Time Current Curves v2

This document provides specifications for an inverse definite minimum time coordination study, including voltage levels, fault currents, relay settings, and curve types for the supply and two relays. The supply uses an extremely inverse curve with a time multiplier setting of 0.35 seconds. Relay 1 uses a very inverse curve with a clearance time of 0.5 seconds. Relay 2 uses a standard inverse curve with a clearance time of 0.4 seconds.

Uploaded by

Michael Oliver
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
67 views2 pages

Time Current Curves v2

This document provides specifications for an inverse definite minimum time coordination study, including voltage levels, fault currents, relay settings, and curve types for the supply and two relays. The supply uses an extremely inverse curve with a time multiplier setting of 0.35 seconds. Relay 1 uses a very inverse curve with a clearance time of 0.5 seconds. Relay 2 uses a standard inverse curve with a clearance time of 0.4 seconds.

Uploaded by

Michael Oliver
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 2

INVERSE DEFINITE MINIMUM TIME

Supply Characteristics
Voltage 11000 V
Available Fault 60 MVA
10.000
Fault Current 3149 A 𝑡=("β"
×𝑇𝑀𝑆)/((𝐼/𝐼_0 )^𝛼−1)
Supply Relay Setting
Curve Type= Extremely Inverse
α= 2
β= 80
TMS= 0.35 Seconds
VS= 11000 V
IS= 400 A
INSTS= 5 Multiplier
I'S= 400 Adjusted to 11000V Base
LTDS= 0.9 Seconds
SetS= 8 Multiplier
Set'S= 3200 Adjusted to 11000V Base
E/F SettingS 0.25 x In
E/F High SettingS 2 x In
E/F Time SettingS 0.4 Seconds
Relay 1
Curve Type1= Very Inverse
α1= 1
β1= 13.5
Clearance1 = 0.5 Seconds
TMS = 0.4 Seconds
V1 = 11000 V 1.000
I1 = 250 A
INST1 = 5 Multiplier
I '1 = 250 Adjusted to 11000V Base
LTD1= 0.8 Seconds
Set1= 12 Multiplier
Set'1= 3000 Adjusted to 11000V Base
E/F Setting1 0.2 x In
E/F High Setting1 3 x In
E/F Time Setting1 0.3 Seconds
Relay 2
Curve Type2= Standard Inverse
α2= 0.02
β2= 0.14
Clearance2 = 0.4 Seconds
TMS = 0.5 Seconds
V2 = 400 V
I2 = 3600 A
INST2 = 6 Multiplier
I '2 = 131 Adjusted to 11000V Base
LTD2= 0.5 Seconds
Set2= 16 Multiplier
Set'2= 2095 Adjusted to 11000V Base
0.100
E/F Setting2 0.3 x In 10 100 1000 10000
E/F High Setting2 5 x In
E/F Time Setting2 0.2 Seconds