Split System Air Conditioners Manual

The document provides installation instructions for Carrier split-system air conditioners. It includes safety considerations and general installation guidelines such as locating the unit away from windows and ensuring slack in refrigerant tubing. Instructions are given for making electrical connections, piping connections, and care/maintenance. Clearance requirements and ambient operating conditions are also outlined.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
104 views20 pages

Split System Air Conditioners Manual

The document provides installation instructions for Carrier split-system air conditioners. It includes safety considerations and general installation guidelines such as locating the unit away from windows and ensuring slack in refrigerant tubing. Instructions are given for making electrical connections, piping connections, and care/maintenance. Clearance requirements and ambient operating conditions are also outlined.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 20

Manuals+ — User Manuals Simplified.

Carrier Split-System Air Conditioners Instruction Manual

Home » Carrier » Carrier Split-System Air Conditioners Instruction Manual

CA13NA 018–060
CA14NA 018–060
CA15NA 018–060
CA16N* 018–061
SPLIT–SYSTEM AIR CONDITIONERS
WITH R–410A REFRIGERANT

Contents [ hide
1 Installation Instructions
2 GENERAL
3 INSTALLATION
4 Make Electrical
Connections
5 CARE AND MAINTENANCE
6 Documents / Resources
7 Related Posts

Installation Instructions

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance, or use can cause an explosion, fire, electrical
shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified
installer, service agency, or your distributor or branch for information or assistance. The qualified installer or
agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual
instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for
brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or
cautions included in the literature and attached to the unit. Consult local building codes and current editions of the
National Electrical Code (NEC) NFPA 70. In Canada, refer to current editions of the Canadian electrical code
CSA 22.1.

Recognize safety information. This is the safety–alert symbol When you see this symbol on the unit and in
instructions or manuals, be alert to the potential for personal injury. Understand these signal words; DANGER,
WARNING, and CAUTION. These words are used with the safety–alert symbol. DANGER identifies the most
serious hazards which will result in severe personal injury or death. WARNING signifies hazards that could result
in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal
injury or product and property damage. NOTE is used to highlight suggestions that will result in enhanced
installation, reliability, or operation.

WARNING

ELECTRICAL SHOCK HAZARD


Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing the system, the main electrical disconnect switch must be in the OFF position. The
ockout and tag switch with a suitable warning label.

WARNING

EXPLOSION HAZARD
Failure to follow this warning could result in death, serious personal injury, and/or property damage.
Never use air or gases containing oxygen for leak testing or operating refrigerant compressors. Pressuri
o an explosion.

GENERAL

NOTE: In some cases, noise in the living area has been traced to gas pulsations from improper installation of
equipment.

1. Locate unit away from windows, patios, decks, etc. where unit operation sound may disturb customer.
2. Ensure that vapor and liquid tube diameters are appropriate for unit capacity.
3. Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends.
4. Leave some slack between structure and unit to absorb vibration.
5. When passing refrigerant tubes through the wall, seal the opening with RTV or other pliable silicon-based caulk
(see Fig. 1).
6. Avoid direct tubing contact with water pipes, ductwork, floor joists, wall studs, floors, and walls.
7. Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact
with tubing (see Fig. 1).
8. Ensure that tubing insulation is pliable and completely surrounds the vapor tube.
9. When necessary, use hanger straps that are 1 in. (25.4 mm) wide and conform to the shape of tubing
insulation (see Fig. 1).
10. Isolate hanger straps from insulation by using metal sleeves bent to conform to the shape of insulation.
NOTE: Avoid contact between tubing and structure

Fig. 1 — Piping Installation

For proper unit operation, check refrigerant charge using the charging information located on the control box cover
and/or in the Check Charge section of this instruction.
IMPORTANT: Maximum liquid–line size is 3/8–in. OD for all residential applications including long line. Refer to
Residential Piping and Longline Guideline for further information.
IMPORTANT: Always install the factory–supplied liquid–line filter drier. If replacing the filter drier, refer to Product
Data Digest for an appropriate part number. Obtain replacement filter driers from your distributor or branch.

INSTALLATION

IMPORTANT: Effective January 1, 2015, all split systems and packaged air conditioners must be installed
pursuant to applicable regional efficiency standards issued by the Department of Energy.

CAUTION

CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when han

Check Equipment and Job Site


UNPACK UNIT
Move to the final location. Remove carton taking care not to damage the unit.
Inspect Equipment
File claim with shipping company prior to installation if the shipment is damaged or incomplete. Locate unit rating
plate on unit corner panel. It contains information needed to properly install the unit. Check rating plate to be sure
unit matches job specifications.
Install on a Solid, Level Mounting Pad
If conditions or local codes require the unit to be attached to the pad, tie-down bolts should be used and fastened
through knockouts provided in the unit base pan. Refer to the unit mounting pattern in Fig. 2 to determine base
pan size and knockout hole location. For hurricane tie-downs, contact the local distributor for details and PE
(Professional Engineer) certification, if required by local authorities.
On rooftop applications, mount on a level platform or frame. Place unit above a load-bearing wall and isolate unit
and tubing set from the structure. Arrange supporting members to adequately support the unit and minimize
transmission of vibration to the building. Consult local codes governing rooftop applications. Roof-mounted units
exposed to winds may require wind baffles. Consult the Application Guideline and Service Manual -Residential
Split System Air Conditioners and Heat Pumps for wind baffle construction.
NOTE: Unit must be level to within ±2 (±3/8 in./ft,.±9.5 mm/m) per compressor manufacturer specifications.
Clearance Requirements
When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow 24 in.
(609.6 mm) clearance to service end of unit and 48 in. (1219.2 mm) (above unit. For proper airflow, a 6–in. (152.4
mm) clearance on 1 side of the unit and 12–in. (304.8 mm) on all remaining sides must be maintained. Maintain a
distance of 24 in. (609.6 mm) between units or 18 in. (457.2 mm) if no overhang within 12 ft. (3.66 m) Position so
water, snow, or ice from roof or eaves cannot fall directly on the unit.
NOTE: 18” (457.2 mm) clearance option described above is approved for outdoor units with wire grille coil
guard only. Units with louver panels require 24” (609.6 mm) between units.
On rooftop applications, locate a unit at least 6 in. (152.4 mm) above roof surface.
Operating Ambient
The minimum outdoor operating ambient in a cooling mode without accessory is 55_F (12.78_C). The maximum
outdoor operating ambient in cooling mode is 125_F (51.7_C) for non–13 SEER models and 115_F (46.11_C) for
13 SEER models.
Make Piping Connections

WARNING

PERSONAL INJURY AND ENVIRONMENTAL HAZARD


Failure to follow this warning could result in personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final unit disposal. Use all service ports and open all flo
regulations require that you do not vent refrigerant into the atmosphere. Recover during system repair or final unit disposa

CAUTION

UNIT DAMAGE HAZARD


Failure to follow this caution may result in equipment damage or improper operation.
If ANY refrigerant tubing is buried, provide a 6–in (152.4 mm). vertical rise at service valve. Refrigerant tubing lengths up t
ial consideration. Do not bury lines more than 36–in. (914.4 mm).
TIEDOWN KNOCKOUT LOCATIONS in. (mm)
UNIT BASE PAN
Dimension in. (mm)
A B C

23 —1/2 X 23 —1/2 (596.9 X


7 —13/16 (198.4) 4–7/16 (112.7) 18–1/16 (458.8)
596.9)

26 X 26 (660.4 X 660.4) 9–1/8 (231.8) 4–7/16 (112.7) 21–1/4 (539.8)

31–1/2 X 31–1/2 (800.1 X 800


9–1/8 (231.8) 6–9/16 (166.7) 24–11/16 (627.1)
.1)

35 X 35 (889 X 889) 9–1/8 (231.8) 6–9/16 (166.7) 28–7/16 (722.3)

Fig. 2 — Tiedown Knockout Locations A05177

Outdoor units may be connected to indoor section using accessory tubing package or field–supplied refrigerant
grade tubing of correct size and condition. Rated tubing diameters shown in Table 1 are recommended up to 80 ft.
(24.38 m). See Product Data for acceptable alternate vapor diameters and associated capacity losses. For tubing
requirements beyond 80 ft. (24.38 m), substantial capacity and performance losses can occur. Following the
recommendations in the Longline Guideline will reduce these losses. Refer to Table 1 for field tubing diameters.
Refer to Table 6 for accessory requirements.

There are no buried–line applications greater than 36–in. (914.4 mm) allowed.
If refrigerant tubes or indoor coils are exposed to the atmosphere, they must be evacuated to 500 microns to
eliminate contamination and moisture in the system.

Outdoor Unit Connected to Factory Approved Indoor Unit


The outdoor unit contains correct system refrigerant charge for operation with factory approved AHRI rated indoor
unit when connected by 15 ft. (4.57 m) of field-supplied or factory–accessory tubing, and factory supplied filter
drier. Check refrigerant charge for maximum efficiency.
Refrigerant Tubing Connection Outdoor
Connect vapor and liquid tubes to fittings on vapor and liquid service valves (see Table 1). Use refrigerant grade
tubing
Sweat Connection

CAUTION

UNIT DAMAGE HAZARD


Failure to follow this caution may result in equipment damage or improper operation.
Service valves must be wrapped in a heat–sinking material such as a wet cloth while brazing.

Use refrigeration-grade tubing. Service valves are closed from the factory and ready for brazing. After wrapping
the service valve with a wet cloth, braze sweat connections using industry-accepted methods and materials.
Consult local code requirements. Refrigerant tubing and indoor coil are now ready for leak testing. This check
should include all field and factory joints.

Table 1 – Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters (In.)
LIQUID RATED VAPOR*

UNIT SIZE Connection & Max. t Connection Diamete


Tube Diameter
ube diameter r

CA13NA, CA14NA, CA15NA, CA16NA, CA16NW

18, 24 3/8 3/4 3/4

30 3/8 3/4 3/4

36 3/8 7/8 7/8

42, 48 3/8 7/8 7/8

60 3/8 7/8 1 —1/8

CA16NA Models Only

37, 49 3/8 7/8 7/8

61 3/8 7/8 1 —1/8

CA16NW Models Only

43 3/8 7/8 7/8

54, 61 3/8 7/8 1 —1/8

* Units are rated with 25 ft. (7.6 m) of lineset. See Product Datasheet for performance data when using different
size and length line sets.
Notes:

1. Do not apply capillary tube to these units.


2. For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 35 ft. (10.7 m) vertical
differential 250 ft. (76.2 m) Total Equivalent Length), refer to the Residential Piping and Longline Guide line—
Air Conditioners and Heat Pumps using Puron refrigerant.
3. For alternate liquid line options on 18—42 size units, see Product Data or Residential Piping and Application
Guideline

Install Liquid–Line Filter Drier Indoor

CAUTION

UNIT DAMAGE HAZARD


Failure to follow this caution may result in equipment damage or improper operation.

1. Installation of filter drier in liquid line is required.


2. Filter drier must be wrapped in a heat–sinking material such as a wet cloth while brazing.
Refer to Fig. 3 and install filter drier as follows:

1. Braze 5–in. liquid tube to the indoor coil.


2. Wrap filter drier with a damp cloth.
3. Braze filter drier to above 5–in. (127 mm) liquid tube. Flow arrow must point towards the indoor coil.
4. Connect and braze the liquid refrigerant tube to the filter drier.

Fig. 3 — Liquid Line Filter Drier

Evacuate Refrigerant Tubing and Indoor Coil

CAUTION

UNIT DAMAGE HAZARD


Failure to follow this caution may result in equipment damage or improper operation.
Never use the system compressor as a vacuum pump.

Refrigerant tubes and indoor coil should be evacuated ystem is free of air and liquid water. A tight dry system will
hold a vacuum of 1000 microns after approximately 7 minutes. See Fig. 4.

Fig. 4 — Deep Vacuum Graph A95424


Final Tubing Check
IMPORTANT: Check to be certain factory tubing on both indoor and outdoor units has not shifted during shipment.
Ensure tubes are not rubbing against each other or any sheet metal or wires. Pay close attention to feeder tubes,
making sure wire ties on feeder tubes are secure and tight.
Installing with Indoor
Piston Outdoor Unit Connected to Factory Approved Indoor Unit
Check piston size shipped with the indoor unit to see if it matches the required indoor piston size. If it does not
match, replace the indoor piston with the correct piston size. Refer to Product Data for piston size.

NOTE: Correct pistons are shipped with select outdoor units in the accessory bag and are only for use in certain
qualified and approved fan coils, i.e. FB4C. (See Product Data for a list of approved fan coils that use accessory
pistons.)
The piston included with the FFMANP* and FPMAN* fan coils are unique to those products and CANNOT be
replaced with the piston shipped with the outdoor unit. Refer to the AHRI Directory to check if a certain
combination can use a piston or requires an accessory TXV.
When changing the indoor pistons, use a backup wrench. Hand tighten hex nut, then tighten with wrench 1/2 turn.
Do not exceed 30 ft−lbs. The indoor piston contains a Teflon ring (or seal) which is used to seat against the inside
of the distributor body and must be installed properly to ensure proper seating. See Fig 5.

Fig. 5 — Indoor (Cooling) Piston

Units with Cooling Mode TXV


Units installed with cooling mode TXV require charging by the subcooling method.

1. Operate unit a minimum of 15 minutes before checking charge.


2. Measure liquid service valve pressure by attaching an accurate gauge to the service port.
3. Measure liquid line temperature by attaching an accurate thermistor type or electronic thermometer to the
liquid line near the outdoor coil.
4. Refer to unit rating plate for required subcooling temperature.
5. Refer to Table 2 — Rating Plate (required) Subcooling Temperature. Find the point where the required
subcooling temperature intersects measured liquid service valve pressure.
6. To obtain the required subcooling temperature at specific liquid line pressure, add refrigerant if liquid line
temperature is higher than indicated or reclaim refrigerant if the temperature is lower. Allow a tolerance of
±3_F(±1.7_C).

NOTE: If conditions are not favorable see Check Charge instructions on page 8.
Units with Indoor Piston
Units installed with indoor pistons require charging by the superheat method.
The following procedure is valid when indoor airflow is within± 21 percent of its rated CFM.

1. Operate unit a minimum of 15 minutes before checking charge.


2. Measure suction pressure by attaching an accurate gauge to the suction valve service port.
3. Measure suction temperature by attaching an accurate thermistor type or electronic thermometer to the suction
line at the service valve.
4. Measure outdoor air dry–bulb temperature with a thermometer.
5. Measure indoor air (entering indoor coil) wet–bulb temperature with a sling psychrometer.
6. RefertoTable3–Superheat Charging — AC Only.Find outdoor temperature and evaporator entering air wet–bulb
temperature. At this intersection, note superheat. Where a dash (—-) appears on the table, do not attempt to
charge system under these conditions, or refrigerant slugging may occur. The charge must be weighed in,
adding or removing 0.6 oz/ft of 3/8 liquid line above or below 15 feet (4.6m) respectively.
7. Refer to Table 4 — Required Suction–Line Temperature. Find superheat temperature (from #6 above) and
suction pressure. At this intersection, note suction line temperature.
8. If the unit has a higher suction line temperature than charted temperature, add refrigerant until the charted
temperature is reached.
9. If the unit has a lower suction line temperature than charted temperature, reclaim the refrigerant until the
charted temperature is reached.
10. When adding refrigerant, charge in liquid form into suction service port using a flow–restricting device.
11. If outdoor air temperature or pressure at suction valve changes, charge to new suction line temperature
indicated on the chart.
12. Optimum performance will be achieved when the operating charge produces 6_F suction superheat at suction
service valve with 95_F(35_C) outdoor ambient and 0_F(27_C) dry-bulb (67_F/19_C) wet bulb) indoor
temperature (DOE “A” test conditions) at rated airflow.

Table 2 – Rating Plate (required) Subcooling Temperatures

R– 410A Required Liquid Line Temperature _F (_C)

Measure Li
quid Pressu ºF (ºC) ºF (ºC) ºF (ºC) ºF (ºC) ºF (ºC) ºF (ºC)
re (PSIG)

6 3 8 4 10 6 12 7 14 8 16 9

251 78 26 76 24 74 23 72 22 70 21 68 20

259 80 27 78 26 76 24 74 23 72 22 70 21
266 82 28 80 27 78 26 76 24 74 23 72 22

274 84 29 82 28 80 27 78 26 76 24 74 23

283 86 30 84 29 82 28 80 27 78 26 76 24

291 88 31 86 30 84 29 82 28 80 27 78 26

299 90 32 88 31 86 30 84 29 82 28 80 27

308 92 33 90 32 88 31 86 30 84 29 82 28

317 94 34 92 33 90 32 88 31 86 30 84 29

326 96 36 94 34 92 33 90 32 88 31 86 30

335 98 37 96 36 94 34 92 33 90 32 88 31

345 100 38 98 37 96 36 94 34 92 33 90 32

364 104 40 102 39 100 38 98 37 96 36 94 34

374 106 41 104 40 102 39 100 38 98 37 96 36

384 108 42 106 41 104 40 102 39 100 38 98 37

395 110 43 108 42 106 41 104 40 102 39 100 38


406 112 44 110 43 108 42 106 41 104 40 102 39

416 114 46 112 44 110 43 108 42 106 41 104 40

427 116 47 114 46 112 44 110 43 108 42 106 41

439 118 48 116 47 114 46 112 44 110 43 108 42

450 120 49 118 48 116 47 114 46 112 44 110 43

462 122 50 120 49 118 48 116 47 114 46 112 44

474 124 51 122 50 120 49 118 48 116 47 114 46

Table 3 – Superheat Charging — AC Only

EVAPORATOR ENTERING AIR TEMPERATURE (_F WB)


OUTDOOR TEMP (
_F)
50 52 54 56 58 60 62 64 67 68 70 72 74 76

55 9 12 14 17 20 23 26 29 32 35 37 40 42 45

60 7 10 12 15 18 21 24 27 30 33 35 38 40 43

65 — 6 10 13 16 19 21 24 27 30 33 36 38 41

70 — — 7 10 13 16 19 21 24 27 30 33 36 39
75 — — — 6 9 12 15 18 21 24 28 31 34 37

80 — — — — 5 8 12 15 18 21 25 28 31 35

85 — — — — — — 8 11 15 19 22 26 30 33

90 — — — — — — 5 9 13 16 20 24 27 31

95 — — — — — — — 6 6 14 18 22 25 29

100 — — — — — — — — 8 12 15 20 23 27

105 — — — — — — — — 5 9 13 17 22 26

110 — — — — — — — — — 6 11 15 20 25

115 — — — — — — — — — — 8 14 18 23

*Optimum performance point, 95_ºF(35_ºC) outdoor ambient and (80_ºF/27_ºC dry bulb), (67_ºF/19_ºC wet bulb)
indoor conditions. (DOE A Test Conditions)
Where a dash (— — ) appears do not attempt to charge the system under these conditions or refrigerant slugging
may occur. The charge must be weighed in.
Note: Superheat _ºF is at low—side service port, Allow a tolerance of ±3_ ºF(±1.7_ºC)
Note: Indoor dry bulb between 70_ºFand80_ºF(21_ºCand27_ºC)

Table 4 – Required Suction–Line Temperature


SUCTION PRESSURE AT SERVICE PORT (PSIG)

SUPERHEAT TE
MP (_F) 107.8 112.2 116.8 121.2 126 130.8 138.8 140.8 145.8

0 35 37 39 41 43 45 47 49 51

2 37 39 41 43 45 47 49 51 53

4 39 41 43 45 47 49 51 53 55

6 41 43 45 47 49 51 53 55 57

8 43 45 47 49 51 53 55 57 59

10 45 47 49 51 53 55 57 59 61

12 47 49 51 53 55 57 59 61 63

14 49 51 53 55 57 59 61 63 65

16 51 53 55 57 59 61 63 65 67

18 53 55 57 59 61 63 65 67 69

20 55 57 59 61 63 65 67 69 71

22 57 59 61 63 65 67 69 71 73

24 59 61 63 65 67 69 71 73 75

26 61 63 65 67 69 71 73 75 77

28 63 65 67 69 71 73 75 77 79

30 65 67 69 71 73 75 77 79 81

32 67 69 71 73 75 77 79 81 83

34 69 71 73 75 77 79 81 83 85

36 71 73 75 77 79 81 83 85 87

38 73 75 77 79 81 83 85 87 89

40 75 77 79 81 83 85 87 89 91

Make Electrical Connections

Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to the system is
within limits shown on the unit rating plate. Contact local power company for correction of improper voltage. See
unit rating plate for recommended circuit protection device.
NOTE: Operation of unit on improper line voltage constitutes abuse and could affect unit reliability. See unit rating
plate. Do not install the unit in a system where voltage may fluctuate above or below permissible limits.
NOTE: Use copper wire only between disconnect switch and unit.
NOTE: Install branch circuit disconnect of adequate size per NEC to handle unit starting current. Locate
disconnect within sight from and readily accessible from the unit, per Section 440–14 of NEC.
Route Ground and Power Wires
Remove access panel to gain access to unit wiring. Extend wires from disconnect through power wiring hole
provided and into the unit control box.

WARNING

ELECTRICAL SHOCK HAZARD


Failure to follow this warning could result in personal injury or death.
The unit cabinet must have uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur.
ctrical wire or metal conduit when installed in accordance with existing electrical codes.

Connect Ground and Power Wires


Connect the ground wire to the ground connection in the control box for safety. Connect power wiring to contactor
as shown in Fig. 6.

Fig. 6 — Line Connections

Connect Control Wiring


Route 24–v control wires through control wiring grommet and connect leads to control wiring (See Fig. 8). Refer to
Installation Instructions packaged with thermostat. Use No. 18 AWG color-coded, insulated (35_C minimum) wire.
If the thermostat is located more than 100 ft. (30.48 m) from the unit, as measured along the control voltage wires,
use No. 16 AWG color-coded wire to avoid excessive voltage drop. All wiring must be NEC Class 2 and must be
separated from incoming power leads.
Use furnace transformer, fan coil transformer, or accessory transformer for control power, 24v/40va minimum.
NOTE: The use of available 24v accessories may exceed the minimum 40va power requirement. Determine total
transformer loading and increase the transformer capacity or split the load with an accessory transformer as
required.

Final Wiring Check


IMPORTANT: Check factory wiring and field wire connections to ensure terminations are secured properly. Check
wire routing to ensure wires are not in contact with tubing, sheet metal, etc.

CompressorCrankcaseHeater
When equipped with a crankcase heater, furnish power to the heater a minimum of 24 hr before starting the unit.
To furnish power to heater only, set thermostat to OFF and close electrical disconnect to the outdoor unit.
A crankcase heater is required if refrigerant tubing is longer than 80 ft. (24.38 m). Refer to the Residential Piping
and Longline Guideline and Service Manual Longline Section– Residential Split–System Air Conditioners and
Heat Pumps.

Install Electrical Accessories


Refer to the individual instructions packaged with kits or accessories when installing.
Start-Up

CAUTION

UNIT OPERATION AND SAFETY HAZARD


Failure to follow this caution may result in personal injury, equipment damage or improper operation.

Do not overcharge the system with refrigerant.


Do not operate the unit in a vacuum or at negative pressure.
Compressor dome temperatures may be hot.

CAUTION

PERSONAL INJURY HAZARD


Failure to follow this caution may result in personal injury.
Wear safety glasses, protective clothing, and gloves when handling refrigerant and observe the following:
Front seating service valves are equipped with Schrader valves.

Follow these steps to properly start-up system:

1. After the system is evacuated, fully open liquid and vapor service valves.
2. Unit is shipped with valve stem(s) front seated (closed) and caps installed. Replace stem caps after the system
is opened to refrigerant flow. Replace caps finger–tight and tighten with wrench an additional 1/12 turn.
3. Close electrical disconnects to energize the system.
4. Set room thermostat at the desired temperature. Be sure the setpoint is below indoor ambient temperature.
5. Set room thermostat to COOL and fan control to ON or AUTO mode, as desired. Operate the unit for 15
minutes. Check system refrigerant charge.

3–Phase Monitor
In 3–phase units a small circuit board is factory installed to monoline voltage. A small led will flash if a phase
problem exists. See code descriptions on the monitor. If LED is flashing, disconnect power to the unit and
interchange 2 fields–wiring leads on the unit contactor.
Fig. 7 — 3–Phase Monitor Control (Applies to 3–Phase Units Only)
Table 5 – Three–Phase Monitor LED Indicators

LED STATUS

OFF No call for compressor operation

FLASHING Reversed-phase

ON Normal

CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

Ensure compressor rotation is correct.

S 3– phase scroll compressors are rotation sensitive.

S A flash LED on phase monitor indicates reverse rotation. (See Table 5)

This will not allow the contractor to be energized.

S Disconnect power to unit and interchange 2 field– wiring leads on the unit contactor.

Sequence of Operation
Turn on power to indoor and outdoor units. The transformer is energized.
On a call for cooling, the thermostat makes circuits R–Y and R–G. Circuit R–Y energizes contactor, starting
outdoor fan motor and compressor circuit. R–G energizes indoor unit blower relay, starting indoor blower motor on
high speed.
When the thermostat is satisfied, its contacts open, de-energizing contactor and blower relay. Compressor and
motors stop. If the indoor unit is equipped with a time–delay relay circuit, the indoor blower will run an additional
90 seconds to increase system efficiency.

Check Charge
The factory charge amount and desired subcooling are shown on the unit rating plate. The charging method is
shown on the information plate inside the unit. To properly check or adjust charge, conditions must be favorable
for subcooling charging. Favorable conditions exist when the outdoor temperature is between 70_F and 100_F
(21.11_C and 37.78_C), and the indoor temperature is between 70_F and 80_F (21.11_C and 26.67_C). Follow
the procedure below:

Adjust charge by adding or removing 0.6 oz/ft of 3/8 liquid line above or below 15ft (4.57 m) respectively.
For standard refrigerant line lengths (80 ft/24.38 m or less), allow the system to operate in cooling mode at least
15 minutes. If conditions are favorable, check system charge by subcooling method. If any adjustment is
necessary, adjust the charge slowly and allow the system to operate for 15 minutes to stabilize before declaring a
properly charged system.

If the indoor temperature is above 80_F (26.67_C), and the outdoor temperature is in the favorable range, adjust
the system charge by weight based on line length and allow the indoor temperature to drop to 80_F (26.67_C)
before attempting to check system charge by subcooling method as described above.

If the indoor temperature is below 70_F (21.11_C), or the outdoor temperature is not in the favorable range,
adjust the charge for line set length above or below 15ft (4.57 m) only. The charge level should then be
appropriate for the system to achieve rated capacity. The charge level could then be checked at another time
when both indoor and outdoor temperatures are in a more favorable range.
NOTE: If the line length is beyond 80 ft (24.38 m) or greater than 35 ft (10.7 m) vertical separation, See Long Line
Guideline for special charging requirements.

Final Checks
IMPORTANT: Before leaving job, be sure to do the following:

1. Ensure that all wiring is routed away from tubing and sheet metal edges to prevent rub–through or wire
pinching.
2. Ensure that all wiring and tubing are secure in the unit before adding panels and covers. Securely fasten all
panels and covers.
3. Tighten service valve stem caps to 1/12–turn past finger tight.
4. Leave the Owner’s Manual with the owner. Explain system operation and periodic maintenance requirements
outlined in the manual.
5. Fill out the Dealer Installation Checklist and place it in the customer file.

CARE AND MAINTENANCE

For continuing high performance and to minimize possible equipment failure, periodic maintenance must be
performed on this equipment.
Frequency of maintenance may vary depending upon geographic areas, such as coastal applications. See
Owner’s Manual for information.
Table 6 – Accessory Usage
REQUIRED FOR LOW– REQUIRED FOR
AMBIENT COOLING AP SEACOAST APPL
REQUIRED FOR L ICATIONS
PLICATIONS
ACCESSORY ONG LINE APPLIC
(Below 55°F/12.8_C) ATIONS* (Within 2 miles/3.
22 km)

Ball Bearing Fan Motor Yes{ No No

Compressor Start Assist Capacitor


Yes Yes No
and Relay

Crankcase Heater Yes Yes No

Evaporator Freeze Thermostat Yes No No

Hard Shut — Off TXV Yes Yes Yes

Liquid Line Solenoid Valve No No No

Motor Master or Low– ambient Pres


Yes] No No
sure Switch

Support Feet Recommended No Recommended

Winter Start Control Yes No No

* For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 35 ft. (10.7 m) vertical differential, refer
to Residential Piping and Longline Guideline.
Additional requirement for Low—Ambient Controller (full modulation feature) MotorMasterr Control.
If the unit equipped with an ECM OD motor, both motor and fan need to be replaced per unit accessory guide to
work properly. The unit will not meet AHRI rated efficiency once motor and fan are replaced to use this accessory.
Fig. 8 — Generic Wiring Diagrams (See Thermostat Installation Instruction for specific unit combinations)

PURON (R–410A) REFRIGERANT QUICK REFERENCE GUIDE

Puron refrigerant operates at 50–70 percent higher pressures than R–22. Be sure that servicing equipment and
replacement
components are designed to operate with Puron refrigerant
Puron refrigerant cylinders are rose-colored.
Recovery cylinder service pressure rating must be 400 PSIG, DOT 4BA400, or DOT BW400.
Puron refrigerant systems should be charged with liquid refrigerant. Use a commercial type metering device in
the manifold hose when charging into suction line with compressor operating
Manifold sets should be 700 psig high side and 180 PSIG low side with 550 psig low–side retard.
Use hoses with a 700 psig service pressure rating.
Leak detectors should be designed to detect HFC refrigerant.
Puron refrigerant, as with other HFCs, is only compatible with POE oils.
Vacuum pumps will not remove moisture from oil.
Do not use liquid–line filter driers with rated working pressures less than 600 psig.
Do not leave Puron suction line filter driers in line longer than 72 hours.
Do not install a suction–line filter drier in the liquid line.
POE oils absorb moisture rapidly. Do not expose oil to the atmosphere.
POE oils may cause damage to certain plastics and roofing materials
Wrap all filter driers and service valves with a wet cloth when brazing.
A factory-approved liquid–line filter drier is required on every unit.
Do NOT use an R–22 TXV.
Never open the system to the atmosphere while it is under a vacuum.
When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen
and replace filter driers.
Evacuate to 500 microns prior to recharging.
Do not vent Puron refrigerant into the atmosphere.
Do not use capillary tube coils.
Observe all warnings, cautions, and bold text.

Copyright 2017 Carrier Corp.


S 7310 W. Morris St.
S Indianapolis, IN 46231
Edition Date: 03/17
Catalog No: CA13NA—16NW—07SI
The manufacturer reserves the right to change, at any time, specifications and designs without notice and without
obligations.