Johnson Controls - Technical Guide R-410A Split-System Air-Cooled Condensing Units and Air Handlers - 505429-jtg-nn-1222
Johnson Controls - Technical Guide R-410A Split-System Air-Cooled Condensing Units and Air Handlers - 505429-jtg-nn-1222
Description
Condensing units and heat pumps are completely assembled, piped
and wired at the factory to provide a single-piece unit for shipment and
rigging. Each unit is pressurized with a holding charge of nitrogen for
storage and shipping.
The compact design, clean styling, small footprint, and quiet operation
Technical guide make these condensing units and heat pumps suitable for almost any
R-410A outdoor location. They can be located on rooftops, because they
Split-system weigh much less than a single package unit of similar capacity and are
much easier to rig and support or on the ground, because the footprint
Air-cooled condensing units is compact allowing a variety of applications.
and air handlers
Both the condensing units and heat pumps are equipped with reliable
Smart Equipment™ microprocessor controls to assure proper
J07YE, J10 through 25YC, and J10 through 20YD operation and unit protection for long product life. Products from 10 to
Condensing unit models 20 ton are available in single or dual (two or four pipe) refrigerant
circuits for redundancy in operation and various applications.
J07PE, J10 through 15PC, and J15 through 20PD
Heat pump unit models The air handling units are completely assembled units, including a
well-insulated cabinet, a DX cooling coil with copper tubing, aluminum
J07 through 20NL and J10 through 20NM fins, expansion valves, distributors, 2 in. throwaway filters, a
Air handling unit models centrifugal blower, a blower motor, an adjustable belt drive, a blower
motor contactor and a small holding charge of nitrogen.
J25NC
Air handling unit models Units are shipped in the vertical position ready for field installation, but
can be easily converted to horizontal position. An added benefit of the
7.5 to 25 ton air handling units is they are designed to operate with either a
60 Hertz condensing unit or a heat pump and no field modification or special
unit is required for heat pump applications.
Table of contents
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Table of contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Condensing unit features and benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Outdoor unit accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Air handling unit features and benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Guide specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Factory- and field-installed options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Physical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Unit limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Cooling and heating ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Capacity Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Air handling and hot water coil accessory heating capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Air handling and steam coil accessory heating capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Airflow performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Sound performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Typical wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Weights and dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Nomenclature
Product Style
Product Category A = Style A
Product Generation
Product Category 1 = First Generation
N = Split System, Air Handler, AC & HP R-410A 2 = Second Generation
3 = Third Generation
Product Identifier
L = Standard Efficiency, 2-Pipe, R-410A w/Intellispeed Installation Options1
M = Standard Efficiency, 4-Pipe, R-410A w/Intellispeed B = IntelliSpeed VFD
C = IntelliSpeed VFD w/Bypass
D = Customer Installed IntelliSpeed VFD
Heat Type & Nominal Heat Capacity
C00 = Cooling Only
Voltage Product Options
2 = 208/230-3-60
1. In order for the IntelliSpeed option to function AA = No Options Installed
correctly some field programming is required.
Airflow 4 = 460-3-60
EJ = E-Coat Evaporator Coil
See unit Installation manual for details. B = 1.5 HP Motor 5 = 575-3-60
C = 2.0 HP Motor
D = 3 HP Motor
E = 5 HP Motor
F = 7.5 HP Motor
• Optional factory-installed powered or non-powered 115 Air handling unit features and benefits
volt GFI outlet.
Features
• Optional factory-installed phase monitor to protect the These air handlers can be arranged for a variety of air
unit from phase loss or phase reversal. discharge patterns in either the horizontal or vertical position.
Refer to the unit installation instructions for other application
Benefits possibilities.
The condensing units and heat pumps can be applied on a Benefits
rooftop or at ground level, due to their ample sub-cooling Air handling units are designed with two distinct modules to
capacity which allows them to be located three or more provide maximum application flexibility. All are shipped as
stories below the evaporator coil. single packages with the blower module mounted on top of
After assembly, the unit is pressure tested and additional leak the coil module. The blower module can be repositioned in
testing is done. During this pressure test, the operation of the the field to meet a large number of vertical and horizontal
high pressure control is checked. As the unit is being applications.
evacuated and dehydrated, the operation of the low pressure The 7.5 to 20 ton blower module includes the blower wheels
control is also checked. along with factory-mounted motor and drive. The 25 ton
Every compressor, condenser fan motor, crankcase heater, blower module includes the blower wheels with field mounted
and electrical control circuit is checked to assure a trouble- motor and drives. All models offer two motor horsepower
free start-up and years of reliable operation. The condenser options to meet both standard and high static airflow
fan guards are vinyl-coated to provide additional rust requirements.
protection and to enhance the appearance of the unit. The coil module includes direct expansion coils, 2 in.
Compressors are mounted on rubber isolators to reduce the throwaway filters with the option to accept 4 in. filters (25 ton
transmission of vibration. Vertical discharge condenser fans 2 in. only), liquid line solenoid valves for capacity reduction,
direct sound upward and away from any surrounding thermal expansion valves, distributors and a non-corrosive,
structures. composite condensate drain pan.
All sheet metal parts are constructed of commercial grade After the headers are brazed onto the coil and the coil is
galvanized steel. After fabrication, each part is thoroughly installed in the unit, the coil is pressurized with nitrogen for
cleaned to remove any grease or dirt from its surfaces. The pressure testing and additional leak testing. After the coil is
external parts are coated with a powder paint to assure a evacuated and dehydrated, it is pressurized with a holding
quality finish for many years. This UL approved coating charge of nitrogen for storage and/or shipping.
system has passed the 750-hour, 20% salt spray test per
ASTM Standard B117. These air handlers, combined with condensing units, provide
years of quiet, efficient and dependable operation.
All condensing unit and heat pump models include a 5-year
limited warranty on the compressors and 1-year limited Unit installation
warranty on all other parts. The matching line of air handling Units may be bottom-supported or ceiling-suspended and
units carries a 1-year limited parts warranty. can be arranged to meet almost any space or duct
requirements. Each unit is available with a choice of blower
Outdoor unit accessories motors horsepower and other accessories to make them
suitable for most applications.
Coil Guards: Wireform coil guards for added protection of
Air Handling units from 10 to 20 ton are available in either two
outdoor coils. Designed to mount on each side of the product
or four pipe configurations. 7.5 and 25 ton are two pipe (only)
if required to provide protection from minor impacts or large
configurations. The dual and single circuit options provide a
debris.
wide variety of application and unit match-up possibilities.
Hail Guards: Hood type hail guards designed to protect the Blower Motors: Different HP motors are available for each
outdoor coils from hail. Can be installed on a single side or unit to meet almost any air delivery requirement. All motors
both to provide protection from storms that may produce hail. are UL approved, have permanently lubricated ball bearings
and are mounted within the insulated cabinet of the units to
Low Ambient Kits: Kits designed to allow the cooling only
minimize the transmission of sound to the surrounding space.
units to operate between 0°F and 40°F in the cooling mode.
1.5-5 HP motors are inherently protected. 7.5 HP motors
Standard cooling is allowed to 45°F. (Not designed for
require motor overload protection.
operation on heat pump units).
Overload Relay (7.5HP): These blower motors do not have
inherent protection and require external motor overload
protection. J20NC/ND/NL/NM "F" models overload relays are
factory installed. J25NC models overload relays are field
installed. Power wiring for blower motor is supplied in the
overload relay kit. See details in the overload relay kit and in
J25NC overload relay setting (all) on page 61.
Johnson Controls Ducted Systems 5
505429-JTG-NN-1222
Factory-mounted components condensate drainage. The coil has copper tubes that have
Part load operation: These air handlers with DX (Direct been mechanically expanded into aluminum fins. Both
Expansion) coils rated at 10 ton of capacity and above have headers are located on the same end of the coil. The coil is
multiple coils with pre-piped distributors, expansion valves leak-tested at 325 psig and dried before the connections are
and solenoid valves. Field modifications are not required for capped for storage and shipping.
part load operations. Capacity reduction not only provides
economical operation, but also maintains stable temperature Bottom return: Air handling unit can be quickly converted to
and humidity levels in the conditioned space. bottom return for both vertical and horizontal applications. All
that is required is the removal of several screws and a single
BAS Control: Smart Equipment™ with Communication panel on 7.5-15 ton and two panels on the 20 ton AHU.
Option Control - The Johnson Controls Smart Equipment™ Optional painted panel can be ordered to cover the side
with Communication Option Control is factory installed. It return opening when utilizing the bottom return.
includes all the features of the Smart Equipment™ control
with an additional gateway to BACnet MS/TP (programmable
to Modbus or N2 protocols).
IntelliSpeed™ Supply Fan Control: (ASHRAE 90.1 This Split-System (Air Condensing / Heat Pump / Air
Compliant) AHU units configured with the IntelliSpeed option Handling) unit is one component of an entire system.
will contain a VFD for multi-speed supply fan operation. This As such it requires specific application considerations
option allows the supply fan RPM to vary based on the with regard to the rest of the system (air handling unit,
number compressors or heating stages energized. duct design, condensing unit, refrigerant piping and
control scheme).
Easy service: Serviceable expansion valves are provided on
every unit. These valves are factory-installed to provide many Failure to properly apply this equipment with the rest
years of trouble-free operation. The expansion valves also of the system may result in premature failure and/or
include a tee fitting to allow easy installation of hot gas reduced performance / increased costs. Warranty
bypass if required. coverage specifically excludes failures due to
improper application and Unitary Products specifically
Coil protection: The indoor coils of these air handlers can disclaims any liability resulting from improper
have factory applied Electrofin coating to provide extended application.
life to the indoor coil in standard applications and additional Please refer to the equipment Technical Guide,
corrosion protection on those applications in sea coast or Installation Manual and the piping applications bulletin
corrosive environments. 247077, service tips letter ST-013-2019 and Split
Accessories System Refrigerant Oil Management White Paper or
call the applications department for Unitary Products
IntelliSpeed™ VFD: Field installed VFD for 25 ton AHU
@ 1-877-UPG-SERV for guidance.
IntelliSpeed multi-speed fan function. The field installed VFD
will allow staged fan and will meet ASHRAE 90.1 or IECC two
speed fan requirements.
Guide specifications
Base sections: Base sections can be used to elevate units
above the floor. If desired, a moderate percentage of outdoor Split-system cooling only condensing units
air may be introduced through these sections by cutting an Models: J07YE, J10 through 25YC, J10 through
access opening to accommodate the outdoor air duct 20YD and split-system heat pump models: J07PE,
connection. These bases include a durable finish to match
J10 through 15PC, and J15 through 20PD
the evaporator blower unit. The base may have to be
insulated for certain applications. General
Hot water coils: Drainable water coils are available for field • Factory-assembled, single piece, air cooled condensing
installation between the blower and the coil modules of both unit designed for outdoor installation.
horizontal and vertical units. Since their casings match the • Factory wired, piped, and tested for leakage and
dimensions and the finish of the basic units, they become an functionality to assure trouble-free installation and start-
integral part of the unit after installation. The coils slide out of up.
their casings for easy installation. Hot water coils have • Rated in accordance with AHRI Standard 340/360.
copper tubes that have been mechanically expanded into
aluminum fins. Both headers are located on the same end of • Designed and tested in accordance with ASHRAE 15
the coil. Safety Code for Mechanical Refrigeration and comply
with NEC.
Steam coils: Steam coils are available for installation • Cooling performance rated in accordance with DOE
between the blower and coil modules of both horizontal and and AHRI test procedures.
vertical units. Since the casing matches the dimensions and
• CSA listed and classified to UL 1995/CAN/CSA No.
the finish of the basic unit, it becomes an integral part of the
236- M90 standards.
unit after installation. The coil slides out of the casings for
easy installation and is pitched in the casings to facilitate
• One year limited parts warranty on complete unit with Outdoor condenser unit coils
an additional four year compressor warranty. • Draw through configuration
Unit operating characteristics • Constructed with Micro-channel aluminum fins and
Operating Range shall be between 125° F to 40° F in cooling aluminum tubing.
as standard from factory. Heat pump unit outdoor unit coils
• The capacity of the condensing unit shall meet or • Draw through configuration
exceed _____ Btuh at a suction temperature of _____
• Constructed with aluminum plate fins mechanically
F. The power consumption at full load shall not exceed
bonded to seamless internally enhanced copper tubes
_____ kW.
with all joints brazed.
• The combination of the condensing unit and the
Condenser fans
evaporator or fan coil unit shall have a total net cooling
capacity of _____ Btuh or greater at conditions of • Direct driven propeller-type fans
_____ cfm entering-air temperature at the evaporator at • Aluminum blades riveted to corrosion resistant steel
_____ F wet bulb and _____ F dry bulb, and air spider brackets.
entering the condensing unit at _____F. • Arranged for vertical air discharge.
• The system shall have an EER of _____ Btuh/ Watt or • Equipped with PVC coated steel wire safety guards.
greater at standard AHRI conditions.
Condenser motors
Installer shall
• Totally enclosed, air over cooled.
• Furnish Johnson Controls air-cooled condensing units,
heat pump or equivalent in accordance with the • Inherent overload protection.
performance schedule shown on the plans, and • Permanently lubricated bearings.
• Unit shall be stored and handled in accordance with unit • Must cycle to allow cooling operation down to 45°F.
manufacturer's instructions. Refrigerant piping
• Install each unit as shown on the plans in accordance • Solid core filter-driers ship loose for field installation.
with the manufacturer’s recommendations and all
• Liquid and suction line service valves with gauge ports.
applicable national and local codes
• Suction and discharge line service ports accessible
Unit construction
from unit. Ports capped for leak prevention.
• Constructed of zinc-coated, galvanized steel.
• Liquid line magnetic check valves
• Exterior surfaces bonded and coated with baked
• Holding charge of nitrogen.
enamel finish by a powder paint process capable of
withstanding a minimum of 750 salt spray hours Electrical requirements
according to ASTM B117. • Single-point connection electrical power.
• Cabinet screws that comply with ASTM B117 salt spray • Nominal unit electrical characteristics shall be _____ v,
test for a minimum of 750 hours. 3-ph, 60 Hz. The unit shall be capable of satisfactory
• Permanently attached heavy-gage perimeter base rails operation within voltage limits of ____ v to _____ v.
with forklift slots and lifting holes. • Condenser fan motors and secondary of transformers
• Removable access panels to all internal components. shall be grounded.
• Separate access panel to controls. Unit controls
• Access panels to allow outdoor coil cleaning. • All 24-volt control circuit, powered by a 24 volt
transformers and protected by a resettable breaker.
Compressors
• Conventional thermostat must provide operation for
• Hermetic scroll type, internally protected with high-
both condensing units and heat pumps without an “O”
pressure relief and over temperature protection.
output from the thermostat.
• Two stage units operate in 50% capacity increments.
• Low voltage terminal strip for simple hook-up.
• Suction gas cooled
• Compressor motor protection shuts down unit for motor
• Voltage range of ±10% of unit nameplate voltage. over-current, over-temperature or low voltage
• Neoprene isolators minimize sound transmission and conditions.
vibration. • Safety lockouts provide reset capability at the space
• Belly-band crankcase heaters keep refrigerant from thermostat or base unit should any of the following
diluting sump oil. standard safety devices trip and shut off compressor:
• Full charge of compressor oil a. Loss-of-charge/Low-pressure switch.
b. High-pressure switch.
c. Control board diagnostics and fault message display. Each unit shall be:
d. Safety lockouts send a 24 volt signal to the control • Covered by a 1-year limited parts warranty on the
board's "X" terminal, allowing notification to the user complete unit and 5-year on compressors.
via the thermostat fault light (if present). • In current production with published literature available
e. In the unlikely event any faults should occur, the unit to check performance, limitations, specifications, power
control board will store the faults in its internal requirements, dimensions, operation and appearance.
memory. The LCD display will scroll the 5 MOST • Indoor unit shall be equipped with a V-belt drive option
critical faults, however, all fault messages can be that will permit the blower RPM to be adjusted to meet
extracted via USB device, displayed real-time via the the CFM requirements of the air delivery system. (Refer
MAP Gateway as well as be broadcasted through a to Technical Guide for Airflow Capabilities.)
BAS system (if applicable). The UCB will provide fault
Each unit enclosure shall have:
messages in plain English to ensure the user can
easily understand the specific fault. • Exterior panels of 18 gauge steel, finished with baked
enamel to provide a long lasting quality appearance
Non-fused disconnect switch
• Removable panels to provide easy access to the
• Factory installed option, internally mounted
internal components for maintenance and service on
• Accessible from outside the unit. condensing units, heat pumps and air handlers
• NEC and UL approved non-fused switch. • Air handling units must have a filter rack that accepts
• Provides power off lockout capability. both 2 in. and 4 in. filters (7.5 - 20 Ton only).
Convenience outlet • The dimensions of each unit shall not exceed those
• Factory-installed, internally mounted. specified in the manufacturers literature.
• Accessible from outside the unit. • The minimum application clearances for condensing
units, heat pumps and air handlers must meet those
• 115V, 20 amp GFI receptacle with independent fuse
specified in the manufacturer’s literature.
protection.
The blower motor shall:
• Required voltage provided by factory-installed step-
down transformer or field supplied 115v circuit. • Be mounted within the insulated cabinet to minimize the
transmission of sound to the surrounding space, and
Low-ambient head pressure control
any motor 7.5 HP or greater must have a service factor
• Standard operation down to 45 °F without a low of 1.15.
ambient kit.
IntelliSpeed discrete fan control shall:
• Operation down to 0°F with a factory-installed or field-
• Control fan speed with a VFD (Variable Frequency
installed low ambient kit accessory. The controller
Drive)
modulates the fan motor speed in response to liquid line
temperature or pressure. • Drive fan speed based on the number of cooling or
heating stages.
Coil guard
• Maximum airflow on first stage cooling not to exceed
Factory or field installed decorative grille shall be placed on
67%.
the units to protect condenser coil after installation.
The Evaporator coil shall:
Hail guard package
• Consist of copper tubes arranged in staggered rows,
Field installed hail guard package shall protect coils against
mechanically expanded into aluminum fins,
damage from hail and other flying debris.
• Be draw-through, and
Coated condenser coils
• Include factory-mounted distributors, expansion valves
Special phenolic or epoxy polymer coating available as a
and solenoid valves for capacity reduction.
factory option on both outdoor and indoor coils.
The blower wheels shall:
Be dynamically balanced to minimize the levels of sound and
vibration generated by the unit.
1
25 ton AHU does not come equipped with a motor, drive or motor protection (Overload Relay). Must be field installed. VFD Rated
Motors must be used in conjunction with any field installed VFD kit. See additional details on Page 67.
Evaporator blower motor variable frequency drive (VFD) kits with VFD bypass switch
Nominal ton HP Voltage Model Description Weight (lb)
208/230-3-60 2VF04601623D VFD kit for discrete fan 110
5 460-3-60 2VF04601633D VFD kit for discrete fan 110
575-3-60 2VF04601658D VFD kit for discrete fan 110
251
208-230-3-60 2VF04601723D VFD kit for discrete fan 130
7.5 460-3-60 2VF04601733D VFD kit for discrete fan 130
575-3-60 2VF04601758D VFD kit for discrete fan 130
1 25 ton AHU does not come equipped with a motor, drive or motor protection (Overload Relay). Must be field installed. VFD Rated
Motors must be used in conjunction with any field installed VFD kit. See additional details on Page 67.
Physical data
Unit limitations
J15PC J15NL 180 10.6 N/A 13.5 168 3.3 104 2.3 5800
J15PD J15NM 174 10.6 N/A 14 160 3.4 100 2.25 6000
J20PD J20NM 230 10.6 N/A 13.5 220 3.3 130 2.2 8000
J10YC J10NL 117 11.2 N/A 15.2 N/A N/A N/A N/A 4000
J10YD J10NM 115 11.4 N/A 15 N/A N/A N/A N/A 3800
J12YC J15NL 148 11 N/A 14.2 N/A N/A N/A N/A 5000
J12YD J15NM 145 11.2 N/A 14.2 N/A N/A N/A N/A 5000
J15YC J15NL 180 11.2 N/A 14.2 N/A N/A N/A N/A 6000
J15YD J15NM 180 11 N/A 14.2 N/A N/A N/A N/A 6000
J20YC J20NL 240 11 N/A 14.8 N/A N/A N/A N/A 7600
J20YD J20NM 240 10.2 N/A 13.4 N/A N/A N/A N/A 8000
3
J25YC J25NC 290 10.1 N/A 13.2 N/A N/A N/A N/A 9400
1
Certified in accordance with the Ducted Systems Large Equipment certification program, which is based on AHRI Standard 340/360.
(Except J25YC)
2
NET capacity includes heat added by the standard motor horsepower. See J07-J20N* Air Handler Blower Motor and Drive Data for
standard motor sizes.
3
Requires field installed VFD kit.
LEGEND
EER = Energy Efficiency Ratio
AHRI = Air Conditioning and Refrigeration Institute
IEER = Integrated Energy Efficiency Ratio
Capacity Performance
Condenser and air handling cooling capacities
J07YE/J07NL
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 110.5 5.5 55.4 46.7 38.1 - - - 105.4 6.2 55.4 46.6 37.9 - - -
72 99.7 5.4 66.0 56.9 47.8 38.7 - - 95.9 6.1 65.0 56.0 47.0 38.1 - -
1875
67 88.9 5.3 76.6 67.0 57.5 48.0 39.2 - 86.3 5.9 74.6 65.4 56.2 47.0 38.1 -
62 81.1 5.2 81.1 75.3 67.2 55.8 48.9 39.7 78.3 5.9 78.3 74.0 65.3 55.2 47.2 38.1
77 111.1 5.6 61.5 50.1 38.8 - - - 106.0 6.2 61.0 49.3 37.7 - - -
72 102.0 5.5 72.0 61.1 50.301 39.5 - - 97.9 6.1 70.6 59.9 49.1 38.4 - -
2250 67 92.8 5.4 82.4 72.1 61.8 50.7 40.1 - 89.7 6.0 80.3 70.4 60.6 49.6 38.8 -
62 86.6 5.3 86.6 80.6 73.4 60.7 51.7 40.8 83.8 6.0 83.8 79.2 72.0 60.1 50.1 39.1
57 80.4 5.2 80.4 80.4 80.4 74.1 63.2 52.3 77.9 6.0 77.9 77.9 77.9 72.4 61.3 50.2
77 111.7 5.6 67.7 53.6 39.4 - - - 106.5 6.2 66.6 52.1 37.5 - - -
72 104.2 5.5 78.0 65.4 52.8 40.2 - - 99.8 6.1 76.3 63.7 51.2 38.7 - -
2625 67 96.8 5.4 88.3 77.3 66.2 53.4 41.0 - 93.1 6.1 85.9 75.4 64.9 52.1 39.5 -
62 92.1 5.4 92.1 86.0 79.6 65.7 54.5 41.9 89.3 6.0 89.3 84.4 78.6 65.1 52.9 40.0
57 87.4 5.3 87.4 87.4 87.4 80.5 67.9 55.4 85.5 6.0 85.5 85.5 85.5 79.3 66.3 53.2
77 112.2 5.6 73.9 57.0 40.1 - - - 107.0 6.3 72.3 54.8 37.3 - - -
72 106.5 5.5 84.0 69.7 55.3 41.0 - - 101.8 6.2 81.9 67.6 53.3 39.0 - -
3000 67 100.8 5.5 94.2 82.4 70.5 56.1 41.9 - 96.5 6.1 91.5 80.4 69.3 54.7 40.2 -
62 97.7 5.4 96.8 91.3 85.8 70.6 57.3 43.1 94.8 6.1 93.9 89.6 85.3 70.1 55.7 41.0
57 94.5 5.4 94.5 94.5 94.5 86.8 72.7 58.5 93.0 6.1 93.0 93.0 93.0 86.3 71.3 56.3
72 108.8 5.6 90.0 73.9 57.8 41.7 - - 103.7 6.2 87.5 71.4 55.4 39.3 - -
67 104.8 5.5 100.0 87.5 74.9 58.8 42.8 - 99.9 6.2 97.1 85.4 73.6 57.2 40.9 -
3375
62 103.2 5.5 101.3 96.6 92.0 75.6 60.1 44.2 100.3 6.2 97.6 94.8 91.9 75.0 58.6 41.9
57 101.6 5.5 100.1 100.1 100.1 93.2 77.4 61.5 100.6 6.2 96.9 96.9 96.9 93.2 76.3 59.3
72 111.1 5.6 96.1 78.2 60.318 42.4 - - 105.7 6.3 93.2 75.3 57.5 39.6 - -
67 108.7 5.6 105.9 92.6 79.3 61.5 43.7 - 103.3 6.2 102.8 90.4 78.0 59.8 41.6 -
3750
62 108.7 5.6 105.8 102.0 98.2 80.6 62.9 45.3 105.7 6.2 101.4 100.0 98.6 80.0 61.4 42.8
57 108.7 5.6 105.6 105.6 105.6 99.6 82.1 64.6 108.1 6.3 100.0 100.0 100.0 100.0 81.3 62.3
95°F 105°F
77 100.4 6.8 55.4 46.5 37.6 - - - 95.3 7.9 52.5 43.8 35.1 - - -
72 92.1 6.7 64.0 55.1 46.3 37.4 - - 87.0 7.8 61.9 53.0 44.1 35.2 - -
1875
67 83.8 6.6 72.7 63.8 54.9 46.0 37.0 - 78.6 7.7 71.3 62.2 53.1 44.1 35.0 -
62 75.6 6.6 75.6 72.7 63.5 54.5 45.6 36.6 74.2 7.7 74.2 70.3 62.1 52.9 43.7 34.5
77 100.8 6.8 60.5 48.5 36.6 - - - 95.8 7.9 58.5 46.5 34.5 - - -
72 93.7 6.7 69.3 58.6 47.931 37.3 - - 88.9 7.8 67.3 56.6 45.9 35.3 - -
2250 67 86.6 6.6 78.1 68.7 59.3 48.4 37.5 - 81.9 7.7 76.0 66.7 57.4 46.5 35.5 -
62 81.0 6.7 81.0 77.8 70.6 59.5 48.4 37.3 79.0 7.7 79.0 75.1 68.9 57.7 46.5 35.3
57 75.4 6.7 75.4 75.4 75.4 70.6 59.4 48.1 76.2 7.7 76.2 76.2 76.2 68.9 57.4 46.0
77 101.3 6.9 65.6 50.6 35.5 - - - 96.3 7.9 64.5 49.2 33.9 - - -
72 95.4 6.8 74.5 62.1 49.6 37.1 - - 90.8 7.8 72.6 60.2 47.8 35.4 - -
2625 67 89.5 6.7 83.4 73.5 63.6 50.8 38.0 - 85.2 7.8 80.7 71.2 61.7 48.9 36.1 -
62 86.5 6.7 86.5 82.8 77.7 64.5 51.3 38.1 83.9 7.8 83.9 79.9 75.6 62.4 49.3 36.1
57 83.5 6.8 83.5 83.5 83.5 78.2 64.6 51.1 82.5 7.8 82.5 82.5 82.5 75.9 62.4 48.9
77 101.7 6.9 70.7 52.6 34.5 - - - 96.9 7.9 70.5 51.9 33.3 - - -
72 97.0 6.8 79.8 65.5 51.3 37.0 - - 92.7 7.9 78.0 63.8 49.6 35.4 - -
3000 67 92.3 6.8 88.8 78.4 68.0 53.2 38.5 - 88.5 7.8 85.4 75.7 66.0 51.3 36.6 -
62 91.9 6.8 91.0 87.9 84.8 69.5 54.2 38.9 88.7 7.8 87.2 84.8 82.3 67.2 52.0 36.9
57 91.5 6.8 91.5 91.5 91.5 85.7 69.9 54.1 88.9 7.8 88.9 88.9 88.9 83.0 67.4 51.8
72 98.6 6.9 85.0 69.0 52.9 36.9 - - 94.6 7.9 83.3 67.4 51.5 35.5 - -
67 95.1 6.8 94.2 83.3 72.4 55.7 38.9 - 91.7 7.9 90.1 80.2 70.2 53.7 37.2 -
3375
62 97.3 6.9 94.0 92.9 91.9 74.5 57.0 39.6 93.5 7.9 90.1 89.6 89.0 71.9 54.8 37.7
57 99.6 6.9 93.8 93.8 93.8 93.2 75.1 57.1 95.3 7.9 90.1 90.1 90.1 90.1 72.4 54.7
72 100.3 6.9 90.3 72.4 54.583 36.7 - - 96.5 7.9 88.7 71.0 53.3 35.6 - -
67 97.9 6.9 97.9 88.2 76.8 58.1 39.4 - 95.0 7.9 94.8 84.7 74.5 56.1 37.8 -
3750
62 102.8 6.9 97.0 97.0 97.0 79.4 59.9 40.4 98.3 7.9 93.0 93.0 93.0 76.7 57.6 38.5
57 107.6 7.0 94.4 94.4 94.4 94.4 80.4 60.0 101.7 8.0 91.2 91.2 91.2 91.2 77.4 57.7
J07YE/J07NL (Continued)
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 90.1 8.9 49.7 41.1 32.5 - - - 85.0 10.0 46.8 38.4 29.9 - - -
72 81.8 8.9 59.8 50.9 41.9 33.0 - - 76.6 9.9 57.7 48.7 39.8 30.8 - -
1875
67 73.5 8.8 70.0 60.7 51.4 42.2 32.9 - 68.3 9.9 68.3 59.1 49.6 40.2 30.9 -
62 72.8 8.7 72.8 67.9 60.8 51.3 41.8 32.4 71.4 9.8 71.4 65.5 59.4 49.7 40.0 30.2
77 90.8 8.9 56.6 44.5 32.4 - - - 85.7 10.0 54.6 42.4 30.2 - - -
72 84.0 8.9 65.3 54.6 43.9 33.3 - - 79.1 9.9 63.3 52.6 42.0 31.3 - -
2250 67 77.2 8.8 74.0 64.8 55.5 44.6 33.6 - 72.5 9.9 72.0 62.8 53.7 42.6 31.6 -
62 77.1 8.8 77.1 72.5 67.1 55.8 44.5 33.2 75.1 9.8 74.3 69.8 65.4 54.0 42.6 31.2
57 76.9 8.7 76.9 76.9 76.9 67.1 55.5 43.8 77.7 9.7 76.7 76.7 76.7 65.3 53.5 41.7
77 91.4 8.9 63.4 47.8 32.2 - - - 86.4 9.9 62.3 46.4 30.5 - - -
72 86.1 8.9 70.7 58.3 46.0 33.6 - - 81.5 9.9 68.8 56.5 44.1 31.8 - -
2625 67 80.9 8.9 78.0 68.9 59.7 47.0 34.2 - 76.6 9.9 75.3 66.5 57.7 45.0 32.3 -
62 81.3 8.8 80.7 77.1 73.5 60.3 47.2 34.1 78.7 9.9 77.0 74.2 71.3 58.3 45.2 32.1
57 81.6 8.8 81.6 81.6 81.6 73.7 60.2 46.7 80.7 9.8 78.7 78.7 78.7 71.5 58.0 44.5
77 92.0 8.9 70.3 51.2 32.1 - - - 87.1 9.9 70.1 50.5 30.8 - - -
72 88.3 8.9 76.2 62.1 48.0 33.9 - - 84.0 9.9 74.4 60.4 46.3 32.3 - -
3000 67 84.6 8.9 82.0 73.0 63.9 49.4 34.8 - 80.8 10.0 78.7 70.2 61.8 47.4 33.0 -
62 85.5 8.9 83.5 81.6 79.8 64.8 49.9 34.9 82.3 9.9 79.7 78.5 77.3 62.5 47.7 33.0
57 86.3 8.8 84.9 84.9 84.9 80.3 65.0 49.6 83.7 9.9 80.8 80.8 80.8 77.6 62.5 47.3
72 90.5 8.9 81.6 65.8 50.0 34.2 - - 86.4 9.9 79.9 64.2 48.5 32.8 - -
67 88.4 8.9 86.1 77.1 68.1 51.8 35.5 - 85.0 10.0 82.0 74.0 65.9 49.8 33.7 -
3375
62 89.7 8.9 86.3 86.2 86.1 69.4 52.6 35.8 85.9 9.9 82.4 82.4 82.4 66.8 50.3 33.9
57 91.0 8.9 86.5 86.5 86.5 86.5 69.7 52.4 86.8 9.9 82.8 82.8 82.8 82.8 67.0 50.1
72 92.7 8.9 87.1 69.5 52.0 34.5 - - 88.9 10.0 85.5 68.1 50.7 33.3 - -
67 92.1 8.9 90.1 81.2 72.2 54.2 36.1 - 89.2 10.0 85.4 77.7 70.0 52.2 34.4 -
3750
62 93.9 9.0 89.1 89.1 89.1 73.9 55.3 36.7 89.5 10.0 85.1 85.1 85.1 71.1 52.9 34.8
57 95.7 9.0 88.1 88.1 88.1 88.1 74.4 55.3 89.8 10.0 84.9 84.9 84.9 84.9 71.4 52.9
1 These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor
efficiency.
2 These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J10YC/J10NL
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 143.5 7.4 78.3 63.2 48.1 - - - 140.2 8.2 77.4 62.2 47.0 - - -
72 132.8 7.2 92.9 78.7 64.5 50.2 - - 129.5 8.1 92.3 77.8 63.4 48.9 - -
3000 67 122.1 7.1 107.6 94.2 80.8 65.9 52.0 - 118.8 7.9 107.3 93.5 79.7 64.7 50.2 -
62 115.4 7.0 114.7 105.9 97.1 79.6 67.9 53.3 114.6 7.8 114.6 105.3 96.0 79.6 66.1 51.1
57 126.6 6.9 126.6 120.0 113.4 98.7 83.9 69.1 119.3 7.8 119.3 117.2 112.4 97.1 81.9 66.7
77 146.3 7.4 86.8 67.2 47.6 - - - 141.0 8.2 85.2 66.0 46.7 - - -
72 135.8 7.3 100.2 83.7 67.1 50.5 - - 132.3 8.1 99.6 82.9 66.1 49.4 - -
3500 67 125.2 7.1 113.7 100.2 86.7 69.4 52.9 - 123.6 8.0 114.0 99.7 85.5 68.2 51.2 -
62 121.6 7.1 121.3 114.9 106.2 86.8 71.8 54.6 120.4 7.9 119.9 112.9 104.8 86.3 69.9 52.4
57 131.4 7.0 131.4 128.1 124.8 108.2 90.7 73.2 124.0 7.9 124.0 124.0 123.7 106.4 88.5 70.7
77 149.1 7.4 95.3 71.1 47.0 - - - 141.7 8.2 93.1 69.8 46.5 - - -
72 138.7 7.3 107.5 88.6 69.8 50.9 - - 135.0 8.1 106.9 87.9 68.9 49.8 - -
4000 67 128.4 7.2 119.8 106.1 92.5 72.9 53.8 - 128.3 8.0 120.8 106.0 91.2 71.6 52.2 -
62 127.8 7.2 127.8 123.8 115.3 94.0 75.7 55.9 126.3 8.0 125.2 120.6 113.6 92.9 73.7 53.7
57 136.2 7.1 136.2 136.2 136.2 117.8 97.5 77.3 128.7 8.0 128.7 128.7 128.7 115.6 95.1 74.7
72 141.7 7.4 114.8 93.6 72.4 51.2 - - 137.7 8.2 114.3 92.9 71.6 50.3 - -
67 131.5 7.2 125.9 112.1 98.4 76.4 54.8 - 133.0 8.1 127.5 112.3 97.0 75.1 53.2 -
4500
62 134.0 7.2 134.0 132.8 124.4 101.2 79.6 57.1 132.1 8.1 132.1 128.2 122.4 99.6 77.5 55.0
57 141.0 7.3 141.0 141.0 141.0 127.3 104.3 81.3 133.4 8.1 133.4 133.4 133.4 124.8 101.7 78.7
72 144.7 7.4 122.1 98.6 75.04 51.5 - - 140.5 8.2 121.6 98.0 74.4 50.8 - -
67 134.7 7.3 132.0 118.1 104.2 80.0 55.7 - 137.8 8.1 134.2 118.5 102.8 78.5 54.2 -
5000
62 140.2 7.3 140.2 140.2 133.4 108.4 83.4 58.4 137.9 8.2 137.9 135.8 131.2 106.3 81.3 56.3
57 145.8 7.4 145.8 145.8 145.8 136.9 111.2 85.4 138.1 8.2 138.1 138.1 138.1 134.0 108.4 82.7
95°F 105°F
77 137.0 9.0 76.4 61.1 45.9 - - - 130.3 10.5 74.7 59.7 44.7 - - -
72 126.3 8.9 91.7 77.0 62.26 47.5 - - 120.3 10.3 89.7 75.0 60.4 45.7 - -
3000 67 115.5 8.7 107.0 92.8 78.6 63.6 48.5 - 110.3 10.0 104.8 90.4 76.0 61.1 46.2 -
62 113.8 8.7 113.8 104.7 95.0 79.6 64.2 48.8 110.0 10.0 108.9 100.3 91.7 76.6 61.4 46.2
57 112.1 8.6 112.1 112.1 111.3 95.6 79.9 64.2 109.7 10.0 109.7 108.8 107.4 92.0 76.6 61.2
77 135.7 9.0 83.7 64.8 45.9 - - - 129.4 10.4 82.9 63.6 44.2 - - -
72 128.8 8.9 99.0 82.1 65.1 48.2 - - 122.8 10.3 97.0 80.0 63.1 46.2 - -
3500 67 121.9 8.8 114.4 99.3 84.3 66.9 49.6 - 116.2 10.1 111.0 96.5 82.0 64.6 47.3 -
62 119.3 8.8 118.6 111.0 103.5 85.7 67.9 50.2 115.2 10.1 113.0 107.0 100.9 83.1 65.2 47.4
57 116.7 8.7 116.7 116.7 116.7 104.5 86.3 68.1 114.1 10.0 112.8 112.8 112.8 101.5 83.2 64.9
77 134.4 9.1 91.0 68.5 46.0 - - - 128.6 10.4 91.2 67.5 43.8 - - -
72 131.3 9.0 106.3 87.2 68.0 48.8 - - 125.3 10.3 104.2 85.1 65.9 46.7 - -
4000 67 128.2 8.9 121.7 105.9 90.0 70.3 50.6 - 122.1 10.1 117.2 102.6 88.0 68.2 48.3 -
62 124.7 8.8 122.6 117.3 112.0 91.8 71.7 51.5 120.3 10.1 117.1 113.6 110.1 89.6 69.1 48.6
57 121.2 8.8 121.2 121.2 121.2 113.4 92.7 72.1 118.5 10.1 115.5 115.5 115.5 111.0 89.8 68.6
72 133.8 9.0 113.7 92.3 70.8 49.4 - - 127.8 10.3 111.4 90.1 68.7 47.3 - -
67 134.5 8.9 129.1 112.4 95.7 73.7 51.7 - 128.0 10.2 123.4 108.7 94.0 71.7 49.4 -
4500
62 130.2 8.9 126.7 123.6 120.5 98.0 75.4 52.9 125.4 10.2 121.2 120.2 119.3 96.1 72.9 49.7
57 125.8 8.9 123.1 123.1 123.1 122.2 99.1 76.1 122.9 10.2 118.2 118.2 118.2 118.2 96.4 72.3
72 136.3 9.0 121.0 97.3 73.68 50.0 - - 130.3 10.3 118.7 95.1 71.4 47.8 - -
67 140.9 9.0 136.5 118.9 101.3 77.0 52.8 - 133.9 10.2 129.6 114.8 99.9 75.2 50.5 -
5000
62 135.6 9.0 130.7 129.9 129.0 104.1 79.2 54.2 130.6 10.2 125.2 125.2 125.2 102.6 76.7 50.9
57 130.4 9.0 125.0 125.0 125.0 125.0 105.6 80.0 127.2 10.2 120.9 120.9 120.9 120.9 103.0 76.0
J10YC/J10NL (Continued)
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 123.6 11.9 73.0 58.2 43.4 - - - 116.9 13.3 71.3 56.7 42.2 - - -
72 114.3 11.6 87.8 73.1 58.5 43.8 - - 108.4 13.0 85.8 71.2 56.6 41.9 - -
3000 67 105.1 11.3 102.6 88.0 73.5 58.7 43.9 - 99.9 12.6 99.9 85.7 70.9 56.2 41.5 -
62 106.2 11.3 103.4 95.9 88.5 73.5 58.6 43.7 102.4 12.6 97.8 91.5 85.2 70.5 55.8 41.1
57 107.4 11.3 102.7 102.7 102.7 88.4 73.3 58.3 105.0 12.7 95.2 95.2 95.2 84.8 70.1 55.3
77 123.2 11.8 82.2 62.4 42.5 - - - 116.9 13.2 81.5 61.2 40.8 - - -
72 116.8 11.6 94.9 78.0 61.1 44.2 - - 110.8 13.0 92.9 76.0 59.1 42.3 - -
3500 67 110.5 11.4 107.6 93.7 79.7 62.3 44.9 - 104.9 12.6 104.3 90.9 77.5 60.0 42.6 -
62 111.0 11.4 107.5 102.9 98.4 80.4 62.5 44.6 106.9 12.6 101.9 98.8 95.8 77.8 59.8 41.8
57 111.5 11.3 106.2 106.2 106.2 98.5 80.1 61.7 109.0 12.7 99.5 99.5 99.5 95.6 77.0 58.5
77 122.7 11.7 91.5 66.5 41.6 - - - 116.9 13.0 91.7 65.6 39.5 - - -
72 119.3 11.6 102.1 82.9 63.8 44.7 - - 113.3 13.0 99.9 80.8 61.7 42.7 - -
4000 67 116.0 11.4 112.7 99.3 86.0 66.0 46.0 - 109.9 12.7 108.1 96.1 84.0 63.9 43.7 -
62 115.9 11.4 111.5 109.9 108.2 87.3 66.5 45.6 111.4 12.6 106.0 106.0 106.0 85.1 63.8 42.6
57 115.7 11.4 109.7 109.7 109.7 108.6 86.9 65.1 113.0 12.6 103.9 103.9 103.9 103.9 84.0 61.7
72 121.8 11.6 109.2 87.9 66.5 45.2 - - 115.8 13.0 107.0 85.7 64.3 43.0 - -
67 121.5 11.4 117.7 105.0 92.3 69.7 47.1 - 115.0 12.7 112.0 101.3 90.6 67.7 44.8 -
4500
62 120.7 11.4 115.6 115.6 115.6 94.2 70.4 46.5 116.0 12.6 110.1 110.1 110.1 92.4 67.9 43.4
57 119.9 11.4 113.2 113.2 113.2 113.2 93.7 68.6 116.9 12.6 108.2 108.2 108.2 108.2 90.9 64.8
72 124.3 11.6 116.3 92.8 69.2 45.6 - - 118.2 12.9 114.0 90.5 66.9 43.4 - -
67 127.0 11.5 122.7 110.6 98.6 73.4 48.2 - 120.0 12.7 115.8 106.5 97.2 71.5 45.9 -
5000
62 125.5 11.4 119.7 119.7 119.7 101.1 74.3 47.5 120.5 12.6 114.2 114.2 114.2 99.6 71.9 44.1
57 124.1 11.4 116.7 116.7 116.7 116.7 100.4 72.0 120.9 12.6 112.6 112.6 112.6 112.6 97.9 68.0
1 These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor
efficiency.
2 These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J10YD/J10NM
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 141.7 6.6 68.4 58.8 49.3 - - - 136.3 7.2 65.9 56.5 47.2 - - -
72 129.3 6.4 86.6 74.2 61.8 49.4 - - 123.6 7.1 84.4 72.2 60.0 47.8 - -
2500
67 116.9 6.3 104.8 89.6 74.3 62.7 50.4 - 111.0 7.0 102.9 87.8 72.7 60.9 48.6 -
62 113.0 6.2 110.9 98.9 86.8 72.3 63.7 52.1 108.8 6.8 106.7 96.1 85.5 72.1 61.7 49.8
77 142.9 6.6 78.3 64.1 49.9 - - - 136.9 7.2 76.8 62.1 47.4 - - -
72 132.3 6.5 94.9 80.1 65.4 50.7 - - 126.5 7.1 92.8 78.1 63.3 48.6 - -
3000 67 121.7 6.4 111.5 96.2 80.9 66.5 51.5 - 116.0 7.0 108.7 94.0 79.3 64.6 49.7 -
62 118.8 6.3 115.9 106.2 96.4 79.3 67.0 52.4 114.4 6.9 111.6 103.4 95.3 79.1 65.4 50.5
57 116.0 6.2 116.0 116.0 111.9 97.3 82.6 68.0 112.9 6.8 112.9 112.9 111.3 96.2 81.2 66.1
77 144.1 6.6 88.2 69.3 50.5 - - - 137.5 7.2 87.8 67.7 47.5 - - -
72 135.3 6.5 103.1 86.0 69.0 51.9 - - 129.3 7.1 101.2 83.9 66.7 49.5 - -
3500 67 126.5 6.4 118.1 102.8 87.5 70.2 52.6 - 121.0 7.0 114.5 100.2 85.9 68.4 50.7 -
62 124.7 6.4 121.3 113.6 105.9 86.4 70.4 52.6 120.0 7.0 116.5 110.8 105.1 86.2 69.1 51.1
57 122.9 6.3 122.9 122.9 120.8 106.3 88.2 70.1 119.1 6.9 118.5 118.5 118.5 105.9 87.5 69.2
77 145.4 6.6 98.1 74.6 51.1 - - - 138.1 7.2 98.8 73.3 47.7 - - -
72 138.3 6.5 111.4 92.0 72.5 53.1 - - 132.1 7.1 109.6 89.8 70.1 50.3 - -
4000 67 131.3 6.4 124.7 109.4 94.0 74.0 53.7 - 126.0 7.0 120.3 106.4 92.5 72.2 51.7 -
62 130.5 6.4 126.5 121.0 115.5 93.4 73.8 52.9 125.7 7.0 121.4 118.1 114.8 93.2 72.8 51.8
57 129.7 6.4 128.2 128.2 128.2 115.4 93.8 72.2 125.3 7.0 122.5 122.5 122.5 115.6 93.9 72.3
72 141.4 6.5 119.7 97.9 76.1 54.4 - - 134.9 7.1 118.0 95.7 73.5 51.2 - -
67 136.6 6.5 131.3 116.0 100.6 77.8 54.9 - 131.5 7.1 126.1 112.6 99.0 75.9 52.7 -
4500
62 136.4 6.5 131.6 128.3 125.1 100.5 77.1 53.1 131.3 7.1 126.4 125.5 124.6 100.3 76.5 52.5
57 136.1 6.5 131.9 131.9 131.9 124.4 99.4 74.3 131.0 7.0 126.6 126.6 126.6 125.2 100.3 75.4
72 144.4 6.5 127.9 103.8 79.7 55.6 - - 137.8 7.1 126.4 101.6 76.8 52.1 - -
67 143.5 6.5 138.0 122.6 107.2 81.6 56.0 - 137.0 7.1 132.0 118.8 105.6 79.7 53.8 -
5000
62 142.2 6.5 138.2 135.7 134.6 107.5 80.5 53.4 136.9 7.1 132.9 132.8 132.9 107.3 80.2 53.2
57 140.9 6.5 139.0 139.0 139.0 133.5 104.9 76.4 136.1 7.1 133.1 133.1 133.1 133.1 106.7 78.5
95°F 105°F
77 130.8 7.9 63.4 54.2 45.1 - - - 127.2 8.5 62.7 53.8 44.9 - - -
72 118.0 7.7 82.2 70.1 58.1 46.1 - - 114.7 8.4 81.3 69.2 57.0 44.9 - -
2500
67 105.2 7.6 100.9 86.1 71.2 59.0 46.9 - 103.0 8.2 99.9 84.5 69.1 57.1 45.1 -
62 104.7 7.5 102.4 93.3 84.2 72.0 59.7 47.4 102.3 8.1 100.0 90.6 81.2 69.4 57.5 45.7
77 131.0 7.8 75.4 60.1 44.8 - - - 127.5 8.5 74.4 59.3 44.2 - - -
72 120.6 7.7 90.7 76.0 61.3 46.6 - - 117.3 8.3 89.4 74.7 60.0 45.4 - -
3000 67 110.4 7.6 105.9 91.8 77.7 62.8 47.8 - 108.1 8.2 104.5 90.1 75.8 61.0 46.1 -
62 110.0 7.5 107.1 100.6 94.2 79.0 63.8 48.5 107.5 8.1 104.6 98.1 91.6 76.6 61.6 46.6
57 109.7 7.4 108.2 108.2 108.2 95.2 79.7 64.2 107.0 8.0 105.0 105.0 105.0 92.3 77.1 61.9
77 131.4 7.8 87.5 66.0 44.6 - - - 127.9 8.4 86.0 64.8 43.6 - - -
72 123.2 7.7 99.2 81.8 64.5 47.1 - - 119.8 8.3 97.5 80.3 63.1 45.8 - -
3500 67 115.5 7.6 110.9 97.6 84.3 66.5 48.8 - 113.5 8.2 109.0 95.8 82.6 64.9 47.2 -
62 115.4 7.6 111.7 108.0 104.2 86.0 67.8 49.6 113.1 8.2 109.0 105.5 102.0 83.9 65.7 47.6
57 115.3 7.5 112.5 112.5 112.5 105.5 86.9 68.3 112.9 8.1 110.0 110.0 110.0 102.9 84.3 65.6
77 132.0 7.8 99.6 72.0 44.4 - - - 128.0 8.4 97.7 70.3 42.9 - - -
72 125.8 7.7 107.8 87.7 67.6 47.6 - - 122.4 8.3 105.6 85.9 66.1 46.3 - -
4000 67 120.9 7.7 115.9 103.4 90.9 70.3 49.7 - 118.2 8.2 113.5 101.4 89.3 68.7 48.2 -
62 120.8 7.6 116.4 115.3 114.2 93.0 71.9 50.8 117.9 8.2 113.8 112.9 112.4 91.1 69.8 48.5
57 120.5 7.6 116.9 116.9 116.9 115.8 94.1 72.4 117.0 8.1 114.0 114.0 114.0 113.5 91.4 69.4
72 128.4 7.7 116.3 93.5 70.8 48.0 - - 124.9 8.3 113.7 91.4 69.1 46.8 - -
67 126.5 7.7 120.9 109.2 97.5 74.0 50.6 - 123.6 8.3 118.0 107.0 96.0 72.6 49.2 -
4500
62 126.2 7.7 121.1 121.1 121.1 100.0 76.0 51.9 123.1 8.2 118.5 118.5 118.5 98.4 73.9 49.5
57 125.8 7.6 121.2 121.2 121.2 121.2 101.3 76.5 122.2 8.2 119.0 119.0 119.0 119.0 98.6 73.1
72 132.1 7.7 124.8 99.4 74.0 48.5 - - 128.9 8.3 121.8 97.0 72.2 47.3 - -
67 131.6 7.7 125.9 115.0 104.0 77.8 51.6 - 128.4 8.3 122.6 112.6 102.7 76.5 50.3 -
5000
62 131.1 7.7 126.7 126.7 126.7 107.1 80.0 53.0 127.8 8.3 123.0 123.0 123.0 105.6 78.0 50.4
57 130.5 7.7 128.6 128.6 128.6 128.6 108.5 80.6 127.1 8.3 123.5 123.5 123.5 123.5 105.8 76.8
J10YD/J10NM
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 120.1 9.8 61.4 53.0 44.6 - - - - - - - - - - -
72 108.2 9.6 79.6 67.2 54.8 42.4 - - - - - - - - - -
2500
67 97.5 9.5 95.4 81.4 65.0 53.3 41.6 - - - - - - - - -
62 96.4 9.3 96.0 85.2 75.2 64.2 53.2 42.2 - - - - - - - -
77 119.9 9.7 72.2 57.7 43.1 - - - - - - - - - - -
72 110.7 9.6 86.9 72.2 57.5 42.9 - - - - - - - - - -
3000 67 104.0 9.5 99.0 86.7 72.0 57.4 42.8 - - - - - - - - -
62 103.4 9.3 99.3 92.9 86.5 71.9 57.3 42.8 - - - - - - - -
57 102.5 9.2 101.0 97.1 97.1 86.4 71.9 57.4 - - - - - - - -
77 119.8 9.7 83.1 62.3 41.6 - - - - - - - - - - -
72 113.1 9.6 94.1 77.2 60.3 43.4 - - - - - - - - - -
3500 67 108.2 9.4 102.9 92.0 79.0 61.5 44.0 - - - - - - - - -
62 107.3 9.3 103.4 100.6 97.7 79.6 61.5 43.4 - - - - - - - -
57 106.4 9.2 105.0 101.8 101.8 97.7 79.0 60.3 - - - - - - - -
77 119.6 9.6 94.0 67.0 40.1 - - - - - - - - - - -
72 115.5 9.5 101.3 82.2 63.0 43.9 - - - - - - - - - -
4000 67 113.0 9.4 108.7 97.3 86.0 65.6 45.2 - - - - - - - - -
62 112.2 9.4 109.0 105.5 104.6 87.3 65.7 44.0 - - - - - - - -
57 111.4 9.3 110.1 106.4 106.4 106.4 86.1 63.2 - - - - - - - -
72 117.9 9.5 108.5 87.2 65.8 44.4 - - - - - - - - - -
67 117.7 9.4 112.2 102.6 93.0 69.7 46.4 - - - - - - - - -
4500
62 117.1 9.4 112.8 111.6 111.6 95.1 69.8 44.6 - - - - - - - -
57 116.3 9.4 113.2 112.0 112.0 112.0 93.3 66.1 - - - - - - - -
72 122.5 9.4 115.0 92.1 68.5 44.9 - - - - - - - - - -
67 122.0 9.4 115.5 107.9 100.0 73.8 47.7 - - - - - - - - -
5000
62 121.4 9.4 115.7 115.7 115.7 102.8 74.0 45.3 - - - - - - - -
57 120.6 9.4 116.0 116.0 116.0 116.0 100.4 69.0 - - - - - - - -
1 These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor
efficiency.
2 These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J12YC/J15NL
Air on Temperature of air on condenser Coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 178.5 10.2 87.6 71.1 54.7 - - - 172.2 11.3 84.0 67.6 51.2 - - -
72 168.2 9.9 111.9 95.4 78.9 62.4 - - 161.2 11.0 108.3 91.9 75.5 59.2 - -
3750 67 157.9 9.6 136.1 119.6 103.1 86.7 70.2 - 150.1 10.7 132.5 116.2 99.8 83.4 67.1 -
62 144.8 9.4 144.8 144.8 129.3 112.8 96.3 79.8 138.9 10.6 138.9 138.9 126.4 110.1 93.7 77.3
57 149.7 9.5 149.7 149.7 137.7 121.2 104.7 88.3 143.9 10.7 143.9 143.9 130.6 114.3 97.9 81.5
77 184.7 10.2 94.2 77.2 58.5 - - - 177.6 11.3 92.4 73.7 55.0 - - -
72 174.0 9.9 121.8 103.1 84.4 65.7 - - 166.2 11.0 118.4 99.8 81.1 62.4 - -
4375 67 163.4 9.6 149.5 129.0 110.3 91.6 72.9 - 154.7 10.8 144.5 125.8 107.1 88.4 69.8 -
62 149.9 9.4 149.9 149.9 138.2 119.8 100.8 82.1 143.2 10.6 143.2 143.2 135.7 117.0 98.4 79.7
57 154.9 9.5 154.9 154.9 147.3 129.1 109.8 91.1 148.4 10.7 148.4 148.4 140.2 121.6 102.9 84.2
77 190.9 10.3 100.7 83.2 62.3 - - - 182.9 11.3 100.8 79.8 58.8 - - -
72 179.9 9.9 131.8 110.8 89.9 68.9 - - 171.2 11.0 128.6 107.6 86.6 65.6 - -
5000 67 168.8 9.6 162.9 138.4 117.5 96.5 75.5 - 159.4 10.8 156.5 135.5 114.5 93.5 72.5 -
62 154.9 9.4 154.9 154.9 147.2 126.8 105.3 84.3 147.5 10.6 147.5 147.5 145.0 124.0 103.0 82.0
57 160.1 9.6 160.1 160.1 156.9 137.0 114.9 94.0 152.9 10.7 152.9 152.9 149.8 128.8 107.8 86.8
72 182.3 10.1 142.7 119.7 96.7 73.7 - - 174.1 11.2 139.0 116.1 93.1 70.2 - -
67 171.1 9.8 168.1 149.4 126.4 103.4 80.4 - 162.1 10.9 160.6 146.0 123.1 100.1 77.2 -
5625
62 157.0 9.6 157.0 157.0 153.1 130.4 107.1 84.1 150.0 10.7 150.0 150.0 148.8 125.8 102.9 79.9
57 162.2 9.7 162.2 162.2 160.6 138.1 114.6 91.6 155.5 10.8 155.5 155.5 153.9 131.0 108.1 85.1
72 184.7 10.2 153.7 128.6 103.6 78.5 - - 177.0 11.3 149.4 124.5 99.7 74.8 - -
67 173.4 9.9 173.4 160.4 135.4 110.4 85.3 - 164.8 11.0 164.8 156.6 131.7 106.8 81.9 -
6250
62 159.0 9.7 159.0 159.0 159.0 134.0 108.9 83.9 152.5 10.8 152.5 152.5 152.5 127.6 102.7 77.8
57 164.4 9.8 164.4 164.4 164.4 139.3 114.3 89.2 158.1 10.9 158.1 158.1 158.1 133.2 108.3 83.4
95°F 105°F
77 166.0 12.3 80.3 64.1 47.8 - - - 159.9 14.1 79.0 62.8 46.6 - - -
72 154.1 12.1 104.7 88.4 72.2 55.9 - - 148.2 13.8 102.8 86.6 70.4 54.2 - -
3750 67 142.3 11.9 129.0 112.7 96.5 80.2 64.0 - 136.4 13.5 126.7 110.5 94.2 78.0 61.8 -
62 132.9 11.7 132.9 132.9 123.6 107.4 91.1 74.9 130.6 13.4 130.6 130.6 122.0 105.8 89.6 73.4
57 138.2 11.8 138.2 138.2 123.6 107.3 91.1 74.8 134.7 13.5 134.7 134.7 119.4 103.2 87.0 70.8
77 170.5 12.3 90.6 70.2 51.6 - - - 163.0 14.0 91.5 68.6 50.0 - - -
72 158.3 12.1 115.0 96.4 77.8 59.1 - - 151.0 13.7 112.8 94.2 75.6 56.9 - -
4375 67 146.1 11.9 139.5 122.6 104.0 85.3 66.7 - 139.1 13.5 134.2 119.8 101.2 82.5 63.9 -
62 136.5 11.7 136.5 136.5 133.2 114.3 95.9 77.3 133.1 13.4 133.1 133.1 130.9 112.1 93.6 75.0
57 142.0 11.8 142.0 142.0 133.2 114.0 95.9 77.3 137.3 13.5 137.3 137.3 128.1 109.2 90.9 72.2
77 175.0 12.3 100.8 76.3 55.3 - - - 166.1 13.9 104.0 74.4 53.4 - - -
72 162.5 12.1 125.4 104.4 83.4 62.3 - - 153.9 13.7 122.9 101.8 80.7 59.6 - -
5000 67 150.0 11.9 150.0 132.5 111.5 90.4 69.4 - 141.7 13.4 141.7 129.1 108.1 87.0 65.9 -
62 140.1 11.7 140.1 140.1 142.8 121.2 100.7 79.7 135.6 13.3 135.6 135.6 139.8 118.5 97.7 76.6
57 145.7 11.8 145.7 145.7 142.8 120.7 100.7 79.7 140.0 13.4 140.0 140.0 136.9 115.3 94.8 73.7
72 165.9 12.2 135.3 112.4 89.5 66.7 - - 157.7 13.8 133.0 110.0 87.1 64.2 - -
67 153.1 12.0 153.1 142.6 119.7 96.8 73.9 - 145.2 13.5 145.2 138.0 116.6 93.7 70.8 -
5625
62 143.1 11.8 143.1 143.1 144.4 121.2 98.6 75.7 138.9 13.4 138.9 138.9 141.0 118.0 95.2 72.3
57 148.7 11.9 148.7 148.7 147.3 123.9 101.5 78.6 143.4 13.5 143.4 143.4 141.8 118.6 96.0 73.1
72 169.3 12.3 145.2 120.5 95.7 71.0 - - 161.4 14.0 143.0 118.3 93.5 68.7 - -
67 156.3 12.1 156.3 152.7 128.0 103.2 78.5 - 148.6 13.7 148.6 146.9 125.2 100.4 75.6 -
6250
62 146.0 11.9 146.0 146.0 146.0 121.3 96.5 71.8 142.2 13.6 142.2 142.2 142.2 117.5 92.7 67.9
57 151.8 12.0 151.8 151.8 151.8 127.0 102.3 77.6 146.8 13.7 146.8 146.8 146.8 122.0 97.2 72.5
J12YC/J15NL (Continued)
Air on Temperature of air on condenser Coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 153.8 15.8 77.6 61.4 45.3 - - - 147.7 17.5 76.3 60.1 44.0 - - -
72 142.2 15.5 101.0 84.8 68.7 52.5 - - 136.2 17.2 99.2 83.0 66.9 50.8 - -
3750 67 130.5 15.1 124.4 108.2 92.0 75.9 59.7 - 124.7 16.8 122.1 105.9 89.8 73.7 57.6 -
62 128.2 15.1 128.2 128.2 120.4 104.2 88.0 71.9 125.8 16.8 125.8 125.8 118.7 102.6 86.5 70.4
57 131.2 15.2 131.2 131.2 115.2 99.0 82.8 66.7 127.8 17.0 127.8 127.8 111.0 94.9 78.7 62.6
77 155.5 15.7 92.3 67.0 48.4 - - - 148.1 17.3 93.2 65.4 46.8 - - -
72 143.8 15.3 110.6 92.0 73.4 54.7 - - 136.5 17.0 108.4 89.8 71.2 52.5 - -
4375 67 132.0 15.0 128.9 117.0 98.3 79.7 61.1 - 125.0 16.6 123.7 114.2 95.5 76.9 58.3 -
62 129.7 15.0 129.7 129.7 128.6 110.0 91.3 72.7 126.2 16.7 126.2 126.2 126.2 107.8 89.1 70.4
57 132.7 15.1 132.7 132.7 123.1 104.4 85.8 67.2 128.1 16.8 128.1 128.1 118.0 99.7 80.8 62.1
77 157.3 15.5 107.1 72.6 51.5 - - - 148.4 17.1 110.2 70.7 49.6 - - -
72 145.4 15.2 120.3 99.2 78.1 57.0 - - 136.8 16.8 117.7 96.6 75.4 54.3 - -
5000 67 133.5 14.9 133.5 125.8 104.7 83.6 62.5 - 125.2 16.4 125.2 122.4 101.3 80.1 59.0 -
62 131.1 14.9 131.1 131.1 136.9 115.8 94.7 73.6 126.6 16.5 126.6 126.6 126.6 113.1 91.6 70.5
57 134.2 15.0 134.2 134.2 131.0 109.9 88.8 67.7 128.5 16.6 128.5 128.5 125.1 104.5 82.8 61.7
72 149.5 15.4 130.6 107.6 84.7 61.7 - - 141.3 17.0 128.2 105.2 82.3 59.3 - -
67 137.3 15.1 137.3 133.4 113.5 90.6 67.6 - 129.3 16.6 129.3 128.8 110.4 87.5 64.5 -
5625
62 134.8 15.1 134.8 134.8 137.7 114.7 91.8 68.8 130.7 16.7 130.7 130.7 130.7 111.5 88.4 65.4
57 138.0 15.2 138.0 138.0 136.4 113.4 90.5 67.5 132.6 16.8 132.6 132.6 130.9 108.2 84.9 62.0
72 153.6 15.6 140.9 116.1 91.3 66.5 - - 145.7 17.2 138.7 113.9 89.1 64.3 - -
67 141.0 15.3 141.0 141.0 122.4 97.6 72.8 - 133.4 16.8 133.4 133.4 119.6 94.8 69.9 -
6250
62 138.5 15.3 138.5 138.5 138.5 113.7 88.9 64.1 134.7 16.9 134.7 134.7 134.7 109.9 85.1 60.2
57 141.8 15.4 141.8 141.8 141.8 117.0 92.2 67.4 136.7 17.1 136.7 136.7 136.7 111.9 87.1 62.3
1 These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor
efficiency.
2 These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J12YD/J15NM
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) Capacity1 Input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 175.3 8.9 99.4 80.2 61.0 - - - 169.8 10.0 96.1 78.2 60.2 - - -
72 158.4 8.7 109.1 93.2 77.3 61.4 - - 152.8 9.9 105.9 90.7 75.5 60.2 - -
3125
67 141.6 8.6 118.9 106.2 93.6 76.0 62.3 - 135.8 9.8 115.6 103.1 90.7 74.7 60.6 -
62 132.6 8.4 132.6 122.1 109.9 90.1 79.0 63.6 129.5 9.7 129.5 118.9 106.0 88.9 76.1 61.2
77 175.6 9.0 105.2 83.9 62.6 - - - 169.6 10.0 103.0 82.0 61.0 - - -
72 161.6 8.8 118.1 99.9 81.8 63.6 - - 155.5 9.9 114.8 97.2 79.5 61.8 - -
3750 67 147.5 8.6 131.0 116.0 100.9 81.2 64.7 - 141.5 9.8 126.7 112.3 97.9 79.5 62.6 -
62 140.1 8.5 132.0 131.1 120.1 98.5 83.9 65.8 136.4 9.7 130.0 127.7 116.4 96.9 81.0 63.3
57 132.7 8.3 132.7 132.7 132.7 121.2 103.1 85.1 130.1 9.7 130.1 130.1 130.1 117.1 99.4 81.6
77 176.0 9.0 111.1 87.7 64.2 - - - 169.4 10.1 109.8 85.8 61.9 - - -
72 164.7 8.8 127.1 106.7 86.2 65.8 - - 158.3 10.0 123.8 103.6 83.5 63.4 - -
4375 67 153.5 8.7 141.0 125.7 108.2 86.5 67.1 - 147.2 9.8 136.0 121.5 105.2 84.3 64.5 -
62 147.7 8.6 141.6 140.2 130.2 106.9 88.7 68.0 143.3 9.8 136.5 136.5 126.8 105.0 85.8 65.3
57 141.9 8.5 141.9 141.9 141.9 131.3 110.4 89.5 139.3 9.8 139.3 139.3 139.3 127.8 107.1 86.4
77 176.3 9.0 117.0 91.4 65.9 - - - 169.2 10.1 116.6 89.7 62.7 - - -
72 167.9 8.9 136.1 113.4 90.7 68.0 - - 161.0 10.0 132.7 110.1 87.5 65.0 - -
5000 67 159.4 8.7 150.0 135.4 115.5 91.7 69.4 - 152.8 9.9 144.9 130.6 112.4 89.1 66.5 -
62 155.2 8.7 150.5 149.3 140.4 115.2 93.6 70.2 150.1 9.9 145.0 145.0 137.2 113.1 90.7 67.4
57 151.0 8.7 151.0 151.0 151.0 141.5 117.7 94.0 147.4 9.9 147.4 147.4 147.4 138.5 114.9 91.2
72 171.0 8.9 145.1 120.1 95.2 70.2 - - 163.7 10.0 141.7 116.6 91.6 66.5 - -
67 165.3 8.8 159.8 145.1 122.9 97.0 71.8 - 158.5 10.0 154.0 139.8 119.6 93.9 68.5 -
5625
62 162.7 8.8 160.0 158.3 150.6 123.6 98.4 72.4 157.0 10.0 154.5 154.1 147.7 121.2 95.5 69.5
57 160.2 8.8 160.2 160.2 160.2 151.6 125.0 98.4 155.5 10.0 155.5 155.5 155.5 149.1 122.6 96.0
72 174.1 9.0 154.1 126.9 99.6 72.4 - - 166.5 10.1 150.7 123.1 95.6 68.1 - -
67 171.2 8.9 168.1 154.8 130.2 102.2 74.2 - 164.2 10.1 163.4 149.0 126.8 98.7 70.5 -
6250
62 170.3 8.9 169.0 167.4 160.7 132.0 103.3 74.6 163.9 10.1 163.6 162.8 158.1 129.2 100.4 71.6
57 169.3 8.8 169.3 169.3 169.3 161.8 132.4 102.9 163.6 10.1 163.6 163.6 163.6 159.8 130.3 100.8
95°F 105°F
77 164.2 11.1 92.9 76.2 59.4 - - - 154.5 13.0 88.8 72.2 55.6 - - -
72 147.2 11.1 102.6 88.1 73.6 59.1 - - 139.1 13.0 99.5 84.9 70.3 55.7 - -
3125
67 130.1 11.0 112.2 100.0 87.8 73.4 58.9 - 123.7 13.0 110.2 97.6 84.9 70.3 55.7 -
62 126.5 10.9 126.5 115.7 102.0 87.6 73.2 58.8 122.1 12.8 122.1 112.0 99.6 85.0 70.4 55.9
77 163.5 11.1 100.7 80.1 59.4 - - - 154.0 13.0 97.2 76.6 56.0 - - -
72 149.5 11.1 111.5 94.4 77.2 60.0 - - 141.6 12.9 108.3 91.1 74.0 56.8 - -
3750 67 135.5 11.0 122.3 108.6 95.0 77.7 60.5 - 129.1 12.9 119.4 105.7 92.0 74.6 57.3 -
62 132.7 11.0 129.0 124.2 112.7 95.4 78.0 60.7 127.8 12.8 127.4 120.3 110.0 92.4 74.9 57.3
57 129.8 11.0 129.8 129.8 129.8 113.1 95.6 78.2 126.5 12.7 126.5 126.5 126.5 110.2 92.4 74.7
77 162.8 11.1 108.5 84.0 59.5 - - - 153.6 12.9 105.6 81.0 56.4 - - -
72 151.8 11.1 120.4 100.6 80.8 61.0 - - 144.1 12.9 117.1 97.4 77.7 58.0 - -
4375 67 140.9 11.0 132.4 117.3 102.1 82.1 62.0 - 134.6 12.8 128.5 113.8 99.1 78.9 58.8 -
62 138.9 11.0 136.2 132.7 123.4 103.2 82.9 62.7 133.6 12.8 133.0 128.5 120.4 99.8 79.3 58.7
57 136.8 11.0 136.8 136.8 136.8 124.2 103.8 83.4 132.6 12.7 132.6 132.6 132.6 120.7 99.7 78.7
77 162.1 11.1 116.2 87.9 59.5 - - - 153.1 12.9 114.0 85.4 56.8 - - -
72 154.2 11.1 129.4 106.9 84.4 61.9 - - 146.5 12.8 125.8 103.6 81.4 59.2 - -
5000 67 146.3 11.1 142.5 125.9 109.2 86.4 63.6 - 140.0 12.8 137.7 121.9 106.1 83.2 60.4 -
62 145.0 11.1 143.0 141.3 134.1 110.9 87.8 64.6 139.3 12.7 139.0 136.7 130.8 107.3 83.7 60.2
57 143.8 11.1 143.8 143.8 143.8 135.4 112.0 88.5 138.6 12.7 138.6 138.6 138.6 131.3 107.1 82.8
72 156.5 11.1 138.3 113.1 88.0 62.8 - - 149.0 12.8 134.6 109.9 85.2 60.4 - -
67 151.7 11.1 150.5 134.5 116.4 90.8 65.2 - 145.5 12.7 145.5 130.0 113.2 87.6 61.9 -
5625
62 151.2 11.1 150.6 149.8 144.8 118.7 92.6 66.6 145.0 12.7 144.8 144.8 141.2 114.7 88.1 61.6
57 150.8 11.1 150.8 150.8 150.8 146.6 120.1 93.6 144.6 12.7 144.6 144.6 144.6 141.8 114.4 86.9
72 158.8 11.1 147.2 119.4 91.6 63.8 - - 151.5 12.7 143.4 116.1 88.9 61.6 - -
67 157.1 11.1 157.1 143.1 123.5 95.1 66.7 - 150.9 12.7 150.5 138.2 120.3 91.9 63.5 -
6250
62 157.4 11.1 157.4 157.4 155.4 126.5 97.5 68.6 150.8 12.7 150.5 150.5 150.5 122.1 92.6 63.0
57 157.8 11.1 157.8 157.8 157.8 157.8 128.3 98.8 150.7 12.7 150.7 150.7 150.7 150.7 121.7 91.0
J12YD/J15NM (Continued)
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) Capacity1 Input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 144.8 15.0 84.7 68.3 51.9 - - - 135.1 16.9 80.6 64.4 48.1 - - -
72 131.0 15.0 96.5 81.7 67.0 52.2 - - 123.0 16.9 93.4 78.5 63.6 48.7 - -
3125
67 120.1 15.0 108.2 95.1 82.0 67.3 52.6 - 117.3 16.8 106.1 92.6 79.1 64.2 49.4 -
62 117.7 14.7 117.7 108.4 97.1 82.4 67.7 53.0 113.3 16.6 113.3 104.7 94.6 79.8 64.9 50.1
77 144.6 14.8 93.7 73.2 52.6 - - - 135.1 16.8 90.3 69.7 49.2 - - -
72 133.7 14.8 105.1 87.9 70.8 53.7 - - 125.7 16.7 101.9 84.7 67.6 50.5 - -
3750 67 125.2 14.8 116.4 102.7 89.0 71.6 54.1 - 123.2 16.6 113.5 99.8 86.0 68.5 50.9 -
62 124.0 14.6 123.0 116.3 107.2 89.4 71.7 53.9 121.9 16.4 119.8 112.3 104.5 86.5 68.5 50.5
57 123.3 14.4 123.3 123.3 123.3 107.3 89.2 71.1 120.0 16.1 120.0 120.0 120.0 104.5 86.0 67.6
77 144.3 14.7 102.7 78.0 53.3 - - - 135.1 16.5 99.9 75.0 50.2 - - -
72 136.3 14.7 113.7 94.2 74.6 55.1 - - 128.5 16.5 110.3 90.9 71.6 52.2 - -
4375 67 129.0 14.7 124.7 110.3 96.0 75.8 55.6 - 125.6 16.5 120.8 106.9 93.0 72.7 52.4 -
62 128.6 14.5 128.0 124.2 117.4 96.5 75.7 54.8 125.0 16.3 123.6 119.9 114.4 93.2 72.0 50.8
57 128.3 14.4 128.3 128.3 128.3 117.2 95.7 74.1 124.1 16.0 124.1 124.1 124.1 113.7 91.6 69.5
77 144.1 14.6 111.7 82.8 54.0 - - - 135.1 16.3 109.5 80.3 51.2 - - -
72 138.9 14.5 122.3 100.4 78.5 56.6 - - 131.3 16.3 118.8 97.2 75.5 53.9 - -
5000 67 133.7 14.5 132.9 118.0 103.0 80.1 57.2 - 130.0 16.2 128.1 114.0 99.9 76.9 53.9 -
62 133.6 14.4 133.3 132.1 127.5 103.6 79.6 55.7 129.1 16.1 128.1 127.5 124.3 99.9 75.6 51.2
57 133.4 14.3 133.4 133.4 133.4 127.1 102.1 77.2 128.2 16.0 128.2 128.2 128.2 122.9 97.2 71.5
72 141.5 14.4 130.9 106.6 82.3 58.0 - - 134.0 16.1 127.2 103.4 79.5 55.6 - -
67 139.2 14.3 139.2 125.6 110.0 84.3 58.7 - 133.0 15.9 132.0 121.1 106.8 81.1 55.4 -
5625
62 138.8 14.3 138.8 138.8 137.7 110.7 83.6 56.6 132.6 15.9 132.1 132.1 132.1 106.6 79.1 51.6
57 138.4 14.3 138.4 138.4 138.4 137.0 108.6 80.2 132.2 15.9 132.2 132.2 132.2 132.2 102.8 73.5
72 145.0 14.3 139.6 112.9 86.2 59.5 - - 139.0 15.9 135.7 109.6 83.5 57.4 - -
67 144.7 14.3 143.1 133.2 117.0 88.6 60.2 - 138.6 15.9 136.0 128.2 113.8 85.4 57.0 -
6250
62 144.1 14.3 143.4 143.4 143.4 117.7 87.6 57.5 137.5 15.9 136.1 136.1 136.1 113.4 82.7 52.0
57 143.5 14.3 143.5 143.5 143.5 143.5 115.0 83.2 136.3 15.9 136.3 136.3 136.3 136.3 108.4 75.5
1 These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor
efficiency.
2 These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J15YC/J15NL
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 223.5 11.8 104.0 85.0 66.0 - - - 214.6 13.1 101.2 82.2 63.3 - - -
72 207.2 11.5 132.3 113.3 94.4 75.4 - - 198.3 12.8 129.0 110.1 91.2 72.2 - -
4500 67 191.0 11.1 160.6 141.7 122.7 103.7 84.7 - 181.9 12.4 156.8 137.9 119.0 100.1 81.1 -
62 176.0 10.8 176.0 171.9 151.4 132.5 113.5 94.5 168.5 12.2 168.5 166.4 147.5 128.6 109.7 90.8
57 175.0 10.8 175.0 175.0 158.1 139.1 120.1 101.1 168.1 12.1 168.1 168.1 150.6 131.7 112.8 93.8
77 229.4 11.9 113.7 92.3 70.8 - - - 220.1 13.2 110.7 89.4 68.1 - - -
72 212.8 11.6 144.1 122.7 101.2 79.7 - - 203.3 12.8 140.7 119.4 98.1 76.8 - -
5250 67 196.1 11.2 174.5 153.0 131.6 110.1 88.7 - 186.5 12.5 170.6 149.3 128.0 106.7 85.4 -
62 180.7 11.0 180.7 178.6 162.4 141.9 119.5 98.1 172.7 12.2 172.7 171.7 158.7 137.4 116.1 94.8
57 179.7 10.9 179.7 179.7 169.6 149.6 126.6 105.2 172.4 12.2 172.4 172.4 162.0 140.7 119.4 98.1
77 235.4 12.0 123.5 99.5 75.6 - - - 225.5 13.3 120.3 96.6 72.9 - - -
72 218.3 11.7 155.9 132.0 108.0 84.1 - - 208.3 12.9 152.3 128.6 105.0 81.3 - -
6000 67 201.2 11.3 188.3 164.4 140.5 116.5 92.6 - 191.1 12.6 184.4 160.7 137.0 113.4 89.7 -
62 185.4 11.1 185.4 185.4 173.4 151.3 125.5 101.6 177.0 12.3 177.0 177.0 169.9 146.2 122.6 98.9
57 184.4 11.0 184.4 184.4 181.0 160.1 133.2 109.2 176.6 12.3 176.6 176.6 173.5 149.8 126.1 102.4
72 221.3 11.3 165.2 139.4 113.7 88.0 - - 213.7 13.6 165.8 140.1 114.5 88.8 - -
67 204.0 11.0 197.5 174.0 147.8 122.0 96.3 - 196.0 13.3 192.7 175.1 149.4 123.8 98.1 -
6750
62 187.9 10.7 187.9 187.9 181.9 157.1 130.4 104.7 181.5 13.0 181.5 181.5 178.0 152.4 126.7 101.1
57 186.8 10.6 186.8 186.8 185.2 161.0 133.7 108.0 181.2 13.0 181.2 181.2 179.6 153.9 128.3 102.6
72 224.2 10.9 174.4 146.9 119.4 91.8 - - 219.0 14.3 179.2 151.6 123.9 96.3 - -
67 206.7 10.6 206.7 183.6 155.1 127.6 100.0 - 201.0 14.0 201.0 189.4 161.8 134.1 106.5 -
7500
62 190.4 10.3 190.4 190.4 190.4 162.8 135.3 107.8 186.1 13.7 186.1 186.1 186.1 158.5 130.9 103.2
57 189.3 10.3 189.3 189.3 189.3 161.8 134.3 106.7 185.7 13.7 185.7 185.7 185.7 158.1 130.5 102.9
95°F 105°F
77 205.8 14.4 98.3 79.5 60.6 - - - 195.5 15.9 95.5 76.6 57.7 - - -
72 189.3 14.0 125.7 106.8 87.9 69.1 - - 179.9 15.7 122.5 103.6 84.7 65.9 - -
4500 67 172.8 13.7 153.0 134.1 115.3 96.4 77.5 - 164.3 15.4 149.5 130.7 111.8 92.9 74.0 -
62 161.0 13.5 161.0 161.0 143.6 124.7 105.9 87.0 153.2 15.2 153.2 153.2 139.8 120.9 102.0 83.1
57 161.3 13.5 161.3 161.3 143.1 124.3 105.4 86.6 154.3 15.2 154.3 154.3 136.3 117.4 98.5 79.6
77 210.7 14.4 107.7 86.6 65.4 - - - 199.9 16.0 107.5 83.6 62.4 - - -
72 193.8 14.1 137.2 116.1 94.9 73.8 - - 183.9 15.8 134.0 112.8 91.6 70.4 - -
5250 67 176.9 13.8 166.7 145.6 124.4 103.3 82.2 - 168.0 15.5 160.4 142.0 120.8 99.6 78.3 -
62 164.8 13.5 164.8 164.8 155.0 132.9 112.7 91.6 156.6 15.2 156.6 156.6 151.0 129.4 108.6 87.4
57 165.1 13.6 165.1 165.1 154.5 131.9 112.2 91.1 157.7 15.2 157.7 157.7 147.2 125.3 104.8 83.6
77 215.5 14.5 117.1 93.7 70.2 - - - 204.2 16.1 119.5 90.5 67.0 - - -
72 198.3 14.2 148.7 125.3 101.9 78.5 - - 187.9 15.8 145.4 121.9 98.4 74.9 - -
6000 67 181.0 13.8 180.4 157.0 133.6 110.2 86.8 - 171.6 15.6 171.3 153.3 129.7 106.2 82.7 -
62 168.6 13.6 168.6 168.6 166.4 141.1 119.6 96.2 160.0 15.3 160.0 160.0 162.3 137.8 115.3 91.7
57 168.9 13.6 168.9 168.9 165.9 139.4 119.1 95.6 161.2 15.3 161.2 161.2 158.2 133.2 111.2 87.6
72 206.1 15.9 166.4 140.8 115.2 89.7 - - 192.5 16.7 159.1 133.4 107.7 82.0 - -
67 188.1 15.6 187.8 176.1 151.0 125.5 99.9 - 175.8 16.4 175.7 166.6 142.0 116.3 90.7 -
6750
62 175.2 15.3 175.2 175.2 174.1 147.6 123.0 97.4 164.0 16.2 164.0 164.0 165.1 139.0 113.7 88.1
57 175.5 15.3 175.5 175.5 174.0 146.9 122.9 97.3 165.1 16.2 165.1 165.1 163.6 137.2 112.3 86.6
72 213.9 17.7 184.0 156.3 128.5 100.8 - - 197.2 17.6 172.7 144.9 117.0 89.2 - -
67 195.2 17.3 195.2 195.2 168.5 140.7 113.0 - 180.0 17.3 180.0 180.0 154.3 126.5 98.6 -
7500
62 181.9 17.0 181.9 181.9 181.9 154.1 126.4 98.6 167.9 17.0 167.9 167.9 167.9 140.1 112.2 84.4
57 182.2 17.0 182.2 182.2 182.2 154.4 126.7 99.0 169.0 17.0 169.0 169.0 169.0 141.2 113.4 85.6
J15YC/J15NL
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 185.3 17.5 92.7 73.7 54.8 - - - 175.0 19.1 89.8 70.9 51.9 - - -
72 170.5 17.3 119.4 100.5 81.5 62.6 - - 161.1 18.9 116.2 97.3 78.4 59.4 - -
4500 67 155.8 17.1 146.1 127.2 108.3 89.3 70.4 - 147.2 18.8 142.6 123.7 104.8 85.8 66.9 -
62 145.5 16.9 145.5 145.5 136.0 117.1 98.2 79.3 137.7 18.6 137.7 137.7 132.2 113.3 94.3 75.4
57 147.3 16.8 147.3 147.3 129.4 110.5 91.6 72.7 140.3 18.5 140.3 140.3 122.6 103.6 84.7 65.8
77 189.1 17.6 107.3 80.6 59.3 - - - 178.3 19.2 107.1 77.6 56.2 - - -
72 174.1 17.4 130.7 109.5 88.2 66.9 - - 164.2 19.1 127.5 106.2 84.8 63.5 - -
5250 67 159.0 17.2 154.2 138.3 117.1 95.8 74.5 - 150.1 18.9 147.9 134.7 113.4 92.1 70.7 -
62 148.5 17.0 148.5 148.5 147.1 125.8 104.5 83.3 140.3 18.7 140.3 140.3 140.3 122.2 100.4 79.1
57 150.4 16.9 150.4 150.4 140.0 118.7 97.4 76.2 143.0 18.6 143.0 143.0 132.7 112.1 90.0 68.7
77 192.9 17.7 121.9 87.4 63.8 - - - 181.6 19.3 124.4 84.3 60.5 - - -
72 177.6 17.5 142.1 118.5 94.8 71.2 - - 167.3 19.2 138.8 115.0 91.3 67.6 - -
6000 67 162.2 17.3 162.2 149.5 125.9 102.3 78.6 - 152.9 19.0 152.9 145.8 122.1 98.3 74.6 -
62 151.5 17.0 151.5 151.5 158.2 134.5 110.9 87.3 142.9 18.8 142.9 142.9 142.9 131.2 106.6 82.8
57 153.4 17.0 153.4 153.4 150.5 126.9 103.3 79.6 145.7 18.7 145.7 145.7 142.8 120.6 95.4 71.6
72 179.0 17.5 151.7 126.0 100.2 74.4 - - 165.5 18.3 144.4 118.5 92.7 66.8 - -
67 163.5 17.3 163.5 157.2 133.0 107.2 81.5 - 151.3 18.2 151.3 147.7 124.0 98.1 72.3 -
6750
62 152.7 17.0 152.7 152.7 156.0 130.3 104.5 78.7 141.4 17.9 141.4 141.4 141.4 121.6 95.3 69.4
57 154.7 17.0 154.7 154.7 153.2 127.4 101.7 75.9 144.2 17.9 144.2 144.2 142.8 117.7 91.0 65.2
72 180.4 17.5 161.4 133.5 105.5 77.6 - - 163.7 17.4 150.1 122.1 94.1 66.0 - -
67 164.8 17.3 164.8 164.8 140.1 112.2 84.3 - 149.7 17.3 149.7 149.7 125.9 97.9 69.9 -
7500
62 153.9 17.0 153.9 153.9 153.9 126.0 98.1 70.2 140.0 17.1 140.0 140.0 140.0 112.0 83.9 55.9
57 155.9 17.0 155.9 155.9 155.9 128.0 100.1 72.1 142.7 17.0 142.7 142.7 142.7 114.7 86.7 58.7
1 These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor
efficiency.
2 These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J15YD/J15NM
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 218.6 12.6 99.2 83.3 67.4 - - - 213.3 13.8 96.4 79.9 63.5 - - -
72 205.5 12.1 124.0 108.1 92.2 76.2 - - 199.4 13.4 122.0 105.5 89.1 72.6 - -
3750
67 192.4 11.7 148.8 132.9 117.0 101.0 85.1 - 185.5 13.1 147.6 131.1 114.6 98.2 81.7 -
62 184.8 11.4 184.8 160.1 142.1 126.2 110.2 94.3 175.3 12.8 175.3 159.7 138.4 121.9 105.5 89.0
77 225.1 12.7 109.7 91.8 73.9 - - - 219.1 13.8 106.1 87.7 69.4 - - -
72 211.6 12.2 136.9 119.0 101.1 83.3 - - 204.8 13.5 134.0 115.7 97.4 79.1 - -
4500 67 198.1 11.8 164.1 146.2 128.4 110.5 92.6 - 190.6 13.1 162.0 143.7 125.4 107.1 88.8 -
62 190.3 11.5 190.3 173.8 155.9 138.1 120.2 102.3 180.1 12.9 180.1 169.7 151.4 133.1 114.7 96.4
57 172.5 11.3 172.5 172.5 158.3 140.4 122.5 104.7 172.4 12.9 172.4 172.4 155.0 136.6 118.3 100.0
77 231.7 12.8 120.1 100.3 80.5 - - - 224.9 13.9 115.7 95.5 75.4 - - -
72 217.8 12.3 149.7 129.9 110.1 90.3 - - 210.3 13.5 146.1 125.9 105.8 85.6 - -
5250 67 203.9 11.9 179.4 159.6 139.8 120.0 100.2 - 195.6 13.2 176.5 156.3 136.1 116.0 95.8 -
62 195.8 11.6 195.8 187.6 169.8 150.0 130.2 110.4 184.9 12.9 184.9 179.7 164.4 144.2 124.0 103.8
57 177.6 11.4 177.6 177.6 172.3 152.5 132.7 112.9 177.0 12.9 177.0 177.0 168.2 148.1 127.9 107.7
77 238.2 12.8 130.5 108.7 87.0 - - - 230.7 13.9 125.4 103.3 81.3 - - -
72 223.9 12.4 162.5 140.8 119.1 97.3 - - 215.7 13.6 158.2 136.1 114.1 92.1 - -
6000 67 209.6 11.9 194.6 172.9 151.2 129.4 107.7 - 200.7 13.2 191.0 168.9 146.9 124.9 102.8 -
62 201.3 11.6 201.3 201.3 183.6 161.9 140.1 118.4 189.7 13.0 189.7 189.7 177.3 155.3 133.3 111.2
57 182.6 11.5 182.6 182.6 182.6 164.6 142.9 121.2 181.5 13.0 181.5 181.5 181.5 159.5 137.5 115.4
72 228.7 12.5 173.9 149.9 125.9 101.9 - - 219.9 13.7 170.4 146.0 121.5 97.0 - -
67 214.1 12.1 206.6 183.7 159.8 135.8 111.8 - 204.5 13.3 199.7 180.9 156.4 131.9 107.4 -
6750
62 205.6 11.8 205.6 205.6 196.7 172.7 148.7 124.8 193.3 13.1 193.3 193.3 187.2 162.7 138.2 113.7
57 186.5 11.6 186.5 186.5 186.5 164.4 140.4 116.4 185.0 13.1 185.0 185.0 185.0 160.5 136.1 111.6
72 233.4 12.7 185.2 158.9 132.7 106.4 - - 224.0 13.8 182.7 155.8 128.9 101.9 - -
67 218.5 12.2 218.5 194.6 168.4 142.1 115.9 - 208.4 13.4 208.4 192.8 165.9 139.0 112.1 -
7500
62 209.8 11.9 209.8 209.8 209.8 183.6 157.3 131.1 197.0 13.2 197.0 197.0 197.0 170.1 143.1 116.2
57 190.4 11.8 190.4 190.4 190.4 164.1 137.9 111.6 188.5 13.2 188.5 188.5 188.5 161.6 134.7 107.8
95°F 105°F
77 208.0 15.0 93.5 76.5 59.6 - - - 199.1 16.8 88.3 74.5 57.6 - - -
72 193.3 14.7 119.9 102.9 85.9 68.9 - - 184.5 16.6 117.4 100.5 83.5 66.5 - -
3750
67 178.6 14.5 146.3 129.3 112.3 95.3 78.3 - 169.8 16.4 146.6 126.4 109.4 92.4 75.5 -
62 165.9 14.3 165.9 159.4 134.7 117.7 100.7 83.7 159.3 16.3 159.3 156.1 131.5 114.6 97.6 80.6
77 213.1 15.0 102.4 83.7 64.9 - - - 203.6 16.8 101.0 81.8 62.7 - - -
72 198.0 14.7 131.2 112.4 93.7 74.9 - - 188.6 16.6 129.2 110.1 90.9 71.7 - -
4500 67 183.0 14.5 160.0 141.2 122.4 103.7 84.9 - 173.7 16.4 157.5 138.3 119.1 100.0 80.8 -
62 169.9 14.3 169.9 165.6 146.8 128.1 109.3 90.5 162.9 16.3 162.9 160.7 143.2 124.1 104.9 85.7
57 172.2 14.4 172.2 170.4 151.6 132.9 114.1 95.3 165.1 16.3 165.1 164.2 145.2 126.0 106.8 87.7
77 218.2 15.0 111.4 90.8 70.3 - - - 208.1 16.8 113.8 89.2 67.8 - - -
72 202.8 14.8 142.5 121.9 101.4 80.9 - - 192.8 16.6 141.0 119.7 98.3 77.0 - -
5250 67 187.4 14.5 173.6 153.1 132.5 112.0 91.4 - 177.5 16.4 168.3 150.2 128.9 107.5 86.1 -
62 174.0 14.3 174.0 171.8 158.9 138.4 117.9 97.3 166.5 16.3 166.5 165.4 154.9 133.6 112.2 90.9
57 176.4 14.4 176.4 175.4 164.2 143.6 123.1 102.5 168.7 16.4 168.7 168.3 157.0 135.6 114.3 92.9
77 223.2 15.0 120.3 98.0 75.6 - - - 212.6 16.8 126.5 96.5 72.9 - - -
72 207.5 14.8 153.8 131.5 109.1 86.8 - - 197.0 16.6 152.8 129.3 105.7 82.2 - -
6000 67 191.7 14.5 187.3 165.0 142.6 120.3 98.0 - 181.3 16.4 179.1 162.1 138.6 115.0 91.5 -
62 178.0 14.3 178.0 178.0 171.1 148.7 126.4 104.1 170.1 16.3 170.1 170.1 166.6 143.1 119.5 96.0
57 180.5 14.4 180.5 180.5 176.7 154.3 132.0 109.7 172.4 16.4 172.4 172.4 168.8 145.3 121.8 98.2
72 211.1 14.8 167.0 142.1 117.1 92.1 - - 201.2 16.6 166.0 140.0 114.0 88.0 - -
67 195.0 14.6 192.8 178.0 153.0 128.1 103.1 - 185.2 16.4 184.1 173.8 149.4 123.4 97.4 -
6750
62 181.1 14.4 181.1 181.1 177.6 152.6 127.7 102.7 173.7 16.3 173.7 173.7 172.0 146.0 120.0 94.0
57 183.6 14.5 183.6 183.6 181.7 156.7 131.7 106.8 176.1 16.4 176.1 176.1 174.3 148.3 122.4 96.4
72 214.6 14.9 180.2 152.6 125.0 97.4 - - 205.4 16.6 179.1 150.7 122.2 93.8 - -
67 198.3 14.6 198.3 191.0 163.4 135.8 108.2 - 189.1 16.4 189.1 185.5 160.2 131.7 103.3 -
7500
62 184.1 14.4 184.1 184.1 184.1 156.5 128.9 101.3 177.4 16.3 177.4 177.4 177.4 149.0 120.5 92.1
57 186.7 14.5 186.7 186.7 186.7 159.1 131.5 103.9 179.8 16.3 179.8 179.8 179.8 151.4 122.9 94.5
J15YD/J15NM (Continued)
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 190.3 18.6 83.0 72.6 55.6 - - - 181.4 20.3 76.6 70.6 53.6 - - -
72 175.7 18.5 115.0 98.0 81.1 64.1 - - 166.8 20.3 112.5 95.6 78.6 61.7 - -
3750
67 161.0 18.4 147.0 123.5 106.5 89.6 72.6 - 152.2 20.3 147.4 120.6 103.6 86.7 69.7 -
62 152.8 18.3 152.8 152.8 128.4 111.4 94.5 77.5 146.2 20.3 146.2 146.2 125.2 108.3 91.3 74.4
77 194.2 18.5 99.6 80.0 60.5 - - - 184.7 20.3 98.1 78.2 58.2 - - -
72 179.2 18.5 127.3 107.7 88.2 68.6 - - 169.9 20.3 125.3 105.4 85.4 65.4 - -
4500 67 164.3 18.4 155.0 135.4 115.9 96.3 76.7 - 155.0 20.3 152.5 132.5 112.6 92.6 72.6 -
62 155.9 18.3 155.9 155.9 139.6 120.1 100.5 80.9 148.9 20.3 148.9 148.9 136.0 116.1 96.1 76.2
57 158.0 18.3 158.0 158.0 138.7 119.1 99.6 80.0 150.8 20.2 150.8 150.8 132.2 112.3 92.3 72.3
77 198.1 18.5 116.2 87.5 65.3 - - - 188.0 20.3 119.7 85.8 62.8 - - -
72 182.8 18.5 139.6 117.4 95.3 73.1 - - 172.9 20.3 138.1 115.1 92.2 69.2 - -
5250 67 167.6 18.4 162.9 147.3 125.2 103.0 80.9 - 157.8 20.3 157.6 144.5 121.5 98.5 75.6 -
62 159.0 18.3 159.0 159.0 150.9 128.7 106.6 84.4 151.5 20.3 151.5 151.5 146.8 123.9 100.9 78.0
57 161.1 18.3 161.1 161.1 149.9 127.7 105.5 83.4 153.5 20.2 153.5 153.5 142.7 119.7 96.8 73.8
77 201.9 18.5 132.8 94.9 70.2 - - - 191.3 20.3 141.2 93.4 67.5 - - -
72 186.4 18.4 151.9 127.1 102.3 77.6 - - 175.9 20.3 150.9 124.9 99.0 73.0 - -
6000 67 170.9 18.4 170.9 159.3 134.5 109.8 85.0 - 160.5 20.3 160.5 156.4 130.4 104.5 78.5 -
62 162.1 18.3 162.1 162.1 162.1 137.4 112.6 87.9 154.2 20.2 154.2 154.2 154.2 131.7 105.7 79.8
57 164.3 18.3 164.3 164.3 161.0 136.3 111.5 86.8 156.2 20.2 156.2 156.2 153.2 127.2 101.3 75.3
72 191.3 18.4 164.9 137.9 110.9 83.8 - - 181.5 20.2 163.8 135.8 107.8 79.7 - -
67 175.4 18.3 175.4 169.6 145.7 118.7 91.7 - 165.6 20.2 165.6 165.4 142.0 114.0 86.0 -
6750
62 166.4 18.2 166.4 166.4 166.4 139.4 112.4 85.3 159.0 20.1 159.0 159.0 159.0 132.7 104.7 76.7
57 168.6 18.2 168.6 168.6 167.0 140.0 113.0 85.9 161.2 20.1 161.2 161.2 159.7 131.6 103.6 75.5
72 196.3 18.3 178.0 148.7 119.4 90.1 - - 187.1 20.0 176.8 146.7 116.6 86.4 - -
67 179.9 18.2 179.9 179.9 156.9 127.6 98.3 - 170.7 20.0 170.7 170.7 153.6 123.5 93.4 -
7500
62 170.7 18.2 170.7 170.7 170.7 141.4 112.1 82.8 163.9 20.0 163.9 163.9 163.9 133.8 103.7 73.5
57 173.0 18.2 173.0 173.0 173.0 143.7 114.4 85.1 166.1 20.0 166.1 166.1 166.1 136.0 105.9 75.7
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor
efficiency.
2. These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J20YC/J20NL
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 302.6 13.0 152.3 127.4 102.5 - - - 293.4 15.0 146.7 123.9 101.2 - - -
72 276.0 13.0 182.6 156.4 130.2 104.0 - - 267.4 14.9 179.2 153.3 127.5 101.6 - -
5000
67 249.4 13.1 213.0 185.5 157.9 130.8 106.3 - 241.4 14.9 211.7 182.7 153.7 127.7 103.0 -
62 236.2 12.9 236.2 213.6 185.6 154.8 134.7 109.2 231.1 14.8 231.1 207.2 180.0 152.5 130.3 105.4
77 305.5 13.0 166.8 134.3 101.8 - - - 296.0 15.1 163.9 132.1 100.4 - - -
72 282.9 13.1 198.3 167.4 136.4 105.5 - - 273.7 15.0 195.2 164.4 133.5 102.6 - -
6000 67 260.2 13.1 229.8 200.4 171.1 138.6 108.2 - 251.5 14.9 226.5 196.6 166.6 135.1 104.5 -
62 249.5 13.0 249.5 229.2 205.8 169.5 141.8 109.8 243.4 14.9 243.4 222.3 199.8 166.4 137.3 106.0
57 238.7 12.8 238.7 238.7 238.7 207.9 175.4 142.8 235.3 14.8 235.3 235.3 232.9 201.5 170.0 138.5
77 308.4 13.1 181.3 141.1 101.0 - - - 298.6 15.1 181.2 140.3 99.5 - - -
72 289.7 13.1 213.9 178.3 142.6 107.0 - - 280.1 15.0 211.2 175.4 139.5 103.7 - -
7000 67 271.0 13.1 246.6 215.4 184.3 146.4 110.1 - 261.7 14.9 241.3 210.4 179.6 142.4 106.0 -
62 262.8 13.0 262.8 244.9 225.9 184.2 148.9 110.3 255.7 14.9 255.2 237.4 219.6 180.3 144.2 106.5
57 254.6 12.9 254.6 254.6 254.6 227.6 187.6 147.6 249.6 14.9 249.6 249.6 249.6 221.0 182.4 143.8
77 311.3 13.2 195.8 148.0 100.2 - - - 301.1 15.2 198.4 148.5 98.7 - - -
72 296.5 13.1 229.6 189.2 148.8 108.5 - - 286.5 15.1 227.2 186.4 145.6 104.8 - -
8000 67 281.8 13.1 263.4 230.4 197.5 154.2 112.0 - 271.9 15.0 256.0 224.3 192.5 149.8 107.6 -
62 276.1 13.0 274.9 260.5 246.1 198.9 155.9 110.9 268.0 15.0 265.5 252.5 239.4 194.2 151.2 107.1
57 270.4 12.9 270.4 270.4 270.4 247.3 199.9 152.4 264.0 15.0 264.0 264.0 264.0 240.6 194.8 149.1
72 303.4 13.1 245.2 200.1 155.0 109.9 - - 292.9 15.1 243.2 197.4 151.6 105.8 - -
67 292.6 13.0 280.2 245.4 210.6 162.0 113.9 - 282.1 15.0 270.8 238.1 205.4 157.1 109.1 -
9000
62 289.4 13.0 285.9 276.1 266.2 213.6 163.0 111.4 280.2 15.0 275.9 267.5 259.2 208.1 158.2 107.6
57 286.3 13.0 283.7 283.7 283.7 267.0 212.1 157.2 278.4 15.0 277.0 277.0 277.0 260.1 207.2 154.4
72 310.2 13.2 260.9 211.1 161.2 111.4 - - 299.3 15.2 259.2 208.4 157.7 106.9 - -
67 303.4 13.0 297.0 260.4 223.8 169.8 115.8 - 292.3 15.1 285.6 251.9 218.3 164.5 110.6 -
10000
62 302.8 13.0 297.0 291.7 286.4 228.2 170.1 111.9 292.5 15.1 286.3 282.6 279.0 222.1 165.1 108.2
57 302.1 13.0 297.0 297.0 297.0 286.6 224.3 162.0 292.8 15.1 286.9 286.9 286.9 279.7 219.6 159.6
95°F 105°F
77 284.1 17.1 141.1 120.5 99.8 - - - 268.2 19.9 134.8 115.0 95.2 - - -
72 258.7 16.9 175.8 150.2 124.7 99.1 - - 244.3 19.5 170.9 145.3 119.7 94.0 - -
5000
67 233.3 16.6 210.4 180.0 149.5 124.6 99.7 - 220.4 19.2 207.0 175.6 144.1 119.1 94.2 -
62 226.1 16.7 226.1 200.8 174.3 150.1 125.9 101.6 216.5 19.2 216.5 193.6 168.5 144.2 119.9 95.6
77 286.4 17.1 161.1 130.0 98.9 - - - 270.5 19.9 155.9 124.7 93.5 - - -
72 264.6 16.9 192.1 161.3 130.6 99.8 - - 250.3 19.6 187.0 156.1 125.2 94.4 - -
6000 67 242.8 16.7 223.2 192.7 162.2 131.5 100.9 - 230.1 19.3 218.0 187.5 156.9 126.1 95.3 -
62 237.3 16.8 236.9 215.3 193.8 163.3 132.7 102.2 227.2 19.3 227.2 208.0 188.6 157.8 127.0 96.2
57 231.8 16.8 231.8 231.8 225.4 195.0 164.6 134.2 224.2 19.3 224.2 224.2 220.3 189.5 158.8 128.0
77 288.7 17.2 181.0 139.5 98.0 - - - 272.8 19.8 177.0 134.4 91.8 - - -
72 270.6 17.0 208.5 172.5 136.4 100.4 - - 256.3 19.6 203.0 166.9 130.8 94.7 - -
7000 67 252.4 16.8 235.9 205.4 174.8 138.4 102.0 - 239.9 19.4 229.0 199.4 169.8 133.0 96.3 -
62 248.6 16.8 246.5 229.9 213.3 176.4 139.6 102.8 237.8 19.4 236.3 222.5 208.7 171.4 134.1 96.8
57 244.7 16.9 244.7 244.7 244.7 214.4 177.2 140.0 235.7 19.4 235.7 235.7 235.7 209.8 171.9 134.0
77 291.0 17.2 201.0 149.1 97.1 - - - 275.0 19.8 198.1 144.1 90.1 - - -
72 276.5 17.0 224.8 183.6 142.3 101.1 - - 262.3 19.6 219.1 177.7 136.4 95.0 - -
8000 67 262.0 16.9 248.6 218.1 187.5 145.3 103.1 - 249.6 19.5 240.0 211.3 182.6 140.0 97.4 -
62 259.8 16.9 256.2 244.4 232.7 189.6 146.4 103.3 248.4 19.5 245.1 237.0 228.8 185.0 141.2 97.4
57 257.6 17.0 257.6 257.6 257.6 233.8 189.8 145.7 247.3 19.5 247.3 247.3 247.3 230.0 185.0 139.9
72 282.5 17.1 241.2 194.7 148.2 101.7 - - 268.3 19.7 235.1 188.5 141.9 95.3 - -
67 271.6 17.0 261.4 230.8 200.2 152.2 104.3 - 259.4 19.5 251.0 223.2 195.4 147.0 98.5 -
9000
62 271.0 17.0 265.8 259.0 252.2 202.7 153.3 103.9 259.1 19.5 253.9 251.4 248.9 198.6 148.3 98.0
57 270.5 17.1 270.3 270.3 270.3 253.3 202.4 151.5 258.8 19.6 256.9 256.9 256.9 250.2 198.1 145.9
72 288.4 17.2 257.5 205.8 154.1 102.4 - - 274.3 19.7 251.1 199.3 147.5 95.6 - -
67 281.1 17.1 274.1 243.5 212.9 159.1 105.4 - 269.1 19.6 262.0 235.1 208.2 153.9 99.6 -
10000
62 282.3 17.1 275.5 273.6 271.6 215.9 160.2 104.4 269.7 19.6 262.7 262.7 262.7 212.2 155.4 98.6
57 283.4 17.2 276.9 276.9 276.9 272.7 214.9 157.2 270.3 19.6 263.5 263.5 263.5 263.5 211.2 151.9
J20YC/J20NL (Continued)
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 252.3 22.7 128.5 109.5 90.6 - - - 236.3 25.5 122.1 104.1 86.0 - - -
72 229.9 22.2 166.1 140.4 114.6 88.9 - - 215.5 24.9 161.2 135.4 109.6 83.9 - -
5000
67 207.5 21.8 203.7 171.2 138.7 113.6 88.6 - 194.6 24.4 194.6 166.8 133.3 108.2 83.0 -
62 207.0 21.8 207.0 186.4 162.7 138.3 114.0 89.6 197.4 24.3 197.4 179.2 156.9 132.5 108.0 83.6
77 254.5 22.6 150.7 119.4 88.1 - - - 238.6 25.4 145.5 114.1 82.7 - - -
72 236.0 22.2 181.8 150.8 119.9 88.9 - - 221.6 24.9 176.6 145.6 114.6 83.5 - -
6000 67 217.4 21.9 212.9 182.3 151.7 120.7 89.6 - 204.7 24.4 204.7 177.1 146.4 115.2 84.0 -
62 217.0 21.8 217.0 200.8 183.4 152.4 121.3 90.2 206.8 24.4 206.8 193.5 178.3 146.9 115.6 84.2
57 216.6 21.8 216.6 216.6 215.2 184.1 153.0 121.8 209.0 24.3 209.0 209.0 209.0 178.6 147.1 115.6
77 256.8 22.5 173.0 129.3 85.6 - - - 240.8 25.2 168.9 124.2 79.4 - - -
72 242.0 22.2 197.5 161.3 125.1 88.9 - - 227.8 24.9 192.1 155.8 119.5 83.2 - -
7000 67 227.3 21.9 222.1 193.4 164.7 127.7 90.7 - 214.8 24.5 214.8 187.4 159.6 122.3 85.0 -
62 227.0 21.9 226.1 215.1 204.2 166.4 128.6 90.8 216.3 24.4 215.8 207.7 199.7 161.4 123.1 84.9
57 226.8 21.9 226.8 226.8 226.8 205.1 166.6 128.0 217.8 24.4 216.4 216.4 216.4 200.5 161.3 122.0
77 259.0 22.4 195.2 139.2 83.1 - - - 243.0 25.1 192.3 134.2 76.1 - - -
72 248.1 22.2 213.3 171.8 130.4 88.9 - - 233.9 24.8 207.5 166.0 124.4 82.9 - -
8000 67 237.2 22.0 231.3 204.5 177.7 134.7 91.7 - 224.8 24.6 222.7 197.7 172.7 129.4 86.0 -
62 237.1 22.0 234.0 229.5 224.9 180.4 136.0 91.5 225.7 24.5 223.0 222.0 221.0 175.9 130.7 85.5
57 236.9 22.0 236.7 236.7 236.7 226.2 180.2 134.2 226.5 24.4 223.2 223.2 223.2 222.4 175.4 128.4
72 254.2 22.2 229.0 182.3 135.6 88.9 - - 240.1 24.8 222.9 176.1 129.3 82.6 - -
67 247.1 22.1 240.6 215.6 190.7 141.7 92.8 - 234.9 24.6 230.2 208.0 185.9 136.5 87.0 -
9000
62 247.1 22.1 242.0 242.0 242.0 194.5 143.3 92.1 235.1 24.6 230.1 230.1 230.1 190.3 138.3 86.2
57 247.0 22.0 243.4 243.4 243.4 243.4 193.8 140.3 235.3 24.5 230.0 230.0 230.0 230.0 189.5 134.8
72 260.3 22.2 244.8 192.8 140.9 88.9 - - 246.2 24.7 238.4 186.3 134.3 82.2 - -
67 257.0 22.1 249.8 226.7 203.6 148.7 93.8 - 245.0 24.7 237.6 218.3 199.0 143.5 88.0 -
10000
62 257.1 22.1 250.0 250.0 250.0 208.5 150.6 92.7 244.5 24.6 237.2 237.2 237.2 204.8 145.8 86.8
57 257.2 22.1 250.1 250.1 250.1 250.1 207.4 146.5 244.1 24.6 236.8 236.8 236.8 236.8 203.6 141.2
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor
efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J20YD/J20NM
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 292.8 14.7 136.9 111.9 87.0 - - - 284.3 16.4 135.2 110.2 85.1 - - -
72 272.9 14.4 174.4 149.4 124.5 99.5 - - 263.5 16.1 171.7 146.7 121.7 96.6 - -
6000 67 253.0 14.0 211.9 186.9 162.0 137.0 112.0 - 242.6 15.8 208.2 183.2 158.2 133.2 108.1 -
62 231.8 13.8 231.8 220.2 195.2 170.2 145.2 120.2 225.5 15.5 225.5 219.3 194.3 169.2 144.2 119.2
57 224.6 13.7 224.6 224.6 207.1 182.1 157.1 132.1 219.3 15.5 219.3 219.3 201.5 176.5 151.5 126.5
77 302.2 14.8 149.9 121.7 93.5 - - - 292.0 16.5 147.3 119.2 91.1 - - -
72 281.7 14.5 190.2 162.0 133.8 105.6 - - 270.5 16.2 186.4 158.3 130.2 102.2 - -
7000 67 261.1 14.2 230.5 202.3 174.1 145.9 117.7 - 249.1 15.9 225.5 197.4 169.3 141.3 113.2 -
62 239.3 13.9 239.3 233.5 209.9 182.9 153.5 125.3 231.5 15.6 231.5 228.4 208.0 179.9 151.8 123.8
57 231.8 13.9 231.8 231.8 222.6 196.1 166.2 138.0 225.2 15.6 225.2 225.2 215.7 187.7 159.6 131.5
77 311.7 14.9 162.8 131.4 100.0 - - - 299.6 16.6 159.4 128.2 97.1 - - -
72 290.5 14.6 206.0 174.5 143.1 111.7 - - 277.6 16.3 201.0 169.9 138.8 107.7 - -
8000 67 269.3 14.3 249.1 217.7 186.2 154.8 123.4 - 255.6 16.0 242.7 211.6 180.5 149.4 118.3 -
62 246.8 14.0 246.8 246.8 224.5 195.6 161.7 130.3 237.6 15.7 237.6 237.6 221.7 190.5 159.4 128.3
57 239.1 14.0 239.1 239.1 238.1 210.2 175.3 143.9 231.1 15.7 231.1 231.1 229.9 198.8 167.7 136.6
72 299.4 14.9 217.9 184.4 150.9 117.3 - - 284.7 16.6 212.0 178.6 145.2 111.7 - -
67 277.5 14.6 267.1 229.8 196.3 162.8 129.3 - 262.2 16.3 255.6 222.1 188.7 155.3 121.9 -
9000
62 254.3 14.3 254.3 254.3 236.8 204.5 169.7 136.2 243.7 16.0 243.7 243.7 231.8 198.4 165.0 131.5
57 246.4 14.2 246.4 246.4 245.9 214.1 178.9 145.4 237.0 16.0 237.0 237.0 236.4 203.0 169.6 136.2
72 308.2 15.2 229.9 194.2 158.6 123.0 - - 291.8 16.9 222.9 187.2 151.5 115.8 - -
67 285.7 14.8 285.0 242.0 206.4 170.8 135.2 - 268.7 16.5 268.4 232.7 197.0 161.3 125.6 -
10000
62 261.9 14.6 261.9 261.9 249.0 213.4 177.7 142.1 249.7 16.3 249.7 249.7 241.9 206.2 170.5 134.8
57 253.7 14.5 253.7 253.7 253.7 218.1 182.5 146.9 242.9 16.3 242.9 242.9 242.9 207.2 171.5 135.8
95°F 105°F
77 275.8 18.1 133.4 108.4 83.3 - - - 262.8 20.3 129.8 104.7 79.5 - - -
72 254.0 17.8 169.0 143.9 118.8 93.8 - - 242.0 20.1 164.8 139.7 114.6 89.5 - -
6000 67 232.2 17.5 204.5 179.5 154.4 129.3 104.3 - 221.1 19.8 199.8 174.7 149.6 124.5 99.4 -
62 219.1 17.2 219.1 218.4 193.3 168.3 143.2 118.2 208.7 19.6 208.7 208.3 185.8 160.7 135.6 110.5
57 214.1 17.3 214.1 214.1 196.0 170.9 145.9 120.8 205.0 19.6 205.0 205.0 186.2 161.1 136.0 110.9
77 281.7 18.2 144.7 116.7 88.8 - - - 268.8 20.4 144.0 113.4 85.3 - - -
72 259.4 17.9 182.5 154.6 126.7 98.7 - - 247.4 20.1 179.0 150.9 122.8 94.7 - -
7000 67 237.1 17.6 220.4 192.5 164.6 136.6 108.7 - 226.1 19.9 214.1 188.4 160.3 132.2 104.1 -
62 223.7 17.3 223.7 223.4 206.1 176.9 150.2 122.3 213.4 19.7 213.4 213.2 199.1 170.4 142.9 114.8
57 218.6 17.4 218.6 218.6 208.9 179.2 153.0 125.1 209.7 19.7 209.7 209.7 199.6 170.6 143.4 115.2
77 287.5 18.3 155.9 125.1 94.3 - - - 274.7 20.5 158.2 122.1 91.0 - - -
72 264.8 18.0 196.1 165.3 134.5 103.7 - - 252.9 20.2 193.2 162.1 131.0 99.9 - -
8000 67 242.0 17.7 236.3 205.5 174.7 143.9 113.1 - 231.1 19.9 228.3 202.2 171.1 140.0 108.8 -
62 228.4 17.4 228.4 228.4 218.8 185.5 157.2 126.4 218.1 19.7 218.1 218.1 212.5 180.1 150.3 119.1
57 223.1 17.4 223.1 223.1 221.8 187.5 160.1 129.3 214.3 19.8 214.3 214.3 212.9 180.1 150.7 119.6
72 270.1 18.3 206.1 172.7 139.4 106.1 - - 258.4 20.5 202.9 169.4 136.0 102.5 - -
67 246.9 18.0 244.1 214.5 181.1 147.8 114.5 - 236.1 20.2 234.7 211.0 177.5 144.1 110.6 -
9000
62 233.0 17.7 233.0 233.0 226.8 192.3 160.2 126.9 222.8 20.0 222.8 222.8 219.3 185.2 152.4 118.9
57 227.6 17.7 227.6 227.6 226.9 191.9 160.3 127.0 218.9 20.0 218.9 218.9 218.2 183.9 151.3 117.8
72 275.4 18.6 216.0 180.2 144.4 108.6 - - 263.8 20.8 212.6 176.7 140.9 105.1 - -
67 251.8 18.2 251.8 223.4 187.6 151.8 116.0 - 241.1 20.5 241.1 219.8 184.0 148.2 112.3 -
10000
62 237.6 18.0 237.6 237.6 234.9 199.1 163.3 127.5 227.5 20.3 227.5 227.5 226.1 190.3 154.5 118.6
57 232.1 18.0 232.1 232.1 232.1 196.3 160.5 124.7 223.6 20.3 223.6 223.6 223.6 187.7 151.9 116.1
J20YD/J20NM (Continued)
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 249.8 22.6 126.1 101.0 75.8 - - - 236.8 24.9 122.5 97.3 72.0 - - -
72 229.9 22.3 160.6 135.4 110.3 85.1 - - 217.9 24.6 156.4 131.2 106.0 80.8 - -
6000 67 210.1 22.0 195.1 169.9 144.8 119.6 94.4 - 199.0 24.3 190.3 165.1 139.9 114.7 89.5 -
62 198.2 21.9 198.2 198.2 178.3 153.1 128.0 102.8 187.8 24.3 187.8 187.8 170.7 145.5 120.3 95.1
57 196.0 21.9 196.0 196.0 176.5 151.3 126.1 101.0 187.0 24.2 187.0 187.0 166.7 141.5 116.3 91.1
77 255.8 22.7 143.3 110.0 81.7 - - - 242.9 24.9 142.6 106.7 78.2 - - -
72 235.5 22.4 175.5 147.2 118.9 90.6 - - 223.6 24.7 172.0 143.5 115.0 86.6 - -
7000 67 215.2 22.1 207.7 184.4 156.1 127.8 99.5 - 204.2 24.4 201.3 180.3 151.8 123.4 94.9 -
62 203.0 22.0 203.0 203.0 192.2 163.9 135.7 107.4 192.7 24.3 192.7 192.7 185.3 157.5 128.4 99.9
57 200.8 22.0 200.8 200.8 190.3 162.0 133.7 105.4 191.9 24.3 191.9 191.9 181.0 153.4 124.1 95.6
77 261.9 22.8 160.5 119.1 87.7 - - - 249.1 25.0 162.8 116.1 84.4 - - -
72 241.1 22.5 190.4 159.0 127.5 96.1 - - 229.3 24.8 187.5 155.8 124.1 92.3 - -
8000 67 220.3 22.2 220.3 198.8 167.4 136.0 104.6 - 209.4 24.5 209.4 195.5 163.8 132.0 100.3 -
62 207.8 22.1 207.8 207.8 206.2 174.8 143.3 111.9 197.6 24.4 197.6 197.6 197.6 169.4 136.4 104.7
57 205.5 22.1 205.5 205.5 204.1 172.7 141.3 109.8 196.7 24.4 196.7 196.7 195.3 165.3 131.8 100.1
72 246.6 22.7 199.8 166.1 132.5 98.8 - - 234.9 25.0 196.6 162.8 129.0 95.2 - -
67 225.3 22.4 225.3 207.6 173.9 140.3 106.6 - 214.6 24.7 214.6 204.1 170.3 136.5 102.7 -
9000
62 212.6 22.3 212.6 212.6 211.8 178.2 144.5 110.9 202.4 24.6 202.4 202.4 202.4 171.1 136.7 102.9
57 210.3 22.3 210.3 210.3 209.5 175.9 142.3 108.6 201.6 24.6 201.6 201.6 200.8 167.9 133.2 99.4
72 252.2 23.0 209.2 173.3 137.4 101.6 - - 240.5 25.2 205.7 169.9 134.0 98.1 - -
67 230.4 22.7 230.4 216.3 180.4 144.6 108.7 - 219.7 24.9 219.7 212.7 176.8 141.0 105.1 -
10000
62 217.4 22.5 217.4 217.4 217.4 181.5 145.7 109.8 207.3 24.8 207.3 207.3 207.3 172.8 136.9 101.0
57 215.0 22.5 215.0 215.0 215.0 179.1 143.3 107.4 206.4 24.8 206.4 206.4 206.4 170.5 134.7 98.8
1 These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor
efficiency.
2 These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J25YC/J25NC
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 360.4 19.3 168.6 143.4 118.2 - - - 347.0 20.6 162.5 138.3 114.1 - - -
72 331.5 19.1 212.8 181.7 150.7 119.6 - - 316.2 20.3 208.8 177.7 146.5 115.4 - -
6250
67 302.5 18.9 256.9 220.0 183.2 155.1 124.8 - 285.4 20.0 255.0 217.0 179.0 148.6 117.0 -
62 291.7 18.8 286.5 251.1 215.6 185.0 161.0 133.7 279.2 20.0 275.5 243.4 211.4 178.9 149.7 118.8
77 365.6 19.4 191.4 154.1 116.8 - - - 350.9 20.6 187.5 150.1 112.8 - - -
72 339.8 19.2 233.1 195.3 157.5 119.7 - - 324.5 20.4 229.1 191.4 153.7 116.0 - -
7500 67 314.0 19.0 274.7 236.5 198.2 162.8 125.5 - 298.0 20.1 270.7 232.6 194.6 157.6 119.6 -
62 304.9 18.9 294.0 268.6 239.0 201.3 169.0 134.1 292.6 20.1 286.7 261.1 235.5 196.9 161.0 123.7
57 295.8 18.9 295.8 295.8 279.7 246.1 212.6 179.0 287.1 20.1 287.1 287.1 276.4 239.3 202.3 165.3
77 370.7 19.4 214.2 164.8 115.4 - - - 354.8 20.6 212.5 162.0 111.4 - - -
72 348.1 19.2 253.4 208.9 164.3 119.8 - - 332.7 20.4 249.4 205.1 160.8 116.5 - -
8750 67 325.5 19.0 292.6 253.0 213.3 170.4 126.1 - 310.7 20.3 286.3 248.2 210.1 166.5 122.2 -
62 318.1 19.0 309.8 286.0 262.3 217.6 177.0 134.4 306.0 20.2 297.9 278.7 259.5 214.9 172.3 128.7
57 310.7 19.0 310.7 310.7 302.6 269.6 228.0 186.3 301.3 20.2 301.3 301.3 301.3 265.6 222.3 179.0
77 375.8 19.5 237.0 175.5 113.9 - - - 358.6 20.7 237.4 173.8 110.1 - - -
72 356.4 19.3 273.7 222.4 171.1 119.9 - - 341.0 20.5 269.7 218.8 167.9 117.0 - -
10000 67 337.0 19.1 310.5 269.4 228.4 178.1 126.8 - 323.4 20.4 302.0 263.8 225.7 175.5 124.9 -
62 331.3 19.1 321.5 303.5 285.6 234.0 185.1 134.8 319.4 20.4 309.2 296.4 283.5 232.9 183.6 133.6
57 325.5 19.1 325.5 325.5 325.5 293.1 243.3 193.6 315.5 20.4 312.9 312.9 312.9 291.8 242.3 192.8
72 364.7 19.4 294.1 236.0 178.0 119.9 - - 349.3 20.6 290.0 232.5 175.1 117.6 - -
67 348.5 19.2 328.4 285.9 243.4 185.7 127.5 - 336.1 20.5 317.6 279.5 241.3 184.5 127.5 -
11250
62 344.4 19.2 333.1 321.0 308.9 250.3 193.1 135.2 332.9 20.5 320.4 314.0 307.6 250.9 194.9 138.5
57 340.4 19.2 334.4 334.4 334.4 316.5 258.7 200.9 329.7 20.5 321.5 321.5 321.5 318.0 262.2 206.5
72 373.0 19.4 314.4 249.6 184.8 120.0 - - 357.6 20.6 310.3 246.3 182.2 118.1 - -
67 359.9 19.3 346.3 302.4 258.5 193.3 128.2 - 348.7 20.6 333.3 295.1 256.9 193.5 130.1 -
12500
62 357.6 19.3 348.6 338.5 332.2 266.7 201.1 135.6 346.3 20.6 333.9 331.6 331.6 268.9 206.2 143.5
57 355.3 19.3 348.9 348.9 348.9 340.0 274.1 208.3 343.9 20.6 334.6 334.6 334.6 334.6 282.2 220.2
95°F 105°F
77 333.6 21.9 156.4 133.2 110.0 - - - 304.1 23.5 156.5 130.8 105.0 - - -
72 300.9 21.5 204.8 173.6 142.4 111.2 - - 277.2 23.2 198.6 167.0 135.5 103.9 - -
6250
67 268.2 21.2 253.1 214.0 174.8 142.0 109.2 - 250.3 23.0 240.8 203.3 165.9 134.1 102.3 -
62 266.6 21.2 264.4 235.8 207.2 172.8 138.4 104.0 252.0 23.0 248.9 222.6 196.3 164.4 132.4 100.4
77 336.3 21.9 183.6 146.2 108.8 - - - 307.7 23.5 181.9 141.8 101.6 - - -
72 309.2 21.6 225.1 187.5 149.8 112.2 - - 285.4 23.3 217.4 179.7 142.0 104.3 - -
7500 67 282.1 21.3 266.6 228.7 190.9 152.3 113.8 - 267.9 23.1 252.9 217.7 182.4 144.2 106.1 -
62 280.3 21.3 275.2 253.6 232.0 192.5 152.9 113.4 266.1 23.1 259.1 241.0 222.8 184.1 145.5 106.8
57 278.5 21.3 278.5 278.5 273.0 232.6 192.1 151.7 264.9 23.1 264.9 264.3 263.2 224.0 184.9 145.7
77 338.9 21.9 210.7 159.1 107.5 - - - 311.3 23.5 207.3 152.8 98.3 - - -
72 317.4 21.7 245.4 201.3 157.3 113.2 - - 293.7 23.4 236.1 192.4 148.6 104.8 - -
8750 67 295.9 21.5 280.0 243.5 207.0 162.7 118.3 - 281.6 23.3 265.0 232.0 198.9 154.4 109.8 -
62 293.9 21.5 286.1 271.4 256.7 212.1 167.5 122.9 278.5 23.3 269.3 259.3 249.3 203.9 158.5 113.2
57 292.0 21.5 292.0 292.0 292.0 261.6 216.7 171.8 276.1 23.3 273.6 273.6 273.6 253.4 207.3 161.1
77 341.5 21.9 237.9 172.1 106.3 - - - 314.9 23.6 232.7 163.8 94.9 - - -
72 325.7 21.7 265.7 215.2 164.7 114.2 - - 301.9 23.4 254.9 205.0 155.2 105.3 - -
10000 67 309.8 21.6 293.4 258.3 223.1 173.0 122.9 - 288.9 23.4 277.1 246.3 215.4 164.5 113.5 -
62 307.6 21.6 296.9 289.2 281.5 231.8 182.1 132.3 288.1 23.4 279.5 277.6 275.7 223.7 171.6 119.5
57 305.4 21.6 300.3 300.3 300.3 290.5 241.2 191.9 287.4 23.4 281.9 281.9 281.9 281.9 229.7 176.5
72 333.9 21.8 286.0 229.0 172.1 115.2 - - 310.1 23.5 273.6 217.7 161.8 105.8 - -
67 323.7 21.7 306.9 273.0 239.2 183.3 127.5 - 301.8 23.5 289.3 260.6 232.0 174.6 117.3 -
11250
62 321.3 21.7 307.7 307.0 306.2 251.4 196.6 141.8 300.2 23.5 289.7 289.7 289.7 243.4 184.7 125.9
57 318.9 21.7 308.6 308.6 308.6 308.6 265.8 212.0 298.6 23.5 290.2 290.2 290.2 290.2 252.0 191.9
72 342.2 21.9 306.2 242.9 179.6 116.2 - - 318.3 23.6 292.4 230.4 168.4 106.3 - -
67 337.5 21.8 320.3 287.8 255.3 193.7 132.0 - 314.6 23.6 300.5 274.9 248.5 184.7 121.0 -
12500
62 335.0 21.8 321.1 321.1 321.1 271.1 211.2 151.3 312.2 23.6 301.5 301.5 301.5 263.2 197.7 132.3
57 332.4 21.8 321.6 321.6 321.6 321.6 290.3 232.1 309.8 23.6 302.2 302.2 302.2 302.2 274.4 207.3
J25YC/J25NC (Continued)
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 274.7 25.1 156.6 128.3 100.0 - - - 245.2 26.8 156.7 125.9 95.0 - - -
72 253.5 24.9 192.5 160.5 128.5 96.5 - - 229.8 26.6 186.4 154.0 121.6 89.2 - -
6250
67 239.5 24.8 228.4 192.7 157.0 126.2 95.5 - 225.6 26.6 216.1 182.1 148.1 118.4 88.6 -
62 237.3 24.8 233.4 209.4 185.5 156.0 126.4 96.9 222.7 26.6 217.9 196.3 174.6 147.6 120.5 93.4
77 279.2 25.2 180.2 137.4 94.5 - - - 250.6 26.9 178.5 133.0 87.4 - - -
72 261.7 25.0 209.7 172.0 134.2 96.5 - - 238.0 26.8 202.0 164.2 126.4 88.6 - -
7500 67 253.6 25.0 239.2 206.6 173.9 136.2 98.4 - 237.7 26.7 225.5 195.5 165.4 128.1 90.7 -
62 252.5 25.0 243.0 228.3 213.6 175.8 138.0 100.2 237.5 26.7 226.9 215.7 204.5 167.5 130.5 93.6
57 251.3 25.0 246.8 246.8 246.8 215.5 177.6 139.8 236.9 26.7 228.2 228.2 228.2 206.9 170.4 133.9
77 283.7 25.2 203.8 146.4 89.0 - - - 256.1 26.9 200.4 140.1 79.8 - - -
72 269.9 25.1 226.9 183.4 140.0 96.5 - - 246.1 26.7 217.7 174.5 131.3 88.1 - -
8750 67 262.5 25.0 250.0 220.4 190.9 146.1 101.3 - 244.4 26.7 235.0 208.9 182.8 137.8 92.8 -
62 260.8 25.0 252.6 247.2 241.8 195.7 149.6 103.5 243.1 26.6 235.8 235.1 234.3 187.5 140.6 93.8
57 260.3 25.0 255.1 255.1 255.1 245.3 197.9 150.4 242.8 26.6 236.7 236.7 236.7 236.7 188.5 139.8
77 288.2 25.2 227.4 155.5 83.6 - - - 261.5 26.9 222.2 147.2 72.2 - - -
72 278.1 25.1 244.1 194.9 145.7 96.5 - - 254.3 26.8 233.4 184.8 136.2 87.6 - -
10000 67 270.5 25.1 260.8 234.3 207.8 156.0 104.2 - 251.2 26.7 244.5 222.3 200.2 147.5 94.8 -
62 269.3 25.1 262.2 262.2 262.2 215.5 161.1 106.7 249.1 26.7 244.8 244.8 244.8 207.4 150.7 93.9
57 268.5 25.1 263.5 263.5 263.5 263.5 218.1 161.1 247.9 26..7 245.1 245.1 245.1 245.1 206.5 145.7
72 286.3 25.2 261.3 206.4 151.4 96.4 - - 262.5 27.0 249.0 195.0 141.0 87.0 - -
67 279.9 25.2 271.6 248.2 224.7 165.9 107.1 - 259.9 27.0 254.0 235.8 217.5 157.2 96.9 -
11250
62 279.1 25.2 271.8 271.8 271.8 235.4 172.7 110.0 258.6 27.0 254.3 254.3 254.3 227.4 160.7 94.1
57 278.2 25.2 271.9 271.9 271.9 271.9 238.3 171.8 257.9 26.9 255.0 255.0 255.0 255.0 224.6 151.6
72 294.5 25.3 278.5 217.8 157.1 96.4 - - 270.6 27.0 263.0 205.3 145.9 86.5 - -
67 291.8 25.3 282.4 262.1 241.7 175.8 110.0 - 268.9 27.0 263.5 249.2 234.9 166.9 99.0 -
12500
62 289.5 25.3 283.3 283.3 283.3 255.2 184.3 113.3 266.8 26.9 263.9 263.9 263.9 247.3 170.8 94.3
57 287.2 25.2 284.5 284.5 284.5 284.5 258.5 182.4 264.6 26.9 264.0 264.0 264.0 264.0 242.6 157.6
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor
efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J10PC/J10NL
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 144.6 7.3 79.0 64.2 49.3 - - - 138.9 8.3 77.2 58.3 39.3 - - -
72 133.6 7.2 95.0 80.2 65.5 50.7 - - 127.7 8.1 92.9 76.1 59.3 42.5 - -
3000 67 122.5 7.1 111.0 96.3 81.7 66.7 51.9 - 116.6 8.0 108.7 94.0 79.3 64.3 49.4 -
62 118.6 7.0 118.6 109.0 97.8 80.9 67.8 52.8 113.8 8.0 113.8 107.4 99.2 85.3 73.2 60.2
57 114.8 7.0 114.8 114.8 114.0 98.9 83.7 68.6 111.1 7.9 111.1 111.1 111.1 108.1 97.0 86.0
77 147.2 7.3 87.7 68.5 49.3 - - - 140.0 8.3 86.4 63.9 41.4 - - -
72 136.5 7.2 103.2 86.0 68.7 51.4 - - 130.2 8.2 101.1 82.3 63.5 44.8 - -
3500 67 125.8 7.1 118.7 103.4 88.0 70.4 53.0 - 120.4 8.0 115.8 100.7 85.7 68.1 50.6 -
62 123.8 7.1 123.8 116.5 107.4 88.2 71.9 54.2 118.9 8.0 118.9 114.4 107.9 90.9 75.3 59.0
57 121.8 7.0 121.8 121.8 121.4 108.8 90.8 72.9 117.5 8.0 117.5 117.5 117.5 115.0 99.9 84.9
77 149.8 7.4 96.5 72.9 49.4 - - - 141.1 8.3 95.6 69.5 43.4 - - -
72 139.5 7.3 111.5 91.7 71.9 52.1 - - 132.7 8.2 109.3 88.5 67.8 47.0 - -
4000 67 129.2 7.2 126.4 110.4 94.4 74.2 54.2 - 124.2 8.1 122.9 107.5 92.1 72.0 51.8 -
62 129.0 7.1 129.0 124.0 116.9 95.5 76.0 55.6 124.1 8.1 124.1 121.4 116.5 96.4 77.3 57.8
57 128.9 7.1 128.9 128.9 128.9 118.6 97.9 77.2 123.9 8.1 123.9 123.9 123.9 121.9 102.9 83.9
72 142.4 7.3 119.7 97.4 75.0 52.7 - - 135.1 8.2 117.4 94.7 72.0 49.3 - -
67 132.5 7.2 132.5 117.4 100.7 78.0 55.3 - 128.0 8.1 128.0 114.3 98.6 75.8 53.0 -
4500
62 134.2 7.2 134.2 131.5 126.4 102.8 80.2 57.0 129.2 8.1 129.2 128.3 125.1 102.0 79.4 56.5
57 135.9 7.2 135.6 135.6 135.6 128.5 105.0 81.5 130.4 8.1 130.4 130.4 130.4 128.7 105.8 82.8
72 145.4 7.3 127.9 103.1 78.2 53.4 - - 137.6 8.2 125.6 100.9 76.3 51.6 - -
67 135.8 7.2 135.8 124.5 107.1 81.7 56.4 - 131.8 8.2 131.8 121.1 105.0 79.6 54.2 -
5000
62 139.4 7.3 139.4 139.0 135.9 110.1 84.3 58.5 134.3 8.2 134.3 134.3 133.8 107.6 81.5 55.3
57 143.0 7.3 142.4 142.4 142.4 138.4 112.1 85.8 136.8 8.2 136.7 136.7 136.7 135.6 108.7 81.8
95°F 105°F
77 133.2 9.2 75.4 52.4 29.3 - - - 123.8 10.5 73.7 53.1 32.6 - - -
72 121.9 9.1 90.9 72.0 53.1 34.2 - - 113.9 10.4 88.3 70.8 53.4 35.9 - -
3000 67 110.7 8.9 106.4 91.6 76.8 61.9 47.0 - 104.0 10.3 103.0 88.5 74.1 59.2 44.3 -
62 109.0 8.9 109.0 105.8 100.6 89.6 78.6 67.7 104.2 10.2 104.2 100.3 94.9 82.6 70.3 58.0
57 107.4 8.9 107.4 107.4 107.4 107.4 107.4 103.3 104.3 10.1 104.3 104.3 104.3 104.3 96.2 86.5
77 132.8 9.2 85.1 59.3 33.4 - - - 123.7 10.5 83.5 59.2 34.9 - - -
72 123.9 9.1 99.0 78.7 58.4 38.1 - - 116.0 10.4 96.0 76.8 57.7 38.5 - -
3500 67 114.9 9.0 112.9 98.1 83.4 65.8 48.2 - 108.2 10.3 108.2 94.5 80.5 62.9 45.4 -
62 114.1 9.0 114.1 112.2 108.4 93.5 78.6 63.8 108.6 10.2 108.6 106.9 103.3 87.4 71.5 55.6
57 113.2 8.9 113.2 113.2 113.2 113.2 109.1 96.9 109.0 10.2 109.0 109.0 109.0 109.0 97.6 83.4
77 132.5 9.2 94.8 66.1 37.5 - - - 123.6 10.5 93.3 65.2 37.1 - - -
72 125.9 9.1 107.1 85.4 63.7 42.0 - - 118.0 10.4 103.7 82.8 62.0 41.1 - -
4000 67 119.2 9.0 119.2 104.6 89.9 69.7 49.5 - 112.4 10.3 112.4 100.4 86.8 66.7 46.5 -
62 119.1 9.0 119.1 118.7 116.1 97.4 78.6 59.9 113.1 10.3 113.1 113.1 111.7 92.2 72.8 53.3
57 119.0 9.0 119.0 119.0 119.0 119.0 107.8 90.5 113.8 10.3 113.8 113.8 113.8 113.8 99.0 80.2
72 127.8 9.1 115.2 92.1 69.0 45.9 - - 120.0 10.4 111.3 88.8 66.3 43.8 - -
67 123.4 9.0 123.4 111.1 96.5 73.6 50.7 - 116.5 10.4 116.5 106.4 93.2 70.4 47.6 -
4500
62 124.1 9.1 124.1 124.1 123.9 101.3 78.6 56.0 117.5 10.4 117.5 117.5 117.5 97.1 74.0 51.0
57 124.8 9.1 124.8 124.8 124.8 124.8 106.5 84.1 118.6 10.4 118.6 118.6 118.6 118.6 100.4 77.1
72 129.8 9.1 123.3 98.8 74.3 49.8 - - 122.1 10.4 119.0 94.8 70.6 46.4 - -
67 127.7 9.1 127.7 117.6 103.0 77.5 52.0 - 120.7 10.4 120.7 112.3 99.6 74.1 48.7 -
5000
62 129.2 9.1 129.2 129.2 129.2 105.2 78.6 52.1 122.0 10.4 122.0 122.0 122.0 101.9 75.2 48.6
57 130.7 9.1 130.7 130.7 130.7 130.7 105.3 77.7 123.3 10.4 123.3 123.3 123.3 123.3 101.8 73.9
J10PC/J10NL (Continued)
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 114.5 11.8 72.0 53.9 35.9 - - - 105.2 13.1 70.2 54.7 39.1 - - -
72 106.0 11.7 85.7 69.7 53.6 37.6 - - 98.0 13.0 83.2 68.5 53.9 39.2 - -
3000 67 97.4 11.6 97.4 85.5 71.4 56.5 41.7 - 90.8 12.9 90.8 82.4 68.7 53.9 39.1 -
62 99.3 11.5 99.3 94.9 89.1 75.5 61.9 48.3 94.4 12.8 94.4 89.5 83.4 68.5 53.5 38.6
57 101.1 11.4 101.1 101.1 101.1 94.5 82.1 69.7 98.0 12.7 95.2 95.2 95.2 83.1 68.0 52.9
77 114.6 11.8 81.9 59.1 36.3 - - - 105.5 13.1 80.3 59.0 37.7 - - -
72 108.1 11.7 93.0 75.0 56.9 38.9 - - 100.2 13.0 90.0 73.1 56.2 39.3 - -
3500 67 101.5 11.6 101.5 90.8 77.6 60.1 42.6 - 94.8 12.9 94.8 87.2 74.7 57.2 39.8 -
62 103.2 11.5 103.2 101.5 98.2 81.3 64.4 47.5 97.7 12.8 97.7 96.2 93.1 75.2 57.3 39.3
57 104.9 11.5 104.9 104.9 104.9 102.5 86.1 69.8 100.7 12.8 98.9 98.9 98.9 93.1 74.7 56.3
77 114.8 11.8 91.8 64.3 36.7 - - - 105.9 13.1 90.4 63.4 36.4 - - -
72 110.2 11.7 100.2 80.2 60.2 40.2 - - 102.3 13.0 96.8 77.7 58.5 39.4 - -
4000 67 105.6 11.6 105.6 96.2 83.7 63.7 43.6 - 98.7 12.9 98.7 92.0 80.7 60.6 40.6 -
62 107.1 11.6 107.1 107.1 107.1 87.1 66.9 46.7 101.0 12.9 101.0 101.0 101.0 81.9 61.0 40.1
57 108.6 11.6 108.6 108.6 108.6 108.6 90.2 69.9 103.4 12.9 102.7 102.7 102.7 102.7 81.4 59.6
72 112.3 11.7 107.5 85.5 63.6 41.6 - - 104.5 13.0 103.7 82.2 60.8 39.4 - -
67 109.6 11.7 109.6 101.6 89.9 67.2 44.5 - 102.7 13.0 102.7 96.8 86.7 64.0 41.4 -
4500
62 111.0 11.7 111.0 111.0 111.0 92.8 69.4 45.9 104.4 13.0 104.4 104.4 104.4 88.6 64.7 40.8
57 112.3 11.6 112.3 112.3 112.3 112.3 94.2 70.0 106.0 12.9 106.0 106.0 106.0 106.0 88.1 63.0
72 114.3 11.7 114.3 90.8 66.9 42.9 - - 106.6 13.0 106.6 86.8 63.2 39.5 - -
67 113.7 11.7 113.7 106.9 96.1 70.8 45.4 - 106.7 13.0 106.7 101.6 92.7 67.4 42.1 -
5000
62 114.8 11.7 114.8 114.8 114.8 98.6 71.9 45.1 107.7 13.0 107.7 107.7 107.7 95.3 68.5 41.6
57 116.0 11.7 116.0 116.0 116.0 116.0 98.3 70.1 108.7 13.0 108.7 108.7 108.7 108.7 94.8 66.3
1 These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor
efficiency.
2 These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J15PC/J15NL
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 223.0 12.5 104.1 85.2 66.4 - - - 216.7 13.8 104.7 85.9 67.0 - - -
72 209.3 12.3 134.7 115.8 97.0 78.1 - - 200.9 13.6 133.0 114.1 95.2 76.3 - -
4500 67 195.7 12.1 165.2 146.4 127.6 108.7 89.9 - 185.0 13.4 161.2 142.3 123.4 104.5 85.7 -
62 176.7 11.8 176.7 176.7 152.0 133.2 114.3 95.5 169.4 13.0 169.4 169.4 151.2 132.4 113.5 94.6
57 179.6 11.8 179.6 179.6 159.1 140.3 121.4 102.6 173.1 13.1 173.1 173.1 154.4 135.5 116.7 97.8
77 229.0 12.6 113.8 93.3 71.8 - - - 221.4 13.9 114.8 93.3 71.7 - - -
72 215.0 12.4 147.9 126.3 104.8 83.3 - - 205.2 13.6 145.0 123.5 101.9 80.3 - -
5250 67 200.9 12.2 181.9 159.4 137.8 116.3 94.8 - 189.1 13.4 175.2 153.7 132.1 110.5 88.9 -
62 181.4 11.8 181.4 181.4 164.3 143.6 121.3 99.8 173.0 13.1 173.0 173.0 161.9 140.3 118.7 97.1
57 184.5 11.9 184.5 184.5 171.9 151.4 128.9 107.4 176.9 13.1 176.9 176.9 165.3 143.7 122.1 100.6
77 235.0 12.6 123.5 101.4 77.2 - - - 226.1 13.9 124.9 100.6 76.4 - - -
72 220.6 12.4 161.0 136.9 112.7 88.5 - - 209.6 13.7 157.1 132.8 108.6 84.3 - -
6000 67 206.2 12.2 198.5 172.3 148.1 123.9 99.8 - 193.1 13.4 189.3 165.0 140.8 116.5 92.2 -
62 186.2 11.9 186.2 186.2 176.7 154.1 128.3 104.1 176.7 13.1 176.7 176.7 172.5 148.2 124.0 99.7
57 189.3 11.9 189.3 189.3 184.8 162.6 136.4 112.2 180.6 13.2 180.6 180.6 176.1 151.8 127.6 103.3
72 223.2 12.5 170.5 144.3 118.1 91.9 - - 213.0 13.7 168.5 142.1 115.7 89.3 - -
67 208.6 12.3 204.8 181.5 155.3 129.1 102.9 - 196.2 13.5 194.3 176.4 150.0 123.6 97.3 -
6750
62 188.4 11.9 188.4 188.4 183.6 158.3 131.3 105.1 179.6 13.2 179.6 179.6 177.5 151.1 124.7 98.3
57 191.6 12.0 191.6 191.6 189.3 164.1 136.9 110.7 183.6 13.2 183.6 183.6 181.3 154.9 128.5 102.2
72 225.9 12.6 179.9 151.7 123.5 95.3 - - 216.4 13.8 179.9 151.4 122.9 94.4 - -
67 211.1 12.4 211.1 190.7 162.5 134.3 106.1 - 199.4 13.5 199.4 187.8 159.3 130.8 102.3 -
7500
62 190.6 12.0 190.6 190.6 190.6 162.4 134.2 106.0 182.5 13.2 182.5 182.5 182.5 154.0 125.5 97.0
57 193.8 12.1 193.8 193.8 193.8 165.6 137.4 109.2 186.5 13.3 186.5 186.5 186.5 158.0 129.5 101.0
95°F 105°F
77 210.5 15.1 105.4 86.5 67.6 - - - 192.8 16.7 98.9 80.0 61.1 - - -
72 192.4 14.9 131.3 112.4 93.4 74.5 - - 177.2 16.5 125.6 106.7 87.8 68.9 - -
4500 67 174.4 14.6 157.1 138.2 119.3 100.4 81.4 - 161.6 16.3 152.4 133.5 114.6 95.7 76.8 -
62 162.0 14.3 162.0 162.0 150.5 131.6 112.6 93.7 150.1 16.0 150.1 150.1 142.4 123.5 104.6 85.7
57 166.6 14.4 166.6 166.6 149.8 130.8 111.9 93.0 155.1 16.1 155.1 155.1 137.9 119.0 100.1 81.2
77 213.8 15.2 115.9 93.2 71.6 - - - 196.5 16.7 114.1 86.9 65.3 - - -
72 195.5 14.9 142.2 120.6 99.0 77.3 - - 180.6 16.5 137.1 115.5 93.8 72.2 - -
5250 67 177.2 14.6 168.6 148.0 126.3 104.7 83.1 - 164.7 16.3 160.1 144.1 122.4 100.8 79.2 -
62 164.7 14.4 164.7 164.7 159.4 136.9 116.1 94.5 153.0 16.1 153.0 153.0 152.2 130.1 108.9 87.3
57 169.2 14.4 169.2 169.2 158.6 136.0 115.3 93.7 158.1 16.1 158.1 158.1 147.3 125.2 104.1 82.4
77 217.2 15.2 126.3 99.9 75.6 - - - 200.2 16.8 129.3 93.8 69.4 - - -
72 198.6 14.9 153.1 128.8 104.5 80.1 - - 184.1 16.5 148.6 124.2 99.9 75.5 - -
6000 67 180.0 14.6 180.0 157.7 133.4 109.0 84.7 - 167.9 16.3 167.9 154.7 130.3 106.0 81.6 -
62 167.3 14.4 167.3 167.3 168.3 142.3 119.6 95.3 155.9 16.1 155.9 155.9 162.0 136.8 113.2 88.9
57 171.9 14.4 171.9 171.9 167.5 141.1 118.8 94.5 161.1 16.1 161.1 161.1 156.7 131.4 108.0 83.7
72 202.8 15.0 166.5 139.9 113.4 86.8 - - 187.4 16.6 160.8 134.3 107.7 81.1 - -
67 183.8 14.7 183.8 171.3 144.7 118.2 91.6 - 170.9 16.4 170.9 163.6 140.5 113.9 87.3 -
6750
62 170.8 14.4 170.8 170.8 171.3 143.9 118.2 91.6 158.7 16.1 158.7 158.7 161.7 134.7 108.6 82.0
57 175.6 14.5 175.6 175.6 173.3 145.8 120.2 93.6 164.0 16.2 164.0 164.0 161.8 134.7 108.6 82.1
72 207.0 15.0 179.8 151.0 122.2 93.5 - - 190.7 16.6 173.1 144.3 115.5 86.7 - -
67 187.6 14.7 187.6 184.9 156.1 127.3 98.5 - 173.9 16.4 173.9 172.5 150.7 121.9 93.1 -
7500
62 174.3 14.4 174.3 174.3 174.3 145.5 116.7 87.9 161.5 16.2 161.5 161.5 161.5 132.7 103.9 75.1
57 179.2 14.5 179.2 179.2 179.2 150.4 121.6 92.8 166.8 16.2 166.8 166.8 166.8 138.1 109.3 80.5
J15PC/J15NL
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 175.1 18.3 92.4 73.5 54.6 - - - 157.4 19.9 85.8 67.0 48.1 - - -
72 162.0 18.1 120.0 101.1 82.2 63.3 - - 146.7 19.8 114.3 95.5 76.6 57.8 - -
4500 67 148.8 18.0 147.6 128.7 109.8 91.0 72.1 - 136.1 19.6 136.1 124.0 105.1 86.3 67.4 -
62 138.1 17.8 138.1 138.1 134.4 115.5 96.6 77.7 126.2 19.5 126.2 126.2 126.2 107.5 88.6 69.7
57 143.6 17.8 143.6 143.6 126.1 107.2 88.3 69.4 132.1 19.6 132.1 132.1 114.2 95.4 76.5 57.6
77 179.2 18.3 112.3 80.6 58.9 - - - 161.8 19.9 110.6 74.3 52.6 - - -
72 165.7 18.1 132.0 110.4 88.7 67.1 - - 150.8 19.8 126.9 105.3 83.6 62.0 - -
5250 67 152.3 18.0 151.7 140.2 118.6 96.9 75.3 - 139.9 19.6 139.9 136.3 114.7 93.0 71.4 -
62 141.3 17.8 141.3 141.3 145.0 123.4 101.7 80.1 129.7 19.5 129.7 129.7 129.7 116.6 94.6 72.9
57 146.9 17.8 146.9 146.9 136.1 114.4 92.8 71.1 135.7 19.6 135.7 135.7 124.8 103.6 81.5 59.9
77 183.2 18.3 132.3 87.6 63.3 - - - 166.2 19.9 135.3 81.5 57.1 - - -
72 169.5 18.1 144.0 119.6 95.3 70.9 - - 154.9 19.8 139.5 115.1 90.6 66.2 - -
6000 67 155.8 18.0 155.8 151.6 127.3 102.9 78.5 - 143.6 19.6 143.6 143.6 124.2 99.8 75.4 -
62 144.5 17.8 144.5 144.5 155.7 131.3 106.9 82.5 133.2 19.5 133.2 133.2 133.2 125.8 100.5 76.1
57 150.2 17.9 150.2 150.2 146.0 121.6 97.3 72.9 139.4 19.6 139.4 139.4 135.3 111.9 86.5 62.1
72 171.9 18.2 155.2 128.6 102.0 75.4 - - 156.4 19.8 149.5 122.9 96.3 69.7 - -
67 158.0 18.0 158.0 155.9 136.3 109.7 83.1 - 145.1 19.7 145.1 145.1 132.0 105.4 78.8 -
6750
62 146.6 17.8 146.6 146.6 152.1 125.6 99.0 72.4 134.5 19.5 134.5 134.5 134.5 116.4 89.4 62.7
57 152.4 17.9 152.4 152.4 150.3 123.7 97.1 70.5 140.8 19.6 140.8 140.8 138.8 112.7 85.5 58.9
72 174.3 18.2 166.3 137.5 108.8 80.0 - - 158.0 19.9 158.0 130.8 102.0 73.2 - -
67 160.2 18.1 160.2 160.2 145.3 116.5 87.7 - 146.5 19.8 146.5 146.5 139.9 111.1 82.3 -
7500
62 148.6 17.9 148.6 148.6 148.6 119.8 91.0 62.3 135.8 19.6 135.8 135.8 135.8 107.0 78.2 49.4
57 154.5 18.0 154.5 154.5 154.5 125.7 96.9 68.1 142.2 19.7 142.2 142.2 142.2 113.4 84.6 55.8
1 These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor
efficiency.
2 These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor
J15PD/J15NM
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 231.4 12.4 111.6 93.0 74.5 - - - 219.9 13.7 106.4 87.9 69.5 - - -
72 215.6 12.0 142.9 124.4 105.8 87.2 - - 204.0 13.4 138.2 119.7 101.2 82.8 - -
4500 67 199.7 11.7 174.3 155.7 137.2 118.6 100.0 - 188.1 13.1 169.9 151.4 133.0 114.5 96.0 -
62 183.7 11.4 183.7 183.7 170.7 152.1 133.6 115.0 174.3 12.8 174.3 174.3 163.8 145.3 126.9 108.4
57 184.6 11.4 184.6 184.6 173.2 154.6 136.1 117.5 175.3 12.8 175.3 175.3 164.8 146.3 127.8 109.4
77 233.6 12.4 117.3 98.2 76.9 - - - 222.0 13.7 114.1 92.9 71.7 - - -
72 217.6 12.1 151.9 130.6 109.3 88.0 - - 206.0 13.4 146.9 125.7 104.5 83.3 - -
5250 67 201.6 11.7 186.5 163.0 141.7 120.4 99.1 - 189.9 13.1 179.7 158.5 137.2 116.0 94.8 -
62 185.5 11.4 185.5 185.5 176.3 155.6 133.7 112.4 176.0 12.8 176.0 176.0 169.1 147.9 126.6 105.4
57 186.3 11.4 186.3 186.3 178.9 158.5 136.3 115.0 177.0 12.8 177.0 177.0 170.1 148.8 127.6 106.4
77 235.8 12.4 123.1 103.4 79.4 - - - 224.2 13.7 121.8 97.9 73.9 - - -
72 219.7 12.1 160.9 136.9 112.8 88.7 - - 208.0 13.4 155.6 131.7 107.7 83.8 - -
6000 67 203.5 11.7 198.8 170.3 146.2 122.2 98.1 - 191.8 13.1 189.4 165.5 141.5 117.6 93.6 -
62 187.2 11.4 187.2 187.2 182.0 159.2 133.8 109.8 177.7 12.9 177.7 177.7 174.3 150.4 126.4 102.5
57 188.0 11.4 188.0 188.0 184.6 162.4 136.5 112.4 178.7 12.9 178.7 178.7 175.4 151.4 127.5 103.5
72 222.5 12.1 171.1 144.6 118.1 91.7 - - 210.6 13.5 165.7 139.4 113.2 86.9 - -
67 206.2 11.8 203.8 179.6 153.2 126.7 100.2 - 194.2 13.2 193.0 174.9 148.6 122.4 96.1 -
6750
62 189.7 11.5 189.7 189.7 187.0 161.2 134.1 107.6 180.0 12.9 180.0 180.0 178.3 152.0 125.7 99.5
57 190.5 11.5 190.5 190.5 188.8 163.3 135.9 109.4 181.0 12.9 181.0 181.0 179.3 153.1 126.8 100.5
72 225.4 12.2 181.3 152.4 123.5 94.6 - - 213.3 13.6 175.8 147.2 118.6 90.0 - -
67 208.9 11.8 208.9 189.0 160.1 131.2 102.3 - 196.7 13.2 196.7 184.4 155.8 127.2 98.6 -
7500
62 192.1 11.5 192.1 192.1 192.1 163.2 134.3 105.5 182.2 13.0 182.2 182.2 182.2 153.6 125.0 96.4
57 193.0 11.5 193.0 193.0 193.0 164.1 135.2 106.3 183.3 13.0 183.3 183.3 183.3 154.7 126.1 97.5
95°F 105°F
77 208.3 15.1 101.3 82.9 64.5 - - - 192.0 17.0 96.4 77.9 59.4 - - -
72 192.4 14.8 133.4 115.0 96.6 78.3 - - 177.3 16.7 128.6 110.2 91.7 73.2 - -
4500 67 176.4 14.5 165.5 147.2 128.8 110.4 92.0 - 162.5 16.4 157.1 142.5 124.0 105.5 87.0 -
62 164.9 14.3 164.9 164.9 156.9 138.5 120.2 101.8 153.2 16.2 153.2 153.2 149.2 130.7 112.3 93.8
57 166.1 14.3 166.1 166.1 156.3 138.0 119.6 101.2 155.2 16.2 155.2 155.2 146.0 127.5 109.0 90.6
77 210.5 15.1 110.9 87.6 66.5 - - - 193.9 17.0 110.4 82.4 61.2 - - -
72 194.3 14.8 141.9 120.8 99.7 78.5 - - 179.0 16.7 136.8 115.7 94.5 73.4 - -
5250 67 178.2 14.5 172.8 153.9 132.8 111.7 90.6 - 164.1 16.4 161.4 149.0 127.8 106.6 85.5 -
62 166.5 14.3 166.5 166.5 161.8 140.1 119.6 98.5 154.7 16.2 154.7 154.7 154.2 132.7 111.9 90.7
57 167.8 14.3 167.8 167.8 161.2 139.2 119.0 97.9 156.8 16.2 156.8 156.8 150.5 128.9 108.2 87.0
77 212.6 15.1 120.6 92.3 68.5 - - - 195.8 17.0 124.4 86.9 63.1 - - -
72 196.3 14.8 150.3 126.5 102.7 78.8 - - 180.8 16.7 145.0 121.2 97.3 73.5 - -
6000 67 180.0 14.5 180.0 160.6 136.8 113.0 89.2 - 165.7 16.4 165.7 155.5 131.6 107.8 83.9 -
62 168.2 14.3 168.2 168.2 166.7 141.6 119.0 95.2 156.2 16.2 156.2 156.2 159.2 134.7 111.5 87.6
57 169.5 14.3 169.5 169.5 166.1 140.4 118.4 94.6 158.3 16.2 158.3 158.3 155.0 130.2 107.3 83.4
72 198.7 14.9 160.3 134.2 108.2 82.1 - - 183.0 16.8 155.6 129.3 103.0 76.7 - -
67 182.2 14.6 182.2 170.2 144.1 118.0 92.0 - 167.8 16.5 167.8 161.5 139.3 113.0 86.7 -
6750
62 170.3 14.3 170.3 170.3 169.5 142.8 117.4 91.3 158.2 16.2 158.2 158.2 159.7 133.0 107.1 80.8
57 171.6 14.4 171.6 171.6 169.9 142.9 117.7 91.6 160.3 16.3 160.3 160.3 158.6 131.9 106.0 79.7
72 201.2 14.9 170.3 142.0 113.6 85.3 - - 185.3 16.8 166.3 137.5 108.8 80.0 - -
67 184.5 14.6 184.5 179.8 151.4 123.1 94.8 - 169.9 16.5 169.9 167.5 147.1 118.3 89.6 -
7500
62 172.4 14.4 172.4 172.4 172.4 144.1 115.7 87.4 160.1 16.3 160.1 160.1 160.1 131.4 102.6 73.9
57 173.7 14.5 173.7 173.7 173.7 145.3 117.0 88.7 162.3 16.4 162.3 162.3 162.3 133.5 104.8 76.0
J15PD/J15NM (Continued)
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 175.7 18.9 91.5 72.9 54.3 - - - 159.4 20.8 86.6 67.9 49.2 - - -
72 162.2 18.6 123.9 105.3 86.8 68.2 - - 147.1 20.5 119.1 100.5 81.8 63.1 - -
4500 67 148.6 18.2 148.6 137.8 119.2 100.6 82.0 - 134.7 20.1 134.7 133.1 114.4 95.7 77.1 -
62 141.5 18.1 141.5 141.5 141.5 123.0 104.4 85.8 129.9 20.0 129.9 129.9 129.9 115.2 96.5 77.8
57 144.4 18.1 144.4 144.4 135.6 117.1 98.5 79.9 133.6 20.1 133.6 133.6 125.3 106.6 88.0 69.3
77 177.4 18.9 109.8 77.2 56.0 - - - 160.8 20.9 109.2 72.0 50.7 - - -
72 163.7 18.6 131.8 110.6 89.4 68.2 - - 148.4 20.5 126.8 105.5 84.3 63.0 - -
5250 67 150.0 18.3 150.0 144.0 122.8 101.6 80.4 - 135.9 20.1 135.9 135.9 117.8 96.5 75.3 -
62 142.9 18.1 142.9 142.9 146.6 125.4 104.2 82.9 131.0 20.0 131.0 131.0 131.0 118.0 96.4 75.2
57 145.8 18.1 145.8 145.8 139.8 118.5 97.3 76.1 134.8 20.1 134.8 134.8 129.1 108.2 86.5 65.2
77 179.0 18.9 128.1 81.5 57.6 - - - 162.3 20.9 131.9 76.1 52.2 - - -
72 165.2 18.6 139.8 115.9 92.0 68.2 - - 149.7 20.5 134.5 110.6 86.7 62.8 - -
6000 67 151.4 18.3 151.4 150.3 126.4 102.6 78.7 - 137.1 20.1 137.1 137.1 121.3 97.4 73.5 -
62 144.2 18.1 144.2 144.2 151.7 127.8 103.9 80.1 132.2 20.0 132.2 132.2 132.2 120.9 96.4 72.5
57 147.1 18.2 147.1 147.1 143.9 120.0 96.1 72.3 136.0 20.1 136.0 136.0 132.8 109.8 85.0 61.1
72 167.3 18.7 151.0 124.5 97.9 71.4 - - 151.6 20.6 146.3 119.6 92.8 66.1 - -
67 153.3 18.3 153.3 152.8 134.6 108.0 81.5 - 138.9 20.2 138.9 138.9 129.8 103.0 76.3 -
6750
62 146.0 18.1 146.0 146.0 149.8 123.2 96.7 70.2 133.9 20.0 133.9 133.9 133.9 113.5 86.4 59.6
57 149.0 18.2 149.0 149.0 147.4 120.9 94.3 67.8 137.7 20.1 137.7 137.7 136.1 109.9 82.6 55.9
72 169.4 18.7 162.2 133.0 103.9 74.7 - - 153.5 20.6 153.5 128.6 99.0 69.4 - -
67 155.3 18.4 155.3 155.3 142.7 113.5 84.3 - 140.7 20.3 140.7 140.7 138.3 108.7 79.1 -
7500
62 147.9 18.2 147.9 147.9 147.9 118.7 89.5 60.3 135.6 20.1 135.6 135.6 135.6 106.0 76.4 46.8
57 150.9 18.3 150.9 150.9 150.9 121.7 92.5 63.3 139.5 20.2 139.5 139.5 139.5 109.9 80.3 50.6
1 These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor
efficiency.
2 These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J20PD/J20NM
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 314.8 15.1 142.6 118.0 93.5 - - - 300.0 17.0 137.0 112.4 87.8 - - -
72 285.9 14.8 177.4 152.9 128.3 103.8 - - 271.7 16.7 171.9 147.4 122.8 98.3 - -
6000 67 257.1 14.5 212.3 187.7 163.2 138.6 114.0 - 243.5 16.4 206.9 182.4 157.8 133.2 108.7 -
62 239.1 14.2 239.1 225.1 200.5 175.9 151.4 126.8 227.5 16.1 227.5 219.3 194.7 170.2 145.6 121.1
57 239.5 14.3 239.5 237.8 213.3 188.7 164.1 139.6 230.2 16.2 230.2 227.8 203.3 178.7 154.1 129.6
77 321.1 15.2 154.7 127.4 100.0 - - - 305.7 17.1 148.9 121.5 94.1 - - -
72 291.7 14.9 192.0 164.7 137.3 110.0 - - 276.9 16.8 186.4 159.0 131.6 104.2 - -
7000 67 262.3 14.6 229.3 201.9 174.6 147.2 119.9 - 248.1 16.5 223.9 196.5 169.1 141.7 114.4 -
62 243.9 14.3 243.9 236.9 214.5 188.2 159.8 132.5 231.9 16.2 231.9 227.7 208.7 181.3 154.0 126.6
57 244.3 14.5 244.3 243.5 228.2 203.0 173.5 146.1 234.5 16.3 234.5 233.4 217.9 190.5 163.1 135.7
77 327.5 15.3 166.9 136.7 106.6 - - - 311.4 17.2 160.9 130.7 100.5 - - -
72 297.5 15.0 206.6 176.5 146.3 116.2 - - 282.1 16.9 200.9 170.7 140.5 110.2 - -
8000 67 267.5 14.8 246.3 216.2 186.0 155.9 125.7 - 252.8 16.6 240.9 210.7 180.5 150.2 120.0 -
62 248.8 14.4 248.8 248.8 228.6 200.4 168.3 138.1 236.2 16.2 236.2 236.2 222.7 192.5 162.3 132.1
57 249.2 14.6 249.2 249.2 243.2 217.3 182.9 152.7 238.9 16.4 238.9 238.9 232.5 202.2 172.0 141.8
72 303.3 15.2 219.3 184.7 150.2 115.7 - - 287.2 17.1 212.0 178.0 144.0 110.1 - -
67 272.7 14.9 262.1 225.5 191.0 156.5 122.0 - 257.4 16.8 251.5 219.1 185.1 151.1 117.1 -
9000
62 253.6 14.6 253.6 253.6 234.7 201.2 165.6 131.1 240.5 16.4 240.5 240.5 228.4 194.4 160.4 126.5
57 254.0 14.7 254.0 254.0 249.7 217.3 180.6 146.1 243.3 16.6 243.3 243.3 238.4 204.4 170.4 136.4
72 309.0 15.4 231.9 193.0 154.1 115.2 - - 292.4 17.3 223.1 185.4 147.6 109.9 - -
67 277.8 15.1 277.8 234.9 196.0 157.1 118.2 - 262.0 17.0 262.0 227.4 189.7 151.9 114.2 -
10000
62 258.4 14.7 258.4 258.4 240.8 201.9 163.0 124.1 244.8 16.6 244.8 244.8 234.1 196.4 158.6 120.9
57 258.8 14.9 258.8 258.8 256.2 217.3 178.4 139.5 247.6 16.8 247.6 247.6 244.3 206.6 168.8 131.1
95°F 105°F
77 285.2 18.9 131.3 106.8 82.2 - - - 264.8 21.2 126.0 101.4 76.8 - - -
72 257.5 18.6 166.4 141.9 117.3 92.8 - - 240.1 20.9 161.0 136.3 111.7 87.1 - -
6000 67 229.9 18.2 201.5 177.0 152.4 127.9 103.3 - 215.3 20.5 195.9 171.3 146.7 122.1 97.5 -
62 216.0 18.0 216.0 213.5 189.0 164.4 139.9 115.3 203.2 20.2 203.2 202.0 183.1 158.5 133.9 109.2
57 220.8 18.1 220.8 217.8 193.2 168.7 144.1 119.6 209.8 20.4 209.8 206.5 181.9 157.3 132.6 108.0
77 290.2 19.0 143.1 115.7 88.3 - - - 269.2 21.3 142.0 110.2 82.7 - - -
72 262.1 18.6 180.8 153.4 126.0 98.5 - - 244.1 20.9 175.3 147.8 120.3 92.8 - -
7000 67 234.0 18.3 218.5 191.1 163.7 136.3 108.8 - 219.0 20.6 208.6 185.4 157.9 130.4 102.9 -
62 219.8 18.0 219.8 218.6 202.9 174.5 148.1 120.7 206.6 20.3 206.6 206.0 197.1 169.1 142.1 114.6
57 224.7 18.2 224.7 223.2 207.5 177.9 152.6 125.2 213.3 20.5 213.3 211.7 195.8 167.2 140.8 113.3
77 295.2 19.0 154.9 124.6 94.3 - - - 273.7 21.4 158.1 119.0 88.5 - - -
72 266.6 18.7 195.2 164.9 134.6 104.3 - - 248.1 21.0 189.7 159.3 128.9 98.4 - -
8000 67 238.0 18.4 235.5 205.2 174.9 144.6 114.3 - 222.6 20.7 221.3 199.6 169.2 138.8 108.3 -
62 223.6 18.1 223.6 223.6 216.9 184.6 156.3 126.0 210.0 20.4 210.0 210.0 211.2 179.7 150.3 119.9
57 228.6 18.3 228.6 228.6 221.8 187.2 161.2 130.9 216.9 20.6 216.9 216.9 209.7 177.2 148.9 118.5
72 271.1 19.0 204.8 171.3 137.9 104.4 - - 252.2 21.2 199.3 165.7 132.2 98.6 - -
67 242.1 18.6 240.8 212.6 179.1 145.7 112.3 - 226.2 20.9 225.6 207.1 173.6 140.0 106.4 -
9000
62 227.4 18.3 227.4 227.4 222.1 187.7 155.2 121.8 213.4 20.6 213.4 213.4 213.0 179.0 145.9 112.4
57 232.5 18.5 232.5 232.5 227.1 191.5 160.2 126.8 220.4 20.8 220.4 220.4 215.2 180.5 148.0 114.5
72 275.7 19.2 214.3 177.7 141.1 104.5 - - 256.2 21.5 208.9 172.2 135.5 98.8 - -
67 246.1 18.8 246.1 219.9 183.4 146.8 110.2 - 229.8 21.1 229.8 214.6 177.9 141.2 104.6 -
10000
62 231.2 18.6 231.2 231.2 227.3 190.8 154.2 117.6 216.8 20.8 216.8 216.8 214.9 178.2 141.5 104.8
57 236.4 18.7 236.4 236.4 232.5 195.9 159.3 122.7 223.9 21.0 223.9 223.9 220.6 183.9 147.2 110.5
J20PD/J20NM (Continued)
Air on Temperature of air on condenser coil
evaporator coil Total Total Sensible capacity (MBh) Total Total Sensible capacity (MBh)
WB capacity1 input Return dry bulb (°F) capacity1 input Return dry bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 244.4 23.6 120.7 96.0 71.4 - - - 224.0 25.9 115.4 90.7 65.9 - - -
72 222.6 23.2 155.5 130.8 106.2 81.5 - - 205.1 25.5 150.0 125.3 100.6 75.8 - -
6000 67 200.8 22.8 190.3 165.6 140.9 116.3 91.6 - 186.2 25.1 184.7 159.9 135.2 110.5 85.7 -
62 190.4 22.5 190.4 190.4 177.2 152.5 127.8 103.2 177.6 24.8 177.6 177.6 171.3 146.5 121.8 97.1
57 198.8 22.8 198.8 195.2 170.5 145.8 121.2 96.5 187.8 25.1 187.8 183.9 159.2 134.4 109.7 85.0
77 248.3 23.6 140.9 104.7 77.1 - - - 227.3 25.9 139.8 99.1 71.4 - - -
72 226.1 23.2 169.8 142.2 114.6 87.0 - - 208.1 25.5 164.3 136.6 108.9 81.3 - -
7000 67 204.0 22.9 198.7 179.8 152.2 124.6 97.0 - 188.9 25.2 188.8 174.1 146.4 118.7 91.1 -
62 193.4 22.6 193.4 193.4 191.3 163.7 136.1 108.5 180.2 24.8 180.2 180.2 180.2 158.3 130.1 102.4
57 201.9 22.8 201.9 200.1 184.1 156.5 128.9 101.3 190.6 25.1 190.6 188.6 172.4 145.8 117.0 89.3
77 252.1 23.7 161.2 113.3 82.7 - - - 230.6 26.0 164.3 107.6 76.9 - - -
72 229.6 23.3 184.1 153.6 123.1 92.5 - - 211.1 25.6 178.6 148.0 117.3 86.7 - -
8000 67 207.1 22.9 207.1 194.0 163.4 132.9 102.4 - 191.7 25.2 191.7 188.3 157.7 127.0 96.4 -
62 196.4 22.6 196.4 196.4 205.4 174.9 144.4 113.8 182.8 24.9 182.8 182.8 182.8 170.1 138.4 107.8
57 205.1 22.9 205.1 205.1 197.7 167.2 136.6 106.1 193.3 25.2 193.3 193.3 185.7 157.2 124.4 93.7
72 233.2 23.5 193.9 160.2 126.5 92.8 - - 214.2 25.8 188.4 154.6 120.8 87.0 - -
67 210.3 23.2 210.3 201.6 168.0 134.3 100.6 - 194.5 25.5 194.5 194.5 162.4 128.6 94.8 -
9000
62 199.4 22.8 199.4 199.4 203.9 170.3 136.6 102.9 185.4 25.1 185.4 185.4 185.4 161.6 127.3 93.5
57 208.3 23.1 208.3 208.3 203.2 169.5 135.9 102.2 196.1 25.4 196.1 196.1 191.3 158.5 123.7 89.9
72 236.7 23.8 203.6 166.8 129.9 93.1 - - 217.2 26.1 198.2 161.3 124.3 87.4 - -
67 213.5 23.4 213.5 209.3 172.5 135.7 98.9 - 197.2 25.7 197.2 197.2 167.1 130.2 93.2 -
10000
62 202.5 23.1 202.5 202.5 202.5 165.6 128.8 92.0 188.1 25.4 188.1 188.1 188.1 153.1 116.1 79.2
57 211.4 23.4 211.4 211.4 208.7 171.9 135.1 98.3 198.9 25.7 198.9 198.9 196.8 159.9 123.0 86.0
1 These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor
efficiency.
2 These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J07PE / J07NL
Air over evaporator coil Capacity1 Outdoor temperature (°F @ 72% RH)
and
CFM DB (°F) kW -10 0 10 20 30 40 50 60
MBH 23.6 33.8 43.9 54.1 64.2 74.3 84.5 94.6
55
KW 4.4 4.5 4.7 4.9 5.0 5.2 5.4 5.6
MBH 22.3 32.5 42.6 52.7 62.9 73.0 83.1 93.3
2250 70
KW 5.2 5.4 5.5 5.7 5.9 6.1 6.2 6.4
MBH 21.1 31.2 41.3 51.5 61.6 71.7 81.9 92.0
80
KW 5.8 6.0 6.2 6.4 6.5 6.7 6.9 7.1
MBH 28.7 38.9 49.0 59.1 69.3 79.4 89.5 99.7
55
KW 3.9 4.0 4.2 4.4 4.6 4.7 4.9 5.1
MBH 27.4 37.5 47.6 57.8 67.9 78.0 88.2 98.3
3000 70
KW 4.7 4.9 5.1 5.2 5.4 5.6 5.8 5.9
MBH 26.1 36.2 46.4 56.5 66.6 76.8 86.9 97.1
80
KW 5.4 5.5 5.7 5.9 6.1 6.2 6.4 6.6
MBH 33.8 44.0 54.1 64.2 74.4 84.5 94.6 104.8
55
KW 3.6 3.8 4.0 4.2 4.3 4.5 4.7 4.8
MBH 32.5 42.6 52.8 62.9 73.0 83.2 93.3 103.5
3750 70
KW 4.5 4.6 4.8 5.0 5.2 5.3 5.5 5.7
MBH 31.2 41.4 51.5 61.6 71.8 81.9 92.1 102.2
80
KW 5.1 5.3 5.5 5.6 5.8 6.0 6.2 6.3
1
These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate
Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated
motor efficiency.
J10PC / J10NL
Air over evaporator coil Capacity1 Outdoor temperature (°F @ 72% RH)
and
CFM DB (°F) kW -10 0 10 20 30 40 50 60
MBH 36.7 51.4 66.2 80.9 95.7 110.4 125.2 139.9
55
KW 6.1 6.4 6.6 6.9 7.1 7.4 7.6 7.9
MBH 28.1 42.9 57.6 72.4 87.1 101.9 116.6 131.4
3000 70
KW 7.2 7.4 7.7 7.9 8.2 8.4 8.7 8.9
MBH 26.1 40.8 55.6 70.3 85.1 99.8 114.6 129.3
80
KW 8.1 8.4 8.6 8.9 9.1 9.4 9.6 9.9
MBH 38.6 53.4 68.1 82.9 97.6 112.4 127.1 141.9
55
KW 5.3 5.6 5.8 6.1 6.3 6.6 6.8 7.1
MBH 30.0 44.7 59.5 74.2 89.0 103.7 118.5 133.2
4000 70
KW 6.4 6.7 6.9 7.2 7.4 7.7 7.9 8.2
MBH 27.9 42.6 57.4 72.1 86.9 101.6 116.4 131.1
80
KW 7.4 7.6 7.9 8.1 8.4 8.6 8.9 9.1
MBH 49.5 64.2 78.9 93.7 108.4 123.2 137.9 152.7
55
KW 5.1 5.3 5.6 5.9 6.1 6.3 6.6 6.8
MBH 40.9 55.6 70.4 85.1 99.9 114.6 129.4 144.1
5000 70
KW 6.2 6.4 6.7 6.9 7.2 7.4 7.6 7.9
MBH 38.8 53.6 68.3 83.1 97.8 112.6 127.3 142.1
80
KW 7.1 7.4 7.6 7.9 8.1 8.4 8.7 8.9
1 These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate
Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated
motor efficiency.
J15PC / J15NL
Air over evaporator coil Capacity1 Outdoor temperature (°F @ 72% RH)
and
CFM DB (°F) kW -10 0 10 20 30 40 50 60
MBH 68.2 80.0 93.8 110.0 129.1 151.5 177.8 208.7
55
KW 11.8 12.2 12.7 13.2 13.7 14.1 14.6 15.1
MBH 61.5 73.2 87.0 103.2 122.3 144.7 171.0 201.9
4500 70
KW 13.5 14.0 14.4 14.9 15.4 15.9 16.3 16.8
MBH 57.6 69.3 83.1 99.3 118.4 140.8 167.1 198.0
80
KW 15.0 15.5 16.0 16.4 16.9 17.4 17.9 18.3
MBH 74.0 85.8 99.6 115.8 134.9 157.3 183.6 214.5
55
KW 11.2 11.7 12.2 12.6 13.1 13.6 14.1 14.6
MBH 67.3 79.0 92.8 109.0 128.1 150.5 176.8 207.7
6000 70
KW 12.9 13.4 13.9 14.4 14.8 15.3 15.8 16.3
MBH 63.4 75.1 88.9 105.1 124.2 146.6 172.9 203.8
80
KW 14.5 14.9 15.4 15.9 16.4 16.8 17.3 17.8
MBH 72.4 84.1 97.9 114.1 133.2 155.6 181.9 212.8
55
KW 12.0 12.5 13.0 13.4 13.9 14.4 14.9 15.4
MBH 65.6 77.3 91.1 107.4 126.4 148.8 175.1 206.0
7500 70
KW 13.7 14.2 14.7 15.2 15.6 16.1 16.6 17.1
MBH 61.7 73.4 87.3 103.5 122.5 144.9 171.2 202.1
80
KW 15.3 15.7 16.2 16.7 17.2 17.6 18.1 18.6
1
These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate
Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated
motor efficiency.
J15PD / J15NM
Air over evaporator coil Capacity1 Outdoor temperature (°F @ 72% RH)
and
CFM DB (°F) kW -10 0 10 20 30 40 50 60
MBH 65.6 77.0 90.3 105.8 123.9 145.1 169.7 198.5
55
KW 10.0 10.5 11.1 11.6 12.2 12.7 13.3 13.8
MBH 62.2 73.6 86.9 102.4 120.5 141.6 166.3 195.1
4500 70
KW 12.0 12.5 13.1 13.6 14.2 14.7 15.3 15.8
MBH 59.5 70.9 84.1 99.7 117.8 138.9 163.6 192.4
80
KW 13.4 13.9 14.5 15.0 15.6 16.1 16.7 17.2
MBH 71.6 83.0 96.3 111.8 129.9 151.0 175.7 204.5
55
KW 9.6 10.2 10.7 11.3 11.8 12.4 12.9 13.4
MBH 68.1 79.5 92.8 108.3 126.5 147.6 172.3 201.1
6000 70
KW 11.6 12.2 12.7 13.3 13.8 14.3 14.9 15.4
MBH 65.4 76.8 90.1 105.6 123.7 144.9 169.6 198.3
80
KW 13.0 13.6 14.1 14.7 15.2 15.8 16.3 16.9
MBH 74.0 85.4 98.7 114.2 132.4 153.5 178.2 207.0
55
KW 11.3 11.8 12.4 12.9 13.5 14.0 14.6 15.1
MBH 70.6 82.0 95.3 110.8 128.9 150.1 174.7 203.5
7500 70
KW 13.3 13.8 14.4 14.9 15.5 16.0 16.6 17.1
MBH 67.9 79.3 92.6 108.1 126.2 147.4 172.0 200.8
80
KW 14.7 15.3 15.8 16.4 16.9 17.5 18.0 18.5
1 These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate
Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated
motor efficiency.
J20PD / J20NM
Air over evaporator coil Capacity1 Outdoor temperature (°F @ 72% RH)
and
CFM DB (°F) kW -10 0 10 20 30 40 50 60
MBH 64.6 79.5 97.4 118.8 144.3 174.9 211.4 255.1
55
KW 15.7 16.5 17.3 18.1 19.0 19.8 20.6 21.4
MBH 69.5 84.4 102.3 123.7 149.2 179.8 216.3 260.0
6000 70
KW 15.4 16.2 17.0 17.9 18.7 19.5 20.3 21.2
MBH 63.3 78.3 96.2 117.5 143.1 173.6 210.2 253.8
80
KW 17.2 18.0 18.8 19.6 20.5 21.3 22.1 23.0
MBH 71.6 86.6 104.5 125.8 151.4 181.9 218.5 262.1
55
KW 15.1 15.9 16.8 17.6 18.4 19.2 20.1 20.9
MBH 76.5 91.5 109.4 130.7 156.3 186.8 223.4 267.0
8000 70
KW 14.8 15.6 16.5 17.3 18.1 19.0 19.8 20.6
MBH 70.4 85.3 103.2 124.6 150.1 180.7 217.2 260.9
80
KW 16.6 17.4 18.3 19.1 19.9 20.7 21.6 22.4
MBH 73.3 88.3 106.1 127.5 153.1 183.6 220.1 263.8
55
KW 15.3 16.1 17.0 17.8 18.6 19.4 20.3 21.1
MBH 78.2 93.2 111.0 132.4 158.0 188.5 225.0 268.7
10000 70
KW 15.0 15.8 16.7 17.5 18.3 19.1 20.0 20.8
MBH 72.1 87.0 104.9 126.3 151.8 182.4 218.9 262.6
80
KW 16.8 17.6 18.5 19.3 20.1 20.9 21.8 22.6
1
These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate
Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated
motor efficiency.
J25NC / 1HW04061
Capacity (MBH)
Unit Hot water
GPM CFM Entering water temperature minus entry air temperature °F.
model coil model
70 90 110 130 150
1
These capacities do not include any blower motor heat.
NOTE: Temperature Water Drop (ºF) = (2 X MBH) / GPM.
25 0.4 0.79
50 1.0 1.00
1HW0406
75 1.8 1.04
J25NC / 1NF0454
Capacity (MBH) @ 2 PSIG1
Unit Steam coil
CFM Dry bulb temperature of air entering coil (°F)
model model
10 30 50 70
1
These capacities do not include any blower motor heat.
Airflow performance
J07NL Upflow and horizontal airflow performance
J07NL Upflow
Available External Static Pressure - IWG
(CFM) 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 1.5 HP and Field
Standard 1.5 HP and Drive High Static 2 HP and Drive
Supplied Drive
2250 754 0.8 828 0.9 902 1.0 988 1.1 1051 1.3 1116 1.4 1183 1.5
2500 707 0.8 777 0.9 851 1.0 925 1.1 996 1.3 1059 1.4 1124 1.5 1191 1.7
2750 735 0.9 805 1.1 879 1.2 953 1.3 1012 1.4 1076 1.6 1141 1.7
3000 705 1.0 767 1.1 837 1.2 911 1.3 973 1.5 1035 1.6 1099 1.7 1164 1.9
3250 741 1.1 802 1.3 872 1.4 947 1.5 1002 1.7 1064 1.8 1127 2.0
3500 780 1.4 842 1.5 912 1.6 974 1.8 1035 1.9 1097 2.1 1161 2.2
3750 823 1.6 884 1.7 954 1.9 1012 2.0 1072 2.2 1134 2.3 Exceeds BHP Limitations
1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.
J07NL Horizontal
Available External Static Pressure - IWG
(CFM) 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 1.5 HP and Field
Standard 1.5 HP and Drive High Static 2 HP and Drive
Supplied Drive
2250 747 0.8 816 0.9 889 1.0 954 1.2 1013 1.3 1071 1.5 1128 1.6
2500 703 0.8 768 0.9 837 1.0 909 1.1 977 1.2 1036 1.4 1094 1.5 1151 1.7
2750 728 0.9 793 1.0 862 1.1 934 1.2 998 1.4 1056 1.5 1114 1.7
3000 696 0.9 757 1.1 822 1.2 891 1.3 961 1.4 1019 1.6 1077 1.7 1135 1.9
3250 729 1.1 790 1.3 855 1.4 924 1.5 984 1.6 1042 1.8 1100 1.9 1159 2.1
3500 766 1.3 826 1.5 892 1.6 953 1.6 1010 1.9 1069 2.0 1127 2.2
3750 806 1.6 867 1.7 932 1.8 984 1.9 1041 2.1 1099 2.3 Exceeds BHP Limitations
1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.
J10NL/NM Upflow
Available External Static Pressure - IWG
(CFM) 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 2 HP and Field
Standard 2 HP and Drive High Static 3 HP and Drive
Supplied Drive
2500 671 0.8 728 0.9 788 1.0 853 1.1 926 1.3 975 1.5 1026 1.6 1077 1.7
2750 684 0.9 741 1.0 801 1.1 866 1.2 933 1.4 982 1.6 1032 1.7 1084 1.8
3000 701 1.0 757 1.1 817 1.3 882 1.4 941 1.5 991 1.7 1041 1.8 1092 2.0
3250 664 1.0 719 1.1 776 1.3 836 1.4 903 1.5 952 1.7 1002 1.8 1052 2.0
3500 685 1.1 741 1.3 797 1.4 858 1.5 917 1.7 966 1.9 1015 2.0 1066 2.2
3750 653 1.1 709 1.3 764 1.4 821 1.6 884 1.7 933 1.9 982 2.0 1031 2.2 1082 2.3
4000 679 1.3 735 1.5 790 1.6 847 1.8 903 1.9 952 2.1 1001 2.3 1050 2.4
4250 707 1.5 762 1.6 818 1.8 875 1.9 924 2.1 973 2.3 1022 2.5 1072 2.7
4500 737 1.7 792 1.9 850 2.0 899 2.2 948 2.4 997 2.6 1046 2.8
4750 768 1.9 824 2.1 877 2.2 926 2.5 975 2.7 1024 2.9 1073 3.0
5000 801 2.1 856 2.3 906 2.5 956 2.8 1005 3.0 1053 3.2 High Static 3 HP and Field Supplied Drive
1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.
J10NL/NM Horizontal
Available External Static Pressure - IWG
(CFM) 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 2 HP and Field
Standard 2 HP and Drive High Static 3 HP and Drive
Supplied Drive
2500 686 0.8 730 0.9 778 0.9 840 1.0 917 1.3 964 1.5 1011 1.6 1060 1.7
2750 698 0.9 742 1.0 790 1.0 852 1.1 924 1.4 971 1.6 1019 1.7 1067 1.9
3000 714 1.0 758 1.1 806 1.1 868 1.2 935 1.6 981 1.7 1029 1.9 1078 2.0
3250 684 1.0 734 1.2 778 1.2 826 1.3 902 1.6 948 1.7 995 1.9 1042 2.0
3500 707 1.2 757 1.3 801 1.4 849 1.4 917 1.7 964 1.9 1010 2.0 1058 2.2
3750 669 1.2 734 1.4 784 1.5 828 1.6 890 1.7 936 1.9 982 2.1 1029 2.2 1076 2.4
4000 699 1.4 764 1.6 814 1.7 858 1.8 910 2.0 956 2.1 1002 2.3 1049 2.4
4250 732 1.6 798 1.8 847 1.9 887 2.0 933 2.2 978 2.4 1025 2.5 1071 2.7
4500 769 1.8 834 2.0 884 2.1 911 2.3 957 2.4 1003 2.6 1049 2.8
4750 808 2.1 874 2.3 891 2.3 937 2.5 983 2.7 1029 2.9 1075 3.1
5000 850 2.3 873 2.4 919 2.6 965 2.8 1011 3.0 1057 3.2 High Static 3 HP and Field Supplied Drive
1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.
J15NL/NM Upflow
Available External Static Pressure - IWG
(CFM) 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 3 HP and Field Supplied Drive Standard 3 HP and Drive High Static 5 HP and Drive
4500 583 1.1 634 1.3 688 1.5 738 1.9 782 2.3 827 2.6
4750 592 1.2 643 1.4 700 1.8 744 2.1 788 2.4 833 2.7
5000 602 1.2 653 1.4 707 1.9 751 2.2 795 2.6 840 2.9
5250 613 1.3 664 1.5 716 2.1 759 2.4 804 2.7 848 3.1
5500 577 1.1 625 1.4 676 1.6 725 2.3 768 2.6 813 2.9 857 3.2
5750 590 1.2 638 1.4 689 1.7 735 2.5 778 2.8 822 3.1
6000 603 1.3 651 1.6 702 2.3 745 2.7 789 3.0 833 3.3
6250 617 1.5 664 1.7 714 2.6 757 2.9 801 3.2 845 3.5
6500 587 1.4 631 1.6 679 1.8 726 2.8 769 3.1 813 3.4 857 3.8
6750 601 1.6 645 1.8 693 2.0 739 3.0 782 3.4 826 3.7
7000 616 1.8 660 2.0 710 2.9 753 3.3 796 3.6 839 3.9
7250 632 2.1 675 2.3 725 3.2 767 3.6 810 3.9 854 4.2
7500 647 2.3 691 2.5 740 3.5 782 3.9 825 4.2 High Static 5 HP and Field Supplied Drive
1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.
J15NL/NM Horizontal
Available External Static Pressure - IWG
(CFM) 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 3 HP and Field Supplied Drive Standard 3 HP and Drive High Static 5 HP and Drive
4500 585 1.5 634 1.6 687 1.8 735 2.0 780 2.5 827 2.7 875 2.9
4750 595 1.6 644 1.7 697 1.9 741 2.4 787 2.7 834 2.9
5000 605 1.7 655 1.8 708 2.0 749 2.6 795 2.9 842 3.1
5250 617 1.8 666 2.0 719 2.1 757 2.8 804 3.1 851 3.3
5500 582 1.8 629 1.9 678 2.1 731 2.3 767 3.0 813 3.2 860 3.4
5750 594 1.9 642 2.1 691 2.2 737 2.4 778 3.2 824 3.4 871 3.7
6000 608 2.1 655 2.2 705 2.4 744 3.1 789 3.4 835 3.7
6250 622 2.2 670 2.4 719 2.6 756 3.3 801 3.6 847 3.9
6500 589 2.2 637 2.4 684 2.6 733 2.7 769 3.6 814 3.9 860 4.1
6750 604 2.4 652 2.6 699 2.8 738 3.5 782 3.8 827 4.1 873 4.4
7000 620 2.6 667 2.8 715 3.0 752 3.8 796 4.1 841 4.4
7250 636 2.8 683 3.0 731 3.2 766 4.1 811 4.4 856 4.7
7500 652 3.0 700 3.2 738 4.0 781 4.4 825 4.7 High Static 5 HP and Field Supplied Drive
1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.
J20NL/NM Upflow
Available External Static Pressure - IWG
(CFM) 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 5 HP and
High Static 5 HP and Drive High Static 7.5 HP and Drive
Field Supplied Drive
6000 732 2.2 789 2.6 846 2.9 900 3.1 959 4.0 1008 4.5 1056 4.9 1102 5.2 1146 5.3
6250 685 1.9 742 2.3 799 2.7 856 3.0 910 3.3 967 4.2 1016 4.7 1064 5.1 1110 5.4 1154 5.5
6500 696 2.1 752 2.5 809 2.8 866 3.2 920 3.4 976 4.4 1025 4.9 1072 5.3 1118 5.6
6750 706 2.2 763 2.6 820 3.0 877 3.3 935 4.0 985 4.6 1034 5.1 1081 5.5 1127 5.8
7000 718 2.4 774 2.8 831 3.2 888 3.5 945 4.2 994 4.8 1043 5.3 1091 5.7 1137 6.0
7250 729 2.6 786 3.0 843 3.3 900 3.6 954 4.5 1004 5.0 1053 5.5 1100 5.9 1146 6.2
7500 741 2.8 798 3.1 855 3.5 912 3.8 965 4.7 1014 5.3 1063 5.8 1111 6.2
7750 700 2.6 754 2.9 810 3.3 868 3.7 925 4.3 975 4.9 1025 5.5 1074 6.0 1121 6.4
8000 712 2.8 767 3.1 823 3.5 881 3.9 936 4.6 986 5.2 1036 5.8 1085 6.3 1132 6.7
8250 726 3.0 780 3.3 837 3.7 894 4.1 948 4.9 998 5.5 1047 6.0 1096 6.5 1144 6.9
8500 740 3.2 794 3.6 850 3.9 908 4.3 959 5.1 1010 5.8 1059 6.3 1108 6.8
8750 754 3.4 808 3.8 865 4.2 922 4.8 972 5.4 1022 6.0 1071 6.6 1120 7.1
9000 768 3.6 823 4.0 879 4.4 934 5.1 984 5.7 1034 6.4 1084 6.9 1133 7.4
9250 783 3.9 838 4.3 894 4.6 947 5.4 997 6.1 1047 6.7 1097 7.2
9500 799 4.1 853 4.5 910 4.9 961 5.8 1011 6.4 1061 7.0 1110 7.6
9750 815 4.4 869 4.8 925 5.5 974 6.1 1024 6.7 1074 7.3 1124 7.9
10000 831 4.7 885 5.0 939 5.9 988 6.5 1038 7.1 1088 7.7 1138 8.3 High Static 7.5 HP and Field Supplied Drive
1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.
J20NL/NM Horizontal
Available External Static Pressure - IWG
(CFM) 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Std. 5 HP
and Field
Standard 5 HP and Drive High Static 7.5 HP and Drive
Supplied
Drive
6000 708 2.0 754 2.3 801 2.6 849 2.8 898 2.9 976 4.0 1021 4.4 1066 4.8 1111 5.1 1155 5.3
6250 715 2.1 761 2.4 808 2.7 856 2.9 906 3.0 984 4.2 1029 4.6 1074 5.0 1118 5.3 1163 5.5
6500 723 2.3 769 2.6 816 2.8 864 3.0 947 3.9 991 4.4 1036 4.8 1081 5.2 1126 5.4
6750 731 2.4 777 2.7 824 3.0 872 3.2 955 4.1 999 4.6 1044 5,0 1089 5.3 1134 5.6
7000 740 2.5 786 2.8 833 3.1 881 3.3 963 4.3 1007 4.7 1052 5.2 1097 5.5 1142 5.8
7250 749 2.7 796 3.0 842 3.3 890 3.5 971 4.5 1015 4.9 1060 5.3 1105 5.7 1150 6.0
7500 712 2.6 759 2.9 806 3.2 852 3.4 900 3.6 979 4.7 1024 5.1 1069 5.5 1114 5.9 1158 6.2
7750 722 2.8 770 3.0 816 3.3 863 3.6 945 4.4 988 4.9 1033 5.3 1078 5.8 1123 6.1
8000 733 2.9 781 3.2 827 3.5 874 3.8 954 4.6 998 5.1 1042 5.5 1087 6.0 1132 6.3
8250 745 3.1 793 3.4 839 3.7 886 4.0 964 4.8 1007 5.3 1052 5.8 1096 6.2 1141 6.5
8500 757 3.3 805 3.6 851 3.9 898 4.2 974 5.1 1017 5.6 1062 6.0 1107 6.4 1152 6.8
8750 770 3.6 818 3.8 864 4.1 942 4.8 984 5.3 1028 5.8 1072 6.3 1117 6.7
9000 784 3.8 831 4.1 878 4.4 953 5.1 995 5.6 1039 6.1 1083 6.5 1128 6.9
9250 798 4.0 845 4.3 923 4.9 964 5.4 1006 5.9 1050 6.3 1094 6.8 1139 7.2
9500 812 4.3 859 4.6 935 5.2 976 5.7 1018 6.2 1062 6.6 1106 7.1 1151 7.5
9750 827 4.5 908 5.1 947 5.5 988 6.0 1030 6.5 1074 6.9 1118 7.4
10000 842 4.8 921 5.4 960 5.8 1001 6.3 1043 6.8 1087 7.3 1131 7.7 High Static 7.5 HP and Field Supplied Drive
1. Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.
2. See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.746 ÷ nameplate rated motor efficiency.
1. J25NC requires the selection, purchase and field installation of the Supply Fan Motor, Drive Kit and Motor Overloads (See Following Page for Item
Selection Tables).
RPM selection
6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn Fully
Unit Model HP Max BHP Motor Sheave Blower Sheave
Open Open Open Open Open Open Closed
Std. 1.5 1.73 1VL40 AK69 -1 690 743 796 849 902 955
J07NL
HS 2 2.30 1VL40 AK56 -1 863 929 995 1062 1128 1194
Std. 2 2.30 1VL40 AK74 -1 641 690 739 789 838 887
J10NL/NM
HS 3 3.45 1VP56 AK84 -1 906 949 992 1035 1078 1121
Std. 3 3.45 1VP50 AK114 -1 565 596 627 659 690 721
J15NL/NM
HS 5 5.75 2VP50 2B5V94 707 745 782 819 856 894 -2
Std. 5 5.75 2VP50 2B5V94 686 722 758 794 830 866 -2
J20NL/NM
HS 7.5 8.63 2VP65 2B5V94 925 960 996 1031 1067 1103 1138
1
Setting not available.
2
Setting not recommended for use with Type B v-belts.
J07NL and J10 - 20 NL/NM air handler blower motor and drive data
Blower Motor Data Drive Data
Adjustable Motor Sheave Fixed Blower Sheave Belts
Unit Blower
Model Frame Model Pitch Model Pitch Pitch
HP RPM SF RPM Bore Desig-
Size Number Diameter Number Diameter Bore (in.) Qty. Length
Range (in.) nation
(in.) (in.) (in.)
Std 1.5 56 1VL40 690 - 955 2.6 - 3.6 0.875 AK69 6.5 1.000 1 42.3 A41
J07NL 1725 1.15
HS 2 56HZ 1VL40 863 - 1194 2.6 - 3.6 0.875 AK56 5.2 1.000 1 40.3 A39
Std. 2 56HZ 1VL40 641 - 887 2.6 - 3.6 0.875 AK74 7.0 1.000 1 45.3 A44
J10NL/NM 1725 1.15
HS 3 56HZ 1VP56 906 - 1121 4.2 - 5.2 0.875 AK84 8.0 1.000 1 48.3 A47
Std. 3 56HZ 1VP50 565 - 721 3.6 - 4.6 0.875 AK114 11.0 1.000 1 45.3 A44
J15NL/NM 1725 1.15
HS 5 184T 2VP50 707 - 894 3.7 - 4.7 1.125 2B5V94 9.7 1.000 2 41.8 B40
Std. 5 184T 2VP50 686 - 866 3.7 - 4.7 1.125 2B5V94 9.7 1.188 2 41.8 B40
J20NL/NM 1725 1.15
HS 7.5 213T 2VP65 925 - 1138 5.2 - 6.4 1.375 2B5V94 9.7 1.188 2 46.8 B45
CFM static pressure and power-altitude and temperature order to use the indoor blower tables for high altitude
corrections applications, certain corrections are necessary.
The information below should be used to assist in application A centrifugal fan is a "constant volume" device. This means
of product when being applied at altitudes at or exceeding that, if the rpm remains constant, the CFM delivered is the
1000 feet above sea level. same regardless of the density of the air. However, since the
air at high altitude is less dense, less static pressure will be
The air flow rates listed in the standard blower performance generated and less power will be required than a similar
tables are based on standard air at sea level. As the altitude application at sea level. Air density correction factors are
or temperature increases, the density of air decreases. In shown in Altitude Factors Table and Temperature Correction
Figure.
1.100
1.050
1.000
Sea Level
0.950
Correction Factor
1000 ft
0.900 2000 ft
3000 ft
0.850
4000 ft
0.800 5000 ft
6000 ft
0.750 7000 ft
8000 ft
0.700
9000 ft
10000 ft
0.650
0.600
40 50 60 70 80 90 100
Air Temperature (ºF)
The examples below will assist in determining the airflow blower tables to select the blower speed and the BHP
performance of the product at altitude. requirement.
Example 1: What are the corrected CFM, static pressure, Solution: As in the example above, no temperature
and BHP at an elevation of 5,000 ft. if the blower information is given so 70°F is assumed.
performance data is 6,000 CFM, 1.5 IWC and 4.0 BHP?
The 1.5" static pressure given is at an elevation of 5,000 ft.
Solution: At an elevation of 5,000 ft. the indoor blower will still The first step is to convert this static pressure to equivalent
deliver 6,000 CFM if the rpm is unchanged. However, the sea level conditions.
Altitude/Temperature Correction Factors table must be used to
determine the static pressure and BHP. Since no temperature Sea level static pressure = 1.5 / .832 = 1.80"
data is given, we will assume an air temperature of 70°F. The
Enter the blower table at 6000 sCFM and static pressure of
table shows the correction factor to be 0.832.
1.8". The rpm listed will be the same rpm needed at 5,000 ft.
Corrected static pressure = 1.5 x 0.832 = 1.248 IWC
Suppose that the corresponding BHP listed in the table is 3.2.
Corrected BHP = 4.0 x 0.832 = 3.328 This value must be corrected for elevation.
Example 2: A system, located at 5,000 feet of elevation, is to BHP at 5,000 ft. = 3.2 x .832 = 2.66
deliver 6,000 CFM at a static pressure of 1.5". Use the unit
Drive selection
1. 3250 CFM
2. 1.4 iwg
3. Using the supply air blower performance table below, the following data point was located: 1100 RPM and 1.8 BHP.
4. Using the RPM selection table below, Model X is found.
5. 1.8 BHP exceeds the maximum continuous BHP rating of the 1.5 HP motor. The 2 HP motor is required.
6. 1100 RPM is within the range of the 2 HP drives.
7. Using the 2 HP motor and drive, 1 turn open will achieve 1128 RPM.
Airflow performance
Example supply air blower performance
Available External Static Pressure - IWG
(CFM) 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard 1.5 HP and Drive High Static 2 HP and Drive
3000 696 0.9 757 1.1 822 1.2 891 1.3 961 1.3 1019 1.5 1077 1.6 1135 1.8
3250 729 1.1 790 1.3 855 1.4 924 1.5 984 1.6 1042 1.7 1100 1.8 1159 2.0
3500 766 1.3 826 1.5 892 1.6 953 1.6 1010 1.8 1069 1.9 1127 2.0
RPM selection
Max Motor Blower 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn Fully
Unit model HP
BHP sheave sheave Open Open Open Open Open Open Closed
Std. 1.5 1.73 1VL40 AK69 N/A 690 743 796 849 902 955
X
HS 2 2.30 1VL40 AK56 N/A 863 929 995 1062 1128 1194
Sound performance
Electrical data
Electrical data for outdoor models
Supply
Max Fuse2/
Blower Electric Heat Option MCA1
Motor HP Power Supply Motor Breaker3 Size
(Amps)
(Amps)
FLA Model KW Stages Amps
J07NL C00B (INTELLISPEED)
None --- --- --- 5.4 15
10 KW 7.5 1 20.8 31.4 35
208-3-60 4.3 16 KW 12 2 33.4 47.0 50
26 KW 19.5 2 54.2 73.0 80
36 KW 27 2 75.1 99.1 100
None --- --- --- 5.3 15
10 KW 10 1 24.1 35.3 40
230-3-60 4.2 16 KW 16 2 38.5 53.4 60
26 KW 26 2 62.5 83.4 90
36 KW 36 2 86.6 113.5 125
1.5
None --- --- --- 2.6 15
10 KW 10 1 12.0 17.7 20
460-3-60 2.1 16 KW 16 2 19.2 26.7 30
26 KW 26 2 31.3 41.7 45
36 KW 36 2 43.3 56.8 60
None --- --- --- 2.3 15
10 KW 10 1 9.6 14.3 15
575-3-60 1.8 16 KW 16 2 15.4 21.5 25
26 KW 26 2 25.0 33.5 35
36 KW 36 2 34.6 45.6 50
J10 (NL/NM) C00C (INTELLISPEED)
None --- --- --- 7.3 15
10 KW 7.5 1 20.8 33.3 35
208-3-60 5.8 16 KW 12 2 33.4 48.9 50
26 KW 19.5 2 54.2 74.9 80
36 KW 27 2 75.1 100.9 110
None --- --- --- 7.3 15
10 KW 10 1 24.1 37.3 40
230-3-60 5.8 16 KW 16 2 38.5 55.4 60
26 KW 26 2 62.5 85.4 90
36 KW 36 2 86.6 115.5 125
2.0
None --- --- --- 3.6 15
10 KW 10 1 12.0 18.7 20
460-3-60 2.9 16 KW 16 2 19.2 27.7 30
26 KW 26 2 31.3 42.7 45
36 KW 36 2 43.3 57.8 60
None --- --- --- 2.8 15
10 KW 10 1 9.6 14.8 15
575-3-60 2.2 16 KW 16 2 15.4 22 25
26 KW 26 2 25.0 34 35
36 KW 36 2 34.6 46.1 50
Supply
Max Fuse2/
Blower Electric Heat Option MCA1
Motor HP Power Supply Motor Breaker3 Size
(Amps)
(Amps)
FLA Model KW Stages Amps
J15 (NL/NM) C00D (INTELLISPEED)
None --- --- --- 10.4 15
10 KW 7.5 1 20.8 36.4 40
16 KW 12 2 33.4 52 60
208-3-60 8.3
26 KW 19.5 2 54.2 78 80
36 KW 27 2 75.1 104.1 110
50 KW4 37.6 2 104.2 140.8 150
None --- --- --- 10.3 15
10 KW 10 1 24.1 40.3 45
16 KW 16 2 38.5 58.4 60
230-3-60 8.2
26 KW 26 2 62.5 88.4 90
36 KW 36 2 86.6 118.5 125
50 KW4 50 2 120.3 130.5 150
3.0
None --- --- --- 5.1 15
10 KW 10 1 12 20.2 25
16 KW 16 2 19.2 29.2 30
460-3-60 4.1
26 KW 26 2 31.3 44.2 45
36 KW 36 2 43.3 59.3 60
50 KW4 50 2 60.1 65.3 70
None --- --- --- 4 15
10 KW 10 1 9.6 16 20
16 KW 16 2 15.4 23.2 25
575-3-60 3.2
26 KW 26 2 25 35.3 40
36 KW 36 2 34.6 47.3 50
50 KW 50 2 48.1 52.1 60
J15 (NL/NM) C00E (INTELLISPEED)
None --- --- --- 16.9 20
10 KW 7.5 1 20.8 42.9 45
16 KW 12 2 33.4 58.5 60
208-3-60 13.5
26 KW 19.5 2 54.2 84.5 90
36 KW 27 2 75.1 110.6 125
50 KW 37.6 2 104.2 147.3 150
None --- --- --- 16.3 20
10 KW 10 1 24.1 46.3 50
16 KW 16 2 38.5 64.4 70
230-3-60 13.0
26 KW 26 2 62.5 94.4 100
36 KW 36 2 86.6 124.5 125
50 KW 50 2 120.3 136.5 150
5.0
None --- --- --- 8.1 15
10 KW 10 1 12.0 23.2 25
16 KW 16 2 19.2 32.2 35
460-3-60 6.5
26 KW 26 2 31.3 47.2 50
36 KW 36 2 43.3 62.3 70
50 KW 50 2 60.1 68.3 70
None --- --- --- 6.5 15
10 KW 10 1 9.6 18.5 20
16 KW 16 2 15.4 25.7 30
575-3-60 5.2
26 KW 26 2 25.0 37.8 40
36 KW 36 2 34.6 49.8 50
50 KW 50 2 48.1 54.6 60
Supply
Max Fuse2/
Blower Electric Heat Option MCA1
Motor HP Power Supply Motor Breaker3 Size
(Amps)
(Amps)
FLA Model KW Stages Amps
J20 (NL/NM) C00E (INTELLISPEED)
None --- --- --- 16.9 20
20 KW 15 1 41.6 68.9 70
208-3-60 13.5
32 KW 24 2 66.6 100.1 110
52 KW 39.1 2 108.5 152.5 175
None -- --- --- 16.3 20
20 KW 20 1 48.1 76.4 80
230-3-60 13.0
32 KW 32 2 77.0 112.5 125
52 KW 52 2 125.1 141.3 150
5.0
None --- --- --- 8.1 15
20 KW 20 1 24.1 38.2 40
460-3-60 6.5
32 KW 32 2 38.5 56.2 60
52 KW 52 2 62.5 70.7 80
None --- --- --- 6.5 15
20 KW 20 1 19.2 30.6 35
575-3-60 5.2
32 KW 32 2 30.8 45.0 45
52 KW 52 2 50.0 56.5 60
J25NC C00N5
208-3-60 16.7 None --- --- --- 21.0 35
230-3-60 15.2 None --- --- --- 19.0 30
5.0
460-3-60 7.6 None --- --- --- 10.0 15
575-3-60 6.1 None --- --- --- 8.0 15
J20 (NL/NM) C00F (INTELLISPEED)
None --- --- --- 25.0 25
20 KW 15 1 41.6 77.0 80
208-3-60 20.0
32 KW 24 2 66.6 108.3 110
52 KW 39.1 2 108.5 160.7 175
None -- --- --- 24.3 25
20 KW 20 1 48.1 84.4 90
230-3-60 19.4
32 KW 32 2 77.0 120.52 125
52 KW 52 2 125.1 149.3 150
7.5
None --- --- --- 12.1 15
20 KW 20 1 24.1 42.2 45
460-3-60 9.7
32 KW 32 2 38.5 60.2 70
52 KW 52 2 62.5 74.7 80
None --- --- --- 9.8 15
20 KW 20 1 19.2 33.8 35
575-3-60 7.8
32 KW 32 2 30.8 48.2 50
52 KW 52 2 50.0 59.8 60
J25NC C00N5
208-3-60 24.2 None --- --- --- 30.0 35
230-3-60 22.0 None --- --- --- 28.0 30
7.5
460-3-60 11.0 None --- --- --- 14.0 15
575-3-60 9.0 None --- --- --- 11.0 20
1 Minimum Circuit Ampacity.
2 Dual Element, Time Delay Type.
3 HACR type per NEC.
4 J15NC/NDC00D Models Only
5 Motors are not shipped with these models. Motor and Drive Kits are required.
ELEMENTARY DIAGRAM
ELEMENTARY DIAGRAM
505429-JTG-NN-1222
ELEMENTARY DIAGRAM
75
505429-JTG-NN-1222
76
A B C D E F G H J K L
505429-JTG-NN-1222
ELEMENTARY DIAGRAM
77
505429-JTG-NN-1222
78
A B C D E F G H J K L
ELEMENTARY DIAGRAM
505429-JTG-NN-1222
ELEMENTARY DIAGRAM
79
505429-JTG-NN-1222
80
A B C D E F G H J K L
ELEMENTARY DIAGRAM
505429-JTG-NN-1222
ELEMENTARY DIAGRAM
Heat pump units
81
505429-JTG-NN-1222
82
A B C D E F G H J K L
ELEMENTARY DIAGRAM
505429-JTG-NN-1222
ELEMENTARY DIAGRAM
83
505429-JTG-NN-1222
84
A B C D E F G H J K L
ELEMENTARY DIAGRAM
505429-JTG-NN-1222
ELEMENTARY DIAGRAM
Typical J25YC, Rawal 2 Pipe
85
505429-JTG-NN-1222
505429-JTG-NN-1222
Component map
M3 M4
PHS
LAC1 LAC2
*CB4
TB1
RC1
RC2
RC3
RC4
FS1 FS2
*DISC
T1
UCB
RW1
SEE DETAIL A T2
TB3
GND2
TB2
M1 M2
*FDD
AUX 4
CCHR1
SEE DETAIL B
TB2
DETAIL B
TB2
TB2
AUX 1 AUX 2 AUX 3
TB3-2
NOTE:
TB3-3 TB3-1
1. UNIT MAY NOT HAVE ALL COMPONENTS
DETAIL A
SHOWN, DEPENDING ON MODEL AND
TB3-1/2/3
OPTIONS INSTALLED.
ELEMENTARY DIAGRAM
Air handling units
87
505429-JTG-NN-1222
505429-JTG-NN-1222
Typical J10 to 20NL, 1.5 to 5 HP blower motor only wiring diagram (10 ton - 2 pipe unit manufactured prior to January
1, 2023)
Typical J10NL, 2 to 3 HP blower motor only wiring diagram (10 ton - 2 pipe unit manufactured after January 1, 2023)
ELEMENTARY DIAGRAM
505429-JTG-NN-1222
LEFT
D A
LEFT
DIM X
D A
DIM X CG
CG
FRONT REAR FRONT REAR
WIDTH
C B
WIDTH
DIM Y
LENGTH
RIGHT C B
J07PE, J10PC,
J07YE, J10YC, J10YD, DIM Y
J12YC, J12YD LENGTH
RIGHT
J15PC, J15PD,
J20PC, J20PD,
J15YC, J15YD,
J20YC, J20YD
J25YC
Note: The front of unit is considered the side with the unit control box.
RIGHT
31.90
REAR FRONT
LEFT
59.10
CONVENIENCE
OUTLET
BASE RAIL
DETAIL A
2.375 2X (Ø 1.375)
KNOCKOUT
30.994
TOP
1.33 2X (Ø 0.875)
KNOCKOUT
3.43 12.126
3.75 9.876
2.097 4.751
BOTTOM
3.883
7.000 10.000 7.000 7.000 23.000 7.000
2.923 3.664
37.000
24.000 2.933
3.563 31.758 1.664
58.500
FRONT RIGHT
SYSTEM 2
2X (Ø 0.875)
KNOCKOUT
2X (Ø 1.375)
KNOCKOUT
15.53
12.70 12.000
SYSTEM 1 10.000
4.875
6.26
4.132
7.52
8.98 2.382
REAR 10.60 LEFT 1.882
REAR
59.10
LEFT RIGHT
FRONT
64.10
BASE RAIL
DETAIL
A
2.375 SYSTEM 2
SYSTEM 1
TOP 2X (Ø 1.375)
30.994 KNOCKOUT
1.33
2X (Ø 0.875)
3.43 KNOCKOUT
3.75 11.375
9.125
2.097 4.750
BOTTOM 4.132
7.000 23.000 7.000 7.000 23.000 7.000
3.913
2.923 37.000 37.000
3.181
64.000 1.913
3.563 59.000
FRONT RIGHT
SYSTEM 2
SYSTEM 1
16.133
13.133
17.367
18.867
20.617
22.617
FRONT
(PIPING DETAIL)
With the piping connections being made at the rear of 7.5 to 12.5 ton units and the front of 15 to 20 ton units, the piping can be
routed to the units from the left or right side.
Electrical connections for power and control wiring are made from the front of the units, right or left of 7.5 to 12.5 ton electrical
control box access or left of the electrical control box access on 15 to 20 ton units. See Unit dimensions and piping and
electrical connection sizes tables for piping sizes and electrical knockout details.
Minimum clearances
Clearance description Distance (in.)
Overhead (Top) 120
Front 36
Rear 24
Left Side 30
Right Side 30
Bottom1 0
1 In all installations where snow accumulates and winter operation is
expected, additional height must be provided to insure normal
condenser airflow.
LEFT
LEFT
A B A B
A B C A B C
WIDTH
WIDTH
CG FRONT CG REAR
FRONT REAR
DIM Y
DIM Y
F E D
F E D D C
D C
DIM X
DIM X LENGTH
LENGTH RIGHT
VERTICAL POSITION
CG CG
Y Y
(F) (C) (F) (C)
MOTOR
X X
MOTOR
Vertical Horizontal
Top view
Ø 1.72 KNOCKOUT 20.31 Ø 1.718 KNOCKOUT FOR 20.313
ELECTRIC HEAT ELECTRIC HEAT
8.84 8.837
9.25 9.246
13.44
15.920
8.22
5.135
4.56
7.06
65.000
6.38
FIELD PIPING
CONNECTIONS
35.000
SYSTEM 2 17.85
20.531
15.50
13.13
SYSTEM 1
10.73
2.000
56.000 30.00
Bottom view
56.00
2.66
AIR IN 11.43
30.00
Horizontal configuration
30.00
35.00
30.00
60.00
Top view
Ø 1.718 KNOCKOUT FOR 23.85
ELECTRIC HEAT
10.00
10.50
18.84
3.79
26.34 21.82
3.66
4.56
7.06
75.00
6.44
FIELD PIPING
CONNECTIONS
42.00
27.53
SYSTEM 2
SYSTEM 1 17.85
15.50
13.13
10.73
2.00
70.50 2.00
1.88
DRAIN 3/4 in. ABS 7.12
74.50 PIPE CONNECTION
33.00
FRONT VIEW - RETURN AIR
INDOOR
RIGHT SIDE VIEW - DRAIN PIPING/CONTROLS
Bottom view
74.50
2.66
AIR IN 14.43
33.000
Horizontal configuration
33.000
42.000
33.000
66.000
Top view
1-1/4 in. CONDUIT KNOCKOUT 1-1/4 in. CONDUIT KNOCKOUT
(Ø 1.718) (Ø 1.718)
ELECTRIC HEAT CONTROL ELECTRIC HEAT POWER
22.86
WIRE CONNECTION CONNECTION
8.83
9.25
15.90
BLOWER OPENING
9.25
4.14 5.14
18.63 25.30
BLOWER OPENING
18.63 54.57
BLOWER OPENING
75.64
3.66
4.56
7.06
65.13
6.44
SYSTEM 2 FIELD PIPING
CONNECTIONS
35.00
19.19
SYSTEM 1
17.85
15.50
13.13
10.73
2.56
1.88
3.56 44.91
2.56 DRAIN 3/4 in. ABS 7.12
PIPE CONNECTION
93.37
30.00
98.50
Bottom view
98.50
45.38 2.72
2.66
30.00
Horizontal configuration
30.00
35.00
30.00
60.00
BLOWER
EVAPORATOR
POSITION COIL POSITION POSITION POSITION
1 2 3 4
POSITION POSITION
POSITION POSITION 7
1 3 5
Top view
62.37 22.03
5.31
2.58
9.05
3.00
19.03
4X Ø 1.093 K0
CONTROLS
CONNECTION
15.92
Ø 1.375 K0
57.69 ELECTRIC HEAT
CONNECTION
36.69
74.59
Ø 1.38 KO
Ø 0.88 LIQUID
CONNECTION
37.28
33.22 Ø 2.13 SUCTION
CONNECTION
Ø 1.38 KO 24.98
Ø 0.88 DRAIN
CONNECTION
7.64
2.36 3.53
46.97 3.37
0.63 4.08
95.59 4.22
100.13 38.06
FRONT (RETURN AIR) VIEW RIGHT SIDE
(SERVICE CONNECTION) VIEW
Horizontal configuration
RETURN
AIR
SUPPLY
AIR
73.3
74.0
Unit dimensions J25NC (Continued)
1
BLOWER
AIR
2 3
AIR
AIR
AIR
EVAPORATOR AIR AIR
COIL
4 5 6
AIR
AIR
Note: *If required, some air can be returned through the bottom of the evaporator section
AIR
7 8 9
AIR
AIR AIR AIR
AIR
AIR
10 11 12
AIR
Horizontal airflow arrangements J25NC
Minimum clearances
Minimum Clearances
Top with Supply Air Opening1 24 in.
Front with Return Air Opening 24 in.
Right Side with access for Piping, Power and
24 in.
Control Wiring Connections2
Left Side 24 in.
Rear3 N/A
Bottom4 N/A
1
This dimension will vary if an electric heater, a supply air
plenum or a base is used.
2 This dimension is required for normal installation and
service.
3
Although no clearance is required for service and
operation, some clearance may be required for routing
the power and control wiring.
4
Allow enough clearance to trap the condensate drain
line.
Note: If the coil has to be removed, the blower section
can be unbolted and set aside and the coil can be
lifted out the top of the evaporator section.
Unit mounting - J07 to 20NL/NM components to suspend an AHU must be field supplied.
Please refer to the units total weight, center of gravity and
The split air handling units can be applied in various corner weights. (Horizontal position) shown in the appropriate
horizontal positions. The Typical Suspension of AHU’s From table for proper support sizing.
Ceiling Figure shows recommended suspension rigging
using properly sized all-thread and metal c-channel. All
END VIEW
MOUNTING DETAIL
All Thread
Steel Rod
Mounting
Bracket
Flat Washer /
Lock Washer
and Nut
Steel C-
channel
SIDE VIEW
Unit mounting - J25NC channels and hardware. The channels extend across the
evaporator coil section, the heating coil section (if included)
The J25NC evaporator blower may be suspended from the and the blower section. Each channel is to be bolted to each
joists with isolation type hangers or hooks. Suspension section as shown.
accessories 1HH0403 (J25NC) may be ordered separately.
All Suspension accessories include three suspension
HORIZONTAL
UNIT SUSPENDED
FROM ABOVE 3
AX BX
D
BX
C
E
VERTICAL UNIT SUPPORTED
3 FROM BELOW
B
BLOWER
F BLOWER
SECTION
1-1/2 SECTION
E 4 B
C CX
SUSPENSION
ANGLES 1 D
BX
BX
4 After these bottom channels are cut per Note 1, a new hole will have
to be drilled at the cut end if the unit is to be mounted on isolators.
Dimensions (in.)
Unit
AX BX CX
J25NC 69-1/4 49-1/16 26-5/8
TB VFD
C S1 S2 G1 G2 66 60 X VFD C W1 W2 Y1 G Y2 0CC X R SD-24 C
3-1 FLT
1
C S1 S2 G1 G2 66 60 X
2
R C Y1 Y2 G W1 W2
TB2
3
THERMOSTAT
4
SINGLE STAGE COMP, TWO STAGE FAN
TB5 TWO STAGE HEAT
UNIT
POWER
SUPPLY
SE CONTROL BOARD
UCB
TB2 VFD COMM THERMOSTAT CONNECTIONS
TB VFD
C S1 S2 G1 G2 66 60 X VFD C W1 W2 Y1 G Y2 0CC X R SD-24 C
3-1 FLT
1
C S1 S2 G1 G2 66 60 X
2
R C Y1 Y2 G W1 W2
TB2
3
THERMOSTAT
4
TWO STAGE COOL/FAN
TB5
TWO STAGE HEAT
Note: On non-J**NC/ND Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on the condensing unit.
C
VALVE SYS 2
BLK 218 / BR
1LLS
O BLK 219 / Y
UNIT
POWER
SUPPLY
SE CONTROL BOARD
UCB
TB2 VFD COMM THERMOSTAT CONNECTIONS
1
C S1 S2 G1 G2 66 60 X
2
R C Y1 Y2 G W1 W2
TB2
3
THERMOSTAT
4
TWO STAGE COOL/FAN
TB5
TWO STAGE HEAT
TB VFD
C S1 S2 G1 G2 66 60 X VFD C W1 W2 Y1 G Y2 0CC X R SD-24 C
3-1 FLT
1
C S1 S2 G1 G2 66 60 X
2
TB2 R C Y1 Y2 G W1 W2
3
THERMOSTAT
4
SINGLE STAGE COMP
TWO SPEED FAN
TB5
TWO STAGE HEAT
EVAPORATOR CONTROL BOX
Typical simplified field wiring diagram – J07NL Evaporator with J07YE Condenser
UNIT
POWER
SUPPLY
SE CONTROL BOARD
UCB
TB2 VFD COMM THERMOSTAT CONNECTIONS
1
C S1 S2 G1 G2 66 60 X
2
R C Y1 Y2 G W1 W2
TB2
3
THERMOSTAT
4
TWO STAGE COOL/FAN
TB5
TWO STAGE HEAT
Typical simplified field wiring diagram – J10-20NL Evaporator with J10-20YC Condenser
Note: On non J**NL/NM Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on the condensing unit.
C
VALVE SYS 2
BLK 218 / BR
1LLS
O BLK 219 / Y
SE CONTROL BOARD
UCB
TB2 VFD COMM THERMOSTAT CONNECTIONS
TB VFD
C S1 S2 G1 G2 66 60 X VFD C W1 W2 Y1 G Y2 0CC X R SD-24 C
3-1 FLT
1
C S1 S2 G1 G2 66 60 X
2
R C Y1 Y2 G W1 W2
TB2
3
THERMOSTAT
4
TWO STAGE COOL/FAN
TB5
TWO STAGE HEAT
Note: On non J**NL/NM Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on
the condensing unit.
UNIT
POWER
SUPPLY
SE CONTROL BOARD
TB2
THERMOSTAT CONNECTIONS
C S1 S2 G1 G2 66 60 X W1 W2 Y1 G Y2 0CC X R SD-24 C
C S1 S2 G1 G2 66 60 X
R C Y1 Y2 G W1 W2
TB1
THERMOSTAT
TWO STAGE COOL
EVAPORATOR CONTROL BOX
Typical field wiring diagram - J25NC evaporator unit with J25YC condenser unit
Note: On non J**NC Evaporator models, isolation relays must be installed to avoid overloading on 75 VA transformers on the condensing unit.
C
VALVE SYS 2
BLK 218 / BR
1LLS
O BLK 219 / Y