ASHRAE 30-2019 Errata (February 2, 2022)

The document provides corrections to ANSI/ASHRAE Standard 30-2019 Method of Testing Liquid Chillers. It lists page numbers where errors were found and provides the corrections, such as changing variables, words, or values. Corrections include changing subscripts, variables, words, and values on various pages of the document.

Uploaded by

Damaso Taracena
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
144 views1 page

ASHRAE 30-2019 Errata (February 2, 2022)

The document provides corrections to ANSI/ASHRAE Standard 30-2019 Method of Testing Liquid Chillers. It lists page numbers where errors were found and provides the corrections, such as changing variables, words, or values. Corrections include changing subscripts, variables, words, and values on various pages of the document.

Uploaded by

Damaso Taracena
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

ERRATA SHEET FOR

ANSI/ASHRAE STANDARD 30-2019


Method of Testing Liquid Chillers

February 2, 2022

The corrections listed in this errata sheet apply to ANSI/ASHRAE Standard 30-2019. The first
printing of 30-2019 is identified as “Product Code: 86087 5/19” on the outside back cover.
Shaded items have been added since the previously published errata sheet dated March 9, 2021 was
distributed

Page Erratum (Note: Additions are shown in underline and deletions are shown in strikethrough.)

7 5.4.2.2. In the Winput equation, change the subscript 𝑖 to j as shown below.

𝑊 𝑊 𝑄

8 5.4.4.2. In both the equation and the table header, correct the variable symbol for pipe
roughness to be the lower-case Greek letter epsilon. Change ∈ to ε as shown below.

0.25
ƒ 2
∈ ε⁄d 5.74
log10 +
3.7 Re0.9

Commercial Pipe, ∈ ε (rms)


New Condition ft m
−4
Steel 1.810 5.510−5
Plastic 6.010−6 1.810−6

15 6.3.1.4.1.1. In the first sentence of Section 6.3.1.4.1.1 change the word “optical” to
“optional” as shown below.

6.3.1.4.1.1 Units with an optional optical integrated evaporator or condenser liquid pump
shall be tested in either of the following two configurations.

22 Table 6-6 Definition of Operating Condition Tolerances and Stability Criteria


(Continued). For evaporator or condenser, entering air mean dry-bulb temperature, heating
(frosting), change the stability criteria term from “5.6” to “0.56” as shown below.

Heating portion: sT ≤ 0.56 5.6 Δ°C [1.00 Δ°F]

Page 1 of 1 2022 ASHRAE. All rights reserved.