ATS12b Wiring

This document provides a wiring diagram and notes for the DC inputs of an Omega v1.2a board. It shows the wiring connections for inputs that control the autostart of two generators including contacts for running status, faults, and remote start/stop controls. Notes provide explanations for the different input functions and their uses based on the installation type.

Uploaded by

Amro Lynch
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
36 views5 pages

ATS12b Wiring

This document provides a wiring diagram and notes for the DC inputs of an Omega v1.2a board. It shows the wiring connections for inputs that control the autostart of two generators including contacts for running status, faults, and remote start/stop controls. Notes provide explanations for the different input functions and their uses based on the installation type.

Uploaded by

Amro Lynch
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

1 2 3 4 5 6

DC Inputs

ST.G2
*

*
A A
10 Note 2 11 12 Note 2 13
ST.G1 ST.G2 ST.G2 Note 1: External contact supplied from the autostart of the genset:
ST.G1
C PI01 PI03
NO C PI01
CO
PI03
NO OMEGA v1.2a Board Contact closed: Genset is running & ready to supply the load (no need for
warm-up delay).
Contact open: Genset has a fault or cannot supply the load.

Note 2: Should be connected to the remote control terminals of the autostart of the
genset.
Contact closed: Genset should start (no need for response delay).
Contact open: Genset should shutdown (no need for cooling delay).

Note 3: This pin can be used when the remote control (R.C.) is set to "Gensets Rdy"
B or "U Present". B

Note 4: This input can be used as Remote Control when the installation type is set to
GG installation and the R.C. is set to "v1.0 Compt."

(-) 5 to 35 V
-VBAT +VBAT G1 OK G2 OK CG1-F/B CG2-F/B Remote Control CG-F/B CM-F/B
C C
~
1 2 3 PI01 4 PI01 5 PI01 6 PI01 7 PI01 8 PI01 9 PI01
Note 1
*Note 1 CG1
*CG2 Note 3 CG
^ CM
PI03 PI03 PI03 PI03 PI03 PI03 PI03 Note 4
P

GND
S.&A.S. Ltd.
ATS12a Wiring Jieh Chouf
Lebanon
[email protected]
*Not connected in MG installation
ATS12b WIRING DIAG:
DC Input/Output
Not connected in GG installation
^
D D
~Connected only in MGG installation
Size FCSM No. DWG No. Rev
B
-NL0
NLATS12a0Sch
ATS12a.Sch 1NL1

Scale Sheet
1NL1ofof 55
-

1 2 3 4 5 6
1 2 3 4 5 6

DC Inputs with MCB/MCO

ST.G2
A
10 Note 2 11 *
12 Note 2 *
13
A

ST.G2 Note 1: External contact supplied from the autostart of the genset:
ST.G1 ST.G1 ST.G2 Contact closed: Genset is running & ready to supply the load (no need for
C PI01 PI03
NO C PI01
CO
PI03
NO OMEGA v1.2a Board warm-up delay).
Contact open: Genset has a fault or cannot supply the load.

Note 2: Should be connected to the remote control terminals of the autostart of the
genset.
Contact closed: Genset should start (no need for response delay).
Contact open: Genset should shutdown (no need for cooling delay).

Note 3: This pin can be used when the remote control (R.C.) is set to "Gensets Rdy"
B
or "U Present". B

Note 4: This input can be used as Remote Control when the installation type is set to
GG installation and the R.C. is set to "v1.0 Compt."

(-) 5 to 35 V
-VBAT +VBAT G1 OK G2 OK CG1-F/B CG2-F/B Remote Control CG-F/B CM-F/B
C C
~
1 2 3 PI01 4 PI01 5 PI01 6 PI01 7 PI01 8 9 PI01
* * PI01 PI01 ^
Note 1 Note 1 MCB/MCO-G1 MCB/MCO-G2 Note 3 CM
PI03 PI03 PI03 PI03 PI03 PI03 Note 4
P MCB/MCO-G1 PI03 PI03 MCB/MCO-G2

GND
S.&A.S. Ltd.
ATS12a Wiring Jieh Chouf
Lebanon

* Not connected in MG installation


[email protected]
ATS12b WIRING DIAG:
DC Input/Output with MCB/MCO
D
^
~
Not connected in GG installation D

Connected only in MGG installation


Size FCSM No. DWG No. Rev
B
-NL0
NLATS12a0Sch
ATS12a.Sch 1NL1

Scale Sheet
2NL2ofof 55
-

1 2 3 4 5 6
1 2 3 4 5 6

AC Inputs

A
G2 G1 Main Supply A
R S T N R S T N R S T N

49 47 45 44 43 41 39 38 37 35 33 32 When Common is needed on Current Transformer


* * * * ^ ^ ^ ^
LINE LINE LINE G2 LINE LINE LINE G1 LINE LINE LINE Main
R G2 S G2 T G2 N R G1 S G1 T G1 N RM SM TM N

CTR - P1 31 P1 PIXF?01 CTR - P1 31 P1 PIXF?01


B OMEGA v1.2a Board Line R Line R B

CTR - P2 30 P2 PIXF?02 CTR - P2 30 P2 PIXF?02


CTR - P2

CTS - P1 CTS - P1
29 P1 PIXF?01 29 P1 PIXF?01
Line S Line S

CTS - P2 28 P2 PIXF?02 CTS - P2


28 P2 PIXF?02
CTT - P1
CTT - P1 27 P1 PIXF?01 27 P1 PIXF?01 COXF?
Line T Line T
C C

CTT - P2 26 P2 PIXF?02 CTT - P2 26 P2 PIXF?02

Current transformers installed on Load Side

S.&A.S. Ltd.
ATS12a Wiring Jieh Chouf
Lebanon
[email protected]
* Not connected in MG installation
ATS12b WIRING DIAG:
AC Inputs
D
^
~
Not connected in GG installation D

Connected only in MGG installation


Size FCSM No. DWG No. Rev
B
-NL0
NLATS12a0Sch
ATS12a.Sch 1NL1

Scale Sheet
3NL3ofof 55
-

1 2 3 4 5 6
1 2 3 4 5 6

AC OUTPUTS with Contactors

LINE R G LINE R M LINE R G1 LINE R G2


A
(Taken from output of CG1 & CG2) PIF?02 PIF?02 PIF?02 Single line diagram A
COF?
PIF?02 FUSE FUSE FUSE
FUSE
PIF?01
~ 22 PIF?01
^ 14 PIF?01 18PIF?01 * G1 G2

PIC?01 PIC?01

1
CG1 CG2 *
PIC?02 PIC?02

2
OMEGA v1.2a Board PIC?01 PIC?01 ~

1
COC?B
^CM PIC?02 PIC?02
CG

2
B B
CM CG1 CG2
C C C

PICM01 PICM01 PICM01 PICG10 PICG10 PICG10 PICG201 PICG201 PICG201 LOAD

PICM03 PICM03 PICM04 PICG103 PICG103 PICG104 PICG203 PICG203 COCG2PICG204


CM CM COCM
CM CG1 CG1 COCG1
CG1 CG2 CG2 CG2
Eng D.NO D.NC Eng D.NO D.NC Eng D.NO D.NC
NOTE 3 NOTE 4 NOTE 3 NOTE 4 NOTE 3 NOTE 4 Note 1: Used as an alarm output if fault exists on G1 or G2 in case
contactors are used for the transfer switch

Note 2: Used as an alarm output if utility is absent in case


contactors are used for the transfer switch
C C
Note 3: For use with motorized circuit breaker to engage it.

24 Note 4: For use with motorized circuit breaker to disengage it.


23 25 15 17 16 19 21 20
PIF?04 PIF?04 NOTE 2 PIF?04 NOTE 1 PIF?04 NOTE 1
- This wiring diagram is for 4-poles contactors.
CM CG CG2 CG1 - 3-poles contactors can be used if it is acceptable to connect the
PIF?01 PIF?01 PIF?01 PIF?01 neutrals of the Mains, G1 & G2 together.
PIC?0A1 PIC?0A1 PIC?0A1 PIC?0A1
A1

A1

A1

A1

CG COC?A CM CG1 CG2 S.&A.S. Ltd.


ATS12a Wiring Jieh Chouf
PIC?0A2 PIC?0A2 PIC?0A2 PIC?0A2
A2

A2

A2

A2

Lebanon

* Not connected in MG installation


[email protected]
ATS12b WIRING DIAG:
NG N Main NG1 NG2 AC Outputs with Contactors
D
(Taken from output of CG1 & CG2) ^
~
Not connected in GG installation D

Connected only in MGG installation


Size FCSM No. DWG No. Rev
B
-NL0
NLATS12a0Sch
ATS12a.Sch 1NL1

Scale Sheet
4NL4ofof 55
-

1 2 3 4 5 6
1 2 3 4 5 6

AC OUTPUTS with MCB/MCO


LINE R M LINE R G1 LINE R G2
PIF?02 PIF?02 PIF?02
A FUSE FUSE FUSE A

22 PIF?01 ^ 14 PIF?01 18 PIF?01 *

Single line diagram

OMEGA v1.2a Board G1 G2

PI01 PI01 PI01

1
B CM CG1 CG2 B
C C C MCB/MCO-M MCB/MCO-G1 MCB/MCO-G2

PICM01 PICM01 PICM01 PICG10 PICG10 PICG10 PICG201 PICG201 PICG201 ^ PI02 PI02 PI02 *

2
PICM03 PICM03 PICM04 PICG103 PICG103 PICG104 PICG203 PICG203 PICG204
CM CM COCM
CM CG1 CG1 COCG1
CG1 CG2 CG2 COCG2
CG2
Eng D.NO D.NC Eng D.NO D.NC Eng D.NO D.NC
NOTE 3 NOTE 4 NOTE 3 NOTE 4 NOTE 3 NOTE 4

LOAD
C C

23 25 24 15 17 16 19 21 20
PIF?04 PIF?04 PIF?04
MCB/MCO-G1 MCB/MCO-G2 MCB/MCO-G1
PIF?01 PIF?01 PIF?01
PIF?04 PIF?04 PIF?04
COF?
MCB/MCO-G2 MCB/MCO-M MCB/MCO-M S.&A.S. Ltd.
PIF?01 PIF?01 CO
PIF?01 ATS12a Wiring Jieh Chouf
Lebanon
ENG ENG ENG [email protected]
M M M * Not connected in MG installation
ATS12b WIRING DIAG:
AC Outputs with MCB/MCO
D D.ENG

MCB/MCO-M MCB/MCO-G1
D.ENG

MCB/MCO-G2
D.ENG

~^ Not connected in GG installation D

Connected only in MGG installation


Size FCSM No. DWG No. Rev
B
-NL0
NLATS12a0Sch
ATS12a.Sch 1NL1

N Main N G1 N G2 Scale Sheet


5NL5ofof 55
-

1 2 3 4 5 6