This document contains settings for an ESM-20 engine monitoring and protection system. It lists various engine parameters such as nominal speed, overspeed limit, and shutdown settings for conditions like low oil pressure or high temperature. Measurement units, output modes, and activation states are provided for parameters like engine speed, temperature, pressure, and switch points.

Uploaded by

wilmer
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
127 views2 pages

ESM-20 Engine Settings Overview

This document contains settings for an ESM-20 engine monitoring and protection system. It lists various engine parameters such as nominal speed, overspeed limit, and shutdown settings for conditions like low oil pressure or high temperature. Measurement units, output modes, and activation states are provided for parameters like engine speed, temperature, pressure, and switch points.

Uploaded by

wilmer
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

ESM-20 settings

05.01.2014 14:13

GENERAL

Project Number
Installation Name
Engine Type
Classification
Engine Nominal Speed 750.0
ESM-20 Art. No.
Engine Numbers
ESM-20 Serial Numbers

PARAMETERS

Parameter Name Value Unit


Frequency from speed sensor at nominal engine speed 100.0 Hz
Overspeed limit of nominal engine speed 115.0 %
Engine speed output 1 mode 4-20 mA
Engine speed instrument range 750 rpm
Limit of slow turning counter 5.0 %
Frequency from TC speed sensor at maximum output 1000 Hz
TC A speed output 1 mode 4-20 mA
TC B speed output 1 mode 4-20 mA
Lubricating oil pressure start blocking level 0.3 bar
Lubricating oil pressure shutdown level 2.0 bar
HT water temperature shutdown level 110 C
HT water temperature instrument range 160 C
HT water temperature channel B enable/disable Disable
Engine shutdown 1 Close to shutdown
Engine shutdown 2 Close to shutdown
Engine shutdown 3 Close to shutdown
External shutdown 1 Close to shutdown
External shutdown 2 Close to shutdown
External shutdown 3 Close to shutdown
External shutdown 4 Close to shutdown
MCM shutdown Close to shutdown
MCM shutdown WBD enable/disable Enable
Stop solenoid 1 energised/de-energised on stop Energised
Stop solenoid 2 energised/de-energised on stop Energised
Stop solenoid 3 energised/de-energised on stop Energised
Stop solenoid 4 energised/de-energised on stop Energised
Failure indication stop solenoid 1 Enable
Failure indication stop solenoid 2 Enable
Failure indication stop solenoid 3 Enable
Failure indication stop solenoid 4 Enable
De-clutch delay 0 sec
Stop 1 off delay 60 sec
External shutdown 3 delay 0 sec
Shutdown prewarning delay 3 sec
Time delay for shutdown blocking 5 sec
External shutdown 3 shutdown blocking Disable
Start blocking from external shutdown 3 input Disable
Engine shutdown 3 shutdown blocking Disable
Status outputs N.O./N.C. Open when active
Lubricating oil shutdown override disable/enable Disable
Stop/shutdown status 1 N.O./N.C. Closed when active
Stop solenoid 1 on stop Enable
De-clutch function enable/disable Disable
Engine shutdown 1 override enable/disable Enable
HT temperature shutdown enable/disable Enable
Speed switch 1 40.0 %
Speed switch 2 13.0 %
Speed switch 3 50.0 %
Speed switch 4 90.0 %
Speed window 1 Low 53.0 %
Speed window 1 High 60.0 %
Speed window 2 Low 60.0 %
Speed window 2 High 67.0 %
Speed switch 1 on-delay 0 sec
Speed switch 2 on-delay 0 sec
Speed switch 3 on-delay 0 sec
Speed switch 4 on-delay 0 sec
Speed window 1 on-delay 2 sec
Speed window 2 on-delay 2 sec