0% found this document useful (0 votes)
314 views10 pages

IECEx BVS 17.0045X 002

The document is an IECEx Certificate of Conformity that certifies the plug and socket system type GHG 51*** ** R * *** as being compliant with international standards for use in explosive atmospheres. It provides details on the equipment, standards tested against, manufacturing locations, and conditions of use. Specific components of the system are also listed that have their own individual certification under the IECEx scheme.

Uploaded by

Muhammad Imran
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
314 views10 pages

IECEx BVS 17.0045X 002

The document is an IECEx Certificate of Conformity that certifies the plug and socket system type GHG 51*** ** R * *** as being compliant with international standards for use in explosive atmospheres. It provides details on the equipment, standards tested against, manufacturing locations, and conditions of use. Specific components of the system are also listed that have their own individual certification under the IECEx scheme.

Uploaded by

Muhammad Imran
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

IECEx Certificate

of Conformity
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification System for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

Certificate No.: IECEx BVS 17.0045X Page 1 of 4 Certificate history:


Issue 1 (2018-01-26)
Status: Current Issue No: 2 Issue 0 (2017-08-31)

Date of Issue: 2018-03-21

Applicant: Cooper Crouse-Hinds GmbH


Neuer Weg-Nord 49
69412 Eberbach
Germany

Equipment: Plug and socket system type GHG 51*** ** R * ***

Optional accessory:

Type of Protection: Equipment protection by flameproof enclosures "d", Equipment protection by intrinsic safety "i", Equipment
dust ignition protection by enclosure "t", Equipment protection by increased safety ''e''

Marking: Ex db eb [ia] IIC/IIB/IIB+H2 T6 Gb


Ex tb IIIC T80°C Db

Approved for issue on behalf of the IECEx Jörg Koch


Certification Body:

Position: Head of Certification Body

Signature:
(for printed version)

Date:
(for printed version)

1. This certificate and schedule may only be reproduced in full.


2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting www.iecex.com or use of this QR Code.

Certificate issued by:

DEKRA EXAM GmbH


Dinnendahlstrasse 9
44809 Bochum
Germany
IECEx Certificate
of Conformity
Certificate No.: IECEx BVS 17.0045X Page 2 of 4

Date of issue: 2018-03-21 Issue No: 2

Manufacturer: Cooper Crouse-Hinds GmbH


Neuer Weg-Nord 49
69412 Eberbach
Germany

Manufacturing S.C. Cooper Industries Romania


locations: S.R.L.
Zona Industriala Vest
Str. III, Nr. 12
310510 Arad
Romania

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the
IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and
found to comply with the IECEx Quality system requirements.This certificate is granted subject to the conditions as set out in IECEx Scheme
Rules, IECEx 02 and Operational Documents as amended

STANDARDS :
The equipment and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found
to comply with the following standards

IEC 60079-0:2011 Explosive atmospheres - Part 0: General requirements


Edition:6.0

IEC 60079-1:2014-06 Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
Edition:7.0

IEC 60079-11:2011 Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
Edition:6.0

IEC 60079-31:2013 Explosive atmospheres - Part 31: Equipment dust ignition protection by enclosure "t"
Edition:2

IEC 60079-7:2015 Explosive atmospheres – Part 7: Equipment protection by increased safety ''e''
Edition:5.0

This Certificate does not indicate compliance with safety and performance requirements
other than those expressly included in the Standards listed above.

TEST & ASSESSMENT REPORTS:


A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in:

Test Report:
DE/BVS/ExTR17.0066/02

Quality Assessment Report:


DE/BVS/QAR11.0009/08
IECEx Certificate
of Conformity
Certificate No.: IECEx BVS 17.0045X Page 3 of 4

Date of issue: 2018-03-21 Issue No: 2

EQUIPMENT:
Equipment and systems covered by this Certificate are as follows:

Subject and Type

See Annex

Description

See Annex

Listing of all components used

See Annex

Listing of all components used referring to older standards

See Annex

Parameters

See Annex

SPECIFIC CONDITIONS OF USE: YES as shown below:


The plugs of the plug and socket system type GHG 51*7* ** R (Gas Group IIB/IIB+H2/IIC) must be protected against mechanical damage > 4
J for an ambient temperature limit below -40 °C.
IECEx Certificate
of Conformity
Certificate No.: IECEx BVS 17.0045X Page 4 of 4

Date of issue: 2018-03-21 Issue No: 2

DETAILS OF CERTIFICATE CHANGES (for issues 1 and above)


• Addition an increased ambient temperature range for the plug Tamb: +55 °C

Annex:

BVS_17_0045x_Cooper_Annex_Issue2.pdf
Certificate No.: IECEx BVS 17.0045X, Issue No.:2
Annex
Page 1 of 6
Subject and Type
Plug and socket system 51 * * * ** R * ***
type GHG
1) 2) 3) 4) 5) 6)

1)
Rated current and voltage 1 = 16 A 110 V - 690 V
2)
Design 3 = Couple
4 = Wall socket
7 = Plug
3)
Number of poles 3 = 3-poles (1+N+PE)
4 = 4-poles (3+PE)
5 = 5-poles (3+N+PE)
4)
Voltage 00 = ≤ 24 V AC
03 = 230 V AC
04 = 110/130 V AC
05 = 690 V AC
06 = 230/415 V AC
07 = 500 V AC
08 = special version
09 = 127/230 V
12 = 42 V AC
5)
Temperature range R = Design variant temperature range
6)
Version 0 = Plastic
3 = Inset metal plate
5-8 = Auxiliary contacts

Description
The plug and socket system type GHG 51*** ** R * *** consists of a flange socket which is built as a wall
socket or a couple, which is used for connection of a plug.
The plug is built in type of protection Increased Safety “e” and Protection by Enclosure “t”.
The wall socket and the couple are built in type of protection Increased Safety “e” and Protection by
Enclosure “t”.
The mounting flange socket type GHG 511 8… . …. is separately certified and built in type of protection
Flameproof Enclosure “d”, Increased Safety “e” and Protection by Enclosure “t”.
The wall socket can be equipped with a separately certified mini terminal type 07-9702-0*2*/****, signal
lamp type GHG41. …. R…, switch block type GHG 41. …. R …., miniature limit switch
type 07-1501-****/****, terminal type MS(D)B 2,5 *** / UK *** or control unit type GHG 411 8***.
Certificate No.: IECEx BVS 17.0045X, Issue No.:2
Annex
Page 2 of 6
Listing of all components used
Subject and type Certificate
Flange socket IECEx BVS 15 15.0088U
GHG 511 8… . ….
Mini terminal IÉCEx PTB 07.0007U
07-9702-0*2*/****
Signal lamp IECEx IBE 13.0031U
GHG41. …. R…

Switch block IECEx IBE 14.0005U


GHG 41. …. R ….

Miniature limit switch IECEx EPS 14.0038 U


07-1501-****/****

Listing of all components used referring to older standards


Subject and type Certificate Standards
Feed-through terminal block IECEx PTB 08.0048 U IEC 60079-0:2011 Ed. 6
1
type MS(D)B 2,5 *** IEC 60079-7:2006 Ed. 4
Terminal Type UK *** IECEx KEM 06.0034 U IEC 60079-0:2011 Ed. 6
1
IEC 60079-7:2006 Ed. 4
1
Control unit IECEx BKI 04.0003 IEC 60079-0:2000 Ed. 3.1
1
GHG 411 8*** IEC 60079-1:2001 Ed. 4
1
IEC 60079-7:2001 Ed. 3
1
IEC 60079-11:1999 Ed. 4
1
No applicable technical differences

Parameters
Plug and socket system - Wall socket type GHG 51*4* ** R **** (Gas Group IIB/IIB+H 2/IIC) -
Flange socket standard material

Rated voltage: 110 - 690 V AC


Rated current: 16 A
Ambient temperature range: -55 °C … +45 °C

Plug and socket system - Wall socket type GHG 51*4* ** R **** (Gas Group IIB+H2/IIC) -
Flange socket standard material

Rated voltage: 110 - 690 V AC


Rated current: 10 A
Ambient temperature range: -55 °C … +55 °C

Plug and socket system - Wall socket type GHG 51*4* ** R **** -
Flange socket alternative material

Rated voltage: 110 - 690 V AC


Rated current: max. 16 A (3-pol.) / without PE (2-pol.)
Ambient temperature range: -45 °C … +55 °C (Gas Group IIB)
-30 °C … +55 °C (Gas Group IIB+H2)
-20 °C … +55 °C (Gas Group IIC)
Certificate No.: IECEx BVS 17.0045X, Issue No.:2
Annex
Page 3 of 6
Plug and socket system - Wall socket type GHG 51*4* ** R **** -
Flange socket alternative material
Rated voltage: 110 - 690 V AC
Rated current: max. 16 A (4-pol. / 5-pol.)
-55 °C … +55 °C (Gas Group IIB/IIB+H2)
Ambient temperature range:
-20 °C … +55 °C (Gas Group IIC)
1)
Plug and socket system - Wall socket type GHG 511 4311 R **** (Gas Group IIC/IIB) -
Flange socket standard material

Rated voltage: 42 V AC
Rated current: 16 A (3-pol.) / without PE (2-pol.)
Ambient temperature range: -55 °C … +55 °C
1)
Plug and socket system - Wall socket type GHG 511 4301 R **** (Gas Group IIC/IIB) -
Flange socket standard material

Rated voltage: 24 V AC
Rated current: 16 A (3-pol.) / without PE (2-pol.)
Ambient temperature range: -55 °C … +55 °C

1)
Plug and socket system - Wall socket type GHG 511 4301 R **** (Gas Group IIC/IIB) -
Flange socket standard material

Rated voltage: 12 V AC
Rated current: 16 A (3-pol.) / without PE (2-pol.)
Ambient temperature range: -55 °C … +55 °C
1)
Plug and socket system - Wall socket type GHG 511 4311 R **** (Gas Group IIC/IIB) -
Flange socket alternative material
Rated voltage: 42 V AC
Rated current: 16 A (3-pol.) / without PE (2-pol.)
-45 °C … +55 °C (Gas Group IIB)
Ambient temperature range: -30 °C … +55 °C (Gas Group IIB+H2)
-20 °C … +55 °C (Gas Group IIC)
1)
Plug and socket system - Wall socket type GHG 511 4301 R **** (Gas Group IIC/IIB) -
Flange socket alternative material

Rated voltage: 24 V AC
Rated current: 16 A (3-pol.) / without PE (2-pol.)
-45 °C … +55 °C (Gas Group IIB)
Ambient temperature range: -30 °C … +55 °C (Gas Group IIB+H2)
-20 °C … +55 °C (Gas Group IIC)
Certificate No.: IECEx BVS 17.0045X, Issue No.:2
Annex
Page 4 of 6
1)
Plug and socket system - Wall socket type GHG 511 4301 R **** (Gas Group IIC/IIB) -
Flange socket alternative material
Rated voltage: 12 V AC
Rated current: 16 A (3-pol.) / without PE (2-pol.)
-45 °C … +55 °C (Gas Group IIB)
Ambient temperature range: -30 °C … +55 °C (Gas Group IIB+H2)
-20 °C … +55 °C (Gas Group IIC)
Plug and socket system - couple type GHG 51*3* ** R **** (Gas Group IIC/IIB) -
standard material

Rated voltage: 110 - 690 V AC


Rated current: 10 A
Ambient temperature range: -20 °C … +55 °C

Plug and socket system - couple type GHG 51*3* ** R **** (Gas Group IIC/IIB) -
standard material

Rated voltage: 110 - 690 V AC


Rated current: 16 A
Ambient temperature range: -20 °C … +45 °C

Plug and socket system - couple type GHG 51*3* ** R **** (Gas Group IIC/IIB/IIB+H2) -
alternative material

Rated voltage: 110 - 690 V AC


Rated current: 16 A
Ambient temperature range: -20 °C … +45 °C
1
Plug and socket system - couple type GHG 511 3311 R **** (Gas Group IIC/IIB) -
standard material

Rated voltage: 42 V AC
Rated current: 16 A
Ambient temperature range: -20 °C … +55 °C

1
Plug and socket system - couple type GHG 511 3301 R **** (Gas Group IIC/IIB) -
standard material

Rated voltage: 24 V AC
Rated current: 16 A
Ambient temperature range: -20 °C … +55 °C

1
Plug and socket system - couple type GHG 511 3301 R **** (Gas Group IIC/IIB) -
standard material

Rated voltage: 12 V AC
Rated current: 16 A
Ambient temperature range: -20 °C … +55 °C
Certificate No.: IECEx BVS 17.0045X, Issue No.:2
Annex
Page 5 of 6
1
Plug and socket system - couple type GHG 511 3311 R **** (Gas Group IIC/IIB/IIB+H2) -
alternative material
Rated voltage: 42 V AC
Rated current: 16 A
Ambient temperature range: -20 °C … +55 °C

1
Plug and socket system - couple type GHG 511 3301 R **** (Gas Group IIC/IIB/IIB+H 2) -
alternative material
Rated voltage: 24 V AC
Rated current: 16 A
Ambient temperature range: -20 °C … +55 °C

1
Plug and socket system - couple type GHG 511 3301 R **** (Gas Group IIC/IIB/IIB+H 2) -
alternative material

Rated voltage: 12 V AC
Rated current: 16 A
Ambient temperature range: -20 °C … +55 °C

Plug and socket system - plug type GHG 51*7* ** R **** (Gas Group IIC/IIB/IIB+H2)
Rated voltage: 110 - 690 V AC
Rated current: 16 A
2
Rated cross section: 2.5 mm
-40 °C … +45 °C
Ambient temperature range:
-55 °C … +45 °C (see Specific Conditions of Use)

Plug and socket system - plug type GHG 51*7* ** R **** (Gas Group IIC/IIB/IIB+H2)

Rated voltage: 110 - V AC


690
Rated current: 16 A
2
Rated cross section: 4 mm
-40 °C … +55 °C
Ambient temperature range:
-55 °C … +55 °C (see 7.1)

Plug and socket system - plug type GHG 51*7* ** R **** (Gas Group IIC/IIB/IIB+H2)

Rated voltage: 110 - 690 V AC


Rated current: 10 A
2
Rated cross section: 2.5 mm
-40 °C … +55 °C
Ambient temperature range:
-55 °C … +55 °C (see Specific Conditions of Use)
Certificate No.: IECEx BVS 17.0045X, Issue No.:2
Annex
Page 6 of 6
1)
Plug and socket system - plug type GHG 511 7311 R **** (Gas Group IIC/IIB/IIB+H2)

Rated voltage: 42 V AC
Rated current: 16 A (3-pol.) / without PE (2-pol.)
-40 °C … +55 °C
Ambient temperature range:
-55 °C … +55 °C (see Specific Conditions of Use)

1)
Plug and socket system - plug type GHG 511 7301 R **** (Gas Group IIC/IIB)
Rated voltage: 24 V AC
Rated current: 16 A
-40 °C … +55 °C
Ambient temperature range:
-55 °C … +55 °C (see Specific Conditions of Use)

1)
Plug and socket system - plug type GHG 511 7301 R **** (Gas Group IIC/IIB)

Rated voltage: 12 V AC
Rated current: 16 A
-40 °C … +55 °C
Ambient temperature range:
-55 °C … +55 °C (see Specific Conditions of Use)
1)
special version

Intrinsically safe circuits (according IBExU 12 ATEX 1047 U / IECEx IBE 13.0031U)

Rated voltage: 10 - 30 V DC
Rated current: max. 38.7 mA
Ui 30 V DC
Ii 120 mA
Pi 750 mW
Ci, Li: negligible

Potential-free switch contact for the connection of an intrinsically safe circuit

Rated voltage: max. 30 V AC / DC


Rated current: max. 400 mA
Ci, Li: negligible

You might also like