EDMT391908
Indoor Units Only
60 Hz
FXAQ-AVM EDMT391908
1. Lineup
2.2 kW 2.8 kW 3.6 kW 4.5 kW 5.6 kW 7.1 kW
Capacity range
0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP
Capacity index 20 25 31.25 40 50 62.5
FXAQ 20AVM 25AVM 32AVM 40AVM 50AVM 63AVM
VM : 1 phase, 220-240/220-230 V, 50/60 Hz
364
FXAQ-AVM EDMT391908
2.
Model FXAQ20AVM FXAQ25AVM
Power supply 1 phase, 220-240/220-230 V, 50/60 Hz 1 phase, 220-240/220-230 V, 50/60 Hz
kcal/h 1,900 2,400
1 3 Cooling capacity Btu/h 7,500 9,600
kW 2.2 2.8
kcal/h 2,200 2,800
2 3 Heating capacity Btu/h 8,500 10,900
kW 2.5 3.2
50 Hz kW 0.040 0.040
Cooling
60 Hz kW 0.040 0.040
Power input
50 Hz kW 0.040 0.040
Heating
60 Hz kW 0.040 0.040
Casing / Colour Resin / White N9.5 Resin / White N9.5
Dimensions: (H×W×D) mm 290×795×266 290×795×266
Rows × Stages × mm
Coil (Cross Fin pitch 2×14×1.4 ( 6.35) 2×14×1.4 ( 6.35)
Face area m2 0.161 (0.103+0.058) 0.161 (0.103+0.058)
Model KFD-280-40-8N KFD-280-40-8N
Type
Motor type DC Fan Motor DC Fan Motor
Fan Motor output × W 40×1 40×1
Number of units
m³/min 9.1/7.0 9.4/7.0
l/s 152/117 157/117
cfm 321/247 332/247
Washable resin net Washable resin net
Liquid pipes mm 6.4 (Flare connection) 6.4 (Flare connection)
Piping Gas pipes mm 12.7 (Flare connection) 12.7 (Flare connection)
Connections
VP13 VP13
Drain pipe mm (External dia. 18, Internal dia. 15) (External dia. 18, Internal dia. 15) 16
Mass kg 12.0 12.0
4 Sound Cooling dB(A) 33.0/28.5 35.0/28.5
pressure
level (H/L) Heating dB(A) 34.0/28.5 36.0/28.5
Safety devices Fuse Fuse
Refrigerant control Electronic expansion valve Electronic expansion valve
Operation manual, Installation manual, Operation manual, Installation manual,
Standard accessories Installation panel, Paper pattern for installation, Installation panel, Paper pattern for installation,
Insulation tape, Clamps, Screws Insulation tape, Clamps, Screws
C: 3D121836A C: 3D121836A
Drawing No.
Sound level C: 4D122383A C: 4D122384A
Notes:
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
2. Indoor temp.: 20°CDB, 15°CWB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m,
kcal/h=kW×860
level difference: 0 m. Btu/h=kW×3412
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. cfm=m³/min×35.3
4. Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward. During l/s=m³/min×1000/60
actual operation, these values are normally somewhat higher as a result of ambient conditions.
365
FXAQ-AVM EDMT391908
Model FXAQ32AVM FXAQ40AVM
Power supply 1 phase, 220-240/220-230 V, 50/60 Hz 1 phase, 220-240/220-230 V, 50/60 Hz
kcal/h 3,100 3,900
1 3 Cooling capacity Btu/h 12,300 15,400
kW 3.6 4.5
kcal/h 3,400 4,300
2 3 Heating capacity Btu/h 13,600 17,100
kW 4.0 5.0
50 Hz kW 0.040 0.050
Cooling
60 Hz kW 0.040 0.050
Power input
50 Hz kW 0.050 0.050
Heating
60 Hz kW 0.050 0.050
Casing / Colour Resin / White N9.5 Resin / White N9.5
Dimensions: (H×W×D) mm 290×795×266 290×1,050×269
Rows × Stages × mm
Coil (Cross Fin pitch 2×14×1.4 ( 6.35) 2×14×1.4 ( 6.35)
Face area m2 0.161 (0.103+0.058) 0.235 (0.145+0.090)
Model KFD-280-40-8N ARW30WBP43DK
Type
Motor type DC Fan Motor DC Fan Motor
Fan Motor output × W 40×1 43×1
Number of units
m³/min 9.8/7.0 12.2/9.7
l/s 163/117 203/162
cfm 346/247 431/342
Washable resin net Washable resin net
Liquid pipes mm 6.4 (Flare connection) 6.4 (Flare connection)
Piping Gas pipes mm 12.7 (Flare connection) 12.7 (Flare connection)
Connections
Drain pipe mm VP13 VP13
(External dia. 18, Internal dia. 15) (External dia. 18, Internal dia. 15)
Mass kg 12.0 15.0
4 Sound Cooling dB(A) 37.5/28.5 37.0/33.5
pressure
level (H/L) Heating dB(A) 38.5/28.5 38.0/33.5
Safety devices Fuse Fuse
Refrigerant control Electronic expansion valve Electronic expansion valve
Operation manual, Installation manual, Operation manual, Installation manual,
Standard accessories Installation panel, Paper pattern for installation, Installation panel, Paper pattern for installation,
Insulation tape, Clamps, Screws Insulation tape, Clamps, Screws
C: 3D121836A C: 3D121836A
Drawing No.
Sound level C: 4D122385A C: 4D122386A
Notes:
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
2. Indoor temp.: 20°CDB, 15°CWB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m,
kcal/h=kW×860
level difference: 0 m. Btu/h=kW×3412
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. cfm=m³/min×35.3
4. Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward. During l/s=m³/min×1000/60
actual operation, these values are normally somewhat higher as a result of ambient conditions.
366
FXAQ-AVM EDMT391908
Model FXAQ50AVM FXAQ63AVM
Power supply 1 phase, 220-240/220-230 V, 50/60 Hz 1 phase, 220-240/220-230 V, 50/60 Hz
kcal/h 4,800 6,100
1 3 Cooling capacity Btu/h 19,100 24,200
kW 5.6 7.1
kcal/h 5,400 6,900
2 3 Heating capacity Btu/h 21,500 27,300
kW 6.3 8.0
50 Hz kW 0.060 0.100
Cooling
60 Hz kW 0.060 0.100
Power input
50 Hz kW 0.070 0.110
Heating
60 Hz kW 0.070 0.110
Casing / Colour Resin / White N9.5 Resin / White N9.5
Dimensions: (H×W×D) mm 290×1,050×269 290×1,050×269
Rows × Stages × mm
Coil (Cross Fin pitch 2×14×1.4 ( 6.35) 2×14×1.4 ( 6.35)
Face area m2 0.235 (0.145+0.090) 0.235 (0.145+0.090)
Model ARW30WBP43DK ARW30WBP43DK
Type
Motor type DC Fan Motor DC Fan Motor
Fan Motor output × W 43×1 43×1
Number of units
m³/min 15.0/12.0 19.0/14.0
l/s 250/200 317/233
cfm 530/424 671/494
Washable resin net Washable resin net
Liquid pipes mm 6.4 (Flare connection) 9.5 (Flare connection)
Piping Gas pipes mm 12.7 (Flare connection) 15.9 (Flare connection)
Connections
VP13 VP13
Drain pipe mm (External dia. 18, Internal dia. 15) (External dia. 18, Internal dia. 15) 16
Mass kg 15.0 15.0
4 Sound Cooling dB(A) 41.0/35.5 46.5/38.5
pressure
level (H/L) Heating dB(A) 42.0/35.5 47.0/38.5
Safety devices Fuse Fuse
Refrigerant control Electronic expansion valve Electronic expansion valve
Operation manual, Installation manual, Operation manual, Installation manual,
Standard accessories Installation panel, Paper pattern for installation, Installation panel, Paper pattern for installation,
Insulation tape, Clamps, Screws Insulation tape, Clamps, Screws
C: 3D121836A C: 3D121836A
Drawing No.
Sound level C: 4D122387A C: 4D122388A
Notes:
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
2. Indoor temp.: 20°CDB, 15°CWB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m,
kcal/h=kW×860
level difference: 0 m. Btu/h=kW×3412
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. cfm=m³/min×35.3
4. Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward. During l/s=m³/min×1000/60
actual operation, these values are normally somewhat higher as a result of ambient conditions.
367