Multi-Functional Digital Panel Meters
Multi-Functional Digital Panel Meters
In order to have a safe and correct use of the instrument, please read this manual carefully and make sure
to pay attention to the following points in use:
一、 Technical parameters
Table 1
Technical parameters Index
Connection mode Three phase three wire、three phase four wire
AC220V、AC450V,the other specification can be
Rated value
custom-made
Voltage Overload Continuously:1.2 times instant:2 times/5s
Consumption ≤2VA(per phase)
Input Resistance >500kΩ
signal Rated value AC 1A 、AC 5A
Current overload Continuously:1.2 times instant:10 times/5s
Current Consumption of
≤1VA(per phase)
the current circuit
Resistance <20mΩ(per phase)
Frequency Input range 45Hz~65Hz
Power Supply voltage range AC/DC85V~264V, 50Hz/60Hz
supply Consumption <5W / 15VA
Battery capacity of the clock ≥200mAh
Clock
Accuracy of the clock(error per
(※) ≤0.5s/d(23℃)
day)
Display Block code LCD or LED display
Voltage Class 0.5 resolving power 0.1V
resolving power
Current Class 0.5
Output Measure 0.001A Conform to GB/T
parameters resolving power 22264-2008
Frequency Class 0.5
0.01Hz
Active power Class 0.5 resolving power 0.1W
Page 1/Total 10
Quick operation manual
resolving power
Reactive power Class 1
0.1var
Power factor Class 0.5 resolving power 0.001
resolving power Conform to GB/T
Active energy Class 0.5S
0.01kWh 17215.322-2008
resolving power Conform to GB/T
Reactive energy Class 2
0.01kvarh 17215.323-2008
Energy Support forward、reverse measurement active energy,
measurement four-quadrant measurement reactive energy.
Active 10000 imp/kWh, reactive 10000imp/kvarh, the other
Pulse constant
Energy constants can be custom-made
Supply active、reactive energy optical signal and
Pulse signal
optocoupler collector open-circuit electrical signal impulse
output(note 2)
output, pulse length:80±16ms。
Auxiliary
Protocol ModBus_RTU
function
Note 1:the other performance index, please refer to GB/T 22264.1-2008 the requirement of the indoor
meters.
Note 2:PD666-2S□、PD666-6S□ series supply 1 set of pulse output, PD666-3S□、PD666-8S□ series
supply 2 set of pulse output.
二、 Wiring instructions:
Page 2/Total 10
Quick operation manual
6-------IB*(input high end of B phase current) 7------IB(output low end of B phase current)
8-------IC*(input high end of C phase current) 9------IC(output low end of C phase current)
Voltage signal wire
11-------UA(input end of A phase voltage) 12-------UB(input end of B phase voltage)
13-------UC(input end of C phase voltage) 14-------UN(input end of earth line voltage)
Auxiliary power supply
1 -------L (input live line of auxiliary power supply) 2 ------N(input earth line of auxiliary power
supply)
Note: add AC/DC85V~264V between L and N(no earth line or live line)
RS485 communication line
58-------A(RS485 A end) 59-------B(RS485 B end)
Energy pulse output line(PD666-2S□、PD666-6S□ series)
65-------output high end of active energy pulse 67-------output low end of active energy pulse
Energy pulse output line(PD666-3S□、PD666-8S□ series)
65-------P+(active energy pulse end) 66-------Q+(reactive energy pulse end)
67-------PQ-(common port)
三、 Instructions of programming parameters
Instruction of keys: “Menu”the key of(“ SET ”) means “confirm”,the key of“Esc” (“ ”)means “exit”,
“ ”means “reduce”and “ ”means “add”. Input the password(assumed to be 701),enter the submenu
item of “system settings”:
五、 Communication protocol
Table 3
Length
Parameter Parameter Instruction of the Read&write
Type of data of data
address code parameters attributes
Word
Keyboard parameters(detailed function see the instruction of the programming parameters,the actual
value of the parameter with(*)= communication parameter value × 0.1)
Page 5/Total 10
Quick operation manual
A phase active power,the single precision floating 2
2014H Pa R
unit is W decimal
B phase active power,the single precision floating 2
unit is W decimal
2016H Pb R
(invalid when three phase
three wire)
C phase active power,the single precision floating 2
2018H Pc R
unit is W decimal
Conjunction reactive single precision floating 2
201AH Qt R
power,the unit is var decimal
A phase reactive power, single precision floating 2
201CH Qa R
the unit is var decimal
B phase reactive power, single precision floating 2
the unit is var decimal
201EH Qb R
(invalid when three phase
three wire)
C phase reactive power, single precision floating 2
2020H Qc R
the unit is var decimal
single precision floating 2
2022H RESERVED reserved R
decimal
single precision floating 2
2024H RESERVED reserved R
decimal
single precision floating 2
2026H RESERVED reserved R
decimal
single precision floating 2
2028H RESERVED reserved R
decimal
single precision floating 2
202AH PFt Conjunction power factor R
decimal
A phase power factor single precision floating 2
202CH PFa (invalid when three phase decimal R
three wire)
B phase power factor single precision floating 2
202EH PFb (invalid when three phase decimal R
three wire)
C phase power factor single precision floating 2
2030H PFc (invalid when three phase decimal R
three wire)
single precision floating 2
2032H RESERVED reserved R
decimal
single precision floating 2
2034H RESERVED reserved R
decimal
single precision floating 2
2036H RESERVED reserved R
decimal
single precision floating 2 R
2038H RESERVED reserved
decimal
single precision floating 2 R
203AH RESERVED reserved
decimal
Page 6/Total 10
Quick operation manual
single precision floating 2 R
203CH RESERVED reserved
decimal
single precision floating 2 R
203EH RESERVED reserved
decimal
single precision floating 2 R
2040H RESERVED reserved
decimal
single precision floating 2 R
2042H RESERVED reserved
decimal
single precision floating 2 R
2044H Freq Frequency
decimal
single precision floating 2 R
2046H RESERVED reserved
decimal
single precision floating 2 R
2048H RESERVED reserved
decimal
single precision floating 2 R
204AH RESERVED reserved
decimal
single precision floating 2 R
204CH RESERVED reserved
decimal
single precision floating 2 R
204EH RESERVED reserved
decimal
Total active power single precision floating 2 R
2050H DmPt
demand decimal
single precision floating 2 R
2052H RESERVED reserved
decimal
Page 7/Total 10
Quick operation manual
single precision floating
4014H RESERVED reserved 2 R
decimal
single precision floating
4016H RESERVED reserved 2 R
decimal
single precision floating
4018H RESERVED reserved 2 R
decimal
single precision floating
401AH RESERVED reserved 2 R
decimal
single precision floating
401CH RESERVED reserved 2 R
decimal
(current)positive active single precision floating
401EH ImpEp 2 R
total energy decimal
single precision floating
4020H RESERVED reserved 2 R
decimal
single precision floating
4022H RESERVED reserved 2 R
decimal
single precision floating
4024H RESERVED reserved 2 R
decimal
single precision floating
4026H RESERVED reserved 2 R
decimal
(current)negative active single precision floating
4028H ExpEp 2 R
total energy decimal
single precision floating
402AH RESERVED reserved 2 R
decimal
single precision floating
402CH RESERVED reserved 2 R
decimal
single precision floating
402EH RESERVED reserved 2 R
decimal
single precision floating
4030H RESERVED reserved 2 R
decimal
(current) first quadrant single precision floating
4032H Q1Eq 2 R
reactive total energy decimal
single precision floating
4034H RESERVED reserved 2 R
decimal
single precision floating
4036H RESERVED reserved 2 R
decimal
single precision floating
4038H RESERVED reserved 2 R
decimal
single precision floating
403AH RESERVED reserved 2 R
decimal
(current) second quadrant single precision floating
403CH Q2Eq 2 R
reactive total energy decimal
single precision floating
403EH RESERVED reserved 2 R
decimal
single precision floating
4040H RESERVED reserved 2 R
decimal
4042H RESERVED reserved single precision floating 2 R
Page 8/Total 10
Quick operation manual
decimal
single precision floating
4044H RESERVED reserved 2 R
decimal
(current) third quadrant single precision floating
4046H Q3Eq 2 R
reactive total energy decimal
single precision floating
4048H RESERVED reserved 2 R
decimal
single precision floating
404AH RESERVED reserved 2 R
decimal
single precision floating
404CH RESERVED reserved 2 R
decimal
single precision floating
404EH RESERVED reserved 2 R
decimal
(current) fourth quadrant single precision floating
4050H Q4Eq 2 R
reactive total energy decimal
single precision floating
4052H RESERVED reserved 2 R
decimal
single precision floating
4054H RESERVED reserved 2 R
decimal
single precision floating
4056H RESERVED reserved 2 R
decimal
single precision floating
4058H RESERVED reserved 2 R
decimal
All the electric quantity data read by the communication is quadratic numerical, the rate is excluded,
complement numbers are the representation of negative numbers. Following is the detailed conversion
method.
Table 4
Parameter
Conversion formula Unit Parameter item
name
Voltage U = URMSx(x=a、b、c)×UrAt×0.1×0.1 V Ua,Ub,Uc,Uab,Ubc,Uca
current I = IRMSx(x=a、b、c) ×IrAt×0.001 A Ia,Ib,Ic
Active power P = Px(x=a、b、c)×UrAt×IrAt×0.1×0.1 W Pt,Pa,Pb,Pc
Reactive power Q = Qx(x=a、b、c)×UrAt×IrAt×0.1×0.1 var Pt,Qa,Qb,Qc
Power factor PF = PFx(x=a、b、c、t)×0.001 PFa,PFb,PFc,PFt
Frequency F = Freq×0.01 Hz F
kWh ImpEp,ExpEp,Q1Eq,
Energy Ep = E× UrAt×IrAt
kvarh Q2Eq,Q3Eq,Q4Eq
Data format: single precision floating decimal adopts standard IEEE754 format; there are total 32 bits of
IEEE single precision floating decimal format, contains three form fields: 23-bit decimal f, 8-bit biased
exponent e, 1-bit symbol s. Put these fields continuously in a 32-bit word and encoding. 0:22 bit contains
23-bit decimal f; 23:30 bit contains 8-bit index number e; the 31st contains the symbol s. As show in the
following:
a) the 31st bit is the sign bit, it’s the positive number when 1, otherwise it’s the complex number, the
reading value is denoted by s;
b)the 30th~23rd bit is the powerful number, the reading value is denoted by e;
Page 9/Total 10
Quick operation manual
c)the 22 ~0 bit total 23 bits is used as coefficient, regarded as binary number, the decimal system of the
nd
decimal is assumed to be x;
then according to specified, the decimal number of the floating number is denoted as: x = (-1)^s × (1
+ f)× 2^(e - 127).
Take A phase current Ia(200CH)as an example:
Read command frame: 01 03 20 0C 00 02 0F C8 (01 is the table address, 03 is the read command, 200C
is A phase current address, 0002 is the data length(floating data), 0FC8 is the check code of CRC16
Return frame: 01 03 04 45 9C 38 00 3C D1 (01 is the table address, 03 is the read command,04is the
returned data quantity of the read register,459C3800 is the floating data, DC70 is the check code of
CRC16)
Ia measurement = 0x459C3800 (floating number)* current ratio*0.001 =4999(decimal number) *
current ratio*0.001。
Take the current ratio Irat(0006H) as an example:
Write command frame: 01 10 00 06 00 01 02 00 0A 26 31 (01 is the table address, 10 is the read
command, 0006 is the current ratio address, 0001 is the number of the registers, 02 is the data quantity of
the read register, 000A is the current ratio data, 26 31 is the check code of CRC16).
Return frame: 01 10 00 06 00 01 E1 C8 (01 is the table address, 10 is the read command,0006isthe
current ratio address, 0001 is the quantity of the registers, E1 C8 is the check code of CRC16).
Page 10/Total 10