Tài liệu 4

This document provides technical specifications for a current monitoring relay with multiple product types. It lists specifications for supply characteristics, LED indications, relay output characteristics, mechanical and electrical life expectancies, contact materials, number of current transformers, trip characteristics, features, and reset modes. The relay is available in three phase and single phase models with inverse time and definite time trip characteristics and adjustable current ranges from 1A to 45A.

Uploaded by

Lung Doan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
41 views2 pages

Tài liệu 4

This document provides technical specifications for a current monitoring relay with multiple product types. It lists specifications for supply characteristics, LED indications, relay output characteristics, mechanical and electrical life expectancies, contact materials, number of current transformers, trip characteristics, features, and reset modes. The relay is available in three phase and single phase models with inverse time and definite time trip characteristics and adjustable current ranges from 1A to 45A.

Uploaded by

Lung Doan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

TECHNICAL SPECIFICATIONS: CURRENT MONITORING RELAY

Three Phase Single Phase


Product:
P1, P2, P3, P4, P5, P6,P7, P8 P9, P10, P11, P12 P13, P14, P15, P16 P17, P18, P19, P20 SERIES CMR
Supply Characteristics:
Auxiliary Supply 220 to 415 VAC, -20 % to +15 %, 50 / 60 Hz 110 to 240 VAC, -20 % to +10 %, 50 / 60 Hz Three Phase Products
Power Consumption (Max.) 12 VA (approx.) 5 VA (approx.)
LED Indication: Inverse Cat. No. Definite Cat. No. Current
Power ON (ON) / Lock Out (Blink) Green LED ON / Green LED Blink P1 17A122CB0 P9 17B122AA0 3 A to 9 A
Over Load (OL) OL LED ON P2 17A222CB0 P10 17B222AA0 8 A to 24 A
Under Load (UL) UL LED ON P3 17A322CB0 P11 17B322AA0 15 A to 45 A
*Phase REV. N.A. P4 17A422CB0 P12 17B422AA0 2 A to 5 A
LED ON:Phase Reverse/Blink: Imbalance (Red LED 3)
P5 17A122OB0 3 A to 9 A
Phase UNB/Loss BLINK: UNB LED N.A.
P6 17A222OB0 8 A to 24 A
Relay Output Characteristics: P7 17A322OB0 15 A to 45 A
Contact Arrangement & Rating 1 C/O ( Fail Safe Operation ) 5A @ 240 VAC P8 17A422OB0 2 A to 5 A
Utilization Category AC-15
120 / 240 V
Ue Rated Voltage V Single Phase Products
3.0 / 1.5 A
Ie Rated Current I
Mechanical Life Expectancy 1 X 107 Operations Inverse Cat.
Cat. No.
No. Trip
Definite Char.
Cat. No. Current
Electrical Life Expectancy 1 X 10 5 Operations @ Rated Load P13 17C112EB0 P17 17D112DA0 3 A to 9 A
Contact Material Ag alloy P14 17C212EB0 P18 17D212DA0 8 A to 24 A
Feature Characteristics: P15 17C312EB0 P19 17D312DA0 15 A to 45 A
Number Of CTs 2 1 P16 17C412EB0 P20 17D412DA0 2 A to 5 A
Trip Characteristics: Inverse Time Definite Time Inverse Time Definite Time
Thermal Memory Yes N.A. Yes 2 A to 5 A Product can be used with External CT.
N.A.
Trip Class (IEC 60255-08) 10 A, 10, 20, & 30 N.A. 5, 10, 20, & 30 N.A. Main Features:
Start Time N.A. 0.2 to 30 s N.A. 0.2 to 30 s Overload Protection Base Mounting
Trip Delay As per trip class 0.2 to 10 s As per trip class 0.2 to 10 s Auto/Manual Reset Selection Easy to Install
Under Load Protection 40% to 90% (Trip Time:5 s +/-1 s) 50% (Trip Time:5 s +/-1 s) 40% to 90% (Trip Time:5 s +/-1 s) 50% (Trip Time:5 s +/-1 s ) LED Indications for all failure conditions Compact Size
Locked Rotor Protection 400% of the Set Value 400% of the Set Value Fail-Safe Protection Test Feature
N.A. N.A. Phase Imbalance Protection
Trip Time:< 4 s after starting Trip Time: < 4 s after starting
Current Imbalance Protection > 50% Imbalance and 70% load condition ( Trip Time < 5 s ) N.A. Phase Loss Protection
> 70% Imbalance and 70% load condition ( Trip Time < 3 s ) N.A. Phase Reverse Protection
Phase Loss Protection
Wide Range of Current Adjustment (1 A to 45 A)
*Phase Reverse Protection Delay 100 ms approx. N.A.
Reset Mode Auto Class 10A=3 min; Class 10=6 min; Class 5=3 min; Class 10=6 min;
6 min 6 min Inverse Time:
Class 20=12 min; Class 30=15 min. Class 20=12 min; Class 30=15 min. Definite Time:
Manual 2 s +/- 1 s Selectable Under Load Protection Under Load Protection
Lock Out (Restarts allowed/Hour) For Class 10A, 10=6; Class20,30=4 6 restarts For Class 5A, 10=6; Class20,30=4 6 restarts applicable per hour Selectable Locked Rotor Protection Selectable Start Time and Trip Time
Reset Time 120 ms to 400 ms 60 ms to 700 ms Selectable Trip Class
Terminals Details L1,L3,15,16,18 L, N, 15, 16, 18
Common Characteristics:
Functional Description:
Test Function Applicable Product: IEC 60255-08 Under Load Protection:
Setting Accuracy +/-5 % Under Load protection is provided by undercurrent trip. It is suitable for
Environmental Testing Std:
Repeat Accuracy +/-2 % small pumps to avoid dry running, cavitations, etc.
On Delay 800 ms +/- 50 ms Vibration IEC 60068-2-6Ed. 7.0 (2007-12) 5 g Phase Imbalance Protection
Pollution degree Type II Cold Heat IEC 60068-2-1Ed. 6.0 (2007-03) Phase Loss Protection:
Dimensions in mm ( W X H X D ) 110.8 X 36.5 X 76.8 Dry Heat IEC 60068-2-2Ed. 5.0 (2007-07) Negative sequence current due to phase imbalance or phase loss may
Mounting Base Mounting Repetitive Shock IEC 60068-2-27
Ed. 4.0 (2008-02), 40 g, 6 ms damage rotor winding. Relay gives excellent protection for Phase
Weight Approx. (Packed) 200 gm Non Repetitive Shock IEC 60068-2-27 Ed. 4.0 (2008-02), 30 g, 15 ms imbalance or phase loss.
Degree of Protection** IP-20 Phase Reverse Protection:
Safety Std: Relay detects the phase reversal during starting only. For this feature
Operating Position Any
Test Voltage between motor start duration should be more than 0.1 seconds.
Maximum Operating Altitude 2000 m IEC 60947-5-1 Ed. 3.0 (2003-11) 2 kV
I/P and O/P RESET :
Operating Temperature -10° C to + 60° C
Impulse Voltage between Auto:
Storage Temperature -25° C to + 70° C IEC 60947-5-1 Ed. 3.0 (2003-11) 2 kV
I/P & O/P In case of Auto reset mode, relay resets within 3 min to 15 min (as per
Relative Humidity 5 to 95% Rh (without condensation) selected class), after trip in case of 3-phase or Single phase Inverse trip
Test Voltage between all
Size Of Wire passing Through CT 16 mm2 Max. Terminal & Enclosure IEC 60947-5-1 Ed. 3.0 (2003-11) 4 kV products and within 6 min or 20 sec (as per product specs),after trip in
Screw Size for Mounting M4 x 20 mm Cheese Head Screw (Blue Zinc Passivation), 2 No’s case of Definite trip products.
Single Fault IEC 61010-1Ed. 3. 0 (2010-06)
Conformity to standards: Manual:
Insulation Resistance UL 508 Ed. 17 (1999-01) >50k For all trips relay can be reset immediately. For manual reset press
Product Certification CE Leakage Current UL 508 Ed. 17 (1999-01) <3.5 mA reset switch For 2 seconds.
EMC:
Harmonic Current Emission IEC 61000-3-2 Ed. 3.2 (2009-04) Class A CAUTION: Terminal Details :
ESD IEC 61000-4-2 Ed. 2.0 (2008-12) Level II 1. Always follow instructions stated in this product leaflet.
Radiated Susceptibility IEC 61000-4-3 Ed. 3.2 (2010-04) Level III 0.45 N.m (4 Lb.in)
2. Before installation, check to ensure that specifications agree with the intended application.
Terminal screw - M2.6

17LL001_11
Electrical Fast Transients IEC 61000-4-4 Ed. 3.0 (2012-04) Level IV 3.5 mm
3. Installation to be done by skilled electrician.
Surge IEC 61000-4-5 Ed. 2.0 (2005-11) Level IV 4. Suitable dampers should be provided in the event of excessive vibrations during installation. 2
1 X 0.2 ....4 mm Rigid Wire
Conducted Susceptibility IEC 61000-4-6 Ed. 3 .0 (2008-10) Level III (Without wire protection)
5. Automation and control devices must be installed so that They are protected against any
Voltage Dips and interruptions IEC 61000-4-11 Ed. 2.0 (2004-03) For Class A 1 X 0.2 ....2.5 mm
2
risk of involuntary Actuation.
Power Frequency Magnetic Field IEC 61000-4-8 Ed. 2.0 (2009-09) Level IV (With wire protection)
6. While using the device with Star Delta Starter, configure the Full Load Motor Current as per
Voltage Flickers & Fluctuations IEC 61000-3-3 Ed. 3 .0 (2013-05) Class A
Conducted Emission CISPR 14-1 Ed. 5.2 (2011-11) Class A
the current in Delta mode. AWG 1 X 22 to 12
Radiated Emission CISPR 14-1 Ed. 5.2 (2011-11) Class A NOTE: Product innovation being a continuous process, we
*Phase Reverse not applicable to 17A122OB0,222OB0,322OB0 & 422OB0 products. **Note: For products 15-45A range, IP protection is not applicable. reserve right to alter specifications without prior notice.
Current Monitoring Relay Series CMR
Functional Description: Overall Dimensions for Product with Terminal: Relay Connection Diagram: Connection Diagram for Single Phase
·Inverse Time:
·Overload protection: Manual Reset Auto Reset
Relay implements the thermal image of the motor during heating N
and cooling periods. If the motor current exceeds 1.11 times the
set value of the current, relay trips the motor as soon as the value
of thermal capacity exceeds threshold value.

Locked Rotor Protection:


Protects motor from locked rotor conditions if load current
exceeds by greater than 400% of set nominal current within
4 sec due to mechanical fault or due to high inertia load.
Test Function:

L
N
L
N
This function can be used to check the trip of the relay. For
START / STOP
test sequence press and hold the TEST switch for 5 sec during 15
15
this time all LEDs glows ON. After relay trip ‘UNB’ LED starts L
16 GIC L
16 GIC

CMR

Blinking for Three Phase products & ‘OL’ LED ON for 1PH CMR

18
products.Press Reset switch for 2 sec. to come out of Test 18

function. N
N
Definite Time: Motor
· Overload Protection: Motor
1) Relay trips if the motor current exceeds 1.11 times set value of
the current for duration of set trip time for runtime ‘OL’ fault.
2) If ‘OL’ fault occurs at motor start up, relay trips after the
current exceeds 1.11 times of set nominal current, by taking Connection Diagram for Three Phase:
Connection for Terminal based products: Input connection between L1 & L3
start time plus trip time.
Relay out put : 15, 16, 18
· Test Function: Manual Reset Auto Reset
This function can be used to check the trip time of the relay. For test
sequence press and hold the TEST switch for 5 sec. Relay trips after MODE Selection:
completion of set values of start time and trip time. During test, ‘UL’
Two position DIP slide switch has been provided on the front facial of the product.
& ‘OL’ LED’s become ON. After relay trip, ‘OL’ LED remains ON.
By using these switches following protection / modes can be made On and OFF.
Press Reset switch for 2 sec. to come out of Test function.
1) Auto Reset mode.
NOTE:
2) Locked Rotor Protection (for Inverse Time products)
For ‘1A’ current, use 3A to 9A range product with 3-wire
3) Underload Protection mode (for Definite Time products)
turns through the Ct’s and select 3A range of nominal current. OR

L1

L1
L3
L3
For ‘1A’ current, use 2A to 5A range product with 2-wire
UL UL
turns through the Ct’s and select 2A range of nominal current. START / STOP
15 15
Lock Out: 16 GIC
L1
16 GIC
L1
In Auto Reset mode of operation Lockout feature enables to restrict AUTO Reset mode = OFF (Manual ON) AUTO Reset mode = ON CMR
CMR

number of restarts of motor per hour in case of continuous fault LOCKED Rotor Protection = OFF LOCKED Rotor Protection = ON 18 18

persistence. once the number of restarts in an hour exceeds the given


limit device enter into Lockout mode in which relay will not turn on Under Load Protection = OFF Under Load Protection = ON N/L2 N/L2

unless device is powered off and on. Motor Motor

EXTERNAL CT INTERFACE:
In case of nominal current setting range requirement is higher than 45A,
MA = AUXILLIARY SUPPLY MC = AUXILLIARY CONTACT
then model with 2 to 5 A current range setting should be used with
external CT interface as shown in connection diagram. INVERSE TRIP CHARACTERISTIC CURVES:
Note:-Always use external CT having secondary rating 5A. Connection Diagram for External CT interface:
e.g.:-In case of external CT with ratio 100:5 is to be used then nominal 10000
current setting knob can be aligned at 40%, 50%, 60%, 70%, 80%
90% & 100% of rated primary current.
External CT with following ratios can also be used:- 50:5, 200:5.
Operating Time(Seconds)

1000

Motor
Crest Factor:
For pure sine wave, the crest factor is 1.414, hence for 8 times current, S1 S2
100
the peak value will be 1.414 X 8 X full scale RMS current.

As the sampling rate is 2kHz, phase reverse detection is not possible S1 S2


for 90 degree angle.
10 START / STOP L1
15
16 GIC
L1/+Ve L3
CMR
S2
1 S2

17LL001_11
0 2 4 6 8 10 18
Multiples of Nominal Current
Warm Curve: Pre loading at 90% of load according to IEC 60255 - 08
L2/N