Problem Unit 1
Problem Unit 1
9. A building has a U-value of 0.5 W/m .K and a total exposed surface area of 384
2
m . The building is subjected to an external load (only sensible) of 2 kW and an
o
internal load of 1.2 kW (sensible). If the required internal temperature is 25 C, state
whether a cooling system is required or a heating system is required when the
o
external temperature is 3 C. How the results will change, if the U-value of the
building is reduced to 0.36 W/m.K?
Since the outdoor temperature at balance point is greater than the external
temperature (Text < Tout,bal);
When the U-value of the building is reduced to 0.36 W/m.K, the new balanced
outdoor temperature is given by:
(Q solar + Q int ) (2 + 1.2)x1000 o
Tout,bal = Tin − = 25 − = 1.85 C
sensible 0.36 x 384
UA
Since now the outdoor temperature at balance point is smaller than the external
temperature (Text > Tout,bal);
The above example shows that adding more insulation to a building extends the
cooling season and reduces the heating season.
10. An air conditioned room that stands on a well ventilated basement measures 3 m
wide, 3 m high and 6 m deep. One of the two 3 m walls faces west and contains a
double glazed glass window of size 1.5 m by 1.5 m, mounted flush with the wall with
no external shading. There are no heat gains through the walls other than the one
facing west. Calculate the sensible, latent and total heat gains on the room, room
sensible heat factor from the following information. What is the required cooling
capacity?
o
Inside conditions : 25 C dry bulb, 50 percent RH
o o
Outside conditions : 43 C dry bulb, 24 C wet bulb
2
U-value for wall : 1.78 W/m .K
2
U-value for roof : 1.316 W/m .K
2
U-value for floor : 1.2 W/m .K
o
Effective Temp. Difference (ETD) for wall: 25 C
o
Effective Temp. Difference (ETD) for roof: 30 C
2
U-value for glass ; 3.12 W/m .K
2
Solar Heat Gain (SHG) of glass ; 300 W/m
Internal Shading Coefficient (SC) of glass: 0.86
External loads:
a) Heat transfer rate through the walls: Since only west wall measuring 3m x 3m with
a glass windows of 1.5m x 1.5m is exposed; the heat transfer rate through this wall is
given by:
c) Heat transfer rate through floor: Since the room stands on a well-ventilated
basement, we can assume the conditions in the basement to be same as that of the
o o
outside (i.e., 43 C dry bulb and 24 C wet bulb), since the floor is not exposed to solar
radiation, the driving temperature difference for the roof is the temperature difference
between the outdoor and indoor, hence:
d) Heat transfer rate through glass: This consists of the radiative as well as
conductive components. Since no information is available on the value of CLF, it is
taken as 1.0. Hence the total heat transfer rate through the glass window is given by:
(Sensible)
e) Heat transfer due to infiltration: The infiltration rate is 0.5 ACH, converting this into
mass flow rate, the infiltration rate in kg/s is given by:
minf = density of air x (ACH x volume of the room)/3600 = 1.095 x (0.5 x 3x3x6)/3600
-3
minf = 8.2125 x 10 kg/s
Sensible heat transfer rate due to infiltration,Qs,inf;
-3
Qs,inf = minfcpm(To−Ti) = 8.2125 x 10 x 1021.6 x (43 – 25) = 151 W (Sensible)
Internal loads:
a) Load due to occupants: The sensible and latent load due to occupants are:
b) Load due to lighting: Assuming a CLF value of 1.0, the load due to lighting is:
Total sensible and latent loads are obtained by summing-up all the sensible and
latent load components (both external as well as internal) as:
To calculate the required cooling capacity, one has to know the losses in return air
ducts. Ventilation may be neglected as the infiltration can take care of the small
ventilation requirement. Hence using a safety factor of 1.25, the required cooling
capacity is: