SCADA
SCADA
.
Application in
Grid Management
Presentation by
A N I L G. P A T I L
2008-09
SCADA ?
Supervisory
Control
And
Data
Acquisition
Formation of National grid
NR-WR-ER-NER parallel operation
NR
Sasaram HVDC b-
Vin HVDC b-to-b
to-b (500 MW)
(500 MW)
WR 400 KV Rourkela-RaipurD/C
ER+NER
220 KV Budhpadar-Korba T/C
(1000 MW)
Generation: Transmission:
Data & Load Despatch Data &
Control Control Centre Control
SCADA
RTU
PT FWP
0 to 250
MW Binary value
O/P +/- 10 mA A.E.
TRANSDUCER
800-0-800 PLCC
VSAT
D.E.
Aux. Supply 48 V Radio
Of CB/Isolator
RTU
FWP VFT
0 to 250 2.4 – 4 KHz
MW PLCC
O/P +/- 10 mA Binary value 50 – 500 KHZ
TRANSDUCER A.E.
800-0-800
D.E.
Tele PLCC
Control 50 – 500 KHZ
Interface
VFT
2.4 – 4 KHz
MMI
220
L.D. Ambazari
How measurands are tele-
transmitted?
• Suppose the bipolar transducer output is (-10 – 0 - +10 mA) and the
transducer range is 800-0-800 MW. The transducer output will be 10mA
at full load which is converted to 250 bits by SINAUT as raw value.
Some multipliers are defined in the processing software to display this
raw value in physical value (analog) and is defined by the equation
• Y=M*X+C
• Where Y is physical value, X is the raw value and M and C are
the characteristic constant.
• 800=M* 250 Here C is zero as the quantity is linear.
•
• M= 800/250 = 3.2
• Hence raw value multiplied by 3.2 will give you the physical value
which is displayed in real time. As KV and Hz are non-linear, hence M
and C both are defined.
How Indications are tele-
transmitted
• The indications/ alarms are tele-transmitted through DE cards in the SINAUTs.
The static input module DE has floating inputs for 32 binary signals of 48 Volts.
There are basically two types of indications, single state and double state.
Isolators and alarms are defined as single state and circuit breakers are defined
as double state. Single state indications are represented through NO auxiliary
contacts and double state indications are represented by NO and NC auxiliary
contacts.
• Logic used for tele-transmission of single state and double state indications.
• Auxiliary contact NO Single state ON 1
•
OFF 0
• EMS Applications
• Expert Systems
• Substation Automation
& Controls
• Distribution Automation
• Outage Management
WRLDC
EMS
SCADA SYSTEM AT SLDC KALWA
SYSTEM
TCI1 TCI2 .. ADM COM MMI ADM COM MMI .. TCI1 TCI2
DC 6 x 64 Kbps
4 Nos.
OPF Link DC
GEB
1 IEC
26 RTUs 10 RTUs 9 IEC RTU
RTUs MPEB
CSEB 13 RTU’s 7 RTU’s
GOA
MMI GCS .. NA
MMI
ICCP ..
Sinaut Spectrum EMS
Chandrapur – Padge .........
HVDC SCADA
ULDC SCADA at WRLDC
Supervisory Control And Data Acquisition
Highlights of SCADA system
➲ Sinaut Spectrum SCADA functions are distributed among 64 Bit,
RISC, SUN Ultra 10 Servers on LAN.
➲ Huge memory capacity, faster speed and response.
400 KV
NE
GENERATION & EXCHANGE OVERVIEW
Maharashtra State Power System Real Time Overview
Typical Real Time Generation Overview
34
ADVANCED SCADA
FUNCTIONS
EMS Applications
• SCADA is a prerequisite for EMS
(Energy Management System) which
offers several powerful functions to
ease the power system operations, to
raise the system security and to
facilitate the personal training. All
these functions serve to reach the
most efficient operations as quick as
possible.
• SCADA system can be extended by
following EMS servers
– Network Analysis (NA)
– Generation Control & Scheduling (GCS)
– Dispatcher Training Simulator (DTS) &
Power System Simulator (PSS)
Network Analysis (NA) Server
• Network analysis functions such as
State estimator, on-line load flow
calculation, on-line short circuit
calculation, contingency evaluation
etc. forms an integral part of the
network control system in many power
utilities.
• Proven to be useful aids in operational
management of network enabling the
timely detection of work points in the
network and as decision making aids in
difficult situations.
Functions of NA Server
LAN
Basic functions
NA Sequence control NA operation/display routines
External Network
Case Bus State
Network Status
Management scheduler estimator
modeling processor
Automatic AGC
Energy
Generation Performance
Accounting
Control Monitor
System
O/P Report List O/P Report List
Fault Comments/
Identification/ Interlock Advices/
Diagnostic Switching Sequence
O/P Result
User
Interface
Expert System
Intelligent Alarm Processor (IAP) : This on line tool produces
automatically a diagnosis when a fault event occurs in the Energy
Network. Typically a fault event creates an alarm inrush and the system
operator would have to look up at up to hundreds of alarm messages.
Therefore IAP provides information about the fault location in case of
network disturbance. It informs to operator the nature and the
consequences of the disturbance quickly and exactly.
Input : The input data for IAP that comes from the SCADA for correct output
(diagnosis )is :
– The topology of the network
– The alarms from the automatism
– Logical working schema of the automatism.
Output (Diagnosis) :
– The date & the time of disturbance
– The faulty equipment (transformer, line, bus bars)
– The protection system which clears the fault.
– Additional information (e.g. breaker failure, automatic recloser successful /
unsuccessful etc. )
The report list shall be invoked on the Basic Signaling Display.
Expert System
• Advantages
– The expert knowledge is made available for any time
use.
– The cognitive load on operator can be reduced by
focusing his attention to compacted relevant network
information.
– Faster response to network event reduces the risk of
additional damages & the duration of outages.
– The potential of human errors is minimized.
– Some critical situations can be avoided at all.
Expert System
• Now let us highlight the major advantage
of integration of real time Expert System in
SCADA, that could have averted blackout
on dt 09.11.2007 in Marathwada area of
MSETCL Power System considering the
following Case Study.
NORMAL STATE
Date : 09.11.2007
Time : 17:26 Hrs Advice from
. Expert System :
Total Load shedding Watch out for
Withdrawn Being Diwali. any Gen. loss
The load of Marathwada Area and ready for
To the tune of 1200 MW implementing
was being catered from following conglomerated
Sources : Load
Total Parly Gen.: 750 MW Management
Plan for evening
Loading on Both 400/220 KV 315 MVA ICTs
peak demand
at Giravali s/s : 330 MW (560 Amps)
management.
220 KV Pusad-Parbhani Ckt: 55 MW
220 KV Pusad-Nanded Ckt.: 125 MW
Advice from Expert
System :
Advice from
Expert System :
Carry out
Time : 18:17 Hrs
Distress load
Overload alarms on both ICTs occurred. shedding in
Stage I alarm occurred at 95% of Full load Nanded,
Stage II alarm occurred at 105% of Full load Parbhani,
Harangul area to
Time : 18 : 23 Hrs the tune of 200
Parly Gen. Unit 6 tripped. Amps to control
Total load on both ICTs reached to 1080 Amps. the loading
DISTURBANCE
TOTAL COLLAPSE
Advice from
Expert System :
Time : 18:28:20 Hrs Advice for
Both 315 MVA ICTs tripped at management for
400 KV Girawali s/s Causing tripping of remaining
remaining gen. units at Parly TPS. existing loads.
Switching
Sequence for
Time : 18:30 Hrs quick restoration
220 KV Pusad, Nanded, Parbhani s/s in dark.