Detail of Calculation Staircase 26 Sty Pressurisation System
Detail of Calculation Staircase 26 Sty Pressurisation System
Design Calculation {Reference -BS 5588 - part 4 & ASHRAE HVAC Application }
Step 1 Estimating Air Flow past thru when 3 doors are opened
The combination of two doors from any two successive storeys and the main discharge door are fully open.
Leakag
Size (m) Qty
Descriptions e Area
(h) (w) no. m
Single leaf doors . 2.1 1.0 2 4.2
Double leaf door to exterior 2.1 1.6 1 3.4
2
Total area of 3 Nos. of doors (m ) 7.6
Egress Velocity , required velocity through doors (minimum 1m/s) = 1.00 m/s
Required Air flow rate through doors (opened doors) = 7.56 m3/s
27216 CMH
Minimum Pressure Differential between staircase & adjacent accommodation space is 50 Pa when all doors are closed.
Pressure differential 50 Pa
Air
No. of Crack
Size Leakage Area Leakage *
Type of door Door Length
n=2
m m qty m m2 (k) m2 m3/s
Single-leaf in rebated frame opening into a
2.1 1.0 1 6.2 0.01 0.011 0.065
pressurisation space
Single-leaf in rebated frame opening outwards from a
2.0 0.8 1 5.6 0.02 0.020 0.117
pressurisation space
Double leaf with or without centre rebate 2.1 1.6 1 9.5 0.03 0.030 0.175
Lift Landing Door 2.0 2.0 1 8.0 0.06 0.060 0.351