0% found this document useful (0 votes)
265 views65 pages

Cables & Power Network Calculations

The smoke emission tests (IEC 61034, BS EN 61034) for low smoke and halogen free cables are used to evaluate and classify the cables according to their smoke producing characteristics when affected by external fire. These tests measure the optical density of smoke produced during combustion of cable samples and classify the cables based on low, medium or high smoke emission levels. Cables with low smoke emission are preferable in areas like public buildings where evacuation time needs to be maximized by reducing smoke hazards.

Uploaded by

salemg82
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
265 views65 pages

Cables & Power Network Calculations

The smoke emission tests (IEC 61034, BS EN 61034) for low smoke and halogen free cables are used to evaluate and classify the cables according to their smoke producing characteristics when affected by external fire. These tests measure the optical density of smoke produced during combustion of cable samples and classify the cables based on low, medium or high smoke emission levels. Cables with low smoke emission are preferable in areas like public buildings where evacuation time needs to be maximized by reducing smoke hazards.

Uploaded by

salemg82
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 65

Cables & Power Network Calculations

By
Ahmed Besheer
Senior Electrical Design Engineer
at Schneider Electric
1 L.V Conventional Cables Construction

2 Self Study Question “Q1”

3 Conventional Cables Classifications

4 General Hints about cables

5 Self Study Question “Q2”


How to write Conventional cables on
6
SLD

7 Fire Cables

8 Self Study Question “Q3”


9 Cable Routing Types

10 Cables Derating Factors Overview


Relation between (Protective device ,
11
Cable & Load)

12 Voltage Drop

13 Short Circuit

14 Solved Example
L.V Conventional
Cables Construction
Low Voltage Cable Construction

1. Conductor
• AL
• CU

2. Insulation or Dielectric
• PVC (Polyvinyl Chloride) - “Thermoplastic”
• XLPE (Cross-linked polyethylene) - “Thermoset”

3. Filler or Assembly
• PVC or Polypropylene to fill spaces between cores to make the round form of cable.
• Polypropylene tape is used as a barrier tape over the laid up cores. Such tape(s) will bind the
cores together and prevents them from opening out
4. Bedding or Inner jacket or Inner Sheath
• PVC bedding , Mandatory in case of armoured cables.
• Used under cable armouring to protect the laid up
cores and as a separation sheath

5. Armouring
• Steel tape or wire tape , it is used for protection of
cable against mechanical stresses.

6. Outer jacket or Outer Sheath


• PVC , it contains & protects all cable layers and its
metallic parts from corrosion.
Self Study Question
“Q1”
Self Study Question “Q1”
✓ State M.V Cable construction
✓ Clarify the function of each layer in this construction.
Interactive Question !
When It’s Mandatory to use Bedding in cables?
Conventional Cables
Classifications
Conventional Cables Classifications
1. According to conductor type
• AL
• CU
2. According to Number of conductors
• Single Core
• Multicores ( 2 or 3 or 4 ) Cores
3. Neutral type “Regarding Multi Cores Cables”
• Full Neutral
• Half Neutral
4. According to Inner Insulation Types
• PVC
• XLPE
Interactive Question !
“Regarding Multi-Cores Cables”
When to use 2 cores , 3 cores , 4 cores cables respectively ?
5. According to Insulation Voltage Level
6. According to Insulation Voltage Level
• PVC (Thermo-plastic)
❖ Lower cost
❖ Max. operating temp. = 70 or 85 °C
❖ Max. short circuit temp. = 160 °C
❖ Softens at high temperatures

• XLPE (Thermo-Setting)
❖ Higher cost
❖ Max. operating temp. = 90 °C
❖ Max. short circuit temp. = 250 °C
❖ Highly resistant against humidity
❖ Rigid, doesn’t Soften at high temperatures
❖ Superior electrical properties (XLPE Cables provides higher current rating than PVC cables for same C.S.A
❖ Superior Moisture resistance capability than PVC cables.
❖ Longer service life compared to PVC Cables
❖ XLPE Cable is environment friendly compared with PVC insulated Cable while burning
7. According to Armouring
• Armoured STA
❖ STA (Steel Tape Armouring)
❖ SWA (Steel Wire Armouring)
❖ DST (Double Steel Tape Armouring)
❖ ATA (Aluminum Tape Armouring)
❖ AWA (Aluminum Wire Armouring)

• Non-Armoured
SWA
General Hints
about Cables
General Hints about cables

✓ Stranded conductors are preferable than solid conductors due to skin effect.

Stranded Solid

✓ Armouring enhances Cable’s mechanical strength but reduces cable’s flexibility.

✓ In case of armoured single core cables , ATA or AWA shall be used


in stead of STA or SWA.
✓Core shape types

Sectoral Circular
Self Study Question
“Q2”
Self Study Question “Q2”
✓ State Difference between SWA & STA Armoured cables
regarding below mentioned points:
• Overall Cable Diameter.
• Overall Cable Weight.

✓ State When to use Full Neutral Cables & Half Neutral Cables.
How to write
Conventional cables
on SLD
Cables Wires
• (4x240) CU/XLPE/PVC • 3X(1X6) CU/PVC
+(1x120) CU/PVC

• (3x240+1X120) CU/PVC/PVC
+(1x120) CU/PVC

• 2//(4x240) CU/XLPE/PVC
+(1x240) CU/PVC

• 4//(4x240) CU/XLPE/PVC
+2//(1x240) CU/PVC
Fire Cables
INTRODUCTION

▪ In a fire accident some people die because of


the fire, but the majority die because of the smoke.

▪ Halogen is added to the plastics used in conductor’s insulation to


give it the property of self-extinguish such as PVC which contain chlorine
atom. Chlorine is one of halogens as Fluorine, Bromide and Iodine. But,
in case of fire, halogens produce great amount of smoke which contains
That hamper visibility required for escaping from a dangerous places or
trying to find an exit out.

▪ (HCI, CO & CO2) which are produced while a conventional cable is


burning out, dissolves in the fluids of the human body organs like lungs,
nose and eye causing cell damage, shortage of oxygen and suffocation.
LS0H Cables
▪ Why to use LSHF cables ?
✓ Doesn’t contain halogen: hydrochloric acid isn’t formed during the fire so there is no threat of suffocation.
✓ Reduces smoke to the minimum: reducing the confusion , panic and suffocation ratio.

▪ When to use LSHF cables ?


✓ In theaters , hotels , hospitals , under ground tunnels and all closed public places where we can’t afford losing
people by suffocation.
• LSFH VS PVC
▪ How to Write LS0H on SLD?
✓ For cables: (4 x70 ) CU/XLPE/LSHF
✓ For wires:3X(1X6) CU/LS0H

✓ Note: LS0H cables have Flame Retardancy properties according to most of cables manufacturers.
What is meant be: fire retardant cable?
o Cables which doesn’t spread fire rapidly according to test certificates IEC / BS.
o Cables which are self-extinguishing.

According to BS EN / IEC60332 There are 3 Categories of flame retardant cables A, B & C

For Example:
BS EN / IEC 60332-3-22 (CAT A): is the most severe test:
sample of cables of length of 3.5m at least, fixed vertically on a ladder, then to be exposed to a flame of
70.000 Btu/h for a period of (40) minutes.
Length of the damage will be measured, the length of charred position on the test sample should not have
reached a height exceeding 2.5 m above the bottom edge of the burner.
Flame Resistance Cables

▪ Why to use Fire Resistant cables ?


✓ Designed to maintain circuit integrity of those vital emergency services during
the fire for certain time (fire safety loads).
✓ The individual conductors are wrapped with a layer of fire resisting mica/glass
tape which prevents phase to phase and phase to earth contact even after the
insulation has been burnt away.

▪ Where to use Fire Resistant cables ?


Feeding all fire safety loads at any type of buildings where the integrity of the circuit is required during the fire
conditions , for example:
✓ Fire pumps.
✓ EMCCs feeding loads related to life safety like: smoke fans & pressurization fans ...etc.
IEC 60331 Fire Resistance Test:
✓ A sample is connected to an electrical supply at its rated voltage from one end with indicator lamps at the other end.
Fire is applied for a period of 90 minutes with temperature on the cable equals to 750°C
✓ The fire shall be extinguished but the cable sample shall remain energized for a further 15 min.
The cable sample must maintain its circuit integrity after the total period of test (105 minutes).

BS 6387 Fire Resistance Test (more stringent than IEC 60331-21):


1.Fire resistant test ( Fire Alone):
Cables are tested by gas burner flame while a current is passing at its rate voltage Four categories are defined:
• Category A: Cables are subjected to fire at 650°C for 3 hours.
• Category B: Cables are subjected to fire at 750°C for 3 hours.
• Category C: Cables are subjected to fire at 950°C for 3 hours.
• Category S: Cables are subjected to fire at 950°C for 20 minutes.
2. Resistance to fire with water:
• Category W: Cables are subjected to fire at 650°C for 15 minutes, then at 650°C with water spray for a further 15 minutes.

3. Resistance to fire with water:


Resistance to fire with mechanical shock:
• Category X: Cables are subjected to fire at 650°C with mechanical shock each 30 seconds for 15 minutes.
• Category Y: Cables are subjected to fire at 750°C with mechanical shock each 30 seconds for 15 minutes.
• Category Z: Cables are subjected to fire at 950°C with mechanical shock each 30 seconds for 15 minutes.

The highest category for BS 6387 is CWZ where the three tests are performed on the three samples of the same cable.
▪ Planning & Design aspects to use Fire Cables:

Planning an electrical safety system means finding answers to these questions:

✓Which electrical system has to be supplied for how long?


✓Which circuits are involved (safety circuits)?
✓Which is the best cable routing for these circuits?
✓Are there restrictions concerning fire load (like fire pump)?
✓How many hours required to evacuate the building acc. to evacuation plan
▪ How to Write Fire Cables on SLD:

• Regarding LS0H Cables:


✓ For cables: (3 x70 + 1 x 35) CU/XLPE/LSHF
✓ For wires: 3X(1X6) CU/LS0H

• Regarding Fire Resistant Cables:


✓ For cables: (3 x70 + 1 x 35) CU/Mica/XLPE/LSHF
✓ For wires: 3X(1X6) CU/LS0H
Interactive Question !
How to write: Multi-Cores Cable – Half Neutral – Steel Tap Armoured –
Fire Resistant – C.S.A = 50 mm^2
Self Study Question
“Q3”
Self Study Question “Q3”
✓ Provide a conclusion about below tests:
▪ For Low Smoke and Halogen free Cables
o Smoke Emission Tests: (IEC 61034, BS EN 61034)
o Acid Gas Emission Tests: (IEC 60754, BS EN 50267)

✓ Provide a conclusion about below tests:


▪ For flame retardant cables
o BS EN 60332, IEC 60332-3

✓ Provide a conclusion about below tests:


▪ For flame resistant cables
o BS BS 6387 , IEC 60331-21
Cable Routing
Types
Cable Routing Types
▪ Free in air
✓ Cables are installed on cable trays or cable ladders.

▪ Laid in ground
✓ Directly buried in ground
✓ Buried in ground inside conduit
✓ Buried in ground inside duct bank “Concrete encasement”

▪ In conduits
✓ Inside wall
Cables Derating
Factors Overview
Type of Circuit Breakers
LV C.Bs

Miniature Circuit Breaker Molded Case Circuit Breaker Air Circuit Breaker
MCB MCCB ACB
Type of trip units trip units

✓There are basically two types of


units:
• mechanical (commonly known as
thermal / magnetic trip units) thermal / magnetic electronic
trip units trip units
• electronic (Micro-logic) trip units
(also known as solid state trip units)

Overload protection

✓Both trip units serve the same thermal relay long time
primary function:
• to provide overcurrent protection,
• to provide the disconnection
magnetic relay short time
of a circuit carrying an excess
current. Short-circuit protection
Choice of protection devices

The difference between a thermal-magnetic and electronic curve

TM

M.L
Relation between
(Protective device ,
Cable & Load)
𝑝 𝑺
IB = or IB = For 3-phase load
√ 3 𝑥 𝑉 𝑥 𝑃.𝐹 √ 3𝑥𝑉

In > IB

In
It =
C.F (𝑡𝑜𝑡𝑎𝑙)
It is the target cable current carrying capacity / target cable Ampacity.
C.F (𝒕𝒐𝒕𝒂𝒍) is the Resultant Correction factor or Resultant Derating factor according to cable installation surrounding
conditions.
Finally the below condition should be applied:

IZ ≥ It > In > Ib
IZ is the standard current carrying capacity or Cable Ampacity of cable mentioned in catalogues / codes.
Voltage Drop
(mv/A/m)𝑥 𝐼𝑏 𝑥 𝐿
V.Dind = = … (v)
1000

Where:
V.D = Voltage Drop (v)
(mv/A/m) = specific voltage drop
L = cable length (m)
Ib = Base current or load current (A)

NOTE:
The previous lows are for individual V.D
Accumulated V.D = Individual V.D + Up stream voltage drop
Accumulated V.D % = 5 % according to NEC
Accumulated V.D % = 2.5 % according to EGY. CODE

𝑉.𝐷 (𝑎𝑐𝑐𝑢𝑚𝑢𝑙𝑎𝑡𝑒𝑑)
V.D% = … (%)
𝑆𝑜𝑢𝑟𝑐𝑒 𝑉𝑜𝑙𝑡𝑎𝑔𝑒
Short Circuit
The negative effects of short-circuits on installations:

Thermal effects
temperature rise in conductors.

Mechanical effects
High electrodynamic forces, High risk of electrical contacts or busbars being deformed or broken.

Electromagnetic effects
Disturbances for measuring devices located near electrical circuits.
𝑉𝑛.𝑙
Is.c = = … short circuit current (KA)
𝑍𝑡
Where:
Vn.L = No load ( L-N ) secondary voltage of distribution transformer (V)
Zt = Total impedance contributing in s.c level (m.Ω)
Transformer Impedance
Transformer Impedance
Cable Impedance
𝐿
Rc = ρ
𝐴
Where:
• Rc = Cable resistance (Ω)
• ρ = Resistivity constant of conductor material (mΩ.mm2/M)
• 𝜌𝑐𝑢 = 23.69 mΩ.mm2/M
• 𝜌𝐴𝑙 = 37.65 mΩ.mm2/M
• L = Cable length (M)
• A = Cross sectional area (mm2)

Xc =
Motors Contribution in Short circuit Value
Short circuit Rating of M.V network acc. To Egy. Code:
Solved Example

You might also like