Johnson Controls - Technical Guide R-410A Split-System Air-Cooled Condensing Units and Air Handlers - 505429-jtg-nn-1222

J07YE, J10 through 25YC, and J10 through 20YD Condensing unit models J07PE, J10 through 15PC, and J15 through 20PD Heat pump unit models J07 through 20NL and J10 through 20NM Air handling unit models J25NC Air handling unit models 7.5 to 25 ton 60 Hertz

Uploaded by

Michael Martin
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
415 views120 pages

Johnson Controls - Technical Guide R-410A Split-System Air-Cooled Condensing Units and Air Handlers - 505429-jtg-nn-1222

J07YE, J10 through 25YC, and J10 through 20YD Condensing unit models J07PE, J10 through 15PC, and J15 through 20PD Heat pump unit models J07 through 20NL and J10 through 20NM Air handling unit models J25NC Air handling unit models 7.5 to 25 ton 60 Hertz

Uploaded by

Michael Martin
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 120

505429-JTG-NN-1222

Description
Condensing units and heat pumps are completely assembled, piped
and wired at the factory to provide a single-piece unit for shipment and
rigging. Each unit is pressurized with a holding charge of nitrogen for
storage and shipping.

The compact design, clean styling, small footprint, and quiet operation
Technical guide make these condensing units and heat pumps suitable for almost any
R-410A outdoor location. They can be located on rooftops, because they
Split-system weigh much less than a single package unit of similar capacity and are
much easier to rig and support or on the ground, because the footprint
Air-cooled condensing units is compact allowing a variety of applications.
and air handlers
Both the condensing units and heat pumps are equipped with reliable
Smart Equipment™ microprocessor controls to assure proper
J07YE, J10 through 25YC, and J10 through 20YD operation and unit protection for long product life. Products from 10 to
Condensing unit models 20 ton are available in single or dual (two or four pipe) refrigerant
circuits for redundancy in operation and various applications.
J07PE, J10 through 15PC, and J15 through 20PD
Heat pump unit models The air handling units are completely assembled units, including a
well-insulated cabinet, a DX cooling coil with copper tubing, aluminum
J07 through 20NL and J10 through 20NM fins, expansion valves, distributors, 2 in. throwaway filters, a
Air handling unit models centrifugal blower, a blower motor, an adjustable belt drive, a blower
motor contactor and a small holding charge of nitrogen.
J25NC
Air handling unit models Units are shipped in the vertical position ready for field installation, but
can be easily converted to horizontal position. An added benefit of the
7.5 to 25 ton air handling units is they are designed to operate with either a
60 Hertz condensing unit or a heat pump and no field modification or special
unit is required for heat pump applications.

J**YC/YD/YE/PC/PE Outdoor Units (Except J25YC)


Field modification or special unit is required.

For heat pump applications

J**NC/NL/NM Indoor Units


J**YC/YD/PC/PD Outdoor Units
505429-JTG-NN-1222

Table of contents
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Table of contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Condensing unit features and benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Outdoor unit accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Air handling unit features and benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Guide specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Factory- and field-installed options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Physical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Unit limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Cooling and heating ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Capacity Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Air handling and hot water coil accessory heating capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Air handling and steam coil accessory heating capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Airflow performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Sound performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Typical wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Weights and dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95

2 Johnson Controls Ducted Systems


505429-JTG-NN-1222

Nomenclature

Configured Split Condenser Model Number Nomenclature


J20 Y C C00 A 2 A AA 2 A
Product Style
Nominal Cooling Capacity - MBH A = Style A
J07 = 7.5 Ton
J10 = 10 Ton Product Generation
J12 = 12.5 Ton 1 = First Generation
J15 = 15 Ton 2 = Second Generation
J20 = 20 Ton 3 = Third Generation
J25 = 25 Ton 4 = Fourth Generation
5 = Fifth Generation
6 = Sixth Generation
Product Category
Product Options
Y = Split System, Condenser, AC, R-410A
P = Split System, Condenser, HP, R-410A AA = None
AB = Phase Monitor
Installation Options AC = Coil Guard
Product Identifier A = None AE = Phase Monitor + Coil Guard
B = Option 1 EA = E-Coat Condenser Coil
C = Standard Efficiency, 2-Pipe
D = Options 1 & 2 EB = E-Coat Condenser Coil + Phase Monitor
D = Standard Efficiency, 4-Pipe
E = Option 3 EC = E-Coat Condenser Coil + Coil Guard
E = Standard Efficiency, 2-Pipe, 2-Stage G = Options 1 & 3 EE = E-Coat Condenser Coil + Coil Guard
J = Options 1, 2 & 3 + Phase Monitor
Q = Options 1, 3 & 5 LA = Low Ambient
Heat Type & Nominal Heat Capacity T = Options 1 & 5 LB = Low Ambient + Phase Monitor
LC = Low Ambient + Coil Guard
C00 = Cooling Only Options LD = Low Ambient + Phase Monitor
+ Coil Guard
1 = Disconnect LJ = Low Ambient + E-Coat Cond. Coil
Airflow 2 = Non Pwr’d Conv Outlet LK = Low Ambient + E-Coat Cond. Coil
A = Standard Motor 3 = BACnet MS/TP on Smart Equipment™ + Phase Monitor
5 = Pwr’d Conv Outlet LL = Low Ambient + E-Coat Cond. Coil
+ Coil Guard
Voltage LM = Low Ambient + E-Coat Cond. Coil
+ Phase Monitor + Coil Guard
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-601
1. 575 Volt HP’s not offered.

Configured Split Air Handler Model Number Nomenclature


J25 N C C00 N 6 A AA 1 A
Nominal Cooling Capacity - MBH
J25 = 25 Ton1

Product Style
Product Category A = Style A

N = Split System, Air Handler, AC R-410A


Product Generation
Product Identifier 1 = First Generation
C = Standard Efficiency, 2-Pipe, R-410A

Heat Type & Nominal Heat Capacity


C00 = Cooling Only
Installation Options Product Options
1. J25ND Not Offered. A = None AA = No Options Installed
EJ = E-Coat Evaporator Coil
2. Motors are not shipped with
25 Ton Air Handler Units.
Airflow
See Field accessories table for N = None (Motor Drive Kit Req)2 Voltage
Motor HP options. 5 = 575-3-60
6 = 208/230/460-3-60

Johnson Controls Ducted Systems 3


505429-JTG-NN-1222

Configured Split Air Handler Model Number Nomenclature


J20 N L C00 E 5 A AA 3 A
Nominal Cooling Capacity - MBH
J07 = 7.5 Ton (available in 2-pipe only)
J10 = 10 Ton
J15 = 15 Ton Product Style
J20 = 20 Ton A = Style A

Product Generation
Product Category 1 = First Generation
N = Split System, Air Handler, AC & HP R-410A 2 = Second Generation
3 = Third Generation

Product Identifier
L = Standard Efficiency, 2-Pipe, R-410A w/Intellispeed Installation Options1
M = Standard Efficiency, 4-Pipe, R-410A w/Intellispeed B = IntelliSpeed VFD
C = IntelliSpeed VFD w/Bypass
D = Customer Installed IntelliSpeed VFD
Heat Type & Nominal Heat Capacity
C00 = Cooling Only
Voltage Product Options
2 = 208/230-3-60
1. In order for the IntelliSpeed option to function AA = No Options Installed
correctly some field programming is required.
Airflow 4 = 460-3-60
EJ = E-Coat Evaporator Coil
See unit Installation manual for details. B = 1.5 HP Motor 5 = 575-3-60
C = 2.0 HP Motor
D = 3 HP Motor
E = 5 HP Motor
F = 7.5 HP Motor

Condensing unit features and benefits


Features • Filter-driers are shipped in the unit's control box for field
installation in the liquid line leaving the outdoor unit.
• Meets or exceeds ASHRAE 90.1 standards.
• Copper stub-outs are factory mounted on the suction
• Scroll compressors provide both high efficiency and and liquid lines to simplify the field piping connections.
reliability. Single two-stage scroll available on the 7.5
• Smart Equipment™ Controls provide stable cooling
ton for both cooling only and heat pump unit and 10 ton
operation at ambient temperatures down to 45°F with
for the cooling only 2 pipe OD unit.
low ambient kits available for operation to 0°F.
• Smart Equipment™ Controls
• Capacity staging for more economical operation and
• Dual refrigerant circuits on J**PD and J**YD models. stable temperature levels within the conditioned space.
• Condensing unit coils are constructed of reliable and • Smart Equipment™ Controls control board uses a three
durable Micro-Channel aluminum tube and fins for long times, you're out philosophy. The high, low-pressure
lasting, efficient operation. Micro-Channel technology switch, anti-freeze protection, low voltage or heating
provides exceptional durability along with reduced high limit must trip three times within two hours before
product weight and less refrigerant charge. Heat pumps the unit control board will lock out the associated
units are equipped with aluminum fin, copper tube coils compressor. An alarm message will be displayed on the
providing durability, reliability and value. LCD screen
• Crankcase heaters that de-energize when compressors • Smart Equipment™ Controls monitor each safety
are operating. independently (high pressure, low pressure, low
• Both high and low pressure controls. Since these voltage) allowing ease of troubleshooting if any
controls are self-contained, there are no capillary lines problems arise.
to be damaged. • Inherently protected condenser fan motors.
• Internal compressor motor protection. • Optional E-coat coated outdoor coils for sea coast or
• Class 2, 24-volt thermostat control circuit protected by a corrosive environment applications.
re-settable breaker. • Optional factory-installed disconnect to allow power to
• Standard factory installed service valves. be removed from the unit when performing periodic
maintenance or for service.
4 Johnson Controls Ducted Systems
505429-JTG-NN-1222

• Optional factory-installed powered or non-powered 115 Air handling unit features and benefits
volt GFI outlet.
Features
• Optional factory-installed phase monitor to protect the These air handlers can be arranged for a variety of air
unit from phase loss or phase reversal. discharge patterns in either the horizontal or vertical position.
Refer to the unit installation instructions for other application
Benefits possibilities.
The condensing units and heat pumps can be applied on a Benefits
rooftop or at ground level, due to their ample sub-cooling Air handling units are designed with two distinct modules to
capacity which allows them to be located three or more provide maximum application flexibility. All are shipped as
stories below the evaporator coil. single packages with the blower module mounted on top of
After assembly, the unit is pressure tested and additional leak the coil module. The blower module can be repositioned in
testing is done. During this pressure test, the operation of the the field to meet a large number of vertical and horizontal
high pressure control is checked. As the unit is being applications.
evacuated and dehydrated, the operation of the low pressure The 7.5 to 20 ton blower module includes the blower wheels
control is also checked. along with factory-mounted motor and drive. The 25 ton
Every compressor, condenser fan motor, crankcase heater, blower module includes the blower wheels with field mounted
and electrical control circuit is checked to assure a trouble- motor and drives. All models offer two motor horsepower
free start-up and years of reliable operation. The condenser options to meet both standard and high static airflow
fan guards are vinyl-coated to provide additional rust requirements.
protection and to enhance the appearance of the unit. The coil module includes direct expansion coils, 2 in.
Compressors are mounted on rubber isolators to reduce the throwaway filters with the option to accept 4 in. filters (25 ton
transmission of vibration. Vertical discharge condenser fans 2 in. only), liquid line solenoid valves for capacity reduction,
direct sound upward and away from any surrounding thermal expansion valves, distributors and a non-corrosive,
structures. composite condensate drain pan.
All sheet metal parts are constructed of commercial grade After the headers are brazed onto the coil and the coil is
galvanized steel. After fabrication, each part is thoroughly installed in the unit, the coil is pressurized with nitrogen for
cleaned to remove any grease or dirt from its surfaces. The pressure testing and additional leak testing. After the coil is
external parts are coated with a powder paint to assure a evacuated and dehydrated, it is pressurized with a holding
quality finish for many years. This UL approved coating charge of nitrogen for storage and/or shipping.
system has passed the 750-hour, 20% salt spray test per
ASTM Standard B117. These air handlers, combined with condensing units, provide
years of quiet, efficient and dependable operation.
All condensing unit and heat pump models include a 5-year
limited warranty on the compressors and 1-year limited Unit installation
warranty on all other parts. The matching line of air handling Units may be bottom-supported or ceiling-suspended and
units carries a 1-year limited parts warranty. can be arranged to meet almost any space or duct
requirements. Each unit is available with a choice of blower
Outdoor unit accessories motors horsepower and other accessories to make them
suitable for most applications.
Coil Guards: Wireform coil guards for added protection of
Air Handling units from 10 to 20 ton are available in either two
outdoor coils. Designed to mount on each side of the product
or four pipe configurations. 7.5 and 25 ton are two pipe (only)
if required to provide protection from minor impacts or large
configurations. The dual and single circuit options provide a
debris.
wide variety of application and unit match-up possibilities.
Hail Guards: Hood type hail guards designed to protect the Blower Motors: Different HP motors are available for each
outdoor coils from hail. Can be installed on a single side or unit to meet almost any air delivery requirement. All motors
both to provide protection from storms that may produce hail. are UL approved, have permanently lubricated ball bearings
and are mounted within the insulated cabinet of the units to
Low Ambient Kits: Kits designed to allow the cooling only
minimize the transmission of sound to the surrounding space.
units to operate between 0°F and 40°F in the cooling mode.
1.5-5 HP motors are inherently protected. 7.5 HP motors
Standard cooling is allowed to 45°F. (Not designed for
require motor overload protection.
operation on heat pump units).
Overload Relay (7.5HP): These blower motors do not have
inherent protection and require external motor overload
protection. J20NC/ND/NL/NM "F" models overload relays are
factory installed. J25NC models overload relays are field
installed. Power wiring for blower motor is supplied in the
overload relay kit. See details in the overload relay kit and in
J25NC overload relay setting (all) on page 61.
Johnson Controls Ducted Systems 5
505429-JTG-NN-1222

Factory-mounted components condensate drainage. The coil has copper tubes that have
Part load operation: These air handlers with DX (Direct been mechanically expanded into aluminum fins. Both
Expansion) coils rated at 10 ton of capacity and above have headers are located on the same end of the coil. The coil is
multiple coils with pre-piped distributors, expansion valves leak-tested at 325 psig and dried before the connections are
and solenoid valves. Field modifications are not required for capped for storage and shipping.
part load operations. Capacity reduction not only provides
economical operation, but also maintains stable temperature Bottom return: Air handling unit can be quickly converted to
and humidity levels in the conditioned space. bottom return for both vertical and horizontal applications. All
that is required is the removal of several screws and a single
BAS Control: Smart Equipment™ with Communication panel on 7.5-15 ton and two panels on the 20 ton AHU.
Option Control - The Johnson Controls Smart Equipment™ Optional painted panel can be ordered to cover the side
with Communication Option Control is factory installed. It return opening when utilizing the bottom return.
includes all the features of the Smart Equipment™ control
with an additional gateway to BACnet MS/TP (programmable
to Modbus or N2 protocols).

IntelliSpeed™ Supply Fan Control: (ASHRAE 90.1 This Split-System (Air Condensing / Heat Pump / Air
Compliant) AHU units configured with the IntelliSpeed option Handling) unit is one component of an entire system.
will contain a VFD for multi-speed supply fan operation. This As such it requires specific application considerations
option allows the supply fan RPM to vary based on the with regard to the rest of the system (air handling unit,
number compressors or heating stages energized. duct design, condensing unit, refrigerant piping and
control scheme).
Easy service: Serviceable expansion valves are provided on
every unit. These valves are factory-installed to provide many Failure to properly apply this equipment with the rest
years of trouble-free operation. The expansion valves also of the system may result in premature failure and/or
include a tee fitting to allow easy installation of hot gas reduced performance / increased costs. Warranty
bypass if required. coverage specifically excludes failures due to
improper application and Unitary Products specifically
Coil protection: The indoor coils of these air handlers can disclaims any liability resulting from improper
have factory applied Electrofin coating to provide extended application.
life to the indoor coil in standard applications and additional Please refer to the equipment Technical Guide,
corrosion protection on those applications in sea coast or Installation Manual and the piping applications bulletin
corrosive environments. 247077, service tips letter ST-013-2019 and Split
Accessories System Refrigerant Oil Management White Paper or
call the applications department for Unitary Products
IntelliSpeed™ VFD: Field installed VFD for 25 ton AHU
@ 1-877-UPG-SERV for guidance.
IntelliSpeed multi-speed fan function. The field installed VFD
will allow staged fan and will meet ASHRAE 90.1 or IECC two
speed fan requirements.
Guide specifications
Base sections: Base sections can be used to elevate units
above the floor. If desired, a moderate percentage of outdoor Split-system cooling only condensing units
air may be introduced through these sections by cutting an Models: J07YE, J10 through 25YC, J10 through
access opening to accommodate the outdoor air duct 20YD and split-system heat pump models: J07PE,
connection. These bases include a durable finish to match
J10 through 15PC, and J15 through 20PD
the evaporator blower unit. The base may have to be
insulated for certain applications. General
Hot water coils: Drainable water coils are available for field • Factory-assembled, single piece, air cooled condensing
installation between the blower and the coil modules of both unit designed for outdoor installation.
horizontal and vertical units. Since their casings match the • Factory wired, piped, and tested for leakage and
dimensions and the finish of the basic units, they become an functionality to assure trouble-free installation and start-
integral part of the unit after installation. The coils slide out of up.
their casings for easy installation. Hot water coils have • Rated in accordance with AHRI Standard 340/360.
copper tubes that have been mechanically expanded into
aluminum fins. Both headers are located on the same end of • Designed and tested in accordance with ASHRAE 15
the coil. Safety Code for Mechanical Refrigeration and comply
with NEC.
Steam coils: Steam coils are available for installation • Cooling performance rated in accordance with DOE
between the blower and coil modules of both horizontal and and AHRI test procedures.
vertical units. Since the casing matches the dimensions and
• CSA listed and classified to UL 1995/CAN/CSA No.
the finish of the basic unit, it becomes an integral part of the
236- M90 standards.
unit after installation. The coil slides out of the casings for
easy installation and is pitched in the casings to facilitate

6 Johnson Controls Ducted Systems


505429-JTG-NN-1222

• One year limited parts warranty on complete unit with Outdoor condenser unit coils
an additional four year compressor warranty. • Draw through configuration
Unit operating characteristics • Constructed with Micro-channel aluminum fins and
Operating Range shall be between 125° F to 40° F in cooling aluminum tubing.
as standard from factory. Heat pump unit outdoor unit coils
• The capacity of the condensing unit shall meet or • Draw through configuration
exceed _____ Btuh at a suction temperature of _____
• Constructed with aluminum plate fins mechanically
F. The power consumption at full load shall not exceed
bonded to seamless internally enhanced copper tubes
_____ kW.
with all joints brazed.
• The combination of the condensing unit and the
Condenser fans
evaporator or fan coil unit shall have a total net cooling
capacity of _____ Btuh or greater at conditions of • Direct driven propeller-type fans
_____ cfm entering-air temperature at the evaporator at • Aluminum blades riveted to corrosion resistant steel
_____ F wet bulb and _____ F dry bulb, and air spider brackets.
entering the condensing unit at _____F. • Arranged for vertical air discharge.
• The system shall have an EER of _____ Btuh/ Watt or • Equipped with PVC coated steel wire safety guards.
greater at standard AHRI conditions.
Condenser motors
Installer shall
• Totally enclosed, air over cooled.
• Furnish Johnson Controls air-cooled condensing units,
heat pump or equivalent in accordance with the • Inherent overload protection.
performance schedule shown on the plans, and • Permanently lubricated bearings.
• Unit shall be stored and handled in accordance with unit • Must cycle to allow cooling operation down to 45°F.
manufacturer's instructions. Refrigerant piping
• Install each unit as shown on the plans in accordance • Solid core filter-driers ship loose for field installation.
with the manufacturer’s recommendations and all
• Liquid and suction line service valves with gauge ports.
applicable national and local codes
• Suction and discharge line service ports accessible
Unit construction
from unit. Ports capped for leak prevention.
• Constructed of zinc-coated, galvanized steel.
• Liquid line magnetic check valves
• Exterior surfaces bonded and coated with baked
• Holding charge of nitrogen.
enamel finish by a powder paint process capable of
withstanding a minimum of 750 salt spray hours Electrical requirements
according to ASTM B117. • Single-point connection electrical power.
• Cabinet screws that comply with ASTM B117 salt spray • Nominal unit electrical characteristics shall be _____ v,
test for a minimum of 750 hours. 3-ph, 60 Hz. The unit shall be capable of satisfactory
• Permanently attached heavy-gage perimeter base rails operation within voltage limits of ____ v to _____ v.
with forklift slots and lifting holes. • Condenser fan motors and secondary of transformers
• Removable access panels to all internal components. shall be grounded.
• Separate access panel to controls. Unit controls
• Access panels to allow outdoor coil cleaning. • All 24-volt control circuit, powered by a 24 volt
transformers and protected by a resettable breaker.
Compressors
• Conventional thermostat must provide operation for
• Hermetic scroll type, internally protected with high-
both condensing units and heat pumps without an “O”
pressure relief and over temperature protection.
output from the thermostat.
• Two stage units operate in 50% capacity increments.
• Low voltage terminal strip for simple hook-up.
• Suction gas cooled
• Compressor motor protection shuts down unit for motor
• Voltage range of ±10% of unit nameplate voltage. over-current, over-temperature or low voltage
• Neoprene isolators minimize sound transmission and conditions.
vibration. • Safety lockouts provide reset capability at the space
• Belly-band crankcase heaters keep refrigerant from thermostat or base unit should any of the following
diluting sump oil. standard safety devices trip and shut off compressor:
• Full charge of compressor oil a. Loss-of-charge/Low-pressure switch.
b. High-pressure switch.

Johnson Controls Ducted Systems 7


505429-JTG-NN-1222

c. Control board diagnostics and fault message display. Each unit shall be:
d. Safety lockouts send a 24 volt signal to the control • Covered by a 1-year limited parts warranty on the
board's "X" terminal, allowing notification to the user complete unit and 5-year on compressors.
via the thermostat fault light (if present). • In current production with published literature available
e. In the unlikely event any faults should occur, the unit to check performance, limitations, specifications, power
control board will store the faults in its internal requirements, dimensions, operation and appearance.
memory. The LCD display will scroll the 5 MOST • Indoor unit shall be equipped with a V-belt drive option
critical faults, however, all fault messages can be that will permit the blower RPM to be adjusted to meet
extracted via USB device, displayed real-time via the the CFM requirements of the air delivery system. (Refer
MAP Gateway as well as be broadcasted through a to Technical Guide for Airflow Capabilities.)
BAS system (if applicable). The UCB will provide fault
Each unit enclosure shall have:
messages in plain English to ensure the user can
easily understand the specific fault. • Exterior panels of 18 gauge steel, finished with baked
enamel to provide a long lasting quality appearance
Non-fused disconnect switch
• Removable panels to provide easy access to the
• Factory installed option, internally mounted
internal components for maintenance and service on
• Accessible from outside the unit. condensing units, heat pumps and air handlers
• NEC and UL approved non-fused switch. • Air handling units must have a filter rack that accepts
• Provides power off lockout capability. both 2 in. and 4 in. filters (7.5 - 20 Ton only).
Convenience outlet • The dimensions of each unit shall not exceed those
• Factory-installed, internally mounted. specified in the manufacturers literature.
• Accessible from outside the unit. • The minimum application clearances for condensing
units, heat pumps and air handlers must meet those
• 115V, 20 amp GFI receptacle with independent fuse
specified in the manufacturer’s literature.
protection.
The blower motor shall:
• Required voltage provided by factory-installed step-
down transformer or field supplied 115v circuit. • Be mounted within the insulated cabinet to minimize the
transmission of sound to the surrounding space, and
Low-ambient head pressure control
any motor 7.5 HP or greater must have a service factor
• Standard operation down to 45 °F without a low of 1.15.
ambient kit.
IntelliSpeed discrete fan control shall:
• Operation down to 0°F with a factory-installed or field-
• Control fan speed with a VFD (Variable Frequency
installed low ambient kit accessory. The controller
Drive)
modulates the fan motor speed in response to liquid line
temperature or pressure. • Drive fan speed based on the number of cooling or
heating stages.
Coil guard
• Maximum airflow on first stage cooling not to exceed
Factory or field installed decorative grille shall be placed on
67%.
the units to protect condenser coil after installation.
The Evaporator coil shall:
Hail guard package
• Consist of copper tubes arranged in staggered rows,
Field installed hail guard package shall protect coils against
mechanically expanded into aluminum fins,
damage from hail and other flying debris.
• Be draw-through, and
Coated condenser coils
• Include factory-mounted distributors, expansion valves
Special phenolic or epoxy polymer coating available as a
and solenoid valves for capacity reduction.
factory option on both outdoor and indoor coils.
The blower wheels shall:
Be dynamically balanced to minimize the levels of sound and
vibration generated by the unit.

8 Johnson Controls Ducted Systems


505429-JTG-NN-1222

Factory- and field-installed options


Condenser units (7.5 ton to 25 ton)
Norman
Options Factory installed Field installed modification
center*
BAS card (BACnet MSTP, Modbus, N2) Yes Yes -
Fused disconnect - - Yes
Powered convenience outlet Yes - -
Electrical/controls Non-powered convenience outlet Yes - -
Disconnect Yes - -
Low ambient Yes Yes -
Phase monitor Yes Yes -
Rawal valve - - Yes
Oil separator - - Yes
Refrigeration Liquid line receiver - - Yes
Copper condenser coils - - Yes
E-coat condenser coils Yes - -
Weather protective packaging - - Yes
Cabinet Hail guard - Yes -
Coil guard Yes - -
Note: *For more information on Modification center options and custom modifications, contact : [email protected]
Air handler units (7.5 ton to 25 ton)
Norman
Options Factory installed Field installed modification
center*
VFD grounding ring - - Yes
Electrical/controls UVC lights - - Yes
Dirty filter switch - Yes -
Hot water coil - Yes -
Heat Steam coil (7.5 ton to 20 ton) - Yes -
Electric heat - Yes -
Hot gas bypass - Yes -
Refrigeration
E-coat coil Yes - -
Multiple airflow-arrangement Standard - -
Filters - throwaway 2 in. Standard - -
Filters - throwaway 4 in. (7.5 ton to 20 ton) - Yes -
Economizer - Yes -
Cabinet
Weather protective packaging Yes - -
Double wall - - Yes
Hinged blower and filter access doors - - Yes
Stainless steel drain pan - - Yes
*For more information on Modification center options and custom modifications, contact : [email protected]

Field-installed accessories - non-electrical (condensing units)


Nominal ton (ACs and HPs) Voltage Model Description Weight (lb)
7.5 and 15 ton All 1CG0403 Coil guard 20

7.5 and 15 ton All 1HG0428 Hail guard 50

10, 12.5, 20 and 25 ton All 1CG0404 Coil guard 27

10, 12.5, 20 and 25 ton All 1HG0429 Hail guard 57

Johnson Controls Ducted Systems 9


505429-JTG-NN-1222

Field-installed accessories - non-electrical (air-handling unit)

Nominal ton Voltage Model Description Weight (lb)


1RG0416 Return air grille 30

1BS0410 Base section 60

7.5 All 1BP0401 Return air block off panel 12

1HW0410 2 row deep hot water coil 143

1NF0456 Single row steam coil 150

1RG0416 Return air grille 30

1BS0410 Base section 60

10 All 1BP0401 Return air block off panel 12

1HW0410 2 row deep hot water coil 143

1NF0456 Single row steam coil 150

1RG0417 Return air grille 45

1BS0411 Base section 75

15 All 1BP0402 Return air block off panel 20

1HW0411 2 row deep hot water coil 179

1NF0457 Single row steam coil 190

1RG0418 Return air grille 60

1BS0412 Base section 100

20 All 1BP0403 Return air block off panel 20

1HW0412 2 row deep hot water coil 213

1NF0458 Single row steam coil 288

Field-installed accessories - non-electrical (25 ton air-handling unit)


Nominal ton Voltage Model Description Weight (lb)
1HW0406 2 row deep hot water coil 225

25 All 1HH0403 Horizontal suspension kit 50

1BS0406 Base section 210

Field-installed accessories - electrical (air handler unit)


Nominal ton Voltage Model Description Weight (lb)
2HJ04701025 10kW electric heat kit 63

2HJ04701625 16kW electric heat kit 70


230
2HJ04702625 26kW electric heat kit 74

2HJ04703625 36kW electric heat kit 77

2HJ04701046 10kW electric heat kit 63

2HJ04701646 16kW electric heat kit 70


7.5 460
2HJ04702646 26kW electric heat kit 74

2HJ04703646 36kW electric heat kit 77

2HJ04701058 10kW electric heat kit 63

2HJ04701658 16kW electric heat kit 70


575
2HJ04702658 26kW electric heat kit 74

2HJ04703658 36kW electric heat kit 77

10 Johnson Controls Ducted Systems


505429-JTG-NN-1222

Nominal ton Voltage Model Description Weight (lb)


2HJ04701025 10kW electric heat kit 63

2HJ04701625 16kW electric heat kit 70


230
2HJ04702625 26kW electric heat kit 74

2HJ04703625 36kW electric heat kit 77

2HJ04701046 10kW electric heat kit 63

2HJ04701646 16kW electric heat kit 70


10 460
2HJ04702646 26kW electric heat kit 74

2HJ04703646 36kW electric heat kit 77

2HJ04701058 10kW electric heat kit 63

2HJ04701658 16kW electric heat kit 70


575
2HJ04702658 26kW electric heat kit 74

2HJ04703658 36kW electric heat kit 77

2HN04601025 10kW electric heat kit 63

2HN04601625 16kW electric heat kit 70

230 2HN04602625 26kW electric heat kit 74

2HN04603625 36kW electric heat kit 77

2HN04605025 50 kW electric heat kit 85

2HN04601046 10kW electric heat kit 63

2HN04601646 16kW electric heat kit 70

15 460 2HN04602646 26kW electric heat kit 74

2HN04603646 36 kW electric heat kit 77

2HN04605046 50kW electric heat kit 85

2HN04601058 10kW electric heat kit 115

2HN04601658 16kW electric heat kit 125

575 2HN04602658 26kW electric heat kit 130

2HN04603658 36kW electric heat kit 140

2HN04605058 50kW electric heat kit 160

2HN04602025 20kW electric heat kit 126

230 2HN04603225 32kW electric heat kit 140

2HN04605225 52kW electric heat kit 160

2HN04602046 20kW electric heat kit 126

20 460 2HN04603246 32kW electric heat kit 140

2HN04605246 52kW electric heat kit 160

2HN04602058 20kW electric heat kit 125

575 2HN04603258 32kW electric heat kit 130

2HN04605258 52kW electric heat kit 140

** Electric Heat is not available on 25 and larger tonnage air handlers.

Evaporator blower motor variable frequency drive (VFD) kits


Nominal ton HP Voltage Model Description Weight (lb)

208/230-3-60 2VF04601423D VFD kit for discrete fan 110

5 460-3-60 2VF04601433D VFD kit for discrete fan 110

575-3-60 2VF04601458D VFD kit for discrete fan 110


251
208-230-3-60 2VF04601523D VFD kit for discrete fan 130

7.5 460-3-60 2VF04601533D VFD kit for discrete fan 130

575-3-60 2VF04601558D VFD kit for discrete fan 130

1
25 ton AHU does not come equipped with a motor, drive or motor protection (Overload Relay). Must be field installed. VFD Rated
Motors must be used in conjunction with any field installed VFD kit. See additional details on Page 67.

Johnson Controls Ducted Systems 11


505429-JTG-NN-1222

Evaporator blower motor variable frequency drive (VFD) kits with VFD bypass switch
Nominal ton HP Voltage Model Description Weight (lb)
208/230-3-60 2VF04601623D VFD kit for discrete fan 110
5 460-3-60 2VF04601633D VFD kit for discrete fan 110
575-3-60 2VF04601658D VFD kit for discrete fan 110
251
208-230-3-60 2VF04601723D VFD kit for discrete fan 130
7.5 460-3-60 2VF04601733D VFD kit for discrete fan 130
575-3-60 2VF04601758D VFD kit for discrete fan 130
1 25 ton AHU does not come equipped with a motor, drive or motor protection (Overload Relay). Must be field installed. VFD Rated
Motors must be used in conjunction with any field installed VFD kit. See additional details on Page 67.

Field-installed accessories - electrical (condensing unit and heat pumps)


Nominal ton Voltage Model Description Weight (lb)
LOW AMBIENT TO 0° F:
2LA04702012 This kit includes one (Variable Head Pressure Control) control to vary condenser fan speed 10
to maintain stable head pressure.
HOT GAS BYPASS KIT
7.5 All 2HG04700524 Includes discharge bypass valve and Copper pipe fittings for field installation. Used to 5
modulate capacity at low load conditions.
PHASE MONITOR KIT
2PM04700124 Includes control and all associated wiring. This accessory provides protection against phase 1.3
reversal, loss or unbalance. (Used on YC/YD/PC/PD Models)
LOW AMBIENT TO 0° F:
2LA04702012 This kit includes one (Variable Head Pressure Control) control to vary condenser fan speed 10
to maintain stable head pressure.
HOT GAS BYPASS KIT
10 All 2HG04700524 Includes discharge bypass valve and Copper pipe fittings for field installation. Used to 5
modulate capacity at low load conditions.
PHASE MONITOR KIT
2PM04700124 Includes control and all associated wiring. This accessory provides protection against phase 1.3
reversal, loss or unbalance. (Used on YC/YD/PC/PD Models)
LOW AMBIENT TO 0° F:
2LA04702012 This kit includes one (Variable Head Pressure Control) control to vary condenser fan speed 10
to maintain stable head pressure.
HOT GAS BYPASS KIT
12.5 All 2HG04700524 Includes discharge bypass valve and Copper pipe fittings for field installation. Used to 5
modulate capacity at low load conditions.
PHASE MONITOR KIT
2PM04700124 Includes control and all associated wiring. This accessory provides protection against phase 1.3
reversal, loss or unbalance.
LOW AMBIENT TO 0° F:
2LA04702024 This kit includes two (Variable Head Pressure Control) control to vary condenser fan speed 10
to maintain stable head pressure.
HOT GAS BYPASS KIT
15 All 2HG04700524 Includes discharge bypass valve and Copper pipe fittings for field installation. Used to 5
modulate capacity at low load conditions.
PHASE MONITOR KIT
2PM04700124 Includes control and all associated wiring. This accessory provides protection against phase 1.3
reversal, loss or unbalance.
LOW AMBIENT TO 0° F:
2LA04702024 This kit includes two (Variable Head Pressure Control) control to vary condenser fan speed 10
to maintain stable head pressure.
HOT GAS BYPASS KIT
20 All 2HG04700624 Includes discharge bypass valve and Copper pipe fittings for field installation. Used to 5
modulate capacity at low load conditions.
PHASE MONITOR KIT
2PM04700124 Includes control and all associated wiring. This accessory provides protection against phase 1.3
reversal, loss or unbalance.
LOW AMBIENT TO 0° F:
2LA04702024 This kit includes two (Variable Head Pressure Control) control to vary condenser fan speed 10
to maintain stable head pressure.
HOT GAS BYPASS KIT
25 All 2HG04700624 Includes discharge bypass valve and Copper pipe fittings for field installation. Used to 5
modulate capacity at low load conditions.
PHASE MONITOR KIT
2PM04700124 Includes control and all associated wiring. This accessory provides protection against phase 1.3
reversal, loss or unbalance.
1 One valve per system. Order two valves if both system 1 and 2 require hot gas bypass.

12 Johnson Controls Ducted Systems


505429-JTG-NN-1222

Physical data

J07YE, J10-25YC, and J10-20YD physical data


Model
Component
J07YE J10YC J10YD J12YC J12YD J15YC J15YD J20YC J20YD J25YC
Nominal Tonnage 7.5 10 10 12.5 12.5 15 15 20 20 25
Refrigerant
Refrigerant type R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A
System #1 14.8 20.63 11.75 24.0 14.75 27.0 13.5 37.5 18.8 35
Operating charge (lb)1
System #2 --- --- 12.0 --- 15.0 --- 13.5 --- 18.8 ---
Holding charge Nitrogen
Dimensions (in.)
Length 59.1 59.1 59.1 59.1 59.1 59.1 59.1 59.1 59.1 59.1
Width 31.9 31.9 31.9 31.9 31.9 64.1 64.1 64.1 64.1 64.1
Height 44.5 50.0 50.0 50.0 50.0 44.5 44.5 50.0 50.0 50.0
Weights (lb)
Shipping 386 433 473 499 511 914 903 913 930 945
Operating 383 430 470 497 508 909 898 910 927 942
Compressors2
Single Single Single Tandem Single Tandem Single Tandem Single Tandem
Type Scroll scroll Scroll scroll Scroll scroll scroll scroll scroll scroll
Quantity 1 1 2 1 2 1 2 1 2 1
System #1 7.5 10 4 12.5 6 15 7.5 20 10 25
Nominal capacity (ton)
System #2 --- --- 6 --- 6.3 --- 7.5 --- 10 ---
System #1 2 2 1 2 1 2 1 2 1 2
Capacity stages
System #2 --- --- 1 --- 1 --- 1 --- 1 ---
Stage #1 60 67 --- --- --- --- --- --- --- ---
Unit Capacity Steps (%)
Stage #2 100 100 --- --- --- --- --- --- --- ---
System data
No. refrigeration circuits 1 1 2 1 2 1 2 1 2 1
Suction line OD (in.) 1 1/8 1 3/8 1 1/8 1 3/8 1 1/8 1 5/8 1 1/8 1 5/8 1 3/8 1 5/8
Liquid line OD (in.) 5/8 7/8 5/8 7/8 5/8 7/8 5/8 7/8 5/8 7/8
Outdoor coil data
Face area (sq. ft.) 23.8 29.0 29.0 29.0 29.0 47.5 47.5 58.1 58.1 58.1
Rows 1 1 1 1 1 1 1 1 1 1
Fins per inch 23 23 23 23 23 23 23 23 23 23
Tube diameter (in./MM) 0.71 / 18 0.71 / 18 0.71 / 18 0.71 / 18 1 / 25 0.71 / 18 0.71 / 18 1.00 / 25 0.71 / 18 0.71 / 18
Circuitry type 2-pass 2-pass 2-pass 2-pass 2-pass 2-pass 2-pass 2-pass 2-pass 2-pass
Refrigerant control --- --- --- --- --- --- --- --- --- ---
Condenser fan data
No. fans/diameter (in.) 2/24. 2/24 2/24 2/24 2/24 4/24 4/24 4/24 4/24 4/24
Type Axial Axial Axial Axial Axial Axial Axial Axial Axial Axial
Drive type Direct Direct Direct Direct Direct Direct Direct Direct Direct Direct
No. speeds 1 1 1 1 1 1 1 1 1 1
System #1 2 2 2 2 2 4 2 4 2 4
Number of motors
System #2 --- --- --- --- --- --- 2 --- 2 ---
Motor HP (ea.) 1/3 3/4 3/4 3/4 3/4 1/3 3/4 3/4 3/4 3/4
Rotation3 CW CW CW CW CW CW CW CW CW CW
RPM 850 1100 1100 1100 1100 850 1100 1100 1100 1100
System #1 7500 9800 7300 9800 8000 15000 9800 17300 9800 19600
Nominal CFM
System #2 --- --- --- --- --- --- 9800 --- 9800 ---
1 Includes matched indoor blower unit with 25 ft of piping.
2 All compressors include crankcase heaters.
3
When viewing the shaft end of the motor.

Johnson Controls Ducted Systems 13


505429-JTG-NN-1222

J07PE, J10-20PC, and J15-20PD physical data


Models
Component
J07PE J10PC J15PC J15PD J20PD
Nominal Tonnage 7.5 10 15 15 20
Refrigerant
Refrigerant type R-410A R-410A R-410A R-410A R-410A
System #1 24.12 31 54.0 27.0 34.0
Operating charge (lb)1
System #2 --- --- --- 27.0 34.0
Holding charge Nitrogen
Dimensions (in.)
Length 59.1 59.1 59.1 59.1 59.1
Width 31.9 31.9 64.1 64.1 64.1
Height 44.5 50.0 44.5 44.5 50.0
Weights (lb)
Shipping 442 574 947 921 1090
Operating 445 605 968 942 1126
Compressors2
Type Single scroll Tandem scroll Tandem scroll Single scroll Single scroll
Quantity 1 1 1 2 2
Cooling
Nominal capacity System #1 7.5 10 15 7.5 10
(ton) System #2 --- --- --- 7.5 10
System #1 2 2 2 1 1
Capacity stages
System #2 --- --- --- 1 1
Unit capacity steps Stage #1 60 --- --- --- ---
(%) Stage #2 100 --- --- --- ---
Heating
Nominal capacity
7.5 10 15 15 20
(ton) System #1 & #2
Capacity stages System #1 & #2 2 1 1 1 1
System data
No. refrigeration
1 1 1 2 2
circuits
Suction line OD (in.) 1 1/8 1 3/8 1 5/8 1 3/8 1 3/8
Liquid line OD (in.) 5/8 7/8 7/8 5/8 5/8
Outdoor coil data
Face area (sq. ft.) 23.8 29.0 47.5 47.5 58.1
Rows 2 2 2 2 2
Fins per inch 20 20 20 20 20
Tube diameter (in./
0.38 / 10 0.38 / 10 0.38 / 10 0.38 / 10 0.38 / 10
mm)
Circuitry type Interlaced Interlaced Interlaced Interlaced Interlaced
Refrigerant control TXV TXV TXV TXV TXV
Condenser fan data
No. fans / diameter
2/24 2/24 4/24 4/24 4/24
(in.)
Type Axial Axial Axial Axial Axial
Drive type Direct Direct Direct Direct Direct
No. speeds 1 1 1 1 1
System #1 2 2 4 2 2
Number of motors
System #2 --- --- --- 2 2
Motor HP (ea.) 1/3 3/4 1/3 1/3 3/4
Rotation3 CW CW CW CW CW
RPM 850 1100 850 850 1100
System #1 7500 9800 15000 7500 9800
Nominal CFM
System #2 --- --- --- 7500 9800
1 Includes matched evaporator unit with 25 ft of piping.
2
All compressors include crankcase heaters.
3 When viewing the shaft end of the motor.

14 Johnson Controls Ducted Systems


505429-JTG-NN-1222

J07 - 20NL and J10 - 20NM indoor unit physical data


Models
Component
J07NL J10NL J10NM J15NL J15NM J20NL J20NM
Nominal Tonnage 7 1/2 10 10 15 15 20 20
Holding charge Nitrogen
Dimensions (in.)
Length 56.0 56.0 56.0 74.5 74.5 98.5 98.5
Width 30.0 30.0 30.0 33.0 33.0 30.0 30.0
Height 65.0 65.0 65.0 75.0 75.0 65.0 65.0
Weights (lb)
Unit Shipping Standard Motor and Drive 542 586 588 794 794 932 932
Unit Shipping High Static Motor and Drive 549 597 599 850 850 963 963
Unit Operating With Standard Motorand Drive 516 563 565 762 762 897 897
Unit Operating With High Static Motor and Drive 523 574 576 788 788 928 928
Indoor blower (forward curve)
Diameter x Width 12 x 12 15 x 15 15 x 15 18 x 18 18 x 18 15 x 15 15 x 15
Quantity 1 1 1 1 1 2 2
Indoor coil
Face area (Sq. Ft.) 10.6 10.6 10.6 18.3 18.3 20.0 20.0
Rows 3 4 4 4 4 4 4
Fins per inch 15 15 15 15 15 15 15
Tube diameter 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Circuitry Type Interlaced Interlaced Interlaced Interlaced Interlaced Interlaced Interlaced
Refrigerant Control TXV TXV TXV TXV TXV TXV TXV
System data
No. Refrigeration Circuits 1 1 2 1 2 1 2
Suction Line OD (in.) 1 1/8 1 3/8 1 1/8 1 5/8 1 3/8 1 5/8 1 3/8
Liquid Line OD (in.) 5/8 7/8 5/8 7/8 5/8 7/8 7/8
Filters
Size and Quantity Per 16 x 25 x 2 4 4 4 --- --- 8 8
Model (In.) 20 x 24 x 2 --- --- --- 6 6 --- ---
Face area (sq. ft.) 11.1 11.1 11.1 20.0 20.0 22.2 22.2
Size and Quantity Per 16 x 25 x 4 4 4 4 --- --- 8 8
Model (In.) 20 x 24 x 4 --- --- --- 6 6 --- ---
Face area (sq. ft.) 11.1 11.1 11.1 18.0 18.0 22.2 22.2

Johnson Controls Ducted Systems 15


505429-JTG-NN-1222

J25NC Indoor unit physical data


Models
Component
J25NC1 2
Nominal Tonnage 25
Holding charge Nitrogen
Dimensions (in.)
Length 100.1
Width 38.1
Height 74.6
Weights (lb)
Unit Shipping 1067
Unit Operating With
5 hp Motor and Drive 1130
7.5 hp Motor and Drive 1157
5 hp Motor and Drive With Field Installed VFD Intellispeed 1158
7.5 hp Motor and Drive Field Installed VFD Intellispeed 1187
Indoor blower (forward curve)
Diameter x Width 18 X 18
Quantity 2
Indoor coil
Face area (Sq. Ft.) 25.8
Rows 4
Fins per inch 16
Tube diameter 3/8
Circuitry Type Split
Refrigerant Control TEV
System data
No. Refrigeration Circuits 1
Suction Line OD (in.) 2 1/8
Liquid Line OD (in.) 7/8
Filters
Size and Quantity Per
20 x 25 x 2 10
Model (In.)
Face area (sq. ft.) 34.7
Accessory
Hot water coil data
Face area (Sq. Ft.) 21.2
Rows 2
Fins per inch 12
Tube diameter (Copper) OD (In.) 1/2
Connections (Supply and Return) OD (In.) 1 3/8
Weight (lb) 150
System coil data
Face area (Sq. Ft.) 18.2
Rows 1
Fins per inch 8
Tube diameter (Copper) (In.) 1
Connection, (NPTE) (In.)
Inlet 2
Outlet 1-1/2
Weight (lb) 160
1
Motors, Drive and Overload Kits must be ordered
separately for the J25NC. The Motor Drive and
Overload Kits are to be field installed.
2
IntelliSpeed discrete fan control option for J25NC is
field installed only. Refer to price pages or equipment
selection tools to select the proper motor, drive, and
IntelliSpeed VFD kit.

16 Johnson Controls Ducted Systems


505429-JTG-NN-1222

Unit limitations

Condenser unit limitations


Outdoor DB temp Indoor DB temp Outdoor DB temp Indoor DB temp
Size Applied voltage1 SCCR
Model Unit voltage cooling (°F) cooling (°F) heating (°F) heating (°F)
(ton) (kVA)
Min Max Max Min† Max Min Max Min Max Min
J07 208/230-3-60 187 252 5
PE 125 40 86 68 70 0 80 50
(7.5) 460-3-60 432 504 5
208/230-3-60 187 252 5
J07
YE 460-3-60 432 504 5 125 40 86 68 - - - -
(7.5)
575-3-60 540 630 5
J10 208/230-3-60 187 252 5
PC 125 40 86 68 70 0 80 50
(10) 460-3-60 432 504 5
208/230-3-60 187 252 5
J10
YC 460-3-60 432 504 5 125 40 86 68 - - - -
(10)
575-3-60 540 630 5
208/230-3-60 187 252 5
J10
YD 460-3-60 432 504 5 115 40 86 68 - - - -
(10)
575-3-60 540 630 5
208/230-3-60 187 252 5
J12
YC/YD 460-3-60 432 504 5 125 40 86 68 - - - -
(12.5)
575-3-60 540 630 5
J15 208/230-3-60 187 252 5
PC/PD 125 40 86 68 70 0 80 50
(15) 460-3-60 432 504 5
208/230-3-60 187 252 5
J15
YC/YD 460-3-60 432 504 5 125 40 86 68 - - - -
(15)
575-3-60 540 630 5
J20 208/230-3-60 187 252 5
PD 125 40 86 68 70 0 80 50
(20) 460-3-60 432 504 5
208/230-3-60 187 252 5
J20
YC/YD 460-3-60 432 504 5 125 40 86 68 - - - -
(20)
575-3-60 540 630 5
208/230-3-60 187 252 5
J25
YC 460-3-60 432 504 5 125 40 86 68 - - - -
(25)
575-3-60 540 630 5
1. Rated in accordance with AHRI Standard 110, Range “A” Utilization Voltage.
†. Low Ambient accessories are available to permit stable system operation at ambient temperatures down to 0°F.

Johnson Controls Ducted Systems 17


505429-JTG-NN-1222

Air handling unit limitations


Entering air temperature degrees °F
Power Voltage variation Supply air range CFM
SCCR Cooling
Model supply Heating DB1
(kVA) DB/WB
voltage
Min. Max. Min. Max. Min. Max. Min. Max.
208/230-3-60 5 187 253 2,250 3,750 65/57 90/77 40 80
J07NL 460-3-60 5 414 506 2,250 3,750 65/57 90/77 40 80
575-3-60 5 540 630 2,250 3,750 65/57 90/77 40 80
208/230-3-60 5 187 253 2,500 5,000 65/57 90/77 40 80
J10NL 460-3-60 5 414 506 2,500 5,000 65/57 90/77 40 80
575-3-60 5 540 630 2,500 5,000 65/57 90/77 40 80
208/230-3-60 5 187 253 2,500 5,000 65/57 90/77 40 80
J10NM 460-3-60 5 414 506 2,500 5,000 65/57 90/77 40 80
575-3-60 5 540 630 2,500 5,000 65/57 90/77 40 80
208/230-3-60 5 187 253 4,500 7,500 65/57 90/77 40 80
J15NL 460-3-60 5 414 506 4,500 7,500 65/57 90/77 40 80
575-3-60 5 540 630 4,500 7,500 65/57 90/77 40 80
208/230-3-60 5 187 253 4,500 7,500 65/57 90/77 40 80
J15NM 460-3-60 5 414 506 4,500 7,500 65/57 90/77 40 80
575-3-60 5 540 630 4,500 7,500 65/57 90/77 40 80
208/230-3-60 5 187 253 6,000 10,000 65/57 90/77 40 80
J20NL 460-3-60 5 414 506 6,000 10,000 65/57 90/77 40 80
575-3-60 5 540 630 6,000 10,000 65/57 90/77 40 80
208/230-3-60 5 187 253 6,000 10,000 65/57 90/77 40 80
J20NM 460-3-60 5 414 506 6,000 10,000 65/57 90/77 40 80
575-3-60 5 540 630 6,000 10,000 65/57 90/77 40 80
208/230-3-60 5 187 253 7,500 12,500 65/57 90/77 40 80
J25ML 460-3-60 5 414 506 7,500 12,500 65/57 90/77 40 80
575-3-60 5 540 630 7,500 12,500 65/57 90/77 40 80
1 Heating Min/Max temperatures apply to steam and hot water coils. Note: Do not apply steam to hot water coils.

18 Johnson Controls Ducted Systems


505429-JTG-NN-1222

Cooling and heating ratings

Cooling and heating rating


System cooling capacity1 Heating capacity1
High outdoor Low outdoor Rated
Outdoor Indoor
unit unit Net capacity2 IEER IEER w/ Net Net airflow
EER 2 (CFM)
(MBH) (CV) IntelliSpeed capacity COP capacity2 COP
(MBh) (MBh)
J07PE J07NL 85 11 N/A 16 78 3.4 45 2.3 2900

J10PC J10NL 113 11 N/A 15.1 104 3.4 69 2.3 3600

J15PC J15NL 180 10.6 N/A 13.5 168 3.3 104 2.3 5800

J15PD J15NM 174 10.6 N/A 14 160 3.4 100 2.25 6000

J20PD J20NM 230 10.6 N/A 13.5 220 3.3 130 2.2 8000

J07YE J07NL 91 11.2 N/A 16 N/A N/A N/A N/A 3000

J10YC J10NL 117 11.2 N/A 15.2 N/A N/A N/A N/A 4000

J10YD J10NM 115 11.4 N/A 15 N/A N/A N/A N/A 3800

J12YC J15NL 148 11 N/A 14.2 N/A N/A N/A N/A 5000

J12YD J15NM 145 11.2 N/A 14.2 N/A N/A N/A N/A 5000

J15YC J15NL 180 11.2 N/A 14.2 N/A N/A N/A N/A 6000

J15YD J15NM 180 11 N/A 14.2 N/A N/A N/A N/A 6000

J20YC J20NL 240 11 N/A 14.8 N/A N/A N/A N/A 7600

J20YD J20NM 240 10.2 N/A 13.4 N/A N/A N/A N/A 8000
3
J25YC J25NC 290 10.1 N/A 13.2 N/A N/A N/A N/A 9400
1
Certified in accordance with the Ducted Systems Large Equipment certification program, which is based on AHRI Standard 340/360.
(Except J25YC)
2
NET capacity includes heat added by the standard motor horsepower. See J07-J20N* Air Handler Blower Motor and Drive Data for
standard motor sizes.
3
Requires field installed VFD kit.

LEGEND
EER = Energy Efficiency Ratio
AHRI = Air Conditioning and Refrigeration Institute
IEER = Integrated Energy Efficiency Ratio

Johnson Controls Ducted Systems 19


505429-JTG-NN-1222

Commercial splits factory provided match-ups - 7.5 to 25 ton


Product AHU
Tonnage 7.5 10 10 15 15 20 20 25
Outdoor Unit
Product Tonnage NL090 NL120 NM120 NL180 NM180 NL240 NM240 NC300
/ Indoor units
7.5 J07PE X — — — — — — —
10 J10PC — X — — — — — —
HP 15 J15PC — — — X — — — —
15 J15PC — — — — X — — —
20 J20PD — — — — — — X —
7.5 J07YC X — — — — — — —
10 J10YC — X — — — — — —
10 J10YD — — X — — — — —
12.5 J12YC — — — X — — — —
12.5 J12YD — — — — X — — —
AC
15 J15YC — — — X — — — —
15 J15YD — — — — X — — —
20 J20YC — — — — — X — —
20 J20YD — — — — — — X —
25 J25YC — — — — — — — X

20 Johnson Controls Ducted Systems


505429-JTG-NN-1222

Capacity Performance
Condenser and air handling cooling capacities

J07YE/J07NL
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 110.5 5.5 55.4 46.7 38.1 - - - 105.4 6.2 55.4 46.6 37.9 - - -
72 99.7 5.4 66.0 56.9 47.8 38.7 - - 95.9 6.1 65.0 56.0 47.0 38.1 - -
1875
67 88.9 5.3 76.6 67.0 57.5 48.0 39.2 - 86.3 5.9 74.6 65.4 56.2 47.0 38.1 -
62 81.1 5.2 81.1 75.3 67.2 55.8 48.9 39.7 78.3 5.9 78.3 74.0 65.3 55.2 47.2 38.1
77 111.1 5.6 61.5 50.1 38.8 - - - 106.0 6.2 61.0 49.3 37.7 - - -
72 102.0 5.5 72.0 61.1 50.301 39.5 - - 97.9 6.1 70.6 59.9 49.1 38.4 - -
2250 67 92.8 5.4 82.4 72.1 61.8 50.7 40.1 - 89.7 6.0 80.3 70.4 60.6 49.6 38.8 -
62 86.6 5.3 86.6 80.6 73.4 60.7 51.7 40.8 83.8 6.0 83.8 79.2 72.0 60.1 50.1 39.1
57 80.4 5.2 80.4 80.4 80.4 74.1 63.2 52.3 77.9 6.0 77.9 77.9 77.9 72.4 61.3 50.2
77 111.7 5.6 67.7 53.6 39.4 - - - 106.5 6.2 66.6 52.1 37.5 - - -
72 104.2 5.5 78.0 65.4 52.8 40.2 - - 99.8 6.1 76.3 63.7 51.2 38.7 - -
2625 67 96.8 5.4 88.3 77.3 66.2 53.4 41.0 - 93.1 6.1 85.9 75.4 64.9 52.1 39.5 -
62 92.1 5.4 92.1 86.0 79.6 65.7 54.5 41.9 89.3 6.0 89.3 84.4 78.6 65.1 52.9 40.0
57 87.4 5.3 87.4 87.4 87.4 80.5 67.9 55.4 85.5 6.0 85.5 85.5 85.5 79.3 66.3 53.2
77 112.2 5.6 73.9 57.0 40.1 - - - 107.0 6.3 72.3 54.8 37.3 - - -
72 106.5 5.5 84.0 69.7 55.3 41.0 - - 101.8 6.2 81.9 67.6 53.3 39.0 - -
3000 67 100.8 5.5 94.2 82.4 70.5 56.1 41.9 - 96.5 6.1 91.5 80.4 69.3 54.7 40.2 -
62 97.7 5.4 96.8 91.3 85.8 70.6 57.3 43.1 94.8 6.1 93.9 89.6 85.3 70.1 55.7 41.0
57 94.5 5.4 94.5 94.5 94.5 86.8 72.7 58.5 93.0 6.1 93.0 93.0 93.0 86.3 71.3 56.3
72 108.8 5.6 90.0 73.9 57.8 41.7 - - 103.7 6.2 87.5 71.4 55.4 39.3 - -
67 104.8 5.5 100.0 87.5 74.9 58.8 42.8 - 99.9 6.2 97.1 85.4 73.6 57.2 40.9 -
3375
62 103.2 5.5 101.3 96.6 92.0 75.6 60.1 44.2 100.3 6.2 97.6 94.8 91.9 75.0 58.6 41.9
57 101.6 5.5 100.1 100.1 100.1 93.2 77.4 61.5 100.6 6.2 96.9 96.9 96.9 93.2 76.3 59.3
72 111.1 5.6 96.1 78.2 60.318 42.4 - - 105.7 6.3 93.2 75.3 57.5 39.6 - -
67 108.7 5.6 105.9 92.6 79.3 61.5 43.7 - 103.3 6.2 102.8 90.4 78.0 59.8 41.6 -
3750
62 108.7 5.6 105.8 102.0 98.2 80.6 62.9 45.3 105.7 6.2 101.4 100.0 98.6 80.0 61.4 42.8
57 108.7 5.6 105.6 105.6 105.6 99.6 82.1 64.6 108.1 6.3 100.0 100.0 100.0 100.0 81.3 62.3
95°F 105°F
77 100.4 6.8 55.4 46.5 37.6 - - - 95.3 7.9 52.5 43.8 35.1 - - -
72 92.1 6.7 64.0 55.1 46.3 37.4 - - 87.0 7.8 61.9 53.0 44.1 35.2 - -
1875
67 83.8 6.6 72.7 63.8 54.9 46.0 37.0 - 78.6 7.7 71.3 62.2 53.1 44.1 35.0 -
62 75.6 6.6 75.6 72.7 63.5 54.5 45.6 36.6 74.2 7.7 74.2 70.3 62.1 52.9 43.7 34.5
77 100.8 6.8 60.5 48.5 36.6 - - - 95.8 7.9 58.5 46.5 34.5 - - -
72 93.7 6.7 69.3 58.6 47.931 37.3 - - 88.9 7.8 67.3 56.6 45.9 35.3 - -
2250 67 86.6 6.6 78.1 68.7 59.3 48.4 37.5 - 81.9 7.7 76.0 66.7 57.4 46.5 35.5 -
62 81.0 6.7 81.0 77.8 70.6 59.5 48.4 37.3 79.0 7.7 79.0 75.1 68.9 57.7 46.5 35.3
57 75.4 6.7 75.4 75.4 75.4 70.6 59.4 48.1 76.2 7.7 76.2 76.2 76.2 68.9 57.4 46.0
77 101.3 6.9 65.6 50.6 35.5 - - - 96.3 7.9 64.5 49.2 33.9 - - -
72 95.4 6.8 74.5 62.1 49.6 37.1 - - 90.8 7.8 72.6 60.2 47.8 35.4 - -
2625 67 89.5 6.7 83.4 73.5 63.6 50.8 38.0 - 85.2 7.8 80.7 71.2 61.7 48.9 36.1 -
62 86.5 6.7 86.5 82.8 77.7 64.5 51.3 38.1 83.9 7.8 83.9 79.9 75.6 62.4 49.3 36.1
57 83.5 6.8 83.5 83.5 83.5 78.2 64.6 51.1 82.5 7.8 82.5 82.5 82.5 75.9 62.4 48.9
77 101.7 6.9 70.7 52.6 34.5 - - - 96.9 7.9 70.5 51.9 33.3 - - -
72 97.0 6.8 79.8 65.5 51.3 37.0 - - 92.7 7.9 78.0 63.8 49.6 35.4 - -
3000 67 92.3 6.8 88.8 78.4 68.0 53.2 38.5 - 88.5 7.8 85.4 75.7 66.0 51.3 36.6 -
62 91.9 6.8 91.0 87.9 84.8 69.5 54.2 38.9 88.7 7.8 87.2 84.8 82.3 67.2 52.0 36.9
57 91.5 6.8 91.5 91.5 91.5 85.7 69.9 54.1 88.9 7.8 88.9 88.9 88.9 83.0 67.4 51.8
72 98.6 6.9 85.0 69.0 52.9 36.9 - - 94.6 7.9 83.3 67.4 51.5 35.5 - -
67 95.1 6.8 94.2 83.3 72.4 55.7 38.9 - 91.7 7.9 90.1 80.2 70.2 53.7 37.2 -
3375
62 97.3 6.9 94.0 92.9 91.9 74.5 57.0 39.6 93.5 7.9 90.1 89.6 89.0 71.9 54.8 37.7
57 99.6 6.9 93.8 93.8 93.8 93.2 75.1 57.1 95.3 7.9 90.1 90.1 90.1 90.1 72.4 54.7
72 100.3 6.9 90.3 72.4 54.583 36.7 - - 96.5 7.9 88.7 71.0 53.3 35.6 - -
67 97.9 6.9 97.9 88.2 76.8 58.1 39.4 - 95.0 7.9 94.8 84.7 74.5 56.1 37.8 -
3750
62 102.8 6.9 97.0 97.0 97.0 79.4 59.9 40.4 98.3 7.9 93.0 93.0 93.0 76.7 57.6 38.5
57 107.6 7.0 94.4 94.4 94.4 94.4 80.4 60.0 101.7 8.0 91.2 91.2 91.2 91.2 77.4 57.7

Johnson Controls Ducted Systems 21


505429-JTG-NN-1222

J07YE/J07NL (Continued)
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 90.1 8.9 49.7 41.1 32.5 - - - 85.0 10.0 46.8 38.4 29.9 - - -
72 81.8 8.9 59.8 50.9 41.9 33.0 - - 76.6 9.9 57.7 48.7 39.8 30.8 - -
1875
67 73.5 8.8 70.0 60.7 51.4 42.2 32.9 - 68.3 9.9 68.3 59.1 49.6 40.2 30.9 -
62 72.8 8.7 72.8 67.9 60.8 51.3 41.8 32.4 71.4 9.8 71.4 65.5 59.4 49.7 40.0 30.2
77 90.8 8.9 56.6 44.5 32.4 - - - 85.7 10.0 54.6 42.4 30.2 - - -
72 84.0 8.9 65.3 54.6 43.9 33.3 - - 79.1 9.9 63.3 52.6 42.0 31.3 - -
2250 67 77.2 8.8 74.0 64.8 55.5 44.6 33.6 - 72.5 9.9 72.0 62.8 53.7 42.6 31.6 -
62 77.1 8.8 77.1 72.5 67.1 55.8 44.5 33.2 75.1 9.8 74.3 69.8 65.4 54.0 42.6 31.2
57 76.9 8.7 76.9 76.9 76.9 67.1 55.5 43.8 77.7 9.7 76.7 76.7 76.7 65.3 53.5 41.7
77 91.4 8.9 63.4 47.8 32.2 - - - 86.4 9.9 62.3 46.4 30.5 - - -
72 86.1 8.9 70.7 58.3 46.0 33.6 - - 81.5 9.9 68.8 56.5 44.1 31.8 - -
2625 67 80.9 8.9 78.0 68.9 59.7 47.0 34.2 - 76.6 9.9 75.3 66.5 57.7 45.0 32.3 -
62 81.3 8.8 80.7 77.1 73.5 60.3 47.2 34.1 78.7 9.9 77.0 74.2 71.3 58.3 45.2 32.1
57 81.6 8.8 81.6 81.6 81.6 73.7 60.2 46.7 80.7 9.8 78.7 78.7 78.7 71.5 58.0 44.5
77 92.0 8.9 70.3 51.2 32.1 - - - 87.1 9.9 70.1 50.5 30.8 - - -
72 88.3 8.9 76.2 62.1 48.0 33.9 - - 84.0 9.9 74.4 60.4 46.3 32.3 - -
3000 67 84.6 8.9 82.0 73.0 63.9 49.4 34.8 - 80.8 10.0 78.7 70.2 61.8 47.4 33.0 -
62 85.5 8.9 83.5 81.6 79.8 64.8 49.9 34.9 82.3 9.9 79.7 78.5 77.3 62.5 47.7 33.0
57 86.3 8.8 84.9 84.9 84.9 80.3 65.0 49.6 83.7 9.9 80.8 80.8 80.8 77.6 62.5 47.3
72 90.5 8.9 81.6 65.8 50.0 34.2 - - 86.4 9.9 79.9 64.2 48.5 32.8 - -
67 88.4 8.9 86.1 77.1 68.1 51.8 35.5 - 85.0 10.0 82.0 74.0 65.9 49.8 33.7 -
3375
62 89.7 8.9 86.3 86.2 86.1 69.4 52.6 35.8 85.9 9.9 82.4 82.4 82.4 66.8 50.3 33.9
57 91.0 8.9 86.5 86.5 86.5 86.5 69.7 52.4 86.8 9.9 82.8 82.8 82.8 82.8 67.0 50.1
72 92.7 8.9 87.1 69.5 52.0 34.5 - - 88.9 10.0 85.5 68.1 50.7 33.3 - -
67 92.1 8.9 90.1 81.2 72.2 54.2 36.1 - 89.2 10.0 85.4 77.7 70.0 52.2 34.4 -
3750
62 93.9 9.0 89.1 89.1 89.1 73.9 55.3 36.7 89.5 10.0 85.1 85.1 85.1 71.1 52.9 34.8
57 95.7 9.0 88.1 88.1 88.1 88.1 74.4 55.3 89.8 10.0 84.9 84.9 84.9 84.9 71.4 52.9
1 These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
2 These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

22 Johnson Controls Ducted Systems


505429-JTG-NN-1222

J10YC/J10NL
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 143.5 7.4 78.3 63.2 48.1 - - - 140.2 8.2 77.4 62.2 47.0 - - -
72 132.8 7.2 92.9 78.7 64.5 50.2 - - 129.5 8.1 92.3 77.8 63.4 48.9 - -
3000 67 122.1 7.1 107.6 94.2 80.8 65.9 52.0 - 118.8 7.9 107.3 93.5 79.7 64.7 50.2 -
62 115.4 7.0 114.7 105.9 97.1 79.6 67.9 53.3 114.6 7.8 114.6 105.3 96.0 79.6 66.1 51.1
57 126.6 6.9 126.6 120.0 113.4 98.7 83.9 69.1 119.3 7.8 119.3 117.2 112.4 97.1 81.9 66.7
77 146.3 7.4 86.8 67.2 47.6 - - - 141.0 8.2 85.2 66.0 46.7 - - -
72 135.8 7.3 100.2 83.7 67.1 50.5 - - 132.3 8.1 99.6 82.9 66.1 49.4 - -
3500 67 125.2 7.1 113.7 100.2 86.7 69.4 52.9 - 123.6 8.0 114.0 99.7 85.5 68.2 51.2 -
62 121.6 7.1 121.3 114.9 106.2 86.8 71.8 54.6 120.4 7.9 119.9 112.9 104.8 86.3 69.9 52.4
57 131.4 7.0 131.4 128.1 124.8 108.2 90.7 73.2 124.0 7.9 124.0 124.0 123.7 106.4 88.5 70.7
77 149.1 7.4 95.3 71.1 47.0 - - - 141.7 8.2 93.1 69.8 46.5 - - -
72 138.7 7.3 107.5 88.6 69.8 50.9 - - 135.0 8.1 106.9 87.9 68.9 49.8 - -
4000 67 128.4 7.2 119.8 106.1 92.5 72.9 53.8 - 128.3 8.0 120.8 106.0 91.2 71.6 52.2 -
62 127.8 7.2 127.8 123.8 115.3 94.0 75.7 55.9 126.3 8.0 125.2 120.6 113.6 92.9 73.7 53.7
57 136.2 7.1 136.2 136.2 136.2 117.8 97.5 77.3 128.7 8.0 128.7 128.7 128.7 115.6 95.1 74.7
72 141.7 7.4 114.8 93.6 72.4 51.2 - - 137.7 8.2 114.3 92.9 71.6 50.3 - -
67 131.5 7.2 125.9 112.1 98.4 76.4 54.8 - 133.0 8.1 127.5 112.3 97.0 75.1 53.2 -
4500
62 134.0 7.2 134.0 132.8 124.4 101.2 79.6 57.1 132.1 8.1 132.1 128.2 122.4 99.6 77.5 55.0
57 141.0 7.3 141.0 141.0 141.0 127.3 104.3 81.3 133.4 8.1 133.4 133.4 133.4 124.8 101.7 78.7
72 144.7 7.4 122.1 98.6 75.04 51.5 - - 140.5 8.2 121.6 98.0 74.4 50.8 - -
67 134.7 7.3 132.0 118.1 104.2 80.0 55.7 - 137.8 8.1 134.2 118.5 102.8 78.5 54.2 -
5000
62 140.2 7.3 140.2 140.2 133.4 108.4 83.4 58.4 137.9 8.2 137.9 135.8 131.2 106.3 81.3 56.3
57 145.8 7.4 145.8 145.8 145.8 136.9 111.2 85.4 138.1 8.2 138.1 138.1 138.1 134.0 108.4 82.7
95°F 105°F
77 137.0 9.0 76.4 61.1 45.9 - - - 130.3 10.5 74.7 59.7 44.7 - - -
72 126.3 8.9 91.7 77.0 62.26 47.5 - - 120.3 10.3 89.7 75.0 60.4 45.7 - -
3000 67 115.5 8.7 107.0 92.8 78.6 63.6 48.5 - 110.3 10.0 104.8 90.4 76.0 61.1 46.2 -
62 113.8 8.7 113.8 104.7 95.0 79.6 64.2 48.8 110.0 10.0 108.9 100.3 91.7 76.6 61.4 46.2
57 112.1 8.6 112.1 112.1 111.3 95.6 79.9 64.2 109.7 10.0 109.7 108.8 107.4 92.0 76.6 61.2
77 135.7 9.0 83.7 64.8 45.9 - - - 129.4 10.4 82.9 63.6 44.2 - - -
72 128.8 8.9 99.0 82.1 65.1 48.2 - - 122.8 10.3 97.0 80.0 63.1 46.2 - -
3500 67 121.9 8.8 114.4 99.3 84.3 66.9 49.6 - 116.2 10.1 111.0 96.5 82.0 64.6 47.3 -
62 119.3 8.8 118.6 111.0 103.5 85.7 67.9 50.2 115.2 10.1 113.0 107.0 100.9 83.1 65.2 47.4
57 116.7 8.7 116.7 116.7 116.7 104.5 86.3 68.1 114.1 10.0 112.8 112.8 112.8 101.5 83.2 64.9
77 134.4 9.1 91.0 68.5 46.0 - - - 128.6 10.4 91.2 67.5 43.8 - - -
72 131.3 9.0 106.3 87.2 68.0 48.8 - - 125.3 10.3 104.2 85.1 65.9 46.7 - -
4000 67 128.2 8.9 121.7 105.9 90.0 70.3 50.6 - 122.1 10.1 117.2 102.6 88.0 68.2 48.3 -
62 124.7 8.8 122.6 117.3 112.0 91.8 71.7 51.5 120.3 10.1 117.1 113.6 110.1 89.6 69.1 48.6
57 121.2 8.8 121.2 121.2 121.2 113.4 92.7 72.1 118.5 10.1 115.5 115.5 115.5 111.0 89.8 68.6
72 133.8 9.0 113.7 92.3 70.8 49.4 - - 127.8 10.3 111.4 90.1 68.7 47.3 - -
67 134.5 8.9 129.1 112.4 95.7 73.7 51.7 - 128.0 10.2 123.4 108.7 94.0 71.7 49.4 -
4500
62 130.2 8.9 126.7 123.6 120.5 98.0 75.4 52.9 125.4 10.2 121.2 120.2 119.3 96.1 72.9 49.7
57 125.8 8.9 123.1 123.1 123.1 122.2 99.1 76.1 122.9 10.2 118.2 118.2 118.2 118.2 96.4 72.3
72 136.3 9.0 121.0 97.3 73.68 50.0 - - 130.3 10.3 118.7 95.1 71.4 47.8 - -
67 140.9 9.0 136.5 118.9 101.3 77.0 52.8 - 133.9 10.2 129.6 114.8 99.9 75.2 50.5 -
5000
62 135.6 9.0 130.7 129.9 129.0 104.1 79.2 54.2 130.6 10.2 125.2 125.2 125.2 102.6 76.7 50.9
57 130.4 9.0 125.0 125.0 125.0 125.0 105.6 80.0 127.2 10.2 120.9 120.9 120.9 120.9 103.0 76.0

Johnson Controls Ducted Systems 23


505429-JTG-NN-1222

J10YC/J10NL (Continued)
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 123.6 11.9 73.0 58.2 43.4 - - - 116.9 13.3 71.3 56.7 42.2 - - -
72 114.3 11.6 87.8 73.1 58.5 43.8 - - 108.4 13.0 85.8 71.2 56.6 41.9 - -
3000 67 105.1 11.3 102.6 88.0 73.5 58.7 43.9 - 99.9 12.6 99.9 85.7 70.9 56.2 41.5 -
62 106.2 11.3 103.4 95.9 88.5 73.5 58.6 43.7 102.4 12.6 97.8 91.5 85.2 70.5 55.8 41.1
57 107.4 11.3 102.7 102.7 102.7 88.4 73.3 58.3 105.0 12.7 95.2 95.2 95.2 84.8 70.1 55.3
77 123.2 11.8 82.2 62.4 42.5 - - - 116.9 13.2 81.5 61.2 40.8 - - -
72 116.8 11.6 94.9 78.0 61.1 44.2 - - 110.8 13.0 92.9 76.0 59.1 42.3 - -
3500 67 110.5 11.4 107.6 93.7 79.7 62.3 44.9 - 104.9 12.6 104.3 90.9 77.5 60.0 42.6 -
62 111.0 11.4 107.5 102.9 98.4 80.4 62.5 44.6 106.9 12.6 101.9 98.8 95.8 77.8 59.8 41.8
57 111.5 11.3 106.2 106.2 106.2 98.5 80.1 61.7 109.0 12.7 99.5 99.5 99.5 95.6 77.0 58.5
77 122.7 11.7 91.5 66.5 41.6 - - - 116.9 13.0 91.7 65.6 39.5 - - -
72 119.3 11.6 102.1 82.9 63.8 44.7 - - 113.3 13.0 99.9 80.8 61.7 42.7 - -
4000 67 116.0 11.4 112.7 99.3 86.0 66.0 46.0 - 109.9 12.7 108.1 96.1 84.0 63.9 43.7 -
62 115.9 11.4 111.5 109.9 108.2 87.3 66.5 45.6 111.4 12.6 106.0 106.0 106.0 85.1 63.8 42.6
57 115.7 11.4 109.7 109.7 109.7 108.6 86.9 65.1 113.0 12.6 103.9 103.9 103.9 103.9 84.0 61.7
72 121.8 11.6 109.2 87.9 66.5 45.2 - - 115.8 13.0 107.0 85.7 64.3 43.0 - -
67 121.5 11.4 117.7 105.0 92.3 69.7 47.1 - 115.0 12.7 112.0 101.3 90.6 67.7 44.8 -
4500
62 120.7 11.4 115.6 115.6 115.6 94.2 70.4 46.5 116.0 12.6 110.1 110.1 110.1 92.4 67.9 43.4
57 119.9 11.4 113.2 113.2 113.2 113.2 93.7 68.6 116.9 12.6 108.2 108.2 108.2 108.2 90.9 64.8
72 124.3 11.6 116.3 92.8 69.2 45.6 - - 118.2 12.9 114.0 90.5 66.9 43.4 - -
67 127.0 11.5 122.7 110.6 98.6 73.4 48.2 - 120.0 12.7 115.8 106.5 97.2 71.5 45.9 -
5000
62 125.5 11.4 119.7 119.7 119.7 101.1 74.3 47.5 120.5 12.6 114.2 114.2 114.2 99.6 71.9 44.1
57 124.1 11.4 116.7 116.7 116.7 116.7 100.4 72.0 120.9 12.6 112.6 112.6 112.6 112.6 97.9 68.0
1 These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
2 These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

24 Johnson Controls Ducted Systems


505429-JTG-NN-1222

J10YD/J10NM
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 141.7 6.6 68.4 58.8 49.3 - - - 136.3 7.2 65.9 56.5 47.2 - - -
72 129.3 6.4 86.6 74.2 61.8 49.4 - - 123.6 7.1 84.4 72.2 60.0 47.8 - -
2500
67 116.9 6.3 104.8 89.6 74.3 62.7 50.4 - 111.0 7.0 102.9 87.8 72.7 60.9 48.6 -
62 113.0 6.2 110.9 98.9 86.8 72.3 63.7 52.1 108.8 6.8 106.7 96.1 85.5 72.1 61.7 49.8
77 142.9 6.6 78.3 64.1 49.9 - - - 136.9 7.2 76.8 62.1 47.4 - - -
72 132.3 6.5 94.9 80.1 65.4 50.7 - - 126.5 7.1 92.8 78.1 63.3 48.6 - -
3000 67 121.7 6.4 111.5 96.2 80.9 66.5 51.5 - 116.0 7.0 108.7 94.0 79.3 64.6 49.7 -
62 118.8 6.3 115.9 106.2 96.4 79.3 67.0 52.4 114.4 6.9 111.6 103.4 95.3 79.1 65.4 50.5
57 116.0 6.2 116.0 116.0 111.9 97.3 82.6 68.0 112.9 6.8 112.9 112.9 111.3 96.2 81.2 66.1
77 144.1 6.6 88.2 69.3 50.5 - - - 137.5 7.2 87.8 67.7 47.5 - - -
72 135.3 6.5 103.1 86.0 69.0 51.9 - - 129.3 7.1 101.2 83.9 66.7 49.5 - -
3500 67 126.5 6.4 118.1 102.8 87.5 70.2 52.6 - 121.0 7.0 114.5 100.2 85.9 68.4 50.7 -
62 124.7 6.4 121.3 113.6 105.9 86.4 70.4 52.6 120.0 7.0 116.5 110.8 105.1 86.2 69.1 51.1
57 122.9 6.3 122.9 122.9 120.8 106.3 88.2 70.1 119.1 6.9 118.5 118.5 118.5 105.9 87.5 69.2
77 145.4 6.6 98.1 74.6 51.1 - - - 138.1 7.2 98.8 73.3 47.7 - - -
72 138.3 6.5 111.4 92.0 72.5 53.1 - - 132.1 7.1 109.6 89.8 70.1 50.3 - -
4000 67 131.3 6.4 124.7 109.4 94.0 74.0 53.7 - 126.0 7.0 120.3 106.4 92.5 72.2 51.7 -
62 130.5 6.4 126.5 121.0 115.5 93.4 73.8 52.9 125.7 7.0 121.4 118.1 114.8 93.2 72.8 51.8
57 129.7 6.4 128.2 128.2 128.2 115.4 93.8 72.2 125.3 7.0 122.5 122.5 122.5 115.6 93.9 72.3
72 141.4 6.5 119.7 97.9 76.1 54.4 - - 134.9 7.1 118.0 95.7 73.5 51.2 - -
67 136.6 6.5 131.3 116.0 100.6 77.8 54.9 - 131.5 7.1 126.1 112.6 99.0 75.9 52.7 -
4500
62 136.4 6.5 131.6 128.3 125.1 100.5 77.1 53.1 131.3 7.1 126.4 125.5 124.6 100.3 76.5 52.5
57 136.1 6.5 131.9 131.9 131.9 124.4 99.4 74.3 131.0 7.0 126.6 126.6 126.6 125.2 100.3 75.4
72 144.4 6.5 127.9 103.8 79.7 55.6 - - 137.8 7.1 126.4 101.6 76.8 52.1 - -
67 143.5 6.5 138.0 122.6 107.2 81.6 56.0 - 137.0 7.1 132.0 118.8 105.6 79.7 53.8 -
5000
62 142.2 6.5 138.2 135.7 134.6 107.5 80.5 53.4 136.9 7.1 132.9 132.8 132.9 107.3 80.2 53.2
57 140.9 6.5 139.0 139.0 139.0 133.5 104.9 76.4 136.1 7.1 133.1 133.1 133.1 133.1 106.7 78.5
95°F 105°F
77 130.8 7.9 63.4 54.2 45.1 - - - 127.2 8.5 62.7 53.8 44.9 - - -
72 118.0 7.7 82.2 70.1 58.1 46.1 - - 114.7 8.4 81.3 69.2 57.0 44.9 - -
2500
67 105.2 7.6 100.9 86.1 71.2 59.0 46.9 - 103.0 8.2 99.9 84.5 69.1 57.1 45.1 -
62 104.7 7.5 102.4 93.3 84.2 72.0 59.7 47.4 102.3 8.1 100.0 90.6 81.2 69.4 57.5 45.7
77 131.0 7.8 75.4 60.1 44.8 - - - 127.5 8.5 74.4 59.3 44.2 - - -
72 120.6 7.7 90.7 76.0 61.3 46.6 - - 117.3 8.3 89.4 74.7 60.0 45.4 - -
3000 67 110.4 7.6 105.9 91.8 77.7 62.8 47.8 - 108.1 8.2 104.5 90.1 75.8 61.0 46.1 -
62 110.0 7.5 107.1 100.6 94.2 79.0 63.8 48.5 107.5 8.1 104.6 98.1 91.6 76.6 61.6 46.6
57 109.7 7.4 108.2 108.2 108.2 95.2 79.7 64.2 107.0 8.0 105.0 105.0 105.0 92.3 77.1 61.9
77 131.4 7.8 87.5 66.0 44.6 - - - 127.9 8.4 86.0 64.8 43.6 - - -
72 123.2 7.7 99.2 81.8 64.5 47.1 - - 119.8 8.3 97.5 80.3 63.1 45.8 - -
3500 67 115.5 7.6 110.9 97.6 84.3 66.5 48.8 - 113.5 8.2 109.0 95.8 82.6 64.9 47.2 -
62 115.4 7.6 111.7 108.0 104.2 86.0 67.8 49.6 113.1 8.2 109.0 105.5 102.0 83.9 65.7 47.6
57 115.3 7.5 112.5 112.5 112.5 105.5 86.9 68.3 112.9 8.1 110.0 110.0 110.0 102.9 84.3 65.6
77 132.0 7.8 99.6 72.0 44.4 - - - 128.0 8.4 97.7 70.3 42.9 - - -
72 125.8 7.7 107.8 87.7 67.6 47.6 - - 122.4 8.3 105.6 85.9 66.1 46.3 - -
4000 67 120.9 7.7 115.9 103.4 90.9 70.3 49.7 - 118.2 8.2 113.5 101.4 89.3 68.7 48.2 -
62 120.8 7.6 116.4 115.3 114.2 93.0 71.9 50.8 117.9 8.2 113.8 112.9 112.4 91.1 69.8 48.5
57 120.5 7.6 116.9 116.9 116.9 115.8 94.1 72.4 117.0 8.1 114.0 114.0 114.0 113.5 91.4 69.4
72 128.4 7.7 116.3 93.5 70.8 48.0 - - 124.9 8.3 113.7 91.4 69.1 46.8 - -
67 126.5 7.7 120.9 109.2 97.5 74.0 50.6 - 123.6 8.3 118.0 107.0 96.0 72.6 49.2 -
4500
62 126.2 7.7 121.1 121.1 121.1 100.0 76.0 51.9 123.1 8.2 118.5 118.5 118.5 98.4 73.9 49.5
57 125.8 7.6 121.2 121.2 121.2 121.2 101.3 76.5 122.2 8.2 119.0 119.0 119.0 119.0 98.6 73.1
72 132.1 7.7 124.8 99.4 74.0 48.5 - - 128.9 8.3 121.8 97.0 72.2 47.3 - -
67 131.6 7.7 125.9 115.0 104.0 77.8 51.6 - 128.4 8.3 122.6 112.6 102.7 76.5 50.3 -
5000
62 131.1 7.7 126.7 126.7 126.7 107.1 80.0 53.0 127.8 8.3 123.0 123.0 123.0 105.6 78.0 50.4
57 130.5 7.7 128.6 128.6 128.6 128.6 108.5 80.6 127.1 8.3 123.5 123.5 123.5 123.5 105.8 76.8

Johnson Controls Ducted Systems 25


505429-JTG-NN-1222

J10YD/J10NM
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 120.1 9.8 61.4 53.0 44.6 - - - - - - - - - - -
72 108.2 9.6 79.6 67.2 54.8 42.4 - - - - - - - - - -
2500
67 97.5 9.5 95.4 81.4 65.0 53.3 41.6 - - - - - - - - -
62 96.4 9.3 96.0 85.2 75.2 64.2 53.2 42.2 - - - - - - - -
77 119.9 9.7 72.2 57.7 43.1 - - - - - - - - - - -
72 110.7 9.6 86.9 72.2 57.5 42.9 - - - - - - - - - -
3000 67 104.0 9.5 99.0 86.7 72.0 57.4 42.8 - - - - - - - - -
62 103.4 9.3 99.3 92.9 86.5 71.9 57.3 42.8 - - - - - - - -
57 102.5 9.2 101.0 97.1 97.1 86.4 71.9 57.4 - - - - - - - -
77 119.8 9.7 83.1 62.3 41.6 - - - - - - - - - - -
72 113.1 9.6 94.1 77.2 60.3 43.4 - - - - - - - - - -
3500 67 108.2 9.4 102.9 92.0 79.0 61.5 44.0 - - - - - - - - -
62 107.3 9.3 103.4 100.6 97.7 79.6 61.5 43.4 - - - - - - - -
57 106.4 9.2 105.0 101.8 101.8 97.7 79.0 60.3 - - - - - - - -
77 119.6 9.6 94.0 67.0 40.1 - - - - - - - - - - -
72 115.5 9.5 101.3 82.2 63.0 43.9 - - - - - - - - - -
4000 67 113.0 9.4 108.7 97.3 86.0 65.6 45.2 - - - - - - - - -
62 112.2 9.4 109.0 105.5 104.6 87.3 65.7 44.0 - - - - - - - -
57 111.4 9.3 110.1 106.4 106.4 106.4 86.1 63.2 - - - - - - - -
72 117.9 9.5 108.5 87.2 65.8 44.4 - - - - - - - - - -
67 117.7 9.4 112.2 102.6 93.0 69.7 46.4 - - - - - - - - -
4500
62 117.1 9.4 112.8 111.6 111.6 95.1 69.8 44.6 - - - - - - - -
57 116.3 9.4 113.2 112.0 112.0 112.0 93.3 66.1 - - - - - - - -
72 122.5 9.4 115.0 92.1 68.5 44.9 - - - - - - - - - -
67 122.0 9.4 115.5 107.9 100.0 73.8 47.7 - - - - - - - - -
5000
62 121.4 9.4 115.7 115.7 115.7 102.8 74.0 45.3 - - - - - - - -
57 120.6 9.4 116.0 116.0 116.0 116.0 100.4 69.0 - - - - - - - -
1 These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
2 These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

26 Johnson Controls Ducted Systems


505429-JTG-NN-1222

J12YC/J15NL
Air on Temperature of air on condenser Coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 178.5 10.2 87.6 71.1 54.7 - - - 172.2 11.3 84.0 67.6 51.2 - - -
72 168.2 9.9 111.9 95.4 78.9 62.4 - - 161.2 11.0 108.3 91.9 75.5 59.2 - -
3750 67 157.9 9.6 136.1 119.6 103.1 86.7 70.2 - 150.1 10.7 132.5 116.2 99.8 83.4 67.1 -
62 144.8 9.4 144.8 144.8 129.3 112.8 96.3 79.8 138.9 10.6 138.9 138.9 126.4 110.1 93.7 77.3
57 149.7 9.5 149.7 149.7 137.7 121.2 104.7 88.3 143.9 10.7 143.9 143.9 130.6 114.3 97.9 81.5
77 184.7 10.2 94.2 77.2 58.5 - - - 177.6 11.3 92.4 73.7 55.0 - - -
72 174.0 9.9 121.8 103.1 84.4 65.7 - - 166.2 11.0 118.4 99.8 81.1 62.4 - -
4375 67 163.4 9.6 149.5 129.0 110.3 91.6 72.9 - 154.7 10.8 144.5 125.8 107.1 88.4 69.8 -
62 149.9 9.4 149.9 149.9 138.2 119.8 100.8 82.1 143.2 10.6 143.2 143.2 135.7 117.0 98.4 79.7
57 154.9 9.5 154.9 154.9 147.3 129.1 109.8 91.1 148.4 10.7 148.4 148.4 140.2 121.6 102.9 84.2
77 190.9 10.3 100.7 83.2 62.3 - - - 182.9 11.3 100.8 79.8 58.8 - - -
72 179.9 9.9 131.8 110.8 89.9 68.9 - - 171.2 11.0 128.6 107.6 86.6 65.6 - -
5000 67 168.8 9.6 162.9 138.4 117.5 96.5 75.5 - 159.4 10.8 156.5 135.5 114.5 93.5 72.5 -
62 154.9 9.4 154.9 154.9 147.2 126.8 105.3 84.3 147.5 10.6 147.5 147.5 145.0 124.0 103.0 82.0
57 160.1 9.6 160.1 160.1 156.9 137.0 114.9 94.0 152.9 10.7 152.9 152.9 149.8 128.8 107.8 86.8
72 182.3 10.1 142.7 119.7 96.7 73.7 - - 174.1 11.2 139.0 116.1 93.1 70.2 - -
67 171.1 9.8 168.1 149.4 126.4 103.4 80.4 - 162.1 10.9 160.6 146.0 123.1 100.1 77.2 -
5625
62 157.0 9.6 157.0 157.0 153.1 130.4 107.1 84.1 150.0 10.7 150.0 150.0 148.8 125.8 102.9 79.9
57 162.2 9.7 162.2 162.2 160.6 138.1 114.6 91.6 155.5 10.8 155.5 155.5 153.9 131.0 108.1 85.1
72 184.7 10.2 153.7 128.6 103.6 78.5 - - 177.0 11.3 149.4 124.5 99.7 74.8 - -
67 173.4 9.9 173.4 160.4 135.4 110.4 85.3 - 164.8 11.0 164.8 156.6 131.7 106.8 81.9 -
6250
62 159.0 9.7 159.0 159.0 159.0 134.0 108.9 83.9 152.5 10.8 152.5 152.5 152.5 127.6 102.7 77.8
57 164.4 9.8 164.4 164.4 164.4 139.3 114.3 89.2 158.1 10.9 158.1 158.1 158.1 133.2 108.3 83.4
95°F 105°F
77 166.0 12.3 80.3 64.1 47.8 - - - 159.9 14.1 79.0 62.8 46.6 - - -
72 154.1 12.1 104.7 88.4 72.2 55.9 - - 148.2 13.8 102.8 86.6 70.4 54.2 - -
3750 67 142.3 11.9 129.0 112.7 96.5 80.2 64.0 - 136.4 13.5 126.7 110.5 94.2 78.0 61.8 -
62 132.9 11.7 132.9 132.9 123.6 107.4 91.1 74.9 130.6 13.4 130.6 130.6 122.0 105.8 89.6 73.4
57 138.2 11.8 138.2 138.2 123.6 107.3 91.1 74.8 134.7 13.5 134.7 134.7 119.4 103.2 87.0 70.8
77 170.5 12.3 90.6 70.2 51.6 - - - 163.0 14.0 91.5 68.6 50.0 - - -
72 158.3 12.1 115.0 96.4 77.8 59.1 - - 151.0 13.7 112.8 94.2 75.6 56.9 - -
4375 67 146.1 11.9 139.5 122.6 104.0 85.3 66.7 - 139.1 13.5 134.2 119.8 101.2 82.5 63.9 -
62 136.5 11.7 136.5 136.5 133.2 114.3 95.9 77.3 133.1 13.4 133.1 133.1 130.9 112.1 93.6 75.0
57 142.0 11.8 142.0 142.0 133.2 114.0 95.9 77.3 137.3 13.5 137.3 137.3 128.1 109.2 90.9 72.2
77 175.0 12.3 100.8 76.3 55.3 - - - 166.1 13.9 104.0 74.4 53.4 - - -
72 162.5 12.1 125.4 104.4 83.4 62.3 - - 153.9 13.7 122.9 101.8 80.7 59.6 - -
5000 67 150.0 11.9 150.0 132.5 111.5 90.4 69.4 - 141.7 13.4 141.7 129.1 108.1 87.0 65.9 -
62 140.1 11.7 140.1 140.1 142.8 121.2 100.7 79.7 135.6 13.3 135.6 135.6 139.8 118.5 97.7 76.6
57 145.7 11.8 145.7 145.7 142.8 120.7 100.7 79.7 140.0 13.4 140.0 140.0 136.9 115.3 94.8 73.7
72 165.9 12.2 135.3 112.4 89.5 66.7 - - 157.7 13.8 133.0 110.0 87.1 64.2 - -
67 153.1 12.0 153.1 142.6 119.7 96.8 73.9 - 145.2 13.5 145.2 138.0 116.6 93.7 70.8 -
5625
62 143.1 11.8 143.1 143.1 144.4 121.2 98.6 75.7 138.9 13.4 138.9 138.9 141.0 118.0 95.2 72.3
57 148.7 11.9 148.7 148.7 147.3 123.9 101.5 78.6 143.4 13.5 143.4 143.4 141.8 118.6 96.0 73.1
72 169.3 12.3 145.2 120.5 95.7 71.0 - - 161.4 14.0 143.0 118.3 93.5 68.7 - -
67 156.3 12.1 156.3 152.7 128.0 103.2 78.5 - 148.6 13.7 148.6 146.9 125.2 100.4 75.6 -
6250
62 146.0 11.9 146.0 146.0 146.0 121.3 96.5 71.8 142.2 13.6 142.2 142.2 142.2 117.5 92.7 67.9
57 151.8 12.0 151.8 151.8 151.8 127.0 102.3 77.6 146.8 13.7 146.8 146.8 146.8 122.0 97.2 72.5

Johnson Controls Ducted Systems 27


505429-JTG-NN-1222

J12YC/J15NL (Continued)
Air on Temperature of air on condenser Coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 153.8 15.8 77.6 61.4 45.3 - - - 147.7 17.5 76.3 60.1 44.0 - - -
72 142.2 15.5 101.0 84.8 68.7 52.5 - - 136.2 17.2 99.2 83.0 66.9 50.8 - -
3750 67 130.5 15.1 124.4 108.2 92.0 75.9 59.7 - 124.7 16.8 122.1 105.9 89.8 73.7 57.6 -
62 128.2 15.1 128.2 128.2 120.4 104.2 88.0 71.9 125.8 16.8 125.8 125.8 118.7 102.6 86.5 70.4
57 131.2 15.2 131.2 131.2 115.2 99.0 82.8 66.7 127.8 17.0 127.8 127.8 111.0 94.9 78.7 62.6
77 155.5 15.7 92.3 67.0 48.4 - - - 148.1 17.3 93.2 65.4 46.8 - - -
72 143.8 15.3 110.6 92.0 73.4 54.7 - - 136.5 17.0 108.4 89.8 71.2 52.5 - -
4375 67 132.0 15.0 128.9 117.0 98.3 79.7 61.1 - 125.0 16.6 123.7 114.2 95.5 76.9 58.3 -
62 129.7 15.0 129.7 129.7 128.6 110.0 91.3 72.7 126.2 16.7 126.2 126.2 126.2 107.8 89.1 70.4
57 132.7 15.1 132.7 132.7 123.1 104.4 85.8 67.2 128.1 16.8 128.1 128.1 118.0 99.7 80.8 62.1
77 157.3 15.5 107.1 72.6 51.5 - - - 148.4 17.1 110.2 70.7 49.6 - - -
72 145.4 15.2 120.3 99.2 78.1 57.0 - - 136.8 16.8 117.7 96.6 75.4 54.3 - -
5000 67 133.5 14.9 133.5 125.8 104.7 83.6 62.5 - 125.2 16.4 125.2 122.4 101.3 80.1 59.0 -
62 131.1 14.9 131.1 131.1 136.9 115.8 94.7 73.6 126.6 16.5 126.6 126.6 126.6 113.1 91.6 70.5
57 134.2 15.0 134.2 134.2 131.0 109.9 88.8 67.7 128.5 16.6 128.5 128.5 125.1 104.5 82.8 61.7
72 149.5 15.4 130.6 107.6 84.7 61.7 - - 141.3 17.0 128.2 105.2 82.3 59.3 - -
67 137.3 15.1 137.3 133.4 113.5 90.6 67.6 - 129.3 16.6 129.3 128.8 110.4 87.5 64.5 -
5625
62 134.8 15.1 134.8 134.8 137.7 114.7 91.8 68.8 130.7 16.7 130.7 130.7 130.7 111.5 88.4 65.4
57 138.0 15.2 138.0 138.0 136.4 113.4 90.5 67.5 132.6 16.8 132.6 132.6 130.9 108.2 84.9 62.0
72 153.6 15.6 140.9 116.1 91.3 66.5 - - 145.7 17.2 138.7 113.9 89.1 64.3 - -
67 141.0 15.3 141.0 141.0 122.4 97.6 72.8 - 133.4 16.8 133.4 133.4 119.6 94.8 69.9 -
6250
62 138.5 15.3 138.5 138.5 138.5 113.7 88.9 64.1 134.7 16.9 134.7 134.7 134.7 109.9 85.1 60.2
57 141.8 15.4 141.8 141.8 141.8 117.0 92.2 67.4 136.7 17.1 136.7 136.7 136.7 111.9 87.1 62.3
1 These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
2 These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

28 Johnson Controls Ducted Systems


505429-JTG-NN-1222

J12YD/J15NM
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) Capacity1 Input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 175.3 8.9 99.4 80.2 61.0 - - - 169.8 10.0 96.1 78.2 60.2 - - -
72 158.4 8.7 109.1 93.2 77.3 61.4 - - 152.8 9.9 105.9 90.7 75.5 60.2 - -
3125
67 141.6 8.6 118.9 106.2 93.6 76.0 62.3 - 135.8 9.8 115.6 103.1 90.7 74.7 60.6 -
62 132.6 8.4 132.6 122.1 109.9 90.1 79.0 63.6 129.5 9.7 129.5 118.9 106.0 88.9 76.1 61.2
77 175.6 9.0 105.2 83.9 62.6 - - - 169.6 10.0 103.0 82.0 61.0 - - -
72 161.6 8.8 118.1 99.9 81.8 63.6 - - 155.5 9.9 114.8 97.2 79.5 61.8 - -
3750 67 147.5 8.6 131.0 116.0 100.9 81.2 64.7 - 141.5 9.8 126.7 112.3 97.9 79.5 62.6 -
62 140.1 8.5 132.0 131.1 120.1 98.5 83.9 65.8 136.4 9.7 130.0 127.7 116.4 96.9 81.0 63.3
57 132.7 8.3 132.7 132.7 132.7 121.2 103.1 85.1 130.1 9.7 130.1 130.1 130.1 117.1 99.4 81.6
77 176.0 9.0 111.1 87.7 64.2 - - - 169.4 10.1 109.8 85.8 61.9 - - -
72 164.7 8.8 127.1 106.7 86.2 65.8 - - 158.3 10.0 123.8 103.6 83.5 63.4 - -
4375 67 153.5 8.7 141.0 125.7 108.2 86.5 67.1 - 147.2 9.8 136.0 121.5 105.2 84.3 64.5 -
62 147.7 8.6 141.6 140.2 130.2 106.9 88.7 68.0 143.3 9.8 136.5 136.5 126.8 105.0 85.8 65.3
57 141.9 8.5 141.9 141.9 141.9 131.3 110.4 89.5 139.3 9.8 139.3 139.3 139.3 127.8 107.1 86.4
77 176.3 9.0 117.0 91.4 65.9 - - - 169.2 10.1 116.6 89.7 62.7 - - -
72 167.9 8.9 136.1 113.4 90.7 68.0 - - 161.0 10.0 132.7 110.1 87.5 65.0 - -
5000 67 159.4 8.7 150.0 135.4 115.5 91.7 69.4 - 152.8 9.9 144.9 130.6 112.4 89.1 66.5 -
62 155.2 8.7 150.5 149.3 140.4 115.2 93.6 70.2 150.1 9.9 145.0 145.0 137.2 113.1 90.7 67.4
57 151.0 8.7 151.0 151.0 151.0 141.5 117.7 94.0 147.4 9.9 147.4 147.4 147.4 138.5 114.9 91.2
72 171.0 8.9 145.1 120.1 95.2 70.2 - - 163.7 10.0 141.7 116.6 91.6 66.5 - -
67 165.3 8.8 159.8 145.1 122.9 97.0 71.8 - 158.5 10.0 154.0 139.8 119.6 93.9 68.5 -
5625
62 162.7 8.8 160.0 158.3 150.6 123.6 98.4 72.4 157.0 10.0 154.5 154.1 147.7 121.2 95.5 69.5
57 160.2 8.8 160.2 160.2 160.2 151.6 125.0 98.4 155.5 10.0 155.5 155.5 155.5 149.1 122.6 96.0
72 174.1 9.0 154.1 126.9 99.6 72.4 - - 166.5 10.1 150.7 123.1 95.6 68.1 - -
67 171.2 8.9 168.1 154.8 130.2 102.2 74.2 - 164.2 10.1 163.4 149.0 126.8 98.7 70.5 -
6250
62 170.3 8.9 169.0 167.4 160.7 132.0 103.3 74.6 163.9 10.1 163.6 162.8 158.1 129.2 100.4 71.6
57 169.3 8.8 169.3 169.3 169.3 161.8 132.4 102.9 163.6 10.1 163.6 163.6 163.6 159.8 130.3 100.8
95°F 105°F
77 164.2 11.1 92.9 76.2 59.4 - - - 154.5 13.0 88.8 72.2 55.6 - - -
72 147.2 11.1 102.6 88.1 73.6 59.1 - - 139.1 13.0 99.5 84.9 70.3 55.7 - -
3125
67 130.1 11.0 112.2 100.0 87.8 73.4 58.9 - 123.7 13.0 110.2 97.6 84.9 70.3 55.7 -
62 126.5 10.9 126.5 115.7 102.0 87.6 73.2 58.8 122.1 12.8 122.1 112.0 99.6 85.0 70.4 55.9
77 163.5 11.1 100.7 80.1 59.4 - - - 154.0 13.0 97.2 76.6 56.0 - - -
72 149.5 11.1 111.5 94.4 77.2 60.0 - - 141.6 12.9 108.3 91.1 74.0 56.8 - -
3750 67 135.5 11.0 122.3 108.6 95.0 77.7 60.5 - 129.1 12.9 119.4 105.7 92.0 74.6 57.3 -
62 132.7 11.0 129.0 124.2 112.7 95.4 78.0 60.7 127.8 12.8 127.4 120.3 110.0 92.4 74.9 57.3
57 129.8 11.0 129.8 129.8 129.8 113.1 95.6 78.2 126.5 12.7 126.5 126.5 126.5 110.2 92.4 74.7
77 162.8 11.1 108.5 84.0 59.5 - - - 153.6 12.9 105.6 81.0 56.4 - - -
72 151.8 11.1 120.4 100.6 80.8 61.0 - - 144.1 12.9 117.1 97.4 77.7 58.0 - -
4375 67 140.9 11.0 132.4 117.3 102.1 82.1 62.0 - 134.6 12.8 128.5 113.8 99.1 78.9 58.8 -
62 138.9 11.0 136.2 132.7 123.4 103.2 82.9 62.7 133.6 12.8 133.0 128.5 120.4 99.8 79.3 58.7
57 136.8 11.0 136.8 136.8 136.8 124.2 103.8 83.4 132.6 12.7 132.6 132.6 132.6 120.7 99.7 78.7
77 162.1 11.1 116.2 87.9 59.5 - - - 153.1 12.9 114.0 85.4 56.8 - - -
72 154.2 11.1 129.4 106.9 84.4 61.9 - - 146.5 12.8 125.8 103.6 81.4 59.2 - -
5000 67 146.3 11.1 142.5 125.9 109.2 86.4 63.6 - 140.0 12.8 137.7 121.9 106.1 83.2 60.4 -
62 145.0 11.1 143.0 141.3 134.1 110.9 87.8 64.6 139.3 12.7 139.0 136.7 130.8 107.3 83.7 60.2
57 143.8 11.1 143.8 143.8 143.8 135.4 112.0 88.5 138.6 12.7 138.6 138.6 138.6 131.3 107.1 82.8
72 156.5 11.1 138.3 113.1 88.0 62.8 - - 149.0 12.8 134.6 109.9 85.2 60.4 - -
67 151.7 11.1 150.5 134.5 116.4 90.8 65.2 - 145.5 12.7 145.5 130.0 113.2 87.6 61.9 -
5625
62 151.2 11.1 150.6 149.8 144.8 118.7 92.6 66.6 145.0 12.7 144.8 144.8 141.2 114.7 88.1 61.6
57 150.8 11.1 150.8 150.8 150.8 146.6 120.1 93.6 144.6 12.7 144.6 144.6 144.6 141.8 114.4 86.9
72 158.8 11.1 147.2 119.4 91.6 63.8 - - 151.5 12.7 143.4 116.1 88.9 61.6 - -
67 157.1 11.1 157.1 143.1 123.5 95.1 66.7 - 150.9 12.7 150.5 138.2 120.3 91.9 63.5 -
6250
62 157.4 11.1 157.4 157.4 155.4 126.5 97.5 68.6 150.8 12.7 150.5 150.5 150.5 122.1 92.6 63.0
57 157.8 11.1 157.8 157.8 157.8 157.8 128.3 98.8 150.7 12.7 150.7 150.7 150.7 150.7 121.7 91.0

Johnson Controls Ducted Systems 29


505429-JTG-NN-1222

J12YD/J15NM (Continued)
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) Capacity1 Input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 144.8 15.0 84.7 68.3 51.9 - - - 135.1 16.9 80.6 64.4 48.1 - - -
72 131.0 15.0 96.5 81.7 67.0 52.2 - - 123.0 16.9 93.4 78.5 63.6 48.7 - -
3125
67 120.1 15.0 108.2 95.1 82.0 67.3 52.6 - 117.3 16.8 106.1 92.6 79.1 64.2 49.4 -
62 117.7 14.7 117.7 108.4 97.1 82.4 67.7 53.0 113.3 16.6 113.3 104.7 94.6 79.8 64.9 50.1
77 144.6 14.8 93.7 73.2 52.6 - - - 135.1 16.8 90.3 69.7 49.2 - - -
72 133.7 14.8 105.1 87.9 70.8 53.7 - - 125.7 16.7 101.9 84.7 67.6 50.5 - -
3750 67 125.2 14.8 116.4 102.7 89.0 71.6 54.1 - 123.2 16.6 113.5 99.8 86.0 68.5 50.9 -
62 124.0 14.6 123.0 116.3 107.2 89.4 71.7 53.9 121.9 16.4 119.8 112.3 104.5 86.5 68.5 50.5
57 123.3 14.4 123.3 123.3 123.3 107.3 89.2 71.1 120.0 16.1 120.0 120.0 120.0 104.5 86.0 67.6
77 144.3 14.7 102.7 78.0 53.3 - - - 135.1 16.5 99.9 75.0 50.2 - - -
72 136.3 14.7 113.7 94.2 74.6 55.1 - - 128.5 16.5 110.3 90.9 71.6 52.2 - -
4375 67 129.0 14.7 124.7 110.3 96.0 75.8 55.6 - 125.6 16.5 120.8 106.9 93.0 72.7 52.4 -
62 128.6 14.5 128.0 124.2 117.4 96.5 75.7 54.8 125.0 16.3 123.6 119.9 114.4 93.2 72.0 50.8
57 128.3 14.4 128.3 128.3 128.3 117.2 95.7 74.1 124.1 16.0 124.1 124.1 124.1 113.7 91.6 69.5
77 144.1 14.6 111.7 82.8 54.0 - - - 135.1 16.3 109.5 80.3 51.2 - - -
72 138.9 14.5 122.3 100.4 78.5 56.6 - - 131.3 16.3 118.8 97.2 75.5 53.9 - -
5000 67 133.7 14.5 132.9 118.0 103.0 80.1 57.2 - 130.0 16.2 128.1 114.0 99.9 76.9 53.9 -
62 133.6 14.4 133.3 132.1 127.5 103.6 79.6 55.7 129.1 16.1 128.1 127.5 124.3 99.9 75.6 51.2
57 133.4 14.3 133.4 133.4 133.4 127.1 102.1 77.2 128.2 16.0 128.2 128.2 128.2 122.9 97.2 71.5
72 141.5 14.4 130.9 106.6 82.3 58.0 - - 134.0 16.1 127.2 103.4 79.5 55.6 - -
67 139.2 14.3 139.2 125.6 110.0 84.3 58.7 - 133.0 15.9 132.0 121.1 106.8 81.1 55.4 -
5625
62 138.8 14.3 138.8 138.8 137.7 110.7 83.6 56.6 132.6 15.9 132.1 132.1 132.1 106.6 79.1 51.6
57 138.4 14.3 138.4 138.4 138.4 137.0 108.6 80.2 132.2 15.9 132.2 132.2 132.2 132.2 102.8 73.5
72 145.0 14.3 139.6 112.9 86.2 59.5 - - 139.0 15.9 135.7 109.6 83.5 57.4 - -
67 144.7 14.3 143.1 133.2 117.0 88.6 60.2 - 138.6 15.9 136.0 128.2 113.8 85.4 57.0 -
6250
62 144.1 14.3 143.4 143.4 143.4 117.7 87.6 57.5 137.5 15.9 136.1 136.1 136.1 113.4 82.7 52.0
57 143.5 14.3 143.5 143.5 143.5 143.5 115.0 83.2 136.3 15.9 136.3 136.3 136.3 136.3 108.4 75.5
1 These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
2 These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

30 Johnson Controls Ducted Systems


505429-JTG-NN-1222

J15YC/J15NL
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 223.5 11.8 104.0 85.0 66.0 - - - 214.6 13.1 101.2 82.2 63.3 - - -
72 207.2 11.5 132.3 113.3 94.4 75.4 - - 198.3 12.8 129.0 110.1 91.2 72.2 - -
4500 67 191.0 11.1 160.6 141.7 122.7 103.7 84.7 - 181.9 12.4 156.8 137.9 119.0 100.1 81.1 -
62 176.0 10.8 176.0 171.9 151.4 132.5 113.5 94.5 168.5 12.2 168.5 166.4 147.5 128.6 109.7 90.8
57 175.0 10.8 175.0 175.0 158.1 139.1 120.1 101.1 168.1 12.1 168.1 168.1 150.6 131.7 112.8 93.8
77 229.4 11.9 113.7 92.3 70.8 - - - 220.1 13.2 110.7 89.4 68.1 - - -
72 212.8 11.6 144.1 122.7 101.2 79.7 - - 203.3 12.8 140.7 119.4 98.1 76.8 - -
5250 67 196.1 11.2 174.5 153.0 131.6 110.1 88.7 - 186.5 12.5 170.6 149.3 128.0 106.7 85.4 -
62 180.7 11.0 180.7 178.6 162.4 141.9 119.5 98.1 172.7 12.2 172.7 171.7 158.7 137.4 116.1 94.8
57 179.7 10.9 179.7 179.7 169.6 149.6 126.6 105.2 172.4 12.2 172.4 172.4 162.0 140.7 119.4 98.1
77 235.4 12.0 123.5 99.5 75.6 - - - 225.5 13.3 120.3 96.6 72.9 - - -
72 218.3 11.7 155.9 132.0 108.0 84.1 - - 208.3 12.9 152.3 128.6 105.0 81.3 - -
6000 67 201.2 11.3 188.3 164.4 140.5 116.5 92.6 - 191.1 12.6 184.4 160.7 137.0 113.4 89.7 -
62 185.4 11.1 185.4 185.4 173.4 151.3 125.5 101.6 177.0 12.3 177.0 177.0 169.9 146.2 122.6 98.9
57 184.4 11.0 184.4 184.4 181.0 160.1 133.2 109.2 176.6 12.3 176.6 176.6 173.5 149.8 126.1 102.4
72 221.3 11.3 165.2 139.4 113.7 88.0 - - 213.7 13.6 165.8 140.1 114.5 88.8 - -
67 204.0 11.0 197.5 174.0 147.8 122.0 96.3 - 196.0 13.3 192.7 175.1 149.4 123.8 98.1 -
6750
62 187.9 10.7 187.9 187.9 181.9 157.1 130.4 104.7 181.5 13.0 181.5 181.5 178.0 152.4 126.7 101.1
57 186.8 10.6 186.8 186.8 185.2 161.0 133.7 108.0 181.2 13.0 181.2 181.2 179.6 153.9 128.3 102.6
72 224.2 10.9 174.4 146.9 119.4 91.8 - - 219.0 14.3 179.2 151.6 123.9 96.3 - -
67 206.7 10.6 206.7 183.6 155.1 127.6 100.0 - 201.0 14.0 201.0 189.4 161.8 134.1 106.5 -
7500
62 190.4 10.3 190.4 190.4 190.4 162.8 135.3 107.8 186.1 13.7 186.1 186.1 186.1 158.5 130.9 103.2
57 189.3 10.3 189.3 189.3 189.3 161.8 134.3 106.7 185.7 13.7 185.7 185.7 185.7 158.1 130.5 102.9
95°F 105°F
77 205.8 14.4 98.3 79.5 60.6 - - - 195.5 15.9 95.5 76.6 57.7 - - -
72 189.3 14.0 125.7 106.8 87.9 69.1 - - 179.9 15.7 122.5 103.6 84.7 65.9 - -
4500 67 172.8 13.7 153.0 134.1 115.3 96.4 77.5 - 164.3 15.4 149.5 130.7 111.8 92.9 74.0 -
62 161.0 13.5 161.0 161.0 143.6 124.7 105.9 87.0 153.2 15.2 153.2 153.2 139.8 120.9 102.0 83.1
57 161.3 13.5 161.3 161.3 143.1 124.3 105.4 86.6 154.3 15.2 154.3 154.3 136.3 117.4 98.5 79.6
77 210.7 14.4 107.7 86.6 65.4 - - - 199.9 16.0 107.5 83.6 62.4 - - -
72 193.8 14.1 137.2 116.1 94.9 73.8 - - 183.9 15.8 134.0 112.8 91.6 70.4 - -
5250 67 176.9 13.8 166.7 145.6 124.4 103.3 82.2 - 168.0 15.5 160.4 142.0 120.8 99.6 78.3 -
62 164.8 13.5 164.8 164.8 155.0 132.9 112.7 91.6 156.6 15.2 156.6 156.6 151.0 129.4 108.6 87.4
57 165.1 13.6 165.1 165.1 154.5 131.9 112.2 91.1 157.7 15.2 157.7 157.7 147.2 125.3 104.8 83.6
77 215.5 14.5 117.1 93.7 70.2 - - - 204.2 16.1 119.5 90.5 67.0 - - -
72 198.3 14.2 148.7 125.3 101.9 78.5 - - 187.9 15.8 145.4 121.9 98.4 74.9 - -
6000 67 181.0 13.8 180.4 157.0 133.6 110.2 86.8 - 171.6 15.6 171.3 153.3 129.7 106.2 82.7 -
62 168.6 13.6 168.6 168.6 166.4 141.1 119.6 96.2 160.0 15.3 160.0 160.0 162.3 137.8 115.3 91.7
57 168.9 13.6 168.9 168.9 165.9 139.4 119.1 95.6 161.2 15.3 161.2 161.2 158.2 133.2 111.2 87.6
72 206.1 15.9 166.4 140.8 115.2 89.7 - - 192.5 16.7 159.1 133.4 107.7 82.0 - -
67 188.1 15.6 187.8 176.1 151.0 125.5 99.9 - 175.8 16.4 175.7 166.6 142.0 116.3 90.7 -
6750
62 175.2 15.3 175.2 175.2 174.1 147.6 123.0 97.4 164.0 16.2 164.0 164.0 165.1 139.0 113.7 88.1
57 175.5 15.3 175.5 175.5 174.0 146.9 122.9 97.3 165.1 16.2 165.1 165.1 163.6 137.2 112.3 86.6
72 213.9 17.7 184.0 156.3 128.5 100.8 - - 197.2 17.6 172.7 144.9 117.0 89.2 - -
67 195.2 17.3 195.2 195.2 168.5 140.7 113.0 - 180.0 17.3 180.0 180.0 154.3 126.5 98.6 -
7500
62 181.9 17.0 181.9 181.9 181.9 154.1 126.4 98.6 167.9 17.0 167.9 167.9 167.9 140.1 112.2 84.4
57 182.2 17.0 182.2 182.2 182.2 154.4 126.7 99.0 169.0 17.0 169.0 169.0 169.0 141.2 113.4 85.6

Johnson Controls Ducted Systems 31


505429-JTG-NN-1222

J15YC/J15NL
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 185.3 17.5 92.7 73.7 54.8 - - - 175.0 19.1 89.8 70.9 51.9 - - -
72 170.5 17.3 119.4 100.5 81.5 62.6 - - 161.1 18.9 116.2 97.3 78.4 59.4 - -
4500 67 155.8 17.1 146.1 127.2 108.3 89.3 70.4 - 147.2 18.8 142.6 123.7 104.8 85.8 66.9 -
62 145.5 16.9 145.5 145.5 136.0 117.1 98.2 79.3 137.7 18.6 137.7 137.7 132.2 113.3 94.3 75.4
57 147.3 16.8 147.3 147.3 129.4 110.5 91.6 72.7 140.3 18.5 140.3 140.3 122.6 103.6 84.7 65.8
77 189.1 17.6 107.3 80.6 59.3 - - - 178.3 19.2 107.1 77.6 56.2 - - -
72 174.1 17.4 130.7 109.5 88.2 66.9 - - 164.2 19.1 127.5 106.2 84.8 63.5 - -
5250 67 159.0 17.2 154.2 138.3 117.1 95.8 74.5 - 150.1 18.9 147.9 134.7 113.4 92.1 70.7 -
62 148.5 17.0 148.5 148.5 147.1 125.8 104.5 83.3 140.3 18.7 140.3 140.3 140.3 122.2 100.4 79.1
57 150.4 16.9 150.4 150.4 140.0 118.7 97.4 76.2 143.0 18.6 143.0 143.0 132.7 112.1 90.0 68.7
77 192.9 17.7 121.9 87.4 63.8 - - - 181.6 19.3 124.4 84.3 60.5 - - -
72 177.6 17.5 142.1 118.5 94.8 71.2 - - 167.3 19.2 138.8 115.0 91.3 67.6 - -
6000 67 162.2 17.3 162.2 149.5 125.9 102.3 78.6 - 152.9 19.0 152.9 145.8 122.1 98.3 74.6 -
62 151.5 17.0 151.5 151.5 158.2 134.5 110.9 87.3 142.9 18.8 142.9 142.9 142.9 131.2 106.6 82.8
57 153.4 17.0 153.4 153.4 150.5 126.9 103.3 79.6 145.7 18.7 145.7 145.7 142.8 120.6 95.4 71.6
72 179.0 17.5 151.7 126.0 100.2 74.4 - - 165.5 18.3 144.4 118.5 92.7 66.8 - -
67 163.5 17.3 163.5 157.2 133.0 107.2 81.5 - 151.3 18.2 151.3 147.7 124.0 98.1 72.3 -
6750
62 152.7 17.0 152.7 152.7 156.0 130.3 104.5 78.7 141.4 17.9 141.4 141.4 141.4 121.6 95.3 69.4
57 154.7 17.0 154.7 154.7 153.2 127.4 101.7 75.9 144.2 17.9 144.2 144.2 142.8 117.7 91.0 65.2
72 180.4 17.5 161.4 133.5 105.5 77.6 - - 163.7 17.4 150.1 122.1 94.1 66.0 - -
67 164.8 17.3 164.8 164.8 140.1 112.2 84.3 - 149.7 17.3 149.7 149.7 125.9 97.9 69.9 -
7500
62 153.9 17.0 153.9 153.9 153.9 126.0 98.1 70.2 140.0 17.1 140.0 140.0 140.0 112.0 83.9 55.9
57 155.9 17.0 155.9 155.9 155.9 128.0 100.1 72.1 142.7 17.0 142.7 142.7 142.7 114.7 86.7 58.7
1 These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
2 These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

32 Johnson Controls Ducted Systems


505429-JTG-NN-1222

J15YD/J15NM
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 218.6 12.6 99.2 83.3 67.4 - - - 213.3 13.8 96.4 79.9 63.5 - - -
72 205.5 12.1 124.0 108.1 92.2 76.2 - - 199.4 13.4 122.0 105.5 89.1 72.6 - -
3750
67 192.4 11.7 148.8 132.9 117.0 101.0 85.1 - 185.5 13.1 147.6 131.1 114.6 98.2 81.7 -
62 184.8 11.4 184.8 160.1 142.1 126.2 110.2 94.3 175.3 12.8 175.3 159.7 138.4 121.9 105.5 89.0
77 225.1 12.7 109.7 91.8 73.9 - - - 219.1 13.8 106.1 87.7 69.4 - - -
72 211.6 12.2 136.9 119.0 101.1 83.3 - - 204.8 13.5 134.0 115.7 97.4 79.1 - -
4500 67 198.1 11.8 164.1 146.2 128.4 110.5 92.6 - 190.6 13.1 162.0 143.7 125.4 107.1 88.8 -
62 190.3 11.5 190.3 173.8 155.9 138.1 120.2 102.3 180.1 12.9 180.1 169.7 151.4 133.1 114.7 96.4
57 172.5 11.3 172.5 172.5 158.3 140.4 122.5 104.7 172.4 12.9 172.4 172.4 155.0 136.6 118.3 100.0
77 231.7 12.8 120.1 100.3 80.5 - - - 224.9 13.9 115.7 95.5 75.4 - - -
72 217.8 12.3 149.7 129.9 110.1 90.3 - - 210.3 13.5 146.1 125.9 105.8 85.6 - -
5250 67 203.9 11.9 179.4 159.6 139.8 120.0 100.2 - 195.6 13.2 176.5 156.3 136.1 116.0 95.8 -
62 195.8 11.6 195.8 187.6 169.8 150.0 130.2 110.4 184.9 12.9 184.9 179.7 164.4 144.2 124.0 103.8
57 177.6 11.4 177.6 177.6 172.3 152.5 132.7 112.9 177.0 12.9 177.0 177.0 168.2 148.1 127.9 107.7
77 238.2 12.8 130.5 108.7 87.0 - - - 230.7 13.9 125.4 103.3 81.3 - - -
72 223.9 12.4 162.5 140.8 119.1 97.3 - - 215.7 13.6 158.2 136.1 114.1 92.1 - -
6000 67 209.6 11.9 194.6 172.9 151.2 129.4 107.7 - 200.7 13.2 191.0 168.9 146.9 124.9 102.8 -
62 201.3 11.6 201.3 201.3 183.6 161.9 140.1 118.4 189.7 13.0 189.7 189.7 177.3 155.3 133.3 111.2
57 182.6 11.5 182.6 182.6 182.6 164.6 142.9 121.2 181.5 13.0 181.5 181.5 181.5 159.5 137.5 115.4
72 228.7 12.5 173.9 149.9 125.9 101.9 - - 219.9 13.7 170.4 146.0 121.5 97.0 - -
67 214.1 12.1 206.6 183.7 159.8 135.8 111.8 - 204.5 13.3 199.7 180.9 156.4 131.9 107.4 -
6750
62 205.6 11.8 205.6 205.6 196.7 172.7 148.7 124.8 193.3 13.1 193.3 193.3 187.2 162.7 138.2 113.7
57 186.5 11.6 186.5 186.5 186.5 164.4 140.4 116.4 185.0 13.1 185.0 185.0 185.0 160.5 136.1 111.6
72 233.4 12.7 185.2 158.9 132.7 106.4 - - 224.0 13.8 182.7 155.8 128.9 101.9 - -
67 218.5 12.2 218.5 194.6 168.4 142.1 115.9 - 208.4 13.4 208.4 192.8 165.9 139.0 112.1 -
7500
62 209.8 11.9 209.8 209.8 209.8 183.6 157.3 131.1 197.0 13.2 197.0 197.0 197.0 170.1 143.1 116.2
57 190.4 11.8 190.4 190.4 190.4 164.1 137.9 111.6 188.5 13.2 188.5 188.5 188.5 161.6 134.7 107.8
95°F 105°F
77 208.0 15.0 93.5 76.5 59.6 - - - 199.1 16.8 88.3 74.5 57.6 - - -
72 193.3 14.7 119.9 102.9 85.9 68.9 - - 184.5 16.6 117.4 100.5 83.5 66.5 - -
3750
67 178.6 14.5 146.3 129.3 112.3 95.3 78.3 - 169.8 16.4 146.6 126.4 109.4 92.4 75.5 -
62 165.9 14.3 165.9 159.4 134.7 117.7 100.7 83.7 159.3 16.3 159.3 156.1 131.5 114.6 97.6 80.6
77 213.1 15.0 102.4 83.7 64.9 - - - 203.6 16.8 101.0 81.8 62.7 - - -
72 198.0 14.7 131.2 112.4 93.7 74.9 - - 188.6 16.6 129.2 110.1 90.9 71.7 - -
4500 67 183.0 14.5 160.0 141.2 122.4 103.7 84.9 - 173.7 16.4 157.5 138.3 119.1 100.0 80.8 -
62 169.9 14.3 169.9 165.6 146.8 128.1 109.3 90.5 162.9 16.3 162.9 160.7 143.2 124.1 104.9 85.7
57 172.2 14.4 172.2 170.4 151.6 132.9 114.1 95.3 165.1 16.3 165.1 164.2 145.2 126.0 106.8 87.7
77 218.2 15.0 111.4 90.8 70.3 - - - 208.1 16.8 113.8 89.2 67.8 - - -
72 202.8 14.8 142.5 121.9 101.4 80.9 - - 192.8 16.6 141.0 119.7 98.3 77.0 - -
5250 67 187.4 14.5 173.6 153.1 132.5 112.0 91.4 - 177.5 16.4 168.3 150.2 128.9 107.5 86.1 -
62 174.0 14.3 174.0 171.8 158.9 138.4 117.9 97.3 166.5 16.3 166.5 165.4 154.9 133.6 112.2 90.9
57 176.4 14.4 176.4 175.4 164.2 143.6 123.1 102.5 168.7 16.4 168.7 168.3 157.0 135.6 114.3 92.9
77 223.2 15.0 120.3 98.0 75.6 - - - 212.6 16.8 126.5 96.5 72.9 - - -
72 207.5 14.8 153.8 131.5 109.1 86.8 - - 197.0 16.6 152.8 129.3 105.7 82.2 - -
6000 67 191.7 14.5 187.3 165.0 142.6 120.3 98.0 - 181.3 16.4 179.1 162.1 138.6 115.0 91.5 -
62 178.0 14.3 178.0 178.0 171.1 148.7 126.4 104.1 170.1 16.3 170.1 170.1 166.6 143.1 119.5 96.0
57 180.5 14.4 180.5 180.5 176.7 154.3 132.0 109.7 172.4 16.4 172.4 172.4 168.8 145.3 121.8 98.2
72 211.1 14.8 167.0 142.1 117.1 92.1 - - 201.2 16.6 166.0 140.0 114.0 88.0 - -
67 195.0 14.6 192.8 178.0 153.0 128.1 103.1 - 185.2 16.4 184.1 173.8 149.4 123.4 97.4 -
6750
62 181.1 14.4 181.1 181.1 177.6 152.6 127.7 102.7 173.7 16.3 173.7 173.7 172.0 146.0 120.0 94.0
57 183.6 14.5 183.6 183.6 181.7 156.7 131.7 106.8 176.1 16.4 176.1 176.1 174.3 148.3 122.4 96.4
72 214.6 14.9 180.2 152.6 125.0 97.4 - - 205.4 16.6 179.1 150.7 122.2 93.8 - -
67 198.3 14.6 198.3 191.0 163.4 135.8 108.2 - 189.1 16.4 189.1 185.5 160.2 131.7 103.3 -
7500
62 184.1 14.4 184.1 184.1 184.1 156.5 128.9 101.3 177.4 16.3 177.4 177.4 177.4 149.0 120.5 92.1
57 186.7 14.5 186.7 186.7 186.7 159.1 131.5 103.9 179.8 16.3 179.8 179.8 179.8 151.4 122.9 94.5

Johnson Controls Ducted Systems 33


505429-JTG-NN-1222

J15YD/J15NM (Continued)
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 190.3 18.6 83.0 72.6 55.6 - - - 181.4 20.3 76.6 70.6 53.6 - - -
72 175.7 18.5 115.0 98.0 81.1 64.1 - - 166.8 20.3 112.5 95.6 78.6 61.7 - -
3750
67 161.0 18.4 147.0 123.5 106.5 89.6 72.6 - 152.2 20.3 147.4 120.6 103.6 86.7 69.7 -
62 152.8 18.3 152.8 152.8 128.4 111.4 94.5 77.5 146.2 20.3 146.2 146.2 125.2 108.3 91.3 74.4
77 194.2 18.5 99.6 80.0 60.5 - - - 184.7 20.3 98.1 78.2 58.2 - - -
72 179.2 18.5 127.3 107.7 88.2 68.6 - - 169.9 20.3 125.3 105.4 85.4 65.4 - -
4500 67 164.3 18.4 155.0 135.4 115.9 96.3 76.7 - 155.0 20.3 152.5 132.5 112.6 92.6 72.6 -
62 155.9 18.3 155.9 155.9 139.6 120.1 100.5 80.9 148.9 20.3 148.9 148.9 136.0 116.1 96.1 76.2
57 158.0 18.3 158.0 158.0 138.7 119.1 99.6 80.0 150.8 20.2 150.8 150.8 132.2 112.3 92.3 72.3
77 198.1 18.5 116.2 87.5 65.3 - - - 188.0 20.3 119.7 85.8 62.8 - - -
72 182.8 18.5 139.6 117.4 95.3 73.1 - - 172.9 20.3 138.1 115.1 92.2 69.2 - -
5250 67 167.6 18.4 162.9 147.3 125.2 103.0 80.9 - 157.8 20.3 157.6 144.5 121.5 98.5 75.6 -
62 159.0 18.3 159.0 159.0 150.9 128.7 106.6 84.4 151.5 20.3 151.5 151.5 146.8 123.9 100.9 78.0
57 161.1 18.3 161.1 161.1 149.9 127.7 105.5 83.4 153.5 20.2 153.5 153.5 142.7 119.7 96.8 73.8
77 201.9 18.5 132.8 94.9 70.2 - - - 191.3 20.3 141.2 93.4 67.5 - - -
72 186.4 18.4 151.9 127.1 102.3 77.6 - - 175.9 20.3 150.9 124.9 99.0 73.0 - -
6000 67 170.9 18.4 170.9 159.3 134.5 109.8 85.0 - 160.5 20.3 160.5 156.4 130.4 104.5 78.5 -
62 162.1 18.3 162.1 162.1 162.1 137.4 112.6 87.9 154.2 20.2 154.2 154.2 154.2 131.7 105.7 79.8
57 164.3 18.3 164.3 164.3 161.0 136.3 111.5 86.8 156.2 20.2 156.2 156.2 153.2 127.2 101.3 75.3
72 191.3 18.4 164.9 137.9 110.9 83.8 - - 181.5 20.2 163.8 135.8 107.8 79.7 - -
67 175.4 18.3 175.4 169.6 145.7 118.7 91.7 - 165.6 20.2 165.6 165.4 142.0 114.0 86.0 -
6750
62 166.4 18.2 166.4 166.4 166.4 139.4 112.4 85.3 159.0 20.1 159.0 159.0 159.0 132.7 104.7 76.7
57 168.6 18.2 168.6 168.6 167.0 140.0 113.0 85.9 161.2 20.1 161.2 161.2 159.7 131.6 103.6 75.5
72 196.3 18.3 178.0 148.7 119.4 90.1 - - 187.1 20.0 176.8 146.7 116.6 86.4 - -
67 179.9 18.2 179.9 179.9 156.9 127.6 98.3 - 170.7 20.0 170.7 170.7 153.6 123.5 93.4 -
7500
62 170.7 18.2 170.7 170.7 170.7 141.4 112.1 82.8 163.9 20.0 163.9 163.9 163.9 133.8 103.7 73.5
57 173.0 18.2 173.0 173.0 173.0 143.7 114.4 85.1 166.1 20.0 166.1 166.1 166.1 136.0 105.9 75.7
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
2. These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

34 Johnson Controls Ducted Systems


505429-JTG-NN-1222

J20YC/J20NL
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 302.6 13.0 152.3 127.4 102.5 - - - 293.4 15.0 146.7 123.9 101.2 - - -
72 276.0 13.0 182.6 156.4 130.2 104.0 - - 267.4 14.9 179.2 153.3 127.5 101.6 - -
5000
67 249.4 13.1 213.0 185.5 157.9 130.8 106.3 - 241.4 14.9 211.7 182.7 153.7 127.7 103.0 -
62 236.2 12.9 236.2 213.6 185.6 154.8 134.7 109.2 231.1 14.8 231.1 207.2 180.0 152.5 130.3 105.4
77 305.5 13.0 166.8 134.3 101.8 - - - 296.0 15.1 163.9 132.1 100.4 - - -
72 282.9 13.1 198.3 167.4 136.4 105.5 - - 273.7 15.0 195.2 164.4 133.5 102.6 - -
6000 67 260.2 13.1 229.8 200.4 171.1 138.6 108.2 - 251.5 14.9 226.5 196.6 166.6 135.1 104.5 -
62 249.5 13.0 249.5 229.2 205.8 169.5 141.8 109.8 243.4 14.9 243.4 222.3 199.8 166.4 137.3 106.0
57 238.7 12.8 238.7 238.7 238.7 207.9 175.4 142.8 235.3 14.8 235.3 235.3 232.9 201.5 170.0 138.5
77 308.4 13.1 181.3 141.1 101.0 - - - 298.6 15.1 181.2 140.3 99.5 - - -
72 289.7 13.1 213.9 178.3 142.6 107.0 - - 280.1 15.0 211.2 175.4 139.5 103.7 - -
7000 67 271.0 13.1 246.6 215.4 184.3 146.4 110.1 - 261.7 14.9 241.3 210.4 179.6 142.4 106.0 -
62 262.8 13.0 262.8 244.9 225.9 184.2 148.9 110.3 255.7 14.9 255.2 237.4 219.6 180.3 144.2 106.5
57 254.6 12.9 254.6 254.6 254.6 227.6 187.6 147.6 249.6 14.9 249.6 249.6 249.6 221.0 182.4 143.8
77 311.3 13.2 195.8 148.0 100.2 - - - 301.1 15.2 198.4 148.5 98.7 - - -
72 296.5 13.1 229.6 189.2 148.8 108.5 - - 286.5 15.1 227.2 186.4 145.6 104.8 - -
8000 67 281.8 13.1 263.4 230.4 197.5 154.2 112.0 - 271.9 15.0 256.0 224.3 192.5 149.8 107.6 -
62 276.1 13.0 274.9 260.5 246.1 198.9 155.9 110.9 268.0 15.0 265.5 252.5 239.4 194.2 151.2 107.1
57 270.4 12.9 270.4 270.4 270.4 247.3 199.9 152.4 264.0 15.0 264.0 264.0 264.0 240.6 194.8 149.1
72 303.4 13.1 245.2 200.1 155.0 109.9 - - 292.9 15.1 243.2 197.4 151.6 105.8 - -
67 292.6 13.0 280.2 245.4 210.6 162.0 113.9 - 282.1 15.0 270.8 238.1 205.4 157.1 109.1 -
9000
62 289.4 13.0 285.9 276.1 266.2 213.6 163.0 111.4 280.2 15.0 275.9 267.5 259.2 208.1 158.2 107.6
57 286.3 13.0 283.7 283.7 283.7 267.0 212.1 157.2 278.4 15.0 277.0 277.0 277.0 260.1 207.2 154.4
72 310.2 13.2 260.9 211.1 161.2 111.4 - - 299.3 15.2 259.2 208.4 157.7 106.9 - -
67 303.4 13.0 297.0 260.4 223.8 169.8 115.8 - 292.3 15.1 285.6 251.9 218.3 164.5 110.6 -
10000
62 302.8 13.0 297.0 291.7 286.4 228.2 170.1 111.9 292.5 15.1 286.3 282.6 279.0 222.1 165.1 108.2
57 302.1 13.0 297.0 297.0 297.0 286.6 224.3 162.0 292.8 15.1 286.9 286.9 286.9 279.7 219.6 159.6
95°F 105°F
77 284.1 17.1 141.1 120.5 99.8 - - - 268.2 19.9 134.8 115.0 95.2 - - -
72 258.7 16.9 175.8 150.2 124.7 99.1 - - 244.3 19.5 170.9 145.3 119.7 94.0 - -
5000
67 233.3 16.6 210.4 180.0 149.5 124.6 99.7 - 220.4 19.2 207.0 175.6 144.1 119.1 94.2 -
62 226.1 16.7 226.1 200.8 174.3 150.1 125.9 101.6 216.5 19.2 216.5 193.6 168.5 144.2 119.9 95.6
77 286.4 17.1 161.1 130.0 98.9 - - - 270.5 19.9 155.9 124.7 93.5 - - -
72 264.6 16.9 192.1 161.3 130.6 99.8 - - 250.3 19.6 187.0 156.1 125.2 94.4 - -
6000 67 242.8 16.7 223.2 192.7 162.2 131.5 100.9 - 230.1 19.3 218.0 187.5 156.9 126.1 95.3 -
62 237.3 16.8 236.9 215.3 193.8 163.3 132.7 102.2 227.2 19.3 227.2 208.0 188.6 157.8 127.0 96.2
57 231.8 16.8 231.8 231.8 225.4 195.0 164.6 134.2 224.2 19.3 224.2 224.2 220.3 189.5 158.8 128.0
77 288.7 17.2 181.0 139.5 98.0 - - - 272.8 19.8 177.0 134.4 91.8 - - -
72 270.6 17.0 208.5 172.5 136.4 100.4 - - 256.3 19.6 203.0 166.9 130.8 94.7 - -
7000 67 252.4 16.8 235.9 205.4 174.8 138.4 102.0 - 239.9 19.4 229.0 199.4 169.8 133.0 96.3 -
62 248.6 16.8 246.5 229.9 213.3 176.4 139.6 102.8 237.8 19.4 236.3 222.5 208.7 171.4 134.1 96.8
57 244.7 16.9 244.7 244.7 244.7 214.4 177.2 140.0 235.7 19.4 235.7 235.7 235.7 209.8 171.9 134.0
77 291.0 17.2 201.0 149.1 97.1 - - - 275.0 19.8 198.1 144.1 90.1 - - -
72 276.5 17.0 224.8 183.6 142.3 101.1 - - 262.3 19.6 219.1 177.7 136.4 95.0 - -
8000 67 262.0 16.9 248.6 218.1 187.5 145.3 103.1 - 249.6 19.5 240.0 211.3 182.6 140.0 97.4 -
62 259.8 16.9 256.2 244.4 232.7 189.6 146.4 103.3 248.4 19.5 245.1 237.0 228.8 185.0 141.2 97.4
57 257.6 17.0 257.6 257.6 257.6 233.8 189.8 145.7 247.3 19.5 247.3 247.3 247.3 230.0 185.0 139.9
72 282.5 17.1 241.2 194.7 148.2 101.7 - - 268.3 19.7 235.1 188.5 141.9 95.3 - -
67 271.6 17.0 261.4 230.8 200.2 152.2 104.3 - 259.4 19.5 251.0 223.2 195.4 147.0 98.5 -
9000
62 271.0 17.0 265.8 259.0 252.2 202.7 153.3 103.9 259.1 19.5 253.9 251.4 248.9 198.6 148.3 98.0
57 270.5 17.1 270.3 270.3 270.3 253.3 202.4 151.5 258.8 19.6 256.9 256.9 256.9 250.2 198.1 145.9
72 288.4 17.2 257.5 205.8 154.1 102.4 - - 274.3 19.7 251.1 199.3 147.5 95.6 - -
67 281.1 17.1 274.1 243.5 212.9 159.1 105.4 - 269.1 19.6 262.0 235.1 208.2 153.9 99.6 -
10000
62 282.3 17.1 275.5 273.6 271.6 215.9 160.2 104.4 269.7 19.6 262.7 262.7 262.7 212.2 155.4 98.6
57 283.4 17.2 276.9 276.9 276.9 272.7 214.9 157.2 270.3 19.6 263.5 263.5 263.5 263.5 211.2 151.9

Johnson Controls Ducted Systems 35


505429-JTG-NN-1222

J20YC/J20NL (Continued)
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 252.3 22.7 128.5 109.5 90.6 - - - 236.3 25.5 122.1 104.1 86.0 - - -
72 229.9 22.2 166.1 140.4 114.6 88.9 - - 215.5 24.9 161.2 135.4 109.6 83.9 - -
5000
67 207.5 21.8 203.7 171.2 138.7 113.6 88.6 - 194.6 24.4 194.6 166.8 133.3 108.2 83.0 -
62 207.0 21.8 207.0 186.4 162.7 138.3 114.0 89.6 197.4 24.3 197.4 179.2 156.9 132.5 108.0 83.6
77 254.5 22.6 150.7 119.4 88.1 - - - 238.6 25.4 145.5 114.1 82.7 - - -
72 236.0 22.2 181.8 150.8 119.9 88.9 - - 221.6 24.9 176.6 145.6 114.6 83.5 - -
6000 67 217.4 21.9 212.9 182.3 151.7 120.7 89.6 - 204.7 24.4 204.7 177.1 146.4 115.2 84.0 -
62 217.0 21.8 217.0 200.8 183.4 152.4 121.3 90.2 206.8 24.4 206.8 193.5 178.3 146.9 115.6 84.2
57 216.6 21.8 216.6 216.6 215.2 184.1 153.0 121.8 209.0 24.3 209.0 209.0 209.0 178.6 147.1 115.6
77 256.8 22.5 173.0 129.3 85.6 - - - 240.8 25.2 168.9 124.2 79.4 - - -
72 242.0 22.2 197.5 161.3 125.1 88.9 - - 227.8 24.9 192.1 155.8 119.5 83.2 - -
7000 67 227.3 21.9 222.1 193.4 164.7 127.7 90.7 - 214.8 24.5 214.8 187.4 159.6 122.3 85.0 -
62 227.0 21.9 226.1 215.1 204.2 166.4 128.6 90.8 216.3 24.4 215.8 207.7 199.7 161.4 123.1 84.9
57 226.8 21.9 226.8 226.8 226.8 205.1 166.6 128.0 217.8 24.4 216.4 216.4 216.4 200.5 161.3 122.0
77 259.0 22.4 195.2 139.2 83.1 - - - 243.0 25.1 192.3 134.2 76.1 - - -
72 248.1 22.2 213.3 171.8 130.4 88.9 - - 233.9 24.8 207.5 166.0 124.4 82.9 - -
8000 67 237.2 22.0 231.3 204.5 177.7 134.7 91.7 - 224.8 24.6 222.7 197.7 172.7 129.4 86.0 -
62 237.1 22.0 234.0 229.5 224.9 180.4 136.0 91.5 225.7 24.5 223.0 222.0 221.0 175.9 130.7 85.5
57 236.9 22.0 236.7 236.7 236.7 226.2 180.2 134.2 226.5 24.4 223.2 223.2 223.2 222.4 175.4 128.4
72 254.2 22.2 229.0 182.3 135.6 88.9 - - 240.1 24.8 222.9 176.1 129.3 82.6 - -
67 247.1 22.1 240.6 215.6 190.7 141.7 92.8 - 234.9 24.6 230.2 208.0 185.9 136.5 87.0 -
9000
62 247.1 22.1 242.0 242.0 242.0 194.5 143.3 92.1 235.1 24.6 230.1 230.1 230.1 190.3 138.3 86.2
57 247.0 22.0 243.4 243.4 243.4 243.4 193.8 140.3 235.3 24.5 230.0 230.0 230.0 230.0 189.5 134.8
72 260.3 22.2 244.8 192.8 140.9 88.9 - - 246.2 24.7 238.4 186.3 134.3 82.2 - -
67 257.0 22.1 249.8 226.7 203.6 148.7 93.8 - 245.0 24.7 237.6 218.3 199.0 143.5 88.0 -
10000
62 257.1 22.1 250.0 250.0 250.0 208.5 150.6 92.7 244.5 24.6 237.2 237.2 237.2 204.8 145.8 86.8
57 257.2 22.1 250.1 250.1 250.1 250.1 207.4 146.5 244.1 24.6 236.8 236.8 236.8 236.8 203.6 141.2
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

36 Johnson Controls Ducted Systems


505429-JTG-NN-1222

J20YD/J20NM
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 292.8 14.7 136.9 111.9 87.0 - - - 284.3 16.4 135.2 110.2 85.1 - - -
72 272.9 14.4 174.4 149.4 124.5 99.5 - - 263.5 16.1 171.7 146.7 121.7 96.6 - -
6000 67 253.0 14.0 211.9 186.9 162.0 137.0 112.0 - 242.6 15.8 208.2 183.2 158.2 133.2 108.1 -
62 231.8 13.8 231.8 220.2 195.2 170.2 145.2 120.2 225.5 15.5 225.5 219.3 194.3 169.2 144.2 119.2
57 224.6 13.7 224.6 224.6 207.1 182.1 157.1 132.1 219.3 15.5 219.3 219.3 201.5 176.5 151.5 126.5
77 302.2 14.8 149.9 121.7 93.5 - - - 292.0 16.5 147.3 119.2 91.1 - - -
72 281.7 14.5 190.2 162.0 133.8 105.6 - - 270.5 16.2 186.4 158.3 130.2 102.2 - -
7000 67 261.1 14.2 230.5 202.3 174.1 145.9 117.7 - 249.1 15.9 225.5 197.4 169.3 141.3 113.2 -
62 239.3 13.9 239.3 233.5 209.9 182.9 153.5 125.3 231.5 15.6 231.5 228.4 208.0 179.9 151.8 123.8
57 231.8 13.9 231.8 231.8 222.6 196.1 166.2 138.0 225.2 15.6 225.2 225.2 215.7 187.7 159.6 131.5
77 311.7 14.9 162.8 131.4 100.0 - - - 299.6 16.6 159.4 128.2 97.1 - - -
72 290.5 14.6 206.0 174.5 143.1 111.7 - - 277.6 16.3 201.0 169.9 138.8 107.7 - -
8000 67 269.3 14.3 249.1 217.7 186.2 154.8 123.4 - 255.6 16.0 242.7 211.6 180.5 149.4 118.3 -
62 246.8 14.0 246.8 246.8 224.5 195.6 161.7 130.3 237.6 15.7 237.6 237.6 221.7 190.5 159.4 128.3
57 239.1 14.0 239.1 239.1 238.1 210.2 175.3 143.9 231.1 15.7 231.1 231.1 229.9 198.8 167.7 136.6
72 299.4 14.9 217.9 184.4 150.9 117.3 - - 284.7 16.6 212.0 178.6 145.2 111.7 - -
67 277.5 14.6 267.1 229.8 196.3 162.8 129.3 - 262.2 16.3 255.6 222.1 188.7 155.3 121.9 -
9000
62 254.3 14.3 254.3 254.3 236.8 204.5 169.7 136.2 243.7 16.0 243.7 243.7 231.8 198.4 165.0 131.5
57 246.4 14.2 246.4 246.4 245.9 214.1 178.9 145.4 237.0 16.0 237.0 237.0 236.4 203.0 169.6 136.2
72 308.2 15.2 229.9 194.2 158.6 123.0 - - 291.8 16.9 222.9 187.2 151.5 115.8 - -
67 285.7 14.8 285.0 242.0 206.4 170.8 135.2 - 268.7 16.5 268.4 232.7 197.0 161.3 125.6 -
10000
62 261.9 14.6 261.9 261.9 249.0 213.4 177.7 142.1 249.7 16.3 249.7 249.7 241.9 206.2 170.5 134.8
57 253.7 14.5 253.7 253.7 253.7 218.1 182.5 146.9 242.9 16.3 242.9 242.9 242.9 207.2 171.5 135.8
95°F 105°F
77 275.8 18.1 133.4 108.4 83.3 - - - 262.8 20.3 129.8 104.7 79.5 - - -
72 254.0 17.8 169.0 143.9 118.8 93.8 - - 242.0 20.1 164.8 139.7 114.6 89.5 - -
6000 67 232.2 17.5 204.5 179.5 154.4 129.3 104.3 - 221.1 19.8 199.8 174.7 149.6 124.5 99.4 -
62 219.1 17.2 219.1 218.4 193.3 168.3 143.2 118.2 208.7 19.6 208.7 208.3 185.8 160.7 135.6 110.5
57 214.1 17.3 214.1 214.1 196.0 170.9 145.9 120.8 205.0 19.6 205.0 205.0 186.2 161.1 136.0 110.9
77 281.7 18.2 144.7 116.7 88.8 - - - 268.8 20.4 144.0 113.4 85.3 - - -
72 259.4 17.9 182.5 154.6 126.7 98.7 - - 247.4 20.1 179.0 150.9 122.8 94.7 - -
7000 67 237.1 17.6 220.4 192.5 164.6 136.6 108.7 - 226.1 19.9 214.1 188.4 160.3 132.2 104.1 -
62 223.7 17.3 223.7 223.4 206.1 176.9 150.2 122.3 213.4 19.7 213.4 213.2 199.1 170.4 142.9 114.8
57 218.6 17.4 218.6 218.6 208.9 179.2 153.0 125.1 209.7 19.7 209.7 209.7 199.6 170.6 143.4 115.2
77 287.5 18.3 155.9 125.1 94.3 - - - 274.7 20.5 158.2 122.1 91.0 - - -
72 264.8 18.0 196.1 165.3 134.5 103.7 - - 252.9 20.2 193.2 162.1 131.0 99.9 - -
8000 67 242.0 17.7 236.3 205.5 174.7 143.9 113.1 - 231.1 19.9 228.3 202.2 171.1 140.0 108.8 -
62 228.4 17.4 228.4 228.4 218.8 185.5 157.2 126.4 218.1 19.7 218.1 218.1 212.5 180.1 150.3 119.1
57 223.1 17.4 223.1 223.1 221.8 187.5 160.1 129.3 214.3 19.8 214.3 214.3 212.9 180.1 150.7 119.6
72 270.1 18.3 206.1 172.7 139.4 106.1 - - 258.4 20.5 202.9 169.4 136.0 102.5 - -
67 246.9 18.0 244.1 214.5 181.1 147.8 114.5 - 236.1 20.2 234.7 211.0 177.5 144.1 110.6 -
9000
62 233.0 17.7 233.0 233.0 226.8 192.3 160.2 126.9 222.8 20.0 222.8 222.8 219.3 185.2 152.4 118.9
57 227.6 17.7 227.6 227.6 226.9 191.9 160.3 127.0 218.9 20.0 218.9 218.9 218.2 183.9 151.3 117.8
72 275.4 18.6 216.0 180.2 144.4 108.6 - - 263.8 20.8 212.6 176.7 140.9 105.1 - -
67 251.8 18.2 251.8 223.4 187.6 151.8 116.0 - 241.1 20.5 241.1 219.8 184.0 148.2 112.3 -
10000
62 237.6 18.0 237.6 237.6 234.9 199.1 163.3 127.5 227.5 20.3 227.5 227.5 226.1 190.3 154.5 118.6
57 232.1 18.0 232.1 232.1 232.1 196.3 160.5 124.7 223.6 20.3 223.6 223.6 223.6 187.7 151.9 116.1

Johnson Controls Ducted Systems 37


505429-JTG-NN-1222

J20YD/J20NM (Continued)
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 249.8 22.6 126.1 101.0 75.8 - - - 236.8 24.9 122.5 97.3 72.0 - - -
72 229.9 22.3 160.6 135.4 110.3 85.1 - - 217.9 24.6 156.4 131.2 106.0 80.8 - -
6000 67 210.1 22.0 195.1 169.9 144.8 119.6 94.4 - 199.0 24.3 190.3 165.1 139.9 114.7 89.5 -
62 198.2 21.9 198.2 198.2 178.3 153.1 128.0 102.8 187.8 24.3 187.8 187.8 170.7 145.5 120.3 95.1
57 196.0 21.9 196.0 196.0 176.5 151.3 126.1 101.0 187.0 24.2 187.0 187.0 166.7 141.5 116.3 91.1
77 255.8 22.7 143.3 110.0 81.7 - - - 242.9 24.9 142.6 106.7 78.2 - - -
72 235.5 22.4 175.5 147.2 118.9 90.6 - - 223.6 24.7 172.0 143.5 115.0 86.6 - -
7000 67 215.2 22.1 207.7 184.4 156.1 127.8 99.5 - 204.2 24.4 201.3 180.3 151.8 123.4 94.9 -
62 203.0 22.0 203.0 203.0 192.2 163.9 135.7 107.4 192.7 24.3 192.7 192.7 185.3 157.5 128.4 99.9
57 200.8 22.0 200.8 200.8 190.3 162.0 133.7 105.4 191.9 24.3 191.9 191.9 181.0 153.4 124.1 95.6
77 261.9 22.8 160.5 119.1 87.7 - - - 249.1 25.0 162.8 116.1 84.4 - - -
72 241.1 22.5 190.4 159.0 127.5 96.1 - - 229.3 24.8 187.5 155.8 124.1 92.3 - -
8000 67 220.3 22.2 220.3 198.8 167.4 136.0 104.6 - 209.4 24.5 209.4 195.5 163.8 132.0 100.3 -
62 207.8 22.1 207.8 207.8 206.2 174.8 143.3 111.9 197.6 24.4 197.6 197.6 197.6 169.4 136.4 104.7
57 205.5 22.1 205.5 205.5 204.1 172.7 141.3 109.8 196.7 24.4 196.7 196.7 195.3 165.3 131.8 100.1
72 246.6 22.7 199.8 166.1 132.5 98.8 - - 234.9 25.0 196.6 162.8 129.0 95.2 - -
67 225.3 22.4 225.3 207.6 173.9 140.3 106.6 - 214.6 24.7 214.6 204.1 170.3 136.5 102.7 -
9000
62 212.6 22.3 212.6 212.6 211.8 178.2 144.5 110.9 202.4 24.6 202.4 202.4 202.4 171.1 136.7 102.9
57 210.3 22.3 210.3 210.3 209.5 175.9 142.3 108.6 201.6 24.6 201.6 201.6 200.8 167.9 133.2 99.4
72 252.2 23.0 209.2 173.3 137.4 101.6 - - 240.5 25.2 205.7 169.9 134.0 98.1 - -
67 230.4 22.7 230.4 216.3 180.4 144.6 108.7 - 219.7 24.9 219.7 212.7 176.8 141.0 105.1 -
10000
62 217.4 22.5 217.4 217.4 217.4 181.5 145.7 109.8 207.3 24.8 207.3 207.3 207.3 172.8 136.9 101.0
57 215.0 22.5 215.0 215.0 215.0 179.1 143.3 107.4 206.4 24.8 206.4 206.4 206.4 170.5 134.7 98.8
1 These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
2 These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

38 Johnson Controls Ducted Systems


505429-JTG-NN-1222

J25YC/J25NC
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 360.4 19.3 168.6 143.4 118.2 - - - 347.0 20.6 162.5 138.3 114.1 - - -
72 331.5 19.1 212.8 181.7 150.7 119.6 - - 316.2 20.3 208.8 177.7 146.5 115.4 - -
6250
67 302.5 18.9 256.9 220.0 183.2 155.1 124.8 - 285.4 20.0 255.0 217.0 179.0 148.6 117.0 -
62 291.7 18.8 286.5 251.1 215.6 185.0 161.0 133.7 279.2 20.0 275.5 243.4 211.4 178.9 149.7 118.8
77 365.6 19.4 191.4 154.1 116.8 - - - 350.9 20.6 187.5 150.1 112.8 - - -
72 339.8 19.2 233.1 195.3 157.5 119.7 - - 324.5 20.4 229.1 191.4 153.7 116.0 - -
7500 67 314.0 19.0 274.7 236.5 198.2 162.8 125.5 - 298.0 20.1 270.7 232.6 194.6 157.6 119.6 -
62 304.9 18.9 294.0 268.6 239.0 201.3 169.0 134.1 292.6 20.1 286.7 261.1 235.5 196.9 161.0 123.7
57 295.8 18.9 295.8 295.8 279.7 246.1 212.6 179.0 287.1 20.1 287.1 287.1 276.4 239.3 202.3 165.3
77 370.7 19.4 214.2 164.8 115.4 - - - 354.8 20.6 212.5 162.0 111.4 - - -
72 348.1 19.2 253.4 208.9 164.3 119.8 - - 332.7 20.4 249.4 205.1 160.8 116.5 - -
8750 67 325.5 19.0 292.6 253.0 213.3 170.4 126.1 - 310.7 20.3 286.3 248.2 210.1 166.5 122.2 -
62 318.1 19.0 309.8 286.0 262.3 217.6 177.0 134.4 306.0 20.2 297.9 278.7 259.5 214.9 172.3 128.7
57 310.7 19.0 310.7 310.7 302.6 269.6 228.0 186.3 301.3 20.2 301.3 301.3 301.3 265.6 222.3 179.0
77 375.8 19.5 237.0 175.5 113.9 - - - 358.6 20.7 237.4 173.8 110.1 - - -
72 356.4 19.3 273.7 222.4 171.1 119.9 - - 341.0 20.5 269.7 218.8 167.9 117.0 - -
10000 67 337.0 19.1 310.5 269.4 228.4 178.1 126.8 - 323.4 20.4 302.0 263.8 225.7 175.5 124.9 -
62 331.3 19.1 321.5 303.5 285.6 234.0 185.1 134.8 319.4 20.4 309.2 296.4 283.5 232.9 183.6 133.6
57 325.5 19.1 325.5 325.5 325.5 293.1 243.3 193.6 315.5 20.4 312.9 312.9 312.9 291.8 242.3 192.8
72 364.7 19.4 294.1 236.0 178.0 119.9 - - 349.3 20.6 290.0 232.5 175.1 117.6 - -
67 348.5 19.2 328.4 285.9 243.4 185.7 127.5 - 336.1 20.5 317.6 279.5 241.3 184.5 127.5 -
11250
62 344.4 19.2 333.1 321.0 308.9 250.3 193.1 135.2 332.9 20.5 320.4 314.0 307.6 250.9 194.9 138.5
57 340.4 19.2 334.4 334.4 334.4 316.5 258.7 200.9 329.7 20.5 321.5 321.5 321.5 318.0 262.2 206.5
72 373.0 19.4 314.4 249.6 184.8 120.0 - - 357.6 20.6 310.3 246.3 182.2 118.1 - -
67 359.9 19.3 346.3 302.4 258.5 193.3 128.2 - 348.7 20.6 333.3 295.1 256.9 193.5 130.1 -
12500
62 357.6 19.3 348.6 338.5 332.2 266.7 201.1 135.6 346.3 20.6 333.9 331.6 331.6 268.9 206.2 143.5
57 355.3 19.3 348.9 348.9 348.9 340.0 274.1 208.3 343.9 20.6 334.6 334.6 334.6 334.6 282.2 220.2
95°F 105°F
77 333.6 21.9 156.4 133.2 110.0 - - - 304.1 23.5 156.5 130.8 105.0 - - -
72 300.9 21.5 204.8 173.6 142.4 111.2 - - 277.2 23.2 198.6 167.0 135.5 103.9 - -
6250
67 268.2 21.2 253.1 214.0 174.8 142.0 109.2 - 250.3 23.0 240.8 203.3 165.9 134.1 102.3 -
62 266.6 21.2 264.4 235.8 207.2 172.8 138.4 104.0 252.0 23.0 248.9 222.6 196.3 164.4 132.4 100.4
77 336.3 21.9 183.6 146.2 108.8 - - - 307.7 23.5 181.9 141.8 101.6 - - -
72 309.2 21.6 225.1 187.5 149.8 112.2 - - 285.4 23.3 217.4 179.7 142.0 104.3 - -
7500 67 282.1 21.3 266.6 228.7 190.9 152.3 113.8 - 267.9 23.1 252.9 217.7 182.4 144.2 106.1 -
62 280.3 21.3 275.2 253.6 232.0 192.5 152.9 113.4 266.1 23.1 259.1 241.0 222.8 184.1 145.5 106.8
57 278.5 21.3 278.5 278.5 273.0 232.6 192.1 151.7 264.9 23.1 264.9 264.3 263.2 224.0 184.9 145.7
77 338.9 21.9 210.7 159.1 107.5 - - - 311.3 23.5 207.3 152.8 98.3 - - -
72 317.4 21.7 245.4 201.3 157.3 113.2 - - 293.7 23.4 236.1 192.4 148.6 104.8 - -
8750 67 295.9 21.5 280.0 243.5 207.0 162.7 118.3 - 281.6 23.3 265.0 232.0 198.9 154.4 109.8 -
62 293.9 21.5 286.1 271.4 256.7 212.1 167.5 122.9 278.5 23.3 269.3 259.3 249.3 203.9 158.5 113.2
57 292.0 21.5 292.0 292.0 292.0 261.6 216.7 171.8 276.1 23.3 273.6 273.6 273.6 253.4 207.3 161.1
77 341.5 21.9 237.9 172.1 106.3 - - - 314.9 23.6 232.7 163.8 94.9 - - -
72 325.7 21.7 265.7 215.2 164.7 114.2 - - 301.9 23.4 254.9 205.0 155.2 105.3 - -
10000 67 309.8 21.6 293.4 258.3 223.1 173.0 122.9 - 288.9 23.4 277.1 246.3 215.4 164.5 113.5 -
62 307.6 21.6 296.9 289.2 281.5 231.8 182.1 132.3 288.1 23.4 279.5 277.6 275.7 223.7 171.6 119.5
57 305.4 21.6 300.3 300.3 300.3 290.5 241.2 191.9 287.4 23.4 281.9 281.9 281.9 281.9 229.7 176.5
72 333.9 21.8 286.0 229.0 172.1 115.2 - - 310.1 23.5 273.6 217.7 161.8 105.8 - -
67 323.7 21.7 306.9 273.0 239.2 183.3 127.5 - 301.8 23.5 289.3 260.6 232.0 174.6 117.3 -
11250
62 321.3 21.7 307.7 307.0 306.2 251.4 196.6 141.8 300.2 23.5 289.7 289.7 289.7 243.4 184.7 125.9
57 318.9 21.7 308.6 308.6 308.6 308.6 265.8 212.0 298.6 23.5 290.2 290.2 290.2 290.2 252.0 191.9
72 342.2 21.9 306.2 242.9 179.6 116.2 - - 318.3 23.6 292.4 230.4 168.4 106.3 - -
67 337.5 21.8 320.3 287.8 255.3 193.7 132.0 - 314.6 23.6 300.5 274.9 248.5 184.7 121.0 -
12500
62 335.0 21.8 321.1 321.1 321.1 271.1 211.2 151.3 312.2 23.6 301.5 301.5 301.5 263.2 197.7 132.3
57 332.4 21.8 321.6 321.6 321.6 321.6 290.3 232.1 309.8 23.6 302.2 302.2 302.2 302.2 274.4 207.3

Johnson Controls Ducted Systems 39


505429-JTG-NN-1222

J25YC/J25NC (Continued)
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 274.7 25.1 156.6 128.3 100.0 - - - 245.2 26.8 156.7 125.9 95.0 - - -
72 253.5 24.9 192.5 160.5 128.5 96.5 - - 229.8 26.6 186.4 154.0 121.6 89.2 - -
6250
67 239.5 24.8 228.4 192.7 157.0 126.2 95.5 - 225.6 26.6 216.1 182.1 148.1 118.4 88.6 -
62 237.3 24.8 233.4 209.4 185.5 156.0 126.4 96.9 222.7 26.6 217.9 196.3 174.6 147.6 120.5 93.4
77 279.2 25.2 180.2 137.4 94.5 - - - 250.6 26.9 178.5 133.0 87.4 - - -
72 261.7 25.0 209.7 172.0 134.2 96.5 - - 238.0 26.8 202.0 164.2 126.4 88.6 - -
7500 67 253.6 25.0 239.2 206.6 173.9 136.2 98.4 - 237.7 26.7 225.5 195.5 165.4 128.1 90.7 -
62 252.5 25.0 243.0 228.3 213.6 175.8 138.0 100.2 237.5 26.7 226.9 215.7 204.5 167.5 130.5 93.6
57 251.3 25.0 246.8 246.8 246.8 215.5 177.6 139.8 236.9 26.7 228.2 228.2 228.2 206.9 170.4 133.9
77 283.7 25.2 203.8 146.4 89.0 - - - 256.1 26.9 200.4 140.1 79.8 - - -
72 269.9 25.1 226.9 183.4 140.0 96.5 - - 246.1 26.7 217.7 174.5 131.3 88.1 - -
8750 67 262.5 25.0 250.0 220.4 190.9 146.1 101.3 - 244.4 26.7 235.0 208.9 182.8 137.8 92.8 -
62 260.8 25.0 252.6 247.2 241.8 195.7 149.6 103.5 243.1 26.6 235.8 235.1 234.3 187.5 140.6 93.8
57 260.3 25.0 255.1 255.1 255.1 245.3 197.9 150.4 242.8 26.6 236.7 236.7 236.7 236.7 188.5 139.8
77 288.2 25.2 227.4 155.5 83.6 - - - 261.5 26.9 222.2 147.2 72.2 - - -
72 278.1 25.1 244.1 194.9 145.7 96.5 - - 254.3 26.8 233.4 184.8 136.2 87.6 - -
10000 67 270.5 25.1 260.8 234.3 207.8 156.0 104.2 - 251.2 26.7 244.5 222.3 200.2 147.5 94.8 -
62 269.3 25.1 262.2 262.2 262.2 215.5 161.1 106.7 249.1 26.7 244.8 244.8 244.8 207.4 150.7 93.9
57 268.5 25.1 263.5 263.5 263.5 263.5 218.1 161.1 247.9 26..7 245.1 245.1 245.1 245.1 206.5 145.7
72 286.3 25.2 261.3 206.4 151.4 96.4 - - 262.5 27.0 249.0 195.0 141.0 87.0 - -
67 279.9 25.2 271.6 248.2 224.7 165.9 107.1 - 259.9 27.0 254.0 235.8 217.5 157.2 96.9 -
11250
62 279.1 25.2 271.8 271.8 271.8 235.4 172.7 110.0 258.6 27.0 254.3 254.3 254.3 227.4 160.7 94.1
57 278.2 25.2 271.9 271.9 271.9 271.9 238.3 171.8 257.9 26.9 255.0 255.0 255.0 255.0 224.6 151.6
72 294.5 25.3 278.5 217.8 157.1 96.4 - - 270.6 27.0 263.0 205.3 145.9 86.5 - -
67 291.8 25.3 282.4 262.1 241.7 175.8 110.0 - 268.9 27.0 263.5 249.2 234.9 166.9 99.0 -
12500
62 289.5 25.3 283.3 283.3 283.3 255.2 184.3 113.3 266.8 26.9 263.9 263.9 263.9 247.3 170.8 94.3
57 287.2 25.2 284.5 284.5 284.5 284.5 258.5 182.4 264.6 26.9 264.0 264.0 264.0 264.0 242.6 157.6
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

40 Johnson Controls Ducted Systems


505429-JTG-NN-1222

Condenser only cooling capacities

Condenser only ratings


Suction press. Temperature of air on condenser coil °F
and
Model 65 75 85 95 105 115
corresponding temp.
PSIG °F MBH KW EER MBH KW EER MBH KW EER MBH KW EER MBH KW EER MBH KW EER
108 35 78 4.8 16.1 75 5.3 14.2 72 5.8 12.4 68 6.5 10.3 61 7.6 8.1 55 8.6 6.4
120 40 88 5 17.6 84 5.5 15.5 81 5.9 13.6 76 6.7 11.4 70 7.7 9.1 64 8.7 7.3
J07YE 131 45 98 5.1 19.1 94 5.6 16.7 89 6.1 14.7 85 6.8 12.4 79 7.8 10 72 8.9 8.2
143 50 108 5.3 20.5 103 5.8 17.8 98 6.2 15.7 93 6.9 13.4 87 8 10.9 81 9 9
157 55 118 5.4 21.8 112 5.9 18.9 107 6.4 16.7 102 7.1 14.4 96 8.1 11.8 90 9.2 9.8
108 35 113 6.1 18.4 105 6.8 15.3 97 7.5 12.8 89 8.3 10.7 81 9.0 9.0 65 9.7 6.7
120 40 124 6.2 19.9 116 7.0 16.7 108 7.7 14.1 101 8.4 11.9 93 9.2 10.2 78 9.9 7.9
J10YC 131 45 135 6.3 21.3 127 7.1 17.9 120 7.9 15.3 112 8.6 13.0 106 9.4 11.3 92 10.1 9.1
143 50 146 6.5 22.6 139 7.2 19.2 131 8.0 16.4 124 8.8 14.1 119 9.6 12.4 106 10.3 10.2
157 55 157 6.6 23.9 150 7.4 20.4 143 8.2 17.5 136 9.0 15.2 131 9.8 13.4 119 10.6 11.3
108 35 102 5.6 18.2 91 6.4 14.2 84 7.1 11.8 79 7.9 10.0 69 9.0 7.7 60 10.0 6.0
120 40 113 5.7 19.8 104 6.5 16.0 98 7.3 13.4 90 8.1 11.1 80 9.1 8.8 72 10.2 7.1
J10YD 131 45 130 5.9 22.0 120 6.6 18.2 112 7.4 15.1 102 8.2 12.4 91 9.3 9.8 85 10.4 8.2
143 50 143 6.0 23.8 136 6.7 20.3 125 7.5 16.7 115 8.4 13.7 103 9.4 11.0 97 10.6 9.2
157 55 160 6.2 25.8 151 6.8 22.2 140 7.6 18.4 127 8.6 14.8 115 9.6 12.0 109 10.9 10.0
108 35 140 6.9 20.1 130 8.1 16.0 120 9.3 12.9 111 10.5 10.6 108 12.1 8.9 106 13.8 7.7
120 40 154 7.3 21.2 144 8.4 17.1 134 9.6 14.0 124 10.7 11.6 120 12.3 9.7 115 14.0 8.3
J12YC 131 45 169 7.6 22.3 159 8.7 18.2 148 9.8 15.0 137 11.0 12.5 131 12.5 10.4 125 14.1 8.8
143 50 184 7.9 23.2 173 9.0 19.2 161 10.1 16.0 150 11.2 13.4 142 12.7 11.2 134 14.3 9.4
157 55 199 8.3 24.1 187 9.3 20.1 175 10.4 16.9 163 11.4 14.2 153 12.9 11.8 144 14.5 9.9
108 35 137 6.5 20.9 129 8.1 16.0 121 9.6 12.6 113 11.1 10.2 103 13.7 7.5 92 14.0 6.6
120 40 149 6.8 22.0 141 8.3 17.1 133 9.7 13.7 126 11.2 11.2 115 13.6 8.5 105 14.2 7.4
J12YD 131 45 162 7.1 22.9 154 8.5 18.2 146 9.9 14.8 138 11.3 12.3 128 13.5 9.4 118 14.5 8.1
143 50 175 7.3 23.8 167 8.7 19.2 158 10.0 15.8 150 11.3 13.3 140 13.5 10.4 130 14.7 8.9
157 55 188 7.6 24.6 179 8.9 20.2 171 10.1 16.9 163 11.4 14.3 153 13.4 11.4 143 15.0 9.6
108 35 169 9.7 17.4 153 10.8 14.3 135 11.5 11.7 125 12.7 9.8 116 14.5 8.0 104 16.0 6.5
120 40 184 10.1 18.2 170 11.0 15.4 154 11.9 13.0 142 13.0 10.9 133 14.8 9.0 121 16.4 7.4
J15YC 131 45 198 10.4 19.1 186 11.3 16.4 172 12.2 14.1 160 13.4 12.0 149 15.1 9.9 137 16.7 8.2
143 50 213 10.7 19.8 203 11.6 17.5 191 12.6 15.2 178 13.7 13.0 166 15.4 10.7 153 17.0 9.0
157 55 227 11.0 20.6 219 11.9 18.4 210 12.9 16.2 196 14.0 14.0 182 15.7 11.6 169 17.3 9.8
108 35 160 10.1 15.9 149 11.0 13.6 141 11.6 12.2 136 12.8 10.6 127 14.5 8.8 121 16.3 7.4
120 40 179 10.2 17.6 168 11.2 15.0 158 11.9 13.3 151 13.1 11.5 141 14.8 9.5 133 16.6 8.0
J15YD 131 45 199 10.3 19.2 186 11.3 16.5 175 12.2 14.4 166 13.4 12.3 154 15.1 10.2 145 16.8 8.6
143 50 218 10.5 20.8 205 11.5 17.8 192 12.5 15.4 180 13.8 13.1 168 15.4 10.9 157 17.1 9.2
157 55 238 10.6 22.4 224 11.7 19.2 209 12.8 16.4 195 14.1 13.9 181 15.7 11.5 169 17.4 9.7
108 35 201 12.7 15.9 195 13.9 14.0 188 15.1 12.4 182 16.2 11.2 176 17.1 10.3 164 18.0 9.1
120 40 223 12.9 17.3 217 14.0 15.5 210 15.2 13.9 204 16.3 12.5 197 17.2 11.5 185 18.2 10.2
J20YC 131 45 245 13.1 18.8 239 14.1 16.9 232 15.2 15.2 225 16.3 13.8 219 17.3 12.6 206 18.4 11.2
143 50 268 13.3 20.2 261 14.3 18.3 254 15.3 16.6 247 16.4 15.0 240 17.5 13.7 226 18.6 12.2
157 55 290 13.5 21.5 283 14.4 19.7 276 15.3 18.0 268 16.4 16.4 261 17.6 14.8 247 18.9 13.1
108 35 210 12.4 17.0 196 13.6 14.3 184 15.1 12.2 173 16.7 10.4 157 18.9 8.3 137 21.2 6.5
120 40 237 12.7 18.6 221 14.0 15.8 208 15.4 13.5 195 17.0 11.5 179 19.2 9.4 161 21.4 7.5
J20YD 131 45 264 13.1 20.1 247 14.3 17.3 231 15.7 14.8 217 17.3 12.6 201 19.5 10.3 184 21.7 8.5
143 50 291 13.5 21.6 273 14.7 18.6 255 15.9 16.0 239 17.6 13.6 223 19.8 11.3 207 22.0 9.4
157 55 317 13.8 22.9 299 15.0 19.9 279 16.2 17.2 261 17.9 14.6 245 20.1 12.2 230 22.3 10.4
108 35 270 17.0 15.9 240 18.3 13.1 211 19.5 10.8 197 22.0 9.0 190 24.5 7.8 185 26.5 7.0
120 40 308 17.4 17.7 275 19.0 14.5 250 20.2 12.4 231 22.7 10.2 218 25.1 8.7 206 27.5 7.5
J25YC 131 45 344 18.1 19.0 317 19.8 16.0 285 21.0 13.6 267 23.1 11.6 247 25.9 9.5 233 28.3 8.2
143 50 382 19.5 19.6 353 20.4 17.3 324 21.8 14.9 301 23.8 12.6 277 26.5 10.5 256 29.0 8.8
157 55 420 20.8 20.2 390 21.0 18.6 360 22.5 16.0 336 24.3 13.8 308 27.2 11.3 281 30.0 9.4

Johnson Controls Ducted Systems 41


505429-JTG-NN-1222

Heat pump and air handling cooling capacities

J07PE/J07NL cooling capacities


Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 107.5 5.3 54.6 46.1 37.6 - - - 102.0 5.9 52.2 43.7 35.3 - - -
72 96.9 5.2 65.0 55.6 46.2 36.8 - - 91.9 5.8 63.0 53.6 44.2 34.7 - -
1875
67 86.3 5.1 75.4 65.1 54.8 45.9 36.9 - 81.8 5.8 73.9 63.5 53.0 44.0 35.0 -
62 83.0 5.0 83.0 73.5 63.4 53.6 46.5 38.0 78.7 5.7 78.7 71.4 61.9 52.6 44.7 36.2
77 108.1 5.3 60.9 49.5 38.0 - - - 102.5 5.9 59.5 47.8 36.0 - - -
72 99.1 5.2 71.3 60.1 48.9 37.7 - - 94.1 5.8 69.4 58.2 47.0 35.7 - -
2250 67 90.1 5.1 81.6 70.7 59.8 48.9 38.0 - 85.7 5.8 79.2 68.5 57.9 47.0 36.1 -
62 87.7 5.1 87.7 79.2 70.7 59.0 49.5 38.9 83.3 5.7 83.3 76.7 68.8 57.7 47.8 37.3
57 85.3 5.0 85.3 85.3 81.6 71.3 61.0 50.6 80.9 5.7 80.9 80.9 79.7 69.5 59.4 49.2
77 108.6 5.3 67.3 52.8 38.4 - - - 102.9 5.9 66.8 51.8 36.8 - - -
72 101.3 5.2 77.5 64.5 51.6 38.6 - - 96.2 5.8 75.7 62.7 49.7 36.8 - -
2625 67 93.9 5.2 87.7 76.2 64.8 52.0 39.1 - 89.6 5.8 84.5 73.6 62.7 50.0 37.3 -
62 92.3 5.1 91.8 84.9 78.0 64.5 52.5 39.8 87.8 5.8 87.8 82.0 75.7 62.9 50.8 38.3
57 90.7 5.1 90.7 90.7 88.9 78.6 66.0 53.3 86.1 5.7 86.1 86.1 86.1 76.5 64.3 52.1
77 109.2 5.3 73.6 56.1 38.7 - - - 103.4 5.9 74.1 55.8 37.5 - - -
72 103.5 5.2 83.7 69.0 54.3 39.6 - - 98.4 5.9 82.0 67.3 52.5 37.8 - -
3000 67 97.8 5.2 93.8 81.8 69.8 55.0 40.2 - 93.4 5.8 89.8 78.7 67.6 53.0 38.5 -
62 97.0 5.2 96.0 90.7 85.3 69.9 55.6 40.7 92.4 5.8 92.0 87.3 82.6 68.0 53.8 39.4
57 96.2 5.1 96.2 96.2 96.2 85.9 70.9 56.0 91.3 5.8 91.3 91.3 91.3 83.4 69.2 55.0
72 105.7 5.2 89.9 73.4 56.9 40.5 - - 100.6 5.9 88.3 71.8 55.3 38.8 - -
67 101.6 5.2 99.9 87.4 74.8 58.0 41.3 - 97.3 5.8 95.1 83.8 72.4 56.0 39.6 -
3375
62 101.6 5.2 100.1 96.4 92.7 75.4 58.6 41.6 96.9 5.8 95.7 92.6 89.5 73.1 56.9 40.5
57 101.7 5.2 99.3 99.3 99.3 93.2 75.9 58.6 96.5 5.8 95.7 95.7 95.7 90.4 74.1 57.9
72 107.9 5.3 96.1 77.9 59.6 41.4 - - 102.8 5.9 94.6 76.4 58.1 39.9 - -
67 105.4 5.2 105.4 92.9 79.8 61.1 42.4 - 101.2 5.8 100.4 88.9 77.3 59.0 40.8 -
3750
62 106.3 5.2 104.3 102.1 100.0 80.8 61.6 42.5 101.5 5.9 99.4 97.9 96.5 78.2 59.9 41.6
57 107.1 5.2 102.5 102.5 102.5 100.5 80.9 61.3 101.7 5.9 98.3 98.3 98.3 97.3 79.1 60.8
95°F 105°F
77 96.4 6.5 49.7 41.3 33.0 - - - 89.2 7.3 48.3 39.7 31.2 - - -
72 86.8 6.4 61.1 51.6 42.1 32.6 - - 80.6 7.2 59.2 49.8 40.3 30.9 - -
1875
67 77.2 6.4 72.4 61.8 51.2 42.1 33.1 - 72.0 7.1 70.2 59.8 49.5 40.3 31.1 -
62 74.4 6.3 74.4 69.2 60.3 51.7 43.0 34.3 71.6 7.1 71.6 66.1 58.6 49.7 40.7 31.7
77 96.8 6.5 58.0 46.1 34.1 - - - 89.8 7.3 56.0 43.9 31.7 - - -
72 89.0 6.5 67.5 56.2 44.9 33.8 - - 82.9 7.2 65.0 54.0 42.9 31.8 - -
2250 67 81.2 6.4 76.9 66.4 55.9 45.1 34.3 - 76.0 7.2 74.0 64.0 54.0 43.1 32.3 -
62 78.9 6.4 78.9 74.1 66.8 56.4 46.0 35.6 75.6 7.1 75.6 70.9 65.2 54.5 43.8 33.1
57 76.6 6.3 76.6 76.6 76.6 67.8 57.8 47.8 75.1 7.1 75.1 75.1 75.1 65.8 55.4 44.9
77 97.2 6.5 66.4 50.8 35.2 - - - 90.4 7.3 63.8 48.0 32.2 - - -
72 91.2 6.5 73.9 60.9 47.9 34.9 - - 85.2 7.2 70.8 58.1 45.4 32.7 - -
2625 67 85.2 6.4 81.4 71.0 60.6 48.1 35.5 - 79.9 7.2 77.9 68.2 58.6 46.0 33.4 -
62 83.3 6.4 83.3 79.0 73.4 61.2 49.1 36.9 79.6 7.2 79.6 75.8 71.7 59.3 46.9 34.5
57 81.5 6.4 81.5 81.5 81.5 74.4 62.6 50.9 79.2 7.1 79.2 79.2 79.2 72.6 60.4 48.1
77 97.6 6.5 74.7 55.5 36.3 - - - 91.0 7.2 71.5 52.1 32.7 - - -
72 93.4 6.5 80.3 65.6 50.8 36.1 - - 87.4 7.2 76.6 62.3 47.9 33.6 - -
3000 67 89.1 6.4 85.9 75.6 65.3 51.0 36.7 - 83.8 7.2 81.7 72.4 63.1 48.9 34.6 -
62 87.8 6.4 87.8 83.9 79.9 66.0 52.1 38.2 83.6 7.2 82.9 80.6 78.3 64.1 50.0 35.9
57 86.5 6.4 86.5 86.5 86.5 81.0 67.5 54.0 83.3 7.2 83.3 83.3 83.3 79.4 65.4 51.3
72 95.5 6.5 86.7 70.2 53.7 37.2 - - 89.7 7.2 82.4 66.4 50.5 34.5 - -
67 93.1 6.5 90.4 80.2 70.1 54.0 37.9 - 87.8 7.2 85.6 76.6 67.6 51.7 35.8 -
3375
62 92.2 6.4 91.2 88.8 86.4 70.8 55.1 39.5 87.6 7.2 86.0 85.4 84.8 69.0 53.1 37.2
57 91.4 6.4 91.4 91.4 91.4 87.5 72.3 57.1 87.4 7.2 86.5 86.5 86.5 86.2 70.4 54.6
72 97.7 6.5 93.1 74.9 56.6 38.4 - - 92.0 7.2 88.2 70.6 53.0 35.4 - -
67 97.1 6.5 94.8 84.8 74.8 57.0 39.1 - 91.7 7.2 89.4 80.8 72.2 54.6 37.0 -
3750
62 96.7 6.5 94.5 93.7 92.9 75.5 58.2 40.8 91.6 7.2 89.2 89.2 89.2 73.8 56.2 38.6
57 96.3 6.5 94.1 94.1 94.1 94.1 77.2 60.3 91.4 7.2 88.9 88.9 88.9 88.9 75.4 57.8

42 Johnson Controls Ducted Systems


505429-JTG-NN-1222

J07PE/J07NL cooling capacities (Continued)


Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 81.9 8.1 46.9 38.1 29.4 - - - 74.6 8.9 45.5 36.6 27.6 - - -
72 74.3 8.0 57.4 48.0 38.6 29.2 - - 68.1 8.8 55.6 46.2 36.8 27.5 - -
1875
67 66.8 7.9 66.8 57.9 47.8 38.4 29.1 - 61.6 8.6 61.6 55.9 46.0 36.6 27.1 -
62 68.7 7.9 68.7 62.9 56.9 47.7 38.4 29.2 65.8 8.7 64.2 59.7 55.3 45.7 36.2 26.6
77 82.7 8.1 54.0 41.7 29.4 - - - 75.7 8.8 52.0 39.5 27.0 - - -
72 76.7 8.0 62.6 51.7 40.7 29.8 - - 70.6 8.7 60.2 49.4 38.6 27.8 - -
2250 67 70.7 7.9 70.7 61.7 52.1 41.2 30.2 - 65.5 8.7 65.5 59.3 50.2 39.2 28.2 -
62 72.2 7.9 71.9 67.7 63.5 52.6 41.6 30.6 68.9 8.7 67.1 64.5 61.9 50.6 39.4 28.1
57 73.7 7.9 72.5 72.5 72.5 63.9 52.9 41.9 72.2 8.7 65.8 65.8 65.8 62.0 50.5 39.0
77 83.6 8.0 61.1 45.2 29.3 - - - 76.8 8.8 58.5 42.4 26.3 - - -
72 79.1 8.0 67.7 55.3 42.9 30.5 - - 73.1 8.7 64.7 52.5 40.4 28.2 - -
2625 67 74.7 7.9 74.4 65.4 56.5 43.9 31.4 - 69.4 8.7 69.4 62.7 54.4 41.9 29.3 -
62 75.8 7.9 74.9 72.5 70.1 57.4 44.7 32.1 72.0 8.7 70.0 69.2 68.5 55.5 42.6 29.6
57 76.9 7.9 75.3 75.3 75.3 70.9 58.1 45.3 74.6 8.7 69.0 69.0 69.0 69.0 55.8 42.5
77 84.5 8.0 68.2 48.7 29.2 - - - 77.9 8.8 65.0 45.3 25.7 - - -
72 81.5 8.0 72.9 59.0 45.0 31.1 - - 75.6 8.7 69.2 55.7 42.2 28.6 - -
3000 67 78.6 7.9 77.6 69.2 60.9 46.7 32.5 - 73.3 8.7 73.3 66.0 58.6 44.5 30.5 -
62 79.3 8.0 77.9 77.3 76.7 62.3 47.9 33.5 75.1 8.7 72.8 72.8 72.8 60.5 45.8 31.2
57 80.1 8.0 78.2 78.2 78.2 77.9 63.3 48.6 76.9 8.7 72.2 72.2 72.2 72.2 61.2 46.0
72 83.9 8.0 78.1 62.6 47.2 31.8 - - 78.1 8.7 73.7 58.8 43.9 29.0 - -
67 82.5 8.0 80.8 73.0 65.2 49.5 33.7 - 77.2 8.7 76.0 69.4 62.8 47.2 31.6 -
3375
62 82.9 8.0 80.9 80.9 80.9 67.2 51.1 35.0 78.2 8.7 75.7 75.7 75.7 65.4 49.0 32.7
57 83.3 8.0 81.0 81.0 81.0 81.0 68.4 52.0 79.3 8.8 75.4 75.4 75.4 75.4 66.5 49.4
72 86.3 8.0 83.2 66.3 49.3 32.4 - - 80.6 8.7 78.3 62.0 45.7 29.4 - -
67 86.4 8.0 84.0 76.8 69.6 52.2 34.8 - 81.0 8.7 78.5 72.8 67.0 49.9 32.7 -
3750
62 86.5 8.0 83.9 83.9 83.9 72.0 54.2 36.4 81.3 8.8 78.6 78.6 78.6 70.3 52.2 34.2
57 86.5 8.0 83.8 83.8 83.8 83.8 73.6 55.3 81.6 8.8 78.6 78.6 78.6 78.6 71.8 52.9
1 These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
2 These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

Johnson Controls Ducted Systems 43


505429-JTG-NN-1222

J10PC/J10NL
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 144.6 7.3 79.0 64.2 49.3 - - - 138.9 8.3 77.2 58.3 39.3 - - -
72 133.6 7.2 95.0 80.2 65.5 50.7 - - 127.7 8.1 92.9 76.1 59.3 42.5 - -
3000 67 122.5 7.1 111.0 96.3 81.7 66.7 51.9 - 116.6 8.0 108.7 94.0 79.3 64.3 49.4 -
62 118.6 7.0 118.6 109.0 97.8 80.9 67.8 52.8 113.8 8.0 113.8 107.4 99.2 85.3 73.2 60.2
57 114.8 7.0 114.8 114.8 114.0 98.9 83.7 68.6 111.1 7.9 111.1 111.1 111.1 108.1 97.0 86.0
77 147.2 7.3 87.7 68.5 49.3 - - - 140.0 8.3 86.4 63.9 41.4 - - -
72 136.5 7.2 103.2 86.0 68.7 51.4 - - 130.2 8.2 101.1 82.3 63.5 44.8 - -
3500 67 125.8 7.1 118.7 103.4 88.0 70.4 53.0 - 120.4 8.0 115.8 100.7 85.7 68.1 50.6 -
62 123.8 7.1 123.8 116.5 107.4 88.2 71.9 54.2 118.9 8.0 118.9 114.4 107.9 90.9 75.3 59.0
57 121.8 7.0 121.8 121.8 121.4 108.8 90.8 72.9 117.5 8.0 117.5 117.5 117.5 115.0 99.9 84.9
77 149.8 7.4 96.5 72.9 49.4 - - - 141.1 8.3 95.6 69.5 43.4 - - -
72 139.5 7.3 111.5 91.7 71.9 52.1 - - 132.7 8.2 109.3 88.5 67.8 47.0 - -
4000 67 129.2 7.2 126.4 110.4 94.4 74.2 54.2 - 124.2 8.1 122.9 107.5 92.1 72.0 51.8 -
62 129.0 7.1 129.0 124.0 116.9 95.5 76.0 55.6 124.1 8.1 124.1 121.4 116.5 96.4 77.3 57.8
57 128.9 7.1 128.9 128.9 128.9 118.6 97.9 77.2 123.9 8.1 123.9 123.9 123.9 121.9 102.9 83.9
72 142.4 7.3 119.7 97.4 75.0 52.7 - - 135.1 8.2 117.4 94.7 72.0 49.3 - -
67 132.5 7.2 132.5 117.4 100.7 78.0 55.3 - 128.0 8.1 128.0 114.3 98.6 75.8 53.0 -
4500
62 134.2 7.2 134.2 131.5 126.4 102.8 80.2 57.0 129.2 8.1 129.2 128.3 125.1 102.0 79.4 56.5
57 135.9 7.2 135.6 135.6 135.6 128.5 105.0 81.5 130.4 8.1 130.4 130.4 130.4 128.7 105.8 82.8
72 145.4 7.3 127.9 103.1 78.2 53.4 - - 137.6 8.2 125.6 100.9 76.3 51.6 - -
67 135.8 7.2 135.8 124.5 107.1 81.7 56.4 - 131.8 8.2 131.8 121.1 105.0 79.6 54.2 -
5000
62 139.4 7.3 139.4 139.0 135.9 110.1 84.3 58.5 134.3 8.2 134.3 134.3 133.8 107.6 81.5 55.3
57 143.0 7.3 142.4 142.4 142.4 138.4 112.1 85.8 136.8 8.2 136.7 136.7 136.7 135.6 108.7 81.8
95°F 105°F
77 133.2 9.2 75.4 52.4 29.3 - - - 123.8 10.5 73.7 53.1 32.6 - - -
72 121.9 9.1 90.9 72.0 53.1 34.2 - - 113.9 10.4 88.3 70.8 53.4 35.9 - -
3000 67 110.7 8.9 106.4 91.6 76.8 61.9 47.0 - 104.0 10.3 103.0 88.5 74.1 59.2 44.3 -
62 109.0 8.9 109.0 105.8 100.6 89.6 78.6 67.7 104.2 10.2 104.2 100.3 94.9 82.6 70.3 58.0
57 107.4 8.9 107.4 107.4 107.4 107.4 107.4 103.3 104.3 10.1 104.3 104.3 104.3 104.3 96.2 86.5
77 132.8 9.2 85.1 59.3 33.4 - - - 123.7 10.5 83.5 59.2 34.9 - - -
72 123.9 9.1 99.0 78.7 58.4 38.1 - - 116.0 10.4 96.0 76.8 57.7 38.5 - -
3500 67 114.9 9.0 112.9 98.1 83.4 65.8 48.2 - 108.2 10.3 108.2 94.5 80.5 62.9 45.4 -
62 114.1 9.0 114.1 112.2 108.4 93.5 78.6 63.8 108.6 10.2 108.6 106.9 103.3 87.4 71.5 55.6
57 113.2 8.9 113.2 113.2 113.2 113.2 109.1 96.9 109.0 10.2 109.0 109.0 109.0 109.0 97.6 83.4
77 132.5 9.2 94.8 66.1 37.5 - - - 123.6 10.5 93.3 65.2 37.1 - - -
72 125.9 9.1 107.1 85.4 63.7 42.0 - - 118.0 10.4 103.7 82.8 62.0 41.1 - -
4000 67 119.2 9.0 119.2 104.6 89.9 69.7 49.5 - 112.4 10.3 112.4 100.4 86.8 66.7 46.5 -
62 119.1 9.0 119.1 118.7 116.1 97.4 78.6 59.9 113.1 10.3 113.1 113.1 111.7 92.2 72.8 53.3
57 119.0 9.0 119.0 119.0 119.0 119.0 107.8 90.5 113.8 10.3 113.8 113.8 113.8 113.8 99.0 80.2
72 127.8 9.1 115.2 92.1 69.0 45.9 - - 120.0 10.4 111.3 88.8 66.3 43.8 - -
67 123.4 9.0 123.4 111.1 96.5 73.6 50.7 - 116.5 10.4 116.5 106.4 93.2 70.4 47.6 -
4500
62 124.1 9.1 124.1 124.1 123.9 101.3 78.6 56.0 117.5 10.4 117.5 117.5 117.5 97.1 74.0 51.0
57 124.8 9.1 124.8 124.8 124.8 124.8 106.5 84.1 118.6 10.4 118.6 118.6 118.6 118.6 100.4 77.1
72 129.8 9.1 123.3 98.8 74.3 49.8 - - 122.1 10.4 119.0 94.8 70.6 46.4 - -
67 127.7 9.1 127.7 117.6 103.0 77.5 52.0 - 120.7 10.4 120.7 112.3 99.6 74.1 48.7 -
5000
62 129.2 9.1 129.2 129.2 129.2 105.2 78.6 52.1 122.0 10.4 122.0 122.0 122.0 101.9 75.2 48.6
57 130.7 9.1 130.7 130.7 130.7 130.7 105.3 77.7 123.3 10.4 123.3 123.3 123.3 123.3 101.8 73.9

44 Johnson Controls Ducted Systems


505429-JTG-NN-1222

J10PC/J10NL (Continued)
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 114.5 11.8 72.0 53.9 35.9 - - - 105.2 13.1 70.2 54.7 39.1 - - -
72 106.0 11.7 85.7 69.7 53.6 37.6 - - 98.0 13.0 83.2 68.5 53.9 39.2 - -
3000 67 97.4 11.6 97.4 85.5 71.4 56.5 41.7 - 90.8 12.9 90.8 82.4 68.7 53.9 39.1 -
62 99.3 11.5 99.3 94.9 89.1 75.5 61.9 48.3 94.4 12.8 94.4 89.5 83.4 68.5 53.5 38.6
57 101.1 11.4 101.1 101.1 101.1 94.5 82.1 69.7 98.0 12.7 95.2 95.2 95.2 83.1 68.0 52.9
77 114.6 11.8 81.9 59.1 36.3 - - - 105.5 13.1 80.3 59.0 37.7 - - -
72 108.1 11.7 93.0 75.0 56.9 38.9 - - 100.2 13.0 90.0 73.1 56.2 39.3 - -
3500 67 101.5 11.6 101.5 90.8 77.6 60.1 42.6 - 94.8 12.9 94.8 87.2 74.7 57.2 39.8 -
62 103.2 11.5 103.2 101.5 98.2 81.3 64.4 47.5 97.7 12.8 97.7 96.2 93.1 75.2 57.3 39.3
57 104.9 11.5 104.9 104.9 104.9 102.5 86.1 69.8 100.7 12.8 98.9 98.9 98.9 93.1 74.7 56.3
77 114.8 11.8 91.8 64.3 36.7 - - - 105.9 13.1 90.4 63.4 36.4 - - -
72 110.2 11.7 100.2 80.2 60.2 40.2 - - 102.3 13.0 96.8 77.7 58.5 39.4 - -
4000 67 105.6 11.6 105.6 96.2 83.7 63.7 43.6 - 98.7 12.9 98.7 92.0 80.7 60.6 40.6 -
62 107.1 11.6 107.1 107.1 107.1 87.1 66.9 46.7 101.0 12.9 101.0 101.0 101.0 81.9 61.0 40.1
57 108.6 11.6 108.6 108.6 108.6 108.6 90.2 69.9 103.4 12.9 102.7 102.7 102.7 102.7 81.4 59.6
72 112.3 11.7 107.5 85.5 63.6 41.6 - - 104.5 13.0 103.7 82.2 60.8 39.4 - -
67 109.6 11.7 109.6 101.6 89.9 67.2 44.5 - 102.7 13.0 102.7 96.8 86.7 64.0 41.4 -
4500
62 111.0 11.7 111.0 111.0 111.0 92.8 69.4 45.9 104.4 13.0 104.4 104.4 104.4 88.6 64.7 40.8
57 112.3 11.6 112.3 112.3 112.3 112.3 94.2 70.0 106.0 12.9 106.0 106.0 106.0 106.0 88.1 63.0
72 114.3 11.7 114.3 90.8 66.9 42.9 - - 106.6 13.0 106.6 86.8 63.2 39.5 - -
67 113.7 11.7 113.7 106.9 96.1 70.8 45.4 - 106.7 13.0 106.7 101.6 92.7 67.4 42.1 -
5000
62 114.8 11.7 114.8 114.8 114.8 98.6 71.9 45.1 107.7 13.0 107.7 107.7 107.7 95.3 68.5 41.6
57 116.0 11.7 116.0 116.0 116.0 116.0 98.3 70.1 108.7 13.0 108.7 108.7 108.7 108.7 94.8 66.3
1 These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
2 These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

Johnson Controls Ducted Systems 45


505429-JTG-NN-1222

J15PC/J15NL
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 223.0 12.5 104.1 85.2 66.4 - - - 216.7 13.8 104.7 85.9 67.0 - - -
72 209.3 12.3 134.7 115.8 97.0 78.1 - - 200.9 13.6 133.0 114.1 95.2 76.3 - -
4500 67 195.7 12.1 165.2 146.4 127.6 108.7 89.9 - 185.0 13.4 161.2 142.3 123.4 104.5 85.7 -
62 176.7 11.8 176.7 176.7 152.0 133.2 114.3 95.5 169.4 13.0 169.4 169.4 151.2 132.4 113.5 94.6
57 179.6 11.8 179.6 179.6 159.1 140.3 121.4 102.6 173.1 13.1 173.1 173.1 154.4 135.5 116.7 97.8
77 229.0 12.6 113.8 93.3 71.8 - - - 221.4 13.9 114.8 93.3 71.7 - - -
72 215.0 12.4 147.9 126.3 104.8 83.3 - - 205.2 13.6 145.0 123.5 101.9 80.3 - -
5250 67 200.9 12.2 181.9 159.4 137.8 116.3 94.8 - 189.1 13.4 175.2 153.7 132.1 110.5 88.9 -
62 181.4 11.8 181.4 181.4 164.3 143.6 121.3 99.8 173.0 13.1 173.0 173.0 161.9 140.3 118.7 97.1
57 184.5 11.9 184.5 184.5 171.9 151.4 128.9 107.4 176.9 13.1 176.9 176.9 165.3 143.7 122.1 100.6
77 235.0 12.6 123.5 101.4 77.2 - - - 226.1 13.9 124.9 100.6 76.4 - - -
72 220.6 12.4 161.0 136.9 112.7 88.5 - - 209.6 13.7 157.1 132.8 108.6 84.3 - -
6000 67 206.2 12.2 198.5 172.3 148.1 123.9 99.8 - 193.1 13.4 189.3 165.0 140.8 116.5 92.2 -
62 186.2 11.9 186.2 186.2 176.7 154.1 128.3 104.1 176.7 13.1 176.7 176.7 172.5 148.2 124.0 99.7
57 189.3 11.9 189.3 189.3 184.8 162.6 136.4 112.2 180.6 13.2 180.6 180.6 176.1 151.8 127.6 103.3
72 223.2 12.5 170.5 144.3 118.1 91.9 - - 213.0 13.7 168.5 142.1 115.7 89.3 - -
67 208.6 12.3 204.8 181.5 155.3 129.1 102.9 - 196.2 13.5 194.3 176.4 150.0 123.6 97.3 -
6750
62 188.4 11.9 188.4 188.4 183.6 158.3 131.3 105.1 179.6 13.2 179.6 179.6 177.5 151.1 124.7 98.3
57 191.6 12.0 191.6 191.6 189.3 164.1 136.9 110.7 183.6 13.2 183.6 183.6 181.3 154.9 128.5 102.2
72 225.9 12.6 179.9 151.7 123.5 95.3 - - 216.4 13.8 179.9 151.4 122.9 94.4 - -
67 211.1 12.4 211.1 190.7 162.5 134.3 106.1 - 199.4 13.5 199.4 187.8 159.3 130.8 102.3 -
7500
62 190.6 12.0 190.6 190.6 190.6 162.4 134.2 106.0 182.5 13.2 182.5 182.5 182.5 154.0 125.5 97.0
57 193.8 12.1 193.8 193.8 193.8 165.6 137.4 109.2 186.5 13.3 186.5 186.5 186.5 158.0 129.5 101.0
95°F 105°F
77 210.5 15.1 105.4 86.5 67.6 - - - 192.8 16.7 98.9 80.0 61.1 - - -
72 192.4 14.9 131.3 112.4 93.4 74.5 - - 177.2 16.5 125.6 106.7 87.8 68.9 - -
4500 67 174.4 14.6 157.1 138.2 119.3 100.4 81.4 - 161.6 16.3 152.4 133.5 114.6 95.7 76.8 -
62 162.0 14.3 162.0 162.0 150.5 131.6 112.6 93.7 150.1 16.0 150.1 150.1 142.4 123.5 104.6 85.7
57 166.6 14.4 166.6 166.6 149.8 130.8 111.9 93.0 155.1 16.1 155.1 155.1 137.9 119.0 100.1 81.2
77 213.8 15.2 115.9 93.2 71.6 - - - 196.5 16.7 114.1 86.9 65.3 - - -
72 195.5 14.9 142.2 120.6 99.0 77.3 - - 180.6 16.5 137.1 115.5 93.8 72.2 - -
5250 67 177.2 14.6 168.6 148.0 126.3 104.7 83.1 - 164.7 16.3 160.1 144.1 122.4 100.8 79.2 -
62 164.7 14.4 164.7 164.7 159.4 136.9 116.1 94.5 153.0 16.1 153.0 153.0 152.2 130.1 108.9 87.3
57 169.2 14.4 169.2 169.2 158.6 136.0 115.3 93.7 158.1 16.1 158.1 158.1 147.3 125.2 104.1 82.4
77 217.2 15.2 126.3 99.9 75.6 - - - 200.2 16.8 129.3 93.8 69.4 - - -
72 198.6 14.9 153.1 128.8 104.5 80.1 - - 184.1 16.5 148.6 124.2 99.9 75.5 - -
6000 67 180.0 14.6 180.0 157.7 133.4 109.0 84.7 - 167.9 16.3 167.9 154.7 130.3 106.0 81.6 -
62 167.3 14.4 167.3 167.3 168.3 142.3 119.6 95.3 155.9 16.1 155.9 155.9 162.0 136.8 113.2 88.9
57 171.9 14.4 171.9 171.9 167.5 141.1 118.8 94.5 161.1 16.1 161.1 161.1 156.7 131.4 108.0 83.7
72 202.8 15.0 166.5 139.9 113.4 86.8 - - 187.4 16.6 160.8 134.3 107.7 81.1 - -
67 183.8 14.7 183.8 171.3 144.7 118.2 91.6 - 170.9 16.4 170.9 163.6 140.5 113.9 87.3 -
6750
62 170.8 14.4 170.8 170.8 171.3 143.9 118.2 91.6 158.7 16.1 158.7 158.7 161.7 134.7 108.6 82.0
57 175.6 14.5 175.6 175.6 173.3 145.8 120.2 93.6 164.0 16.2 164.0 164.0 161.8 134.7 108.6 82.1
72 207.0 15.0 179.8 151.0 122.2 93.5 - - 190.7 16.6 173.1 144.3 115.5 86.7 - -
67 187.6 14.7 187.6 184.9 156.1 127.3 98.5 - 173.9 16.4 173.9 172.5 150.7 121.9 93.1 -
7500
62 174.3 14.4 174.3 174.3 174.3 145.5 116.7 87.9 161.5 16.2 161.5 161.5 161.5 132.7 103.9 75.1
57 179.2 14.5 179.2 179.2 179.2 150.4 121.6 92.8 166.8 16.2 166.8 166.8 166.8 138.1 109.3 80.5

46 Johnson Controls Ducted Systems


505429-JTG-NN-1222

J15PC/J15NL
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 175.1 18.3 92.4 73.5 54.6 - - - 157.4 19.9 85.8 67.0 48.1 - - -
72 162.0 18.1 120.0 101.1 82.2 63.3 - - 146.7 19.8 114.3 95.5 76.6 57.8 - -
4500 67 148.8 18.0 147.6 128.7 109.8 91.0 72.1 - 136.1 19.6 136.1 124.0 105.1 86.3 67.4 -
62 138.1 17.8 138.1 138.1 134.4 115.5 96.6 77.7 126.2 19.5 126.2 126.2 126.2 107.5 88.6 69.7
57 143.6 17.8 143.6 143.6 126.1 107.2 88.3 69.4 132.1 19.6 132.1 132.1 114.2 95.4 76.5 57.6
77 179.2 18.3 112.3 80.6 58.9 - - - 161.8 19.9 110.6 74.3 52.6 - - -
72 165.7 18.1 132.0 110.4 88.7 67.1 - - 150.8 19.8 126.9 105.3 83.6 62.0 - -
5250 67 152.3 18.0 151.7 140.2 118.6 96.9 75.3 - 139.9 19.6 139.9 136.3 114.7 93.0 71.4 -
62 141.3 17.8 141.3 141.3 145.0 123.4 101.7 80.1 129.7 19.5 129.7 129.7 129.7 116.6 94.6 72.9
57 146.9 17.8 146.9 146.9 136.1 114.4 92.8 71.1 135.7 19.6 135.7 135.7 124.8 103.6 81.5 59.9
77 183.2 18.3 132.3 87.6 63.3 - - - 166.2 19.9 135.3 81.5 57.1 - - -
72 169.5 18.1 144.0 119.6 95.3 70.9 - - 154.9 19.8 139.5 115.1 90.6 66.2 - -
6000 67 155.8 18.0 155.8 151.6 127.3 102.9 78.5 - 143.6 19.6 143.6 143.6 124.2 99.8 75.4 -
62 144.5 17.8 144.5 144.5 155.7 131.3 106.9 82.5 133.2 19.5 133.2 133.2 133.2 125.8 100.5 76.1
57 150.2 17.9 150.2 150.2 146.0 121.6 97.3 72.9 139.4 19.6 139.4 139.4 135.3 111.9 86.5 62.1
72 171.9 18.2 155.2 128.6 102.0 75.4 - - 156.4 19.8 149.5 122.9 96.3 69.7 - -
67 158.0 18.0 158.0 155.9 136.3 109.7 83.1 - 145.1 19.7 145.1 145.1 132.0 105.4 78.8 -
6750
62 146.6 17.8 146.6 146.6 152.1 125.6 99.0 72.4 134.5 19.5 134.5 134.5 134.5 116.4 89.4 62.7
57 152.4 17.9 152.4 152.4 150.3 123.7 97.1 70.5 140.8 19.6 140.8 140.8 138.8 112.7 85.5 58.9
72 174.3 18.2 166.3 137.5 108.8 80.0 - - 158.0 19.9 158.0 130.8 102.0 73.2 - -
67 160.2 18.1 160.2 160.2 145.3 116.5 87.7 - 146.5 19.8 146.5 146.5 139.9 111.1 82.3 -
7500
62 148.6 17.9 148.6 148.6 148.6 119.8 91.0 62.3 135.8 19.6 135.8 135.8 135.8 107.0 78.2 49.4
57 154.5 18.0 154.5 154.5 154.5 125.7 96.9 68.1 142.2 19.7 142.2 142.2 142.2 113.4 84.6 55.8
1 These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
2 These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor

Johnson Controls Ducted Systems 47


505429-JTG-NN-1222

J15PD/J15NM
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 231.4 12.4 111.6 93.0 74.5 - - - 219.9 13.7 106.4 87.9 69.5 - - -
72 215.6 12.0 142.9 124.4 105.8 87.2 - - 204.0 13.4 138.2 119.7 101.2 82.8 - -
4500 67 199.7 11.7 174.3 155.7 137.2 118.6 100.0 - 188.1 13.1 169.9 151.4 133.0 114.5 96.0 -
62 183.7 11.4 183.7 183.7 170.7 152.1 133.6 115.0 174.3 12.8 174.3 174.3 163.8 145.3 126.9 108.4
57 184.6 11.4 184.6 184.6 173.2 154.6 136.1 117.5 175.3 12.8 175.3 175.3 164.8 146.3 127.8 109.4
77 233.6 12.4 117.3 98.2 76.9 - - - 222.0 13.7 114.1 92.9 71.7 - - -
72 217.6 12.1 151.9 130.6 109.3 88.0 - - 206.0 13.4 146.9 125.7 104.5 83.3 - -
5250 67 201.6 11.7 186.5 163.0 141.7 120.4 99.1 - 189.9 13.1 179.7 158.5 137.2 116.0 94.8 -
62 185.5 11.4 185.5 185.5 176.3 155.6 133.7 112.4 176.0 12.8 176.0 176.0 169.1 147.9 126.6 105.4
57 186.3 11.4 186.3 186.3 178.9 158.5 136.3 115.0 177.0 12.8 177.0 177.0 170.1 148.8 127.6 106.4
77 235.8 12.4 123.1 103.4 79.4 - - - 224.2 13.7 121.8 97.9 73.9 - - -
72 219.7 12.1 160.9 136.9 112.8 88.7 - - 208.0 13.4 155.6 131.7 107.7 83.8 - -
6000 67 203.5 11.7 198.8 170.3 146.2 122.2 98.1 - 191.8 13.1 189.4 165.5 141.5 117.6 93.6 -
62 187.2 11.4 187.2 187.2 182.0 159.2 133.8 109.8 177.7 12.9 177.7 177.7 174.3 150.4 126.4 102.5
57 188.0 11.4 188.0 188.0 184.6 162.4 136.5 112.4 178.7 12.9 178.7 178.7 175.4 151.4 127.5 103.5
72 222.5 12.1 171.1 144.6 118.1 91.7 - - 210.6 13.5 165.7 139.4 113.2 86.9 - -
67 206.2 11.8 203.8 179.6 153.2 126.7 100.2 - 194.2 13.2 193.0 174.9 148.6 122.4 96.1 -
6750
62 189.7 11.5 189.7 189.7 187.0 161.2 134.1 107.6 180.0 12.9 180.0 180.0 178.3 152.0 125.7 99.5
57 190.5 11.5 190.5 190.5 188.8 163.3 135.9 109.4 181.0 12.9 181.0 181.0 179.3 153.1 126.8 100.5
72 225.4 12.2 181.3 152.4 123.5 94.6 - - 213.3 13.6 175.8 147.2 118.6 90.0 - -
67 208.9 11.8 208.9 189.0 160.1 131.2 102.3 - 196.7 13.2 196.7 184.4 155.8 127.2 98.6 -
7500
62 192.1 11.5 192.1 192.1 192.1 163.2 134.3 105.5 182.2 13.0 182.2 182.2 182.2 153.6 125.0 96.4
57 193.0 11.5 193.0 193.0 193.0 164.1 135.2 106.3 183.3 13.0 183.3 183.3 183.3 154.7 126.1 97.5
95°F 105°F
77 208.3 15.1 101.3 82.9 64.5 - - - 192.0 17.0 96.4 77.9 59.4 - - -
72 192.4 14.8 133.4 115.0 96.6 78.3 - - 177.3 16.7 128.6 110.2 91.7 73.2 - -
4500 67 176.4 14.5 165.5 147.2 128.8 110.4 92.0 - 162.5 16.4 157.1 142.5 124.0 105.5 87.0 -
62 164.9 14.3 164.9 164.9 156.9 138.5 120.2 101.8 153.2 16.2 153.2 153.2 149.2 130.7 112.3 93.8
57 166.1 14.3 166.1 166.1 156.3 138.0 119.6 101.2 155.2 16.2 155.2 155.2 146.0 127.5 109.0 90.6
77 210.5 15.1 110.9 87.6 66.5 - - - 193.9 17.0 110.4 82.4 61.2 - - -
72 194.3 14.8 141.9 120.8 99.7 78.5 - - 179.0 16.7 136.8 115.7 94.5 73.4 - -
5250 67 178.2 14.5 172.8 153.9 132.8 111.7 90.6 - 164.1 16.4 161.4 149.0 127.8 106.6 85.5 -
62 166.5 14.3 166.5 166.5 161.8 140.1 119.6 98.5 154.7 16.2 154.7 154.7 154.2 132.7 111.9 90.7
57 167.8 14.3 167.8 167.8 161.2 139.2 119.0 97.9 156.8 16.2 156.8 156.8 150.5 128.9 108.2 87.0
77 212.6 15.1 120.6 92.3 68.5 - - - 195.8 17.0 124.4 86.9 63.1 - - -
72 196.3 14.8 150.3 126.5 102.7 78.8 - - 180.8 16.7 145.0 121.2 97.3 73.5 - -
6000 67 180.0 14.5 180.0 160.6 136.8 113.0 89.2 - 165.7 16.4 165.7 155.5 131.6 107.8 83.9 -
62 168.2 14.3 168.2 168.2 166.7 141.6 119.0 95.2 156.2 16.2 156.2 156.2 159.2 134.7 111.5 87.6
57 169.5 14.3 169.5 169.5 166.1 140.4 118.4 94.6 158.3 16.2 158.3 158.3 155.0 130.2 107.3 83.4
72 198.7 14.9 160.3 134.2 108.2 82.1 - - 183.0 16.8 155.6 129.3 103.0 76.7 - -
67 182.2 14.6 182.2 170.2 144.1 118.0 92.0 - 167.8 16.5 167.8 161.5 139.3 113.0 86.7 -
6750
62 170.3 14.3 170.3 170.3 169.5 142.8 117.4 91.3 158.2 16.2 158.2 158.2 159.7 133.0 107.1 80.8
57 171.6 14.4 171.6 171.6 169.9 142.9 117.7 91.6 160.3 16.3 160.3 160.3 158.6 131.9 106.0 79.7
72 201.2 14.9 170.3 142.0 113.6 85.3 - - 185.3 16.8 166.3 137.5 108.8 80.0 - -
67 184.5 14.6 184.5 179.8 151.4 123.1 94.8 - 169.9 16.5 169.9 167.5 147.1 118.3 89.6 -
7500
62 172.4 14.4 172.4 172.4 172.4 144.1 115.7 87.4 160.1 16.3 160.1 160.1 160.1 131.4 102.6 73.9
57 173.7 14.5 173.7 173.7 173.7 145.3 117.0 88.7 162.3 16.4 162.3 162.3 162.3 133.5 104.8 76.0

48 Johnson Controls Ducted Systems


505429-JTG-NN-1222

J15PD/J15NM (Continued)
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 175.7 18.9 91.5 72.9 54.3 - - - 159.4 20.8 86.6 67.9 49.2 - - -
72 162.2 18.6 123.9 105.3 86.8 68.2 - - 147.1 20.5 119.1 100.5 81.8 63.1 - -
4500 67 148.6 18.2 148.6 137.8 119.2 100.6 82.0 - 134.7 20.1 134.7 133.1 114.4 95.7 77.1 -
62 141.5 18.1 141.5 141.5 141.5 123.0 104.4 85.8 129.9 20.0 129.9 129.9 129.9 115.2 96.5 77.8
57 144.4 18.1 144.4 144.4 135.6 117.1 98.5 79.9 133.6 20.1 133.6 133.6 125.3 106.6 88.0 69.3
77 177.4 18.9 109.8 77.2 56.0 - - - 160.8 20.9 109.2 72.0 50.7 - - -
72 163.7 18.6 131.8 110.6 89.4 68.2 - - 148.4 20.5 126.8 105.5 84.3 63.0 - -
5250 67 150.0 18.3 150.0 144.0 122.8 101.6 80.4 - 135.9 20.1 135.9 135.9 117.8 96.5 75.3 -
62 142.9 18.1 142.9 142.9 146.6 125.4 104.2 82.9 131.0 20.0 131.0 131.0 131.0 118.0 96.4 75.2
57 145.8 18.1 145.8 145.8 139.8 118.5 97.3 76.1 134.8 20.1 134.8 134.8 129.1 108.2 86.5 65.2
77 179.0 18.9 128.1 81.5 57.6 - - - 162.3 20.9 131.9 76.1 52.2 - - -
72 165.2 18.6 139.8 115.9 92.0 68.2 - - 149.7 20.5 134.5 110.6 86.7 62.8 - -
6000 67 151.4 18.3 151.4 150.3 126.4 102.6 78.7 - 137.1 20.1 137.1 137.1 121.3 97.4 73.5 -
62 144.2 18.1 144.2 144.2 151.7 127.8 103.9 80.1 132.2 20.0 132.2 132.2 132.2 120.9 96.4 72.5
57 147.1 18.2 147.1 147.1 143.9 120.0 96.1 72.3 136.0 20.1 136.0 136.0 132.8 109.8 85.0 61.1
72 167.3 18.7 151.0 124.5 97.9 71.4 - - 151.6 20.6 146.3 119.6 92.8 66.1 - -
67 153.3 18.3 153.3 152.8 134.6 108.0 81.5 - 138.9 20.2 138.9 138.9 129.8 103.0 76.3 -
6750
62 146.0 18.1 146.0 146.0 149.8 123.2 96.7 70.2 133.9 20.0 133.9 133.9 133.9 113.5 86.4 59.6
57 149.0 18.2 149.0 149.0 147.4 120.9 94.3 67.8 137.7 20.1 137.7 137.7 136.1 109.9 82.6 55.9
72 169.4 18.7 162.2 133.0 103.9 74.7 - - 153.5 20.6 153.5 128.6 99.0 69.4 - -
67 155.3 18.4 155.3 155.3 142.7 113.5 84.3 - 140.7 20.3 140.7 140.7 138.3 108.7 79.1 -
7500
62 147.9 18.2 147.9 147.9 147.9 118.7 89.5 60.3 135.6 20.1 135.6 135.6 135.6 106.0 76.4 46.8
57 150.9 18.3 150.9 150.9 150.9 121.7 92.5 63.3 139.5 20.2 139.5 139.5 139.5 109.9 80.3 50.6
1 These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
2 These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

Johnson Controls Ducted Systems 49


505429-JTG-NN-1222

J20PD/J20NM
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 314.8 15.1 142.6 118.0 93.5 - - - 300.0 17.0 137.0 112.4 87.8 - - -
72 285.9 14.8 177.4 152.9 128.3 103.8 - - 271.7 16.7 171.9 147.4 122.8 98.3 - -
6000 67 257.1 14.5 212.3 187.7 163.2 138.6 114.0 - 243.5 16.4 206.9 182.4 157.8 133.2 108.7 -
62 239.1 14.2 239.1 225.1 200.5 175.9 151.4 126.8 227.5 16.1 227.5 219.3 194.7 170.2 145.6 121.1
57 239.5 14.3 239.5 237.8 213.3 188.7 164.1 139.6 230.2 16.2 230.2 227.8 203.3 178.7 154.1 129.6
77 321.1 15.2 154.7 127.4 100.0 - - - 305.7 17.1 148.9 121.5 94.1 - - -
72 291.7 14.9 192.0 164.7 137.3 110.0 - - 276.9 16.8 186.4 159.0 131.6 104.2 - -
7000 67 262.3 14.6 229.3 201.9 174.6 147.2 119.9 - 248.1 16.5 223.9 196.5 169.1 141.7 114.4 -
62 243.9 14.3 243.9 236.9 214.5 188.2 159.8 132.5 231.9 16.2 231.9 227.7 208.7 181.3 154.0 126.6
57 244.3 14.5 244.3 243.5 228.2 203.0 173.5 146.1 234.5 16.3 234.5 233.4 217.9 190.5 163.1 135.7
77 327.5 15.3 166.9 136.7 106.6 - - - 311.4 17.2 160.9 130.7 100.5 - - -
72 297.5 15.0 206.6 176.5 146.3 116.2 - - 282.1 16.9 200.9 170.7 140.5 110.2 - -
8000 67 267.5 14.8 246.3 216.2 186.0 155.9 125.7 - 252.8 16.6 240.9 210.7 180.5 150.2 120.0 -
62 248.8 14.4 248.8 248.8 228.6 200.4 168.3 138.1 236.2 16.2 236.2 236.2 222.7 192.5 162.3 132.1
57 249.2 14.6 249.2 249.2 243.2 217.3 182.9 152.7 238.9 16.4 238.9 238.9 232.5 202.2 172.0 141.8
72 303.3 15.2 219.3 184.7 150.2 115.7 - - 287.2 17.1 212.0 178.0 144.0 110.1 - -
67 272.7 14.9 262.1 225.5 191.0 156.5 122.0 - 257.4 16.8 251.5 219.1 185.1 151.1 117.1 -
9000
62 253.6 14.6 253.6 253.6 234.7 201.2 165.6 131.1 240.5 16.4 240.5 240.5 228.4 194.4 160.4 126.5
57 254.0 14.7 254.0 254.0 249.7 217.3 180.6 146.1 243.3 16.6 243.3 243.3 238.4 204.4 170.4 136.4
72 309.0 15.4 231.9 193.0 154.1 115.2 - - 292.4 17.3 223.1 185.4 147.6 109.9 - -
67 277.8 15.1 277.8 234.9 196.0 157.1 118.2 - 262.0 17.0 262.0 227.4 189.7 151.9 114.2 -
10000
62 258.4 14.7 258.4 258.4 240.8 201.9 163.0 124.1 244.8 16.6 244.8 244.8 234.1 196.4 158.6 120.9
57 258.8 14.9 258.8 258.8 256.2 217.3 178.4 139.5 247.6 16.8 247.6 247.6 244.3 206.6 168.8 131.1
95°F 105°F
77 285.2 18.9 131.3 106.8 82.2 - - - 264.8 21.2 126.0 101.4 76.8 - - -
72 257.5 18.6 166.4 141.9 117.3 92.8 - - 240.1 20.9 161.0 136.3 111.7 87.1 - -
6000 67 229.9 18.2 201.5 177.0 152.4 127.9 103.3 - 215.3 20.5 195.9 171.3 146.7 122.1 97.5 -
62 216.0 18.0 216.0 213.5 189.0 164.4 139.9 115.3 203.2 20.2 203.2 202.0 183.1 158.5 133.9 109.2
57 220.8 18.1 220.8 217.8 193.2 168.7 144.1 119.6 209.8 20.4 209.8 206.5 181.9 157.3 132.6 108.0
77 290.2 19.0 143.1 115.7 88.3 - - - 269.2 21.3 142.0 110.2 82.7 - - -
72 262.1 18.6 180.8 153.4 126.0 98.5 - - 244.1 20.9 175.3 147.8 120.3 92.8 - -
7000 67 234.0 18.3 218.5 191.1 163.7 136.3 108.8 - 219.0 20.6 208.6 185.4 157.9 130.4 102.9 -
62 219.8 18.0 219.8 218.6 202.9 174.5 148.1 120.7 206.6 20.3 206.6 206.0 197.1 169.1 142.1 114.6
57 224.7 18.2 224.7 223.2 207.5 177.9 152.6 125.2 213.3 20.5 213.3 211.7 195.8 167.2 140.8 113.3
77 295.2 19.0 154.9 124.6 94.3 - - - 273.7 21.4 158.1 119.0 88.5 - - -
72 266.6 18.7 195.2 164.9 134.6 104.3 - - 248.1 21.0 189.7 159.3 128.9 98.4 - -
8000 67 238.0 18.4 235.5 205.2 174.9 144.6 114.3 - 222.6 20.7 221.3 199.6 169.2 138.8 108.3 -
62 223.6 18.1 223.6 223.6 216.9 184.6 156.3 126.0 210.0 20.4 210.0 210.0 211.2 179.7 150.3 119.9
57 228.6 18.3 228.6 228.6 221.8 187.2 161.2 130.9 216.9 20.6 216.9 216.9 209.7 177.2 148.9 118.5
72 271.1 19.0 204.8 171.3 137.9 104.4 - - 252.2 21.2 199.3 165.7 132.2 98.6 - -
67 242.1 18.6 240.8 212.6 179.1 145.7 112.3 - 226.2 20.9 225.6 207.1 173.6 140.0 106.4 -
9000
62 227.4 18.3 227.4 227.4 222.1 187.7 155.2 121.8 213.4 20.6 213.4 213.4 213.0 179.0 145.9 112.4
57 232.5 18.5 232.5 232.5 227.1 191.5 160.2 126.8 220.4 20.8 220.4 220.4 215.2 180.5 148.0 114.5
72 275.7 19.2 214.3 177.7 141.1 104.5 - - 256.2 21.5 208.9 172.2 135.5 98.8 - -
67 246.1 18.8 246.1 219.9 183.4 146.8 110.2 - 229.8 21.1 229.8 214.6 177.9 141.2 104.6 -
10000
62 231.2 18.6 231.2 231.2 227.3 190.8 154.2 117.6 216.8 20.8 216.8 216.8 214.9 178.2 141.5 104.8
57 236.4 18.7 236.4 236.4 232.5 195.9 159.3 122.7 223.9 21.0 223.9 223.9 220.6 183.9 147.2 110.5

50 Johnson Controls Ducted Systems


505429-JTG-NN-1222

J20PD/J20NM (Continued)
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 244.4 23.6 120.7 96.0 71.4 - - - 224.0 25.9 115.4 90.7 65.9 - - -
72 222.6 23.2 155.5 130.8 106.2 81.5 - - 205.1 25.5 150.0 125.3 100.6 75.8 - -
6000 67 200.8 22.8 190.3 165.6 140.9 116.3 91.6 - 186.2 25.1 184.7 159.9 135.2 110.5 85.7 -
62 190.4 22.5 190.4 190.4 177.2 152.5 127.8 103.2 177.6 24.8 177.6 177.6 171.3 146.5 121.8 97.1
57 198.8 22.8 198.8 195.2 170.5 145.8 121.2 96.5 187.8 25.1 187.8 183.9 159.2 134.4 109.7 85.0
77 248.3 23.6 140.9 104.7 77.1 - - - 227.3 25.9 139.8 99.1 71.4 - - -
72 226.1 23.2 169.8 142.2 114.6 87.0 - - 208.1 25.5 164.3 136.6 108.9 81.3 - -
7000 67 204.0 22.9 198.7 179.8 152.2 124.6 97.0 - 188.9 25.2 188.8 174.1 146.4 118.7 91.1 -
62 193.4 22.6 193.4 193.4 191.3 163.7 136.1 108.5 180.2 24.8 180.2 180.2 180.2 158.3 130.1 102.4
57 201.9 22.8 201.9 200.1 184.1 156.5 128.9 101.3 190.6 25.1 190.6 188.6 172.4 145.8 117.0 89.3
77 252.1 23.7 161.2 113.3 82.7 - - - 230.6 26.0 164.3 107.6 76.9 - - -
72 229.6 23.3 184.1 153.6 123.1 92.5 - - 211.1 25.6 178.6 148.0 117.3 86.7 - -
8000 67 207.1 22.9 207.1 194.0 163.4 132.9 102.4 - 191.7 25.2 191.7 188.3 157.7 127.0 96.4 -
62 196.4 22.6 196.4 196.4 205.4 174.9 144.4 113.8 182.8 24.9 182.8 182.8 182.8 170.1 138.4 107.8
57 205.1 22.9 205.1 205.1 197.7 167.2 136.6 106.1 193.3 25.2 193.3 193.3 185.7 157.2 124.4 93.7
72 233.2 23.5 193.9 160.2 126.5 92.8 - - 214.2 25.8 188.4 154.6 120.8 87.0 - -
67 210.3 23.2 210.3 201.6 168.0 134.3 100.6 - 194.5 25.5 194.5 194.5 162.4 128.6 94.8 -
9000
62 199.4 22.8 199.4 199.4 203.9 170.3 136.6 102.9 185.4 25.1 185.4 185.4 185.4 161.6 127.3 93.5
57 208.3 23.1 208.3 208.3 203.2 169.5 135.9 102.2 196.1 25.4 196.1 196.1 191.3 158.5 123.7 89.9
72 236.7 23.8 203.6 166.8 129.9 93.1 - - 217.2 26.1 198.2 161.3 124.3 87.4 - -
67 213.5 23.4 213.5 209.3 172.5 135.7 98.9 - 197.2 25.7 197.2 197.2 167.1 130.2 93.2 -
10000
62 202.5 23.1 202.5 202.5 202.5 165.6 128.8 92.0 188.1 25.4 188.1 188.1 188.1 153.1 116.1 79.2
57 211.4 23.4 211.4 211.4 208.7 171.9 135.1 98.3 198.9 25.7 198.9 198.9 196.8 159.9 123.0 86.0
1 These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated motor
efficiency.
2 These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

Johnson Controls Ducted Systems 51


505429-JTG-NN-1222

Heat pump and air handler heating capacities

J07PE / J07NL
Air over evaporator coil Capacity1 Outdoor temperature (°F @ 72% RH)
and
CFM DB (°F) kW -10 0 10 20 30 40 50 60
MBH 23.6 33.8 43.9 54.1 64.2 74.3 84.5 94.6
55
KW 4.4 4.5 4.7 4.9 5.0 5.2 5.4 5.6
MBH 22.3 32.5 42.6 52.7 62.9 73.0 83.1 93.3
2250 70
KW 5.2 5.4 5.5 5.7 5.9 6.1 6.2 6.4
MBH 21.1 31.2 41.3 51.5 61.6 71.7 81.9 92.0
80
KW 5.8 6.0 6.2 6.4 6.5 6.7 6.9 7.1
MBH 28.7 38.9 49.0 59.1 69.3 79.4 89.5 99.7
55
KW 3.9 4.0 4.2 4.4 4.6 4.7 4.9 5.1
MBH 27.4 37.5 47.6 57.8 67.9 78.0 88.2 98.3
3000 70
KW 4.7 4.9 5.1 5.2 5.4 5.6 5.8 5.9
MBH 26.1 36.2 46.4 56.5 66.6 76.8 86.9 97.1
80
KW 5.4 5.5 5.7 5.9 6.1 6.2 6.4 6.6
MBH 33.8 44.0 54.1 64.2 74.4 84.5 94.6 104.8
55
KW 3.6 3.8 4.0 4.2 4.3 4.5 4.7 4.8
MBH 32.5 42.6 52.8 62.9 73.0 83.2 93.3 103.5
3750 70
KW 4.5 4.6 4.8 5.0 5.2 5.3 5.5 5.7
MBH 31.2 41.4 51.5 61.6 71.8 81.9 92.1 102.2
80
KW 5.1 5.3 5.5 5.6 5.8 6.0 6.2 6.3
1
These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate
Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated
motor efficiency.

J10PC / J10NL
Air over evaporator coil Capacity1 Outdoor temperature (°F @ 72% RH)
and
CFM DB (°F) kW -10 0 10 20 30 40 50 60
MBH 36.7 51.4 66.2 80.9 95.7 110.4 125.2 139.9
55
KW 6.1 6.4 6.6 6.9 7.1 7.4 7.6 7.9
MBH 28.1 42.9 57.6 72.4 87.1 101.9 116.6 131.4
3000 70
KW 7.2 7.4 7.7 7.9 8.2 8.4 8.7 8.9
MBH 26.1 40.8 55.6 70.3 85.1 99.8 114.6 129.3
80
KW 8.1 8.4 8.6 8.9 9.1 9.4 9.6 9.9
MBH 38.6 53.4 68.1 82.9 97.6 112.4 127.1 141.9
55
KW 5.3 5.6 5.8 6.1 6.3 6.6 6.8 7.1
MBH 30.0 44.7 59.5 74.2 89.0 103.7 118.5 133.2
4000 70
KW 6.4 6.7 6.9 7.2 7.4 7.7 7.9 8.2
MBH 27.9 42.6 57.4 72.1 86.9 101.6 116.4 131.1
80
KW 7.4 7.6 7.9 8.1 8.4 8.6 8.9 9.1
MBH 49.5 64.2 78.9 93.7 108.4 123.2 137.9 152.7
55
KW 5.1 5.3 5.6 5.9 6.1 6.3 6.6 6.8
MBH 40.9 55.6 70.4 85.1 99.9 114.6 129.4 144.1
5000 70
KW 6.2 6.4 6.7 6.9 7.2 7.4 7.6 7.9
MBH 38.8 53.6 68.3 83.1 97.8 112.6 127.3 142.1
80
KW 7.1 7.4 7.6 7.9 8.1 8.4 8.7 8.9
1 These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate
Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated
motor efficiency.

52 Johnson Controls Ducted Systems


505429-JTG-NN-1222

J15PC / J15NL
Air over evaporator coil Capacity1 Outdoor temperature (°F @ 72% RH)
and
CFM DB (°F) kW -10 0 10 20 30 40 50 60
MBH 68.2 80.0 93.8 110.0 129.1 151.5 177.8 208.7
55
KW 11.8 12.2 12.7 13.2 13.7 14.1 14.6 15.1
MBH 61.5 73.2 87.0 103.2 122.3 144.7 171.0 201.9
4500 70
KW 13.5 14.0 14.4 14.9 15.4 15.9 16.3 16.8
MBH 57.6 69.3 83.1 99.3 118.4 140.8 167.1 198.0
80
KW 15.0 15.5 16.0 16.4 16.9 17.4 17.9 18.3
MBH 74.0 85.8 99.6 115.8 134.9 157.3 183.6 214.5
55
KW 11.2 11.7 12.2 12.6 13.1 13.6 14.1 14.6
MBH 67.3 79.0 92.8 109.0 128.1 150.5 176.8 207.7
6000 70
KW 12.9 13.4 13.9 14.4 14.8 15.3 15.8 16.3
MBH 63.4 75.1 88.9 105.1 124.2 146.6 172.9 203.8
80
KW 14.5 14.9 15.4 15.9 16.4 16.8 17.3 17.8
MBH 72.4 84.1 97.9 114.1 133.2 155.6 181.9 212.8
55
KW 12.0 12.5 13.0 13.4 13.9 14.4 14.9 15.4
MBH 65.6 77.3 91.1 107.4 126.4 148.8 175.1 206.0
7500 70
KW 13.7 14.2 14.7 15.2 15.6 16.1 16.6 17.1
MBH 61.7 73.4 87.3 103.5 122.5 144.9 171.2 202.1
80
KW 15.3 15.7 16.2 16.7 17.2 17.6 18.1 18.6
1
These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate
Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated
motor efficiency.

J15PD / J15NM
Air over evaporator coil Capacity1 Outdoor temperature (°F @ 72% RH)
and
CFM DB (°F) kW -10 0 10 20 30 40 50 60
MBH 65.6 77.0 90.3 105.8 123.9 145.1 169.7 198.5
55
KW 10.0 10.5 11.1 11.6 12.2 12.7 13.3 13.8
MBH 62.2 73.6 86.9 102.4 120.5 141.6 166.3 195.1
4500 70
KW 12.0 12.5 13.1 13.6 14.2 14.7 15.3 15.8
MBH 59.5 70.9 84.1 99.7 117.8 138.9 163.6 192.4
80
KW 13.4 13.9 14.5 15.0 15.6 16.1 16.7 17.2
MBH 71.6 83.0 96.3 111.8 129.9 151.0 175.7 204.5
55
KW 9.6 10.2 10.7 11.3 11.8 12.4 12.9 13.4
MBH 68.1 79.5 92.8 108.3 126.5 147.6 172.3 201.1
6000 70
KW 11.6 12.2 12.7 13.3 13.8 14.3 14.9 15.4
MBH 65.4 76.8 90.1 105.6 123.7 144.9 169.6 198.3
80
KW 13.0 13.6 14.1 14.7 15.2 15.8 16.3 16.9
MBH 74.0 85.4 98.7 114.2 132.4 153.5 178.2 207.0
55
KW 11.3 11.8 12.4 12.9 13.5 14.0 14.6 15.1
MBH 70.6 82.0 95.3 110.8 128.9 150.1 174.7 203.5
7500 70
KW 13.3 13.8 14.4 14.9 15.5 16.0 16.6 17.1
MBH 67.9 79.3 92.6 108.1 126.2 147.4 172.0 200.8
80
KW 14.7 15.3 15.8 16.4 16.9 17.5 18.0 18.5
1 These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate
Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated
motor efficiency.

Johnson Controls Ducted Systems 53


505429-JTG-NN-1222

J20PD / J20NM
Air over evaporator coil Capacity1 Outdoor temperature (°F @ 72% RH)
and
CFM DB (°F) kW -10 0 10 20 30 40 50 60
MBH 64.6 79.5 97.4 118.8 144.3 174.9 211.4 255.1
55
KW 15.7 16.5 17.3 18.1 19.0 19.8 20.6 21.4
MBH 69.5 84.4 102.3 123.7 149.2 179.8 216.3 260.0
6000 70
KW 15.4 16.2 17.0 17.9 18.7 19.5 20.3 21.2
MBH 63.3 78.3 96.2 117.5 143.1 173.6 210.2 253.8
80
KW 17.2 18.0 18.8 19.6 20.5 21.3 22.1 23.0
MBH 71.6 86.6 104.5 125.8 151.4 181.9 218.5 262.1
55
KW 15.1 15.9 16.8 17.6 18.4 19.2 20.1 20.9
MBH 76.5 91.5 109.4 130.7 156.3 186.8 223.4 267.0
8000 70
KW 14.8 15.6 16.5 17.3 18.1 19.0 19.8 20.6
MBH 70.4 85.3 103.2 124.6 150.1 180.7 217.2 260.9
80
KW 16.6 17.4 18.3 19.1 19.9 20.7 21.6 22.4
MBH 73.3 88.3 106.1 127.5 153.1 183.6 220.1 263.8
55
KW 15.3 16.1 17.0 17.8 18.6 19.4 20.3 21.1
MBH 78.2 93.2 111.0 132.4 158.0 188.5 225.0 268.7
10000 70
KW 15.0 15.8 16.7 17.5 18.3 19.1 20.0 20.8
MBH 72.1 87.0 104.9 126.3 151.8 182.4 218.9 262.6
80
KW 16.8 17.6 18.5 19.3 20.1 20.9 21.8 22.6
1
These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate
Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746  nameplate rated
motor efficiency.

54 Johnson Controls Ducted Systems


505429-JTG-NN-1222

Air handling and hot water coil accessory heating capacity

J25NC / 1HW04061
Capacity (MBH)
Unit Hot water
GPM CFM Entering water temperature minus entry air temperature °F.
model coil model
70 90 110 130 150

6,000 204 263 325 384 443

8,000 236 304 372 440 508


J25NC 1HW0406 50
10,000 265 341 416 492 568

12,000 291 374 457 540 623

1
These capacities do not include any blower motor heat.
NOTE: Temperature Water Drop (ºF) = (2 X MBH) / GPM.

Hot water coil capacity correction and pressure drop Vs GPM1


Pressure drop
Hot water coil model GPM Capacity correction factor
PSI

25 0.4 0.79

50 1.0 1.00
1HW0406
75 1.8 1.04

100 3.4 1.07

1 For pressure drop in feet (water), multiply these values by 2.31.

Air handling and steam coil accessory heating capacity

J25NC / 1NF0454
Capacity (MBH) @ 2 PSIG1
Unit Steam coil
CFM Dry bulb temperature of air entering coil (°F)
model model
10 30 50 70

6,000 471 424 380 330

8,000 535 483 432 380


J25NC 1NF0454
10,000 592 535 478 422

12,000 642 580 518 456

1
These capacities do not include any blower motor heat.

Steam coil capacity correction factors for high steam pressure


Steam pressure (PSIG) 5 10 15 20 25

Capacity correction factor 1.05 1.12 1.19 1.25 1.30

NOTE: Steam Rate = (lbs/Hr.) = 1.025 x MBH

Johnson Controls Ducted Systems 55


505429-JTG-NN-1222

Airflow performance
J07NL Upflow and horizontal airflow performance

J07NL Upflow
Available External Static Pressure - IWG
(CFM) 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 1.5 HP and Field
Standard 1.5 HP and Drive High Static 2 HP and Drive
Supplied Drive
2250 754 0.8 828 0.9 902 1.0 988 1.1 1051 1.3 1116 1.4 1183 1.5
2500 707 0.8 777 0.9 851 1.0 925 1.1 996 1.3 1059 1.4 1124 1.5 1191 1.7
2750 735 0.9 805 1.1 879 1.2 953 1.3 1012 1.4 1076 1.6 1141 1.7
3000 705 1.0 767 1.1 837 1.2 911 1.3 973 1.5 1035 1.6 1099 1.7 1164 1.9
3250 741 1.1 802 1.3 872 1.4 947 1.5 1002 1.7 1064 1.8 1127 2.0
3500 780 1.4 842 1.5 912 1.6 974 1.8 1035 1.9 1097 2.1 1161 2.2
3750 823 1.6 884 1.7 954 1.9 1012 2.0 1072 2.2 1134 2.3 Exceeds BHP Limitations

1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.

J07NL Horizontal
Available External Static Pressure - IWG
(CFM) 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 1.5 HP and Field
Standard 1.5 HP and Drive High Static 2 HP and Drive
Supplied Drive
2250 747 0.8 816 0.9 889 1.0 954 1.2 1013 1.3 1071 1.5 1128 1.6
2500 703 0.8 768 0.9 837 1.0 909 1.1 977 1.2 1036 1.4 1094 1.5 1151 1.7
2750 728 0.9 793 1.0 862 1.1 934 1.2 998 1.4 1056 1.5 1114 1.7
3000 696 0.9 757 1.1 822 1.2 891 1.3 961 1.4 1019 1.6 1077 1.7 1135 1.9
3250 729 1.1 790 1.3 855 1.4 924 1.5 984 1.6 1042 1.8 1100 1.9 1159 2.1
3500 766 1.3 826 1.5 892 1.6 953 1.6 1010 1.9 1069 2.0 1127 2.2
3750 806 1.6 867 1.7 932 1.8 984 1.9 1041 2.1 1099 2.3 Exceeds BHP Limitations

1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.

56 Johnson Controls Ducted Systems


505429-JTG-NN-1222

J10NL/NM Upflow and horizontal airflow performance

J10NL/NM Upflow
Available External Static Pressure - IWG
(CFM) 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 2 HP and Field
Standard 2 HP and Drive High Static 3 HP and Drive
Supplied Drive
2500 671 0.8 728 0.9 788 1.0 853 1.1 926 1.3 975 1.5 1026 1.6 1077 1.7
2750 684 0.9 741 1.0 801 1.1 866 1.2 933 1.4 982 1.6 1032 1.7 1084 1.8
3000 701 1.0 757 1.1 817 1.3 882 1.4 941 1.5 991 1.7 1041 1.8 1092 2.0
3250 664 1.0 719 1.1 776 1.3 836 1.4 903 1.5 952 1.7 1002 1.8 1052 2.0
3500 685 1.1 741 1.3 797 1.4 858 1.5 917 1.7 966 1.9 1015 2.0 1066 2.2
3750 653 1.1 709 1.3 764 1.4 821 1.6 884 1.7 933 1.9 982 2.0 1031 2.2 1082 2.3
4000 679 1.3 735 1.5 790 1.6 847 1.8 903 1.9 952 2.1 1001 2.3 1050 2.4
4250 707 1.5 762 1.6 818 1.8 875 1.9 924 2.1 973 2.3 1022 2.5 1072 2.7
4500 737 1.7 792 1.9 850 2.0 899 2.2 948 2.4 997 2.6 1046 2.8
4750 768 1.9 824 2.1 877 2.2 926 2.5 975 2.7 1024 2.9 1073 3.0
5000 801 2.1 856 2.3 906 2.5 956 2.8 1005 3.0 1053 3.2 High Static 3 HP and Field Supplied Drive

1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.

J10NL/NM Horizontal
Available External Static Pressure - IWG
(CFM) 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 2 HP and Field
Standard 2 HP and Drive High Static 3 HP and Drive
Supplied Drive
2500 686 0.8 730 0.9 778 0.9 840 1.0 917 1.3 964 1.5 1011 1.6 1060 1.7
2750 698 0.9 742 1.0 790 1.0 852 1.1 924 1.4 971 1.6 1019 1.7 1067 1.9
3000 714 1.0 758 1.1 806 1.1 868 1.2 935 1.6 981 1.7 1029 1.9 1078 2.0
3250 684 1.0 734 1.2 778 1.2 826 1.3 902 1.6 948 1.7 995 1.9 1042 2.0
3500 707 1.2 757 1.3 801 1.4 849 1.4 917 1.7 964 1.9 1010 2.0 1058 2.2
3750 669 1.2 734 1.4 784 1.5 828 1.6 890 1.7 936 1.9 982 2.1 1029 2.2 1076 2.4
4000 699 1.4 764 1.6 814 1.7 858 1.8 910 2.0 956 2.1 1002 2.3 1049 2.4
4250 732 1.6 798 1.8 847 1.9 887 2.0 933 2.2 978 2.4 1025 2.5 1071 2.7
4500 769 1.8 834 2.0 884 2.1 911 2.3 957 2.4 1003 2.6 1049 2.8
4750 808 2.1 874 2.3 891 2.3 937 2.5 983 2.7 1029 2.9 1075 3.1
5000 850 2.3 873 2.4 919 2.6 965 2.8 1011 3.0 1057 3.2 High Static 3 HP and Field Supplied Drive

1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.

Johnson Controls Ducted Systems 57


505429-JTG-NN-1222

J15NL/NM Upflow and horizontal airflow performance

J15NL/NM Upflow
Available External Static Pressure - IWG
(CFM) 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 3 HP and Field Supplied Drive Standard 3 HP and Drive High Static 5 HP and Drive
4500 583 1.1 634 1.3 688 1.5 738 1.9 782 2.3 827 2.6
4750 592 1.2 643 1.4 700 1.8 744 2.1 788 2.4 833 2.7
5000 602 1.2 653 1.4 707 1.9 751 2.2 795 2.6 840 2.9
5250 613 1.3 664 1.5 716 2.1 759 2.4 804 2.7 848 3.1
5500 577 1.1 625 1.4 676 1.6 725 2.3 768 2.6 813 2.9 857 3.2
5750 590 1.2 638 1.4 689 1.7 735 2.5 778 2.8 822 3.1
6000 603 1.3 651 1.6 702 2.3 745 2.7 789 3.0 833 3.3
6250 617 1.5 664 1.7 714 2.6 757 2.9 801 3.2 845 3.5
6500 587 1.4 631 1.6 679 1.8 726 2.8 769 3.1 813 3.4 857 3.8
6750 601 1.6 645 1.8 693 2.0 739 3.0 782 3.4 826 3.7
7000 616 1.8 660 2.0 710 2.9 753 3.3 796 3.6 839 3.9
7250 632 2.1 675 2.3 725 3.2 767 3.6 810 3.9 854 4.2
7500 647 2.3 691 2.5 740 3.5 782 3.9 825 4.2 High Static 5 HP and Field Supplied Drive

1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.

J15NL/NM Horizontal
Available External Static Pressure - IWG
(CFM) 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 3 HP and Field Supplied Drive Standard 3 HP and Drive High Static 5 HP and Drive
4500 585 1.5 634 1.6 687 1.8 735 2.0 780 2.5 827 2.7 875 2.9
4750 595 1.6 644 1.7 697 1.9 741 2.4 787 2.7 834 2.9
5000 605 1.7 655 1.8 708 2.0 749 2.6 795 2.9 842 3.1
5250 617 1.8 666 2.0 719 2.1 757 2.8 804 3.1 851 3.3
5500 582 1.8 629 1.9 678 2.1 731 2.3 767 3.0 813 3.2 860 3.4
5750 594 1.9 642 2.1 691 2.2 737 2.4 778 3.2 824 3.4 871 3.7
6000 608 2.1 655 2.2 705 2.4 744 3.1 789 3.4 835 3.7
6250 622 2.2 670 2.4 719 2.6 756 3.3 801 3.6 847 3.9
6500 589 2.2 637 2.4 684 2.6 733 2.7 769 3.6 814 3.9 860 4.1
6750 604 2.4 652 2.6 699 2.8 738 3.5 782 3.8 827 4.1 873 4.4
7000 620 2.6 667 2.8 715 3.0 752 3.8 796 4.1 841 4.4
7250 636 2.8 683 3.0 731 3.2 766 4.1 811 4.4 856 4.7
7500 652 3.0 700 3.2 738 4.0 781 4.4 825 4.7 High Static 5 HP and Field Supplied Drive

1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.

58 Johnson Controls Ducted Systems


505429-JTG-NN-1222

J20NL/NM Upflow and horizontal airflow performance

J20NL/NM Upflow
Available External Static Pressure - IWG
(CFM) 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 5 HP and
High Static 5 HP and Drive High Static 7.5 HP and Drive
Field Supplied Drive
6000 732 2.2 789 2.6 846 2.9 900 3.1 959 4.0 1008 4.5 1056 4.9 1102 5.2 1146 5.3
6250 685 1.9 742 2.3 799 2.7 856 3.0 910 3.3 967 4.2 1016 4.7 1064 5.1 1110 5.4 1154 5.5
6500 696 2.1 752 2.5 809 2.8 866 3.2 920 3.4 976 4.4 1025 4.9 1072 5.3 1118 5.6
6750 706 2.2 763 2.6 820 3.0 877 3.3 935 4.0 985 4.6 1034 5.1 1081 5.5 1127 5.8
7000 718 2.4 774 2.8 831 3.2 888 3.5 945 4.2 994 4.8 1043 5.3 1091 5.7 1137 6.0
7250 729 2.6 786 3.0 843 3.3 900 3.6 954 4.5 1004 5.0 1053 5.5 1100 5.9 1146 6.2
7500 741 2.8 798 3.1 855 3.5 912 3.8 965 4.7 1014 5.3 1063 5.8 1111 6.2
7750 700 2.6 754 2.9 810 3.3 868 3.7 925 4.3 975 4.9 1025 5.5 1074 6.0 1121 6.4
8000 712 2.8 767 3.1 823 3.5 881 3.9 936 4.6 986 5.2 1036 5.8 1085 6.3 1132 6.7
8250 726 3.0 780 3.3 837 3.7 894 4.1 948 4.9 998 5.5 1047 6.0 1096 6.5 1144 6.9
8500 740 3.2 794 3.6 850 3.9 908 4.3 959 5.1 1010 5.8 1059 6.3 1108 6.8
8750 754 3.4 808 3.8 865 4.2 922 4.8 972 5.4 1022 6.0 1071 6.6 1120 7.1
9000 768 3.6 823 4.0 879 4.4 934 5.1 984 5.7 1034 6.4 1084 6.9 1133 7.4
9250 783 3.9 838 4.3 894 4.6 947 5.4 997 6.1 1047 6.7 1097 7.2
9500 799 4.1 853 4.5 910 4.9 961 5.8 1011 6.4 1061 7.0 1110 7.6
9750 815 4.4 869 4.8 925 5.5 974 6.1 1024 6.7 1074 7.3 1124 7.9
10000 831 4.7 885 5.0 939 5.9 988 6.5 1038 7.1 1088 7.7 1138 8.3 High Static 7.5 HP and Field Supplied Drive

1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.

J20NL/NM Horizontal
Available External Static Pressure - IWG
(CFM) 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 5 HP
and Field
Standard 5 HP and Drive High Static 7.5 HP and Drive
Supplied
Drive
6000 708 2.0 754 2.3 801 2.6 849 2.8 898 2.9 976 4.0 1021 4.4 1066 4.8 1111 5.1 1155 5.3
6250 715 2.1 761 2.4 808 2.7 856 2.9 906 3.0 984 4.2 1029 4.6 1074 5.0 1118 5.3 1163 5.5
6500 723 2.3 769 2.6 816 2.8 864 3.0 947 3.9 991 4.4 1036 4.8 1081 5.2 1126 5.4
6750 731 2.4 777 2.7 824 3.0 872 3.2 955 4.1 999 4.6 1044 5,0 1089 5.3 1134 5.6
7000 740 2.5 786 2.8 833 3.1 881 3.3 963 4.3 1007 4.7 1052 5.2 1097 5.5 1142 5.8
7250 749 2.7 796 3.0 842 3.3 890 3.5 971 4.5 1015 4.9 1060 5.3 1105 5.7 1150 6.0
7500 712 2.6 759 2.9 806 3.2 852 3.4 900 3.6 979 4.7 1024 5.1 1069 5.5 1114 5.9 1158 6.2
7750 722 2.8 770 3.0 816 3.3 863 3.6 945 4.4 988 4.9 1033 5.3 1078 5.8 1123 6.1
8000 733 2.9 781 3.2 827 3.5 874 3.8 954 4.6 998 5.1 1042 5.5 1087 6.0 1132 6.3
8250 745 3.1 793 3.4 839 3.7 886 4.0 964 4.8 1007 5.3 1052 5.8 1096 6.2 1141 6.5
8500 757 3.3 805 3.6 851 3.9 898 4.2 974 5.1 1017 5.6 1062 6.0 1107 6.4 1152 6.8
8750 770 3.6 818 3.8 864 4.1 942 4.8 984 5.3 1028 5.8 1072 6.3 1117 6.7
9000 784 3.8 831 4.1 878 4.4 953 5.1 995 5.6 1039 6.1 1083 6.5 1128 6.9
9250 798 4.0 845 4.3 923 4.9 964 5.4 1006 5.9 1050 6.3 1094 6.8 1139 7.2
9500 812 4.3 859 4.6 935 5.2 976 5.7 1018 6.2 1062 6.6 1106 7.1 1151 7.5
9750 827 4.5 908 5.1 947 5.5 988 6.0 1030 6.5 1074 6.9 1118 7.4
10000 842 4.8 921 5.4 960 5.8 1001 6.3 1043 6.8 1087 7.3 1131 7.7 High Static 7.5 HP and Field Supplied Drive

1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.

Johnson Controls Ducted Systems 59


505429-JTG-NN-1222

J25NC Airflow performance1


Avaiable External Static Pressure - IWG
CFM 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Motor and Drive 7.5 HP Motor and Drive
7500 600 2.04 648 2.50 694 3.00 738 3.54 781 4.08 823 4.63 863 5.16 903 5.66 942 6.10 981 6.49
5 HP and
7750 Field 603 2.17 652 2.63 698 3.13 742 3.67 785 4.22 827 4.76 867 5.29 907 5.79 946 6.24 984 6.62
8000 supplied 608 2.32 656 2.78 702 3.28 747 3.81 789 4.36 831 4.91 871 5.44 911 5.93 950 6.38 989 6.77
Drive
8250 613 2.48 661 2.93 707 3.44 752 3.97 795 4.52 836 5.07 877 5.60 916 6.09 955 6.54 994 6.92
8500 619 2.65 667 3.10 713 3.61 758 4.14 800 4.69 842 5.24 882 5.77 922 6.26 961 6.71 1000 7.09
8750 575 2.43 625 2.83 673 3.28 720 3.79 764 4.32 807 4.87 848 5.42 889 5.95 928 6.44 967 6.89 1006 7.27
9000 581 2.62 632 3.02 680 3.47 726 3.98 771 4.51 814 5.06 855 5.61 896 6.14 935 6.63 974 7.08 1013 7.46
9250 589 2.82 639 3.21 687 3.67 734 4.17 778 4.71 821 5.26 862 5.80 903 6.33 942 6.83 982 7.28
9500 596 3.02 647 3.42 695 3.88 741 4.38 786 4.91 829 5.46 870 6.01 910 6.54 950 7.03 989 7.48
9750 604 3.23 655 3.63 703 4.09 749 4.59 794 5.13 836 5.67 878 6.22 918 6.75 958 7.25
10000 613 3.45 663 3.85 711 4.31 758 4.81 802 5.34 845 5.89 886 6.44 927 6.97 966 7.46
10250 621 3.68 672 4.07 720 4.53 766 5.03 811 5.57 853 6.12 895 6.66 935 7.19
10500 630 3.9 680 4.30 729 4.76 775 5.26 819 5.80 862 6.34 904 6.89 944 7.42
10750 639 4.14 689 4.53 738 4.99 784 5.50 828 6.03 871 6.58 913 7.12
11000 648 4.37 699 4.77 747 5.23 793 5.73 837 6.27 880 6.82 922 7.36
11250 657 4.62 708 5.01 756 5.47 802 5.97 847 6.51 890 7.06
11500 667 4.86 717 5.26 766 5.71 812 6.22 856 6.75 899 7.30
11750 676 5.11 727 5.50 775 5.96 821 6.46 866 7.00
12000 686 5.36 737 5.75 785 6.21 831 6.71 876 7.25 High static 7.5 HP and Field Supplied Drive
12250 696 5.61 746 6.00 795 6.46 841 6.97 885 7.50
12500 706 5.86 756 6.26 805 6.72 851 7.22

1. J25NC requires the selection, purchase and field installation of the Supply Fan Motor, Drive Kit and Motor Overloads (See Following Page for Item
Selection Tables).

RPM selection
6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn Fully
Unit Model HP Max BHP Motor Sheave Blower Sheave
Open Open Open Open Open Open Closed
Std. 1.5 1.73 1VL40 AK69 -1 690 743 796 849 902 955
J07NL
HS 2 2.30 1VL40 AK56 -1 863 929 995 1062 1128 1194
Std. 2 2.30 1VL40 AK74 -1 641 690 739 789 838 887
J10NL/NM
HS 3 3.45 1VP56 AK84 -1 906 949 992 1035 1078 1121
Std. 3 3.45 1VP50 AK114 -1 565 596 627 659 690 721
J15NL/NM
HS 5 5.75 2VP50 2B5V94 707 745 782 819 856 894 -2
Std. 5 5.75 2VP50 2B5V94 686 722 758 794 830 866 -2
J20NL/NM
HS 7.5 8.63 2VP65 2B5V94 925 960 996 1031 1067 1103 1138
1
Setting not available.
2
Setting not recommended for use with Type B v-belts.

J07NL and J10 - 20 NL/NM air handler blower motor and drive data
Blower Motor Data Drive Data
Adjustable Motor Sheave Fixed Blower Sheave Belts
Unit Blower
Model Frame Model Pitch Model Pitch Pitch
HP RPM SF RPM Bore Desig-
Size Number Diameter Number Diameter Bore (in.) Qty. Length
Range (in.) nation
(in.) (in.) (in.)
Std 1.5 56 1VL40 690 - 955 2.6 - 3.6 0.875 AK69 6.5 1.000 1 42.3 A41
J07NL 1725 1.15
HS 2 56HZ 1VL40 863 - 1194 2.6 - 3.6 0.875 AK56 5.2 1.000 1 40.3 A39
Std. 2 56HZ 1VL40 641 - 887 2.6 - 3.6 0.875 AK74 7.0 1.000 1 45.3 A44
J10NL/NM 1725 1.15
HS 3 56HZ 1VP56 906 - 1121 4.2 - 5.2 0.875 AK84 8.0 1.000 1 48.3 A47
Std. 3 56HZ 1VP50 565 - 721 3.6 - 4.6 0.875 AK114 11.0 1.000 1 45.3 A44
J15NL/NM 1725 1.15
HS 5 184T 2VP50 707 - 894 3.7 - 4.7 1.125 2B5V94 9.7 1.000 2 41.8 B40
Std. 5 184T 2VP50 686 - 866 3.7 - 4.7 1.125 2B5V94 9.7 1.188 2 41.8 B40
J20NL/NM 1725 1.15
HS 7.5 213T 2VP65 925 - 1138 5.2 - 6.4 1.375 2B5V94 9.7 1.188 2 46.8 B45

60 Johnson Controls Ducted Systems


505429-JTG-NN-1222

J25NC drive kit data


Adjustable Motor Sheave Fixed Blower Sheave Belts
Unit Drive Kit Model Sheave Blower Pitch Sheave Pitch Pitch
Model Number Bore Bore Desig-
Model RPM Diameter Model Diameter Qty. Length
(in.) (in.) nation
Number Range (in.) Number (in.) (in.)
1LD0440 2VP56 575 - 719 4.0 - 5.0 1 1/8 2AK124 12.0 1 3/16 2 63.3 A62
J25NC 1LD0407 2VP60 659 - 815 4.2 - 5.2 1 3/8 2AK114 11.0 1 3/16 2 63.3 A62
1LD0442 2VP71 762 - 906 5.3 - 6.3 1 3/8 2AK124 12.0 1 3/16 2 63.3 A62

J25NC motor kit data (Non-VFD rated motors)


Motor Kit
Frame Voltage
Unit Model HP Model
Size (3PH-60Hz)
Number
2LP04605133 208/230/460V
5 184
2LP04605158 575V
J25NC
2LP04607133 208/230/460V
7.5 213
2LP04607158 575V

J25NC motor kit data (VFD rated motors)


Motor Kit
Frame Voltage (3PH-
Unit Model HP Model
Size 60Hz)
Number
2LP04605233 230/460V
5 184
J25NC w/ 2LP04605258 575V
VFD 2LP04607233 208/230/460V
7.5 213
2LP04607258 575V

J25NC overload relay kits (Non-VFD rated motors)1


Unit Voltage 208/230V 460V 575V
Model Motor HP Overload relay kit
5 2MP04701 2MP04702 2MP04703
J25NC
7.5 2MP04704 2MP04705 2MP04705
1 Overload is included in the VFD kit.

J25NC overload relay setting (all)


Unit Voltage 208/230V 460V 575V

Model Motor HP Overload relay setting (full load amps) 1,2

5 13.5/13.0 6.5 5.2


J25NC
7.5 20.0/19.4 9.7 7.5

1 Motors with Service Factor of 1.15 or Greater: Adjust overload relay


dial to the motor nameplate Full Load Amps (FLA).
2 Motors with Service Factor Less Than 1.15: Adjust overload relay dial
based on the formula: Motor nameplate FLA x 0.90 = relay setting

Johnson Controls Ducted Systems 61


505429-JTG-NN-1222

Additional static resistance


Wet Indoor1 Bottom Electric heat kW
Model CFM 2 in. filters
coil return 10 16 26 36 50
2250 0.03 0.10 0.02 0.01 0.02 0.03 0.04 ---
2500 0.03 0.11 0.03 0.01 0.02 0.03 0.05 ---
2750 0.02 0.11 0.03 0.01 0.03 0.04 0.07 ---
J07NL 3000 0.02 0.12 0.04 0.01 0.03 0.05 0.08 ---
3250 0.01 0.13 0.04 0.02 0.04 0.06 0.09 ---
3500 0.00 0.14 0.05 0.02 0.04 0.07 0.10 ---
3750 0.00 0.15 0.06 0.02 0.05 0.08 0.12 ---
3000 0.08 0.12 0.04 0.01 0.03 0.05 0.08 ---
3250 0.07 0.13 0.04 0.02 0.04 0.06 0.09 ---
3500 0.07 0.14 0.05 0.02 0.04 0.07 0.10 ---
3750 0.06 0.15 0.06 0.02 0.05 0.08 0.12 ---
J10NL/NM 4000 0.05 0.16 0.07 0.03 0.06 0.09 0.14 ---
4250 0.04 0.18 0.08 0.03 0.06 0.10 0.15 ---
4500 0.03 0.19 0.09 0.03 0.07 0.11 0.17 ---
4750 0.02 0.21 0.10 0.04 0.08 0.13 0.19 ---
5000 0.00 0.23 0.11 0.04 0.09 0.14 0.21 ---
4500 0.07 0.11 0.03 0.03 0.07 0.11 0.17 0.21
4750 0.06 0.11 0.03 0.04 0.08 0.13 0.19 0.22
5000 0.06 0.11 0.04 0.04 0.09 0.14 0.21 0.24
5250 0.06 0.12 0.04 0.05 0.10 0.15 0.23 0.26
5500 0.05 0.12 0.04 0.05 0.11 0.17 0.25 0.29
5750 0.05 0.12 0.05 0.06 0.12 0.19 0.28 0.32
J15NL/NM 6000 0.05 0.13 0.05 0.06 0.13 0.20 0.30 0.35
6250 0.04 0.14 0.06 0.07 0.14 0.22 0.33 0.38
6500 0.03 0.14 0.06 0.07 0.15 0.24 0.35 0.42
6750 0.03 0.15 0.07 0.08 0.17 0.26 0.38 0.47
7000 0.02 0.16 0.07 0.08 0.18 0.28 0.41 0.50
7250 0.01 0.16 0.08 0.09 0.19 0.30 0.44 0.53
7500 0.00 0.17 0.08 0.10 0.20 0.32 0.47 0.56

Wet indoor Bottom Electric heat kW


Model CFM 2 in. filters
coil return 20 32 52
6000 0.08 0.12 0.06 0.01 0.03 0.05
6250 0.08 0.13 0.06 0.02 0.03 0.05
6500 0.08 0.13 0.07 0.02 0.04 0.06
6750 0.07 0.14 0.07 0.02 0.04 0.06
7000 0.07 0.14 0.08 0.02 0.04 0.07
7250 0.06 0.15 0.08 0.02 0.05 0.07
7500 0.06 0.16 0.09 0.02 0.05 0.08
7750 0.05 0.16 0.09 0.02 0.05 0.08
J20NL/NM 8000 0.05 0.17 0.10 0.03 0.06 0.09
8250 0.04 0.18 0.10 0.03 0.06 0.09
8500 0.04 0.19 0.11 0.03 0.06 0.10
8750 0.03 0.20 0.12 0.03 0.07 0.11
9000 0.02 0.21 0.12 0.03 0.07 0.11
9250 0.01 0.22 0.13 0.04 0.08 0.12
9500 0.00 0.23 0.00 0.04 0.08 0.13
9750 0.00 0.24 0.00 0.04 0.09 0.13
10000 0.00 0.25 0.00 0.04 0.09 0.14
1
Pressure drop added by condensate over a dry coil.

62 Johnson Controls Ducted Systems


505429-JTG-NN-1222

Additional static resistance (Continued)


Model CFM Hot water coil Steam coil
8000 0.06 0.11
9000 0.07 0.14
J25NC 10000 0.08 0.17
11000 0.09 0.20
12000 0.10 0.23

CFM static pressure and power-altitude and temperature order to use the indoor blower tables for high altitude
corrections applications, certain corrections are necessary.

The information below should be used to assist in application A centrifugal fan is a "constant volume" device. This means
of product when being applied at altitudes at or exceeding that, if the rpm remains constant, the CFM delivered is the
1000 feet above sea level. same regardless of the density of the air. However, since the
air at high altitude is less dense, less static pressure will be
The air flow rates listed in the standard blower performance generated and less power will be required than a similar
tables are based on standard air at sea level. As the altitude application at sea level. Air density correction factors are
or temperature increases, the density of air decreases. In shown in Altitude Factors Table and Temperature Correction
Figure.

Johnson Controls Ducted Systems 63


505429-JTG-NN-1222

Altitude/temperature correction factors table


Air Altitude (Ft.)
temp. 0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000
40 1.060 1.022 0.986 0.950 0.916 0.882 0.849 0.818 0.788 0.758 0.729
50 1.039 1.002 0.966 0.931 0.898 0.864 0.832 0.802 0.772 0.743 0.715
60 1.019 0.982 0.948 0.913 0.880 0.848 0.816 0.787 0.757 0.729 0.701
70 1.000 0.964 0.930 0.896 0.864 0.832 0.801 0.772 0.743 0.715 0.688
80 0.982 0.947 0.913 0.880 0.848 0.817 0.787 0.758 0.730 0.702 0.676
90 0.964 0.929 0.897 0.864 0.833 0.802 0.772 0.744 0.716 0.689 0.663
100 0.946 0.912 0.880 0.848 0.817 0.787 0.758 0.730 0.703 0.676 0.651

1.100

1.050

1.000
Sea Level
0.950
Correction Factor

1000 ft
0.900 2000 ft
3000 ft
0.850
4000 ft
0.800 5000 ft
6000 ft
0.750 7000 ft
8000 ft
0.700
9000 ft
10000 ft
0.650

0.600
40 50 60 70 80 90 100
Air Temperature (ºF)

Altitude/temperature correction factors figure

The examples below will assist in determining the airflow blower tables to select the blower speed and the BHP
performance of the product at altitude. requirement.

Example 1: What are the corrected CFM, static pressure, Solution: As in the example above, no temperature
and BHP at an elevation of 5,000 ft. if the blower information is given so 70°F is assumed.
performance data is 6,000 CFM, 1.5 IWC and 4.0 BHP?
The 1.5" static pressure given is at an elevation of 5,000 ft.
Solution: At an elevation of 5,000 ft. the indoor blower will still The first step is to convert this static pressure to equivalent
deliver 6,000 CFM if the rpm is unchanged. However, the sea level conditions.
Altitude/Temperature Correction Factors table must be used to
determine the static pressure and BHP. Since no temperature Sea level static pressure = 1.5 / .832 = 1.80"
data is given, we will assume an air temperature of 70°F. The
Enter the blower table at 6000 sCFM and static pressure of
table shows the correction factor to be 0.832.
1.8". The rpm listed will be the same rpm needed at 5,000 ft.
Corrected static pressure = 1.5 x 0.832 = 1.248 IWC
Suppose that the corresponding BHP listed in the table is 3.2.
Corrected BHP = 4.0 x 0.832 = 3.328 This value must be corrected for elevation.

Example 2: A system, located at 5,000 feet of elevation, is to BHP at 5,000 ft. = 3.2 x .832 = 2.66
deliver 6,000 CFM at a static pressure of 1.5". Use the unit

64 Johnson Controls Ducted Systems


505429-JTG-NN-1222

Drive selection

1. Determine Upflow or Horizontal supply duct Application.


2. Determine desired airflow.
3. Calculate or measure the amount of external static pressure.
4. Using the operating point, determined from steps 1, 2 and 3, locate this point on the appropriate supply air blower
performance table. (Linear interpolation may be necessary.)
5. Noting the RPM and BHP from step 4, locate the appropriate motor and/or drive on the RPM selection table.
6. Review the BHP compared to the motor options available. Select the appropriate motor and, or drive.
7. Review the RPM range for the motor options available. Select the appropriate drive if multiple drives are available for the
chosen motor.
8. Determine turns open to obtain the desired operation point.
Example

1. 3250 CFM
2. 1.4 iwg
3. Using the supply air blower performance table below, the following data point was located: 1100 RPM and 1.8 BHP.
4. Using the RPM selection table below, Model X is found.
5. 1.8 BHP exceeds the maximum continuous BHP rating of the 1.5 HP motor. The 2 HP motor is required.
6. 1100 RPM is within the range of the 2 HP drives.
7. Using the 2 HP motor and drive, 1 turn open will achieve 1128 RPM.

Airflow performance
Example supply air blower performance
Available External Static Pressure - IWG
(CFM) 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard 1.5 HP and Drive High Static 2 HP and Drive

3000 696 0.9 757 1.1 822 1.2 891 1.3 961 1.3 1019 1.5 1077 1.6 1135 1.8
3250 729 1.1 790 1.3 855 1.4 924 1.5 984 1.6 1042 1.7 1100 1.8 1159 2.0
3500 766 1.3 826 1.5 892 1.6 953 1.6 1010 1.8 1069 1.9 1127 2.0

RPM selection
Max Motor Blower 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn Fully
Unit model HP
BHP sheave sheave Open Open Open Open Open Open Closed
Std. 1.5 1.73 1VL40 AK69 N/A 690 743 796 849 902 955
X
HS 2 2.30 1VL40 AK56 N/A 863 929 995 1062 1128 1194

Johnson Controls Ducted Systems 65


505429-JTG-NN-1222

Sound performance

Outdoor sound power levels (dB), 60 Hz


Size Sound Octave Bands (Hz)
Model
(ton) Rating1 63 125 250 500 1000 2000 4000 8000
J07 PE 83 75 81 82 81 79 73 68 62
(7.5) YE 83 77 88 83 82 79 73 68 64
PC 88.0 87.0 92.5 86.0 86.0 83.5 79.5 74.5 69.5
J10
YC 90.5 92.5 91.0 92.5 89.0 84.5 80.5 76.5 72.5
(10.0)
YD 90 92 89 91 88 85 80 77 71
J12 YC 91 96 88 90 89 86 82 77 71
(12.5) YD 91 92 92 92 89 86 81 78 73
PC 93 93 96 93 90 89 84 77 71
J15 PD 93 93 96 93 90 89 84 77 71
(15.0) YC 89 88 90 89 87 84 81 77 72
YD 93 93 96 93 90 89 84 77 71
PD 93 93 96 93 90 89 84 77 71
J20
YC 93 93 96 93 90 89 84 77 71
(20.0)
YD 93 93 96 93 90 89 84 77 71
J25
YC 93 93 96 93 90 89 84 77 71
(25.0)
1 Rated in accordance with AHRI 270 Standard.

66 Johnson Controls Ducted Systems


505429-JTG-NN-1222

Electrical data
Electrical data for outdoor models

Electrical data - outdoor unit - AC without powered convenience outlet


Pwr
Compressors Compressor #1 Compressor #2 Outdoor Fan Motor Conv Minimum Maximum
Model Outlet Circuit Fuse Size
Power RLA MCC LRA RLA MCC LRA Power FLA Ampacity1 (A)2
Qty HP Qty FLA
Supply (each) (each) (each) (each) (each) (each) Supply (each)
208/230-3-60 1 26.9 41.9 164 - - - 208/230-1-60 1/3 2 1.65 - 36.9 50
J07YE 460-3-60 1 13.4 18.7 94 - - - 460-1-60 1/3 2 1.1 - 19.0 25
575-3-60 1 10 14 65 - - - 575-1-60 1/3 2 0.65 - 13.8 20
208/230-3-60 1 32.6 50.8 240 - - - 208/230-1-60 3/4 2 3 - 46.4 60
J10YC 460-3-60 1 14.8 23.1 130 - - - 460-1-60 3/4 2 1.6 - 21.7 30
575-3-60 1 11.1 17.3 93.7 - - - 575-1-60 3/4 2 1.4 - 16.3 25
208/230-3-60 2 12.8 20 120.4 19.6 31 136 208/230-1-60 3/4 2 2.8 - 42.9 60
J10YD 460-3-60 2 6.4 10 55.1 8.2 13 66.1 460-1-60 3/4 2 1.6 - 19.9 25
575-3-60 2 5.4 9 41 6.6 10 55.3 575-1-60 3/4 2 1.2 - 16.1 20
208/230-3-60 2 22.4 35 149 22.4 35 149 208/230-1-60 3/4 2 2.8 - 56.0 70
J12YC 460-3-60 2 10.6 17 75 10.6 17 75 460-1-60 3/4 2 1.6 - 27.1 35
575-3-60 2 7.7 12 54 7.7 12 54 575-1-60 3/4 2 1.2 - 19.7 25
208/230-3-60 2 19.6 31 136 22.4 35 149 208/230-1-60 3/4 2 2.8 - 53.2 70
J12YD 460-3-60 2 8.2 13 66.1 10.6 17 75 460-1-60 3/4 2 1.6 - 24.7 35
575-3-60 2 6.6 10 55.3 7.7 12 54 575-1-60 3/4 2 1.2 - 18.6 25
208/230-3-60 2 25 39 164 25 39 164 208/230-1-60 3/4 4 1.65 - 59.6 80
J15YC 460-3-60 2 12.2 19 100 12.2 19 100 460-1-60 3/4 4 1.1 - 29.7 40
575-3-60 2 9 14 78 9 14 78 575-1-60 3/4 4 0.65 - 21.6 30
208/230-3-60 2 25 39 164 25 39 164 208/230-1-60 3/4 4 2.8 - 61.9 80
J15YD 460-3-60 2 12.2 19 100 12.2 19 100 460-1-60 3/4 4 1.6 - 30.7 40
575-3-60 2 9 14 78 9 14 78 575-1-60 3/4 4 1.2 - 22.7 30
208/230-3-60 2 29.6 207.5 46 34.6 54 255 208/230-1-60 3/4 4 2.8 - 78.5 100
J20YC 460-3-60 2 13.9 100.2 22 16 25 140 460-1-60 3/4 4 1.6 - 37.1 50
575-3-60 2 10.1 78 16 12.7 19.8 107.6 575-1-60 3/4 4 1.2 - 28.4 40
208/230-3-60 2 30.1 47 225 30.1 47 225 208/230-1-60 3/4 4 2.8 - 73.3 100
J20YD 460-3-60 2 16.7 26 114 16.7 26 114 460-1-60 3/4 4 1.6 - 41 50
575-3-60 2 12.2 19 80 12.2 19 80 575-1-60 3/4 4 1.2 - 29.9 40
208/230-3-60 2 41.9 270 65 41.9 270 65 208/230-1-60 3/4 4 2.8 - 99.9 125
J25YC 460-3-60 2 20.1 147 31 20.1 147 31 460-1-60 3/4 4 1.6 - 48.4 60
575-3-60 2 17.7 109 28 17.7 109 28 575-1-60 3/4 4 1.2 - 42.2 50
1
Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.
2 Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.

Johnson Controls Ducted Systems 67


505429-JTG-NN-1222

Electrical data - outdoor unit - AC with powered convenience outlet


Pwr Conv
Compressors Compressor #1 Compressor #2 Outdoor Fan Motor Minimum Maximum
Outlet
Model Circuit Fuse Size
Power RLA MCC LRA RLA MCC LRA Power FLA Ampacity1 (A)2
Qty HP Qty FLA
Supply (each) (each) (each) (each) (each) (each) Supply (each)
208/230-3-60 1 26.9 41.9 164 - - - 208/230-1-60 1/3 2 1.65 20 46.9 60
J07YE 460-3-60 1 13.4 18.7 94 - - - 460-1-60 1/3 2 1.1 20 24.0 30
575-3-60 1 10 14 65 - - - 575-1-60 1/3 2 0.65 20 17.8 25
208/230-3-60 1 32.6 50.8 240 - - - 208/230-1-60 3/4 2 3.0 20 56.4 80
J10YC 460-3-60 1 14.8 23.1 130 - - - 460-1-60 3/4 2 1.6 20 26.7 35
575-3-60 1 11.1 17.3 93.7 - - - 575-1-60 3/4 2 1.4 20 20.3 30
208/230-3-60 2 12.8 20 120.4 19.6 31 136 208/230-1-60 3/4 2 2.8 20 52.9 70
J10YD 460-3-60 2 6.4 10 55.1 8.2 13 66.1 460-1-60 3/4 2 1.6 20 24.9 30
575-3-60 2 5.4 9 41 6.6 10 55.3 575-1-60 3/4 2 1.2 20 20.1 25
208/230-3-60 2 22.4 35 149 22.4 35 149 208/230-1-60 3/4 2 2.8 20 66.0 80
J12YC 460-3-60 2 10.6 17 75 10.6 17 75 460-1-60 3/4 2 1.6 20 32.1 40
575-3-60 2 7.7 12 54 7.7 12 54 575-1-60 3/4 2 1.2 20 23.7 30
208/230-3-60 2 19.6 31 136 22.4 35 149 208/230-1-60 3/4 2 2.8 20 63.2 80
J12YD 460-3-60 2 8.2 13 66.1 10.6 17 75 460-1-60 3/4 2 1.6 20 29.7 40
575-3-60 2 6.6 10 55.3 7.7 12 54 575-1-60 3/4 2 1.2 20 22.6 30
208/230-3-60 2 25.0 39 164 25 39 164 208/230-1-60 3/4 4 1.65 20 69.6 90
J15YC 460-3-60 2 12.2 19 100 12.2 19 100 460-1-60 3/4 4 1.1 20 34.7 45
575-3-60 2 9.0 14 78 9 14 78 575-1-60 3/4 4 0.65 20 25.6 30
208/230-3-60 2 25 39 164 25 39 164 208/230-1-60 3/4 4 2.8 20 71.9 90
J15YD 460-3-60 2 12.2 19 100 12.2 19 100 460-1-60 3/4 4 1.6 20 35.7 45
575-3-60 2 9 14 78 9 14 78 575-1-60 3/4 4 1.2 20 26.7 35
208/230-3-60 2 29.6 207.5 46 34.6 54 255 208/230-1-60 3/4 4 2.8 20 88.5 110
J20YC 460-3-60 2 13.9 100.2 22 16 25 140 460-1-60 3/4 4 1.6 20 42.1 50
575-3-60 2 10.1 78 16 12.7 19.8 107.6 575-1-60 3/4 4 1.2 20 32.4 45
208/230-3-60 2 30.1 47 225 30.1 47 225 208/230-1-60 3/4 4 2.8 20 83.3 110
J20YD 460-3-60 2 16.7 26 114 16.7 26 114 460-1-60 3/4 4 1.6 20 45.8 60
575-3-60 2 12.2 19 80 12.2 19 80 575-1-60 3/4 4 1.2 20 33.9 45
208/230-3-60 2 41.9 270 65 41.9 270 65 208/230-1-60 3/4 4 2.8 20 109.9 150
J25YC 460-3-60 2 20.1 147 31 20.1 147 31 460-1-60 3/4 4 1.6 20 53.4 70
575-3-60 2 17.7 109 28 17.7 109 28 575-1-60 3/4 4 1.2 20 46.2 60
1 Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.
2
Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.

68 Johnson Controls Ducted Systems


505429-JTG-NN-1222

Electrical data - outdoor unit - HP without powered convenience outlet


Compressors Compressor #1 Compressor #2 Outdoor Fan Motor Pwr Conv Outlet Minimum Maximum
Model Power RLA MCC LRA RLA MCC LRA Power FLA Circuit Fuse Size
Supply
Qty
(each) (each) (each) (each) (each) (each) Supply
HP Qty
(each)
FLA Ampacity1 (A)2

208/230-3-60 1 25.3 39.5 184 - - - 208/230-1-60 1/3 2 1.65 - 34.9 45


J07PE
460-3-60 1 9.6 15 84 - - - 460-1-60 1/3 2 1.1 - 14.2 20
208/230-3-60 2 15.7 24.5 110 15.7 24.5 110 208/230-1-60 3/4 2 2.8 - 41.6 50
J10PC
460-3-60 2 7.7 12 52 7.7 12 52 460-1-60 3/4 2 1.6 - 20.8 25
208/230-3-60 2 25 39 164 25 39 164 208/230-1-60 1/3 4 1.65 - 59.6 80
J15PC
460-3-60 2 12.2 19 100 12.2 19 100 460-1-60 1/3 4 1.1 - 29.7 40
208/230-3-60 2 25 39 164 25 39 164 208/230-1-60 1/3 4 1.65 - 59.6 80
J15PD
460-3-60 2 12.2 19 100 12.2 19 100 460-1-60 1/3 4 1.1 - 29.7 40
208/230-3-60 2 30.1 47 225 30.1 47 225 208/230-1-60 3/4 4 2.8 - 73.3 100
J20PD
460-3-60 2 16.7 26 114 16.7 26 114 460-1-60 3/4 4 1.6 - 41 50
1
Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.
2 Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.

Electrical data - outdoor unit - HP with powered convenience outlet


Compressors Compressor #1 Compressor #2 Outdoor Fan Motor Pwr Conv Outlet Minimum Maximum
Model Power RLA MCC LRA RLA MCC LRA Power FLA Circuit Fuse Size
Supply
Qty
(each) (each) (each) (each) (each) (each) Supply
HP Qty
(each)
FLA Ampacity1 (A)2

208/230-3-60 1 25.3 39.5 184 - - - 208/230-1-60 1/3 2 1.65 20 44.9 60


J07PE
460-3-60 1 9.6 15 84 - - - 460-1-60 1/3 2 1.1 20 19.2 25
208/230-3-60 2 15.7 24.5 110 15.7 24.5 110 208/230-1-60 3/4 2 2.8 20 51.6 60
J10PC
460-3-60 2 7.7 12 52 7.7 12 52 460-1-60 3/4 2 1.6 20 25.8 30
208/230-3-60 2 25 39 164 25 39 164 208/230-1-60 1/3 4 1.65 20 69.6 90
J15PC
460-3-60 2 12.2 19 100 12.2 19 100 460-1-60 1/3 4 1.1 20 34.7 45
208/230-3-60 2 25 39 164 25 39 164 208/230-1-60 1/3 4 1.65 20 69.6 90
J15PD
460-3-60 2 12.2 19 100 12.2 19 100 460-1-60 1/3 4 1.1 20 34.7 45
208/230-3-60 2 30.1 47 225 30.1 47 225 208/230-1-60 3/4 4 2.8 20 83.3 110
J20PD
460-3-60 2 16.7 26 114 16.7 26 114 460-1-60 3/4 4 1.6 20 46 60
1
Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.
2
Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.

Johnson Controls Ducted Systems 69


505429-JTG-NN-1222

Electrical data for indoor models

Supply
Max Fuse2/
Blower Electric Heat Option MCA1
Motor HP Power Supply Motor Breaker3 Size
(Amps)
(Amps)
FLA Model KW Stages Amps
J07NL C00B (INTELLISPEED)
None --- --- --- 5.4 15
10 KW 7.5 1 20.8 31.4 35
208-3-60 4.3 16 KW 12 2 33.4 47.0 50
26 KW 19.5 2 54.2 73.0 80
36 KW 27 2 75.1 99.1 100
None --- --- --- 5.3 15
10 KW 10 1 24.1 35.3 40
230-3-60 4.2 16 KW 16 2 38.5 53.4 60
26 KW 26 2 62.5 83.4 90
36 KW 36 2 86.6 113.5 125
1.5
None --- --- --- 2.6 15
10 KW 10 1 12.0 17.7 20
460-3-60 2.1 16 KW 16 2 19.2 26.7 30
26 KW 26 2 31.3 41.7 45
36 KW 36 2 43.3 56.8 60
None --- --- --- 2.3 15
10 KW 10 1 9.6 14.3 15
575-3-60 1.8 16 KW 16 2 15.4 21.5 25
26 KW 26 2 25.0 33.5 35
36 KW 36 2 34.6 45.6 50
J10 (NL/NM) C00C (INTELLISPEED)
None --- --- --- 7.3 15
10 KW 7.5 1 20.8 33.3 35
208-3-60 5.8 16 KW 12 2 33.4 48.9 50
26 KW 19.5 2 54.2 74.9 80
36 KW 27 2 75.1 100.9 110
None --- --- --- 7.3 15
10 KW 10 1 24.1 37.3 40
230-3-60 5.8 16 KW 16 2 38.5 55.4 60
26 KW 26 2 62.5 85.4 90
36 KW 36 2 86.6 115.5 125
2.0
None --- --- --- 3.6 15
10 KW 10 1 12.0 18.7 20
460-3-60 2.9 16 KW 16 2 19.2 27.7 30
26 KW 26 2 31.3 42.7 45
36 KW 36 2 43.3 57.8 60
None --- --- --- 2.8 15
10 KW 10 1 9.6 14.8 15
575-3-60 2.2 16 KW 16 2 15.4 22 25
26 KW 26 2 25.0 34 35
36 KW 36 2 34.6 46.1 50

70 Johnson Controls Ducted Systems


505429-JTG-NN-1222

Supply
Max Fuse2/
Blower Electric Heat Option MCA1
Motor HP Power Supply Motor Breaker3 Size
(Amps)
(Amps)
FLA Model KW Stages Amps
J15 (NL/NM) C00D (INTELLISPEED)
None --- --- --- 10.4 15
10 KW 7.5 1 20.8 36.4 40
16 KW 12 2 33.4 52 60
208-3-60 8.3
26 KW 19.5 2 54.2 78 80
36 KW 27 2 75.1 104.1 110
50 KW4 37.6 2 104.2 140.8 150
None --- --- --- 10.3 15
10 KW 10 1 24.1 40.3 45
16 KW 16 2 38.5 58.4 60
230-3-60 8.2
26 KW 26 2 62.5 88.4 90
36 KW 36 2 86.6 118.5 125
50 KW4 50 2 120.3 130.5 150
3.0
None --- --- --- 5.1 15
10 KW 10 1 12 20.2 25
16 KW 16 2 19.2 29.2 30
460-3-60 4.1
26 KW 26 2 31.3 44.2 45
36 KW 36 2 43.3 59.3 60
50 KW4 50 2 60.1 65.3 70
None --- --- --- 4 15
10 KW 10 1 9.6 16 20
16 KW 16 2 15.4 23.2 25
575-3-60 3.2
26 KW 26 2 25 35.3 40
36 KW 36 2 34.6 47.3 50
50 KW 50 2 48.1 52.1 60
J15 (NL/NM) C00E (INTELLISPEED)
None --- --- --- 16.9 20
10 KW 7.5 1 20.8 42.9 45
16 KW 12 2 33.4 58.5 60
208-3-60 13.5
26 KW 19.5 2 54.2 84.5 90
36 KW 27 2 75.1 110.6 125
50 KW 37.6 2 104.2 147.3 150
None --- --- --- 16.3 20
10 KW 10 1 24.1 46.3 50
16 KW 16 2 38.5 64.4 70
230-3-60 13.0
26 KW 26 2 62.5 94.4 100
36 KW 36 2 86.6 124.5 125
50 KW 50 2 120.3 136.5 150
5.0
None --- --- --- 8.1 15
10 KW 10 1 12.0 23.2 25
16 KW 16 2 19.2 32.2 35
460-3-60 6.5
26 KW 26 2 31.3 47.2 50
36 KW 36 2 43.3 62.3 70
50 KW 50 2 60.1 68.3 70
None --- --- --- 6.5 15
10 KW 10 1 9.6 18.5 20
16 KW 16 2 15.4 25.7 30
575-3-60 5.2
26 KW 26 2 25.0 37.8 40
36 KW 36 2 34.6 49.8 50
50 KW 50 2 48.1 54.6 60

Johnson Controls Ducted Systems 71


505429-JTG-NN-1222

Supply
Max Fuse2/
Blower Electric Heat Option MCA1
Motor HP Power Supply Motor Breaker3 Size
(Amps)
(Amps)
FLA Model KW Stages Amps
J20 (NL/NM) C00E (INTELLISPEED)
None --- --- --- 16.9 20
20 KW 15 1 41.6 68.9 70
208-3-60 13.5
32 KW 24 2 66.6 100.1 110
52 KW 39.1 2 108.5 152.5 175
None -- --- --- 16.3 20
20 KW 20 1 48.1 76.4 80
230-3-60 13.0
32 KW 32 2 77.0 112.5 125
52 KW 52 2 125.1 141.3 150
5.0
None --- --- --- 8.1 15
20 KW 20 1 24.1 38.2 40
460-3-60 6.5
32 KW 32 2 38.5 56.2 60
52 KW 52 2 62.5 70.7 80
None --- --- --- 6.5 15
20 KW 20 1 19.2 30.6 35
575-3-60 5.2
32 KW 32 2 30.8 45.0 45
52 KW 52 2 50.0 56.5 60

J25NC C00N5
208-3-60 16.7 None --- --- --- 21.0 35
230-3-60 15.2 None --- --- --- 19.0 30
5.0
460-3-60 7.6 None --- --- --- 10.0 15
575-3-60 6.1 None --- --- --- 8.0 15
J20 (NL/NM) C00F (INTELLISPEED)
None --- --- --- 25.0 25
20 KW 15 1 41.6 77.0 80
208-3-60 20.0
32 KW 24 2 66.6 108.3 110
52 KW 39.1 2 108.5 160.7 175
None -- --- --- 24.3 25
20 KW 20 1 48.1 84.4 90
230-3-60 19.4
32 KW 32 2 77.0 120.52 125
52 KW 52 2 125.1 149.3 150
7.5
None --- --- --- 12.1 15
20 KW 20 1 24.1 42.2 45
460-3-60 9.7
32 KW 32 2 38.5 60.2 70
52 KW 52 2 62.5 74.7 80
None --- --- --- 9.8 15
20 KW 20 1 19.2 33.8 35
575-3-60 7.8
32 KW 32 2 30.8 48.2 50
52 KW 52 2 50.0 59.8 60
J25NC C00N5
208-3-60 24.2 None --- --- --- 30.0 35
230-3-60 22.0 None --- --- --- 28.0 30
7.5
460-3-60 11.0 None --- --- --- 14.0 15
575-3-60 9.0 None --- --- --- 11.0 20
1 Minimum Circuit Ampacity.
2 Dual Element, Time Delay Type.
3 HACR type per NEC.
4 J15NC/NDC00D Models Only
5 Motors are not shipped with these models. Motor and Drive Kits are required.

72 Johnson Controls Ducted Systems


505429-JTG-NN-1222

Typical wiring diagrams


Air conditioning condensing units

Typical J07YE wiring diagram

ELEMENTARY DIAGRAM

G5829906A REV A SHT 1 OF 2


CAUTION - OPEN ALL DISCONNECTS
BEFORE SERVICING THIS UNIT.
L
K
J
H
G
F
E
D
C
B
A

Johnson Controls Ducted Systems 73


74
A B C D E F G H J K L

ELEMENTARY DIAGRAM
505429-JTG-NN-1222

Typical J10YC wiring diagram

CAUTION - OPEN ALL DISCONNECTS


BEFORE SERVICING THIS UNIT.
G6151575A REV A SHT 1 OF 2

Johnson Controls Ducted Systems


A B C D E F G H J K L

ELEMENTARY DIAGRAM

Johnson Controls Ducted Systems


Typical J12YC wiring diagram

CAUTION - OPEN ALL DISCONNECTS


BEFORE SERVICING THIS UNIT.
G5829894A REV A SHT 1 OF 2

75
505429-JTG-NN-1222
76
A B C D E F G H J K L
505429-JTG-NN-1222

Typical J10 - 12YD wiring diagram

CAUTION - OPEN ALL DISCONNECTS


BEFORE SERVICING THIS UNIT.
G5829899A REV A SHT 1 OF 2

Johnson Controls Ducted Systems


A B C D E F G H J K L

ELEMENTARY DIAGRAM

Johnson Controls Ducted Systems


Typical J15YC wiring diagram

CAUTION - OPEN ALL DISCONNECTS


BEFORE SERVICING THIS UNIT.
G5829895A REV A SHT 1 OF 2

77
505429-JTG-NN-1222
78
A B C D E F G H J K L

ELEMENTARY DIAGRAM
505429-JTG-NN-1222

Typical J20YC wiring diagram

CAUTION - OPEN ALL DISCONNECTS


BEFORE SERVICING THIS UNIT.
G5829896A REV A SHT 1 OF 2

Johnson Controls Ducted Systems


A B C D E F G H J K L

ELEMENTARY DIAGRAM

Johnson Controls Ducted Systems


Typical J25YC wiring diagram

CAUTION - OPEN ALL DISCONNECTS


BEFORE SERVICING THIS UNIT.
G5829897A REV A SHT 1 OF 2

79
505429-JTG-NN-1222
80
A B C D E F G H J K L

ELEMENTARY DIAGRAM
505429-JTG-NN-1222

Typical J15 - 20YD wiring diagram

CAUTION - OPEN ALL DISCONNECTS


BEFORE SERVICING THIS UNIT.
G5829900A REV A SHT 1 OF 2

Johnson Controls Ducted Systems


A B C D E F G H J K L

ELEMENTARY DIAGRAM
Heat pump units

Johnson Controls Ducted Systems


Typical J07PE wiring diagram

CAUTION - OPEN ALL DISCONNECTS


BEFORE SERVICING THIS UNIT.
G5829907A REV A SHT 1 OF 2

81
505429-JTG-NN-1222
82
A B C D E F G H J K L

ELEMENTARY DIAGRAM
505429-JTG-NN-1222

Typical J10PC wiring diagram

CAUTION - OPEN ALL DISCONNECTS


BEFORE SERVICING THIS UNIT.
G5829902A REV A SHT 1 OF 2

Johnson Controls Ducted Systems


A B C D E F G H J K L

ELEMENTARY DIAGRAM

Johnson Controls Ducted Systems


Typical J15PC wiring diagram

CAUTION - OPEN ALL DISCONNECTS


BEFORE SERVICING THIS UNIT.
G5829903A REV A SHT 1 OF 2

83
505429-JTG-NN-1222
84
A B C D E F G H J K L

ELEMENTARY DIAGRAM
505429-JTG-NN-1222

Typical J15 - 20PD wiring diagram

CAUTION - OPEN ALL DISCONNECTS


BEFORE SERVICING THIS UNIT.
G5829904A REV A SHT 1 OF 2

Johnson Controls Ducted Systems


A B C D E F G H J K L

ELEMENTARY DIAGRAM
Typical J25YC, Rawal 2 Pipe

Johnson Controls Ducted Systems


CAUTION - OPEN ALL DISCONNECTS
BEFORE SERVICING THIS UNIT.
G5829898A REV A SHT 1 OF 2

85
505429-JTG-NN-1222
505429-JTG-NN-1222

Component map

M3 M4

PHS

LAC1 LAC2

*CB4
TB1

RC1

RC2

RC3

RC4
FS1 FS2

*DISC
T1
UCB
RW1
SEE DETAIL A T2
TB3

GND2

TB2
M1 M2
*FDD
AUX 4
CCHR1
SEE DETAIL B
TB2
DETAIL B
TB2
TB2
AUX 1 AUX 2 AUX 3

TB3-2

NOTE:
TB3-3 TB3-1
1. UNIT MAY NOT HAVE ALL COMPONENTS
DETAIL A
SHOWN, DEPENDING ON MODEL AND
TB3-1/2/3
OPTIONS INSTALLED.

2. COMPONENTS DESIGNATED WITH A (*)


ARE OPTIONAL ITEMS. COMPONENT MAP
G6161070A REV A

86 Johnson Controls Ducted Systems


A B C D E F G

ELEMENTARY DIAGRAM
Air handling units

Johnson Controls Ducted Systems


Typical J07NL wiring diagram

CAUTION - OPEN ALL DISCONNECTS


BEFORE SERVICING THIS UNIT.
G5850399A REV A SHT 1 OF 1

87
505429-JTG-NN-1222
505429-JTG-NN-1222

Typical J10 to 20NL, 1.5 to 5 HP blower motor only wiring diagram (10 ton - 2 pipe unit manufactured prior to January
1, 2023)

G6232402A REV B SHT 1 OF 1


ELEMENTARY DIAGRAM

CAUTION - OPEN ALL DISCONNECTS


BEFORE SERVICING THIS UNIT.
G
F
E
D
C
B
A

88 Johnson Controls Ducted Systems


505429-JTG-NN-1222

Typical J10NL, 2 to 3 HP blower motor only wiring diagram (10 ton - 2 pipe unit manufactured after January 1, 2023)

G6255405A REV B SHT 1 OF 1


ELEMENTARY DIAGRAM

CAUTION - OPEN ALL DISCONNECTS


BEFORE SERVICING THIS UNIT.
G
F
E
D
C
B
A

Johnson Controls Ducted Systems 89


505429-JTG-NN-1222

Typical J20NL, 7.5 HP blower motor 208/230 V only wiring diagram

G5850401A REV A SHT 1 OF 1


ELEMENTARY DIAGRAM

CAUTION - OPEN ALL DISCONNECTS


BEFORE SERVICING THIS UNIT.
G
F
E
D
C
B
A

90 Johnson Controls Ducted Systems


505429-JTG-NN-1222

Typical J20NL, 7.5 HP blower motor 460/575 V only wiring diagram

G5850402A REV A SHT 1 OF 1


ELEMENTARY DIAGRAM

CAUTION - OPEN ALL DISCONNECTS


BEFORE SERVICING THIS UNIT.
G
F
E
D
C
B
A

Johnson Controls Ducted Systems 91


505429-JTG-NN-1222

Typical J20NM, 7.5 HP Blower motor 208/230 V only wiring diagram

G5850403A REV A SHT 1 OF 1


ELEMENTARY DIAGRAM

CAUTION - OPEN ALL DISCONNECTS


BEFORE SERVICING THIS UNIT.
G
F
E
D
C
B
A

92 Johnson Controls Ducted Systems


505429-JTG-NN-1222

Typical J20NM, 7.5 HP blower motor 460/575 V only wiring diagram

G5850404A REV A SHT 1 OF 1


ELEMENTARY DIAGRAM

CAUTION - OPEN ALL DISCONNECTS


BEFORE SERVICING THIS UNIT.
G
F
E
D
C
B
A

Johnson Controls Ducted Systems 93


94
A B C D E F G H J K L

ELEMENTARY DIAGRAM
505429-JTG-NN-1222

Typical J25NC wiring diagram

CAUTION - OPEN ALL DISCONNECTS


BEFORE SERVICING THIS UNIT.
G5508518A REV C SHT 1 OF 1

Johnson Controls Ducted Systems


505429-JTG-NN-1222

Weights and dimensions

Corner weights and center of gravity AC/HP units


Weight (lbs.) Center of Gravity (in.) 4 Point Load Location (lbs.)
Model
Shipping Operating X Y A B C D
J07PE 445 442 16.25 32.5 119.9 125.6 100.5 95.9
J10PC 543 574 16.4 32.3 153 161 134 127
J15PC 947 968 32.5 33 266 274 217 211
J15PD 921 942 34 32.5 243 275 225 199
J20PD 1090 1126 31.2 31.8 311 295 253 267
J07YE 386 383 18 33.5 95.0 124.3 92.8 70.9
J10YC 433 430 18 33 105 135 107 83
J10YD 473 470 17.0 32.4 120 137 113 99
J12YC 499 497 17 32.3 127 145 120 105
J12YD 511 508 16.8 33.4 136 151 116 105
J15YC 914 909 32.5 31.5 239 246 215 209
J15YD 903 898 32.5 31.5 236 243 213 207
J20YC 913 910 31.2 33.0 261 248 195 206
J20YD 930 927 32.7 31.8 244 255 218 210
J25YC 945 942 30.3 31 261 234 212 236

LEFT

D A

LEFT

DIM X
D A
DIM X CG
CG
FRONT REAR FRONT REAR

WIDTH

C B
WIDTH
DIM Y

LENGTH

RIGHT C B
J07PE, J10PC,
J07YE, J10YC, J10YD, DIM Y
J12YC, J12YD LENGTH

RIGHT

J15PC, J15PD,
J20PC, J20PD,
J15YC, J15YD,
J20YC, J20YD
J25YC

Note: The front of unit is considered the side with the unit control box.

Johnson Controls Ducted Systems 95


505429-JTG-NN-1222

RIGHT

31.90
REAR FRONT

LEFT
59.10

CONVENIENCE
OUTLET

BASE RAIL
DETAIL A

2.375 2X (Ø 1.375)
KNOCKOUT
30.994
TOP

1.33 2X (Ø 0.875)
KNOCKOUT

3.43 12.126
3.75 9.876

2.097 4.751

BOTTOM
3.883
7.000 10.000 7.000 7.000 23.000 7.000
2.923 3.664
37.000
24.000 2.933
3.563 31.758 1.664
58.500
FRONT RIGHT

SYSTEM 2

2X (Ø 0.875)
KNOCKOUT

2X (Ø 1.375)
KNOCKOUT
15.53
12.70 12.000
SYSTEM 1 10.000
4.875

6.26
4.132
7.52
8.98 2.382
REAR 10.60 LEFT 1.882

Unit dimensions JJ07PE, J10PC, J07YE, J10YC/YD, J12YC/YD

Unit height dimensions


Model A
J07PE 44.5
J10PC 50.0
J07YE 44.5
J10YC 50.0
J10YD 50.0
J12YC 50.0
J12YD 50.0

96 Johnson Controls Ducted Systems


505429-JTG-NN-1222

REAR

59.10
LEFT RIGHT

FRONT
64.10

BASE RAIL
DETAIL

A
2.375 SYSTEM 2

SYSTEM 1
TOP 2X (Ø 1.375)
30.994 KNOCKOUT
1.33

2X (Ø 0.875)
3.43 KNOCKOUT
3.75 11.375
9.125
2.097 4.750

BOTTOM 4.132
7.000 23.000 7.000 7.000 23.000 7.000
3.913
2.923 37.000 37.000
3.181
64.000 1.913
3.563 59.000

FRONT RIGHT

SYSTEM 2

SYSTEM 1

16.133
13.133

17.367
18.867
20.617
22.617
FRONT
(PIPING DETAIL)

Unit dimensions J15PC/PD, J20PC/PD, J15YC/YD, J20YC/YD

Piping and electrical connection sizes (in.)


Model J07PE J10PC J07YE J10YC J10YD J12YC J12YD
No. Refrigeration Circuits 1 1 1 1 2 1 2
Suction Line OD (in.) 1 1/8 1 3/8 1 3/8 1 3/8 1 1/8 1 3/8 1 1/8
Liquid Line OD (in.) 5/8 7/8 5/8 7/8 5/8 7/8 5/8
Power Wiring Knockout 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8
Control Wiring Knockout 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8

Model J15PC J15PD J20PD J15YC J15YD J20YC J20YD J25YC


No. Refrigeration Circuits 1 2 2 1 2 1 2 1
Suction Line OD (in.) 1 5/8 1 3/8 1 3/8 1 5/8 1 1/8 1 5/8 1 3/8 1 5/8
Liquid Line OD (in.) 7/8 5/8 5/8 7/8 5/8 7/8 5/8 7/8
Power Wiring Knockout 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8
Control Wiring Knockout 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8

Johnson Controls Ducted Systems 97


505429-JTG-NN-1222

Unit height dimensions


Model A
J15PC 44.5
J15PD 44.5
J20PD 50.0
J15YC 44.5
J15YD 44.5
J20YC 50.0
J20YD 50.0
J25YC 50.0

Piping and electrical connections


Piping connections are made from the rear of 7.5 to 12.5 ton units and the front of 15 to 20 ton units. Connections can be made
directly to the suction and liquid line service valves.

With the piping connections being made at the rear of 7.5 to 12.5 ton units and the front of 15 to 20 ton units, the piping can be
routed to the units from the left or right side.

Electrical connections for power and control wiring are made from the front of the units, right or left of 7.5 to 12.5 ton electrical
control box access or left of the electrical control box access on 15 to 20 ton units. See Unit dimensions and piping and
electrical connection sizes tables for piping sizes and electrical knockout details.

Minimum clearances
Clearance description Distance (in.)
Overhead (Top) 120
Front 36
Rear 24
Left Side 30
Right Side 30
Bottom1 0
1 In all installations where snow accumulates and winter operation is
expected, additional height must be provided to insure normal
condenser airflow.

98 Johnson Controls Ducted Systems


505429-JTG-NN-1222

Corner weights and center of gravity J07 to 20Nl/NM units


Drive Shipping Operating Center of Gravity 4 point Load Location (lb) 6 point Load Location (lb)
Model
Option Wt (lb) Wt (lb) CG X CG Y A B C D A B C D E F
Vertical Airflow
Std. Mtr. and Drv. 542 516 16.2 26.5 113 132 146 125 73 81 90 100 90 81
J07NL
High Static Mtr. and Drv. 549 523 16.2 26.5 114 133 148 127 74 82 91 102 91 83
Std. Mtr. and Drv. 586 563 15.4 26.6 130 138 152 143 86 89 93 102 98 95
J10NL
High Static Mtr. and Drv. 597 574 15.4 26.6 132 140 155 146 87 91 94 104 100 97
Std. Mtr. and Drv. 588 565 15.4 26.8 131 139 152 143 87 90 94 102 98 94
J10NM
High Static Mtr. and Drv. 599 576 15.4 26.8 133 141 155 146 88 92 95 104 100 96
Std. Mtr. and Drv. 794 762 17.9 34.3 161 191 223 188 104 116 131 153 136 122
J15NL
High Static Mtr. and Drv. 820 788 17.9 34.3 166 197 231 195 108 120 135 158 141 126
Std. Mtr. and Drv. 794 762 17.9 34.3 161 191 223 188 104 116 131 153 136 122
J15NM
High Static Mtr. and Drv. 820 788 17.9 34.3 166 197 231 195 108 120 135 158 141 126
Std. Mtr. and Drv. 932 897 15.7 42.4 184 202 267 244 121 128 136 180 170 160
J20NL
High Static Mtr. and Drv. 963 928 15.6 42.3 191 207 276 254 125 132 140 187 176 167
Std. Mtr. and Drv. 932 897 15.7 42.4 184 202 267 244 121 128 136 180 170 160
J20NM
High Static Mtr. and Drv. 963 928 15.6 42.3 191 207 276 254 125 132 140 187 176 167
Horizontal Airflow
Std. Mtr. and Drv. 542 516 30.6 26.5 120 125 138 133 79 82 84 93 91 88
J07NL
High Static Mtr. and Drv. 549 523 30.8 26.5 121 127 141 134 80 83 86 95 92 89
Std. Mtr. and Drv. 586 563 30.5 26.6 132 136 150 145 87 89 91 101 98 96
J10NL
High Static Mtr. and Drv. 597 574 30.8 26.6 133 140 155 147 88 91 94 104 100 97
Std. Mtr. and Drv. 588 565 30.5 26.8 133 137 150 145 88 90 92 100 98 96
J10NM
High Static Mtr. and Drv. 599 576 30.7 26.8 134 141 154 147 89 92 95 104 100 97
Std. Mtr. and Drv. 794 762 33.7 34.3 172 179 210 201 114 117 121 141 137 133
J15NL
High Static Mtr. and Drv. 820 788 34.3 34.3 174 189 221 204 115 121 127 149 142 135
Std. Mtr. and Drv. 794 762 33.7 34.3 172 179 210 201 114 117 121 141 137 133
J15NM
High Static Mtr. and Drv. 820 788 34.3 34.3 174 189 221 204 115 121 127 149 142 135
Std. Mtr. and Drv. 932 897 30.5 42.4 190 196 259 251 126 129 131 174 170 167
J20NL
High Static Mtr. and Drv. 963 928 30.9 42.3 193 205 273 257 127 133 138 184 176 169
Std. Mtr. and Drv. 932 897 30.5 42.4 190 196 259 251 126 129 131 174 170 167
J20NM
High Static Mtr. and Drv. 963 928 30.9 42.3 193 205 273 257 127 133 138 184 176 169

LEFT
LEFT
A B A B
A B C A B C

WIDTH
WIDTH
CG FRONT CG REAR
FRONT REAR

DIM Y
DIM Y
F E D
F E D D C
D C
DIM X
DIM X LENGTH
LENGTH RIGHT

RIGHT HORIZONTAL POSITION

VERTICAL POSITION

Johnson Controls Ducted Systems 99


505429-JTG-NN-1222

Corner weights and center of gravity J25NC unit


Evaporator Blower Drive Weight Center of 4 Point Load Location 6 Point Load Location
Section Section Section (lbs.) Gravity (lbs.) (lbs.)
Model Drive HP
Cabinet Cabinet Cabinet Ship Opera
CG X CG Y A B C D A B C D E F
Wt (lb) Wt (lb) Wt (lb) ping ting
Vertical Airflow
5 539 463 111 1067 1130 19.0 45.5 296 321 267 247 204 220 194 172 159 180
J25NC
7.5 539 463 138 1067 1157 19.3 45.1 301 335 274 246 206 229 202 179 161 181
Horizontal Airflow
5 539 463 111 1067 1130 35.2 45.5 320 297 247 266 220 204 180 160 172 194
J25NC
7.5 539 463 137.8 1067 1157 35.4 45.1 329 307 252 269 225 210 185 164 176 198
Vertical Airflow With VFD and Intellispeed
5 539 491 111 1067 1158 19.0 45.4 304 329 273 253 209 226 199 176 163 184
J25NC
7.5 539 493 138 1067 1187 19.3 45.1 309 344 281 253 211 235 207 183 165 186
Horizontal Airflow With VFD and Intellispeed
5 539 491 111 1067 1158 35.7 45.4 324 308 256 269 223 212 187 166 174 196
J25NC
7.5 539 493 137.8 1067 1187 35.9 45.1 333 320 262 272 227 218 192 171 178 200

D (E) (D) C D (E) (D) C

CG CG
Y Y
(F) (C) (F) (C)

MOTOR
X X
MOTOR

A (A) (B) B A (A) (B) B

Vertical Horizontal

100 Johnson Controls Ducted Systems


505429-JTG-NN-1222

Top view
Ø 1.72 KNOCKOUT 20.31 Ø 1.718 KNOCKOUT FOR 20.313
ELECTRIC HEAT ELECTRIC HEAT

8.84 8.837

9.25 9.246
13.44
15.920

8.22
5.135

17.59 15.63 14.645 18.628

TOP VIEW - BLOWER OUTLET TOP VIEW - BLOWER OUTLET


7.5 TON INDOOR 10 TON INDOOR

Front and side view


1-1/4 in. CONDUIT 3.66
KNOCKOUT Ø 1.718
POWER ACCESS

4.56
7.06

3/4 in. CONDUIT


KNOCKOUT Ø 1.093
CONTROLS ACCES

65.000

6.38

FIELD PIPING
CONNECTIONS

35.000

SYSTEM 2 17.85
20.531
15.50

13.13
SYSTEM 1
10.73

2.000

DRAIN 3/4 in. ABS 1.88


52.000 2.000 PIPE CONNECTION 7.12

56.000 30.00

FRONT VIEW - RETURN AIR RIGHT SIDE VIEW - DRAIN PIPING/CONTROLS


7.5 - 10 TON INDOOR

Unit dimensions J07/10NL and J10NM

Johnson Controls Ducted Systems 101


505429-JTG-NN-1222

Bottom view

56.00

2.72 50.75 2.72

2.66

AIR IN 11.43

30.00

Horizontal configuration

30.00

35.00

30.00

60.00

Unit dimensions J07/10NL and J10NM (Continued)

102 Johnson Controls Ducted Systems


505429-JTG-NN-1222

Top view
Ø 1.718 KNOCKOUT FOR 23.85
ELECTRIC HEAT

10.00

10.50

18.84

3.79

26.34 21.82

TOP VIEW - BLOWER OUTLET

Front and side view

3.66

4.56
7.06

1-1/4 in. CONDUIT


KNOCKOUT Ø 1.718
POWER ACCESS

3/4 in. CONDUIT


KNOCKOUT Ø 1.093
CONTROLS ACCESS

75.00

6.44

FIELD PIPING
CONNECTIONS
42.00

27.53

SYSTEM 2

SYSTEM 1 17.85
15.50
13.13
10.73

2.00

70.50 2.00
1.88
DRAIN 3/4 in. ABS 7.12
74.50 PIPE CONNECTION

33.00
FRONT VIEW - RETURN AIR
INDOOR
RIGHT SIDE VIEW - DRAIN PIPING/CONTROLS

Unit dimensions J15NL/NM

Johnson Controls Ducted Systems 103


505429-JTG-NN-1222

Bottom view
74.50

2.72 69.25 2.72

2.66

AIR IN 14.43

33.000

Horizontal configuration
33.000

42.000

33.000

66.000

Unit dimensions J15NL/NM (Continued)

104 Johnson Controls Ducted Systems


505429-JTG-NN-1222

Top view
1-1/4 in. CONDUIT KNOCKOUT 1-1/4 in. CONDUIT KNOCKOUT
(Ø 1.718) (Ø 1.718)
ELECTRIC HEAT CONTROL ELECTRIC HEAT POWER
22.86
WIRE CONNECTION CONNECTION

8.83

9.25

15.90
BLOWER OPENING

9.25

4.14 5.14

1-1/4 in. CONDUIT KNOCKOUT 1-1/4 in. CONDUIT KNOCKOUT


(Ø 1.718) (Ø 1.718)
ELECTRIC HEAT POWER ELECTRIC HEAT CONTROL
CONNECTION WIRE CONNECTION

18.63 25.30
BLOWER OPENING
18.63 54.57
BLOWER OPENING
75.64

TOP VIEW BLOWER OUTLET


INDOOR

Front and side view

3.66

4.56
7.06

1-1/4 in. CONDUIT


KNOCKOUT (Ø 1.718)
POWER ACCESS

3/4 in. CONDUIT


KNOCKOUT (Ø 1.093)
CONTROLS ACCESS

65.13

6.44
SYSTEM 2 FIELD PIPING
CONNECTIONS
35.00

19.19

SYSTEM 1
17.85
15.50
13.13
10.73
2.56
1.88

3.56 44.91
2.56 DRAIN 3/4 in. ABS 7.12
PIPE CONNECTION
93.37
30.00
98.50

FRONT VIEW - RETURN AIR


INDOOR
RIGHT SIDE VIEW - DRAIN PIPING/CONTROLS

Unit dimensions J20NL/NM

Johnson Controls Ducted Systems 105


505429-JTG-NN-1222

Bottom view

98.50

2.72 45.38 50.59

45.38 2.72

2.66

AIR IN AIR IN 11.43

30.00

Horizontal configuration

30.00

35.00

30.00

60.00

Unit dimensions J20NL/NM (Continued)

106 Johnson Controls Ducted Systems


505429-JTG-NN-1222

BLOWER

EVAPORATOR
POSITION COIL POSITION POSITION POSITION
1 2 3 4

POSITION POSITION POSITION POSITION


5 6 7 8
Vertical airflow arrangements J07 to 20 NL and J10 to 20NM

POSITION POSITION
POSITION POSITION 7
1 3 5

POSITION POSITION POSITION POSITION


2 4 6 8
Horizontal airflow arrangements J07 to 20NL and J10 to 20NM

Johnson Controls Ducted Systems 107


505429-JTG-NN-1222

Top view

62.37 22.03

22.49 22.02 5.31

5.31

2.58

9.05

3.00
19.03

4X Ø 1.093 K0
CONTROLS
CONNECTION

15.92

Ø 1.375 K0
57.69 ELECTRIC HEAT
CONNECTION

Front and side view

36.69

74.59

Ø 1.38 KO
Ø 0.88 LIQUID
CONNECTION

37.28
33.22 Ø 2.13 SUCTION
CONNECTION

Ø 1.38 KO 24.98
Ø 0.88 DRAIN
CONNECTION

7.64
2.36 3.53

46.97 3.37
0.63 4.08
95.59 4.22
100.13 38.06
FRONT (RETURN AIR) VIEW RIGHT SIDE
(SERVICE CONNECTION) VIEW

Unit dimensions J25NC

108 Johnson Controls Ducted Systems


505429-JTG-NN-1222

Horizontal configuration

RETURN
AIR

SUPPLY
AIR

73.3
74.0
Unit dimensions J25NC (Continued)

1
BLOWER
AIR

2 3

AIR

AIR

AIR
EVAPORATOR AIR AIR
COIL

4 5 6

AIR

AIR

AIR AIR AIR

Vertical airflow arrangements J25NC

Note: *If required, some air can be returned through the bottom of the evaporator section

Johnson Controls Ducted Systems 109


505429-JTG-NN-1222

AIR
7 8 9

AIR
AIR AIR AIR

AIR
AIR
10 11 12

AIR AIR AIR


AIR

AIR
Horizontal airflow arrangements J25NC

Piping, electrical and duct opening connection sizes


Model J07NL J10NL J10NM J15NL J15NM J20NL J20NM J25NL
System data
No. Refrigeration Circuits 1 1 2 1 2 1 2 1
Suction Line OD (in.) 1 1/8 1 3/8 1 1/8 1 5/8 1 3/8 1 5/8 1 3/8 2 1/8
Liquid Line OD (in.) 5/8 7/8 5/8 7/8 5/8 7/8 7/8 7/8
Power Wiring Knockout 1 3/4 1 3/4 1 3/4 1 3/4 1 3/4 1 3/4 1 3/4 7/8
Control Wiring Knockout 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8
Electric Heat Wiring Knockout 1 3/4 1 3/4 1 3/4 1 3/4 1 3/4 1 3/4 1 3/4 7/8
Drain Line Fitting PVC Stub 3/4 3/4 3/4 3/4 3/4 3/4 3/4 7/81
Blower outlet
Number 1 1 1 1 1 2 2 2
Width 13.4 15.9 15.9 18.9 18.9 15.9 15.9 22
Length 15.6 18.6 18.6 21.6 21.6 18.6 18.6 22
Return air inlet
Width 20.5 20.5 20.5 27.3 27.3 19.2 19.2 33.2
Length 52.0 52.0 52.0 71.9 71.9 93.4 93.4 95.6
1 7/8 In Steel pipe

Minimum clearances
Minimum Clearances
Top with Supply Air Opening1 24 in.
Front with Return Air Opening 24 in.
Right Side with access for Piping, Power and
24 in.
Control Wiring Connections2
Left Side 24 in.
Rear3 N/A
Bottom4 N/A
1
This dimension will vary if an electric heater, a supply air
plenum or a base is used.
2 This dimension is required for normal installation and
service.
3
Although no clearance is required for service and
operation, some clearance may be required for routing
the power and control wiring.
4
Allow enough clearance to trap the condensate drain
line.
Note: If the coil has to be removed, the blower section
can be unbolted and set aside and the coil can be
lifted out the top of the evaporator section.

110 Johnson Controls Ducted Systems


505429-JTG-NN-1222

Unit mounting - J07 to 20NL/NM components to suspend an AHU must be field supplied.
Please refer to the units total weight, center of gravity and
The split air handling units can be applied in various corner weights. (Horizontal position) shown in the appropriate
horizontal positions. The Typical Suspension of AHU’s From table for proper support sizing.
Ceiling Figure shows recommended suspension rigging
using properly sized all-thread and metal c-channel. All

END VIEW

MOUNTING DETAIL
All Thread
Steel Rod

Mounting
Bracket

Flat Washer /
Lock Washer
and Nut

Steel C-
channel

SIDE VIEW

Typical suspension of AHU’s from ceiling

Johnson Controls Ducted Systems 111


505429-JTG-NN-1222

Unit mounting - J25NC channels and hardware. The channels extend across the
evaporator coil section, the heating coil section (if included)
The J25NC evaporator blower may be suspended from the and the blower section. Each channel is to be bolted to each
joists with isolation type hangers or hooks. Suspension section as shown.
accessories 1HH0403 (J25NC) may be ordered separately.
All Suspension accessories include three suspension

HORIZONTAL
UNIT SUSPENDED
FROM ABOVE 3
AX BX
D

BX
C
E
VERTICAL UNIT SUPPORTED
3 FROM BELOW
B
BLOWER
F BLOWER
SECTION
1-1/2 SECTION

EVAP . COIL A EVAP.


SECTION COIL
SECTION
U3 O
U HEATING COIL 2 A

E 4 B
C CX
SUSPENSION
ANGLES 1 D
BX
BX

1 The same channels can be used in either position. When used to


support a vertical unit, these channels should be cut to match the
bottom dimension of the evaporator section.

The suspension channels have two sets of mounting holes to


2
accommodate horizontal units with or without a heating coil. On
a horizontal unit without a heating coil, the suspension channels
will extend 3” beyond both ends of the unit.

3 The same channels can be used to support a horizontal, floor-


mounted unit from below.

4 After these bottom channels are cut per Note 1, a new hole will have
to be drilled at the cut end if the unit is to be mounted on isolators.

Typical suspension of J25NC

Unit mounting dimensions- J25NC

Dimensions (in.)
Unit
AX BX CX
J25NC 69-1/4 49-1/16 26-5/8

112 Johnson Controls Ducted Systems


505429-JTG-NN-1222

CONDENSER CONTROL BOX

UCB SE CONTROL BOARD


TB2 VFD COMM THERMOSTAT CONNECTIONS

TB VFD
C S1 S2 G1 G2 66 60 X VFD C W1 W2 Y1 G Y2 0CC X R SD-24 C
3-1 FLT

1
C S1 S2 G1 G2 66 60 X

2
R C Y1 Y2 G W1 W2
TB2
3
THERMOSTAT
4
SINGLE STAGE COMP, TWO STAGE FAN
TB5 TWO STAGE HEAT

Note: Do Not Use a heat Pump


EVAPORATOR CONTROL BOX Thermostat
Typical simplified field wiring diagram – J07NL Evaporator with J07PE Heat Pump Condenser

UNIT
POWER
SUPPLY

Typical simplified field wiring diagram – J07NL Evaporator

Johnson Controls Ducted Systems 113


505429-JTG-NN-1222

CONDENSER CONTROL BOX

SE CONTROL BOARD
UCB
TB2 VFD COMM THERMOSTAT CONNECTIONS

TB VFD
C S1 S2 G1 G2 66 60 X VFD C W1 W2 Y1 G Y2 0CC X R SD-24 C
3-1 FLT

1
C S1 S2 G1 G2 66 60 X

2
R C Y1 Y2 G W1 W2
TB2
3

THERMOSTAT
4
TWO STAGE COOL/FAN
TB5
TWO STAGE HEAT

Note: Do Not Use a heat Pump


EVAPORATOR CONTROL BOX Thermostat
Typical simplified field wiring diagram – J10-15NL Evaporator with J10-15PC Heat Pump Condenser

Note: On non-J**NC/ND Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on the condensing unit.

C
VALVE SYS 2
BLK 218 / BR
1LLS
O BLK 219 / Y

Typical J10-20NL liquid line solenoid wiring

UNIT
POWER
SUPPLY

Typical simplified field wiring diagram – J10-15NL Evaporator

114 Johnson Controls Ducted Systems


505429-JTG-NN-1222

CONDENSER CONTROL BOX

SE CONTROL BOARD
UCB
TB2 VFD COMM THERMOSTAT CONNECTIONS

TB VFD W1 W2 Y1 G Y2 0CC X R SD-24 C


C S1 S2 G1 G2 66 60 X VFD C
3-1 FLT

1
C S1 S2 G1 G2 66 60 X

2
R C Y1 Y2 G W1 W2
TB2
3

THERMOSTAT
4
TWO STAGE COOL/FAN
TB5
TWO STAGE HEAT

Note: Do Not Use a heat Pump


EVAPORATOR CONTROL BOX Thermostat
Typical simplified field wiring diagram – J15-20NM Evaporator with J15-20PD Heat Pump Condenser

Typical simplified field wiring diagram – J15-20NM Evaporator

Johnson Controls Ducted Systems 115


505429-JTG-NN-1222

CONDENSER CONTROL BOX

UCB SE CONTROL BOARD


TB2 VFD COMM THERMOSTAT CONNECTIONS

TB VFD
C S1 S2 G1 G2 66 60 X VFD C W1 W2 Y1 G Y2 0CC X R SD-24 C
3-1 FLT

1
C S1 S2 G1 G2 66 60 X

2
TB2 R C Y1 Y2 G W1 W2
3
THERMOSTAT
4
SINGLE STAGE COMP
TWO SPEED FAN
TB5
TWO STAGE HEAT
EVAPORATOR CONTROL BOX
Typical simplified field wiring diagram – J07NL Evaporator with J07YE Condenser

UNIT
POWER
SUPPLY

Typical simplified field wiring diagram – J07NL Evaporator

116 Johnson Controls Ducted Systems


505429-JTG-NN-1222

CONDENSER CONTROL BOX

SE CONTROL BOARD
UCB
TB2 VFD COMM THERMOSTAT CONNECTIONS

TB VFD W1 W2 Y1 G Y2 0CC X R SD-24 C


C S1 S2 G1 G2 66 60 X VFD C
3-1 FLT

1
C S1 S2 G1 G2 66 60 X

2
R C Y1 Y2 G W1 W2
TB2
3

THERMOSTAT
4
TWO STAGE COOL/FAN
TB5
TWO STAGE HEAT

EVAPORATOR CONTROL BOX

Typical Simplified Field Wiring Diagram – NL120 thru 240


Evaporator with YC120 thru 240 Condenser

Typical simplified field wiring diagram – J10-20NL Evaporator with J10-20YC Condenser

Note: On non J**NL/NM Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on the condensing unit.

C
VALVE SYS 2
BLK 218 / BR
1LLS
O BLK 219 / Y

Typical J10-20NL liquid line solenoid wiring

Typical simplified field wiring diagram – J10-20NL Evaporator

Johnson Controls Ducted Systems 117


505429-JTG-NN-1222

CONDENSER CONTROL BOX

SE CONTROL BOARD
UCB
TB2 VFD COMM THERMOSTAT CONNECTIONS

TB VFD
C S1 S2 G1 G2 66 60 X VFD C W1 W2 Y1 G Y2 0CC X R SD-24 C
3-1 FLT

1
C S1 S2 G1 G2 66 60 X

2
R C Y1 Y2 G W1 W2
TB2
3

THERMOSTAT
4
TWO STAGE COOL/FAN
TB5
TWO STAGE HEAT

EVAPORATOR CONTROL BOX


Typical simplified field wiring diagram – J10-20NM Evaporator with J10-20YD Condenser

Note: On non J**NL/NM Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on
the condensing unit.

UNIT
POWER
SUPPLY

Typical simplified field wiring diagram – J10-20NM Evaporator

118 Johnson Controls Ducted Systems


505429-JTG-NN-1222

CONDENSER CONTROL BOX

SE CONTROL BOARD
TB2
THERMOSTAT CONNECTIONS

C S1 S2 G1 G2 66 60 X W1 W2 Y1 G Y2 0CC X R SD-24 C

C S1 S2 G1 G2 66 60 X

R C Y1 Y2 G W1 W2
TB1

THERMOSTAT
TWO STAGE COOL
EVAPORATOR CONTROL BOX

Typical field wiring diagram - J25NC evaporator unit with J25YC condenser unit
Note: On non J**NC Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on the condensing unit.

C
VALVE SYS 2
BLK 218 / BR
1LLS
O BLK 219 / Y

Typical J25NC liquid line solenoid wiring

Typical field wiring diagram - J25NC evaporator

Johnson Controls Ducted Systems 119


Subject to change without notice. Printed in U.S.A. 505429-JTG-NN-1222
Copyright © 2022 by Johnson Controls, Inc. All rights reserved. Supersedes: 505429-JTG-MM-1122

York International Corporation


5005 York Drive
Norman, OK 73069