0% found this document useful (0 votes)
104 views2 pages

MLTB

This document provides technical specifications for the POWER MASTER PM 200 main low tension board. Some key details include: - It complies with various international standards for panel construction, protection levels, busbars, components, and specifications from Kuwait Oil Company and Kuwait National Petroleum Company. - It has a rated voltage of 415/240V and 50Hz, insulation voltage of 800V, and impulse withstand voltage of 8kV. Fault level ratings include 50kA/65kA/100kA withstanding current and 105kA/143kA/220kA peak withstand current. - The board features tinned electrolytic copper busbars with 99.9% purity that are

Uploaded by

DHINAKARAN Kumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
104 views2 pages

MLTB

This document provides technical specifications for the POWER MASTER PM 200 main low tension board. Some key details include: - It complies with various international standards for panel construction, protection levels, busbars, components, and specifications from Kuwait Oil Company and Kuwait National Petroleum Company. - It has a rated voltage of 415/240V and 50Hz, insulation voltage of 800V, and impulse withstand voltage of 8kV. Fault level ratings include 50kA/65kA/100kA withstanding current and 105kA/143kA/220kA peak withstand current. - The board features tinned electrolytic copper busbars with 99.9% purity that are

Uploaded by

DHINAKARAN Kumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

POWER MASTER “PM 200”, MAIN LOW TENSION BOARD(MLTB)

Technical data:

Standard compliance to :
MEW S1/IEC 60439-1 : Panel construction
IEC 60529 : Degree of protection
BS 159/IEC : Busbars/Connections
IEC 60947 : Breakers/Contactors/Other components
BS 88/IEC 60269 : Fuses
BS 142/IEC 60255 : Electrical protective relays
BS 3938/IEC 60185 : Current transformers
IEC 60051/BS 89 : Meterings
And other relevant standards. : Kuwait Oil Company(KOC) Specifications
Kuwait National Petroluem Co.(KNPC) Specifications

System : 3 Phase & Neutral + Earth


Rated operational voltage & frequency (Ue,f) : 415/240V*, 50Hz.
Rated insulation voltage (Ui) : 800V
Rated impulse withstand voltage (Uimp) : 8 KV
Overvoltage category : IV
Pollution degree : 3
*Other voltages on request.
Fault level rating :
Rated short time withstand current for busbars (Icw) : 50KA/65KA/100KA for 1sec.
Rated peak withstand current for busbars (Ipk) : 105KA/143KA/220KA
Rated conditional short circuit current (Icc) : Upto 65KA

Busbars : Tinned Electrolytic Copper with 99.9% purity(BS 1482)


Marked(BS 159) : for phase identification (colour coded or sleeved)
Rating : RYB…1600A/2000A/2500A/3000A/4000A/6000A
: N…….50% or 100% of phase busbar
: E…….50% of phase busbar

Enclosures :
Material : Electro galvanized, Zinc coated steel sheet
Painting : Powder coating, Shade RAL-7032, light grey.
Degree of protection(IEC 60529) : IP 42 / IP 52 / IP 54 / IP 55
Form of internal seperation(IEC 60439-1) : Form 3b / Form 4
Cable entry : Top or Bottom
PM 200 MLTB offers advantages that sets safety & ease of maintenance
ƒ Fully Type tested assembly (TTA)
ƒ Compartmentalized 4 functional spaces namely Breaker,Auxilaries,Busbars,Cable
ƒ Ensure the protection of person against direct contact with live parts
ƒ Safety of operation, due to the impossibility of withdrawing or opening a door of live
circuit breaker
ƒ Interchangeability of the elements of the same type
ƒ Modifying breaker rating or changing it without disconnecting the whole assembly
ƒ Standardization of basic components
ƒ Front or Rear access for cable termination
ƒ Top or Bottom cable entry
ƒ Can be attached to MCC to form a combined Power cum Motor control center

STANDARD OVERALL DIMENSIONS FOR MLTP


1 DEPTH, 3 WIDTHS & 3 SIZES EXTENSIONS.
The Power Master PM 200(MLTP) range may
be used to build switchboards of various depths & widths by
connecting basic frames and extensions;

Basic frame is available in only ONE depth;


• 645mm – Common for ACB section & outgoing
sections.

Basic frame is available in only THREE widths;


• 650mm – for a) TP ACB of frame upto 2000A.
b) Outgoing section(front cable
connection with side extension).
• 750mm – for a) TP ACB of frame upto 3200A
and 4P ACB of frame upto 2000A.
b) Outgoing section(rear cable
connection).
• 850mm – for a) 4P ACB of frame upto 3200A.
b) Two tier ACBs and Buscoupler ACB
section.

Side/Rear Extensions in FOUR Sizes;


• 200mm – rear extension for outgoing section(for rear
cable access only).
• 300mm – side or rear extension for cable alley for
outgoing section.
• 400mm – (side extension for front cable connection &
rear extension for rear cable connection).

¾Side or rear extension with sizes depends upon the configuration required i.e front or rear excess for cabling,
top or bottom busbars, form of seperation(form 3 or 4) and no. of cables.

Sizes other than mentioned above available on request and to be co-ordinated with Ebomac design
department.
Development is a continuous process thus ebomac reserves the right to change data or design without any prior notice.

Electrical Boards Manufacturing Co. K.S.C.


Office & Factory:-……… Showrooms:-…………..
Sabhan Industrial Area
P.O.Box 25428, Safat 13115 Kuwait Shuwaikh-Tel: 4812260 fax: 4812202
Tel. : +965 472 7550……………... Hawalli- Tel: 2656704 fax: 2624704
Fax. :+965 476 5059, 476 3016
E-mail : [email protected]
DESIGN ENGINEERING DEPT.
Website : www.ebomac.com
Ref: EBMC/LF-LT/2002 Vol.1