COOLING LOAD ESTIMATOR - Bilik Kaunselor 01
Temperature DB (oC) WB (oC) Hum Ratio
Outdoor temp to 33.3 28 0.0219 Room area 16.5 m2 è Imtiaz - Blok Pentadbiran (Ground)
Room temp ti 23 17 0.00969 Room Height 3.0 m
Daily Range DR 11
SENSIBLE COOLING LOAD
Conduction (A) Solar (B) Total Cooling (A) + (B)
Area (m2) U (W/m2.oC) CLTD Load-C (W) SC SGHF CLF Load-S (W) Load (W) Load (Btu/hr)
Windows
North 8.8 è 0.00 347 0 0.00 0.00
NE 8.8 è 0.00 637 0 0.00 0.00
East 8.8 è 0.00 618 0 0.00 0.00
SE 8.8 è 0.00 230 0 0.00 0.00
South 8.8 è 0.00 120 0 0.00 0.00
SW 2.7 6.3 8.8 è 149.69 0.88 230 0.83 453.5784 603.27 2,058.43
West 8.8 è 0.00 618 0 0.00 0.00
NW 8.8 è 0.00 637 0 0.00 0.00
Conduction Total Cooling
Area (m2) U (W/m2.oC) CLTD Load-C (W) Load (W) Load (Btu/hr)
Walls (Less glass)
North 12.9 è 0.00 0.00 0.00
NE 15.9 è 0.00 0.00 0.00
East 19.9 è 0.00 0.00 0.00
SE 20.9 è 0.00 0.00 0.00
South 22.9 è 0.00 0.00 0.00
SW 6.3 1.49 24.9 è 233.74 233.74 797.54
West 22.9 è 0.00 0.00 0.00
NW 15.9 è 0.00 0.00 0.00
Conduction Total Cooling
Area (m2) U (W/m2.oC) CLTD Load-C (W) Load (W) Load (Btu/hr)
Roof
w/o ceiling 33.8 è 0.00 0.00 0.00
wth ceiling 0 0.761 29.8 è 0.00 0.00 0.00
Conduction Total Cooling
Area (m2) U (W/m2.oC) Δt Load-C (W) Load (W) Load (Btu/hr)
Partition
Partition 16 1.695 10 è 271.20 271.20 925.37
Floors 16.5 0.8 10 è 132.00 132.00 450.40
Total Cooling
Numbers SHG CLF Load (W) Load (W) Load (Btu/hr)
Internal sources
People 3 70 1 è 210.00 210.00 716.55
Total Cooling
Area (m2) Density (W/m2) CLF Factor Load (W) Load (W) Load (Btu/hr)
Internal sources
Light 16.5 18 1 1.2 356.40 356.40 1,216.09
Power 16.5 50 1 1 825.00 825.00 2,815.02
Total Cooling
No of people Rate (Lps/p) Vent (L/s) Δt Load (W) Load (W) Load (Btu/hr)
Ventilation
People vent 3 2.5 7.5 10.3 95.02 95.02 324.21
Infilteration (base on ACH = 0.3) 4 10.3 52.21 52.21 178.16
GRAND TOTAL SENSIBLE COOLING LOAD 2,778.83 9,481.77
LATENT COOLING LOAD Total Cooling
Numbers SHG CLF Load (W) Load (W) Load (Btu/hr)
Internal sources
People 3 45 1 è 135.00 135.00 460.64
Total Cooling
No of people Rate (Lps/p) Vent (L/s) Δw Load (W) Load (W) Load (Btu/hr)
Ventilation
People vent 3 2.5 7.5 0.01221 275.64 275.64 940.52
Infilteration (base on ACH = 0.3) 4 0.01221 151.47 151.47 516.84
GRAND TOTAL LATENT COOLING LOAD 562.11 1,918.00
SPACE COOLING LOAD (Btu/hr) 11,399.78
Engineering check (Btuh/sq.ft) 64.21
Sensible Heat Ratio (SHR) 0.83
Supply air (Cfm) 493.27
Engineering check (Cfm/ton) 519.24
Supply Air Flow = Sensible Heat Gain Notes:
1210 (Room Db - Supply Db) Supply air temperature = T air leaving coil
= 2,778.83 Nos of row 4
1210 (23 - 13.1) BPF (By Pass Factor) 0.10
= 0.23 m3/s Troom 23 Deg C
= 493 Cfm Tapparatus dew point,room 12.07 Deg C
Tair leaving coil 13.1 Deg C
% Outside air = Ventilation
Supply air
= 25
493
= 4.99
say 5%
Mixture air = Outside air x % OA
Room air x (100-%OA)
= 33.3 x 0.05 = 1.66
23 x 0.95 = 21.85
Mixture 23.51
o
say 23.51 C