This document provides the technical specifications for the MXE 3G 1kVA 1x1 UPS with an internal battery. The UPS has a maximum output of 1000VA/900W. It has a wide input voltage range of 100-300VAC and can operate in temperatures up to 50 degrees Celsius. Key features include true online double conversion, high efficiency up to 98%, and flexible battery charging capabilities. The UPS is suitable for applications such as networking, servers, storage, security systems, and industrial automation.

Uploaded by

Leonardo Ramos
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
89 views4 pages

MXE 3G 1 KVA Inbuilt Battery

This document provides the technical specifications for the MXE 3G 1kVA 1x1 UPS with an internal battery. The UPS has a maximum output of 1000VA/900W. It has a wide input voltage range of 100-300VAC and can operate in temperatures up to 50 degrees Celsius. Key features include true online double conversion, high efficiency up to 98%, and flexible battery charging capabilities. The UPS is suitable for applications such as networking, servers, storage, security systems, and industrial automation.

Uploaded by

Leonardo Ramos
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

MXE 3G 1kVA 1x1 (Inbuilt Battery) UPS Technical Specification

MXE 3G 1 kVA
01 kVA 1x1 (Inbuilt Battery) UPS
Manufacturer’s declaration in accordance with IEC 62040-3

Value Proposition:
High Performance
True Online Double Conversion
True Input PF 0.99
True output PF 0.9
Output THDv 2%
Higher Power Density
Higher Efficiency upto 98% in ECO Mode
Support Critical Virtualization

High Reliability and Adaptability


Wide Input Voltage Range 110 to 300 Vac
Inbuilt Hardware Current Limit Technology.
Upgraded Phase Lock Algorithm
Inbuilt Over-voltage Cut-off Device
Inbuilt Over Temperature Protection.
Upto 50 Degree Celsius operation @50%
Load (Specific to XL Model)
Better Overload Protection upto 105% Constant

High Flexibility and Availability


Adjustable Charging Current 0 to 1.5 Amps
Better Short Ckt Handling Capacity.
Auto Fault Recovery.
Conformal Coated Boards.
More Accessories.

Major Application
Networking/Server/Storage.
Wiring Closets.
Security and Surveillance System.
Industrial Automation Control.
Laboratory Equipment.
ATM/Telecom/Railway Signalling.
MXE 3G 1kVA

Technical Specification 1 kVA-Inbuilt Battery


Model Name MXE 3G 1000i
Catalog number MXE 3G 1K
Plant Part Number 9103-53862FC1
S7 Code 11158
INPUT Characteristics
Acceptable Input Voltage 100VAC-300VAC
Phase Single phase with ground
Transfer Voltage Range (low load) 100VAC-300VAC (40% load)
Transfer Voltage Range (100% load) 176VAC-300VAC
-Line low loss 176VAC/100VAC (±3%)
-Line low comeback 186VAC/110VAC (±3%)
-Line high loss 300VAC (±3%)
-Line high comeback 290VAC (±3%)
Nominal input current (r.m.s)
4.5A
@ 230V input and battery fully recharged
Inrush Current Limit 8*Irms
THDi 5 % typical, 7% Max with R full load @ 230v input
Input Power Factor ≥0.99(R FULL LOAD) @ 230V input
Input Frequency Range 45-55Hz / 54-66Hz
Input protection Breaker
OVCD Withstand 440Vac, 24Hours
Generator Set 2.2 x UPS Rating Power
OUTPUT Characteristics
Output Power(VA) max 1000
Output Power(W) max 900
Output Power Factor 0.9
Output Waveform Pure sine wave
Output nominal voltage 220VAC/230VAC/240VAC
Output Voltage Variation ±1%
Output Transient recovery 100ms (IEC 62040-3 Non-linear load)
< 2% THD, linear load@Line mode
< 2% THD, linear load @ battery mode, battery voltage 12V / per battery
Output Voltage distortion
< 6% THD, linear load@Line mode
< 6% THD, linear load @ battery mode, battery voltage 12V / per battery
Output Frequnecy in inverter mode Synchronization range 45-55Hz / 54-66Hz
Output Frequency Slew rate 1 Hz/s
Output Frequency in Battery mode (50/60±0.05) Hz
Transfer time Inverter Mode to Battery Mode. 0ms
Transfer Time Inverter Mode to Bypass Mode. 4ms
Line mode efficiency @ full load with battery fully charged >89%
ECO mode efficiency @ full load with battery fully charged >97.5%
Battery mode efficiency @ full load 12Vdc/Battery >84.4%
100%~105% :Constant
105%~130% :60s
Overload Capability (Line mode)
130%~150% :10s
>150% :300ms
100%~105% :Constant
105%~130% :10s
Overload Capability (Battery mode) 130%~150% :1s
>150% :300ms
>105% and Vbat<10.5V: 300ms

2
MXE 3G 1kVA

BATTERY Characteristics
DC Voltage 24VDC
21VDC,
Battery-Low Voltage(full load)
10.5V/pcs
Battery shutdown voltage @ 0 ~ 20% Load (for long run model) / 0~ 30% (for
21.4VDC,10.7V/pcs
standard model)
Battery shutdown voltage @ 20 ~ 70% Load (for long run model) / 30%~70% load (for
20.4VDC, 10.2V/pcs
standard model)
Battery shutdown voltage @ > 70% Load 19VDC, 9,5V/pcs
Charger Current 1.5A
Leakage current < 150uA
FEATURES
ECO Mode YES
EPO Function YES
Battery Capacity Calculation YES
Fan Speed Control YES
Frequency Converter Mode(CVCF) YES, 60% load
INTERFACE
RS232 NA
USB YES
COM Slot YES
NMC card Optional
AS400 card(Dry contact card) Optional
Modbus card Optional
Input connection IRAM Inet 10A
Outlet socket 3 x IRAM 10A outlets
MECHANICAL
WxHxD (mm) 144 x 228 x 356
Net Weight 9.2Kg
Operating Temperature Range 0°C ~ 40 °C
Relative Humidity 0 ~ 95% (No condensing)
Audible Noise <40dB at front 1m @ typical load
Regulations and Standards
-ESD IEC 61000-4-2 Level 3
-RS IEC 61000-4-3 Level 3
-EFT IEC 61000-4-4 Level 4
-Surge IEC 61000-4-5 Level 4
-Safety BIS
-Transportation ISTA 2A
-Protection IP20 (static)
ACCESSORIES
User manual Yes
External battery power cord NA

3
MXE 3G 1kVA

EMC
Conduction Class 2 Ref Std: IEC 62040-2:2005
Radiation Class 2 Ref Std IEC 62040-2:2005
Low frequency conducted disturbances Criteria A Ref Std : IEC61000-2-2:2002
Harmonic current Class A Ref Std :IEC 61000-3-2:2014
ESD Criteria B, Level 3 Ref Std : IEC 61000-4-2:2008

RS Criteria A, Level 3 Ref Std IEC 61000-4-3:2006+AMD1:2007+AMD2:2010 CSV

EFT Criteria B ,Level 4 Ref Std :IEC 61000-4-4:2012


Criteria B,
Surge DM Level 3: 2KV,
CM Level 4: 4KV Ref Std : IEC 61000-4-5:2014
C/S Criteria A, level 3 Ref Std : IEC61000-4-6:2013
M/S Criteria B, level 4 Ref Std : IEC61000-4-8:2009
Voltage Dips, short interruptions and voltage variations Criteria B ,Level 4 Ref Std : IEC61000-4-11: 2004
Certificate
BIS YES
CE YES