IOM - Transmitter - ABB - 266HSH Modbus (From Webpage)
IOM - Transmitter - ABB - 266HSH Modbus (From Webpage)
A B B M E A S U R E M E N T & A N A LY T I C S | O P E R AT I N G I N S T R U C T I O N | O I/ 2 6 6 H S H M T- E N
The 2600T family provides comprehensive range of Further publications for 2600T series pressure
top quality pressure measurement products, products are available for free download from
specifically designed to meet the widest range of www.abb.com/pressure
applications ranging from arduous conditions in
offshore oil and gas to the laboratory environment
of the pharmaceutical industry.
Data Sheet
DS/2101130-EN
Product
Operating Instruction
OI/266HSHMT-EN
Product
Table of contents
2 2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A
1 Introduction Caution. Only qualified and authorized specialist personnel should be
charged with installation, electrical connection, commissioning, and
1.1 Instruction manual structure maintenance of the transmitter. Qualified personnel are persons who
The present manual provides information on installing, have experience in installation, electrical wiring connection,
operating, troubleshooting the 266 pressure transmitter. commissioning, and operation of the transmitter or similar devices,
Every section of the present manual is specifically dedicated and hold the necessary qualifications such as:
to the specific phase of the transmitter lifecycle starting — Training or instruction, i.e., authorization to operate and maintain
from the receipt of the transmitter and its identification, devices or systems according to safety engineering standards for
passing to the installation, to the electrical connections, to electrical circuits, high pressures, and aggressive media
the configuration and to the troubleshooting and
maintenance operations. — Training or instruction in accordance with safety engineering
standards regarding maintenance and use of adequate safety
1.2 Models covered by this manual systems.
The present manual can be used for the Modbus 266 For safety reasons, ABB draws your attention to the fact that only
pressure model. sufficiently insulated tools conforming to EN 60900 may be used.
Full compliance with the general safety requirements must — Adding material, e.g., by painting over the name plate
be observed during operation of the device. In addition to or welding/soldering on parts.
the general information, the individual sections in the
— Removing material, e.g., by drilling the housing.
manual contain descriptions of processes or procedural
instructions with specific safety information. Repairs, alterations and enhancements, or the installation
of replacement parts are only permissible as far as these
Only by observing all of the safety information can you
are described in the manual. Approval by ABB must be
reduce to the minimum the risk of hazards for personnel
requested for any activities beyond this scope. Repairs
and/or environment. These instructions are intended as an
performed by ABB-authorized centers are excluded from
overview and do not contain detailed information on all
this.
available models or every conceivable event that may occur
during setup, operation, and maintenance work.
2.3 Technical limit values
For additional information, or in the event of specific The device is designed for use exclusively within the values
problems not covered in detail by these operating stated on the name plates and within the technical limit
instructions, please contact the manufacturer. In addition, values specified on the data sheets.
ABB declares that the contents of this manual are not part
of any prior or existing agreements, commitments, or legal The following technical limit values must be observed:
relationships; nor are they intended to amend these. — The Maximum Working Pressure may not be
All obligations of ABB arise from the conditions of the exceeded.
relevant sales agreement, which also contains the solely — The Maximum ambient operating temperature may
binding warranty regulations in full. These contractual not be exceeded.
warranty provisions are neither extended nor limited by the
information provided in this manual. — The Maximum process temperature may not be
exceeded.
— The enclosure method of protection type must be
observed.
2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A 3
2.4 Warranty provision 2.9 Disposal
Using the device in a manner that does not fall within the ABB actively promotes environmental awareness and has
scope of its intended use, disregarding this manual, using an operational management system that meets the
underqualified personnel, or making unauthorized requirements of ISO 9001:2015, ISO 14001:2015, and OHSAS
alterations, releases the manufacturer from any liability for 18001:2007. Our products and solutions are intended to
any resulting damage. This makes the manufacturer’s have minimum impact on the environment and persons
warranty null and void. during manufacturing, storage, transport, use and
disposal.
2.5 Use of instruction This includes the environmentally friendly use of natural
Danger – <Serious damage to health/risk to life>. This resources. ABB conducts an open dialog with the public
message indicates that an imminent risk is present. Failure to through its publications.
avoid this will result in death or serious injury. This product/solution is manufactured from materials that
can be reused by specialist recycling companies.
Caution – <Minor injuries>. This message indicates a
potentially dangerous situation. Failure to avoid this could 2.10 Information on WEEE Directive 2012/19/EU
result in minor injuries. This may also be used for property (Waste Electrical and Electronic Equipment)
damage warnings. This product or solution is subject to the WEEE Directive
2012/19/EU or corresponding national laws. Starting from
August 15th 2018, electrical and electronic equipment
Important. This message indicates indicates operator tips or marked with the crossed-out wheeled bin symbol may not
particularly useful information. It does not indicate a be disposed as unsorted municipal waste. Waste of
dangerous or damaging situation. electrical and electronic equipment (WEEE) shall be treated
separately using the national collection framework
Warning – <Bodily injury>. This message indicates a potentially available to customers for the return, recycling and
dangerous situation. Failure to avoid this could result in death treatment of WEEE.
or serious injury. Proper disposal prevents negative effects on people and
the environment, and supports the reuse of valuable raw
Attention – <Property damage>. This message indicates a materials. ABB can accept and dispose of returns for a fee.
potentially damaging situation. Failure to avoid this could
result in damage to the product or its surrounding area. 2.11 Transport and storage
— After unpacking the pressure transmitter, check the
2.6 Operator liability device for transport damage.
Prior to using corrosive and abrasive materials for — Check the packaging material for accessories.
measurement purposes, the operator must check the level
of resistance of all parts coming into contact with the — During intermediate storage or transport, store the
materials to be measured. pressure transmitter in the original packaging only.
ABB will gladly support you in selecting the materials, but For information on permissible ambient conditions for
cannot accept any liability in doing so. storage and transport, see paragraph “4.4 Storage” and
product datasheet. Although there is no limit on the
The operators must strictly observe the applicable national duration of storage, the warranty conditions stipulated on
regulations with regard to installation, function tests, the order acknowledgment from the supplier still apply.
repairs, and maintenance of electrical devices.
2.12 Safety information for electrical installation
2.7 Qualified personnel Electrical connections may only be established by
Installation, commissioning, and maintenance of the authorized specialist personnel in accordance with the
device may only be performed by trained specialist electrical circuit diagrams. The electrical connection
personnel who have been authorized by the plant operator. information in the manual must be observed; otherwise,
The specialist personnel must have read and understood the applicable protection type may be affected. Ground
the manual and comply with its instructions. the measurement system according to requirements.
4 2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A
Corrective maintenance work may only be performed by
trained personnel.
— Before removing the device, depressurize it and any
adjacent lines or containers.
— Check whether hazardous materials have been used
as materials to be measured before opening the
device. Residual amounts of hazardous substances
may still be present in the device and could escape
when the device is opened.
— Within the scope of operator responsibility, check the
following as part of a regular inspection:
Pressure-bearing walls/lining of the pressure
device
Measurement-related function
Leak-tightness
Wear (corrosion)
3 Transmitter overview
3.1 Transmitter components overview
Figure 1: Differential pressure transmitter components
Important. This picture shows transmitters equipped with Barrel type housing. Please consider that DIN housings are available.
2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A 5
3.2 Range & Span consideration
The 2600T Transmitter Specification Sheets provide all information concerning the Range and Span limits in relation to
the model and the sensor code.
The terminology currently used to define the various parameters is as follows:
URL: Upper Range Limit of a specific sensor. The highest value of the measured value that the transmitter can
be adjusted to measure.
LRL: Lower Range Limit of a specific sensor. The lowest value of the measured value that the transmitter can
be adjusted to measure.
URV: Upper Range Value. The highest value of the measured value to which the transmitter is calibrated.
LRV: Lower Range Value. The lowest value of the measured value to which the transmitter is calibrated.
SPAN: The algebraic difference between the Upper and Lower Range Values. The minimum span is the
minimum value that can be used without degradation of the specified performance.
TD: (or Turn Down Ratio) is the ratio between the maximum span and the calibrated span.
The transmitter can be calibrated with any range between the LRL and the URL with the following limitations:
LRL ≤ LRV ≤ (URL - CAL SPAN)
CAL SPAN ≥ MIN SPAN
URV ≤ URL
4 Opening the box Both certification and tag plates are supplied self-adhesive
attached to the electronics housing, as standard. Option I2
allows to select these plates as metal AISI 316 ss fastened to
4.1 Identification
the electronics housing with rivets.
The instrument is identified by the data plates shown in
Figure 2. The certification plate (ref. A): contains the The instrument may be used as a pressure accessory
certification related parameters for use in Hazardous area. (category III) as defined by the Pressure Equipment Directive
2014/68/EU. In this case, near the CE mark, you will find the
The Nameplate (ref. B), always made of AISI 316 ss, provides number of the notified body (0474) that have verified the
information concerning the model code, maximum working compliance. 266 pressure transmitters are in compliance
pressure, range and span limits, power supply, output signal, with EMC 2004/108/CE*.
diaphragms material, fill fluid, range limit, serial number,
maximum process working pressure (PS) and temperature
(TS).
The Tag plate, instead, provides customer tag number and
calibrated range.
6 2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A
B
Calib.
Range C
2600T Tag
Number
PRESSURE TRANSMITTER
4.3 Handling
The instrument does not require any special precautions
during handling although normal good practice should be
observed.
AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA
BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB
CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC
DDDDDDDDDDDDDDDDDDDDDDDDDDDDDDDD
2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A 7
5 Mounting
5.1 General 5.3 Mounting the transmitter
Study these installation instructions carefully before 5.3.1 Transmitter factory configuration consideration
proceeding. Failure to observe the warnings and The 266 pressure transmitter in your hands has been
instructions may cause a malfunction or personal hazard. factory calibrated to reflect the published declared
Before installing the transmitter, check whether the device performance specification; no further calibration is
design meets the requirements of the measuring point required in normal condition. ABB typically configures 266
from a measurement technology and safety point of view. pressure transmitters according to the user requirements.
A typical configuration includes:
This applies in respect of the:
— TAG number
— Explosion protection certification
— Calibrated span
— Measuring range
— Gauge pressure stability — Output linearization
8 2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A
5.4.3 B6 and B7 Barrel housing bracket details
1 – U-bolt
2 – U-bolt fixing washers and nuts
3 – Transmitter fixing bolts
4 – B6 or B7 bracket
5 – Fitting adapter (supplied with 266HSH)
2
Figure 5: Pipe and wall mounting bracket kits for P style transmitter with Barrel housing
72 (2.83)
145 (5.71)
11 (0.43)
72 (2.83)
18 (0.71)
16 (0.63)
54 (2.13)
1/2 - 14 NPT
39 (1.54)
Figure 6: Model 266H or 266N Hi overload resistant P-Style transmitter with DIN housing installed on a 2”pipe with optional bracket
(B7 Stainless Steel 316L)
2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A 9
128 (5.04) 29 (1.14) 120 (4.72) 30 (1.19)
83 (3.27) 18 (0.71) 18 (0.71)
66 (2.60)
72 (2.83)
145 (5.71)
11 (0.43)
56 (2.20) max.
72 (2.83)
1/2 - 14 NPT
105 (4.13) 22 (0.87) width across
flats of exagon 117 (4.60)
Figure 7: Model 266G or 266A P-Style transmitter with DIN housing installed on a 2”pipe with optional bracket
(B7 Stainless Steel 316L)
1 – U-bolt
2 – U-bolt fixing bolt and washer
3 – Transmitter fixing bolts
4 – B7 bracket
Figure 8: Pipe and wall mounting bracket kit (B7) for P style transmitter with DIN housing
10 2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A
6 Setup NOTICE
If cable glands are not used, the red transport screw
plugs must be replaced with suitable screw plugs when
6.1 Temperature measurement
the transmitter is installed. This is because the transport
— Mount the temperature sensor in the downstream pipe
screw plugs are not certified as protected against
of the primary element.
explosion. This requirement is particularly relevant in
— Consider the downstream straight pipe requirements.
hazardous areas
— If there is a significant difference between the
temperature of the measuring medium and the
Cable entries with an M20 x 1.5 thread
ambient temperature, the measuring error caused by
Devices with an M20 x 1.5 thread are optional supplied
heat conduction must be minimized by insulating the
with factory-installed cable glands and sealing plugs.
installation location accordingly.
— Use class “A” sensors to maximize accuracy.
Cable entries with a 1/2” NPT thread
The supplied transport sealing plugs do not have IP
6.2 General information
rating 4X / IP67 and are not approved for use in
The relevant directives must be complied with for the
potentially explosive atmospheres.
electrical installation! Because the transmitter cannot be
The transport sealing plugs must be replaced with
switched off, surge protection devices, lightning
suitable cable glands or sealing plugs during device
protection, or grid disconnect possibilities must be
installation. When selecting the cable glands or sealing
provided at the plant.
plugs, make sure they have the required IP rating and
Check that the existing supply voltage corresponds to that
explosion protection!
indicated on the rating plate. The same lines are used for
To offer IP rating 4X / IP67, the cable glands / sealing
both the power supply and the output signal.
plugs must be screwed in using a suitable sealing
If an optional surge protector is provided and if the
compound.
transmitter is used in a hazardous area, energy must only
be supplied via a voltage source with electrical isolation
Cable entry for PT100 temperature sensor
from the grid. Because the inherently safe power circuits of
A metal cable gland should always be used for the Pt100
the transmitter are grounded, a sufficient equipotential
cable since a shielded cable is used.
bonding must be ensured for the entire supply line.
Connect the shielding within the metal cable gland!
8.6.3 Installing the connecting cables
To offer IP rating 4X / IP67, the cable glands / sealing
Ensure that a drip loop (water trap) is used when installing
plugs must be screwed in using a suitable sealing
the connecting cables for the sensor.
compound.
If necessary, rotate the transmitter housing accordingly..
Safety instructions for use in Division 1
Conduit requirements for Div. 1 installations are not
addressed in this procedure. To avoid creating a
hazardous situation, ensure compliance with the
applicable standards, regulations, and recommendations
for installation in the country of use. Resistance
thermometer installation in classified Div. 1
2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A 11
6
L=
65 x 10
–
Cf + 10000 Terminal Function/comment
RxC C PWR+ Power supply
Where: PWR-
A (+) Modbus interface RS485
L = Line length in meters
B (-)
R = Total resistance in Ω (ohms) 1, 2, 3, 4 Terminals for connecting the Pt100
C = Line capacitance in pF/m resistance thermometer
Cf = Maximum internal capacitance of the HART field i NOTICE
devices located in the circuit, in pF
Connection of a Pt100 temperature sensor
Avoid routing cables with other electrical cables (with For the purpose of simulation, a 178 Ω resistor (206 °C /
inductive load, etc.) or near large electrical equipment. 402.8 °F) with 2 jumpers has been installed between the
terminals for the Pt100 connection.
6.5 Grounding This resistor (including the jumpers in the case of 4-wire
connections) must be removed before connecting the
Pressure transmitter housing should be grounded or Pt100 If a Pt100 is not connected, the resistor must not be
earthed in accordance with national and local electrical removed.
codes. Ground connection is mandatory for surge
protector equipped devices in order to ensure proper 6.7 Electrical data for inputs and outputs
functioning. Devices with Modbus communication
Protective grounding terminals (PE) are available outside Terminals PWR + / PWR -
and/or inside the housing of the transmitter. Both ground Supply Voltage 10.5 ... 30 V DC
terminals are electrically connected and it up to the user to
decide which one to use. The most effective transmitter
case grounding method is direct connection to earth i NOTICE
ground with impedance equal or less of 5 ohm. For current draw requirements see Fig. 25.
For power consumption based on specific supply voltages
6.1 Surge protector equipped terminal block see Fig. 26.
(optional)
i NOTICE
The Modbus protocol is not secure, as such the intended
application should be assessed to ensure that these
protocols are suitable before implementation.
12 2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A
Using the Modbus protocol allows devices made by Cable specification
different manufacturers to exchange information via the The maximum permissible length depends on the baud
same communication bus, without the need for any rate, the cable (diameter, capacity and surge impedance),
special interface devices to be used. the number of loads in the device chain, and the network
Up to 32 devices can be connected on one Modbus line. configuration (2-core or 4-core).
The Modbus network can be expanded using repeaters. — At a baud rate of 9600 and with a conductor cross
section of at least 0.14 mm2 (AWG 26), the maximum
length is 1000 m (3280 ft).
— If a 4-core cable is used in a 2-wire system, the
maximum length must be halved.
— The spur lines must be short (maximum of 20 m
[66ft]).
— When using a distributor with “n” connections, the
maximum length of each branch is calculated as follows:
40 m (131 ft) divided by “n”.
2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A 13
Figure 13:
14 2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A
6.8 Write Protection
Write protection prevents the configuration data from
being overwritten by unauthorized users.
If write protection is enabled, the “Z” and “S” buttons
(both internal or external) are disabled. However, it is still
possible to read out the configuration data using the
graphical user interface (DTM) or another, similar
communication tool. The control unit may be leaded if
required.
7.3.1 Write protection activation via external push button
When the instrument features the external non-intrusive
push buttons (digit R1 within instrument code), the write
protection function can be performed as follows:
— Remove the identification plate (see figure 17) by
releasing the holding screw lying on the bottom left
corner.
Figure 14: Pushbutton functionalities
— Use a suitable screwdriver to press the switch down
fully. (see figure 14)
6.10 Correct the zero shift
— Then turn the switch clockwise by 90°.
The zero shift caused by the installation may be cancelled
in different ways:
Important. To deactivate the switch, push it down slightly and then
turn counterclockwise by 90°. — Pressing the “Z” button (under the identification plate
6.8.1 Write protection activation via dip switch on the top of the transmitter, if present) or the “Zero”
internal button (on the connection board) for few
Standard instruments do not feature the external, non seconds will cause the output to go at 4 mA.
intrusive Zero, Span and Write Protection push buttons. To
activate this function it is necessary to proceed as — It is also possible to align the digital PV value to zero.
detailed below: To accomplish it raise the dip sw. 3 on the communication
— Remove instrument cover and the integrated digital board to the up (1) position and press the zero button.This
LCD display (if installed). functionality will align the PV digital value to 0 and if the
calibrated span it is zero based, the output will go at 4
— On the connection board, place dip switch 4 in “up” mA.
position.
— Using the optional LCD with keypad (“Configuration
6.9 Correcting the lower range value / zero shift of the pressure transmitter using the integral LCD
HMI” for further information).
During installation of the transmitter, transmitter, zero
shifts caused by mounting (e.g., a slightly oblique
mounting position due to a remote seal, etc.) may occur;
these must be corrected.
2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A 15
6.11 Installing/Removing the LCD display 7 Operation
—Unscrew the housing cover of the communication
board/LCD side. 7.1 Local push buttons functionality (option R1)
266 transmitters allow local adjustments via the on-board
Important. With an Ex d / Flameproof design, please refer to non intrusive push buttons, when selected. The push
the section “Securing the housing cover in flameproof areas”. buttons are located under the identification nameplate. To
gain access to the local adjustments release the fixing
— L1/L5 display versions can be installed in different screws of the nameplate and rotate clockwise the
positions (90° rotations) identification plate.
— LS display installation shall be performed carefully
plugging in sensor connections Warning - Potential damage to parts. Operating the control
buttons with a magnetic screwdriver is not permitted.
Important. Retighten the housing cover until it is hand-tight. If
necessary, refer to the section “Securing the housing cover in
1
flameproof areas”.
1 - Identification
nameplate
Important. Picture shows L1/L5 display versions. LS windowed
cover is dimensionally different (short) but features the same 2 - Zero pushbutton
threads and requires the same installation practices. 2
4 3 - Span pushbutton
6.12 Securing the housing cover in flameproof areas 4 - Write-protection
3
Each of the front faces of the electronics housing features pushbutton
a locking screw (hex-head socket screw) on the bottom
side.
— Install the housing cover to the housing by hand-
tightening it. Figure 17: Pushbutton functionalities
— Turn the locking screw counterclockwise to secure 7.2 Factory settings
the housing cover. This involves unscrewing the screw
Transmitters are calibrated at the factory to full span (0 to
until the screw head stops at the housing cover.
URL) or according to the customer’s span if specified. The
calibrated range is provided on the name plate whereas
the tag number on the additional tag plate. The calibrated
range and tag number are provided on the name plate. If
this data has not been specified, the transmitter will be
delivered with the following configuration:
Parameter Factory setting
Lower Range Value (LRV) (4 mA) Zero
Upper Range Value (URV) (20
Upper Range Limit (URL)
mA)
Output transfer function Linear
Damping 1 second
Transmitter failure (alarm) Upscale (21 mA)
1 line PV and output signal
Optional LCD HMI scale
bargraph
16 2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A
7.4 Configuring the transmitter without an 7.5 LRV and URV configuration
integral LCD HMI — Apply the pressure for the “lower range value” and
The “lower range value” and “span” parameters can be set wait approx. 30 s until it has stabilized.
directly on the transmitter using the external or internal — Press the “Z” button (internal or external) for at least
push buttons. 5 seconds. This sets the output current to 4 mA.
The transmitter has been calibrated by the manufacturer — Apply the pressure for the “upper range value” and
based on the order information. The tag plate contains wait approx. 30 s until it has stabilized.
information on the “lower range value” and “upper range
value” set. In general, the following applies: — Press the “S” button (internal or external) for at least 5
seconds. This sets the output current to 20 mA.
Important. Reducing station with adjustable pressure and — If required, reset the damping to its original value.
reference displays can be used as pressure generators.
— Record the new settings. The respective parameter
When making the connection, please ensure that there are no will be stored in the non-volatile memory 10 seconds
residual fluids (for gaseous testing materials) or air bubbles after the “Z” or “S” buttons are last pressed.
(for fluid testing materials) in the impulse lines, since these
can lead to errors during inspection. Any potential measuring
error for the pressure generator should be at least three times
smaller than the desired measuring error for the transmitter. It
is recommended that the damping is set to 1 second.
Message Description
! Oper Done The push button operation has been successfully executed
! Proc Too
The Pressure measured in input is too low and not acceptable for the requested operation
Low
! Proc Too
The Pressure measured in input is too high and not acceptable for the requested operation
High
! New URV
The Zero (Z) operation cannot be accepted because the URV would be shifted outside the Upper Sensor limit
Error
The Span (S) operation cannot be accepted because the new URV would be too close to the LRV and their difference lower
! Span Error
than the Minimum Span value
! Oper
The push button operation has been refused because the Write Protection is enabled.
Disabled
! LRV Too
New LRV is too low and not acceptable for the requested operation
Low
LRV Too
New LRV is too high low and not acceptable for the requested operation
High
URV Too
New URV is too low and not acceptable for the requested operation
Low
URV Too
New URV is too high and not acceptable for the requested operation
High
Device is armed to accept HART command 73 “Find Device”. This message can be triggered only during the device wakeup
Armed
operation
Important. When the transmitter has been rezeroed following the above procedure, a zero bias/offset value is applied and
stored in the transmitter memory.
Important. This action can be performed both by using the external, non-intrusive push buttons (option R1) and the on-board
buttons of the integrated LCD display.
2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A 17
i NOTICE Replace mode (DIP switches 1 and 2)
In normal mode the DIP switches 1 and 2 are in position 0.
Always disconnect the device from the power supply
If a replacement procedure is necessary, they will be
before making changes to DIP switches.
activated.
The device must then be restarted for the new configura-
— When replacing the electronics or the sensor,
tions to be loaded.
disconnect
the power supply and move DIP switch 1 to position 1.
— When replacing the secondary electronics, disconnect
the power supply and move DIP switch 2 to position 0.
— The sensor can be replaced when DIP switch 2 is in
position 1
i NOTICE
We recommend resetting the corresponding DIP switch to
position 0 after each replace operation.
18 2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A
Figure 19: Display keypad of L1 and L5 LCD display options
The keys (1) , (4) , (2) and (3) are available for the menu-controlled configuration.
— The menu/submenu name is shown at top of LCD display.
— The number/line of the currently selected menu item is displayed in the upper right of the LCD display.
— A scroll bar is located on the right edge of the LCD display which shows the relative position of the currently
selected menu item within the menu.
— Both of the keys (1) and (4) can have various functions. The meaning of these buttons is displayed below in
the LCD display above the respective button.
— You can browse through the menu or select a number within a parameter value using both keys (2) and (3) .
The button (4) selects the desired menu item.
Button (1)
Meaning
functionalities
Exit Exit menu
Back Back one submenu
Cancel Exit without saving selected parameter value
Next Select next position for entering numerical values or letters
The integrated LCD display (LS option) is located in the housing compartment with windowed cover of 266 Standard
HART version. It can be used to visualize the process measured variables as well as to configure the transmitter as
allowed only by the relevant “Easy Setup menu” which is the only menu available for Standard HART version.
Configuration is performed by the on-board buttons which are present when option “R1” is not selected or by external
Z and S push buttons under nameplate when “R1” is selected. In addition, diagnostic information is provided.
7.8 LCD (L1 and LS option) activation considerations
Gain access to the display by unscrewing the windowed cover. Please observe the Hazardous area prescription before
proceeding with the cover removal. For activation, see below.
2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A 19
7.10
7.8 Configuration of the pressure transmitter
Important. After 30 seconds without action on on-board buttons or
using the optional LCD HMI with keypad (menu-
controlled) external Z/S pushbuttons, the Standard HART transmitter
automatically exit the configuration menu.
The integral LCD option (L1 or L5 option) is connected on
the 266 Advanced HART communication board. It can be For Advanced HART and Safety HART versions the HMI
used to visualize the process measured variables as well
menu is divided in the following sections which can be
as to configure the display and the transmitter.
selected by acting on the keys (2) and (3) , once on
In addition, diagnostic information is provided. To access the display the desired sub-menu icon will be visualized,
the functionality of the HMI an activation procedure confirm your selection with the [SELECT] key (4) .
needs to be carried out. The keypad activation procedure
is different between the TTG (Through-The-Glass) L5 Follow the instruction on the screen to perform the
option and the conventional L1 option integral LCD. configuration of the different parameters.
7.12 HMI menu structure This menu allows the set-up of different functions
Standard HART version features only the Easy Setup menu relevant to the display itself. The menu driven structure
in a dedicated structure, different from other HART will guide you through the choice of some functional
versions. Once accessed the menu should be completed aspects as the display language and contrast. Moreover,
it is possible to choose in details what you want to see on
until the last step HART Revision is reached, then to return
the display: one or two lines with or without bargraph.
to the normal display view. For each step follow the Inside this menu there is the possibility of setting a
instructions on the screen and consider that for alfa/ protection password (security) and the display scaling
numeric parameters it is required to move digit by digit (linearization type, unit, LRV, URV). Display revision
until the right bottom corner display OK. Pressing the number available.
right on-board button or the external S pushbutton the
operation is confirmed, while pressing the left on-board
button or the external Z pushbutton the display change to
CANCEL to abort the operation by the associated button
(right/S).
20 2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A
Menu 3
Display
Exit Select
This menu allows the set up of different functions rele- This menu gives you all information about the device. The
vant to the display itself. The menu driven structure will menu driven structure will show you what is the sensor
guide you through theDisplay
choice of some functional
1 aspects type, the hardware and software
Display 1 revisions, the high and low
Language
as the display
Languagelanguage and contrast. Moreover, it is pos- sensor limits as well as the minimum applicable span.
English
sible to choose in details what you want to see on the dis-
Display Revision Language Deutsch
play: one or two lines with or without bar graph. Inside
Contrast Italiano
this menu there is the possibility of setting a protection
Mode
password
Back
(security) and the display scaling linearization
Select Cancel
type, unit, LRV, URV). Display revision number available.
Display 2 Display 2
Language
Display Revision Display Revision
Contrast
Mode 10.03.04
Back Select Back
The last section of this structured and driven menu gives
This menu allows the local calibration of the instrument.
you the possibility of changing the communication tag and
The menu driven structure will guide you through the
the MULTI-DROP mode with HART address numbers of the
choice of pressure sensor trimming (low or 3high), the out-
Display Display 2 Contrast
device.
put setting (set
Language to 4 or 20 mA) and at the end you can reset
these parameters
Display Revision sensor trimming, to user sen-
(to factory Contrast
sor trimming or to factory output trimming).
Contrast Max 100
Mode 50.000 Min 0
Back Select Back Edit Next
2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A 21
Min -14.504
0.0000 psi
Next Edit Next OK
6000.0 psi
PV Upper Range Value
Max 8702.3
Menu 1 Easy Setup Min -14.504
Easy Setup psi
InNext
the configuration level, Edit
use the (2) (3)
+Next OK
ABB266
English 1 Italian
English
Language
Tag Easy Setup Langauage Once in the alphabetic menu use Next (1)
German EasyTagSetup 11
Next Easy Setup Edit 2 Next OK
English key to position the cursor on the charac-
Language English ABB266
ABB2661
Italian
Set PV to Zero
Tag Easy Setup German Langauage ter that you want to change. Scroll the
Next
Next Easy Setup Edit 2
Edit Next Tag OK
English Italian
ABB266 ABB266 Langauage
Language English character list with (2) + (3), once on the
Tag
Next
Next
Easy Setup
Easy Setup
Edit 1
Edit 2 4
German PVTag
Next
Next
Next Unit
EditOK
OK selected one press “next” key (1) once
Italian
English
Language English ABB266
ABB266
Pa
PV
completed press “ok” (4).
TagUnit Easy
Next Easy Setup
Setup
Edit 2 4
German EasyTag
kPa
Next Setup
PV Unit
12
OK Display Line 1 View
ABB266
Next Edit Next
Italian OK
English MPa Pressure
ABB266
Pa
PV Unit Easy Setup
Tag psi Display
psi Line 1 View Scaled Outlet
Next Edit 2 kPa
Next Tag OK
Next Easy Setup Edit 4 Next PV Unit OK Press the (4) key Scroll the eng. units list
Output Percent
0.0000
This function set to psi
zero the PV value and to 4 mA the analogue output.
PV
Easy Setup 11
Lower Range Value
Set PV to Zero Simply press “ok” (4) key to activate the PV to zero function. Press Next
Max 8702.3
6000.0 psi
Easy Setup 12 Display Line 1 View
PV Upper Range Value Pressure
nu 1 Display Line 1 View
Easy Setup 13 Max 8702.3
Scaled Outlet
Process Temp Unit
Min -14.504
°C
Setup psi Output Percent
Process
Next Temp Unit Edit
Totalizer 1 °F
Totalizer 1
Next OK
Next Edit °R
Next OK
°C °K
Easy Setup 8 Linearization Type
Select Next Edit Cancel OK
Linear
Linearization Type Linearization curve
Cylindric Lying Tank
Easy Setup Linear 14 SphericalProcess
Tank Temp LVR
Next Edit Next OK
Process Temp LVR set -60.000 °C
Easy Setup 11 Max Damping
-60.000 °C
0.000
Damping
Next Edit Next OK
Max 60.000
Process Temp
Easy SetupUVR set 11 650.00° C
Max
Set PV to Zero
650.00 °C
Next Edit Next OK
Next Edit
2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A 23
Menu 2
Device Setup - Output Scaling
Device Setup - SW Write Protection - Factory Reset
- Process Variable
- Transfer Function
Exit Select
Set PV
Pa
kPa
MPa
psi
Next OK
Set PV 2 Set PV 2
Unit
Lower Range Value Lower Range Value
Upper Range Value
0.0000 psi
Back Select Next Edit
0.0000 psi
Max 8702.3
Min -14.504
Next OK
Set PV 3 3
Set PV
Unit
Lower Range Value Upper Range Value
Upper Range Value
psi
Back Select Next Edit
6000.0 psi
Next OK
24 2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A
Process Variable 3 Apply PV 1 Apply PV
PV Type Lower Range Value Lower Range Value
Set PV Upper Range Value
Apply PV
Parallel Shift
Back Select Back Select Back OK
Apply PV 1 Apply PV
Lower Range Value Upper Range Value
Upper Range Value
Set PV
Max 100.00
Min 0.0000
Next OK
Set PV to Value
Max
Next OK
PV Bias PV Bias
Set PV to Zero Reset PV Bias
Set PV to Value
Reset PV Bias
2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A 25
Device Setup 4 Output Scaling 1 Output Scaling 1 Output Scaling
Sw Write Protection Damping
Damping
Process Variable Unit
Transfer Function Lower Range Value
Output Scaling Upper Range Value 0.0000 Min 0.0000
Back Select Back Select Back Select Next OK
Pressure
inH2o 68F
inH2o
mmH2o
Cancel OK
Unit 2 Unit 2
Pressure
Flow Flow
Mass and Volume
Density Invalid
Back Select Back Edit
Flow
L/h
Imp Gal/min
Cancel OK
Unit 3 Unit 3
Pressure
Flow Mass and Volume
Mass and Volume
Density Invalid
Back Select Back Edit
SCF
hL
kg
Cancel OK
Unit 4 Unit 4
Pressure
Flow Density
Mass and Volume
Density Invalid
Back Select Back Edit
Density
SGV
ug/L
lb/
Cancel OK
Unit 5 Unit 5
Flow
Mass and Volume Level
Density
Level Invalid
Back Select Back Edit
26 2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A
Level
ft
m
mm
cm
Cancel OK
Unit 6 Unit 5
Other
h
day
uS
%
Cancel OK
2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A 27
Menu 3
Display Menu
Display - Language - Line 1 View
- Display Revision - Line 2 View
- Contrast - Bar View
Exit Select -Mode
Display 2 Display 2
Language
Display Revision Display Revision
Contrast
Mode 10.03.04
Back Select Back
28 2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A
Display 8 Display Scaling 1 Display 1 Linearization Type
Line 1 View Linearization type Linear
Line 2 View Unit Linearization Square Root
Bar View Lower range value Sqrt. 3rd power
Display Scaling Upper range value Linear Sqrt. 5th power
Back Select Back Select Back Edit Back OK
Pressure
inH2o 68F
inH2o
mmH2o
Cancel OK
Unit 2 Unit 2
Pressure
Flow Flow
Mass and Volume
Density Invalid
Back Select Back Edit
Flow
L/h
Imp Gal/min
Cancel OK
Unit 3 Unit 3
Pressure
Flow Mass and Volume
Mass and Volume
Density Invalid
Back Select Back Edit
SCF
hL
kg
Cancel OK
Unit 4 Unit 4
Pressure
Flow Density
Mass and Volume
Density Invalid
Back Select Back Edit
Density
SGV
ug/L
lb/
Cancel OK
2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A 29
Menu 5
Calibrate Calibrate
- Main Pressure Sensor
- Temperature Sensor
Exit Select
Calibrate
Unit 1 Main Pressure Sensor 1 Main Pressure Sensor 1 Low Trimming
Main Pressure
Main Pressure Sensor
Sensor Low Trimming 0.000
Temperature Sensor High Trimming Low Trimming
Max 60000
Min -100.00
Back
Back Select
Select Back Select Next Edit Next OK
6 Min -100.00
Main
Main Pressure
Pressure Sensor
Sensor Low Trimming
Low Trimming -60.000 °C
Temperature Sensor High Trimming
Max
-60.000 °C
Back Select Back Select Next Edit Next OK
Low Trimming
High Trimming 650.00 °C
High Trimming
Max
650.00 °C
Back Select Next Edit Next OK
30 2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A
Menu 7
Diagnostics
Diagnostics
... - Monitoring
Exit Select
Monitoring 3 Monitoring 3
Pressure
Output % Output %
Scaled Output
Static Pressure
Back Select Back
Monitoring 4 Monitoring 4
Pressure
Output % Scaled Output
Scaled Output
Static Pressure 2
Back Select Back
Monitoring 6 Monitoring 6
Output %
Scaled Output Sensor Temperature
Static Pressure
Sensor Temperature 24.326 °C
Back Select Back
2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A 31
Menu 8
Device Info
Device Info - High Sensor Limit - Hardware Revision
- Low Sensor Limit - Software Revision
- Minimum Span
Exit Select
32 2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A
Menu 9
Communication Communication
- Protocol Settings
- Protocol
Exit Select - HART Address
Communication 1 Communication 1
Protocol Settings
Protocol Settings
Protocol
HART Address
Software
Back Select Back
7.11 Damping (DAMPING)
7.13
Pressure transmitter output signals that are noisy as a
result of the process can be smoothed (damped)
electrically.
The additional time constant can be set between 0 s and
60 s in increments of 0.0001 s. Damping does not affect
the value shown on the digital display as a physical unit. It
only affects the parameters derived from this, such as the
analog output current, free process variable, input signal
for the controller, and so on.
The damping adjustment can be performed in different
ways:
— Via the the local HMI:
Enter the menu: > Device Setup > Output Scaling
> Damping.
Set the damping to the desired value.
— Via the Asset Vision Basic Software:
See Asset Vision Software Operating Instructions.
— Via the Hand Held Terminal:
See relevant operating instruction
2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A 33
7.14
7.12 Configuration with the PC/laptop You can use a handheld terminal to read out or configure/
or handheld terminal calibrate the transmitter. If a communication resistor is
A graphical user interface (DTM) is required for installed in the connected supply unit, you can clamp the
configuration of the transmitter via PC or laptop. For handheld terminal directly along the 4 ... 20 mA line. If no
operating instructions, please refer to the software communication resistor is present (min. 250 Ω), you will
description. need to install one in the line. The handheld terminal is
connected between the resistor and transmitter, not
The 266 transmitters can be configured by either one of between the resistor and supply unit.
the following device.
— Hand Held terminals like the ABB 691HT, ABB
DHH800-MFC, Emerson Process 375 and 475
provided the 266 EDD has been downloaded and
enabled in the terminal.
— ABB Asset Vision Basic, a new free of charge
software configurator downloadable at www.abb.
com/Instrumentation.
— Any DTM based software for HART instruments
configuration provided it is compatible with EDD or
DTM.
A - Transmitter
B - Supply unit (communication
resistor not provided in supply
unit)
Figure 21: Connection examples with communication resistor in the connection line
34 2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A
For additional information, refer to the operating 7.15 Advanced HART software revision history
instructions included with the handheld terminal.
Revision Release
Description
If the transmitter has been configured in the factory From To date
according to customer specifications for the measuring 7.1.11 First release 09/2009
point, all you have to do is mount the transmitter as
prescribed (to correct potential zero shifts, refer to the Bug Fixing:
section “Correcting the zero shift”), and switch it on. The — microbar and millitor units added
measuring point will now be ready for use. — HART command 35 bug fixed. By HART
If, however, you wish to make changes to the specificaiton #35 unit should not be
configuration, a handheld terminal or - preferably - a set pv unit
graphical user interface (DTM) is required. This DTM tool — if the local indicator was not mounted,
renders the device fully configurable. It supports both the only one operation via push buttons
HART protocol and PROFIBUS PA fieldbus protocol, and was performed
can be run on a PC or laptop, or as part of an automation
— MWP diagnosis classification become
system. Where FOUNDATION Fieldbus is concerned, the 7.1.11 7.1.12 06/2010
Maintenance instead of
device description (DD), which can be loaded onto various
configuration tools, is required for configuration Off-Specification
purposes. Improvements:
— replacement functionality improved
Refer to the installation manual provided with the
— internal improvements to reduce
software for the steps required to install the operating
tool. The most important parameters can be set via the factory configuration
path “Parametrize_Differential Pressure Measurement”. — more/stronger checks about process
variables goodness
The program offers the option of configuring, polling, and
— HART response time reduced (30%)
testing the transmitter.
In addition, offline configuration can be performed by Improvements:
means of an internal database. — factory configuration speeded up
7.1.12 7.1.14 01/2011
Each configuration step is subject to a plausibility check. — service detailed diagnosis
You can call up context-sensitive help at any time by implemented
pressing the “F1” key. Immediately after you have received
Bug Fixing:
the transmitter or before you change the configuration,
we recommend that you save the existing configuration — sensor trimming via local display was
data to a separate data storage medium, via the path performend only in kPa
“File_Save”. — diagnosis “Replace Error” no more
shown
7.13 Configuration with the graphical user
7.15 7.1.14 7.1.15 — unit strings on display (Nm3, bbl, t) 01/2013
interface (DTM) - System requirements were wrong
— Operating control program (e.g., ABB Asset Vision New Features:
Basic version 1.00.17 or higher) — new language (French & Spanish) on
2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A 35
7.16 Standard HART software revision history
7.17
Revision
Description Release date
From To
7.1.56 7.1.74
Several bug fixing
(HART 5)
10/2018
7.2.50 7.2.54 Several bug fixing and certification
(HART 7) HART burst mode removed
8 Error messages
8.1 LCD Display messages
The LCD HMI in case of transmitter errors or malfunctioning is capable of displaying specific error/fault
messages to help the user in identifying the problem and resolve it. In case of an alarm, a message consisting
of an icon and text appears at the bottom of the process display, as shown hereafter. Use the (1) key to call up
the information level. Use the “Diagnostics” menu to call up the error description with a help text. In the error
description, the error number is displayed in the second line (M028.018). Two further lines are used to describe
the error. The device status is divided into four groups. The message text beside this icon in the display
provides information about where to look for the error. There are the following areas: Electronic, Sensor,
Configuration, Operanting and Process.
Icon Description
Error / Failure
Maintenance required
36 2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A
8.2 Error states and alarms
— Communication Board / Electronic related error messages.
— Sensor related error messages
Note for the calibration of the current output by the user. For 266 Transmitters with SW.-Rev. </= 7.1.15 and alarm current setting
to ‘low alarm’ The calibration of the current output by the user requires to perform the calibration procedure with a suitable
configuration tool (DTM, EDD, FIM) and to finalize the procedure by saving the process with “save configuration as default”.
2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A 37
— Configuration related error messages.
Error
Tx LCD message Possible cause Suggested action Tx response
message
The Static Pressure Value produced in Use a HART configurator (DTM - Hand held) to
Input Simulation
C088.030 output is derived by the value place device back in to normal operating mode no effect
Active
simulated in input. (Remove the input simulation).
The Sensor Temperature Value Use a HART configurator (DTM - Hand held) to
Input Simulation
C088.030 produced in output is derived by the place device back in to normal operating mode no effect
Active
value simulated in input. (Remove the input simulation).
The Electronics or the Sensor have Change the replacement direction (if possible)-
38 2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A
— Operation related error messages
One (HIGH or LOW) or both connections between the Check valves and impulse line.
M018.038 PILD Output pressure sensor and the process is blocked either by Clean impulse line if necessary and no effect
plugging or closed valves. initiate PILD training.
PILD-Changed Op. Process conditions have changed to an extent that new A new Training is necessary for this new
M016.039 no effect
Conditions settings for the PILD algorithm are needed. process condition.
2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A 39
9 Maintenance — Check that there is no leakage from the sensor/
flange interface or from the vent/drain valves.
If transmitters are used as intended under normal
operating conditions, no maintenance is required. It is — The process flanges bolts (for 266DSx/MSx/PSx/
sufficient to check the output signal at regular intervals VSx/RSx models) should not show excessive rust.
(in accordance with the operating conditions), as In case one of the check points above fails, please replace
described in the instructions in the section “Operation the damaged part with an original spare part.
resp. Configuration of the transmitter”. If deposits are
expected to accumulate, the measuring equipment should The use of non original spare parts makes the warranty
be cleaned on a regular basis, in accordance with the void. In case you want ABB to perform the repair, please
operating conditions. Cleaning should ideally be carried send back the transmitter to your local ABB office
out in a workshop. complete with the return form that you find in this manual
appendix and include it with the device.
Important. In case of aggressive environment and any critical
condition, ABB recommends to check O-rings periodically. In 9.3 Removing/Installing the process flanges
case of damage, user shall replace them with original spare 1. Slacken the process flange screws by working on
parts. each in a crosswise manner (hexagon head, SW 17
mm (0.67inch) for 266DS/266PS/266VS or SW 13 mm
Repair and maintenance activities may only be performed (0.51 inch) / SW 17 mm (0.67 inch) for 266MS/266RS).
by authorized customer service personnel.
2. Carefully remove the process flange, making sure
When replacing or repairing individual components, that the isolating diaphragms are not damaged in
original spare parts must be used. the process.
Attention – Potential damage to parts. The electronic 3. Use a soft brush and a suitable solvent to clean the
components of the printed circuit board can be damaged by isolating diaphragms and - if necessary - the process
static electricity (observe ESD guidelines). Make sure that the flange.
static electricity in your body is discharged when touching
electronic components. If a remote seal is mounted on the 4. Insert the new process flange O-rings in the process
measuring equipment, it must not be removed (please refer to flange.
the dedicated document).
5. Attach the process flange to the measuring cell.
40 2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A
— Respect the below table indications for reinstalling the process flanges.
9.4 Pressure transducer replacement 11. The 266 can reconfigure itself with the previous
configured parameters thanks to the auto-
If the pressure transducer needs to be replaced proceed as configuration functionality.
follows:
12. Before powering on the transmitter raise dip-switches
1. Insulate the transmitter from the process by acting on 1 and 2 in up position. Connect the transmitter to
the manifolds or on the insulation valves. power supply, wait ten seconds and lower dip-
switched 1 and 2.
2. Open the vent valves to allow sensor depressurization.
13. After installing the transmitter on the bracket and
3. Disconnect the power supply and disconnect the connecting it to the manifold, perform a PV zero bias.
wiring.
7. Release the tang screw until nd rotate the housing until 3. Disconnect the power supply and disconnect the
its complete removal. wiring.
8. Unscrew the fixing bolts from the transducer and 4. Open the communication board compartment cover
remove the process flanges. and remove the LCD display (if installed).
9. The orings placed between the diaphragm and the 5. Remove the communication board and gently
flange (Viton or PTFE) must be replaced after every disconnect the connector.
disassembly.
6. Connect the sensor flat cable to the new electronic
10. Reassemble the flanges following the steps above in module with dip switch 1 in up position.
reverse order.
7. Connect the transmitter to power supply, wait ten
2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A 41
seconds and lower dip-switch 1 to 0 position. 266 can
Important. The number close to the CE marking of the
reconfigure itself with the previous configured
transmitter safety label identifies the Notified Body which has
parameters thanks to the auto-configuration responsibility for the surveillance of the production.
functionality.
9.6 Electronic upgrade from Standard to Advanced The other marking refers to the protection type used
HART according to relevant EN standards:
— Ex ia: Intrinsic safety, protection level “a”
Attention. In case of electronic upgrade from Standard to
Advanced HART it is necessary to perform a full transmitter — IIC: Gas group
reconfiguration since all customized data will be lost.
— T4: Temperature class of the transmitter
To upgrade the electronic module, proceed as follows: (corresponding to 135°C max) with a Ta from -50°C to
+85°C
1. Follow all points listed in the previous paragraph from
1 to 5. — T5: Temperature class of the transmitter
(corresponding to 100°C max) with a Ta from -50°C to
2. Connect the larger flat to the new electronic which +40°C
have to feature dip-switches 1 and 2 in up position.
— T6: Temperature class of the transmitter
3. Connect the transmitter to power supply, wait ten (corresponding to 85°C max) with a Ta from -50°C to
seconds and lower dip-switched 1 and 2. +40°C
42 2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A
b) Certificate ATEX II 1/2 G Ex ia IIC T4/T5/T6 Ga and II Ex ia IIIC T85°C Da
1/2 D Ex ia IIIC T85°C Da
IECEx certificate number
FM Approvals certificate number
IECEx FME 16.0003X (Tremezzina, Minden, Bangalore,
FM09ATEX0024X (Tremezzina, Minden, Bangalore and Shangai products)
Shanghai products)
The other marking refers to the protection type used
Important. This ATEX Category depends on the according to relevant EN standards:
application (see below) and also on the intrinsic safety
level of the transmitter supply (associated apparatus) — Ex ia: Intrinsic safety, protection level “a”
which can sometimes suitably be [ib] instead of [ia]. As it
— IIC: Gas group
is well known, the level of an intrinsic safety system is
determined by the lowest level of the various apparatus — T4: Temperature class of the transmitter
used, i.e., in the case of [ib] supply, the system takes over (corresponding to 135°C max) with a Ta from -50°C to
this level of protection. +85°C
The meaning of ATEX code is as follows: — T5: Temperature class of the transmitter
(corresponding to 100°C max) with a Ta from -50°C to
— II: Group for surface areas (not mines) +40°C
— 1/2: Category - It means that only a part of the — T6: Temperature class of the transmitter
transmitter complies with category 1 and a second (corresponding to 85°C max) with a Ta from -50°C to
part complies with category 2 (see next application +40°C
sketch).
About the applications, this transmitter can be used in
— G: Gas (dangerous media) Zone “0” (Gas) classified areas (continuous hazard) with
— D: Dust (dangerous media) its “process part” only, whereas the remaining part of the
transmitter, i.e. its enclosure, can be used in Zone 1 (Gas),
— T85°C: Maximum surface temperature of the only (see sketch below). Reason of this is the process part
transmitter enclosure with a Ta from -50°C to +40°C of the transmitter (normally called primary transducer)
for Dust (not Gas) with a dust layer up to 50 mm that provides inside separation elements to seal off the
depth. T85°C: as before for Dust for a Ta +85°C. electrical sensor from the continuously hazardous
process, according to the EN 60079-1. About Dust
Certificate IECEx Ex ia IIC T4/T5/T6 and
application, the transmitter is suitable for “Zone 21”
according to the EN 60079-0 and EN 60079-11 as it is
shown on the relevant part of the sketches.
Tank Silo
Primary transducer
266 Tx
266 Tx Category 1/2 Da Ex ia
Dangerous Category 1/2 Ga Ex ia Dangerous
medium medium
(process) (process)
Note: the transmitter can be connected to either [ib] or [ia] Note: the protection is mainly assured by the “IP” degree
supply (associated apparatus)certified [Ex ia] associated to the low power from supply. This can either be
Note for “Primary transducer”: see the certification for [ia] or [ib]
exceptions
2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A 43
c) Certificate ATEX II 1/2 G Ex db IIC T6 Ga/Gb and II 1/2 D Certificate IECEx Ex db IIC T6 Ga/Gb and Ex tb IIIC T85°C
Ex tb IIIC T85°C Db Db, Ta= -50°C to +75°C - IP67
FM Approvals Certificate number IECEx FME 16.0002X (Tremezzina, Minden and Shanghai
products)
FM09ATEX0023X (Tremezzina, Minden, Bangalore and
Shanghai products) The other marking refers to the protection type used
according to relevant EN Standards:
— Ex d: Explosion proof
The meaning of ATEX code is as follows:
— IIC: Gas group
— II: Group for surface areas (not mines)
— T6: Temperature class of the transmitter
— 1/2: Category - It means that only a part of the
(corresponding to 85°C max) with a Ta from -50°C to
transmitter complies with category 1 and a second
+75°C
part complies with category 2 (see next application
sketch).
About the applications, this transmitter can be used in
— G: Gas (dangerous media) Zone “0” (Gas) classified areas (continuous hazard) with
its “process part” only, whereas the remaining part of the
— D: Dust (dangerous media)
transmitter, i.e. its enclosure, can be used in Zone 1 (Gas),
— T85°C: Maximum surface temperature of the only (see sketch below). Reason of this is the process part
transmitter enclosure with a Ta (ambient of the transmitter (normally called primary transducer)
temperature) +75°C for Dust (not Gas) with a dust that provides inside separation elements to seal off the
layer up to 50 mm depth. electrical sensor from the continuously hazardous
process, according to the EN 60079-1.
Important. The number close to the CE marking of the About Dust application, the transmitter is suitable for
transmitter safety label identifies the Notified Body which has “Zone 21” according to the EN 60079-1 as it is shown on
responsibility for the surveillance of the production. the relevant part of the sketches.
Tank Silo
Primary transducer
266 Tx
Dangerous Dangerous
266 Tx Category 1/2 Db Ex
medium medium
Category 1/2 Ga Ex d tb
(process) (process)
IP code
About the degree of protection provided by the enclosure of the pressure transmitter, the 2600T SERIES has been
certified IP67 according to EN 60529 standard. The first characteristic numeral indicates the protection of the inside
electronics against ingress of solid foreign objects including dusts.
The assigned “6” means an enclosure dust-tight (no ingress of dust).
The second characteristic numeral indicates the protection of the inside electronics against ingress of water.
The assigned “7”means an enclosure water-protected against a temporary immersion in water under standardized
conditions of pressure and time.
44 2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A
According to ATEX Directive (European Directive 2014/34/
Important. It is the technical support for the ABB Declaration
EU and relative Standards which can assure compliance with of Conformity.
Essential Safety Requirements, i.e., EN 60079-0 (General
requirements) EN 60079-15 (Specification for electrical
Important. When installed this transmitter must be supplied by
apparatus with type of protection “n”), the pressure
a voltage limiting device which will prevent the rated voltage of
transmitters of the 2600T SERIES have been certified for the 42 V d.c. being exceeded.
following group, categories, media of dangerous
atmosphere, temperature classes, types of protection.
About the applications, this transmitter can be used in Zone
Examples of application are also shown below by simple
2 (Gas) (unlikely/infrequent hazard) as it shown on the
sketches.
following skecth (left side).
d) Certificate ATEX II 3 G Ex ic IIC T4/T5/T6 Gc IP67 and II 3 D
— II 3D Ex tD A22 IP67 T85°C
Ex tc IIIC T85°C Dc
— II: Group for surface areas (not mines)
Ta = -50°C to +75°C - IP67
— 3: Category of equipment
FM Approvals Certificate number
— D: Gas (Dangerous media)
FM09ATEX0025X (Tremezzina, Minden, Bangalore and
Shanghai products) — Ex tc: type of protection “tc” means protection by
enclosure technique
The meaning of Atex code is as follows :
— IP67: degree of protection of the transmitter acc.
— II: Group for surface areas (not mines)
EN60529
— 3: Category of equipment
— T85°C: Maximum surface temperature of the
— G: Gas (Dangerous media) transmitter enclosure with a Ta from -50°C to +40°C
— Ex nL: type of protection “n” with “energy limitation” for Dust (not Gas)
— IIC: gas group About the applications, this transmitter can be used in Zone
22 (Dust) (unlikely/infrequent hazard) as it shown on the
— T4: Temperature class of the transmitter (which
following skecth (right side).
corresponds to 135°C max) with a Ta from -50°C to
+85°C
— T5: Temperature class of the transmitter (which
corresponds to 100°C max) with a Ta from -50°C to
+40°C
— T6: Temperature class of the transmitter (which
corresponds to 85°C max) with a Ta from -50°C to
+40°C
Zone 2 Zone 22
Important - Note for pressure transmitter with combined approval. Before installation of the Transmitter, the customer should
permanently mark his chosen Protection Concept on the safety label. The transmitter can only be used with according to this
Protection Concept for the whole life. If two or more types of protection box (on safety label) are permanent marked, the pressure
transmitter must be removed from hazardous classified locations. The selected Type of Protection is allowed to be changed only
by manufacturer after a new satisfactory assessment.
2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A 45
10.1.1 Entities for “L5” option E, F and G, hazardous (classified) locations.
(display with TTG technology)
— Suitable for Class II, III, Division 2, Groups F and G,
HART Version with “L5” option (display TTG)
Ui= 30Vdc Ci= 5nF Li= uH hazardous (classified) locations.
Temperature Temperature Minimum Maximum Imax Power
— NonIncendive for Class I, Division 2, Groups A, B, C
Class - Gas Class - Dust amb. °C amb. °C mA W
T4 T135°C -50°C +60°C 100 0,75
and D, in accordance with Nonincendive field wiring
T4 T135°C -50°C +60°C 160 1 requirements for hazardous (classified) locations.
T5 T100°C -50°C +56°C 100 1,75
T6 T85°C -50°C +44°C 50 0,4 — Intrinsically Safe for use in Class I, II and III, Division
1, Groups A, B, C, D, E, F, and G in accordance with
PROFIBUS Version with “L5” option (display TTG) Entity requirements for hazardous (classified)
Ui= 17,5 Vdc Ii= 360 mA Pi= 2,52 W Ci= 5nF Li= 10 uH
Temperature Temperature Minimum Maximum locations.
Class - Gas Class - Dust amb. °C amb. °C — Temperature class T4 to T6 (dependent on the
T4 T135°C -50°C +60°C
T5 T100°C -50°C +56°C
maximum input current and the maximum ambient
T6 T85°C -50°C +44°C temperature).
FF / FISCO Version with “L5” option (display TTG) — Ambient Temperature range -40°C to +85°C
Ui= 17,5 Vdc Ii= 380 mA Pi= 5,32 W Ci= 5nF Li= 10 uH (dependent on the maximum input current and the
Temperature Temperature Minimum Maximum maximum temperature class).
Class - Gas Class - Dust amb. °C amb. °C
T4 T135°C -50°C +60°C — Electrical Supply range Minimum 10.5 Volts,
T5 T100°C -50°C +56°C Maximum 42 Volts (dependent on the type of
T6 T85°C -50°C +44°C
protection, maximum ambient temperature,
10.2 Ex Safety aspects and IP Protection maximum temperature class and communication
(North America) protocol).
10.2.1 Applicable standards — Type 4X applications Indoors/Outdoors.
According to FM Approvals Standards which can assure
compliance with Essential Safety Requirements. For a correct installation in field of 2600T Series pressure
transmitters please see the related control drawing.
FM 3600: Electrical Equipment for use in Hazardous
(Classified) Locations, General Note that the associated apparatus must be FM
Requirements. approved.
FM 3610: Intrinsically Safe Apparatus and Associated
Apparatus for Use in Class I, II, III, Division 1,
and Class I, Zone 0 & 1 Hazardous
(Classified) Locations.
10.2.2 Classifications
The 2600T Series pressure transmitters have been
certified by FM Approvals for the following Class,
Divisions and Gas groups, hazardous classified locations,
temperature class and types of protection.
46 2 6 6 H S H M O D B U S T R A N S M I T T E R | P R E S S U R E / T E M P E R AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H S H M T- E N R E V. A
—
Contact Us
Kansas Office
2705 Centennial Boulevard
Liberal, KS 67901
Ph: +1 620 626 4350
OI/266/HSHMT-EN 11.2019
—
We reserve the right to make technical changes or modify the contents of this document
without prior notice. With regard to purchase orders, the agreed particulars shall prevail.
ABB does not accept any responsibility whatsoever for potential errors or possible lack of
information in this document.
We reserve all rights in this document and in the subject matter and illustrations contained
therein. Any reproduction, disclosure to third parties or utilization of its contents – in
whole or in parts – is forbidden without prior written consent of ABB.
© ABB 2018
All rights reserved 3KXP000002R4201