Last updated: 19/06/2023 10:33:16
CONDENSATE
CONTROL 25 LTR
Product group: 655 Product number: 774828
NALFLEET™ Condensate Control™ is blend of liquid neutralising amines boiler water treatment product
designed for effective corrosion control and protection in steam and condensate systems.
Product information
This product supersedes product no: 571323
Features
Easy to use liquid treatment
Neutralises the acids occurring in the condensate system
Volatilizes and carries over with the steam and so it is recycled
Simple test to determine level of treatment
Used for protection of condensate and feed water systems in boiler systems of all pressures
Benefits
Dosage is economical and efficient
Less maintenance required
Lower operating costs and increased reliability
Specification
General Physical properties
Invent Hazard Material (IMO/EU) classification C-9 Appearance Colourless
Density [g/ml] 1.0
Form Liquid
pH 12
Technical data
Not Compatible Avoid copper, brass and aluminium.
Documents
SDoC and MD for IHM
Directions for use
Dosage and Control
The condensate is tested for pH to determine the dosage level. The pH limits are 8.5-9.2. For an average system e.g. 10 m3, the dosage is approximately
0.65 ltr/day
Dosing Method
NALFLEET™ Condensate Control is best dosed continuously using an automatic dosing unit. The treatment can be dosed together with the oxygen
scavenger.
Suitable dosage points are:
Boiler feed line after recirculation valve
Condensate pump discharge NALFLEET™ Condensate Control can be fed using an automatic dosing system. Consult your WSS representative for specific
dosing instructions.
Sampling and Testing
A representative sample of condensate should be drawn for analysis daily. The sample should always be taken from the same point, cooled and tested
immediately. Follow the test kit instructions and log the results in Waterproof. The results should be sent to WSS as stated in the Waterproof instructions.
Condensate Control Dosing Parameters (all pressure groups)
Standard pH range is 8.5 to 9.2
Measured pH
If pH < 8.5: Increase Dosage by 25%. Retest after 24 hrs or shorter. If pH within 8.5 to 9.2: Within control. No adjustment needed, continue with
routine monitoring. If pH > 9.2: Decrease dosage by 25%. Retest after 24 hrs or shorter.
These are recommended values based on experience and are in no way intended to replace the boiler manufacturer's specifications or company
regulations.
It is important that regular testing is carried out to ensure levels of treatment are correct. Use dosage chart to maintain condensate pH between 8.5-9.2.
Related products
Is frequently bought together with
680843
COOLTREAT AL 25 LTR
571364
VAPTREAT 25LTR
571356
ROCOR NB LIQUID 25 LTR
735977
MAR-71 BIOCIDE 3X5L NOT IN USA&CAN
638676
EVAPORATOR DEFOAMER 4X5 LTR
777701
BWT LIQUID PLUS 25 LTR
777710
NALFLEET 2000 25 LTR