Boll Filter Protection System Program
Boll Filter Protection System Program
Siemensstraße 10 - 14
50170 Kerpen
Germany
www.bollfilter.com
1/38
2 / 38 Operating instructions Typ 2310
Betriebsanleitung Typ 2310
Table of Contents
1 Preface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
1.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Warranty and liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3 Copyright . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2 Basic safety instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
2.1 Warning signs and symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.2 Proper use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.3 Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.4 Obligations of the user/operator . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.5 Selection of staff and qualification . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.6 Organizational measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.6.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.7 Safety instructions for operating personnel . . . . . . . . . . . . . . . . . . . 11
2.7.1 Personal safety clothing and equipment . . . . . . . . . . . . . . . . . . . . . 11
3 Technical data of the control box and control cabinet components .13
3.1 Power components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.1.1 Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.1.2 Motor actuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.1.3 Control of the electric actuator EPI2-063-BK . . . . . . . . . . . . . . . . . . 13
3.1.4 Voltage supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.1.5 Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.2 Control circuit board inputs/outputs . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.2.1 Optocoupler inputs (E1-E5), terminals 31 - 40 . . . . . . . . . . . . . . . . 14
3.2.2 Analogue input 4-20 mA, terminals 41 -42 . . . . . . . . . . . . . . . . . . . 14
3.2.3 Live relay outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.2.4 Floating relay outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
4.1 Device functions and control flow . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.1.1 Software. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.1.2 Main switch operating feedback contact . . . . . . . . . . . . . . . . . . . . . 16
4.1.3 Control voltage monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.1.4 Motor fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.1.5 Actuator fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.1.6 DP too high backflushing filter (ΔP100 %). . . . . . . . . . . . . . . . . . . . 17
4.1.7 Operating hours counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.1.8 Error memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.1.9 Differential pressure transmitter 4-20 mA . . . . . . . . . . . . . . . . . . . . 17
4.1.10 DPT-Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.1.11 C key (additional functions display) . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.1.12 DP-Alarm (flushing frequency monitoring) . . . . . . . . . . . . . . . . . . . . 18
4.1.13 Message A4 "Flushing Active" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.1.14 Time delay differential pressure ΔP75% and ΔP100% . . . . . . . . . . 18
4.1.15 Function Remote On/Off (remote switching) . . . . . . . . . . . . . . . . . . 19
4.1.16 Initialisation incl. automatic control box type - setting . . . . . . . . . . . 19
4.2 "Operation" mode display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.3 Text messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.3.1 Text display after switching on. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
These operating instructions are intended for the user of the control box and his
employees. They contain texts, images and drawings that, without express
approval by the manufacturer, may not be
• duplicated,
• distributed or
• otherwise disclosed, neither in full nor in part.
Any infringement will result in liability for damages.
DANGER!
Danger to life / Serious harm to health!
Indicates an imminently hazardous situation involving a high risk which, if not
avoided, will result in death or severe (irreversible) injury.
ATTENTION
Material damage!
Indicates a situation which could lead to damage to the product itself or to objects
in its vicinity.
NOTE
Indicates special user tips and other particularly useful or important information.
DISPOSAL
Indicates special measures relating to environmental protection.
DANGER!
Risk of accidents due to improper installation
A failure of the device resulting from improper installation of the electronic control
box or the connected equipment could cause severe personal injury or even fatal
injury. Therefore, in addition to the general safety rules for equipment in industrial
power installations, comply with the following points in particular:
• The installation of the control box should only be performed by qualified
specialist staff in accordance with the conditions of IEC 364 and DIN VDE
0105 for electrical equipment.
• All applicable laws, conditions, regulations and instructions relating to the
installation of electrical equipment must be observed in relation to the
installation location.
• Settings for IP00 protection class devices (in the case of an opened control
cabinet or where there are no covers) must only be made by authorized
specialist staff, with the devices switched off and in compliance with the local
safety and accident prevention regulations.
• The control box may only be operated in the permitted area of use.
The safety clothing and equipment stipulated by the company for all work on the
control box must be worn.
3.1.1 Supply
The electric actuator type EPI2-063-BK is controlled via the outputs VS, VE1 and
VE2 (terminals 6, 8 and 10, see the control cabinet diagrams) of control circuit
board A2.
3.1.5 Fuses
ATTENTION
For the primary transformer connection 208 V and 230 V, the provided F1, F2
and F3 fuses with 2 amps must be used.
NOTE
The connections and designations are to be taken from the respective control
cabinet diagrams.
NOTE
The connections and designations are to be taken from the respective control
cabinet diagrams.
1 Fastening
2 Display and operating elements
3 Housing
4 Main switch
5 Connection
7 6 5
4.1.1 Software
The software for the type 2300 and type 2310 control boxes has been
amalgamated compared to the preceding type 2200 and type 2210 control boxes
in order to reduce the different versions, because the hardware of the control
circuit board A2 used (see control cabinet diagrams) is identical.
As soon as the main switch is actuated, the mains voltage is applied and the
control box is operating correctly, the "Operation" LED (green) comes on and the
relay "control voltage monitoring" is actuated. In the event of loss of the operating
voltage or a defective fuse on the control circuit board, no LED comes on and the
"control voltage monitoring" relay is no longer actuated.
If the measured motor current exceeds the set setpoint of the P9 parameter, a
message is output to the display and a floating signal is output to the relay
outputs. The motor and backflushing are immediately switched off. After clearing
of the fault, the user must acknowledge the alarm message by pressing the Q
key.
When the actuator signals a fault, the contact of input E3 (terminals 35 and 36,
see control cabinet diagram) is opened. This is followed by a message on the
display and a floating signal is output to relay output A2 (terminals 19-21, see
control cabinet diagrams). Backflushing is stopped and the actuator is switched
off. After clearing of the fault, the user must acknowledge the alarm message by
pressing the Q key.
The operating hours counter records the operating hours when the control box is
switched on. The operating hours are displayed by multiple pressing of the C key
(explanation - see section "C key").
The internal error memory records all errors and events including specification of
the operating hours. Reading out of the error memory is only allowed for
authorised persons.
4.1.10 DPT-Alarm
If key C (additional functions display) is pressed once, the number of flushes that
have been performed is output to the display for 3 seconds.
NOTE
If the C key is pressed repeatedly, each pressing causes the following additional
information to be displayed in the specified sequence:
• Currently measured differential pressure provided a differential pressure
transmitter is installed and the parameter P15 "DPT” Select has been set in
the control box.
• Operating hours with the control box switched on.
• Currently measured motor current, provided a filter type with a gear motor is
installed and has been set in the control box.
• DP-Alarm (flushing frequency monitoring) on or off
• Actual remaining time "DP1 delayed", if a time delay has been set in the
control box "Parameter P16 differential pressure delay time" and the contact
of input E1 (terminals 39 + 40, see control cabinet wiring diagrams) has been
closed for the flushing differential pressure ΔP75%.
• Actual remaining time "DP2 delayed", if a time delay has been set in the
control box "Parameter P16 differential pressure delay time" and the contact
of input E1 (terminals 37 + 38, see control cabinet wiring diagrams) has been
closed for the flushing differential pressure ΔP100%.
Output A4 "Flushing active" (terminals 25, 26 and 27, see control cabinet wiring
diagrams) is activated as soon as a flushing has been triggered at the filter.
The differential pressure signals "DP flushing [75%]" and "DP too high [100%] of
the connected differential pressure measuring device (differential pressure
switch [DPS] or differential pressure transmitter [DPT]) can be delayed
dependent on the application (for a detailed setting explanation see the section
"P16 DP delayed").
If the contact of input E4 ("Filter Blockage" (terminals 33 and 34, see control
cabinet wiring diagrams) has been closed, outputs A5 (terminals 28, 29 and 30,
see control cabinet diagrams) is activated and the control box switches to off
condition. All outputs and control time meters (e.g. forced flushing time) are
reset.
The remote function can only be activated once the message "Flushing active"
is no longer present.
Typical representation on the display if remote control is activated:
NOTE
Initialisation is not started if an operator has previously set the necessary control
box type according to the operating instructions.
An error message "P0 filter type" is output if a signal of the electric actuator is
active at input E3, initialisation has already been completed and the the wrong
control box types 0 (6.18/6.19/6.44) or 18 (aquaBoll) have been set by the
operator.
NOTE
The software of the preceding type 2200 and type 2210 control boxes have been
amalgamated in order to reduce the different versions for type 2300 and type
2310.
The type 2310 control box can only be used for filter types 6.18 and aquaBoll with
electric actuator type EPI2-063-BK (230 V version).
The following control box types are only intended to be used for control box type
2300.
ATTENTION
Control box types 0, 1, 2, 4, 6, 8, 10, 12, 14, 16 and 18 must not be used because
of the difference in hardware between type 2300 and type 2310 (see control
cabinet diagrams).
NOTE
3S Means the remaining flushing or after-blowing time equals 3 seconds.
Flushing number
xxxxxx Pc Number of flushes
The number of flushes is saved and backed up for protection against mains
failure.
NOTE
• The "Alarm" LED (red) comes on for each alarm message.
• All alarm messages are saved an backed up to protect against mains failure.
• In alternation with the operating messages, the alarm message is output
every 2 seconds to the second line of the display.
• Once the Q key is pressed, the alarm messages are deleted, however, only
once the source of the alarm has been cleared. If the source of the alarm has
not been cleared, the alarm message reappears.
To access the setting level - Parameter selection and view - the keys ▲ and ▼
are pressed simultaneously until the "Operation" LED (green) goes out
(approximately 3 seconds). The first line of the display shows the parameter, the
second line the parameter value. Now all parameters can be displayed by
repeated pressing of the ▲ or ▼ key.
To access the setting level - Parameter change and storage - the middle key is
pressed until the "Operation" LED (green) flashes (approximately 3 seconds).
Now the parameter can be changed by repeated pressing of the ▲ or ▼ key. To
save the set value and return to the - Parameter selection and view - setting level,
the middle key is pressed until the "Operation" LED (green) goes out
(approximately 3 seconds).
To access the operating level, the keys ▲ and ▼ are pressed simultaneously
until the "Operation" LED (green) comes on (approximately 3 seconds).
NOTE
To save the newly set parameter, you must always return to the operating level.
NOTE
This parameter can be set for all filter types (Factory setting: Off).
It is important to note that after activation this message is only shown on the
display. If required, this message can be routed to a floating relay output
(terminals 19-27, see control cabinet diagrams) by setting parameter P17 alarm
relay A2, A3, A4 (configurable alarm outputs) accordingly.
Adjustable Off/on
Factory setting Basic value
Off
NOTE
The motor fault setting is dependent on the installed and approved standard gear
motors 0.09 kW, 0.12 kW or 0.18 kW.
Star connection settings:
0.09 kW - Standard - Gear motor = 0.4 amp
0.12 kW - Standard - Gear motor = 0.65 amp
0.18 kW - Standard - Gear motor = 0.8 amp
Adjustable D German
ES Spanish
F French
EN English
NOTE
This parameter is visible for all P0 filter types.
The testcode is divided into two areas:
• Advanced settings:
In the first area, entry of a testcode grants access to an advanced setting
level, in which additional parameters (such as P15, P16 and P17) can be set.
(Detailed description see "P15 DP-Select", P16 DP Differential pressure
delay time" and "P17 Alarm relay A2, A3, A4")
• Test mode:
In the second area, entry of the testcode provides access to a test mode,
which is only intended for authorised persons. Additionally, the internal error
memory can be read out to a USB stick.
NOTE
Entry of Testcode 44 opens an advanced setting, which allows selection of the
differential pressure evaluation between differential pressure switch (DPS =
standard) and differential pressure transmitter (DPT = optional).
The advanced setting "P15 DP-Select" is only required if a differential pressure
transmitter (output signal: 4-20 mA and electrical connection type: three-wire) is
used to control the filter.
(Detailed explanation on setting and operation see Fig. 4.6)
NOTE
The maximum measurable differential pressure of the installed differential
pressure transmitter must be set prior to commissioning.
NOTE
The differential pressure signal "Differential pressure flushing ΔP 75%" must be
set prior to commissioning.
NOTE
The differential pressure signal "Differential pressure too high ΔP 100%" must be
set prior to commissioning.
NOTE
Entry of Testcode 10 opens an advanced setting, which enables selection of a
time delay for the differential pressure signals ΔP 75% and ΔP 100%.
(Detailed explanation on setting and operation see Fig. 4.7)
NOTE
Entry of Testcode 75 opens an advanced setting that enables configuration of the
alarm outputs A2, A3 and A4.
The advanced setting "P17 Alarm Relay A2, A3, A4" is necessary if the customer
requires alarm outputs that differ from the standard at the system level (see
standard control cabinet diagrams).
(See Fig. 4-8 for detailed explanation of Adjustment and operation)
Inputs
Pressure switch "DP reached backflushing filter" 75 %
Pressure switch "DP too high backflushing filter" 100 %
Customer input Filter blockage (Remote On/Off)
Outputs
Motor
Electric flushing valve
Floating contacts
1) Key F
2) The elapsed forced flushing time
3) Pressure switch "DP reached backflushing filter"
Additional functions in the DP-Alarm is switched on (flushing frequency
monitoring)
If, before the forced flushing time elapses, flushing is triggered via the "DP
reached backflushing filter", a DP-Alarm is signalled (flushing frequency alarm)
(setting See Section "P8 DP-Alarm").
Parametrisation of the alarm outputs is performed in section "P17 Alarm Relay
A2, A3, A4".
Peculiarities
• All alarms are displayed, signalled over floating contacts and saved.
• If the control box is in configuration mode, manual triggering of flushing is not
possible.
• If the "Control box type" parameter is changed, the functions are restarted.
NOTE
Setting values can be matched to the respective requirements as necessary.
NOTE
Refer to the control cabinet diagrams for the spare parts for the control box.
DISPOSAL
Observe the regulations for environmental protection. Make sure that the
removed components are disposed of properly and in an environmentally friendly
manner.