KP ENGINEERING JUDGMENT FIRESTOP DETAIL
F-RATING = 1-HR. (SEE NOTE NO. 6 BELOW)
FRONT VIEW
A B
MAX. 1"
A B
1 SECTION A-A 4 1 5 SECTION B-B 5
4
MAX. 1"
5 5
6 6 6 6
SIDE A SIDE A
2 SIDE B SIDE B
2
MAX. 0" MAX. 0"
HILTI, Inc. Sheet 1 of 2 Drawing No.
Plano, Texas USA (800) 879-8000 Scale 7/64" = 1"
Hilti Firestop Systems
Designed by
Date
Mar. 04, 2022
548714a
Saving Lives thr vation and Education
KP ENGINEERING JUDGMENT FIRESTOP DETAIL
PROJECT : AMLI BROADWAY PARK
CONTRACTOR : -ALTERNATE RESISTANCE SPECIALISTS
F-RATING = 1-HR. (SEE NOTE NO. 6 BELOW)
1. WOOD FLOOR/CEILING ASSEMBLY (UL/cUL CLASSIFIED L500 SERIES) WITH [OPTIONAL]
GYPCRETE TOPPING (1-HR. FIRE-RATING).
2. GYPSUM WALL ASSEMBLY (UL/cUL CLASSIFIED) WITH MINIMUM 2" x 4" WOOD STUDS (1-HR.
FIRE-RATING).
3. WOOD TRUSS (NOMINAL 2" x 4" OR 2" x 6" LUMBER) (NON FIRE-RATED).
4. MINIMUM 5/8" DEPTH HILTI CP 606 FLEXIBLE FIRESTOP SEALANT.
5. MINIMUM 5/8" DEPTH HILTI FS-ONE MAX INTUMESCENT FIRESTOP SEALANT, EXTENDING
MINIMUM 2" INTO JOINT BEYOND PENETRANT.
6. MINIMUM 1/2" BEAD HILTI CP 606 FLEXIBLE FIRESTOP SEALANT TO COMPLETELY COVER JOINT
INTERFACE.
NOTES : 1. MAXIMUM WIDTH OF JOINT = 1".
2. ANNULAR SPACE = MINIMUM 1/4", MAXIMUM 3/4".
3. THIS SYSTEM IS NOT DESIGNED TO REPLACE MUD AND TAPE WHERE REQUIRED.
4. THIS SYSTEM IS DESIGNED AS A STATIC SYSTEM ONLY.
5. T-RATING MAY NOT EQUAL F-RATING IN ACCORDANCE WITH UL 2079.
6. FIRE-RATING OF ASSEMBLY IS DEPENDENT UPON THE PERFORMANCE OF WOOD
TRUSS UNDER FIRE CONDITIONS.
THIS ENGINEERING JUDGMENT REPRESENTS A FIRESTOP SYSTEM THAT WOULD BE EXPECTED TO PASS THE STATED RATINGS IF
(REFERENCE : UL/cUL SYSTEM NO. W-L-7130, HW-D-0209, HW-S-0090, FW-D-0041 & W-L-1054)
HILTI, Inc. Sheet 2 of 2 Drawing No.
Plano, Texas USA (800) 879-8000 Scale -
Hilti Firestop Systems
Designed by
Date
Mar. 04, 2022
548714a