GWR FMP54
GWR FMP54
Technical Information
Levelflex FMP51, FMP52,
FMP54
Guided wave radar
Application
• Rod, rope or coax probe
• Process connection: Starting 3/4" thread, flange or process connections for hygiene
requirements (Tri-Clamp, 11851)
• Process temperature: –196 to +450 °C (–320 to +842 °F)
• Process pressure: –1 to +400 bar (–14.5 to +5 800 psi)
• Maximum measuring range: Rod 10 m (33 ft); rope 45 m (148 ft); coax 6 m (20 ft)
• Accuracy: ±2 mm (±0.08 in)
• International explosion protection certificates; WHG; marine approval; steam
boiler approval; EN10204-3.1
• Linearity protocol (3-point, 5-point)
Your benefits
• Reliable measurement even for changing product and process conditions
• HistoROM data management for easy commissioning, maintenance and
diagnostics
• Highest reliability due to Multi-Echo Tracking
• Hardware and software developed according to IEC 61508 (up to SIL3)
• Seamless integration into control or asset management systems
• Intuitive user interface in national languages
• Easy proof test for SIL and WHG
• Heartbeat Technology™
Levelflex FMP51, FMP52, FMP54
Table of contents
2 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Device-specific accessories . . . . . . . . . . . . . . . . . . . . . . 123
Communication-specific accessories . . . . . . . . . . . . . . . 131
Service-specific accessories . . . . . . . . . . . . . . . . . . . . . 132
System components . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Standard documentation . . . . . . . . . . . . . . . . . . . . . . . 133
Supplementary documentation . . . . . . . . . . . . . . . . . . . 133
Safety documentation . . . . . . . . . . . . . . . . . . . . . . . . . 134
Patents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Endress+Hauser 3
Levelflex FMP51, FMP52, FMP54
Symbol Meaning
DANGER!
DANGER This symbol alerts you to a dangerous situation. Failure to avoid this situation will
result in serious or fatal injury.
WARNING!
WARNING This symbol alerts you to a dangerous situation. Failure to avoid this situation can
result in serious or fatal injury.
CAUTION!
CAUTION This symbol alerts you to a dangerous situation. Failure to avoid this situation can
result in minor or medium injury.
NOTE!
NOTICE This symbol contains information on procedures and other facts which do not result in
personal injury.
Electrical symbols
Symbol Meaning
Direct current
Alternating current
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a
grounding system.
Symbol Meaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation.
A Reference to page.
Reference to graphic.
Visual inspection.
4 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Symbols in graphics
Symbol Meaning
1. , 2. , 3. … Series of steps
A, B, C, ... Views
Hazardous area
- Indicates a hazardous area.
Symbol Meaning
Safety instructions
Observe the safety instructions contained in the associated Operating Instructions.
Endress+Hauser 5
Levelflex FMP51, FMP52, FMP54
20 mA
100%
D
E
LN F
4 mA
0%
A0011360
If, for rope probes, the DC value is less than 7, then measurement is not possible in the area of
the straining weight (0 to 250 mm (0 to 9.84 in) from end of probe; lower blocking distance).
6 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Dielectric constant
The dielectric constant (DC) of the medium has a direct impact on the degree of reflection of the
highfrequency pulses. In the case of large DC values, such as for water or ammonia, there is strong
pulse reflection while, with low DC values, such as for hydrocarbons, weak pulse reflection is
experienced.
Input
The reflected pulses are transmitted from the probe to the electronics. There, a microprocessor
analyzes the signals and identifies the level echo which was generated by the reflection of the high-
frequency pulses at the product surface. This clear signal detection system benefits from over 30
years' experience with pulse time-of-flight procedures that have been integrated into the
development of the PulseMaster® software.
The distance D to the product surface is proportional to the time of flight t of the impulse:
D = c · t/2,
where c is the speed of light.
Based on the known empty distance E, the level L is calculated:
L=E–D
The reference point R of the measurement is located at the process connection. For details see the
dimensional drawing:
• FMP51: → 81
• FMP52: → 84
• FMP54: → 85
The Levelflex possesses functions for interference echo suppression that can be activated by the user.
They guarantee that interference echoes from e.g. internals and struts are not interpreted as level
echoes.
Output
The Levelflex is preset at the factory to the probe length ordered so that in most cases only the
application parameters that automatically adapt the device to the measuring conditions need to be
entered. For models with a current output, the factory adjustment for zero point E and span F is 4
mA and 20 mA, for digital outputs and the display module 0 % and 100 %. A linearization function
with max. 32 points, which is based on a table entered manually or semi-automatically, can be
activated on site or via remote operation. This function allows the level to be converted into units of
volume or mass, for example.
Endress+Hauser 7
Levelflex FMP51, FMP52, FMP54
Interface measurement
When the high-frequency pulses hit the surface of the medium, only a percentage of the
transmission pulse is reflected. In the case of media with a low DC1, in particular, the other part
penetrates the medium. The pulse is reflected once more at the interface point to a second medium
with a higher DC2. The distance to the interface layer now can also be determined taking into
account the delayed time-of-flight of the pulse through the upper medium.
LL
C0
DK1 (DC1) C1 =
DK1
LI
DK2 (DC2)
A0011178
In addition, the following general conditions must be observed for interface measurement:
• The DC of the upper medium must be known and constant 1). The DC can be determined with the
aid of the DC manual CP00019F or the "DC Values App". In addition, if the interface thickness is
existing and known, the DC can be calculated automatically via FieldCare.
• The DC of the upper medium may not be greater than 10.
• The DC difference between the upper medium and lower medium must be >10.
• The upper medium must have a minimum thickness of 60 mm (2.4 in).
• Emulsion layers in the area of the interface can strongly attenuate the signal. However, emulsion
layers up to 50 mm (2 in) are admissible.
For dielectric constants (DC values) of many media commonly used in various industries refer
to:
• the Endress+Hauser DC manual (CP01076F)
• the Endress+Hauser "DC Values App" (available for Android and iOS)
1) For FMP55: Under certain conditions measurement is possible even with a changing DC. For details please contact your Endress+Hauser
representative.
8 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Endress+Hauser 9
Levelflex FMP51, FMP52, FMP54
Probe selection
The various types of probe in combination with the process connections are suitable for the following
applications 2):
Levelflex FMP51
A0011387 A0011359
A0011388
AL 12 mm (AlloyC)
AM 1/2" (AlloyC)
BA 16 mm (316L)
BC divisible
BB 0.63 in (316L)
BD divisible
For application level and interface level and interface level and interface
measurement in liquids measurement in liquids measurement in liquids
1) Punched for process connections G1-1/2" or flange; multiple holes for 316L, one hole for AlloyC
2) Maximum probe length for indivisible rod probes: 4 m (13 ft)
2) If required, rod and rope probes can be replaced. They are secured with Nord-Lock washers or a thread coating. For further information on
service and spare parts please contact the Endress+Hauser service.
10 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Levelflex FMP52
A0011357
A0011358
For application level and interface level and interface measurement in corrosive liquids
measurement in corrosive
liquids
Levelflex FMP54
A0011357 A0011359
A0011358
For application level and interface level and interface level and interface
measurement in liquids measurement in liquids measurement in liquids
Endress+Hauser 11
Levelflex FMP51, FMP52, FMP54
Input
Measured variable The measured variable is the distance between the reference point and the product surface.
Subject to the empty distance entered "E" the level is calculated.
Alternatively, the level can be converted into other variables (volume, mass) by means of
linearization (32 points).
Measuring range The following table describes the media groups and the possible measuring range as a function of
the media group.
2 1.6...1.9 • liquefied gas, e.g. propane • one-piece: 4 m (13 ft) 15 to 22 m (49 to 72 ft) 6 m (20 ft)
• solvent • divisible: 10 m (33 ft)
• Freon
• palm oil
3 1.9...2.5 mineral oils, fuels • one-piece: 4 m (13 ft) 22 to 32 m (72 to 105 ft) 6 m (20 ft)
• divisible: 10 m (33 ft)
6 >7 • aqueous solutions • one-piece: 4 m (13 ft) 45 m (148 ft) 6 m (20 ft)
• alcohols • divisible: 10 m (33 ft)
• ammonia
12 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Levelflex FMP52
1)
Measuring range
Media group DC (εr) Typical liquids PFA-coated PFA-coated
rod probes rope probes
• Reduction of the max. possible measuring range through buildup, above all of moist products.
• Due to the high diffusion rate of ammonia it is recommended with gas-tight bushing 3) for
measurements in this medium.
Endress+Hauser 13
Levelflex FMP51, FMP52, FMP54
Blocking distance The upper blocking distance (= UB) is the minimum distance from the reference point of the
measurement (mounting flange) to the maximum level.
R
SD UB
100%
E
F
LN
0%
A0011279
14 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Output
Output signal HART
PROFIBUS PA
FOUNDATION Fieldbus
Switch output
For HART devices, the switch output is available as an option. See product structure, feature 20:
"Power Supply, Output", option B: "2-wire; 4-20mA HART, switch output"
Devices with PROFIBUS PA and FOUNDATION Fieldbus always have a switch output.
Endress+Hauser 15
Levelflex FMP51, FMP52, FMP54
Switch output
Switching behavior Binary (conductive or non-conductive), switches when the programmable switch
point is reached
Insulation voltage floating, Insulation voltage 1 350 VDC to power supply aund 500 VAC to ground
Switch point freely programmable, separately for switch-on and switch-off point
Switching delay freely programmable from 0 to 100 s, separately for switch-on and switch-off
point
Linearization The linearization function of the device allows the conversion of the measured value into any unit of
length or volume. Linearization tables for calculating the volume in cylindrical tanks are pre-
programmed. Other tables of up to 32 value pairs can be entered manually or semi-automatically.
Galvanic isolation All circuits for the outputs are galvanically isolated from each other.
16 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Manufacturer ID 17 (0x11)
HART device variables The measured values can be freely assigned to the device variables.
Measured values for PV (primary variable)
• Level linearized
• Distance
• Interface 1)
• Interface distance 1)
• Upper interface thickness 1)
• Electronic temperature
• Relative echo amplitude
• Relative interface amplitude 1)
Measured values for SV, TV, FV (second, third and fourth variable)
• Level linearized
• Distance
• Interface linearized 1)
• Interface distance 1)
• Upper interface thickness 1)
• Terminal voltage
• Electronic temperature
• Absolute echo amplitude
• Relative echo amplitude
• Absolute interface amplitude 1)
• Relative interface amplitude 1)
• Calculated DC
Minimum start-up voltage for device version "2-wire; 4-20mA HART" 1): 17.5 V
Start-up time 45 s
Set-up time 1s
Endress+Hauser 17
Levelflex FMP51, FMP52, FMP54
PROFIBUS PA
Manufacturer ID 17 (0x11)
18 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
FOUNDATION Fieldbus
Manufacturer ID 0x452B48
Number of VCRs 44
Permanent entries 1
Client VCRs 0
Server VCRs 10
Source VCRs 43
Sink VCRs 0
Subscriber VCRs 43
Publisher VCRs 43
Slot time 4
Endress+Hauser 19
Levelflex FMP51, FMP52, FMP54
Transducer Blocks
Block Content Output values
Setup Transducer Block Contains all parameters for a standard commissioning • Level or volume 1)
procedure (Channel 1)
• Distance (Channel 2)
Advanced Setup Contains all parameters for a more detailed no output values
Transducer Block configuration of the device
Display Transducer Block Contains all parameters for the configuration of the no output values
display module
Expert Information Contains information about the state of the device no output values
Transducer Block
Service Sensor Transducer Contains parameters which can only be operated by no output values
Block Endress+Hauser service personnel
Service Information Contains information on the state of device which is no output values
Transducer Block relevant for service operations
Data Transfer Transducer Contains parameters which allow to backup the device no output values
Block configuration in the display module and to restore it
into the device.
20 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Function Blocks
Block Content Number of Number of Execution Functionality
permanent instantiable time
blocks blocks
Up to 20 blocks can be instantiated in the device altogether, including the blocks already
instantiated on delivery.
Endress+Hauser 21
Levelflex FMP51, FMP52, FMP54
Power supply
Terminal assignment 2-wire: 4-20mA HART
! 2- w
4-2 ire le
0 v el
HA mA
[21 RT
4-2
0m
A ]
ope
A
n Sp
a
711 re pa
HA 20mA
08x rt
xx
RT
4...
+
1 -
1 2 4 5 6
mm
2
10
+ +
–
–
# 4...20 mA
3 B
7 +
1-c 1 -
1 2 4 5 han
nel 4-2 2
ove 0m
[16
] rvo A
ltage
pro
tec
tion
+ +
–
–
# 4...20 mA
3
A0011294
22 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
10
9
8
% 2- w
4-2 ire
0
HA mA
[02 RT
PF
S
A /03
] ope
n Sp
a
711 re pa
HA 20 mA
08x rt
3+ ++ xx
31 --
RT
4...
42 +
7
1 -
mm
2 6
4-
10
+ +
–
-
≥250 Ω 4...20 mA
$
1 2 3 4 5 B
3+ 11 +
3 -
4-2 4
0m +
2-c
A/ 1 -
han 4-2 2
4- nel
ove F IEL 0m
DB A/
[17 rvo
] ltag
ep US
rote
ctio
n
+ +
–
-
≥250 Ω 4...20 mA
$
1 2 3 4 5
A0013759
Endress+Hauser 23
Levelflex FMP51, FMP52, FMP54
14
13
12
# 2- w
4-2 ire le
0 v el
HA mA
[04 RT
4-2
0m
A /05
]
A
ope
A
n Sp
20m
a
711 re pa
HA 20mA
08x rt
xx
+
4 ...
3 -
RT
11
4 ...
4 +
1 -
mm
2
+ +
10
1 " –
-
4...20 mA
9 8 4
+ +
2 " –
-
4...20 mA
3 5 6 7 4
B
+ +
1 " –
- +
3 -
4...20 mA 4-2 4
10 0m +
9 8 4 2-c
A/ 1 -
han
nel 4- 2
[17
ove FIE 20mA
] rvo LD /
ltag
ep
B U
ro S
tec
tion
+ +
2 " –
-
4...20 mA
3 5 6 7 4
A0013923
This version is also suited for single-channel operation. In this case, current output 1 (terminals
1 and 2) must be used.
24 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
13
12
11
! 2- w
4-2 ire
0
HA mA
[08 RT
A ]
= V
o pe
48
n Sp
4...
a
711 re pa
HA 20 mA
08x rt
10.
L+ xx
1 L-
RT
4...
2 +
10 9
3 -
mm
4 8
10
7
+ !
-
≥250 Ω 4...20 mA
6
1 2 3 4 5
A0011340
Endress+Hauser 25
Levelflex FMP51, FMP52, FMP54
13
12
11
! 2- w
4-2 ire
0
HA mA
[09 RT
A ]
~
3V
ope
n
..25
Sp
a
711 re pa
HA 20 mA
9 0.
08x rt
xx
L
1 N
RT
4...
2 +
10 9
3 -
mm
4 8
10
7
+ !
-
≥250 Ω 4...20 mA
6
1 2 3 4 5
A0018965
LCAUTION
To ensure electrical safety:
‣ Do not disconnect the protective connection (6).
‣ Disconnect the supply voltage before disconnecting the protective earth (7).
Connect protective earth to the internal ground terminal (7) before connecting the supply
voltage. If necessary, connect the potential matching line to the external ground terminal (11).
In order to ensure electromagnetic compatibility (EMC): Do not only ground the device via the
protective earth conductor of the supply cable. Instead, the functional grounding must also be
connected to the process connection (flange or threaded connection) or to the external ground
terminal.
An easily accessible power switch must be installed in the proximity of the device. The power
switch must be marked as a disconnector for the device (IEC/EN61010).
26 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
! 2-
F4IEwire
-20L lev
mD
ABU el
FA
P IE/F S
06/ LD
[2 F B PFS
A 07]
2 U S
op en Sp
a
7110 re pa
US
0283x4 rt
3+ ++ x5x7
B
31 --
/LFDF
PIAE
42 +
F
2
1 2-
mm
4-
10
3
1
B
3+ 6 +
3 -
4-2 4 +
0m
2-c
A/ 1 -
han
nel 4-2 2
4- [17
ove F IEL 0m
A
] rvo
ltag DB /
1 ep US
rote
ctio
n
A0011341
Endress+Hauser 27
Levelflex FMP51, FMP52, FMP54
+
3+ 1
2
Ri + 3+
-
Ri
4-
A0015909
4-
10 Connection of a relay A0015910
28 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
HART
+1 10
+2 11 HMX50
12
-3
16
4
17
5 18
6
7
8
9
13
14
15
19
20
21
FXA195
22 23 24 HART
24V DC
A0023287
12 Connection diagram for HART loop converter HMX50 (example: passive 2-wire device and current outputs
connected as power source)
The HART loop converter HMX50 can be acquired using the order number 71063562.
Additional documentation: TI00429F and BA00371F.
Endress+Hauser 29
Levelflex FMP51, FMP52, FMP54
Device plug connectors For the versions with fieldbus plug connector (M12 or 7/8"), the signal line can be connected
without opening the housing.
2 not connected
1 2 3 Signal -
A0011175
4 Ground
2 Signal +
2 4 3 Not connected
A0011176
4 Screen
30 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Ex ia / IS 11.5 to 30 V
0
10 20 30 35 U0 [V]
11.5 22.5
A0035511
• Ex d / XP 13.5 to 30 V 4) R [Ω]
• Ex ic[ia]
• Ex tD / DIP
500
0
U0 [V]
10 20 30
13.5 24.5
A0034969
Endress+Hauser 31
Levelflex FMP51, FMP52, FMP54
• Ex ia / IS 13.5 to 30 V 3)
• Ex ia + Ex d[ia] / IS + XP 0
10 20 30 U0 [V]
13.5 24.5 35
A0034971
any Channel 1:
13.5 to 30 V 3) 4) R [Ω]
500
0
U0 [V]
10 20 30
13.5 24.5
A0034969
Channel 2:
12 to 30 V R [W]
500
0
10 20 30 U0 [V]
12 23
A0022583
32 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Endress+Hauser 33
Levelflex FMP51, FMP52, FMP54
K: 4-wire 90-253VAC; 4-20mA HART 90 to 253 VAC (50 to 60 Hz), overvoltage 500 Ω
category II
Polarity sensitive No
Nominal current 3.6 to 22 mA, the start-up current for multidrop mode can be parametrized (is
set to 3.6 mA on delivery)
PROFIBUS PA
Nominal current 14 mA
34 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
FOUNDATION Fieldbus
FISCO
Ui 17.5 V
Ii 550 mA
Pi 5.5 W
Ci 5 nF
Li 10 μH
Endress+Hauser 35
Levelflex FMP51, FMP52, FMP54
HART
• A normal device cable suffices if only the analog signal is used.
• A shielded cable is recommended if using the HART protocol. Observe grounding concept of the
plant.
• For 4-wire devices: Standard device cable is sufficient for the power line.
PROFIBUS
Use a twisted, screened two-wire cable, preferably cable type A.
For further information on the cable specifications, see Operating Instructions BA00034S
"PROFIBUS DP/PA: Guidelines for planning and commissioning", PNO Guideline 2.092
"PROFIBUS PA User and Installation Guideline" and IEC 61158-2 (MBP).
FOUNDATION Fieldbus
Endress+Hauser recommends using twisted, shielded two-wire cables.
For further information on the cable specifications, see Operating Instructions BA00013S
"FOUNDATION Fieldbus Overview", FOUNDATION Fieldbus Guideline and IEC 61158-2 (MBP).
Overvoltage protection If the measuring device is used for level measurement in flammable liquids which requires the use of
overvoltage protection according to DIN EN 60079-14, standard for
test procedures 60060-1 (10 kA, pulse 8/20 μs), an overvoltage protection module has to be
installed.
Technical data
36 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Performance characteristics
Reference operating • Temperature = +24 °C (+75 °F) ±5 °C (±9 °F)
conditions • Pressure = 960 mbar abs. (14 psia) ±100 mbar (±1.45 psi)
• Humidity = 60 % ±15 %
• Reflection factor ≥ 0,8 (water surface for coax probe, metal plate for rod and rope probe with min.
1 m (40 in) diameter)
• Flange for rod or rope probe ≥ 300 mm (12 in) diameter
• Distance to obstacles ≥ 1 m (40 in)
• For interface measurement:
– Coax probe
– DC of the lower medium = 80 (water)
– DC of the upper medium = 2 (oil)
Reference accuracy Typical data under reference operating conditions: DIN EN IEC 61298-2 / DIN EN IEC 60770-1,
percentage values in relation to the span.
Interface measurement:
• Measuring distance up to 500 mm (19.7 in):
±20 mm (±0.79 in)
• Measuring distance > 500 mm (19.7 in): ±10 mm (±0.39 in)
• If the thickness of the upper medium is < 100 mm (3.94 in):
±40 mm (±1.57 in)
Endress+Hauser 37
Levelflex FMP51, FMP52, FMP54
Differing from this, the following measuring error is present in the vicinity of the lower probe
end:
D
80 (3.15)
60 (2.36) DC = 2
40 (1.57)
DC = 80
20 (0.79)
0
-20 (-0.79)
-40 (-1.57)
-60 (-2.36)
-80 (-3.15)
50 (1.97)
100 (3.94)
150 (5.91)
250 (9.84)
300 (11.8)
A
20 (0.79)
200 (7.87)
40 (1.57)
80 (3.15)
A0021480
D
80 (3.15)
60 (2.36) DC = 80
40 (1.57)
20 (0.79)
0
-20 (-0.79)
-40 (-1.57)
-60 (-2.36)
-80 (-3.15)
50 (1.97)
100 (3.94)
150 (5.91)
200 (7.87)
300 (11.8)
A
0
20 (0.79)
250 (9.84)
A0021482
38 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
D
120 (4.72)
100 (3.94)
80 (3.15) DC = 2
60 (2.36) DC = 80
40 (1.57)
20 (0.79)
0
-20 (-0.79)
-40 (-1.57)
-60 (-2.36)
-80 (-3.15)
-100 (-3.94)
-120 (-4.72)
50 (1.97)
150 (5.91)
300 (11.8)
A
0
30 (0.79)
100 (3.94)
200 (7.87)
250 (9.84)
A0021483
15 Measuring error at the end-of-probe for probes with metallic centering disk (product structure: feature
610 "Accessory mounted", option OA, OB or OC)
A Distance from probe end [mm(in)]
D Measuring error: Sum of non-linearity, non-repeatability and hysteresis
If for rope probes the DC value is less than 7, then measurement is not possible in the area of
the straining weight (0 to 250 mm from end of probe; lower blocking distance).
Endress+Hauser 39
Levelflex FMP51, FMP52, FMP54
In the area of the upper probe end, the measuring error is as follows (rod/rope only):
R
D
40 (1.57)
30 (1.18) DC = 2
DC = 80
10 (0.39)
2 (0.08)
0 (0)
- 2 (- 0.08)
- 10 (-0.39)
- 30 (- 1.18)
- 40 (- 1.57)
Resolution • digital: 1 mm
• analog: 1 μA
Reaction time The reaction time can be parametrized. The following step response times (as per DIN EN IEC
61298-2 / DIN EN IEC 60770-1) 4) are valid if the damping is switched off:
Level measurement
Interface measurement
Influence of ambient The measurements are carried out in accordance with DIN EN IEC 61298-3 / DIN EN IEC
temperature 60770-1
• digital (HART, PROFIBUS PA, FOUNDATION Fieldbus): average TK = 0.6 mm/10 K
For devices with remote sensor 5) there is an additional offset of ±0.3 mm/10K (±0.01 in/10K) per
1 m (3.3 ft) of the remote cable.
• analog (current output):
– zero point (4 mA): average TK = 0.02 %/10 K
– span (20 mA): average TK = 0.05 %/10 K
4) According to DIN EN IEC 61298-2 / DIN EN IEC 60770-1 the response time is the time which passes after a sudden change of the input signal
until the output signal for the first time assumes 90% of the steady-state value.
5) Product structure: Feature 600, options MB, MC or MD)
40 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Influence of gas layer High pressures reduce the propagation velocity of the measuring signals in the gas/vapor above the
fluid. This effect depends on the kind of gas/vapor and of its temperature. This results in a
systematic measuring error that gets bigger as the distance increases between the reference point of
the measurement (flange) and the product surface. The following table illustrates this measured
error for a few typical gases/vapors (with regard to distance; a positive value means that too large a
distance is being measured):
°C °F 1 bar (14.5 psi) 10 bar (145 psi) 50 bar (725 psi) 100 bar (1450 psi) 200 bar (2900 psi) 400 bar (5800 psi)
°C °F 1 bar 2 bar 5 bar 10 bar 20 bar 50 bar 100 bar 200 bar
(14.5 psi) (29 psi) (72.5 psi) (145 psi) (290 psi) (725 psi) (1450 psi) (2900 psi)
Gas phase compensation PROFIBUS and FOUNDATION Fieldbus devices can receive the signal of an external pressure sensor
with external pressure through the bus and use it to perform a pressure dependent time-of-flight correction. In the case of
sensor (PROFIBUS PA / saturated steam in the temperature range from 100 to 350 °C (212 to 662 °f), for example, the
FOUNDATION Fieldbus) measuring error of the distance measurement can be reduced by this method from up to 29 %
(without compensation) to less than 3 % (with compensation).
Endress+Hauser 41
Levelflex FMP51, FMP52, FMP54
Gas phase compensation Under high pressure the propagation speed of microwave signals is reduced in the steam (polar
with reference signal (option media) above the liquid to be measured. As a result, the Levelflex indicates the level too low
for FMP54) → 41.
As an option Levelflex is available in a version with automatic gas phase correction, which corrects
this error (feature 540 "Application Package", option EF: "Gas Phase Compensation Lref= 300 mm" or
EG: "Gas Phase Compensation Lref= 550 mm"). This version of the Levelflex generates a reference
reflection in the distance Lref from the flange by a diameter step of the probe rod. The reference
reflection must be at least 150 mm (6") above the highest level. By means of the shift of the
reference reflection the actual propagation speed is measured and the level value will be
automatically corrected.
(11.8/21.7)
(11.8/21.7)
300/550
300/550
Lref
Lref
Dref
iD
LN
LN
max max
150 (5.91)
150 (5.91)
min min
A0014534
17 FMP54 with reference signal for gas phase compensation; dimensions: mm (in)
Coax probes with reference reflection can be installed in any tank (free in the tank or into a
bypass). Coax probes are completely mounted and adjusted ex works. After mounting they are
ready for use, additional settings are not necessary.
Rod probes are only recommended if the installation of a coax probe is not possible (e.g. if the
bypass diameter is too small).
Rod probes with reference reflection are only suited for mounting in stilling wells and side
gauges (bypasses). The diameter Dref of the probe rod in the range of the reference distance Lref
must be chosen depending on the pipe inner diameter iD, see table below. In the range of the
reference distance Lref the pipe has to be cylindrical; changes of the cross section, for example at
flanged connections, are only allowed up to 5% of the inside diamter iD.
Additionally, the settings must be checked by an expert person after mounting and corrected if
necessary.
Inner diameter iD of the stilling well/bypass Diameter Dref of the rod probe within the reference distance
Lref
42 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Reference distance Lref 300 mm (11.8") or 550 mm (21.7"), see feature 540 of the product
structure
Area of application
Level measurements with high pressure for measuring ranges up to a few meters in polar media with
a dielectric constant DC > 7 (e.g. water or ammonia), which would cause a high measuring error
without the compensation.
The accuracy of measurement at reference conditions is the higher the larger the reference length
Lref and the samller the measuring range:
45
40
35
Lref = 300 mm
30
Delta [mm]
25
20
Lref = 550 mm
15
10
5
0 500 1000 1500 2000 2500 3000 3500 4000
D [mm]
A0014535
If there are fast changes in pressure, there may be an additional error, since the mesured reference
distance is filtered with the time constant of the level measurement. In addition, conditions of
imbalance - for example due to heating - may cause density gradients within the medium and
condensation of steam at the probe. As a result, the level readings at different locations inside the
tank may vary slightly. Caused by this application influences the measuring error may be increased
by a factor up to 2 to 3.
Endress+Hauser 43
Levelflex FMP51, FMP52, FMP54
Mounting
Mounting requirements Suitable mounting position
1 2 3
A 4
A0012606
Mounting distances
• Distance (A) between wall and rod or rope probe:
– for smooth metallic walls: > 50 mm (2 in)
– for plastic walls: > 300 mm (12 in) to metallic parts outside the vessel
– for concrete walls: > 500 mm (20 in), otherwise the available measuring range may be reduced.
• Distance (B) between rod or rope probe and internal fittings in the vessel: > 300 mm (12 in)
• When using more than one Levelflex:
Minimum distance between the sensor axes: 100 mm (3.94 in)
• Distance (C) from end of probe to bottom of the vessel:
– Rope probe: > 150 mm (6 in)
– Rod probe: > 10 mm (0.4 in)
– Coax probe: > 10 mm (0.4 in)
For coax probes the distance to the wall and to internal fittings is arbitrary.
44 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Additional conditions
• When mounting in the open, a weather protection cover (1) may be installed to protect the device
against extreme weather conditions.
• In metallic vessels: Preferably do not mount the probe in the center of the vessel (2), as this would
lead to increased interference echoes.
If a central mounting position can not be avoided, it is crucial to perform an interference echo
suppresion(mapping) after the commissioning of the device.
• Do not mount the probe in the filling curtain (3).
• Avoid buckling the rope probe during installation or operation (e.g. through product movement
against silo wall) by selecting a suitable mounting location.
With suspended rope probes (probe end not fixed at the bottom) the distance between the
probe rope and internal fittings in the tank must not fall below 300 mm (12") during the entire
process. A sporadic contact between the probe weight and the cone of the vessel, however, does
not influence the measurement as long as the dielectric constant of the medium is at least DC =
1.8.
When mounting the electronics housing into a recess (e.g. in a concrete ceiling), observe a
minimum distance of 100 mm (4 inch) between the cover of the terminal compartment /
electronics compartment and the wall. Otherwise the connection compartment / electronics
compartment is not accessible after installation.
Endress+Hauser 45
Levelflex FMP51, FMP52, FMP54
A B
6 Nm 6 Nm
(4.42 lbf ft) (4.42 lbf ft)
6 Nm 6 Nm
(4.42 lbf ft) (4.42 lbf ft)
A0014794
46 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Divisible probes
14 mm
14 mm
A0021647
If there is little mounting space (distance to the ceiling), it is advisable to use divisible rod probes (
16 mm).
• max. probe length 10 m (394 in)
• max. sideways capacity 30 Nm
• probes are separable several times with the following lengths of the individual parts:
– 500 mm (20 in)
– 1 000 mm (40 in)
• torque: 15 Nm
Endress+Hauser 47
Levelflex FMP51, FMP52, FMP54
with:
cw: Friction factor
ρ [kg/m3]: Density of the medium
v [m/s]: Velocity of the medium perpendicular to the probe rod
d [m]: Diameter of the probe rod
L [m]: Level
LN [m]: Probe length
Calculation example
L = LN (worst case) LN
v L
d
A0014175
48 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
A0014182-EN
Endress+Hauser 49
Levelflex FMP51, FMP52, FMP54
Threaded connection
A0015121
Seal
The thread as well as the type of seal comply to DIN 3852 Part 1, screwed plug form A.
They can be sealed with the following types of sealing rings:
• Thread G3/4": According to DIN 7603 with the dimensions 27 x 32 mm
• Thread G1-1/2": According to DIN 7603 with the dimensions 48 x 55 mm
Please use a sealing ring according to this standard in the form A, C or D and of a material that is
resistant to the application.
For the length of the screwed plug refer to the dimensional drawing:
• FMP51: → 81
• FMP54: → 85
50 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Nozzle mounting
£150 (6)
H
ø £150 (6)
A0015122
H Length of the center rod or the rigid part of the rope probe
Endress+Hauser 51
Levelflex FMP51, FMP52, FMP54
Probe Max. nozzle height (= length of the center rod) Option to be selected in feature 060 ("Probe")
FMP51 150 mm LA
6 inch LB
300 mm MB
12 inch MD
FMP52 150 mm OA
6 inch OC
300 mm OB
12 inch OD
52 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Endress+Hauser 53
Levelflex FMP51, FMP52, FMP54
1
3
2
A0014199
54 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
minimum maximum
EN
DN40/PN40 4 35 55
DN50/PN16 4 45 65
DN50/PN40 4 45 65
DN80/PN16 8 40 55
DN80/PN40 8 40 55
DN100/PN16 8 40 60
DN100/PN40 8 55 80
DN150/PN16 8 75 115
DN150/PN40 8 95 145
ASME
1½"/150lbs 4 20 30
1½"/300lbs 4 30 40
2"/150lbs 4 40 55
2"/300lbs 8 20 30
3"/150lbs 4 65 95
3"/300lbs 8 40 55
4"/150lbs 8 45 70
4"/300lbs 8 55 80
6"/150lbs 8 85 125
6"/300lbs 12 60 90
JIS
10K 40A 4 30 45
10K 50A 4 40 60
10K 80A 8 25 35
10K 100A 8 35 55
Endress+Hauser 55
Levelflex FMP51, FMP52, FMP54
B
2
A
A0012609
A Sag of the rope: ≥ 1 cm per 1m of the probe length (0.12 inch per 1 ft of the probe length)
B Reliably grounded end of probe
C Reliably isolated end of probe
1: Mounting and contact with a bolt
2 Mounting kit isolated
• The end of the probe needs to be secured under the following conditions:
if otherwise the probe sporadically comes into contact with the wall of the vessel, the outlet cone,
internal fittings or other parts of the installation.
• The end of probe can be secured at its internal thread
rope 4 mm (1/6"), 316: M 14
• The fixing must be either reliably grounded or reliably insulated. If it is not possible to mount the
probe weight with a reliably insulated connection, it can be secured using an isolated eyelet, which
is available as an accessory.
• In order to prevent an extremely high tensile load (e.g. due to thermal expansion) and the risk of
rope crack, the rope has to be slack. Make the rope longer than the required measuring range such
that there is a sag in the middle of the rope that is ≥ 1cm/(1 m rope length) [0.12 inch/(1 ft rope
length)].
Tensile load limit of rope probes: → 48
56 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
øa
øb
»50 (1.97)
3
ø<25 (1.0)
»3 (0.12)
»50 (1.97) 6
mm (in)
A0012607
NOTICE
Poor grounding of the end of probe may cause measuring errors.
‣ Apply a narrow sleeve which has good electrical contact to the probe.
NOTICE
Welding may damage the main electronics module.
‣ Before welding: Ground the probe and dismount electronics.
Endress+Hauser 57
Levelflex FMP51, FMP52, FMP54
A0012608
58 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
A B
C
1
ød
2
(3.94)
³100
3 ød
(3.94)
³100
øD
2
4
A0012615
20 Dimensions: mm (in)
A Mounting in a stilling well
B Mounting in a bypass
C Center washer or centering star
1 Metallic center washer (316L) for level measurement
2 Fixing screw; torque: 25 Nm ± 5 Nm
3 Non-metallic centering star (PEEK, PFA) for interface measurement
4 Minimum distance between end of probe and lower edge of the bypass; see table below
Allocation of probe type and center washer or centering star to pipe diameter
Feature 610 - Accessory mounted
Minimum distance between end of probe and lower edge of the bypass
Type of probe Minimum distance
Endress+Hauser 59
Levelflex FMP51, FMP52, FMP54
60 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
A0014141
Endress+Hauser 61
Levelflex FMP51, FMP52, FMP54
Underground tanks
A0014142
Use a coax probe for nozzles with large diameters in order to avoid reflections at the nozzle wall.
62 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Installation at an angle
LN
a
A0014145
Endress+Hauser 63
Levelflex FMP51, FMP52, FMP54
Non-metallic vessels
A0012527
1 Non-metallic vessel
2 Metal sheet or metal flange
64 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
1
3
A0014150
Requirements
• The dielectric constant of the medium must be at least DC > 7.
• The tank wall must be non-conductvie.
• Maximum wall thickness (a):
– Plastic: < 15 mm (0.6")
– Glass: < 10 mm (0.4")
• There may be no metallic reinforcements fixed to the tank.
Mounting conditions:
• The probe must be mounted directly to the tank wall (no open space)
• A plastic half pipe with a diameter of approx. 200 mm (8"), or some other protective unit, must be
affixed externally to the probe to prevent any influences on the measurement.
• If the tank diameter is less than 300 mm (12"):
A metallic grounding sheet must be installed at the opposite side of the tank. The sheet must be
conductively connected to the process connection and cover about the half of the vessel's
circumference.
• If the tank diameter exceeds 300 mm (12"):
A metal sheet with a diameter of at least 200 mm (8") must be mounted to the probe at the
process connection. Its orientation must be perpendicular to the probe (see above).
Endress+Hauser 65
Levelflex FMP51, FMP52, FMP54
2 3
1
MAX MAX
A0014653
2 3
40 (1.57)
40 (1.57)
1
MAX MAX
mm (in)
A0014654
A0014657
66 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
2 3
2 3
MAX MAX MAX MAX
1 1
A0014658
Endress+Hauser 67
Levelflex FMP51, FMP52, FMP54
A0014153
Planning instructions:
• In normal cases, use a rod probe. When installing into a metallic displacer chamber up to 150 mm,
you have all the advantages of a coax probe.
• It must be ensured that the probe does not come into contact with the side wall. Where necessary,
use a center washer or centering star at the lower end of the probe (feature 610 of the product
structure).
• The center washer or centering star must be adapted as accurately as possible to the internal
diameter of the displacer chamber to also ensure perfect operation in the area of the probe end.
Additional information on interface measurement
• In the case of oil and water the centering disk or centering star should be positioned at the lower
edge of the lower disposal (water level).
• The pipe may not exhibit any steps in diameter. Use the coax probe where necessary.
• In the case of rod probes, it must be ensured that the probe does not come into contact with the
wall. If necessary, use a center washer or centering star at the end of the probe.
• A plastic centering star has to be used for interface measurement (feature 610, options OD and
OE).
68 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Local display –20 to +70 °C (–4 to +158 °F), the readability of the display may be impaired at
temperatures outside the temperature range.
1) This range is valid if option JN "Ambient temperature transmitter –50 °C (–58 °F)" has been selected in
ordering feature 580 "Test, Certificate". If the temperature is permanently below –40 °C (–40 °F), failure
rates may be increased.
Ambient temperature limits The following diagrams take into account only function requirements. There may be further
restrictions for certified device versions. Please refere to the separate Safety Instructions → 134.
Endress+Hauser 69
Levelflex FMP51, FMP52, FMP54
With a temperature (Tp) at the process connection the admissible ambient temperature (Ta) is
reduced according to the following diagram (temperature derating):
[°C] ([°F])Ta
Ta
+80 (+176)
GT20: +58(+136)
Tp
GT18: +48(+118)
A: 4...20 mA HART GT19: +29(+84)
-40/-50 (-40/-58)³ Tp
-40 +82 +200 [°C]
(-40) (+180) (+392) ([°F])
[°C] ([°F])Ta +79
(+174)
GT18/20: +79 (+174)
GT19: +74 (+165) GT20: +54(+129)
C: 4...20 mA HART
4...20 mA GT18: +48(+118)
L: 10.4...48 VDC
-40/-50 (-40/-58)³ Tp
-40 +74 +200 [°C]
(-40) (+165) (+392) ([°F])
[°C] ([°F])Ta
+81 (+178)
GT20: +57(+134)
GT18: +48(+118)
G 1: PROFIBUS PA
FOUNDATION Fieldbus
-40 (-40) Tp
-40 +81 +200 [°C]
(-40) (+178) (+392) ([°F])
[°C] ([°F])Ta
+79 (+174)
GT20: +54(+129)
GT18: +48(+118)
2
G : PROFIBUS PA
FOUNDATION Fieldbus
Switch output
-40 (-40) Tp
-40 +79 +200 [°C]
(-40) (+174) (+392) ([°F])
A0013687
70 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
[°C] ([°F])Ta
Ta
+80(+176)
GT20: +57(+135)
Tp
GT18: +49(+120)
Endress+Hauser 71
Levelflex FMP51, FMP52, FMP54
[°C] ([°F])Ta
Ta
+80(+176)
GT20: +59(+138)
Tp
GT18: +53(+127)
GT19: -34(-29) A: 4...20 mA HART GT19: +33(+91)
GT18: -37(-34)
GT20: -38(-36)
-40(-40)³ Tp
-50 -40 +82 +200 [°C]
(-58) (-40) (+180) (+392) ([°F])
[°C] ([°F])Ta +79
(+174)
GT18/20: +79 (+174)
GT19: +74 (+165)
GT20: +55(+131)
C: 4...20 mA HART GT18: +51(+124)
4...20 mA
GT19: +33(+91)
GT19: -34(-29) K: 90...253 VAC
GT18: -37(-34)
GT20: -38(-36) L: 10.4...48 VDC
-40(-40)³ Tp
-50 -40 +74 +200 [°C]
(-58) (-40) (+165) (+392) ([°F])
[°C] ([°F])Ta
+81 (+178)
GT20: +58(+136)
GT18: +53(+127)
1
G : PROFIBUS PA
FOUNDATION Fieldbus
GT18: -37(-35)
GT20: -38(-36)
-40(-40)³ Tp
-50 -40 +81 +200 [°C]
(-58) (-40) (+178) (+392) ([°F])
[°C] ([°F])Ta
+79 (+174)
GT20: +55(+131)
2
PROFIBUS PA GT18: +51(+124)
G :
FOUNDATION Fieldbus
Switch output
GT18: -37(-35)
GT20: -38(-36)
-40(-40)³ Tp
-50 -40 +79 +200 [°C]
(-58) (-40) (+174) (+392) ([°F])
A0013689
72 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
T a [°C] ([°F])Ta
+80(+176)
GT20: +60(+140)
Tp GT18: +53(+127)
GT19: +38(+100)
GT19: -36(-33) A: 4...20 mA HART
GT18: -37(-35)
GT20: -38(-36)
-40(-40) Tp
-50 -40 +82 +200 [°C]
(-58) (-40) (+180) (+392) ([°F])
[°C] ([°F])Ta +79
(+174)
GT18/20: +79 (+174)
GT19: +74 (+165) GT20: +56(+133)
C: 4...20 mA HART GT18: +51(+124)
4...20 mA GT19: +38(+100)
GT19: -36(-33) K: 90...253 VAC
GT18: -37(-35)
GT20: -38(-36) L: 10.4...48 VDC
-40(-40) Tp
-50 -40 +74 +200 [°C]
(-58) (-40) (+165) (+392) ([°F])
[°C] ([°F])Ta
+81(+178)
GT20: +59(+138)
GT18: +53(+127)
G 1: PROFIBUS PA
FOUNDATION Fieldbus
GT18: -37(-35)
GT20: -38(-36)
-40(-40) Tp
-50 -40 +81 +200 [°C]
(-58) (-40) (+178) (+392) ([°F])
[°C] ([°F])Ta
+79(+174)
GT20: +56(+133)
GT18: +51(+124)
2
G : PROFIBUS PA
FOUNDATION Fieldbus
Switch output
GT18: -37(-35)
GT20: -38(-36)
-40(-40) Tp
-50 -40 +79 +200 [°C]
(-58) (-40) (+174) (+392) ([°F])
A0013633
1) For PROFIBUS PA and FOUNDATION Fieldbus the temperature derating depends on the usage of the
switch output. (G1: switch output not connected; G2: switch output connected).
2) For saturated steam applications the process temperature should not exceed 150 °C (302 °F). For higher
process temperatures use FMP54.
Endress+Hauser 73
Levelflex FMP51, FMP52, FMP54
T a [°C] ([°F])Ta
+80(+176)
Tp GT20: +62(+144)
GT18: +56(+133)
GT19: +42(+108)
GT19: -5(+23) A: 4...20 mA HART
GT18: -16(+3)
GT20: -23(-9)
-40/-50 (-40/-58)³ Tp
-196 -40 +82 +280 [°C]
(-321) (-40) (+180) (+536) ([°F])
[°C] ([°F])Ta +79
(+174)
GT18/20: +79 (+174)
GT19: +74 (+165) GT20: +59(+138)
GT18: +52(+126)
C: 4...20 mA HART
GT19: +42(+108)
4...20 mA
GT19: -5(+23)
K: 90...253 VAC
GT18: -16(+3)
GT20: -23(-9) L: 10.4...48 VDC
-40/-50 (-40/-58)³ Tp
-196 -40 +74 +280 [°C]
(-321) (-40) (+165) (+536) ([°F])
[°C] ([°F])Ta
+81 (+178)
GT20: +61(+142)
GT18: +55(+130)
G 1: PROFIBUS PA
FOUNDATION Fieldbus
GT18: -16(+3)
GT20: -23(-9)
-40 (-40) Tp
-196 -40 +81 +280 [°C]
(-321) (-40) (+178) (+536) ([°F])
[°C] ([°F])Ta
+79 (+174)
GT20: +58(+137)
GT18: +55(+126)
2
G : PROFIBUS PA
FOUNDATION Fieldbus
Switch output
GT18: -16(+3)
GT20: -23(-9)
-40 (-40) Tp
-196 -40 +79 +280 [°C]
(-321) (-40) (+174) (+536) ([°F])
A0013631
74 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
[°C] ([°F])Ta
Ta
+80(+176)
GT20: +56(+133)
Tp GT18: +54(+129)
[°C] ([°F])Ta
+81(+178)
GT20: +55(+131)
GT18: +53(+127)
G 1: PROFIBUS PA
FOUNDATION Fieldbus
GT18: -27(-16)
GT20: -28(-18)
-40 (-40) Tp
-196 -40 +81 +450 [°C]
(-321) (-40) (+178) (+842) ([°F])
[°C] ([°F])Ta
+79(+174)
GT20: +52(+126)
GT18: +50(+123)
2
G : PROFIBUS PA
FOUNDATION Fieldbus
Switch output
GT18: -27(-16)
GT20: -28(-18)
-40 (-40) Tp
-196 -40 +79 +450 [°C]
(-321) (-40) (+173) (+842) ([°F])
A0013632
Endress+Hauser 75
Levelflex FMP51, FMP52, FMP54
Cleaning the probe Depending on the application, contamination or buildup can accumulate on the probe. A thin, even
layer only influences measurement slightly. Thick layers can dampen the signal and then reduce the
measuring range. Severe, uneven buildup, adhesion e.g. through crystallization, can lead to incorrect
measurement. In this case, we recommend that you use a non-contact measuring principle, or check
the probe regularly for soiling.
Electromagnetic Electromagnetic compatibility to all relevant requirements of the EN 61326- series and NAMUR
compatibility (EMC) recommendation EMC (NE21). For details see declaration of conformity. 10). If only the analogue
signal is used, unshielded interconnection lines are sufficient for the installation. In case of using the
digital signal (HART/ PA/ FF) use shielded interconnection lines.
Use a shielded cable when working with a digital communications signal.
Max. fluctuations during EMC- tests: < 0.5 % of the span.
When installing the probes in metal and concrete tanks and when using a coax probe:
• Interference emission to EN 61326 - x series, electrical equipment Class B.
• Interference immunity to EN 61326 - x series, requirements for industrial areas and NAMUR
Recommendation NE 21 (EMC)
The measured value can be affected by strong electromagnetic fields when installing rod and rope
probes without a shielding/metallic wall, e.g. in plastic and wooden silos.
• Interference emission to EN 61326 - x series, electrical equipment Class A.
• Interference immunity: the measured value can be affected by strong electromagnetic fields.
7) This range is valid if option JN "Ambient temperature transmitter –50 °C (–58 °F)" has been selected in ordering features 580 "Test, Certificate". If
the temperature is permanently below –40 °C (–40 °F), failure rates may be increased.
8) also valid for the "Sensor remote" version
9) This restriction is valid if the following options of the product structure have been selected at the same time: 030 ("Display, Operation") = C
("SD02") or E ("SD03"); 040 ("Housing") = A ("GT19").
10) Can be downloaded from www.endress.com.
76 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Process
Process temperature range The maximum permitted temperature at the process connection is determined by the O-ring version
ordered:
FMP51 FKM (Viton GLT 37559) –30 to +150 °C (–22 to +302 °F)
FMP52 — –50 to +200 °C (–58 to +392 °F); completely coated FDA, 3A,
EHEDG, USP
Cl. VI 3)
For FMP52: High process temperatures (> 150 °C (302 °F)) may possibly accelerate diffusion of
the process medium through the probe coating, which may reduce the operating time.
The sensor material 1.4404/316L is resistant against attacks by internal corrosion according to
AD 2000 - instruction sheet W2 for operating temperatures up to 400 °C (752 °F) and
operating times of 100,000 hours (11.4 years). In case of higher temperatures the suitability of
the material must be checked by the operator. Acids, in particular, may cause corrosion attacks.
With uncoated probes, the medium temperature may be higher, under the condition that the
maximum process temperature specified in the table above is not exceeded at the process
connection.
However, when using rope probes, the stability of the probe rope is reduced by structural
changes at temperatures above 350 °C (662 °F).
Endress+Hauser 77
Levelflex FMP51, FMP52, FMP54
[bar] ([psi]) p
420 (6090)
400 (5800)
380 (5510)
350 (5075)
320 (4640)
300 (4350) Tp
-196 -100 0 +100 200 300 400 450 [°C]
(-321) (-148) (+32) (+212) (+392) (+572) (+752) (+842) ([°F])
A0014005
Expansion of the rope probes Elongation through temperature increase from 30 °C (86 °F) to 150 °C (302 °F): 2 mm / m rope
through temperature length
78 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Mechanical construction
Dimensions Dimensions of the electronics housing
R110 98 (3.86)*
78 (3.07) 90 (3.54)
07)
(4.
3.5
146 (5.75)
ø108.5 (4.27)
142 (5.59)
115.25 (4.54)
ø10
A0011666
R110
99 (3.9)*
78 (3.07) 90 (3.54)
)
.17
6 (4
144 (5.67)
ø106 (4.17)
ø10
113.5 (4.47)
A0011346
R110 98 (3.86)*
78 (3.07) 90 (3.54)
07)
(4.
ø112 (4.41)
145.5 (5.73)
3.5
141.5 (5.57)
ø108.5 (4.27)
ø10
61 (2.4)
A0020751
Endress+Hauser 79
Levelflex FMP51, FMP52, FMP54
A B
ø42...60
(1.65...2.36)
52 (2)
122 (4.8) 127...140
161 (6.34) (5...5.51)
162...175
(6.38...6.89)
(3.4)
(2.8)
86
70
A0014793
For the "Sensor remote" device version (see feature 060 of the product structure), the mounting
bracket is part of the delivery. If required, it can also be ordered as an accessory (order code
71102216).
122(4.8)
(2.05)
52
15 (0.6)
ø10
(0. .2
4)
(2.4)
61
43 (1.7)
ø82.5
(3.25)
A0023856
29 Connection piece for the remote probe; dimensions: mm (in); Length of the connecting cable: as ordered
80 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
(0.98)
25
(2.72)
SW36
69
AF36
R G¾
NPT¾
E F G H
ø4 (0.16) ø4 (0.16)
ø8 (0.31) ø22 (0.87)
LN
150 (5.91)
20 (0.79)
12 (0.47)
4 (0.16)
2 (0.08)
A0012645
Endress+Hauser 81
Levelflex FMP51, FMP52, FMP54
B C D
78 (3.1)
78 (3.1)
78 (3.1)
(0.98)
(1.02)
25
26
SW55 SW55
AF55 AF55
R
G1½ NPT1½
I J K L M N
(1.54)
39
SW10
AF10 SW14
SW10 AF14
AF10 SW10 ø16 (0.63)
ø4 (0.16) AF10
1000 (39.4)
LN
ø12 (0.47)
40 (1.57)
SW14
AF14
2.2 (0.09)
min. 50 (1.97)
max. 551 (21.7)
max. 1051 (41.4)
150 (5.91)
20 (0.79)
12 (0.47)
4 (0.16)
P
9 (0.35)
Q Q
S
82 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
OA Rod center washer 316L; pipe diameter DN80/3" + DN100/4" S = 4 mm (0.16 in) T = 75 mm (2.95 in)
OB Rod center washer 316L; pipe diameter DN50/2" + DN65/2-1/2" S = 4 mm (0.16 in) T = 45 mm (1.77 in)
OC Rod center washer 316L; pipe diameter DN80/3" + DN100/4" S = 4 mm (0.16 in) T = 75 mm (2.95 in)
OD Rod centering star PEEK; interface measurement; pipe diameter S = 7 mm (0.28 in) T = 48 to 95 mm (1.9 to 3.7 in)
DN50/2" + DN100/4"
OE Rod centering star PFA; interface measurement; pipe diameter P = 10 mm (0.39 in) Q = 37 mm (1.46 in)
DN40/1-1/2" + DN50/2"
M40
8 (0.31)
A0035223
Endress+Hauser 83
Levelflex FMP51, FMP52, FMP54
A B C D E
64 91
2.52 3.58
(3.19)
(3.23)
(3.31)
(3.23)
(3.23)
81
82
84
82
82 R
F G
ø16 (0.63)
ø16 (0.63)
LN
ø4 (0.16)
ø37 (1.46)
118 (4.65)
ø22 (0.87)
A0012757
84 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
A B C D
132 (5.2)
132 (5.2)
342 (13.5)
315 (12.4)
SW60 SW60
267 (10.5)
SW60 AF60 SW60 AF60
240 (9.45)
AF60 AF60
159 (6.26)
159 (6.26)
ø90 ø90
ø90 ø90 (3.54) (3.54)
(3.54) (3.54)
R
SW14
37 (1.46)
SW14 SW14
37 (1.46)
SW14
8 (0.31)
8 (0.31)
8 (0.31)
8 (0.31)
AF14
AF14 AF14 AF14
E F G H I
ø16 (0.63)
SW14 SW14
AF14 AF14
ø16 (0.63) 1000 (39.4)
500 (19.7)
SW14
AF14
LN
ø4 (0.16) ø4 (0.16)
SW14
SW14 AF14
AF14
SW14
2.2 (0.09)
max. 1051 (41.4)
min. 50 (1.97)
M AF14
150 (5.91)
20 (0.79)
12 (0.47)
L
9 (0.35)
4 (0.16)
2 (0.08)
M
N
A0012778
Endress+Hauser 85
Levelflex FMP51, FMP52, FMP54
N Thickness of the center washer or centering star; table of values: see below
O Diameter of the center washer or centering star; table of values: see below
R Reference point of the measurement
OA Rod center washer 316L; pipe diameter DN80/3" + DN100/4" N = 4 mm (0.16 in) O = 75 mm (2.95 in)
OB Rod center washer 316L; pipe diameter DN50/2" + DN65/2-1/2" N = 4 mm (0.16 in) O = 45 mm (1.77 in)
OC Rod center washer 316L; pipe diameter DN80/3" + DN100/4" N = 4 mm (0.16 in) O = 75 mm (2.95 in)
OD Rod centering star PEEK; interface measurement; pipe diameter N = 7 mm (0.28 in) O = 48 to 95 mm (1.9 to 3.7 in)
DN50/2" + DN100/4"
OE Rod centering star PFA; interface measurement; pipe diameter L = 10 mm (0.39 in) M = 37 mm (1.46 in)
DN40/1-1/2" + DN50/2"
86 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Admissible tolerance [mm -5 (-0,2) -10 (-0,39) -20 (-0,79) -30 (-1,18)
(in)]
Rope probes
Admissible tolerance [mm -10 (-0,39) -20 (-0,79) -30 (-1,18) -40 (-1,57)
(in)]
Surface roughness of AlloyC- Ra = 3.2 μm; lower surface roughness levels are available on request.
coated flanges
This value is valid for flanges with "AlloyC>316/316L"; see product structure, feature 100 "Process
connection". For other flanges the surface roughness matches the corresponding flange standard.
Shortening probes If necessary, probes can be shortened. When doing so, the following must be observed:
Endress+Hauser 87
Levelflex FMP51, FMP52, FMP54
Weight Housing
Part Weight
Sensor approx. 0.8 kg Rod probe 8 mm approx. 0.4 kg/m probe length
Rope probe 4 mm approx. 0.,1 kg/m probe length Coax probe approx. 1.2 kg/m probe length
Sensor approx. 1.2 kg + weight of flange Rod probe 16 mm approx. 1.1 kg/m probe length
Rope probe 4 mm approx. 0.1 kg/m probe length Coax probe approx. 3.0 kg/m probe length
FMP52
Part Weight Part Weight
Sensor approx. 1.2 kg + weight of flange Rope probe 4 mm approx. 0.5 kg/m probe length
FMP54
Part Weight Part Weight
Sensor - version approx. 6.7 kg + weight of flange Rope probe 4 mm approx. 0.1 kg/m probe length
XT
Sensor - version approx. 7.7 kg + weight of flange Rod probe 16 mm approx. 1.6 kg/m probe length
HT
88 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
5.2
6
5.1
7
4 3 9 8
A0013788
5.1 Dummy plug, cable gland, adapter or plug • Dummy plug, depending on the device version:
(depending on the device version) – PE
– PBT-GF
• Cable gland: 316L (1.4404) or nickel-plated brass
• Adapter: 316L (1.4404/1.4435)
• Seal: EPDM
• M12 plug: Nickel-plated brass 1)
• 7/8" plug: 316 (1.4401) 2)
5.2 Dummy plug, cable gland or adapter (depending on • Dummy plug: 316L (1.4404)
the device version) • Cable gland: 316L (1.4404) or nickel-plated brass
• Adapter: 316L (1.4404/1.4435)
• Seal: EPDM
6 Dummy plug or M12 socket (depending on the • Dummy plug: 316L (1.4404)
device version) • M12 socket: 316L (1.4404)
1) For the version with M12 plug the sealing material is Viton.
2) For the version with 7/8" plug, the sealing material is NBR.
Endress+Hauser 89
Levelflex FMP51, FMP52, FMP54
5.2
6
5.1
7
4 9 8
A0013788
1 Housing PBT
5.1 Dummy plug, cable gland, adapter or plug • Dummy plug, depending on the device version:
(depending on the device version) – PE
– PBT-GF
• Cable gland, depending on the device version:
– Nickel-plated brass (CuZn)
– PA
• Adapter: 316L (1.4404/1.4435)
• Seal: EPDM
• M12 plug: Nickel-plated brass 1)
• 7/8" plug: 316 (1.4401) 2)
5.2 Dummy plug, cable gland or adapter (depending on • Dummy plug, depending on the device version:
the device version) – PE
– PBT-GF
– Nickel-plated steel
• Cable gland, depending on the device version:
– Nickel-plated brass (CuZn)
– PA
• Adapter: 316L (1.4404/1.4435)
• Seal: EPDM
6 Dummy plug or M12 socket (depending on the • Dummy plug: Nickel-plated brass (CuZn)
device version) • M12 socket: Nickel-plated GD-Zn
1) For the version with M12 plug the sealing material is Viton.
2) For the version with 7/8" plug, the sealing material is NBR.
90 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
5.2
6
5.1
7
4 3 9 8
A0013788
2.1 Cover of the electronics compartment; RAL 7035 • Cover: AlSi10Mg(<0,1% Cu)
(gray) • Window: Glass
• Cover seal: NBR
• Seal of the window: NBR
• Thread-coating: Graphite-based lubricant varnish
2.2 Cover of the terminal compartment; RAL 7035 • Cover: AlSi10Mg(<0,1% Cu)
(gray) • Cover seal: NBR
• Thread-coating: Graphite-based lubricant varnish
5.1 Dummy plug, cable gland, adapter or plug • Dummy plug, depending on the device version:
(depending on the device version) – PE
– PBT-GF
• Cable gland, depending on the device version:
– Nickel-plated brass (CuZn)
– PA
• Adapter: 316L (1.4404/1.4435)
• Seal: EPDM
• M12 plug: Nickel-plated brass 1)
• 7/8" plug: 316 (1.4401) 2)
5.2 Dummy plug, cable gland or adapter (depending on • Dummy plug, depending on the device version:
the device version) – PE
– PBT-GF
– Nickel-plated steel
• Cable gland, depending on the device version:
– Nickel-plated brass (CuZn)
– PA
• Adapter: 316L (1.4404/1.4435)
• Seal: EPDM
6 Dummy plug or M12 socket (depending on the • Dummy plug : Nickel-plated brass (CuZn)
device version) • M12 socket: Nickel-plated GD-Zn
Endress+Hauser 91
Levelflex FMP51, FMP52, FMP54
1) For the version with M12 plug the sealing material is Viton.
2) For the version with 7/8" plug, the sealing material is NBR.
92 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Materials: Process Endress+Hauser supplies DIN/EN flanges and threaded process connections made of stainless
connection steel according to AISI 316L (DIN/EN material number 1.4404 or 1.4435). With regard to their
temperature stability properties, the materials 1.4404 and 1.4435 are grouped under 13E0 in
EN 1092-1:2007 Tab. G.3.1-1. The chemical composition of the two materials can be identical.
Levelflex FMP51
Levelflex FMP52
1 316L (1.4404)
1 2 ASME: 316/316L
1 1 EN: 316L (1.4404)
3 1
2
3
JIS: 316L (1.4435)
5 3 3 3 316L (1.4404)
4 4 4 4 4 4 Coating 2 mm (0.08 in): PTFE (Dyneon USP Cl. VI 1)
A0013868
A0013865
A0013866 A0013867
A0013869
TFM1600)
5 304L (1.4307)
1) Plastic parts in contact with process have been tested according to USP <88> Class VI-70°C.
Levelflex FMP54
1 316L (1.4404)
1 1 2 316L (1.4404)
1 1
3 ASME: 316/316L
EN: 316L (1.4404)
2
7 2 7 2 JIS: 316L (1.4435)
2
7 7 3
4 Alloy C22 (2.4602)
3 4
4
5
4 5 5 316L (1.4404)
4 5 6
5 6 6 Nordlock washer: 1.4547
6 A0013883
6 A0013882
A0013880 A0013881
7 Ceramic Al2O3 99.7 %, pure graphite
Endress+Hauser 93
Levelflex FMP51, FMP52, FMP54
4 mm
(1/6") 12.7 Thread Thread No. Material
4 mm 8 mm Thread
with mm (1/2") G1-1/2 G1-1/2
(1/6") (1/3") G3/4
centering AlloyC AlloyC 316L
disk
Levelflex FMP51
Rod probe
1 316L (1.4404)
1
12
11
A0013860 A0013861
94 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Levelflex FMP52
1 316L (1.4404)
1 1
2 Coating 2 mm (0.08 in): PFA (Daikin PFA AP230)
5 2
2
A0013870 A0013871
Levelflex FMP54
1) For probes with gas phase compensation this is also the material of the reference rod.
Endress+Hauser 95
Levelflex FMP51, FMP52, FMP54
12
12
11
10
A0015143
Screw/nuts A4-70
96 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
4 3
A0021722
1 Cable FRNC
Screw A4-70
Endress+Hauser 97
Levelflex FMP51, FMP52, FMP54
Materials: Weather
protection cover 1
2
3
7 4
5
6
A0015473
No Part: Material
6 Ground terminal
• Screw: A4
• Spring washer: A4
• Clamp: 316L (1.4404)
• Holder: 316L (1.4404)
7 • Washer: A4
• Cheese head screw: A4-70
98 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Operability
Operating concept Operator-oriented menu structure for user-specific tasks
• Commissioning
• Operation
• Diagnostics
• Expert level
Operating languages
• English
• Deutsch
• Français
• Español
• Italiano
• Nederlands
• Portuguesa
• Polski
• русский язык (Russian)
• Svenska
• Türkçe
• 中文 (Chinese)
• 日本語 (Japanese)
• 한국어 (Korean)
• Bahasa Indonesia
• tiếng Việt (Vietnamese)
• čeština (Czech)
Feature 500 of the product structure determines which of these languages is preset on delivery.
Endress+Hauser 99
Levelflex FMP51, FMP52, FMP54
A0032219 A0032221
Format for displaying measured variables and status variables can be individually configured
Permitted ambient temperature for the display: –20 to +70 °C (–4 to +158 °F)
The readability of the display may be impaired at temperatures outside the temperature
range.
Operating local operation with 3 push buttons (, , external operation via touch control; 3 optical
elements ) keys: , ,
A0032215
100 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
2 3 6 8
1 4 5 7
A0028746
2 3
PROFIBUS DP
ENDRESS + HAUSER
PROFIBUS PA
T
4 4 4
A0015775
1 Segment coupler
2 Computer with Profiboard/Proficard and operating tool (e.g. DeviceCare/FieldCare
3 PLC (Progrommable Logic Controller)
4 Transmitter
5 Additional functions (valves etc.)
Endress+Hauser 101
Levelflex FMP51, FMP52, FMP54
IN
BT
FF-HSE
1
FF-H1 SB 2
PS BT
LD 4
3
BT ENDRESS + HAUSER
– +
%
PS
FF-H1
BT
1
2
A0017188
IN Industrial network
SB Safety Barrier
BT Bus Terminator
102 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
1
A0032466
1 Service interface (CDI) of the measuring device (= Endress+Hauser Common Data Interface)
2 Commubox FXA291
3 Computer with DeviceCare/FieldCare operating tool
Endress+Hauser 103
Levelflex FMP51, FMP52, FMP54
Integration in tank gauging The Endress+Hauser Tank Side Monitor NRF590 provides integrated communications for sites with
system multiple tanks, each with one or more sensors on the tank, such as radar, spot or average
temperature, capacitive probe for water detection and/or pressure sensors. Multiple protocols out of
the Tank Side Monitor guarantee connectivity to nearly any of the existing industry standard tank
gauging protocols. Optional connectivity of analog 4...20 mA sensors, digital I/O and analog output
simplify full tank sensor integration. Use of the proven concept of the intrinsically safe HART bus for
all on-tank sensors yields extremely low wiring costs, while at the same time providing maximum
safety, reliability and data availability.
1 2 3
4 5
8 NXA820
16...253 VAC
A0016590
104 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
SupplyCare inventory SupplyCare is a web-based operating program for coordinating the flow of material and information
management software along the supply chain. SupplyCare provides a comprehensive overview of the levels of
geographically distributed tanks and silos, for instance, providing complete transparency over the
current inventory situation, regardless of time and location.
Based on the measuring and transmission technology installed onsite, the current inventory data are
collected and sent to SupplyCare. Critical levels are clearly indicated and calculated forecasts provide
additional security for material requirements planning.
The main functions of SupplyCare:
Inventory visualization
SupplyCare determines the inventory levels in tanks and silos at regular intervals. It displays current
and historical inventory data and calculated forecasts of future demand. The overview page can be
configured to suit the user's preferences.
Master data management
With SupplyCare you can create and manage the master data for locations, companies, tanks,
products and users, as well as user authorization.
Report Configurator
The Report Configurator can be used to create personalized reports quickly and easily. The reports
can be saved in a variety of formats, such as Excel, PDF, CSV and XML. The reports can be
transmitted in many ways, such as by http, ftp or e-mail.
Event management
Events, such as when levels drop below the safety stock level or plan points, are indicated by the
software. In addition, SupplyCare can also notify pre-defined users by e-mail.
Alarms
If technical problems occur, e.g. connection issues, alarms are triggered and alarm e-mails are sent to
the System Administrator and the Local System Administrator.
Delivery planning
The integrated delivery planning function automatically generates an order proposal if a pre-set
minimum inventory level is undershot. Scheduled deliveries and disposals are monitored
continuously by SupplyCare. SupplyCare notifies the user if scheduled deliveries and disposals are not
going to be met as planned.
Analysis
In the Analysis module, the most important indicators for the inflow and outflow of the individual
tanks are calculated and displayed as data and charts. Key indicators of material management are
automatically calculated and form the basis for optimizing the delivery and storage process.
Geographical visualization
All the tanks and the tank inventories are represented graphically on a map (based on Google Maps).
The tanks and inventory situations can be filtered by tank group, product, supplier or location.
Multi-language support
The multi-language user interface supports 9 languages, thereby enabling global collaboration on a
single platform. The language and settings are recognized automatically using the browser settings.
SupplyCare Enterprise
SupplyCare Enterprise runs by default as a service under Microsoft Windows on an application server
in an Apache Tomcat environment. The operators and administrators operate the application via a
Web browser from their workstations.
Endress+Hauser 105
Levelflex FMP51, FMP52, FMP54
2
3
10
5 7 8
9
.
A0034288
106 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
1
3
WWW
4
10
5 7 8
9
.
A0034289
With SupplyCare Hosting, users do not need to make the initial software purchase or install and run
the IT infrastructure needed. Endress+Hauser constantly update SupplyCare Hosting and enhance
the capability of the software in conjunction with the customer. The hosted version of SupplyCare is
thus always up-to-date and can be customized to meet different customer requirements. Other
services are also offered in addition to the IT infrastructure and the software that is installed in a
secure, redundant Endress+Hauser data center. These services include defined availability of the
global Endress+Hauser Service and Support Organization and defined response times in a service
event.
Endress+Hauser 107
Levelflex FMP51, FMP52, FMP54
CE mark The measuring system meets the legal requirements of the applicable EC guidelines. These are listed
in the corresponding EC Declaration of Conformity together with the standards applied.
Endress+Hauser confirms successful testing of the device by affixing to it the CE mark.
RoHS The measuring system complies with the substance restrictions of the Restriction on Hazardous
Substances Directive 2011/65/EU (RoHS 2).
RCM-Tick marking The supplied product or measuring system meets the ACMA (Australian Communications and Media
Authority) requirements for network integrity, interoperability, performance characteristics as well
as health and safety regulations. Here, especially the regulatory arrangements for electromagnetic
compatibility are met. The products are labelled with the RCM- Tick marking on the name plate.
A0029561
Ex approval The devices are certified for use in hazardous areas and the relevant safety instructions are provided
in the separate "Safety Instructions" (XA) document. Reference is made to this document on the
nameplate.
The separate documentation "Safety Instructions" (XA) containing all the relevant explosion
protection data is available from your Endress+Hauser Sales Center. Correlation of
documentations to the device → 134.
Dual seal according to The devices have been designed according to ANSI/ISA 12.27.01 as dual seal devices, allowing the
ANSI/ISA 12.27.01 user to waive the use and save the cost of installing external secondary process seals in the conduit
as required by the process sealing sections of ANSI/NFPA 70 (NEC) and CSA 22.1 (CEC) These
instruments comply with the North-American installation practice and provide a very safe and cost-
saving installation for pressurized applications with hazardous fluids.
Further information can be found in the Safety Instructions (XA) of the relevant devices.
Functional Safety Used for level monitoring (MIN, MAX, range) up to SIL 3 (homogeneous redundancy), independently
assessed by TÜV Rhineland as per IEC 61508. Other information see documentation SD00326F:
"Functional Safety Manual".
108 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Sanitary compatibility The following table shows which device versions meet the requirements of 3A-Sanitary Standard No.
74 and are certified by the EHEDG.
FMP52
060: Probe CA
Rod 16mm PFA>316L
CB
Rod 0.63 in PFA>316L
TLK
Tri-Clamp ISO2852 DN70-76.1 (3"), PTFE>316L
TNK
Tri-Clamp ISO2852 DN38 (1-1/2"), PTFE>316L
Suitable fittings and seals must be used to ensure hygiene-compliant design according to the
specifications of 3A and EHEDG.
The gap-free connections can be cleaned without residue using the usual cleaning methods (CIP
and SIP).
Wetted non-metallic parts of the FMP52 conform to FDA 21 CFR 177.1550 and USP Class VI.
ASME B31.1 and B31.3 • The dimensions, materials of construction, pressure / temperature ratings and identification
markings of the device comply with the requirements of AMSE B31.1 and ASME B31.3
• Declaration of conformity: see product structure, feature 580, option KV.
Pressure equipment with Pressure instruments with a flange and threaded boss that do not have a pressurized housing do not
allowable pressure fall within the scope of the Pressure Equipment Directive, irrespective of the maximum allowable
≤ 200 bar (2 900 psi) pressure.
Reasons:
According to Article 2, point 5 of EU Directive 2014/68/EU, pressure accessories are defined as
"devices with an operational function and having pressure-bearing housings".
If a pressure instrument does not have a pressure-bearing housing (no identifiable pressure chamber
of its own), there is no pressure accessory present within the meaning of the Directive.
Endress+Hauser 109
Levelflex FMP51, FMP52, FMP54
Pressure equipment with Pressure equipment designated for application in every process fluid having a pressurized volume V
allowable pressure > of <0.1 l and a max. allowable pressure PS > 200 bar (2 900 psi) shall satisfy the essential safety
200 bar (2 900 psi) requirements set out in Annex I of the Pressure Equipment Directive 2014/68/EU. According to
Article 13 pressure equipment shall be classified by category in accordance with Annex II. The
conformity assessment of the pressure equipment shall be determined by the category I under
consideration of the above-mentioned low pressurized volume. These devices shall be provided with
CE marking.
Reasons:
• Pressure Equipment Directive 2014/68/EU, Article 13 and Annex II
• Pressure equipment directive 2014/68/EU, Commission's Working Group "Pressure", Guideline
A-05
Note:
A partial examination shall be performed for pressure instruments that are part of safety equipment
for the protection of a pipe or vessel from exceeding allowable limits (equipment with safety
function in accordance with Pressure Equipment Directive 2014/68/EU, Article 2, point 4).
The conformity assessment was performed according to module A; and proof of static strength and
fatigue strength according to EN 13445 and AD2000.
The FMP54 is not suitable for use with unstable gases at nominal pressures above 200 bar (2900
psi).
Steam boiler approval The FMP54 is approved as a limiting device for high water (HW) and low water (LW) for liquids in
containers which are subject to the requirements of EN12952-11 and EN12953-9 (certified by TÜV
Nord).
Product structure: Feature 590 "Additional Approval", option LX "Steam boiler approval".
For details refer to Safety Instructions SD00349F and Planning Recommendations SD01071F.
Device with steam boiler approval always have a SIL approval as well.
GL ABS LR BV DNV
FMP51
FMP52
FMP54 - - - - -
Telecommunications Complies with part 15 of the FCC rules for an unintentional radiator. All probes meet the
requirements for a Class A digital device.
In addition, all probes in metallic tanks as well as the coax probe meet the requirements for a Class B
digital device.
CRN approval Some device versions have a CRN approval. Devices are CRN approved if the folowing two conditions
are met:
• The device has a CSA or FM approval (Product structure: Feature 010 "Approval")
• The device has a CRN approved process connection according to the following table.
AAJ NPS 2" Cl. 600 RF, 316/316L flange ASME B16.5
ABJ NPS 3" Cl. 600 RF, 316/316L flange ASME B16.5
AEJ NPS 1-1/2" Cl. 150 RF, 316/316L flange ASME B16.5
110 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
AFJ NPS 2" Cl. 150 RF, 316/316L flange ASME B16.5
AGJ NPS 3" Cl. 150 RF, 316/316L flange ASME B16.5
AHJ NPS 4" Cl. 150 RF, 316/316L flange ASME B16.5
AJJ NPS 6" Cl. 150 RF, 316/316L flange ASME B16.5
AKJ NPS 8" Cl. 150 RF, 316/316L flange ASME B16.5
AOJ NPS 4" Cl. 600 RF, 316/316L flange ASME B16.5
AQJ NPS 1-1/2" Cl. 300 RF, 316/316L flange ASME B16.5
ARJ NPS 2" Cl. 300 RF, 316/316L flange ASME B16.5
ASJ NPS 3" Cl. 300 RF, 316/316L flange ASME B16.5
ATJ NPS 4" Cl. 300 RF, 316/316L flange ASME B16.5
AZJ NPS 4" Cl. 900 RF, 316/316L flange ASME B16.5
A6J NPS 2" Cl. 1500 RF, 316/316L Flansch ASME B16.5
A7J NPS 3" Cl. 1500 RF, 316/316L flange ASME B16.5
A8J NPS 4" Cl. 1500 RF, 316/316L flange ASME B16.5
• Process connections without CRN approval are not included in this table.
Endress+Hauser 111
Levelflex FMP51, FMP52, FMP54
• Refer to the product structure to see which process connections are available for a specific
device type.
• CRN approved devices are marked with the registration number 0F14480.5C on the
nameplate.
Track record FMP5x is the upgrade model of the corresponding FMP4x series.
112 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
KG 3.1 Material certificate+PMI test (XRF), internal procedure, wetted metallic • FMP51
parts, EN10204-3.1 inspection certificate • FMP54
KR Liquid penetrant test ASME VIII-1 (PT), wetted/pressurized metallic parts, • FMP51
inspection certificate • FMP54
Test reports, declarations and material test certificates can be obtained electronically from the
W@M Device Viewer :
Enter the serial number from the nameplate (www.endress.com/deviceviewer)
This applies to the options of the following ordering features:
• 550 "Calibration"
• 580 "Test, Certificate"
Product documentation on Test reports, declarations and material certificates can be ordered as hardcopies via ordering feature
paper 570 "Service", option I7 „Product documentation on paper“. The printouts will be enclosed in the
product delivery.
Endress+Hauser 113
Levelflex FMP51, FMP52, FMP54
114 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Ordering information
Ordering information Detailed ordering information is available from the following sources:
• In the Product Configurator on the Endress+Hauser website: www.endress.com -> Click "Corporate"
-> Select your country -> Click "Products" -> Select the product using the filters and search field ->
Open product page -> The "Configure" button to the right of the product image opens the Product
Configurator.
• From your Endress+Hauser Sales Center: www.addresses.endress.com
Product Configurator - the tool for individual product configuration
• Up-to-the-minute configuration data
• Depending on the device: Direct input of measuring point-specific information such as
measuring range or operating language
• Automatic verification of exclusion criteria
• Automatic creation of the order code and its breakdown in PDF or Excel output format
• Ability to order directly in the Endress+Hauser Online Shop
Endress+Hauser 115
Levelflex FMP51, FMP52, FMP54
3-point linearity protocol The following notes must be taken into account if option F3 ("3 point linearity protocol") has
been selected in feature 550 ("Calibration").
Depending on the probe the 3 points of the linearity protocol are defined as follows:
A
1 1
2 2
LN
B
3 3
C
A0021843
Rod or coax probe 1) Divisible rod probe Rope probe Rope probe
LN ≤ 6 m (20 ft) LN > 6 m (20 ft) LN ≤ 6 m (20 ft) LN > 6 m (20 ft)
Position of 1st measuring • FMP51/FMP52/FMP54 withoput gas phase compensation/ A = 350 mm (13.8 in) A = 350 mm (13.8 in)
point FMP55:
A = 350 mm (13.8 in)
• FMP54 with gas phase compensation, Lref = 300 mm (11 in):
A = 600 mm (23.6 in)
• FMP54 with gas phase compensation, Lref = 550 mm (21 in):
A = 850 mm (33.5 in)
Position of 2nd measuring centrally between 1st and centrally between 1st and 3rd centrally between 1st and centrally between 1st and
point 3rd measuring point measuring point 3rd measuring point 3rd measuring point
Position of 3rd measuring measured from the measured from the top end of the measured from the measured from the top
point bottom end of the probe: probe: bottom end of the probe: end of the probe:
C = 250 mm (9.84 in) A+B = 5 750 mm (226 in) C = 500 mm (19.7 in) A+B = 5 500 mm (217 in)
Minimum measuring B ≥ 400 mm (15.7 in) B ≥ 400 mm (15.7 in) B ≥ 400 mm (15.7 in) B ≥ 400 mm (15.7 in)
range
Minimum length of probe LN ≥ 1 000 mm (39.4 in) LN ≥ 1 000 mm (39.4 in) LN ≥ 1 250 mm (49.2 in) LN ≥ 1 250 mm (49.2 in)
• For rod and rope probes the linearity check is performed with the complete device.
• For divisible rod probes a reference probe is used instead of the original one.
• For coax probes the electronics is mounted to a reference rod probe and the linearity check is
performed to this configuration.
• The linearity is checked under reference conditions.
116 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
5-point linearity protocol The following notes must be taken into account if option F4 ("5 point linearity protocol") has
been selected in feature 550 ("Calibration").
The five points of the linearity protocol are evenly distributetd across the measuring range (0% to
100%). In order to define the measuring range, Empty calibration (E) and Full calibration (F) have
to be specified 11).
The following restrictions have to be taken into account when defining E and F:
A
E
B
F
C
A0014673
FMP54 w/o gas phase compensation A ≥ 250 mm (10 in) B ≥ 400 mm (16 in)
FMP54 with gas phase compensation, Lref = 300 mm A ≥ 450 mm (18 in) B ≥ 400 mm (16 in)
FMP54 with gas phase compensation, Lref = 550 mm A ≥ 700 mm (28 in) B ≥ 400 mm (16 in)
11) If E and F are not specified, probe dependent default values will be used instead.
Endress+Hauser 117
Levelflex FMP51, FMP52, FMP54
• For rod and rope probes the linearity check is performed with the complete device.
• For coax probes the electronics is mounted to a reference rod probe and the linearity check is
performed to this configuration.
• The linearity is checked under reference conditions.
The selected values of Empty calibration and Full calibration are only used to record the
linearity protocol and are reset to their probe specific default values thereafter. If values
different from the default are required, they must be ordered as a customized parametrization
→ 119.
118 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Customized parametrization If the option IJ "Customized parametrization HART", IK "Customized parametrization PA" or IL
"Customized parametrization FF" has been selected in feature 570 "Service", customer specific
presettings can be selected for the following parameters:
Setup → Adv. Setup → Current output 1/2 → Failure mode HART • Min
• Max
• Last valid value
Setup → Adv. Setup → Current output 1/2 → Burst mode HART • Off
• On
Designation in the Electronic The first 32 characters of the measuring point designation
Name Plate (ENP)
Designation on the display The first 12 characters of the measuring point designation
module
Endress+Hauser 119
Levelflex FMP51, FMP52, FMP54
Application Packages
Heartbeat Diagnostics Availability
Available in all device versions.
Function
• Continuous self-monitoring of the device.
• Diagnostic messages output to
– the local display.
– an asset management system (e.g. FieldCare/DeviceCare).
– an automation system (e.g. PLC).
Advantages
• Device condition information is available immediately and processed in time.
• The status signals are classified in accordance with VDI/VDE 2650 and NAMUR recommendation
NE 107 and contain information about the cause of the error and remedial action.
Detailed description
See Operating Instructions of the device (→ 133); chapter "Diagnostics and trouble shooting"
120 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Advantages
• No onsite presence is required to use the function.
• The DTM 12) triggers verification in the device and interprets the results. No specific knowledge is
required on the part of the user.
• The verification report can be used to prove quality measures to a third party.
• Heartbeat Verification can replace other maintenance tasks (e.g. periodic check) or extend the
test intervals.
• The Heartbeat Verification module contains a wizard for the proof test which must be performed
at appropriate intervals for the following applications:
– SIL (IEC61508/IEC61511)
– WHG (German Water Resources Act)
• To perform a proof test, the device must be locked (SIL/WHG locking).
• The wizard can be used via FieldCare, DeviceCare or a DTM-based process control system.
In the case of SIL-locked and WHG-locked devices, it is not possible to perform verification
without additional measures (e.g. by-passing of the output current) because the output current
must be simulated (Increased safety mode) or the level must be approached manually (Expert
mode) during subsequent re-locking (SIL/WHG locking).
Detailed description
SD01872F
12) DTM: Device Type Manager; controls device operation via DeviceCare, FieldCare or a DTM-based process control system.
13) Only relevant for devices with SIL or WHG approval: order code 590 ("Additional approval"), option LA ("SIL") or LC ("WHG").
Endress+Hauser 121
Levelflex FMP51, FMP52, FMP54
Function
• In addition to the verification parameters, the corresponding parameter values are also logged.
• Existing measured variables, such as the echo amplitude, are used in the Foam detection and
Build-up detection wizards.
The Foam detection and Build-up detection wizards cannot be used together.
Advantages
• Early detection of changes (trends) to ensure plant availability and product quality.
• Use of information for the proactive planning of measures (e.g. cleaning/maintenance).
• Identification of undesirable process conditions as the basis to optimizing the facility and the
processes.
• Automated control of measures to remove foam or buildup.
Detailed description
SD01872F
122 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Accessories
Device-specific accessories Weather protection cover
Accessory Description
222 (8.74)
A0015466
4)
38
35°
65°
(6.1
156
A0015472
Enclosed",
The weather protection cover can be ordered together with the device (product structure, feature 620 "Accessory
option PB "Weather Protection Cover").
Alternatively, it can be separately ordered as an accessory; order code 71162242.
Endress+Hauser 123
Levelflex FMP51, FMP52, FMP54
Accessory Description
ø42...60
(1.65...2.36)
52 (2)
122 (4.8) 127...140
161 (6.34) (5...5.51)
162...175
(6.38...6.89)
(3.4)
(2.8)
86
70
A0014793
the
For the "Sensor remote" device version (see feature 060 of the product structure), the mounting bracket is part of
delivery. If required, it can also be ordered as an accessory (order code 71102216).
124 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Accessory Description
1 Nozzle height
2 Extension rod
3 Center washer
010 Approval:
A A: Non-hazardous area
1 1: ATEX II 1G
2 2: ATEX II 1D
A Not selected
Endress+Hauser 125
Levelflex FMP51, FMP52, FMP54
Accessory Description
A0013586
The mounting kit can also be ordered directly with the device (see the
Levelflex product structure, feature 620 "Accessory Enclosed", option PG
"Mounting kit, isolated, rope").
126 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Centering star
Accessory Description
3)
.6
can be used for
(0
6
• FMP51
ø1
7 (0.28)
• FMP54
max. 50 (1.97)
ø48 (1.89)
ø75 (2.95)
ø95 (3.74)
A0014576
The centering star is suitable for probes with a rod diameter of 16 mm (0.6 in) and
can be used in pipes from DN50 (2") up to DN100 (4"). Markings on the 4-leg
centering star ensure a simple tailoring. Hence the centering star can be adapted to
the pipe diameter. See also Operating Instructions BA00377F/00/A2.
• Material of centering star: PEEK (statically dissipative)
• Material of retaining rings: PH15-7Mo (UNS S15700)
• Admissible process temperature: –60 to +200 °C (–76 to +392 °F)
• Order code: 71069064
Iflower
the centering star is inserted in a bypass, it must be positioned below the
bypass outlet. This has to be accounted for when choosing the probe
length. Generally, the centering star should not be mounted higher than 50
mm (1.97") from the probe end. It is recommended not to insert the PEEK
centering star in the measuring range of the rod probe.
The PEEK centering star can also be ordered directly with the device (see the
Levelflex product structure, feature 610 "Accessory mounted", option OD). In
this case it is not fastened by the retaining rings. Instead it is fixed to the end
of the probe rod by a hexagonal headed bolt (A4-70) and a Nord-Lock
washer (1.4547).
Endress+Hauser 127
Levelflex FMP51, FMP52, FMP54
Accessory Description
10 (0.39)
• 16.4 mm (0.65 in)
• 37 mm (1.46 in)
can be used for
A: ø16.4 (0.65)
B: ø37 (1.46)
• FMP51
• FMP52
• FMP54
A0014577
The centering star is suitable for probes with a rod diameter of 8 mm (0.3 in),
12 mm (0.47 in) and 16 mm (0.63 in) (also coated rod probes) and can be used in
pipes from DN40 (1½") up to DN50 (2"). See also Operating Instructions
BA00378F/00/A2.
• Material: PFA
• Admissible process temperature: –200 to +200 °C (–382 to +392 °F)
• Order code
– Probe 8 mm (0.3 in): 71162453
– Probe 12 mm (0.47 in): 71157270
– Probe 16 mm (0.63 in): 71069065
The PFA centering star can also be ordered directly with the device (see the
Levelflex product structure, feature 610 "Accessory mounted", option OE).
Accessory Description
5,5
can be used for
• FMP51
• FMP54
5
8
Ø4
Ø75
Ø9
5
A0035182
The centering star is suitable for probes with a rope diameter of 4 mm (¹⁄₆ in) (also
coated rod probes). See also Operating Instructions SD01961F.
• Material: PEEK
• Admissible process temperature: –60 to +250 °C (–76 to +482 °F)
• Order code
– 71373490 (1 pc.)
– 71373492 (5 pcs.)
The PFA centering star can also be ordered directly with the device (see the
Levelflex product structure, feature 610 "Accessory mounted", option OD).
128 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Accessories Description
2.
1.
4.
3.
A0019128
• Material:
– Plastic PBT
– 316L/1.4404
– Aluminum
• Degree of protection: IP68 / NEMA 6P and IP66 / NEMA 4x
• Suitable for display modules:
– SD02 (push buttons)
– SD03 (touch control)
• Connecting cable:
– Cable supplied with device up to 30 m (98 ft)
– Standard cable supplied by customer up to 60 m (196 ft)
• Ambient temperature range: –40 to 80 °C (–40 to 176 °F)
• Ambient temperature range (option): –50 to 80 °C (–58 to 176 °F) 1)
• IfL ortheM).remote display should be used, order the device version "Prepared for display FHX50" (feature 030, version
For the FHX50, you must select option A: "Prepared for display FHX50" under feature 050 "Measuring
device version".
• If the device version "Prepared for display FHX50" was not originally ordered and a FHX50 display is to be
retrofitted, you must select version B "Not prepared for display FHX50" under feature 050: "Measuring device
version" when ordering the FHX50. In this case, a retrofit kit for the device is supplied with the FHX50. The kit
can be used to prepare the device so that the FHX50 can be used.
FHX50
Use of the FHX50 may be restricted for transmitters with an approval. A device can only be retrofitted with the
if the option L or M ("Prepared for FHX50") is listed under Basic specifications, item 4 "Display, operation" in
the Safety Instructions (XA) for the device.
Also pay attention to the Safety Instructions (XA) of the FHX50.
Endress+Hauser 129
Levelflex FMP51, FMP52, FMP54
Overvoltage protection
Accessory Description
A0021734
Technical data
• Resistance per channel: 2 * 0.5 Ωmax
• Threshold DC voltage: 400 to 700 V
• Threshold impulse voltage: < 800 V
• Capacitance at 1 MHz: < 1.5 pF
• Nominal arrest impulse voltage (8/20 μs): 10 kA
• Suited for wire cross-sections: 0.2 to 2.5 mm2 (24 to 14 AWG)
130 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Accessory Description
Commubox FXA291 Connects Endress+Hauser field devices with CDI interface (= Endress+Hauser
Common Data Interface) to the USB interface of a computer.
Order code: 51516983
Accessory Description
HART Loop Converter Evaluates the dynamic HART variables and converts them to analog current signals
HMX50 or limit values.
Order code: 71063562
Accessory Description
Accessories Description
Connect Sensor Fully integrated, battery-powered gateway for simple applications with SupplyCare Hosting.
FXA30/FXA30B Up to 4 field devices with 4 to 20 mA communication (FXA30/FXA30B), serial Modbus
(FXA30B) or HART (FXA30B) can be connected. With its robust design and ability to run for
years on the battery, it is ideal for remote monitoring in isolated locations. Version with LTE
(USA, Canada and Mexico only) or 3G mobile transmission for worldwide communication.
BA01710S.
For details, see "Technical Information" TI01356S and Operating Instructions
Accessories Description
Fieldgate Fieldgates enable communication between connected 4 to 20 mA, Modbus RS485 and
FXA42 Modbus TCP devices and SupplyCare Hosting or SupplyCare Enterprise. The signals are
transmitted either via Ethernet TCP/IP, WLAN or mobile communications (UMTS). Advanced
automation capabilities are available, such as an integrated Web-PLC, OpenVPN and other
functions.
BA01778S.
For details, see "Technical Information" TI01297S and Operating Instructions
Accessories Description
SupplyCare Inventory management software that visualizes levels, volumes, masses, temperatures,
Enterprise pressures, densities or other tank parameters. The parameters are recorded and transmitted
SCE30B by means of gateways of the type Fieldgate FXA42.
This Web-based software is installed on a local server and can also be visualized and
operated with mobile terminals such as a smartphone or tablet.
BA00055S
For details, see "Technical Information" TI01228S and Operating Instructions
Endress+Hauser 131
Levelflex FMP51, FMP52, FMP54
Accessories Description
SupplyCare Inventory management software that visualizes levels, volumes, masses, temperatures,
Hosting SCH30 pressures, densities or other tank parameters. The parameters are recorded and transmitted
by means of gateways of the type Fieldgate FXA42, FXA30 and FXA30B.
SupplyCare Hosting is offered as a hosting service (Software as a Service, SaaS). In the
Endress+Hauser portal, the user is provided with the data over the Internet.
BA00050S.
For details, see "Technical Information" TI01229S and Operating Instructions
Accessory Description
Field Xpert SFX350 Field Xpert SFX350 is a mobile computer for commissioning and maintenance. It
enables efficient device configuration and diagnostics for HART and FOUNDATION
fieldbus devices in the non-Ex area.
Accessory Description
Field Xpert SFX370 Field Xpert SFX370 is a mobile computer for commissioning and maintenance. It
enables efficient device configuration and diagnostics for HART and FOUNDATION
fieldbus devices in the non-Ex area and the Ex area.
DeviceCare SFE100 Configuration tool for HART, PROFIBUS and FOUNDATION Fieldbus devices
Graphic Data Manager The graphic data manager Memograph M provides information on all the relevant
Memograph M process variables. Measured values are recorded correctly, limit values are
monitored and measuring points analyzed. The data are stored in the 256 MB
internal memory and also on an SD card or USB stick.
RN221N Active barrier with power supply for safe separation of 4 to 20 mA current circuits.
Provides bi-directional HART transmission.
RNS221 Transmitter supply for 2-wire sensors or transmitters exclusively for non-Ex areas.
Provides bi-directional communication using the HART communication sockets.
132 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Documentation
For an overview of the scope of the associated Technical Documentation, refer to the following:
• The W@M Device Viewer : Enter the serial number from the nameplate
(www.endress.com/deviceviewer)
• The Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the
2-D matrix code (QR code) on the nameplate.
Continuous level measurement in liquids and bulk solids Competence brochure CP00023F
Selection and engineering guide for the process industry
Endress+Hauser 133
Levelflex FMP51, FMP52, FMP54
Feature 010 Approval Available for Feature 020: "Power Supply; Output"
1)
A B 2) C 3) E 4)/G 5) K 6)/L 7)
BC ATEX II 1/2G Ex d[ia] IIC T6 Ga/Gb • FMP51 XA00499F XA00499F XA00499F XA00519F XA01133F
• FMP52
• FMP54
BD ATEX II 1/3G Ex ic[ia] IIC T6 Ga/Gc • FMP51 XA00497F XA01127F XA01128F XA00517F -
• FMP52
• FMP54
BF ATEX II 1/2D Ex t IIIC Da/Db FMP54 XA00501F XA00501F XA00501F XA00521F XA00501F
BL ATEX II 1/3G Ex nA[ia] IIC T6 Ga/Gc • FMP51 XA00497F XA01127F XA01128F XA00517F XA01129F
• FMP52
• FMP54
B2 ATEX II 1/2G Ex ia IIC T6 Ga/Gb, 1/2D Ex ia IIIC Da/Db • FMP51 XA00502F XA00502F XA00502F XA00522F -
• FMP52
• FMP54
B3 ATEX II 1/2G Ex d[ia] IIC T6 Ga/Gb, 1/2 D Ex t IIIC • FMP51 XA00503F XA00503F XA00503F XA00523F XA01136F
Da/Db • FMP52
• FMP54
B4 ATEX II 1/2G Ex ia IIC T6 Ga/Gb, Ex d[ia] IIC T6 Ga/Gb • FMP51 XA00500F XA01134F XA01135F XA00520F -
• FMP52
• FMP54
CD CSA C/US DIP Cl.II,III Div.1 Gr.E-G FMP54 XA00529F XA00529F XA00529F XA00570F XA00529F
C2 CSA C/US IS Cl.I,II,III Div.1 Gr.A-G, NI Cl.1 Div.2, Ex ia • FMP51 XA00530F XA00530F XA00530F XA00571F XA00530F
• FMP52
• FMP54
C3 CSA C/US XP Cl.I,II,III Div.1 Gr.A-G, NI Cl.1 Div.2, Ex d • FMP51 XA00529F XA00529F XA00529F XA00570F XA00529F
• FMP52
• FMP54
FB FM IS Cl.I,II,III Div.1 Gr.A-G, AEx ia, NI Cl.1 Div.2 • FMP51 XA00531F XA00531F XA00531F XA00573F XA00531F
• FMP52
• FMP54
FD FM XP Cl.I,II,III Div.1 Gr.A-G, AEx d, NI Cl.1 Div.2 • FMP51 XA00532F XA00532F XA00532F XA00572F XA00532F
• FMP52
• FMP54
FE FM DIP Cl.II,III Div.1 Gr.E-G FMP54 XA00532F XA00532F XA00532F XA00572F XA00532F
134 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Feature 010 Approval Available for Feature 020: "Power Supply; Output"
1)
A B 2) C 3) E 4)/G 5) K 6)/L 7)
GC EAC Ex d[ia] IIC T6 Ga/Gb • FMP51 XA01382F XA01382F XA01382F XA01383F XA01382F
• FMP52
• FMP54
IC IEC Ex d[ia] IIC T6 Ga/Gb • FMP51 XA00499F XA00499F XA00499F XA00519F XA01133F
• FMP52
• FMP54
IL IEC Ex nA[ia] IIC T6 Ga/Gc • FMP51 XA00497F XA01127F XA01128F XA00517F XA01129F
• FMP52
• FMP54
I2 IEC Ex ia IIC T6 Ga/Gb, Ex ia IIIC Da/Db • FMP51 XA00502F XA00502F XA00502F XA00522F -
• FMP52
• FMP54
I3 IEC Ex d [ia] IIC T6 Ga/Gb, Ex t IIIC Da/Db • FMP51 XA00503F XA00503F XA00503F XA00523F XA01136F
• FMP52
• FMP54
I4 IEC Ex II 1/2G Ex ia IIC T6 Ga/Gb, Ex d[ia] IIC T6 Ga/Gb • FMP51 XA00500F XA01134F XA01135F XA00520F -
• FMP52
• FMP54
Endress+Hauser 135
Levelflex FMP51, FMP52, FMP54
Feature 010 Approval Available for Feature 020: "Power Supply; Output"
1)
A B 2) C 3) E 4)/G 5) K 6)/L 7)
NC NEPSI Ex d[ia] IIC T6 Ga/Gb • FMP51 XA00636F XA00636F XA00636F XA00642F XA00636F
• FMP52
• FMP54
NF NEPSI DIP A20/21 T85…90oC IP66 FMP54 XA00637F XA00637F XA00637F XA00643F XA00637F
N2 NEPSI Ex ia IIC T6 Ga/Gb, Ex iaD 20/21 T85…90°C • FMP51 XA00638F XA00638F XA00638F XA00644F XA00638F
• FMP52
• FMP54
N3 NEPSI Ex d[ia] IIC T6 Ga/Gb, DIP A20/21 T85…90°C • FMP51 XA00639F XA00639F XA00639F XA00645F XA00639F
IP66 • FMP52
• FMP54
8A FM/CSA IS+XP Cl.I,II,III Div.1 Gr.A-G • FMP51 XA00531F XA00531F XA00531F XA00572F XA00531F
• FMP52 XA00532F XA00532F XA00532F XA00573F XA00532F
• FMP54
For certified devices the relevant Safety Instructions (XA) are indicated on the nameplate.
136 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
14) The marking of certificates not mentioned in this table are not affected by the FHX50.
Endress+Hauser 137
Levelflex FMP51, FMP52, FMP54
Registered trademarks
HART®
Registered trademark of the FieldComm Group, Austin, USA
PROFIBUS®
Registered trademark of the PROFIBUS User Organization, Karlsruhe, Germany
FOUNDATIONTM Fieldbus
Registered trademark of the FieldComm Group, Austin, Texas, USA
KALREZ®, VITON®
Registered trademark of DuPont Performance Elastomers L.L.C., Wilmington, USA
TEFLON®
Registered trademark of E.I. DuPont de Nemours & Co., Wilmington, USA
TRI CLAMP®
Registered trademark of Alfa Laval Inc., Kenosha, USA
NORD-LOCK®
Registered trademark of Nord-Lock International AB
FISHER®
Registered trademark of Fisher Controls International LLC, Marshalltown, USA
MASONEILAN®
Registered trademark of Dresser, Inc., Addison, USA
138 Endress+Hauser
Levelflex FMP51, FMP52, FMP54
Patents
This product may be protected by at least one of the following patents.
Further patents are pending.
US Patents EP Patents
5.827.985 ---
5.884.231 ---
5.973.637 ---
6.140.940 ---
6.481.276 ---
6.640.628 ---
6.691.570 ---
6.847.214 ---
7.441.454 ---
7.477.059 ---
7.965.087 ---
Endress+Hauser 139
*71384596*
71384596
www.addresses.endress.com