CALCULATION OF LINE-GROUND FAULT CURRENTS IN A THREE-WINDING TRANSFORMER (WYE-WYE WITH BURIED DELTA) - LinkedIn

This document discusses the calculation of line-ground fault currents in a three-winding transformer with a wye-wye configuration and a buried delta tertiary winding. It provides the positive, negative, and zero sequence impedance diagrams for line-ground faults on the primary and secondary sides. The calculations determine the fault currents on the primary, secondary, and tertiary windings to properly set ground fault relay protections.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
484 views7 pages

CALCULATION OF LINE-GROUND FAULT CURRENTS IN A THREE-WINDING TRANSFORMER (WYE-WYE WITH BURIED DELTA) - LinkedIn

This document discusses the calculation of line-ground fault currents in a three-winding transformer with a wye-wye configuration and a buried delta tertiary winding. It provides the positive, negative, and zero sequence impedance diagrams for line-ground faults on the primary and secondary sides. The calculations determine the fault currents on the primary, secondary, and tertiary windings to properly set ground fault relay protections.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

8/18/23, 11:03 PM (99+) CALCULATION OF LINE-GROUND FAULT CURRENTS IN A THREE-WINDING TRANSFORMER (WYE-WYE WITH …

2 99+ Try
Home My Network Jobs Messaging Notifications Me For Business

Create your own newsletter


Start your own discussion with a newsletter on LinkedIn. Share what you know and build
your thought leadership with every new edition.

Try it out

CALCULATION OF LINE-
GROUND FAULT
CURRENTS IN A THREE-
WINDING
TRANSFORMER (WYE-
WYE WITH BURIED
DELTA)
Nikhil Ardeshna, P.Eng, P.E. 1 article Following
Sr. Electrical Engineer

September 9, 2020

Open Immersive Reader

AUTHORS:

Nikhil Ardeshna P.Eng, P.E, Sr. Electrical Engineer, Actemium


Canada

Stephen Hill, CET, Engineering Manager, Actemium Canada

ABSTRACT:

There are many references available on the calculation of


fault currents involving transformers (Delta-Wye or Wye-
Wye or Delta-Delta) for various types of faults (3-Phase,
Line-Ground, Line-Line or Line-Line-Ground) on either side
of the transformer but very limited references are available
on the fault currents involving a Three-Winding
Transformer (Wye-Wye and buried tertiary (Delta) winding).
Line-Ground (L-G) fault on the Primary and Secondary side
are discussed in this white paper. Calculation of L-G fault

https://www.linkedin.com/pulse/calculation-line-ground-fault-currents-three-winding-nikhil/ 1/8
8/18/23, 11:03 PM (99+) CALCULATION OF LINE-GROUND FAULT CURRENTS IN A THREE-WINDING TRANSFORMER (WYE-WYE WITH …

currents on Primary, Secondary and Buried Tertiary winding


are important for proper relay settings.

INTRODUCTION:

In a three-winding transformer with Wye-Wye Buried


Tertiary (Delta), the Tertiary winding does not serve loads
and hence also called Buried Stabilizing Winding. The
corner of the Delta winding shall be grounded, and this is
done in a couple of ways. Either only one terminal of the
Delta corner will be brought out or two terminals are
brought outside, and the Delta is formed using a link
between the two bushings. The advantages of adding the
buried Delta in a Wye-Wye transformer:

1. It stabilizes the neutral point of the fundamental


frequency voltages when the neutral is not grounded

2. It provides a circulating path for 3rd harmonics

3. It provides a path for balancing currents when the


transformer Secondary must supply unbalanced loads

The three-winding transformer considered in this paper has


its Primary Wye solidly grounded and Secondary Wye
grounded using a 400A, 20 Ohm Neutral Grounding
Resistor (NGR).

CALCULATION:

In this paper, calculation of fault currents for the following


cases have been discussed:

CASE 1: L-G Fault on Secondary side

CASE 2: L-G Fault on Primary side

https://www.linkedin.com/pulse/calculation-line-ground-fault-currents-three-winding-nikhil/ 2/8
8/18/23, 11:03 PM (99+) CALCULATION OF LINE-GROUND FAULT CURRENTS IN A THREE-WINDING TRANSFORMER (WYE-WYE WITH …

THREE WINDING TRANSFORMER:

Typical impedances available from the manufacturer for this


three-winding transformer are shown below:

ZPS – Leakage imp. measured on Primary side with


Secondary shorted and Tertiary open

ZPT – Leakage imp. measured on Primary side with


Secondary open and Tertiary shorted

ZST – Leakage imp. measured on Secondary side with


Primary side open and Tertiary shorted

The impedances of each winding can be calculated as:

For the calculation scenarios in this paper, the following


values are assumed:

CASE 1: L-G FAULT ON SECONDARY


SIDE (13.8KV)

https://www.linkedin.com/pulse/calculation-line-ground-fault-currents-three-winding-nikhil/ 3/8
8/18/23, 11:03 PM (99+) CALCULATION OF LINE-GROUND FAULT CURRENTS IN A THREE-WINDING TRANSFORMER (WYE-WYE WITH …

Positive, Negative and Zero sequence impedance network


diagram is shown below in Fig. 3. Pre-fault voltage assumed
as 1.05 pu. 

https://www.linkedin.com/pulse/calculation-line-ground-fault-currents-three-winding-nikhil/ 4/8
8/18/23, 11:03 PM (99+) CALCULATION OF LINE-GROUND FAULT CURRENTS IN A THREE-WINDING TRANSFORMER (WYE-WYE WITH …

CASE 2: L-G FAULT ON PRIMARY


SIDE (69kV)

Positive, Negative and Zero Sequence impedance network


diagram is shown below in Figures 7 & 8. Pre-fault voltage
assumed as 1.05 pu. 

https://www.linkedin.com/pulse/calculation-line-ground-fault-currents-three-winding-nikhil/ 5/8
8/18/23, 11:03 PM (99+) CALCULATION OF LINE-GROUND FAULT CURRENTS IN A THREE-WINDING TRANSFORMER (WYE-WYE WITH …

https://www.linkedin.com/pulse/calculation-line-ground-fault-currents-three-winding-nikhil/ 6/8
8/18/23, 11:03 PM (99+) CALCULATION OF LINE-GROUND FAULT CURRENTS IN A THREE-WINDING TRANSFORMER (WYE-WYE WITH …

CONCLUSION:

Depending on the fault location, currents flowing on


primary and secondary side are calculated. These
calculations are necessary for the ground fault relay
protection settings. Please note the sample calculation does
not account for any source on secondary side.

REFERENCES:

1. Protective Relaying – Principles and Applications, 3rd


Edition by J. Lewis Blackburn and Thomas J. Domin.

2. IEEE C57.158-2017 - IEEE Guide for the Application of


Tertiary and Stabilizing Windings in Power Transformers
Report this

Published by
Nikhil Ardeshna, P.Eng, P.E. 1 article Following
Sr. Electrical Engineer
Published • 2y

Actemium Canada, Stephen Hill

Like Comment Share

Khaleel Ahmed Mohammed and 33 others


34 6 comments

Reactions

+22

6 Comments
Most relevant

Add a comment…

Venky V. • 2nd 2y
Engineering Manager

Well written and informative.


Thank you for sharing.

Like Reply · 1 Reply

Nikhil Ardeshna, P.Eng, P.E. • Following 2y


Sr. Electrical Engineer

Thank you Venky V.

Like Reply

Guru Dalip • 3rd+ 2y


CSU Electrical Supervisor at Bechtel Oil, Gas, & Chemicals

Excellent work Nikhil! Thanks for sharing

Like · 1 Reply · 1 Reply

Nikhil Ardeshna, P.Eng, P.E. • Following 2y


Sr. Electrical Engineer

Thank you Guru Dalip

https://www.linkedin.com/pulse/calculation-line-ground-fault-currents-three-winding-nikhil/ 7/8

You might also like