FC102
FC102
Design Guide
VLT HVAC Drive
Contents
2.11 Earth Leakage Current 2.12 Brake Function 2.13 Extreme Running Conditions
4 How to Order
4.1 Ordering Form 4.2 Ordering Numbers
5 How to Install
5.1 Mechanical Installation
5.1.2 Mechanical Dimensions 5.1.5 Lifting
Contents
88 89 94 103 105 109 111 111 115 115 115 116 116 116 116 117 118 119 119 120 120 121 121 122 122 123 124 124 128 129 130 134 134 137 141 141 165 169
5.3 Final Set-Up and Test 5.4 Additional Connections 5.5 Installation of Misc. Connections 5.6 Safety 5.7 EMC-correct Installation
6 Application Examples
6.1.1 Start/Stop 6.1.2 Pulse Start/Stop 6.1.3 Potentiometer Reference 6.1.4 Automatic Motor Adaptation (AMA) 6.1.5 Smart Logic Control 6.1.6 Smart Logic Control Programming 6.1.7 SLC Application Example 6.1.8 BASIC Cascade Controller 6.1.9 Pump Staging with Lead Pump Alternation 6.1.10 System Status and Operation 6.1.11 Fixed Variable Speed Pump Wiring Diagram 6.1.12 Lead Pump Alternation Wiring Diagram 6.1.13 Cascade Controller Wiring Diagram 6.1.14 Start/Stop Conditions
Contents
8.4 Acoustic Noise 8.5 Peak Voltage on Motor 8.6 Special Conditions
8.7.1 Alarm Words 8.7.2 Warning Words 8.7.3 Extended Status Words 8.7.4 Fault Messages
Index
1 1
This guide can be used with all VLT HVAC Drive frequency converters with software version 3.5.x. The actual software version number can be read from 15-43 Software Version.
1.1.1 Copyright, Limitation of Liability and Revision Rights
This publication contains information proprietary to Danfoss. By accepting and using this manual the user agrees that the information contained herein will be used solely for operating equipment from Danfoss or equipment from other vendors provided that such equipment is intended for communication with Danfoss equipment over a serial communication link. This publication is protected under the Copyright laws of Denmark and most other countries. Danfoss does not warrant that a software program produced according to the guidelines provided in this manual will function properly in every physical, hardware or software environment. Although Danfoss has tested and reviewed the documentation within this manual, Danfoss makes no warranty or representation, neither expressed nor implied, with respect to this documentation, including its quality, performance, or fitness for a particular purpose. In no event shall Danfoss be liable for direct, indirect, special, incidental, or consequential damages arising out of the use, or the inability to use information contained in this manual, even if advised of the possibility of such damages. In particular, Danfoss is not responsible for any costs, including but not limited to those incurred as a result of lost profits or revenue, loss or damage of equipment, loss of computer programs, loss of data, the costs to substitute these, or any claims by third parties.
1.1.3 Approvals
1 1
1.1.4 Symbols
Symbols used in this guide.
NOTE
Indicates something to be noted by the reader.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury or equipment damage.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
* Indicates default setting
x = Revision number yy = Language code Danfoss technical literature is available in print from your local Danfoss Sales Office or online at: www.danfoss.com/BusinessAreas/DrivesSolutions/Documentations/Technical+Documentation.htm
1 1
1.1.5 Abbreviations
Alternating current American wire gauge Ampere/AMP Automatic Motor Adaptation Current limit Degrees Celsius Direct current Drive Dependent Electro Magnetic Compatibility Electronic Thermal Relay frequency converter Gram Hertz Horsepower Kilohertz Local Control Panel Meter Millihenry Inductance Milliampere Millisecond Minute Motion Control Tool Nanofarad Newton Meters Nominal motor current Nominal motor frequency Nominal motor power Nominal motor voltage Parameter Protective Extra Low Voltage Printed Circuit Board Rated Inverter Output Current Revolutions Per Minute Regenerative terminals Second Synchronous Motor Speed Torque limit Volts The maximum output current The rated output current supplied by the frequency converter AC AWG A AMA ILIM C DC D-TYPE EMC ETR FC g Hz hp kHz LCP m mH mA ms min MCT nF Nm IM,N fM,N PM,N UM,N par. PELV PCB IINV RPM Regen sec. ns TLIM V IVLT,MAX IVLT,N
1.1.6 Definitions
Drive: IVLT,MAX The maximum output current. IVLT,N The rated output current supplied by the frequency converter. UVLT, MAX The maximum output voltage. Input:
Control command Start and stop the connected motor with the LCP or the digital inputs. Functions are divided into two groups. Functions in group 1 have higher priority than functions in group 2. Group Reset, Coasting stop, Reset 1 and Coasting stop, Quickstop, DC braking, Stop and the "Off" key. Group Start, Pulse start, Reversing, 2 Start reversing, Jog and Freeze output
PM,N The rated motor power (nameplate data). TM,N The rated torque (motor). UM The instantaneous motor voltage. UM,N The rated motor voltage (nameplate data). Break-away torque
Torque Pull-out 175ZA078.10
1 1
Motor: fJOG The motor frequency when the jog function is activated (via digital terminals). fM The motor frequency. fMAX The maximum motor frequency. fMIN The minimum motor frequency. fM,N The rated motor frequency (nameplate data). IM The motor current. IM,N The rated motor current (nameplate data). nM,N The rated motor speed (nameplate data).
rpm
VLT The efficiency of the frequency converter is defined as the ratio between the power output and the power input. Start-disable command A stop command belonging to the group 1 control commands - see this group. Stop command See Control commands. References: Analog Reference A signal transmitted to the analog inputs 53 or 54, can be voltage or current. Bus Reference A signal transmitted to the serial communication port (FC port).
1 1
Preset Reference A defined preset reference to be set from -100% to +100% of the reference range. Selection of eight preset references via the digital terminals. Pulse Reference A pulse frequency signal transmitted to the digital inputs (terminal 29 or 33). RefMAX Determines the relationship between the reference input at 100% full scale value (typically 10 V, 20mA) and the resulting reference. The maximum reference value set in 3-03 Maximum Reference. RefMIN Determines the relationship between the reference input at 0% value (typically 0V, 0mA, 4mA) and the resulting reference. The minimum reference value set in 3-02 Minimum Reference Miscellaneous: Analog Inputs The analog inputs are used for controlling various functions of the frequency converter. There are two types of analog inputs: Current input, 0-20 mA and 4-20 mA Voltage input, 0-10 V DC. Analog Outputs The analog outputs can supply a signal of 0-20 mA, 4-20 mA, or a digital signal. Automatic Motor Adaptation, AMA AMA algorithm determines the electrical parameters for the connected motor at standstill. Brake Resistor The brake resistor is a module capable of absorbing the brake power generated in regenerative braking. This regenerative braking power increases the intermediate circuit voltage and a brake chopper ensures that the power is transmitted to the brake resistor. CT Characteristics Constant torque characteristics used for screw and scroll refrigeration compressors. Digital Inputs The digital inputs can be used for controlling various functions of the frequency converter.
Digital Outputs The frequency converter features two Solid State outputs that can supply a 24 V DC (max. 40 mA) signal. DSP Digital Signal Processor. Relay Outputs: The frequency converter features two programmable Relay Outputs. ETR Electronic Thermal Relay is a thermal load calculation based on present load and time. Its purpose is to estimate the motor temperature. GLCP: Graphical Local Control Panel (LCP102) Initialising If initialising is carried out (14-22 Operation Mode), the programmable parameters of the frequency converter return to their default settings. Intermittent Duty Cycle An intermittent duty rating refers to a sequence of duty cycles. Each cycle consists of an on-load and an off-load period. The operation can be either periodic duty or noneperiodic duty. LCP The Local Control Panel (LCP)keypad makes up a complete interface for control and programming of the frequency converter. The control panelkeypad is detachable and can be installed up to 3 metres from the frequency converter, i.e. in a front panel by means of the installation kit option. The Local Control Panel is available in two versions: Numerical LCP101 (NLCP) Graphical LCP102 (GLCP)
lsb Least significant bit. MCM Short for Mille Circular Mil, an American measuring unit for cable cross-section. 1 MCM 0.5067 mm2. msb Most significant bit. NLCP Numerical Local Control Panel LCP101
On-line/Off-line Parameters Changes to on-line parameters are activated immediately after the data value is changed. Changes to off-line parameters are not activated until you enter [OK] on the LCP. PID Controller The PID controller maintains the desired speed, pressure, temperature, etc. by adjusting the output frequency to match the varying load. RCD Residual Current Device. Set-up You can save parameter settings in four Set-ups. Change between the four parameter Set-ups and edit one Set-up, while another Set-up is active. SFAVM Switching pattern called Stator Flux oriented Asynchronous V ector M odulation (14-00 Switching Pattern). Slip Compensation The frequency converter compensates for the motor slip by giving the frequency a supplement that follows the measured motor load keeping the motor speed almost constant. Smart Logic Control (SLC) The SLC is a sequence of user defined actions executed when the associated user defined events are evaluated as true by the SLC. Thermistor: A temperature-dependent resistor placed where the temperature is to be monitored (frequency converter or motor). Trip A state entered in fault situations, e.g. if the frequency converter is subject to an over-temperature or when the frequency converter is protecting the motor, process or mechanism. Restart is prevented until the cause of the fault has disappeared and the trip state is cancelled by activating reset or, in some cases, by being programmed to reset automatically. Trip may not be used for personal safety. Trip Locked A state entered in fault situations when the frequency converter is protecting itself and requiring physical intervention, e.g. if the frequency converter is subject to a short circuit on the output. A locked trip can only be cancelled by cutting off mains, removing the cause of the fault, and reconnecting the frequency converter. Restart is
prevented until the trip state is cancelled by activating reset or, in some cases, by being programmed to reset automatically. Trip locked may not be used for personal safety. VT Characteristics Variable torque characteristics used for pumps and fans. VVCplus If compared with standard voltage/frequency ratio control, Voltage Vector Control (VVCplus) improves the dynamics and the stability, both when the speed reference is changed and in relation to the load torque. 60 AVM Switching pattern called 60Asynchronous Vector Modulation (See 14-00 Switching Pattern).
1 1
I 1 cos 1 I RMS
The power factor indicates to which extent the frequency converter imposes a load on the mains supply. The lower the power factor, the higher the IRMS for the same kW performance.
2 2 2 2 I RMS = I 1 + I 5 + I 7 + . . + I n
In addition, a high power factor indicates that the different harmonic currents are low. The frequency converters' built-in DC coils produce a high power factor, which minimizes the imposed load on the mains supply.
2 2
2.1 Safety 2.1.1 Safety Note
CAUTION
WARNING
The voltage of the frequency converter is dangerous whenever connected to mains. Incorrect installation of the motor, frequency converter or fieldbus may cause death, serious personal injury or damage to the equipment. Consequently, the instructions in this manual, as well as national and local rules and safety regulations, must be complied with. Safety Regulations 1. The frequency converter must be disconnected from mains if repair work is to be carried out. Check that the mains supply has been disconnected and that the necessary time has passed before removing motor and mains plugs. 2. The [STOP/RESET] key on the LCP of the frequency converter does not disconnect the equipment from mains and is thus not to be used as a safety switch. Correct protective earthing of the equipment must be established, the user must be protected against supply voltage, and the motor must be protected against overload in accordance with applicable national and local regulations. The earth leakage currents are higher than 3.5 mA. Protection against motor overload is set by 1-90 Motor Thermal Protection. If this function is desired, set 1-90 Motor Thermal Protection to data value [ETR trip] (default value) or data value [ETR warning]. Note: The function is initialized at 1.16 x rated motor current and rated motor frequency. For the North American market: The ETR functions provide class 20 motor overload protection in accordance with NEC. Do not remove the plugs for the motor and mains supply while the frequency converter is connected to mains. Check that the mains supply has been disconnected and that the necessary time has passed before removing motor and mains plugs. Please note that the frequency converter has more voltage inputs than L1, L2 and L3, when load sharing (linking of DC intermediate circuit) and external 24 V DC have been installed. Check that all voltage inputs have been disconnected and that the necessary time has passed before commencing repair work.
380 - 500 V, enclosure A, B and C: At altitudes above 2 km, please contact Danfoss regarding PELV. 380 - 500 V, enclosure D, E and F: At altitudes above 3 km, please contact Danfoss regarding PELV. 525 - 690 V: At altitudes above 2 km, please contact Danfoss regarding PELV.
WARNING
Warning against Unintended Start 1. The motor can be brought to a stop by means of digital commands, bus commands, references or a local stop, while the frequency converter is connected to mains. If personal safety considerations make it necessary to ensure that no unintended start occurs, these stop functions are not sufficient. While parameters are being changed, the motor may start. Consequently, the stop key [STOP/RESET] must always be activated; following which data can be modified. A motor that has been stopped may start if faults occur in the electronics of the frequency converter, or if a temporary overload or a fault in the supply mains or the motor connection ceases.
2.
3.
3.
4. 5.
WARNING
Touching the electrical parts may be fatal - even after the equipment has been disconnected from mains. Also make sure that other voltage inputs have been disconnected, such as external 24 V DC, load sharing (linkage of DC intermediate circuit), as well as the motor connection for kinetic back up. Refer to the Operating Instructions for further safety guidelines.
6.
WARNING
The frequency converter DC link capacitors remain charged after power has been disconnected. To avoid an electrical shock hazard, disconnect the frequency converter from the mains before carrying out maintenance. Wait at least as follows before doing service on the frequency converter:
7.
10
Voltage (V) 200 240 380 480 525 600 525 690
Min. Waiting Time (Minutes) 4 1.1 - 3.7 kW 1.1 - 7.5 kW 1.1 - 7.5 kW 15 5.5 - 45 kW 11 - 90 kW 11 - 90 kW 11 - 90 kW 45 - 400 kW 450 1400 kW 110 - 250 kW 315 1000 kW 20 30 40
The EMC directive came into effect January 1, 1996. Danfoss CE-labels in accordance with the directive and issues a declaration of conformity upon request. To carry out EMCcorrect installation, see the instructions in this Design Guide. In addition, we specify which standards our products comply with. We offer the filters presented in the specifications and provide other types of assistance to ensure the optimum EMC result. The frequency converter is most often used by professionals of the trade as a complex component forming part of a larger appliance, system or installation. It must be noted that the responsibility for the final EMC properties of the appliance, system or installation rests with the installer.
2 2
Be aware that there may be high voltage on the DC link even when the LEDs are turned off.
2.
3.
11
2 2
CAUTION
The frequency converter should not be installed in environments with airborne liquids, particles, or gases capable of affecting and damaging the electronic components. Failure to take the necessary protective measures increases the risk of stoppages, thus reducing the life of the frequency converter. Liquids can be carried through the air and condense in the frequency converter and may cause corrosion of components and metal parts. Steam, oil, and salt water may cause corrosion of components and metal parts. In such environments, use equipment with enclosure rating IP 54/55. As an extra protection, coated printed circuit boards can be ordered as an option. Airborne Particles such as dust may cause mechanical, electrical, or thermal failure in the frequency converter. A typical indicator of excessive levels of airborne particles is dust particles around the frequency converter fan. In very dusty environments, use equipment with enclosure rating IP 54/55 or a cabinet for IP 00/IP 20/TYPE 1 equipment. In environments with high temperatures and humidity, corrosive gases such as sulphur, nitrogen, and chlorine compounds will cause chemical processes on the frequency converter components. Such chemical reactions will rapidly affect and damage the electronic components. In such environments, mount the equipment in a cabinet with fresh air ventilation, keeping aggressive gases away from the frequency converter. An extra protection in such areas is a coating of the printed circuit boards, which can be ordered as an option.
NOTE
Mounting frequency converters in aggressive environments increases the risk of stoppages and considerably reduces the life of the converter. Before installing the frequency converter, check the ambient air for liquids, particles, and gases. This is done by observing existing installations in this environment. Typical indicators of harmful airborne liquids are water or oil on metal parts, or corrosion of metal parts.
12
Excessive dust particle levels are often found on installation cabinets and existing electrical installations. One indicator of aggressive airborne gases is blackening of copper rails and cable ends on existing installations. D and E enclosures have a stainless steel back-channel option to provide additional protection in aggressive environments. Proper ventilation is still required for the internal components of the drive. Contact Danfoss for additional information.
It is designed and approved suitable for the requirements of Safety Category 3 in EN 954-1. This functionality is called Safe Stop. Prior to integration and use of Safe Stop in an installation, a thorough risk analysis on the installation must be carried out in order to determine whether the Safe Stop functionality and safety category are appropriate and sufficient.
2 2
WARNING
In order to install and use the Safe Stop function in accordance with the requirements of Safety Category 3 in EN 954-1, the related information and instructions of the relevant Design Guide must be followed! The information and instructions of the Operating Instructions are not sufficient for a correct and safe use of the Safe Stop functionality!
IEC/EN 60068-2-6: Vibration (sinusoidal) - 1970 IEC/EN 60068-2-64: Vibration, broad-band random
13
2 2
91 (L1) 92 (L2) 93 (L3) 95 PE 88 (-) 89 (+) 50 (+10 V OUT) S201 53 (A IN) 1 2 ON S202 1 2 ON 54 (A IN) ON=0-20mA OFF=0-10V Switch Mode Power Supply 24Vdc 15mA 200mA + + -
Motor
DC bus
Brake resistor
03 02 01 240Vac, 2A
55 (COM A IN) 12 (+24V OUT) 13 (+24V OUT) 18 (D IN) 19 (D IN) 20 (COM D IN) 27 (D IN/OUT) 24V 0V 29 (D IN/OUT) 24V 0V 32 (D IN) 33 (D IN) * 37 (D IN) 24V (NPN) 0V (PNP) 24V (NPN) 0V (PNP) 24V (NPN) 0V (PNP) S801 RS-485 Interface 24V (NPN) 0V (PNP) S801 1 2 ON P 5-00 24V (NPN) 0V (PNP) 24V (NPN) 0V (PNP) relay2
06 05 04
240Vac, 2A 400Vac, 2A
ON=Terminated OFF=Open
5V
Illustration 2.1 Diagram showing all electrical terminals. (Terminal 37 present for units with Safe Stop Function only.)
14
130BA544.11
2 2
15
2 2
To carry out an installation of a Category 0 Stop (EN60204) in conformity with Safety Category 3 (EN954-1), follow these instructions: 1. The bridge (jumper) between Terminal 37 and 24V DC must be removed. Cutting or breaking the jumper is not sufficient. Remove it entirely to avoid short-circuiting. See jumper on Illustration 2.2. 2. Connect terminal 37 to 24V DC by a short-circuit protected cable. The 24V DC voltage supply must be interruptible by an EN954-1 Category 3 circuit interrupt device. If the interrupt device and the frequency converter are placed in the same installation panel, you can use an unscreened cable instead of a screened one.
12
37
Illustration 2.3 shows a Stopping Category 0 (EN 60204-1) with safety Category 3 (EN 954-1). The circuit interrupt is caused by an opening door contact. The illustration also shows how to connect a non-safety related hardware coast.
16
130BT314.10
6 phase Coast
Mains
130BB566.10
Door contact
2 2
Safety device Cat.3 (Circuit interrupt device, possibly with release input) 12 37 Safe channel Recti er Control board Frequency Converter
R1
R2
5Vdc
Inverter
Illustration 2.3 Essential aspects of an installation to achieve a Stopping Category 0 (EN 60204-1) with safety Category 3 (EN 954-1).
2.7 Advantages
120
A 100 SYSTEM CURVE 130BA780.10 180
2.7.1 Why use a Frequency Converter for Controlling Fans and Pumps?
A frequency converter takes advantage of the fact that centrifugal fans and pumps follow the laws of proportionality for such fans and pumps. For further information see the text and figure The Laws of Proportionality.
PRESSURE%
80 60 40 20 B FAN CURVE
20
40
60
140
160
Illustration 2.4 The graph is showing fan curves (A, B and C) for reduced fan volumes.
17
130BA781.10
100% 80%
2 2
50%
25%
20
40
60
80 100 Voume %
120
140
160
180
12,5%
Power ~n3
50%
80% 100%
120 100 INPUT POWER % 80 60 40 20 ENERGY CONSUMED 20 40 60 80 100 Voume % 120 140 160 180
Q1 n1 = Q2 n2 H1 n1 2 Pressure : = H2 n2 P1 n1 3 Power : = P2 n2 Flow :
( ) ( )
Illustration 2.5 When using a frequency converter to reduce fan capacity to 60% - more than 50% energy savings may be obtained in typical applications.
18
175HA208.10 n
2 2
Discharge damper
Costlier installation
100
Input power %
Energy consumed
60
40
Energy consumed
20
60
60
Energy consumed
60
Volume %
Illustration 2.7 Discharge dampers reduce power consumption somewhat. Inlet Guide Vans offer a 40% reduction but are expensive to install. The Danfoss frequency converter solution reduces energy consumption with more than 50% and is easy to install.
130BA779.11
19
2 2
Hours Power A1 - B1
5 15 20 20 20 20
100 8760
(mwg) 60 50 40 30
1650rpm
175HA209.11
Hs
(m3 /h)
(kW) 60 50
Pshaft
A1
40 30 20 10
Generally speaking, the VLT HVAC Drive has a cos of 1 and provides power factor correction for the cos of the motor, which means that there is no need to make allowance for the cos of the motor when sizing the power factor correction unit.
1650rpm
B1
1050rpm 750rpm 200
1350rpm
C1
0 100
300
20
700 600 4 % Full load current 500 400 300 200 100 0 3
175HA227.10
800
+ Flow
Fan M
V.A.V outlets
x3
M VLT
Pump x3
M VLT
Duct
Local D.D.C. control
Main B.M.S
Illustration 2.8 The illustration shows a fan system controlled by frequency converters.
V.A.V. Sensor P
Cooling section
= =
Sensor T = Temperature
Inlet guide vane Fan section Supply air V.A.V Sensors PT outlets 175HA205.12
Fan M
Return
M x6 Starter
Pump
M x6 Starter
Pump
Duct
Starter
Main B.M.S
175HA206.11
Cooling section
Heating section
Fan section
2 2
21
2 2
22
2 2
Cooling coil
Frequency converter
D1
Pressure transmitter
Return fan 3
Flow
D3
23
2 2
Cooling coil
Frequency converter
Temperature signal
Supply fan D1
D2 Frequency converter
Pressure signal
Return fan
D3
24
2 2
25
2 2
Frequency converter
Water Inlet
Temperature Sensor
BASIN
Water Outlet
Supply
26
130BB453.10
2 2
27
2 2
28
Flowmeter F
Flowmeter F
130BB456.10
2 2
CHILLER
Frequency converter
Frequency converter
CHILLER
29
2 2
P Frequency converter 3
CHILLER
CHILLER
Frequency converter
30
2 2
P 14-50
LC Filter (5A)
The frequency converter is a high performance unit for demanding applications. It can handle various kinds of motor control principles such as U/f special motor mode and VVCPLUS and can handle normal squirrel cage asynchronous motors. Short circuit behavior on this frequency converter depends on the 3 current transducers in the motor phases. In 1-00 Configuration Mode it can be selected if open or closed loop is to be used
Reference handling Remote reference Auto mode Hand mode Local reference scaled to RPM or Hz LCP Hand on, o and auto on keys P 3-13 Reference site
100%
0%
In the configuration shown in Illustration 2.10, 1-00 Configuration Mode is set to Open loop [0]. The resulting reference from the reference handling system or the local reference is received and fed through the ramp limitation and speed limitation before being sent to the motor control. The output from the motor control is then limited by the maximum frequency limit.
31
2 2
Hand on
Auto on
Reset
Hand Off Auto LCP Keys Hand Hand -> Off Auto Auto -> Off All keys All keys
Reference Site 3-13 Reference Site Linked to Hand / Auto Linked to Hand / Auto Linked to Hand / Auto Linked to Hand / Auto Local Remote
Active Reference
The table shows under which conditions either the Local Reference or the Remote Reference is active. One of them is always active, but both can not be active at the same time. Local reference will force the configuration mode to open loop, independent on the setting of 1-00 Configuration Mode. Local Reference will be restored at power-down.
32
2 2
100% Ref. Handling (Illustration) + _ *[-1] PID 100% -100% 0% Scale to speed To motor control
While the default values for the frequency converters Closed Loop controller will often provide satisfactory performance, the control of the system can often be optimized by adjusting some of the Closed Loop controllers parameters. It is also possible to autotune the PI constants.
33
2 2
Feedback Feedback 1 Source P 20-00 Feedback 2 Source P 20-03 Feedback 3 Source P 20-06 Feedback conv. P 20-01 Feedback conv. P 20-04 Feedback conv. P 20-07 Feedback 1 Feedback 1 only Feedback 2 only Feedback 3 only Sum (1+2+3) Di erence (1-2) Average (1+2+3) Minimum (1|2|3) Maximum (1|2|3)
Feedback 2
0%
Feedback 3
Feedback handling can be configured to work with applications requiring advanced control, such as multiple setpoints and multiple feedbacks. Three types of control are common. Single Zone, Single Setpoint Single Zone Single Setpoint is a basic configuration. Setpoint 1 is added to any other reference (if any, see Reference Handling) and the feedback signal is selected using 20-20 Feedback Function. Multi Zone, Single Setpoint Multi Zone Single Setpoint uses two or three feedback sensors but only one setpoint. The feedbacks can be added, subtracted (only feedback 1 and 2) or averaged. In addition, the maximum or minimum value may be used. Setpoint 1 is used exclusively in this configuration. If Multi Setpoint Min [13] is selected, the setpoint/feedback pair with the largest difference controls the speed of the drive. Multi Setpoint Maximum [14] attempts to keep all zones at or below their respective setpoints, while Multi Setpoint Min [13] attempts to keep all zones at or above their respective setpoints. Example: A two zone two setpoint application Zone 1 setpoint is 15 bar and the feedback is 5.5 bar. Zone 2 setpoint is 4.4 bar and the feedback is 4.6 bar. If Multi Setpoint Max [14] is selected, Zone 1s setpoint and feedback are sent to the PID controller, since this has the smaller difference (feedback is higher than setpoint, resulting in a negative difference). If Multi Setpoint Min [13] is selected, Zone 2s setpoint and feedback is sent to the PID controller, since this has the larger difference (feedback is lower than setpoint, resulting in a positive difference).
34
2 2
Ref.+ -
FB conversion
FB signal P
130BA358.11
35
2 2
P 3-14 Preset relative ref. Input command: Preset ref. bit0, bit1, bit2 [0] [1] [2] [3] P 3-10 Preset ref. [4] [5] [6] [7] P 3-04 Ref. function Y No function Analog inputs P 3-15 Ref. 1 source Frequency inputs Ext. closed loop outputs DigiPot on 200% o Input command: Ref. Preset 100%
Freeze ref. & increase/ decrease ref. Scale to Closed loop unit Relative X+X*Y /100
Remote ref.
Closed loop
Input command: Speed up/ speed down No function Analog inputs P 3-16 Ref. 2 source Frequency inputs Ext. closed loop outputs DigiPot External reference in % No function Analog inputs P 3-17 Ref. 3 source Frequency inputs Ext. closed loop outputs DigiPot Setpoint Closed loop 200% 0% Open loop P 1-00 Con guration mode Increase 0/1 Decrease 0/1 Clear 0/1 DigiPot Digipot ref. 200% Ref. in %
Bus reference
36
Preset references. External references (analog inputs, pulse frequency inputs, digital potentiometer inputs and serial communication bus references). The Preset relative reference. Feedback controlled setpoint.
In a ventilation system, the temperature is to be maintained at a constant value. The desired temperature is set between -5 and +35C using a 0-10V potentiometer. Because this is a cooling application, if the temperature is above the set-point value, the speed of the fan must be increased to provide more cooling air flow. The temperature sensor has a range of -10 to +40C and uses a two-wire transmitter to provide a 4-20mA signal. The output frequency range of the frequency converter is 10 to 50Hz. 1. 2. Start/Stop via switch connected between terminals 12 (+24V) and 18. Temperature reference via a potentiometer (-5 to +35C, 0 10V) connected to terminals 50 (+10V), 53 (input) and 55 (common). Temperature feedback via transmitter (-10-40C, 4-20mA) connected to terminal 54. Switch S202 behind the LCP set to ON (current input).
130BA175.11
2 2
Up to 8 preset references can be programmed in the drive. The active preset reference can be selected using digital inputs or the serial communications bus. The reference can also be supplied externally, most commonly from an analog input. This external source is selected by one of the 3 Reference Source parameters (3-15 Reference 1 Source, 3-16 Reference 2 Source and 3-17 Reference 3 Source). Digipot is a digital potentiometer. This is also commonly called a Speed Up/Speed Down Control or a Floating Point Control. To set it up, one digital input is programmed to increase the reference while another digital input is programmed to decrease the reference. A third digital input can be used to reset the Digipot reference. All reference resources and the bus reference are added to produce the total External Reference. The External Reference, the Preset Reference or the sum of the two can be selected to be the active reference. Finally, this reference can by be scaled using 3-14 Preset Relative Reference. The scaled reference is calculated as follows:
Reference = X + X
3.
L1 L2 L3 N PE F1
91 92 93 95
Y ( 100 )
12 37
L1 L2 L3 PE
Where X is the external reference, the preset reference or the sum of these and Y is 3-14 Preset Relative Reference in [%]. If Y, 3-14 Preset Relative Reference is set to 0%, the reference will not be affected by the scaling.
18 50 53 55 54 Transmitter
V W PE
96 97 98 99
M 3
Temperature transmitter
Heat
37
2 2
3) Make sure the frequency converter limits are set to safe values Check that the ramp settings are within capabilities of the 3-41 drive and allowed application operating specifications. 3-42
Prohibit the motor from reversing (if necessary) Set acceptable limits for the motor speed.
Switch from open loop to closed loop. 4) Configure the feedback to the PID controller. Select the appropriate reference/feedback unit. 5) Configure the set-point reference for the PID controller. Set acceptable limits for the set-point reference. Choose current or voltage by switches S201 / S202
6) Scale the analog inputs used for set-point reference and feedback. Scale Analog Input 53 for the pressure range of the potentiometer (0 - 10 Bar, 0 - 10 V). 6-10 6-11 6-14 6-15 0V 10 V (default) 0 Bar 10 Bar 4 mA 20 mA (default) 0 Bar 10 Bar See Optimization of the PID Controller, below.
Scale Analog Input 54 for pressure sensor (0 - 10 Bar, 4 - 20 6-22 mA) 6-23 6-24 6-25 7) Tune the PID controller parameters. Adjust the drives Closed Loop Controller, if needed. 8) Finished! Save the parameter setting to the LCP for safe keeping 0-50 20-93 20-94
38
2 2
3.
4.
z z z z PE
L1 L2 L3 PE
CS
CS
CS
CS
Earth Plane
39
2 2
If the screen is to be placed on a mounting plate for the frequency converter, the mounting plate must be made of metal, because the screen currents have to be conveyed back to the unit. Moreover, ensure good electrical contact from the mounting plate through the mounting screws to the frequency converter chassis. When unscreened cables are used, some emission requirements are not complied with, although the immunity requirements are observed. In order to reduce the interference level from the entire system (unit + installation), make motor and brake cables as short as possible. Avoid placing cables with a sensitive signal level alongside motor and brake cables. Radio interference higher than 50MHz (airborne) is especially generated by the control electronics. Please see for more information on EMC.
Category C1 C2
Definition Frequency converters installed in the first environment (home and office) with a supply voltage less than 1000V. Frequency converters installed in the first environment (home and office) with a supply voltage less than 1000V, which are neither plug-in nor movable and are intended to be installed and commissioned by a professional. Frequency converters installed in the second environment (industrial) with a supply voltage lower than 1000V. Frequency converters installed in the second environment with a supply voltage equal to or above 1000 V or rated current equal to or above 400A or intended for use in complex systems.
C3 C4
When the generic emission standards are used the frequency converters are required to comply with the following limits
Environment First environment (home and office) Second environment (industrial environment) Generic standard EN/IEC 61000-6-3 Emission standard for residential, commercial and light industrial environments. EN/IEC 61000-6-4 Emission standard for industrial environments. Conducted emission requirement according to the limits given in EN 55011 Class B Class A Group 1
40
2 2
Standard H1 1.1-45kW 200-240V 1.1-9 kW 380-480V H2 1.1-3.7kW 200-240V 5.5-45kW 200-240V 1.1-7.5kW 380-480V 11-90kW 380-480V 110-1000kW 380-480V 11-90kW 525-690V 45-1400kW 525-690V H3 1.1-45kW 200-240V 1.1-90kW 380-480V H4 110-1000kW 380-480V 45-400kW 525-690V 11-90kW 525-690V Hx 1.1-90 kW 525-600 V T6 T4 T7 T7 T2 T4 T2 T2 T4 T4 T4 T7 T7 T2 T4
EN 55011 Class EN 55011 Class A1 B 50 m 50 m No No No No No No No 10 m 10 m No No No Yes Yes No No No No No No No Yes Yes Yes No Yes -
No No No No No No No No No No No No No No -
HX, H1, H2 or H3 is defined in the type code pos. 16 - 17 for EMC filters HX - No EMC filters built in the frequency converter (600V units only) H1 - Integrated EMC filter. Fulfil Class A1/B H2 - No additional EMC filter. Fulfil Class A2 H3 - Integrated EMC filter. Fulfil class A1/B (Frame size A1 only) H4 - Integrated EMC filter. Fulfil class A1
Harmonic currents Hz
I1 50Hz
I5 250Hz
I7 350Hz
The harmonics do not affect the power consumption directly but increase the heat losses in the installation (transformer, cables). Consequently, in plants with a high percentage of rectifier load, maintain harmonic currents at a low level to avoid overload of the transformer and high temperature in the cables.
175HA034.10
41
NOTE
Some of the harmonic currents might disturb communication equipment connected to the same transformer or cause resonance in connection with power-factor correction batteries. To ensure low harmonic currents, the frequency converter is equipped with intermediate circuit coils as standard. This normally reduces the input current I RMS by 40%. The voltage distortion on the mains supply voltage depends on the size of the harmonic currents multiplied by the mains impedance for the frequency in question. The total voltage distortion THD is calculated on the basis of the individual voltage harmonics using this formula:
THD % = U
2 2 2 + U + ... + U 5 7 N
Provided that the short-circuit power of the supply Ssc is greater than or equal to:
SSC = 3 RSCE U mains I equ =
3 120 400 I equ
2 2
at the interface point between the users supply and the public system (Rsce). It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power Ssc greater than or equal to specified above. Other power sizes can be connected to the public supply network by consultation with the distribution network operator. Compliance with various system level guidelines: The harmonic current data in the table are given in accordance with IEC/EN61000-3-12 with reference to the Power Drive Systems product standard. They may be used as the basis for calculation of the harmonic currents' influence on the power supply system and for the documentation of compliance with relevant regional guidelines: IEEE 519 -1992; G5/4.
(UN% of U)
Harmonic current distortion factor (%) THD Actual (typical) Limit for Rsce120 46 48 PWHD 45 46
EN 61000-4-2 (IEC 61000-4-2): Electrostatic discharges (ESD): Simulation of electrostatic discharges from human beings. EN 61000-4-3 (IEC 61000-4-3): Incoming electromagnetic field radiation, amplitude modulated simulation of the effects of radar and radio communication equipment as well as mobile communications equipment.
42
EN 61000-4-4 (IEC 61000-4-4): Burst transients: Simulation of interference brought about by switching a contactor, relay or similar devices. EN 61000-4-5 (IEC 61000-4-5): Surge transients: Simulation of transients brought about e.g. by lightning that strikes near installations.
Burst IEC 61000-4-4 B 4 kV CM 4 kV CM 4 kV CM 4 kV CM 2 kV CM 2 kV CM 2 kV CM 2 kV CM 2 kV CM 2 kV CM Surge IEC 61000-4-5 B 2 kV/2 DM 4 kV/12 CM 4 kV/2 1) 4 kV/2 2 kV/2 2 kV/2 1) 1) 1) 4 kV/2 1)
EN 61000-4-6 (IEC 61000-4-6): RF Common mode: Simulation of the effect from radio-transmission equipment joined by connection cables.
2 2
Voltage range: 200-240V, 380-480V Basic standard ESD IEC 61000-4-2 B 8 kV AD 6 kV CD Radiated electromagnetic field IEC 61000-4-3 A 10 V/m RF common mode voltage IEC 61000-4-6 A 10VRMS 10VRMS 10VRMS 10VRMS 10VRMS 10VRMS 10VRMS 10VRMS 10VRMS 10VRMS
Acceptance criterion Line Motor Brake Load sharing Control wires Standard bus Relay wires Application and Fieldbus options LCP cable External 24 V DC Enclosure
1) Injection on cable shield AD: Air Discharge CD: Contact Discharge CM: Common mode DM: Differential mode
The components that make up the electrical isolation, as described below, also comply with the requirements for higher isolation and the relevant test as described in EN 61800-5-1. The PELV galvanic isolation can be shown in six locations (see Illustration 2.14): In order to maintain PELV all connections made to the control terminals must be PELV, e.g. thermistor must be reinforced/double insulated. 1. 2. 3. 4. 5. 6. Power supply (SMPS) incl. signal isolation of UDC, indicating the intermediate current voltage. Gate drive that runs the IGBTs (trigger transformers/opto-couplers). Current transducers. Opto-coupler, brake module. Internal inrush, RFI, and temperature measurement circuits. Custom relays.
2.10 Galvanic isolation (PELV) 2.10.1 PELV - Protective Extra Low Voltage
PELV offers protection by way of extra low voltage. Protection against electric shock is ensured when the electrical supply is of the PELV type and the installation is made as described in local/national regulations on PELV supplies. All control terminals and relay terminals 01-03/04-06 comply with PELV (Protective Extra Low Voltage) (Does not apply to grounded Delta leg above 400V). Galvanic (ensured) isolation is obtained by fulfilling requirements for higher isolation and by providing the relevant creapage/clearance distances. These requirements are described in the EN 61800-5-1 standard.
43
130BA056.10
2 2
6 5 4 1 2
current is influenced by the cable length and power size. Pa > Pb.
The functional galvanic isolation (a and b on drawing) is for the 24V back-up option and for the RS-485 standard bus interface.
THVD=0% THVD=5%
WARNING
Installation at high altitude: 380 - 500V, enclosure A, B and C: At altitudes above 2km, please contact Danfoss regarding PELV. 380 - 500V, enclosure D, E and F: At altitudes above 3km, please contact Danfoss regarding PELV. 525 - 690 V: At altitudes above 2km, please contact Danfoss regarding PELV.
Illustration 2.16 Principle drawing showing how the leakage current is influenced by line distortion.
WARNING
Touching the electrical parts could be fatal - even after the equipment has been disconnected from mains. Also make sure that other voltage inputs have been disconnected, such as load sharing (linkage of DC intermediate circuit), as well as the motor connection for kinetic back-up. Before touching any electrical parts, wait at least the amount of time indicated in the Safety Precautions section. Shorter time is allowed only if indicated on the nameplate for the specific unit.
NOTE
When a filter is used, turn off 14-50 RFI Filter when charging the filter, to avoid that a high leakage current makes the RCD switch. EN/IEC61800-5-1 (Power Drive System Product Standard) requires special care if the leakage current exceeds 3,5mA. Earth grounding must be reinforced in one of the following ways:
Earth ground wire (terminal 95) of at least 10mm2 Two separate earth ground wires both complying with the dimensioning rules
See EN/IEC61800-5-1 and EN50178 for further information. Using RCDs Where residual current devices (RCDs), also known as earth leakage circuit breakers (ELCBs), are used, comply with the following: Use RCDs of type B only which are capable of detecting AC and DC currents Use RCDs with an inrush delay to prevent faults due to transient earth currents Dimension RCDs according to the system configuration and environmental considerations
44
130BB955.10
Lleakage[mA]
130BB958.10
If the amount of kinetic energy transferred to the resistor in each braking period is not known, the average power can be calculated on the basis of the cycle time and braking time also called intermitted duty cycle. The resistor intermittent duty cycle is an indication of the duty cycle at which the resistor is active. The below figure shows a typical braking cycle. The intermittent duty cycle for the resistor is calculated as follows: Duty Cycle = tb / T T = cycle time in seconds tb is the braking time in seconds (as part of the total cycle time)
Load 130BA167.10
2 2
Illustration 2.18 Principle Drawing Showing how the Cut-off Frequency of the RCD will Influence what is Responded to/ Measured.
130BB957.10
Speed
ta
tc
tb
to
ta
tc
tb
to
ta
WARNING
Residual Current Device This product can cause a d.c. current in the protective conductor. Where a residual current device (RCD) is used for protection in case of direct or indirect contact, only an RCD of Type B is allowed on the supply side of this product. Otherwise, another protective measure shall be applied, such as separation from the environment by double or reinforced insulation, or isolation from the supply system by a transformer. See also Application Note Protection against Electrical Hazards MN.90.G2.02. Protective earthing of the frequency converter and the use of RCD's must always follow national and local regulations.
Time
Danfoss offers brake resistors with duty cycle of 5%, 10% and 40% suitable for use with the VLT HVAC Drive frequency converter series. If a 10% duty cycle resistor is applied, this is able of absorbing braking power upto 10% of the cycle time with the remaining 90% being used to dissipate heat from the resistor. For further selection advice, please contact Danfoss.
As can be seen, the brake resistance depends on the intermediate circuit voltage (UDC). The brake function of the frequency converter is settled in 3 areas of mains power supply:
45
Size
Brake active
2 2
NOTE
Check that the brake resistor can cope with a voltage of 410V, 820V or 975V - unless Danfoss brake resistors are used. Danfoss recommends the brake resistance Rrec, i.e. one that guarantees that the frequency converter is able to brake at the highest braking torque (Mbr(%)) of 110%. The formula can be written as:
2 U dc x 100 Rrec = Pmotor x M br (%) x x motor
NOTE
Monitoring the brake power is not a safety function; a thermal switch is required for that purpose. The brake resistor circuit is not earth leakage protected. Over voltage control (OVC) (exclusive brake resistor) can be selected as an alternative brake function in 2-17 Over-voltage Control. This function is active for all units. The function ensures that a trip can be avoided if the DC link voltage increases. This is done by increasing the output frequency to limit the voltage from the DC link. It is a very useful function, e.g. if the ramp-down time is too short since tripping of the frequency converter is avoided. In this situation the rampdown time is extended.
motor is typically at 0.90 is typically at 0.98 For 200V, 480V and 600V frequency converters, Rrec at 160% braking torque is written as:
200V : Rrec = Pmotor 375300 480V : Rrec = 1) Pmotor 2) Pmotor 630137 600V : Rrec = Pmotor 480V : Rrec = 690V : Rrec = 832664 428914 107780
Pmotor
1) For frequency converters 7.5kW shaft output 2) For frequency converters > 7.5kW shaft output
NOTE
The resistor brake circuit resistance selected should not be higher than that recommended by Danfoss. If a brake resistor with a higher ohmic value is selected, the braking torque may not be achieved because there is a risk that the frequency converter cuts out for safety reasons.
NOTE
If a short circuit in the brake transistor occurs, power dissipation in the brake resistor is only prevented by using a mains switch or contactor to disconnect the mains for the frequency converter. (The contactor can be controlled by the frequency converter).
WARNING
Do not touch the brake resistor as it can get very hot while/ after braking.
46
Switching on the Output Switching on the output between the motor and the frequency converter is fully permitted. You cannot damage the frequency converter in any way by switching on the output. However, fault messages may appear. Motor-generated Over-voltage The voltage in the intermediate circuit is increased when the motor acts as a generator. This occurs in following cases: 1. The load drives the motor (at constant output frequency from the frequency converter), ie. the load generates energy. During deceleration ("ramp-down") if the moment of inertia is high, the friction is low and the rampdown time is too short for the energy to be dissipated as a loss in the frequency converter, the motor and the installation. Incorrect slip compensation setting may cause higher DC link voltage.
175ZA052.12
t [s]
2 2
IM IM,N(par. 1-24)
Illustration 2.19 The X-axis is showing the ratio between Imotor and Imotor nominal. The Y-axis is showing the time in seconds before the ETR cuts off and trips the frequency converter. The curves are showing the characteristic nominal speed at twice the nominal speed and at 0,2x the nominal speed.
2.
3.
The control unit may attempt to correct the ramp if possible (2-17 Over-voltage Control. The inverter turns off to protect the transistors and the intermediate circuit capacitors when a certain voltage level is reached. See 2-10 Brake Function and 2-17 Over-voltage Control to select the method used for controlling the intermediate circuit voltage level. Mains Drop-out During a mains drop-out, the frequency converter keeps running until the intermediate circuit voltage drops below the minimum stop level, which is typically 15% below the frequency converter's lowest rated supply voltage. The mains voltage before the drop-out and the motor load determines how long it takes for the inverter to coast. Static Overload in VVCplus mode When the frequency converter is overloaded (the torque limit in 4-16 Torque Limit Motor Mode/4-17 Torque Limit Generator Mode is reached), the controls reduces the output frequency to reduce the load. If the overload is excessive, a current may occur that makes the frequency converter cut out after approx. 5-10 sec. Operation within the torque limit is limited in time (0-60 sec) in 14-25 Trip Delay at Torque Limit.
It is clear that at lower speed the ETR cuts of at lower heat due to less cooling of the motor. In that way the motor are protected from being over heated even at low speed. The ETR feature is calculating the motor temperature based on actual current and speed. The calculated temperature is visible as a read out parameter in 16-18 Motor Thermal in the frequency converter. The thermistor cut-out value is > 3k. Integrate a thermistor (PTC sensor) in the motor for winding protection. Motor protection can be implemented using a range of techniques: PTC sensor in motor windings; mechanical thermal switch (Klixon type); or Electronic Thermal Relay (ETR).
R () 175HA183.10 [C] -20C nominel -5C nominel nominel +5C
550
250
47
2 2
Using a digital input and 24V as power supply: Example: The frequency converter trips when the motor temperature is too high. Parameter set-up: Set 1-90 Motor Thermal Protection to Thermistor Trip [2] Set 1-93 Thermistor Source to Digital Input 33 [6]
130BA151.11 +24V GND
Supply Voltage Threshold VCut-out Values Cut-out Values 24 10 10 < 6.6k - > 10.8k < 800 - > 2.7k < 3.0k - > 3.0k
NOTE
Check that the chosen supply voltage follows the specification of the used thermistor element. Summary With the Torque limit feature the motor is protected for being overloaded independent of the speed. With the ETR the motor is protected for being over heated and there is no need for any further motor protection. That means when the motor is heated up the ETR timer controls for how long time the motor can be running at the high temperature before it is stopped in order to prevent over heating. If the motor is overloaded without reaching the temperature where the ETR shuts of the motor, the torque limit is protecting the motor and application for being overloaded. ETR is activated in 1-90 Motor Thermal Protection and is controlled in 4-16 Torque Limit Motor Mode. The time before the torque limit warning trips the frequency converter is set in 14-25 Trip Delay at Torque Limit.
12 13 18 19 27 29 32 33 20 37
OFF
A B
PTC / Thermistor
ON <6.6 k >10.8 k R
Using a digital input and 10V as power supply: Example: The frequency converter trips when the motor temperature is too high. Parameter set-up: Set 1-90 Motor Thermal Protection to Thermistor Trip [2] Set 1-93 Thermistor Source to Digital Input 33 [6]
+10V 130BA152.10 OFF
12 13 18 19 27 29 32 33 20 37
39 42 50 53 54 55
Using an analog input and 10V as power supply: Example: The frequency converter trips when the motor temperature is too high. Parameter set-up: Set 1-90 Motor Thermal Protection to Thermistor Trip [2] Set 1-93 Thermistor Source to Analog Input 54 [2] Do not select a reference source.
+10V 130BA153.11 >3.0 k R
39 42 50 53 54 55
OFF
48
3 3
A kV .1 11 A A F
S
D IA L TE STR UA S LIS DU AN ION IN E M AT IC SE PL AP
Remove the LCP (Local Control Panel), the terminal cover, and the LCP frame from the frequency converter. Fit the MCB1xx option card into slot B. Connect the control cables and relieve the cable by the enclosed cable strips. Remove the knock out in the extended LCP frame delivered in the option set, so that the option will fit under the extended LCP frame. Fit the extended LCP frame and terminal cover. Fit the LCP or blind cover in the extended LCP frame. Connect power to the frequency converter. Set up the input/output functions in the corresponding parameters, as mentioned in the section General Technical Data.
D
LCP Frame
LCP Cradle
DC-
DC+
61 6 39 42 50
Remove
53 5
jumper
to activate
Safe Stop
12 13 18 19 27 28 32 38 2
Illustration 3.2 A5, B1, B2, B4, C1, C2, C3 and C4 Enclosures
Remove the LCP and the LCP cradle Fit the MCB 1xx option card into slot B Connect the control cables and relieve the cable by the enclosed cable strips Fit the cradle Fit the LCP
130BA708.10
49
MCB 101 General Purpose I/O SW. ver. XX.XX GND(1) DOUT3 DOUT4 COM DIN DIN7 DIN8 DIN9
130BA208.10
FC Series
AIN3 11
3 3
X30/
10
AIN4 12
24V
Galvanic isolation in the MCB 101 Digital/analog inputs are galvanically isolated from other inputs/outputs on the MCB 101 and in the control card of the frequency converter. Digital/analog outputs in the MCB 101 are galvanically isolated from other inputs/outputs on the MCB 101, but not from these on the control card of the frequency converter. If the digital inputs 7, 8 or 9 are to be switched by use of the internal 24V power supply (terminal 9) the connection between terminal 1 and 5 which is shown in Illustration 3.3 has to be established.
130BA209.10 Control card (FC 100/200/300) CPU General Purpose I/O option MCB 101 CAN BUS 0V 24V
CPU 0V DIG IN RIN= 5kohm COM DIN GND(1) DOUT3 DIG & ANALOG OUT 0/24VDC DOUT4 0/24VDC AOUT2 0/4-20mA 24V 24V ANALOG IN RIN= 10kohm GND(2)
DIN7
DIN8
DIN9
AIN3
AIN4
X30/
10
11
12
>600 ohm
<500 ohm
0-10 VDC
>600 ohm
0-10 VDC
50
3 3
When the relay option kit is ordered separately the kit includes: Relay Module MCB 105
Extended LCP frame and enlarged terminal cover Label for covering access to switches S201, S202 and S801 Cable strips for fastening cables to relay module
130BA709.10
RK A M 0 32 EN A0 G4 D 00 15 A E IN BF 8 D 12 kV D R1 0 .1 A 0B N: .9A 11 M B2 S/ 14 0A 3F nt z 6. 11 T5 rre XP 0H 1 C/ cu e XX 00 0/6 0Hz 45 1 ag CIA 1 5 0 x ak N 0V 10 a le : XX -48 0- b M h C : X 0 in m hig T/ N x38 -U Ta .) d kst 0 in an te P/ : 3 3x 20 m k CD ns (4 IN T: IS/IP U t / R ra O AS L /F ks T L te CH UA AL EN U sk M E IN AN U an M N UIP UP Fr E MA / SE IR EQ T 61 L SE ge VO ar 42 RO FU ch 13 NT RE x1 CO R P 76 L O D IA L F TE STR UA S LIS DU AN ION IN E M AT IC SE PL AP
UT CA :
IO
AR W
ed or St
N:
NI
NG
61
68
39
Re mo ve
42
50
to
12
13
jum p
53
er
54
18
acti
19
vate
27
29
Saf eS top
32
33
20
LA
BE
L
9 6
DISMOUNT RELAY CARD TO ACCESS RS485 TERMINATION (S801) OR CURRENT/VOLTAGE SWITCHES (S201, S202)
A2-A3-B3
1)
A5-B1-B2-B4-C1-C2-C3-C4
IMPORTANT! The label MUST be placed on the LCP frame as shown (UL approved).
51
DC-
DC+
3 3
61 6
LABE
1
39 42
50 53 5
Remov e jumpe
r to activat e Safe
Stop
12 13
18 19 27
28 32
38 2
DISMOUNT RELAY CARD TO ACCESS RS485 TERMINATION (S801) OR CURRENT/VOLTAGE SWITCHES (S201, S202)
WARNING
Warning Dual supply How to add the MCB 105 option: See mounting instructions in the beginning of section Options and Accessories
The power to the live part connections on relay terminals must be disconnected. Do not mix live parts with control signals (PELV). Select the relay functions in 5-40 Function Relay [6-8], 5-41 On Delay, Relay [6-8] and 5-42 Off Delay, Relay [6-8].
NB! (Index [6] is relay 7, index [7] is relay 8, and index [8] is relay 9)
130BA177.10
130BA162.10
Relay 7
Relay 8
Relay 9
NC 1 2 3 4 5 6 7
NC 8
NC 9 10 11 12
8-
9m
2m
1 2
NC 4 5
NC NC 8 9 10 11 12
1 2
NC 4 5
NC NC 8 9 10 11 12
NC 4 5
NC NC 8 9 10 11 12
LIVE PART
LIVE PART
PELV
PELV
PELV
PELV
LIVE PART
LIVE PART
LIVE PART
WARNING
Do not combine low voltage parts and PELV systems. At a single fault the whole system might become dangerous to touch and it could result in death or serious injury.
52
130BA176.10
130BA710.10
3 3
24V DC 15 % (max. 37 V in 10sec.) 2.2A 0.9A 75m < 10uF < 0.6sec.
130BA216.10
35 36
9 6
When MCB 107, 24V backup option is supplying the control circuit, the internal 24V supply is automatically disconnected.
130BA028.11
35
36
35 36
Providing battery back-up of clock function on control card As general extension of analog I/O selection available on control card, e.g. for multi-zone control with three pressure transmitters Turning frequency converter into de-central I/O block supporting Building Management System with inputs for sensors and outputs for operating dampers and valve actuators
2.
53
Support Extended PID controllers with I/Os for set point inputs, transmitter/sensor inputs and outputs for actuators.
130BA405.11
CONTROL CARD (FREQUENCY CONVERTER) CPU 0V ANALOG I/O OPTION MCB 109 CAN BUS 24 VDC
OR
0 - 10V DC 0-20mA (voltage input 0-10V) by mounting a 510 resistor across terminals (see NB!) 4-20mA (voltage input 2-10V) by mounting a 510 resistor across terminals (see NB) Ni1000 temperature sensor of 1000 at 0 C. Specifications according to DIN43760 Pt1000 temperature sensor of 1000 at 0 C. Specifications according to IEC 60751
3 3
CPU
RTC
3V LITHIUM BATTERY
ANALOG INPUT
0-10 VDC
0-10 VDC
0-10 VDC
AOUT
AOUT
AOUT
AIN
AIN
AIN
10
11
12
NOTE
Please note the values available within the different standard groups of resistors: E12: Closest standard value is 470, creating an input of 449.9 and 8.997V. E24: Closest standard value is 510, creating an input of 486.4 and 9.728V. E48: Closest standard value is 511, creating an input of 487.3 and 9.746V. E96: Closest standard value is 523, creating an input of 498.2 and 9.964V. Analog inputs - terminal X42/1-6 Parameter group for read out: 18-3*. See also VLT HVAC Drive Programming Guide. Parameter groups for set-up: 26-0*, 26-1*, 26-2* and 26-3*. See also VLT HVAC Drive Programming Guide.
0-10 VDC
0-10 VDC
Pt1000/ Ni 1000
Illustration 3.6 Principle diagram for Analog I/O mounted in frequency converter.
Resolution 11 bits
Accuracy -50C 1 Kelvin +150C 2 Kelvin 0.2% of full scale at cal. temperature
Sampling 3Hz
Max load -
Impedance -
0 - 10V DC
10 bits
2.4Hz
Approximately 5k
When used for voltage, analog inputs are scalable by parameters for each input. When used for temperature sensor, analog inputs scaling is preset to necessary signal level for specified temperature span. When analog inputs are used for temperature sensors, it is possible to read out feedback value in both C and F.
When operating with temperature sensors, maximum cable length to connect sensors is 80m non-screened / nontwisted wires. Analog outputs - terminal X42/7-12 Parameter group for read out and write: 18-3*. See also VLT HVAC Drive Programming Guide Parameter groups for set-up: 26-4*, 26-5* and 26-6*. See also VLT HVAC Drive Programming Guide
54
Real-time clock (RTC) with back-up The data format of RTC includes year, month, date, hour, minutes and weekday. Accuracy of clock is better than 20 ppm at 25 C.
Analog outputs are scalable by parameters for each output. The function assigned is selectable via a parameter and have same options as for analog outputs on control card. For a more detailed description of parameters, please refer to the VLT HVAC Drive Programming Guide. The built-in lithium back-up battery lasts on average for minimum 10 years, when frequency converter is operating at 40 C ambient temperature. If battery pack back-up fails, analog I/O option must be exchanged.
3 3
Option B Code No.130B1137 Reference for 10, 12 20-28 VDC 10 mA 20-28 VDC 60 mA
11 10 12 NC NC NC T1 X44 1 T2 2 3 4 5
NC
NC
NC
NC 9
12
13
TP
PTC M3~
TP
ATEX Certification with The MCB 112 has been certified for ATEX which means that the FC 102 together with the MCB 112 can now be used with motors in potentially explosive atmospheres. See the Operating Instructions for the MCB 112 for more information.
DO 10
55
3 3
Electrical Data Resistor connection: PTC compliant with DIN 44081 and DIN 44082 Number Shut-off value Reset value Trigger tolerance Collective resistance of the sensor loop Terminal voltage Sensor current Short circuit Power consumption Testing conditions: EN 60 947-8 Measurement voltage surge resistance Overvoltage category Degree of pollution Measurement isolation voltage Vbis Reliable galvanic isolation until Vi Perm. ambient temperature Moisture EMC resistance EMC emissions Vibration resistance Shock resistance Safety system values: EN 61508 for Tu = 75C ongoing SIL HFT PFD (for yearly functional test) SFF s + DD DU Ordering number 130B1137
1..6 resistors in series 3.3.... 3.65 ... 3.85 1.7 .... 1.8 ... 1.95 6C < 1.65 2.5V for R 3.65, 9V for R = 1mA 20 R 40 60 mA
6000V III 2 690V 500V -20C ... +60C EN 60068-2-1 Dry heat 5 --- 95%, no condensation permissible EN61000-6-2 EN61000-6-4 10 ... 1000Hz 1.14g 50g
2 for maintenance cycle of 2 years 1 for maintenance cycle of 3 years 0 4.10 *10-3 90% 8515 FIT 932 FIT
56
Sensor input for temperature transmitters PT100 and PT1000 for monitoring bearing temperatures As general extension of analog inputs with one additional input for multi-zone control or differential pressure measurements Support extended PID controllers with I/Os for set point, transmitter/sensor inputs
The option can generate an alarm if the measured temperature is either below low limit or above high limit specified by the user. The individual measured temperature on each sensor input can be read out in the display or by readout parameters. If an alarm occurs, the relays or digital outputs can be programmed to be active high by selecting [21] Thermal Warning in parameter group 5-**. A fault condition has a common warning/alarm number associated with it, which is Alarm/Warning 20, Temp. input error. Any present output can be programmed to be active in case the warning or alarm appears.
3 3
Typical motors, designed with temperature sensors for protecting bearings from being overloaded, are fitted with 3 PT100/1000 temperature sensors. One in front, one in the back end bearing, and one in the motor windings. The Danfoss Option MCB 114 supports 2- or 3-wire sensors with individual temperature limits for under/over temperature. An auto detection of sensor type, PT100 or PT1000 takes place at power up.
3 PT100/1000 PT 100 2 or 3 wire/PT1000 2 or 3 wire 1Hz for each channel 10 bit -50 - 204C -58 - 399F
Galvanic Isolation The sensors to be connected are expected to be galvanically isolated from the mains voltage level IEC 61800-5-1 and UL508C Cabling Maximum signal cable length
500m
57
3 3
130BB326.10
Option B
Code No. 130B1272
GND TEMP WIRE GND TEMP WIRE GND TEMP WIRE GND 1 1 2 2 3 3
X48/ 1
9 10 11 12
4-20mA 2 or 3 wire
2 or 3 wire
2 or 3 wire
2 or 3 wire
NAMUR Terminals NAMUR is an international association of automation technology users in the process industries, primarily chemical and pharmaceutical industries in Germany. Selection of this option provides terminals organized and labeled to the specifications of the NAMUR standard for drive input and output terminals. This requires MCB 112 PTC Thermistor Card and MCB 113 Extended Relay Card. RCD (Residual Current Device) Uses the core balance method to monitor ground fault currents in grounded and high-resistance grounded systems (TN and TT systems in IEC terminology). There is a prewarning (50% of main alarm set-point) and a main alarm setpoint. Associated with each set-point is an SPDT alarm relay for external use. Requires an external window-type current transformer (supplied and installed by customer).
Terminal 1 2 3 4, 7, 10 5, 8, 11 6, 9, 12
Function 24V DC to supply 4-20mA sensor 4-20mA input Analog input GND Temperature input 3rd wire input if 3 wire sensors are used Temp. input GND
Integrated into the drives safe-stop circuit IEC 60755 Type B device monitors AC, pulsed DC, and pure DC ground fault currents LED bar graph indicator of the ground fault current level from 10100% of the set-point Fault memory TEST / RESET button
Insulation Resistance Monitor (IRM) Monitors the insulation resistance in ungrounded systems (IT systems in IEC terminology) between the system phase conductors and ground. There is an ohmic pre-warning and a main alarm set-point for the insulation level. Associated with each set-point is an SPDT alarm relay for external use. Note: only one insulation resistance monitor can be connected to each ungrounded (IT) system.
Integrated into the drives safe-stop circuit LCD display of the ohmic value of the insulation resistance Fault Memory INFO, TEST, and RESET buttons
Transformer Tap Setup If the Cabinet Light & Outlet and/or the Space Heaters & Thermostat are installed Transformer T1 requires it taps to be set to the proper input voltage. A 380-480/ 500 V drive will initially be set to the 525 V tap and a 525-690 V drive will be set to the 690 V tap to insure no over-voltage of secondary equipment occurs if the tap is not changed prior to power being applied. See the table below to set the proper tap at terminal T1 located in the rectifier cabinet. For location in the drive, see illustration of rectifier in the Power Connections section.
IEC Emergency Stop with Pilz Safety Relay Includes a redundant 4-wire emergency-stop push-button mounted on the front of the enclosure and a Pilz relay that monitors it in conjunction with the drives safe-stop circuit and the mains contactor located in the options cabinet.
58
Operation switch (on/off) Short-circuit and overload protection with test function Manual reset function 3-phase power matching incoming mains voltage for powering auxiliary customer equipment Not available if two manual motor starters are selected Terminals are off when the incoming power to the drive is off Power for the fused protected terminals will be provided from the load side of any supplied contactor, circuit breaker, or disconnect switch.
Manual Motor Starters Provide 3-phase power for electric blowers often required for larger motors. Power for the starters is provided from the load side of any supplied contactor, circuit breaker, or disconnect switch. Power is fused before each motor starter, and is off when the incoming power to the drive is off. Up to two starters are allowed (one if a 30A, fuse-protected circuit is ordered). Integrated into the drives safe-stop circuit. Unit features include:
Ma
(0 R2
.08
130BA139.11
Min 72(2.8)
3 3
59
3 3
Illustration 3.7 LCP Kit with Graphical LCP, Fasteners, 3m Cable and Gasket. LCP Kit without LCP is also available. Ordering number: 130B1117 For IP55 units the ordering number is 130B1129.
Illustration 3.8 LCP Kit with Numerical LCP, Fastenes and Gasket.
60
A Top cover B Brim C Base part D Base cover E Screw(s) Place the top cover as shown. If an A or B option is used the brim must be fitted to cover the top inlet. Place the base part C at the bottom of the drive and use the clamps from the accessory bag to correctly fasten the cables. Holes for cable glands: Size A2: 2x M25 and 3xM32 Size A3: 3xM25 and 3xM32
130BT323.10
130BT324.10
3 3
D
D
E
E
A2 Enclosure
130BB045.10
A3 Enclosure
130BB044.10 A
Dimensions Enclosure type A2 A3 B3 B4 C3 C4 Height (mm) A 372 372 475 670 755 950 Width (mm) B 90 130 165 255 329 391 Depth (mm) C* 205 205 249 246 337 337
B C
B C
* If option A/B is used, the depth will increase (see section Mechanical Dimensions for details)
A2, A3, B3
B4, C3, C4
61
3 3
A Top cover B Brim C Base part D Base cover E Screw(s) F - Fan cover G - Top clip When option module A and/or option module B is/are used, the brim (B) must be fitted to the top cover (A).
130BT620.12
A B
Autom
VLT ati
on Drive
Automa tionDriv e
VLT
D F
B3 Enclosure
B4 - C3 - C4 Enclosure
NOTE
Side-by-side installation is not possible when using the IP 21/ IP 4X/ TYPE 1 Enclosure Kit
62
130BT621.12
3 3
63
How to Order
4 How to Order
Example of Drive Configurator interface set-up: The numbers shown in the boxes refer to the letter/figure number of the Type Code String - read from left to right.
Product groups Power rating Phases Mains Voltage Enclosure Enclosure type Enclosure class Control supply voltage Hardware configuration RFI filter 16-17 18 19 20 21 22 23 24-27 28 29-30 31-32 33-34 35 36-37 38-39 Brake Display (LCP) Coating PCB Mains option Adaptation A Adaptation B Software release Software language A options B options C0 options, MCO C1 options C option software D options 1-3 8-10 11 12 13-15
4 4
64
How to Order
Description
Product group & FC Series Power rating Number of phases
Pos
1-6 8-10 11
Possible choice
FC 102 1.1- 90 kW (P1K1 - P90K) Three phases (T) T T T T 2: 4: 6: 7: 200-240 V AC 380-480 V AC 525-600 VAC 525-690V AC
Description
Adaptation Adaptation Software release Software language
Pos
22 23 24-27 28
Possible choice
X: Standard 0: European metric thread in cable entries. Reserved Actual software AX: No options A0: MCA 101 Profibus DP V1 A4: MCA 104 DeviceNet AG: MCA 108 Lonworks AJ: MCA 109 BACnet gateway AL: MCA 120 Profinet AN: MCA 121 EtherNet/IP AQ: MCA 122 Modbus TCP BX: No option BK: MCB 101 General purpose I/O option BP: MCB 105 Relay option BO: MCB 109 Analog I/O option B2: MCB 112 PTC Thermistor Card B4: MCB 114 Sensor input option CX: No options X: No options XX: Standard software DX: No option D0: DC back-up
4 4
Mains voltage
11-12
Enclosure
13-15
E20: IP20 E21: IP21/NEMA Type 1 E55: IP55/NEMA Type 12 E66: IP66 P21: IP21/NEMA Type 1 w/ backplate P55: IP55/NEMA Type 12 w/ backplate Z55: A4 Frame IP55 Z66: A4 Frame IP66 H1: RFI filter class A1/B H2: RFI filter class A2 H3: RFI filter class A1/B (reduced cable length) Hx: No RFI filter X: No brake chopper included B: Brake chopper included T: Safe Stop U: Safe + brake G: Graphical Local Control Panel (GLCP) N: Numeric Local Control Panel (NLCP) X: No Local Control Panel X. No coated PCB C: Coated PCB X: No Mains disconnect switch and Load Sharing 1: With Mains disconnect switch (IP55 only) 8: Mains disconnect and Load Sharing D: Load Sharing See Chapter 8 for max. cable sizes.
A options
29-30
B options
31-32
RFI filter
16-17
Brake
18
Display
19
Coating PCB
20
Mains option
21
The various Options and Accessories are described further in the VLT HVAC Drive Design Guide, MG.11.BX.YY.
65
How to Order
4 4
Display
19
20 21
B options
31-32
The various options are described further in this Design Guide. 1): Available for all D frames. E frames 380-480/500 VAC only 2) Consult factory for applications requiring maritime certification 66 MG.11.BA.02 - VLT is a registered Danfoss trademark
How to Order
Product group Drive series Power rating Phases Mains voltage Enclosure
1-3 4-6 8-10 11 1112 1315 500 - 1400 kW Three phases (T) T 5: 380-500 VAC T 7: 525-690 VAC E21: IP 21/ NEMA Type 1 E54: IP 54/ NEMA Type 12 L2X: IP21/NEMA 1 with cabinet light & IEC 230V power outlet L5X: IP54/NEMA 12 with cabinet light & IEC 230V power outlet L2A: IP21/NEMA 1 with cabinet light & NAM 115V power outlet L5A: IP54/NEMA 12 with cabinet light & NAM 115V power outlet H21: IP21 with space heater and thermostat H54: IP54 with space heater and thermostat R2X: IP21/NEMA1 with space heater, thermostat, light & IEC 230V outlet R5X: IP54/NEMA12 with space heater, thermostat, light & IEC 230V outlet R2A: IP21/NEMA1 with space heater, thermostat, light, & NAM 115V outlet R5A: IP54/NEMA12 with space heater, thermostat, light, & NAM 115V outlet H2: RFI filter, class A2 (standard) H4: RFI filter, class A12, 3) HE: RCD with Class A2 RFI filter2) HF: RCD with class A1 RFI filter2, 3) HG: IRM with Class A2 RFI filter2) HH: IRM with class A1 RFI filter2, 3) HJ: NAMUR terminals and class A2 RFI filter1) HK: NAMUR terminals with class A1 RFI filter1, 2, 3) HL: RCD with NAMUR terminals and class A2 RFI filter1, 2) HM: RCD with NAMUR terminals and class A1 RFI filter1, 2, 3) HN: IRM with NAMUR terminals and class A2 RFI filter1, 2) HP: IRM with NAMUR terminals and class A1 RFI filter1, 2, 3)
4 4
RFI filter
1617
Brake
18
B: Brake IGBT mounted X: No brake IGBT R: Regeneration terminals M: IEC Emergency stop push-button (with Pilz safety relay)4) N: IEC Emergency stop push-button with brake IGBT and brake terminals P: IEC Emergency stop push-button with regeneration terminals4)
4)
19 20 21
G: Graphical Local Control Panel LCP C: Coated PCB X: No mains option 32): Mains disconnect and Fuse 52): Mains disconnect, Fuse and Load sharing 7: Fuse A: Fuse and Load sharing D: Load sharing E: Mains disconnect, contactor & fuses2) F: Mains circuit breaker, contactor & fuses
2)
G: Mains disconnect, contactor, loadsharing terminals & fuses2) H: Mains circuit breaker, contactor, loadsharing terminals & fuses2) J: Mains circuit breaker & fuses
2) 2)
67
How to Order
4 4
B options
31-32
68
How to Order
Type
Description
Ordering no.
Miscellaneous hardware I
DC link connector IP 21/4X top/ TYPE 1 kit IP 21/4X top/ TYPE 1 kit IP 21/4X top/ TYPE 1 kit IP 21/4X top/ TYPE 1 kit IP 21/4X top/ TYPE 1 kit IP 21/4X top/ TYPE 1 kit IP21/4X top IP21/4X top IP 21/4X top IP 21/4X top IP 21/4X top IP 21/4X top Panel Through Mount Kit Panel Through Mount Kit Panel Through Mount Kit Panel Through Mount Kit Panel Through Mount Kit Terminal block for DC link connnection on A2/A3 IP21/NEMA1 Top + bottom A2 IP21/NEMA1 Top + bottom A3 IP21/NEMA1 Top + bottom B3 130B1187 IP21/NEMA1 Top + bottom B4 130B1189 IP21/NEMA1 Top + bottom C3 130B1191 IP21/NEMA1 Top + bottom C4 130B1193 IP21 Top Cover A2 IP21 Top Cover A3 IP21 Top Cover B3 IP21 Top Cover B4 IP21 Top Cover C3 IP21 Top Cover C4 Enclosure, frame size A5 Enclosure, frame size B1 Enclosure, frame size B2 Enclosure, frame size C1 Enclosure, frame size C2 130B1132 130B1133 130B1188 130B1190 130B1192 130B1194 130B1028 130B1046 130B1047 130B1048
Miscellaneous hardware I
Terminal blocks Screw terminal blocks for replacing spring loaded terminals 1 pc 10 pin 1 pc 6 pin and 1 pc 3 pin connectors 130B1116 Backplate Backplate Backplate Backplate Backplate Backplate Backplate Backplate Backplate Backplate LCPs and kits LCP 101 LCP 102 LCP cable LCP kit Numerical Local Control Panel (NLCP) Separate LCP cable, 3 m Panel mounting kit including graphical LCP, fasteners, 3 m cable and gasket 130B1124 A5 IP55 / NEMA 12 B1 IP21 / IP55 / NEMA 12 B2 IP21 / IP55 / NEMA 12 C1 IP21 / IP55 / NEMA 12 C2 IP21 / IP55 / NEMA 12 A5 IP66 B1 IP66 B2 IP66 C1 IP66 C2 IP66 130B1098 130B3383 130B3397 130B3910 130B3911 130B3242 130B3434 130B3465 130B3468 130B3491
4 4
Panel mounting kit including 130B1114 numerical LCP, fasteners and gasket Panel mounting kit for all LCPs including fasteners, 3 m cable and gasket Panel mounting kit for all LCPs including fasteners and gasket without cable 130B1117
Profibus D-Sub Connector kit for IP20 9 Profibus top entry kit
Table 4.2 Options can be ordered as factory built-in options, see ordering information.
69
How to Order
Type Options for Slot A MCA 101 MCA 104 MCA 108 MCA 109 MCA 120 MCA 121 MCA 122 Options for Slot B MCB 101 MCB 105 MCB 109 MCB 112 MCB 114 Option for Slot D MCB 107 External Options Ethernet IP
Description
Profibus option DP V0/V1 DeviceNet option Lonworks BACnet gateway for build-in. Not to be used with Relay Option MCB 105 card Profinet Ethernet Modbus TCP General purpose Input Output option Relay option Analog I/O option and battery back-up for real-time clock ATEX PTC Sensor input - unocated Sensor input - coated 24 V DC back-up Ethernet master
4 4
For information on fieldbus and application option compatibility with older software versions, please contact your Danfoss supplier.
70
How to Order
Type Spare Parts Control board FC Control board FC Fan A2 Fan A3 Fan A5 Fan B1 Fan B2 Fan B3 Fan B4 Fan B4 Fan C1 Fan C2 Fan C3 Fan C4 Miscellaneous hardware II Accessory bag A2 Accessory bag A3 Accessory bag A5 Accessory bag B1 Accessory bag B2 Accessory bag B3 Accessory bag B4 Accessory bag B4 Accessory bag C1 Accessory bag C2 Accessory bag C3 Accessory bag C4 Accessory bag C4
Description Ordering no. With Safe Stop Function Without Safe Stop Function Fan, frame size A2 Fan, frame size A3 Fan, frame size A5 Fan external, frame size B1 Fan external, frame size B2 Fan external, frame size B3 Fan external, 18.5/22 kW Fan external 22/30 kW Fan external, frame size C1 Fan external, frame size C2 Fan external, frame size C3 Fan external, frame size C4 Accessory bag, frame size A2 Accessory bag, frame size A3 Accessory bag, frame size A5 Accessory bag, frame size B1 Accessory bag, frame size B2 Accessory bag, frame size B3 Accessory bag, frame size B4 Accessory bag, frame size B4 Accessory bag, frame size C1 Accessory bag, frame size C2 Accessory bag, frame size C3 Accessory bag, frame size C4 Accessory bag, frame size C4 130B1150 130B1151 130B1009 130B1010 130B1017 130B3407 130B3406 130B3563 130B3699 130B3701 130B3865 130B3867 130B4292 130B4294 130B1022 130B1022 130B1023 130B2060 130B2061 130B0980 130B1300 130B1301 130B0046 130B0047 130B0981 130B0982 130B0983 Small Big Small Big Comments
4 4
71
How to Order
4 4
72
How to Order
380-415 VAC, 50 Hz IAHF,N [A] 10 19 26 35 43 72 101 144 180 217 289 324 370 506 578 648 694 740 380 - 415 VAC, 60 Hz IAHF,N [A] 10 19 26 35 43 72 101 144 180 217 289 324 370 506 578 648 694 740 Typical Motor Used [HP] 1.1 - 4 5.5 - 7.5 11 15 - 18.5 22 30 - 37 45 - 55 75 90 110 132 160 200 250 315 355 400 450 Danfoss Ordering Number AHF 005 130B2540 130B2460 130B2461 130B2462 130B2463 130B2464 130B2465 130B2466 130B2467 130B2468 130B2469 130B2470 130B2471 130B2468 + 130B2469 2x 130B2469 2x130B2470 130B2470 + 130B2471 2x130B2471 AHF 010 130B2541 130B2472 130B2473 130B2474 130B2475 130B2476 130B2477 130B2478 130B2479 130B2480 130B2481 130B2482 130B2483 130B2480 + 130B2481 2x 130B2481 2x130B2482 130B2482 + 130B2483 130B2483 Frequency Converter Size P1K1 - P4K0 P5K5 - P7K5 P11K P15K, P18K P22K P30K - P37K P45K - P55K P75K P90K P110 P132 P160 P200 P250 P315 P355 P400 P450 Typical Motor Used [kW] 1.1 - 4 5.5 - 7.5 11 15 - 18.5 22 30 - 37 45 - 55 75 90 110 132 160 200 250 315 355 400 450 Danfoss Ordering Number AHF 005 175G6600 175G6601 175G6602 175G6603 175G6604 175G6605 175G6606 175G6607 175G6608 175G6609 175G6610 175G6611 175G6688 175G6609 + 175G6610 2x 175G6610 2x175G6611 175G6611 + 175G6688 2x175G6688 AHF 010 175G6622 175G6623 175G6624 175G6625 175G6626 175G6627 175G6628 175G6629 175G6630 175G6631 175G6632 175G6633 175G6691 175G6631 + 175G6632 2x 175G6632 2x175G6633 175G6633 + 175G6691 2x175G6691 P200 P250 P315 P355 P400 P450 Frequency ConverterSize P1K1, P4K0 P5K5 - P7K5 P11K P15K - P18K P22K P30K - P37K P45K - P55K P75K P90K P110 P132 - P160
4 4
73
How to Order
440-480 VAC, 60 Hz IAHF,N [A] 10 19 26 35 43 72 101 144 180 217 289 370 434 506 578 648 694 740 Typical Motor Used [HP] 1.5 - 7.5 10 - 15 20 25 - 30 40 50 - 60 75 100 - 125 150 200 250 350 350 450 500 550-600 600 650 Danfoss Ordering Number AHF 005 130B2538 175G6612 175G6613 175G6614 175G6615 175G6616 175G6617 175G6618 175G6619 175G6620 175G6621 175G6690 2x175G6620 175G6620 + 175G6621 2x 175G6621 2x175G6689 175G6689 + 175G6690 2x175G6690 AHF 010 130B2539 175G6634 175G6635 175G6636 175G6637 175G6638 175G6639 175G6640 175G6641 175G6642 175G6643 175G6693 2x175G6642 175G6642 + 175G6643 2x 175G6643 2x175G6692 175G6692 + 175G6693 2x175G6693 Frequency Converter Size P1K1 - P5K5 P7K5 - P11K P15K P18K - P22K P30K P37K - P45K P55K P75K - P90K P110 P132 P160 P200 P250 P315 P355 P400 P450 P500
4 4
Matching the frequency converter and filter is pre-calculated based on 400V/480V and on a typical motor load (4 pole) and 110 % torque.
500-525 VAC, 50 Hz IAHF,N [A] 10 19 26 35 43 72 101 144 180 217 289 324 397 434 506 578 613 Typical Motor Used [kW] 1.1 - 7.5 11 15 -18.5 22 30 37 -45 55 75 - 90 110 132 160 - 200 250 315 355 400 450 500 Danfoss Ordering Number AHF 005 175G6644 175G6645 175G6646 175G6647 175G6648 175G6649 175G6650 175G6651 175G6652 175G6653 175G6654 175G6655 175G6652 + 175G6653 2x175G6653 175G6653 + 175G6654 2X 175G6654 175G6654 + 175G6655 AHF 010 175G6656 175G6657 175G6658 175G6659 175G6660 175G6661 175G6662 175G6663 175G6664 175G6665 175G6666 175G6667 175G6641 + 175G6665 2x175G6665 175G6665 + 175G6666 2X 175G6666 175G6666 + 175G6667 Frequency Converter Size P1K1 - P7K5 P11K P15K - P18K P22K P30K P45K - P55K P75K P90K - P110 P132 P160 P200 - P250 P315 P400 P450 P500 P560 P630
74
How to Order
690 VAC, 50 Hz IAHF,N [A] 43 72 101 144 180 217 288 324 397 434 505 576 612 730 Typical Motor Used [kW] 45 45 - 55 75 - 90 110 132 160 200 - 250 315 400 450 500 560 630 710 Danfoss Ordering Number AHF 005 130B2328 130B2330 130B2331 130B2333 130B2334 130B2335 2x130B2333 130B2334 + 130B2335 130B2334 + 130B2335 2x130B2335 * * * * AHF 010 130B2293 130B2295 130B2296 130B2298 130B2299 130B2300 130B2301 130B2302 130B2299 + 130B2300 2x130B2300 130B2300 + 130B2301 2x130B2301 130B2301 + 130B2300 2x130B2302 P37K - P45K P55K - P75K P90K - P110 P132 P160 P200 - P250 P315 P400 P450 P500 P560 P630 P710 Frequency Converter Size
4 4
75
How to Order
Part No. IP20 130B2441 130B2441 130B2443 130B2443 130B2444 130B2446 130B2446 130B2446 130B2447 130B2448 130B2448 130B2307 130B2308 130B2309 130B2310 130B2310 130B2311 130B2311 130B2312 130B2313 130B2313 130B2314 130B2314 130B2315 130B2315 130B2316 130B2316 130B2317 130B2317 130B2318 130B2318 2x130B2317 2x130B2317 2x130B2318
Part No. IP00 130B2406 130B2406 130B2408 130B2408 130B2409 130B2411 130B2411 130B2411 130B2412 130B2413 130B2413 130B2281 130B2282 130B2283 130B2284 130B2284 130B2285 130B2285 130B2286 130B2287 130B2287 130B2288 130B2288 130B2289 130B2289 130B2290 130B2290 130B2291 130B2291 130B2292 130B2292 2x130B2291 2x130B2291 2x130B2292
4 4
When using Sine-wave filters, the switching frequency should comply with filter specifications in 14-01 Switching Frequency.
NOTE
See also Output Filter Design Guide, MG.90.Nx.yy
76
How to Order
Part No. IP20 130B2341 130B2341 130B2341 130B2341 130B2341 130B2341 130B2341 130B2342 130B2342 130B2342 130B2342 130B2343 130B2344 130B2344 130B2345 130B2345 130B2346 130B2346 130B2347 130B2347 130B2348 130B2370 130B2370 130B2370 130B2371 130B2371 130B2381 130B2381 130B2382 130B2383 130B2383 130B2384 130B2384 2x130B2382
Part No. IP00 130B2321 130B2321 130B2321 130B2321 130B2321 130B2321 130B2321 130B2322 130B2322 130B2322 130B2322 130B2323 130B2324 130B2324 130B2325 130B2325 130B2326 130B2326 130B2327 130B2327 130B2329 130B2341 130B2341 130B2341 130B2342 130B2342 130B2337 130B2337 130B2338 130B2339 130B2339 130B2340 130B2340 2x130B2338
4 4
NOTE
When using Sine-wave filters, the switching frequency should comply with filter specifications in 14-01 Switching Frequency.
NOTE
See also Output Filter Design Guide, MG.90.Nx.yy
77
How to Order
4 4
NOTE
See also Output Filter Design Guide, MG.90.Nx.yy
78
How to Order
4 4
NOTE
See also Output Filter Design Guide, MG.90.Nx.yy
NOTE
See Brake Resistor Design Guide, MG.90.Ox.yy
79
How to Install
5 How to Install
A3
130BA810.10
A4
130BB458.10
A5
130BA811.10
B1
130BA812.10
B2
130BA813.10
5 5
IP20/21*
IP20/21*
IP55/66
C B b e
IP55/66
IP21/55/66
IP21/55/66
f A c d e b a
B4
130BA827.10
C1
130BA814.10
C2
130BA815.10
130BA648.11
C3
130BA828.10
C4
130BA829.10
IP20/21*
IP20/21*
IP21/55/66
e
IP21/55/66
130BA715.11
IP20/21*
IP20/21*
Top and bottom mounting holes. (B4+C3+C4 only) Accessory bags containing necessary brackets, screws and connectors are included with the frequency converter upon delivery. * IP21 can be established with a kit as described in the section: IP 21/ IP 4X/ TYPE 1 Enclosure Kit in the Design Guide.
80
Mechanical Dimensions A3 3.0-3.7 5.5-7.5 1.1-7.5 21 20 Type 1 Chassis 372 375 350 90 130 90 70 205 220 8.0 11 5.5 9 5.3 6.6 7.0 9.7 14 23 9 9 6 9 9 5.5 5.5 6.5 6.5 9 11 11 12 12 19 9 9 27 8.0 8.0 8.2 8.2 12 12 19 220 220 175 200 260 260 205 205 175 200 260 260 248 262 8 12 6.8 7.9 12 110 110 171 215 210 210 140 200 242 242 8.5 15 23.5 130 130 200 242 242 242 165 231 170 170 242 242 242 205 231 130 130 200 242 242 242 165 231 308 308 308 272 310 310 12 19 9.0 9.8 45 257 350 401 402 454 624 380 495 648 268 375 390 420 480 650 399 520 680 374 419 595 770 739 370 370 370 334 335 335 12 19 9.0 9.8 65 246 372 390 420 480 650 350 460 680 770 490 630 550 521 308 308 308 270 333 333 8.5 17 35 21 55/66 Type 1 55/66 Type 12 21/ 55/66 Type 1/12 21/ 55/66 Type 1/12 20 Chassis 20 Chassis 21/ 55/66 Type 1/12 21/ 55/66 Type 1/12 20 Chassis 20 Chassis 600 800 660 631 370 370 370 330 333 333 8.5 17 50 1.1-2.2 1.1-3.7 1.1-4.0 1.1-7.5 1.1-7.5 5.5-11 11-18.5 11-18.5 15 22-30 11-30 11-30 5.5-11 11-18.5 11-18.5 15-18.5 22-37 22-37 18.5-30 37-55 37-55 37-45 75-90 37-90 37-90 22-30 45-55 45-55 37-45 75-90 75-90 A4 A5 B1 B2 B3 B4 C1 C2 C3 C4
How to Install
A2
1.1-2.2 1.1-4.0
IP NEMA
20 Chassis
Height (mm)
Enclosure
A**
246
A2
374
Back plate
A1
268
257
Width (mm)
Enclosure
90
130
Back plate
90
70
Depth (mm)
205
C*
220
8.0
Diameter
11
Diameter
5.5
4.9
** The free space requirements are above and below the bare enclosure height measurement A. See section Mechanical Mounting for further information.
81
5 5
5 5
130BA819.10
130BA816.10
130BA817.10
130BA820.10
130BA818.10
130BA821.10
130BA885.10
130BA959.10
IP21/54
130BA878.10
b d
j
c
Enclosure F1
Enclosure F2
130BA881.10
130BA879.10
130BB003.13
61.4
BACK
130BA651.10
All measurements in mm
70.4 FRONT
361.7
130BB004.13
624 (24.6)
14
25
130BB006.10
624 [24.6]
Enclosure F3
Enclosure F4
2X578 [22.8]
776 [30.6]
2x579 (22.8)
578 (22.8)
130BB005.13
579 [22.8]
130BB092.10
82 D4 E1 E2 F1/F3 F2/F4
How to Install
D1
D2
D3
F3 F1
F4 F3
IP21/54
IP21/54
IP00
IP00
IP21/54
IP00
Mechanical dimensions D2 160-250 200-400 21/54 Type 1/12 1730 650 570 570 570 736 736 927 927 650 650 840 831 1569 1962 2159 927 1220 1490 2197 1705 2324 2324 2324 00 Chassis 00 Chassis 21/54 Type 1/12 00 Chassis 21/54 Type 1/12 21/54 Type 1/12 21/54 Type 1/12 21/54 Type 1/12 2324 2559 927 110-132 45-160 160-250 200-400 315-450 450-630 315-450 450-630 500-710 710-900 800-1000 1000-1400 500-710 710-900 800-1000 1000-1400 D3 D4 E1 E2 F1 F2 F3 F4
How to Install
D1
110-132 45-160
IP NEMA
Width
1730
Height
650
Depth
570
FCDrive dimensions: (mm) 1589 420 380 22/0.9 25/1.0 25/1.0 20/0.8 11/0.4 22/0.9 10/0.4 51/2.0 25/1.0 49/1.9 11/0.4 151 91 138 11/0.4 11/0.4 313 277 1004 1246 1299 1541 49/1.9 49/1.9 25/1.0 25/1.0 51/2.0 51/2.0 10/0.4 10/0.4 22/0.9 22/0.9 11/0.4 11/0.4 20/0.8 20/0.8 27/1.1 13/0.5 25/1.0 25/1.0 25/1.0 25/1.0 25/1.0 25/1.0 25/1.0 25/1.0 22/0.9 22/0.9 56/2.2 23/0.9 375 375 494 494 607 408 408 600 585 1400 1046 1327 2000 1547 2281 2281 1800 607 2281 2000 607 2281 2400 607
Height
Back plate
1209
Width
420
380
22/0.9
25/1.0
Hole diameter
25/1.0
20/0.8
11/0.4
22/0.9
10/0.4
51/2.0
25/1.0
49/1.9
Hole diameter
11/0.4
104
Please contact Danfoss for more detailed information and CAD drawings for your own planning purposes.
83
5 5
5 5
03 02 01
06 05 04
E F
10
10
06
06
130BT339.10
RELAY 1
ISOA0021
61 68
39 42 50
39 42 50 53 54 5
WARNIN
Risk of Electric Disconn Shock ect mains - Dual supply and loadsha ring before service
G:
130BT348.10
WARNING
WARNING:
Risk of Electric Disconnect Shock - Dual supply mains and loadsharing before service
STORED CHARGE 15 MIN. AFTER DO NOT TOUCH UNTIL DISCONNECT CHARGE ION RESIDUELLE. ATTENDRE 15 MIN. APRES DECONNEXIO N
61 68
Risk of Electric Disconnect Shock - Dual supply mains and loadsharing before service
WARNING
39 42 50 53 54
95 99
95
RELAY 1
RELAY 2
99
service
Frame size B3
Frame size B4
130BT347.10
Risk of Electric Shock - Dual Discunnect supply mains and loadsharing before
WARNING
130BT346.10
Frame size C3
Frame size C4
1 + 2 only available in units with brake chopper. For DC link connection (Load sharing) the connector 1 can be ordered separately (Code no. 130B1064)
An eight pole connector is included in accessory bag for FC 102 without Safe Stop.
130BT349.10
61 68
53 54 5
06 05 04
03 02 01
03 02 01
06 05 04
03 02 01
06 05 04
U V 96 9 W 7 98
03 02 01
L1 L 2 91 9 L3 2 93
RELAY 1
130BT309.10
130BT330.10
G I
Risk of Electric Shock - Dual supply Disconnect mains and loadsharing before service
WARNING:
61 68
39 42 50 53
54 5
130BA406.10
06 05 04
03 02 01
84
A B
61 68 6
39 42 50 53 54 5
Accessory Bags: Find the following parts included in the frequency converter accessory bags
C D
How to Install
How to Install
A2 100 B4 200
A3 100 C1 200
A5 100 C2 225
B1 200 C3 200
B2 200 C4 225
B3 200
5 5
1. 2.
Drill holes in accordance with the measurements given. Provide screws suitable for the surface on which you want to mount the frequency converter. Retighten all four screws.
130BA219.10 130BA228.10
IP66 Drive A
Table 5.2 When mounting enclosure sizes A5, B1, B2, B3, B4, C1, C2, C3 and C4 on a non-solid back wall, the drive must be provided with a back plate A due to insufficient cooling air over the heat sink.
130BA392.10
85
How to Install
Always lift the frequency converter in the dedicated lifting eyes. For all D and E2 (IP00) enclosures, use a bar to avoid bending the lifting holes of the frequency converter.
176FA245.10
5 5
Illustration 5.1 Recommended Lifting Method, Frame Sizes D and E. Illustration 5.3 Recommended Lifting Method, Frame Size F2 (460V, 1000 to 1200 HP, 575/690V, 1250 to 1350 HP).
The lifting bar must be able to handle the weight of the frequency converter. See Mechanical Dimensions for the weight of the different frame sizes. Maximum diameter for bar is 2.5 cm (1 inch). The angle from the top of the drive to the lifting cable should be 60C or greater.
130BA832.11
Illustration 5.4 Recommended Lifting Method, Frame Size F3 (460V, 600 to 900 HP, 575/690V, 900 to 1150 HP).
Illustration 5.2 Recommended Lifting Method, Frame Size F1 (460V, 600 to 900 HP, 575/690V, 900 to 1150 HP).
Illustration 5.5 Recommended Lifting Method, Frame Size F4 (460V, 1000 to 1200 HP, 575/690V, 1250 to 1350 HP).
86
130BA835.11
130BA833.11
WARNING
130BA834.11
5.1.5 Lifting
How to Install
NOTE
The plinth is provided in the same packaging as the frequency converter but is not attached to frame sizes F1-F4 during shipment. The plinth is required to allow airflow to the drive to provide proper cooling. The F frames should be positioned on top of the plinth in the final installation location. The angle from the top of the drive to the lifting cable should be 60C or greater. In addition to the drawings above a spreader bar is an acceptable way to lift the F Frame.
WARNING
Pay attention to the requirements that apply to integration and field mounting kit. Observe the information in the list to avoid serious injury or equipment damage, especially when installing large units.
The frequency converter is cooled by means of air circulation. To protect the unit from overheating, it must be ensured that the ambient temperature does not exceed the maximum temperature stated for the frequency converter and that the 24-hour average temperature is not exceeded. Locate the maximum temperature and 24-hour average in the paragraph Derating for Ambient Temperature. If the ambient temperature is in the range of 45 C - 55 C, derating of the frequency converter will become relevant, see Derating for Ambient Temperature. The service life of the frequency converter is reduced if derating for ambient temperature is not taken into account.
CAUTION
5 5
87
How to Install
NOTE
For the VLT HVAC Drive High Power series mains and motor connections, please see VLT HVAC Drive High Power Operating Instructions MG.11.FX.YY.
NOTE
Cables General All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper (60/75 C) conductors are recommended. Details of terminal tightening torques.
Power (kW) Enclo200-240V 380-480V 525-600V 525-690V sure A2 A3 A4 A5 B1 B2 B3 B4 C1 C2 C3 C4 D1/D3 D2/D4 E1/E2 F1/F33) F2/F43) 1.1 - 3.0 3.7 1.1-2.2 1.1 - 3.7 5.5 - 11 15 5.5 - 11 15 - 18.5 18.5 - 30 37 - 45 22 - 30 37 - 45 1.1 - 4.0 5.5 - 7.5 1.1-4 1.1 - 7.5 22 30 22 - 37 37 - 55 75 - 90 45 - 55 75 - 90 110-132 160-250 315-450 500-710 800-1000 1.1 - 7.5 11 30 30 90 45-160 200-400 450-630 710-900 1000-1400 22 30 22 - 37 37 - 55 75 - 90 45 - 55 75 - 90 11 - 18.5 11 - 18.5 1.1 - 4.0 5.5 - 7.5 Mains 1.8 1.8 1.8 1.8 1.8 2.5 4.52) 1.8 4.5 10 14/241) 10 14/24 19 19 19 19 19
1)
5 5
Torque (Nm) Motor 1.8 1.8 1.8 1.8 1.8 2.5 4.52) 1.8 4.5 10 14/241) 10 14/24 19 19 19 19 19
1)
DC connection 1.8 1.8 1.8 1.8 1.5 3.7 3.7 1.8 4.5 10 14 10 14 9.6 9.6 19 19 19
Brake 1.8 1.8 1.8 1.8 1.5 2.5 3.7 1.8 4.5 10 14 10 14 9.6 9.6 9.6 9.6 9.6
Earth 3 3 3 3 3 3 3 3 3 3 3 3 3 19 19 19 19 19
Relay 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6
11 - 18.5 11 - 18.5
1) For different cable dimensions x/y, where x 95mm2 and y 95mm2. 2) Cable dimensions above 18.5kW 35mm2 and below 22kW 10mm2. 3) For data on the F frame sizes consult FC 100 High Power Operating Instructions.
88
How to Install
91 (L1) 92 (L2) 93 (L3) 95 PE 88 (-) 89 (+) 50 (+10 V OUT) S201 53 (A IN) 1 2 ON S202 1 2 ON 54 (A IN) ON=0-20mA OFF=0-10V Switch Mode Power Supply 24Vdc 15mA 200mA + + -
DC bus
5 5
240Vac, 2A
03 02 01
55 (COM A IN) 12 (+24V OUT) 13 (+24V OUT) 18 (D IN) 19 (D IN) 20 (COM D IN) 27 (D IN/OUT) 24V 0V 29 (D IN/OUT) 24V 0V 32 (D IN) 33 (D IN) * 37 (D IN) 24V (NPN) 0V (PNP) 24V (NPN) 0V (PNP) 24V (NPN) 0V (PNP) S801 RS-485 Interface 24V (NPN) 0V (PNP) S801 1 2 ON P 5-00 24V (NPN) 0V (PNP) 24V (NPN) 0V (PNP) relay2
06 05 04
240Vac, 2A 400Vac, 2A
ON=Terminated OFF=Open
5V
Illustration 5.6 Diagram Showing all Electrical Terminals. (Terminal 37 Present for Units with Safe Stop Function only.)
89
How to Install
Terminal description Terminal 1+2+3-Relay1 Terminal 4+5+6-Relay2 Terminal 12 Supply Terminal 13 Supply Terminal 18 Digital Input Terminal 19 Digital Input Terminal 20 Terminal 27 Digital Input/Output Terminal 29 Digital Input/Output Terminal 32 Digital Input Terminal 33 Digital Input Terminal 37 Digital Input Terminal 42 Analog Output Terminal 53 Analog Input Terminal 54 Analog Input
Parameter number 5-40 5-40 5-10 5-11 5-12/5-30 5-13/5-31 5-14 5-15 6-50 3-15/6-1*/20-0* 3-15/6-2*/20-0*
Factory default No operation No operation +24 V DC +24 V DC Start No operation Common Coast inverse Jog No operation No operation Safe Stop Speed 0-HighLim Reference Feedback
5 5
Very long control cables and analog signals may, in rare cases and depending on installation, result in 50/60 Hz earth loops due to noise from mains supply cables. If this occurs, break the screen or insert a 100 nF capacitor between screen and chassis.
If it is necessary to split the screen to install a motor isolator or motor relay, the screen must be continued with the lowest possible HF impedance.
NOTE
The common of digital / analog inputs and outputs should be connected to separate common terminals 20, 39, and 55. This will avoid ground current interference among groups. For example, it avoids switching on digital inputs disturbing analog inputs.
F frame Requirements F1/F3 requirements: Motor phase cable quantities must be multiples of 2, resulting in 2, 4, 6, or 8 (1 cable is not allowed) to obtain equal amount of wires attached to both inverter module terminals. The cables are required to be equal length within 10% between the inverter module terminals and the first common point of a phase. The recommended common point is the motor terminals. F2/F4 requirements: Motor phase cable quantities must be multiples of 3, resulting in 3, 6, 9, or 12 (1 or 2 cables are not allowed) to obtain equal amount of wires attached to each inverter module terminal. The wires are required to be equal length within 10% between the inverter module terminals and the first common point of a phase. The recommended common point is the motor terminals. Output junction box requirements: The length, minimum 2.5 meters, and quantity of cables must be equal from each inverter module to the common terminal in the junction box.
NOTE
Control cables must be screened/armoured.
Use a screened/armoured motor cable to comply with EMC emission specifications. Keep the motor cable as short as possible to reduce the noise level and leakage currents. Connect the motor cable screen to both the decoupling plate of the frequency converter and to the metal cabinet of the motor. Make the screen connections with the largest possible surface area (cable clamp). This is done by using the supplied installation devices in the frequency converter. Avoid mounting with twisted screen ends (pigtails), which will spoil high frequency screening effects.
NOTE
If a retrofit application requires unequal amount of wires per phase, please consult the factory for requirements and documentation or use the top/bottom entry side cabinet busbar option.
90
How to Install
Cable length and cross-section The frequency converter has been tested with a given length of cable and a given cross-section of that cable. If the crosssection is increased, the cable capacitance - and thus the leakage current - may increase, and the cable length must be reduced correspondingly. Switching frequency When frequency converters are used together with Sinewave filters to reduce the acoustic noise from a motor, the switching frequency must be set according to the Sine-wave filter instruction in 14-01 Switching Frequency. Aluminium conductors Aluminium conductors are not recommended. Terminals can accept aluminium conductors but the conductor surface has to be clean and the oxidation must be removed and sealed by neutral acid free Vaseline grease before the conductor is connected. Furthermore, the terminal screw must be retightened after two days due to the softness of the aluminium. It is crucial to keep the connection a gas tight joint, otherwise the aluminium surface will oxidize again.
M32 A
M25
M32 B
M32 C
130BB325.10
M25
18
Illustration 5.9 Cable entry holes for enclosure B1. The suggested use of the holes are purely recommendations and other solutions are possible.
5 5
42.9 A
33.1 B
42.9 C
26.3
Illustration 5.10 Cable entry holes for enclosure B2. The suggested use of the holes are purely recommendations and other solutions are possible.
130BA609.11
26.3
17
M40 A
M20
M32 B
M40 C
33,1 A
21
33,1 B
33,1 C
Illustration 5.11 Cable entry holes for enclosure B2. The suggested use of the holes are purely recommendations and other solutions are possible.
Illustration 5.8 Cable entry holes for enclosure B1. The suggested use of the holes are purely recommendations and other solutions are possible.
130BB324.10
Illustration 5.7 Cable entry holes for enclosure A5. The suggested use of the holes are purely recommendations and other solutions are possible.
M25
130BA610.11
26.3
17
91
How to Install
130BA643.11
M15
M25
M16
M25
NOTE
M63 A M63 C M50 B
5 5
Illustration 5.12 Cable entry holes for enclosure C1. The suggested use of the holes are purely recommendations and other solutions are possible.
The gland plate must be fitted to the frequency converter to ensure the specified protection degree, as well as ensuring proper cooling of the unit. If the gland plate is not mounted, the frequency converter may trip on Alarm 69, Pwr. Card Temp Cable entries viewed from the bottom of the frequency converter - 1) Mains side 2) Motor side
130BA644.10
M63 A
M63 C
M50 B
35
Legend: A: Line in
202.8 62.5
1.
Remove cable entry from the frequency converter (Avoiding foreign parts falling into the frequency converter when removing knockouts) Cable entry has to be supported around the knockout you intend to remove. The knockout can now be removed with a strong mandrel and a hammer. Remove burrs from the hole. Mount Cable entry on frequency converter.
2. 3. 4. 5.
92
98.6
130.0
176FA289.11
Illustration 5.13 Cable entry holes for enclosure C2. The suggested use of the holes are purely recommendations and other solutions are possible.
130BB073.10
M16
M25
M16
M25
How to Install
35
37.7 (1.485) 2X 216.5 535.0 (8.524) (21.063) 2X 281.3 (11.075) 35.5 (1.398) 36.2 (1.425)
199.5 (7.854) 258.5 (10.177) 533.0 (20.984) 597.0 (23.504) 1130.0 (44.488) 1192.8 (46.961)
202.8
62.5
130.0
98.6
130BA843.12
176FA289.11
1265.3 (49.815)
593.0 (23.346)
1925.8 (75.819)
5 5
130BA839.10 199.5 (7.854) 258.2 (10.167) 1 994.3 (39.146)
350
F1-F4: Cable entries viewed from the bottom of the frequency converter - 1) Place conduits in marked areas
593.0 (23.346) 37.7 (1.485) 1 130BA837.12 668.3 (26.311) 460.0 (18.110) 199.5 (7.854) 258.5 (10.177) 533.0 (20.984) 595.8 (23.457) 35.5 (1.398) 1328.8 (52.315)
2X 216.5 (8.524) 535.0 (21.063) 2X 281.8 (11.096) 35.5 (1.398) 533.0 (20.984) 597.0 (23.504) 1130.0 (44.488) 1191.8 (46.921)
36.2 (1.425)
535.0 (21.063)
2324.8 (91.528)
36.2 (1.425)
5.2.8 Fuses
A frequency converter that works correctly limits the current it can draw from the supply. Still, it is recommended to use fuses and/ or Circuit Breakers on the supply side as protection in case of component break-down inside the frequency converter (first fault).
130BA841.12
994.3 [39.146]
535.0 [21.063]
216.5 [8.524]
NOTE
This is mandatory in order to ensure compliance with IEC 60364 for CE or NEC 2009 for UL.
281.8 [11.096]
35.5 [1.398]
1 1727.8 [68.024]
WARNING
Personnel and property must be protected against the consequence of component break-down internally in the frequency converter. Branch Circuit Protection In order to protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines etc., must be protected against short-circuit and over-current according to national/international regulations.
NOTE
The recommendations given do not cover Branch circuit protection for UL!
93
How to Install
Short-circuit protection: Danfoss recommends using the fuses/Circuit Breakers listed in and to protect service personnel and property in case of component break-down in the frequency converter. Over current protection: The frequency converter provides overload protection to limit threats to human life, property damage and to avoid
fire hazard due to overheating of the cables in the installation. The frequency converter is equipped with an internal over current protection (4-18 Current Limit) that can be used for upstream overload protection (UL-applications excluded). Moreover, fuses or Circuit Breakers can be used to provide the over current protection in the installation. Over current protection must always be carried out according to national regulations.
5 5
1) Max. fuses - see national/international regulations for selecting an applicable fuse size. Table 5.5 Non-UL Fuses 200V to 480V
If UL/cUL is not to be complied with, Danfoss recommends using the following fuses, which will ensure compliance with EN50178:
Frequency Converter P110 - P250 P315 - P450 Table 5.6 Compliance with EN50178 Voltage (V) 380 - 480 380 - 480 Type type gG type gR
94
How to Install
UL compliance fuses
Frequency converter 200-240V kW K25-K37 K55-1K1 1K5 2K2 3K0 3K7 5K5 7K5 11K 15K 18K5 22K 30K 37K 45K Type RK1 KTN-R05 KTN-R10 KTN-R15 KTN-R20 KTN-R25 KTN-R30 KTN-R50 KTN-R50 KTN-R60 KTN-R80 KTN-R125 KTN-R125 FWX-150 FWX-200 FWX-250 Type J JKS-05 JKS-10 JKS-15 JKS-20 JKS-25 JKS-30 JKS-50 JKS-60 JKS-60 JKS-80 JKS-150 JKS-150 Type T JJN-05 JJN-10 JJN-15 JJN-20 JJN-25 JJN-30 JJN-50 JJN-60 JJN-60 JJN-80 JJN-125 JJN-125 Type RK1 5017906-005 5017906-010 5017906-015 5012406-020 5012406-025 5012406-030 5012406-050 5012406-050 5014006-063 5014006-080 2028220-125 2028220-125 2028220-150 2028220-200 2028220-250 Type RK1 KLN-R005 KLN-R10 KLN-R15 KLN-R20 KLN-R25 KLN-R30 KLN-R50 KLN-R60 KLN-R60 KLN-R80 KLN-R125 KLN-R125 L25S-150 L25S-200 L25S-250 Type CC ATM-R05 ATM-R10 ATM-R15 ATM-R20 ATM-R25 ATM-R30 A2K-60R A2K-80R A2K-125R A2K-125R A25X-150 A25X-200 A25X-250 Type RK1 A2K-05R A2K-10R A2K-15R A2K-20R A2K-25R A2K-30R A2K-50R A2K-50R A2K-60R A2K-80R A2K-125R A2K-125R A25X-150 A25X-200 A25X-250 Bussmann Bussmann Bussmann SIBA Littel fuse FerrazShawmut FerrazShawmut
5 5
Table 5.7 UL Fuses, 200-240V Frequency converter kW K37-1K1 1K5-2K2 3K0 4K0 5K5 7K5 11K 15K 18K 22K 30K 37K 45K 55K 75K 90K FerrazShawmut Type CC ATM-R6 ATM-R10 ATM-R16 ATM-R20 ATM-R25 ATM-R30 FerrazShawmut Type RK1 A6K-6R A6K-10R A6K-16R A6K-20R A6K-25R A6K-30R A6K-40R A6K-40R A6K-50R A6K-60R A6K-80R A6K-100R A6K-125R A6K-150R A50-P225 A50-P250
Bussmann
Bussmann
Bussmann
SIBA
Littel fuse
380-480V, 525-600V Type RK1 KTS-R6 KTS-R10 KTS-R15 KTS-R20 KTS-R25 KTS-R30 KTS-R40 KTS-R40 KTS-R50 KTS-R60 KTS-R80 KTS-R100 KTS-R125 KTS-R150 FWH-220 FWH-250 Type J JKS-6 JKS-10 JKS-15 JKS-20 JKS-25 JKS-30 JKS-40 JKS-40 JKS-50 JKS-60 JKS-80 JKS-100 JKS-150 JKS-150 Type T JJS-6 JJS-10 JJS-15 JJS-20 JJS-25 JJS-30 JJS-40 JJS-40 JJS-50 JJS-60 JJS-80 JJS-100 JJS-150 JJS-150 Type RK1 5017906-006 5017906-010 5017906-016 5017906-020 5017906-025 5012406-032 5014006-040 5014006-040 5014006-050 5014006-063 2028220-100 2028220-125 2028220-125 2028220-160 2028220-200 2028220-250 Type RK1 KLS-R6 KLS-R10 KLS-R16 KLS-R20 KLS-R25 KLS-R30 KLS-R40 KLS-R40 KLS-R50 KLS-R60 KLS-R80 KLS-R100 KLS-R125 KLS-R150 L50S-225 L50S-250
KTS-fuses from Bussmann may substitute KTN for 240V frequency converters. FWH-fuses from Bussmann may substitute FWX for 240V frequency converters. KLSR fuses from LITTEL FUSE may substitute KLNR fuses for 240V frequency converters. L50S fuses from LITTEL FUSE may substitute L50S fuses for 240V frequency converters. A6KR fuses from FERRAZ SHAWMUT may substitute A2KR for 240V frequency converters. A50X fuses from FERRAZ SHAWMUT may substitute A25X for 240V frequency converters.
95
How to Install
UL Compliance 380-480V, frame sizes D, E and F The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240V, or 480V, or 500V, or 600V depending on the drive voltage rating. With the proper fusing the drive Short Circuit Current Rating (SCCR) is 100,000 Arms.
Bussmann E1958 JFHR2** FWH300 FWH350 FWH400 FWH500 FWH600 Bussmann E4273 T/JDDZ** JJS300 JJS350 JJS400 JJS500 JJS600 SIBA E180276 JFHR2 2061032.315 2061032.35 2061032.40 2061032.50 2062032.63 LittelFuse E71611 JFHR2** L50S-300 L50S-350 L50S-400 L50S-500 L50S-600 FerrazShawmut E60314 JFHR2** A50-P300 A50-P350 A50-P400 A50-P500 A50-P600 Bussmann E4274 H/JDDZ** NOS300 NOS350 NOS400 NOS500 NOS600 Bussmann E125085 JFHR2* 170M3017 170M3018 170M4012 170M4014 170M4016 Internal Option Bussmann 170M3018 170M3018 170M4016 170M4016 170M4016
5 5
Table 5.9 Frame Size D, Line Fuses, 380-480V Size/ Type P315 P355 P400 P450 Bussma nn PN* 170M4 017 170M6 013 170M6 013 170M6 013 Bussmann PN* 170M8611 170M8611 170M6467 170M6467 170M8611 170M6467
Rating 1100A, 1000V 1100A, 1000V 1400A, 700V 1400A, 700V 1100A, 1000V 1400A, 700V
Siba 20 781 32.1000 20 781 32.1000 20 681 32.1400 20 681 32.1400 20 781 32.1000 20 681 32.1400
Table 5.10 Frame Size E, Line Fuses, 380-480V Internal Bussmann Option 170M7082 170M7082 170M7082 170M7082 170M7083 170M7083
Rating 1600A, 700V 1600A, 700V 2000A, 700V 2000A, 700V 2500A, 700V 2500A, 700V
Siba 20 695 32.1600 20 695 32.1600 20 695 32.2000 20 695 32.2000 20 695 32.2500 20 695 32.2500
*170M fuses from Bussmann shown use the -/80 visual indicator, -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and amperage may be substituted for external use **Any minimum 500V UL listed fuse with associated current rating may be used to meet UL requirements.
96
How to Install
Size/ Type Internal Option Bussmann 170M3015 170M3015 170M3015 170M3015 170M3018 170M3018 170M3018 170M5011 P800 170M5011 P900 170M5011 P1M0 170M5011 P1M2 P1M4 Siba 20 610 32.700 20 610 32.700 20 630 32.900 20 630 32.900 Size/Type P710 P710 P800 P900 P1M0 P1M2 P1M4
Rating 1600A, 700V 1600A, 700V 1600A, 700V 1600A, 700V 2000A, 700V 2500A, 700V
Siba 20 695 32.1600 20 695 32.1600 20 695 32.1600 20 695 32.1600 20 695 32.2000 20 695 32.2500
Size/ Type
Amps
P45K P55K P75K P90K P110 P132 P160 P200 P250 P315 P400
125 160 200 200 250 315 350 350 400 500 550
5 5
Table 5.15 Frame Size F, Line Fuses, 525-690V Bussmann PN* 170M8611 170M8611 170M8611 170M8611 170M8611 170M8611
Rating 1100A, 1000V 1100A, 1000V 1100A, 1000V 1100A, 1000V 1100A, 1000V 1100A, 1000V
Siba 20 781 32. 1000 20 781 32. 1000 20 781 32. 1000 20 781 32. 1000 20 781 32. 1000 20 781 32.1000
Table 5.13 Frame Size D, E and F 525-690V Size/ Type P450 P500 P560 P630 Bussman n PN* 170M401 7 170M401 7 170M601 3 170M601 3
*170M fuses from Bussmann shown use the -/80 visual indicator, -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and amperage may be substituted for external use. Suitable for use on a circuit capable of delivering not more than 100 000 rms symmetrical amperes, 500/600/690 Volts maximum when protected by the above fuses. Supplementary fuses
Frame size D, E and F Table 5.17 SMPS Fuse Bussmann PN* KTK-4 Rating 4 A, 600 V
97
How to Install
LittelFuse
Frame size F
Rating 30 A, 600 V
KLK-15 KLK-15
15A, 600 V 15A, 600 V Table 5.20 30 A Fuse Protected Terminal Fuse
Frame size Table 5.18 Fan Fuses Bussmann PN* 2.5-4.0 A LPJ-6 SP or SPI Alternative Fuses Any listed Class J Dual Element, Time Delay, 6A Any listed Class J Dual Element, Time Delay, 10 A Any listed Class J Dual Element, Time Delay, 10 A Any listed Class J Dual Element, Time Delay, 15 A Any listed Class J Dual Element, Time Delay, 15 A Any listed Class J Dual Element, Time Delay, 20A Any listed Class J Dual Element, Time Delay, 25 A Any listed Class J Dual Element, Time Delay, 20 A F Rating 6 A, 600 V
Rating 6 A, 600 V
5 5
Table 5.21 Control Transformer Fuse Frame size F Table 5.22 NAMUR Fuse Alternative Fuses Any listed Class CC, 6 A Bussmann PN* GMC-800MA Rating 800 mA, 250 V
P710P1M4, 525-690 V
Frame size F
Rating 6 A, 600 V
P500P1M0, 380-480 V
4.0-6.3 A
P710P1M4, 525-690 V
P500P1M0, 380-480 V
6.3 - 10 A
P710P1M4, 525-690 V
P500P1M0, 380-480 V
10 - 16 A
P710P1M4, 525-690 V
98
How to Install
130BT311.10
1. 2. 3. 4.
10 pole plug digital I/O. 3 pole plug RS485 Bus. 6 pole analog I/O. USB Connection.
1.
9 - 10 mm (0.37 in)
130BA150.10
2.
3.
130BT306.10
130BA012.11
130BT312.10
5 5
39
69
4
42
50
53
54
55
61
68
12
13
18
19
27
29
32
33
20
37
To remove the cable from the terminal: 1. Insert a screw driver1) in the square hole. 2.
1)
99
How to Install
1. 2.
Mount terminals from the accessory bag to the front of the frequency converter. Connect terminals 18 and 27 to +24 V (terminal 12/13)
12
13
18
19
27
29
32
33
20
37
5 5
Speed
100
130BA156.12
+24V
P 5 - 12 [6]
P 5 - 10[9]
How to Install
91 (L1) 92 (L2) 93 (L3) 95 PE 88 (-) 89 (+) 50 (+10 V OUT) S201 53 (A IN) 1 2 ON S202 1 2 ON 54 (A IN) ON=0-20mA OFF=0-10V Switch Mode Power Supply 24Vdc 15mA 200mA + + -
DC bus
5 5
03 02 01 240Vac, 2A
55 (COM A IN) 12 (+24V OUT) 13 (+24V OUT) 18 (D IN) 19 (D IN) 20 (COM D IN) 27 (D IN/OUT) 24V 0V 29 (D IN/OUT) 24V 0V 32 (D IN) 33 (D IN) * 37 (D IN) 24V (NPN) 0V (PNP) 24V (NPN) 0V (PNP) 24V (NPN) 0V (PNP) S801 RS-485 Interface 24V (NPN) 0V (PNP) S801 1 2 ON P 5-00 24V (NPN) 0V (PNP) 24V (NPN) 0V (PNP) relay2
06 05 04
240Vac, 2A 400Vac, 2A
ON=Terminated OFF=Open
5V
Very long control cables and analog signals may in rare cases and depending on installation result in 50/60 Hz earth loops due to noise from mains supply cables. If this occurs, you may have to break the screen or insert a 100 nF capacitor between screen and chassis. The digital and analog in- and outputs must be connected separately to the frequency converter common inputs (terminal 20, 55, 39) to avoid ground currents from both groups to affect other groups. For example, switching on the digital input may disturb the analog input signal.
NOTE
Control cables must be screened/armoured.
101
How to Install
See section entitled Earthing of Screened/Armoured Control Cables for the correct termination of control cables.
130BA681.10
A53 A54 U- I U- I
VLT
NOTE
It is recommended to only change switch position at power off.
102
N O
5 5
130BT310.10
1 2
1.
Use a clamp from the accessory bag to connect the screen to the frequency converter decoupling plate for control cables.
How to Install
Performing an AMA will ensure optimum performance. The AMA measures the values from the motor model equivalent diagram. 1. Connect terminal 27 to terminal 12 or set 5-12 Terminal 27 Digital Input to 'No function' (5-12 Terminal 27 Digital Input [0]) Activate the AMA 1-29 Automatic Motor Adaptation (AMA). Choose between complete or reduced AMA. If an LC filter is mounted, run only the reduced AMA, or remove the LC filter during the AMA procedure. Press the [OK] key. The display shows Press [Hand on] to start. Press the [Hand on] key. A progress bar indicates if the AMA is in progress.
2. 3.
4. 5.
5 5
Stop the AMA during operation 1. Press the [OFF] key - the frequency converter enters into alarm mode and the display shows that the AMA was terminated by the user.
Successful AMA 1. 2. The display shows Press [OK] to finish AMA. Press the [OK] key to exit the AMA state.
Unsuccessful AMA 1. The frequency converter enters into alarm mode. A description of the alarm can be found in the Troubleshooting section. "Report Value in the [Alarm Log] shows the last measuring sequence carried out by the AMA, before the frequency converter entered alarm mode. This number along with the description of the alarm will assist you in troubleshooting. If you contact Danfoss Service, make sure to mention number and alarm description.
2.
Unsuccessful AMA is often caused by incorrectly registered motor name plate data or too big difference between the motor power size and the frequency converter power size. Step 4. Set speed limit and ramp time
Y 50 3,6 V Hz A
1,7L B IP 65 H1/1A
103
How to Install
4-11 Motor Speed Low Limit [RPM] or 4-12 Motor Speed Low Limit [Hz] 4-13 Motor Speed High Limit [RPM] or 4-14 Motor Speed High Limit [Hz]
5 5
104
How to Install
5 5
F OF
Frame size A5 B1 B2
Type Kraus&Naimer KG20A T303 Kraus&Naimer KG64 T303 Kraus&Naimer KG64 T303
Terminal connections
130BB182.10 L1 L2 L3 31 43
T1
T2
T3
32
44
C1 C1 C2 C2
37 kW 45-55 kW 75 kW 90 kW
T1
T2
T3
14
105
130BB181.10
L1
L2
L3
13
How to Install
A KLIXON switch must be installed that is `normally closed'. If this function is not used, 106 and 104 must be short-circuited together. Normally closed: 104-106 (factory installed jumper) Normally open: 104-105
Terminal No. 106, 104, 105 Function Brake resistor temperature switch.
NOTE
If the temperature of the brake resistor gets too high and the thermal switch drops out, the frequency converter will stop braking. The motor will start coasting.
175ZA877.10 106 NC 104 C 105 NO
5 5
The connector located on the power card provides the connection of line voltage for the cooling fans. The fans are connected from factory to be supplied form a common AC line (jumpers between 100-102 and 101-103). If external supply is needed, the jumpers are removed and the supply is connected to terminals 100 and 101. A 5 Amp fuse should be used for protection. In UL applications this should be LittleFuse KLK-5 or equivalent.
Relay 2
Terminal 01: common Terminal 02: normal open 240V AC Terminal 03: normal closed 240V AC
Terminal 04: common Terminal 05: normal open 400V AC Terminal 06: normal closed 240V AC
106
How to Install
Additional relay outputs can be added to the frequency converter by using option module MCB 105.
130BA047.10
relay1 03
130BA170.10
Relay 1 and relay 2 are programmed in 5-40 Function Relay, 5-41 On Delay, Relay, and 5-42 Off Delay, Relay.
240Vac, 2A 02
5 5
01
relay2 06 240Vac, 2A
LC lter
05 400Vac, 2A
04
107
How to Install
5 5
96
97
98
96
97
98
108
How to Install
5.
Use an insulated bearing as recommended by the motor manufacturer (note: Motors from reputable manufacturers will typically have these fitted as standard in motors of this size)
If found to be necessary and after consultation with Danfoss: 6. Lower the IGBT switching frequency 7. 8. 9. 10. Modify the inverter waveform, 60 AVM vs. SFAVM Install a shaft grounding system or use an isolating coupling between motor and load Use minimum speed settings if possible Use a dU/dt or sinus filter
NOTE
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. The USB connection is connected to protection earth on the frequency converter. Use only an isolated laptop as PC connection to the USB connector on the frequency converter.
130BT308.11
5 5
Illustration 5.24 For control cable connections, see section on Control Terminals.
In order to avoid potential equalizing currents in the screen, earth the cable screen via terminal 61, which is connected to the frame via an RC-link. Bus termination The RS-485 bus must be terminated by a resistor network at both ends. For this purpose, set switch S801 on the control card for "ON". For more information, see the paragraph Switches S201, S202, and S801. Communication protocol must be set to 8-30 Protocol.
PC-based Configuration Tool MCT 10 Set-up Software All frequency converters are equipped with a serial communication port. Danfoss provides a PC tool for communication between PC and frequency converter, PCbased Configuration Tool MCT 10 Set-up Software. MCT 10 Set-up Software MCT 10 Set-up Software has been designed as an easy to use interactive tool for setting parameters in our frequency converters. The PC-based Configuration Tool MCT 10 Set-up Software will be useful for:
Planning a communication network off-line. MCT 10 Set-up Software contains a complete frequency converter database Commissioning frequency converters on line
109
How to Install
Saving settings for all frequency converters Replacing a frequency converter in a network Expanding an existing network Future developed drives will be supported
Ordering number: Please order the CD containing the PC-based Configuration Tool MCT 10 Set-up Software using code number 130B1000. MCT 10 Set-up Software can also be downloaded from the Danfoss Internet: http://www.danfoss.com/BusinessAreas/ DrivesSolutions/Softwaredownload/DDPC+Software +Program.htm.
5 5
The PC-based Configuration Tool MCT 10 Set-up Software supports Profibus DP-V1 via a Master class 2 connection. It makes it possible to on line read/write parameters in a frequency converter via the Profibus network. This will eliminate the need for an extra communication network. See Operating Instructions, MG.33.Cx.yy and MN.90.Ex.yy for more information about the features supported by the Profibus DP V1 functions. Save Drive Settings: 1. Connect a PC to the unit via USB com port 2. 3. 4. Open PC-based Configuration Tool MCT 10 Set-up Software Choose Read from drive Choose Save as
5.5.3 MCT 31
MCT 31 The MCT 31 harmonic calculation PC tool enables easy estimation of the harmonic distortion in a given application. Both the harmonic distortion of Danfoss frequency converters as well as non-Danfoss frequency converters with different additional harmonic reduction devices, such as Danfoss AHF filters and 12-18-pulse rectifiers, can be calculated. Ordering number: Please order your CD containing the MCT 31 PC tool using code number 130B1031. MCT 31 can also be downloaded from the Danfoss Internet: http://www.danfoss.com/BusinessAreas/DrivesSolutions/ Softwaredownload/DDPC+Software+Program.htm.
All parameters are now stored in the PC. Load Drive Settings: 1. Connect a PC to the unit via USB com port 2. 3. 4. 5. Open PC-based Configuration Tool MCT 10 Set-up Software Choose Open stored files will be shown Open the appropriate file Choose Write to drive
All parameter settings are now transferred to the frequency converter. A separate manual for PC-based Configuration Tool MCT 10 Set-up Software is available. The PC-based Configuration Tool MCT 10 Set-up Software modules The following modules are included in the software package:
MCT 10 Set-up Software Setting parameters Copy to and from frequency converters Documentation and print out of parameter settings incl. diagrams Ext. User Interface Preventive Maintenance Schedule Clock settings Timed Action Programming Smart Logic Controller Set-up
110
How to Install
WARNING
When running high voltage tests of the entire installation, interrupt the mains and motor connection if the leakage currents are too high.
Installations using rigid metal conduits are not required to use screened cable, but the motor cable must be installed in conduit separate from the control and mains cables. Full connection of the conduit from the drive to the motor is required. The EMC performance of flexible conduits varies a lot and information from the manufacturer must be obtained. Connect the screen/armour/conduit to earth at both ends for motor cables as well as for control cables. In some cases, it is not possible to connect the screen in both ends. If so, connect the screen at the frequency converter. See also Earthing of Braided Screened/Armoured Control Cables. Avoid terminating the screen/armour with twisted ends (pigtails). It increases the high frequency impedance of the screen, which reduces its effectiveness at high frequencies. Use low impedance cable clamps or EMC cable glands instead. Avoid using unscreened/unarmoured motor or control cables inside cabinets housing the drive(s), whenever this can be avoided.
5 5
WARNING
The earth leakage current from the frequency converter exceeds 3.5 mA. To ensure a good mechanical connection from the earth cable to the earth connection (terminal 95), the cable cross-section must be at least 10 mm2 or 2 rated earth wires terminated separately.
Leave the screen as close to the connectors as possible. Illustration 5.25 shows an example of an EMC-correct electrical installation of an IP 20 frequency converter. The frequency converter is fitted in an installation cabinet with an output contactor and connected to a PLC, which is installed in a separate cabinet. Other ways of doing the installation may have just as good an EMC performance, provided the above guide lines to engineering practice are followed. If the installation is not carried out according to the guideline and if unscreened cables and control wires are used, some emission requirements are not complied with, although the immunity requirements are fulfilled. See the paragraph EMC test results.
111
How to Install
PLC etc.
Panel
5 5
Min. 200mm between control cables, motor cable and mains cable
Motor cable
L3 N PE F1
130BA175.11
L1 L2
91 92 93 95 L1 L2 L3 PE
12 37 18 50 53 55 54 Transmitter
V W PE
96 97 98 99
M 3
112
130BA048.13
How to Install
The contact resistance between the individual screen conductors. The screen coverage, i.e. the physical area of the cable covered by the screen - often stated as a percentage value. Screen type, i.e. braided or twisted pattern. Aluminium-clad with copper wire. Twisted copper wire or armoured steel wire cable. Single-layer braided copper wire with varying percentage screen coverage. This is the typical Danfoss reference cable. Double-layer braided copper wire. Twin layer of braided copper wire with a magnetic, screened/armoured intermediate layer. Cable that runs in copper tube or steel tube. Lead cable with 1.1mm wall thickness.
a. b. c.
d 1 10 10 10 e
175ZA166.13
Transfer impedance (ZT) can be assessed on the basis of the following factors: The conductibility of the screen material.
5 5
d. e. f. g.
0,01
0,1
10
100 MHz g
113
How to Install
FC
Generally speaking, control cables must be braided screened/armoured and the screen must be connected by means of a cable clamp at both ends to the metal cabinet of the unit.
PLC etc.
PE
PE
The drawing below indicates how correct earthing is carried out and what to do if in doubt. a. Correct earthing Control cables and cables for serial communication must be fitted with cable clamps at both ends to ensure the best possible electrical contact. Wrong earthing Do not use twisted cable ends (pigtails). They increase the screen impedance at high frequencies. Protection with respect to earth potential between PLC and frequency converter If the earth potential between the frequency converter and the PLC (etc.) is different, electric noise may occur that will disturb the entire system. Solve this problem by fitting an equalising cable, next to the control cable. Minimum cable crosssection: 16 mm 2. For 50/60 Hz earth loops If very long control cables are used, 50/60 Hz earth loops may occur. Solve this problem by connecting one end of the screen to earth via a 100nF capacitor (keeping leads short). Cables for serial communication Eliminate low-frequency noise currents between two frequency converters by connecting one end of the screen to terminal 61. This terminal is connected to earth via an internal RC link. Use twisted-pair cables to reduce the differential mode interference between the conductors.
PE PE PE PE Min. 16mm2 Equalizing cable PLC etc.
FC
5 5
PE
PE
PLC etc. FC
b.
c.
FC
d.
PE 100nF
PE
FC
FC
e.
69 68 61 PE
68 69
114
130BA051.11
PLC etc.
Application Examples
6 Application Examples
6.1.1 Start/Stop
Terminal 18 = start/stop 5-10 Terminal 18 Digital Input [8] Start Terminal 27 = No operation 5-12 Terminal 27 Digital Input [0] No operation (Default coast inverse 5-10 Terminal 18 Digital Input = Start (default) 5-12 Terminal 27 Digital Input = coast inverse (default)
130BA155.12 P 5-10 [8] P 5-12 [0] +24V +24V
6 6
12 13 18 19 27 29 32 33 20 37
12
13
18
19
27
29
32
33
20
37
Start/Stop
Safe Stop
Speed
Start
Stop inverse
Safe Stop
Illustration 6.1 Terminal 37: Available only with Safe Stop Function!
Illustration 6.2 Terminal 37: Available only with Safe Stop Function
115
Application Examples
current of the frequency converter. AMA can be carried out on up to one oversize motor.
It is possible to carry out a reduced AMA test with a Sine-wave filter installed. Avoid carrying out a complete AMA with a Sine-wave filter. If an overall setting is required, remove the Sine-wave filter while running a total AMA. After completion of the AMA, reinsert the Sine-wave filter. If motors are coupled in parallel, use only reduced AMA if any. Avoid running a complete AMA when using synchronous motors. If synchronous motors are applied, run a reduced AMA and manually set the extended motor data. The AMA function does not apply to permanent magnet motors. The frequency converter does not produce motor torque during an AMA. During an AMA, it is imperative that the application does not force the motor shaft to run, which is known to happen with e.g. wind milling in ventilation systems. This disturbs the AMA function.
6 6
39 42 50 53 54 55
1 kW
For the best adjustment of the frequency converter, carry out AMA on a cold motor. Repeated AMA runs may lead to a heating of the motor, which results in an increase of the stator resistance, Rs. Normally, this is not critical. AMA can only be carried out if the rated motor current is minimum 35% of the rated output
116
Application Examples
It is possible to program from 0 to 20 events and actions. When the last event / action has been executed, the sequence starts over again from event [1] / action [1]. The illustration shows an example with three events / actions:
130BA062.13
6 6
State 2
State 3
Term 18 P 5-10(start)
Set the ramping times in 3-41 Ramp 1 Ramp Up Time and 3-42 Ramp 1 Ramp Down Time to the wanted times
tramp = tacc nnorm ( par . 1 25) ref RPM
Set term 27 to No Operation (5-12 Terminal 27 Digital Input) Set Preset reference 0 to first preset speed (3-10 Preset Reference [0]) in percentage of Max reference speed (3-03 Maximum Reference). Ex.: 60% Set preset reference 1 to second preset speed (3-10 Preset Reference [1] Ex.: 0 % (zero). Set the timer 0 for constant running speed in 13-20 SL Controller Timer [0]. Ex.: 2 sec.
Set Event 1 in 13-51 SL Controller Event [1] to True [1] Set Event 2 in 13-51 SL Controller Event [2] to On Reference [4] Set Event 3 in 13-51 SL Controller Event [3] to Time Out 0 [30] Set Event 4 in 13-51 SL Controller Event [4] to False [0] Set Action 1 in 13-52 SL Controller Action [1] to Select preset 0 [10] Set Action 2 in 13-52 SL Controller Action [2] to Start Timer 0 [29] Set Action 3 in 13-52 SL Controller Action [3] to Select preset 1 [11] Set Action 4 in 13-52 SL Controller Action [4] to No Action [1]
117
Application Examples
Start command
State 0 Stop command Event 2 On Reference (4) Action 2 Start Timer (29)
State 1
6 6
State 2
Set the Smart Logic Control in 13-00 SL Controller Mode to ON. Start / stop command is applied on terminal 18. If stop signal is applied the frequency converter will ramp down and go into free mode.
In the BASIC Cascade Controller the frequency converter controls a variable speed motor as the variable speed pump (lead) and can stage up to two additional constant speed pumps on and off. By varying the speed of the initial pump, variable speed control of the entire system is provided. This maintains constant pressure while eliminating pressure surges, resulting in reduced system stress and quieter operation in pumping systems. Fixed Lead Pump The motors must be of equal size. The BASIC Cascade Controller allows the frequency converter to control up to 3 equal size pumps using the drives two built-in relays. When the variable pump (lead) is connected directly to the frequency converter, the other 2 pumps are controlled by the two built-in relays. When lead pump alternations is enabled, pumps are connected to the built-in relays and the frequency converter is capable of operating 2 pumps. Lead Pump Alternation The motors must be of equal size. This function makes it possible to cycle the frequency converter between the pumps in the system (maximum of 2 pumps). In this operation the run time between pumps is equalized reducing the required pump maintenance and increasing reliability and lifetime of the system. The alternation of the lead pump can take place at a command signal or at staging (adding another pump). The command can be a manual alternation or an alternation event signal. If the alternation event is selected, the lead pump alternation takes place every time the event occurs. Selections include whenever an alternation timer expires, at a predefined time of day or when the lead pump goes into
Pressure Sensor
Motor starter
The BASIC Cascade Controller is used for pump applications where a certain pressure (head) or level needs to be maintained over a wide dynamic range. Running a large pump at variable speed over a wide for range is not an ideal solution because of low pump efficiency and because there is a practical limit of about 25% rated full load speed for running a pump.
118
130BA148.11
Application Examples
sleep mode. Staging is determined by the actual system load. A separate parameter limits alternation only to take place if total capacity required is > 50%. Total pump capacity is determined as lead pump plus fixed speed pumps capacities. Bandwidth Management In cascade control systems, to avoid frequent switching of fixed speed pumps, the desired system pressure is kept within a bandwidth rather than at a constant level. The Staging Bandwidth provides the required bandwidth for operation. When a large and quick change in system pressure occurs, the Override Bandwidth overrides the Staging Bandwidth to prevent immediate response to a short duration pressure change. An Override Bandwidth Timer can be programmed to prevent staging until the system pressure has stabilized and normal control established. When the Cascade Controller is enabled and running normally and the frequency converter issues a trip alarm, the system head is maintained by staging and destaging fixed speed pumps. To prevent frequent staging and destaging and minimize pressure fluxuations, a wider Fixed Speed Bandwidth is used instead of the Staging bandwidth.
the fixed speed pump will be cut out (de-staged). The lead pump continues to ramp up and then ramps down to a stop and the two relays are cut out. After a time delay, the relay for the fixed speed pump cuts in (staged) and this pump becomes the new lead pump. The new lead pump ramps up to maximum speed and then down to minimum speed when ramping down and reaching the staging frequency, the old lead pump is now cut in (staged) on the mains as the new fixed speed pump. If the lead pump has been running at minimum frequency (fmin) for a programmed amount of time, with a fixed speed pump running, the lead pump contributes little to the system. When the programmed value of the timer expires, the lead pump is removed, avoiding a deal heat water circulation problem.
6 6
Pumps Status, is a read out of the status for the relays assigned to each pump. The display shows pumps that are disabled, off, running on the frequency converter or running on the mains/ motor starter. Cascade Status, is a read out of the status for the Cascade Controller. The display shows the Cascade Controller is disabled, all pumps are off, and emergency has stopped all pumps, all pumps are running, fixed speed pumps are being staged/destaged and lead pump alternation is occurring. De-stage at No-Flow ensures that all fixed speed pumps are stopped individually until the no-flow status disappears.
With lead pump alternation enabled, a maximum of two pumps are controlled. At an alternation command, the lead pump will ramp to minimum frequency (fmin) and after a delay will ramp to maximum frequency (fmax). When the speed of the lead pump reaches the destaging frequency,
119
Application Examples
Power Section
RELAY 1
6 6
R1 R2
RELAY 2
k3 k2 K1
k3 k1 K2 K3
K1 K4
K1 K3 K4
Every pump must be connected to two contactors (K1/K2 and K3/K4) with a mechanical interlock. Thermal relays or other motor protection devices must be applied according to local regulation and/or individual demands.
RELAY 1 (R1) and RELAY 2 (R2) are the built-in relays in the frequency converter. When all relays are de-energized, the first built in relay to be energized will cut in the contactor corresponding to the pump controlled by the relay. E.g. RELAY 1 cuts in contactor K1, which becomes the lead pump. K1 blocks for K2 via the mechanical interlock preventing mains to be connected to the output of the frequency converter (via K1). Auxiliary break contact on K1 prevents K3 to cut in. RELAY 2 controls contactor K4 for on/off control of the fixed speed pump. At alternation both relays de-energizes and now RELAY 2 will be energized as the first relay.
120
Application Examples
Power Card
RELAY 2 (cascade pump 2.) RELAY 1 (cascade pump 1.)
Control Card
D IN1/D OUT (Safety Interlock) A IN1 A IN2 (Feedback 1 res.) D IN1/D OUT COM A OUT
+ 24V OUT
+ 10V OUT
+24V OUT
COM D IN
MOTOR 96 U 97 V 98 W PE 91 L1
MAINS 92 L2 93 L3 01 02 03 04 05 06
12
13
18
19
27
29
32
33
20
39
42
50
53
54
55
COM A IN
A OUT1
D IN 1 (Start)
D IN 1
D IN 1
D IN1
6 6
L1 L2 L3 PE
Ramps up (if stopped and there is a demand) Staging (if stopped and there is a demand)
Off Auto On
Ramps down
Starts and stops according to commands via Staging/Destaging terminals or serial bus
121
7.1.1 Overview
RS-485 is a two-wire bus interface compatible with multidrop network topology, i.e. nodes can be connected as a bus, or via drop cables from a common trunk line. A total of 32 nodes can be connected to one network segment. Repeaters divide network segments. Please note that each repeater functions as a node within the segment in which it is installed. Each node connected within a given network must have a unique node address, across all segments. Terminate each segment at both ends, using either the termination switch (S801) of the frequency converters or a biased termination resistor network. Always use screened twisted pair (STP) cable for bus cabling, and always follow good common installation practice. Low-impedance earth connection of the screen at every node is important, including at high frequencies. Thus, connect a large surface of the screen to earth, for example with a cable clamp or a conductive cable gland. It may be necessary to apply potential-equalizing cables to maintain the same earth potential throughout the network. Particularly in installations with long cables. To prevent impedance mismatch, always use the same type of cable throughout the entire network. When connecting a motor to the frequency converter, always use screened motor cable.
Cable: Screened twisted pair (STP) Impedance: 120 Cable length: Max. 1200m (including drop lines) Max. 500m station-to-station
7 7
61 68 69
39
42
50
53
54
55
NOTE
Screened, twisted-pair cables are recommended in order to reduce noise between conductors.
122
130BB021.10
ON S801 1 2
The RS-485 communication cable must be kept away from motor and brake resistor cables to avoid coupling of high frequency noise from one cable to another. Normally a distance of 200mm (8 inches) is sufficient, but keeping the greatest possible distance between the cables is generally recommended, especially where cables run in parallel over long distances. When crossing is unavoidable, the RS-485 cable must cross motor and brake resistor cables at an angle of 90 degrees.
130BA080.10
Fieldbus cable
7 7
Min.200mm
90 crossing
Brake resistor
123
The physical layer is RS-485, thus utilizing the RS-485 port built into the frequency converter. The FC protocol supports different telegram formats:
control options, including controlling the setpoint of the frequency converter when its internal PID controller is used.
A short format of 8 bytes for process data. A long format of 16 bytes that also includes a parameter channel. A format used for texts.
7 7
Start Stop of the frequency converter in various ways: Coast stop Quick stop DC Brake stop Normal (ramp) stop Reset after a fault trip Run at a variety of preset speeds Run in reverse Change of the active set-up Control of the two relays built into the frequency converter
The Bus Reference is commonly used for speed control. It is also possible to access the parameters, read their values, and where possible, write values to them. This permits a range of
Start bit
A number of data bytes (variable, depending on the type of telegram) follows. A data control byte (BCC) completes the telegram.
195NA099.10
STX
LGE
ADR
DATA
BCC
124
The 10 represents the fixed characters, while the n is variable (depending on the length of the text).
7 7
STX
LGE
ADR
PCD1
PCD2
BCC
125
Parameter block The parameter block is used to transfer parameters between master and slave. The data block is made up of 12 bytes (6 words) and also contains the process block.
STX LGE ADR PKE IND
PWEhigh
PWElow
PCD1
PCD2
BCC
Text block The text block is used to read or write texts via the data block.
STX LGE ADR PKE IND Ch1 Ch2 Chn PCD1 PCD2 BCC 130BA270.10
7 7
PKE
IND
PWEhigh
PWElow
AK 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
PNU
Bits no. 12-15 transfer parameter commands from master to slave and return processed slave responses to the master.
Parameter commands master slave Bit no. 15 0 0 0 0 1 1 1 14 0 0 0 0 1 1 1 13 0 0 1 1 0 1 1 12 0 1 0 1 1 0 1 No command Read parameter value Write parameter value in RAM (word) Write parameter value in RAM (double word) Write parameter value in RAM and EEprom (double word) Write parameter value in RAM and EEprom (word) Read/write text Parameter command
Parameter number
126
130BA271.10
Response slave master Bit no. 15 0 0 0 0 1 14 0 0 0 1 1 13 0 0 1 1 1 12 0 1 0 1 1 No response Parameter value transferred (word) Parameter value transferred (double word) Command cannot be performed text transferred Response
If the command cannot be performed, the slave sends this response: 0111 Command cannot be performed - and issues the following fault report in the parameter value (PWE):
PWE low (Hex) 0 1 2 3 4 5 11 82 83 Fault Report The parameter number used does not exit There is no write access to the defined parameter Data value exceeds the parameter's limits The sub index used does not exit The parameter is not the array type The data type does not match the defined parameter Data change in the defined parameter is not possible in the frequency converter's present mode. Certain parameters can only be changed when the motor is turned off There is no bus access to the defined parameter Data change is not possible because factory setup is selected
7 7
corresponds to Danish, select the data value by entering the value in the PWE block. See Example - Selecting a data value. Serial communication is only capable of reading parameters containing data type 9 (text string). 15-40 FC Type to 15-53 Power Card Serial Number contain data type 9. For example, read the unit size and mains voltage range in 15-40 FC Type. When a text string is transferred (read), the length of the telegram is variable, and the texts are of different lengths. The telegram length is defined in the second byte of the telegram, LGE. When using text transfer the index character indicates whether it is a read or a write command. To read a text via the PWE block, set the parameter command (AK) to F Hex. The index character high-byte must be 4. Some parameters contain text that can be written to via the serial bus. To write a text via the PWE block, set the parameter command (AK) to F Hex. The index characters high-byte must be 5.
130BA275.10 PKE Read text Write text Fx xx Fx xx IND 04 00 05 00 PWE high PWE low
127
Conversion factor
1000000 100000 10000 1000 100 10 1 0.1 0.01 0.001 0.0001 0.00001 0.000001 0.0000001
7 7
7.4.12 Conversion
The various attributes of each parameter are displayed in the section Factory Settings. Parameter values are transferred as whole numbers only. Conversion factors are therefore used to transfer decimals. 4-12 Motor Speed Low Limit [Hz] has a conversion factor of 0.1. To preset the minimum frequency to 10 Hz, transfer the value 100. A conversion factor of 0.1 means that the value transferred is multiplied by 0.1. The value 100 is thus perceived as 10.0. Examples: 0s --> conversion index 0 0.00s --> conversion index -2 0ms --> conversion index -3 0.00ms --> conversion index -5
E19E PKE
H 0000 IND
128
NOTE
4-14 Motor Speed High Limit [Hz] is a single word, and the parameter command for write in EEPROM is E. Parameter number 4-14 is 19E in hexadecimal. The response from the slave to the master will be:
130BA093.10
119E PKE
H 0000 IND
7 7
1155 PKE
H 0000 IND
If the value in 3-41 Ramp 1 Ramp Up Time is 10 s, the response from the slave to the master will be:
130BA267.10
1155 PKE
H 0000 IND
3E8 Hex corresponds to 1000 decimal. The conversion index for 3-41 Ramp 1 Ramp Up Time is -2, i.e. 0.01. 3-41 Ramp 1 Ramp Up Time is of the type Unsigned 32.
Start Stop of the frequency converter in various ways: Coast stop Quick stop
129
Reset after a fault trip Run at a variety of preset speeds Run in reverse Change the active set-up Control the frequency converters built-in relay
The Bus Reference is commonly used for speed control. It is also possible to access the parameters, read their values, and where possible, write values to them. This permits a range of control options, including controlling the setpoint of the frequency converter when its internal PI controller is used.
7 7
7.8 Modbus RTU Message Framing Structure 7.8.1 Frequency Converter with Modbus RTU
The controllers are set up to communicate on the Modbus network using RTU (Remote Terminal Unit) mode, with each byte in a message containing 2 4-bit hexadecimal characters. The format for each byte is shown below.
Start bit Data byte Stop/ parity Stop
The address field of a message frame contains 8 bits. Valid slave device addresses are in the range of 0 247 decimal. The individual slave devices are assigned addresses in the range of 1 247. (0 is reserved for broadcast mode, which all slaves recognize.) A master addresses a slave by placing the slave address in the address field of the message. When the slave sends its response, it places its own address in this address field to let the master know which slave is responding.
130
This tells the master what kind of error occurred, or the reason for the exception. Please also refer to the sections Function Codes Supported by Modbus RTU and Exception Codes.
7 7
131
Holding register 40001 is addressed as register 0000 in the data address field of the message. The function code field already specifies a holding register operation. Therefore, the 4XXXX reference is implicit. Holding register 40108 is addressed as register 006BHEX (107 decimal).
Signal Direction Master to slave Master to slave Slave to master Slave to master Master to slave
7 7
132
Holding registers Register Number 00001-00006 00007 00008 00009 00010-00990 01000-01990 02000-02990 03000-03990 04000-04990 ... 49000-49990 50000 50010 ... 50200 50210 Description Reserved Last error code from an FC data object interface Reserved Parameter index* 000 parameter group (parameters 001 through 099) 100 parameter group (parameters 100 through 199) 200 parameter group (parameters 200 through 299) 300 parameter group (parameters 300 through 399) 400 parameter group (parameters 400 through 499) ... 4900 parameter group (parameters 4900 through 4999) Input data: frequency converter control word register (CTW). Input data: Bus reference register (REF). ... Output data: frequency converter status word register (STW). Output data: frequency converter main actual value register (MAV).
7 7
* Used to specify the index number to be used when accessing an indexed parameter.
Diagnostic 8 s
Restart communication Return diagnostic register Clear counters and diagnostic register Return bus message count Return bus communication error count Return bus exception error count Return slave message count
11 12 13 14
Illegal function The function code received in the query is not an allowable action for the server (or slave). This may be because the function code is only applicable to newer devices, and was not implemented in the unit selected. It could also indicate that the server (or slave) is in the wrong state to process a request of this type, for example because it is not configured and is being asked to return register values.
133
7 7
4 Slave device failure
7.10 Examples
The following examples illustrate various Modbus RTU commands. If an error occurs, please refer to the Exception Codes section.
7.9.3 IND
The array index is set in Holding Register 9 and used when accessing array parameters.
134
Field Name Slave Address Function Starting Address HI Starting Address LO No. of Points HI No. of Points LO Error Check (CRC)
Example (HEX) 01 (frequency converter address) 01 (read coils) 00 20 (32 decimals) Coil 33 00 10 (16 decimals) -
Response The normal response is an echo of the query, returned after the coil state has been forced.
Field Name Slave Address Function Force Data HI Force Data LO Quantity of Coils HI Quantity of Coils LO Error Check (CRC) Example (HEX) 01 05 FF 00 00 01 -
Response The coil status in the response message is packed as one coil per bit of the data field. Status is indicated as: 1 = ON; 0 = OFF. The LSB of the first data byte contains the coil addressed in the query. The other coils follow toward the high order end of this byte, and from low order to high order in subsequent bytes. If the returned coil quantity is not a multiple of eight, the remaining bits in the final data byte will be padded with zeros (toward the high order end of the byte). The Byte Count field specifies the number of complete bytes of data.
Field Name Slave Address Function Byte Count Data (Coils 40-33) Data (Coils 48-41) Error Check (CRC) Example (HEX) 01 (frequency converter address) 01 (read coils) 02 (2 bytes of data) 07 06 (STW=0607hex) -
7 7
NOTE
Coil addresses start at zero, i.e. coil 17 is addressed as 16.
Field Name Slave Address Function Coil Address HI Coil Address LO Quantity of Coils HI Quantity of Coils LO Byte Count Force Data HI (Coils 8-1) Force Data LO (Coils 10-9) Error Check (CRC) Example (HEX) 01 (frequency converter address) 0F (write multiple coils) 00 10 (coil address 17) 00 10 (16 coils) 02 20 00 (ref. = 2000hex) -
NOTE
Coils and registers are addressed explicit with an off-set of -1 in Modbus. I.e. Coil 33 is addressed as Coil 32.
Response The normal response returns the slave address, function code, starting address, and quantity of coiles forced.
Field Name Slave Address Function Coil Address HI Coil Address LO Quantity of Coils HI Quantity of Coils LO Error Check (CRC) Example (HEX) 01 (frequency converter address) 0F (write multiple coils) 00 10 (coil address 17) 00 10 (16 coils) -
135
Response Response The normal response is an echo of the query, returned after the register contents have been passed.
Field Name Slave Address Function Register Address HI Register Address LO Preset Data HI Preset Data LO Error Check (CRC) Example (HEX) 01 06 03 E7 00 01 -
7 7
Response The register data in the response message are packed as two bytes per register, with the binary contents right justified within each byte. For each register, the first byte contains the high order bits and the second contains the low order bits. Example: Hex 0016E360 = 1.500.000 = 1500 RPM.
Field Name Slave Address Function Byte Count Data HI (Register 3030) Data LO (Register 3030) Data HI (Register 3031) Data LO (Register 3031) Error Check (CRC) Example (HEX) 01 03 04 00 16 E3 60 -
136
Response The normal response returns the slave address, function code, starting address, and quantity of registers preset.
Field Name Slave Address Function Starting Address HI Starting Address LO No. of Registers HI No. of registers LO Error Check (CRC) Example (HEX) 01 10 04 19 00 02 -
Parameter 3-10 Preset Reference [0] 3-10 Preset Reference [1] 3-10 Preset Reference [2] 3-10 Preset Reference [3]
Bit 01 0 0 1 1
Bit 00 0 1 0 1
NOTE
Make a selection in 8-56 Preset Reference Select to define how Bit 00/01 gates with the corresponding function on the digital inputs. Bit 02, DC brake: Bit 02 = 0 leads to DC braking and stop. Set braking current and duration in 2-01 DC Brake Current and 2-02 DC Braking Time. Bit 02 = 1 leads to ramping. Bit 03, Coasting: Bit 03 = 0: The frequency converter immediately "lets go" of the motor, (the output transistors are "shut off") and it coasts to a standstill. Bit 03 = 1: The frequency converter starts the motor if the other starting conditions are met. Make a selection in 8-50 Coasting Select to define how Bit 03 gates with the corresponding function on a digital input. Bit 04, Quick stop: Bit 04 = 0: Makes the motor speed ramp down to stop (set in 3-81 Quick Stop Ramp Time). Bit 05, Hold output frequency Bit 05 = 0: The present output frequency (in Hz) freezes. Change the frozen output frequency only by means of the digital inputs (5-10 Terminal 18 Digital Input to 5-15 Terminal 33 Digital Input) programmed to Speed up and Slow down.
7.11 Danfoss FC Control Profile 7.11.1 Control Word According to FC Profile (8-10 Control Profile = FC profile)
130BA274.10 Master-slave CTW Speed ref.
7 7
Bit no.:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Bit 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
Bit value = 0 Reference value Reference value DC brake Coasting Quick stop Hold output frequency Ramp stop No function No function Ramp 1 Data invalid No function No function Parameter set-up Parameter set-up No function
Bit value = 1 external selection lsb external selection msb Ramp No coasting Ramp use ramp Start Reset Jog Ramp 2 Data valid Relay 01 active Relay 02 active selection lsb selection msb Reverse
NOTE
If Freeze output is active, the frequency converter can only be stopped by the following:
Explanation of the Control Bits Bits 00/01 Bits 00 and 01 are used to choose between the four reference values, which are pre-programmed in 3-10 Preset Reference according to the following table:
Bit 03 Coasting stop Bit 02 DC braking Digital input (5-10 Terminal 18 Digital Input to 5-15 Terminal 33 Digital Input) programmed to DC braking, Coasting stop, or Reset and coasting stop.
Bit 06, Ramp stop/start: Bit 06 = 0: Causes a stop and makes the motor speed ramp down to stop via the selected ramp down parameter. Bit 06
137
= 1: Permits the frequency converter to start the motor, if the other starting conditions are met. Make a selection in 8-53 Start Select to define how Bit 06 Ramp stop/start gates with the corresponding function on a digital input. Bit 07, Reset: Bit 07 = 0: No reset. Bit 07 = 1: Resets a trip. Reset is activated on the signals leading edge, i.e. when changing from logic 0 to logic 1. Bit 08, Jog: Bit 08 = 1: The output frequency is determined by 3-19 Jog Speed [RPM]. Bit 09, Selection of ramp 1/2: Bit 09 = "0": Ramp 1 is active (3-41 Ramp 1 Ramp Up Time to 3-42 Ramp 1 Ramp Down Time). Bit 09 = "1": Ramp 2 (3-51 Ramp 2 Ramp Up Time to 3-52 Ramp 2 Ramp Down Time) is active. Bit 10, Data not valid/Data valid: Tell the frequency converter whether to use or ignore the control word. Bit 10 = 0: The control word is ignored. Bit 10 = 1: The control word is used. This function is relevant because the telegram always contains the control word, regardless of the telegram type. Thus, you can turn off the control word if you do not want to use it when updating or reading parameters. Bit 11, Relay 01: Bit 11 = "0": Relay not activated. Bit 11 = "1": Relay 01 activated provided that Control word bit 11 is chosen in 5-40 Function Relay. Bit 12, Relay 04: Bit 12 = "0": Relay 04 is not activated. Bit 12 = "1": Relay 04 is activated provided that Control word bit 12 is chosen in 5-40 Function Relay. Bit 13/14, Selection of set-up: Use bits 13 and 14 to choose from the four menu set-ups according to the shown table: .
Set-up 1 2 3 4 Bit 14 0 0 1 1 Bit 13 0 1 0 1
Bit 15 Reverse: Bit 15 = 0: No reversing. Bit 15 = 1: Reversing. In the default setting, reversing is set to digital in 8-54 Reversing Select. Bit 15 causes reversing only when Ser. communication, Logic or or Logic and is selected.
7 7
The function is only possible when Multi Set-Ups is selected in 0-10 Active Set-up. Make a selection in 8-55 Set-up Select to define how Bit 13/14 gates with the corresponding function on the digital inputs.
138
7.11.2 Status Word According to FC Profile (STW) (8-10 Control Profile = FC profile)
130BA273.10 Slave-master STW Output freq.
Bit 04, No error/error (no trip): Bit 04 = 0: The frequency converter is not in fault mode. Bit 04 = 1: The frequency converter shows an error but does not trip. Bit 05, Not used: Bit 05 is not used in the status word. Bit 06, No error / triplock: Bit 06 = 0: The frequency converter is not in fault mode. Bit 06 = 1: The frequency converter is tripped and locked.
Bit no.:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Bit 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
Bit = 0 Control not ready Drive not ready Coasting No error No error Reserved No error No warning Speed reference Local operation Out of frequency limit No operation Drive OK Voltage OK Torque OK Timer OK
Bit = 1 Control ready Drive ready Enable Trip Error (no trip) Triplock Warning Speed = reference Bus control Frequency limit OK In operation Stopped, auto start Voltage exceeded Torque exceeded Timer exceeded
Bit 07, No warning/warning: Bit 07 = 0: There are no warnings. Bit 07 = 1: A warning has occurred. Bit 08, Speed reference/speed = reference: Bit 08 = 0: The motor is running but the present speed is different from the preset speed reference. It might e.g. be the case when the speed ramps up/down during start/stop. Bit 08 = 1: The motor speed matches the preset speed reference. Bit 09, Local operation/bus control: Bit 09 = 0: [STOP/RESET] is activate on the control unit or Local control in 3-13 Reference Site is selected. You cannot control the frequency converter via serial communication. Bit 09 = 1 It is possible to control the frequency converter via the fieldbus / serial communication. Bit 10, Out of frequency limit: Bit 10 = 0: The output frequency has reached the value in 4-11 Motor Speed Low Limit [RPM] or 4-13 Motor Speed High Limit [RPM]. Bit 10 = "1": The output frequency is within the defined limits. Bit 11, No operation/in operation: Bit 11 = 0: The motor is not running. Bit 11 = 1: The frequency converter has a start signal or the output frequency is greater than 0 Hz. Bit 12, Drive OK/stopped, autostart: Bit 12 = 0: There is no temporary over temperature on the inverter. Bit 12 = 1: The inverter stops because of over temperature but the unit does not trip and will resume operation once the over temperature stops. Bit 13, Voltage OK/limit exceeded: Bit 13 = 0: There are no voltage warnings. Bit 13 = 1: The DC voltage in the frequency converters intermediate circuit is too low or too high.
7 7
Explanation of the Status Bits Bit 00, Control not ready/ready: Bit 00 = 0: The frequency converter trips. Bit 00 = 1: The frequency converter controls are ready but the power component does not necessarily receive any power supply (in case of external 24 V supply to controls). Bit 01, Drive ready: Bit 01 = 1: The frequency converter is ready for operation but the coasting command is active via the digital inputs or via serial communication. Bit 02, Coasting stop: Bit 02 = 0: The frequency converter releases the motor. Bit 02 = 1: The frequency converter starts the motor with a start command. Bit 03, No error/trip: Bit 03 = 0 : The frequency converter is not in fault mode. Bit 03 = 1: The frequency converter trips. To re-establish operation, enter [Reset].
139
Bit 14, Torque OK/limit exceeded: Bit 14 = 0: The motor current is lower than the torque limit selected in 4-18 Current Limit. Bit 14 = 1: The torque limit in 4-18 Current Limit is exceeded. Bit 15, Timer OK/limit exceeded:
Bit 15 = 0: The timers for motor thermal protection and thermal protection are not exceeded 100%. Bit 15 = 1: One of the timers exceeds 100%. All bits in the STW are set to 0 if the connection between the Interbus option and the frequency converter is lost, or an internal communication problem has occurred.
7 7
-100% (C000hex)
0% (0hex)
100% (4000hex)
140
P1K1 1.1
P1K5 1.5
P2K2 2.2
P3K0 3
P3K7 3.7
A2
A2
A2
A3
A3
A5 A5 1.5
A5 A5 2.0
A5 A5 2.9
A5 A5 4.0
A5 A5 4.9
130BA058.10
8 8
4/10
5.9 6.5 20
6.8 7.5 20
9.5 10.5 20
11.3 12.4 32
15.0 16.5 32
130BA057.10
141
Mains supply 200-240V AC - Normal overload 110% for 1 minute Frequency Converter Typical Shaft Output [kW] IP20/Chassis (A2+A3 may be converted to IP21 using a conversion kit. (Please see also items Mechanical mounting in Operating Instructions and IP21/Type 1 Enclosure kit in the Design Guide.)) IP55/NEMA 12 IP66/NEMA 12 Typical Shaft Output [hp] at 208V Output current Continuous (3 x 200-240V) [A] Intermittent (3 x 200-240V) [A] Continuous kVA (208V AC) [kVA] Max. cable size: (mains, motor, brake) [mm2 /AWG] Max. input current Continuous (3 x 200-240V) [A]
130BA057.10
2)
P1K1 1.1
P1K5 1.5
P2K2 2.2
P3K0 3
P3K7 3.7
A2
A2
A2
A3
A3
A4/A5 A5 1.5
A4/A5 A5 2.0
A4/A5 A5 2.9
A5 A5 4.0
A5 A5 4.9
130BA058.10
4/10
8 8
5.9 6.5 20
6.8 7.5 20
9.5 10.5 20
11.3 12.4 32
15.0 16.5 32
Intermittent (3 x 200-240V) [A] Max. pre-fuses1) [A] Environment Estimated power loss at rated max. load [W] Weight enclosure IP20 Weight enclosure IP21 Weight enclosure IP55 Weight enclosure IP66 Efficiency
3) 4)
142
IP20/Chassis (B3+4 and C3+4 may be converted to IP21 using a conversion kit. (Please see also items B3 B3 B3 B4 B4 C3 C3 C4 C4
Mechanical mounting in Operating Instructions and IP21/Type 1 Enclosure kit in the Design Guide.)) IP21/NEMA 1 IP55/NEMA 12 IP66/NEMA 12 B1 B1 B1 P5K5 5.5 7.5 10 15 20 25 30 40 P7K5 7.5 P11K 11 P15K 15 P18K 18.5 P22K 22 P30K 30 P37K 37 50 B1 B1 B1 B1 B1 B1 B2 B2 B2 C1 C1 C1 C1 C1 C1 C1 C1 C1 C2 C2 C2 C2 C2 C2 P45K 45 60
Output current 24.2 16/6 35/2 30.8 46.2 59.4 74.8 88.0 35/2 115 143 70/3/0 170 185/ kcmil350
28.0
42.0
54.0
130BA058.10
MG.11.BA.02 - VLT is a registered Danfoss trademark 269 12 23 23 23 0.96 26.6 8.7 12 23 23 23 0.96 33.9 11.1 310 447 12 23 23 23 0.96 50.8 16.6 602 23.5 27 27 27 0.96 65.3 21.4 737 23.5 45 45 45 0.96 82.3 26.9 845 35 45 45 45 0.97 96.8 31.7 [kg] [kg] [kg] [kg] 10/7 35/2 50/1/0 (B4=35/2)
at rated max. load [W] Weight enclosure IP20 Weight enclosure IP21 Weight enclosure IP55 Weight enclosure IP66
[mm2 /AWG]
2)
143
8 8
8 8
130BA058.10
130BA057.10
144 P1K1 1.1 1.5 2.0 2.9 4.0 5.0 7.5 10 P1K5 1.5 P2K2 2.2 P3K0 3 P4K0 4 P5K5 5.5 P7K5 7.5 A2 A2 A2 A2 A2 A3 A3 A4/A5 A4/A5 3 3.3 2.7 3.0 2.1 2.4 2.8 2.7 3.9 3.8 5.0 5.0 6.9 6.5 4.1 4.5 3.4 3.7 5.6 6.2 4.8 5.3 7.2 7.9 6.3 6.9 10 11 8.2 9.0 A4/A5 A4/A5 A4/A5 A4/A5 A4/A5 A4/A5 A4/A5 A4/A5 A5 A5 13 14.3 11 12.1 9.0 8.8 A5 A5 16 17.6 14.5 15.4 11.0 11.6
2)
IP20/Chassis (A2+A3 may be converted to IP21 using a conversion kit. (Please see also items
Mechanical mounting in Operating Instructions and IP 1/Type 1 Enclosure kit in the Design Guide.)) IP55/NEMA 12 IP66/NEMA 12
Output current
Continuous (3 x 380-440V) [A] Intermittent (3 x 380-440V) [A] Continuous (3 x 441-480V) [A] Intermittent (3 x 441-480V) [A]
Continuous kVA (400V AC) [kVA] Continuous kVA (460V AC) [kVA] Max. cable size: (mains, motor, brake) 4/10
[[mm2/ AWG]
Max. input current 2.7 3.0 2.7 3.0 10 3.1 3.4 10 4.1 3.7 5.0 5.5 4.3 4.7 20 6.5 7.2 5.7 6.3 20 9.0 9.9 7.4 8.1 20 11.7 12.9 9.9 10.9 32 14.4 15.8 13.0 14.3 32
Efficiency
3)
Mains Supply 3 x 380-480V AC - Normal overload 110% for 1 minute P11K 11 15 B3 B1 B1 B1 24 26.4 21 23.1 16.6 16.7 22.2 21.5 26 27.1 30.5 31.9 42.3 41.4 50.6 51.8 62.4 63.7 32 35.2 27 29.7 37.5 41.3 34 37.4 44 48.4 40 44 61 67.1 52 61.6 73 80.3 65 71.5 90 99 80 88 106 117 105 116 73.4 83.7 147 162 130 143 102 104 B1 B1 B1 B1 B1 B1 B2 B2 B2 B2 B2 B2 C1 C1 C1 C1 C1 C1 C1 C1 C1 C2 C2 C2 B3 B3 B4 B4 B4 C3 C3 C4 C4 C2 C2 C2 177 195 160 176 123 128 20 25 30 40 50 60 75 100 125 P15K 15 P18K 18.5 P22K 22 P30K 30 P37K 37 P45K 45 P55K 55 P75K 75 P90K 90
IP20/Chassis (B3+4 and C3+4 may be converted to IP21 using a conversion kit (Please contact Danfoss)
Output current
130BA058.10
Continuous (3 x 380-439V) [A] Intermittent (3 x 380-439V) [A] Continuous (3 x 440-480V) [A] Intermittent (3 x 440-480V) [A]
Continuous kVA (400V AC) [kVA] Continuous kVA 460V AC) [kVA]
Max. cable size: 10/7 16/6 35/2 35/2 50/1/0 (B4=35/2) 35/2 95/ 4/0 70/3/0 120/ MCM250 185/ kcmil350
AWG]
2)
Max. input current 22 24.2 19 20.9 63 63 63 31.9 25 27.5 37.4 31 34.1 44 36 39.6 63 29 34 40 55 60.5 47 51.7 80 66 72.6 59 64.9 100 82 90.2 73 80.3 125 96 106 95 105 160 133 146 118 130 250 161 177 145 160 250
130BA057.10
Max. pre-fuses1)[A]
Environment 278 12 23 23 23 0.98 12 23 23 23 0.98 392 465 12 23 23 23 0.98 525 23.5 27 27 27 0.98 698 23.5 27 27 27 0.98 739 23.5 45 45 45 0.98 843 35 45 45 45 0.98 1083 35 45 45 45 0.98 1384 50 65 65 65 0.98 1474 50 65 65 65 0.99
Estimated power loss IP20 IP21 IP55 IP66 [kg] [kg] [kg] [kg]
Efficiency
3)
145
8 8
Mains supply 200-240V AC - Normal overload 110% for 1 minute Frequency Converter Typical Shaft Output [kW] IP20/Chassis (A2+A3 may be converted to IP21 using a conversion kit. (Please see also items Mechanical mounting in Operating Instructions and IP21/Type 1 Enclosure kit in the Design Guide.)) IP55/NEMA 12 IP66/NEMA 12 Typical Shaft Output [hp] at 208V Output current Continuous (3 x 200-240V) [A] Intermittent (3 x 200-240V) [A] Continuous kVA (208V AC) [kVA] Max. cable size: (mains, motor, brake) [mm2 /AWG] Max. input current Continuous (3 x 200-240V) [A] Intermittent (3 x 200-240V) [A] Max. pre-fuses1) [A] Environment Estimated power loss at rated max. load [W] Weight enclosure IP20 Weight enclosure IP21 Weight enclosure IP55 Weight enclosure IP66 Efficiency Table 8.6 Mains Supply 200-240V AC
3) 4) 2)
P1K1 1.1
P1K5 1.5
P2K2 2.2
P3K0 3
P3K7 3.7
A2
A2
A2
A3
A3
A5 A5 1.5
A5 A5 2.0
A5 A5 2.9
A5 A5 4.0
A5 A5 4.9
130BA058.10
4/10
8 8
5.9 6.5 20
6.8 7.5 20
9.5 10.5 20
11.3 12.4 32
15.0 16.5 32
130BA057.10
146
Mains Supply 3 x 380-480V AC - Normal overload 110% for 1 minute P1K1 1.1 1.5 2.0 2.9 4.0 5.0 7.5 10 P1K5 1.5 P2K2 2.2 P3K0 3 P4K0 4 P5K5 5.5 P7K5 7.5
IP20/Chassis (A2+A3 may be converted to IP21 using a conversion kit. (Please see also items A2 A2 A2 A2 A2 A3
Mechanical mounting in Operating Instructions and IP21/Type 1 Enclosure kit in the Design Guide.)) IP55/NEMA 12 IP66/NEMA 12 A4/A5 A4/A5 A4/A5 A4/A5 A4/A5 A4/A5 A4/A5 A4/A5 A4/A5 A4/A5 A5 A5
A3
A5 A5
Output current 3 3.3 2.7 3.0 2.1 2.4 2.8 2.7 3.9 3.8 5.0 5.0 6.9 6.5 4.1 4.5 3.4 3.7 5.6 6.2 4.8 5.3 7.2 7.9 6.3 6.9 10 11 8.2 9.0 13 14.3 11 12.1 9.0 8.8 16 17.6 14.5 15.4 11.0 11.6
130BA058.10
Continuous (3 x 380-440V) [A] Intermittent (3 x 380-440V) [A] Continuous (3 x 441-480V) [A] Intermittent (3 x 441-480V) [A]
Continuous kVA (400V AC) [kVA] Continuous kVA (460V AC) [kVA] Max. cable size: (mains, motor, brake)
2)
[[mm2/ AWG]
4/10
Max. input current 2.7 3.0 2.7 3.0 10 3.1 3.4 10 4.1 3.7 5.0 5.5 4.3 4.7 20 6.5 7.2 5.7 6.3 20 9.0 9.9 7.4 8.1 20 11.7 12.9 9.9 10.9 32 14.4 15.8 13.0 14.3 32
130BA057.10
Efficiency
3)
147
8 8
8 8
130BA058.10
130BA057.10
148 P11K 11 15 B3 B1 B1 B1 24 26.4 21 23.1 16.6 16.7 22.2 21.5 26 27.1 30.5 31.9 42.3 41.4 50.6 51.8 62.4 63.7 32 35.2 27 29.7 37.5 41.3 34 37.4 44 48.4 40 44 61 67.1 52 61.6 73 80.3 65 71.5 90 99 80 88 106 117 105 116 73.4 83.7 147 162 130 143 102 104 B1 B1 B1 B1 B1 B1 B2 B2 B2 B2 B2 B2 C1 C1 C1 C1 C1 C1 C1 C1 C1 C2 C2 C2 B3 B3 B4 B4 B4 C3 C3 C4 C4 C2 C2 C2 177 195 160 176 123 128 20 25 30 40 50 60 75 100 125 P15K 15 P18K 18.5 P22K 22 P30K 30 P37K 37 P45K 45 P55K 55 P75K 75 P90K 90 10/7 16/6 35/2 35/2 50/1/0 (B4=35/2) 35/2 95/ 4/0 70/3/0 120/ MCM250 185/ kcmil350 22 24.2 19 20.9 63 63 63 31.9 25 27.5 37.4 31 34.1 44 36 39.6 63 29 34 40 55 60.5 47 51.7 80 66 72.6 59 64.9 100 82 90.2 73 80.3 125 96 106 95 105 160 133 146 118 130 250 161 177 145 160 250
4)
IP20/Chassis (B3+4 and C3+4 may be converted to IP21 using a conversion kit (Please contact Danfoss)
Output current
Continuous (3 x 380-439V) [A] Intermittent (3 x 380-439V) [A] Continuous (3 x 440-480V) [A] Intermittent (3 x 440-480V) [A]
Continuous kVA (400V AC) [kVA] Continuous kVA 460V AC) [kVA]
AWG]
2)
MG.11.BA.02 - VLT is a registered Danfoss trademark 278 12 23 23 23 0.98 12 23 23 23 0.98 392 465 12 23 23 23 0.98 525 23.5 27 27 27 0.98 698 23.5 27 27 27 0.98 739 23.5 45 45 45 0.98 843 35 45 45 45 0.98 IP20 IP21 IP55 IP66 [kg] [kg] [kg] [kg]
Max. pre-fuses1)[A]
Efficiency
3)
Mains supply 3 x 525-600V AC Normal overload 110% for 1 minute P1K1 1.1 A3 A3 A5 A5 A3 A3 A5 A5 A3 A3 A5 A5 A3 A3 A5 A5 A2 A2 A5 A5 A3 A3 A5 A5 A3 A3 A5 A5 A3 A3 A5 A5 B3 B1 B1 B1 B3 B1 B1 B1 B3 B1 B1 B1 B4 B2 B2 B2 B4 B2 B2 B2 B4 C1 C1 C1 C3 C1 C1 C1 C3 C1 C1 C1 C4 C2 C2 C2 C4 C2 C2 C2 1.5 2.2 3 3.7 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 P1K5 P2K2 P3K0 P3K P4K0 7 P5K5 P7K5 P11K P15K P18K P22K P30K P37K P45K P55K P75K P90K
Size:
Output current 2.6 2.9 2.4 2.6 2.5 2.4 2.7 3.9 4.9 6.1 9.0 11.0 17.9 21.9 26.9 2.8 3.9 5.0 6.1 9.0 11.0 18.1 21.9 26.7 34.3 33.9 3.0 4.3 5.4 6.7 9.9 12.1 20 24 30 37 45 41 40.8 2.7 3.9 4.9 6.1 9.0 11.0 18 22 27 34 41 52 57 51.4 51.8 3.2 4.5 5.7 7.0 10.5 12.7 21 25 31 40 47 59 72 62 68 61.9 61.7 2.9 4.1 5.2 6.4 9.5 11.5 19 23 28 36 43 54 65 87 96 83 91 82.9 82.7 105 116 100 110 100 99.6 137 151 131 144 130.5 130.5 120/ MCM2 50 10/ 7 25/ 4 50/ 1/0 95/ 4/0 150/ MCM2 16/ 6 35/ 2 50/ 1/0 95/ 4/0
130BA058.10
Continuous (3 x 525-550V) [A] Intermittent (3 x 525-550V) [A] Continuous (3 x 525-600V) [A] Intermittent (3 x 525-600V) [A] Continuous kVA (525V AC) [kVA] Continuous kVA (575 V AC) [kVA] Max. cable size, IP21/55/66 (mains, motor, brake) 4/ 10
[mm2]/[AWG]
2)
[mm2]/[AWG]
2)
35/2
Table 8.9
5)
149
8 8
8 8
130BA057.10
150 P4K0 P5K5 P7K5 P11K P15K P18K P22K P30K P37K P45K P55K P75K P90K 2.4 2.7 10 10 20 20 20 32 32 63 63 63 63 80 100 125 160 3.0 4.5 5.7 6.4 9.5 11.5 19 23 28 36 43 54 65 87 105 250 2.7 4.1 5.2 5.8 8.6 10.4 17.2 20.9 25.4 32.7 39 49 59 78.9 95.3 124.3 137 250 50 6.5 13.5 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.98 0.98 0.98 0.98 0.98 13.5 13.5 13.5 13.5 13.5 14.2 14.2 23 23 23 27 27 27 0.98 6.5 6.5 6.5 6.5 6.6 6.6 12 12 12 23.5 23.5 23.5 65 92 122 145 195 261 300 400 475 525 700 750 850 35 45 0.98 1100 35 45 0.98 1400 50 65 0.98 1500 50 65 0.98
Mains supply 3 x 525-600V ACNormal overload 110% for 1 minute - continued P3K Size: P1K1 P1K5 P2K2 P3K0 7
at rated max. load [W] Weight enclosure IP20 [kg] Weight enclosure IP21/55 [kg]
4)
Efficiency
4)
Table 8.10
5)
Mains supply 3 x 525-600V AC Normal overload 110% for 1 minute P1K1 1.1 A3 A3 A5 A5 A3 A3 A5 A5 A3 A3 A5 A5 A3 A3 A5 A5 A2 A2 A5 A5 A3 A3 A5 A5 A3 A3 A5 A5 A3 A3 A5 A5 B3 B1 B1 B1 B3 B1 B1 B1 B3 B1 B1 B1 B4 B2 B2 B2 B4 B2 B2 B2 B4 C1 C1 C1 C3 C1 C1 C1 C3 C1 C1 C1 C4 C2 C2 C2 C4 C2 C2 C2 1.5 2.2 3 3.7 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 P1K5 P2K2 P3K0 P3K P4K0 7 P5K5 P7K5 P11K P15K P18K P22K P30K P37K P45K P55K P75K P90K
Size:
Output current 2.6 2.9 2.4 2.6 2.5 2.4 2.7 3.9 4.9 6.1 9.0 11.0 17.9 21.9 26.9 2.8 3.9 5.0 6.1 9.0 11.0 18.1 21.9 26.7 34.3 33.9 3.0 4.3 5.4 6.7 9.9 12.1 20 24 30 37 45 41 40.8 2.7 3.9 4.9 6.1 9.0 11.0 18 22 27 34 41 52 57 51.4 51.8 3.2 4.5 5.7 7.0 10.5 12.7 21 25 31 40 47 59 72 62 68 61.9 61.7 2.9 4.1 5.2 6.4 9.5 11.5 19 23 28 36 43 54 65 87 96 83 91 82.9 82.7 105 116 100 110 100 99.6 137 151 131 144 130.5 130.5 120/ MCM2 50 10/ 7 25/ 4 50/ 1/0 95/ 4/0 150/ MCM2 16/ 6 35/ 2 50/ 1/0 95/ 4/0
130BA058.10
Continuous (3 x 525-550V) [A] Intermittent (3 x 525-550V) [A] Continuous (3 x 525-600V) [A] Intermittent (3 x 525-600V) [A] Continuous kVA (525V AC) [kVA] Continuous kVA (575V AC) [kVA] Max. cable size, IP21/55/66 (mains, motor, brake) 4/ 10
[mm2]/[AWG]
2)
[mm2]/[AWG]
2)
35/2
Table 8.11
5)
151
8 8
8 8
130BA057.10
152 P4K0 P5K5 P7K5 P11K P15K P18K P22K P30K P37K P45K P55K P75K P90K 2.4 2.7 10 10 20 20 20 32 32 63 63 63 63 80 100 125 160 3.0 4.5 5.7 6.4 9.5 11.5 19 23 28 36 43 54 65 87 105 250 2.7 4.1 5.2 5.8 8.6 10.4 17.2 20.9 25.4 32.7 39 49 59 78.9 95.3 124.3 137 250 50 6.5 13.5 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.98 0.98 0.98 0.98 0.98 13.5 13.5 13.5 13.5 13.5 14.2 14.2 23 23 23 27 27 27 0.98 6.5 6.5 6.5 6.5 6.6 6.6 12 12 12 23.5 23.5 23.5 65 92 122 145 195 261 300 400 475 525 700 750 850 35 45 0.98 1100 35 45 0.98 1400 50 65 0.98 1500 50 65 0.98
Mains supply 3 x 525-600V ACNormal overload 110% for 1 minute - continued P3K Size: P1K1 P1K5 P2K2 P3K0 7
at rated max. load [W] Weight enclosure IP20 [kg] Weight enclosure IP21/55 [kg]
4)
Efficiency
4)
Table 8.12
5)
Mains Supply 3 x 380-480V AC P110 Typical Shaft output at 400V [kW] Typical Shaft output at 460V [HP] Enclosure IP21 Enclosure IP54 Enclosure IP00 Output current Continuous (at 400V) [A] Intermittent (60 sec overload) (at 400V) [A] Continuous (at 460/480V) [A] Intermittent (60 sec overload) (at 460/480V) [A] Continuous KVA (at 400V) [KVA] Continuous KVA (at 460V) [KVA] Continuous (at 400V) [A] Continuous (at 460/480V) [A] Max. cable size, mains motor, brake and load share [mm2 (AWG2))] Max. external prefuses [A] 1 Estimated power loss at rated max. load [W]
4)
130BA229.10
110 150 D1 D1 D3
212
260
315
395
480
233
286
347
435
528
130BA230.10
190
240
302
361
443
209
264
332
397
487
147 151
180 191
218 241
274 288
333 353
8 8
183
231
291
348
427
2 x 70 (2 x 2/0)
2 x 70 (2 x 2/0)
300
350
400
500
630
3234
3782
4213
5119
5893
, 400V Estimated power loss at rated max. load [W] , 460V Weight, enclosure IP21, IP54 [kg] Weight, enclosure IP00 [kg] Efficiency4) Output frequency Heatsink overtemp. trip Power card ambient trip
2947
3665
4063
4652
5634
4)
96
104
125
136
151
82
91
123
138
90C
110C
110C 60C
110 C
110C
153
Mains Supply 3 x 380-480V AC P315 Typical Shaft output at 400V [kW] Typical Shaft output at 460V [HP] Enclosure IP21 Enclosure IP54 Enclosure IP00 Output current Continuous (at 400V) [A] Intermittent (60 sec overload) (at 400V) [A] Continuous (at 460/480V) [A] Intermittent (60 sec overload) (at 460/480V) [A] Continuous KVA (at 400V) [KVA] Continuous KVA (at 460V) [KVA] Continuous (at 400V) [A]
130BA229.10
315 450 E1 E1 E2
600
658
745
800
130BA230.10
660
724
820
880
540
590
678
730
594
649
746
803
8 8
Max. input current
416 430
456 470
516 540
554 582
590
647
733
787
531
580
667
718
Max. cable size, mains, motor and load share [mm2 (AWG2))] Max. cable size, brake [mm2 (AWG2)) Max. external pre-fuses [A] 1 Estimated power loss at rated max. load [W] 400V Estimated power loss at rated max. load [W] 460V
4)
6790
7701
8879
9670
4)
6082
6953
8089
8803
Weight, enclosure IP21, IP54 [kg] Weight, enclosure IP00 [kg] Efficiency4) Output frequency Heatsink overtemp. trip Power card ambient trip
263 221
272 236
313 277
154
Mains Supply 3 x 380-480V AC P500 Typical Shaft output at 400V [kW] Typical Shaft output at 460V [HP] Enclosure IP21, 54 without/ with options cabinet Output current Continuous (at 400V) [A] Intermittent (60 sec overload) (at 400V) [A] Continuous (at 460/480V) [A] Intermittent (60 sec overload) (at 460/480V) [A] Continuous KVA (at 400V) [KVA] Continuous KVA (at 460V) [KVA] Continuous (at 400V) [A] Continuous (at 460/480V) [A] Max. cable size,motor [mm2 (AWG2))] Max. cable size,mains F1/F2 [mm2 (AWG2))] Max. cable size,mains F3/F4 [mm2 (AWG2))] Max. cable size, loadsharing [mm2 (AWG2))] Max. cable size, brake [mm2 (AWG2)) Max. external pre-fuses [A] 1 Est. power loss at rated max. load [W]4) , 400V, F1 & F2 Est. power loss at rated max. load [W] 4) , 460V, F1 & F2 Max added losses of A1 RFI, Circuit Breaker or Disconnect, & Contactor, F3 & F4 Max Panel Options Losses Weight, enclosure IP21, IP54 [kg] Weight Rectifier Module [kg] Weight Inverter Module [kg] Efficiency4) Output frequency Heatsink overtemp. trip Power card ambient trip 1600 10647 9414 12338 11006 13201 12353 4x185 (4x350 mcm) 2000 15436 14041 18084 17137
130BA230.10
Max. input current 857 759 964 867 1090 1022 1227 1129 1422 1344 1675 1490
8 8
130BA229.10
8x150 (8x300 mcm) 8x240 (8x500 mcm) 8x456 (8x900 mcm) 4x120 (4x250 mcm)
963
1054
1093 400
1230
2280
2541
155
Mains Supply 3 x 380-480V AC P110 Typical Shaft output at 400V [kW] Typical Shaft output at 460V [HP] Enclosure IP21 Enclosure IP54 Enclosure IP00 Output current Continuous (at 400V) [A] Intermittent (60 sec overload) (at 400V) [A] Continuous (at 460/480V) [A] Intermittent (60 sec overload) (at 460/480V) [A] Continuous KVA (at 400V) [KVA] Continuous KVA (at 460V) [KVA] Continuous (at 400V) [A] Continuous (at 460/480V) [A] Max. cable size, mains motor, brake and load share [mm2 (AWG2))] Max. external prefuses [A] 1 Estimated power loss at rated max. load [W]
4)
130BA229.10
110 150 D1 D1 D3
212
260
315
395
480
233
286
347
435
528
130BA230.10
190
240
302
361
443
209
264
332
397
487
8 8
Max. input current
147 151
180 191
218 241
274 288
333 353
204
251
304
381
463
183
231
291
348
427
2 x 70 (2 x 2/0)
2 x 70 (2 x 2/0)
300
350
400
500
630
3234
3782
4213
5119
5893
, 400V Estimated power loss at rated max. load [W] , 460V Weight, enclosure IP21, IP54 [kg] Weight, enclosure IP00 [kg] Efficiency4) Output frequency Heatsink overtemp. trip Power card ambient trip
2947
3665
4063
4652
5634
4)
96
104
125
136
151
82
91
123
138
90C
110C
110C 60C
110 C
110C
156
Mains Supply 3 x 380-480V AC P315 Typical Shaft output at 400V [kW] Typical Shaft output at 460V [HP] Enclosure IP21 Enclosure IP54 Enclosure IP00 Output current Continuous (at 400V) [A] Intermittent (60 sec overload) (at 400V) [A] Continuous (at 460/480V) [A] Intermittent (60 sec overload) (at 460/480V) [A] Continuous KVA (at 400V) [KVA] Continuous KVA (at 460V) [KVA] Continuous (at 400V) [A]
130BA229.10
315 450 E1 E1 E2
600
658
745
800
130BA230.10
660
724
820
880
540
590
678
730
594
649
746
803
416 430
456 470
516 540
554 582
8 8
531
580
667
718
Max. cable size, mains, motor and load share [mm2 (AWG2))] Max. cable size, brake [mm2 (AWG2)) Max. external pre-fuses [A] 1 Estimated power loss at rated max. load [W] 400V Estimated power loss at rated max. load [W] 460V
4)
6790
7701
8879
9670
4)
6082
6953
8089
8803
Weight, enclosure IP21, IP54 [kg] Weight, enclosure IP00 [kg] Efficiency4) Output frequency Heatsink overtemp. trip Power card ambient trip
263 221
272 236
313 277
157
Mains Supply 3 x 380-480V AC P500 Typical Shaft output at 400V [kW] Typical Shaft output at 460V [HP] Enclosure IP21, 54 without/ with options cabinet Output current Continuous (at 400V) [A] Intermittent (60 sec overload) (at 400V) [A] Continuous (at 460/480V) [A] Intermittent (60 sec overload) (at 460/480V) [A] Continuous KVA (at 400V) [KVA] Continuous KVA (at 460V) [KVA] Continuous (at 400V) [A] Continuous (at 460/ 480 V) [A] Max. cable size,motor [mm2 (AWG2))] Max. cable size,mains F1/F2 [mm2 (AWG2))] Max. cable size,mains F3/F4 [mm2 (AWG2))] Max. cable size, loadsharing [mm2 (AWG2))] Max. cable size, brake [mm2 (AWG2)) Max. external pre-fuses [A] 1 Est. power loss at rated max. load [W]4) , 400V, F1 & F2 Est. power loss at rated max. load [W] 4) , 460V, F1 & F2 Max added losses of A1 RFI, Circuit Breaker or Disconnect, & Contactor, F3 & F4 Max Panel Options Losses Weight, enclosure IP21, IP54 [kg] Weight Rectifier Module [kg] Weight Inverter Module [kg] Efficiency4) Output frequency Heatsink overtemp. trip Power card ambient trip 1600 10647 9414 12338 11006 13201 12353 4x185 (4x350 mcm) 2000 15436 14041 18084 17137
130BA230.10
8 8
Max. input current 857 759 964 867 1090 1022 1227 1129 1422 1344 1675 1490
130BA229.10
8x150 (8x300 mcm) 8x240 (8x500 mcm) 8x456 (8x900 mcm) 4x120 (4x250 mcm)
963
1054
1093 400
1230
2280
2541
158
P11K 11 10 B2 B2 14 15.4 13 14.3 13.3 12.9 15.5 35 1/0 95 4/0 18.1 17.9 21.5 21.9 21.9 26.3 26.7 26.9 32.3 34.3 33.8 40.6 41 40.8 49 51.4 51.8 62.1 61.9 61.7 74.1 19.8 24.2 29.7 37.4 45.1 57.2 68.2 18 22 27 34 41 52 62 83 91.3 82.9 82.7 99.2 20.9 25.3 30.8 39.6 47.3 59.4 71.5 95.7 19 23 28 36 43 54 65 87 105 115.5 100 110 100 99.6 119.5
Normal overload P15K 15 16.4 B2 B2 P30K 30 33 B2 B2 P37K 37 40 C2 C2 P45K 45 50 C2 C2 P55K 55 60 C2 C2 P75K 75 75 C2 C2 P90K 90 100 C2 C2
130BA058.10
15 16.5 63 201 27 27 27 27 27 27 27 27 27 27 285 335 375 430 592 65 65 63 63 63 80 100 21.5 26.4 31.9 39.6 53.9
19.5
24
29
36
49
130BA057.10
Size: Typical Shaft Output [kW] Typical Shaft Output [HP] at 575V IP21/NEMA 1 IP55/NEMA 12 Output current Continuous (3 x 525-550V) [A] Intermittent (3 x 525-550V) [A] Continuous (3 x 551-690V) [A] Intermittent (3 x 551-690V) [A] Continuous kVA (550V AC) [kVA] Continuous kVA (575V AC) [kVA] Continuous kVA (690V AC) [kVA] Max. cable size (mains, motor, brake) [mm2]/[AWG] 2) Max. input current Continuous (3 x 525-690V) [A] Intermittent (3 x 525-690V) [A] Max. pre-fuses1) [A] Environment: Estimated power loss at rated max. load [W] 4) Weight: IP21 [kg]
IP55 [kg]
0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 Efficiency 4) 1) For type of fuse see section Fuses 2) American Wire Gauge 3) Measured using 5 m screened motor cables at rated load and rated frequency 4) The typical power loss is at normal load conditions and expected to be within +/- 15% (tolerance relates to variety in voltage and cable conditions). Values are based on a typical motor efficiency (eff2/eff3 border line). Lower efficiency motors will also add to the power loss in the frequency converter and vice versa. If the switching frequency is raised from nominal the power losses may rise significantly. LCP and typical control card power consumptions are included. Further options and customer load may add up to 30 Watts to the losses. (Though typically only 4 Watts extra for a fully loaded control card or options for slot A or slot B, each). Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (+/- 5%). 5) Motor and mains cable: 300MCM/150mm2
159
8 8
Mains Supply 3 x 525-690V AC P110 Typical Shaft output at 550V [kW] Typical Shaft output at 575V [HP] Typical Shaft output at 690V [kW] Enclosure IP21 Enclosure IP54 Enclosure IP00 Output current Continuous (at 550V) [A] Intermittent (60 sec overload) (at 550V) [A] Continuous (at 575/690V) [A] Intermittent (60 sec overload) (at 575/690V) [A] Continuous KVA (at 550V) [KVA] Continuous KVA (at 575V) [KVA] Continuous KVA (at 690V) [KVA] Max. input current Continuous (at 550V) [A] Continuous (at 575V) [A] Continuous (at 690V) [A] Max. cable size, mains motor, load share and brake [mm2 (AWG)] Max. external pre-fuses [A] 1 Estimated power loss at rated max. load [W]
4)
130BA229.10
130BA230.10
90 125 110 D1 D1 D2
137 151
131
211
266
319
8 8
130
158
198
245
299
124
151
189
234
286
128
155
197
240
296
2 x 70 (2 x 2/0)
250
315
350
350
400
2533
2963
3430
4051
4867
2662
3430
3612
4292
5156
, 690V Weight, Enclosure IP21, IP54 [kg] Weight, Enclosure IP00 [kg] Efficiency4) Output frequency Heatsink overtemp. trip Power card ambient trip 85C
96 82
125 112
136 123
110 C
110 C
160
Mains Supply 3 x 525-690V AC P315 Typical Shaft output at 550V [kW] Typical Shaft output at 575V [HP] Typical Shaft output at 690V [kW] Enclosure IP21 Enclosure IP54 Enclosure IP00 Output current Continuous (at 550V) [A] Intermittent (60 sec overload) (at 550V) [A] Continuous (at 575/690V) [A] Intermittent (60 sec overload) (at 575/690V) [A] Continuous KVA (at 550V) [KVA] Continuous KVA (at 575V) [KVA] Continuous KVA (at 690V) [KVA] Max. input current Continuous (at 550V) [A]
130BA229.10
130BA230.10
8 8
355
408
453
339
390
434
Continuous (at 690V) [A] Max. cable size, mains, motor and load share [mm2 (AWG)] Max. cable size, brake [mm2 (AWG)] Max. external pre-fuses [A] Estimated power loss
1
352 2 x 150 (2 x 300 mcm) 2 x 150 (2 x 300 mcm) 500 5493 5821 151 138
400 2 x 150 (2 x 300 mcm) 2 x 150 (2 x 300 mcm) 550 5852 6149 165 151 0.98
434 4 x 240 (4 x 500 mcm) 2 x 185 (2 x 350 mcm) 700 6132 6440 263 221
at rated max. load [W] 4) , 600V Estimated power loss at rated max. load [W] 4) , 690V Weight, enclosure IP21, IP54 [kg] Weight, enclosure IP00 [kg] Efficiency4) Output frequency Heatsink overtemp. trip Power card ambient trip
161
Mains Supply 3 x 525-690V AC P500 Typical Shaft output at 550V [kW] Typical Shaft output at 575V [HP] Typical Shaft output at 690V [kW] Enclosure IP21 Enclosure IP54 Enclosure IP00 Output current Continuous (at 550V) [A] Intermittent (60 sec overload) (at 550V) [A] Continuous (at 575/690V) [A] Intermittent (60 sec overload) (at 575/690V) [A] Continuous KVA (at 550V) [KVA] Continuous KVA (at 575V) [KVA] Continuous KVA (at 690V) [KVA] Max. input current Continuous (at 550V) [A]
130BA229.10
130BA230.10
8 8
504
574
607
482
549
607
Continuous (at 690V) [A] Max. cable size, mains, motor and load share [mm2 (AWG)] Max. cable size, brake [mm2 (AWG)] Max. external pre-fuses [A] Estimated power loss Estimated power loss at rated max. load [W] 4) , 690V Weight, enclosure IP21, IP54 [kg] Weight, enclosure IP00 [kg] Efficiency4) Output frequency Heatsink overtemp. trip Power card ambient trip
1
482 4x240 (4x500 mcm) 2 x 185 (2 x 350 mcm) 700 6903 7249 263 221
549 4x240 (4x500 mcm) 2 x 185 (2 x 350 mcm) 900 8343 8727 272 236 0.98 0 - 500Hz 110C 68C
607 4x240 (4x500 mcm) 2 x 185 (2 x 350 mcm) 900 9244 9673 313 277
162
Mains Supply 3 x 525-690V AC P710 Typical Shaft output at 550V [kW] Typical Shaft output at 575V [HP] Typical Shaft output at 690V [kW] Enclosure IP21, 54 without/ with options cabinet Output current Continuous (at 550V) [A] Intermittent (60 s overload, at 550V) [A] Continuous (at 575/690V) [A] Intermittent (60 s overload, at 575/690V) [A] Continuous KVA (at 550V) [KVA] Continuous KVA (at 575V) [KVA] Continuous KVA (at 690V) [KVA]
130BA230.10
8 8
163
Max. input current Continuous (at 550V) [A] Continuous (at 575V) [A] Continuous (at 690V) [A] Max. cable size,motor [mm2 (AWG2))] Max. cable size,mains F1/F2 [mm2 (AWG2))] Max. cable size,mains F3/F4 [mm2 (AWG2))] Max. cable size, loadsharing [mm2 (AWG2))] Max. cable size, brake [mm2 (AWG2)) Max. external pre-fuses [A] Est. power loss
1)
130BA229.10
8x240 (8x500 mcm) 8x456 8x900 mcm 4x120 (4x250 mcm) 4x185 (4x350 mcm) 1600 10771 12272 13835 15592 6x185 (6x350 mcm) 2000 18281 2500 20825
8 8
at rated max. load [W] 4), 600V, F1 & F2 Est. power loss at rated max. load [W] 4), 690V, F1 & F2 Max added losses of Circuit Breaker or Disconnect & Contactor, F3 & F4 Max Panel Options Losses Weight,enclosure IP21, IP54 [kg] Weight, Rectifier Module [kg] Weight, Inverter Module [kg] Efficiency4) Output frequency Heatsink overtemp. trip Power card amb. trip
11315
12903
14533
16375
19207
21857
427
532
615
665
863
1044
400 1004/ 1299 1246/ 1541 102 136 0.98 0-500Hz 95C 68C 136 102
1) For type of fuse see section Fuses. 2) American Wire Gauge. 3) Measured using 5m screened motor cables at rated load and rated frequency. 4) The typical power loss is at nominal load conditions and expected to be within +/-15% (tolerence relates to variety in voltage and cable conditions). Values are based on a typical motor efficiency (eff2/eff3 border line). Motors with lower efficiency will also add to the power loss in the frequency converter and opposite. If the switching frequency is increased comed to the default setting, the power losses may rise significantly. LCP and typical control card power consumptions are included. Further options and customer load may add up to 30W to the losses. (Though typical only 4W extra for a fully loaded control card, or options for slot A or slot B, each). Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (+/-5%).
164
Mains voltage low / mains drop-out: During low mains voltage or a mains drop-out, the FC continues until the intermediate circuit voltage drops below the minimum stop level, which corresponds typically to 15% below the FC's lowest rated supply voltage. Power-up and full torque cannot be expected at mains voltage lower than 10% below the FC's lowest rated supply voltage. Supply frequency Max. imbalance temporary between mains phases True Power Factor () Displacement Power Factor (cos) near unity Switching on input supply L1, L2, L3 (power-ups) enclosure type A Switching on input supply L1, L2, L3 (power-ups) enclosure type B, C Switching on input supply L1, L2, L3 (power-ups) enclosure type D, E, F Environment according to EN60664-1 Motor output (U, V, W): Output voltage Output frequency Switching on output Ramp times
*
50/60Hz 5% 3.0% of rated supply voltage 0.9 nominal at rated load (> 0.98) maximum twice/min. maximum once/min. maximum once/2 min. overvoltage category III / pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 480/600 V maximum. 0 - 100% of supply voltage 0 - 1000Hz* Unlimited 1 - 3600 sec.
8 8
Dependent on power size. maximum 110% for 1 min.* maximum 135% up to 0.5 sec.* maximum 110% for 1 min.*
Torque characteristics: Starting torque (Constant torque) Starting torque Overload torque (Constant torque) *Percentage relates to the frequency converter's nominal torque. Cable lengths and cross sections: Max. motor cable length, screened/armoured Max. motor cable length, unscreened/unarmoured Max. cross section to motor, mains, load sharing and brake * Maximum cross section to control terminals, rigid wire Maximum cross section to control terminals, flexible cable Maximum cross section to control terminals, cable with enclosed core Minimum cross section to control terminals * See Mains Supply tables for more information! Digital inputs: Programmable digital inputs Terminal number Logic Voltage level Voltage level, logic'0' PNP Voltage level, logic'1' PNP Voltage level, logic '0' NPN Voltage level, logic '1' NPN Maximum voltage on input Input resistance, Ri
VLT HVAC Drive: 150m VLT HVAC Drive: 300m 1.5mm2/16 AWG (2 x 0.75mm2) 1mm2/18 AWG 0.5mm2/20 AWG 0.25mm2
4 (6) 18, 19, 27 29 32, 33, PNP or NPN 0 - 24V DC < 5V DC > 10V DC > 19V DC < 14V DC 28V DC approx. 4 k
1), 1),
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. 1) Terminals 27 and 29 can also be programmed as output.
165
Analog inputs: Number of analog inputs Terminal number Modes Mode select Voltage mode Voltage level Input resistance, Ri Max. voltage Current mode Current level Input resistance, Ri Max. current Resolution for analog inputs Accuracy of analog inputs Bandwidth
2 53, 54 Voltage or current Switch S201 and switch S202 Switch S201/switch S202 = OFF (U) : 0 to + 10V (scaleable) approx. 10k 20V Switch S201/switch S202 = ON (I) 0/4 to 20mA (scaleable) approx. 200 30mA 10 bit (+ sign) Max. error 0.5% of full scale : 200Hz
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
130BA117.10 PELV isolation +24V 18 Control
8 8
Mains
High voltage
Motor
DC-Bus
Pulse inputs: Programmable pulse inputs Terminal number pulse Max. frequency at terminal, 29, 33 Max. frequency at terminal, 29, 33 Min. frequency at terminal 29, 33 Voltage level Maximum voltage on input Input resistance, Ri Pulse input accuracy (0.1 - 1 kHz) Analog output: Number of programmable analog outputs Terminal number Current range at analog output Max. resistor load to common at analog output Accuracy on analog output Resolution on analog output Control card, RS-485 serial communication: Terminal number Terminal number 61
2 29, 33 110kHz (Push-pull driven) 5kHz (open collector) 4Hz see section on Digital input 28V DC approx. 4k Max. error: 0.1% of full scale 1 42 0/4 - 20mA 500 Max. error: 0.8% of full scale 8 bit
The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. 68 (P,TX+, RX+), 69 (N,TX-, RX-) Common for terminals 68 and 69
The RS-485 serial communication circuit is functionally seated from other central circuits and galvanically isolated from the supply voltage (PELV). Digital output: Programmable digital/pulse outputs Terminal number Voltage level at digital/frequency output
166 MG.11.BA.02 - VLT is a registered Danfoss trademark
2 27, 29 1) 0 - 24V
Max. output current (sink or source) Max. load at frequency output Max. capacitive load at frequency output Minimum output frequency at frequency output Maximum output frequency at frequency output Accuracy of frequency output Resolution of frequency outputs 1) Terminal 27 and 29 can also be programmed as input.
40mA 1 k 10nF 0Hz 32kHz Max. error: 0.1% of full scale 12 bit
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. Control card, 24 V DC output: Terminal number Max. load 12, 13 : 200mA
The 24V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital inputs and outputs. Relay outputs: Programmable relay outputs Relay 01 Terminal number Max. terminal load (AC-1)1) on 1-3 (NC), 1-2 (NO) (Resistive load) Max. terminal load (AC-15)1) (Inductive load @ cos 0.4) Max. terminal load (DC-1)1) on 1-2 (NO), 1-3 (NC) (Resistive load) Max. terminal load (DC-13)1) (Inductive load) Relay 02 Terminal number Max. terminal load (AC-1)1) on 4-5 (NO) (Resistive load)2)3) Max. terminal load (AC-15)1) on 4-5 (NO) (Inductive load @ cos 0.4) Max. terminal load (DC-1)1) on 4-5 (NO) (Resistive load) Max. terminal load (DC-13)1) on 4-5 (NO) (Inductive load) Max. terminal load (AC-1)1) on 4-6 (NC) (Resistive load) Max. terminal load (AC-15)1) on 4-6 (NC) (Inductive load @ cos 0.4) Max. terminal load (DC-1)1) on 4-6 (NC) (Resistive load) Max. terminal load (DC-13)1) on 4-6 (NC) (Inductive load) Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO) Environment according to EN 60664-1 2 1-3 (break), 1-2 (make) 240V AC, 2A 240V AC, 0.2 A 60V DC, 1A 24V DC, 0.1A 4-6 (break), 4-5 (make) 400V AC, 2 A 240V AC, 0.2 A 80V DC, 2 A 24V DC, 0.1A 240V AC, 2 A 240V AC, 0.2A 50V DC, 2 A 24V DC, 0.1 A 24V DC 10mA, 24V AC 20mA overvoltage category III/pollution degree 2
8 8
1) IEC 60947 parts 4 and 5 The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV). 2) Overvoltage Category II 3) UL applications 300V AC 2A Control card, 10 V DC output: Terminal number Output voltage Max. load The 10V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. Control characteristics: Resolution of output frequency at 0 - 1000Hz System response time (terminals 18, 19, 27, 29, 32, 33) Speed control range (open loop) Speed accuracy (open loop) All control characteristics are based on a 4-pole asynchronous motor Surroundings: Enclosure type Enclosure type Enclosure type Enclosure type A B1/B2 B3/B4 C1/C2 IP 20/Chassis, IP 21kit/Type 1, IP55/Type12, IP 66/Type12 IP 21/Type 1, IP55/Type12, IP 66/12 IP20/Chassis IP 21/Type 1, IP55/Type 12, IP66/12 : +/- 0.003Hz : 2ms 1:100 of synchronous speed 30 - 4000 rpm: Maximum error of 8 rpm 50 10.5V0.5V 25mA
167
Enclosure type C3/C4 IP20/Chassis Enclosure type D1/D2/E1 IP21/Type 1, IP54/Type12 Enclosure type D3/D4/E2 IP00/Chassis Enclosure type F1/F3 IP21, 54/Type1, 12 Enclosure type F2/F4 IP21, 54/Type1, 12 IP21/NEMA 1/IP 4X on top of enclosure Enclosure kit available enclosure type D Vibration test enclosure A, B, C 1.0g Vibration test enclosure D, E, F 0.7 g Relative humidity 5% - 95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation Aggressive environment (IEC 60068-2-43) H2S test class Kd Test method according to IEC 60068-2-43 H2S (10 days) Ambient temperature (at 60 AVM switching mode) - with derating max. 55 C1) - with full output power of typical EFF2 motors (up to 90% output current) - at full continuous FC output current
1)
For more information on derating see the Design Guide, section on Special Conditions.
8 8
Minimum ambient temperature during full-scale operation Minimum ambient temperature at reduced performance Temperature during storage/transport Maximum altitude above sea level without derating Maximum altitude above sea level with derating Derating for high altitude, see section on special conditions EMC standards, Emission EMC standards, Immunity See section on special conditions! Control card performance: Scan interval Control card, USB serial communication: USB standard USB plug
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3 EN 61800-3, EN 61000-6-1/2, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
CAUTION
Connection to PC is carried out via a standard host/device USB cable. The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. The USB connection is not galvanically isolated from protection earth. Use only isolated laptop/PC as connection to the USB connector on frequency converter or an isolated USB cable/converter.
168
Relative E ciency
Protection and Features Electronic thermal motor protection against overload. Temperature monitoring of the heatsink ensures that the frequency converter trips if the temperature reaches 95C 5C. An overload temperature cannot be reset until the temperature of the heatsink is below 70C 5C (Guideline these temperatures may vary for different power sizes, enclosures etc.). The frequency converter has an auto derating function to avoid it's heatsink reaching 95C. The frequency converter is protected against shortcircuits on motor terminals U, V, W. If a mains phase is missing, the frequency converter trips or issues a warning (depending on the load). Monitoring of the intermediate circuit voltage ensures that the frequency converter trips if the intermediate circuit voltage is too low or too high. The frequency converter is protected against earth faults on motor terminals U, V, W.
1.0 0.99 0.98 0.97 0.96 0.95 0.94 0.93 0.92 0% 50% 100% load 100% % Speed 75% load 150% 50% load
Example: Assume a 55kW, 380-480V AC frequency converter at 25% load at 50% speed. The graph is showing 0,97 - rated efficiency for a 55kW FC is 0.98. The actual efficiency is then: 0.97x0.98=0.95. Efficiency of the motor (MOTOR ) The efficiency of a motor connected to the frequency converter depends on magnetizing level. In general, the efficiency is just as good as with mains operation. The efficiency of the motor depends on the type of motor. In the range of 75-100% of the rated torque, the efficiency of the motor is practically constant, both when it is controlled by the frequency converter and when it runs directly on mains. In small motors, the influence from the U/f characteristic on efficiency is marginal. However, in motors from 11kW and up, the advantages are significant. In general, the switching frequency does not affect the efficiency of small motors. Motors from 11kW and up have their efficiency improved (1-2%). This is because the sine shape of the motor current is almost perfect at high switching frequency. Efficiency of the system (SYSTEM) To calculate the system efficiency, the efficiency of the frequency converter (VLT) is multiplied by the efficiency of the motor (MOTOR): SYSTEM = VLT x MOTOR
130BB252.11
1.01
8 8
8.3 Efficiency
Efficiency of the frequency converter (VLT) The load on the frequency converter has little effect on its efficiency. In general, the efficiency is the same at the rated motor frequency fM,N, even if the motor supplies 100% of the rated shaft torque or only 75%, i.e. in case of part loads. This also means that the efficiency of the frequency converter does not change even if other U/f characteristics are chosen. However, the U/f characteristics influence the efficiency of the motor. The efficiency declines a little when the switching frequency is set to a value of above 5 kHz. The efficiency will also be slightly reduced if the mains voltage is 480 V, or if the motor cable is longer than 30m. Frequency converter efficiency calculation Calculate the efficiency of the frequency converter at different loads based on Illustration 8.1. The factor in this graph must be multiplied with the specific efficiency factor listed in the specification tables:
169
The natural induction causes an overshoot UPEAK in the motor voltage before it stabilizes itself at a level depending on the voltage in the intermediate circuit. The rise time and the peak voltage UPEAK affect the service life of the motor. If the peak voltage is too high, especially motors without phase coil insulation are affected. If the motor cable is short (a few metres), the rise time and peak voltage are lower. If the motor cable is long (100m), the rise time and peak voltage increases. In motors without phase insulation paper or other insulation reinforcement suitable for operation with voltage supply (such as a frequency converter), fit a sine-wave filter on the output of the frequency converter. To obtain approximate values for cable lengths and voltages not mentioned below, use the following rules of thumb: 1. 2. 3. Rise time increases/decreases proportionally with cable length. UPEAK = DC link voltage x 1.9 (DC link voltage = Mains voltage x 1.35).
dU dt =
8 8
* 315kW, 380-480V AC and 450-500kW, 525-690V AC only. ** Remaining E1/E2 power sizes. *** For D, E and F sizes, reduced fan speed is at 87%, measured at 200V.
0.8 U PEAK
Risetime
Data are measured according to IEC 60034-17. Cable lengths are in metres.
Frequency Converter, P5K5, T2 Cable length [m] 36 50 100 150 Frequency Converter, P7K5, T2 Cable length [m] 5 50 100 150 Mains voltage [V] 230 230 230 230 Rise time [sec] 0.13 0.23 0.54 0.66 011893-0001 0.510 0.590 0.580 0.560 dU/dt [kV/sec] 3.090 2.034 0.865 0.674
170
Frequency Converter, P11K, T2 Cable length [m] 36 136 150 Frequency Converter, P15K, T2 Cable length [m] 30 100 150 Frequency Converter, P18K, T2 Cable length [m] 36 136 150 Frequency Converter, P22K, T2 Cable length [m] 36 136 150 Frequency Converter, P30K, T2 Cable length [m] 15 50 150 Frequency Converter, P37K, T2 Cable length [m] 30 100 150 Frequency Converter, P45K, T2 Cable length [m] 30 100 150 Mains voltage [V] 240 240 240 Rise time [sec] 0.300 0.536 0.776 Vpeak [kV] 0.598 0.566 0.546 dU/dt [kV/sec] 1.593 0.843 0.559 Mains voltage [V] 240 240 240 Rise time [sec] 0.300 0.536 0.776 Vpeak [kV] 0.598 0.566 0.546 dU/dt [kV/sec] 1.593 0.843 0.559 Mains voltage [V] 240 240 240 Rise time [sec] 0.194 0.252 0.444 Vpeak [kV] 0.626 0.574 0.538 dU/dt [kV/sec] 2.581 1.929 0.977 Mains voltage [V] 240 240 240 Rise time [sec] 0.244 0.560 0.720 Vpeak [kV] 0.608 0.580 0.574 dU/dt [kV/sec] 1.993 0.832 0.661 Mains voltage [V] 240 240 240 Rise time [sec] 0.244 0.568 0.720 Vpeak [kV] 0.608 0.580 0.574 dU/dt [kV/sec] 1.993 0.832 0.661 Mains voltage [V] 240 240 240 Rise time [sec] 0.556 0.592 0.708 Vpeak [kV] 0.650 0.594 0.575 dU/dt [kV/sec] 0.935 0.807 0.669 240 240 240 Rise time [sec] 0.264 0.536 0.568 Vpeak [kV] 0.624 0.596 0.568 dU/dt [kV/sec] 1.894 0.896 0.806
8 8
171
Frequency Converter, P1K5, T4 Cable length [m] 5 50 150 Frequency Converter, P4K0, T4 Cable length [m] 5 50 150 Frequency Converter, P7K5, T4 Cable length [m] 5 50 150 Frequency Converter, P11K, T4 Cable length [m] 15 100 150 Frequency Converter, P15K, T4 Cable length [m] 36 100 150 Frequency Converter, P18K, T4 Cable length [m] 36 100 150 Frequency Converter, P22K, T4 Cable length [m] 36 100 150 Mains voltage [V] 400 400 400 Rise time [sec] 0.232 0.410 0.430 Vpeak [kV] 0.950 0.980 0.970 dU/dt [kV/sec] 3.534 1.927 1.860 Mains voltage [V] 400 400 400 Rise time [sec] 0.344 1.000 1.400 Vpeak [kV] 1.040 1.190 1.040 dU/dt [kV/sec] 2.442 0.950 0.596 Mains voltage [V] 400 400 400 Rise time [sec] 0.422 0.464 0.896 Vpeak [kV] 1.060 0.900 1.000 dU/dt [kV/sec] 2.014 1.616 0.915 Mains voltage [V] 400 400 400 Rise time [sec] 0.408 0.364 0.400 Vpeak [kV] 0.718 1.050 0.980 dU/dt [kV/sec] 1.402 2.376 2.000 Mains voltage [V] 400 400 400 Rise time [sec] 0.04755 0.207 0.6742 Vpeak [kV] 0.739 1.040 1.030 dU/dt [kV/sec] 8.035 4.548 2.828 Mains voltage [V] 400 400 400 Rise time [sec] 0.172 0.310 0.370 1.190 Vpeak [kV] 0.890 dU/dt [kV/sec] 4.156 2.564 1.770 Mains voltage [V] 400 400 400 Rise time [sec] 0.640 0.470 0.760 Vpeak [kV] 0.690 0.985 1.045 dU/dt [kV/sec] 0.862 0.985 0.947
8 8
172
Frequency Converter, P30K, T4 Cable length [m] 15 100 150 Frequency Converter, P37K, T4 Cable length [m] 5 50 100 150 Frequency Converter, P45K, T4 Cable length [m] 36 50 100 150 Frequency Converter, P55K, T4 Cable length [m] 10 Frequency Converter, P75K, T4 Cable length [m] 5 Mains voltage [V] 480 Rise time [sec] 0.371 Vpeak [kV] 1.170 dU/dt [kV/sec] 2.466 Mains voltage [V] 400 Rise time [sec] 0.350 Vpeak [kV] 0.932 dU/dt [kV/sec] 2.130 Mains voltage [V] 400 400 400 400 Rise time [sec] 0.254 0.465 0.815 0.890 Vpeak [kV] 1.056 1.048 1.032 1.016 dU/dt [kV/sec] 3.326 1.803 1.013 0.913 Mains voltage 480 480 480 480 Rise time [sec] 0.270 0.435 0.840 0.940 Vpeak [kV] 1.276 1.184 1.188 1.212 dU/dt [kV/sec] 3.781 2.177 1.131 1.031 Mains voltage [V] 400 400 400 Rise time [sec] 0.271 0.440 0.520 Vpeak [kV] 1.000 1.000 0.990 dU/dt [kV/sec] 3.100 1.818 1.510
8 8
Frequency Converter, P90K, T4 Cable length [m] 5 Mains voltage [V] 400 Rise time [sec] 0.364 Vpeak [kV] 1.030 dU/dt [kV/sec] 2.264
Frequency Converter, P315 - P1M0, T4 Cable length [m] 30 30 30 30 1) With Danfoss dU/dt filter. Mains voltage [V] 500 400 500 400
1 1
173
Frequency Converter, P450 - P1M4, T7 Cable length [m] 30 30 30 1) With Danfoss dU/dt filter. Mains voltage [V] 690 575 690
1)
8 8
1 km
2 km
3 km
Altitude (km)
An alternative is to lower the ambient temperature at high altitudes and thereby ensure 100% output current at high altitudes. As an example of how to read the graph, the situation at 2 km is elaborated. At a temperature of 45 C (TAMB, MAX - 3.3 K), 91% of the rated output current is available. At a temperature of 41.7 C, 100% of the rated output current is available.
174
95
130BB008.10
IOUT(%) 100
power is proportional to the cube of the speed, there is no need for additional cooling or de-rating of the motor. In the graphs shown below, the typical VT curve is below the maximum torque with de-rating and maximum torque with forced cooling at all speeds.
Maximum load for a standard motor at 40 C driven by a frequency converter type VLT FCxxx
90
85
500
1000
1500
2000
2500
3000
100 80
1)
130BB009.10
(C) 45
T%
60 40 20
Amb. Temp.
40
HO
10
20
30
40
50 v%
60
70
80
90
100 110
35
NO
Legend: Typical torque at VT load Max torque with forced cooling Max torque Note 1) Over-syncronous speed operation will result in the available motor torque decreasing inversely proportional with the increase in speed. This must be considered during the design phase to avoid over-loading of the motor.
130BA893.10
80
120
30
500
3000
8 8
Derating of output current versus altitude at TAMB, MAX for frame sizes D, E and F.
A warning or an alarm is signalled by the relevant LED on the front of the frequency converter and indicated by a code on the display. A warning remains active until its cause is no longer present. Under certain circumstances operation of the motor may still be continued. Warning messages may be critical, but are not necessarily so. In the event of an alarm, the frequency converter will have tripped. Alarms must be reset to restart operation once their cause has been rectified. This may be done in four ways: 1. By using the [RESET] control button on the LCP. 2. 3. 4. Via a digital input with the Reset function. Via serial communication/optional fieldbus. By resetting automatically using the [Auto Reset] function, which is a default setting for VLT HVAC Drive Drive, see 14-20 Reset Mode in the FC 100 Programming Guide
175
NOTE
After a manual reset using the [RESET] button on the LCP, the [AUTO ON] or [HAND ON] button must be pressed to restart the motor. If an alarm cannot be reset, the reason may be that its cause has not been rectified, or the alarm is trip-locked (see also table on following page).
CAUTION
Alarms that are trip-locked offer additional protection, means that the mains supply must be switched off before the alarm can be reset. After being switched back on, the frequency converter is no longer blocked and may be reset as described above once the cause has been rectified. Alarms that are not trip-locked can also be reset using the automatic reset function in 14-20 Reset Mode (Warning: automatic wake-up is possible!) If a warning and alarm is marked against a code in the table on the following page, this means that either a warning occurs before an alarm, or it can be specified whether it is a warning or an alarm that is to be displayed for a given fault. This is possible, for instance, in 1-90 Motor Thermal Protection. After an alarm or trip, the motor carries on coasting, and the alarm and warning flash on the frequency converter. Once the problem has been rectified, only the alarm continues flashing. Warning
X (X) (X) (X) X X X X X (X) (X) X X X X X X (X) (X) X X X X X (X) X X X (X) X (X) X (X) (X) (X) X X X X (X) X (X) X (X) (X) (X) X X X X X X (X) (X) (X) X 4-58 4-58 4-58 2-15 2-13 14-53 (X) X X X X X 8-04 1-90 1-90 (X) (X) (X) 6-01 1-80 14-12
8 8
No. Description
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 10 Volts low Live zero error No motor Mains phase loss DC link voltage high DC link voltage low DC over voltage DC under voltage Inverter overloaded Motor ETR over temperature Motor thermistor over temperature Torque limit Over Current Earth fault Hardware mismatch Short Circuit Control word timeout Start failed Internal Fan Fault External Fan Fault Brake resistor short-circuited Brake resistor power limit Brake chopper short-circuited Brake check Drive over temperature Motor phase U missing Motor phase V missing Motor phase W missing Inrush fault Fieldbus communication fault Out of frequency range Mains failure Phase Imbalance
Alarm/ Trip
Alarm/Trip Lock
Parameter Reference
176
No. Description
38 39 40 41 42 42 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 62 64 65 66 67 69 70 71 72 73 76 79 80 91 92 93 94 95 96 97 98 Internal fault Heatsink sensor Overload of Digital Output Terminal 27 Overload of Digital Output Terminal 29 Overload of Digital Output On X30/6 Overload of Digital Output On X30/7 Pwr. card supply 24 V supply low 1.8 V supply low Speed limit AMA calibration failed AMA check Unom and Inom AMA low Inom AMA motor too big AMA motor too small AMA Parameter out of range AMA interrupted by user AMA timeout AMA internal fault Current limit External Interlock Output Frequency at Maximum Limit Voltage Limit Control Board Over-temperature Heat sink Temperature Low Option Configuration has Changed Pwr. Card Temp Illegal FC configuration PTC 1 Safe Stop Dangerous Failure Safe Stop Auto Restart Power Unit Setup Illegal PS config Drive Initialized to Default Value Analog input 54 wrong settings NoFlow Dry Pump End of Curve Broken Belt Start Delayed Stop Delayed Clock Fault
Warning
Alarm/ Trip
X X
Alarm/Trip Lock
X X
Parameter Reference
1-86
8 8
201 Fire M was Active 202 Fire M Limits Exceeded 203 Missing Motor 204 Locked Rotor 243 Brake IGBT 244 Heatsink temp 245 Heatsink sensor 246 Pwr.card supply 247 Pwr.card temp 248 Illegal PS config X X X X X X X X X X X X X
177
No. Description
250 New spare parts 251 New Type Code Table 8.14 Alarm/Warning code list
Warning
Alarm/ Trip
X
Alarm/Trip Lock
X X
Parameter Reference
(X) Dependent on parameter 1) Can not be Auto reset via 14-20 Reset Mode A trip is the action when an alarm has appeared. The trip will coast the motor and can be reset by pressing the reset button or make a reset by a digital input (parameter group 5-1* [1]). The original event that caused an alarm cannot damage the frequency converter or cause dangerous conditions. A trip lock is an action when an alarm occurs, which may cause damage to frequency converter or connected parts. A Trip Lock situation can only be reset by a power cycling.
Alarm Word and Extended Status Word Bit 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 Hex 00000001 00000002 00000004 00000008 00000010 00000020 00000040 00000080 00000100 00000200 00000400 00000800 00001000 00002000 00004000 00008000 00010000 00020000 00040000 00080000 00100000 00200000 00400000 00800000 01000000 02000000 04000000 08000000 10000000 20000000 40000000 Dec 1 2 4 8 16 32 64 128 256 512 1024 2048 4096 8192 16384 32768 65536 131072 262144 524288 1048576 2097152 4194304 8388608 16777216 33554432 67108864 134217728 268435456 536870912 1073741824 Alarm Word Brake Check Pwr. Card Temp Earth Fault Ctrl.Card Temp Ctrl. Word TO Over Current Torque Limit Motor Th Over Motor ETR Over Inverter Overld. DC under Volt DC over Volt Short Circuit Inrush Fault Mains ph. Loss AMA Not OK Live Zero Error Internal Fault Brake Overload U phase Loss V phase Loss W phase Loss Fieldbus Fault 24 V Supply Low Mains Failure 1.8V Supply Low Brake Resistor Brake IGBT Option Change Drive Initialized Safe Stop
LED indication Warning Alarm Trip locked yellow flashing red yellow and red
8 8
Warning Word Brake Check Pwr. Card Temp Earth Fault Ctrl.Card Temp Ctrl. Word TO Over Current Torque Limit Motor Th Over Motor ETR Over Inverter Overld. DC under Volt DC over Volt DC Voltage Low DC Voltage High Mains ph. Loss No Motor Live Zero Error 10V Low Brake Overload Brake Resistor Brake IGBT Speed Limit Fieldbus Fault 24V Supply Low Mains Failure Current Limit Low Temp Voltage Limit Unused Unused Unused
Extended Status Word Ramping AMA Running Start CW/CCW Slow Down Catch Up Feedback High Feedback Low Output Current High Output Current Low Output Freq High Output Freq Low Brake Check OK Braking Max Braking Out of Speed Range OVC Active
Table 8.15 Description of Alarm Word, Warning Word and Extended Status Word
178
The alarm words, warning words and extended status words can be read out via serial bus or optional fieldbus for diagnosis. See also 16-90 Alarm Word, 16-92 Warning Word and 16-94 Ext. Status Word.
8 8
179
8 8
180
8 8
181
Troubleshooting Connect a brake resistor Extend the ramp time Change the ramp type Activate functions in 2-10 Brake Function Increase 14-26 Trip Delay at Inverter Fault WARNING/ALARM 8, DC under voltage If the intermediate circuit voltage (DC) drops below the under voltage limit, the frequency converter checks if a 24V DC backup supply is connected. If no 24V DC backup supply is connected, the frequency converter trips after a fixed time delay. The time delay varies with unit size. Troubleshooting Check that the supply voltage matches the frequency converter voltage. Perform Input voltage test Perform soft charge and rectifier circuit test WARNING/ALARM 9, Inverter overload The frequency converter is about to cut out because of an overload (too high current for too long). The counter for electronic, thermal inverter protection gives a warning at 98% and trips at 100%, while giving an alarm. The frequency converter cannot be reset until the counter is below 90%. The fault is that the frequency converter is overloaded by more than 100% for too long. Troubleshooting Compare the output current shown on the LCP with the frequency converter rated current. Compare the output current shown on the LCP with measured motor current. Display the Thermal Drive Load on the LCP and monitor the value. When running above the frequency converter continuous current rating, the counter should increase. When running below the frequency converter continuous current rating, the counter should decrease. See the derating section in the Design Guide for more details if a high switching frequency is required. WARNING/ALARM 10, Motor overload temperature According to the electronic thermal protection (ETR), the motor is too hot. Select whether the frequency converter gives a warning or an alarm when the counter reaches 100% in 1-90 Motor Thermal Protection. The fault occurs when the motor is overloaded by more than 100% for too long. Troubleshooting Check for motor overheating. Check if the motor is mechanically overloaded Check that the motor current set in 1-24 Motor Current is correct.
8 8
182
Ensure that Motor data in parameters 1-20 through 1-25 are set correctly. If an external fan is in use, check in 1-91 Motor External Fan that it is selected. Running AMA in 1-29 Automatic Motor Adaptation (AMA) may tune the frequency converter to the motor more accurately and reduce thermal loading. WARNING/ALARM 11, Motor thermistor over temp The thermistor might be disconnected. Select whether the frequency converter gives a warning or an alarm in 1-90 Motor Thermal Protection. Troubleshooting Check for motor overheating. Check if the motor is mechanically overloaded. When using terminal 53 or 54, check that the thermistor is connected correctly between either terminal 53 or 54 (analog voltage input) and terminal 50 (+10V supply) and that the terminal switch for 53 or 54 is set for voltage. Check 1-93 Thermistor Source selects terminal 53 or 54. When using digital inputs 18 or 19, check that the thermistor is connected correctly between either terminal 18 or 19 (digital input PNP only) and terminal 50. Check 1-93 Thermistor Source selects terminal 18 or 19. WARNING/ALARM 12, Torque limit The torque has exceeded the value in 4-16 Torque Limit Motor Mode or the value in 4-17 Torque Limit Generator Mode. 14-25 Trip Delay at Torque Limit can change this from a warning only condition to a warning followed by an alarm. Troubleshooting If the motor torque limit is exceeded during ramp up, extend the ramp up time. If the generator torque limit is exceeded during ramp down, extend the ramp down time. If torque limit occurs while running, possibly increase the torque limit. Be sure the system can operate safely at a higher torque. Check the application for excessive current draw on the motor. WARNING/ALARM 13, Over current The inverter peak current limit (approx. 200% of the rated current) is exceeded. The warning lasts about 1.5 sec., then the frequency converter trips and issues an alarm. This fault may be caused by shock loading or fast acceleration with high inertia loads. If extended mechanical brake control is selected, trip can be reset externally.
Troubleshooting Remove power and check if the motor shaft can be turned. Check that the motor size matches the frequency converter. Check parameters 1-20 through 1-25 for correct motor data. ALARM 14, Earth (ground) fault There is current from the output phases to earth, either in the cable between the frequency converter and the motor or in the motor itself. Troubleshooting Remove power to the frequency converter and repair the earth fault. Check for earth faults in the motor by measuring the resistance to ground of the motor leads and the motor with a megohmmeter. ALARM 15, Hardware mismatch A fitted option is not operational with the present control board hardware or software. Record the value of the following parameters and contact your Danfoss supplier: 15-40 FC Type 15-41 Power Section 15-42 Voltage 15-43 Software Version 15-45 Actual Typecode String 15-49 SW ID Control Card 15-50 SW ID Power Card 15-60 Option Mounted 15-61 Option SW Version ALARM 16, Short circuit There is a short circuit in the motor or motor wiring. Remove power to the frequency converter and repair the short circuit. WARNING/ALARM 17, Control word timeout There is no communication to the frequency converter. The warning will only be active when 8-04 Control Timeout Function is NOT set to [0] OFF. If 8-04 Control Timeout Function is set to Stop and Trip, a warning appears and the frequency converter ramps down until it stops then displays an alarm. Troubleshooting Check connections on the serial communication cable. Increase 8-03 Control Timeout Time Check operation of the communication equipment. Verify proper installation based on EMC requirements.
8 8
183
ALARM 18, Start failed The speed has not been able to exceed 1-77 Compressor Start Max Speed [RPM] during start within the allowed time. (set in 1-79 Compressor Start Max Time to Trip). This may be caused by a blocked motor. WARNING 23, Internal fan fault The fan warning function checks if the fan is running. The fan warning can be disabled in 14-53 Fan Monitor. Troubleshooting Check for proper fan operation. Cycle power to the frequency converter and check that the fan operates briefly at start up. Check the sensors on the heatsink and control card. WARNING 24, External fan fault The fan warning function checks if the fan is running. The fan warning can be disabled in 14-53 Fan Monitor. Troubleshooting Check for proper fan operation. Cycle power to the frequency converter and check that the fan operates briefly at start up. Check the sensors on the heatsink and control card. WARNING 25, Brake resistor short circuit The brake resistor is monitored during operation. If a short circuit occurs, the brake function is disabled and the warning appears. The frequency converter is still operational but without the brake function. Remove power to the frequency converter and replace the brake resistor (see 2-15 Brake Check). WARNING/ALARM 26, Brake resistor power limit The power transmitted to the brake resistor is calculated as a mean value over the last 120 seconds of run time. The calculation is based on the intermediate circuit voltage and the brake resistance value set in 2-16 AC brake Max. Current. The warning is active when the dissipated braking is higher than 90% of the brake resistance power. If Trip [2] is selected in 2-13 Brake Power Monitoring, the frequency converter will trip when the dissipated braking power reaches 100%. WARNING/ALARM 27, Brake chopper fault The brake transistor is monitored during operation and if a short circuit occurs, the brake function is disabled and a warning is issued. The frequency converter is still operational but, since the brake transistor has short-circuited, substantial power is transmitted to the brake resistor, even if it is inactive. Remove power to the frequency converter and remove the brake resistor. WARNING/ALARM 28, Brake check failed The brake resistor is not connected or not working. Check 2-15 Brake Check. ALARM 29, Heatsink temp The maximum temperature of the heatsink has been exceeded. The temperature fault will not reset until the temperature falls below the reset heatsink temperature. The
trip and reset points are based on the frequency converter power size. Troubleshooting Check for the following conditions. Ambient temperature too high. Motor cable too long. Incorrect airflow clearance above and below the frequency converter. Blocked airflow around the frequency converter. Damaged heatsink fan. Dirty heatsink. ALARM 30, Motor phase U missing Motor phase U between the frequency converter and the motor is missing. Remove power from the frequency converter and check motor phase U. ALARM 31, Motor phase V missing Motor phase V between the frequency converter and the motor is missing. Remove power from the frequency converter and check motor phase V. ALARM 32, Motor phase W missing Motor phase W between the frequency converter and the motor is missing. Remove power from the frequency converter and check motor phase W. ALARM 33, Inrush fault Too many power-ups have occurred within a short time period. Let the unit cool to operating temperature. WARNING/ALARM 34, communication fault Communication between the and the communication option card is not operating. WARNING/ALARM 36, Mains failure This warning/alarm is only active if the supply voltage to the frequency converter is lost and 14-10 Mains Failure is NOT set to [0] No Function. Check the fuses to the frequency converter and mains power supply to the unit. ALARM 38, Internal fault When an internal fault occurs, a code number defined in the table below is displayed. Troubleshooting Cycle power to the frequency converter. Check that the option is properly installed. Check for loose or missing wiring. It may be necessary to contact your Danfoss supplier or service department. Note the code number for further troubleshooting directions.
8 8
184
No.
0 256-258 512-519 783 1024-1284 1299 1300 1302 1315 1316 1318 1379-2819 2820 2821 2822 3072-5122 5123 5124 5125 5126 5376-6231
Text
Serial port cannot be initialised. Contact yourDanfoss supplier or DanfossService Department. Power EEPROM data is defect or too old Internal fault. Contact yourDanfoss supplier or Danfoss Service Department. Parameter value outside of min/max limits Internal fault. Contact your Danfoss supplier or the Danfoss Service Department. Option SW in slot A is too old Option SW in slot B is too old Option SW in slot C1 is too old Option SW in slot A is not supported (not allowed) Option SW in slot B is not supported (not allowed) Option SW in slot C1 is not supported (not allowed) Internal fault. Contact yourDanfoss supplier or DanfossService Department. LCP stack overflow Serial port overflow USB port overflow Parameter value is outside its limits Option in slot A: Hardware incompatible with control board hardware Option in slot B: Hardware incompatible with control board hardware Option in slot C0: Hardware incompatible with control board hardware Option in slot C1: Hardware incompatible with control board hardware Internal fault. Contact yourDanfoss supplier or DanfossService Department.
ALARM 45, Earth fault 2 Earth (ground) fault on start up. Troubleshooting Check for proper earthing (grounding) and loose connections. Check for proper wire size. Check motor cables for short-circuits or leakage currents. ALARM 46, Power card supply The supply on the power card is out of range. There are three power supplies generated by the switch mode power supply (SMPS) on the power card: 24V, 5V, +/18V. When powered with 24V DC with the MCB 107 option, only the 24V and 5V supplies are monitored. When powered with three phase mains voltage, all three supplied are monitored. Troubleshooting Check for a defective power card. Check for a defective control card. Check for a defective option card. If a 24V DC power supply is used, verify proper supply power. WARNING 47, 24V supply low The 24 V DC is measured on the control card. The external 24V DC backup power supply may be overloaded, otherwise contact your Danfoss supplier. WARNING 48, 1.8V supply low The 1.8V DC supply used on the control card is outside of allowable limits. The power supply is measured on the control card. Check for a defective control card. If an option card is present, check for an overvoltage condition. WARNING 49, Speed limit When the speed is not within the specified range in 4-11 Motor Speed Low Limit [RPM] and 4-13 Motor Speed High Limit [RPM], the frequency converter will show a warning. When the speed is below the specified limit in 1-86 Trip Speed Low [RPM] (except when starting or stopping) the frequency converter will trip. ALARM 50, AMA calibration failed Contact yourDanfoss supplier or DanfossService Department. ALARM 51, AMA check Unom and Inom The settings for motor voltage, motor current, and motor power are wrong. Check the settings in parameters 1-20 to 1-25. ALARM 52, AMA low Inom The motor current is too low. Check the setting in 4-18 Current Limit. ALARM 53, AMA motor too big The motor is too big for the AMA to operate. ALARM 54, AMA motor too small The motor is too small for the AMA to operate.
8 8
ALARM 39, Heatsink sensor No feedback from the heatsink temperature sensor. The signal from the IGBT thermal sensor is not available on the power card. The problem could be on the power card, on the gate drive card, or the ribbon cable between the power card and gate drive card. WARNING 40, Overload of digital output terminal 27 Check the load connected to terminal 27 or remove shortcircuit connection. Check 5-00 Digital I/O Mode and 5-01 Terminal 27 Mode. WARNING 41, Overload of digital output terminal 29 Check the load connected to terminal 29 or remove shortcircuit connection. Check 5-00 Digital I/O Mode and 5-02 Terminal 29 Mode. WARNING 42, Overload of digital output on X30/6 or overload of digital output on X30/7 For X30/6, check the load connected to X30/6 or remove short-circuit connection. Check 5-32 Term X30/6 Digi Out (MCB 101). For X30/7, check the load connected to X30/7 or remove short-circuit connection. Check 5-33 Term X30/7 Digi Out (MCB 101).
185
ALARM 55, AMA Parameter out of range The parameter values of the motor are outside of the acceptable range. AMAwill not run. ALARM 56, AMA interrupted by user The AMA has been interrupted by the user. ALARM 57, AMA timeout Try to restart AMA again. Repeated restarts may over heat the motor. ALARM 58, AMA internal fault Contact your Danfoss supplier. WARNING 59, Current limit The current is higher than the value in 4-18 Current Limit. Ensure that Motor data in parameters 1-20 through 1-25 are set correctly. Possibly increase the current limit. Be sure the system can operate safely at a higher limit. ALARM 60, External interlock A digital input signal is indicating a fault condition external to the frequency converter. An external interlock has commanded the frequency converter to trip. Clear the external fault condition. To resume normal operation, apply 24V DC to the terminal programmed for external interlock. Reset the frequency converter. WARNING 62, Output frequency at maximum limit The output frequency has reached the value set in 4-19 Max Output Frequency. Check the application to determine the cause. Possibly increase the output frequency limit. Be sure the system can operate safely at a higher output frequency. The warning will clear when the output drops below the maximum limit. WARNING/ALARM 65, Control card over temperature The cutout temperature of the control card is 80 C. Troubleshooting Check that the ambient operating temperature is within limits. Check for clogged filters. Check fan operation. Check the control card. WARNING 66, Heatsink temperature low The frequency converter is too cold to operate. This warning is based on the temperature sensor in the IGBT module. Increase the ambient temperature of the unit. Also, a trickle amount of current can be supplied to the frequency converter whenever the motor is stopped by setting 2-00 DC Hold/Preheat Current at 5% and 1-80 Function at Stop. ALARM 67, Option module configuration has changed One or more options have either been added or removed since the last power down. Check that the configuration change is intentional and reset the frequency converter.
ALARM 68, Safe stop activated Loss of the 24V DC signal on terminal 37 has caused the frequency converter to trip. To resume normal operation, apply 24V DC to terminal 37 and reset the frequency converter. ALARM 69, Power card temperaturePower card temperature The temperature sensor on the power card is either too hot or too cold. Troubleshooting Check that the ambient operating temperature is within limits. Check for clogged filters. Check fan operation. Check the power card. ALARM 70, Illegal FC configuration The control card and power card are incompatible. Contact your supplier with the typecode of the unit from the nameplate and the part numbers of the cards to check compatibility. ALARM 80, Drive initialised to default value Parameter settings are initialised to default settings after a manual reset. Reset the unit to clear the alarm. ALARM 92, No flow A no-flow condition has been detected in the system. 22-23 No-Flow Function is set for alarm. Troubleshoot the system and reset the frequency converter after the fault has been cleared. ALARM 93, Dry pump A no-flow condition in the system with the frequency converter operating at high speed may indicate a dry pump. 22-26 Dry Pump Function is set for alarm. Troubleshoot the system and reset the frequency converter after the fault has been cleared. ALARM 94, End of curve Feedback is lower than the set point. This may indicate leakage in the system. 22-50 End of Curve Function is set for alarm. Troubleshoot the system and reset the frequency converter after the fault has been cleared. ALARM 95, Broken belt Torque is below the torque level set for no load, indicating a broken belt. 22-60 Broken Belt Function is set for alarm. Troubleshoot the system and reset the frequency converter after the fault has been cleared. ALARM 96, Start delayed Motor start has been delayed due to short-cycle protection. 22-76 Interval between Starts is enabled. Troubleshoot the system and reset the frequency converter after the fault has been cleared. WARNING 97, Stop delayed Stopping the motor has been delayed due to short cycle protection. 22-76 Interval between Starts is enabled. Troubleshoot the system and reset the frequency converter after the fault has been cleared.
8 8
186
WARNING 98, Clock fault Time is not set or the RTC clock has failed. Reset the clock in 0-70 Date and Time. WARNING, 200 Fire mode This indicates the frequency controller is operating in fire mode. The warning clears when fire mode is removed. See the fire mode data in the alarm log. WARNING 201, Fire mode was active This indicates the frequency controller had entered fire mode. Cycle power to the unit to remove the warning. See the fire mode data in the alarm log. WARNING 202, Fire mode limits exceeded While operating in fire mode one or more alarm conditions has been ignored which would normally trip the unit. Operating in this condition voids unit warranty. Cycle power to the unit to remove the warning. See the fire mode data in the alarm log. WARNING 203, Missing motor With a frequency converter operating multi-motors, an under-load condition was detected. This could indicate a missing motor. Inspect the system for proper operation. WARNING 204, Locked rotor With a frequency converter operating multi-motors, an overload condition was detected. This could indicate a locked rotor. Inspect the motor for proper operation. WARNING 250, New spare part A component in the frequency converter has been replaced. Reset the frequency converter for normal operation. WARNING 251, New typecode A component in the frequency converter has been replaced and the typecode changed. Reset the frequency converter for normal operation.
8 8
187
Index
Index A
Abbreviations........................................................................................... 6 Accessory Bags...................................................................................... 84 Acoustic Noise..................................................................................... 169 Aggressive Environments.................................................................. 12 Air Humidity........................................................................................... 12 Alarm Words........................................................................................ 179 Alarm/Warning Code List................................................................ 178 Alarms And Warnings....................................................................... 175 Aluminium Conductors...................................................................... 91 AMA........................................................................................................ 116 Analog I/O Option MCB 109........................................................................ 53 I/O Selection...................................................................................... 53 Inputs.............................................................................. 7, 182, 8, 165 Output............................................................................................... 166 Outputs - Terminal X30/5+8........................................................ 50 Voltage Inputs - Terminal X30/10-12........................................ 50 Application Examples......................................................................... 22 Automatic Adaptations To Ensure Performance..................................... 174 Motor Adaptation.......................................................................... 116 Motor Adaptation (AMA)............................................................ 103 AWG..................................................................................... 141, 142, 146
Cable Clamp................................................................................................. 114 Clamps............................................................................................... 111 Length And Cross-section............................................................. 91 Lengths And Cross Sections...................................................... 165 Caution..................................................................................................... 10 CAV System............................................................................................. 24 CE Conformity And Labelling........................................................... 11 Central VAV Systems........................................................................... 23 Clearance.............................................................................................. 184 Clockwise Rotation............................................................................ 108 Closed Loop Control For A Ventilation System......................... 37 CO2 Sensor.............................................................................................. 24 Coasting................................................................................... 139, 7, 137 Communication Option................................................................... 184 Comparison Of Energy Savings....................................................... 19 Condenser Pumps................................................................................ 27 Conducted Emission........................................................................... 41 Constant Air Volume.......................................................................................... 24 Torque Applications (CT Mode)............................................... 175 Control Cable Terminals................................................................................ 99 Cables............................................................... 111, 90, 101, 89, 101 Card Performance......................................................................... 168 Card, 10 V DC Output................................................................... 167 Card, 24 V DC Output................................................................... 167 Card, RS-485 Serial Communication:...................................... 166 Card, USB Serial Communication:............................................ 168 Characteristics................................................................................ 167 Potential.............................................................................................. 30 Structure Closed Loop.................................................................... 33 Structure Open Loop...................................................................... 31 Terminals............................................................................................. 99 Word................................................................................................... 137 Cooling Cooling.............................................................................................. 175 Conditions.......................................................................................... 85 Tower Fan........................................................................................... 25 Copyright, Limitation Of Liability And Revision Rights............. 4 Cos Compensation.......................................................................... 20 Current Limit.................................................................................................... 183 Rating................................................................................................. 182
BACnet...................................................................................................... 70 Balancing Contractor.......................................................................... 28 Basic Wiring Example....................................................................... 100 Battery Back-up Of Clock Function................................................ 53 Better Control........................................................................................ 20 Brake Function.............................................................................................. 46 Power............................................................................................... 8, 46 Resistor................................................................................................ 45 Resistor Cabling................................................................................ 46 Resistor Calculation......................................................................... 45 Resistor Temperature Switch.................................................... 106 Resistors................................................................................. 59, 79, 59 Braking................................................................................................... 184 Branch Circuit Protection................................................................... 93 Break-away Torque................................................................................. 7 Building Management System..................................................................... 53 Management System, BMS........................................................... 19 Bypass Frequency Ranges................................................................. 25
Dampers................................................................................................... 23 Data Types Supported By The Frequency Converter............ 128 DC Brake................................................................................................... 137 Link..................................................................................................... 182 Definitions................................................................................................. 7
188
Index
Derating Derating............................................................................................ 182 For Ambient Temperature......................................................... 174 For Low Air Pressure..................................................................... 174 For Running At Low Speed........................................................ 175 DeviceNet................................................................................................ 70 Differential Pressure............................................................................ 30 Digital Input................................................................................................... 183 Inputs - Terminal X30/1-4............................................................. 50 Inputs:................................................................................................ 165 Output............................................................................................... 166 Outputs - Terminal X30/5-7.......................................................... 50 Direction Of Motor Rotation.......................................................... 108 Disposal Instruction............................................................................. 11 Drive Configurator............................................................................... 64 DU/dt Filters........................................................................................... 63
FC Profile................................................................................................. 137 With Modbus RTU......................................................................... 124 Feedback..................................................................................... 185, 186 Field Mounting...................................................................................... 87 Final Set-Up And Test....................................................................... 103 Flow Meter.............................................................................................. 28 Frame Size F Panel Options.............................................................. 58 Freeze Output.......................................................................................... 7 Frequency Converter Hardware Setup........................................................ 123 Converter Set-up........................................................................... 124 Converter With Modbus RTU.................................................... 129 Function Codes Supported By Modbus RTU............................ 133 Fuse Tables............................................................................................. 96 Fuses................................................................................................ 184, 93
Earth Leakage Current............................................................... 111, 44 Earthing Earthing............................................................................................. 114 Of Screened/Armoured Control Cables................................ 114 Efficiency............................................................................................... 169 Electrical Installation......................................................................... 89, 90, 101 Installation - EMC Precautions.................................................. 111 Terminals............................................................................................. 13 Elegram Length (LGE)....................................................................... 125 EMC EMC..................................................................................................... 183 Directive 89/336/EEC...................................................................... 12 Precautions...................................................................................... 123 Test Results......................................................................................... 41 Emission Requirements...................................................................... 40 Enclosure Knock-outs......................................................................... 91 Energy Savings............................................................................... 20, 18 Equalising Cable,................................................................................ 114 ETR........................................................................................................... 107 Evaporator Flow Rate.......................................................................... 28 Example Of Closed Loop PID Control............................................ 37 Extended Status Word..................................................................................... 181 Status Word 2.................................................................................. 181 External 24V DC Supply................................................................................... 53 Fan Supply....................................................................................... 106 Extreme Running Conditions........................................................... 46
General Aspects Of EMC Emissions............................................................ 39 Aspects Of Harmonics Emission................................................. 41 Specifications.................................................................................. 165 Gland/Conduit Entry - IP21 (NEMA 1) And IP54 (NEMA12)......... 92
Harmonic Filters.................................................................................... 72 Harmonics Emission Requirements................................................................. 42 Test Results (Emission)................................................................... 42 High Power Series Mains And Motor Connections........................ 88 Voltage Test..................................................................................... 111 Hold Output Frequency................................................................... 137 How To Connect A PC To The Frequency Converter.................. 109 To Control The Frequency Converter..................................... 133
I/Os For Set Point Inputs.................................................................... 54 IEC Emergency Stop With Pilz Safety Relay................................. 58 IGVs............................................................................................................ 23 Immunity Requirements.................................................................... 42 Index (IND)............................................................................................ 127 Input Terminals.......................................................................................... 182 Voltage.............................................................................................. 182 Installation Installation....................................................................................... 183 At High Altitudes.............................................................................. 10 Insulation Resistance Monitor (IRM).............................................. 58 Intermediate Circuit.......................................................... 47, 169, 170
189
Index
Jog....................................................................................................... 7, 138
NAMUR..................................................................................................... 58 Network Connection......................................................................... 122 Ni1000 Temperature Sensor............................................................. 54 Non-UL Fuses 200V To 480V............................................................. 94
Laws Of Proportionality...................................................................... 18 LCP........................................................................................................... 7, 8 Lead Pump Alternation Wiring Diagram................................... 120 Leakage Current.................................................................................... 44 Lifting........................................................................................................ 86 Literature.................................................................................................... 5 Load Drive Settings........................................................................... 110 Local (Hand On) And Remote (Auto On) Control............................. 32 Speed Determination..................................................................... 28 Low Evaporator Temperature.......................................................... 28
Options And Accessories................................................................... 49 Ordering Numbers.............................................................................................. 64 Numbers: DU/dt Filters, 380-480V AC...................................... 78 Numbers: DU/dt Filters, 525-600/690V AC............................. 79 Numbers: Harmonic Filters........................................................... 72 Numbers: High Power Kits............................................................ 72 Numbers: Options And Accessories.......................................... 69 Numbers: Sine Wave Filter Modules, 200-500 VAC............. 76 Numbers: Sine-Wave Filter Modules, 525-600/690 VAC.......... 77 Output Current.............................................................................................. 182 Filters.................................................................................................... 63 Performance (U, V, W).................................................................. 165 Outputs For Actuators........................................................................ 54
Mains Disconnectors................................................................................. 105 Drop-out.............................................................................................. 47 Supply............................................ 9, 141, 146, 142, 149, 151, 159 Supply 3 X 525-690V AC.............................................................. 160 Voltage..................................................................................... 182, 185 Manual Motor Starters................................................................................... 59 PID Adjustment................................................................................ 39 MCB 105 Option.................................................................................... 51 MCT 31................................................................................................... 110 Mechanical Dimensions................................................................................. 83, 81 Dimensions - High Power............................................................. 82 Mounting............................................................................................ 85 Modbus Communication............................................................................. 123 Exception Codes............................................................................ 133 Moment Of Inertia................................................................................ 47 Motor Bearing Currents............................................................................ 108 Cables......................................................................................... 111, 90 Current..................................................................................... 182, 185 Data........................................................................................... 183, 186 Leads.................................................................................................. 183 Name Plate....................................................................................... 103 Name Plate Data............................................................................ 103 Output............................................................................................... 165 Parameters....................................................................................... 116 Phases.................................................................................................. 46 Power................................................................................................. 185 Protection............................................................................... 107, 169 Rotation............................................................................................ 108 Thermal Protection....................................................... 140, 47, 108 Voltage.............................................................................................. 170
190
Parallel Connection Of Motors...................................................... 107 Parameter Number (PNU)................................................................................ 127 Values................................................................................................. 134 Pay Back Period..................................................................................... 20 PC Software Tools.............................................................................. 109 PC-based Configuration Tool MCT 10 Set-up Software....... 109 Peak Voltage On Motor.................................................................... 170 PELV - Protective Extra Low Voltage.............................................. 43 PLC........................................................................................................... 114 Potentiometer Reference................................................................ 116 Power Factor...................................................................................................... 9 Factor Correction............................................................................. 20 Primary Pumps...................................................................................... 28 Principle Diagram................................................................................. 54 Profibus Profibus................................................................................................ 70 DP-V1................................................................................................. 110 Programmable Minimum Frequency Setting............................ 25
Index
Programming Programming.................................................................................. 182 Order..................................................................................................... 38 Protection Protection............................................................................. 12, 43, 45 And Features................................................................................... 169 Protocol Overview............................................................................. 123 Pt1000 Temperature Sensor............................................................. 54 Public Supply Network....................................................................... 42 Pulse Inputs................................................................................................. 166 Start/Stop......................................................................................... 115 Pump Impeller....................................................................................... 27
Set Speed Limit And Ramp Time.................................................. 103 Short Circuit (Motor Phase Phase).............................................. 46 Sine-wave Filters................................................................................... 63 Smart Logic Control................................................................................... 116 Logic Control Programming...................................................... 116 Soft-starter.............................................................................................. 20 Software Version.................................................................................................... 4 Versions............................................................................................... 70 Space Heaters And Thermostat....................................................... 58 Star/Delta Starter.................................................................................. 20 Start/Stop Start/Stop......................................................................................... 115 Conditions........................................................................................ 121 Static Overload In VVCplus Mode................................................... 47 Status Word.......................................................................................... 139 Stopping Category 0 (EN 60204-1)................................................. 17 Successful AMA................................................................................... 103 Supply Voltage.......................................................................... 182, 184 Surroundings:...................................................................................... 167 Switches S201, S202, And S801..................................................... 102 Switching Frequency................................................................................. 182, 91 On The Output.................................................................................. 47 Symbols...................................................................................................... 5 System Status And Operation....................................................... 119
Radiated Emission................................................................................ 41 Rated Motor Speed................................................................................ 7 RCD RCD................................................................................................... 9, 45 (Residual Current Device)............................................................. 58 Read Holding Registers (03 HEX).................................................. 136 Real-time Clock (RTC).......................................................................... 55 Reference Handling............................................................................. 36 Relay Option MCB 105............................................................................... 51 Output............................................................................................... 106 Outputs............................................................................................. 167 Removal Of Knockouts For Extra Cables...................................... 92 Reset.................................................................................... 182, 184, 186 Residual Current Device........................................................... 45, 114 Return Fan............................................................................................... 23 Rise Time............................................................................................... 170 RS-485 Bus Connection.................................................................... 109
The Clear Advantage - Energy Savings............................................. 17 EMC Directive (2004/108/EC)....................................................... 11 Low-voltage Directive (2006/95/EC)......................................... 11 Machinery Directive (2006/42/EC)............................................. 11 Thermistor........................................................................................ 183, 9 Throttling Valve..................................................................................... 27 Tightening Of Terminals.................................................................... 88 Torque Characteristics..................................................................... 165 Transmitter/sensor Inputs................................................................. 54 Troubleshooting....................................................................... 182, 175 Tuning The Drive Closed Loop Controller................................... 38 Type Code String High Power................................................................ 66 Code String Low And Medium Power...................................... 65
Safe Stop....................................................................................................... 13 Stop Installation............................................................................... 16 Safety Category 3 (EN 954-1)..................................................................... 17 Earth Connection........................................................................... 111 Note...................................................................................................... 10 Regulations........................................................................................ 10 Requirements Of Mechanical Installation............................... 87 Save Drive Settings............................................................................ 110 Screened/armoured.......................................................................... 101 Screened/armoured............................................................................ 90 Screening Of Cables............................................................................ 90 Secondary Pumps................................................................................. 30 Serial Communication.......................................................... 114, 168, 183 Communication Port......................................................................... 7
UL Fuses, 200-240V.............................................................................. 95 Unsuccessful AMA............................................................................. 103 USB Connection.................................................................................... 99 Use Of EMC-Correct Cables............................................................ 112
191
Index
Variable (Quadratic) Torque Applications (VT)..................................... 175 Air Volume.......................................................................................... 23 Control Of Flow And Pressure..................................................... 20 Varying Flow Over 1 Year................................................................... 20 VAV............................................................................................................ 23 Vibration And Shock............................................................................ 13 Vibrations................................................................................................ 25 Voltage Level....................................................................................... 165 VVCplus....................................................................................................... 9
Warning Against Unintended Start............................................................. 10 Words................................................................................................. 180 What Is CE Conformity And Labelling?................................................ 11 Is Covered........................................................................................... 11
192
www.danfoss.com/drives
130R0084
MG11BA02
*MG11BA02*
Rev. 2010-12-17