ACS-2 Plus-Installationmanua P31903 02 0G0 08
ACS-2 Plus-Installationmanua P31903 02 0G0 08
ACS-2plus
Item no. 026547, 026548
Table of contents
1. Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1 Installation and subsequent extensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.2 Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.3 Firmwareupdate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2. Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3. General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4. Protective measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
7. Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
8. Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
10. Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
12. Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
13. Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
14. Structure/diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
15. Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
17.1 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
17.2 Technical data 026547, ACS-2plus, 230 V version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
17.3 Technical data 026548, ACS-2plus, 12 V version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Installation instructions / ACS-2 plus 5
Appendix
1. Master sheet for terminal assignment empty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
3. Factory settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
4. Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
6 Installation instructions / ACS-2 plus
1. Safety instructions
* Please read this manual carefully and completely before installing and starting to work with the ACS-2
plus.
* The manufacturer cannot be held liable for damage resulting from use contrary to the designated
purpose.
* Store the documents accompanying the product and the product-specific notes in a safe place.
* Mounting, programming, maintenance and repair work must be carried out only by authorized and
trained persons.
* Soldering and connecting work on the entire system may only be carried out when disconnected from
the power supply.
* Soldering work must only be performed with a temperature-regulated soldering iron, galvanically
separated from the power supply.
* The VDE safety regulations and the prescriptions of the local electricity supplier have to be observed.
* Danger: The ACS-2 plus must not be used in an explosion endangered environment or in rooms
with metal- or plastic-decomposing vapors.
The VDE regulations and the regulations of the electricity supplier must be observed during installation. Carry
out the connections between the control unit and the external devices according to the connection diagrams.
When using a DC door strike, special attention is to be paid to correct polarity. Use only DC door strikes
equipped with a protective diode.
Installation instructions / ACS-2 plus 7
1.2 Symbols
The following symbols are used in this manual:
Indicates danger.
Non observance can create a risk for people or the machine.
2. Overview
3. General information
Access control systems are required if, for safety reasons, access to rooms or buildings is reserved to a certain
group of persons only.
Software
Novar GmbH offers a powerful and practice-oriented access control system. MultiAccess for Windows or IQ
MultiAccess is the parent user software for the connected access control devices. The definition of the access
rights for persons, actions, time orders and the transmission of the data to the hardware are carried out by
means of this software.
Hardware
The ACS-Compact, ACS-1, ACS -2 plus and ACS-2 plus are used as access control controllers and are
responsible for the complete functional sequence. After receiving the data from MultiAccess for Windows or IQ
MultiAccess, the controllers are ready for stand-alone operation. This means that the access control remains
active without any restrictions even if MultiAccess for Windows or IQ MultiAccess is not running.
When starting MultiAccess for Windows or IQ MultiAccess, the bookings carried out in the meantime are
automatically entered in the booking log file.
The display panel is another device. This device is not used for access control but for the indication of the
present location of certain persons, the door states and actions.
The ethernet interface (LAN) links between the PC and the controllers and is also responsible for antipassback
control. The PC configured with IQ MultiAccess must be in operation.
When ACS-2 plus are used in simplified mode the interface converter 026817.03 can be used.
If only one ACS-2 plus is connected, direct connection via the serial interface RS232 is also possible.
4. Protective measures
Protective measures against electrostatic discharge
Modern semiconductor devices are increasingly endangered by electrostatic charges. The higher the integration
density the finer the structures on the chip. This leads to increased stress susceptibility.
With certain semiconductor devices, damage may already be caused at a voltage of less than 20V. This is a very
low value if you consider that, when walking over a carpet, more than 1000V may be generated.
Damage caused by electrostatic discharge only rarely leads to an immediate total failure. The semiconductor
structures are only affected to such a degree that the function is still available. However, a "burning trace" laid
once initiates a chemical process on the chip, which only makes the component unusable after a longer time
(possibly after several months).
- Discharge yourself by touching a suitable object (e.g., heating, water pipe, etc.)
in the immediate vicinity before starting to work on endangered parts.
- Use only soldering irons that are galvanically separated from the power supply and equipped
with an electronic temperature control.
A basic protection or a fine protection has already already been integrated into the corresponding devices by
Novar GmbH according to VdS requirements.
Complete protection against damage caused by lightning strokes and overvoltages is assured by the measures
taken for the external and internal lightning protection. The overvoltage protection is also called medium and
coarse protection. The consideration of additional requirements and measures for the installation of system
components mainly depends on the installation site and the equipment connected to the system.
Overvoltage caused, for example, by switching actions causes a very steep rise of voltage. This means that the
voltage can reach values of several kV within a few µs. Such voltage pulses are also called transients. They are
responsible for the destruction of electronic components.
Overvoltage protection means suitable measures which enable the absorption of such transients.
The energy resulting from a lightning discharge causes the destruction of unprotected devices. Switching
actions in electrical systems also cause overvoltages.
High-frequency compensation processes in power supply networks are continued on high-voltage lines and are
coupled in the low-voltage level. Overvoltages and high-frequency istil
nterference power transients in low-voltage installations may also be caused by voltage drops, phase control,
etc. The rate of raise of current may even reach higher values than a lightning stroke.
Installation instructions / ACS-2 plus 11
The grounding bridges are located on the CPU board near the power supply unit connector (see chapter 15.1)
Connect the shield soldering bar to the ground conductor and keep the grounding bridges closed
The DB1 and DB2 grounding bridges establish a capacitive coupling between the ground conductor and the
system operating voltage.
This way of wiring normally offers the best protection against mains-borne interferences and interferences
caused by cable shield discharges. However, this connection must only be used if PE and N are connected
separately (modern grounding) and if it is guaranteed that the ground conductor does not carry any low- or high-
frequency signals.
Connect the shield soldering bar to the ground conductor and open the grounding bridges
The capacitive coupling to the system operating voltage is now interrupted by the separated grounding bridges.
This connection can be used if the ground conductor is susceptible to interferences and it is feared capacitive
coupling could transmit these to the ACS-2 plus.
Connect the shield soldering bar to a proper system ground and keep the grounding bridges closed
The shield soldering bar must be connected to the newly created
system ground.
In case of a heavily loaded ground conductor, this is the
only possibility to guarantee a proper
deviation of the interferences
on the line shields.
- The shielding of the incoming line is to be connected to the shield soldering bar of the ACS-2 plus. The
shielding of the outgoing line is not connected.
- The shield terminal bar in each ACS-2 plus must be connected to a separate PE.
(min. cable cross-section 1,5mm²)
If, when using 12V devices, it is technically not possible to connect ground potential to each ACS-2
plus, it is recommended to use a three wire cable for the power supply. The third core carries the
ground potential of the common power supply unit. This wire is connected to the shield terminal bar in
each ACS-2 plus. This method is only a temporary solution and should only be used in exceptional
cases.
- The shielding of the reader line is connected on one side to the shield terminal bar in the ACS-2 plus.
- The above mentioned points also principally apply to the ACS-2 plus module bus .
Please observe the informations about grounding and shielding in chapter 5.2.
mains frequency 40 – 60 Hz
current consumption depends on the reader type, the number of readers and the interface type
The door strike must be taken into consideration if its supply comes from the ACS-2 plus. The current
consumption of a door strike depends on the type, but lies somewhere between 200mA and 500mA.
The current consumption of an energized door strike must be known for each ACS-2 plus
when designing a 12V system.
The following drawing (powered on) shows the voltage drop of a 1.5mm2 cable compared to a 4mm2 cable. A
power consumption of 1A is calculated for each ACS-2 plus.
Observe the outgoing and return line.
14 Installation instructions / ACS-2 plus
The voltage diagrams 1 and 2 compare the effects of two cable cross-sections.
The required line cross-section must be calculated using the graphs shown above.
The local requirements must be observed for the line cross-section. VDE 0100 applies to
Germany. The output fuse of the power supply unit must have the appropriate current rating.
The highest current rating is determined by the smallest line cross-section of the supply cable.
Installation instructions / ACS-2 plus 15
6.1.1 Principle:
The RS485 interface used is a bidirectional interface with bus capability. Up to 32 users can be connected which
can be transmitters as well as receivers. The line ends are provided with a terminating resistor.
The terminating resistors can be set on the interface by means of jumpers.
16 Installation instructions / ACS-2 plus
Potential separation
Each RS485 line must be provided with one non-floating interface. The other interfaces must be floating. The
best position of the non-floating interface is in the middle of the RS485 line. The ACS-2 plus, fitted with the
interface which is not floating, must have a good grounding. If this is not the case, you should select another
ACS-2 plus. Here a good grounding is more important than the center of the RS485 line.
Terminating resistors
The terminating resistors must be placed at the first and the last device of a line. Here it depends on the type
of wiring.
Connection to the network via standard Ethernet cable (Cat 5 or higher) connected to a HUB, router or switch
via network terminal box (RJ45).
18 Installation instructions / ACS-2 plus
Network:
MultiAccess for Windows or IQ MultiAccess makes it possible to use existing networks.
MultiAccess for Windows can be accessed from up to 64 workstations. With IQ MultiAccess
there are no limitations. Any combinations with other controllers are possible.
Installation instructions / ACS-2 plus 19
COM1/COM2 1 DCD
9-pole 2 RxD
3 TxD
4 DTR
5 GND
6 DSR
7 RTS
8 CTS
9 RI
COM1/COM2 2 TxD
25-pole 3 RxD
4 RTS
5 CTS
6 DSR
7 GND
8 DCD
20 DTR
22 RI
Interface converter 1 D1
2 D
3 D*
4 D1*
5 GND
7. Configuration
The ACS-2 plus controls the access to a room. The use of an additional interior reader makes it possible to
control also the exit of a room. The readers must function according to the same reading principle (magnetic card
reader, contactless reader or chip card reader).
The ACS-2 plus recognizes by means of the door monitoring contact whether the door was opened, was open
too long or the door was opened by force.
8. Mounting
8.1 Installation site
The installation site of the central unit must meet the following conditions:
6. The commissioning of the device is described in chapter 10. The individual steps to be carried out while
the cover housing is open must be checked.
Then mount the housing cover, close it with the housing screws and seal it.
To assure safe and easy working, we recommend removing the battery holder during the
installation of the peripheral devices.
Danger!
A batteriy change must only be carried out by qualified personell introduced to the VDE
regulations.
Lithium battery (type CR 2477N, 3 V 950 mAh) for data preservation in ACS-2plus = item no. 018050.
Procedure
Example in IQ MultiAccess:
In IQ NetEdit:
a) Logical view
b) Select controller
c) Reset alarms/notifications
d) Select alarm to reset.
Batteries and recharchable batteries - even free from heavy metal - must not be disposed of in domestic
waste. According to EU guidline 2006/66/EG users are obligated to return batteries for recycling. In Germany
they will be accepted for free at each selling point; alternatively they can be dispensed in public storage
vessels for old batteries or at public waste disposal authorities.
Pb for lead
Cd for cadmium
Hg for mercury
0 0 0 0 0 Address 1 =
factory setting
1 0 0 0 0 Address 2
0 1 0 0 0 Address 3
1 1 0 0 0 Address 4
0 0 1 0 0 Address 5
1 0 1 0 0 Address 6
0 1 1 0 0 Address 7
1 1 1 0 0 Address 8
0 0 0 1 0 Address 9
1 0 0 1 0 Address 10
0 1 0 1 0 Address 11
1 1 0 1 0 Address 12
0 0 1 1 0 Address 13
1 0 1 1 0 Address 14
0 1 1 1 0 Address 15
1 1 1 1 0 Address 16
0 0 0 0 1 Address 17
1 0 0 0 1 Address 18
0 1 0 0 1 Address 19
1 1 0 0 1 Address 20
0 0 1 0 1 Address 21
1 0 1 0 1 Address 22
0 1 1 0 1 Address 23
1 1 1 0 1 Address 24
0 0 0 1 1 Address 25
1 0 0 1 1 Address 26
0 1 0 1 1 Address 27
1 1 0 1 1 Address 28
0 0 1 1 1 Address 29
1 0 1 1 1 Address 30
0 1 1 1 1 Address 31
1 1 1 1 1 Address 32
0 = OFF
1 = ON
Installation instructions / ACS-2 plus 29
0 = OFF
1 = ON
If the switch 8 ON state is detected, LED 1 on the CPU board flashes green until the next reset is carried out.
The flashing green LED indicates that a function is in process. When this LED lights permanently, the function
has been completed
Procedure of bootstrapping:
1. Set all DIP switches to ON
2. Reset (reset push-button)
3. LED 1 flashes (wait)
4. LED 1 lights permanently
5. Switch DIP S1 to the required
position (baud-rate, address,
protocol, etc.)
6. Reset (reset push-button)
30 Installation instructions / ACS-2 plus
Table 5: Special function for ACS-2 plus Setup (see Chapter 10).
1 2 3 4 5 6 7 8 Function
0 0 0 0 0 0 0 0 Setup via hyperterminal
An unintentional activation of the switch 8 can be ignored by resetting it to OFF (while the LED
1 flashes). After the reset, the device does not switch to the service mode and the switches keep
their original meaning.
Generally, a reset must be carried out, the setup must be controlled or set again and the
controller must be parameterized after activation / deactivation of the service mode (see
operating manual for for MultiAccess for Windows or IQ MultiAccess).
1 2 3 4 5 6 7 8 Designation
0 = OFF 1 = ON x = any
1 2 Designation
This switch block serves for selecting the firmware version. The factory setting ensures that the current version
is always automatically loaded. (This function becomes only valid after a firmware update and is described in this
context. It is irrelevant in the present version 1).
1 2 Designation
1 0 Factory setting
Installation instructions / ACS-2 plus 31
Bear in mind that only one slot is available for the following memory cards. The memory extension required can
be determined by the following calculation:
Use the table in the appendix to simplify the determination of the required memory and memory extension.
ID no.: Enter the number of digits of the identification code to be used in the column no. of digits
required (e.g., 20 in case of 20-digit coding according to Novar or DIN).
Divide this number by 2 (the required number of bytes results) and enter the result in the
column value.
If the result of the division is no integer (e.g., 7.5), the result must be rounded upwards
to the next integer (in this case, to 8) and entered in the column rounded to the next
integer.
PIN-code: Enter the number of digits of the PIN code to be used in the column no. of digits required
(the PIN code may comprise min. 4 and max. 8 digits).
Divide this number by 2 (the required number of bytes results) and enter the result in the
column value.
If the result of the division is no integer (e.g., 2.5), the result must be rounded upwards
to the next integer (in this case, to 3) and entered in the column rounded to the next
integer.
Version no.: Enter the number of digits of the version number to be used in the column no. of digits
required. In the case of contactless cards, a unique number comprising 20 digits is used.
In this case, no version number is required (input = 0). In all other cases, the version
number may comprise 2 digits. It is recommended to enter 2.
Divide this number by 2 (the required number of bytes results) and enter the result in the
column value.
If the result of the division is no integer (e.g., 0.5), the result must be rounded upwards
to the next integer (in this case, to 1) and entered in the column rounded to the next
integer.
R/T-zones: Enter the number of room/timezones required. Divide this amount by 8 and round to the
next integer. The ACS-2 plus will store only the room/time zones which are allocated to
doors controlled by this controller.
1
Please observe the minimum and maximum values shown in the column no. of digits possible.
Installation instructions / ACS-2 plus 33
Indexing: If indexing is employed, each werden je Ausweis 6 BYTES belegt. Without indexing, the
value of this field is 0.
Macros An ACS-2 plus can manage up to 64 macros. Enter in the column no. of digits required
the number of the macros to be implemented.
Divide this number by 8 (the required number of bytes results) and enter the result in the
column value.
If the result of the division is no integer (e.g., 1.5), the result must be rounded upwards
to the next integer (in this case, to 2) and entered in the column rounded to the next
integer.
Add the values entered in the column rounded to the next integer and enter the result in the field there below
(memory requirements per ID-card).
Enter the required number of cards in the field on the right-hand side (max. 65000).
Multiply the values entered in the fields memory requirements per ID-card and no. of ID-cards and enter the value
in the field memory requirements.
Enter the value of the field memory requirements also in the field subtotal 1.
If working neither with BRE nor with APB, this entire block can be skipped.
BRE This line can be skipped if not using the "barring repeated entry" function. If the BRE
function is activated, the number to be entered results from the number of door sides for
which the barring is required.16
Multiply this number by 4 (the required number of bytes results) and enter the result in
the column Total..
APB This line can be skipped if not using the "Antipassback control" function. Enter 1 in the
“Total” field for active APB.
Unique fixed value: For active BRE or for active APB or active BRE and APB, the specified fixed
value of 4 is to be added to the value(s) of the total fields.
(Even when BRE and APB are active together, only 4 is to be added,
not 8!).
The memory requirement per ID card is calculated by adding the values in the Totals
column. Multiply this value with the number of the needed ID-cards and enter the result
in the Memory requirements field.
2
For details about BRE / APB (= Barring Repeated Entry / Antipassback) look into the advanced functions
of MultiAccess for Windows (P32201-46-0G0-xx) or IQ MultiAccess (P032205-46-0G0-xx).
34 Installation instructions / ACS-2 plus
Booking: Each booking occupies 9 bytes. Multiply this value by the number of bookings to be stored and
enter the result in the column total.
A unique fixed value of 45 bytes is required for the bookings. Add this value to the value of the
field total and enter the result in the field memory requirements.
Enter the value of the field memory requirements, also in the subtotal 3 field.
Add the values of the fields Subtotal 1, Subtotal 2 and Subtotal 3 and enter the result in the field Required total
memory.
Enter the (rounded) value of the field total memory requirements in the 4 empty and gray highlighted fields and
subtract this value from the free memory space shown above. If the result of one of these subtractions is at least
0 or a positive value, the memory extension of the corresponding column is required.
Installation instructions / ACS-2 plus 35
Example: The memory requirements for an ACS-2 plus controller is to be calculated based on the following
conditions:
Calculation:
If the calculated required memory space exceeds the max. free memory space, alternative calculations
using various lower values can be carried out. It is, for example, possible to reduce the number of bookings
to be stored. Is it possible to switch less relays? Do you really require all room/time zones?
Approximate value
The standard equipment of 1 MB (0.5 MB free) is sufficient, according to the above mentioned calculation
method, for approx. 1,500 cards and approx. 20,000 bookings.
The required memory space for both of zones and ID cards will be displayed when the maximum values
are entered in IQ NetEdit (refer to the IQ MultiAccess Installation Instructions, P32205-26-0G0-xx,
additional settings tab).
3
The new trademark corresponds with the previous effeff coding.
36 Installation instructions / ACS-2 plus
Never insert or remove the memory card while the ACS 2plus is powered up!
If the memory card is removed, all of the ACS-2plus data is irrevocably lost.
Procedure:
If you use a 12V DC power supply, please observe that the output voltage must be free of
ground potential.
9.2 Battery
The ACS-2 plus is equipped with an battery holder for: 1 x 018002 Battery 12V 2.0Ah
If the power supply is not part of the central unit, it must be mounted closely (with no
clearance) to ensure that an attack on the connection cable is not possible without
mechanically having to damage the housing.
We recommend screwing the central unit and the power supply directly together. No
consumers from other systems may be connected to the voltage of the power supply.
Only use approved batteries for the power supply. Only use batteries of the same age and
originating from the same production series.
By means of a flexible “Dual Lock” fastening tape, the ACS-2 plus can be attached to an battery 12V / 2.0A,
item no. 018002.
Cover with “Dual Lock” fastening tape Cover with installed battery
Stick one “Dual Lock” tape (item no. 055280) to the inside of the ACS-2 plus (see illustration) and one “Dual
Lock” tape to the battery.
The end-of-charging voltage of the battery charging unit is correctly set in the factory for Sonnenschein
batterys of the A500 series.
If it is necessary to change the setting, proceed as described in the chapter "Adjusting the end-of-charging
voltage".
1. The power supply must have reached the operating temperature. This requires the power supply to
be switched on for at least two hours with rated load and closed housing.
3. Adjust the voltage at the battery terminals or at MP1 and MP2 by means of the PO1 potentiometer
under consideration of the ambient temperature according to the table below.
Make sure of the battery type!
2. If the battery voltage deviates by >200mV from the nominal value, then adjust PO4 accordingly.
Larger actuators (e.g., door strikes) or devices with higher current consumption cannot be
supplied.
Installation instructions / ACS-2 plus 39
The power supply must be connected to the mains via a separate fuse. If the electrical
installation is equipped with a residual current operated circuit-breaker (FI circuit-breaker), the
power supply must be provided with an own residual current operated circuit-breaker. The
fuse and the FI circuit-breaker should be located within the safety area, if possible.
If the power supply is not part of the central unit, it must be mounted nearby (with no
clearance) to ensure that an attack on the connection cable without mechanical damage to
the housings is not possible.
We recommend screwing the central unit and the power supply together. No consumers from
other systems may be connected to the voltage of the power supply.
Only use approved batterys for the power supply. Only use batterys of the same age
and originating from the same production series.
Installation
Disconnect the unit from the power supply when carrying out installation work.
When installing the power supply/charging unit in a central housing, make sure that the insulating foil included
in the delivery is placed between the bottom of the housing and the lower side of the board. Make sure
that the device is firmly screwed to the bottom of the housing.
The ground conductor connected to the supply circuit must be connected close to the connecting terminals of
the supply voltage.
When fastening the power line (NYM 3 x 1,5 mm²), make sure that the min. air gaps (4mm) and creep
distances
(5mm) between the electronic components or the peripheral devices and the power line are maintained.
If the neutral conductor cannot be clearly identified, a second fuse protection must be provided in the supply
circuit enabling a 2-pole separation from the supply circuit.
After installation, protect the connecting terminals against unintentional contact by means of the covers
included in the delivery.
40 Installation instructions / ACS-2 plus
Functional description
It is used to charge the batterys. The charging current is limited to 120 mA.
The battery charging current is monitored and tracked depending on the temperature by means of an
NTC resistor.
The end-of-charging voltage of the battery charging unit is correctly set in the factory for
Sonnenschein batterys of the A500 series.
If it is necessary to change the setting, proceed as described in the chapter "Adjusting the end-of-
charging
voltage".
The suppy voltage for the central unit and the external consumers need not be adjusted.
If, during battery operation, the battery voltage falls below 9.5V, the power supply to the central unit and the
external consumers is switched off (cutoff relay).
Thus, unpredictable reactions in case of undervoltage are avoided and the battery is protected against total
discharge.
Faults:
3. Adjust the voltage at the battery terminals by means of the RV2 potentiometer under consideration
of the ambient temperature according to the table below.
Make sure of the battery type!
2. If the battery voltage deviates by >200mV from the nominal value, then adjust PO4 accordingly.
42 Installation instructions / ACS-2 plus
10. Commissioning
During commissioning of the ACS-2 plus, the following steps must be carried out:
Please refer to the table in the appendix containing the factory settings which are valid after bootstrap
and setting the controller as long as the factory settings have been applied or have not been changed.
Variant 1: Basic setting via the DIP switch S1 (see chapter 8.5.1)
There are only limited possibilities in making settings via the DIP switches (as described in
the tables in chapter 8.5).
The variant 2 of the ACS-2 plus setup offers considerably more comfortable and extensive
possibilities.
General description: The ACS-2 plus setup makes it possible to check and to modify, if
necessary, the current settings of the ACS-2 plus. This is also
possible during normal operation without impeding operations.
The number of parameters to be modified depends on the DIP
switch setting of the S1 switch block.
44 Installation instructions / ACS-2 plus
Cable assignment:
1 2 3 4 5 6 7 8 Function
******************************************************************************
** SETUP - ACS-2 plus **
******************************************************************************
Setup from: APPL. Login.
Label: [<no-name...>]
1. Communication
2. System
3. Save
4. Exit
No.:_
Meanings:
Setup from: Shows the mode via which the setup was called.
BOOT-Login
The setup was called during the booting process of the ACS-2 plus.
If cea [Enter] is not entered within this time during the booting
process, the APPL.-Login is called.
Certain DIP switch settings have priority and do not permit any
modifications in the Communication - To Host area (see section
Dependencies in this chapter). This error is signaled by the
message "Defined by DIP switch".
General: The last line is the dialogue line. Here, different entries are allowed depending on the
cursor position. Use either small or capital letters. When entering a character which
is not allowed at this point or when pressing the Enter key only, no modification is
carried out. In this case, the program skips back to the next higher level (max. the
main menu).
False entries can be erased by character with the backspace key.
To delete the character buffer press the backspace key at least 3 times.
1. Communication:
Currently, there is only selection 1. To Host. Here, the parameters used by the ACS-2
plus for the communication with the host can be checked and set. The currently set
protocol is marked with "=>". The other current values are shown in the Status line.
48 Installation instructions / ACS-2 plus
Example:
The current value is marked with "=>". To modify the values enter "y" and confirm
with Enter. Then you can select one of the consecutive numbers.
Address: The current address and the permitted address range are displayed.
The value can be changed by entering “y” + Enter (at the question
Change? Y/N) and the desired address (the factory setting is 32).
Group address: The current group address and the permitted address range are
displayed. The value can be changed by entering “y” + Enter (at the
question Change? Y/N) and the desired address (the factory setting
is 30).
With the event protocol, the following fields must be checked or modified, if
Installation instructions / ACS-2 plus 49
necessary:
Example:
Network device: In this field the network card used must be entered.
1. Software version
2. Init / Delete component
No.: _
Software version: This display is used for information only and cannot be
modified. It shows the firmware version of the device.
Init / Erase component: This menu item makes it possible to delete or reinitialize the
content of the exception handler. The exception handler is
a reserved internal memory area in which operations which
are relevant for the operating system are logged like in a log
file. The evaluation of these data, e.g., in case of incorrect
operation of the controller, is reserved for Novar GmbH
employees.
If this log file is to be created at a certain time, the previous
content can be deleted via this function.
3. Save: If the modifications made are to be saved, this menu item must be selected
before quitting the setup via the menu item 4. Exit.
The setup and its consequences remain active until quitting the setup via
Exit!
Installation instructions / ACS-2 plus 51
Event protocol
Baud rate 19200
MVA (virtual address of the current controller from NetEdit).
DVA (virtual target address of the computer communicated with that of the controller = MVA
of the corresponding computer from NetEdit).
Dependencies:
1. If at least one of the DIP switches 6 and 7 of the S1 switch block (see 8.5.1) is set to ON, the
DIP switch settings have priority. This means that areas which cannot be modified via the
setup contain a corresponding note and the individual parameters cannot be selected.
2. When using the interface of the ACS-2 plus controller for RDT, the interface is already used
by the RDT protocol.
(See also chapter 8.6 = DIP switches and the corresponding documents of the used interface cards).
Transferring the hardware configuration to the access control software is done by a special configuration
program which is part of the access control software. Detailed examples how to configer an ACS-2 plus
controller can be found in the manual of the configuration software.
52 Installation instructions / ACS-2 plus
For differentiation of the controller types ACS-2plus and ACS-2 plus, the ACS-2 plus from firmware 7.00 on
activates all LEDs and the buzzer while booting.
The buzzer stop push-button makes it possible to reset the buzzer manually. To do so, press the push-button
at least for 3 seconds with a suitable object.
Installation instructions / ACS-2 plus 53
The buzzer can be reset by pressing for approx. 3 seconds the buzzer stop push-button located on the front
plate.
Additionally, the key and LED functions of the macro control of IQ MultiAccess are valid (see separate manual
"Supplementary functions of IQ MultiAccess", P32205-46-0G0-xx).
54 Installation instructions / ACS-2 plus
12. Outputs
12.1 Semiconductor outputs
The ACS-2 plus board is provided with 3 semiconductor outputs:
The watchdog output (ST 5-2) signals (12V) that at least one watchdog reset occurred
since the last hardware reset.
The connected strikes with load current function can be checked for tampering (see also
chapter 15.4.1).
An alarm is released when a watchdog reset occurs while the jumper ST8 is connected.
If the ACS-2 plus fails once, the relays 1 and 2 are so defined that the doors remain closed. It is not possible
to change the definition of these relays. The status of relay 3 (alarm) und relay 4 (tamper) can be defined using
jumper ST16.
ST 16 Description
13. Inputs
13.1 Digital inputs
The four digital inputs are freely programmable via NetEdit.
14. Structure/diagrams
14.1 CPU component mounting diagram
S1, S2, S3, S4: See also chapter 8.5 = DIP switches.
Installation instructions / ACS-2 plus 57
Number Explanation
ST6 Door strike monitoring jumper 1-3; 2-4 = no door strike monitoring
Jumper 3-5, or 4-6 = with door strike monitoring (only
admissible with connected door strike item no. 019 042 /
019 042.01. Deactivate if other devices, such as a flash
lamp, are connected to these outputs/relays).
ST10 Alarm lines 7 and 8 / inputs 11 and 12 PIN 1 = Alarm line 7/ input 11
(terminate with 12.1 kOhm) PIN 2 = 0V
PIN 3 = alarm line 8/ input 12
ST14 Power supply connector for the controller voltage 45 and 46 (with 026547 12V DC, not
stabilized)
ST16 Basic definition of tamper / alarm relay (above board layout version no. 467.00-75-01/02)
Jumper 1-3 = Relay 3 (alarm) activated during system failure
Jumper 2-4 = Relay 4 (tamper) activated during system failure
Jumper 3-5 = Relay 3 (alarm) deactivated during system failure
Jumper 4-6 = Relay 4 (tamper) deactivated during system failure
LD3 If this LED lights up, then the ACS-2 plus runs with flash 1
LD4 If this LED lights up, then the ACS-2 plus runs with flash 2
15. Connections
8
The standard factory settings of the inputs and outputs are described in this overview. However, individual
assignments are also possible if required. In this case, we recommend noting the changed assignment for
each ACS-2 plus controller. Copy and fill in the empty terminal assignment overview in the appendix and
store it together with the corresponding controller!
60 Installation instructions / ACS-2 plus
9
Inputs 11 and 12 as well as watchdog and danger signal output see chapters 13.2 and 14.1
Installation instructions / ACS-2 plus 61
Tamper monitoring for the strike with load current function is possible. For this, a DC door strike must be
connected as shown above.
This function is not possible with a no-load current door strike and a door strike supplied with alternating
voltage or supplied by an external voltage source - not by the voltage source which supplies the ACS-2 plus.
The tamper monitoring for "door strike 1" and "door strike 2" must be deactivated (otherwise a board failure
of the ACS-2 plus is caused).
Fail safe door strike = no-load current door strike: The door is blocked if the coil is energized
Tamper monitoring for the fauil safe door strike is not possible.
The differential alarm lines (inputs 5 - 10) must be terminated with 12K1.
Door monitoring
The interior door handle contact activates a door release on the ACS-2 plus. The door can
be passed without the error message "Unauthorized door release".
An external contact, e.g., a magnetic contact, must be used for door monitoring. The bolt
switching contact is only evaluated for positive drive condition when the intrusion detection
system is "disarmed". Its status is only shown when the intrusion detection system is
"disarmed". The bolt switching contact alarm group does not release and store an alarm when
the intrusion detection system is "armed".
64 Installation instructions / ACS-2 plus
15.6 Turnstile
The ACS-2 plus can manage, besides a standard door, 3 types of turnstiles. They differ from each other by
the number or the evaluation of the monitoring contacts.
With the door closed, the monitoring contact is likewise closed. The respective alarm line recognizes the
necessary 12.1 KΩ, and thus a closed door. If the door is opened (A), the monitoring contact also opens and
signals that the door is open. The monitoring contact does not close until the door is closed again (B) and the
door is recognized as closed.
In normal condition (with door closed) one of the contact makers A to D closes the monitoring contact (contact
maker A is used in the example).
Case 1) Exterior reader enabled. “Door open” is signaled when the turnstile is activated in the left
rotational direction. Contact maker B closes the monitoring contact again. The door is
recognized as closed.
Case 2) Interior reader enabled. In the right rotational direction, the monitoring contact is closed again
by contact maker D.
The rotational direction cannot be evaluated with this type. APB10 is recognized on the reader
used for the booking. If both sides are enabled, both persons are logged.
10
For details about BRE / APB (= Barring Repeated Entry / Antipassback), see the "Advanced functions of
MAfW"
(P32201-46-0G0-xx) and "Advanced functions of IQ MultiAccess" (P32205-46-0G0-xx).
Installation instructions / ACS-2 plus 65
Left rotational direction: = Exterior reader enabled. The contact maker A activates the inner monitoring
contact; afterwards, contact maker B activates the outer monitoring contact. In
between, the door is recognized as closed.
Right rotational direction: = Interior reader enabled. The contact maker A activates the outer
monitoring contact; afterwards, contact maker D activates the inner
monitoring contact. In between, the door is recognized as closed.
66 Installation instructions / ACS-2 plus
Left rotational direction: = Exterior reader activated. The respective monitoring contact is activated (in our
illustration, it was the inner contact).
Right rotational direction: = Interior reader activated. The respective monitoring contact is activated (in
our illustration, it was the outer contact).
Installation instructions / ACS-2 plus 67
The terminals 10 and 11 of the reader must only be connected with motorized readers.
If only one reader is used, this reader is always connected as reader 1.
ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus
(see chapter 8.5):
1 ON Clock 1
1
2 ON Data 1 Pull
3 ON Clock 2 down
2
4 ON Data 2
S2 5 OFF Clock 1
1
6 OFF Data 1 Pull
7 OFF Clock 2 up
2
8 OFF Data 2
68 Installation instructions / ACS-2 plus
The terminals 14 and 15 of the reader must only be connected with motorized readers.
If only one reader is used, this reader is always connected as reader 1.
ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus
(see chapter 8.5):
1 ON Clock 1
1
2 ON Data 1 Pull
3 ON Clock 2 down
2
4 ON Data 2
S2 5 OFF Clock 1
1
6 OFF Data 1 Pull
7 OFF Clock 2 up
2
8 OFF Data 2
Installation instructions / ACS-2 plus 69
ACS-2 plus terminal assignment, DIP switch positions on the CPU board of the ACS-2 plus
(see chapter 8.5):
1 ON Clock 1
1
2 ON Data 1 Pull
3 ON Clock 2 down
2
4 ON Data 2
S2 5 OFF Clock 1
1
6 OFF Data 1 Pull
7 OFF Clock 2 up
2
8 OFF Data 2
70 Installation instructions / ACS-2 plus
ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus
(see chapter 8.5):
1 ON Clock 1
1
2 ON Data 1 Pull
3 ON Clock 2 down
2
4 ON Data 2
S2 5 OFF Clock 1
1
6 OFF Data 1 Pull
7 OFF Clock 2 up
2
8 OFF Data 2
Installation instructions / ACS-2 plus 71
2747010 Magnetic card reader module for Siedle “Vario” System, item no.
027545 - 027548
ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus
(see chapter 8.5):
1 ON Clock 1
1
2 ON Data 1 Pull
3 ON Clock 2 down
2
4 ON Data 2
S2 5 OFF Clock 1
1
6 OFF Data 1 Pull
7 OFF Clock 2 up
2
8 OFF Data 2
72 Installation instructions / ACS-2 plus
ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus
(see chapter 8.5):
1 ON Clock 1
1
2 ON Data 1 Pull
3 ON Clock 2 down
2
4 ON Data 2
S2 5 OFF Clock 1
1
6 OFF Data 1 Pull
7 OFF Clock 2 up
2
8 OFF Data 2
Installation instructions / ACS-2 plus 73
ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus
(see chapter 8.5):
1 ON Clock 1
1
2 ON Data 1 Pull
3 ON Clock 2 down
2
4 ON Data 2
S2 5 OFF Clock 1
1
6 OFF Data 1 Pull
7 OFF Clock 2 up
2
8 OFF Data 2
74 Installation instructions / ACS-2 plus
ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus
(see chapter 8.5):
1 ON Clock 1
1
2 ON Data 1 Pull
3 ON Clock 2 down
2
4 ON Data 2
S2 5 OFF Clock 1
1
6 OFF Data 1 Pull
7 OFF Clock 2 up
2
8 OFF Data 2
Installation instructions / ACS-2 plus 75
ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus
(see chapter 8.5):
1 ON Clock 1
1
2 ON Data 1 Pull
3 ON Clock 2 down
2
4 ON Data 2
S2 5 OFF Clock 1
1
6 OFF Data 1 Pull
7 OFF Clock 2 up
2
8 OFF Data 2
76 Installation instructions / ACS-2 plus
Terminal assignment ACS-2 plus: Settings of the DIP switches located on the CPU board of
the ACS-2 plus (see chapter 8.5):
1 ON Clock 1
1
2 ON Data 1 Pull
3 ON Clock 2 down
2
4 ON Data 2
S2 5 OFF Clock 1
1
6 OFF Data 1 Pull
7 OFF Clock 2 up
2
8 OFF Data 2
Installation instructions / ACS-2 plus 77
Terminal assignment ACS-2 plus: Settings of the DIP switches located on the CPU board of
the ACS-2 plus (see chapter 8.5):
1 ON Clock 1
1
2 ON Data 1 Pull
3 ON Clock 2 down
2
4 ON Data 2
S2 5 OFF Clock 1
1
6 OFF Data 1 Pull
7 OFF Clock 2 up
2
8 OFF Data 2
78 Installation instructions / ACS-2 plus
ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus
(see chapter 8.5):
1 OFF Clock 1
1
2 OFF Data 1
Pull
down
3 OFF Clock 2
2
4 OFF Data 2
S2
5 ON Clock 1
1
6 ON Data 1
Pull up
7 ON Clock 2
2
8 ON Data 2
Installation instructions / ACS-2 plus 79
ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus
(see chapter 8.5):
1 ON Clock 1
1
2 ON Data 1 Pull
3 ON Clock 2 down
2
4 ON Data 2
S2 5 OFF Clock 1
1
6 OFF Data 1
Pull
7 OFF Clock 2 up
2
OFF Data 2
8
80 Installation instructions / ACS-2 plus
ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus
(see chapter 8.5):
1 OFF Clock 1
1
2 OFF Data 1 Pull
3 OFF Clock 2 down
2
4 OFF Data 2
S2 5 ON Clock 1
1
6 ON Data 1 Pull
7 ON Clock 2 up
2
8 ON Data 2
Installation instructions / ACS-2 plus 81
Terminal assignment ACS-2 plus: Settings of the DIP switches located on the CPU board of
the ACS-2 plus (see chapter 9.6):
1 ON Clock 1
1
2 ON Data 1 Pull
3 ON Clock 2 down
2
4 ON Data 2
S2 5 OFF Clock 1
1
6 OFF Data 1 Pull
7 OFF Clock 2 up
2
8 OFF Data 2
82 Installation instructions / ACS-2 plus
Terminal assignment ACS-2 plus : Settings of the DIP switches located on the CPU board of
the ACS-2 plus (see chapter 9.6):
1 OFF Clock 1
1
2 OFF Data 1
Pull
down
3 OFF Clock 2
2
4 OFF Data 2
S2
5 ON Clock 1
1
6 ON Data 1
Pull up
7 ON Clock 2
2
8 ON Data 2
Installation instructions / ACS-2 plus 83
ACS-2 plus terminal assignment: DIP switch positions on the CPU board of the ACS-2 plus
(see chapter 8.5):
1 ON Clock 1
1
2 ON Data 1 Pull
3 ON Clock 2 down
2
4 ON Data 2
S2 5 OFF Clock 1
1
6 OFF Data 1 Pull
7 OFF Clock 2 up
2
8 OFF Data 2
84 Installation instructions / ACS-2 plus
Appendix
3. Factory settings
4. Index
Installation instructions / ACS-2 plus 91
Company:...................................................................................................................................
Device No...................................................Site:.........................................................................
92 Installation instructions / ACS-2 plus
Installation instructions / ACS-2 plus 93
Factory settings
List in alphabetic order:
Index
Access control system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Access rights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
ACS-2 plus-Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13, 24, 29, 36, 43, 47, 51f, 53
Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9ff
Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8,18, 27f, 43, 48f, 61f, 93
Alarm
general . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53, 63
lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55, 55f, 89
relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45, 61f, 64, 89
reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24f
Hyperterminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35, 51
Installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Interface
connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22f, 67
converter / multiplier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9, 18f, 22f, 26, 34, 48
current loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15, 18
ethernet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18, 48
general . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13, 15f, 18, 22f, 45, 89
installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
multiplier / converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9, 18f, 22f, 26, 34, 48
RS232 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9, 18f
RS485 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15, 18f, 26, 45
serial . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Interior door handle contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
IQ MultiAccess . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7, 9, 18, 21, 30f, 35
Installation instructions / ACS-2 plus 95
Keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77ff, 89
Magnetic contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Master-Slave connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Memory
cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37, 42
extension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7f, 28ff, 49, 59, 64
MultiAccess for Windows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7, 9, 18, 20f, 30, 35, 47, 48
Output
fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
general . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16, 22, 40, 53, 55, 81
interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
semiconductor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61, 64
signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 9
Semiconductor output (see output)
Service (function / switch) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8, 34f, 64, 93
Shield terminal bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11f, 29, 41
Shielding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 10, 11f, 64
Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7, 9, 30, 38, 42, 43, 57, 59, 64
Switching contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Terminating resistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15ff, 47
Terminal assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66, 61f, 75ff
Threat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Time orders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Turnstile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22, 64
Update . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7, 29