Technical Specification
Direct Buried Double Jacket Fiber Optic Cable
Containing 12 ITU-T G.652.D Compliant Single Mode Optical Fibers
GENERAL
The cable is applicable for outdoor, direct burial for underground networks. The cable can also be installed inside HDPE sub ducts.
REFERENCE STANDARDS
The offered fiber optic cable complies to ITU-T G.652.D as necessary, following to the client request. The offered cable is also fully
compliant to the relevant IEC specifications, especially IEC 60794-3, IEC 60793-2-50 B1.3, and related TIA/ EIA standards.
CABLE STRUCTURE
Cable DIN code : A-DQ(ZN)2Y(SR)2Y 2X6 E9/125/245 0.35F2.0 + 0.20H18 LG
- Fiber type is standard single mode according to ITU-T G.652.D or IEC 60793-2-50 B1.3 recommendation
- Fiber colour sequence : blue, orange, green, brown, grey, and white
- Loose Tube stranding sequence : blue, orange, filler, filler, and filler
- Each six fibers are inserted into thixotropic gel-filled coloured thermoplastic (PC-PBT) loose buffer tubes
- Glass reinforced plastic (GRP/FRP) non-metallic, anti buckling central strength element
- The loose buffer tubes and filler (if necessary) are SZ-stranded around FRP and bound with polyester yarns
- Water ingression protection is applied
- Aramid yarns as peripheral strength element
- Ripcord to ease jacket opening
- Corrugated steel tape armour as rodent bite protection under the outer jacket
- Black UV resistant High Density Polyethylene (HDPE) jacket as inner & outer protection
CABLE MARKINGS
The cable is printed with white-coloured markings as below format.
[m] CCS INDONESIA [year] KABEL OPTIK SM.D B-LT 12/2T PLUS CORNING OPTICAL FIBER [m+1]
CABLE END SEALING, DELIVERY LENGTH AND PACKAGE
Both cable ends are protected by means of heat shrinkable endcaps then to be firmly attached to the cable drums. All cable drums
are properly covered. Sufficient identification, precaution and handling information labels including the test report are attached to
the cable drum. The minimum delivery length is 2000m per drum. Specific delivery lengths may be produced upon request.
CABLE PARAMETERS
ITEM SPECIFICATION
Spec ITU.T G.652.D
Fiber
Number 12
Loose Tube Material PC, PBT
Loose Buffer Tube Filling Compound Thixotropic gel
Number 2
Fiber / Tube 6
Central Member Material Glass Reinforced Plastic (GRP)
Water Blocking Material Swellable Water Blocking Material
Material Polyethylene
Filler
Quantity 2
Peripheral Strength Element Material Aramid Yarn
Metal Protection Material Corrugated Steel Tape
Ripcord Quantity Two (2) Under Each of Cable Sheathing
Inner & Outer Sheath Material Black UV Resistant High Density Polyethylene
CCSI Doc. No.: B-42BF52-001 Rev.0 Manufacturer: Customer Approval
Date: 09-November-2015 PT CCS Indonesia
Page: 1 of 2 [company, sign & name]
OPTICAL AND MECHANICAL CHARACTERISTICS OF SINGLE MODE G.652.D OPTICAL FIBER
Reference Standard ITU-T G.652.D, IEC 60793-2-50 B1.3
Type Single Mode Low Loss CWDM & DWDM Capable
Attenuation on Finished Cables 0.35 dB/km at 1310 nm & 0.20 dB/km at 1550nm
Point of Discontinuity < 0.05 dB
Cable Cut Off Wavelength < 1260 nm
PMD Link Design Value < 0.06 ps/√km
≤ 2.0 ps/nm.km at 1310 nm
Chromatic Dispersion ≤ 18.0 ps/nm.km at 1550 nm
≤ 22.0 ps/nm.km at 1625 nm
9.2 ± 0.4 µm at 1310 nm
Mode Field Diameter
10.4 ± 0.5 µm at 1550 nm
Colour Coating Diameter ≤ 260 µm
Uncoloured Coating Diameter ≤ 247 µm
Cladding Diameter 125 +/- 0.7 µm
Cladding Non Circularity ≤ 0.7 %
Core/ Cladding Concentricity Error ≤ 0.5 µm
Coating/ Cladding Concentricity ≤ 12 µm
Proof Test 0.69 Gpa
Attenuation under Bending Load @ 1310 and 1550 nm with 100
≤ 0.03 dB/ km
turns with 50 mm Mandrel Diameter
Optical Return Loss > 60 dB
Index of Refraction (IOR) Values 1.4676 at 1310 nm & 1.4682 at 1550nm
TECHNICAL CHARACTERISTIC
ITEM SPECIFICATION
Operating Tensile Strength (Refer to IEC 60794-1-E1) 2900 N
Crush Strength (Refer to IEC 60794-1-E3) 5000 N/ 100 mm
Impact Strength (Refer to IEC 60794-1-E4) 15 Nm
Torsion (Refer to IEC 60794-1-E7) 30 twists, 2 direction @ 180˚, Load 250N
Minimum Bending Radius (Refer to IEC 60794-1-E11) 20 x Cable Outside Diameter
Operating & Storage Temperature Up to 70° C
Water Ingression Resistance (Refer to IEC 60794-1-F5B) No leakage for 24 hour testing with 1-m Height water column
Cable Diameter (Nominal) 12.0 mm
Cable Dimensions
Cable Weight (Nominal) 145 kg/km
CROSS-SECTIONAL DRAWING FOR DIRECT BURIED CABLES Outer UV Resistant Black Jacket
Filler
Steel Tape
GRP Central Member
Loose Tube Contain Optical Fibers
Swellable Water Blocking Yarn
Swellable Water Blocking Tape
Aramid Yarn Strength Member
Ripcord
CCSI Doc. No.: B-42BF52-001 Rev.0 Manufacturer: Customer Approval
Date: 09-November-2015 PT CCS Indonesia
Page: 2 of 2 [company, sign & name]