of the isolation transformer is 115 VAC, which feeds a switched-mode Power Supply Unit
(PSU) with an input range of 90 to 264 VAC. This gives the RTU greater protection against over-voltage
inputs, allowing well above the nominal values of LV (Low Voltage) to be accommodated without
damage to the RTU. This can help particularly in rural over-head networks where such voltages can
be a problem.
The PSU provides a regulated 36 VDC rail, which the RTU uses for all internal supplies (battery charger,
logic, comms, etc.) The exception is the actuator supply, which is supplied from batteries.
The LV supply needs to be located as close as possible to the RTU and switchgear in order to avoid
noise and damaging voltage spikes caused by faults and lightning strikes. It also needs to be properly
earthed to achieve adequate protection against damaging voltages.
It is important that the earthing does not compromise this isolation so, if the LV supply is separate
from the switchgear/transformer, the LV earth must not be connected to the RTU earth. Isolating
SWA (Steel Wire Armoured) glands are available as a cost-option extra.
For information about RTU earthing, see Earthing the RTU (page 23).

Figure 14: Substation earthing guidelines

22 Gemini 3
December 2015 LIOM07-002

Important guidance notes


In all cases, you should refer to the reference documentation for your local earthing standards for
guidance on earthing techniques and values.
■ Ensure that the RMU is connected to the substation earth ring with at least 70 mm² copper wire.
■ Ensure that the RTU is connected to the same earth as the RMU with 70 mm² copper wire.
■ Ensure that the substation earth complies with your local standards.
Note This must be less than 10 ohms.

■ It is very important that the LV supply earth is NOT connected to the RTU or any local earth point
as this will by-pass the insulation of the transformer. The LV supply earth wire should therefore
be disconnected and left secured but insulated from any part of the isolation transformer or local
earth points.

Earthing the RTU


There are two main reasons to make sure that the RTU is correctly earthed:
■ For electrical safety
■ To prevent damage to I/O ports and the RTU power supplies
The RTU can also be used in two main arrangements:
■ Primary or secondary-substation location
■ Overhead line installation
In general, the RTU should be solidly earthed to the switchgear using min. 70 mm² copper cable and
in turn the switchgear should be connected to the main substation earth ring using min. 70 mm²
copper cable. The LV (Low Voltage) supply transformer should also be earthed to the main substation
earth ring to prevent excessive input voltage caused by lightning strikes or electrical faults.
Note If communications utilising antennas with grounded coaxial cable are to be used, extra
precautions may be necessary. Consult your comms installation specialist or Lucy Electric (EMS) Limited
for further information.

Gemini 3 23
LIOM07-002 December 2015

The figure below shows a typical earthing configuration for an underground arrangement – Gemini
3 with an RMU (Ring Main Unit) and transformer showing 70 mm² cable attached to earthing points.

Figure 15: Typical underground earthing configuration

Important This is only a representative configuration. Refer to your company and local standards
or consult Lucy Electric (EMS) Limited for a detailed arrangement.
For overhead-line switchgear, the LV supply is generally sourced from a pole-mounted VT. In this case,
the RTU, VT (Voltage Transformer), and switchgear should be earthed using an earth mat.

Umbilical cables to switchgear – installation


In order to monitor the status of the switchgear and control it, there needs to be an electrical
connection to the RTU. This is done using an umbilical cable which at one end has either wires or
plugs into the switchgear marshalling box and at the other end plugs into the appropriate Switch
Control Module (SCM) or Dual Switch Module (DSM) on the RTU.

24 Gemini 3
December 2015 LIOM07-002

The figure below shows the connection of the umbilical cable from the switchgear to the RTU.

Figure 16: Umbilical cable connection from the RTU to a Lucy VRN2a marshalling box

Gland plate sockets are available as an option. The figure below shows a typical fixed gland plate.

Figure 17: Typical fixed gland plate

Gemini 3 25
LIOM07-002 December 2015

A split gland plate removes the need for multiple plugs and sockets in the umbilical cable. The figure
below shows a typical split gland plate.

Figure 18: Typical split gland plate

Note The split gland plate is subject to change.

Environmental conditions
The Gemini 3 RTU has been designed to work in either indoor or outdoor environments. Its enclosure
is rated to IP55 and has a temperature range of –25° C to 55° C ambient.
The IP55 rating means that the RTU will not allow any significant levels of dust to enter the RTU in
dry dusty conditions. In addition, significant amounts of water will not enter the RTU under heavy
rain conditions.
In very hot, sunny desert conditions a sunshade is also available to mask the RTU from the direct rays
of the sun.

26 Gemini 3
December 2015 LIOM07-002

Figure 19: Gemini 3 with a sunshade fitted

Figure 20: Gemini 3 without a sunshade fitted

Software configuration
The Gemini 3 has a very wide range of parameters that must be configured in order to interface with
its controlling SCADA system and switchgear. You configure these parameters using the Configuration
Tool.

Gemini 3 27
LIOM07-002 December 2015

Check the software and other requirements


To run the Configuration Tool, a laptop, tablet or desktop computer to the following specification
is recommended:

Component Specification

CPU 800 MHz or greater required

RAM 1 GB or greater recommended

Disk space 500 MB free or greater recommended

Operating system Windows Vista 32-bit/64-bit or later


For Mac OS X or Linux – consult Lucy

Java Version 7 or later

Ethernet port 10/100 Ethernet port for connecting to RTU

Download the Configuration Tool


1. Configure your computer to receive an automatic IP address from the RTU, which has an embedded
DHCP server on the MCM (Master Control Module).
2. Connect an RJ45 Ethernet cable from your computer to the ETH-1 port on the MCM. (By default,
the ETH-1 port is used for local configuration using a computer.)
The RTU allocates an IP address to your computer (usually 192.168.1.10).

3. Once you have been allocated an IP address, use a web browser to go to https://192.168.1.1.
This is the IP address of the Gemini 3 RTU web server.

4. When you are asked for authentication, type the following credentials:

Option Description
User Name gemini3
Password password

5. Click Download the Configuration Tool.


6. Save G3ConfigTool.jar to a suitable location on your computer’s hard disk.

Start the Configuration Tool


1. Using Windows Explorer, locate G3ConfigTool.jar, and then double-click it.
2. In the Login dialog box, type the following, and then click Login:

Option Description
User Name Admin
Password blank

RTU Address 192.168.1.1

28 Gemini 3
December 2015 LIOM07-002

Chapter

4
Commissioning
Hardware

Communications check
The communications check is required to perform the following tasks:
■ Make sure that events occurring in the RTU are successfully reported to the SCADA system.
■ Make sure that controls issued by the SCADA system are successfully carried out on the switchgear.
If the switchgear is live, these checks can be performed with the aid of the Lucy RMU simulator (RTU
commissioning tool).
Events such as switch open/close, insulation low etc. can be initiated on the simulator and confirmed
by the control engineer in the SCADA control centre.
Controls can also be issued from the SCADA control centre and confirmed by the local installation
engineer. There is a special control indication (dummy control) on the MCM which simply illuminates
an LED which also proves that the communication system is working. It is also possible to do automatic
controls with the RMU simulator (RTU commissioning tool).

RMU switchgear simulator


In order to perform the functional checks referred to in the previous section, the RTU must be powered
up and connected to the switchgear via its umbilical cable.
However, if the switchgear is live, this might not be possible unless permission is given from the
control centre. In this situation, you can use a switchgear (RMU) simulator to simulate alarms, analogue
inputs, and controls without operating the switchgear.

Gemini 3 29
LIOM07-002 December 2015

The figure below shows the Lucy RMU simulator (RTU commissioning tool) connected to the Gemini
3 RTU.

Figure 21: Lucy RMU simulator connected to a Gemini 3

Software
The main use of the Configuration Tool during RTU commissioning is to set the specific RTU address
for the location of the RTU, as well as to perform some functional checks to make sure that the RTU
is functioning normally, including the following:
■ Testing output controls (including Switchgear)
■ Verifying input states
■ Checking communications
■ Viewing alarms

Commission the RTU software


The Commissioning wizard helps commissioning engineers to quickly create a basic configuration
file, which can then be adjusted later to meet the exact requirements of the SCADA system.
1. Start the Configuration Tool.
2. Click Commissioning > Wizard > Start Commissioning.

30 Gemini 3
December 2015 LIOM07-002

3. On the Site Information page, follow the instructions on screen, and then click Next.
■ Fields shaded white are optional.
■ Fields shaded blue are required.
■ Fields shaded red are incomplete.
You will find extra information about some of the settings in the table below.

Setting Description

DNP3 RTU Address Type an address in the range 0–65535.

4. On the Configure Switchgear page, follow the instructions on screen, and then click Next.
5. On the Configure SCADA page, follow the instructions on screen, and then click Next.
6. On the Configure Field Device page, follow the instructions on screen, and then click Next.
The field device settings displayed are taken from Configuration > Ports > RS-485.

7. On the Finish page, follow the instructions on screen.


To modify the existing commissioning settings, click Commissioning > Wizard > Re-run
Commissioning.

Connect the RTU to your network


By default, the ETH-0 (Ethernet 0) port on the Gemini 3 RTU is used to communicate with the SCADA.
You use the Configuration Tool to change the default IP address settings for the ETH-0 port so that
the RTU is connected to the same network as the SCADA.
1. Start the Configuration Tool.
2. On the File menu, click Read Configuration to download the configuration file from the RTU
into the Configuration Tool.
3. Go to Configuration > Ports > ETH-0.
4. Select the Configure check box.
5. Click Static IP.
6. In the IP Address, Submask, and Gateway boxes, type the IP address settings for the RTU.
7. On the File menu, click Write Configuration.
Caution! The configuration file is written to the RTU with no further prompting.

8. On the Done dialog box, click Activate Now.


9. On the Success dialog box, click Restart Now
The RTU is warm restarted.

10. Connect the RTU to your network using the ETH-0 connector on the new IP address.
Tip You can confirm that the RTU is connected to your network by pinging its IP address from another
computer on your network.

Gemini 3 31
LIOM07-002 December 2015

Chapter

5
Maintenance
Maintenance guidelines
Before servicing the RTU
Before servicing the RTU, make sure to do the following:
■ De-commission the RTU, so that the SCADA control room is aware. In addition, if the RTU is put
in out-of-service mode using the Configuration Tool, all SCADA communications are stopped.
■ Set the correct RTU state. Set it to LOCAL to allow local operations, or to OFF to inhibit all
switchgear operations. To set the correct mode, use the Local Remote Module (if fitted), otherwise
use the MODE button on the HMI or MCM.

After servicing the RTU


After servicing the RTU, check the following items:
■ All of the connectors are in their proper places, and firmly connected.
■ All of the modules have their LEDs working as expected, such as slow-blinking green OK LEDs,
fixed green PWR LEDs, and blinking green CAN LEDs. Problems will be shown in the alarm section
in the Configuration Tool as active alarms. If they are still active after acknowledging them, the
problem might be still there and must be solved.
■ All of the RTU functionality is working as expected. A checklist and test procedure might be
followed, checking also in cooperation with the SCADA control room if possible.
■ The RTU is left in an operable state, usually setting the RTU in REMOTE mode.
Note If not left in this state, remote control is not possible.

■ The RTU box is locked properly (if applicable).


During all the service stages, follow all security measures in order to avoid accidents and problems.

Maintaining and upgrading the RTU


Routine maintenance of the Gemini 3 RTU covers three areas:
■ Enclosure integrity
■ Battery condition
■ Backplane and modules
Tip Restock any missing spare fuses during routine maintenance. For information, see Spare fuses
(page 11).

32 Gemini 3
December 2015 LIOM07-002

If you are unsure about any of the items in the checklists below, contact Lucy Electric (EMS) Limited
for advice using the details on the back cover of this manual.

Check the enclosure integrity


The Gemini 3 is designed for long term use in an outdoor environment, so it is important to make
sure that the control electronics are properly protected from the elements. Carry out the following
hardware checks to make sure that the case is fully weatherproof:
■ Check the outer door seal for security.
■ Check that the door latches function correctly.
■ Check that the door hinges are functioning correctly and are securely attached.
■ Remove any debris which may have collected in the lip of the outer stainless steel case.
■ Check for any signs of water entry.

Check the battery


The Gemini 3 has a built-in battery test that applies a load to the battery to make sure that it can
supply load. This test can only be activated remotely or locally using the Configuration Tool.
■ Check that the battery connections are free of corrosion.
■ For sealed lead-acid batteries, apply a smear of silicone grease to the connections to prevent
corrosion.
■ Check that the battery connections are tight.

Check the backplane and modules


■ Inspect the internal wiring for damage or any loose connections.
■ Check the tightness of all connections on the interface terminal blocks.
■ Check the tightness of the power input connections.

Gemini 3 33
LIOM07-002 December 2015

Appendix

A
Technical specification
Option Description

Outer Enclosure Default – painted/coated mild steel


Optional – 304-grade stainless steel

Degree of IP55
Protection

Operating Cabinet - 25° C to 55° C ambient


Temperature
Electronics -25° C to 70° C

Relative Up to 95%
Humidity

Method of Floor, wall, pole or RMU switchgear


Mounting

Dimensions 5 slot cubicle (for up to 5 modules)


■ Height = 600 mm
■ Width = 400 mm
■ Depth = 241 mm
■ Weight = 42 kg with lead acid battery pack, 29 kg without

Processor MCM = ARM


Modules
Other modules = ARM Cortex-M

Power Supply Note This option is user selectable on the power supply unit.
I/P (from LV)
Switch selectable 115 or 230 VAC via 5 kV isolation transformer
Due to the arrangement of this transformer/switched mode PSU combination, peak voltages of up to
160 VAC (115 V) or 320 VAC (230 V) can be accommodated without damage
Source capacity required – 100/200 VA depending on configuration of RTU
100 VA maximum for 5-slot RTU

Peripheral The Gemini 3 RTU provides a number of DC outputs to power peripheral equipment:
Equipment
■ DSM – 24 V (none isolated) from each switch connector. Maximum current 1 A per module.
Power
■ PSM – 24 V (none isolated). Maximum current 400 mA.
■ PSM – Either one or two isolated 12/24 V supplies (depending on unit specification). 12 V output(s)
maximum current 2.5 A, 24 V output(s) maximum current 400 mA.
The total RMS power consumption on all outputs should not exceed 25 W for reliable long term
operation. Total peak power consumption should not exceed 50 W.

Battery Type 24 V 14 Ah sealed lead-acid or 11 Ah NiMH options

Battery Charger Internal, intelligent , temperature-compensated

34 Gemini 3
December 2015 LIOM07-002

Option Description

Battery Runtime RTU only (no comms) - using 14 Ah lead acid batteries, typically 24 hrs after which a min of 5 switch
operations can be completed

Control Modular
Electronics

Inner Enclosure Modular - aluminium extrusions

Ventilation Natural

Communication RS-232, Ethernet


Interfaces

Communication Radio, GSM, GPRS, Fibre


Media

Protocols DNP3.0 serial, DNP3.0 TCP/IP, IEC 60870-5-104


Note The RTU currently uses these protocols in the slave role when communicating with the SCADA
control centre.
Modbus RTU (RS-485) or TCP Master

Controls Local control via optional HMI or laptop computer


Remote control from SCADA

Switchgear Plug-in multi-core cables to switchgear, directly to DSM module or RTU mounted sockets (cost option)
Interface

Configuration On computer, Java-based Configuration Tool application

Gemini 3 35
LIOM07-002 December 2015

Appendix

B
Module LED states
MCM (Master Control Module) LEDs
LED Description Healthy state Alarm states

OK RTU health Slow-blinking green Fast-blinking green - warning


alarm
Slow-blinking red - error alarm
Fast-blinking red - critical alarm

PWR Module's internal 3.3 V power rail Fixed green

CAN CAN bus traffic Fast-blinking green

LED Description Healthy state Indication

DUMMY Dummy switch control Fixed green or red The DUMMY switch is in the
Open position, which shows that
Used for RTU testing and SCADA You can use the Configuration
the dummy relay is working.
feedback purposes. Tool to set this LED to display the
Open colour as either green or
red in use.

PSM (Power Supply Module) LEDs


LED Description Healthy state Alarm states

OK RTU health Slow-blinking green Fast-blinking green - warning


alarm
Slow-blinking red - error alarm
Fast-blinking red - critical alarm
Fast-blinking red/green -
bootloader mode

PWR Module's internal 3.3 V power rail Fixed green Fixed red - internal fault

CAN CANbus traffic Fast-blinking green - CAN Off - no traffic received


heartbeat message Fixed red or orange - CANbus
error or address ID clash

LED Healthy state Indication Alarm states

AC SUPPLY Fixed green AC supply on Fixed red - AC supply off

LOGIC SUPPLY Fixed green Logic supply on Fixed red - logic supply off

36 Gemini 3
December 2015 LIOM07-002

LED Healthy state Indication Alarm states

MOTOR SUPPLY Fixed green Motor supply on

BATT CHARGER Fixed green Battery charger on Fixed red - battery charger
or battery fault
Off - battery charger off
Fast-blinking green -
battery over temperature,
charging suspended

BATT HEALTH Fixed green Battery charged Fixed red - battery low or
disconnected
Fast-blinking red - RTU
about to shutdown low
battery
Fast-blinking green -
battery test in progress

FAN Fixed green Fan on Fixed red - fan supply


fault

DC 1 Fixed green Power supply on Fixed red - power supply


fail or fault
DC 2 Off - power supply off

24V AUX

DSM (Dual Switch Module) LEDs


LED Description Healthy state Alarm states

OK RTU health Slow-blinking green Fast-blinking green - warning


alarm
Slow-blinking red - error alarm
Fast-blinking red - critical alarm

PWR Module's internal 3.3 V power rail Fixed green

CAN CAN bus traffic Fast-blinking green

Gemini 3 37
LIOM07-002 December 2015

LED Description Healthy state Indication

Inputs

IP Switch contacts open Fixed green or red The switch contacts are open.
You can use the Configuration Tool
to set this LED to display the
IP Switch contacts closed Switch Open colour as either The switch contacts are closed.
green or red in use.
■ If Switch Open is configured
to display as red, then Switch
Closed will display as green.
■ If Switch Open is configured
to display as green, then
Switch Closed will display as
red.
Only one of the Switch Open and
Switch Closed LEDs will be lit at
any one time.

IN Inputs 1-10 LEDs will be on or off according to Shows the associated input status.
number input state.

Outputs

OP M+ Motor +ve On when switchgear operation in Power is switched on to switchgear


progress, otherwise off. actuator.

OP Switchgear open operation in Off When on, shows that a switchgear


progress open operation is in progress.
You can use the Configuration Tool
to set this LED to display the
OP Switchgear close operation in Switch Open colour as either When on, shows that a switchgear
progress green or red in use. close operation is in progress.
■ If Switch Open is configured
to display as red, then Switch
Closed will display as green.
■ If Switch Open is configured
to display as green, then
Switch Closed will display as
red.

OP 1 Output 1 Off When on, shows that output 1 is


active.

38 Gemini 3
December 2015 LIOM07-002

IOM (Input Output Module) LEDs


LED Description Healthy state Alarm states

OK RTU health Slow-blinking green Fast-blinking green - warning


alarm
Slow-blinking red - error alarm
Fast-blinking red - critical alarm

PWR Module's internal 3.3 V power rail Fixed green

CAN CAN bus traffic Fast-blinking green

LED State Indication

DI Digital Inputs Fixed green Link made between A and B inputs

Off Link between A and B is open circuit

DO Digital Outputs Fixed green Relay is on

Off Relay is off

FPM (Fault Passage Module) LEDs


LED Description Healthy state Alarm states

OK RTU health Slow-blinking green Fast-blinking green - warning


alarm
Slow-blinking red - error alarm
Fast-blinking red - critical alarm

PWR Module's internal 3.3 V power rail Fixed green

CAN CAN bus traffic Fast-blinking green

LED Description State

PF-A Phase fault A Fixed red - fault present


Off - fault not present
EF-A Earth fault A

PF-B Phase fault B

EF-B Earth fault B

Gemini 3 39
LIOM07-002 December 2015

Appendix

C
Module connector details
This appendix contains connector details of the digital inputs, digital outputs, and analogue inputs
for each module.
Note The connectors in the following tables are displayed viewed from the front.

40 Gemini 3
December 2015 LIOM07-002

MCM (Master Control Module) connector details

J905 J803
Config

J901
J801
J904 Config

J802
J902
Control/SCADA

J800
J903 Control/SCADA

Figure 22: MCM connector details

J905 J803
USB RS-232 B (configuration)
Connector Type Connector Type
USB Type A 9wD Male
Layout Pin Signal Layout Pin Signal
1 +5V 1 DCD
2 USB Data + 2 RX
3 USB Data - 3 TX
4 0V 4 DTR
Notes 5 ISO 0V
■ For factory use only. 6 DSR
7 RTS
8 CTS
9 RI

Gemini 3 41
LIOM07-002 December 2015

J901 J801
Debug ETH-1 (configuration)
Connector Type Connector Type
Molex Micro-Fit 3.0 RJ45 (8W)
Layout Pin Signal Layout Pin Signal
1 0V 1 TPOUT+
2 RX 2 TPOUT-
3 TX 3 TPN+
4 Boot Mode Select 4 TCT_RCT
5 No connection
6 TPN-
7 No connection
8 Earth

J904
Door switch
Connector Type
Molex 5569
Layout Pin Signal
1 Door Switch Input*
2 0V
* Link to 0V when door is closed

J902 J802
RS485 RS-232 A (control/SCADA)
Connector Type Connector Type
Multicomp MC series 3.5 mm Pluggable Terminal Block 9wD Male
Layout Pin Signal Layout Pin Signal
1 Termination* 1 DCD
2 Termination* 2 RX
3 RS485 A+ 3 TX
4 RS485 B- 4 DTR
5 ISO 0V 5 ISO 0V
*Link pins 1 and 2 to terminate with 120 Ω 6 DSR
7 RTS
8 CTS
9 RI

J903 J800
HMI ETH-0 (control/SCADA)
Connector Type Connector Type
RJ45 (6 way) RJ45 (8 way)
Layout Pin Signal Layout Pin Signal

42 Gemini 3
December 2015 LIOM07-002

J903 J800
1 0V 1 TPOUT+
2 HMI Detect 2 TPOUT-
3 CAN H 3 TPN+
4 CAN L 4 TCT_RCT
5 No connection 5 TCT_RCT
6 HMI Power (+36V) 6 TPN-
7 No connection
8 Earth

Gemini 3 43
LIOM07-002 December 2015

PSM (Power Supply Module) connector details

J804

J800 J802

J803

J801

Figure 23: PSM connector details

J804
DC outputs
Connector Type
Multicomp MC000061 3.5 mm Screw Terminal Block
Layout Pin Signal
1 DC 1 +ve
2 DC 1 -ve
3 DC 2 +ve
4 DC 2 -ve
5 24V Aux +ve
6 0V Aux -ve
7 24V Aux +ve
8 0V Aux -ve

J800 J802
Battery sensor Battery
Connector Type Connector Type
Molex Micro-Fit 3.0 JST VL Plug
Layout Pin Signal Layout Pin Signal

44 Gemini 3
December 2015 LIOM07-002

J800 J802
1 APP Flash Write Enable 2 Battery Positive
2 Clock
3 Data 1 Battery Negative
4 0V
5 3V3
6 ID Flash Write Enable

J803 J801
Optional fan DC supply
Connector Type Connector Type
Molex 5569 (4 way) Molex 5569 (8 way)
Layout Pin Signal Layout Pin Signal
1 Fan Speed Input* 1 Battery Test Load +
2 No connection 2 Battery Test Load -
3 Fan DC+ (24V switched) 3 Battery Load Control
4 Fan DC- (0V) 4 PSU RX*
* Open collector output from fan 5 PSU TX*
6 PSU Status*
7 DC In -
8 DC In +

Gemini 3 45
LIOM07-002 December 2015

DSM (Dual Switch Module) connector details

J900 J901

SW901

J702

J700
J4

J3

Figure 24: DSM connector details

SW901 The Module ID Switch is used to set the address of multiple modules of the same type. Each module
of the same type must have a unique ID (between 1-7) set by this switch.
Module ID Switch
Notes
■ Any position other than 1-7 will disable the card and it will not be detected by the Configuration
Tool.
■ If a module ID is changed, the RTU must be restarted and the modules re-registered.

J900 J901
Switch A inputs 8 to 10 Switch B inputs 8 to 10
Connector Type Connector Type
Multicomp MC series 3.5 mm Pluggable Terminal Block Multicomp MC series 3.5 mm Pluggable Terminal Block
Layout Pin Signal Layout Pin Signal
6 SW A Indicator 8 6 SW B Indicator 8
5 Isolated GND 5 Isolated GND
4 SW A Indicator 9 4 SW B Indicator 9
3 Isolated GND 3 Isolated GND
2 SW A Indicator 10 2 SW B Indicator 10
1 Isolated GND 1 Isolated GND
Notes
■ Connect Isolated GND to Indicator inputs to activate, typical loop “wetting” current <2 mA at 12 VDC.

46 Gemini 3
December 2015 LIOM07-002

J4 J3
Phase current from Switch A CT input Phase current from Switch B CT input
Connector Type Connector Type
Molex 5569 Molex 5569
Layout Pin Signal Layout Pin Signal
1 Connected to J4 pin 4 1 Connected to J3 pin 4
2 CT A Sensor 2 CT B Sensor
3 Connected to J4 pin 6 3 Connected to J3 pin 6
4 Connected to J4 pin 1 4 Connected to J3 pin 1
5 CT A Sensor 5 CT B Sensor
6 Connected to J4 pin 3 6 Connected to J3 pin 3
Notes
■ Nominal 1A, maximum input current 2A.

Gemini 3 47
LIOM07-002 December 2015

J702 J700
Switch A connector Switch B connector
Connector Type Connector Type
Molex 5569 Molex 5569
Layout Pin Signal Layout Pin Signal
1 Motor +VE 1 Motor +VE
2 +24V 2 +24V
3 SW A Spare output relay 3 SW B Spare output relay
A A
4 SW A Close relay A 4 SW B Close relay A
5 SW A Open relay A 5 SW B Open relay A
6 Isolated GND 6 Isolated GND
7 SW A Indicator 2 7 SW B Indicator 2
8 Isolated GND 8 Isolated GND
9 SW A Indicator 3 9 SW B Indicator 3
10 Isolated GND 10 Isolated GND
11 SW A Indicator 5 11 SW B Indicator 5
12 SW A Indicator 6 12 SW B Indicator 6
13 Motor -VE 13 Motor -VE
14 No connection 14 No connection
15 SW A Spare output relay 15 SW B Spare output relay
B B
16 SW A Close relay B 16 SW B Close relay B
17 SW A Open relay B 17 SW B Open relay B
18 SW A Indicator 4 18 SW B Indicator 4
19 Isolated GND 19 Isolated GND
20 SW A Open status 20 SW B Open status
Indicator Indicator
21 SW A Close status 21 SW B Close status
Indicator Indicator
22 SW A Indicator 1 22 SW B Indicator 1
23 SW A Indicator 7 23 SW B Indicator 7
24 Isolated GND 24 Isolated GND
Notes
■ Motor +VE relay switched, 24-26 VDC relative to Motor -VE, peak current 16A
■ Switch Close and Open are software configurable to switch A contacts to Motor +VE (pull up), Motor -VE (pull down)
or B contacts (Link). Max current 2A.
■ +24V relative to Motor –VE, max current 1A (SW A and SW B combined).
■ Connect Isolated GND to Indicator inputs to activate, typical loop “wetting” current <2 mA at 12 VDC.

48 Gemini 3
December 2015 LIOM07-002

IOM (Input Output Module) connector details

SW901

J902 J661

J651

J905 J652

J906 J653

J907 J654

Figure 25: IOM connector details

SW901 The Module ID Switch is used to set the address of multiple modules of the same type. Each module
of the same type must have a unique ID (between 1-7) set by this switch.
Module ID Switch
Notes
■ Any position other than 1-7 will disable the card and it will not be detected by the Configuration
Tool.
■ If a module ID is changed, the RTU must be restarted and the modules re-registered.

Gemini 3 49
LIOM07-002 December 2015

J902 J661
Digital inputs 1 - 4 Battery connection
Connector Type Connector Type
Multicomp MC series 3.5 mm Pluggable Terminal Block Molex 03953-11002 5.08 mm Screw Terminal Block
Layout Pin Signal Layout Pin Signal
8 Digital In 1A 1 Battery +ve
7 Digital In 1B
6 Digital In 2A 2 Battery -ve
5 Digital In 2B
4 Digital In 3A
3 Digital In 3B
2 Digital In 4A
1 Digital In 4B
Notes
■ Connect B In (isolated 0V) to A In to activate, typical loop
“wetting” current <2 mA at 3.3 VDC.

J651
Current transformer input
Connector Type
Multicomp MC series 3.5 mm Pluggable Terminal Block
Layout Pin Signal
1 CT Input A*
2 CT Input B*

* 2A maximum current

J905 J652
Digital inputs 5-8 Analogue inputs 1-4
Connector Type Connector Type
Multicomp MC series 3.5 mm Pluggable Terminal Block Multicomp MC series 3.5 mm Pluggable Terminal Block
Layout Pin Signal Layout Pin Signal
8 Digital In 5A 1 Analogue Input 1
7 Digital In 5B 2 Isolated 0V
6 Digital In 6A 3 Analogue Input 2
5 Digital In 6B 4 Isolated 0V
4 Digital In 7A 5 Analogue Input 3
3 Digital In 7B 6 Isolated 0V
2 Digital In 8A 7 Analogue Input 4
1 Digital In 8B 8 Isolated 0V
Notes Notes
■ Connect B In (isolated 0V) to A In to activate, typical loop ■ Analogue inputs can be factory configured as 0-10V
“wetting” current <2 mA at 3.3 VDC. voltage inputs or 4-20 mA current inputs.

50 Gemini 3
December 2015 LIOM07-002

J906 J653
Digital inputs 9-12 Analogue inputs 5-8
Connector Type Connector Type
Multicomp MC series 3.5 mm Pluggable Terminal Block Multicomp MC series 3.5 mm Pluggable Terminal Block
Layout Pin Signal Layout Pin Signal
8 Digital In 9A 1 Analogue Input 5
7 Digital In 9B 2 Isolated 0V
6 Digital In 10A 3 Analogue Input 6
5 Digital In 10B 4 Isolated 0V
4 Digital In 11A 5 Analogue Input 7
3 Digital In 11B 6 Isolated 0V
2 Digital In 12A 7 Analogue Input 8
1 Digital In 12B 8 Isolated 0V
Notes Notes
■ Connect B In (isolated 0V) to A In to activate. ■ Analogue inputs can be factory configured as 0-10V
voltage inputs or 4-20 mA current inputs.
■ Input current <2 mA.

J907 J654
Digital inputs 13-16 Digital outputs 1-4
Connector Type Connector Type
Multicomp MC series 3.5 mm Pluggable Terminal Block Multicomp MC series 3.5 mm Pluggable Terminal Block
Layout Pin Signal Layout Pin Signal
8 Digital In 13A 1 Digital Out 1 Relay NC
7 Digital In 13B 2 Digital Out 1 Relay Com
6 Digital In 14A 3 Digital Out 1 Relay NO
5 Digital In 14B 4 Digital Out 2 Relay NC
4 Digital In 15A 5 Digital Out 2 Relay Com
3 Digital In 15B 6 Digital Out 2 Relay NO
2 Digital In 16A 7 Digital Out 3 Relay Com
1 Digital In 16B 8 Digital Out 3 Relay NO
Notes Notes
■ Connect B In (isolated 0V) to A In to activate, typical loop ■ NC = Normally Closed
“wetting” current <2 mA at 3.3 VDC.
■ Com = Common
■ NO = Normally Open

Gemini 3 51
LIOM07-002 December 2015

FPM (Fault Passage Module) connector details

SW901

J802

J800

J806 J807

Figure 26: FPM connector details

SW901 The Module ID Switch is used to set the address of multiple modules of the same type. Each module
of the same type must have a unique ID (between 1-7) set by this switch.
Module ID Switch
Notes
■ Any position other than 1-7 will disable the card and it will not be detected by the Configuration
Tool.
■ If a module ID is changed, the RTU must be restarted and the modules re-registered.

J806 J807
4-20 mA inputs 1 & 2
Connector Type Connector Type
Multicomp MC series 3.5 mm Pluggable Terminal Block Multicomp MC series 3.5 mm Pluggable Terminal Block
Layout Pin Signal Layout Pin Signal
1 Isolated 24V** 1 Isolated 24V**
2 Input 1* 2 Input 3*
3 Isolated 24V** 3 Isolated 0V
4 Input 2* 4 Isolated 0V
* Input impedance 250 Ω
** Maximum current 50 mA per output

52 Gemini 3
December 2015 LIOM07-002

Reference: J802 Reference: J800


3-phase current inputs from switch A CTs 3-phase current inputs from switch B CTs
Connector Type Connector Type
Molex 5569 Molex 5569
Layout Pin Signal Layout Pin Signal
1 Common A 1 Common B
2 Common A 2 Common B
3 Common A 3 Common B
4 Phase A3 4 Phase B3
5 Phase A2 5 Phase B2
6 Phase A1 6 Phase B1
Notes
■ Nominal 1A per input, maximum per input current 2A.

Gemini 3 53
LIOM07-002 December 2015

Appendix

D
Gemini 3 cubicle specification
Depending on the backplane used, the Gemini 3 will require a suitable outer enclosure or cubicle.
The Gemini 3 cubicle has the following features:
■ Constructed from stainless steel.
■ Optional split gland plate for easy fitting of umbilical cables and gland plate sockets available.
■ Optional pad-lockable physical local/remote switch module available.

Cubicle connections

54 Gemini 3
December 2015 LIOM07-002

Switch connector #1
Description Switch 1

Connector Type ITT Cannon 28+4 Neptune Series Socket

Layout Pin Signal

A +24 VDC (permanent)

B 0V

C +24 VDC Actuator Supply (switched)

D Open Command

E Close Command

F FPI Reset/CB Trip Command

G FPI Reset/CB Trip Command Common

H General Alarm/Indication Common

J Switch/CB Closed Indication

K Switch/CB Open Indication

L Actuator Disabled Indication

M SF6 Gas Low Indication

N FPI/Protection Operated Indication

P TLF/Relay Operated Alarm

R L1 HV Voltage not present indication

S L2 HV Voltage not present indication

T L3 HV Voltage not present indication

U DFPI/Protection Operated Indication

V Spare (wired to tail)

W Spare (wired to tail)

aa Spare (wired to tail)

ee L1 Phase CT

Ff L2 Phase CT

gg L3 Phase CT

hh L1/L2/L3 Phase CT Common

Notes
■ Socket contact fitted in positions 1, 2, 3
■ +24 VDC permanent supply. Maximum total current for switch connectors 1-4 < 1 A.

Gemini 3 55
LIOM07-002 December 2015

Switch connector #2
Description Switch 2

Connector Type ITT Cannon 28+4 Neptune Series Socket

Layout Pin Signal

A +24 VDC (permanent)

B 0V

C +24 VDC Actuator Supply (switched)

D Open Command

E Close Command

F FPI Reset/CB Trip Command

G FPI Reset/CB Trip Command Common

H General Alarm/Indication Common

J Switch/CB Closed Indication

K Switch/CB Open Indication

L Actuator Disabled Indication

M SF6 Gas Low Indication

N FPI/Protection Operated Indication

P TLF/Relay Operated Alarm

R L1 HV Voltage not present indication

S L2 HV Voltage not present indication

T L3 HV Voltage not present indication

U DFPI/Protection Operated Indication

V Indicator Input 9 (DSM 1B)

W Indicator Input 10 (DSM 1B)

aa Spare (wired to tail)

ee L1 Phase CT

Ff L2 Phase CT

gg L3 Phase CT

hh L1/L2/L3 Phase CT Common

Notes
■ Socket contact fitted in positions 1, 2, 3
■ +24 VDC permanent supply. Maximum total current for switch connectors 1-4 < 1 A.

56 Gemini 3
December 2015 LIOM07-002

Switch connector #3
Description Switch 3

Connector Type ITT Cannon 28+4 Neptune Series Socket

Layout Pin Signal

A +24 VDC (permanent)

B 0V

C +24 VDC Actuator Supply (switched)

D Open Command

E Close Command

F FPI Reset/CB Trip Command

G FPI Reset/CB Trip Command Common

H General Alarm/Indication Common

J Switch/CB Closed Indication

K Switch/CB Open Indication

L Actuator Disabled Indication

M SF6 Gas Low Indication

N FPI/Protection Operated Indication

P TLF/Relay Operated Alarm

R L1 HV Voltage not present indication

S L2 HV Voltage not present indication

T L3 HV Voltage not present indication

U DFPI/Protection Operated Indication

V Indicator Input 9 (DSM 2A)

W Indicator Input 10 (DSM 2A)

aa Spare (wired to tail)

ee L1 Phase CT

Ff L2 Phase CT

gg L3 Phase CT

hh L1/L2/L3 Phase CT Common

Notes
■ Socket contact fitted in positions 1, 2, 3
■ +24 VDC permanent supply. Maximum total current for switch connectors 1-4 < 1 A.

Gemini 3 57
LIOM07-002 December 2015

Switch connector #4
Description Switch 4

Connector Type ITT Cannon 28+4 Neptune Series Socket

Layout Pin Signal

A +24 VDC (permanent)

B 0V

C +24 VDC Actuator Supply (switched)

D Open Command

E Close Command

F FPI Reset/CB Trip Command

G FPI Reset/CB Trip Command Common

H General Alarm/Indication Common

J Switch/CB Closed Indication

K Switch/CB Open Indication

L Actuator Disabled Indication

M SF6 Gas Low Indication

N FPI/Protection Operated Indication

P TLF/Relay Operated Alarm

R L1 HV Voltage not present indication

S L2 HV Voltage not present indication

T L3 HV Voltage not present indication

U DFPI/Protection Operated Indication

V Indicator Input 9 (DSM 2B)

W Indicator Input 10 (DSM 2B)

aa Spare (wired to tail)

ee L1 Phase CT

Ff L2 Phase CT

gg L3 Phase CT

hh L1/L2/L3 Phase CT Common

Notes
■ Socket contact fitted in positions 1, 2, 3
■ +24 VDC permanent supply. Maximum total current for switch connectors 1-4 < 1 A.

58 Gemini 3
December 2015 LIOM07-002

I/O connector
Description General I/O

Connector Type ITT Cannon 19-way Neptune Series Socket

Layout Pin Signal

A +24 VDC

B 0V

C Alarm Common

D Intruder Alarm (DSM 1 Indicator 8)

E Flood Alarm (DSM 1 Indicator 9)

F Substation Air Temperature

G Substation Air Temperature Common

H TX1 Temperature

J TX1 Temperature Common

K TX2 Temperature

L TX2 Temperature Common

Notes
■ Link alarm inputs to alarm common to activate, typical loop “wetting” current <2 mA at 12 VDC.
■ Temperature inputs - 4–20 mA current loop
■ Temperature Common - isolated 24V supply, max current 50 mA per output (individually fused
with resettable fuses).
■ 24 VDC is common to I/O, COM1 and COM2 connectors. Maximum total current 400 mA

RS-485 connector
Description COM1, COM2

Connector Type Neutrik Ethercon Socket with sealing kit

Layout Pin Signal

1 RS-485 A+

2 RS-485 B-

3 MCM Isolated 0V

4 +24 VDC

5 +24 VDC

6 No connection

7 0V

8 0V

Gemini 3 59
LIOM07-002 December 2015

Notes
■ RS-485 runs on an isolated supply. The MCM isolated 0V must be connected at the device, unless
the device has an isolated RS-485 port.
■ 24 VDC is common to I/O, COM1 and COM2 connectors. Maximum total current 400 mA

Dimensions
The figure below shows the dimensional/mounting details for a 5-slot split gland plate cubicle RTU.

Figure 27: 5-slot cubicle RTU dimensional/mounting details

60 Gemini 3
December 2015 LIOM07-002

Appendix

E
EMC and environmental tests
The Gemini 3 is fully environmentally-tested for both electromagnetic compatibility (EMC) and the
environmental conditions that it is designed to work in.
Note The type tests only apply to the Gemini 3 RTU in its enclosure. For OEM variants, consult Lucy
Electric (EMS) Limited for advice using the details on the back cover of this manual. Any
customer-specified third-party equipment to be included in the RTU (such as a communication device)
must be agreed as being suitable for the application.

Option Description

EMC Electromagnetic compatibility

Insulation Damage due to voltage difference

Safety Operator safety from touch potentials

Temperature Correct operation of Gemini 3 (high & low degrees Celsius)

Humidity Condensation

Vibration Shock, bump, seismic

Overall
Test Standard Description

Environmental Test Requirements For ENA EATS 48-5 Issue 3 2010 UK Energy Networks Association overall
Protection and Control Equipment and standard
Systems

EMC tests
Test Standard Level

Radiated Emission (below 1GHz) CISPR 11 -

Radiated Emission (above 1GHz) CISPR 22 -

Conducted Emission CISPR 22 -

Radiated radiofrequency IEC 61000-4-3 Level 3


electromagnetic field

Electrostatic discharge IEC 61000-4-2 Level 4

Gemini 3 61
LIOM07-002 December 2015

Test Standard Level

Power frequency magnetic field IEC 61000-4-8 Level 5

Conducted disturbance induced by rf IEC 61000-4-6 Level 3


fields

Fast transients IEC 61000-4-4 Level 4

Slow damped ocillatory waves IEC 61000-4-18 Level 3

Surge IEC 61000-4-5 Level 4

AC and DC voltage dips & interruptions IEC 61000-4-11 -

AC and DC voltage interruptions IEC 61000-4-11 -

Conducted disturbance induced by rf IEC 61000-4-6 Level 3


fields

Fast transients IEC 61000-4-4 Level 4

Slow damped oscillatory waves IEC 61000-4-18 -

Surge IEC 61000-4-5 Level 4

Conducted disturbance induced by rf IEC 61000-4-6 Level 3


fields

Fast transients IEC 61000-4-4 Level 4

Slow damped ocillatory waves IEC 61000-4-18 Level 3

Surge IEC 61000-4-5 Level 4

Power Frequency IEC 61000-4-16 Level 4

Conducted disturbance induced by rf IEC 61000-4-6 Level 3


fields

Fast transients IEC 61000-4-4 Level 4

Pulse magnetic field immunity test IEC 61000-4-9 +A1 Level 5

Damped oscillatory magnetic field IEC 61000-4-10 Level 5


immunity test

Electrical tests
Test Standard Description

Dielectric BS EN 60255-27:2014 Section 10.6.4.3 No flashover

Impulse Voltage BS EN 60255-27:2014 Section 10.6.4.2 No disruptive discharge

Environmental tests
Test Standard 60255 Section/Level

Temperature Cold Heat Storage BS EN 60068-2-1:2007 60255-1 - 6.12.3.4

Temperature Cold Heat Operating BS EN 60068-2-1:2007 60255-1 - 6.12.3.2

62 Gemini 3
December 2015 LIOM07-002

Test Standard 60255 Section/Level

Temperature Dry Heat Storage BS EN 60068-2-2:2007 60255-1 - 6.12.3.3

Temperature Dry Heat Operating BS EN 60068-2-2:2007 60255-1 - 6.12.3.1

Test Cab: Damp heat, steady state BS EN 60068-2-78:2002 60255-1 - 6.12.3.6

Damp Heat, Cyclic BS EN 60068-2-30:2005 60255-1 - 6.12.3.7

Degrees of protection provided by BS EN 60529:1992 + A2:2013 IP55


enclosures (IP code)

Solar Radiation BS 7527-2.4:1991 -

Test N: Change of temperature 60068-2-14 60255-1 - 6.12.3.5

Mechanical tests
Test Standard 60255 Section Level

Vibration BS EN 60068-2-6 BS EN 60255-21-1:1996 Response Class 2, Endurance


Class 1

Shock BS EN 60068-2-27 BS EN 60255-21-2:1996 Response Class 2, Endurance


Class 1

Bump BS EN 60255-21-2:1996 Class 1

Seismic BS EN 60255-21-3:1995 Class 1

Gemini 3 63
LIOM07-002 December 2015

Glossary
Ah ampere-hour
A unit of electric charge used to measure battery capacity.

APN Access Point Name


CT current transformer
CTS Clear To Send (RS-232)
DCD Data Carrier Detect (RS-232)
DHCP Dynamic Host Configuration Protocol
Network client devices use DHCP to request Internet Protocol parameters
such as an IP address from a network server,

DNP3 Distributed Network Protocol, version 3


DSR Data Set Ready (RS-232)
DTR Data Terminal Ready (RS-232)
dynamic IP An IP address that is automatically assigned by a DHCP server. Opposite
of static IP.
EMC electromagnetic compatibility
Devices that meet EMC requirements can operate within a system’s
expected electromagnetic limits.

ENA Energy Network Association


FPI Fault Passage Indicator
Gemini Lucy Electric’s range of automation components.
Gemini 3 The third generation of Lucy Electric’s general-purpose RTU.
GND ground potential
GPRS General Packet Radio Service
GSM Global System for Mobile Communications (originally Groupe Spécial
Mobile)
The default global standard for mobile communications.

HMI Human Machine Interface


IEC 60870-5-101 Also known as IEC 101.
A protocol for the monitoring, control, and associated communications
of electrical power systems.
It is primarily used with relatively slow transmission media on the serial
port.

IEC 60870-5-104 Also known as IEC 104.


A protocol that enables communication between control stations and
substations using a standard TCP/IP network.
It is primarily used over a standard Ethernet network.

IP55 Ingress Protection rating (for water and solid objects)

64 Gemini 3
December 2015 LIOM07-002

LED light-emitting diode


LV low voltage
0–415 volts

NUA Each serial port (NTP1 and NTP2) on a Paknet Radio-Pad has a unique
14-digit Network User Address (NUA). The NUA of each port is printed on
a label on the Radio-Pad packaging box.
OEM original equipment manufacturer
Paknet Vodafone’s Packet Radio Service
The Vodafone core network is known as the Packet Radio Network (PRN)
and the Radio-Pad utilisation of this is called the Packet Radio Service (PRS)
or Paknet.

PSTN public switched telephone network


PSU power supply unit
RI Ring Indicator (RS-232)
RMU ring main unit
RS-232, RS-485 Standards for transmission of data using serial communication.
RTS Request To Send (RS-232)
RTU remote terminal unit
RX Receive Data (RS-232)
SCADA Supervisory Control And Data Acquisition
static IP An IP address that is configured manually. Opposite of dynamic IP.
SWA steel wire armoured
TX Transmit Data (RS-232)
VAC voltage (alternating current)
VDC voltage (direct current)
VT voltage transformer

Gemini 3 65
LIOM07-002 December 2015

Index
cubicle connections 54–59
A Gemini 3 RTU 54
I/O connector 59
analogue inputs 40 RS-485 connector 59
Switch connector #1 55
Switch connector #2 56
B Switch connector #3 57
Switch connector #4 58
backplane 8, 33
cubicle specification, Gemini 3 RTU 54
checking 33
Gemini 3 RTU 8
batteries 10–11
deep-discharge protection 10 D
Gemini 3 RTU 10 data radio 13
optimal charging 10 deep-discharge protection, batteries 10
testing 11 digital inputs 40
battery, checking 33 digital outputs 40
door and battery 10
switches 10
C downloading Configuration Tool 28
DSM (Dual Switch Module) 12, 37, 46
checking 33
connector details 46
backplane 33
LED states 37
battery 33
overview 12
checklist, unit installation 17
commissioning 29–30
hardware 29
RTU software 30 E
software 30 earthing Gemini 3 RTU 23
communications 12 electrical installation, Gemini 3 RTU 20
channel 12 electrical tests 62
devices 12 EMC and environmental tests 61–63
communications check 29 about 61
communications devices 13–15 electrical tests 62
data radio 13 EMC tests 61
fibre 14 environmental tests 62
serial 15 mechanical tests 63
components 9 overall 61
Gemini 3 RTU 9 EMC tests 61
Configuration Tool 27–28 enclosure integrity, checking 33
about 27 environmental conditions 26
downloading 28 environmental tests 62
hardware requirements 28 Ethernet, modem 14
software requirements 28
starting 28
configuring Gemini 3 parameters 27
connecting RTU to network 31 F
connector details 41, 44, 46, 49, 52 features, modules 12
DSM (Dual Switch Module) 46 fibre 14
FPM (Fault Passage Module) 52 FPM (Fault Passage Module) 12, 39, 52
IOM (Input Output Module) 49 connector details 52
MCM (Master Control Module) 41 LED states 39
PSM (Power Supply Module 44 overview 12

66 Gemini 3
December 2015 LIOM07-002

fuses 11
detecting blown 11 L
locations 11
spare 11 low-voltage supply, Gemini 3 RTU 20

G M
Gemini 3 parameters, configuring 27 maintenance 32–33
Gemini 3 RTU 7–11, 16, 18–20, 23, 27, 34, checking 33
54, 60 guidelines 32
backplane 8 RTU 32
batteries 10 MCM (Master Control Module) 12, 36, 41
components 9 connector details 41
cubicle connections 54 LED states 36
cubicle dimensions 60 overview 12
cubicle specification 54 mechanical tests 63
earthing 23 modem 13–14
electrical installation 20 Ethernet 14
ground-mounted installation 16 GPRS 13
line-mounted installation 16 module installation, guidelines 18
low-voltage supply 20 module LEDs 36–37, 39
modules, about 11 alarm states 36–37, 39
mounting 19 healthy state 36–37, 39
overview 7 modules 11–12
parameters, configuring 27 about 11
positioning 18 features 12
technical specification 34 mounting Gemini 3 RTU 19
upgradeability 8
GPRS, modem 13
guidelines 18, 32 N
maintenance 32
network, connecting RTU to 31
module installation 18

H O
optimal charging, batteries 10
hardware, commissioning 29
overview 7, 12
HMI (Human Machine Interface), overview 12
DSM (Dual Switch Module) 12
FPM (Fault Passage Module) 12
Gemini 3 RTU 7
I HMI (Human Machine Interface) 12
I/O connector 59 IOM (Input Output Module) 12
installation 16, 24 MCM (Master Control Module) 12
ground-mounted 16 PSM (Power Supply Module) 12
line-mounted 16
umbilical cables 24
IOM (Input Output Module) 12, 39, 49 P
connector details 49
positioning Gemini 3 RTU 18
LED states 39
PSM (Power Supply Module) 12, 36, 44
overview 12
connector details 44
IP address settings, RTU 31
LED states 36
overview 12

Gemini 3 67
LIOM07-002 December 2015

servicing RTU 32
R software, commissioning 30
spare fuses 11
RMU switchgear simulator 29 sunshade, RTU 26
RS-232, serial communications devices 15 switch connectors 55–58
RS-485 connector 59 switches 10
RTU 8, 26, 31–32 door and battery 10
configuration, updating 8
firmware, updating 8
IP address settings 31
maintenance 32 T
servicing 32 technical specification, Gemini 3 RTU 34
sunshade 26 temperature range 26
RTU software 30 testing batteries 11
commissioning 30

U
S
unit installation, checklist 17
safety information iii upgradeability, Gemini 3 RTU 8
serial communications devices 15

68 Gemini 3
Lucy Electric worldwide offices
Lucy Electric Ltd Lucy Electric Arabia Co Ltd Lucy Asia Pacific Sdn Bhd
Howland Road, Thame, Oxfordshire, Novotel Business Centre, PO Box 35340, L13A-03-03A, PJX-HM Shah Tower,
OX9 3UJ, United Kingdom Dammam 31488, Saudi Arabia No16A Jalan Persiaran Barat, 46050 Petaling Jaya,
Tel: +44 1844 267 267 General Tel: +966 3 8147 910 Selangor, Malaysia
Tel: +44 1844 267 222 Sales Fax: +966 3 8147 914 Tel: +60 374 910 700
Fax: +44 1844 267 223 Email: salessa@lucyelectric.com Fax: + 60 379 316 923
Email: salesuk@lucyelectric.com Email: salesmy@lucyelectric.com

Lucy Middle East FZE Lucy Electric South Africa (Pty) Ltd Lucy Electric (Beijing) Co Ltd
PO Box 17335, Jebel Ali, Dubai, Unit 2, Cranberry Industrial Park, Cranberry Street, Room 1122, Tower A, Gateway Square,
United Arab Emirates Laser Park, Honeydew, 2170, South Africa No 18 Xiaguangli, North Road East Third Ring,
Tel: +97 148 129 999 Tel: +27 11 025 7490 Chaoyang District, Beijing, China, 100027
Fax: +97 148 129 900 Fax: +27 11 794 3277 Tel: +86 1059 231 176
Email: salesme@lucyelectric.com Email: salesza@lucyelectric.com Fax: +86 1059 231 177
Postal Address: Email: salescn@lucyelectric.com
Lucy Electric (Thailand) Limited PO Box 1078, Honeydew, 2040, South Africa
388 Exchange Tower, 37th Floor,
Unit 3702, Sukhumvit Road, Klongtoey,
Bangkok 10110, Thailand
Tel: +66 (0) 2 663 4290
Fax: +66 (0) 2 663 4293
Email: salesth@lucyelectric.com
Contractor : National Projects & Contruction LLC 1 SLD

Over All SLD


Employer : ALDAR Projects 2

Country of Origin
Consultant : PARSONS 3

Signal List
Client : ADDC 4

Tele-Information Plan
SS : RMU Substations 5

6 Cable Overview List


Internal Project No:

Adaptation Design
Project Name : Madinat Al Riyadh City Ph-6A & 6B 7

8 I/O Connection Diagram

MATERIAL SUBMITTAL: DMS-RTU for RMU.Rev.01


9 RTU Functional Specification

10 RTU Detailed Design

11 RTU Method Statement

12 RTU FAT Procedure

13 RTU SAT Procedure

14 POINT TO POINT TEST PROCEDURE

15 Warranty Certificate
1 2 3 4 5 6 7 8 9 10

A A

EARTH
POINT

B B

GEMINI 3
RTU LED INTERNAL
C C
MODULES LIGHTS UR5i SL
ROUTER COMMS MCB
(METAL CONDENSATION
PSM G-3 MCM G-3 DSM G-3 DSM G-3 OPTION) VENT UR5i
ROUTER
Lite

GEMINI 3 RTU
OK PWR CAN OK PWR CAN OK PWR CAN OK PWR CAN

DC SUPPLY LOCAL REMOTE OFF IN 8 IN 8


LOGIC SUPPLY
MOTOR SUPPLY DUMMY MODE AUTO A B IN 9 A B IN 9

MODULE CONFIGURATION (PLASTIC


SW875

IN 10 IN 10 PWR
HMI GEMINI 3
FAN / SWITCHED AUX L809 Module
Id
Module
Id
lu OPTION)
TVS808

C809
Electric
USB

DC 1
RS232-B

L808
C808
DC 2 L807 A B A B
IP IP
TVS806

C807
J905
24V AUX L806
C806
IP IP
C805

DC 1+ IN 1 IN 1
DEBUG

X650

DC 1-
DC OUTPUTS

SW A IN 2 SW A IN 2
DC 2+ R803
J803

DC 2-
J901
IN 3 IN 3

G-3 DSM DSM


24V AUX IN 4 IN 4
G-3 G-3
ETH-1

PSM MCM
J904

D
0V
24V AUX
0V DOOR SW J801
IN 5
IN 6
IN 5
IN 6
Lite
G-3 MCM
G-3
CAN
OK PWR CAN
OK PWR CAN

IN 8 HMI D
TVS653
IN 7 IN 7 OK PWR
G-3
SENSOR

OK OK IN 8
24V DC

TVS804

OK PWR CAN PWR CAN PWR CAN


INPUT

J902
IN 9
OP M+ OP M+ OK PWR CAN PSM TE OFF A B
T + - 0

L804
C804
OP OP Lite PWR CAN LOCAL REMO IN 9 IN 10
C803
B
RS232-A

OK
RS485

L803
A
TVS802

L802
OP OP MODE AUTO IN 10
DC SUPPLY DUMMY
C802

SW875
Module
OUTPUT
24V AUX

C801
L801 OP 1 OP 1
/FAN

LY Id
LOGIC SUPP
DC SUPPLY LOCAL REMOTE OFF Module
C800
L800

IN 8 IN 8 MOTOR SUPP
LY
1

Id A B
SW B SW B L80
IP

808
TVS656

C809
CT A CT A

TVS
9
A B IP
LOGIC SUPPLY
L80

RS232-B
J802
PWROK MENU
C808
IP

USB
8

IN 1

806
L80

HED AUX IP
C807

TVS
DUMMY MODE A B A B
7

IN 9 IN 9 FAN / SWITC
L80

IN 2
5
ETH-0

C806
IN 1
J90

AUTO
HMI

MOTOR SUPPLY
6

HMI
C80

DC 1 5

IN 2 SW A IN 3

0
X65
SW875
CT B CT B DC 2 IN 3 IN 4
SW A

DEBUG
R80
J80
3 PW
R
IN 10 IN 10 24V AUX IN 5
3
J800
1 IN 4
DC 1+ IN 6
J90

OPEN IN 5 GEM
lu

ETH-1
DC 1-
PSM MCM Lucy Lucy IN 7

DC OUTPUTS
4
IN 6 INI
DSM DSM
J90
DC 2+
Lite ACT DC 2- IN 7 OP M+ 3
LOCAL 24V AUX TVSJ80
6531
OP M+ OP
FAN / SWITCHED AUX DOOR SW

804
0V
Module Module

TVS
CLOSE
MODE
REMOTE 24V AUX
2
OP OP
L809
J90

0V L80
OP 1
Id Id OP
C804

TVS808
C809 C80 4

RS232-A
802
USB
L80 3

DC 1

T + - 0
OFF 3
OP 1

TVS
24V DC
INPUT
RS232-B
L80
L808

RS485
C802

SENSOR
C80 2
C808 L80 1
CT A
SW B
1

DC 2 L807 A B A B C80
L80 0
0

SW B CT A
IP IP

TVS806

656
C807

OUTPUT

TVS
24V AUX
J905 J80

/FAN
2

24V AUX L806


C806
IP IP
CT B

ETH-0
CT B

PSU
C805

HMI
DC 1+ IN 1 IN 1 Lucy

DEBUG
J80
0

X650
RELAYS DC 1-
Lucy
DSM

DC OUTPUTS
SW A IN 2 SW A IN 2 MCM lu DSM PW
R
DC 2+ R803
J803

DC 2-
J901
IN 3 IN 3 PSM
OK

MEN
24V AUX IN 4 IN 4 Lite U

ETH-1
J904 OP
EN
0V IN 5 IN 5
E 24V AUX CLO E
0V IN 6 IN 6 SE LOCA
L
DOOR SW J801
REMO
TEM AC
T
TVS653
IN 7 IN 7 OFF OD
E
SENSOR

24V DC

TVS804
INPUT
J902
OP M+ OP M+

T + - 0
L804
C804
C803 OP OP

RS232-A
RS485
L803

TVS802
L802
OP OP
C802
OUTPUT
24V AUX

C801
L801 OP 1 OP 1
/FAN

C800
L800

1
SW B SW B
SUPPLY

TVS656
CT A CT A
NiMH
J802

MCB

ETH-0
11 AH

HMI
CT B CT B
BATT J800

PSM
Lite
MCM lu DSM
Lucy
DSM
Lucy

F F
DOOR &
BATTERY
SWITCH PSM lite
MCM MODULE
MODULE
EXPANSION SLOT

G
DSM MODULES G

UMBILICAL LOCAL REMOTE SWITCH


PAINTED STEEL ENTRY VIA SPLIT
ENCLOSURE - IP55
SEE SHEET 2 FOR ENCLOSURE DIMENSIONS
GLAND PLATE
ECN STANDARD TOLERANCES: ISO 2768-m.
FOR ADDITIONAL INFO. SEE DRG. 72219 C COPYRIGHT LUCY ELECTRIC (EMS). ALL RIGHTS RESERVED. ALL DIMENSIONS IN MILLIMETERS UNLESS OTHERWISE STATED
NUMBER

MOD. jones_mc DRAWN jones_mc G3 RTU, 5 SLOT IP55, MCM, IEC 104,
MOD.
APPRV. __
DRAWN
APPRV. CO
PSM-lite, 1X12V-COMMS, 2x DSM, LOCAL
H H
REM SW, 11AH NIMH, HMI, OEM PSU & TEMP
DATE 06/01/21 DATE 06/01/21 SENSOR, UR5i ROUTER - ADDC
MATERIAL: FINISH: ENGINEERING SOURCING CRITICALITY: SHEET NO: PROJECTION DO NOT SCALE THE REPRODUCTION OR TRANSMISSION OF ALL OR PART OF THIS
FROM A3 WORK, WHETHER BY PHOTOCOPYING OR STORING IN ANY MEDIUM
00 CATEGORY 2 1 OF 3
1st ANGLE IF IN DOUBT ASK
BY ELECTRONIC MEANS OR OTHERWISE, WITHOUT THE PRIOR
WRITTEN PERMISSION OF THE OWNER, IS PROHIBITED. AUT0004360 REV. 1
1 2 3 4 5 6 7 8 9 10

A A

268

220

M 10
B B

C C

635 REF

600

530
D D

E E

35
453

400

330
F F
290

48
241

G G

ECN STANDARD TOLERANCES: ISO 2768-m.


FOR ADDITIONAL INFO. SEE DRG. 72219 C COPYRIGHT LUCY ELECTRIC (EMS). ALL RIGHTS RESERVED. ALL DIMENSIONS IN MILLIMETERS UNLESS OTHERWISE STATED
NUMBER

MOD. jones_mc DRAWN jones_mc G3 RTU, 5 SLOT IP55, MCM, IEC 104,
MOD.
APPRV. __
DRAWN
APPRV. CO
PSM-lite, 1X12V-COMMS, 2x DSM, LOCAL
H H
REM SW, 11AH NIMH, HMI, OEM PSU & TEMP
DATE 06/01/21 DATE 06/01/21 SENSOR, UR5i ROUTER - ADDC
MATERIAL: FINISH: ENGINEERING SOURCING CRITICALITY: SHEET NO: PROJECTION DO NOT SCALE THE REPRODUCTION OR TRANSMISSION OF ALL OR PART OF THIS
FROM A3 WORK, WHETHER BY PHOTOCOPYING OR STORING IN ANY MEDIUM
00 CATEGORY 2 2 OF 3
1st ANGLE IF IN DOUBT ASK
BY ELECTRONIC MEANS OR OTHERWISE, WITHOUT THE PRIOR
WRITTEN PERMISSION OF THE OWNER, IS PROHIBITED. AUT0004360 REV. 1
1 2 3 4 5 6 7 8 9 10

A A

PSM
Lite
G-3 MCM G-3 DSM G-3 DSM G-3
OK PWR CAN OK PWR CAN OK PWR CAN OK PWR CAN

DC SUPPLY LOCAL REMOTE OFF IN 8 IN 8


LOGIC SUPPLY
MOTOR SUPPLY DUMMY MODE AUTO A B IN 9 A B IN 9

SW875
IN 10 IN 10 PWR
HMI GEMINI 3
FAN / SWITCHED AUX Module Module

lu
L809
Id Id

TVS808
C809
Electric

USB
DC 1

RS232-B
L808
C808
DC 2 L807 A B A B
IP IP

TVS806
C807
J905
24V AUX L806
C806
IP IP
C805

B DC 1+ IN 1 IN 1 B

DEBUG

X650
DC 1-

DC OUTPUTS
SW A IN 2 SW A IN 2
DC 2+ R803
J803

DC 2-
J901
IN 3 IN 3
24V AUX IN 4 IN 4

ETH-1
J904
0V IN 5 IN 5
24V AUX
0V IN 6 IN 6
DOOR SW J801
TVS653
IN 7 IN 7

SENSOR

24V DC

TVS804
INPUT
J902
OP M+ OP M+

T + - 0
L804
C804
C803 OP OP

RS232-A
RS485
L803

TVS802
L802
OP OP
C802

OUTPUT
24V AUX
C801
L801 OP 1 OP 1

/FAN
C800
L800

1
SW B SW B

TVS656
J802 CT A CT A
PWROK MENU

ETH-0
HMI
CT B CT B
J800

OPEN
PSM
Lite
MCM lu DSM
Lucy
DSM
Lucy

ACT
LOCAL
CLOSE
MODE
REMOTE
OFF

56
C C

164 35 177

D D

46

255

224
E E

145
F F

G G

ECN STANDARD TOLERANCES: ISO 2768-m.


FOR ADDITIONAL INFO. SEE DRG. 72219 C COPYRIGHT LUCY ELECTRIC (EMS). ALL RIGHTS RESERVED. ALL DIMENSIONS IN MILLIMETERS UNLESS OTHERWISE STATED
NUMBER

MOD. jones_mc DRAWN jones_mc G3 RTU, 5 SLOT IP55, MCM, IEC 104,
MOD.
APPRV. ___
DRAWN
APPRV. CO
PSM-lite, 1X12V-COMMS, 2x DSM, LOCAL
H H
REM SW, 11AH NIMH, HMI, OEM PSU & TEMP
DATE 06/01/21 DATE 06/01/21 SENSOR, UR5i ROUTER - ADDC
MATERIAL: FINISH: ENGINEERING SOURCING CRITICALITY: SHEET NO: PROJECTION DO NOT SCALE THE REPRODUCTION OR TRANSMISSION OF ALL OR PART OF THIS
FROM A3 WORK, WHETHER BY PHOTOCOPYING OR STORING IN ANY MEDIUM
00 CATEGORY 2 3 OF 3
1st ANGLE IF IN DOUBT ASK
BY ELECTRONIC MEANS OR OTHERWISE, WITHOUT THE PRIOR
WRITTEN PERMISSION OF THE OWNER, IS PROHIBITED. AUT0004360 REV. 1
A B C D E F G H J K

120mm 690mm 10000mm 1500mm


100mm
0 J2 0

24W MiniFit
MINIFIT JR 24W CONNECTOR
DSM2 SW A

To J3 pin 3
To J3 pin 15
Overall Label
Switch 3: DSM2/SWA M4 M5
J3 J4
M6 M7 Gland M25
Gland M25 Black on White Wire ID labels
6 DUMMY CB CLOSED 150mm Cable tie 150mm Cable tie
1 6 slightly loose on all wires to 1
5 J21 DUMMY CB CLOSED
5 4 DUMMY CB OPEN allow rotation
4 J5 DUMMY CB OPEN
3
3 2
Wires to be covered in spiral wrap W6
2 J20
1
1
3.5mm Term Block
AUT0003815 _ 3 SW1 + 3
TRM/QRM
DSM2 A 1
RS1 +24V (switched actuator supply) K5 / 1 - 1
J17 viewed from cable entry side 2
RS1 0V (actuator supply) K22 / 1 - 2
3
2 J1 / J3 W5 M3 4 RS1 (K01) Open Command (o/p) K10 / 1 - 3 2
To J3 pin 3
To J3 pin 15
RS1 (K01) Close Command (o/p) K12 / 1 - 4
13 1 Spiral Wrap 9mm id M2 M8 M1 Gland Locknut M25
5
6 RS1 (K01) Indication Common L3 / 1 - 7
Flexible Steel Conduit RS1 (K01) Indication Closed (i/p) L4 / 1 - 8
14 2 Gland Locknut M25 M9 Carrier strip 7
RS1 (K01) Indication Opened (i/p) L5 / 1 - 9
15 3 Cable marker S 8
J1 9 RS1/RS3 (K01/K03) EF Indication Common L61 / 1 - 64 / 78
16 4
M14 M10 10 RS1/RS3 (K01/K03) EF Indication L63 / 1 - 66 / 80
MINIFIT JR 24W CONNECTOR Brady Label Cable marker W RS1 (K01) Spare Indication Common - 153
17 5 24W MiniFit M11 11
RS1 (K01) Spare Indication (i/p) - 154
DSM1 SW A Cable marker 1
3 18 6 M12 12
RS2 +24V (switched actuator supply) 3
Cable marker + M13 13 K5 / 2 - 15
19 7 RS2 0V (actuator supply) K22 / 2 - 16
Cable marker 3 14
20 8 RS2 (K03) Open Command (o/p) K10 / 2 - 17
Overall Label 15
16 RS2 (K03) Close Command (o/p) K12 / 2 - 18
21 9 Switch 1: DSM1/SWA RS2 (K03) Indication Common L3 / 2 - 21
17
22 10 RS2 (K03) Indication Closed (i/p) L4 / 2 - 22
18
19 RS2 (K03) Indication Opened (i/p) L5 / 2 - 23
23 11 Low Gas Indication Common L30 - 43
20
24 12 Low Gas Indication L32 - 45
21
4 22 RS2 (K03) Spare Indication Common - 165 4
Connectors viewed from cable entry side RS2 (K03) Spare Indication (i/p) - 166

Cable DSM1/SWA DSM2/SWA Function Wire Flying Lead End


Ident J1 J3
Pin Pin

1 1 RS1 Actuator +VE (switched) 1.5mmsq Black Pin Crimp


2 13 RS1 Actuator -VE (0V) 1.5mmsq Black Pin Crimp
5 3 5 RS1 (K01) Open Command 1 mmsq Red Pin Crimp 5
Dress cable from J1 as shown above
4 4 RS1 (K01) Close Command 1 mmsq Red Pin Crimp
5 19 RS1 (K01) Indication Common 1 mmsq Red Pin Crimp
6 21 SW1 (K01) Closed Indication 1 mmsq Red Pin Crimp
7 20 RS1 (K01) Open Indication 1 mmsq Red Pin Crimp
8 24 RS1/3 (K01/3) EF Ind Common 1 mmsq Red Pin Crimp
J24 9 22 RS1/3 (K01/3) EF Ind 1 mmsq Red Pin Crimp
Socket Crimp for connectors J1 & J2 10 6 RS1 (K01) Spare Ind Common 1 mmsq Red Pin Crimp
11 18 RS1 (K01) Spare Ind 1 mmsq Red Pin Crimp
6 12 1 RS2 Actuator +VE (switched) 1.5mmsq Black Pin Crimp 6
13 13 RS2 Actuator -VE (0V) 1.5mmsq Black Pin Crimp
14 5 RS2 (K03) Open Command 1 mmsq Red Pin Crimp
15 4 RS2 (K03) Close Command 1 mmsq Red Pin Crimp
W1 Wire Black 1.5 sqmm Tri-rated 16 19 RS2 (K03) Indication Common 1 mmsq Red Pin Crimp
2 x 12.31m 17 21 RS2 (K03) Closed Indication 1 mmsq Red Pin Crimp
18 20 RS2 (K03) Open Indication 1 mmsq Red Pin Crimp
19 8 Low Gas Common Ind 1 mmsq Red Pin Crimp
W2 Wire Black 1sqmm Tri-rated
20 9 Low Gas Ind 1 mmsq Red Pin Crimp
17 x 12.31m
7 21 6 RS2 (K03) Spare Ind Common 1 mmsq Red Pin Crimp 7
W3 Wire Black 1sqmm Tri-rated 22 18 RS2 (K03) Spare Ind 1 mmsq Red Pin Crimp
4 x 100 mm

NOTES
8 8
1. Fit wire identification labels on both ends of all wires
M15 Seal-top Bag
for labels

REV DATE REF CHANGE DESIGN


THE COPYRIGHT IN THIS DOCUMENT IS THE PROPERTY OF DATE: SCHEMATIC NUMBER: TITLE: Gemini 3 RTU (DSM) to RMU 10m
1 25/06/19 ... Electric
2 09/08/19 ....
Initial Release Based on AUT0003200
Add wiring for dummy close signal
LUCY SWITCHGEAR (EMS) LTD, TRADING AS LUCY ELECTRIC
THE DOCUMENT IS SUPPLIED BY LUCY SWITCHGEAR (EMS) LTD
30/08/2019 AUT0003815 SHEET
TRM/QRM SW1 & 3 to Flying Leads
9 TITLE: 9
3 30/08/19 ECR 22948 Correct conduit gland part no. & dummy CB wires ON THE EXPRESS TERMS THAT IT BE TREATED AS UNIT 14 THORPE LANE FILE
. ../../.. .... ............ CONFIDENTAL, AND THAT IT MAY NOT BE COPIED, USED, THORPE WAY IND. EST. SHEET: NAME: AUT0003815_3 G3 Umbilical DSM RTU 10m T
. ../../.. .... ............ OR DISCLOSED FOR ANY OTHER PURPOSE THAN THAT BANBURY OX16 4UT
. ../../.. .... ............ WHICH IT IS SUPPLIED WITHOUT EXPRESS WRITTEN CONSENT. +44(0)1295 270448 1 of 1 BY: CHO REV: 3
A B C D E F G H J K
A B C D E F G H J K

160mm 690mm 10000mm 1500mm


0 0

Relay - A1

Trip Coil Interposing Relay


1 1

A1 A2

Wire Black 1sqmm Tri-rated


14 14
2 W2 2
W1
Relay - 14

Overall Labels (supplied loose) 13 13 Wire Black 1.5 sqmm Tri-rated


2 x 550 mm 12.8m
Switch 2: DSM1/CT B 12 12
Switch 4: DSM2/CT B
M4 M1 M5
Gland M25 Flexible Steel Conduit Gland M25
1 = +24V DC Perm
To DIN
Rail
MINIFIT 6W CONNECTOR Term Black on White Wire ID labels
3 J2 Wires to be covered in spiral wrap slightly loose on all wires to 3
allow rotation
4 1
5 2 AUT0003814 _ 3 W7
6 3
Lucy TRM/QRM
1
J1 J2
W6 M3 2 +24VDC Permanent (Trip Coil Supply) K1 - 41
6W MiniFit MINIFIT JR 24W CONNECTOR Bag with loose parts 0VDC Permanent To be assigned
J1 3
4 13 1 Spiral Wrap 9mm id M2 See below Gland Locknut M25 4
CB Trip (Open) Command (o/p) K2 - 42 4
14 2 Gland Locknut M25 CB Indication common L3 / * - 33
SUPPLY LOOSE IN A BAG CABLE TIED TO CABLE 5
24W MiniFit CB Indication Closed (i/p) L4 / * - 34
15 3 M6 6
Carrier strip for ovalgrip cable markers CB Indication Opened (i/p) L5 / * - 35
M13 7 CB Relay Trip Common (i/p)
16 4 M7 Ovalgrip cable marker S 8 RL11 - 96

17 5
110mm Brady Label
M8 Ovalgrip cable marker W
9
CB Relay Trip (i/p)
CB Watchdog Relay (i/p)
RL13 - 98
RL01 - 93
10
CB Watchdog Relay Common (i/p)
18 6 M9 Ovalgrip cable marker 2 11
1 CB Phase Y (S1) CT (i/p)
RL03 - 95
D30 - 122
12
19 7 M10 Ovalgrip cable marker 4 13
1 CB Phase Y (S2) CT (i/p) D130 - 124
5 CB Spare Indication Common (i/p) - 155 5
20 8 Socket Crimp for connectors J1 & J2 Overall Labels (supplied loose) M11 150mm Cable tie 14
CB Spare Indication (i/p) - 156
15
21 9 M12 150mm Cable tie 16 CB Spare Output (volt-free N/O) - 151 / 165
Switch 2: DSM1/SWB CB Spare Output (volt-free N/O) - 152 / 166
22 10
Switch 4: DSM2/SWB
23 11
24 12
Connectors viewed from cable entry side
Cable DSM DSM Interposing Function Wire Flying Lead End
6 Ident J1 J2 Relay 6
Pin Pin Terminal

N/A 1 A1 +24VDC Switched to interposing rly 1 mmsq N/A

1 DIN +24VDC (Permanent-Trip Coil Sply) 1.5mmsq Red Pin Crimp


Term
Dress cable from J1 as shown above 2 13 0VDC (Permanent) 1.5mmsq Red Pin Crimp
3 14 Trip (Open) Command 1 mmsq Red Pin Crimp
7 4 19 Switch Indication Common 1 mmsq Red Pin Crimp 7
5 21 Closed Indication 1 mmsq Red Pin Crimp
W3 Wire Black 1.5 sqmm Tri-rated 6 20 Open Indication 1 mmsq Red Pin Crimp
2x12.3m 7 8 Relay Trip Common 1 mmsq Red Pin Crimp
8 7 Relay Trip 1 mmsq Red Pin Crimp
W4 Wire Black 1.5 sqmm Tri-rated 9 22 Watchdog Relay 1 mmsq Red Pin Crimp
4x12.35m 10 24 Watchdog Relay Common 1 mmsq Red Pin Crimp
11 2 CT L2 (Y Phase) 1.5mmsq Blue 15mm hook blade
W5 Wire Black 1sqmm Tri-rated
12 5 CT Common 1.5mmsq Blue 15mm hook blade
12 x 12.3m
13 6 Spare Indication Common 1 mmsq Red Pin Crimp NOTES
8 14 18 Spare Indication 1 mmsq Red Pin Crimp 8
15 15 Spare Output 1 mmsq Red Pin Crimp 1. Fit wire identification labels on both ends of all wires
16 3 Spare Output 1 mmsq Red Pin Crimp

REV DATE REF CHANGE DESIGN


THE COPYRIGHT IN THIS DOCUMENT IS THE PROPERTY OF DATE: SCHEMATIC NUMBER: TITLE: Gemini 3 RTU (DSM/FPM) to RMU 10m
1 25/06/19 ... Electric
2 24/07/19 ECR 22749
Initial Release Based on AUT0003200
Spare O/P added
LUCY SWITCHGEAR (EMS) LTD, TRADING AS LUCY ELECTRIC
THE DOCUMENT IS SUPPLIED BY LUCY SWITCHGEAR (EMS) LTD
27/08/2019 AUT0003814 SHEET
to Flying Leads
9 TITLE: 9
3 27/08/19 ECR 22948 Correct conduit gland part no. ON THE EXPRESS TERMS THAT IT BE TREATED AS UNIT 14 THORPE LANE FILE
M14 Seal-top Bag . ../../.. .... ............ CONFIDENTAL, AND THAT IT MAY NOT BE COPIED, USED, THORPE WAY IND. EST. SHEET: NAME: AUT0003814_3 G3 UMBILICAL ADDC_ADWE
for labels . ../../.. .... ............ OR DISCLOSED FOR ANY OTHER PURPOSE THAN THAT BANBURY OX16 4UT
. ../../.. .... ............ WHICH IT IS SUPPLIED WITHOUT EXPRESS WRITTEN CONSENT. +44(0)1295 270448 1 of 1 BY: CHO REV: 3
A B C D E F G H J K
M
COMM V DC V

COMM V DC V

C
HMI GEMINI 3
PWR

Lucy Electric
PSM G3 DSM 1 G-3 DSM 2 G-3 MCM G-3
O PWR CAN PLUS PLUS
O PWR CAN O PWR CAN O PWR CAN

AC SUPPL LOCAL REMOTE O


LOGIC SUPPL IN IN
MOTOR SUPPL A IN A IN DUMM MODE AUTO
ATT CHARGER
IN 0 IN 0
ATT HEALTH
AN
M M
DC ID ID PWR O MENU
DC A A

US
IP IP

RS 3
V AU
DC IP IP
DC IN IN OPEN

DC OUTPUTS

DE UG
DC
SW A IN SW A IN
DC ACT
IN 3 IN 3 LOCAL
V AU
CLOSE REMOTE MODE
0V IN IN
V AU O

CON IG
IN IN NC3
0V

ETH
IN IN
V
IN IN DOOR SW

RTU DC S
COM

V DC
V OP M OP M
ATT

OP OP

0
0V
3

OP OP

V AU

RS 3 A
AN
OP OP

RS
T
NC3
TO MCM
DOOR SW

ATT
SW SW
ATT CT A CT A
COM

SCADA
ETH 0
HMI
N MH CT CT
ATTER PAC
V PSM
A AH
ATTER CONNECTOR DSM DSM MCM
POWER SUPPL MODULE PSM

N
LV DISTRI UTION
OARD AT RMU ROOM
L

REV DATE DESCRIPTION DWN CHK APP SIGN DATE


PRO ECT: DWG. TITLE:
RTU POWER SCHEME FOR 11KV
DWG. NO.:
LUC MIDDLE EAST E DISTRIBUTION SUBSTATIONS -ADDC RTU POWER SCHEMATIC
P.O. BOX: 17335, DUBAI, UNITED ARAB EMIRATES

TEL: +971-4 812 9999, FAX: +971-4 812 9900 . REV. : 0 SH.NO:3 SCALE : NTS
0 11.10.2020 RTU - AS BUILT DRAWING RK RK MA RK 11.10.2020 .
SHEET: A3
Distribution Substation Automation
Client : Abu Dhabi Distribution Company (ADDC)
Contract No. :
Distribution Substation :TRM / QRM

List of Components in RTU


SN Items QTY Remarks
1 MCM(Master Control Module) 1

2 PSM(Power Supply Module) 1

3 DSM(Dual Switch Module) 2

4 Battery Charger 1

5 Battery 1

Page 1 of 1
List Of Componenets REV.1
Contractor : National Projects & Contruction LLC 1 SLD

Over All SLD


Employer : ALDAR Projects 2

Country of Origin
Consultant : PARSONS 3

Signal List
Client : ADDC 4

Tele-Information Plan
SS : RMU Substations 5

6 Cable Overview List


Internal Project No:

Adaptation Design
Project Name : Madinat Al Riyadh City Ph-6A & 6B 7

8 I/O Connection Diagram

MATERIAL SUBMITTAL: DMS-RTU for RMU.Rev.01


9 RTU Functional Specification

10 RTU Detailed Design

11 RTU Method Statement

12 RTU FAT Procedure

13 RTU SAT Procedure

14 POINT TO POINT TEST PROCEDURE

15 Warranty Certificate
METHOD OF STATEMENT FOR RTU
INSTALLATION & COMMISSOING

Contract :

Contractor : LUCY MIDDLE EAST

Rev .0 Page 1
REVISION HISTORY

Version Date Edited Comments/Modifications

Rev.0 28/01/2018 RK Issued for Approval

Rev .0 Page 2
TABLE OF CONTENTS
1. PURPOSE

2. SAFETY

3. PRE-REQUISITES FOR EXECUTION OF WORKS

4. INSTALLATION & PRE-COMMISSOING PROCEDURE

5. SAT REPORT - RTU

Rev .0 Page 3
1. PURPOSE

The purpose of this document is to describe the work procedure for the installation of Lucy RTU
in ADDC substations after site survey is completed.

2. SAFETY

All standard ADEWA safety procedures shall be followed as per attached risk assessment.

3. PRE-REQUISITES FOR EXECUTION OF WORKS

The Installation works can be done before shutdown. Installation and commissioning for the substations are
to be arranged with the Operation & Planning Department and permit to be acquired accordingly. Permits
are to be taken from the field operational Engineer by a contractor at the substation.

4. INSTALLATION & PRE-COMMISSOING PROCEDURE

The site works for the substation shall start after the following steps.
1. Apply and obtain Permit to work/LAP without shutdown from ADDC
2. Ensure drawings and SAT sheets are available.
3. Open all terminals links in the Marshalling panel to isolate the DMS/RTU Related Connections in
RMU and Filed side.
4. Install RTU Panel on the Wall or floor stand based on site survey and approved location from
DEWA.
5. Check Local/Remote Switch on the RTU is switched to OFF position.
6. Install cable trucking as required based on the substation.
7. Connect the earthing cable between RTU outer box Earthing and the nearest earthing connection.
8. Plug in the umbilical cables in the RTU panel and make sure that they are not tensioned /bent.

Rev .0 Page 4
9. Gland the other side of umbilical cable to the RMUs Marshalling box and Field side.
10. Follow the connection schedule in SAT document to connect the wires into the Marshalling box
terminals.
11. Connect the incoming power supply cable from the nearest Socket.
12. Make sure PSU (power supply unit in RTU) switches are OFF, connect power supply cable from
socket to RTU power terminals.
13. Check the voltage.
14. Plug in the Battery connector to the PSU (Make sure Battery switches is OFF).
15. Turn RTU On by Switching the PSU Battery switch & PSU LV switch to ON.
16. Configure/Parameterize the RTU and perform SAT.
17. After SAT close all the terminals links in the Marshalling box and verify the online status of the
switches and breakers.
18. Perform the Point to Point test with DMS/SCADA.
19. Cancel the Permit.

5. SAT REPORT - RTU

All the tests performed and their results are to be recorded in the enclosed SAT report format and to be
signed by all concerned for record.

Rev .0 Page 5
HAZARD IDENTIFICATION, RISK ASSESSMENT AND RISK CONTROL

BEFORE AFTER
Consequences
Activity Hazard Cause of Hazard Recommended Control Measures
/ Impact
Risk Risk
Risk Rating Risk Evaluation
Level Level
Number Severity Likehood Risk H/M/L Number Severity Likehood Risk H/M/L
1 Manual lifting All workers Fall of person on Injury All workers to be informed and trained on the
Pulling or Pushing likely to use same level Property 1 4 1 4 M hazards associated with manual lifting and handling 1 4 1 4 M
manual effort at Fall of object on damage and to include the following :-
work same level
Protruding objects Determine if load can be better shifted by other
Manual handling / means (wheels, mechanical etc.).
lifting
Determine the proper route of lifting/carrying.

Clearing the route and prepare lifting and dropping


point levels.

Precautions to be taken against sharp objects and


obstacles.

Ensure proper grip, posture and movements are


adopted.

Observe correct lifting and manual handling


techniques.

Exercise to maintain fitness and combat physical


fatigue and injury.

Where necessary the correct use of PPE.


2 Lifting operation Crane toppling Position of crane Major injury Position of crane shall be on an even surface.
on loose surface Fatality 1 4 1 4 M 1 4 1 4 M
Instability of All outriggers shall be extended fully.
outriggers
The Soil has to be checked for rigidity before placing
the rigger.

Failure of lifting Not tested Major injury Planned lifting operation.


tackles / slings Excessive use Death 1 5 1 5 H 1 4 1 4 M
Damage Valid test certificate.

Regular visual inspection of slings,hooks & latches


to be carried out.

Page 1 of 3
HAZARD IDENTIFICATION, RISK ASSESSMENT AND RISK CONTROL

BEFORE AFTER
Consequences
Activity Hazard Cause of Hazard Recommended Control Measures
/ Impact
Risk Risk
Risk Rating Risk Evaluation
Level Level
Material falling Unplanned lifting Damage to Safety latch- frequent visual inspection
from height operation equipment 1 4 1 4 M 1 4 1 4 M
Failure of lifting Major injury Don't allow people to work directly below load being
tackles Death lifted or under suspended load.
Lack of
knowledge Manufacture's lifting instruction to be followed.

Lifting area to be cordoned off.

3 Movement of Heavy Inconvinience to Road accidents Injury NOC from appropriate authorities must be obtained
vehicles public Property damage Fatality 1 5 1 5 H where required. 1 4 1 4 M
Hindrance for
other motorist Install signs and barricades.

Banksman shall be provided.

Flashing lights to be provided during work at night.

Work area to be cordoned off.

4 Portable power tools Electric shock Defective tools Injury Insulated power tools.
Leaking electric Fatality 1 4 1 4 M 1 4 1 4 M
cable Regular visual inspection of the condition of wires.
Use in wet
condition

Hit by rotating Safety guard not Minor injury Proper guard.


objects available 1 4 1 4 M 1 4 1 4 M

5 Hand tools Hit by the sharp Improper method Minor injury Use hand gloves.
edges of the of work 1 3 1 3 L 1 3 1 3 L
tool Blunt edges

Slipping and Broken handles Injury Suitable tool for work.


falling of tool Cracked parts 1 3 1 3 L 1 3 1 3 L
Regular visual inspection.

Careful Handling of Tools.

Page 2 of 3
HAZARD IDENTIFICATION, RISK ASSESSMENT AND RISK CONTROL

BEFORE AFTER
Consequences
Activity Hazard Cause of Hazard Recommended Control Measures
/ Impact
Risk Risk
Risk Rating Risk Evaluation
Level Level
6 Tesing of equipment Electric shock Testing Major injury All testing equipment should be earthed
equipment not Fatality 1 5 1 5 H 1 3 1 3 L
earthed The Supply wire has to be checked visually for
damage in the insulation.

Electric shock HV hand gloves Major injury HV hand gloves to be used during high voltage
not provided Fatality 1 5 1 5 H testing. 1 4 1 4 M

Electric shock Working in the Major injury No one should be allowed to work near or in the
testing area Fatality 1 4 1 4 M testing area. 1 4 1 4 M

Testing area shall be cordoned off.

Proper signs to be provided for keeping away


unauthorized persons.
Electric shock Damaged, Major injury All testing equipment including HV test kit shall have
Incalibrated Burn 1 5 1 5 H valid calibration certificate. 1 4 1 4 M
testing equipment Fatality
Regular visual inspection.

Use of proper cables.

The Testing Instrument and the Testing Equipment


has to be earthed.

Page 3 of 3
Contractor : National Projects & Contruction LLC 1 SLD

Over All SLD


Employer : ALDAR Projects 2

Country of Origin
Consultant : PARSONS 3

Signal List
Client : ADDC 4

Tele-Information Plan
SS : RMU Substations 5

6 Cable Overview List


Internal Project No:

Adaptation Design
Project Name : Madinat Al Riyadh City Ph-6A & 6B 7

8 I/O Connection Diagram

MATERIAL SUBMITTAL: DMS-RTU for RMU.Rev.01


9 RTU Functional Specification

10 RTU Detailed Design

11 RTU Method Statement

12 RTU FAT Procedure

13 RTU SAT Procedure

14 POINT TO POINT TEST PROCEDURE

15 Warranty Certificate
XML Report Page 1 of 14

UUT Report
vidt°
Station ID G3PROD-RTU5
Serial Number G3-07-AUT0002224-02-30020140.-
Date 09 October 2018
Time 12:11:25
Operator Sonar_G
Execution Time 766.2 seconds
Number of Results 218
OUT Result Passed

Begin Sequence: MaInSequence


C \ sw cies \ G3RTUTestRigybequenceSdaul "U"
Limits
Low High
Comparison Type
Step Status Measurement Units Limit Limit
Get MCM Barcode (Password Done
extracted later)
ButtonHit:
Response: G3-05-AUT00011.62-02 002977 MAC: 00 OC:C6:82:07:00-01

PIM Barcode to Password Done

Limits
Low High
Comparison Type
Steil Status Measurement Units Limit Limit

Earth Bonding .-- Passed

egln Sequence: Earth Bonen° Tests


C:\SwRea WaRTLITeStillQ \ sequences vtulanna
Limits
Low High
Comparison Type
Step Status Measurement Units Limit Limit

Connect Earth Cable to Cabinet


Outer Earth Stud. Connect AC to Passed __
terminal blocks
Connect Tester Earth cable to outer
Passed -
Earth Stud on RTU cabinet

< 0,1 Ohm Passed

< 0.1 Ohm Passed l.-

< 0,1 Ohm Passed

< 0.1 Ohm Passed —

c 0.1 Ohm Passed

End Sequer'ce Earth Bonding re ts

Limits
Low High
Comparison Type
Step Status Measurement Units Limit Limit

MiSC Checks Passed ..-

Begin Sequence: Miss Checks


ncesAUTOOO2224
Limits
Low
High Comparison type
Step Status Measurement Units Limit Limit
Check PSU is selected for 230VAC
Passed
+ sticker attached
Spare Fuses are Fitted Inside the
Passed
Door with Correct Ratings

file://uk-thm-san103v.wlucynet.com/sharedhome_01/Automation-P/RootFolder/05_R... 10/14/2018
XML Report Page 2 of 14 •

Module ID left to right: NM, DSM


Passed
(1) DSM(2) MOM 8, HMI

Connect Battery Test Cable to RTU. Passed

Turn ON the Main and Battery


Passed I
Power Switches.

Turn on COMMS MOB Passed f


Jr
Connect ETH-0, ETH-1 and DEBUG
Passed
Cables to MOM,

End Sequence: Misc Checks

Limits
Low High
Comparison Type
Step Status Measurement Units Limit Limit

Visual Checks Passed

Begin Sequence: Visual Checks


Ci sw dev G3RTUTestRi Se u nces AUT0002224.se
Limits
Low High
Comparison Type
Step Status Measurement Units Limit Limit
Connect switch cables 1-4 to TBs
1-100 Connect CT test cable to Cr Passed
TBs. C
Connect 4-20mA test cable to 4-
20m4 Tes Connect 24V test cable Passed 7'
to 241/ TBs.

Check RTU for scratches and swarf Passed /

Rating plated fitted to outside of


cabinet, serial number label fitted passed /
to inside of door

All looms securely fitted Passed (

Connectors plugged in securely Passed /

Gland plate, cable glands and 1


blanking 'plugs have gaskets flitted. passed /
Cable glands have sealing discs
fitted. :

galleries fitted and strapped down Passed I


Cover fitted to auxiliary IEC passed i
connecter on PSU
Check backplane, PSU, battery
mounting, door switch and HMI are Passed
mounted securely I
Verify comms device plate has DIN (
Passed
rail fitted
MOM RS485 connector fitted with
Passed I
mating 5 Way connector
Correct with reference to assembly !
Passed (
drawing
MOM OFF LEO lit MCMREMOTE LEO
Passed
lit MCM LOCAL LED lit

12V +/-0.iV Passed


(

End Sequence: Visual Checks

1 Limits
Low High
Comparison Type
Step Status Measurement Units Limit Limit

Check Heater Passed u--

Begin Sequence: Check Heater


Ci \ sw dev \ G3RTUTestlitig \sequences nu rimucc
Limits
Low High
Comparison Type
Step Status Measurement Units Limit Limit

Power meter reads 20W+/-5W Passed n

passed I
Power meter reads 70W+/-20W
and Slowly decreases HUMidistat

fi1e://uk-thrn-san103v.w1ucynet.com/sharedhome_01/Automation-P/RootFolder/05 R... 10/14/2018


XML Report Page 3 of 14

LED lights
Power meter reads 20W+/-5W.
Passed ..-.
HumMistat LED goes off
Power meter reads 20W+/-5W. Passed
Flumidistat LED goes off
Passed s-
Power meter reads 20W+/-5W

nd Sequence: check Heater

Limits
Low High Comparison Type
Step Status Measurement Units Limit Limit
Record serial numbers of modules,
P5U, battery sensor using Passed
G3MOchileAssemblyTOO1 application ..--

Enable HAT mode Passed r

Enable CT test on switch A only Done m

DSMJA Passed -(r.l

Number of Loops:
Number of Passes:
Number of Failures: 0
Final Loop Index:

D5M_IA (Loop Indices)

D5M_IA (Loop Older: 0) Passed


.....,- I

Begin Sequence: MainSequence


CRew
Limits
Low nigh Comparison Type
Step Status Measurement Units Limit Limit

Indicator Test (Sw A) Passed er

Begin Sequence: _Test Indicators


C: sw
Limits
Low
High Comparison Type
Step Status Measurement Units Limit Limit
Testing
Passed
10_10_SW_A_CLOSED_INPUT
r
Testing 10_1D_SW_A_OPEN_INPUT Passed

Testing .-
Passed
10_10_SW_A_INDICATION_I —
Testing Passed
10_10_5W_AJNDICATION_2
Testing passed
10 ID SW A 1NDICATION_3
Testing e-
Passed
10 ID SW A INDICATION_C
,
Testing
Passed
10_1D_SW_A_INDICATION_5
2
Testing
Passed
10_1D_SW_A_INDICATION_6 it-
Testing i
Passed .7
10_1D_SW_A_INDICATIONS ,
Testing
Passed I
10 M SW A INDICATION _8
Testing i
Passed
10_10_SW_A_INDICATION_9
Testing
10_1D_SW_A_INDICATIONJO
Passed '17

End Sequence: _Test Indicators

Limits
Low High
Comparison Type
Step Status Measurement Units Limit Limit

Motor Power On (Sw A) Passed sds

file://uk-thm-san103v.wlueynet.com/sharedhome_01/Automation-P/RootFolder/05_R... 10/14/2018
XML Report Page 4 of 14 .

Begin Severna: sub_NotorPower_On Test


CIken dev‘d3RTUTestglg Sequences \ DSMMIC2 T SW A. seq
Urn Es
Low Mph I
Step Status Measurement nita Limit Comparison Type
Limit
Check Motor Power SW1/3 Passed estiU
23.5 le 22 24 GELE(a. c.)

End Sequence: Sub_taotorPower_On Test

Umila
Low Nigh Corn dean Type
Step Status Measurement Units Limit Limit

Test Open CND (Sw A) Passed

Begin Sequence: Test Open CND


aw der G3RTUTerta uences DSMMIt2 T SW A.
Limits
Low High
Comparison Type
Step Status Measurement Units Limit Unlit
Check. Default Voltage Passed 11.70 V 11 13 GELE(sa de)
Check OpenCMD e Low V Passed 0.0662 V CELE( sa 0)
CELE( s.. C.)
Check Default Voltage Passed 11.70 V 11 13
‘0,
Ole& SW A OpenCelD • High V Passed 23.39 V 23 25 GELE(>. <e)

End Sequence: Test Open CND

Limits
Law High
Comparison Type
Step Status Measurement Units Limit Limit

Test Close DID (5w A) Passed

Begin Sequence: Test Close CMD


uences OSNIIK2 T SW A.
Limits
Wet 14101. comparison TYPe
Step Status Measurement Units Limit Um!!
Check Default Voltage (SW A) Passed 11.73 V 11 13 CELE(' e C-)
Cheek SW A ClosedCMD e Low V Passed 0.0662 V -1 1 G51.5(>. <-)
Check SW A Default Voltage Passed 11.72 V 11 13 GELE(7 • C-)
Check SIVA ClosedCMD a High V Passed 23.38 V 23 25 GELE(k. d')

End Sequence: Test an. CMD

Limits
Low Nigh
Compadson Type
Step Status Measurement Unita Limit limit

Test Output I (SW A) Passed

Begin Sequence: Test Mal

Limits

I-Hw High Comparison Type


Step Status Measurement Units Limit limit
Check SW A Output-1 Default Passed 0.005133 V 0.5 Gni (>. 0)
Voltage
Check SWA Otitput_l e High V Panel, 24.03 V 23.5 24.5 GELE(>. cm)

End Sequence: Test Outl

limits
Low 111011 Comparison Type
Step Status Measurement Units Limit Limit

Motor Pear OFF (Sw A) Passed

file://u1c-thm-san103v.wlucynet.com/sharedhome_01/Automation-P/RootFolder/05_R... 10/14/2018
, XML Report Page 5 of 14

Begin Sequence: Sub_MotorPower_OFF Test


C•Ww detAG3RTUTestRiq \ Sequences \ LISMMK2 Test SW A.saq
Limits
Low High
Comparison Type
Step Status Measurement Units Limit Limit
Check Motor Power SW1/3 OFF Passed -0.002747 V GELEf>e <T)

End Sequence: Sub_MotorPower_OFF Test

Limits
Low High
Comparison Type
Step Status Measurement Units Limit Limit

CT Tests (Sw A) Passed

Begin Sequence: Sub_CT Tests


sw des G3RTUTestIll Se uences 13SMMIC2 Tes Sw A.
Limits
Low High
Comparison Type
Step Status Measurement Units Limit Limit

If (True/ Done

End If Done

Check SW_A CT and DSM current measurements Passed 997.4 mA 982.4 1023 GELE(>= <=)
CT Measurement: 1002
DSM Measurement percentage from recorded CT value i 99.5
Check SW_A CT and DSM current measurements Passed 1996 mA 1967 2047 GELEC>a 4 =7
Cr Measurement: 2007
DSM Measurement percentage from recorded CT value : 99.08

nd Sequence: Sub_CT Tests

Limits

Comparison Type
Step Status Measurement Units 1.1

mwit LHim
igiht

Test 4-20mA inputs Passed

Begin Sequence: Test 0-20mA


sw_devG3RTUTestRin Seuu ncesDSM
Limits
Low High
Comparison Type
Step Status Measurement Units Limit Limit

Check 4-20mA 1 Passed 10.91 10.8 11.2 GTLT(> 4)

Check 4-20mA 2 Passed 10.89 10.8 11.2 GTLT(> 4)

Check ISO 24V Passed 20.86 15 25 GELE(>4- <A)

nd Segue ce: Test 4-20mA

End Sequence: MeinSequence

Limits
Low High
Step Comparison Type
Status Measurement Units Limit Limit
Enable CT test on switch A only Done

DSM_111 Passed

Number of Loops:
Number of Passes:
Number of Failures: 0
Final Loop Index:

Dew_10 (Loop Indices)

DSM_1B (Loop Index: 0) Passed

file://uk-thm-san103v.wlucynet.com/sharedhome_01/Automation-P/RootFolder/05_R... 10/14/2018
XML Report Page 6 of 14

Begin Sequence: MainSequence


C: sw DSMMK2 TestSW B
Limits
Low High u_
Comparison Type
Step Status Measurement Units Limit Limit

Indicator Test (Sw B) Passed

Begin Sequence: _Test Indicators


sw det G3RTUTestRI Se uences DSMMI(2 Te5CSW B.s
Limits
Low High
Step Status Measurement Units Limit Limit giiiiiigari"" irgge
Reset DSM1 DIO Done

Reset DSM2 DIO Done

Limits
Low High
Comparison Type
Step Status Measurement Units Limit Limit
Testing
Passed
10_1D_SW_B_CLOSE9LINPUT

Testing 10_10_SW_B_OPEN_INPUT Passed

Testing
Passed
10_1D_SW_B_INDICATIONtl
Testing
Passed
10_ID_SW_B_INDICATION_2
Testing
Passed
103D_SW_B_INDICATIONt3
Testing
Passed
10_ID_SW_B_INDICATION _4
Testing
Passed
10_10_SW_B_INDICATION_5
Testing
Passed
10_ID_SW_B_INDICATION_6
Testing
Passed
10_ID_SW_B_INDICATION _7
Testing
Pa d
10JD_SW_B_INDICATIONfi
Testing
Passed
103D_SW_B_INDICATION_9
Testing
Passed
10_1D_SW_B_INDICATIONJO

End Se uence: Test Indicators

Limits
Low High
Comparison
Step Status Measurement Units Limit Limit o ggge

Motor Power On (Sw B) Passed

Begin Sequence: Sub_MatorPower_On Test


C:\sw_dev GERTUTestRIg \ Sequences \ OSMMI(2 Test_SW B s
Limits
Low High
Comparison Type
Step Statue Measurement Units Limit Limit

Check Motor Power SW2/4 Passed 23.56 V I 22 20 GELE(>4 4.)

End Sequence Sub_MotorPower_On Test

Limits

Logi High Comparison Type


Step Status Measurement Units Limit Limit

Test Open CMD (Svc B) Passed

Begin Sequence: Test Open CMD


C:Ww deiNG3RTUTestRig \ Sequ nem DSMMK2 Test_SW B.seq
Limits
I I II I

file://uk-thm-san103v.w1ucynet.com/sharedh0me 01/Automation-P/RootFolder/O5_R... 10/14/2018


. XML Report Page 7 of 14

Low High Comparison type


Step Status Measurement Units Limit Limit

Check SWB Default voltage (Open) Passed 11.74 V 11 13 GELE(>= <-)

Passed 0.06817 V GELF(p.= <-)


Check OpenCMD = Low V
Check SW B Default Voltage 11.73 V 11 13 GELE(5.= .2.2-)
Passed
(Open)
Check SW B OpenCMD = High V Passed 23.38 V 23 25 GELE(e= <=)

End Sequence Test Open CHO

Limits
Low HMIs
- Comparison type
Step Status Measurement Units Limit Limit

Test Close CMD (Sw B) Passed

Begin Sequence: Test Close CHO



Limits
Low High
Comparison type
Step Status Measurement Unns Limit Limit
Check Default Voltage (SW B) Passed 11.74 V 11 13 CELE> = <-7

Check SW B ClosedCMD = Low V Passed 0.0593 V GELE(e= <=)

Check SW A Default Voltage Passed 11.74 V 11 13 GELE(9= <e)

Check SW 8 ClosedCMD = High V Passed 23.38 V 23 25 GETE(>= <=)

End Sequence: Test Close CMD

LIMOS
LOW High
Comparison Type
Step Status Measurement Units Limit Limit

Test Output 1 (Sw B) Passed

Begin Sequence Test Outl


B se
Limits
Low Hig
h Comparison Type
Step Status Measurement Units Limit Limit
Check SW B Output_1 Default 0002178 V -0.5 0.5 GELE(>= <e)
Passed
Voltage
Check SW B Output_l = High V Passed 23.84 V 23.5 24.5 GELE(>- <=-)

End Sequence: Test Outl

Limits
Low
High Comparison Type
Step Status Measurement UMW Limit Limit

Motor Power OFF (Sw B) Passed

Begin Sequence: Sub_MotorPower_OFF Test


C:Ww_dey \ GORTUTestRig \ Sequences \ DS101K2 Test_SW B.seq
Lim tS
Low High
Omparlson Type
Step Status Measurement Units Limit Limit
Check Motor Power SW1/3 OFF Passed 0.0002082 GELE(>= <-)

End Sequence: Sub MotorPower_OFF Test

End Sequence: MainSequence

Limits
Low High
Comparison Type
Step Status Measurement Units Limit Limit

DSM_PA Passed

Number of Loops:
Number of Passes:

file://uk-thm-san103v.wlucynet.com/sharedhome_01/Automation-P/RootFolder/05_R... 10/14/2018
XML Report Page 8 of 14

Number of Failures: 0
Final Loop Index:

DSM_2A (Loop Indices)

OSM_PA (Loop Index: 0) Passed


I

Begin Sequence: MainSequence


sw dev 03RTUTestRi Se u nces DSMP4K2 Tes SW As
Limits
Low High
Comparison Type
Step Status Measurement Units Limit Limit

Else Done

Limits
Low High r
Step Status Measurement Units Limit Limit ahhhariscm Type

Indicator Test (Sw A) Passed

Begin Sequence: _Test Indicators


C:\sw
Limits
Low High _
Step Status Measurement Units Limit Limit L"hari"" Type
Testing I Passed
10_ID_SW_A_GLOSED_INPUT

Testing 10_1D_SW_A_OPEN_INPUT Passed

Testing
Passed
10_ID_SW A INDICATION_I.
Testing
PAssed
10_1D_SW_A_INDICATION_2
Testing
Passed
10_1D_SW_A_INDICATION_3
Testing
Passed
10_ID_SW_A_INDIGATION_4
Testing
Passed
10_1D_SW_A_INDICATION_5
Testing
Passed
103D_SW_A_INDICATION_6
Testing
Passed
10_ID_SW_A_INDICATION_7
Testing
Passed
10_ID_SW_A_INDIGATION_8
Testing
Passed
10_1D_SW_A_INDICATION_9
Testing
Passed
10_1D_SW_A_INDICATION_10

End Sequence: _Test Indicators

Limns

Step Status Measurement Units Litw


it L
ilim
giht Chinhalihmi Type

Motor Power On (Sw A) Passed

Begin Sequence: Sub_Moto Power_On Test


.l.vflRTUTntRin Span ncesOSMMK2 Test SW A
Limits
Low High
Comparison Type
Step Status Measurement Units Limit Limit

Check Motor Power SW1/3 Passed 23.49 V 22 24 GELE(>- <-) Vt

nd Sequence: Sub_MotorPower_On To

Limits
Low High
Compadson Type
Step Status Measurement Units Umit Limit

Test Open CMD (Sw A) Passed

file://uk-thm-san103v.w1ueynet.com/sharedh0me_01/Automation-P/RootFolder/05 R... 10/14/2018


XML Report Page 9 of 14

Begin Sequence: Test Open CM


C• \ sw dev \ G3RTUTestitig \ Sequ nces OSIIMK2 Test_sw A.seq
Limits
Low Hint
- Comparison Type
Step Status Measurement Units Limit Limit

Check Default Voltage Passed 11.84 V 11 13 GELE(>= 4-)


Check OpencIND = Low V Passed 0.05718 V GELE(w= <-)
Check Default Voltage Passed 11.83 V 11 13 GELE(6= 4=1

Check SW A opencm0 - High V Passed 23.54 V 23 25 GELE(>- 4-)

End Sequence Test Open CMD

Limits
Low
High Comparison Type
Step Status Measurement Units Limit Limit

Test Close CMD (Sw A) Passed

Begin Sequence: Test Close CMD


Test SW A s
Limits
Low High Comparison Type
Step Status Measurement Units Limit Limit

Check Default Voltage (SW A) Passed 11.74 V 11 13 GELE(7.= <=)


Check SW A ClosedCMD = Low V Passed 0.0662 V GELE(9= ca)

Check SW A Default Voltage Passed 11.74 V 11 13 GELE(s= <=)

Check SWA ClosedCMD = High V Passed 23.39 V 23 25 GELE(Pi= 4-)

End Sequence: Test Close CMD

Limits
Low High
Comparison Type
Step Status Measurement Units Limit Limit

Test Output 1 (Sw A) Passed

Begin Sequence: Test Out1


v RT Te Ri Se uences DSMME2 Tes SW As
Limits
Low High Comparison Type
Step Status Measurement Units Limit Limit

Check SW A Output_1 Default 0.5


Passed 0.0002082 V GELE()- <-7
Voltage
Check SWA Output_1.- High V Passed 23.83 V 23.5 24.5 GELE(>- <-)

nd Sequence: Test Out1

Limits
Low High
Comparison Type
Step Status Measurement Units Limit Limit

Motor Power OFF (Sw A) Passed

Begin Sequence: Sub_MotorPower_OFF Test


C: \ sw dev G3RTI/TestRig \ sequences \ DSMMK2 Test SW A.seq
Limits

Low High
Comparison Type
Step Status Measurement Units Limit Limit

Check Motor Power SW1/3 OFF Passed -0.003731 V GELE(> - 4-)

End Sequence: Sub_MetorPower_OFF Test

End Sequence: MainSequence

Limits
Law High
Comparison Type
Step Status Measurement Units Limit Limit

file://uk-thm-san103v.wlueynet.corn/sharedhome_01/Automation-P/RootFolder/05 R... 10/14/2018


XML Report Page 10 of 14

DSM_2B Passed I
I I I I
Number of Loops:
Number of Passes:
Number of Failures: 0
Final Loop Index:

DSM_211 (Loop Indices)

DSM_213 (Loop Index: 0) Passed

Begin equence: MainSequence


\ sw
Limits
I Low High
Comparison Type
I Step Status Measurement Units Limit Limit

Indicator test (Sw B) Passed

Begin Sequence: _Test Indicators


2 TCSLSW B
Urn its
Low High c •
comparison
Step Status Measurement Units Limit Limit Type

Reset DSM1D10 Done

Reset DSM2 DIO Done

Limits
Low High
Comparison Type
Step Status Measurement Units Limit Limit
Testing
Passed
10_1D_SW_B_CLOSED_INPUT

Testing 10_1D_SW_B_OPEN_IN1111T Passed

Testing
PBSSed
10_1D_SW_EUNDICATION_1
Testing
Passed
10_ID_SW_B_INDICATION_2
Testing Passed
I0_ID_SW_B_INDICATION_3
Testing
PaSSed
10_ID_SW_B_INDICATION_4
Testing Passed
10_ID_SW_B_INDICATION_S
Testing
Passed
10_10_SW_B_INDICATION_6
Testing
Passed
10_ID_SW_B_INDICATIONJ
Testing
Passed
10_1D_SW_B_INDICAllON_S
Testing Passed
10_10_SW_B_INDICATION_9
Testing Passed
10_1D_SW_B_INDICAllON_10

End Sequence: _Test Indicators

, Limits
I Low High
Comparison Type
1 Step Status Measurement Units Limit Limit

Motor Power On (Sw B) Passed

Begin Sequence: Sub_MotorPower_On T st


C: \ sw dev \ G3RTUTestRig \ Sequences \ DSMMIO Te SW Lam
Urnits
Low High
Comparison Type
Status Measurement Units Limit Limit
Step
Passed 23491V 22 20 GELE(>4 <a)
Check Motor Power SW2/4

End Sequence: Sub_MotorPower_On Test

file://uk-thm-san103v.wlucynet.com/sharedhome_01/Automation-P/RootFolder/05_R. 10/14/2018
XML Report Page 11 of 14

Limits
Low High
Comparison Type
Step Status Measurement Units Limit Limit

Test Open CMD (Sw B) Passed

Begin Sequence: Test Open 041)


D MHZ Tes SW Bee
Limits
Low High
- Comparison Type
Step Status Measurement Units Limit Limit
Check SWB Default Voltage (Open) Passed 1174 V 11 13 GELE(>A <A)
Check OpenCMD - Low V Passed 006915 V GELE(>= is-)
Check SW B Default Voltage GELE(>- <m)
Passed 11.73 V 11 13
(Open)
Check SW B OpenCMD A High V Passed 23.37 V 23 25 CELE( >o <°)

End Sequence: Test Open Ott/

Limits
Low High
Comparison Type
Step Status Measurement Units Limit Limit

Test Close CMD (Sw B) Passed

Begin Sequence: Test Close CMD


C: Sw des O3RTUTestill S uences DSMMK2 Tes SW Use
Limits
Low High
Comparison Type
Step Status Measurement Units Limit Limit
Check Default Voltage (SW B) Passed 11.73 V 11 13 GELE(>A <A) SW-
Check SW B ClosedOMD = Low V Passed 0.06127 V GELE(>- <A) too'

Check SW A Default Voltage Passed 11.72 V 11 13 GELE(>4 <..)


Check SW B ClosedCMD = High V Passed 23.38 V 23 25 GELE(s-- <-) ••••9-

End Sequence: Test Close CMD

Limits
Low High
Comparison Type
Step Status Measurement Urals Limit Limit

Test Output 1 (Sw B) Passed

Begin Sequence: Test Doti


sw dev G3RTUTestRI Se uences DSMMK2 Tes SW B.
Limits
Low High
Comparison Type
Step Status Measurement Units Limit Limit
Check SW B Output_1 Default
Passed 0.001193 V -0.5 0.5 GELE(.5.= <-)
Voltage
Check SW B Output_1 - High V Passed 23.83 V 23.5 24.5 GELE(>= <=.)

End Sequence: Test Outt

Limits
Low High
Comparison Type
Step Status Measurement Units Umit Limit

Motor Power OFF (Sw B) Passed

Begin Sequence: Sub_MotorPower_OFF Test

Limits
Low High
Status Measurement Units Comparison Type
Step Limit Limit
Check Motor Power 5 W113 OFF Passed 0.003153 V GELE(>. < 4-)

ad Sequence: Sub_MotorPower_OFF Te t

1
file://uk-thm-san103v.wlucynet.com/sharedhome 01/Automation-P/RootFolder/05_R... 10/14/2018
XML Report Page 12 of 14 •

End Sequence: MainSeqtience

Limits
Low
High ComparisonType
Step Status Measurement Units Limit Limit
NM Passed
Number of Loops:
Number of Passes:
Number of Failures: 0
Final Loop Index:

NM (Loop Indices)
PSM (Loop Index: 0) Passed

Begin 5 quence: MainSequence


C:
Limits
Low High
Step Status Measurement Units Limit Limit gginggri""Tyge

Test No Load Battery Voltage Passed 0.01892 V 1NEON

Test No Load Battery Current Passed 0 A 0.1 LT(4)


Set BAT CHARGER_VOLT_SET =- Done
127

Limits
Low High comparison type
Step Status Measurement Units Limit Limit gge
Test Load Battery Voltage Passed 24.08 V 23 25 GELEI> <-7

I Limits
Low High
Limit Limit Comparison Type
Step Status Measurement Units
Set BAT CHARGER_VOLT_SET = pane
30
Test PSM Battery Sense Voltage passed 30.15 V 29.13 31.56 GELN>i- <-7
Measurement 1
cDAQ VSense Value: 30.34
VSense Measurement Error: 99.38
Set BAT_CHARGER_YOLT_SET = cane
240
Test PSM Battery Sense Voltage passed 19.43 V 18.67 20.23 GELE(A- <=)
Measurement 2
cDAQ VSense Value: 19.45
VSense Measurement Error: 99.9
Set BAT_CHARGER_VOLT_SET -T pane
100
Test NM Battery Sens Voltage Passed 2544 V 24.54 26.58 GELEI>.= 4=7
Measurement 3
cDAQ VSense Value: 25.56
VSense Measurement Error : 99.54
Passive Battery Load Test Passed 1.83 A 1.5 3.5 GELE(> e=) z
Limits
Low High Comparison Type
Step Status Measurement Units Limit Limit

Check DC Current within Bounds Passed 346.2 mA 760 LT(4)

Battery Temp Test Passed 28.13 5 45 GELE(>iii <=)

PSU Teo* Test Passed i 38.25 10 60 GELE(>= <-)

AC Status Test Passed 1 1 EQ(—)

End Sequence: MainSequence

Limits
Low Mali Comparison Type
-
Status Measurement Unite Limit Limit
Step

file://uk-thm-san103v.wlucynet.com/sharedhome_01/Automation-P/RootFolder/05_R... 10/14/2018
. XML Report Page 13 of 14

1Load Customer Software 1"s"' I

Begin Sequence: Load Customer Software


224.se
Limits
Low High
Comparison Type
Step Status Measurement Units Limit Limit

Reprogram MCM with new file Done


system

Load Customer Software Done

ExitCocie: 0

End Sequence: Load Customer Software

Limits
Low High
- Comparison Type
Step Status Measurement Units Limit Limit

HMI and Door Switch Tests Passed

Begin Sequence: HMI and Door Switch T sis


'sw devG3RTUTestRin\SeauencesAUTOOO2224
Limits
Low High
Comparison Type
Step Status Measurement Units Limit Limit

HMI Display shows correct menu


Passed
HMI Display shows correct menu
HMI Display shows correct menu passed
HMI Display shows correct menu
Displayed text Scrolls to left
Displayed text scrolls to right
Passed
Displayed text scrolls up Displayed
text scrolls down
Return to Info menu Return to
Passed
main menu
Display shows an extending
dashed line Display shows an Passed
extending dashed line
HMI, cabinet light and module
LEDs extinguish HMI and module Passed
LEDs light
PSM BAIT HEALTH LED lights
Passed
Green RTU continues to operate

End Sequence: HMI and Door Switch Tests

Limits
Low High
Comparison Type
Step Status Measurement Units Limit Limit

Disconnect RTU Passed

Begin Sequence: Disconnect RTU


C:\sw _devG3RTUTestRinSeciu nces AUT0002224 Se
Limits
Low High
Compadson Tape
Step Status Measurement Units Limit Limit
Disconnect battery, mains and
network cables Connect internal Passed
IEC cable
Disconnect all cables from terminal
Passed
blocks

Close and lock door Passed

End Sequence: Disconnect RTU

End Sequence: MainSequence

End UUT Report

file://uk-thm-san103v.wlueynet.com/sharedhome 01/Automation-P/RootFolder/05_R... 10/14/2018


XML Report Page 14 of 14

file://uk-thm-san103v.wlueynet.com/sharedhome_01/Automation-P/RootFolder/05_R... 10/14/2018
, DO'cu.ment Title 03 RTU PSU Test Procedure
: Document No. BAN-GEN-PRO-I-
Electric
' Reference Document
' Issue No. 1 Date 09/10/2018 Page 5 of 5
i'

G3 PSU TEST RESULT SHEET


PSU Model # A1JT0003272 Serial # G3-07-AUT0003272-01- iglao053 d oi ,
Date 6,1 i i ,, 1 ig Initials n VG SB PG GS

Multi-meter if AEG-302 Flash Tester # AEG-301 Earth Bond


Tester #

Test
1 RTU power, Input and Serial number labels fitted.
3.15A fuses fitted.
RTU Power switches correct orientation.
‘(---
Wring correct and secure.
Transformer tightened to 6Nm.

Power supply tightened to 1Nm.


Earth stud tightened to 2Nm. %----
1

2 Earth bonding test pass (4 6,/ -0-) 1.-----


3 Flash test pass.
(ci 2 2.2 /e1) \ - - - p -SS
4 115V--; input
Auxiliary output test box LED on. N.-----
Multi-meter reads +36V (+I- 0.5V). 3 6. a
5 230V- input
Auxiliary output test box LED on. L..----
Multi-meter reads +36V (+/- 0.5V). 3 t , I Int
6 230V- label and auxiliary output blanking plug fitted. ‘....---

4.0 Relevant Records

The assembly BOM and drawings reside in Teamcenter under the respective RTU part number.

5.0 Change His ory

Date Created Issue Reason for Change


09/10/2018 1 First draft

PREPARED BY: m qreruswau APPROVED BY: s molt DATE: 09/10/18

Please ensure you are using the latest issue of this document by referring to the Documents Master List
Contractor : National Projects & Contruction LLC 1 SLD

Over All SLD


Employer : ALDAR Projects 2

Country of Origin
Consultant : PARSONS 3

Signal List
Client : ADDC 4

Tele-Information Plan
SS : RMU Substations 5

6 Cable Overview List


Internal Project No:

Adaptation Design
Project Name : Madinat Al Riyadh City Ph-6A & 6B 7

8 I/O Connection Diagram

MATERIAL SUBMITTAL: DMS-RTU for RMU.Rev.01


9 RTU Functional Specification

10 RTU Detailed Design

11 RTU Method Statement

12 RTU FAT Procedure

13 RTU SAT Procedure

14 POINT TO POINT TEST PROCEDURE

15 Warranty Certificate
RTU SAT Test Book

Installation Inspection Check List

For

Lucy RMU Substation

SUBSTATION NAME: _________ ___________

SAT-RTU 1 of 19
Revision History

Version Date Edited Comments/Modifications

Issued for Approval


SAT_0 23/9/2019 RK

SAT-RTU 2 of 19
The following visual check is to be carried out as General Installation
Inspection for the DMS Substation equipments provided as part of
the DMS adaption and RTU works.

1. Check the position and installation of following Equipments, as


applicable. The layout is attached to the test record.

Equipment Name Checks Remarks


RTU Cabinet – YY01 O.K
MCB Box – YH01 O.K

2. Check the Cable trays and trunking between the DMS IFC and
RTU for proper installation. O.K

3. Check the Cabling for the LVAC supply to the RTU for O.K
proper installation.

4. Check the Labelling of various DMS equipment and O.K


Associated cabling in ACDB, MCB, RTU and DMS IFC.

5. Check the earthing of RTU for proper connection to station O.K


earth.

SAT-RTU 3 of 19
Record of Remarks

In the summary list, items shall be entered that have been tested, but the
test result is not in line with the SAT test document.

Item Description Code Action Date

The below signature confirms that the test results were within the
specified boundaries and that no relevant errors were found.

Signature: Signature: Signature: Date:

(LUCY) (ADDC) (ADDC)

SAT-RTU 4 of 19
SAT Test Book

For Lucy RTU

RMU Substation

_____________ _____________

SAT-RTU 5 of 19
Table of Contents

1 Introduction……………………………………..…………. ...…...7
1.1 RTU Testing/Commissioning Definitions………….……….........7
1.1.1 Aims of the RTU SAT…………………………………….…...7
1.1.2 Fundamentals of the Test……………………………….……...7
1.1.3 RTU Site Acceptance Test…………………………………….8
1.1.4 Test Equipments……………………………………………….8
1.1.5 Recording of Tests…………………………………….……….8
1.1.6 Associated Test Documentation……………………….……….9
1.2 Test Details………………………………………….…….......10
1.2.1 RTU Signal Test Procedure…………………………….…….10

2 RTU SAT Test sheets…………………………………………….11


2.1 RTU Module Configuration Checks……………………………11
2.2 RTU Cubicle………………………………………….………...11
2.3 Time Synchronization………………………………......………12
2.4 RTU Software/Parameter Versions…………………………….13
2.5 Status indications at the RTU Module……………………….....13
2.6 Normal operation from Local Control panel including Hit & Run
Function………………………………………………………..14
2.7 Record of Remarks……………………………..………………..15

Appendix 1 : RTU SAT Analogue Measurements Test Sheets

Appendix 2 : RTU 1/O Connection Schedule

Appendix 3 : Cables Overview

SAT-RTU 6 of 19
1 Introduction

The following are the step-by-step procedure involved in testing and


commissioning the RTU signals from the SCADA terminals to checking
the IEC messages up to the RTU output to the communication interface.

1.1 RTU Testing/Commissioning Definitions

1.1.1 Aims of the RTU SAT

The purpose of this document is to describe the test procedures to be


carried out to provide sufficient evidence of correct configuration, testing
and commissioning of the Remote Terminal Unit.

The Tests shall be performed by Lucy Personnel and are witnessed by the
customer or his nominated representative. Each test (or sequence of tests)
will be signed upon completion by the Lucy Test Engineer and the
present witnesses.

The primary intention of this document for testing is to guide the engineer
in testing all areas of the RTU and associated I/O signals.

1.1.2 Fundamentals of the Test

Any of the following tests that cannot be performed during the RTU SAT
shall be performed during final commissioning.

The RTU SAT will verify the correct IEC address used for the Control
Centre communication using the protocol test kit (ASE) as per the RTU
I/O connection diagram.

SAT-RTU 7 of 19
1.1.3 RTU Site Acceptance Test

The RTU SAT will generally cover the following:

 Verification of RTU Hardware.


 Verification and Recording of installed RTU Firmware Versions.
 Verification of Digital signals from control panel via DMS IFC to the
RTU.
 Verification of Analogue signals from output of CT via DMS IFC to
the RTU.
 Verification of IEC messages as per the RTU I/O connection diagram.
 Verification or remote Timer Synchronization.

1.1.4 Test Equipments

The test equipments generally consist of the following:

 1 Laptop PC with ASE IEC-101/104 protocol test software,


 1 CT Secondary Current Injection Kit
 Multimeter(s)

1.1.5 Recording of Tests

All test results shall be recorded on the associated test documentation and
their attachments as applicable. A correct test shall be recorded on the
record sheets by placing a tick next to the appropriate data in each row
and in each column on each sheet. Once the sheet has all data ticked it
shall be signed in the bottom right corner to show that no more tests are
required.

SAT-RTU 8 of 19
1.1.6 Associated Test Documentation

Generally a set of following documents will be used for reference and


conducting the testing and commissioning of the RTU.

Title
Analogue measurement test sheet. (Appendix 1)
RTU I/O connection diagram (Appendix 2)
Cables Overview (Appendix 3)

SAT-RTU 9 of 19
1.2 Test Details

This section defines the hardware and software that are used as part
of SAT and the method by which the test equipment will be employed.

1.2.1 RTU Signal Test Procedure

 Testing will be performed using a combination of simulation and test


equipments.
 Alarms and Indications will be simulated from the associated
disconnecting DMS IFC terminals to verify signal transfer to the
Digital Inputs of the RTU.
 Commands from the RTU will be measured at the associated
disconnecting DMS IFC terminals to verify the correct command.
 Analogue inputs will be simulated by an adjustable current
simulator/CT Secondary current injection kit and will be injected via
the associated disconnecting DMS IFC terminals for the feeder under
test.
 The IEC 101/104 protocol analyzer (ASE) will be used to verify the
RTU processing of the above signals as messages on the
communication port.

SAT-RTU 10 of 19
2 RTU SAT Test sheets

2.1 RTU Module Configuration Checks

The RTU Module configuration will be checked for the number of


bays (switch/CB) as per the TRM/QRM stations.

2.2 RTU Cubicle


RTU S/N: _______________________
Substation Name: _______________________
Switchgear S/N: _______________________
Switchgear S/N: _______________________

The list below mentioned the main items to be checked as part of SAT.
Cabinet features Checks Remarks
RMU Type TRM/QRM:________ O.K
Door Fastening O.K
Check that the panel is fully secured to O.K
the wall
Check that the panel door can be fully O.K
opened
Cable inlet O.K
Cable Marking & Identification as per O.K
cable schedule & cable overview.
Battery: S/N O.K
Battery Type & Rating: O.K
Check Battery is correctly connected O.K
Check there no cracks and leakage of O.K
Batteries
Power supply 230 VAC terminal O.K
Mac Address: O.K
RTU IP Address: O.K

The below signature confirms that the test results were within the
specified boundaries and that no relevant errors were found.

Signature: Signature: Signature: Date:

(LUCY) (ADDC) (ADDC)

SAT-RTU 11 of 19
2.3 Time Synchronization

Actions Status Remarks


1. Check that the RTU is in O.K (check in events log)
operation and the RTU does
not have correct time
Displayed prior to the test.
2. Issue time Sync. Command O.K (Simulate master from
from ASE protocol test PC. GI_Clocksync test)

3. Check that the IEC protocol is O.K


stamped with accurate time
(whole time stamp) when signals
are simulated on the RTU and
alternatively verify the event log
for the synchronized time.

The below signature confirms that the test results were within the
specified boundaries and that no relevant errors were found.

Signature: Signature: Signature: Date:

(LUCY) (ADDC) (ADDC)

SAT-RTU 12 of 19
2.4 RTU Software / Parameter Versions

The following tables shall identify the installed RTU Firmware/Software


versions used during the test.

Item Description Version Number


1 CPU board (firmware/ARM) Version
2 Control board Version
4 Configuration Version
5 Gemini RTU Setup Version

2.5 Status indications at the RTU Module

Check the LED indications located on the control panel HMI.

Description Colour Checked


All blinking Green/Red O.K

 With all LEDs flashing the RTU software watchdog has tripped out,
this will happen for 10 seconds on startup and then after if the control
unit software has halted

For Normal Operation all LED’s are glowing steady.

SAT-RTU 13 of 19
2.6 Normal operation from Local Control panel including Hit &
Run function

For testing purpose DMS IFC Terminal will be isolated & Dummy relay
(with deactivated switching contacts) will be used.
Actions Status Remarks
1. RTU is in normal Operation. O.K
Move Local/Remote switch into
local mode. Verify actual status
of LBS/CB to be used for the
test.
2. Set & Note the setting for “local O.K
Manoeuvre Delay” (Hit &
Run):_______ Sec
3. Press Open or Close command O.K
button on local panel for the Bay
to be tested (without pressing
Control enable button at the
same time). Local command
should not be executed.
4. Press Open or Close command O.K
and Control enable button on
local panel simultaneously for the
Bay to be tested. Local command
should be executed.
5. Confirm the functionality of Hit O.K
& Run, corresponding to setting
in item no 2 above.
6. Check for all LBS & CB for O.K
various operations.
(Dummy relay tested via RTU
configurator)

The below signature confirms that the test results were within the
specified boundaries and that no relevant errors were found.

Signature: Signature: Signature: Date:

(LUCY) (ADDC) (ADDC)

SAT-RTU 14 of 19
2.7 Record of Remarks

In the summary list, items shall be entered that have been tested, but the
test result is not in line with the SAT test document.

Item Description Code Action Date

The below signature confirms that the test results were within the
specified boundaries and that no relevant errors were found.

Signature: Signature: Signature: Date:

(LUCY) (ADDC) (ADDC)

SAT-RTU 15 of 19
Appendix 1

RTU SAT Analogue Measurement test Sheets

Substation Name :
Bay Type : TRANSFORMER FEEDER
Bay No :
Bay No :

Current: From Direct Secondary injection. CT RATIO: 150/1A


Bay % current AC mA Expected Actual Accuracy Remarks
Injected INPUT Scaled Value Value
0 0.00 0
K02 50 0.50 750
100 1.00 1500
0 0.00 0
K04 50 0.50 750
100 1.00 1500

Note: Expected scaled value will be filled in as per the RTU Analogue
input configuration prior to the test, as applicable for bay type.

Date ADDC ADDC LUCY


Name
Signature
Date

SAT-RTU 16 of 19
Appendix 2
RTU I/O Connection Schedule

Cable Schedule - RTU to Switchgear (QRM)

CABLE [1]
Connections for QRM Version with 24 Way Umbilical Cable: -

Non Alarm
Umbilical /
GEMINI V3.0 RMU MB
Cable Description Non
RTU Terminal No Terminal No
Core No Active
State
DSM 1A +24VS 1 K5/1 1 `+'24V DC (Switched) -
DSM 1A - 0VS 2 K22/1 2 ` 0V DC -
DSM 1A -SW1 DO 3 K10/1 3 K01 Open command NO
DSM 1A-SW1 DO 4 K12/1 4 K01 Close command NO
DSM 1A -SW1 DI 5 L4/1 8 K01 Close Indication NO
DSM 1A -SW1 DI 6 L5/1 9 K01 Open Indication NO
DSM 1A -DI COM 7 L3/1 7 K01 Common Indication -
DSM 1A -DI 1 8 L63/1 66/80 K01/K03 Earth Fault Indicator NO
DSM 1A -DI COM 9 L61/1 64/78 K01/K03 Earth Fault Indicator Common -
DSM 1A -DI 4 10 - Spare DI NO
DSM 1A – DI COM 11 - Spare DI Com -
DSM 2A +24VS 12 K5/2 15 `+'24V DC (Switched) NO
DSM 2A - 0VS 13 K22/2 16 ` 0V DC -
DSM 2A -SW1 DO 14 K10/2 17 K03 Open command NO
DSM 2A -SW1 DO 15 K12/2 18 K03 Close command NO
DSM 2A -SW1 DI 16 L4/2 22 K03 Close Indication NO
DSM 2A -SW1 DI 17 L5/2 23 K03 Open Indication NO
DSM 2A -DI COM 18 L3/2 21 K03 Common Indication -
DSM 2A -DI COM 19 L30 43 Low Gas Indicator Common -
DSM 2A -DI 3 20 L32 45 Low Gas Indicator NO
DSM 2A -DI 4 21 - Spare DI NO
DSM 2A – DI COM 22 - Spare DI com

SAT-RTU 17 of 19
Cable Schedule - RTU to Switchgear (QRM)

CABLE [2]
Connections for QRM Version with 19 Way Umbilical Cable: -

Non
Alarm
Umbilical
GEMINI V3.0 RMU MB /
Cable Description
RTU Terminal No Terminal No Non
Core No
Active
State
Aux TB 1 from Charger 1 K1 41 `+'24V DC (Switched to Interposing relay) -
Aux TB 2 from Charger 2 - 139/143/160 ` 0 Vdc -
DSM 1B -SW2 DO 3 K2 42 K02 Open Command NO
DSM 1B -SW2 DO 4 - - Spare -
DSM 1B -SW2 DI 5 L4/3 34 K02 Close Indication NO
DSM 1B -SW2 DI 6 L5/3 35 K02 Open Indication NO
DSM 1B -DI COM 7 L3/3 33 K02 Common Indication -
DSM 1B -DI COM 8 RL11 96 K02 Overcurrent/Earth fault trip Common NO
DSM 1B -DI 2 9 RL13 98 K02 Overcurrent/Earth fault trip -
DSM 1B -DI COM 10 RL03 95 K02 Protection Relay Failure Common -
DSM 1B -DI 4 11 RL01 93 K02 Protection Relay Failure -
DSM 1B -AI CT B 12 D30 122 K02 Y Phase CT -
DSM 1B -AI CT B 13 D130 124 K02 Y Phase CT -
DSM 1B -DI 4 14 - Spare DI NO
DSM 1B -DI COM 15 - Spare DI com
DSM 1B -DO 1 16 - Spare DI NO
DSM 1B- DO1 COM 17 - Spare DI com

SAT-RTU 18 of 19
Cable Overview / QRM

Cable
From To Description
tag

W500 LV power supply MCB Box Incoming LV Supply


W501 MCB Box RTU Panel Outgoing LV supply
W101 RTU Panel DMS IFC Cable 1: MV Switchgear Control & Monitoring (Umbilical cable)
W102 RTU Panel DMS IFC Cable 2: MV Switchgear Control & Monitoring (Umbilical cable)
W103 RTU Panel DMS IFC Cable 3: MV Switchgear Control & Monitoring (Umbilical cable)

SAT-RTU 19 of 19
Contractor : National Projects & Contruction LLC 1 SLD

Over All SLD


Employer : ALDAR Projects 2

Country of Origin
Consultant : PARSONS 3

Signal List
Client : ADDC 4

Tele-Information Plan
SS : RMU Substations 5

6 Cable Overview List


Internal Project No:

Adaptation Design
Project Name : Madinat Al Riyadh City Ph-6A & 6B 7

8 I/O Connection Diagram

MATERIAL SUBMITTAL: DMS-RTU for RMU.Rev.01


9 RTU Functional Specification

10 RTU Detailed Design

11 RTU Method Statement

12 RTU FAT Procedure

13 RTU SAT Procedure

14 POINT TO POINT TEST PROCEDURE

15 Warranty Certificate
METHOD OF STATEMENT FOR POINT TO POINT

Contract :

Contractor : LUCY MIDDLE EAST

Rev .0 Page 1
REVISION HISTORY

Version Date Edited Comments/Modifications

Rev.0 28/01/2021 RK Issued for Approval

Rev .0 Page 2
TABLE OF CONTENTS

1. PURPOSE

2. SAFETY

3. PRE-REQUISITES FOR EXECUTION OF WORKS

4. POINT TO POINT PROCEDURE

5. APPENDIX – Record of Remarks.

6. APPENDIX – Analogue Measurement.

7. APPENDIX – RTU IO Connection Schedule

1. PURPOSE

The purpose of this document is to describe the work procedure for the installation
of Lucy RTU in ADDC substations after site survey is completed.

2. SAFETY

All standard ADEWA safety procedures shall be followed as per attached risk
assessment.

Rev .0 Page 3
3. PRE-REQUISITES FOR EXECUTION OF WORKS

The Installation works can be done before shutdown. Installation and


commissioning for the substations are to be arranged with the Operation &
Planning Department and permit to be acquired accordingly. Permits are to be
taken from the field operational Engineer by a contractor at the substation.

4. POINT TO POINT PROCEDURE

The site works for the substation shall start after the following steps.
1. Apply and obtain Permit to work/LAP without shutdown from ADDC
2. Ensure IO list for substation and Terminal list are available.
3. Configure the SCADA timing parameters in RTU as per substation.
4. Configure the IO address in RTU as per IO list.
5. Open all terminals links in the Marshalling panel to isolate the DMS/RTU
Related Connections in RMU and Filed side, If RMU is Live.
6. Check Local/Remote Switch on the RTU is switched to OFF position.
7. Simulate the IO points in RTU and Filed side.
8. If RMU is shutdown, perform the required operations on RMU and Filed
side as per IO list.
9. Observe the IO points as per IO address in RTU and DMS/SCADA
10.Make sure the Time sync in RTU with Master station.
11.After P2P closes all the terminals links in the Marshalling box and verifies
the online status of the switches and breakers.
12.Cancel the Permit/LAP.

Rev .0 Page 4
Appendix – Analogue Measurement.

Bay Type : TRANSFORMER FEEDER

Bay No :

Bay No :

Current: From Direct Secondary injection. CT RATIO: 150/1A

Bay % current AC mA Expected Actual Accuracy Remarks

Injected INPUT Scaled Value Value

0 0.00 0

K02 50 0.50 750

100 1.00 1500

0 0.00 0

K04 50 0.50 750

100 1.00 1500

Note: Expected scaled value will be filled in as per the RTU Analogue input
configuration prior to the test, as applicable for bay type.

Rev .0 Page 5
5. Appendix -Record of Remarks

In the summary list, items shall be entered that have been tested, but the test result
is not in line with the P2P test document.

Item Description Code Action Date

The below signature confirms that the test results were within the specified
boundaries and that no relevant errors were found.

Date ADDC Consultant LUCY

Name

Signature

Date

Rev .0 Page 6
HAZARD IDENTIFICATION, RISK ASSESSMENT AND RISK CONTROL

BEFORE AFTER
Consequences
Activity Hazard Cause of Hazard Recommended Control Measures
/ Impact
Risk Risk
Risk Rating Risk Evaluation
Level Level
Number Severity Likehood Risk H/M/L Number Severity Likehood Risk H/M/L
1 Manual lifting All workers Fall of person on Injury All workers to be informed and trained on the
Pulling or Pushing likely to use same level Property 1 4 1 4 M hazards associated with manual lifting and handling 1 4 1 4 M
manual effort at Fall of object on damage and to include the following :-
work same level
Protruding objects Determine if load can be better shifted by other
Manual handling / means (wheels, mechanical etc.).
lifting
Determine the proper route of lifting/carrying.

Clearing the route and prepare lifting and dropping


point levels.

Precautions to be taken against sharp objects and


obstacles.

Ensure proper grip, posture and movements are


adopted.

Observe correct lifting and manual handling


techniques.

Exercise to maintain fitness and combat physical


fatigue and injury.

Where necessary the correct use of PPE.


2 Lifting operation Crane toppling Position of crane Major injury Position of crane shall be on an even surface.
on loose surface Fatality 1 4 1 4 M 1 4 1 4 M
Instability of All outriggers shall be extended fully.
outriggers
The Soil has to be checked for rigidity before placing
the rigger.

Failure of lifting Not tested Major injury Planned lifting operation.


tackles / slings Excessive use Death 1 5 1 5 H 1 4 1 4 M
Damage Valid test certificate.

Regular visual inspection of slings,hooks & latches


to be carried out.

Page 1 of 3
HAZARD IDENTIFICATION, RISK ASSESSMENT AND RISK CONTROL

BEFORE AFTER
Consequences
Activity Hazard Cause of Hazard Recommended Control Measures
/ Impact
Risk Risk
Risk Rating Risk Evaluation
Level Level
Material falling Unplanned lifting Damage to Safety latch- frequent visual inspection
from height operation equipment 1 4 1 4 M 1 4 1 4 M
Failure of lifting Major injury Don't allow people to work directly below load being
tackles Death lifted or under suspended load.
Lack of
knowledge Manufacture's lifting instruction to be followed.

Lifting area to be cordoned off.

3 Movement of Heavy Inconvinience to Road accidents Injury NOC from appropriate authorities must be obtained
vehicles public Property damage Fatality 1 5 1 5 H where required. 1 4 1 4 M
Hindrance for
other motorist Install signs and barricades.

Banksman shall be provided.

Flashing lights to be provided during work at night.

Work area to be cordoned off.

4 Portable power tools Electric shock Defective tools Injury Insulated power tools.
Leaking electric Fatality 1 4 1 4 M 1 4 1 4 M
cable Regular visual inspection of the condition of wires.
Use in wet
condition

Hit by rotating Safety guard not Minor injury Proper guard.


objects available 1 4 1 4 M 1 4 1 4 M

5 Hand tools Hit by the sharp Improper method Minor injury Use hand gloves.
edges of the of work 1 3 1 3 L 1 3 1 3 L
tool Blunt edges

Slipping and Broken handles Injury Suitable tool for work.


falling of tool Cracked parts 1 3 1 3 L 1 3 1 3 L
Regular visual inspection.

Careful Handling of Tools.

Page 2 of 3
HAZARD IDENTIFICATION, RISK ASSESSMENT AND RISK CONTROL

BEFORE AFTER
Consequences
Activity Hazard Cause of Hazard Recommended Control Measures
/ Impact
Risk Risk
Risk Rating Risk Evaluation
Level Level
6 Tesing of equipment Electric shock Testing Major injury All testing equipment should be earthed
equipment not Fatality 1 5 1 5 H 1 3 1 3 L
earthed The Supply wire has to be checked visually for
damage in the insulation.

Electric shock HV hand gloves Major injury HV hand gloves to be used during high voltage
not provided Fatality 1 5 1 5 H testing. 1 4 1 4 M

Electric shock Working in the Major injury No one should be allowed to work near or in the
testing area Fatality 1 4 1 4 M testing area. 1 4 1 4 M

Testing area shall be cordoned off.

Proper signs to be provided for keeping away


unauthorized persons.
Electric shock Damaged, Major injury All testing equipment including HV test kit shall have
Incalibrated Burn 1 5 1 5 H valid calibration certificate. 1 4 1 4 M
testing equipment Fatality
Regular visual inspection.

Use of proper cables.

The Testing Instrument and the Testing Equipment


has to be earthed.

Page 3 of 3
Contractor : National Projects & Contruction LLC 1 SLD

Over All SLD


Employer : ALDAR Projects 2

Country of Origin
Consultant : PARSONS 3

Signal List
Client : ADDC 4

Tele-Information Plan
SS : RMU Substations 5

6 Cable Overview List


Internal Project No:

Adaptation Design
Project Name : Madinat Al Riyadh City Ph-6A & 6B 7

8 I/O Connection Diagram

MATERIAL SUBMITTAL: DMS-RTU for RMU.Rev.01


9 RTU Functional Specification

10 RTU Detailed Design

11 RTU Method Statement

12 RTU FAT Procedure

13 RTU SAT Procedure

14 POINT TO POINT TEST PROCEDURE

15 Warranty Certificate
‫ﻟـــــــوﺳـــــﻲ اﻟــــﺷـــــــرق اﻷوﺳــــــــط‬
‫ممح‬
‫م‬.‫ع‬.‫ دﺑﻲ – أ‬،‫ ﺟﺑل ﻋﻠﻲ‬،١٧٣٣٥ : ‫ ب‬.‫ص‬
+٩٧١٤٨١٢٩٩٩٩ :‫ھﺎﺗف‬
+٩٧١٤٨١٢٩٩٠٠ :‫ﻓﺎﻛس‬
PO Box 17335 • Jebel Ali, Dubai, UAE
Tel: +971 4 812 9999
Project: Riyadh City Ph-6A & 6B Fax: +971 4 812 9900
Client: ALDAR Projects Website: www.lucyelectric.com
PMC: KBR
Consultant: PARSONS
Contractor: National Projects & Construction LLC Ref: Inv No. Date

Delivery Date:
Attention: Abu Dhabi Distribution Company (ADDC)

Greetings,

We (on behalf of Lucy Switchgear FZE, Jebel Ali, Dubai - UAE), hereby warranty the Remote Terminal Unit
type " RTU", serial number: from all defects arising from faulty design or workmanship or of defective
material for a period of twelve (12) months from the commissioning date or eighteen (18) months from
delivery date i.e. (date), whichever is earlier. Our guarantee does not include responsibility for damage
due to misuse, neglect, improper installation, poor transportation and off loading at site.

Our obligation is limited to the replacement of our material involved and does not include the
consequential costs and / or losses.