0% found this document useful (0 votes)
1K views96 pages

ACS-2 Plus-Installationmanua P31903 02 0G0 08

This document provides installation instructions for an ACS-2plus controller. It details safety instructions, interface and bus topology, mounting instructions, power supply requirements, and commissioning steps.

Uploaded by

Vaggros
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views96 pages

ACS-2 Plus-Installationmanua P31903 02 0G0 08

This document provides installation instructions for an ACS-2plus controller. It details safety instructions, interface and bus topology, mounting instructions, power supply requirements, and commissioning steps.

Uploaded by

Vaggros
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Installation Instructions

ACS-2plus
Item no. 026547, 026548

P31903-02-0G0-08 Software-Version Subject to change


ZAC2P.00.0V0.10xx without notice
2012-09-20
.
Installation instructions / ACS-2 plus 3

Table of contents

1. Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1 Installation and subsequent extensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.2 Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.3 Firmwareupdate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

2. Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

3. General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

4. Protective measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

5. Important installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

5.1 Grounding / Shielding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11


5.2 Shielded lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.2.1 General shielding principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.3 Supply voltage and cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.3.1 ACS-2 plus 230V version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.3.2 ACS-2 plus 12V version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

6. Interface and bus topology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

6.1 Interface technology, RS485 bus systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15


6.1.1 Principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.1.2 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.1.3 Potential separation and terminating resistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.1.4 Ethernet connection (RJ45) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

6.2 Connection examples and networks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17


6.3 Interface connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
6.4 Pin assignment tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6.5 Connection examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

7. Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

8. Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

8.1 Installation site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23


8.2 Mounting ACS-2 plus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
8.3 Installing the interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
8.4 Inserting / changing lithium battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
8.5 DIP switches on the CPU board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
8.5.1 DIP switch S1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
8.5.2 DIP switch S2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
8.5.3 DIP switch S3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
8.5.4 DIP switch S4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

8.6 Memory extension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31


8.6.1 Calculating the memory requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
8.6.2 Inserting / changing memory card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
4 Installation instructions / ACS-2 plus

9. Dimensioning of the power supply unit and the battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

9.1 Dimensioning of the power supply unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37


9.2 Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
9.3 Integrated power supply unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

10. Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

10.1 Setup ACS-2 plus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43


10.2 Defining the controller in NetEdit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

11. LEDs, buzzer and buzzer stop push-button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

12. Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

12.1 Semiconductor outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54


12.2 Relay outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

13. Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

13.1 Digital inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55


13.2 Alarm lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

14. Structure/diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

14.1 CPU component mounting diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56


14.2 ACS-2 plus-structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

15. Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

15.1 Terminal assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59


15.2 General connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
15.3 Pin assignment of the host interface connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
15.4 Connecting a door strike . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
15.4.1 Connecting a fail secure door strike (with load current function) . . . . . . . . . . . . . 61
15.4.2 Connecting a fail safe door strike (with no load current function) . . . . . . . . . . . . . 62

15.5 Electric safety lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63


15.6 Turnstile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
15.6.1 Turnstile with one monitoring contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
15.6.2 Turnstile with two monitoring contacts in common . . . . . . . . . . . . . . . . . . . . . . . . 65
15.6.3 Turnstile with two separate monitoring contacts . . . . . . . . . . . . . . . . . . . . . . . . . . 66

16. Connection diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

17. Connections / technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89

17.1 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
17.2 Technical data 026547, ACS-2plus, 230 V version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
17.3 Technical data 026548, ACS-2plus, 12 V version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Installation instructions / ACS-2 plus 5

Appendix
1. Master sheet for terminal assignment empty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91

2. Master sheet for memory requirement calculation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92

3. Factory settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93

4. Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
6 Installation instructions / ACS-2 plus

1. Safety instructions

Danger for device or user if ignoring the following safety instructions!

* Please read this manual carefully and completely before installing and starting to work with the ACS-2
plus.

* Only use the ACS-2 plus:


- according to the designated use and
- in technically perfect condition
- in correctly installed condition
- according to the technical data.

* The manufacturer cannot be held liable for damage resulting from use contrary to the designated
purpose.

* Store the documents accompanying the product and the product-specific notes in a safe place.

* Mounting, programming, maintenance and repair work must be carried out only by authorized and
trained persons.

* Soldering and connecting work on the entire system may only be carried out when disconnected from
the power supply.

* Soldering work must only be performed with a temperature-regulated soldering iron, galvanically
separated from the power supply.

* The VDE safety regulations and the prescriptions of the local electricity supplier have to be observed.

* Danger: The ACS-2 plus must not be used in an explosion endangered environment or in rooms
with metal- or plastic-decomposing vapors.

1.1 Installation and subsequent extensions


Attention: Switch off the supply voltage before opening the device.

The VDE regulations and the regulations of the electricity supplier must be observed during installation. Carry
out the connections between the control unit and the external devices according to the connection diagrams.

A separator (circuit breaker) must be integrated in the installation of the building.

Use only shielded lines (see chapter 5 = Important installation instructions).

When using a DC door strike, special attention is to be paid to correct polarity. Use only DC door strikes
equipped with a protective diode.
Installation instructions / ACS-2 plus 7

1.2 Symbols
The following symbols are used in this manual:

Indicates danger.
Non observance can create a risk for people or the machine.

Gives important information on a subject, procedural information and warnings about


steps you make that could have far-reaching consequences.

Describes useful and practical mounting tips.

1.3 Firmware update


The firmware update can be done by an update via the superior software (e. g. IQ MultiAccess). The procedure
is described in the corresonding software manual. In general we recommend to update always to the latest
available version in order to use all features - including new options. The current firmware can be found on the
installation CD of IQ MultiAccess, it will be automatically copied into the firmware download directory of the IQ
MultiAccess computer (server) during the installation routine or can be downloaded for free from our homepage.
8 Installation instructions / ACS-2 plus

2. Overview

Functon (in alphabetical order) to set up via page


Address S1 or º Setup 28
Battery 39
Baud rate S1 or º Setup 29
Clock/Data S2 32
Flashbank S3 32
Interface card BU 4 / BU 5 26
Memory expansion BU 2 32
Power supply unit 39
Protocol S1 or º Setup 28
Service S1 29
Setup S1 28, 29, 46
Installation instructions / ACS-2 plus 9

3. General information
Access control systems are required if, for safety reasons, access to rooms or buildings is reserved to a certain
group of persons only.

Software
Novar GmbH offers a powerful and practice-oriented access control system. MultiAccess for Windows or IQ
MultiAccess is the parent user software for the connected access control devices. The definition of the access
rights for persons, actions, time orders and the transmission of the data to the hardware are carried out by
means of this software.

Hardware
The ACS-Compact, ACS-1, ACS -2 plus and ACS-2 plus are used as access control controllers and are
responsible for the complete functional sequence. After receiving the data from MultiAccess for Windows or IQ
MultiAccess, the controllers are ready for stand-alone operation. This means that the access control remains
active without any restrictions even if MultiAccess for Windows or IQ MultiAccess is not running.
When starting MultiAccess for Windows or IQ MultiAccess, the bookings carried out in the meantime are
automatically entered in the booking log file.

The display panel is another device. This device is not used for access control but for the indication of the
present location of certain persons, the door states and actions.

The ethernet interface (LAN) links between the PC and the controllers and is also responsible for antipassback
control. The PC configured with IQ MultiAccess must be in operation.

When ACS-2 plus are used in simplified mode the interface converter 026817.03 can be used.

If only one ACS-2 plus is connected, direct connection via the serial interface RS232 is also possible.

Combinations of these connection versions are possible.


10 Installation instructions / ACS-2 plus

4. Protective measures
Protective measures against electrostatic discharge
Modern semiconductor devices are increasingly endangered by electrostatic charges. The higher the integration
density the finer the structures on the chip. This leads to increased stress susceptibility.

With certain semiconductor devices, damage may already be caused at a voltage of less than 20V. This is a very
low value if you consider that, when walking over a carpet, more than 1000V may be generated.

Damage caused by electrostatic discharge only rarely leads to an immediate total failure. The semiconductor
structures are only affected to such a degree that the function is still available. However, a "burning trace" laid
once initiates a chemical process on the chip, which only makes the component unusable after a longer time
(possibly after several months).

Protection against electrostatic charge


The generating of electrostatic charging can generally not be avoided. The only possibility is, therefore, to
protect the electronics from such dangerous voltages.

- Discharge yourself by touching a suitable object (e.g., heating, water pipe, etc.)
in the immediate vicinity before starting to work on endangered parts.

- Use only soldering irons that are galvanically separated from the power supply and equipped
with an electronic temperature control.

Protective measures against overvoltages - transients


A protective shielding and grounding must be provided in order to avoid malfunctions and the destruction of
system components due to atmospheric overvoltage, indirect or conditionally direct effects of thunderstorms.
See DIN VDE 0845 part 1, Protection of telecommunication systems against lightning strokes, static charges
and overvoltages caused by power installations - measures against overvoltages.

A basic protection or a fine protection has already already been integrated into the corresponding devices by
Novar GmbH according to VdS requirements.

Complete protection against damage caused by lightning strokes and overvoltages is assured by the measures
taken for the external and internal lightning protection. The overvoltage protection is also called medium and
coarse protection. The consideration of additional requirements and measures for the installation of system
components mainly depends on the installation site and the equipment connected to the system.

Overvoltage caused, for example, by switching actions causes a very steep rise of voltage. This means that the
voltage can reach values of several kV within a few µs. Such voltage pulses are also called transients. They are
responsible for the destruction of electronic components.
Overvoltage protection means suitable measures which enable the absorption of such transients.

Causes of transient interference voltages


Transient voltages are often caused by atmospheric discharge, i.e., a lightning stroke. A lightning discharge may
release currents reaching maximum values of 100kA and more with very short rise times. This lightning current
causes a high voltage drop of the earth resistance of the building and the high lightning current steepness
induces high voltages in conductive loops.

The energy resulting from a lightning discharge causes the destruction of unprotected devices. Switching
actions in electrical systems also cause overvoltages.

High-frequency compensation processes in power supply networks are continued on high-voltage lines and are
coupled in the low-voltage level. Overvoltages and high-frequency istil
nterference power transients in low-voltage installations may also be caused by voltage drops, phase control,
etc. The rate of raise of current may even reach higher values than a lightning stroke.
Installation instructions / ACS-2 plus 11

5. Important installation instructions


(See also chapter 2 = Safety instructions)

5.1 Grounding / shielding


Use shielded lines and a suitable shielding connection for protection against electromagnetic interference
couplings occurring, for example, when switching electric appliances on and off.
Make sure that the line shields in the distribution boxes are connected so that there are no links to other
potentials. In the ACS-2 plus, all shields should be connected to one point using the shortest possible way.
The shield soldering bar serves as support for the connection of the ground conductors and line shields (see
below).

Circuit diagram DB1 and DB2 grounding bridges:

The grounding bridges are located on the CPU board near the power supply unit connector (see chapter 15.1)

The following shielding connections are possible:

Connect the shield soldering bar to the ground conductor and keep the grounding bridges closed
The DB1 and DB2 grounding bridges establish a capacitive coupling between the ground conductor and the
system operating voltage.
This way of wiring normally offers the best protection against mains-borne interferences and interferences
caused by cable shield discharges. However, this connection must only be used if PE and N are connected
separately (modern grounding) and if it is guaranteed that the ground conductor does not carry any low- or high-
frequency signals.

Connect the shield soldering bar to the ground conductor and open the grounding bridges
The capacitive coupling to the system operating voltage is now interrupted by the separated grounding bridges.
This connection can be used if the ground conductor is susceptible to interferences and it is feared capacitive
coupling could transmit these to the ACS-2 plus.

Connect the shield soldering bar to a proper system ground and keep the grounding bridges closed
The shield soldering bar must be connected to the newly created
system ground.
In case of a heavily loaded ground conductor, this is the
only possibility to guarantee a proper
deviation of the interferences
on the line shields.

To be observed: VDE 0800 part 2 edition July 1980


VDE 0800 part 2 AI draft
November 1982
12 Installation instructions / ACS-2 plus

5.2 Shielded lines


- Die ACS-2 plus devices are daisy chained via a shielded line.

Use cables of category Cat 5 or higher!

- The shielding of the incoming line is to be connected to the shield soldering bar of the ACS-2 plus. The
shielding of the outgoing line is not connected.

- The shield terminal bar in each ACS-2 plus must be connected to a separate PE.
(min. cable cross-section 1,5mm²)

If, when using 12V devices, it is technically not possible to connect ground potential to each ACS-2
plus, it is recommended to use a three wire cable for the power supply. The third core carries the
ground potential of the common power supply unit. This wire is connected to the shield terminal bar in
each ACS-2 plus. This method is only a temporary solution and should only be used in exceptional
cases.

- The shielding of the reader line is connected on one side to the shield terminal bar in the ACS-2 plus.

- The above mentioned points also principally apply to the ACS-2 plus module bus .

5.2.1 General shielding principle:


Installation instructions / ACS-2 plus 13

5.3 Supply voltage and cables

Please observe the informations about grounding and shielding in chapter 5.2.

5.3.1 ACS-2 plus 230 V version


Parameter Value

operating voltage range 230 V AC –15% +10%

mains frequency 40 – 60 Hz

power supply cable type NYM 3 x 1,5 mm²

5.3.2 ACS-2 plus 12V version


Parameter Value

operating voltage range 10.0V to 15.0V DC

current consumption depends on the reader type, the number of readers and the interface type

The door strike must be taken into consideration if its supply comes from the ACS-2 plus. The current
consumption of a door strike depends on the type, but lies somewhere between 200mA and 500mA.

The current consumption of an energized door strike must be known for each ACS-2 plus
when designing a 12V system.

The following drawing (powered on) shows the voltage drop of a 1.5mm2 cable compared to a 4mm2 cable. A
power consumption of 1A is calculated for each ACS-2 plus.
Observe the outgoing and return line.
14 Installation instructions / ACS-2 plus

The voltage diagrams 1 and 2 compare the effects of two cable cross-sections.
The required line cross-section must be calculated using the graphs shown above.

Note! Pay attention to legal rulings!

The local requirements must be observed for the line cross-section. VDE 0100 applies to
Germany. The output fuse of the power supply unit must have the appropriate current rating.
The highest current rating is determined by the smallest line cross-section of the supply cable.
Installation instructions / ACS-2 plus 15

6. Interface and bus topology


6.1 Interface technology, RS485 bus systems
There are two types of data transmission, point-to-point connection and multipoint connection.
Point-to-point connection means that two controllers are communicating with each other. A point-to-point
connection can be realized by means of an RS232 and a current loop interface.
Multipoint connection means that several controllers are communicating with each other. The RS485 interface
corresponds to a multipoint connection.

A bus topology is used for the RS485- interface.

6.1.1 Principle:

6.1.2 General information

The RS485 interface used is a bidirectional interface with bus capability. Up to 32 users can be connected which
can be transmitters as well as receivers. The line ends are provided with a terminating resistor.
The terminating resistors can be set on the interface by means of jumpers.
16 Installation instructions / ACS-2 plus

6.1.3 Potential separation and terminating resistor

Potential separation

Each RS485 line must be provided with one non-floating interface. The other interfaces must be floating. The
best position of the non-floating interface is in the middle of the RS485 line. The ACS-2 plus, fitted with the
interface which is not floating, must have a good grounding. If this is not the case, you should select another
ACS-2 plus. Here a good grounding is more important than the center of the RS485 line.

Terminating resistors

The terminating resistors must be placed at the first and the last device of a line. Here it depends on the type
of wiring.

Caution! Malfunction possible!

Star-shaped cabling of the devices is not allowed.


Installation instructions / ACS-2 plus 17

6.1.4 Ethernet connection (RJ45)


When installing an Ethernet interface card (Item no. 026840.29) instead of an RS 485 interface card, the ACS-2
plus can be linked to an existing network via Ethernet.
For more information about the interface installation, please refer to the mounting and installation instructions for
the interface.

6.2 Connection examples and networks


Example 1: Connection via interface converter. One or two RS485 lines, 5-wire line, ACS-2 plus only
application for up to 8 controllers with MultiAccess for Windows, 16 with IQ MultiAccess.

Example 4: Ethernet connection

Connection to the network via standard Ethernet cable (Cat 5 or higher) connected to a HUB, router or switch
via network terminal box (RJ45).
18 Installation instructions / ACS-2 plus

Example 3: Remote data transmission (RDT) and network

Remote data transmission (RDT):


Remote stations can be managed via Remote data transmission. It is possible to link one ACS-8
controller to one modem.

Network:
MultiAccess for Windows or IQ MultiAccess makes it possible to use existing networks.
MultiAccess for Windows can be accessed from up to 64 workstations. With IQ MultiAccess
there are no limitations. Any combinations with other controllers are possible.
Installation instructions / ACS-2 plus 19

6.3 Interface connections


These interface-
connections and the following
two tables help you to find the
required pin assignment.

The data lines must be switched


between the interface converter
and the first RS485 device. All
following devices are to be
connected 1 : 1
20 Installation instructions / ACS-2 plus

6.4 Pin assignment tables


Table 1: Pin assignment of interface converter and PC.

Device Pin RS232 RS485 (3-wire) RS485 (5-wire) Current


Loop

COM1/COM2 1 DCD
9-pole 2 RxD
3 TxD
4 DTR
5 GND
6 DSR
7 RTS
8 CTS
9 RI

COM1/COM2 2 TxD
25-pole 3 RxD
4 RTS
5 CTS
6 DSR
7 GND
8 DCD
20 DTR
22 RI

Interface converter 1 D1
2 D
3 D*
4 D1*
5 GND

Table 2: Pin assignment of the controllers/terminals

Device Pin RS232 RS485 (3-wire) RS485 (5-wire) Current


Loop

ACS-1, ACS-Compact, 1 GND GND GND T GND


ACS-2, ACS-2 plus, 2 TxD D D T+
ACS-2 plus 3 RxD D* D* R+
TRS6, TRS8, 4 D1 R GND
TRS10, TRS15 5 D1*

Display panel, 1 R GND


TRS20 / TRS30 2 TxD D D T+
3 RxD D* D* R+
4
5 GND GND GND T GND
6 D1
7 D1*
Installation instructions / ACS-2 plus 21

6.5 Connection examples

Example 1: Connection via interface converter RS485 5-wire technique.

Example 2: Connection via Ethernet.


22 Installation instructions / ACS-2 plus

7. Configuration

The ACS-2 plus controls the access to a room. The use of an additional interior reader makes it possible to
control also the exit of a room. The readers must function according to the same reading principle (magnetic card
reader, contactless reader or chip card reader).
The ACS-2 plus recognizes by means of the door monitoring contact whether the door was opened, was open
too long or the door was opened by force.

Configuration example 1: 2 entrance doors

Only the access to a room is controlled via a reader. It is possible


to exit the room without identification.
A door release push-button in the secured zone makes it possible
to release the door lock manually.
Up to 2 doors can be conventionally controlled via the ACS-2 plus.

Configuration example 2: 1 entrance door with


interior and exterior reader

Room access and exit are controlled by two readers. The


“antipassback control” option can be activated. Thus, the
whereabouts for each person can be determined.

Configuration example 3: Turnstile for entrance and exit

The ACS-2 plus can also be operated in the "turnstile" mode.


Instead of the door strike the turnstile is controlled. The door strike
relay 1 is used for the direction of rotation 1 and the door strike
relay 2 is used for the direction of rotation 2.
Installation instructions / ACS-2 plus 23

8. Mounting
8.1 Installation site
The installation site of the central unit must meet the following conditions:

* within the indoor area of a building


* within the secured area
* easily accessible
* no extraordinary environmental conditions, e.g., aggresive vapors, high
humidity, etc.
* mounting at eye level
* not visible from the outside
* sufficient strength to resist being pulled off
* sufficient lateral distance to adjacent devices
* inside wall of the secured zone – if the device can only be mounted on the outside wall,
break-through monitoring might be required.

8.2 Mounting ACS-2 plus


24 Installation instructions / ACS-2 plus

6. The commissioning of the device is described in chapter 10. The individual steps to be carried out while
the cover housing is open must be checked.
Then mount the housing cover, close it with the housing screws and seal it.

To assure safe and easy working, we recommend removing the battery holder during the
installation of the peripheral devices.

8.3 Installing the interface

The ACS-2 plus is delivered without any Interface card.


Depending on the connection type, a corresponding interface card must be installed and
configured.

Procedure for the installation / replacement of the interface:

- Switch the power supply off.

- Before removing the interface from the anti-


static film, discharge yourself
by first ouching the shield terminal bar
with both hands.

- Touch the interface only on the side and


try to avoid contact with
the connectors.

- Insert the interface. See illustration.

- Secure the interface with the provided screw.

- Please also read the document


accompanying the interface.
Installation instructions / ACS-2 plus 25

8.4 Insert/change lithium battery

Danger!

The device contains a lithium battery.


To avoid the risk of fire or burns, the battery must not be damaged, short-circuited or
reloaded. Do not contact it with fire or water. There is a risk of explosion if the battery is
changed improperly.
Replace the battery only by the same or an equivalent type recommended by the
manufacturer.
Dispose used batteries according to EU guidline 2006/66 (see info next page).

A batteriy change must only be carried out by qualified personell introduced to the VDE
regulations.

Danger of data loss / disruption in operation!


All data will be lost if the device is set to dead-voltage and the battery is removed. Data
must be reloaded to the controller via the AC-software function “Load data”. According
to the amount of data, this procedure may vary in length of time. During this time the
concerned doors are without any function.

If the power fails, the data is maintained by a lithium battery.


The life span of the lithium battery is approx. 3 years. If a power failure occurs for a lengthy period, the capacity
of the battery is considerably reduced.
Since the status of the battery cannot be clearly determined it is recommended that the battery be changed every
two years.

Lithium battery (type CR 2477N, 3 V 950 mAh) for data preservation in ACS-2plus = item no. 018050.

“Battery empty” Message


The ACS-2plus continuously checks the status of the lithium battery. If the voltage reaches a critical state,
MultiAccess for Windows or IQ MultiAccess issues the “Battery empty” message and the “Tamper” LED of the
ACS-2plus lights up.

In this instance, the battery must be replaced immediately.

Procedure

1. Open the device as described in


chapter 8.2 ,steps 1 to 4.

Bear in mind that the tamper switch is


activated; you have to reset the
tamper message of the respective
controller in MultiAccess for Windows
or IQ Multi Access.

Example in MultiAccess for Windows:


- System data
- System parameter
- Terminal
- Alarm/display reset
26 Installation instructions / ACS-2 plus

Example in IQ MultiAccess:
In IQ NetEdit:
a) Logical view
b) Select controller
c) Reset alarms/notifications
d) Select alarm to reset.

or in IQ MultiAccess (as of V7)


a) Controllers
b) Select controller
c) “Common” tab
d) Reset alarms/notifications
e) Select alarm to reset.

The "Tamper" LED of the ACS-2 plus extinguishes.

2. Pull lithium battery off plastic holder.

3. Insert new battery.

4. Reconnect the removed cables and close the device.


MultiAccess for Windows or IQ MultiAccess displays “Battery ok”. If necessary repeat “Reset Alarms”.
Installation instructions / ACS-2 plus 27

Notes on environment / disposal

Batteries and recharchable batteries - even free from heavy metal - must not be disposed of in domestic
waste. According to EU guidline 2006/66/EG users are obligated to return batteries for recycling. In Germany
they will be accepted for free at each selling point; alternatively they can be dispensed in public storage
vessels for old batteries or at public waste disposal authorities.

Outside of Germany please observe the local regulations on battery disposal.

Commercial batteries may contain heavy metal labelled by:

Pb for lead
Cd for cadmium
Hg for mercury

Please protect used lithium batteries (Li) against short-circuit by masking


both terminals using adhesive tapes or by depositing them into the original
packing.
28 Installation instructions / ACS-2 plus

8.5 DIP switches on the CPU board


(See also chapter 1 = Overview and chapter 14 = CPU component mounting diagram)

8.5.1 DIP switch S1


Table 1: Addresses
1 2 3 4 5 Function

0 0 0 0 0 Address 1 =
factory setting
1 0 0 0 0 Address 2
0 1 0 0 0 Address 3
1 1 0 0 0 Address 4
0 0 1 0 0 Address 5
1 0 1 0 0 Address 6
0 1 1 0 0 Address 7
1 1 1 0 0 Address 8
0 0 0 1 0 Address 9
1 0 0 1 0 Address 10
0 1 0 1 0 Address 11
1 1 0 1 0 Address 12
0 0 1 1 0 Address 13
1 0 1 1 0 Address 14
0 1 1 1 0 Address 15
1 1 1 1 0 Address 16
0 0 0 0 1 Address 17
1 0 0 0 1 Address 18
0 1 0 0 1 Address 19
1 1 0 0 1 Address 20
0 0 1 0 1 Address 21
1 0 1 0 1 Address 22
0 1 1 0 1 Address 23
1 1 1 0 1 Address 24
0 0 0 1 1 Address 25
1 0 0 1 1 Address 26
0 1 0 1 1 Address 27
1 1 0 1 1 Address 28
0 0 1 1 1 Address 29
1 0 1 1 1 Address 30
0 1 1 1 1 Address 31
1 1 1 1 1 Address 32

0 = OFF
1 = ON
Installation instructions / ACS-2 plus 29

Table 2: Protocol and Baud rate


6 7 Function Connected to Comment
0 0 Setup via terminal e. g. Event protocol (for The switch positions 1-7 are
program ethernet) ignored (see chapter 11).
0 1 9-Bit-Protocol = factory With these protocols, the
setting baud rate is set at 19200.
1 0 DIN-66090-Protocol Interface converter
COMx
1 1 RDT-Protocol Modem
ISDN card

0 = OFF
1 = ON

Table 3: Service function


8 Function
0 Factory setting (= service function not active / switch positions 1 - 7 according to table 1 and 2)
1 Service function (meaning of the switches 1 - 7 see table 4)

Warning! Switch 8 is reserved for service level functions and should


not be changed from the factory setting of OFF. Changing the
switch setting may cause loss of data.

Do not change factory settings!

Table 4: functions with the service switch activated


1 2 3 4 5 6 7 8 Function
1 1 1 1 1 1 1 1 Bootstrap

If the switch 8 ON state is detected, LED 1 on the CPU board flashes green until the next reset is carried out.
The flashing green LED indicates that a function is in process. When this LED lights permanently, the function
has been completed

Procedure of bootstrapping:
1. Set all DIP switches to ON
2. Reset (reset push-button)
3. LED 1 flashes (wait)
4. LED 1 lights permanently
5. Switch DIP S1 to the required
position (baud-rate, address,
protocol, etc.)
6. Reset (reset push-button)
30 Installation instructions / ACS-2 plus

Table 5: Special function for ACS-2 plus Setup (see Chapter 10).
1 2 3 4 5 6 7 8 Function
0 0 0 0 0 0 0 0 Setup via hyperterminal

An unintentional activation of the switch 8 can be ignored by resetting it to OFF (while the LED
1 flashes). After the reset, the device does not switch to the service mode and the switches keep
their original meaning.

Generally, a reset must be carried out, the setup must be controlled or set again and the
controller must be parameterized after activation / deactivation of the service mode (see
operating manual for for MultiAccess for Windows or IQ MultiAccess).

8.5.2 DIP switch S2


The settings of this switches depend on the used reader types (see chapter 16).

1 2 3 4 5 6 7 8 Designation

1 x x x 0 x x x Clock 1 (Pull down) Factory setting

x 1 x x x 0 x x Data 1 (Pull down)

x x 1 x x x 0 x Clock 2 (Pull down)

x x x 1 x x x 0 Data 2 (Pull down)

0 x x x 1 x x x Clock 1 (Pull up)

x 0 x x x 1 x x Data 1 (Pull up)

x x 0 x x x 1 x Clock 2 (Pull up)

x x x 0 x x x 1 Data 2 (Pull up)

0 = OFF 1 = ON x = any

8.5.3 DIP switch S3

1 2 Designation

0 0 The current flash bank is automatically selected. Factory setting

1 0 Flash 1 always active Only after consultation with


factory support
0 1 Flash 2 always active

1 1 Flash 1 always active

This switch block serves for selecting the firmware version. The factory setting ensures that the current version
is always automatically loaded. (This function becomes only valid after a firmware update and is described in this
context. It is irrelevant in the present version 1).

8.5.4 DIP switch S4


This switch block is reserved only for factory setting and internal test purposes. Therefore, the following factory
setting should not be changed:

1 2 Designation

1 0 Factory setting
Installation instructions / ACS-2 plus 31

8.6 Memory extention


The ACS-2 plus is equipped with a 1MByte memory which is firmly mounted on the CPU board.

The following additional memory extensions are possible:

- 026596 1 MB RAM memory card

- 026597 2 MB RAM memory card

- 026598 3 MB RAM memory card

Bear in mind that only one slot is available for the following memory cards. The memory extension required can
be determined by the following calculation:

8.6.1 Calculating the memory requirements


The memory requirements depend on the type and number of cards used as well as on the number of bookings
to be stored.

Use the table in the appendix to simplify the determination of the required memory and memory extension.

The following example explains the use of this table:


32 Installation instructions / ACS-2 plus

The gray highlighted fields must be filled in1:

1. Calculation of the memory requirements for the cards

Header: This is a preset value using 13 bytes for each card.

ID no.:  Enter the number of digits of the identification code to be used in the column no. of digits
required (e.g., 20 in case of 20-digit coding according to Novar or DIN).

 Divide this number by 2 (the required number of bytes results) and enter the result in the
column value.

 If the result of the division is no integer (e.g., 7.5), the result must be rounded upwards
to the next integer (in this case, to 8) and entered in the column rounded to the next
integer.

PIN-code:  Enter the number of digits of the PIN code to be used in the column no. of digits required
(the PIN code may comprise min. 4 and max. 8 digits).

 Divide this number by 2 (the required number of bytes results) and enter the result in the
column value.

 If the result of the division is no integer (e.g., 2.5), the result must be rounded upwards
to the next integer (in this case, to 3) and entered in the column rounded to the next
integer.

Version no.:  Enter the number of digits of the version number to be used in the column no. of digits
required. In the case of contactless cards, a unique number comprising 20 digits is used.
In this case, no version number is required (input = 0). In all other cases, the version
number may comprise 2 digits. It is recommended to enter 2.

 Divide this number by 2 (the required number of bytes results) and enter the result in the
column value.

 If the result of the division is no integer (e.g., 0.5), the result must be rounded upwards
to the next integer (in this case, to 1) and entered in the column rounded to the next
integer.

R/T-zones:  Enter the number of room/timezones required. Divide this amount by 8 and round to the
next integer. The ACS-2 plus will store only the room/time zones which are allocated to
doors controlled by this controller.

1
Please observe the minimum and maximum values shown in the column no. of digits possible.
Installation instructions / ACS-2 plus 33

Indexing:  If indexing is employed, each werden je Ausweis 6 BYTES belegt. Without indexing, the
value of this field is 0.

Macros  An ACS-2 plus can manage up to 64 macros. Enter in the column no. of digits required
the number of the macros to be implemented.

 Divide this number by 8 (the required number of bytes results) and enter the result in the
column value.

 If the result of the division is no integer (e.g., 1.5), the result must be rounded upwards
to the next integer (in this case, to 2) and entered in the column rounded to the next
integer.

Add the values entered in the column rounded to the next integer and enter the result in the field there below
(memory requirements per ID-card).
Enter the required number of cards in the field on the right-hand side (max. 65000).
Multiply the values entered in the fields memory requirements per ID-card and no. of ID-cards and enter the value
in the field memory requirements.
Enter the value of the field memory requirements also in the field subtotal 1.

2. Memory requirement calculation for BRE/APB2

 If working neither with BRE nor with APB, this entire block can be skipped.

BRE  This line can be skipped if not using the "barring repeated entry" function. If the BRE
function is activated, the number to be entered results from the number of door sides for
which the barring is required.16

 Multiply this number by 4 (the required number of bytes results) and enter the result in
the column Total..

APB  This line can be skipped if not using the "Antipassback control" function. Enter 1 in the
“Total” field for active APB.

Unique fixed value: For active BRE or for active APB or active BRE and APB, the specified fixed
value of 4 is to be added to the value(s) of the total fields.

(Even when BRE and APB are active together, only 4 is to be added,
not 8!).

 The memory requirement per ID card is calculated by adding the values in the Totals
column. Multiply this value with the number of the needed ID-cards and enter the result
in the Memory requirements field.

Enter the result in the subtotal 2 field.

2
For details about BRE / APB (= Barring Repeated Entry / Antipassback) look into the advanced functions
of MultiAccess for Windows (P32201-46-0G0-xx) or IQ MultiAccess (P032205-46-0G0-xx).
34 Installation instructions / ACS-2 plus

3. Calculation of the memory required for bookings

Booking: Each booking occupies 9 bytes. Multiply this value by the number of bookings to be stored and
enter the result in the column total.

A unique fixed value of 45 bytes is required for the bookings. Add this value to the value of the
field total and enter the result in the field memory requirements.

Enter the value of the field memory requirements, also in the subtotal 3 field.

Add the values of the fields Subtotal 1, Subtotal 2 and Subtotal 3 and enter the result in the field Required total
memory.

4. Analysis of the required RAM extension

Enter the (rounded) value of the field total memory requirements in the 4 empty and gray highlighted fields and
subtract this value from the free memory space shown above. If the result of one of these subtractions is at least
0 or a positive value, the memory extension of the corresponding column is required.
Installation instructions / ACS-2 plus 35

Example: The memory requirements for an ACS-2 plus controller is to be calculated based on the following
conditions:

 10,000 ESSER coded contactless cards3


 6-digit PIN code
 20 room/time zones
 Antipassback control
 Control of 7 macros
 100,000 bookings
 5 timers for BRE

Calculation:

Result: A 1 MB memory extension is required.

If the calculated required memory space exceeds the max. free memory space, alternative calculations
using various lower values can be carried out. It is, for example, possible to reduce the number of bookings
to be stored. Is it possible to switch less relays? Do you really require all room/time zones?

Approximate value
The standard equipment of 1 MB (0.5 MB free) is sufficient, according to the above mentioned calculation
method, for approx. 1,500 cards and approx. 20,000 bookings.

The required memory space for both of zones and ID cards will be displayed when the maximum values
are entered in IQ NetEdit (refer to the IQ MultiAccess Installation Instructions, P32205-26-0G0-xx,
additional settings tab).

3
The new trademark corresponds with the previous effeff coding.
36 Installation instructions / ACS-2 plus

8.6.2 Inserting / changing memory card

Caution! Data loss possible!

Never insert or remove the memory card while the ACS 2plus is powered up!
If the memory card is removed, all of the ACS-2plus data is irrevocably lost.

Danger of data loss / disruption in operation!


All data will be lost if the device is set to dead-voltage and the battery is removed. Data
must be reloaded to the controller via the AC-software function “Load data”. According
to the amount of data, this procedure may vary in length of time. During this time the
concerned doors are without any function.

Procedure:

1. Switch the ACS-2 plus off.

2. Disconnect the CPU board


completely from the power
supply (remove the battery,
disconnect the battery and
emergency power supply).

3. Before you take the memory


card out of the antistatic film,
discharge yourself by touching
the shield terminal bar with
both hands.

4. Touch the memory card only


on the side and try to avoid
contact, as far as possible, with
the connectors.

5. Insert the memory card. The


slot is located approximately in
the middle of the board. Fasten
it with the 4 screws provided.

6. Bootstrap the device according


to description on page 37
(table 3 and 4).

7. If the terminal settings have


been done via setup (cf.
chapter 10.1, variant 2), the
setup must be repeated.

8. Run “Load data / parameter-


ization” for the corresponding
controller in the AC-software.
Installation instructions / ACS-2 plus 37

9. Dimensioning of the power supply unit and the battery


9.1 Dimensioning of the power supply unit
The ACS-2 plus (Item no.026547) is delivered with a power supply/charging unit.
The ACS-2 plus (Item no.026548) is delivered without a power supply unit. The power supply is to be mounted
seperately or you can use an already existing power supply, e. g. from a hazard detection system.

If you use a 12V DC power supply, please observe that the output voltage must be free of
ground potential.

9.2 Battery
The ACS-2 plus is equipped with an battery holder for: 1 x 018002 Battery 12V 2.0Ah

Directives for the power supply


 The power supply must be connected to the mains via a separate fuse. If the electrical
installation is equipped with a residual current operated circuit-breaker (FI circuit-breaker), the
power supply must be provided with an own residual current operated circuit-breaker. The
fuse and the FI circuit-breaker should be located within the safety area, if possible.

 If the power supply is not part of the central unit, it must be mounted closely (with no
clearance) to ensure that an attack on the connection cable is not possible without
mechanically having to damage the housing.

 We recommend screwing the central unit and the power supply directly together. No
consumers from other systems may be connected to the voltage of the power supply.

 Only use approved batteries for the power supply. Only use batteries of the same age and
originating from the same production series.

By means of a flexible “Dual Lock” fastening tape, the ACS-2 plus can be attached to an battery 12V / 2.0A,
item no. 018002.

Cover with “Dual Lock” fastening tape Cover with installed battery

Stick one “Dual Lock” tape (item no. 055280) to the inside of the ACS-2 plus (see illustration) and one “Dual
Lock” tape to the battery.

Make sure that the surface is dry and free of grease.

Then press the battery on the Velcro fastening tape.


Use the red (+) and black/red (-) cable of the PCB for connecting the battery to the PCB.
38 Installation instructions / ACS-2 plus

The end-of-charging voltage of the battery charging unit is correctly set in the factory for Sonnenschein
batterys of the A500 series.
If it is necessary to change the setting, proceed as described in the chapter "Adjusting the end-of-charging
voltage".

Adjusting the end-of-charging voltage

1. The power supply must have reached the operating temperature. This requires the power supply to
be switched on for at least two hours with rated load and closed housing.

2. Connect the charged battery.


An incompletely charged battery causes an incorrect adjustment!

3. Adjust the voltage at the battery terminals or at MP1 and MP2 by means of the PO1 potentiometer
under consideration of the ambient temperature according to the table below.
Make sure of the battery type!

Warning! Destruction of device possible!

Ensure that only the PO4 potentiometer is adjusted...

1. After having measured the temperature

2. If the battery voltage deviates by >200mV from the nominal value, then adjust PO4 accordingly.

Determination of the current consumption when the power is on (example):

The ACS-2 plus controls two doors.

Component Current consumption Comment


CPU 200 mA Including alarm relay and tamper relay, because these are normally
activated.

Interface 200 mA RS485 interface with potential seperation


Reader (2x) 140 mA Two contactless readers each 70mA
Door strike (2x) 460 mA Novar door strike with direct current load function
Total 1000 mA

Larger actuators (e.g., door strikes) or devices with higher current consumption cannot be
supplied.
Installation instructions / ACS-2 plus 39

9.3 Integrated power supply unit

M Fully electronic power


supply/
charging unit
M Voltage stabilized
M Current limitation
M Redundancy standby
operation
with battery monitoring
M Total discharge protection
M Charge monitoring
M Battery fault detection
M Up to 2Ah battery
capacity

Directives for the power supply

 The power supply must be connected to the mains via a separate fuse. If the electrical
installation is equipped with a residual current operated circuit-breaker (FI circuit-breaker), the
power supply must be provided with an own residual current operated circuit-breaker. The
fuse and the FI circuit-breaker should be located within the safety area, if possible.

 If the power supply is not part of the central unit, it must be mounted nearby (with no
clearance) to ensure that an attack on the connection cable without mechanical damage to
the housings is not possible.

 We recommend screwing the central unit and the power supply together. No consumers from
other systems may be connected to the voltage of the power supply.

 Only use approved batterys for the power supply. Only use batterys of the same age
and originating from the same production series.

Installation

Warning! Danger for man and / or device


Please note safety instructions!

Disconnect the unit from the power supply when carrying out installation work.

When installing the power supply/charging unit in a central housing, make sure that the insulating foil included
in the delivery is placed between the bottom of the housing and the lower side of the board. Make sure
that the device is firmly screwed to the bottom of the housing.

The ground conductor connected to the supply circuit must be connected close to the connecting terminals of
the supply voltage.

When fastening the power line (NYM 3 x 1,5 mm²), make sure that the min. air gaps (4mm) and creep
distances
(5mm) between the electronic components or the peripheral devices and the power line are maintained.
If the neutral conductor cannot be clearly identified, a second fuse protection must be provided in the supply
circuit enabling a 2-pole separation from the supply circuit.

After installation, protect the connecting terminals against unintentional contact by means of the covers
included in the delivery.
40 Installation instructions / ACS-2 plus

Functional description

Two independent control loops are mounted on the mother board.

First control loop:

It supplies the central unit and the connected readers.

- protected with 2.0 AF (including external consumers)

- Second control loop:

It is used to charge the batterys. The charging current is limited to 120 mA.

The battery charging current is monitored and tracked depending on the temperature by means of an
NTC resistor.

The end-of-charging voltage of the battery charging unit is correctly set in the factory for
Sonnenschein batterys of the A500 series.
If it is necessary to change the setting, proceed as described in the chapter "Adjusting the end-of-
charging
voltage".

- Not stabilized powersupply Uext

A not stabilized direct current voltage is available for external consumers.

The suppy voltage for the central unit and the external consumers need not be adjusted.

Switching the power supply off:

If, during battery operation, the battery voltage falls below 9.5V, the power supply to the central unit and the
external consumers is switched off (cutoff relay).

Thus, unpredictable reactions in case of undervoltage are avoided and the battery is protected against total
discharge.

Faults:

The messages are issued via the outputs

Fault (ST1/3), HIGH active

The following fault causes are possible:

Power / ext. consumers / charging controller defective /


Battery defective or missing

Power supply (ST1/6), output , HIGH active.

This output is active when the power is on.


Installation instructions / ACS-2 plus 41

Adjusting the end-of-charging voltage

1. The power supply must have reached the operating temperature.


This requires the power supply to be switched on for at least two hours with rated load and closed
housing.

2. Connect the charged battery.


An incompletely charged battery leads to an incorrect adjustment!

3. Adjust the voltage at the battery terminals by means of the RV2 potentiometer under consideration
of the ambient temperature according to the table below.
Make sure of the battery type!

Warning! Destruction of device possible!

Ensure that only the PO4 potentiometer is adjusted...

1. After having measured the temperature

2. If the battery voltage deviates by >200mV from the nominal value, then adjust PO4 accordingly.
42 Installation instructions / ACS-2 plus

Connection/component mounting diagram


Installation instructions / ACS-2 plus 43

10. Commissioning
During commissioning of the ACS-2 plus, the following steps must be carried out:

1. Insertion of the back-up battery (see chapter 8.4).


2. Connection to the mains.
3. Bootstrap via the DIP switch S1 (see chapter 8.5.1, table 4).
The ACS-2 plus is brought to the defined initial state.
4. Checking/setting the necessary parameters via DIP switches or the ACS-2 plus setup.
5. Setting the controllers in NetEdit / IQ NetEdit (see chapter 10.2 and NetEdit / IQ MultiAccess
installation instructions).
6. Bootstrap of the controller via the MultiAccess for Windows software (see user manual of
MultiAccess for Windows part B, chapters 5 and 6) and/or IQ NetEdit / IQ MultiAccess.

Please refer to the table in the appendix containing the factory settings which are valid after bootstrap
and setting the controller as long as the factory settings have been applied or have not been changed.

10.1 ACS-2 plus setup


The ACS-2 plus is delivered in a predefined initial state (see factory settings in the following or in the
appendix).
This initial state must be checked and changed if necessary. There are two possibilities:

Variant 1: Basic setting via the DIP switch S1 (see chapter 8.5.1)

Procedure: 1. Setting the protocol


2. Setting the baud rate
3. Setting the address

There are only limited possibilities in making settings via the DIP switches (as described in
the tables in chapter 8.5).

The variant 2 of the ACS-2 plus setup offers considerably more comfortable and extensive
possibilities.

Variant 2: Basic setting via ACS-2 plus setup

General description: The ACS-2 plus setup makes it possible to check and to modify, if
necessary, the current settings of the ACS-2 plus. This is also
possible during normal operation without impeding operations.
The number of parameters to be modified depends on the DIP
switch setting of the S1 switch block.
44 Installation instructions / ACS-2 plus

Requirements: Laptop / notebook


Terminal program (e.g., Hyperterminal, Telemate, etc.
9-pole serial cable (socket - socket)

Cable assignment:

Procedure:  Set DIP switch S1 1-8 to OFF / 0:

1 2 3 4 5 6 7 8 Function

0 0 0 0 0 0 0 0 Setup via hyperterminal

 Turn the controller off briefly or press the Reset button.

 Use the above mentioned cable to connect one of the serial


interfaces of the notebook to the ST1 serial interface of the
ACS-2 plus (see chapter 14).

 Start your terminal program, e.g., Hyperterminal


Start - Programs - Accessories - (Communication with
Windows 2000) - Hyperterminal)

 Enter a unique name (e.g., ACS-2 plus setup) at New


Connection and select a corresponding icon. Confirm with
OK.
Installation instructions / ACS-2 plus 45

 In the following window under Connect using, select the


interface of the notebook to which the cable is connected
(COM1 in our example). The entries in the other fields are
irrelevant.

 In the next window, select the following settings and confirm


with OK.

 An empty input field appears.

 Enter in small letters: cea

and confirm with Enter. This input is not displayed on the


screen. In case of false entries, we recommend pressing
the backspace key several times in order to delete the
keyboard/input buffer.
46 Installation instructions / ACS-2 plus

This will open the ACS-2 plus setup:

******************************************************************************
** SETUP - ACS-2 plus **
******************************************************************************
Setup from: APPL. Login.
Label: [<no-name...>]

1. Communication
2. System
3. Save
4. Exit
No.:_

Meanings:

Setup from: Shows the mode via which the setup was called.

 APPL.-Login = Application login


The setup was called during current operation of the ACS-2 plus.

 BOOT-Login
The setup was called during the booting process of the ACS-2 plus.

The entry of cea [Enter] must be given within 3 seconds


during the booting process of the ACS-2 plus. During this
time the LED 1 (located on the CPU board on the left-hand
side of the heat sink, see 14.1) lights up green.

If cea [Enter] is not entered within this time during the booting
process, the APPL.-Login is called.

ACS-2 plus booting: Either interrupt the power supply for a


short period of time (pull the
power connector, deactivate the
emergency power supply, if
necessary),
Installation instructions / ACS-2 plus 47

or press the Reset button.

Normally, the APPL.-Login is sufficient.

Advantages: The normal course of operations is not disturbed.


Login must not be carried out within the above
mentioned 3 seconds during the booting process.

Certain DIP switch settings have priority and do not permit any
modifications in the Communication - To Host area (see section
Dependencies in this chapter). This error is signaled by the
message "Defined by DIP switch".

All peripheral devices connected to this ACS-2 plus


are out of operation (the doors are closed) during
BOOT-Login until the ACS-2 plus setup is left
again.

Label: shows the designation of the current ACS-2 plus.

Example: [<no-name...>] = no name was given.

If the controller already exists in NetEdit, the designation given there


is shown under Label.

Important: Use only unique designations!

The individual menu items:

General: The last line is the dialogue line. Here, different entries are allowed depending on the
cursor position. Use either small or capital letters. When entering a character which
is not allowed at this point or when pressing the Enter key only, no modification is
carried out. In this case, the program skips back to the next higher level (max. the
main menu).
False entries can be erased by character with the backspace key.
To delete the character buffer press the backspace key at least 3 times.

1. Communication:

Currently, there is only selection 1. To Host. Here, the parameters used by the ACS-2
plus for the communication with the host can be checked and set. The currently set
protocol is marked with "=>". The other current values are shown in the Status line.
48 Installation instructions / ACS-2 plus

Example:

1. 9-bit AC/CU Prot.


2.=>DIN prot.
3. RDT prot.
4. Event prot.
Status: Addr: 32; GAddr: 30; 19200 Baud
Change? Y/N:_

The current value is marked with "=>". To modify the values enter "y" and confirm
with Enter. Then you can select one of the consecutive numbers.

Settings and their use:

9-bit AC/CU prot.: ------

DIN prot.: Direct connection to RS232 (e.g., PC/notebook) or interface


converter

RDT prot.: For modem operation

Event prot.: For network operation via Ethernet interface

The following information can be checked and modified if necessary depending on


the selected protocol:

Baud rate: The current value is marked with "=>".


The value can be changed by entering “y” + Enter (at the question
Change? Y/N) and the consecutive number of the desired baud rate
(the factory setting is 19200).

Address: The current address and the permitted address range are displayed.
The value can be changed by entering “y” + Enter (at the question
Change? Y/N) and the desired address (the factory setting is 32).

Group address: The current group address and the permitted address range are
displayed. The value can be changed by entering “y” + Enter (at the
question Change? Y/N) and the desired address (the factory setting
is 30).

Difference between address - group address:


A maximum of 32 controllers can be managed via the address (addresses
1 - 32). An additional group address is used to extend the address range and
the number of controllers managed (max. 30 x 32 = 960 (MultiAccess for
Windows can currently manage a maximum of 512 controllers)).

Example: Group address Addresses


1 1 - 32
2 1 - 32
3 1 - 32
4 1 - 32
etc.
30 1 - 32

With the event protocol, the following fields must be checked or modified, if
Installation instructions / ACS-2 plus 49

necessary:

MVA: My Virtual Address.


When using the event protocol, the communication between the
controller and the host is controlled by events, i.e., as soon as a
booking is carried out on the controller, the booking is sent to the
host by the controller. In contrast with the common network
communication during which the server continuously polls the
controllers to check whether data are ready to be fetched, the
network is during this procedure only loaded when an event occurs.
Thus the general network performance is loaded less.
Each controller requires a unique virtual address for identification.
The current value is shown. This value can be changed to one of the
permitted values if necessary.

Each address may only exist once in the complete network!

DVA: Destination Virtual Address


The event protocol makes it possible to assign a virtual destination
address (the address to which the controller sends the data) to each
controller.

Example:

The virtual address (MVA) of every user is taken from NetEdit.


50 Installation instructions / ACS-2 plus

Network device: In this field the network card used must be entered.

Example: 1=>W&T Com-Server


2 = Novar TR/AC Ethernet (Item no. 026840.20)
Change? Y/N:_

2. System: This menu items offers the following possibilities:

1. Software version
2. Init / Delete component
No.: _

Software version: This display is used for information only and cannot be
modified. It shows the firmware version of the device.

Example: Softw: ZACS2.01.00.00


Date: 02.06.03
Press <Enter>....

It is recommended to check this information first since the described


functions partly depend on the firmware.

Init / Erase component: This menu item makes it possible to delete or reinitialize the
content of the exception handler. The exception handler is
a reserved internal memory area in which operations which
are relevant for the operating system are logged like in a log
file. The evaluation of these data, e.g., in case of incorrect
operation of the controller, is reserved for Novar GmbH
employees.
If this log file is to be created at a certain time, the previous
content can be deleted via this function.

3. Save: If the modifications made are to be saved, this menu item must be selected
before quitting the setup via the menu item 4. Exit.

4. Exit See 3. Save.


When quitting the setup via this menu item without prior selection of menu
item 3. Save, all modification are ignored and the original settings are
maintained.

The setup and its consequences remain active until quitting the setup via
Exit!
Installation instructions / ACS-2 plus 51

Settings for netwerk connection with Ethernet card:


As described previously, the following settings must be carried out:

 Event protocol
 Baud rate 19200
 MVA (virtual address of the current controller from NetEdit).
 DVA (virtual target address of the computer communicated with that of the controller = MVA
of the corresponding computer from NetEdit).

Dependencies:

1. If at least one of the DIP switches 6 and 7 of the S1 switch block (see 8.5.1) is set to ON, the
DIP switch settings have priority. This means that areas which cannot be modified via the
setup contain a corresponding note and the individual parameters cannot be selected.

Example: 1. 9-bit AC/CU prot.


2. DIN prot.:
3.=>RDT prot.
4. Event prot.
Status: Addr: 32; 19200 Baud
*** Defined by DIP switch! ***
Press <Enter>...

2. When using the interface of the ACS-2 plus controller for RDT, the interface is already used
by the RDT protocol.

Procedure: - Disconnect the RDT cable from the ACS-2 plus


- Connect the "setup" cable
- Carry out the boot login

10.2 Defining the controller in IQ NetEdit


After hardware installation (mounting and wiring the controllers) and setting the hardware parameters
(controller address, baud rate, protocol) using the DIP switches or the ACS-2 plus setup, the devices must then
be defined in the access control software.

(See also chapter 8.6 = DIP switches and the corresponding documents of the used interface cards).

Transferring the hardware configuration to the access control software is done by a special configuration
program which is part of the access control software. Detailed examples how to configer an ACS-2 plus
controller can be found in the manual of the configuration software.
52 Installation instructions / ACS-2 plus

11. LEDs, buzzer and buzzer stop push-button


The LEDS, the buzzer and the buzzer stop push-button are located on the LED board in the housing cover.

For differentiation of the controller types ACS-2plus and ACS-2 plus, the ACS-2 plus from firmware 7.00 on
activates all LEDs and the buzzer while booting.

The functions of the individual LEDs are explained in the following.

The buzzer stop push-button makes it possible to reset the buzzer manually. To do so, press the push-button
at least for 3 seconds with a suitable object.
Installation instructions / ACS-2 plus 53

Functions of the LEDs and the buzzer of the ACS-2 plus

LED/buzzer State Meaning


Off No operating voltage
Slow flashing Not parameterized
Normal (green)
Fast flashing Parameterization running
On Ready
Off No fault

On Battery/battery fault Without storing


Fault (yellow) Line failure (except for central reset)
Central reset
Off No tamper
Tamper (red):
On Tamper With storing
Off No alarm

On Number of incorrect With storing


Alarm (red): attempts
Unauthorized opening or
door was open too long
Off No message
Alert (red):
On Threat With storing
Off No message or manually reset
Buzzer
Fast interval Tamper/alarm With storing
On Line/battery/battery failure Without storing

The buzzer can be reset by pressing for approx. 3 seconds the buzzer stop push-button located on the front
plate.

Meaning of the LEDs of AC readers

LED-colour Basic After reading a Meaning


condition data carrier

yellow on Ready to read

yellow off - Device is idle


- Controller is not parameterized
- PIN- or door code entry is active

yellow flashing Reader is not allocated to any door

green on Permanent release

red on Permanent block

green on Door release

red on Data carrier not authorized

red flashing Read error

Additionally, the key and LED functions of the macro control of IQ MultiAccess are valid (see separate manual
"Supplementary functions of IQ MultiAccess", P32205-46-0G0-xx).
54 Installation instructions / ACS-2 plus

12. Outputs
12.1 Semiconductor outputs
The ACS-2 plus board is provided with 3 semiconductor outputs:

The output 5 (terminal 24)


and the output 6 (ST 5-3) are freely programmable via NetEdit.

The watchdog output (ST 5-2) signals (12V) that at least one watchdog reset occurred
since the last hardware reset.

Transistor in common collector circuit.


Two conditions are possible:
- Transistor conducting ( approx. 12V DC at the output).
- Transistor blocking (open output).

To be observed: Max. current carrying capacity = 50 mA,


short-circuit proof.

12.2 Relay outputs


The ACS-2 plus is fitted with 4 potential-free relay outputs with the following factory settings (see 15.1):

 2 door strike relays

The connected strikes with load current function can be checked for tampering (see also
chapter 15.4.1).

 1 tamper relay (activated when tampering occurs).


 1 alarm relay (activated during operation. It is released in case of an alarm or
when disconnected from the power).

An alarm is released when a watchdog reset occurs while the jumper ST8 is connected.

If the ACS-2 plus fails once, the relays 1 and 2 are so defined that the doors remain closed. It is not possible
to change the definition of these relays. The status of relay 3 (alarm) und relay 4 (tamper) can be defined using
jumper ST16.

Setting the reset status of relay 3 (alarm) and relay 4 (tamper):


 Press Reset button and hold
 Check if relay 3 (alarm relay) is OK, place jumper ST16 on 2-4 or 4-6, if necessary
 Check if relay 4 (tamper relay) is OK, place jumper ST16 on 1-3 or 3-5, if necessary
 Release Reset button again.
Installation instructions / ACS-2 plus 55

ST 16 Description

1-3 Relay 3 (alarm) is activated during system failure

2-4 Relay 4 (tamper) is activated during system failure

3-5 Relay 3 (alarm) is deactivated during system failure

4-6 Relay 4 (tamper) is deactivated during system failure

13. Inputs
13.1 Digital inputs
The four digital inputs are freely programmable via NetEdit.

13.2 Alarm lines


The eight alarm lines are freely programmable via NetEdit.
56 Installation instructions / ACS-2 plus

14. Structure/diagrams
14.1 CPU component mounting diagram

S1, S2, S3, S4: See also chapter 8.5 = DIP switches.
Installation instructions / ACS-2 plus 57

Description of the CPU board shown on the opposite page

Number Explanation

ST1 Extention plug for external modem certified byNovar GmbH

ST2 w.o. function

ST4 Power supply unit connector PIN 1+ 2 = OPEN


PIN 3 >1V-> battery fault
PIN 4 = 10-15V
PIN 5 = 0V
PIN 6 >1V-> power failure

ST5 Watchdog and danger signal output PIN 1 = 0V,


12V semiconductor outputs, 50mA, short-circuit proof PIN 2 = Watchdog output,
PIN 3 =output 6

ST6 Door strike monitoring jumper 1-3; 2-4 = no door strike monitoring
Jumper 3-5, or 4-6 = with door strike monitoring (only
admissible with connected door strike item no. 019 042 /
019 042.01. Deactivate if other devices, such as a flash
lamp, are connected to these outputs/relays).

ST7 Cover contact connection (open = tamper)

ST8 Jumper used to connect the watchdog to the alarm relay.

ST10 Alarm lines 7 and 8 / inputs 11 and 12 PIN 1 = Alarm line 7/ input 11
(terminate with 12.1 kOhm) PIN 2 = 0V
PIN 3 = alarm line 8/ input 12

ST13 Connector for LED board in the housing cover

ST14 Power supply connector for the controller voltage 45 and 46 (with 026547 12V DC, not
stabilized)

ST16 Basic definition of tamper / alarm relay (above board layout version no. 467.00-75-01/02)
Jumper 1-3 = Relay 3 (alarm) activated during system failure
Jumper 2-4 = Relay 4 (tamper) activated during system failure
Jumper 3-5 = Relay 3 (alarm) deactivated during system failure
Jumper 4-6 = Relay 4 (tamper) deactivated during system failure

BU2 Expansion connector for e.g., RAM cards

BU3 Service connector

BU4 and BU5 Slot for the host interface card

LD100 The LED lights up if a watchdog reset occurred previously

LD1 Software LED (see chapters 8.5.1 and 10.1)

LD3 If this LED lights up, then the ACS-2 plus runs with flash 1

LD4 If this LED lights up, then the ACS-2 plus runs with flash 2

Si1 1.0AT, for the terminals 13 and 22

Si2 belongs with ST2, therefore likewise w.o. function (1.0AF)

DB1 and DB2 Grounding/shielding (see chapter 5.1)


58 Installation instructions / ACS-2 plus

14.2 ACS-2 plus structure


Installation instructions / ACS-2 plus 59

15. Connections

15.1 Terminal assignment8

8
The standard factory settings of the inputs and outputs are described in this overview. However, individual
assignments are also possible if required. In this case, we recommend noting the changed assignment for
each ACS-2 plus controller. Copy and fill in the empty terminal assignment overview in the appendix and
store it together with the corresponding controller!
60 Installation instructions / ACS-2 plus

15.2 General connection diagram9

15.3 Pin assignment of the host interface connections


Pin RS232 RS485 (3-wire) RS485 (5-wire) Current loop
1 GND GND GND T GND
2 TxD D D T+
3 RxD D* D* R+
4 - - D1 R GND
5 - - D1* -

9
Inputs 11 and 12 as well as watchdog and danger signal output see chapters 13.2 and 14.1
Installation instructions / ACS-2 plus 61

15.4 Connecting a door strike


15.4.1 Connecting a fail secure door strike
Fail secure door strike = strike with load current function: The door is released if the coil is
energized

Tamper monitoring for the strike with load current function is possible. For this, a DC door strike must be
connected as shown above.

This function is not possible with a no-load current door strike and a door strike supplied with alternating
voltage or supplied by an external voltage source - not by the voltage source which supplies the ACS-2 plus.
The tamper monitoring for "door strike 1" and "door strike 2" must be deactivated (otherwise a board failure
of the ACS-2 plus is caused).

ACS-2 plus terminal assignment: With tamper monitoring


for relay 1: jumper ST6 = 4 - 6
for relay 2: jumper ST6 = 3 - 5

Without tamper monitoring (= standard)


for relay 1: jumper ST6 = 2 -4
for relay 2: jumper ST6 = 1 - 3
62 Installation instructions / ACS-2 plus

15.4.2 Connecting a fail safe door strike

Fail safe door strike = no-load current door strike: The door is blocked if the coil is energized

Tamper monitoring for the fauil safe door strike is not possible.

ACS-2 plus terminal assignment: for relay 1: jumper ST6 = 2 -4


for relay 2: jumper ST6 = 1 - 3
Installation instructions / ACS-2 plus 63

15.5 Electric safety lock

The differential alarm lines (inputs 5 - 10) must be terminated with 12K1.

Door monitoring
The interior door handle contact activates a door release on the ACS-2 plus. The door can
be passed without the error message "Unauthorized door release".
An external contact, e.g., a magnetic contact, must be used for door monitoring. The bolt
switching contact is only evaluated for positive drive condition when the intrusion detection
system is "disarmed". Its status is only shown when the intrusion detection system is
"disarmed". The bolt switching contact alarm group does not release and store an alarm when
the intrusion detection system is "armed".
64 Installation instructions / ACS-2 plus

15.6 Turnstile
The ACS-2 plus can manage, besides a standard door, 3 types of turnstiles. They differ from each other by
the number or the evaluation of the monitoring contacts.

Flow chart of a door monitoring with monitoring contacts to a “normal” door:

With the door closed, the monitoring contact is likewise closed. The respective alarm line recognizes the
necessary 12.1 KΩ, and thus a closed door. If the door is opened (A), the monitoring contact also opens and
signals that the door is open. The monitoring contact does not close until the door is closed again (B) and the
door is recognized as closed.

15.6.1 Turnstile with one monitoring contact


The door monitoring for a turnstile with a monitoring contact basically corresponds to a “normal” door.

In normal condition (with door closed) one of the contact makers A to D closes the monitoring contact (contact
maker A is used in the example).

Case 1) Exterior reader enabled. “Door open” is signaled when the turnstile is activated in the left
rotational direction. Contact maker B closes the monitoring contact again. The door is
recognized as closed.

Case 2) Interior reader enabled. In the right rotational direction, the monitoring contact is closed again
by contact maker D.

The rotational direction cannot be evaluated with this type. APB10 is recognized on the reader
used for the booking. If both sides are enabled, both persons are logged.

10
For details about BRE / APB (= Barring Repeated Entry / Antipassback), see the "Advanced functions of
MAfW"
(P32201-46-0G0-xx) and "Advanced functions of IQ MultiAccess" (P32205-46-0G0-xx).
Installation instructions / ACS-2 plus 65

15.6.2 Turnstile with two monitoring contacts in common


In this variation, depending on the rotary direction, first the one monitoring contact is activated and then the
other. The rotational direction is detected by means of the sequence.

Left rotational direction: = Exterior reader enabled. The contact maker A activates the inner monitoring
contact; afterwards, contact maker B activates the outer monitoring contact. In
between, the door is recognized as closed.

Right rotational direction: = Interior reader enabled. The contact maker A activates the outer
monitoring contact; afterwards, contact maker D activates the inner
monitoring contact. In between, the door is recognized as closed.
66 Installation instructions / ACS-2 plus

15.6.3 Turnstile with 2 two separate monitoring contacts


This variation corresponds basically to point 16.4.3, but the way in which the contact makers of the monitoring
contacts are organized results in a modified pulse sequence:

Left rotational direction: = Exterior reader activated. The respective monitoring contact is activated (in our
illustration, it was the inner contact).

Right rotational direction: = Interior reader activated. The respective monitoring contact is activated (in
our illustration, it was the outer contact).
Installation instructions / ACS-2 plus 67

16. Connection diagrams


Connection diagram for:
2601000 Magnetic card mortise reader, sm
2601600 Motorized magnetic card reader, sm
2634200 Chip card reader, sm
2634500 Chip card reader module for Siedle “Vario” System, item no. 027545 -
027548

2605300 Magnetic card swipe reader, sm

The terminals 10 and 11 of the reader must only be connected with motorized readers.
If only one reader is used, this reader is always connected as reader 1.

ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus
(see chapter 8.5):

Switch DIP Position Designation Reader


block

1 ON Clock 1
1
2 ON Data 1 Pull
3 ON Clock 2 down
2
4 ON Data 2
S2 5 OFF Clock 1
1
6 OFF Data 1 Pull
7 OFF Clock 2 up
2
8 OFF Data 2
68 Installation instructions / ACS-2 plus

Connection diagram for:


2601100 Magnetic card mortise reader, fm

2601700 Motorized magnetic card reader, fm

The terminals 14 and 15 of the reader must only be connected with motorized readers.
If only one reader is used, this reader is always connected as reader 1.

ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus
(see chapter 8.5):

Switch DI Position Designation Reader


block P

1 ON Clock 1
1
2 ON Data 1 Pull
3 ON Clock 2 down
2
4 ON Data 2
S2 5 OFF Clock 1
1
6 OFF Data 1 Pull
7 OFF Clock 2 up
2
8 OFF Data 2
Installation instructions / ACS-2 plus 69

Connection diagram for:


27710 Magnetic card mortise reader, sm, with keypad
27711 Motorized magnetic card reader, sm
27712 Magnetic card reader, sm
27740 Chip card reader, sm, without keypad
27741 Chip card reader, sm, with keypad

If only one reader is used, this reader is always connected as reader 1.

ACS-2 plus terminal assignment, DIP switch positions on the CPU board of the ACS-2 plus
(see chapter 8.5):

Switch DIP Position Designation Reader


block

1 ON Clock 1
1
2 ON Data 1 Pull
3 ON Clock 2 down
2
4 ON Data 2
S2 5 OFF Clock 1
1
6 OFF Data 1 Pull
7 OFF Clock 2 up
2
8 OFF Data 2
70 Installation instructions / ACS-2 plus

Connection diagram for


2604600 Magnetic card mortise reader, sm, with keypad
2604700 Motorized magnetic card reader, sm, with keypad
2634300 Chip card reader, sm, with keypad
2605400 Magnetic card swipe reader, sm, with keypad

If only one reader is used, this reader is always connected as reader 1.

ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus
(see chapter 8.5):

Switch DIP Position Designation Reader


block

1 ON Clock 1
1
2 ON Data 1 Pull
3 ON Clock 2 down
2
4 ON Data 2
S2 5 OFF Clock 1
1
6 OFF Data 1 Pull
7 OFF Clock 2 up
2
8 OFF Data 2
Installation instructions / ACS-2 plus 71

Connection diagram for:


2634000 Chip card reader, fm

2747010 Magnetic card reader module for Siedle “Vario” System, item no.
027545 - 027548

27580 "Plug in" magnetic card reader

If only one reader is used, this reader is always connected as reader 1.

ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus
(see chapter 8.5):

Switch DIP Position Designation Reader


block

1 ON Clock 1
1
2 ON Data 1 Pull
3 ON Clock 2 down
2
4 ON Data 2
S2 5 OFF Clock 1
1
6 OFF Data 1 Pull
7 OFF Clock 2 up
2
8 OFF Data 2
72 Installation instructions / ACS-2 plus

Connection diagram for:


2636600 Contactless reader, increased reading range

2636610 Contactless reader, increased reading range

If only one reader is


used, this reader
is always connected
as reader 1.

ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus
(see chapter 8.5):

Switch DIP Position Designation Reader


block

1 ON Clock 1
1
2 ON Data 1 Pull
3 ON Clock 2 down
2
4 ON Data 2
S2 5 OFF Clock 1
1
6 OFF Data 1 Pull
7 OFF Clock 2 up
2
8 OFF Data 2
Installation instructions / ACS-2 plus 73

Connection diagram for:


2638300 Contactless reader, sm, with keypad

If only one reader is used, this reader is always connected as reader 1.

ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus
(see chapter 8.5):

Switch DIP Position Designation Reader


block

1 ON Clock 1
1
2 ON Data 1 Pull
3 ON Clock 2 down
2
4 ON Data 2
S2 5 OFF Clock 1
1
6 OFF Data 1 Pull
7 OFF Clock 2 up
2
8 OFF Data 2
74 Installation instructions / ACS-2 plus

Connection diagram for:


2638700 Contactless reader, fm

If only one reader is used, this reader is always connected as reader 1.

ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus
(see chapter 8.5):

Switch DIP Position Designation Reader


block

1 ON Clock 1
1
2 ON Data 1 Pull
3 ON Clock 2 down
2
4 ON Data 2
S2 5 OFF Clock 1
1
6 OFF Data 1 Pull
7 OFF Clock 2 up
2
8 OFF Data 2
Installation instructions / ACS-2 plus 75

Connection diagram for:


26492 Legic reader without keypad, sm
26494 Mifare reader without keypad, sm

26481 Contactless reader with keypad, sm


2639000 Contactless reader, sm
2639010 Contactless reader, sm
26491 Legic reader with keypad, sm
26493 Mifare reader with keypad, sm

If only one reader is used, this reader is always connected as reader 1.

ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus
(see chapter 8.5):

Switch DIP Position Designation Reader


block

1 ON Clock 1
1
2 ON Data 1 Pull
3 ON Clock 2 down
2
4 ON Data 2
S2 5 OFF Clock 1
1
6 OFF Data 1 Pull
7 OFF Clock 2 up
2
8 OFF Data 2
76 Installation instructions / ACS-2 plus

Connection diagram for:


26420 Accentic reader proX2 without keypad
26421 Accentic reader proX2 with keypad
26422 Accentic reader mifare without keypad
26423 Accentic reader mifare with keypad
26424 Accentic reader Legic without keypad
26425 Accentic reader Legic with keypad

If only one reader is used, it is always connected as reader 1.

Terminal assignment ACS-2 plus: Settings of the DIP switches located on the CPU board of
the ACS-2 plus (see chapter 8.5):

Switch DIP Setting Designation Reader


block

1 ON Clock 1
1
2 ON Data 1 Pull
3 ON Clock 2 down
2
4 ON Data 2
S2 5 OFF Clock 1
1
6 OFF Data 1 Pull
7 OFF Clock 2 up
2
8 OFF Data 2
Installation instructions / ACS-2 plus 77

Connection diagram for:


29340 Accentic Fingerkey IK3

29341 Accentic Fingerkey mifare

If only one reader is used, it is always connected as reader 1.

Terminal assignment ACS-2 plus: Settings of the DIP switches located on the CPU board of
the ACS-2 plus (see chapter 8.5):

Switch DIP Setting Designation Reader


block

1 ON Clock 1
1
2 ON Data 1 Pull
3 ON Clock 2 down
2
4 ON Data 2
S2 5 OFF Clock 1
1
6 OFF Data 1 Pull
7 OFF Clock 2 up
2
8 OFF Data 2
78 Installation instructions / ACS-2 plus

Connection diagram for:


27660 Insertic 50 reader proX1/2
27662 Insertic 50 reader mifare
27664 Insertic 50 reader Legic
27666 Insertic reader proX1/2 without keypad
27667 Insertic reader proX1/2 with keypad
27670 Insertic reader mifare without keypad
27671 Insertic reader mifare with keypad

If only one reader is used, this reader is always connected as reader 1.

ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus
(see chapter 8.5):

Switch- DIP Position Designation Reader


block

1 OFF Clock 1
1
2 OFF Data 1
Pull
down
3 OFF Clock 2
2
4 OFF Data 2
S2
5 ON Clock 1
1
6 ON Data 1
Pull up
7 ON Clock 2
2
8 ON Data 2
Installation instructions / ACS-2 plus 79

Connection diagram for:


26480 Contactless reader, sm

2648010 Contactless reader, sm

If only one reader is used, this reader is always connected as reader 1.

ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus
(see chapter 8.5):

Switch DIP Position Designation Reader


block

1 ON Clock 1
1
2 ON Data 1 Pull
3 ON Clock 2 down
2
4 ON Data 2

S2 5 OFF Clock 1
1
6 OFF Data 1
Pull
7 OFF Clock 2 up
2
OFF Data 2
8
80 Installation instructions / ACS-2 plus

Connection diagram for:


26484 Legic reader (Oris)

26485 Mifare reader (Oris)

If only one reader is used, this reader is always connected as reader 1.

ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus
(see chapter 8.5):

Switch DIP Position Designation Reader


block

1 OFF Clock 1
1
2 OFF Data 1 Pull
3 OFF Clock 2 down
2
4 OFF Data 2
S2 5 ON Clock 1
1
6 ON Data 1 Pull
7 ON Clock 2 up
2
8 ON Data 2
Installation instructions / ACS-2 plus 81

Connection diagram for:


027540 - 027543 proximity / contactless reader, Siedle

If only one reader is used, it is always connected as reader 1.

Terminal assignment ACS-2 plus: Settings of the DIP switches located on the CPU board of
the ACS-2 plus (see chapter 9.6):

Switch DIP Setting Designation Reader


block

1 ON Clock 1
1
2 ON Data 1 Pull
3 ON Clock 2 down
2
4 ON Data 2
S2 5 OFF Clock 1
1
6 OFF Data 1 Pull
7 OFF Clock 2 up
2
8 OFF Data 2
82 Installation instructions / ACS-2 plus

Connection diagram for:


023330 - 023343 contactless proX2 reader Siedle

If only one reader is used, it is always connected as reader 1.

Terminal assignment ACS-2 plus : Settings of the DIP switches located on the CPU board of
the ACS-2 plus (see chapter 9.6):

Switch DIP Setting Designation Reader


block

1 OFF Clock 1
1
2 OFF Data 1
Pull
down
3 OFF Clock 2
2
4 OFF Data 2
S2
5 ON Clock 1
1
6 ON Data 1
Pull up
7 ON Clock 2
2
8 ON Data 2
Installation instructions / ACS-2 plus 83

Connection diagram for:

27575 Contactless reader “Plug in”

2757520 Contactless reader “Plug in”

27577 Mifare reader “Plug in”

27579 Legic reader “Plug in”

If only one reader is used, this reader is always connected as reader 1.

ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus
(see chapter 8.5):

Switch DIP Position Designation Reader


block

1 ON Clock 1
1
2 ON Data 1 Pull
3 ON Clock 2 down
2
4 ON Data 2
S2 5 OFF Clock 1
1
6 OFF Data 1 Pull
7 OFF Clock 2 up
2
8 OFF Data 2
84 Installation instructions / ACS-2 plus

Connection diagram for:


2757020 Keypad with analogue interface, “Plug in”
Installation instructions / ACS-2 plus 85

Connection diagram for:


2607002 Keypad, sm housing

2607202 Keypad, fm housing

2607102 Keypad, sm housing, splashproof

2607302 Keypad, fm housing, splashproof


86 Installation instructions / ACS-2 plus

Connection diagram for:


26064 Keypad, sm plastic housing
Installation instructions / ACS-2 plus 87
88 Installation instructions / ACS-2 plus
Installation instructions / ACS-2 plus 89

17. Connections / technical data


17.1 Connections
Interface to the host system: 1 x interface slot inserted with:
- RS232 interface (026840.03)
- RS485 interface (026692, 026693)
- Ethernet interface (026840.29)
- Current-Loop interface (026840.16)
Keypad: 2 x external keypads with 2-wire technique connectable.
(The keypad can also be combined with a reader.)
Reader: 2 x external clock data readers connectable.
Supported reader types:
- contactless reader
- magnetic card reader
- chip card reader
Relays: 2 x door strike relays, max. 1.25 A / 24 V (Observe notes in chapter 15.4.1!)
1 x alarm relay
1 x tamper relay
Outputs: 2 x semiconductor outputs
1 x watchdog output (semiconductor)
Inputs: 8 x alarm line inputs
4 x semiconductor inputs (e.g., door strike key, monitoring contact)
Housing monitoring: 1 x cover contact (tamper)
Extensions: 1 x universal slot for RAM extension and future applications.
Battery support: 1 x 018002 (2.0 Ah)

17.2 Technical data 026547, ACS-2 plus, 230V version


Rated operating voltage 230 V AC
Operating voltage range 230 V AC -15% to +10%
Mains frequency 60 - 40 Hz
Power comsumption 24 VA
Output voltage Uext. 12 V DC not stabilized
Maximal current drain 1,0 A
Maximal charging current 120 mA
Allowed battery capacity 2.0 Ah
No. of batterys connectable 1 max.
Battery monitoring permanently with temperature-controlled charging current
Operating temperature range 0EC to +45EC
Storage temperature range -25EC to +70EC
Protection class accord. to DIN40050 IP40
Environmental class accord. to VdS II
Housing dimensions in mm 250 x 210 x 100

17.3 Technical data 026548, ACS-2 plus, 12V version


Rated operating voltage 12 V DC
Operating voltage range 10 V DC to 15 V DC
Maximum residual ripple 35 mV
Current (typical) 200 mA
Max. current consumption with U_b 400 mA
Operating temperature range -0°C to +45°C
Storage temperature range -25°C to +70°C
Protection class according to DIN 40050 IP40
Environmental class according to VdS II
Contact rating of the relays 30 V DC/1A
Dimensions of the housing in mm 250 x 210 x 100
90 Installation instructions / ACS-2 plus

Appendix

1. Master sheet for terminal assignment, empty


(For the documentation of individual in- and output assignments deviating from the standard
assignment)

2. Master sheet for the calculation of the memory requirements,


empty
(For the calculation of the memory requirements for the ACS-2 plus controllers)

3. Factory settings

4. Index
Installation instructions / ACS-2 plus 91

Terminal assignments deviating from the standard

Company:...................................................................................................................................

Device No...................................................Site:.........................................................................
92 Installation instructions / ACS-2 plus
Installation instructions / ACS-2 plus 93

Factory settings
List in alphabetic order:

Function Factory setting Switch block DIP Chapter Table

Address Address 1 S1 1 = OFF 851 1


2 = OFF
3 = OFF
4 = OFF
5 = OFF

Baud rate 19200 S1 6 = OFF 851 2


7 = ON

Clock/Data Modus Clock 1 (Pull down) S2 1 = ON 851 1


Data 1 (Pull down) 2 = ON
Clock 2 (Pull down) 3 = ON
Data 2 (Pull down) 4 = ON
5 = OFF
6 = OFF
7 = OFF
8 = OFF

factory internal not active S4 1 = ON 854 1


functions 2 = OFF

Flash bank The current version S3 1 = OFF 853 1


must be used 2 = OFF

Protocol 9-bit protocol S1 6 = OFF 851 2


7 = ON

Service function not active S1 8=0 851 3


94 Installation instructions / ACS-2 plus

Index
Access control system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Access rights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
ACS-2 plus-Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13, 24, 29, 36, 43, 47, 51f, 53
Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9ff
Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8,18, 27f, 43, 48f, 61f, 93
Alarm
general . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53, 63
lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55, 55f, 89
relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45, 61f, 64, 89
reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24f

Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8, 26ff, 34ff, 53, 57, 89


Bootstrap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34, 42, 43
Buzzer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

Clock/Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7, 29, 62,81,93ff


Comissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24, 37
Component mounting diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42, 57
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27, 29, 59
Connection
cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43, 46
diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
ethernet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18f, 58
general . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Hyperterminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22, 29
network / ethernet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18f, 58
RS232 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9, 15, 48
RS485 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
shielding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
variants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9, 15, 17, 18ff, 23f, 30f, 42, 47, 43f, 54ff, 64
CPU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12, 27f, 37, 42, 45, 53, 64f, 75ff

Data (see Clock/Data)


DIP switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25ff, 40f, 47, 48f, 67ff, 93
Door strike
DC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 39, 61
fail safe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
fail secure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
general . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13, 22, 39, 53
load current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54, 61
monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
no load current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61f
relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22, 54, 91

Electric safety lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55


End-of-charge voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44, 47f

Factory settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10ff, 24ff, 40, 48, 54, 90, 91


Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7, 35, 57, 93
Flash(bank) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7f, 34f, 64, 93
Fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 14, 37, 39, 53

General connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 49, 67ff, 75


Grounding bridges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10, 11, 13, 16, 64
Group addresses (see address)

Hyperterminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35, 51

Installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Interface
connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22f, 67
converter / multiplier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9, 18f, 22f, 26, 34, 48
current loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15, 18
ethernet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18, 48
general . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13, 15f, 18, 22f, 45, 89
installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
multiplier / converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9, 18f, 22f, 26, 34, 48
RS232 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9, 18f
RS485 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15, 18f, 26, 45
serial . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Interior door handle contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
IQ MultiAccess . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7, 9, 18, 21, 30f, 35
Installation instructions / ACS-2 plus 95

IQ NetEdit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31, 41, 43, 59

Jumpers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13, 61, 53, 61f

Keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77ff, 89

LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30f, 34f, 53, 59f, 53


Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7, 10ff, 46, 54, 53, 55, 64, 55f, 89

Lithium battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30f

Magnetic contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Master-Slave connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Memory
cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37, 42
extension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7f, 28ff, 49, 59, 64
MultiAccess for Windows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7, 9, 18, 20f, 30, 35, 47, 48

NetEdit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31, 41, 43, 54, 56, 48f, 61f


No-load current door strike . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

Output
fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
general . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16, 22, 40, 53, 55, 81
interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
semiconductor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61, 64
signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Parameterization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35, 42, 53


Pin
code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38, 41, 53
general . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Potential seperation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Power supply unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8, 11f, 14, 43ff, 46, 64
Power failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30, 65
Protective measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 10
Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8, 34, 43, 54ff, 93

RAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37, 40, 65, 89


Reader . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12f, 27, 35, 45, 47, 53, 71ff, 89
Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27, 41, 45, 47, 61ff, 61f
RS232 interface (see interface)
RS485 interface (see interface)

Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 9
Semiconductor output (see output)
Service (function / switch) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8, 34f, 64, 93
Shield terminal bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11f, 29, 41
Shielding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 10, 11f, 64
Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7, 9, 30, 38, 42, 43, 57, 59, 64
Switching contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Terminating resistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15ff, 47
Terminal assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66, 61f, 75ff
Threat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Time orders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Turnstile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22, 64

Update . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7, 29

Watchdog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61, 64, 67, 89


Honeywell Security Group
Novar GmbH
Johannes-Mauthe-Straße 14
D-72458 Albstadt P31903-02-0G0-08
2012-09-20
www.honeywell.com/security/de © 2012 Novar GmbH

You might also like